LENNOX Evaporator Coils Manual L0806276

User Manual: LENNOX LENNOX Evaporator Coils Manual LENNOX Evaporator Coils Owner's Manual, LENNOX Evaporator Coils installation guides

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadLENNOX  Evaporator Coils Manual L0806276
Open PDF In BrowserView PDF
LENNOX

INSTALLATION
INSTRUCTIONS

(c)2001 Lennox Industries Inc.
Dallas, Texas

CR26 Series Coils
EVAPORATOR
504,361M
4/2001

COILS

F]_puTeCh

n ical
blications

Lithe U.S.A.

Supersedes 503,379M

RETAIN THESE

INSTRUCTIONS

FOR FUTURE

CR26 downflow evaporator coils are designed for use with
condensing units or heat pumps. Each coil is equipped with
a compression fitting that provides convenient field installation of a refrigerant metering device. Either a refrigerant
metering orifice (provided with some Lennox condensing
units) or a thermal expansion valve (ordered separately)
may be used in condensing unit applications. A check / expansion valve (ordered separately) is the only metering device approved for use in heat pump applications.
Refer to the Lennox Engineering Handbook for proper use
of these coils with Lennox furnaces, condensing units, heat
pumps and line sets.

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.

ACAUTION

Package 1 of 1 contains the following:
1 - CR26 evaporator coil
2 - Adaptor rails for width adjustment only
1 - Bag assembly containing
1 - Suction line 90 ° street elbow
1 - Heat shield
1 - Liquid line stub (3/8" copper swedged)
4- Screws
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
NOTE - If there is no pressure when the rubber plug is punctured, check the coil for leaks before installing the coil.

The CR26 coils are shipped with a 10 psi dry air holding
charge. Puncture the suction line rubber plug to release the
charge. Remove the rubber plug.
Loosen and remove the liquid line compression fitting. Remove and discard the plug which is in the distributor body.
This releases the liquid line charge.
NOTE - If there is no pressure when the plugs are removed, check the coil for leaks before installing it.
An adaptor may be necessary to match the furnace supply
opening with the inlet opening of the coil cabinet. Adaptor
rails are supplied to provide width adjustment. See tables
5, 6, 7, 8, and 9 for the coil/furnace match-ups with or without transitions.

AWARNING

IMPORTANT

04/01

IIIHIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

USE

504,361M
Page 1

IIIlllIIIIIIIIIIIIIIIIIIIIIIII

1- See table 1 for the dimensions of the floor opening required to accommodate the supply air opening and the
plenum. If the unit is installed against a wall, the rear
edge of the opening must be at least 1" (25 mm) from
the wall. Cut an appropriately sized opening,
Table

Gas Furnace with
Adaptor Rails and Coil

gas
furnace

1
Floor Opening

Unit

Side

to Side

Front

to Rear

CR26-18N, -30N, -36N

14-1/4" (3.6 m)

22-1/8" (5.6 m)

CR26-36W, -48N, -60N

19-1/4" (4.9 m)

22-1/8" (5.6 m)

CR26-48W

24-1/4" (6.2 m)

22-1/8" (5.6 m)

CR26-60W

24-1/4" (6.2 m)

22-1/8" (5.6 m)

2- Lower the plenum through the floor opening. Align the
flanges on the base of the unit with the matching
flanges on the plenum, then lower the unit over the plenum. The coil cabinet must be level or sloped slightly
toward the drain outlet and secured and sealed to the
plenum, If the furnace and coil cabinet are the same
size, skip to step four.

adaptor
rails

Seal
between
adaptor
and furnace.

short flange
(90 ° angle)

the
rail
the rear
of the coil
cabinet.

CR26
coil
Adjusting the Coil Cabinet Width
3- Install the provided adaptor rails or filler pieces on the
coil if necessary. Align the adaptor rails with the rear
of the coil cabinet. Figure 2 illustrates how the furnace,
coil, and adapter rails fit together,
G40/50 Furnace Applications
Use the provided rails to match the coil to the furnace.
Refer to tables 5 through 9 for correct rail widths,
Place the adaptor rail flat on the top of the coil cabinet.
See figure 1, Bend the short flange up 90° at the perforation. Use the four provided screws to secure the rails
to the coil cabinet,

Adaptor Rail
Installation

Adaptor
Rails

Figure 2
Applications other than the G40/G50 If you use the CR26 coil with furnaces other than the
G40/G50, and the furnace's width is smaller than the
coil inlet opening, install filler pieces (field-provided).
See figure 3,
If the supply opening on the furnace is larger than the
evaporator cabinet inlet opening, use an adaptor and
furnace support (field-provided). See figure 4.

Short

Flange
bend)

FURNACE

Align the adaptor
rail with the rear of

I

J
FILLER PIECES

the coil cabinet.

AIR FLOW

CR26
Secure With
Two Screws
On Each Side

PLENUM

Figure 1

Figure 3

Page 2

FILLER PIECES

Seal between
filler pieces
and furnace.

FURNACE

FURNACE
SUPPORT

,_ADAPTOR!

AIR FLOW

0

Seal between
furnace supports
J
and furnace.

CR26
PLENUM

Figure 4

ACAUTION

4- Seal between the furnace cabinet and the coil cabinet
to prevent air leaks.
5- As you lower the furnace onto the coil, align the flanges
of the furnace and the the coil cabinet,

1 - Place a field-provided heat shield, such as a wet rag,
against the piping plate and around the piping stubs,
and sweat in the suction line. The heat shield must be
in place to guard against heat damage to the paint,
2 - Slide the liquid line compression nut onto the provided
liquid line stub. Insert the field-supplied liquid line into
the liquid line stub for brazing.
3- Braze liquid line and coil connections. Use a silver
alloy brazing rod (5 or 6 percent silver alloy for copperto-copper connections or 45 percent silver alloy for
copper-to-brass or copper-to-steel connections),
4- Remove the heat shield after brazing and allow the
connections to cool.
5 - Select the appropriate refrigerant metering device:
• refrigerant flow control orifice
or
• expansion valve
See the following sections: Refrigerant Flow Control
Orifice and (Check/) Thermal Expansion Valve. Follow
these sections and table 3 to install the appropriate metering device, See figure 5,
Typical

The refrigerant line sets should be sized according to the
recommendations given in the condensing unit installation
instructions, Refer to table 2 for sweat connection sizes, A
field-provided adapter may be required to match line set
connections.
Table 2

Metering

Device

Installation
orifice

distributor
tubes

orifice
housing

valve OR orifice _
o-ring

Refrigerant Line Connections
Model No.

CR26-18

Suction (Vapor)
Line Sweat Size
inches

mm

5/8

15.9

Liquid
Sweat
inches
3/8

Line
Size

expansion
valve (opt.)

mm

strainer

9.5
o-ring

CR26-30,-36

3/4

19.0

3/8

9.5

CR26-48

7/8

19.0

3/8

9.5

CR26-60

1-1/8

28.6

3/8

9.5

liquid line
stub
suction line

Sensing

Bulb

Figure 5

Page 3

Refrigerant Flow Control

Orifice

NOTE - A properly sized refrigerant flow control orifice may
be provided with the outdoor unit. Refer to table 3 to ensure
proper sizing of the refrigerant flow control orifice. An improperly sized flow control orifice can lead to diminished
capacities and/or efficiencies, as well as potential damage
to the unit.
• 10ACB and HS29 condensing units are shipped
with a matching metering orifice,
• See table 3 for the correct metering device matchup.
a - Ensure that the orifice is installed with the nylon seat
pointing toward the distributor.
b - Apply a small amount of refrigerant oil on the O-ring
and insert the O-ring securely into the orifice housing,
c - Screw the liquid line stub to the orifice housing, Tighten the compression fitting to 20 ft-lbs,
d - The suction line service port has no core, Make sure
that the service port cap is tightened securely.
e - Insulate the refrigerant lines at the connections to prevent sweating, Continue with step 7.

A IMPORTANT

Page 4

(Check/) Thermal Expansion Valve
NOTE - Refer to table 3 to ensure selection of proper
(check/) expansion valve.
a - Remove factory-installed metering orifice from orifice
housing,
b - Apply a small amount of refrigerant oil on the O-ring
(shipped with the valve assembly) and place it securely in the orifice housing,
c - Insert the expansion valve into the orifice housing and
tighten the expansion valve compression fitting.
d - Screw the liquid line compression nut (with the liquid
line) on the threaded end of the expansion valve,
Tighten the fitting to 20 ft.-Ibs.
e - Install the expansion valve equalizer line on the suction line service port.
NOTE - Make sure that the equalizer line fitting is tightened securely.
f - Use the clamp provided with the valve assembly to secure the sensing bulb to the suction line. Continue with
step 7.

,& IMPORTANT

Table 3
CONDENSING UNIT /
HEAT PUMP

Table 3 (Continued)

METERING
THERMALEXR
VALVE(TXV)/
CHECKEXR
VALVE(CTXV) /

CONDENSING UNIT/
HEAT PUMP

DEVICE

METERING

DEVICE

THERMAL EXR
CATALOG
NO.

ORIFICE
SIZE

MODEL NO.

TONNAGE

O

42J35

.047

HP29-36

3

CTXV

56J 19

NA

1.5

O

42J39

.055

HP29-42

3.5

CTXV

56J20

NA

10ACB-24*

2

O

66J87

.062

HP29-48

4

CTXV

56J20

NA

10ACB-30*
10ACB-36*

2.5
3

O
O

42J46
42J48

.068
.073

HP29-60

5

CTXV

56J20

NA

2

CTXV

56J 19

NA

MODEL NO.

TONNAGE

10ACB-12*

1

10ACB-18*

ORIFICE

(O)

ORIFICE

10ACB-42*

3.5

O

42J52

.080

10ACB-48*

4

O

42J54

.084

10ACB-60*

5

TXV
O

26K35
42J58

NA
.092

12ACB-24
HS26-24
HS27-24
12ACB-30
HS26-30
HS27-30

TXV

2

2.5

12ACB-36
HS21-36
HS26-36
HS27-36

TXV

3

12ACB-42
HS26-42
HS27-42
HS29-42"

TXV

3.5

HS21-48
HS26-48

4

HS21-60
HS26-60

5

HS26-18

1.5

HS29-12*

1

HS29-18*

TXV

1.5

HS29-24"

2

HS29-30"

2.5

HS29-36"

3

HS29-42"

3.5

VALVE(TXV)
CHECK EXR/
VALVE(CTXV) /

26K34

12HPB-24
HP26-24
HP27-24
HS32-24"*

NA

26K34

NA

26K34

NA

26K35

NA

TXV

26K35

NA

TXV

26K35

NA

TXV

26K34

NA

TXV

26K49

NA

O

42J35

.047

TXV

26K49

NA

O

42J39

.055

TXV

26K49

NA

O

66J87

.062

TXV

26K34

NA
.067

O

42J45

TXV

26K34

NA

O

42J48

.073

O

42J51

.078

HS29-48"

4

O

42J55

.086

HS29-60"

5

O

42J61

.098

CATALOG
NO.

ORIFICE
SIZE

(O)

2

TXV

37L51

NA

HS32-30"*

2.5

TXV

37L51

NA

HS32-36"*

3

TXV

37L51

NA

HS32-42"*

3.5

TXV

39L72

NA

HS32-48"*

4

TXV

39L72

NA

HS32-60"*

5

TXV

39L72

NA

10HPB-18

1.5

CTXV

56J19

NA

10H PB-24

2

CTXV

56J 19

NA

10H PB-30

2.5

CTXV

56J 19

NA

10H PB-36

3

CTXV

56J 19

NA

10H PB-42

3.5

CTXV

56J20

NA

10HPB-48

4

CTXV

56J20

NA

10H PB-60

5

CTXV

56J20

NA

2

CTXV

56J 19

NA

2.5

CTXV

56J19

NA

3

CTXV

56J 19

NA

3.5

CTXV

56J20

NA

4

CTXV

56J20

NA

5

CTXV

56J20

NA

12HPB-24
HP26-24
HP27-24
12HPB-30
HP26-30
HP27-30
12HPB-36
HP26-36
HP27-36
12HPB-42
HP26-42
HP27-42
12HPB-48
HP26-48
HP27-48
12HPB-60
HP26-60
HP27-60
HP32-24"*

2

CTXV

49L24

NA

HP32-30"*

2.5

CTXV

49L24

NA

HP32-36"*

3

CTXV

49L24

NA

3.5

CTXV

49L25

NA

HP29-18
HP29-24

1.5
2

CTXV
CTXV

56J19
56J19

NA
NA

HP32-42"*
HP32-48"*

4

CTXV

49L25

NA

HP29-30

2.5

CTXV

56J19

NA

HP32-60"*

5

CTXV

49L25

NA

*Refrigerant

metering

**(Check)Expansion
or heat pump.

orifice

shipped

valve shipped

with condensing

with R410A

unit.

condensing

unit

Page 5

*Refrigerant metering orifice shipped with condensing unit.
**(Check)Expansion valve shipped with R4 IOA condensing unit
or heat pump.

Table 4
Air Resistance

Makedrainconnections
fromthe3/4"(19mm)pipenipple
onpanwitha 3/4"(19mm)drainpipe.Routedrainpipe
downward
toanopendrainorsump,Neverconnectdrain
toa closedsystem.

Air Volume

CR26-18N

It is veryimportant
thatproperairvolumebeprovided
over
theevaporator
coil.A draftgaugereading
mustbetakento
makesurestaticpressurefallswithintheproperrange.
1- Air testholesmustbefieldprovidedin therightfront
accesspanel.
CAUTION--Remove

_

CR26-30N

panel before drilling holes.

Drill two 5/16" (8 mm) holes in locations shown in figure
6, Replace panel.

CR26-36N

t,_____IRTEST HOLE LOCATIONS

t+

cfm

L/s

in. w.g.

500

235

.02

5

600

285

.05

12

CR26-36W

+l
t-1/2"

--_

ACCESS PANEL

1-1/2'

_T-

NO TE--Remove

panel

before drilling test holes.
CR26-48N

Figure 6
2- Connect draft gauge. Zero end of draft gauge scale
connects to air entering hole of coil. Insert gauge
hoses into test holes about 5/16" (8 mm), Seal around
holes with permagum,
3- Place the thermostat fan switch in continuous position
with no heating or cooling demand. Turn on power to
unit, and the furnace blower will begin operating,
4- Table 4 lists the range of air volumes and equivalent
draft gauge readings for this unit, Observe draft gauge
reading, If reading is above required air volume, decrease blower speed, Refer to furnace wiring diagram
for changing direct drive blower speed, Do not exceed
maximum air volume as indicated in diagram blower
speed table,
5- On belt drive blowers, check amperage draw on motor
by connecting an ammeter to one leg of the motor supply line, Compare this reading with the full load amps
listed on the motor nameplate. The motor pulley must
be adjusted not to exceed the motor nameplate full
load amps for motor listed,
6- After required draft gauge readings are obtained, remove draft lines and seal air test holes,
7- Set the room thermostat to desired temperature,

Page 6

CR26-48W

CR26-60N

CR26-60W

Pa

800

380

.12

30

1000

470

.20

50

800

380

15

37

1000

470

25

62

1200

565

38

94

1400

660

51

127

800

380

17

42

1000

470

25

62

1200

565

34

85

1400

660

45

112

1600

755

55

137

800

380

09

22

1000

470

15

37

1200

565

21

52

1400

660

28

70

1600

755

38

94

1200

565

18

45

1400

660

22

55

1600

755

,28

70

1800

850

33

82

2000

945

40

100

1200

565

14

35

1400

660

18

45

1600

755

23

57

1800

850

29

72

2000

945

35

87

1400

660

20

50

1600

755

26

65

1800

850

32

80

2000

945

39

97

2200

1040

46

115

2400

1135

55

137

1400

660

14

35

1600

755

17

42

1800

850

22

55

2000

945

27

67

2200

1040

32

80

2400

1135

37

92

2600

1225

43

107

RIGHT FRONT
_

Total Resistance

Mode! No.

Table 5
Coil Model

Furnace
Model

CR2618N-F

CR2630N-2N

*CR2636N-F

CR2636W-F

*CR2648N-F

CR2648W-F

*CR2660N-F

CR2660W-F

G40/50DF-24A-045
G40/50DF-36A-070
G40/50DF-36B-090
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiili_liilllliiiiliiiillliiillli_iiliiiliiilii!!liiiilliiiiliiillilliiiii!!_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiil_!_ii
iii:!il
¸i¸ill
¸ii!iiiiiiii!iiiiiiiiiiiiiiiiii!i!!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiill
¸i!i!iiiiiiiiiiiiill

G40/50DF-48C-090
G40/50DF-48C-110
G40/50DF-60D-135
Coil matches

furnace size and air volume.

Coil matches

air volume.

Coil does not match the furnace size and requires a field-fabricated

The coil does not match the furnace
3 - 3/16" adaptor

transition.

size.

rail supplied with the coil.

iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii;iii
i: 2 - 3/16" adaptor rail supplied with the coil.
NOTE - ff the application requires more air than a narrow (N) coil allows, use a wide (W) coil in the next column, ff wide coils
are used instead of narrow coils, a field-fabricated
transition is necessary. Use the furnace adaptor rails provided with the
wide coils.

Table 6
Coil Model
Furnace
Model

CR2618N-F

CR2630N-2N

CR2636N-F

AM30Q2/3-70

CR26-

I CR26-

36W-F

t 48N-F

CR2648W-F

CR2660N-F

CR2660W-F

*CR2660N-F

CR2660W-F

AM30Q3/4-70
AM30Q3/4-90
AM30Q3/4-105
AM30Q4/5-90
AM30Q4/5-120

I

Coil matches

air handler size and air volume.

Coil matches
transition.

air volume.

Coil does not match the air handler size and requires

a field-fabricated

The coil does not match the air handler size.

Table 7
Coil Model
Furnace
Model

CR2618N-F

CR2630N-2N

*CR2636N-F

GHR26Q3-75

CR26-

I *CR26-

36W-F

t48N-F

t CR26-

48W-F

GHR26Q3/4-100
GHR26Q4t5-100
GHR26Q4t5-120

I

Coil matches

furnace size and air volume.

Coil matches

air volume.

Coil does not match the furnace size and requires a field-fabricated

The coil does not match the furnace

transition.

size.

NOTE - ff the application requires more air than a narrow (N) coil allows, use a wide (W) ceil in the next column, ff wide coils
are used instead of narrow coils, a field-fabricated
transition is necessary. Use the furnace adaptor rails provided with the
wide coils.

Page 7

Table 8
Coil

Furnace
Model

CR2618N-F

CR2630N-2N

*CR2636N-F

CR2636W-F

Model
*CR2648N-F

CR2648W-F

*CR2660N-F

CR2660W-F

2-60
3-60
G24M
G24MX
80MGF
80MGFX

2-75
3-75
4-75
3/4-100
4/5-100
3/4-120
4t5-120
4t5-140
Coil matches

furnace size and air volume.

Coil matches

air volume.

Coil does not match the furnace size and requires a field-fabricated

The coil does not match the furnace
3 - 3/16" adaptor

transition.

size.

rail supplied with the coil.

iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiil_
2 - 3/16" adaptor rail supplied with the coil.
NOTE - ff the application requires more air than a narrow (N) coil allows, use a wide (W) coil in the next column, ff wide coils
are used instead of narrow coils, a field-fabricated
transition is necessa_
Use the furnace adaptor rails provided with the
wide coils.

Table 9
Coil Model

Furnace
Model

CR2618N-F

CR2630N-2N

CR2648W-F

CR2660N-F

OHR23-Q3-150/120
OHR23-Q5-140/154
Coil matches

furnace size and air volume.

Coil matches air volume. Coil does not match the furnace size and requires a field-fabricated
The coil does not match the furnace size.

Page 8

transition.

CR2660W-F



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 8
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Mon Jun 30 04:47:28 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu