LENNOX Furnace/Heater, Gas Manual L0806201
User Manual: LENNOX LENNOX Furnace/Heater, Gas Manual LENNOX Furnace/Heater, Gas Owner's Manual, LENNOX Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 50
Download | |
Open PDF In Browser | View PDF |
INSTALLATION INSTRUCTIONS _;_,2006 Lennox Industries Inc. Dallas, Texas, USA G60UHV(X) Series GAS FURNACE 505,121M 09/2006 Supersedes 06/2006 _-_") Technical _--_.L_Publications Lithe U.S.A. Unit Dimensions ................................ G60UHV(X) Parts Arrangement ................... G60UHV(X) Gas Furnace ........................ Shipping and Packing List ........................ Safety Information ............................... General ........................................ Combustion, Dilution & Ventilation Air .............. Setting Equipment ............................... Filters .......................................... Duct System .................................... Venting ........................................ Gas Piping ..................................... Electrical ....................................... Integrated Control Board Settings ................. Unit Start-Up ................................... Gas Pressure Adjustment ........................ High Altitude Information ......................... Other Unit Adjustments .......................... Heating Sequence of Operation ................... Service ........................................ Repair Parts List ................................ Ignition Control Board Diagnostic Codes ........... Troubleshooting ................................. Start-Up & Performance Check List ................ RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 2 3 4 4 4 5 6 9 13 13 13 21 22 28 37 38 38 38 39 40 42 43 44 50 AWARNING Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Installation and service must be performed by a qualified installer, service agency or the gas supplier. WHAT TO DO IF YOU SMELL GAS: • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Leave the building immediately. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. 09/06 iiiHiinlnlllllllllnllllllllllllllllll 505,121M Page1 IIIlllllllllllllllllllllllllllllllll *NOTE - 60C and 60D units that require air volumes over 1800 cfm (850 L/s) must have one of the following: 1. Return air from single side with transition which will accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Required to maintain proper air velocity.) 2. Return air from single side with optional RAB Return Air Base. 3. Return air from bottom. 4. Return air from both sides. 5. Return air from bottom and one side. Refer to Engineering Handbook for additional information. 3"3/4 (95)-I_1 F D FLUE OUTLET (Top) _OPTIONAL _---'---'--_----__--_. EXTERNAL _ _ 23-3/4 t603_ SIDE RETURN - II • , AIR FILTER KIT I_-._ 25 (635) (Either Side) TOP VIEW **Flue outlet may be horizontal but furnace must be vented vertically _Optional external side return air filter kit cannot be used with the optional RAB Return Air Base. I - uI =I TOP VIEW 3-1/4 (83) Right 8-1/8 (206) Left --I 4 |3-31, <1-9/16 (14) = t -_ l I 28 -1/2 (724) L n._ _._ 9/16 '91-(14) 19-7/16._ (494) (95) \ 14 (356) Right 13-1/4 (337) Left _OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT (Either Side) 40 (1016) 4-7/8 (124) Right 2-1/4 (57) Left 14-3/4 (375) (406) |/ 5/8 (16) 23-1/2 (597) *Bottom Return Air Opening SIDE VIEW 3/4(19) 3/4 (19) -I_ 4-1/4 (108) *Bottom Return Air Opening FRONT VIEW Model No. A B C D in. mm in. mm in. mm in. mm G6OUHV-36A-070 14-1/2 368 13-3/8 340 13 330 4-1/2 114 G6OUHV-36B-090 17-1/2 446 16-3/8 416 16 406 6 152 21 533 19-7/8 454 19-1/2 495 7-3/4 197 24-1/2 622 23-3/8 546 23 584 9-1/2 241 G6OUHV-6OC-O9O, G6OUHV-60C-110 G6OUHV-6OD-135 Page 2 Air Deflector G60UH-60C-110 Units Only FlueBoxGasket Gasket Flue Collector Box Heat Exchanger Flue Transition Combustion Air Orifice Combustion Air Pressure Switch Assembly (two switches) Combustion Air Inducer ./ Flame Sensor Limit Shield _Flame _ Air Intake Rollout Switches _ Primary Cover _ \ \ Limit Burner //_ _ Box Tol /I I Kz'2 I I NOx Insert Gas Valve Gas Orifices Gasket \ Bracket Ignitor Secondary Limit(s) Sight Glass Burner Box Cover Burner Box Bottom Control Transformer Power Choke (1 hp Only) Circuit Breaker Door Interlock Switch Two-Stage, Variable Speed Integrated Control Board FIGURE 1 Page 3 Variable Speed Blower Motor The G60UHV(X)gas furnaceis equippedwith a twostage,variablespeedintegrated control.Thiscontrolensurescompatibility withLennox'HarmonyIllzonecontrol system,aswellas a thermostatwhichprovideshumidity control.EachG60UHV(X) unitis shippedreadyforinstallationintheupfloworhorizontal position(leftorright).The furnaceisshippedwiththebottompanelinplace.Thebottompanelmustberemovediftheunitistobeinstalledina horizontal application. Thepanelmayalsoberemovedin upflowapplications. In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1). The National Fuel Gas Code is available from the following address: American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036 In Canada, installation must conform with current National Standard of Canada CSA-B149 installation codes for natural gas and propane gas burning appliances and equipment, local plumbing or waste water codes and other applicable local codes. Adequate clearance must be made around the air openings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standards. Package1 of 1 contains 1- Assembled G60UHV(X) unit 1- Bagassemblycontaining thefollowing: 2 -Screws 3 -Wirenuts 1-Snapbushing 1-Snapplug 1- Wiretie 1-Vent warning label Vent installations must be consistent with the venting tables (in this instruction) and applicable provisions of local building codes. This furnace is CSA Intemational certified for installation clearances to combustible material as listed on the unit The following items may be ordered separately: 1- Thermostat nameplate and in the tables in figures 6 and 11. Accessibility and service clearances must take precedence over fire protection clearances. 1 - Hanging bracket (for horizontal installations) 1 - Propane/LP changeover kit 1 - Return air base NOTE- For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring. 1 - High altitude kit 1 - Side filter kit For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid 1 -Owner's manual and warranty card Check equipment for shipping damage. If you find any damage, immediately contact the last carrier. physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards. ,&WARNING NOTE - Furnace must be adjusted to obtain a temperature rise(high and bw fire) within the range(s) specified on the unit nameplate. Failure to do so may cause erratic limit operation. This G60UHV(X) furnace must be installed so that its electrical components are protected from water. ,&,CAUTION G60UHV(X) units are CSA International certified to ANSI Z21.47 and CSA 2.3 standard. When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting. Page 4 Wheninstalled, thisfurnacemustbeelectrically grounded according tolocalcodes.Inaddition,intheUnitedStates, installationmustconformwiththecurrentNationalElectricCode,ANSI/NFPA No.70.TheNationalElectricCode (ANSI/NFPA No.70) is availablefromthe followingaddress: NationalFireProtection Association 1 BatteryMarchPark Quincy,MA02269 InCanada,allelectricalwiringandgrounding fortheunit mustbeinstalled according tothecurrentregulations ofthe CanadianElectricalCodePartI (CSAStandardC22.1) and/orlocalcodes. NOTE - This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermit- • One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside. • The furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned following final construction clean-up. • All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified according to these installation instructions. NOTE - The Commonwealth of Massachusetts lates these additional requirements: • Gas furnaces shall be installed by a llcensedplumber or gas fittter only. tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem- • The gas cock must be "T handle" perature must not exceed 85°F (29 °C) dry bulb. Lennox does not recommend the use of G60UHV(X) units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit. type. • When a furnace is installed in an attic, the passageway to and service area surrounding the equipment shall be floored. The G60UHV(X) furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms in the upflow or horizontal position. This furnace design has not been CSA International certified for installation in mobile homes, recreational vehicles, or outdoors. stipu- These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. In addition to the requirements outlined previously, the following general recommendations must be considered when installing a G60UHV(X) furnace: G60UHV(X) units may be used for heating of buildings or structures under construction, if the following conditions are met: • The vent system must be permanently installed per these installation instructions. • A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not aflowed. • The return air duct must be provided and sealed to the furnace. • Return air temperature range between 60°F (16°C) and 80°F (27°C) must be maintained. • Air filters must be instafled in the system and must be maintained during construction. • Air filters must be replaced upon construction completion. • The input rate and temperature rise must be set per the furnace rating plate. Page 5 • Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the chimney or vent termination point. • Do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation. • Do not block the furnace combustion air openings with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation. • When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace. j WARNING ACAUTION In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today's homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation. In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in this section to install G60UHV(X) furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1). This reprinted material is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety. In Canada, refer to the standard CSA B149 installation codes. &CAUTION All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliances will operate inefficiently and unsafely, Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house, When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide, In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components, The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space, Unconfined Space An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1,42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space, This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by Page 6 infiltration,If thefurnaceis locatedin a buildingof tight construction withweatherstrippingandcaulkingaround thewindowsanddoors,followthe procedures in the air fromoutsidesection, Confined Space A confined space is an area with a volume less than 50 cubic feet (1,42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms, When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace, This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition, Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside. _ CHIMNEY _ _ /_ EQUIPMENT IN CONFINED SPACE ALL AIR FROM INSIDE OR GAS Air from Inside If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm 2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas-fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 2. Air from Outside If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm 2) per 4,000 Btu (1,17 kW) per hour d total input rating of all equipment in the enclosure, See figures 3 and 4. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm 2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure, See figure 5. h HEATER FURNACE 1_ OPENINGS (To Adjacent Room) _ ,,,,j, I I WiTER / ,, ,, ,, ,, ,,,: I I ,, NOTE - Each opening shall have a free area of at least one square inch (645 mm 2) per 1,000 Btu (.29 kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (64516 ram2). When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation. FIGURE 2 Page 7 EQUIPMENT IN CONFINED SPACE ALL AIR FROM OUTSIDE (Inlet Air from Crawlspace and Outlet Air to Ventilated Attic) CHIMNEY OR GAS VENT VENTILATION LOUVERS (Each end of altic) I ...... I OUTLET AIR FURNACE WATER HEATER VENTILATION LOUVERS (For unheated crawl ._ INLET AIR _1 _rrrm rrrm I NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4, 000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure. FIGURE 3 A TT_. EQUIPMENT IN CONFINED SPACE ALL AIR FROM OUTSIDE CHIMNEY OR GAS _ JJ_ I I "b__JY EQUIPMENT IN CONFINED SPACE _ ALLAIRFROM (All Air Through Ventilated Attic) VENT'_ VENTILATION LOUVERS (Each end of attic) FURNACE !lq!ll INLET AIR Ends 12 in. above bottom NLET AI II II l . . 1T-T. II II II IL_ I I I I I I I I I I I___J I I I I I I I I I I I I I I I I I I I I I I I NOTE - Each air duct opening shaft have a free area of at least one square inch (645 mm 2) per 2,000 Btu (. 59 kW) per hour of the total input rating of aft equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shaft have a free area of at least one square inch (645 mm 2) per 4,000 Btu (1.17 kW) per hour of the total input rating of aft other equipment in the enclosure. HEATER NO TE-The inlet and outlet air openings shaft each have a free area of at least one square inch (645 mm 2) per 4,000 Btu (1.17 kW) per hour of the total input rating of aft equipment in the enclosure. FIGURE 4 FIGURE 5 Page 8 on the unit nameplate, Minimum clearances for closet or alcove installations are shown in figure 6. -&WARNING Upflow Application Installation Clearances Top Left Side Right Side The G60UHV(X) gas furnace can be installed as shipped in either the upflow position or the horizontal position, with right-hand or left-hand air discharge. Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level. NOTE - Units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be removed before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg will not touch the blower housing. NOTE - G60UHV-60D-135 units are equipped with a ship- ping pad under the blower housing. Remove the shipping pad prior to operation. Upflow Applications Allow for clearances to combustible materials as indicated Page 9 Bottom Type of Vent Connector Type C Type B1 Top 1 in. (25 ram) 1 in. (25 ram) *Front 3 in. (76 ram) 3 in. (76 ram) Back 0 0 Sides 01- 0 Vent 6 in. (152 ram) 1 in. (25 ram) Floor 05 05 *Front clearance in alcove installation must be 24 in. (610 ram). Maintain a minimum of 24 in. (610 ram) for front service access. SFor installation on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring. 1-Left side requires 3 inches if a single wall vent is used on 14-1/2 inch cabinets, or 2 inches if a single wall vent is used on 17-1/2 inch cabinets. FIGURE 6 Return Return Air -- Upflow air can be brought in through side of the furnace installed furnace on a platform is installed an airtight platform seal between to ensure Markings cabinet NOTE is equipped operates make and the properly with a removable on both sides of the furnace that require at the maximum - When If the with bottom return, the bottom of the furnace Side Return Air (with transition and filter) or either and bottom 20" X 25" X 1" (508mm X635mm X 25mm) Cleanable Filter installation, are provided for installations the bottom in an upflow application, that the furnace safely. The furnace panel to facilitate Applications cabinet _/ side return air. Cut the furnace dimensions air volumes over shown 1800 cfm on page 2. (850 L/s) are required with 60C or 60D models in an upflow application, the following return air options are available: Return Air Plenum 1 - Return air from single side with transition which will accommodate 20 x 25 x I in. (508 x 635 x 25 ram) cleanable air filter. (Required to maintain proper air velocity.) See figure 7. 2 - Return air from single side Air Base. See figure 8. 3 - Return air from bottom. with optional RAB Return 4 - Return air from both sides. 5 - Return air from bottom Refer to Engineering FIGURE 7 and one side. Handbook for additional information, (Upflow Applications Optional Return Air Base Only -- For use with B, C and D cabinets only) J I I © m 4 14 "-_ ;-.91-- 102)1 AIR FLOW L v (446) RAB-B 21 (533) RAB-C Overall 7 =1 1 Minimum 11 (279) I 2 Maximun_ 1 Unit side return air 1A 1356)_ Opening ___ jl__ _ I 7-1/4 (184) 24-1/2 f (Maximum) t 17-1/2 1 23 (584) (98M60) (98M58) (622) RAB-D (98M59) I OPTIONAL RAB RETURN AIR BASE (570) Overall 'Maximum) 5-5/8 SIDE (143) AIR OPENINGS (Either Side) _1_ 1 22-7-16 _J_ RETURN 23 (584) ._ _ 3/4 (19) 7/8 .._ (22) 91--- 27-5/8 (702) SIDE VIEW FRONT VIEW NOTE- Optional Side Return Air Filter Kits are not for use with RAB Return Air Base. 1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet. 2 To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred. NOTE- Optional Side Return Air Filter Kits are not for use with RAB Return Air Base. FIGURE 8 Page 10 Removingthe Bottom Panel Leveling Bolt Installation Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel, Once the bottom panel has been removed, reinstall the bottom cap. See figure 9, Inches (mm) 3/8 (10) Furnace Front 3/8 1-3/4 (44) Removing the Bottom Panel 1-3/4 (44) Leveling Leveling Bolt Locations Bolt (3/8) 3/8 (10) 1-3/4 (44) 1-3t4 (44) FIGURE 10 Screw Horizontal Applications The G60UHV(X) furnace can be installed in horizontal applications, \/ Bottom Cap Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 11, Bottom Horizontal Application Installation Clearances FIGURE 9 Top Leveling an Upflow Unit When the side return air inlets are used in an upflow application, it may be necessary to install leveling bolts on the Left End bottom of the furnace. Use field-supplied corrosion-resistant 5/16 inch machine bolts (4) and nuts (8), See figure 10, Right End Bottom Vent Connector Type NOTE - The maximum length of the bolt is 1-1/2 inches. 1 - Lie the furnace on its back and drill a 5/16 inch diame- Type C Type B1 ter hole in each corner of the furnace's bottom, See figure 10 for the correct location of the holes, Drill through the bottom panel and the bottom flange of the cabinet. Top 0 0 *Front 3 in. (76 ram) 3 in, (76 ram) Back 0 0 2 - Install one bolt and two nuts into each hole. Screw the first nut onto a bolt and then insert the bolt into a hole. A Ends 2 in. (51 ram) 2 in. (51 ram) Vent fiat washer may be added between the nut and the bottom of the unit. 3 - Screw another nut onto the bolt on the inside of the furnace base. A fiat washer may be added between the nut and the bottom of the unit, 4 - Adjust the outside nut to the appropriate height and tighten the inside nut to secure the arrangement, Bottom 6 in. (152 ram) 05 1 in. (25 ram) 05 *Front clearance in alcove installation must be 24 in. (610 ram). Maintain a minimum of 24 in. (610 ram) for front service access. SFor installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring. Page 11 FIGURE 11 Thisfurnacemaybeinstalledineitheranatticora crawlspace.Eithersuspendthe furnacefromroof raftersor floorjoists,asshowninfigure12,orinstallthefurnaceon a platform,as shownin figure13.Theunitmustbesupportedat bothendsandbeneaththeblowerdecktopreventsagging. Typical Horizontal Application Unit Suspended in Attic or Crawlspace Horizontal Application Unit Installed on Platform NOTE - Line contact is permissible. See the unit nameplate for clearances. \ \ \ "x, Leave sufficient clearance between rod and unit to remove access panel. FIGURE 13 WARNING FIGURE 12 NOTE - Heavy-gauge perforated sheet metal straps (plumbers' straps) may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be providedfor both the ends and the middle of the furnace to prevent sagging. The straps must not interfere with the plenum or exhaust piping installation. Securing screws should be 1/2 inch from the top edge and 1-1/2 inch from the side edge in all cases. Cooling coils and supply and return air plenums must be supported separately. NOTE - When the furnace is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the evaporator coil to drain. Return Air -- Horizontal Applications Return air can be brought in through the end of a furnace installed in a horizontal application. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 9. Page 12 _&WARNING Thisunitis notequippedwitha filteror rack.A field-providedhigh-velocity filteris requiredfortheunittooperate properly,Table1 listsrecommended filtersizes, A filtermustbein placeanytimetheunitisoperating, TABLE1 Furnace Cabinet Size Filter Size Side Return Bottom Return 14-1/2" 16X25X1 (1) 14X25X 1 (1) 17-1/2" 16X25X1 (1) 16X25X 1 (1) 21" 16X25X1 (1) 20 X 25 X 1 (1) 24-1/2" 16X25X1 (2) 24 X 25 X 1 (1) Use industry-approved standards (such as those published by Air Conditioning Contractors of America or American Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution. A 4-inch diameter flue transition is factory-installed on the combustion air inducer outlet of all models. Modifying or removing the flue transition will cause the unit to operate unsafely and will void the unit certification. The vent connector does not require insulation. The combustion air inducer may be rotated clockwise or counterclockwise by 90 ° to allow for top or side vent discharge in all applications. When the unit is installed, the flue transition must be in the 9 o'clock, 12 o'clock or 3 o'clock position. The unit will not vent properly with the flue transition pointed down in the 6 o'clock position. Remove the four mounting screws, rotate the assembly (including the gasket), then reinstall the mounting screws. See figure 14. Use the provided wire tie to bundle the pressure switch wires with the inducer motor power leads. Route the wires away from moving parts and the heat of the inducer motor to prevent damage to the wires. Combustion (Upflow Position) MOUNTING SCREW% ______ NOTE - Do not operate the furnace with an external static pressure that exceeds 0.8 inches w.c. Higher external static pressures may cause erratic tim# operation. Supply Air Plenum Flue Transition If the furnace is installed without a cooling coil, a removable access panel must be installed in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after the furnace is installed. The furnace access (Do not remove) panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system. Air Inducer (Remove) 90 ° _ L Mounting Screws (Remove) FIGURE 14 Return Air Plenum Return air must not be drawn from a room where this furnace, or any other gas appliance (ie., a water heater), is installed. When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system. In upfiow applications, the return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. Ira filter is installed, size the return air duct to fit the filter frame. Page 13 Optional Flue Outlet (Horizontal Installation) Top View of Furnace Top Cap -----_. f_ Flue Outlet Hole (Reattach Cutout Here) _-J_'J IIII/! I Supply Air Opening Optional Flue Outlet FIGURE 15 Usesheetmetalshearstoremove thecutoutfromtheside ofthecabinet.Usethetwoprovided sheetmetalscrewsto installthecutoutonthetopcaptocovertheoriginalflue outletopening.Seefigure15, TheG60UHV(X) seriesunitsareclassified asfan-assisted CategoryI furnaceswhenverticallyventedaccordingto thelatesteditionof NationalFuelGasCode(NFPA54 / ANSI Z223.1) in the USA and the current standards of CSA B149 Natural Gas and Propane Installation Codes in Canada. A fan-assisted Category I furnace is an appliance equipped with an integral mechanical means to either draw or force combustion products through the combustion chamber and/or heat exchanger. NQ TE - Use these instructions as a guide. They do not supersede local codes, This furnace must be vented according to all local codes these installation instructions, and the provided venting tables in these instructions The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223,1 ) and are provided as a guide for proper vent installation, Proper application, termination, construction and location of vents must conform to local codes having jurisdiction. In the absence of local codes, the NFGC serves as the defining document, Refer to the tables and the venting information contained in these instructions to properly size and install the venting system, A, IMPORTANT Use self-drilling sheet metal screws or a mechanical fastener to firmly secure the vent pipe to the round collar of the flue transition. If self-drilling screws are used to attach the vent pipe, it is recommended that three be used. Drive one self-drilling screw through the front and one through each side of the vent pipe and collar. See figure 16. Install the first vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet, Venting Using a Masonry Chimney The following additional requirements apply when a lined masonry chimney is used to vent this furnace. Masonry chimneys used to vent Category I central furnaces must be either tile-lined or lined with a listed metal lining system or dedicated gas vent, Unlined masonry chimneys are prohibited, See figures 17 and 18 for common venting. A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney. An exterior masonry chimney that is not tile-lined must be lined with B1 vent or a listed insulated flexible metal vent. An exterior tile-lined chimney that is sealed and capped may be lined with a listed uninsulated flexible metal vent, If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting method must be found. G60UHV units installed in upflow applications may be vented into a tile-lined masonry chimney without using a listed metal liner, provided that the optional masonry chimney vent adapter kit (18M79) is used. Instructions provided with the kit must be followed exactly. Insulation for the flexible vent pipe must be an encapsulated fiberglass sleeve recommended by the flexible vent pipe manufacturer, See figure 17, Common Venting Using Metal-Lined Masonry Chimney AWARNING MAX. LENGTH +- SEE NOTE 1 BELOW. l 5_!15o,) I MINLENGTH-AS rnm]rnurn SHORT AS PRACTICAL I SEALjD II _ i i EXTERIOR II ___v VENT CONNECTION i_-'_- I', ; 4,n+{,02o, METAL LINER CH_MNEYW_TH J VENT PIPE J SEALED FIREPLACE OPENING NOTE FURNACE and NOTE FLUE TRANSITIC COLLAR used. 1 - Refer the venting 2 - Either Refer tables for CSA-B149 FIGURE 16 to the provided tables in venting CSA-B149 single-walled to the requirements in in USA and Canada. installations the in the USA Canada. vent shown FIGURE 17 Page 14 for installations or doable-walled capacity installations for installations tables for connector may in the provided venting tables be venting in current Common Venting Using Tile-Lined Interior Masonry Chimney and Combined Vent Connector J MINIMUM LENGTH FOR MAXIMUM NOTE- Refer to provided venting tables for installations in the USA and the venting tables in current CSA-B149 for installations in Canada. F1 _ H H = AS SHORT LENGTH I i= ! ' SEE NOTE I _T L-_-- _ I I I A p_THAENRcE FURNACE _N/ TO LEFT I I I =" I ] 'l IJ_ _ I _ F_ 4--4 ........... __ I AS PRACTICAL. _ --_ I A I _ _ I ._ I CONNECTOR I SEE I [ I NOTE 1 BELOW J INTERIOR TILE=LINED MASONRY CHIMNEY I ]J _"_ [/_ ] _ I I ] _ VENT _ I NOTE-thechimneymustbeproperly sizedperprovided venting tables or lined with llsted metal llning system. I_ iiiMANDN_INTLYL A CE NOTE - Either single-walled or double-walled vent connector may be used. Refer to the capacity requirements as shown in the provided venting tables for installations in USA and the venting tables in current CSA-B149 for installations in Canada. FIGURE 18 DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose granular insulating material klMPORTANT Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney. Never connect a Category I appliance to a chimney that is servicing a solid-fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed. A type B or listed chimney lining system that passes through an unused masonry chimney flue is not considered to be exposed to the outdoors. General Venting Requirements Vent all G60UHV(X) furnaces according to these instructions: 1 - Vent diameter recommendations and maximum allow- A fan-assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met: • The chimney is currently serving at least one drafthood equipped appliance • The vent connectors and chimney are sized according to the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes in Canada. If type B1 double-wall vent is used inside a chimney, no other appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products. A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings and the vent manufacturer's instructions. When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting G60UHV(X) series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions. able piping runs are found in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes for Canada. 2 - In no case should the vent or vent connector diameter be less than the diameter specified in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes for Canada. 3 - The minimum vent capacity determined by the sizing tables must be less than the low fire input rating and the maximum vent capacity must be greater than the high fire input rating. 4 - Single appliance vents - If the vertical vent or tile-lined chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to determine the minimum vent capacity and the vent connector diameter to determine the maximum vent capacity, The flow area of the vertical vent, however, shall not exceed 7 times the flow area of the listed appliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods. Page 15 5- Multiple appliance vents - The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods. 6 - The entire length of single wall metal vent connector shall be readily accessible for inspection, cleaning, and replacement. 7 - Single appliance venting configurations with zero lateral lengths (tables 3 and 4) are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90 ° elbow or equivalent (for example two 45 ° elbows equal one 90 ° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10% (0.90 x maximum listed capacity). 8 - The common venting tables (5, 6, 7, and 8) were generated using a maximum horizontal vent connector length of 1-1/2 feet (.46 m) for each inch (25 mm) of connector diameter as follows: TABLE 2 Connector Diameter inches (mm) Maximum Horizontal Connector Length feet (m) 3 (76) 4-1/2 (1.37) 4 (102) 6 (1.83) 5 (127) 7-1/2 (2.29) 6 (152) 9 (2.74) 7 (178) 10-1/2 (3.20) 9 - If the common vertical vent is offset, the maximum common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent d two 90 ° elbows (0.80 x maximum common vent capacity). The horizontal length of the offset shall not exceed 1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter. 10 - The vent pipe should be as short as possible with the least number of elbows and angles required to complete the job. Route the vent connector to the vent using the shortest possible route. 11 - A vent connector shall be supported without any dips or sags and shall slope a minimum of 1/4 inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance. 12 - Vent connectors shall be firmly attached to the furnace flue collar by self-drilling screws or other approved means, except vent connectors of listed type B vent material which shall be assembled according to the manufacturer's instructions. Joints between sections of single wall connector piping shall be fastened by screws or other approved means. 13-When the vent connector used for Category I appliances must be located in or pass through a crawlspace or other areas which may be cold, that portion of the vent connector shall be constructed of listed double-wall type B vent material or material having equivalent insulation qualities. 14 - All venting pipe passing through floors, walls, and ceilings must be installed with the listed clearance to combustible materials and be fire stopped according to local codes. In absence of local codes, refer to NFGC (Z223.1). 15 - No portion of the venting system can extend into, or pass through any circulation air duct or plenum. 16- Vent connectors serving Category I appliances shall not be connected to any portion of mechanical draft systems operating under positive pressure such as Category Ill or IV venting systems. 17 - If vent connectors are combined prior to entering the common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10%, the equivalent of one 90 ° elbow (0.90 x maximum common vent capacity). 18 - The common vent diameter must always be at least as large as the largest vent connector diameter. 19 - In no case, shall the vent connector be sized more than two consecutive table size diameters over the size of the draft hood outlet or flue collar outlet. 20 - Do not install a manual damper, barometric draft regulator or flue restrictor between the furnace and the chimney. 21 - When connecting this appliance to an existing dedicated or common venting system, you must inspect the venting system's general condition and look for signs of corrosion. The existing vent pipe size must conform to these instructions and the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes for Canada. If the existing venting system does not meet these requirements, it must be resized. Page 16 TABLE 3 Capacity Height H (feet) 6 8 10 15 20 30 NOTE - Single Lateral L (feet) of Type B Double-Wall Vents with Type B Double-Wall Connectors Serving a Single Category I Appliance Vent and Connector 4 Inch 3 Inch Appliance MIN Diameter - D (inches) 5 Inch Input Rating in Thousands MAX MIN 6 Inch of Btu Per Hour MAX MIN MAX MIN MAX 0 0 78 0 152 0 251 0 375 2 13 51 18 97 27 157 32 232 4 21 49 30 94 39 153 50 227 6 25 46 36 91 47 149 59 223 0 0 84 0 165 0 276 0 415 2 12 57 16 109 25 178 28 263 5 23 53 32 103 42 171 53 255 8 28 49 39 98 51 164 64 247 0 0 88 0 175 0 295 0 447 2 12 61 17 118 23 194 26 289 5 23 57 32 113 41 187 52 280 10 30 51 41 104 54 176 67 267 0 0 94 0 191 0 327 0 502 2 11 69 15 136 20 226 22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 50 229 62 351 15 34 58 46 124 59 217 73 337 20 48 52 55 116 69 206 84 322 0 0 100 0 213 0 374 0 587 2 9 81 13 166 14 283 18 432 5 21 77 28 160 36 275 45 421 10 27 70 37 150 48 262 59 405 15 33 64 44 141 57 249 70 389 20 56 58 53 132 66 237 80 374 30 NR NR 73 113 88 214 104 346 appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90 ° elbow or equivalent (for example two 45 ° elbows equal one 90 ° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity). Page 17 TABLE 4 Capacity of Type B Double-Wall Vents with Single-Wall Metal Connectors Serving a Single Category I Appliance Vent and Connector Height H (feet) 6 8 10 15 20 30 Lateral L (feet) 3 Inch Diameter - D (inches) 4 Inch Appliance MIN 5 Inch Input Rating in Thousands MAX MIN MIN MAX 0 38 77 59 151 85 2 39 51 60 96 85 4 NR NR 74 92 6 NR NR 83 0 37 83 2 39 5 6 Inch of Btu Per Hour MAX MIN MAX 249 126 373 156 123 231 102 152 146 225 89 114 147 163 220 58 164 83 273 123 412 56 59 108 83 176 121 261 NR NR 77 102 107 168 151 252 8 NR NR 90 95 122 161 175 243 0 37 87 57 174 82 293 120 444 2 39 61 59 117 82 193 119 287 5 52 56 76 111 105 185 148 277 10 NR NR 97 100 132 171 188 261 0 36 93 56 190 80 325 116 499 2 38 69 57 136 80 225 115 337 5 51 63 75 128 102 216 144 326 10 NR NR 95 116 128 201 182 308 15 NR NR NR NR 158 186 220 290 0 35 96 54 200 78 346 114 537 2 37 74 56 148 78 248 113 375 5 50 68 73 140 100 239 141 363 10 NR NR 93 129 125 223 177 344 15 NR NR NR NR 155 208 216 325 20 NR NR NR NR 186 192 254 306 0 34 99 53 211 76 372 110 584 2 37 80 55 164 76 281 109 429 5 49 74 72 157 98 271 136 417 10 NR NR 91 144 122 255 171 397 15 NR NR 115 131 151 239 208 377 20 NR NR NR NR 181 223 246 357 30 NR NR NR NR NR NR NR NR NOTE - Single appfiance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90 ° elbow or equivalent (for example two 45 ° elbows equal one 90 ° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity). Page 18 TABLE 5 Vent Connector Capacity Type B Double-Wall Vents with Type B Double-Wall Connectors Serving Two or More Category I Appliances Vent Height H (feet) Connector Rise R (feet) 6 8 10 15 20 30 Vent and Connector 3 Inch Diameter - D (inches) 4 Inch 5 Inch Appliance Input Rating in Thousands of Btu Per Hour MIN MAX MIN MAX MIN MAX 1 22 37 35 66 46 2 23 41 37 75 48 3 24 44 38 81 1 22 40 35 2 23 44 3 24 47 6 Inch MIN MAX 106 58 164 121 60 183 49 132 62 199 72 49 114 64 176 36 80 51 128 66 195 37 87 53 139 67 210 1 22 43 34 78 49 123 65 189 2 23 47 36 86 51 136 67 206 3 24 50 37 92 52 146 69 220 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 1 20 62 31 113 45 181 60 288 2 21 64 33 118 47 190 62 299 3 22 66 34 123 48 198 64 309 TABLE 6 Common Vent Capacity Type B Double-Wall Vents with Type B Double-Wall Connectors Serving Two or More Category I Appliances Common Vent Diameter Vent Height H (feet) 4 Inch - D (inches) 5 Inch 6 Inch FAN + FAN FAN + NAT Appliance FAN + FAN 6 92 81 140 116 204 8 101 90 155 129 224 10 110 97 169 141 15 125 112 195 20 136 123 30 152 138 7 Inch Input Rating in Thousands of Btu Per Hour FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT 161 309 248 178 339 275 243 194 367 299 164 283 228 427 352 215 183 314 255 475 394 244 210 361 297 547 459 Page 19 TABLE 7 Vent Connector Capacity Type B Double-Wall Vents with Single-Wall Metal Connectors Serving Two or More Category I Appliances Vent Height H (feet) 6 15 30 Vent and Connector Diameter - D (inches) Connector Rise R (feet) MIN MAX I NR NR NR NR NR 2 NR NR NR NR 3 NR NR NR NR 1 NR NR 79 2 NR NR 3 NR NR 1 47 2 3 3 Inch 4 Inch 5 Inch Appliance Input Rating in Thousands of Btu Per Hour MIN MAX MIN MAX 6 Inch MIN MAX NR NR NR NR NR 168 182 121 131 174 198 87 116 138 177 214 83 94 121 150 185 230 87 100 127 160 193 243 60 77 110 113 175 169 278 50 62 81 115 117 185 177 290 54 64 85 119 122 193 185 300 TABLE 8 Common Vent Capacity Type B Double-Wall Vents with Single-Wall Metal Connectors Serving Two or More Category I Appliances Common Vent Diameter Vent Height 4 Inch - D (inches) 5 Inch 6 Inch 7 Inch H (feet) FAN + FAN FAN + NAT Appliance FAN + FAN Input Rating in Thousands of Btu Per Hour FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT 6 89 78 136 113 200 158 304 244 8 98 87 151 126 218 173 331 269 10 106 94 163 137 237 189 357 292 15 121 108 189 159 275 221 416 343 20 131 118 208 177 305 247 463 383 30 145 132 236 202 350 286 533 446 Removal of the Furnace from Common Vent and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. In the event that an existing furnace is removed from a venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances, Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting requirements section. 1 - Seal any unused openings in the common venting system, 4 - Follow the lighting instructions, Turn on the appliance that is being inspected, Adjust the thermostat so that the appliance operates continuously, 5 - After the main burner has operated for 5 minutes, test for leaks of flue gases at the draft hood relief opening, Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe, leakage, corrosion, or other deficiencies which could cause an unsafe condition, 6 - After determining that each appliance connected to the common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace dampers, and any other gas-burning appliances to their previous mode of operation, 3 - Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located 7 - If a venting problem is found during any of the preceding tests, the common venting system must be modified to correct the problem, 2 - Inspect the venting system for proper size and horizontal pitch, Determine that there is no blockage, restriction, Page 20 Resizethecommonventingsystemto the minimum ventpipesizedeterminedby usingthe appropriate tablesinAppendixG. (Thesearein thecurrentstandardsoftheNationalFuelGasCodeANSIZ223.1in theUSA,andtheappropriate Category1 NaturalGas andPropaneappliances ventingsizingtablesin the currentstandardsof theCSAB149NaturalGasand PropaneInstallation CodesinCanada.) 3 - The gas piping must not run in or through air ducts, clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts. 4 - The piping should be sloped 1/4 inch (6,4 mm) per 15 feet (4,57 m) upward toward the meter from the furnace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hangers or straps, Install a drip leg inside vertical pipe runs to the unit. 5 - A 1/8" N.RT. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection. See figures 26 and 27. XkCAUTION 6 - In some localities, codes may require the installation of a manual main shut-off valve and union (furnished by the installer) external to the unit, The union must be of the ground joint type. klMPORTANT Gas Supply 1 - This unit is shipped standard for left or right side installation of gas piping (or top entry in horizontal applications). Connect the gas supply to the piping assembly. 2 - When connecting the gas supply piping, consider factors such as length of run, number of fittings, and furnace rating to avoid excessive pressure drop. Table 9 lists recommended pipe sizes for typical applications. NOTE - If emergency shutoff is necessa04 shut off the main manual gas valve and disconnect main power to the furnace. The installer should properly label these devices. TABLE 9 Gas Pipe Capacity - ft3/hr (m3/hr) Nominal Iron Pipe Size inches (ram) 3/8 Length of Pipe - feet (m) Internal Diameter inches (ram) 10 (3.048) 20 (6.096) 30 (9.144) 40 (12.192) 50 (15.240) 60 (18.288) .493 (12.522) 95 (2.69) 65 (1.84) 52 (1.47) 45 (1.27) 4O (1.13) 36 (1.02) 33 (.73) .622 (17.799) 175 (4.96) 120 (3.40) 97 (2.75) 82 (2.32) 73 (2.07) 66 .824 (20.930) 360 (10.19) 250 (7.08) 2OO (5.66) 170 (4.81) 151 (4.28) 1.049 (26.645) 680 (919.25) 465 (13.17) 375 (10.62) 32O (9.06) 1.380 (35.052) 1400 (39.64) 950 (26.90) 77O (21.80) 66O (18.69) (16.42) 53O (15.01) 490 (13.87) 46O (13.03) 430 (12.18) (11.33) (38.1) 1.610 (40.894) 2100 (59.46) 460 (41.34) 1180 (33.41) 990 (28.03) 9OO (25.48) 810 (22.94) 75O (21.24) 69O (19.54) 65O (18.41) 62O (17.56) 2 (50.8) 2.067 (52.502) 3950 (111.85) 2750 (77.87) 2200 (62.30) 1900 (53.80) 1680 (47.57) 1520 (43.04) 1400 (39.64) 1300 (36.81) 1220 (34.55) 1150 (32.56) 2-1/2 (63.5) 2.469 (67.713) 6300 (178.39) 4350 (123.17) 3520 (99.67) 3000 (84.95 2650 (75.04) 2400 (67.96) 2250 (63.71) 2050 (58.05) 1950 (55.22) 1850 (52.38) 3 (76.2) 3.068 (77.927) 11000 (311.48) 7700 (218.03) 6250 (176.98) 5300 (150.07) 4750 (134.50) 4300 (121.76) 3900 (110.43) 3700 (104.77) 3450 (97.69) 3250 (92.03) (9.53) 1/2 (12.7) 3/4 (19.05) 1 (25.4) 1-1/4 (31.75) 1-1/2 NOTE - Capacity given 285 (8.07) 580 80 (24.384) 90 (27.432) lOO (30.480) 31 (.88) 29 (.82) 27 (.76) 61 (1.73) 57 (1.61) 53 (1.5o) 5O (1.42) (3.91) 125 (3.54) 118 (3.34) 110 (3.11) 103 (2.92) 26O (7.36) 24O 22O (6.23) 2O5 195 (6.80) (5.80) (5.52) 400 (1.87) 138 70 (21.336) in cubic feet (m3 ) of gas per hour and based on O.60 specific gravity gas. Page 21 Left Side Piping (Standard) MANUAL MAIN SHUT-OFF AUTOMATIC GAS VALVE (with manual shuboff valve) AUTOMATIC GAS VALVE (with manual shut-off valve) VALVE (With 1/8 in. NPT Plugged Tap Shown) MANUAL SHUT-OFF VALVE (With 1/8 in. NPT Plugged Tap Shown) JOINT UNION GROUND JOINT UNION _DRIP Right Side Piping (Alternate) FIELD PROVIDED ANDINSTALLED DRIP LEG LEG FIGURE 19 Leak Check After gas piping is completed, carefully check all piping connections (factory- and field-installed) for gas leaks, Use a leak detecting solution or other preferred means. NOTE - If emergency shutoff is necessa04 shut off the main manual gas valve and disconnect the main power to the furnace. The installer should properly label these devices. ELECTROSTATIC DISCHARGE (ESD) Precautions and Procedures kCAUTION ,CAUTION The furnace must be isolated from the gas supply system by closing #s individual manual shut-off valve during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.). The unit is equipped with a field make-up box, The makeup box may be moved to the right side of the furnace to facilitate installation, If the make-up box is moved to the right side, the excess wire must be pulled into the blower compartment, Secure the excess wire to the existing harness to protect it from damage. ,IMPORTANT INTERIOR MAKE-UP BOX INSTALLATION MAKE-UP BOX ISOLATE GAS VALVE SHUT-OFF VALVE WILL NOT HOLD NORMAL TEST PRESSURE MANUAL MAIN \ FURNACE | CAP 6 FIGURE 20 FIGURE 21 Page 22 INTERIOR MAKE-UP National Electric Code (ANSI/NFPA No, 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada, A green ground wire is provided in the field make-up box, NOTE- The G6OUHV(X) furnace contains electron- BOX INSTALLATION MAKE-UP Left side J BOX ic compon en ts that are polarity sen sitive, Make sure that the furnace is wired correctly and is properly grounded, 7 - One line voltage "EAC" 1/4" spade terminal is provided on the furnace control board. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg d the circuit being connected to the one of the provided neutral terminals. See figure 25 for control board configuration, This terminal is energized when the indoor blower is operating, 8- FIGURE 22 Refer to figure 23 for schematic wiring diagram and troubleshooting and table 10 and figure 24 for field wiring, 1 - Select circuit protection and wire size according to the unit nameplate. The power supply wiring must meet Class I restrictions, 2 - Holes are on both sides of the furnace cabinet to facilitate wiring, 3 - Install a separate disconnect switch (protected by either fuse or circuit breaker) near the furnace so that power can be turned off for servicing, 4 - Before connecting the thermostat or the power wiring, check to make sure the wires will be long enough for servicing at a later date, Remove the blower access panel to check the length of the wire, 5- Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wiring diagrams shown in table 10 and figure 24, Use 18-gauge wire or larger that is suitable for Class II rating for thermostat connections, One line voltage *'HUM" 1/4" spade terminal is provided on the furnace control board. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 25 for control board configuration. This terminal is energized in the heating mode whenever the combustion air inducer is operating. 9 - One 24V "H" terminal is provided on the furnace control board terminal block. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit being connected to either ground or the "C" terminal. See figure 25 for control board configuration. 10-Install the room thermostat according to the instructions provided with the thermostat, See table 10 for field wiring connections in varying applications. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat, Indoor Blower Speeds 1- When the thermostat is set to "FAN ON," the indoor blower will run continuously at approximately 38% of the second-stage cooling speed when there is no cooling or heating demand, 2- When the G60UHV(X) is running in the heating mode, the indoor blower will run on the heating speed designated by the positions of DIP switches 11 and 12. 3- When there is a cooling demand, the indoor blower will run on the cooling speed designated by the positions of DIP switches 5 and 6, 6 - Electrically ground the unit according to local codes or, in the absence of local codes, according to the current Page 23 TABLE 10 Field Wiring Applications Thermostat 1 Heat/1 Cool Jumper Settings W915 Two-Stage DIP Switch 1 Cooling ON Intact (See figure 25) W914 Dehumidification W951 or Harmony Heat Pumps III Intact Intact NOTE - Use DiP switch 2 to set second-stage heat ON delay. QFF-IO minutes. ON-15 minutes. Wiring Connections Sl T'STAT CONTROL TERM. STRIP @ ® ® ®______ ® _, ® 1 Heat / 2 Cool OUTDOOR UNIT ON Cut Intact Intact NOTE - Use DIP switch 2 to set second-stage heat QN delay. OFF-IO minutes. ON-15 minutes. Sl T'STAT ® ® % CONTROL TERM. STRIP OUTDOOR UNIT @ ® ® ® ® ® @ ® @. @ ® @ @ @ 1 Heat / 2 Cool with t'stat with humidity control NOTE - Use DIP switch 2 to set second-stage heat ON delay. QFF-fO minutes. ON-15 minutes. ON Cut Cut Intact $1 T'STAT CONTROL TERM. STRIP OUTDOOR UNIT @ @ ® ® ® @ Page 24 ® ® _---_ @---@ ®---_ TABLE 10 Field Wiring Applications (Continued) Jumper Settings (See figure 25) W915 W914 DehuThermostat DIP Switch 1 Two-Stage Cooling midification or Harmony III W951 Heat Pumps 2 Heat / 2 Cool OFF Cut Intact Intact Wiring Connections $1 T'STAT CONTROL TERM. STRIP OUTDOOR UNIT @ ® ® ® @. @2 Heat / 2 Cool with t'stat with humidity control OFF Cut Cut Intact $1 T'STAT ® ® @ ® ® ® @ @ CONTROL TERM. STRIP @ @ @ @. ®. ® ®. ® ® OUTDOOR UNIT ® @----@ ®----@ @ L 12 Heat / 1 Cool OFF Intact Intact Intact $1 T'STAT CONTROL TERM. STRIP OUTDOOR UNIT @ ® ® 0- 4_- ® L Page 25 @ G60UHV(X) Schematic Wiring Diagram FIGURE 23 Page 26 TYPICAL G60UHV(X) FIELD WIRING DIAGRAM t20V ACC G PR]HARY GAS LI ...,m.ili-- D _ CONDUCTORS FIELD INSTALLED FIELD INSTALLED INDUCE'R HOTOR P84 _ CQHBUSTIQN 0 = $51 I@@@_)©@@1 f , i 3t59 i = I RQLLDUT $VITCH _ E $_/ITCH Tt _i $21 TRANSFOR_R SEC_Y LIMIT =_ J INTEGRATED CONTROL = SVITCH __P159 PtSS THERMOSTAT 0 SENSOR RDLLOUT SVITCH CLASS II 24V LINE VOLTAGE VALVE HIGH HEAT oQ%o FLAME ONLY. AIR BURNERS N ...,,e-i. USE COPPER J84 .......... c ..... ] _ ............... ! 2 L._. C_8 L_t.U.._HH_-H2L _.H_-i i. ......................... .........,, r ............... , , ?_1111 _ .d.-r-J-_..÷_- t_---- _-e I I I t HDTI_ J 24V IN_U'T...... FIGURE 24 TWO-STAGE, VARIABLE SPEED INTEGRATED CONTROL BOARD I OOOq 1/4" QUICK sl STATUS= E-COW- DIAGNOSTIC LEDs HEATING INDOOR BLOWER DIP SWITCHES SWITCHES DIP CONNECT TERMINALS HUM : 120 VAC OUTPUT TO HUMIDIFIER XMFR : 12O VAC OUTPUT TO TRANSFORMER LI : 120 VAC INPUT TO CONTROL CIRC : 120 VAC OUTPUT TO CIRCULATING BLOWER EAC : 120 VAC OUTPUT TO ELECTRONIC AIR CLEANER NEUTRALS= 120 VAC NEUTRAL ON-BOARD JUMPERS THERMOSTAT CONNECTIONS (TB1) DS: DEHUMIDIFICATIONSIGNAL W2: HEATDEMAND FROM2ND STAGET'STAT Wl: HEAT DEMAND FROM IST STAGE T'STAT R: CLASS 2 VOLTAGE TO THERMOSTAT G: MANUAL FAN FROM T'STAT C: THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GROUND (TR) & CHASIS GROUND (GRD) YI: THERMOSTAT Is_"STAGE COOL SIGNAL Y2: THERMOSTAT 2nd STAGE COOL SIGNAL 0--THERMOSTAT SIGNAL TO HEAT PUMP REVERSINGVALVE H= 24V HUMIDIFIER OUTPUT L= LENNOX SYSTEM OPERATION MONITOR 1= FUTURE USE DIP SWITCH FUNCTIONS HTG DIP SWITCH(ES) 1 2 3 and 4 INDOOR BLOWER DIP SWITCH(ES) 5 and 6 7 and 8 9 and 10 11 and 12 FIGURE 25 Page 27 FUNCTION T'stat Heat Staqes (sin qle or two-staqe) Second Staqe ON Delay (sin qle-staqe t'stat) Heatinq Fan OFF Delay FUNCTION Coolinq Blower Cooling Heating Mode Speed Mode Mode Blower Speed Adiustment Blower Ramping Blower Speed Profile TABLE 11 Blower Off Delay Switch Settings G60UHVunitsareequippedwitha two-stage,variable speedintegratedcontrol.This controlmanagesignition timing,heatingmodefan off delaysandindoorblower speedsbasedon selectionsmadeusingthe controldip switchesandjumpers.The controlincludesan internal watchguard featurewhichautomatically resetstheignition controlwhenithasbeenlockedout.Afteronehourofcontinuousthermostatdemandfor heat,thewatchguard will breakandremakethermostat demandto thefurnaceand automatically resetthecontrolto relightthefurnace. HeatingOperationDIPSwitchSettings Switch 1 -- ThermostatSelection-- Thisunitmaybe usedwitheithera single-stage or two-stagethermostat. Thethermostat selection ismadeusinga DIPswitchwhich mustbeproperlypositioned fortheparticular application. TheDIPswitchis factory-positioned for usewitha twostagethermostat. If a single-stage thermostat istobeused, theDIPswitchmustberepositioned, a - Select "OFF" for two-stage heating operation conSelect "ON" for two-stage heating operation controlled by a single-stage heating thermostat, This setting provides a timed delay before second-stage heat is initiated, Switch 2 -- Second Stage Delay (Used with SingleStage Thermostat Only) -- This switch is used to determine the second stage on delay when a single-stage thermostat is being used. The switch is factory-set in the OFF position, which provides a 10-minute delay before secondstage heat is initiated, If the switch is toggled to the ON position, it will provide a 15-minute delay before secondstage heat is initiated, This switch is only activated when the thermostat selector jumper is positioned for SINGLEstage thermostat use, Switches 3 and 4 -- Blower-Off Delay -- The blower-on delay of 45 seconds is not adjustable. The blower-off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 3 and 4 on the integrated control board, The unit is shipped from the factory with a blower-off delay of 90 seconds, The blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a supply air temperature between 90 ° and 110°F at the exact moment that the blower is de-energized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures,Table 11 provides the blower off timings that will result from different switch settings, Switch 3 Switch 4 Off On 90 120 180 Off On On Off Off On Indoor Blower Operation DIP Switch Settings Switches 5 and 6 -- Cooling Mode Blower Speed -Switches 5 and 6 are used to select cooling blower motor speed. The unit is shipped from the factory with the dip switches positioned for high speed (4) indoor blower motor operation during the cooling mode. The table below provides the cooling mode blower speeds that will result from different switch settings. Refer to tables 16 through 25 for corresponding cfm values, TABLE 12 Cooling Mode Blower Speeds trolled by a two-stage heating thermostat (factory setting); b- Blower Off Delay (Seconds) 60 Speed 1 - Low 2 - Medium Low Switch 5 On Off Switch 6 On On 3 - Medium High 4 - High (Factory) On Off Off Off Switches 7 and 8 -- Blower Speed Adjustment -Switches 7 and 8 are used to select blower speed adjustment settings. The unit is shipped from the factory with the dip switches positioned for NORMAL (no) adjustment, The dip switches may be positioned to adjust the blower speed by +10% or -10% to better suit the application, The table below provides blower speed adjustments that will result from different switch settings. Refer to tables 16 through 25 for corresponding cfm values, TABLE 13 Blower Speed Adjustment Adjustment +10% (approx,) NORMAL (Factory) Switch 7 On Off Switch 8 Off Off -10% (approx,) Off On Switches 9 and 10 -- Cooling Mode Blower Speed Ramping -- Switches 9 and 10 are used to select cooling mode blower speed ramping options, Blower speed ramping may be used to enhance dehumidification performance. The switches are factory set at option A which has the greatest effect on blower motor performance. Table 14 provides the cooling mode blower speed ramping options that will result from different switch settings, The cooling mode blower speed ramping options are detailed on the next page, NOTE - The off portion of the selected ramp profile also applies during heat pump operation in dual fuel applications, Page 28 TABLE 14 Cooling Mode Blower Speed Ramping Ramping Option Switch 9 Switch 10 A (Factory) B C Off On Off Off Off On D On On • • • • Switches 11 and 12 -- Heating Mode Blower Speed -Switches 11 and 12 are used to select heating mode blower motor speed, The unit is shipped from the factory with the dip switches positioned for medium low (2) speed indoor blower motor operation during the heating mode. The table Ramping Option A (Factory Selection) Motor runs at 50% for 30 seconds. Motor then runs at 82% for approximately 7-1/2 minutes. If demand has not been satisfied after 7-1/2 minutes, motor runs at 100% until demand is satisfied. Once demand is met, motor runs at 50% for 30 seconds then ramps down to stop. 71/2MIN 82% CFM _ 100% CFM __ OFF COOL,NG DEMAND • • Ramping Option B Motor runs at 82% for approximately 7-1/2 minutes. If demand has not been satisfied after 7-1/2 minutes, motor runs at 100% until demand is satisfied. Once demand is met, motor ramps down to stop. ( OFF 82%CFM / -- 7 1/2 MIN _ COOLING OFF DEMAND 100% CFM --'1_" • Ramping Option C Motor runs at 100% until demand is satisfied. • Once demand is met, motor runs at 100% for 45 seconds then ramps down to stop. OFF OFF ._p-- -- 100% CFM -DEMAND Ramping Option D • Motor runs at 100% until demand is satisfied. • Once demand is met, motor ramps down to stop. COOLING 100% CFM DEMAND _OFF below provides the heating mode blower speeds that will result from different switch settings, Refer to tables 16 through 25 for corresponding cfm values, TABLE 15 Heating Mode Blower Speeds Speed 1 - Low Switch 11 On Switch 12 On 2 - Medium Low (Factory) 3 - Medium High Off On On Off 4 - High Off Off On-Board Jumper W914 On-board jumper W914, which connects terminals DS and R on the integrated control board, must be cut when the furnace is installed with either the Harmony III zone control board or a thermostat which features humidity control, If the jumper is left intact the PMW signal from the HARMONY Ill control will be blocked and also lead to control damage. Refer to table 27 for operation sequence in applications including G60UHV, a thermostat which features humidity control and a single-speed outdoor unit. Table 28 gives the operation sequence in applications with a twospeed outdoor unit, On-Board Jumper W951 On-board jumper W951, which connects terminals R and O on the integrated control board, must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the jumper is left intact, terminal "O" will remain energized eliminating the HEAT MODE in the heat pump. On-Board Jumper W915 On-board jumper W915, which connects terminals Y1 and Y2 on the integrated control board, must be cut if two-stage cooling will be used. If the jumper is not cut the outdoor unit will operate in second-stage cooling only. Status LEDs (SPEED, CFM, STATUS, E-COM) The green SPEED LED indicates circulating blower speed in response to the DS signal. The LED is lit during normal blower operation and is off during a dehumidification demand. In Harmony III applications, the brightness of the LED indicates the requested blower speed. The green CFM LED indicates the blower air flow. Count the number of blinks between the two-second pauses to determine the CFM. Each blink represents approximately 100 CFM. The STATUS LED flashes diagnostic codes, which are detailed on page 43. The green E-COM LED indicates that the control is receiving and processing of commands and inputs. The LED may flash rapidly or may display a single flash, depending upon the activity. Page 29 TABLE 16 G60UHV-36A-070 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM Speed Switch Positions "ADJUST" Switch Positions Second Stage "HEAT" Speed 2 3 1 4 Second Stage "COOL" Speed 2 3 1 4 cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s + 895 420 1015 480 1275 600 1320 625 1000 470 1165 550 1260 595 1380 650 NORM 815 385 925 435 1120 530 1170 555 915 430 1035 490 1115 525 1230 580 -- 740 350 845 400 1000 475 1040 490 830 390 945 445 990 470 1085 510 "ADJUST" Switch Positions cfm L/s + 820 390 930 440 1140 NORM 755 355 855 405 1020 695 325 775 365 920 435 i 1 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s 4 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s 1 cfm L/s cfm L/s 540 1195 480 1060 565 730 3455 810 385 865 500 670 315 745 350 785 965 455 630 295 690 325 725 4 cfm L/s 410 910 430 370 850 400 340 770 365 NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s). Lennox Harmony Ill" Zone Control Applications - Minimum blower speed is 426 cfm (200 L!s). TABLE 17 G60UHV-36B-090 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM Speed Switch Positions "ADJUST" Switch Positions ;econd Stage "HEAT" Speed 2 3 1 4 Second Stage "COOL" Speed 2 3 1 cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s + N/A N/A 1025 485 1265 600 1320 625 1005 NORM N/A N/A N/A N/A 1125 530 1170 555 905 N/A N/A N/A N/A 1010 475 1045 495 825 i "ADJUST" Switch Positions 1 cfm L/s First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s 4 L/s cfm L/s cfm L/s 475 1165 550 1260 595 1385 655 425 1035 490 1110 525 1225 580 390 940 445 1000 470 1090 515 1 cfm L/s 4 cfm cfm L/s First Stage "COOL" Speed 2 3 cfm L/s cfm L/s 4 cfm L/s + N/A N/A 940 445 1140 540 1185 560 725 340 810 385 860 405 920 435 NORM N/A N/A N/A N/A 1030 485 1065 505 670 315 740 350 785 370 840 395 -- N/A N/A N/A N/A 925 435 950 450 625 295 695 330 725 345 770 365 N/A - First and second stage HEAT positions shown cannot be used on this model. NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Onty speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s). Lennox Harmony Ill" Zone Controt Applications - Minimum blower speed is 453 cfm (215 L/s). Page 30 TABLE 18 G60UHV-60C-090 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Bottom; both sides; or bottom and one side. Speed Switch Positions "ADJUST" Switch Positions + NORM -"ADJUST" Switch Positions Second Stage "HEAT" Speed 2 3 1 4 Second Stage "COOL" Speed 2 3 1 4 cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s 1570 1425 1270 740 675 600 1770 1625 1435 835 765 680 1965 1810 1635 925 855 770 2185 1990 1790 1030 940 845 1680 1520 1355 795 715 640 1795 1635 1460 845 770 690 2015 1855 1670 950 875 785 2255 2065 1845 1065 975 870 1 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s cfm L/s + 1430 675 1625 770 1815 NORM -- 1290 1165 610 550 1470 1300 695 615 1660 1470 4 1 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s cfm L/s cfm L/s 855 1990 940 1170 550 1250 590 1425 780 695 1830 1635 865 770 1060 930 500 440 1140 1015 540 480 1280 1155 4 cfm L/s 670 1600 755 605 545 1445 1285 680 605 NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s). Lennox Harmony Ill ' Zone Control Applications - Minimum blower speed is 478 cfm (225 Us). TABLE 19 G60UHV-60C-090 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Single side return air - Bold volumes require field-fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter. Speed Switch Positions "ADJUST" Switch Positions + NORM i Second Stage "HEAT" Speed 2 3 1 cfm 1520 1380 1230 L/s 715 650 580 "ADJUST" Switch Positions cfm L/s + NORM i 1385 1255 1135 655 590 535 1 cfm 1705 1540 1395 L/s 805 730 660 cfm 1910 1750 1570 L/s 900 825 740 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s 1560 1425 1265 735 670 600 1765 1580 1430 835 745 675 4 cfm 2120 1925 1745 Second Stage "COOL" Speed 2 3 1 L/s 1000 910 825 cfm 1605 1475 1305 4 L/s 760 695 615 1 cfm L/s cfm L/s 1945 1785 1570 920 840 740 1125 1020 890 530 480 420 cfm 1745 1565 1410 L/s 825 740 665 cfm 1955 1785 1590 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s 1210 1100 980 570 520 465 1370 1235 1115 NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s). Lennox Harmony Iit" Zone Control Applications - Minimum blower speed is 478 cfm (225 L/s). Page 31 L/s 925 840 750 650 580 525 4 cfm 2195 1985 1795 L/s 1035 935 845 4 cfm L/s 1525 1385 1235 720 655 580 TABLE 20 G60UHV-60C-090 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Side return air with optional RAB return air base. Speed Switch Positions "ADJUST" Switch Positions + NORM -"ADJUST" Switch Positions Second Stage "HEAT" Speed 2 3 1 4 Second Stage "COOL" Speed 2 3 1 4 cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s 1505 1370 1215 710 645 575 1690 1535 1375 800 725 650 1900 1745 1535 895 825 725 2090 1915 1705 985 905 805 1625 1450 1310 765 685 620 1715 1560 1405 810 735 660 1940 1765 1595 915 835 755 2175 1945 1795 1030 915 850 1 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s cfm L/s + 1370 650 1540 725 1745 NORM -- 1240 1135 585 535 1405 1265 665 600 1565 1420 4 1 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s cfm L/s cfm L/s 825 1925 910 1130 530 1205 570 1360 740 670 1765 1560 830 735 1025 900 485 425 1100 985 520 465 1240 1115 4 cfm L/s 645 1530 720 585 525 1385 1240 655 585 N/A - First and second stage HEAT positions shown cannot be used on this model. NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 Us). Lennox Harmony Ill ' Zone Control Applications - Minimum blower speed is 478 cfm (225 Us). TABLE 21 G60UHV-60C-110 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Bottom; both sides; or bottom and one side. Speed Switch Positions "ADJUST" Switch Positions + NORM -- Second Stage "HEAT" Speed 2 3 1 cfm 1510 1365 N/A L/s 715 645 N/A "ADJUST" Switch Positions cfm L/s + NORM -- 1370 1245 N/A 650 585 N/A 1 cfm 1700 1545 1375 L/s 805 730 650 cfm 1895 1725 1545 L/s 895 815 730 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s 1560 1410 1255 735 665 595 1750 1590 1420 825 750 670 4 cfm 2105 1915 1715 Second Stage "COOL" Speed 2 3 1 L/s 995 905 810 cfm 1610 1460 1295 4 L/s 760 690 610 1 cfm L/s cfm L/s 1925 1760 1575 910 830 745 1125 1015 900 530 480 425 cfm 1730 1575 1395 L/s 815 745 660 cfm 1955 1780 1600 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s 1190 1090 975 565 515 460 1350 1230 1110 N/A - First and second stage HEAT positions shown cannot be used on this model. NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 Us). Lennox Harmony Ill" Zone Controt Applications - Minimum blower speed is 483 cfm (230 L/s). Page 32 L/s 920 840 755 640 580 525 4 cfm 2185 1995 1780 L/s 1030 940 840 4 cfm L/s 1530 1360 1235 720 640 580 TABLE 22 G60UHV-60C-110 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air O _tions: Single side return air - Bold volumes require field-fabricated transition to accommodate 20 x 25 x 1 in. 508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter. Speed Switch Positions "ADJUST" Switch Positions Second Stage "HEAT" Speed 1 2 Second Stage "COOL" 3 4 1 2 Speed 4 3 + cfm 1540 L/s 725 cfm 1750 L/s 825 cfm 1945 L/s 915 cfm 2170 L/s 1025 cfm 1635 L/s 770 cfm 1760 L/s 830 cfm 1995 L/s 940 cfm 2225 L/s 1050 NORM i 1385 1230 655 580 1635 1390 770 655 1785 1585 845 750 1960 1760 925 830 1485 1310 700 620 1610 1415 760 665 1820 1620 860 765 2035 1815 960 855 "ADJUST" Switch Positions cfm L/s + NORM i 1390 1255 1135 655 590 535 1 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s 1595 1425 1265 750 675 600 1785 1615 1435 4 845 765 675 1 cfm L/s cfm L/s 1955 1800 1610 925 850 760 1140 1030 925 540 485 435 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s 1215 1105 990 575 520 470 1370 1245 1125 4 645 585 530 cfm L/s 1555 1400 1255 735 660 595 NOTES - The effect of static pressure included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s). Lennox Harmony Ill" Zone Control Applications - Minimum blower speed is 483 cfm (230 L/s). TABLE 23 G60UHV-60C-110 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Side return air with optional RAB return air base. Speed Switch Positions "ADJUST" Switch Positions + NORM i "ADJUST" Switch Positions Second Stage "HEAT" Speed 2 3 1 cfm 1490 1340 N/A L/s 705 635 N/A 1 cfm 1680 1525 1350 L/s 790 720 635 cfm 1875 1715 1525 L/s 885 810 720 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s cfm L/s + 1375 650 1570 740 1765 NORM -- 1255 N/A 590 N/A 1425 1255 870 590 1570 1415 4 cfm 2085 1885 1700 Second Stage "COOL" Speed 2 3 1 L/s 985 890 805 cfm 1620 1470 1305 4 L/s 765 695 615 1 cfm 1735 1595 1400 L/s 820 750 660 cfm 1950 1780 1605 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s cfm L/s cfm L/s 830 1935 915 1017 480 1075 510 1375 740 665 1750 1880 825 885 1025 920 485 435 1100 990 520 470 1235 1000 N/A - First and second stage HEAT positions shown cannot be used on this model. NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s). Lennox Harmony Ill ' Zone Control Applications - Minimum blower speed is 483 cfm (230 L!s). Page 33 L/s 920 840 760 4 cfm 2185 1975 1785 L/s 1030 935 845 4 cfm L/s 650 1540 725 585 470 1385 1110 855 525 TABLE 24 G60UHV-60D-135 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Bottom; both sides; or bottom and one side. Speed Switch Positions "ADJUST" Switch Positions Second Stage "HEAT" Speed 2 3 1 4 Second Stage "COOL" Speed 2 3 1 4 cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s + 1470 695 1665 785 1855 875 2050 970 1575 745 1695 800 1900 900 2140 1010 NORM 1335 630 1520 715 1695 800 1870 885 1430 675 1540 725 1745 825 1945 920 N/A N/A 1340 630 1510 710 1675 790 1275 600 1370 645 1565 740 1735 820 i "ADJUST" Switch Positions 1 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s cfm L/s + 1345 635 1520 715 1710 NORM 1220 575 1375 650 -- N/A N/A 1230 580 4 1 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s cfm L/s cfm L/s 805 1880 890 1100 520 1180 560 1330 1545 730 1725 815 1000 475 1075 510 1380 650 1535 725 900 425 670 455 4 cfm L/s 625 1495 705 1205 570 1350 635 1095 515 1210 570 N/A - First and second stage HEAT positions shown cannot be used on this model. NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 Us). Lennox Harmony Ill ' Zone Control Applications - Minimum blower speed is 495 cfm (235 Us). TABLE 25 G60UHV-60D-135 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Single side return air - Bold volumes require field-fabricated transition to accommodate 20 x 25 x 1 in. 508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter. Speed Switch Positions "ADJUST" Switch Positions Second Stage "HEAT" Speed 2 3 1 4 Second Stage "COOL" Speed 2 3 1 4 + cfm 1405 L/s 665 cfm 1600 L/s 755 cfm 1775 L/s 840 cfm 1965 L/s 925 cfm 1500 L/s 705 cfm 1620 L/s 765 cfm 1815 L/s 860 cfm 2040 L/s 965 NORM i N/A N/A N/A N/A 1440 N/A 680 N/A 1635 1445 770 685 1800 1620 850 765 1360 1225 645 580 1470 1310 695 620 1660 1490 785 705 1860 1670 875 785 "ADJUST" Switch Positions cfm L/s + NORM i 1285 N/A N/A 605 N/A N/A 1 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s 1450 1325 N/A 685 625 N/A 1635 1485 1325 770 700 625 4 1 cfm L/s cfm L/s 1800 1660 1460 850 785 690 1075 955 870 505 450 410 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s 1150 1040 930 545 490 440 1275 1165 1065 N/A - First and second stage HEAT positions shown cannot be used on this model. NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 Us). Lennox Harmony Ill" Zone Control Applications - Minimum blower speed is 495 cfm (235 Us). Page 34 605 550 500 4 cfm L/s 1425 1300 1175 675 615 555 TABLE 26 G60UHV-60D-135 BLOWER MOTOR PERFORMANCE 0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range Factory Settings: Heating Speed - 2; Cooling Speed - 4; Speed Adjust - NORM. Return Air Options: Side return air with optional RAB return air base. Speed Switch Positions "ADJUST" Switch Positions + NORM -"ADJUST" Switch Positions Second Stage "HEAT" Speed 2 3 1 4 Second Stage "COOL" Speed 2 3 1 4 cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s 1425 N/A N/A 675 N/A N/A 1615 1455 N/A 760 690 N/A 1795 1640 1455 845 775 685 1975 1805 1630 930 850 770 1505 1370 1225 710 650 580 1620 1470 1320 765 695 625 1815 1670 1500 855 790 705 2035 1850 1670 960 875 790 First Stage "HEAT" Speed 2 3 cfm L/s cfm L/s 1 cfm L/s + 1305 615 1470 695 1655 NORM -- N/A N/A N/A N/A 1345 N/A 635 N/A 1505 1340 4 1 First Stage "COOL" Speed 2 3 cfm L/s cfm L/s cfm L/s cfm L/s 780 1825 860 1075 510 1155 545 1295 710 635 1670 1475 790 695 980 875 465 415 1050 935 495 440 1175 1070 4 cfm L/s 610 1445 680 555 505 1305 1180 615 555 N/A - First and second stage HEAT positions shown cannot be used on this model. NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm (235 L/s). Lennox Harmony Ill ' Zone Control Applications - Minimum blower speed is 495 cfm (235 L/s). G60UHV, OPERATING SEQUENCE Thermostat with NO CALL ' S¥S tEM DEMAND • . Thermostat Condition System TABLE 27 OPERATING SEQUENCE Humidity Control Feature and Single-Speed Y1 Step O I Demand III G W 1 Relative Outdoor Unit S¥S t EM RESPONSE Humidity ....... Compressor Blower CFM (COOL) Comments Compressor and indoor blower follow thermostat demand Status D Acceptable 24 VAC High lOO% FOR DEHUMIDIFICATION Normal Operation 1 On On On BASIC MODE (only active on a Y1 thermostat demand) Normal Operation 1 On Dehumidification Call 2 On PRECISION MODE (operates On On On Acceptable 24 VAC High lOO% On On Demand 0 VAC High 70% ind_ oendent of a Y1 thermostat SignatureStat T" thermostat energizes Y1 and deenergizes D on a call for de-humidification demand) Normal Operation 1 On On On Acceptable 24 VAC High 100% Dehumidification call 2 On On On Demand 0 VAC High 70% Dehumidification call ONLY 1 On On On Demand 0 VAC High 70% Jumpers at indoor unit with a single stage outdoor unit With Condensing unit - Cut W914 (R to DS) on SureLight board With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight board Dehumidification mode begins when humidity is greater than set point SignatureStat T`' thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a temperature that is cooler than the room thermostat setpoint* Thermostat used: 51M26 -- 1 heat/1 cool or 51M28 -- 2 heat/2 cool for heat pumps *In Precision mode, SignatureStat "thermostat will allow room temperature up to 2 °F (1.2°C) cooler than room temperature setting in order to meet humidity control demand. Page 35 TABLE 28 OPERATING SEQUENCE G60UHV, Thermostat with Humidity Control Feature and Two-Speed Outdoor Unit _-I SYS EM DEMAND I SEQUENCE OPERATING Thermostat System Ste Condition P Demand Relative Humidity ww 1 T S¥S EM RESPONSE Status I Compressor Blower CFM ....... Comments (COOL) D NO CALL FOR DEHUMIDIFICATION Normal Operation Y1 1 On Normal Operation Y2 2 On ROOM THERMOSTAT On On On Acceptable 24 VAC Low On On Acceptable 24 VAC High 70% 100% Compressor and indoor blower follow thermostat demand CALLS FOR FIRST STAGE COl)LING BASIC MODE (only active on a Y1 thermostat demand) Normal Operation 1 On Dehumidification Call 2 On On On On Acceptable 24 VAC Low 70% On On Demand 0 VAC High 70% PRECISION MODE (operates independent Normal Operation 1 On Dehumidification call 2 On Dehumidification call ONLY 1 On On On SignatureStat T" thermostat energizes Y2 and deenergizes D on a call for de-humidification of a Y1 thermostat demand) On On Acceptable 24 VAC Low 70% On On Demand 0 VAC High 70% Dehumidification mode begins when humidity is greater than set point 70% SignatureStat T_ thermostat will try to maintain room humidity setpoint by allowing the room space On On Demand 0 VAC High to maintain a temperature that is cooler than the room ROOM THERMOSTAT thermostat setpoint* CALLS FOR FIRST AND SECOND STAGE COOLING BASIC MODE (only active on a Y1 thermostat demand) Normal Operation 1 On On On On Acceptable Dehumidification Call 2 On On On On Demand PRECISION MODE (operates independent Normal Operation 1 On Dehumidification call 2 On 1 On Dehumidification call ONLY 24 VAC High 10o% 0 VAC High 7o% SignatureStat T" thermostat energizes Y2 and deenergizes D on a call for de-humidification of a Y1 thermostat demand) On On Acceptable 24 VAC Low 70% On On On Demand 0 VAC High 70% On On On Demand 0 VAC High 70% Jumpers at indoor unit with a two stage outdoor unit Cut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2) With Condensing unit - Cut W914 (R to DS) on SureLight board With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight board Dehumidification mode begins when humidity is greater than set point SignatureStat T_ thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a temperature that is cooler than the room thermostat setpoint* Thermostat used: 51M27 -- 2 heat/2 cool or 51M28 -- 2 heat/2 cool for heat pumps *In Precision mode, SignatureStat "thermostat will allow room temperature up to 2 °F (1.2°C) coolerthan room temperature setting in order to meet humidity control demand. Page 36 4 - This furnace is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand. FOR YOUR SAFETY READ BEFORE LIGHTING 5 - Remove the upper access panel. 6 - White Rodgers 36E Gas Valve - Switch gas valve lever to OFF. See figure 26. Honeywell VR8205 Gas Valve - Turn knob on gas valve clockwise _ to OFF. Do not force. See figure 27. AWARNING 7 - Wait five minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you do not smell gas go to next step. AWARNING WHITE RODGERS 36E SERIES GAS VALVE HIGH FIRE MANIFOLD PRESSURE ADJUSTMENT ON SIDE (under cap) ACAUTION MANIFOLD TAP ON SIDE BEFORE LIGHTING smell all around the appliance area for gas, Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. INLET PRESSURE TAP ON SIDE GAS VALVE SHOWN IN OFF POSITION FIGURE 26 The gas valve on the G60UHV(X) unit may be equipped with either a gas control knob or gas control lever. Use only your hand to push the lever or to turn the gas control knob. Never use tools, If the knob will not tum or if the lever will not HONEYWELL VR8205 SERIES GAS VALVE HIGH FIRE ADJUSTING SCREW (under cap) move by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion. Placing the furnace LOW FIRE MANIFOLD PRESSURE ADJUSTMENT ON SIDE (under cap) MANIFOLD PRESSURE TAP into operation: G60UHV(X) units are equipped with an automatic ignition system. Do not attempt to manually light burners on these furnaces, Each time the thermostat calls for heat, the burners will automatically light, The ignitor does not get hot when there is no call for heat on units with an automatic LOW FIRE (under cap) INLET PRESSI _E TAP GAS VALVE SHOWN IN OFF POSITION ignition system, FIGURE 27 AWARNING 8 - White Rodgers 36E Gas Valve - Switch gas valve lever to ON. See figure 26, Honeywell VR8205 Gas Valve - Turn knob on gas valve counterclockwise 41_ to ON. Do not force, See figure 27, Gas Valve Operation (Figures 26 and 27) 9 - Replace the upper access panel, 1 - STOP! Read the safety information at the beginning of this section. 10- Turn on all electrical power to to the unit, 2 - Set the thermostat to the lowest setting, NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line, 3 - Turn off all electrical power to the unit, 11- Set the thermostat to desired setting, Page 37 12- Iftheappliance willnotoperate, followtheinstructions "TurningOffGastoUnit"andcallyourservicetechnicianor gas supplier. NOTE - In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities. Turning Off Gas to Unit NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure. 1 - Set the thermostat to the lowest setting, 2 - Turn off all electrical power to the unit if service is to be performed, 3 - Remove the upper access panel. 4 - White Rodgers 36E Gas Valve- Switch gas valve leverto OFF. Honeywell VR8205 Gas Valve - Turn knob on gas valve clockwise _ll to OFF, Do not force, 5 - Replace the upper access panel, Primary and Secondary The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are located in the blower compartment, attached to the back side of the blower, These limits are factory set and require no adjustment. Flame Rollout Switches Gas Flow To check for proper gas flow to the combustion chamber, determine the Btu (kW) input from the unit nameplate, Divide this input rating by the Btu (kW) per cubic foot (cubic meter) of available gas, The result is the required number of cubic feet (cubic meter) per hour. Determine the flow of gas through the gas meter for two minutes and multiply by 30 to get the hourly flow of gas, Gas Pressure 1 - Check the gas line pressure with the unit firing at maximum rate, A minimum of 4,5 in, w,c, for natural gas or 11,0 in, w,c, for LP/propane gas should be maintained, 2- After the line pressure has been checked and adjusted, check the low fire and high fire manifold pressures, See figures 26 and 27 for the location of the manifold pressure adjustment screws. Low and high fire manifold pressures are given in table 29, A natural gas to LP/propane gas changeover kit is required to convert the unit, Limits (Two) These manually reset switches are located on (or inside of) the burner box, If tripped, check for adequate combustion air before resetting. Pressure Switches The pressure switch assembly (includes two switches) is located in the heating compartment adjacent to the combustion air inducer. These switches check for proper combustion air inducer operation before allowing ignition trial, The switches are factory-set and require no adjustment, Temperature Rise Place the unit into operation with a second-stage heating demand. After supply and return air temperatures have stabilized, check the temperature rise. If necessary, adjust the heating blower speed to maintain the temperature rise within the range shown on the unit nameplate, Increase the blower speed to decrease the temperature rise, Decrease the blower speed to increase the temperature rise. Failure to properly adjust the temperature rise may cause erratic limit operation, Thermostat Heat Anticipation Set the heat anticipator setting (if adjustable) according to Refer to table 29 for high altitude requirements and manthe amp draw listed on the wiring diagram that is attached to the unit, ifold pressure settings at all altitudes. TABLE 29 High Altitude Requirements / Manifold Pressure Settings Altitude Model Input Size -070 -090 0 - 4500 ft. (0 - 1372 m) Gas Required Conversion Kit Pressure Switch Nat. N/A LPG 59M13" Nat, LPG 4,501 - 7500 ft. (1373 - 2286 m) Required Conversion Kit Pressure Switch No Change N/A No Change 59M13" N/A No Change 59M13" No Change Manifold Pressure at all altitudes 7501-10,000 ft. (2286 - 3048 m) Required Conversion Kit Pressure Switch No Change 59M16 No Change 59M14" N/A 18M61 59M13" 18M61 Low Fire High Fire in. w.g. kPa 0.42 3.5 0.87 1.22 10.0 2.5 1.7 0.42 3.5 0.87 4.9 1.22 10.0 2.5 in. w.g. kPa 18M64 1.7 18M64 4.9 59M16 18M64 59M14" 18M64 -110 Nat. N/A No Change N/A 18M63 59M16 18M61 1.7 0.42 3.5 0.87 -135 LPG 59M13" No Change 59M13" 18M63 59M14" 18M61 4.9 1.22 10.0 2.5 Pressure switch is factory set. No adjustment necessary. All models use the factory installed pressure switch from 0-4500 feet (0-1370 m). *LPG/Propane conversion kit includes LP regulator. Page 38 Electrical 1 - Checkallwiringforlooseconnections. 2 - Checkforthecorrectvoltageat thefurnace(furnace operating). 3 - Checkamp-draw ontheblowermotor. MotorNameplate Actual NOTE - Do not secure the electrical conduit directly to the air ducts or structure. Electronic Ignition The two-stage, variable speed integrated control used in G60UHV units has an added feature of an internal Watchguard control, The feature serves as an automatic reset device for ignition control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure, After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the control to begin the ignition sequence, Flue And Chimney 1 - Check flue pipe, chimney and all connections for tightness and to make sure there is no blockage, 2 - Check unit for proper draft. 3 - Is pressure switch closed? Obstructed flue will cause unit to shut off at pressure switch. Check flue and outlet for blockages. 4 - Reset manual flame rollout switches on burner box, Failure To Operate If the unit fails to operate, check the following: 1 - Is the thermostat calling for heat? 2 - Are access panels securely in place? 3 - Is the main disconnect switch closed? 4 - Is there a blown fuse or tripped circuit breaker? 5 - Is the filter dirty or plugged? Dirty or plugged filters will cause the limit control to shut the unit off. 6 - Is gas turned on at the meter? 7 - Is the manual main shut-off valve open? 8 - Is the internal manual shut-off valve open? 9 - Is the unit ignition system in lock out? If the unit locks out again, call the service technician to inspect the unit for blockages. NOTE - The control board thermostat selection DIP switch is factory-set in the "TWO-STAGE" position. Applications Using a Two-Stage Thermostat A - Heating Sequence -- Control Board Thermostat Selection DIP Switch in "Two-Stage" Position (Factory Setting) 1 - On a call for heat, thermostat first-stage contacts close sending a signal to the integrated control. The integrated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is energized at low speed and the 120 VAC humidifier terminal is energized. 2 - Once the control receives a signal that the low pressure switch has closed, the combustion air inducer begins a 15-second pre-purge in low speed. 3 - After the pre-purge is complete, a 20-second initial ignitor warm-up period begins. The combustion air inducer continues to operate at low speed. 4 - After the 20-second warm-up period has ended, the gas valve is energized on low fire (first stage) and ignition occurs, At the same time, the control module sends a signal to begin an indoor blower 45-second ON-delay. When the delay ends, the indoor blower motor is energized on the low fire heating speed and the 24V humidifier terminal is energized. The furnace will continue this operation as long as the thermostat has a first-stage heating demand, 5 - If second-stage heat is required, the thermostat second-stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30-second second-stage recognition delay. 6 - At the end of the recognition delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high fire (second stage) pressure switch to make sure it is closed.The high fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heating speed. 7 - When the demand for high fire (second stage) heat is satisfied, thecombustion air inducer is switched to the low-fire heating speed and the high-fire (second stage) gas valve is de-energized. The low-fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low-fire heating speed. 8 - When the thermostat demand for low-fire (first stage) heat is satisfied, the gas valve is de-energized and the field-selected indoor blower off delay begins. The combustion air inducer begins a 5-second post-purge period. 9 - When the combustion air post-purge period is complete, the inducer and humidifier terminals are de-energized. The indoor blower is de-energized at the end of the off delay, Applications Using A Single-Stage Thermostat B - Heating Sequence -- Control Board Thermostat Selection DIP Switch in "Single-Stage" Position NOTE - In these applications, two-stage heat will be initiated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes). 1 - On a call for heat, thermostat first-stage contacts close sending a signal to the integrated control. The integrated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is energized at low speed and the 120 VAC humidifier terminal is energized, 2 - Once the control receives a signal that the low pressure switch has closed, the combustion air inducer begins a 15-second pre-purge in low speed, 3 - After the pre-purge is complete, a 20-second initial ignitor warm-up period begins. The combustion air inducer continues to operate at low speed. Page 39 4 - Afterthe20-second warm-up periodhasended,thegas valveisenergized onlowfire(firststage)andignition occurs.Atthesametime,thecontrolmodulesendsa signalto beginan indoorblower45-secondON-delay. Whenthedelayends,theindoorblowermotorisenergizedonthelowfire heatingspeedandthe24Vhumidifierterminalis energized. Theintegrated control alsoinitiatesa second-stage ondelay(factory-set at 10minutes;adjustable to 15minutes). 5 - Iftheheatingdemandcontinuesbeyondthesecondstageon delay,the integratedcontrolenergizesthe combustion airinducerathighspeed.Thecontrolalso checksthehighfire(secondstage)pressure switchto makesureit isclosed.The highfire(second stage)gas valveis energized andtheindoorblowermotoris energizedforoperation atthehighfire heatingspeed. 6 - Whenthethermostat heatingdemandissatisfied, thecombustion airinducerbeginsa 5-second lowspeed post-purge.Thefield-selected indoorbloweroffdelay begins.The indoorbloweroperatesat the low-fire heatingspeed. 7 - Whenthecombustion air post-purge periodis complete,theinducerandhumidifier terminalsarede-energized.Theindoorbloweris de-energized attheend oftheoffdelay. Flue And Chimney Check the flue pipe, chimney and all connections for tightness and to make sure there is no blockage, Electrical 1 - Check all wiring for loose connections. 2 - Check for the correct voltage at the furnace (furnace operating), 3 - Check amp-draw on the blower motor. Motor Nameplate Actual Cleaning the Heat Exchanger and Burners NOTE - Use papers or protective covering in front of the furnace during cleaning. Cleaning the heat exchanger requires a steel spring "snake," a reversible drill and a vacuum cleaner, The steel spring snake may be constructed by purchasing a 4 ft, long by 1/4 inch diameter steel wire cable and a 1/4 inch diameter wire brush, These items are available at a hardware store. Insert wire end of brush into the open end of the spring cable. Crimp the cable around the brush so that the brush is secured and will not come off during cleaning, Attach the other end of the cable to the reversible drill to com.............................................................................................................................................................................. plete the tool for cleaning the heat exchanger. 1 - Turn off both electrical and gas power supplies to furnace. 2 - Remove flue pipe and top cap from the unit. Label the pressure switch wires, then disconnect them. 3 - Remove the four screws that secure the combustion air inducer. Carefully remove the combustion air inducer to avoid damaging blower gasket. If gasket is damaged, it must be replaced to prevent leakage. See figure 1. 4 - Remove the collector box located behind the combus- AWARNING ACAUTION At the beginning of each heating season, a qualified technician should check the system as follows: Blower Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed. AWARNING Filters All G60UHV(X) filters are installed external to the unit. Filters should be inspected monthly, Clean or replace the filters when necessary to ensure that the furnace operates properly. Replacement filters must be rated for high velocity airflow, Table 1 lists recommended filter sizes, tion air inducer. Be careful with the collector box gasket. If the gasket is damaged, it must be replaced to prevent leakage. 5 - Label the wires from gas valve and rollout switches, then disconnect them. 6 - Remove the four screws securing the burner box cover and remove the cover. 7 - Disconnect gas supply piping. Remove six screws securing the burner box / manifold assembly to the vestibule panel and remove the assembly from the unit. Take care not to damage the gasket. 8 - NOx units only - Remove the three screws that attach the NOx insert to the corbel at the entrance to each heat exchanger section. Carefully remove the NOx insert from each section. See figure 29. 9 - Insert the brush end of cable snake into the top of one of the heat exchanger openings, Do not force the cable into the heat exchanger. Insert the cable and operate the drill on slow speed, Move the cable in and out of the heat exchanger section three or four times or until sufficient cleaning is accomplished. Reverse drill and slowly work the cable out of opening, Page 40 G60UHV(X) BURNER & HEAT EXCHANGER 12- Remove the cable from the heat exchanger. Use a vacuum cleaner to remove debris knocked loose during cleaning. 13- Attach the exhaust end (positive pressure) of the vacuum cleaner to the top of the heat exchanger section. Any loose debris will be forced to the bottom of the heat exchanger section. Vacuum debris from bottom openings. REMOVAL HEATEXCHANGER 14- Replace collector box and combustion air inducer. Check gaskets for damage. Damaged gaskets must be replaced to avoid heat exchanger leaks. Replace all screws to the collector box and combustion air inducer. Failure to replace all screws may cause leaks. GASKET 15- To clean the burner, run a vacuum cleaner with a soft brush attachment over the face of burners. Visually inspect inside the burners and crossovers for any blockage caused by foreign matter. Remove any blockage. 16- NOx units only - Reattach the NOx inserts to the corbels at the entrance to each heat exchanger opening. See figure 29. BOX ASSEMBLY GAS VALVE ASSEMBLY 17- Re-install gasket and burner box / manifold assembly onto the vestibule panel. Replace burner box cover and re-secure using screws. NOTE - Gasket must be replaced if it was damaged during disassembly. FIGURE 28 NOxlNSERTS (X modelsonly) 18- Reconnect wires to pressure switch, roll-out switches, gas valve and combustion air inducer. Refer to unit wiring diagram. 19- Re-install top cap and re-secure vent pipe to combustion air inducer outlet. 20- Reconnect gas supply piping. / 21- Turn on power and gas supply to unit. 22- Set thermostat and check for proper operation. 23- Check all piping connections, factory and field, for gas leaks. Use a leak detecting solution or other preferred means, CAUTION FIGURE 29 10- Repeat procedure for each heat exchanger section. 11- After each of the top heat exchanger sections has been cleaned, insert the brush end of the cable snake into the bottom openings of each of the heat exchanger sections and clean as described in step 8. 24- Ira leak is detected, repair leak. shut gas and electricity offand 25- Repeat steps 23 and 24 until no leaks are detected. 26- Replace front access panel. Page 41 Thefollowingrepairpartsareavailablethroughindependent Lennoxdealers.Whenorderingparts,includethecomplete furnacemodelnumberlistedontheCSAInternational nameplate -- Example: G60UHV(X)-36A-070-7. CabinetParts HeatingParts Upperaccesspanel FlameSensor Blowerpanel Heatexchanger assembly Topcap Gasmanifold ControlPanelParts Two-speed combustion airinducer Transformer Two-stage gasvalve Two-stage, variablespeedintegrated controlboard Mainburnercluster Doorinterlockswitch Mainburnerorifices Circuitbreaker Pressure switch BlowerParts Ignitor Blowerwheel Primarylimitcontrol Flamerolloutswitch Blowerhousing Motor Secondary limit Motorelectronics Powerchoke(1hponly) Motormountingframe Motorcapacitor Blowerhousingcutoffplate Page42 FLASH CODE (x. Y) I STATUS FLASH / ERROR DESCRIPTION CODE DESCRIPTIONS Pulse A 114 second flash followed by four seconds of off time. Heartbeat Constant 1/2 second bright and 1/2 second dim cycles. X+Y LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four seconds, then repeats. Pulse Power on - Standby. Heartbeat Normal operation - signaled when heating demand initiated at thermostat. FLAME CODES 1+2 Low flame current -- run mode. 1+3 Flame sensed out of sequence -- flame still present. PRESSURE SWITCH CODES 2+3 Low pressure switch failed open. 2+4 Low pressure switch failed closed. 2+5 High pressure switch failed open. 2+6 High pressure switch failed closed. 2+7 Low pressure switch opened during ignition trial or heating demand. LIMIT CODE 3+1 Limit switch open. WATCHGUARD CODES 4+1 Watchguard -- Exceeded maximum number of retries. 4+2 Watchguard -- Exceeded maximum number of retries or last retry was due to pressure switch opening. 4+3 Watchguard -- Exceeded maximum number of retries or last retry was due to flame failure. 4+5 Watchguard -- Limit remained open longer than three minutes. 4+6 Watchguard -- Flame sensed out of sequence; flame signal gone. 4+7 Ignitor circuit fault -- Failed ignitor or triggering circuitry. 4+8 Low line voltage. HARD LOCKOUT CODES 5+1 Hard lockout -- Rollout circuit open or previously opened. 5+2 Control failed self check, internal error (control will restart if error recovers). 5+3 No Earth ground (control will restart if error recovers). 5+4 Reversed line voltage polarity (control will restart if the error recovers). 5+6 Low secondary (24VAC) voltage. Page 43 HEATING SEQUENCE OF OPERATION NORMAL AND ABNORMAL HEATING MODE I POWER ON I CONTROL SELF-CHECK 1 I POLARITY OKAY? STATUS ERROR CODE 5 + 4, POLARITY REVERSED, I._ YES IS THERE A PROPER GROUND? I GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. (RESET CONTROL BY TURNING MAIN POWER OFF.) OKAY? .__.1 STATUS 5 + 3. GROUNDED. SIGNAL HOLDS UNTIL ERROR UNIT ISCODE PROPERLY YES _ A NORMAL OPERATION: STATUS LED -- PULSE COMBUSTION AIR INDUCER OFF. INDOOR BLOWER ON. HAS PRIMARY OR SECONDARY LIMIT RESET WITHIN 3 MINUTES? STATUS ERROR CODE 3 + 1. ,1 / I y_:.q B THERMOSTAT CALLS FOR HEAT: STATUS LED -- HEARTBEAT I YES PRIMARY AND SECONDARY 60-MINUTE LIMIT WATCHGUARD MODE. GAS VALVE OFF, COMBUSTION AIR INDUCER OFF, INDOOR BLOWER OFF WITH DELAY. LIMIT STATUS ERROR CODE 4 + 5. SWITCHESyEs _LOSED? I ROLLOUT SWITCH CLOSED? YES I YES I r I L _ FIRST (LOW) STAGE PRESSURE CONTACTS OPEN? SECOND SWITCH _ (HIGH)coNTACTS YES STAGE_ PRESSURE OPEN? TWO-STAGE [.NO GAS VALVE OFF. COMBUSTION AIR INDUCER OFR INDOOR BLOWER OFR CONTROL REMAINS UNTIL PRESSURE SWITCH IS DETECTED OPEN. STATUS ERROR CODE 2 + 4 SWITCH OR SINGLE-STAGE THERMOSTAT CALL FOR HEAT I_ I i._..._ 1 STATUS LED -- HEARTBEAT I GAS VALVE OFR COMBUSTION AIR INDUCER ON. INDOOR BLOWER ON. STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR T'STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM, CONTINUED ON NEXT PAGE GAS VALVE OFR COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFR CONTROL WILL NOT ATTEMPT SECOND-STAGE OPERATION DURING THIS HEAT DEMAND. FIRST-STAGE OPERATION WILL BE ATTEMPTED. STATUS ERROR CODE 2 + 6. I Page 44 YES HEATING SEQUENCE OF OPERATION CONTINUED I THERMOSTAT CALLS FOR HEAT STATUS LED - HEARTBEAT. (Refer to box A on previous page) NO GAS VALVE OFR COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. UNIT WILL RETRY AFTER 5-MINUTE WAIT PERIOD, STATUS ERROR CODE 2 + 3. FIRST-STAGE (LOW F,RE)PRESSURE I SWITCH CLOSED WITHIN 2.5 MINUTES? YES _ m 15-SECOND COMBUSTION AIR INDUCER PRE-PURGE INITIATED BY CLOSED FIRST-STAGE PRESSURE SWITCH (or 15 SECOND INTER-PURGE PERIOD.) STATUS LED -- HEARTBEAT. [ i IGNITOR STATUS WARM-UP LED -- HEARTBEAT. I_0 SECONDStJ YES I I _ J NO is IGNITOR INTACT AND CONNECTED? i SIGNAL HOLDS UNTIL IGNITOR IS REPLACED COMBUSTION OR AIRRECONNECTED, INDUCER OFF, IGNITOR OFF. STATUS ERROR CODE 4 + 7. YES I PERIOD, 4-SECOND TRIAL FOR IGNITION. I GAS VALVE OPENS, IGNITOR ENERGIZED DURING I AT END OF IGNITOR 20 SECOND WARM UP I 4-SECOND TR AL UNT L FLAME SENSED, ---4 IS VOLTAGE ABOVE 90 VOLTS? .o_ YES I I 4-SECOND FLAME STABILIZATION PERIOD. I NO COMBUSTION AIR INDUCER OFF, IGNITER OFF. SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95 VOLTS, STATUS ERROR CODE 4 + 8. CAN FLAME BE PROVEN WITHIN 4 SECONDS AFTER GAS VALVE OPENS? FLAME RECTIFICATION CURRENT CHECK ( > 0.20 microamps) GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER OFF. STATUS LED -- HEARTBEAT. HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND? I Lt I _r NO YES lr WATCHGUARD MODE. GAS VALVE OFF, COMBUSTION AIR INDUCER OFR INDOOR BLOWER OFF. STATUS ERROR CODE 4 + 1. IS 60-MINUTE RESET PERIOD COMPLETE? YES YES _ I HAS CONTROL FLAMEyES PRESENT?_ [ CONTINUED ON NEXT PAGE RESET IGNITION SEQUENCE FOUR (4) TIMES? WATCHGUARD MODE, STATUS ERROR CODE 4 + 3. IN--_-_° J Page 45 I NO HEATING SEQUENCE OF OPERATION CONTINUED I THERMOSTAT CALLS FOR HEAT. STATUS LED -- HEARTBEAT SEE BOX A. FLAME SIGNAL ABOVE ( > 1.40 microamps) LOW FLAME SIGNAL (Does not affect control operation) STATUS ERROR CODE 1 + 2. YES I SINGLE-STAGE THERMOSTAT MODE 'L (DiP SWITCH SET AT 'SINGLE") I I' I TWO STAGE THERMOSTAT MODE I. (DIP SWITCH SET AT "TWO") YES _ I ROLLOUT SWITCHES CLOSED? CLOSED? PRESSURE FIRST-STAGE SWITCH (LOWCLOSED? FIRE) YES _l FIRST-STAGE F GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER ON. STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS UNTIL PRIMARY ROLLOUT & SECONDARY SWITCH IS LIMIT RESET SWITCHES AND MAIN POWER IS INTERRUPTED OR THERMOSTAT IS CYCLED OFF/ON FOR 3 SECOND MINIMUM. _, q 45-SECOND STATUS INDOORLED BLOWER ON DELAY BEGINS. -- HEARTBEAT. YES _ YES I I_ j YES _ START SECOND-STAGE RECOGNITION ON DELAY (10 OR 15 MINUTES). STATUS LED -- HEARTBEAT I , I _ NO HEAT DEMAND SATISFIED? k- INDOOR BLOWER ON. I GAS VALVE STATUS OFF, COMBUSTION AIR3 INDUCER OFF, ERROR CODE + 1. YES _ l GAS VALVE OFF, COMBUSTION AIR INDUCER OFF FOLLOWING POST PURGE. INDOOR BLOWER OFF WITH DELAY STATUS LED -- PULSE q I ABNORMAL FLASH CODE. NOTE - IF SECOND-STAGE PRESSURE SWITCH SECOND WASSTAGE ORIGINALLY PRESSURE FOUND SWITCH CLOSED, CLOSED? ABNORMAL CODE WILL FLASH. NO _I YES _ SECOND-STAGE 30-SECOND DELAY ON BEGINSJ STATUS LED -- HEARTBEAT. YES _ SECOND-STAGE COMBUSTION AIR INDUCER ON. SECOND-STAGE GAS VALVE ON. HIGH HEAT INDOOR BLOWER SPEED ON. STATUS LED -- HEARTBEAT. YES SECOND-STAGE PRESSURE SWITCH CLOSED IN LESS THAN TEN (10) SECONDS? STATUS LED -- HEARTBEAT YES _ CONTINUED ON NEXT PAGE SWITCH CLOSED WITHIN 3 MINUTES? PRIMARY SECONDARY LIMITperiod (IndoorHAS blower on low OR speed during 3-minute NO1, SECOND-STAGE HEAT DEMAND REQUIRED? SECOND-STAGE HEAT DEMAND. YES _ t I GAS VALVE OFF, COMBUSTION AIR INDUCER OFF, INDOOR BLOWER OFF WITH DELAY LY..ES_ LIMITSTATUS SWITCH ERROR WATCHGUARD I CODE 4 +MODE. 5 IS 60-MINUTE RESET PERIOD COMPLETE? | GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER OFF AFTER DELAY. STATUS ERROR CODE 2 + 3. CONTROL RESTARTS IGNITION SEQUENCE IF PRESSURE SWITCH CLOSES WITHIN 2-1/2 MINUTES. YES SECOND-STAGE PRESSURE SWITCH CLOSED AT BEGINNING OF HEAT DEMAND? STATUS ERROR CODE 2 + 6. ._.o I SECOND STAGE HEAT DEMAND STATUS LED -- HEARTBEAT. No f RETURNS TO FIRST-STAGE HEAT MODE WHICH CONTINUES UNTIL SECOND-STAGE PRESSURE SWITCH CAN BE PROVEN or HEAT DEMAND IS SATISFIED. FIVE (5) MINUTE WAIT PERIOD INITIATED BEFORE RETRY. WERE 5 ATTEMPTS MADE FOR SECOND-STAGE HEAT? YES _ CONTINUES FIRST-STAGE HEATING DEMAND. WILL NOT REATTEMPT SECOND-STAGE HEATING DEMAND, STATUS ERROR CODE 2 + 5. Page 46 I HEATING SEQUENCE OF OPERATION CONTINUED SEE BOX A NORMAL OPERATION. SEE BOX B THERMOSTAT CALLS FOR HEAT. I RETURN TO FIRST-STAGE HEAT MODE. FIRST-STAGE CONTINUES UNTIL SECONDSTAGE PRESSURE SWITCH CAN BE PROVEN I SECOND-STAGE (HIGH CLOSED? FIRE) HEAT PRESSURE SWITCH or HEAT DEMAND IS SATISFIED. A FIVE (5) MINUTE WAIT PERIOD IS INITIATED BEFORE RETRY. WERE 5 ATTEMPTS MADE FOR NO YES _ I HEAT DEMAND SATISFIED? STATUS LED -- HEARTBEAT. [ SINGLE-STAGE THERMOSTAT MODE (DiP SWITCH SET AT "SINGLE") YES I L YES I I SECOND-STaGE HEAT? NO ,_ SEE BOX C FIRST-STAGE HEAT DEMAND SATISFIED? I YES 1 1 I 1 I ' I I. TWO STAGE THERMOSTAT MODE? (DIP SWITCH SET AT "TWO") 3, I J YES'f I GAS VALVE OFF, COMBUSTION AIR INDUCER OFF AFTER 5-SECOND LOW SPEED POST PURGE PERIOD, INDOOR BLOWER OFF DELAY INITIATED ON LOW HEAT SPEED, STATUS LED - HEARTBEAT. DEMAND SATISFIED SIMULTANEOUSLY. STATUS LED -- HEARTBEAT. FIRST AND SECOND STAGE HEAT I I ._ STATUS LED -- HEARTBEAT. SECOND STAGE HEAT DEMAND SASTISFIED? YES _ AND INDOOR BLOWER RETURN TO FIRSTSTAGE OPERATION. GAS VALVE, COMBUSTION AIR INDUCER STATUS LED -- HEARTBEAT. FIRST STAGE HEAT DEMAND SATISFIED? YES DEMAND FOR HEAT SATISFIED. POWER ON STAND BY. STATUS LED -- PULSE. OFF AFTER 5-SECOND LOW SPEED POSTPURGE PERIOD. INDOOR BLOWER OFF. GAS VALVE OFF. COMBUSTION AIR INDUCER DELAY INITIATED ON LOW HEAT SPEED, STATUS LED -- PULSE, 4 Page 47 I COOLING SEQUENCE OF OPERATION I POWER ON I 4, IS POLARITY SIGNAL POLARITY REVERSED. CONTROL WILL CONTINUE TO CALL FOR COOLING IN THIS CONDITION, STATUS ERROR CODE 5 + 4. REVERSED? I PROPER IS THERE GROUND? CONTROL WILL CONTINUE TO CALL FOR COOLING IN THIS CONDITION, SIGNAL IMPROPER GROUND AT LED. STATUS ERROR CODE 5 + 3. NO 9 _ YES I THERMOSTAT I CALLS FOR FIRST-STAGE COOL. I 4, COMPRESSOR AND CONDENSER ENERGIZED. FAN 4, INDOOR BLOWER ENERGIZED ON FIRST STAGE COOL SPEED AFTER 2 SECOND DELAY. 4, _1 FIRST-STAGE I THERMOSTAT DEMAND FOR COOL SATISFIED? CALLS FOR SECOND-STAGE 4, I_ COOL, COMPRESSOR AND BLOWER CONDENSER FAN DE-ENERGIZED. NDOOR DE-ENEG ZED. I I ,NDOOR BLOWER RAMPS UP TO SECOND-STAGE COOL SPEED I 4, ISECOND-STAGE DEMAND FOR COOL SAT'SF'ED? I YES 4, I Page 48 CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION MANUAL FAN SELECTION MADE AT THERMOSTAT AFTER 2 SECOND DELAY, INDOOR BLOWER IS ENERGIZED ON CONTINUOUS FAN SPEED. I= YES I THERMOSTAT CALLS FOR FIRST STAGE ii YES I COOL. I THERMOSTAT CALLS FOR FIRST-STAGE YES I I I YES II COOLING DELAY, INDOOR SPEED BLOWERAFTER RAMPSA 2-SECOND TO FIRST STAGE FIRST-STAGE HEAT. LOW HEAT SPEED, AFTERSWITCHES 45-SECONDTO DELAY, INDOOR BLOWER COOL DEMAND SATISFIED? FIRST-STAGE NO_ SECOND STAGE COOL DEMAND HEAT DEMAND SATISFIED. I _YI NO I I THERMOSTAT CALLS FOR SECOND-STAGE HEAT. I YES I I INDOOR BLOWER RAMPS TO SECOND STAGE COOL SPEED INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED AFTER 30-SECOND RECOGNITION PERIOD. I YES I SECOND STAGE COOL DEMAND SAT,SFIED? I I YES I INDOOR BLOWER COOL RAMPSSPEED. DOWN TO FIRST STAGE SECOND-STAGE HEAT DEMAND SATISFIED. I YES p q Page 49 INDOOR BLOWERHEATRAMPSsPEED.DOWN TO LOW I JobName Job No. JobLocation City State Installer City State UnitModelNo. Technician Date SerialNo. Heating Section [] Electrical Connections Tight? Line Voltage Blower Motor H.P. Blower Motor Amps Gas Piping Connections Tight & Leak-Tested? [] Fuel Type: Natural Gas? LP/Propane Gas? [] Line Pressure Furnace Btu Input (High fire) Low Fire Manifold Pressure w.c.- Nat,: High Fire Manifold Pressure w.c.- Nat,: [] Flue Connections Tight? Combustion Gas Tested (high fire and low fire)? Blower ON delay confirmed? (45 Seconds Fixed On) [] __ w.c. - LP/Propane w.c. - LP/Propane Proper Draft? [] 002 [] [] CO External Static Pressure? (0.8 maximum) Blower OFF Delay Setting (60, 90, 120 or 180)? Filter Clean & Secure? D Temperature Rise [] Thermostat Heat Anticipator Setting? Thermostat Level? [] Page 50
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 50 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 04:42:46 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools