LENNOX Controls And HVAC Accessories Manual L0806303
User Manual: LENNOX LENNOX Controls and HVAC Accessories Manual LENNOX Controls and HVAC Accessories Owner's Manual, LENNOX Controls and HVAC Accessories installation guides
Open the PDF directly: View PDF .
Page Count: 12
Download | |
Open PDF In Browser | View PDF |
KITS COMMON TO HEATING AND COOLING EQUIPMENT ,1,_ 1998 Lennox Industries Inc. Dallas, Texas 502,818M 11/98 LOW AMBIENT CONTROL KIT Supersedes 3/96 INSTALLATION INSTRUCTIONS FOR LOW AMBIENT USED WITH SINGLE-COMPRESSOR Package 1 of 1 contains: CONTROL KIT LB-57113BM HEAT PUMP UNITS (27J00) A-Pressure Switch Assembly 1- Low ambient pressure switch assembly (Sll) 1- Disconnect power to unit. 1- 36" (914 mm) length of 1/4" (6,35 mm) copper tube with flare nuts 2- Remove compressor compartment 1- Relay 1- 20-Foot length of wire access panel, 3- Install valve depressor tee discharge line gauge port. 4- Install pressure switch in compressor compartment with screws provided. Switch should be installed in a vertical position higher than mid-point of compressor. See figure 1. 4- 20" Lengths of wire 1- Bag assembly each containing: 8-Wire nuts TYPICAL INSTALLATION 2-Saddle valves Sll LOW AMBIENT PRESSURE SWITCH 4-#10-16 X 5/8" S,D,S,T. screws 1-Schrader depressor tee with seal cap COMPRESSOR The low ambient pressure switch (Sll) cycles the outdoor fan while allowing compressor operation in the cooling cycle. This intermittent fan operation results in a high evaporating temperature which allows the system to operate without icing the evaporator coil and SHOCK LOOP DISCHARGE LINE losing capacity. This kit is designed for use in ambient temperatures no lower than 30°F. S24 LOSS OF CHARGE SWITCH Lennox recommends a belly-band style crankcase heater (P-8-8852, 240v, 45w) be added to compressors which do not have one. A freezestat (LB-62858CA) should also be added to any system using a low ambient kit. NOTE - Do not use this low ambient kit on units with capillary tube metering devices. Install an expansion valve metering device if using this kit. Page 1 HIGH PRESSURE SWITCH VALVE DEPRESSOR TEE 5- FIGURE 1 Connect copper line to low ambient pressure switch and open side of depressor tee (provided). Provide a shock loop in copper tubing to prevent breakage from vibration, Tighten connections, Depressor tee port with valve core is used as service port, If necessary, valve core can be moved to other leg of tee, B-Low Ambient Pressure Switch Setting (S11) LOW AMBIENT PRESSURE SWITCH Sll One of two types of pressure switches are provided, The Ranco switch has one square and one round adjustment knob and the AIco switch has two square adjustment knobs, RANCO MODEL ROUND CUT-IN ADJUSTMENT KNOB SQUARE DIFFERENTIAL ADJUSTMENT KNOB Ranco Model The low ambient pressure switch provided in the kit is factory set for 285 psig (1965 kPa) cut-in and 140 psig DETAIL \ (965 kPa) cut-out, If necessary, follows: adjust low ambient pressure switch as 1-Rotate round knob to set cut-in pressure, Refer to right set of indicating numbers on face of control, See figure 3, 2- Rotate square knob to set differential indicator to 145 psig (999 kPa), Refer to left set of indicating numbers, Alco Model If necessary, follows: CUT-IN PRESSURE READOUT ON RIGHT DIFFERENTIAL PRESSURE READOUT ON LEFT adjust low ambient pressure switch as PRESSURE SWITCH IS FACTORY-SET AND 145 PSlG DIFFERENTIAL AT 285 PSIG CUT-IN (140 PSlG CUT-OUT) 1-Rotate the square knob located on the left to set cut-in pressure, Refer to left set of indicating numbers on face of control, See figure 2, 2- Rotate the square knob located on the right to set differential indicator to 145 psig (999 kPa), Refer to right set of indicating numbers, 3- Use only terminals 1 and 4 when connecting wiring, NOTE - Disregard "Cut out minus Diff. is Cut In" statement on face of control. This does not apply in this appfication. C-Low Ambient ALCO MODEL ROUND CUT-IN ADJUSTMENT KNOB SQUARE DIFFERENTIAL ADJUSTMENT KNOB \ Relay (K58) 1- Install low ambient relay in control box, CUT-IN PRESSURE READOUT ON LEFT DIFFERENTIAL PRESSURE READOUT ON RIGHT FIGURE 2 Page 2 Lowambientkitsareshownwithoptionalarrowsonunit wiringdiagrams, If unitwiringdiagramis notavailable or Lowambientpressureswitch$11iswiredin serieswith doesnotshowthelowambientkit,referto appropriate outdoorfanrelayor compressor contactor(single-stage wiring diagramin figures 3 through 13 for wiring connections, orspeedunits), Sll LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN DIRECTLY (LINE VOLTAGE) TO "R" LOW VO LT TERM STRIP K4 DEFROST RELAY ! REMOVE i_= _r"= THIS WIRE D i TO "0" LOW VOLT TERM STRIP $11 LOW AMBIENT PRESSURE SWITCH REMOVE THIS ,_......."d/VIRE TO K1-1 K31 PIN 5 COMP "C" K58 LOW AMBIENT I RELAY 11 31 TO C12 TERM C ? ' • I TO 24V COM L1 REVERSING VALVE TO K1-1 MOTOR ] TO C12 TERMINAL FIELD WIRING FACTORY WIRING SEE SCHEMATIC FAN FIGURE 4 FIGURE 3 Page 3 F TYPICAL SINGLE-COMPRESSOR ($11 LOW AMBIENT CONTROL HEAT PUMP UNIT WIRING DIAGRAM SWITCHES OUTDOOR FAN DIRECTLY) 24V POWER [_ HB (FOR DS (FOR G21V) TBI4 HB G21V,B,CB,CBH21) ECON DS __ __ ECON __ E G Wl Wl Tw2 W2 cc W < L _o _o o < KEY A4 BI B4 Cl C5 C7 C]2 CMC] HRI Y2 K4-3 $54 HOOKUP Z_HEATCRAFT WIRE,REMOVE WHEN OFF CONTROL (A4) IS WITH WHITE-RODGERS ELECTRONIC THERMOSTAT YI RELAY-HARD START RELAY-LOW AMB. KIT VALVE-REVERSING SENSOR-AMBIENT COMPENSATION 54 $5 LIMIT=HIGH LIMIT-HIGH $6 GEl $23 SWITCH,DEFROST SWITCH=PRESSURE,LOW THERMOSTAT-LO AMB. 524 SWITCH=LOSS $54 TBI& THERMOSTAT-SERVICE TERMINAL STRIP-LOW ) $6 $54 i PRESSURE SWITCH TEMPERATURE AMB. KIT CUT IN OF CHARGE LIGHT VOLTAGE & RT3 USED WITH GE OR HONEYWELL THERMOSTAT COMMON LE TERt DESIGNATION P T A g u 2 KSE K58,-I LJ RTS LI L2 w USED. OR START CONTACTOR-COMPRESSOR RELAY-DEFROST RELAY-EMERGENCY HEAT _55€ _FACTORY TIMED FAN KI,-I KA,-I,_,3 K26,-I C R(LI MP(N DESCRIPTION COMPONENT CONTROL-TIMED OFF COMPRESSOR MOTOR-OUTDOOR FAN CAPACITOR-OUTDOOR CAPACITOR=COMPRESSOR CAPACITOR-COMPRESSOR CAPACITOR=DUAL CONTROL-DEFROST HEATER-COMPRESSOR VOLTAGE 208=250/60/E 220-240/50/E G(SL) DENOTES LINE VOLTAGE CLASS COMPONENTS OPTIONAL II FIELD VOLTAGE INSTALLED FIELD WIRING Z_FOR USE WITH COPPER CONDUCTORS ONLY, REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM FUSE 51ZE GROUND z:_USED ONLY FHERMOSTAT Z_ "T" VOLTAGE IF COMPRESSOR 15 NOT INTERNAL UNITS ONLY E I.ENNDX, o,o._,..,oo. WIRING DIAGRAM_//_ HEAT PUMP-OUTDOOR UNITS C7 HEAT SEE PICTORIAL FIGURE 3 FIGURE 4 Page 4 PUMP SECTION-B $11 LOW AMBIENT PRESSURE CONTROL SWITCHES OUTDOOR FAN(S) THROUGH A RELAY OR CONTACTOR (PILOT CIRCUIT) HP17-953, 1353 TWO-SPEED FIELD WIRING FACTORY WIRING TO K70-1 PIN 4 24 V POWER K4 DEFROST RELAY K45 REVERSING VALVE RELAY REMOVE THIS WIRE ==_r= == I 1 $11 LOW AMBIENT PRESSURE SWITCH 2 31 I"" '_-_-] - K58 LOW I l AMBIENT RELAY __ I I 4 ---1--_'7 I TO 24V COM VELR1SING I K'° l CONDENSER FAN CONTACTOR Iw_w SEE SCHEMATIC FIGURE 6 FIGURE 5 Page 5 TO 2!V COM TYPICAL SINGLE-COMPRESSOR ($11 LOW AMBIENT CONTROL SWITCHES HEAT PUMP UNIT WIRING DIAGRAM OUTDOOR FAN THROUGH A RELAY OR CONTACTOR (PILOT CIRCUIT) ECON TBI4 [] [] )K45 )t_ I _ K8 I Z_X SPII _ _ _ DESCRIPTION KEY _MED COMPONENT OFF ................ 61 IOMPRESSOR B4 B5 _OTOR IO_OR Cl ;APABITOR GONOENSER CZ ;APAC[_OR CONDENSER FI USE HRI CONTROL CONTROL FAN FAN TRANSFORMER 1EATER FAN FAN TI COMPRESSOR KI, I,Z _DN3ACTOR KZ. K4 1.2 I,Z,3 :ONTAETOR COMPRESSOR _ELAY DEFROST ) KIO, K24 I 1 ONTACTOR CONDENSER IELAY CONTROL.SOLENOIO ] K¢5, 1,2 _ELAY REVERSING KBG, 1,2 _ELAY STA_E I,COOL K57, I 4_LA'f 51AGE 2,L:OOL STAGE STAGE I,CONTROL Z CONTROL Sp KZ_ R7 2*V COMPRESSOR FAN VALVE VALVE [] A FIELD z_ PROVIDED SOLENOID PROVIDED z STAGE LINE LINE 2 L_ON POLE -y* CONTACTOR VOLTAGE USED ONLY SEE PICTORIAL FIGURE 5 FIGURE 6 Page 6 OPTION USEO FOR _ STAGE CODLING ONLY. 24VAC,SVA MAX, NEC/CEC CLASS VALVE OPTION COOLING VOLTAGE VOLTAGE 2 IS FIELD USED FOR ONLY. FACTORY INSTALLED FIELD INSTALLED K70, K71 I IT5 _ELAY _ELA_ K79, LI [Jo !,P _ELAY /ALVE /ALVE LVAV,SPII REVERSING SDLENOIO,2 R7 R?[_ R4 1FSI£T[OR CIJRRFNT IESISTOR CURRENT 5_ITCH LIMIT. HI _ SII _ITCH 3_[TCH 524 _4g 19 _iV[_CH IV/ITCH _[514 ]LOCK SECTION IOPTIONALI STAGE £FN£1NC_ SENSING PRESSURE STAGE [OPT/ [OPT) DEFROST. LOW AMB COMPRE550R KIT LOSS OF DEFROST CHARGE TERMINATION CONTROL TERMINAL B ILO_ VOLTAGE) TYPICAL SINGLE-COMPRESSOR ($11 LOW AMBIENT PACKAGED HEAT PUMP UNIT WIRING DIAGRAM CONTROL SWITCHES OUTDOOR CHP16-2 TO 5 TON UNITS IZ =31 FAN DIRECTLY) P35 REMOVE J35 I 1 KlO -I-_Z=-t CONDENSER[ FAN RELAY -- v -- / \ II II , II / I , 1 3 THIS WIRE N1 c°_RTpS° _ K58LOW I AMBIENT RELAY --1_4, _'ICOMPRESSOR 1 I 1 ---4 LOW AMBIENT PRESSURE SWITCH COMP1 _O O > 04 o l- B4 OUTDOOR i _CA FAN MOTOR 1 pACcIlToR SEE SCHEMATIC ------ FIGURE 9 FIELD WIRING FACTORY WIRING FIGURE 7 TYPICAL SINGLE-COMPRESSOR LOW AMBIENT WIRING FOR UNITS CONTAINING 68J29 AND 68J84 DEFROST BOARDS (CMC1) CMC1 DEFROST CONTROL / 3/ _ _1----I R "= \\ .... THIS WIRE K1 COMPRESSOR CONTACTOR K58 LOW AMBIENT RELAY ,--_ REMOVE j. 22 ! __ L_ FIGURE 8 Page 7 LOW PRESAMBIENT SURE SWITCH FIELD WIRING FACTORY WIRING TYPICAL SINGLE-COMPRESSOR ($11 LOW AMBIENT PACKAGED HEAT PUMP UNIT WIRING DIAGRAM CONTROL SWITCHES OUTDOOR FAN DIRECTLY) CHP16-2 TO 5 TON UNITS P2 / -6 "x, TBE b 2AV ) NOTE-IF ANY WIRE IN THIS APPLIANCE MUST BE REPLACED WITH WIRE OF LIKE AND INSULATION THICKNESS. DISCONNECT ALL POWER BEFORE IS REPLACED, SIZE, RATING POWER [_ IT SERViCiNG -I < WARNING-ELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES sT, BLOWER [] HEAT I [] VALVE [] COOL [ [] S74 P35 , REV C_ ILD Z_NOTE-FOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM J35 TJ I_T_III OVERCURRENT PROTECTION SIZE z_CONNECTIONS FOR REMOTE MOUNTED SMOKE -8 !¢V Is[ _1 AIT, DETECTOR ()Z_OEFROST (_Z_ IST MAX LOAD O. IVA 2AVAC THERMOSTAT OPEN (16oC) CLASS 1I CLOSE (2_C) NEVER CONNECT MORE THAN ONE MOTOR IMPORTANT= PREVENT MOTOR BURNOUT, LEAD TO ANY TO ONE CONNECTION. TAPE UNUSED MOTOR LEADS :DI K_I.)_J3S-3 KA-I 24V DENOTES OPTIONAL L,I? L (RI <- " , ' _ t . I FIELD WIRING DESCRIPTION COMPONENT (S_E NOT_ _) COMPRESSOR _OTOR_BLOWER _OTOR-OUTDOOR FAN ]APACITOR-OUTDOOR FAN :APACITOR-BLOWER MOTOR :APACITOR-COMPRESSOR ;APACITOR-COMPRESSORIHARD TIMER-DEFROST_COMPRESSOR =USE-TRANSFORMER Tl JACK-TEST JACK-BLOWER MOTOR KI,-I K3,-I,2 K4,-1_2_3 KIO,-I,2 K31 KS8,-I LI P2 P35 P43 54 $6 SIi 546 574 575 T[ TBI ]ONTACTOR_COMPRESSOR 3ONTACTOR-BLOWER RELAY-DEFROST RELAY-OUTDOOR FAN RELAY-HARD START KIT R_AY-LOW AMbieNT KIT CALVE-REVERSING aLUG-ELECTRIC HEAT _LUG-TEST _LUG_BLOWER MOTOR SWITCH-LIMIT_HI PRESS(MANUAL THERMOSTAT-DEFROST SWITCH-LOW PRESS,LOW AMB KIT SWITCH-PRESSURE_ DEFROST SWITCH-FIRESTAT I SWITCH-FIRESTAT 2 [RANSFORMER=CONTRO_ TERMINAL STRIP-LOW VOLTAGE POWEBSUPPLY J _ C7 /ENNI_.__¢_ VOLTAGE FIELD START ...... z_. WIRING DIAGRAMI6/gB I __220-240/50/I __ HEAT PUMP SECTION B25 FIGURE 7 FIGURE 9 Page 8 RESET INSTALLED HEAT PUMPS-PACKAGED SEE PICTORIAL COMMON [] COMPONENTS KEY AI7 61 83 B4 CI C4 C5 C7 CMCI F1 J35 J43 LINE C4 60°F 35_F $11 LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN DIRECTLY (LINE VOLTAGE) SINGLE PHASE TO: K1-1 TERMINAL K31 TERMINAL K69 TERMINAL COMPRESSOR T1 5 L1 TERMINAL BOX TERMINAL 1 K4 DEFROST RELAY \ REMOVE THIS WIRE LOW AMBIENT PRESSURE Sll SWITCH B4 OUTDOOR FAN MOTOR TO K31 TERMINAL 4 I I ---_ N 12_,_°_g a I RE_AY )m I I I1 I I € TO 24V COM L1 REVERSING VALVE FIELD WIRING FACTORY WIRING SEE SCHEMATIC FIGURE 11 FIGURE 10 Page 9 TO C12 TERMINAL F TYPICAL SINGLE-COMPRESSOR, TWO-STAGE, SINGLE PHASE HEAT PUMP UNIT WIRING DIAGRAM ($11 Low Ambient Control Switches Outdoor Fan Directly) 4'r TBI5 24V POWER _] HB DS ECON ECON BLOWER _]AUX I L NOTEELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES. Y2 0 HEAT AUX I HEAT 2 wP Eiii]COOL/HEAT REV _DENOTES 2 VALVE COMPONENTS OPTIONAL E_]COOL/HEAT I z_sS54 HOOKUP WITH WHITE-ROOGERS OR HEATCRAFT ELECTRONIC THERMOSTAT Z_SSA GE @ < & RT3 HOOKUP WITH OR HONEYWELL THERMOSTAT z_FUELMASTER HOOKUP _S 554 (WF) DESCRIPTION KEY COMPONENT M4 CONTROL-TWO SPEED 3_COMPRESSOR _AMOTOR-OUTDOOR FAN _7 CAPACITOR-COMP,HARO START _l_ CAPACITOR-DUAL CMCICONTROL-OEFROST,COMPRESSOR HRE HEATER-COMPRESSOR 1 J44 JACK-TWO SPEED CONTROL
Source Exif Data:File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 12 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 04:48:01 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools