LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0805500

User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 19

LENNOX
¢_2002 Lennox Industries Inc.
Dallas, Texas
HSXA12 outdoor units use R410A which is an ozone
friendly HFC refrigerant. This unit must be installed with a
matching indoor coil and line set as outlined in the Lennox
Engineering Handbook. HSXA12 outdoor units are de-
signed for use in expansion valve (TXV) and fixed orifice
systems. Refer to the Lennox Engineering Handbook for
expansion valve kits which must be ordered separately, A
filter dryer approved for use with R410A has been shipped
with the unit. This component must be installed prior to op-
erating the unit. Failure to install the provided filter dryer
will void the warranty.
1 - Assembled HSXA12 outdoor unit
1 - Liquid line filter drier (approved for use with R410A
systems)
1 - Fixed orifice refrigerant metering device
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
INSTALLATION
INSTRUCTIONS
HSXA12 Series Units
CONDENSING UNITS FT_ Technical
504,540M .LLL[ Publications
04/04
Supersedes 12/03 Lithe U.S.A.
HSXA12 Outdoor Unit ........................... 1
Shipping And Packing List ....................... 1
General Information ............................. 1
Unit Dimensions ................................ 2
Setting the Unit ................................. 3
Electrical ...................................... 3
Refrigerant Piping .............................. 5
Flushing Existing Line Set & Indoor Coil ........... 5
Refrigerant Metering Device .................... 11
Manifold Gauge Set ............................ 11
Service Valves ................................ 12
Leak Testing .................................. 13
Evacuation ................................... 13
Start-up ...................................... 14
Charging ..................................... 14
System Operation ............................. 18
Maintenance .................................. 18
Optional Accessories .......................... 18
HSXA12 Check Points ......................... 19
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
These instructions are intended as a general guide and do
not supersede national or local codes in any way. Consult
authorities having jurisdiction before installation.
WARNING
AWARNING
,IMPORTANT
04/04
IIIHllllllllliillllillllillllillllill Page 1
504,540M
IIIHllllllllliillliilllllllllillllilllllill
IN LET._ AIR
4-3/8
(111)
4-3/8
(111)
INLET
©
AIR
INLET'_ AIR
Top View
C _-_
INLET
©
AIR
OPTIONAL UNIT
STAND-OFF KIT
(Field Installed)
(Around perimeter of base)
VAPOR LINE
CONNECTION
LIQUID LINE
CONNECTION
6-3/8
(162)
OUTDOOR
COIL FAN
Top View Base Section
_- C
DISCHARGEr AIR
4-3/8
(111)
COMPRESSOR_
A
ELECTRICAL
INLETS
VAPOR &
LIQUID LINE
CONNECTION
2-3/4 (70)
Side View 3/4
(19) OPTIONAL UNIT
STAND-OFF KIT
(Field Installed)
Side View
HSXA12-018
HSXA12-024
HSXA12-030
HSXA12-036
HSXA12-042
HSXA12-048
HSXA12-060
Model No.
in,
mm
in.
mm
in,
mm
A
25
635
33
838
29
737
B
24-1/4
616
32-1/4
819
28-1/4
718
C
24-1/4
616
24-1/4
616
28-1/4
718
Page 2
&CAUTION
Roof Mounting
Install unit at a minimum of 4 inches above the surface of
the roof. Care must be taken to ensure weight of unit is
properly distributed over roof joists and rafters, Either red-
wood or steel supports are recommended,
kCAUTION
Refer to unit dimensions for sizing mounting slab, plat-
forms or supports, Refer to figure 1 for installation clear-
ances,
Installation Clearances
(914 ram)
*NO TE -A service clearance of 30" (762 mm) must be main-
tained on one of the sides adjacent to the control box. Clear-
ance to one of the other three sides must be 36" (914 mm).
Clearance to one of the remaining two sides may be 12" (304
mm) and the final side may be 6" (152 mm).
NOTE -A clearance of 24" (610 mm) must be maintained
between two units.
NOTE -48" (1219 mm) clearance required on top
of unit. Maximum soffit overhang is 36" (914 mm).
Figure 1
Slab Mounting
When installing a unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground will not collect around the unit. See figure 2.
Slab should have a slope tolerance away from the building
of 2 degrees or 2 inches per 5 feet (51 mm per 1524 mm),
Refer to roof mounting section for barrier construction if
unit must face prevailing winter winds,
Slab Mounting At Ground Level
structure 'i_ discharge air
J,
12
Mounting slab must slope
away from building,
Figure 2
ground level
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
A WARNING
1 - Install line voltage power supply to unit from a properly
sized disconnect switch,
2 - Ground unit at unit disconnect switch or to an earth
ground,
NOTE -To facilitate conduit, a hole is in the bottom of
the control box. Connect conduit to the control box us
ing a proper conduit fitting.
NO TE -Units are approved for use only with copper
conductors.
24V, Class II circuit connections are made in the low
voltage junction box, Refer to figure 4 for field wiring
diagram,
NOTE -A complete unit wiring diagram is located in
side the unit control box coven
3 - Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations,
4 - Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit, See figure 3,
Page 3
Thermostat
[Wl;
tV_
v
@
©
NOTE
power
heat
cooling
indoor blower
common
Thermostat Designations
Indoor Unit
®
-(_-
@
NOTE -see unit wiring diagram for
power supply connections.
Outdoor Unit
E_ Y1 Outdoor Unit
[_ C Outdoor Unit
..... /\ .....
-If the indoor unit is not equipped with blower relay It must be field-provided and installed (P-8-3251 or equivalent).
Figure 3
Typical Field Wiring Diagram
_0_ TDOOR
FAN
PURPLE
LACK
ANGE
RED
A
NOTE-
FOR USE WITH COPPER CONDUCTORS
ONLY.REFER TO UNIT RATING
PLATE FOR MINIMUM CIRCUIT
AMPACITY AND MAXIMUM OVER-
YELLOW
COMPRESSOR
START *
CAPACITOR CI2
DUAL
CAPACITOR
__ ©
K3 I*A4
POTENTIAL RELAY* TIMED OFF CONTROL
KI
BLACK COMPRESSOR
CONTACTOR
l,'
50
CURRENT PROTECTION SIZE
WARNING-
ELECTRIC SHOCK HAZARD, CAN CAUSE
INJURY OR DEATH. UNIT MUST BE
GROUNDED IN ACCORDANCE WITH
NATIONAL AND LOCAL CODES
208-230/60/I
"A
D
1
GROUND
*May be optional
Figure 4
Page 4
IftheHSXA12unitisbeinginstalledwithanindoorcoiland
lineset,maketherefrigerantconnectionsasoutlinedinthis
section.Ifanexistinglinesetand/orindoorcoilisgoingto
beusedtocompletetheHSXA12system,refertothissec-
tion,aswellastheflushingsectionwhichfollows,
Fieldrefrigerantpipingconsistsof liquidandvaporlines
fromtheoutdoorunit(sweatconnections)totheindoorcoil
(flareorsweatconnections).UseLennoxL15(sweat,non-
flare)serieslinesetsasshownintable1orusefield-fabri-
catedrefrigerantlines.Referto RefrigerantPipingGuide
(Corp,9351-L9)for propersize,type,andapplicationof
field-fabricatedlines.Valvesizesarealsolistedintable1.
Refrigerant Line Connections
HSXA12 Matched with New Indoor Coil and Line Set
If the HSXA12 is being used with an existing indoor coil
which was equipped with a liquid line which served as
a metering device (RFCI), the liquid line must be re-
placed prior to the installation of the HSXA12 unit.
If refrigerant lines are routed through a wall, seal and isolate
the opening so vibration is not transmitted to the building,
Table 1
Refrigerant Line Sets
Valve Field Size Recommended Line Set
Connections
Model L15
Liquid Vapor Liquid Vapor Line Sets
Line Line Line Line
L15-26
3/8 in. 5/8 in. 3/8 in, 5/8 in, 15 if, - 50 ft.
-018 (10 mm) (16 mm) (10 mm) (19 mm) (4.6 m- 15 m)
024 L15-41
-030 3/8 in, 3/4 in, 3/8 in, 3/4 in, 15 ft. - 50 ft.
-036 (10mm) (19mm) (10mm) (19mm) (4.6m-15m)
-042 3/8 in. 7/8 in. 3/8 in, 7/8 in, L15-65
-048 (10 mm) (22 mm) (10 mm) (22 mm) 15 ft, - 50 ft.
(4.6 m - 15 m)
-060 3/8 in, 1-1/8 in, 3/8 in, 1-1/8 in. Field
(10 mm) (29 mm) (10 mm) (29 mm) Fabricated
NOTE -Units are designed for line sets of up to fifty feet (15
m). For applications longer than fifty feet, consult the Len-
nox Refrigerant Piping Guide (Corp. 9351-L9). Select line
set diameters from table 1 to ensure that oil returns to the
compressor.
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is
important to properly isolate the refrigerant lines to prevent
unnecessary vibration, Line set contact with the structure
(wall, ceiling or floor) causes some objectionable noise
when vibration is translated into sound, As a result, more
energy or vibration can be expected. Closer attention to
line set isolation must be observed,
Following are some points to consider when placing and
installing a high-efficiency outdoor unit:
1-Placement -Be aware some localities are adopting
sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmis-
sion.
2- Line Set Isolation -The following illustrations demon-
strate procedures which ensure proper refrigerant line
set isolation. Figure 5 shows how to install line sets on
vertical runs. Figure 6 shows how to install line sets on
horizontal runs. Figure 7 shows how to make a transition
from horizontal to vertical. Finally, figure 8 shows how to
place the outdoor unit and line set.
Page 5
Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
NOTE -Similar installation practices should be used if
line set is to be installed on exterior of outside wall.
Outside Wall
\
rWood Block _,
Between Studs
E
J
Liquid Line
Vapor Line
(wrapped
Wall
L_ Caulk
PVC Pipe Fiberglass
Insulation
IMPORTANT- Refrigerant
lines must not contact
structure.
IMPORTANT- Refrigerant
lines must not contact wall.
\
m
m
m
r-,tit
Vapor Line Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Strap
Sleeve
Figure 5
Page 6
Refrigerant Line Sets:
Installing Horizontal Runs
To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties.
8 feet
Floor Joist or
Roof Rafter
j /
/
/
8 feet
Wire Tie
(around vapor line only)
Tape or Wire Tie
Strapping Material (around vapor line only)
\
Tape or Wire Tie
Metal Sleeve
h
r/jf
_) Floor Joist or Roof Rafter )
Strap the vapor line to the joist or rafter at 8 ft.
intervals then strap the liquid line to the vapor line.
Figure 6
Page 7
Refrigerant Line Sets:
Transition From Vertical To Horizontal
Anchored Heavy
Nylon Wire Tie
Wall
Stud
Metal /
Sleeve
I
i/
Va )or Line
Wrapped in
Armaflex
Strap Liquid Line
To Vapor Line
Liquid Line
Automotive
Muffler-Type
Hanger
Wall
Stud
Metal
Sleeve
)
Strap Liquid Line
To Vapor Line
Liquid Line
Vapor Line
Wrapped in
Armaflex
Figure 7
Outside Unit Placement and Installation
Install unit away from windows.
Two 90° elbows
installed in line set
will reduce line set
vibration.
Figure 8
Page 8
AWARNING
Brazing Connection Procedure
1 - Cut ends of the refrigerant lines square (free from nicks
or dents). Debur the ends, The pipe must remain
round, do not pinch end of the line.
2 - Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the sys-
tem.
3 - Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper-to-copper brazing or 45 percent
silver alloy for copper-to-brass or copper-to-steel braz-
ing) which are rated for use with R410A refrigerant.
Wrap a wet cloth around the valve body and the copper
tube stub. Remove light maroon washers from service
valves and shield light maroon stickers in order to pro-
tect them during brazing. Braze the line set to the ser-
vice valve.
4 - Wrap a wet cloth around the valve body and copper
tube stub to protect it from heat damage during braz-
ing. Wrap another wet cloth underneath the valve body
to protect the base paint.
Quench the joints with a wet cloth to prevent possible
heat damage to the valve core and opening port.
NOTE -The tube end must stay bottomed in the fitting
during final assembly to ensure proper seating, sealing
and rigidity.
5 - Install the provided fixed orifice (or thermal expan-
sion valve which is sold separately and approved
for use with R410A refrigerant) in the liquid line at the
indoor coil.
6 - Install the provided filter drier (approved for use with
R410A refrigerant) in the liquid line as close as pos-
sible to the expansion device. Do not leave the filter
drier uncapped for more than 10 to 15 minutes
prior to brazing, evacuation, and leak testing.
Polyol ester oils used in this system absorb mois-
ture quickly. Failure to install the filter drier will
void the warranty.
,WARNING
,IMPORTANT
-&CAUTION
Required Equipment
You will need the following equipment in order to flush the
existing line set and indoor coil: two clean R22 recovery
bottles, an oilless recovery machine that has a pump down
feature, and two sets of gauges (one for use with R22 and
one for use with the R410A).
Flushing Procedure
1 - Remove existing R22 refrigerant using the appropri-
ate procedure below.
If the existing outdoor unit is not equipped with
shut-off valves, or if the unit is not operational
AND you plan to use the existing R22 refrigerant
to flush the system -Disconnect all power to the ex-
isting outdoor unit. Connect to the existing unit, a
Page 9
cleanrecoverycylinderandthe recoverymachine
accordingtotheinstructionsprovidedwiththerecov-
erymachine.RemoveallR22refrigerantfromtheex-
istingsystem,Refertogaugesaftershutdowntocon-
firmthattheentiresystemiscompletelyvoidofrefrig-
erant,Disconnecttheliquidandvaporlinesfromthe
existingoutdoorunit,
If the existing outdoor unit is equipped with
manual shut-off valves AND you plan to use NEW
R22 refrigerant to flush the system - Start the exist-
ing R22 system in the cooling mode and close the liq-
uid line valve. Pump all of the existing R22 refrigerant
back into the outdoor unit. (It may be necessary to by-
pass the low pressure switches to ensure complete
refrigerant evacuation,) When the low side system
pressures reach 0 psig, close the vapor line valve.
Disconnect all power to the existing outdoor unit, Re-
fer to gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into
the low side of the system, Disconnect the liquid and
vapor lines from the existing outdoor unit,
2 - Remove the existing outdoor unit. Set the new R410A
unit and follow the brazing connection procedure
which begins on the previous page to make line set
connections. DO NOT install the provided fixed ori-
fice yet.
Make low voltage and line voltage connections to the
new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this
time.
3 - Remove the existing refrigerant flow control orifice or
thermal expansion valve before continuing with flush-
ing procedures, The existing devices are not ap-
proved for use with R410A refrigerant and may pre-
vent proper flushing, Use a field-provided fitting to re-
connect the lines,
&IMPORTANT
Inverted R22 Cylinder
(Contains clean R22 to
be used for flushing)
Flushing Connections
Low High
Pressure Pressure
Service Valve
HSXA12
Unit
GAUGE MANIFOLD
Indoor Coil Existing Liquid Line Liquid Line
Service Valve
Closed
RECOVERY CYLINDER
Tank Return
Inlet
Discharge
RECOVERY MACHINE
NOTE- The inverted R22 cylin-
der must contain at least the
same amount of refrigerant as
was recovered from the existing
system.
Figure 9
Page 10
4- Removethe pressuretap valve cores from the
HSXA12unit'sservicevalves,ConnectanR22cylin-
derwithcleanrefrigeranttothevaporservicevalve.
ConnecttheR22gaugesettotheliquidlinevalveand
connectarecoverymachinewithanemptyrecovery
tanktothegaugeset,
5- Settherecoverymachineforliquidrecoveryandstart
therecoverymachine,Openthegaugesetvalvesto
allowtherecoverymachinetopullavacuumontheex-
istingsystemlinesetandindoorcoil,
6 - InvertthecylinderofcleanR22andopenitsvalveto
allowliquidrefrigeranttoflowintothesystemthrough
thevaporlinevalve.Allowtherefrigerantto passfrom
thecylinderandthroughthelinesetandtheindoorcoil
beforeitenterstherecoverymachine.
7- Afteralloftheliquidrefrigeranthasbeenrecovered,
switchtherecoverymachinetovaporrecoverysothat
alloftheR22vaporisrecovered.Allowtherecovery
machinetopulla vacuumonthesystem.
NOTE -A single system flush should remove all of the
mineral oil from the existing refrigerant lines and in-
door coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush. Each time the system
is flushed, you must allow the recovery machine
to pull a vacuum on the system at the end of the
procedure.
8- Close the valve on the inverted R22 drum and the
gauge set valves, Pump the remaining refrigerant out
of the recovery machine and turn the machine off,
9 - Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery ma-
chine, gauges and R22 refrigerant drum, Reinstall
pressure tap valve cores into HSXA12 service valves,
10 -Install the provided fixed orifice in the liquid line at the
indoor coil.
may not be appropriately sized. Refer to the Engineering
Handbook for specific orifice information.
Table 2
Fixed Orifice Drill Sizes
Unit Fixed Orifice Part # Drill Size
HSXA12-018 29M88 .05
HSXA12-024 42J43 .063
HSXA12-030 42J43 .063
HSXA12-036 42J47 .071
HSXA12-042 42J51 .078
HSXA12-048 29M93 .081
HSXA12-060 42J57 .090
Install the fixed orifice as shown in figure 10. Do not twist
the cap tubes when loosening the seal nut from the orifice
housing. Use a wrench to back up the distributor,
Metering Device Installation
I_ ..._.j(fa ctorC;i.[inCsta iie d )
distributor _valve OR orifice
o-ring
J
O
expansion
valve (opt.)
// e
o-ring
strainer
liquidline
stub
Figure 10
Expansion Valve Systems
Expansion valves equipped with Chatleff type fittings are
available from Lennox, Refer to the Engineering Handbook
for expansion valves for use with specific match-ups.
If you install an expansion valve with an indoor coil that
includes a fixed orifice, remove the orifice before the
expansion valve is installed.
HSXA12 units are applicable to either fixed orifice or an
expansion valve system. See the indoor coil installation
instructions and the Lennox Engineering Handbook for
approved TXV and fixed orifice match-ups and application
information, Table 1 lists the unit liquid and vapor line sizes
and corresponding line sets,
Fixed Orifice Systems
HSXA12 units are shipped with a fixed orifice refrigerant
metering device. Replace the existing indoor unit fixed ori-
fice with the orifice supplied with the outdoor unit, Place the
supplied fixed orifice sticker on the indoor cabinet after
installation. See table 2 for the fixed orifice size for each
unit, In nonstandard applications, the provided fixed orifice
, IMPORTANT
Manifold gauge sets used with systems charged with
R410A refrigerant must be capable of handling the higher
system operating pressures, The gauges should be rated
for use with pressures of 0 - 800 on the high side and a low
side of 30" vacuum to 250 psi with dampened speed to 500
psi. Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating,
Page 11
Theliquidlineandvaporlineservicevalves(figures11and
12)andgaugeportsareusedforleaktesting,evacuating,
chargingandcheckingcharge,Seetable3fortorquere-
quirements,
Eachvalveisequippedwithaserviceportwhichhasafac-
tory-installedSchradervalve.A serviceportcapprotects
theSchradervalvefromcontaminationandservesasthe
primaryleakseal. Table3
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft,-lb. 11 NM
Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM
Compressor bolts 90 in.-lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
To Access Schrader Port:
1 - Remove service port cap with an adjustable wrench.
2 - Connect gauge to the service port.
3- When testing is completed, replace service port cap.
Tighten finger tight, then tighten an additional 1/6 turn.
To Open Service Valve:
1 - Remove stem cap with an adjustable wrench.
2 - Use a service wrench with a hex-head extension to
back the stem out counterclockwise as far as it will go.
NOTE -Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 - Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn,
To Close Service Valve:
1 - Remove the stem cap with an adjustable wrench.
2 - Use a service wrench with a hex-head extension to
turn the stem clockwise to seat the valve, Tighten it
firmly.
NOTE -Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 - Replace the stem cap, Tighten finger tight, then tighten
an additional 1/6 turn.
Service Valve
(Valve Closed)
serviCeport _,_m cap
to outdoor coil
insert hex
wrench here
service
port cap
Schrader valve open
to line set when valve is
closed (front seated)
indoor coil
(valve front seated)
insert hex
wrench here
Service Valve
(Valve Open)
service
port \
to outdoor coil
stem cap
©
service port to indoor coil
cap Schrader
valve
Figure 11
Vapor Line (Ball Type) Service Valve
Vapor line service valves function the same way as the oth-
er valves; the difference is in the construction, These
valves are not rebuildable, If a valve has failed, you must
replace it. A ball valve is illustrated in figure 12,
The ball valve is equipped with a service port with a factory-
installed Schrader valve, A service port cap protects the
Schrader valve from contamination and assures a leak-
free seal.
Page 12
Ball Valve (Valve Open)
Use Adjustable Wrench
To open: rotate Stem Counter-clockwise 90 °.
To close: rotate Stem Clockwise 90 °.
to outdoor coil _.,i------ stem cap
"q__J/ stem
ball
(shown open)
service port
cap
service port
Schrader valve
to indoor coil
Figure 12
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks.
WARNING
2 - With both manifold valves closed, connect the cylinder
of R410A refrigerant. Open the valve on the R410A cyl-
inder (vapor only).
3 - Open the high pressure side of the manifold to allow
R410A into the line set and indoor unit. Weigh in a trace
amount of R410A. [A trace amount is a maximum of 2
ounces (57 g) refrigerant or 3 pounds (31 kPa) pres-
sure]. Close the valve on the R410A cylinder and the
valve on the high pressure side of the manifold gauge
set. Disconnect R410A cylinder.
4 - Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 - Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)
6 - Adjust nitrogen pressure to 150 psig (1034 kPa). Open
the valve on the high side of the manifold gauge set in or-
der to pressurize the line set and the indoor unit.
7 - After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R410A
mixture. Correct any leaks and recheck.
XklMPORTANT
,WARNING
WARNING
Using an Electronic Leak Detector
1 - Connect a cylinder of R410A to the center port of the
manifold gauge set.
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.
XkIMPORTANT
1 - Connect manifold gauge set to the service valve ports
as follows:
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2 - Connect micron gauge.
Page 13
3- Connectthevacuumpump(withvacuumgauge)tothe
centerportofthemanifoldgaugeset.
4- Openbothmanifoldvalvesand startthe vacuum
pump.
5- Evacuatethelinesetandindoorunittoan absolute
pressureof23,000microns(29.01inchesof mercu-
ry).Duringtheearlystagesof evacuation,it isdesir-
abletoclosethemanifoldgaugevalveatleastonceto
determineifthereisa rapidriseinabsolutepressure.
A rapidriseinpressureindicatesa relativelylargeleak.
Ifthisoccurs,repeattheleaktestingprocedure.
NOTE -The term absolute pressure means the total
actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure,
6 - When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit,
Close the manifold gauge valves,
A,WARNING
IMPORTANT
1 - Rotate fan to check for frozen bearings or binding.
2 - Inspect all factory- and field-installed wiring for loose
connections.
3 - After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system,
4 - Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn,
5 - Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.
6 - Set the thermostat for a cooling demand. Turn on pow-
er to the indoor blower and close the outdoor unit dis-
connect switch to start the unit.
_Recheck voltage while the unit is running, Power must
be within range shown on the nameplate,
7 - Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8 - Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9- When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set.
This system is charged with R410A refrigerant which oper-
ates at much higher pressures than R22, The provided liq-
uid line filter drier is approved for use with R410A, Do not
replace it with components designed for use with R22, This
unit is NOT approved for use with coils which use capillary
tubes as a refrigerant metering device,
Factory Charge
Units are factory charged with the amount of R410A refrig-
erant indicated on the unit rating plate, This charge is
based on a matching indoor coil and outdoor coil with 15 ft.
(4.6 m) line set. For varying lengths of line set, refer to table
4 for refrigerant charge adjustment.
Table 4
Liquid Line Set Oz. per 5 ft. (grams per 1.5 m) adjust
Diameter from 15 ft. (4.6 m) line set*
3/8 in, 3 ounces per 5 feet
(10 ram) (85g per 1.5 m)
*If line length is greater than 15 ft. (4.6 m), add this amounL If line
length is less than 15 ft. (4.6 m), subtract this amounL
klMPORTANT
Page 14
The compressor is charged with sufficient polyol ester
oil for line set lengths up to 50 feet (15.2 m). If oil must
be added to the compressor in the field, Copeland has
approved Mobil EAL'" Arctic 22CC and ICI EMKA-
RATE "_ RL32CF.
Units Delivered Void of Charge
If the system is void of refrigerant, clean the system us-
ing the procedure described below.
1 - Use nitrogen to pressurize the system and check for
leaks. Repair leaks, if possible,
2 - Evacuate the system to remove as much of the mois-
ture as possible,
3 - Use nitrogen to break the vacuum and install the pro-
vided filter drier in the system,
4 - Evacuate the system again. Then, weigh the appropri-
ate amount of R410A refrigerant (listed on unit name-
plate) into the system,
5 - Monitor the system to determine the amount of mois-
ture remaining in the oil. Use test kit 10N46 to verify
that the moisture content is within the kit's dry color
range. It may be necessary to replace the filter drier
several times to achieve the required dryness level, If
system dryness is not verified, the compressor will
fail in the future.
Checking Charge
The outdoor unit should be charged during warm weather,
However, applications arise in which charging must occur
in the colder months, The method of charging is deter-
mined by the unit's refrigerant metering device and the
outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:
1 - Connect the manifold gauge set to the service valves:
low pressure gauge to vapor valve service port
high pressure gauge to liquid valve service port
Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of R410A,
2 - Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in
the cooling cycle.
3 - Use a digital thermometer to record the outdoor ambi-
ent temperature,
4 - When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68°F
(20°C). When pressures have stabilized, use a digital
thermometer to record the liquid line temperature,
5 - The outdoor temperature will determine which charg-
ing method to use, Proceed with the appropriate charg-
ing procedure,
Weighing in the Charge Fixed Orifice or
TXV Systems - Outdoor Temp. < 65°F (18°C)
If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit, Do this after any leaks have been re-
paired.
1 - Recover the refrigerant from the unit,
2 - Conduct a leak check, then evacuate as previously
outlined,
3 - Weigh in the unit nameplate charge,
If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other proce-
dures outlined below.
Charging Using the Subcooling Method
Fixed Orifice Systems
Outdoor Temp. _>65°F (18°C))
If you charge a fixed orifice system when the outdoor ambi-
ent is 65<_F(18<_C)or above, use the subcooling method to
charge the unit.
1 - With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature.
2 - At the same time, record the liquid line pressure reading.
3 - Use a temperature/pressure chart for R410A to deter-
mine the saturation temperature for the liquid line pres-
sure reading, See table 5,
4 - Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine sub-
cooling. (Saturation temperature - Liquid line tem-
perature = Subcooling)
5 - Compare the subcooling value with those in table 6, If
subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant,
Page 15
Temperature
oF
32
33
34
35
36
37
38
39
4O
41
42
43
44
45
46
47
48
49
5O
51
52
53
54
55
56
57
58
59
6O
61
62
Outdoor
Temp. °F (°C)
65 (18)
70 (21)
75 (24)
80 (27)
85 (29)
90 (32)
95 (35)
100(38)
105 (41)
110 (43)
115 (45t
Pressure
Psig
1O018
102.9
105.0
107.1
109.2
111.4
113.6
115.8
118.0
120.3
122.6
125.0
127.3
129.7
132.2
134.6
137.1
139.6
142.2
144.8
147.4
150.1
152.8
155.5
158.2
161.0
163.9
166.7
169.6
172.6
195.5
Table 5
R410A Temperature/Pressure Chart
Temperature
oF
63
64
65
66
67
68
69
7O
71
72
73
74
75
76
77
78
79
8O
81
82
83
84
85
86
87
88
89
9O
91
92
93
Pressure
Psig
178.5
181.6
184.3
187.7
190.9
194.1
197.3
200.6
203.9
207.2
210.6
214.0
217.4
220.9
224.4
228.0
231.6
235.3
239.0
242.7
246.5
250.3
254.1
258.0
262.0
266.0
270.0
274.1
278.2
282.3
286.5
Temperature
oF
94
95
96
97
98
99
IO0
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
Pressure
Psig
290.8
295.1
299.4
303.8
308.2
312.7
317.2
321.8
326.4
331.0
335.7
340.5
345.3
350.1
355.0
360.0
365.0
370.0
375.1
380.2
385.4
390.7
396.0
401.3
406.7
412.2
417.7
423.2
428.8
434.5
440.2
Temperature
oF
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
Pressure
Psig
445.9
451.8
457.6
463.5
469.5
475.6
481.6
487.8
494.0
500.2
506.5
512.9
519.3
525.8
532.4
539.0
545.6
552.3
559.1
565.9
572.8
579.8
586.8
593.8
601.0
608.1
615.4
622.7
630.1
637.5
645.0
-018
13 (7.2)
12 (6.7)
11 (6.1)
9 (5)
8 (4.5)
6 (3.3)
5 (2.8)
5 (2.8)
4 (2.2)
3 (1.7)
2 (1.1t
Table 6
Subcooling Values for Fixed Orifice Systems
-024
13 (7.2)
11 (6.1)
10 (5.6)
9(5)
7 (3.9)
6 (3.3)
5 (2.8)
4 (2.2)
4 (2.2)
3 (1.7)
3(1.7t
Liquid Subcoolin 9 [+ l°F (.6°C)]
-030
16 (8.9)
15 (8.3)
14 (7.8)
13 (7.2)
12 (6.7)
10 (5.6)
9 (5)
8 (4.5)
7 (3.9)
6 (3.3)
5(2.8t
-036 -042
12 (6.7) 11 (6.4)
11 (6.1) 10 (5.6)
10 (5.6) 9 (5)
9 (5) 8 (4.5)
8 (4.5) 7 (3.9)
7 (3.9) 6 (3.3)
6 (3.3) 6 (3.3)
5 (2.8) 5 (2.8)
4 (2.2) 4 (2.2)
4 (2.2) 3 (1.7)
3(1.7t 3 (1.7t
-048
14 (7.8)
13 (7.2)
12 (6.7)
11(6.1)
10 (5.6)
9 (5)
8 (4.5)
7 (3.9)
7 (3.9)
6 (3.3)
6(3.3t
-060
13 (7.2)
12 (6.7)
11(6.1)
10 (5.6)
10 (5.6)
9 (5)
8 (4.5)
7 (3.9)
6 (3.3)
6 (3.3)
5 (2.8t
Page 16
Approach Method and
Normal Operating Pressures
TXV Systems - Outdoor Temp. >_65°F (18°C)
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
1-Record outdoor ambient temperature using a digital
thermometer.
2-Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 - Compare stabilized pressures with those provided in
table 8, "Normal Operating Pressures." Minor varia-
tions in these pressures may be expected due to differ-
ences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.
Approach Method
4 - Use the same digital thermometer you used to check
the outdoor ambient temperature to check the liquid
line temperature.
5 - The difference between the ambient and liquid temper-
atures should match values given in table 7. If the val-
ues don't agree with the those in table 7, add refriger-
ant to lower the approach temperature, or recover re-
frigerant from the system to increase the approach
temperature.
Be aware of the R410A refrigerant cylinder. It will be
rose-colored. Refrigerant should be added through the
vapor valve in the liquid state. Some R410A cylinders
are equipped with a dip tube which allows you to
draw liquid refrigerant from the bottom of the cylin-
der without turning the cylinder upside-down. The
cylinder will be marked if it is equipped with a dip
tube.
Table 7
HSXA12 Approach Values
Approach Temperature
Model No. Liquid Line -
Outdoor Ambient °F (°C)
-018 10 (5.6)
-024 12 (6,7)
-030 13 (7.2)
-036 12 (6.7)
-042 11 (6.1)
-048 13 (7,2)
-060 14 (7,8)
AIMPORTANT
Table 8
Normal Operating Pressures In psig (liquid +/- 10 and vapor +/- 5 PSIG)*
Out. Coil
Mode Entering Air
Temp.
OF(oc)
65 (18.3)
75 (23.9)
fixed 85 (29.4)
orifice 95 (35.o)
105 (40.6)
65 (18.3)
75 (23.9)
TXV 85 (29.4)
95 (35.0)
105 (40.6)
*These are
to vary.
-018
LIQ SUC
238 123
275 131
317 136
362 141
410 144
234 133
270 135
312 137
361 138
409 141
-024
LIQ SUC LIQ
261 131 261
300 135 300
343 139 343
391 143 387
441 147 434
256 134 256
298 137 296
344 140 339
394 142 384
448 143 432
-030
SUC
128
133
138
141
145
137
139
141
144
146
typical pressures only. Indoor indoor match up, indoor
-036
LIQ SUC
268 130
308 134
351 138
398 142
447 146
264 135
305 138
349 139
396 140
446 143
-042
LIQ SUC
254 121
296 128
340 133
389 138
440 142
256 124
296 127
341 133
389 136
440 140
-048
LIQ SUC
270 124
311 130
356 134
404 139
456 143
269 131
312 133
357 135
406 137
460 140
-060
LIQ SUC
280 121
332 126
379 130
427 135
479 140
262 121
304 127
349 132
397 136
449 140
air quality, and indoor load will cause the pressures
Page 17
Theoutdoorunitandindoorblowercycleondemandfrom
theroomthermostat.Whenthethermostatblowerswitchis
intheONposition,theindoorbloweroperatescontinuously.
Compressor Time Belay (TB1)
A compressortimedelayisusedto preventcompressor
shortcyclingandto preventthecompressorfromrunning
backwards.Whenthereisdemandforacoolingcycle,the
controldelayscompressoroperationforabout5minutes(+
2minutes).Donotbypassthecontrol.
High Pressure Switch
HSXA12 units are equipped with a high pressure switch
that is located in the liquid line of the compressor. The
switch (SPST, manual reset, normally closed) removes
power from the compressor when discharge pressure rises
above factory setting at 640 + 10 psi.
Low Pressure Switch
HSXA12 units are also equipped with a low pressure switch
that is located in the vapor line of the compressor. The
switch (SPST, auto-reset, normally closed) removes power
from the compressor when vapor line pressure drops be-
low factory setting at 40 + 5 psi.
Filter Brier
A filter drier is shipped with each HSXA12 unit. The filter
drier must be field installed in the liquid line between the
liquid line service valve and the expansion valve. This fil-
ter drier must be installed to ensure a clean, moisture-
free system. Failure to install the filter drier will void
the warranty. A replacement filter drier is available as
from Lennox.
1 - Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Ensure the power is turned
off before you clean the coil.
2 - Outdoor fan motor is prelubricated and sealed. No fur-
ther lubrication is needed.
3 - Visually inspect connecting lines and coils for evidence
of oil leaks.
4 - Check wiring for loose connections.
5 - Check for correct voltage at unit (unit operating).
6 - Check amp-draw outdoor fan motor.
Unit nameplate Actual
NQ TE -If owner complains of insufficient cooling, the
unit should be gauged and refrigerant charge
checked. Refer to section on refrigerant charging in
this instruction.
Indoor Coil
1 - Clean coil, if necessary.
2 - Check connecting lines and coils for evidence of oil
leaks.
3 - Check condensate line and clean, if necessary.
Indoor Unit
1 - Clean or change filters.
2 - Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure.
3 - Belt Drive Blowers - Check belt for wear and proper
tension.
4 - Check all wiring for loose connections
5 - Check for correct voltage at unit (blower operating).
6 - Check amp-draw on blower motor
Unit nameplate Actual
AWARNING
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
season, the system should be checked as follows:
Refer to the Engineering Handbook for optional accesso-
ries that may apply to this unit. The following may or may
not apply:
Loss of Charge Kit
High Pressure Switch Kit
Compressor Monitor
Compressor Crankcase Heater
Hail Guards
Mounting Bases
Timed Off Control
Stand-off Kit
Sound Cover
• LowAmbient Kit
Page 18
Start-up and Performance Check List
Job Name Job No, Date
Job Location City State
Installer City State
Unit Model No, Serial No, Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? [] Indoor Filter Clean? []
Indoor Blower RPM S,R Drop Over Indoor (Dry)
Discharge Pressure Vapor Pressure
Refrigerant Lines: Leak Checked? [] Properly Insulated? []
Service Valves Fully Opened? [] Service Valve Caps Tight? []
Voltage With Compressor Operating -- Calibrated? []
Supply Voltage (Unit Off) __
-- Outdoor Coil Entering Air Temp,
Refrigerant Charge Checked? []
Outdoor Fan Checked? []
Thermostat
Properly Set? [] Level? []
Page 19

Navigation menu