LENNOX Furnace/Heater, Oil Manual L0806376
User Manual: LENNOX LENNOX Furnace/Heater, Oil Manual LENNOX Furnace/Heater, Oil Owner's Manual, LENNOX Furnace/Heater, Oil installation guides
Open the PDF directly: View PDF .
Page Count: 23
Download | |
Open PDF In Browser | View PDF |
LENNOX INSTALLATION INSTRUCTIONS '_ 2002 Lennox industries inc. Dallas, Texas, USA OF23 SERIES UNITS OIL UNITS 504,627M 38152A060 01/04 Supersedes Front Flue Model _-_--_ Technical ,LLL_ Publications Lithe U.S.A. 04/02 General ..................................... Shipping & Packing List ....................... OF23 Unit Dimensions .......................... OF23 Start-Up & Performance Check List ....... OF23 Unit Parts Arrangement .................... OF23 Oil AFII Burner Parts Arrangement .......... Requirements ................................. Locate & Level Unit ............................ Unit Adjustments .............................. Venting ...................................... Flue Connect ions ............................ Supply & Return Air Plenums .................... Oil Supply Lines Sizing ...................... Connect Oil Supply Line and Filter ............. Leak Check ................................ Electrical Wiring .............................. Start-Up & Adjustment ......................... Service ..................................... Troubleshooting .............................. 1 1 2 2 3 4 4 4 5 6 11 11 11 13 13 12 15 16 17 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING These instructions are intended as a general guide and do not supersede local codes in any way. Only qualified technicians can install and service the Lennox Elite® Series OF23 oil furnaces. In Canada, refer to CSA B139 for recommended installation procedures, Consult authorities who have jurisdiction before installation. ,A, CAUTION A WARNING 1- Assembled oil furnace 1- Barometric draft control A, CAUTION 1- Side exhaust pipe collar (front flue units only) 1- Direct intake collar (AFII burner units only) Check the components for shipping damage. If you find any damage, immediately contact the last carrier. 01/04 IIIHIIIIIIIIIIIIIIIIIIIIIllllllllllll 504,627M Page 1 IIIHIIIIIIIIIIIIIIIIIIIIIIIII 3/4 (19) f 3/4 / (19) f 3-1/4 & 1-1/2 (38) I G -IP.-(83_'_-_ 3/4 (19) / _1 F TOP FLUE OUTLET / 3/4 A (19) / TOP VIEW FLUE CONNECTION OF23Q314-1051120R, OF23Q5-140/154R OF23Q5-175/210R I_ C AIR_]TF LOW i _ AIR t i FLOW i iI FLUE CONNECTION OF23Q3/4-105/140 & OF23Q5-140/154 (On Heat Exchanger) ELECTRICAL INLETS / SIDE FLUE OUTLET CENTERING HOLE (Field Fabricate Either Side) C_ ""_I I OPT. OUTDOOR COMBUSTION _O AIR INLET CENTERING HOLE (Right Side Only) c (Field Right L 6-1/2 (165) | A 1 (25) B (_) ,, I SIDE VIEW Model No. .... ,4, _ - OIL PIPING INLET/ (Both Sides) Fabricate Side only) 1 FRONT C D VIEW E x F (Supply) E x G (Return) in. mm in. mm in. mm in. mm in. mm in. mm 19-1/2 4959 37 940 52-1/2 1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406 OF23Q3/4-105/120R 19-1/2 495 37 940 52-1/2 1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406 OF23Q5-140/154 22-1/2 572 37 940 52-1/2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x406 52-1/2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x406 55 1397 29 737 22-1/2 x 23-1/8 572 x 587 22-1/2 x 16-1/2 572 x 419 OF23Q3/4-105/120 OF23Q5-140/154R 22-1/2 572 37 940 OF23Q5-175/210R 24 610 39-1/4 997 i!i!i!ialFiii iii3 ii ii ...... Job Name Job Location Installer Unit Model No. Job No. Date City State City Serial No. State Serviceman HEATING SECTION Electrical Connections Tight? PROPER DRAFT 13 Supply Voltage Draft Reading (recommended Blower Motor Amps % CO 2 (recommended Blower Motor H.P. Flue Connections Blower Motor Lubrication O.K.? Piping Connections Tight? [] Burner Model No. Oil Pump Pressure [recommended Tight? [] • Fan Control Setting (maximum [] .03-.04 inches w.c.) 12%) All Valves Open? [] Fan Control Cutout Serial Number Filter Clean & Secure? [] 130 ° F) (55°C) Temperature Rise Vent Clear? [] THERMOSTAT minimum 140 psi] Calibrated?[] Page 2 Heat Anticipator Properly Set? [] Level? [] flue opening filter clean-out port indoor blower limit switch control box with fan control board heat exchanger observation port Beckett_ _,AFII Burner (Shown) clean-out port Figure FLANGE GASKET RETAINING CLIP AIR TUBE ASSY FOR FB HEADS AIR TUBE SCREWS 1 ELECTRONICIGNITION TRANSFORMER FLANGE IGNITOR REARACCESS DOOR GASKET PRIMARY CONTROL 4X4 BOX X DOORASSY 1/4"HEX X HEAD SCREW NUT INSULATOR NOZZLE ADAPTER FUELPUMP NOZZLE LINE ELECTRODE HEAD / ASSY. ELECTRODE ASSY MOTOR VALVE Figure 2 Page 3 BLOWER WHEEL INLET AIR SCOOP Table 1 I I WARNING Combustion Air Opening Dimensions Combustion Air Opening Dimensions (2 required) Model No. O23-105/120 O23-105R/120R 10" X 20" (254 mm X 508 mm) O23-140/154 023-140R/154R 11" X 22" (279 mm X 559 mm) O23-175R/210R O23-175R/210R 20" X 40" (508 mm X 1016 mm) This unit is approved for use on combustible flooring and for clearances to combustible material as listed on unit rating plate and in table 2, Unit service and accessibility clearances take precedence over fire protection clearances, Table 2 Installation Clearances Installation of Lennox oil-fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA-B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recommendations of the National Environmental Systems Contractors Association and any state or provincial laws or local ordinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instructions in this manual. Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31. Air for combustion and ventilation must conform to standards outlined in section 140 d NFPA No. 31 or, in Canada, CSA Standard B139. When installing OF23 units in confined spaces such as utility rooms, two combustion air openings are required. Dimensions of combustion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6" (152 mm) from the room's ceiling. The combustion air opening should provide a minimum free area one-half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area containing the furnace below the level of the furnace burner. A IMPORTANT Clearances All Unit Sizes inches (mm) top of plenum and duct 2 (51) plenum sides 3 (76) sides* 6 (152) rear 24 (610) front 4 (102) flue pipe measured vertical** (measured from above) 9 (229) NOTE-Service access clearance must be maintained. *Clearance to allow inspection of furnace and flue connector shall be provided, 24" (610 mm) at rear and on one side of furnace should be allowed for cleaning and service of the blower. **Minimum clearance shown for flue pipe may be reduced by using special protection as provided by local building codes and the National Fire Protection Association Standards and CSA 189. NOTE - When service clearances are greater than fire protection clearances, service clearances take precedence. Unit must be adjusted to obtain a temperature rise within the range listed in table 3 in the Start-Up section of this manual. When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70, or Canadian Electric Code (CEC) if an external electrical source is utilized. Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63<_F(17<_C) temperature rise. Page 4 Nozzle Adjustment Thecompactdesignof thisfurnacemakesit idealfora basementor utilityroominstallation. Choosea central locationfor thefurnaceso thatsupplyair ductsapproximatelythe samelength.Thiswill alloweachroomto receivethe properamountof heat.Thefurnaceshouldbe placedsothattheflueconnection tothechimneywillbeof minimumlengthandhavea minimumnumberofelbows. 1- Setthe unitin desiredlocationkeepingin mindthe clearances listedintable2.Alsokeepinmindoilsupply connections, electricalsupply,flue connections andsufficientclearancefor installingandservicing unit. 2- Leveltheunitfromsidetosideandfromfronttorear.If the furnaceis not level,placefireproofwedgesor shimsbetweenthe lowsideof the furnaceandthe floor.Makesuretheweightofthefurnaceisdistributed evenlyonallfourcorners.Strainon sidesof cabinet causingcrackingand poppingnoisesmayoccurif weightoffurnaceis notevenlydistributed. Proper adjustment of the nozzle assembly is critical because alignment may have changed during shipping. Before the furnace and oil lines are installed, the nozzle assembly must be checked. This may easily be done by removing the entire burner assembly (not just the nozzle) from the furnace. The lower firing nozzle is factory installed. This should be verified by the installer. Inspect the spark transformer leads also to ensure they are still attached to the electrodes. Note that OF23-105/120 and OF23-140/154 series units use the Beckett AFII burner. OF23-175/210R series units use the Beckett AFG burner. The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for removing the burner assembly from the vestibule. By loosening the nuts and by turning the whole burner assembly counterclockwise (figure 3), the entire burner assembly will come out of the furnace. There is adequate wire to remove the burner without disconnecting wires. Once removed, just turn the burner around in the vest panel area. OF23 Series Burner Removal First, loosen three nuts which attach burner to vest panel. Neitherthenozzlesettingnortheairadjustments arefactory set.Thefurnaceis fire testedandthe limitcontrolis checkedtomakesureitfunctionsproperly;nofactorysettingsare made.Duringinstallation, thefurnacemustbe "setup,"The installingdealer/contractor musthaveand usepropertestequipment inordertocorrectly setuptheoil furnace,Propertestingequipmentis requiredto ensure correctoperation oftheunit.Theuseoftestequipment is nowmorecriticalthaneverduetotightertolerances neededto keepthefurnaceoperating efficiently. Amongthetestequipment for anoilfurnace,the proper combustion testkitshouldcontainthefollowing: • Draftgauge • CO2or 02Analyzer • Smoketester • Pressure gauge • Hightemperature thermometer • Oilvacuumgauge • BeckettT-500gauge • Knowledge ofpropertestequipment operation CAUTION Next, rotate burner counterclockwise on slots then pull toward rou. Figure 3 To correctly adjust the nozzle, use a Beckett #T-500 gauge. Insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the tip of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustration sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. Corrections are made by sliding the entire nozzle assembly forward or backward within the blast tube (figure 4). At the same time, nozzle alignment must be checked. To check nozzle alignment, again insert the small end of gauge into the end cone and measure the nozzle and electrode alignment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not centered, but found to be too far left or right, a new nozzle assembly will need to be ordered. Do not attempt to adjust by bending the 90 degree elbow in the oil line. Page 5 Beckett Burner Oil Burner must be removed Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized according to the requirements of the National Fire Protection Association. The smallest dimensions d the chimney should be at least equal to the diameter d the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least ,04" w,c, (9,9 Pa) is required during burner operation, Nozzle Adjustment from furnace for this procedure. 2 gauge 1 1 - Local building codes may have more stringent installation requirements and should be consulted before installation of unit, To Adjust Nozzle 1-Loosen screw. 2-Slide entire nozzle/electrode nozzle just touches gauge. 2 - The vent connector should be as short as possible to do the job, assembly back and forth until Figure 3 - The vent connector should not be smaller than the outlet diameter of the vent outlet of the furnace. 4 4 - Pipe should be at least 24 gauge galvanized, WARNING I 5 - Single wall vent pipe should not run outside or through any unconditioned space, 6 - Chimney should extend 3 feet (0.9 m) above highest point where the vent passes through the roof, and 2 feet (0,6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m), 7- The vent must not pass through a floor or ceiling, Clearances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it, WARNING 8 - The vent may pass through a wall where provisions have been made for a thimble as specified in the Standards of the National Board of Fire Underwriters, See figure 5, Wall Thimble CAUTION combustible wall WARNING vent Figure NOTE - Oil burning equipment may be vented into an approved masonry chimney or type L vent. (Type L vent is similar in construction to type B gas vent except it carries a higher temperature rating and is constructed with an inner liner of stainless steel rather than aluminum). pipe 5 9 - The vent pipe should slope upward toward the chimney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers. See figure 6. Page 6 Front Flue / Masonry barometric control* in either location 15- All vent pipe run through unconditioned areas or outside shall be constructed of factory built chimney sections. See figure 7, Chimney liner 16- Where condensation of vent gas is apparent, the vent should be repaired or replaced, Accumulation of condensation in the vent is unacceptable. \ 17- Vent connectors serving this appliance shall not be connected into any portion of mechanical draft systems operating under positive pressure, clean out 18- Keep the area around the vent terminal free of snow, ice and debris, NOTE - If vent pipe needs to exit from side of cabinet, use the pilot hole (located on either side of the unit) to cut a 6" (152 mm) round hole. Attach finishing plate (provided) with four sheet metal screws to cover rough edges. masonry chimney clean out Rear Flue / Masonry Front Flue / Factory-Built barometric control* _ (in either location) Chimney _' - -_S .......... I -- barometric control* in either location ' factory \ lean o Chimney _ drain for condensate _m,m, asonry i built chimney chimney *Barometric control may be installed in either vertical or horizontal section of flue pipe within 18" of flue outlet of furnace. Figure 6 Rear Flue / Factory-Built 10- Extend the vent pipe into the chimney so that it is flush with the inside of the vent liner. Seal the joint between the pipe and the liner. 11- The furnace shall be connected to a factory built chimney or vent complying with a recognized standard, or masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction, barometric control* (in either Jc location 12- When two or more appliances vent into a common vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the area of the additional vent or vent connection. Chimney must be able to sufficiently vent all appliances operating at the same time, 13- The vent pipe shall not be connected to a chimney vent serving a solid fuel appliance or any mechanical draft system, 14- All unused chimney openings should be closed, factory built himney drain for condensate i o i o I *Barometric control may be installed in either vertical or horizontal section of flue pipe within 18" of flue outlet of furnace. Figure Page 7 Chimney 7 Combustion and Ventilation Air (Confined and Unconfined Spaces) In the past, there was no problem in bringing in sufficient amounts of outdoor air for combustion - infiltration provided all the air that was needed and then some. In today's homes built with energy conservation in mind, tight construction practices make it necessary to bring in air from outside for combustion, Consideration must also be given to the use of exhaust fans, appliance vents, chimneys and fireplaces because they force additional air that could be used for combustion out of the house, Unless outside air is brought into the home for combustion, negative pressure (pressure outside is greater than inside pressure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. Combustion gases enter the living space creating a potentially dangerous situation, space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration, If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures outlined for using air from the outside for combustion and ventilation, Confined Space A confined space is an area with volume less than 50 cubic feet (1,4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms, In the absence of local codes concerning air for combustion and ventilation, the following section outlines guidelines and recommends procedures for operating oil furnaces in a manner that ensures efficient and safe operation. Special consideration must be given to combustion air needs as well as requirements for exhaust vents and oil piping, When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace, This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside, Combustion Air from an Adjacent The importance of the previous paragraph cannot be overstated. Users may inadvertently block fresh air intakes after installation, Air Requirements Ak CAUTION All oil-fired appliances require air to be used for the combustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will operate in an inefficient and unsafe manner. Enough air must be provided to meet the needs of all fuel-burning appliances, as well as appliances such as exhaust fans which force air out of the home. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down-draft situation. Insufficient amounts of air also cause incomplete combustion which can result in sooting. Requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or confined space. If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (6,4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all fuel-fired equipment in the confined space. Each opening must be at least 100 square inches (614,5 square centimeters), One opening shall be within 12" (305 mm) of the top of the enclosure and one opening within 12" (305 mm) of the bottom (See figure 8), Equipment An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that Page 8 Space Chimney or Oil Vent Oil Furnace Openings (To Adjacent Room) ' Space In Confined rom Inside i Unconfined Space ii ii "1 ii ii ii ii ii I" ii "I i I° ' NO TE-Each opening shall have a free area of at least I square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (614.5 square centimeters). Figure 8 Air from Outside Equipment If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12" (305 mm) of the top of the enclosure and one within 12" (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of total input rating of all equipment in the enclosure (See figures 9 and 10). When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 2,000 Btu (586 W) per total input rating of all equipment in the enclosure (See figure 11). In Confined AII Air From Outside Or Oil Vent 1 1 I I 1 I 1 I I Heater I I I I 1 I Chimney or Oil Vent '_ Figure Water Heater Ventilation Louvers Inlet (For unheate( crawt Air rrrm r 1 r NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (!! 72 W) per hour of the total input rating of all equipment in the enclosure. 1 1 I 1 I 1 I I I NOTE-Each air duct opening shall have a free area d at least one square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure, ff the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area d at least one square inch (6.4 square centimeters) per 4,000 Btu (!! 72 W) per hour of the total input rating of all other equipment in the enclosure. Equipment In Confined Space All Air From Outside (Inlet Air from Crawl Space and Outlet Air to Ventilated Attic) Oil Furnace Space 11 When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3" (76 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation. CAUTION Figure 9 Equipment In Confined Space All Air From Outside (All Air Through Ventilated Attic) Chimney or Oil Vent Ventilation Louvers • (Each End Of Attic) A Oil CAUTION Inlet Air (Ends 12" Above BoSom) Furnace Water Heater NO TE-The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure. Figure 10 Direct Connection of Outdoor Air for Combustion The Beckett AFII burner was designed to allow for direct air intake piping (4" [102 mm]). The maximum equivalent length of pipe is 70 feet (21.3 m). A 90 _ elbow equals 6 feet (1.8 m). The enclosed intake pipe ring may be used to facilitate direct air intake to the burner through the right side of the cabinet. The AFG burner requires a special kit for direct air intake. Refer to kit instructions. Page 9 ToconverttheAFItburnerfromconfinedspacetooutside combustion air,removethethreescrewswhichattachthe inletairscooptotheburnerandinsert4"(102mm)directair intakepiping. Theuseofa barometric reliefplacedin theintakepipeis recommended whenoutdoorcombustionair is directly connected totheburner.Thiswillallowconfinedspaceair tobeusedascombustion airintheeventthattheopening totheoutdoorairbecomes blocked.Usea barometric relief intheintaketoreducethechanceofsooting. 7- If improper venting is observed during any of the above tests, the common venting system must be corrected. Horizontal Venting The OF23 is approved for horizontal venting with the following mechanical vent systems: Tjernlund (sideshot) #SSlC (Cat. #35E08) or Field Controls #SWG-5 (Cat. #35P08) with the CK-61 (Cat. #18N28) control kit. Refer to the manufacturers' installation instructions for proper installation procedures and service parts information. The barometric draft control must be installed within 18 inches of the furnace flue outlet. See figure 12 for barometric draft control location. CAUTION Do not common vent with any other appliance when using sidewall vent system. Removal of Unit from Common Venting System In the event that an existing furnace is removed from a venting system commonly run with separate appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted while each appliance is in operation and the other appliances not in operation remain connected to the common venting system. If venting system has been installed improperly, the system must be corrected as outlined in the previous section. The maximum equivalent length of pipe is 70 equivalent feet. A 90 _ elbow equals 6 ft. Minimum length is 15 equivalent feet. Calculate the equivalent vent pipe footage from the furnace to the mechanical vent system (Tjernlund or Field Controls) by adding the straight vent pipe length and the equivalent elbow lengths together. Front Flue / Horizontal 1 - Seal any unused openings in the common venting system. bar°_;tlr) c 2 - Visually inspect venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition. 3 - Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. Venting "__::-- control for [ZZ horizontal venting Rear Flue / Horizontal barometric Venting control* 4 - Following the lighting instruction on the unit, place the appliance being inspected in operation. Adjust thermostat so appliance will operate continuously. 5 - Test for spillage using a draft gauge. 6 - After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other fuel burning appliance to its previous condition of use. *Barometric control must be installed in the horizontal venting system and located within 18" of flue outlet of furnace. Page 10 Figure 12 vent connector, plus 50% of the area of any additional flues or vent connectors. Install the barometric draft control (provided) and flue pipe according to instructions packed with control. IMPORTANT Inspect flue pipe annually. Clean soot or ash from flue pipe, if necessary. If pipe is rusted, replace. Radiation Install draft control at least 12 inches beyond the furnace. If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe. Follow the instructions packed with the draft control. Alternate Side Flue Connections Shield Installation combustible material (25 mm) min The vent pipe may exit the top or sides of the cabinet. A hole is provided in the top cap for top exit. For side exit, lo- unit cabinet cate the center hole punched in the side of the cabinet. See unit dimensions on page 2. Using it as the center point, cut a 6 inch (152 mm) round hole in the cabinet's side. Using it as the center point, cut a 6 inch (152 mm) round hole in the cabinet's side. Install the barometric draft control within 18 12" (305 mm) min 7" (178 mm) inches d the furnace flue outlet. Attach the provided finishing plate to cover rough edges. noncombustible spacers radiation shields (see note 1) Secure return air plenum to unit using sheet metal screws. NOTE - The following are suggested procedures that should be followed when installing the supply air plenum. 1- Use sealing strips of fiberglass. 2- In all cases, the plenum should be secured to furnace or evaporator cabinet with sheet metal screws. 3- Install supply and return air ducts as desired. B see note 3 Ensure that the restrictions of the piping system, plus any lift involved, do not exceed the capability of the oil pump. Use the following guidelines when determining whether to NOTE 1-Radiation shields must be constructed of 24 gauge sheet metal minimum. NOTE 2-Radiation shields required when A is less than 9" (229 ram), use a single-or two-stage oil pump. NOTE 3-Radiation shields should extend from the top of the unit to the top of the flue pipe. Figure One-Pipe System 13 For front flue models, the enclosed exhaust pipe ring may be used for pipe to exit the left or right side of cabinet. Center line marks are provided in cabinet. Use 24 gauge or heavier galvanized smoke pipe and fittings to connect furnace to vent. Connect flue pipe to chimney using the least number of elbows and angles possible. Flue pipe or vent connector must be inserted into but not beyond the outside wall of the chimney flue. No reduction in diameter of flue pipe is acceptable. It is best to have flue pipe as short and direct as possible. Where two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the largest flue or When using a one-pipe system with the oil tank above the burner and a vacuum of 6" (152 mm) Hg or less, a singlestage fuel pump with a supply line and no return line should be adequate. See figure 14. Manual bleeding of the fuel pump is required on initial start up. Failure to bleed air from the oil pump could result in an air lock/oil starvation condition. NOTE - As an extra precaution, cycle heating on and off ten times after bleeding air from the oil pump. This will eliminate air in the gun assembly. To determine the length of the run for piping, refer to table 2 Page 11 r_ Oil Piping I I One-Pipe System alrv LII dl I_ o o_L fill / , pipe fuel um P: P Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe, Install oil supply pipe under floor or near walls to protect it from damage, Avoid running pipes along joists or reverberating surfaces. Always use flare fittings. All fittings must be accessible. Do not use compression fittings. Aux Filter t-)_r O O II T;,k I ..... II / _nut-o_ o ° ol o_-I I1 o;;I o_ o_ _ Valve ] Maximum I One Pipe Lift ITlllT--It_ _k IMPORTANT 18ft<24m) _ ,' _'-' t ,_ ......... xql !') Uu Table Two-Pi )e Maximum x_,o ;,o;,o;,o;,o;,o;,o;,o;, Lift "H" Figure 14 Table 2 One-Pipe Oil Sizing 0) Line Length Pipe Diameter (OD Tubing) (0.0 m) 2' 0-50' (15 m) 3/8" (10 mm) (0.6 m) 51-100' (15 m) 1/2" (12 mm) 4' (1.2m) 6' Two-Pipe System (1.8m) When using a two-pipe system with the oil tank below the level of the burner, a single-stage fuel pump should be used in lift conditions of up to 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg or less. See figure 15. Use a two-stage fuel pump when lift exceeds 10 feet (3 m) and/or a vacuum of 10" (254 mm) Hg to 15" (381 mm) Hg, Both conditions require that you use of a two-pipe system, which consists of a return line that purges the fuel pump of air by returning it to the tank. To determine the run and lift for piping, refer to table 3. 8' (2.4m) 10' (3.0m) 12' (3.7m) 14' (4.3m) 16' (4.9m) 18' (5.5m) Oil Piping Two-pipe System Fill Pipe \ Air Vent _, r] "_11 I eturn /_IF_J __ _ _ I p,pe _,,__ • J_-v_7_L_._- : ,)-_ -_ _-1o2 mint J outside tank fuel pump above Figure 15 bottom of tank Pipe Length (H + R) 3450 RPM- 3 GPH (11.4 LPH) 3/8" (10 mm) OD 1/2" (12 mm) OD Tubing Tubing Single Stage Two Stage Single Stage Two Stage 84' (25.6 m) 73' (22.3 m) 63' (19.2 m) 52' (15.8 m) 42' (12.8 m) 31' (9.4 m) 21' (6.4 m) 93' (28.3 m) 85' (25.9 m) 77' (23.5 m) 69' (21.0 m) 60' (18.3 m) 52' (15.9 m) 44' (13.4 m) 36' (11.0 m) 27' (8.2 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 83' (25.3 m) 41' (12.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 100' (30.5 m) 76' (23.2 m) fuel pump 3 F Aux Filter One-Pipe Systems A _ CAUTION / The burner is shipped with fuel pump set for one-pipe operation. For one-pipe systems, the oil supply pipe is connected to the inlet tap on the pump, A one-pipe system should only be used where there is gravity oil flow to the pump and the pipe is not run at any point above the oil level in the tank. Page 12 1 - Connect theinletpipetothepumpinlet,Starttheburner. 2 - Arrangetheprimaryburnercontrolforcontinuous operationduringpurging,Seefigure14, 3 - Turnthebleedvalveoneturncounterclockwise, 4 - Bleedtheunituntilallairbubblesdisappear. NOTE - Hurried bleeding will prevent the unit from operating properly. 5 - Tighten the bleed valve securely, Table 4 Oil Filters (All Models) Oil Filters Cat. Number 10 micron filter (no mounting bracket) 81P89 10 micron filter (mounting bracket) 53P92 10 micron replacement cartridge for filter, 45 gph 53P93 Filter restriction indicator gauge 53P90 Two-Pipe Systems If the installation requires a two-pipe operation, install the bypass plug included in the bag which is attached to the pump, To convert the pump, install the bypass plug according to the provided pump instructions, Notice in the two-pipe system the return pipe must terminate in the tank 3" (76 mm) to 4" (102 mm) above the supply inlet. Ensure the return pipe terminates at the correct measurement or air may escape into the system, This could result in loss of prime, After oil piping is completed, carefully check all piping connections (factory and field) for oil leaks, Oil Line Heater (Optional) A heater for the oil pipe is available for applications that are located in cold climates, The heater warms the oil pipe to assist the initial start-up. NOTE- If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended. All wiring must conform to the National Electric Code (NEC), or Canadian Electric Code (CEC) and any local 1 - Remove 1/4" plug from return port, 2 - Insert bypass plug and tighten it, See figure 15. 3 - Attach the return and inlet pipes, Start the burner. Air bleeding is automatic, NOTE - If a faster bleed is necessarj4 open the bleed valve, codes, Refer to figure 16 for terminal designations on fan control board, 1- Refer to appliance rating plate for proper fuse size, 2- Install room thermostat and make wire connections to the fan control board, Avoid installing thermostat on an outside wall or where it can be affected by radiant heat, Set the adjustable heat anticipator on thermostat according to the wiring diagram sticker provided on unit, 4 - The return pipe must terminate 3" to 4" above the supply pipe inlet, See figure 15, NOTE - If the return pipe does not terminate where it should, air may enter the system, and prime may be lost. An oil filter is required for all models. Install filter inside the building between the tank shut-off valve and the burner. Locate filter close to burner for easy maintenance, Table 4 lists the filters for the OF23 furnace, Consult the burner manufacturer's instructions that are in- cluded with the unit for further details concerning oil supply pipe connections. 3- Install a separate fused disconnect switch near unit so power can be shut off for servicing. 4- Complete line voltage wiring from disconnect switch near unit to make-up box. NOTE - An equipment ground screw is provided. Refer to unit wiring diagram and figure 16 for 0F23 series units. Ground unit using a suitable ground wire. 5- Any accessory rated up to 1 amp can be connected to the accessory terminal. The accessory terminal is energized when the blower is in operation. Page 13 Fan Control Board © thermostat terminal _[] strip DEL^¥_F SELECT ° o Figure 16 Typical I OF23 Wiring Diagram f POtL_ _Y JLENCTION 120 VOLT BOX -_ FACTORY WIRING LINE VOLTAGE-FIELD LOW VOLTAGE-FIELD TI TRANSFORMER YLW | r...._! F, 5AMP YLW [ -'" I RED B3 CIRCULATING S_A4RT :H FAN I.T AUX LIMIT MAIN LIMIT (IF USED) SlO NG_s I. I G (p _) (_ I L LI'L _E NOTES, _s I Y c _ _. _? J 0 _" IONITOR_ I I_T I I _ _._ I I.'F: J j IF HONIZONTAL APPLICATION IS USED, PURPLE IS WIRE COLON DESIGNATION. 5. THERMOSTAT HEAT ANTICIPATO_ 4. CONE_CT REOUIflED MOTOR LEAD TO HEAT TERMINAL ON TERMINAL BOARD. S. WHEN THE SAME MOTOR SPEED IS TO BE USED FOR HEAT AND COOL,DISCONNECT AND ISOLATE THE UNUSED MOTOR SPEED LEAD. CONNECT THE REC_JIRED MOTOR SPEED LEAD TO THE NEAT TERMINAL AND ADD A JUMPER WIRE BETWEEN THE HEAT AND COOL TERMINALS. SETTING--O. 0 LZ 0 u 2 ______R_ o F{'_-_....._ PUMP VALVE ._, HEAT ONLY(TWO WIRE) z_v.z FOR THERMOSTAT.CONNECT R & W. I BO SEC SWITCH SETTINGS 90 REC 120 GEC I50 GEC c_NGING J u -L_____ ONIT L_N_OX® IF ANY WIRE IN THIS APPLIANCE IS REPLACED, IT MUST B_ REPLACED WITH LIKE SIZE,HATING IKSULATION THICKNESS AND TERMINATIOn4 2. 0 CELL, CAD *HT DELAY OFF DIP s2'rY_ TH_MOSTATI( R BLUE INTERRUPT _TO_ NOTE 2 o w,_,, OTI _H 0R26 _; '_/ _-s_ NOTE Z 0 TZ 0 l l-t-- // RED-GEE CONTROL Wfl,tITE ORANGE Ii°i°i]-l Ij CAPACITOR R7184S A3 PRIMARY 02302-70 02503-1051120 02305- 140/154 0F2303- 105/120 OIL lAMP HEATING UNITS-OIL 0F2305-140115_ 0HR2305- I(R/120 OF2303-105/I2OR 0HR2305-1401154 0F2305-140/154R 01=2305-175/210 HEAT-SECT tON ,q;;::;;. N=I Form No. 534,563W _O_S Figure 17 Page 14 I.•*_*= I_•trl*• la,_. Lithe U.S*A. Typical OF23 Wiring Diagram 24V POWER I L ILIMIT T _p ECON P94 SS A ON 140,154 _TO CHANGE MOTOR SPEED TAP AND FOR BLOWER SPEED GELECIION PROCEDURE,REFER TO INSTALLATION A INSTRUCTION, SWITCH OPENS A $21 CSA UNTTS WHEN FLAME USED ON OHR23 SERIES (G) HEAT (WI) IS SIGHTED _ F22 ONLY ORANGE KE25-1 A WHILE K56 DELAY DELAY NOTEIF ANY WIRE IN THIS APPLIANCE IS REPLACED, IT MUST BE REPLACED WITH WIRE OF LIKE SIZE, RATING,INSULATION ¸THICKNESS AND TERMINATION THERMOSTAT HEAl ¸¸ ANTICIPATION 023/OF23/OHR23 UNITS.. 0,1 AMP ON OFF I I WHITE :s i:iJ LzAv SLOWER SPEED CHART FACTORY CONNECTED SPEED TAPS UNIIS COMMON (C/ MOTOR SPEEDS AVAILABLE 2 ALL IB [ SPEED TAPS EOUIPMENT GROUND BLOWER SPEED SELEC]ION HI LO IBK YLW BLUE RED I I._IIRUA® IMPORTANT-TO PREVENT MOTOR BURNOUT,NEVER CONNECT MORE THAN ONE MOTOR LEAD TO ANY ONE CONNECTION. L_ IF HEATING AND LOW I ONLY _WHEN AN ACCESSORY IS BEING USED IN A CONTINUOUS PAN APPLICATION WITHOUT S6B (CONTINUOUS FAN SWITCH].THE ACCESSORY MUST BE WIRED BETWEEN LI AND N ON BCC BOARD. SET FOR BLOWER H[R HEARING 02302=70 02303 105/E 20 02505 140/E 54 0F2505105/120 0F2505-140/154 SPEED OIL UNIIS 0F2305 105/120R DF2505] _-0/I!:i4R OF 2505 = 175/210 OHR25Q5 105/120 O_ R2505 = 140/154 ARE TG BE GAME,CGNNECT JUMPER BETWEEN $68-1 AND AI5 H(AS SHOWN).REMOVE UNUSED MOTOR SPEED WIRE. N_w Form I .... No, 554,564W LINE VOLTAGE FIELD INSTALLED CLASS II VOLTAGE FIELD WIRING 41969005 (_)zoo_ Le_ Figure 18 Page 15 _d_ fr_s la_ L fho U.S. A Beforestartingunit,makesuretheoiltankis adequately filledwithcleanNo,1 or No, 2 furnace oil, NOTE - Water, rust or other contaminants in oil supply system will cause malfunction and failure of the internal parts of the fuel unit. readings, subtract the readings. The difference in temperatures in the supply and return air plenums should approximate the temperatures listed in table 5 and the appliance rating plate. If not, adjust the blower motor pulley to adjust the blower speed. Table 5 OF23 Unit nozzle size, spray, angle, & pattern input rating BTU/HR output rating BTU/HR head temp rise F ° -105 .65GPH-.80 ° B 105,000 85,000 FB3 60 -105R .65GPH-.80 ° B 105,000 85,000 FB3 65 -120 *.75GPH-.80 ° B 119,000 97,000 FB3 70 -120R *.75GPH-.80 ° B 119,000 97,000 FB3 70 -140 .85GPH-.80 ° B 140,000 113,000 FB6 60 -140R .85GPH-.80 ° B 140,000 113,000 FB6 65 -154 *I.00GPH-.80 °B 154,000 125,000 FB6 60 -154R *I.00GPH-.80 °B 154,000 125,000 FB6 70 -175 1.10GPH- .80 ° B 175,000 142,000 FB6 70 -210R 1.25GPH- .80 ° B 210,000 166,000 FB6 70 CAUTION Ai, CAUTION 1- Set thermostat for heating demand and turn on electrical supply to unit, 2- Check initial air adjustment, All units are equipped with an air adjustment dial on the right side of the burner. See burner parts arrangement illustration. 3- Turn unit on. Place a can or container under the bleed port located on the fuel pump. Loosen nut on bleed port to release air and oil mixture from fuel line, Allow mixture to escape until a steady stream of oil is emitted from the port, Drain at least 1/2 pint of oil from the pump, Retighten nut on bleed port. NOTE - A two-line fuel system will normally bleed itself by forcing air back to the tank through the return line. This type of bleeding procedure is not necessary. 4- If burner fails to start, push reset button on primary safety control and the burner motor reset button once. See part arrangement illustration, *Nozzle must be field provided for field conversion to higher heating input. Oil burner pump pressure is !40 psi for each unit. C - Limit Control Limit Control -- Do not adjust from factory setting. D - Fan Control The fan on time of 30 seconds is not adjustable, Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by moving the delay switches on the fan control board, Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 19, Set the heat fan off delay switches to either 60, 90, 120, or 150 seconds. The factory setting is 90 seconds. CAUTION Delay Off Switch 5- If burner fails to light again, refer to the troubleshooting section in this manual, 60 sec 90 sec A - Fuel Pump Pressure Adjustment Measure fuel pump pressure with unit off. Attach pressure gauge to pump outlet, Turn unit on and check pressure and compare to table 3, Adjust if necessary, B - Temperature Rise Adjustment To measure temperature rise, place plenum thermometers in warm air and return air plenums, Locate thermometer in warm air plenum where thermometer will not "see" the heat exchanger to prevent it from picking up radiant heat. Set thermostat to its highest setting to start unit, After plenum thermometers have reached their highest and steadiest Figure Settings 120 sec 150 sec 19 E - Burner Adjustment The following instructions are essential to the proper operation of OF23 series oil furnaces, To prevent sooting, these instructions must be followed in sequence: 1 - Draft This test should be taken at the breach between the outlet of the vent connector and the barometric draft control. Generally a 1/4" hole will need to be drilled for the draft gauge to be inserted into the vent connector. Page 16 A minimumof 0,03draftmustbeestablished withoutthe burnerinoperation, Withtheburnerinoperation, thedraft shouldbe 0.04to 0.05.Thisis VERYcriticalto theflame retentionheadburners. Oilfurnaceinstallations alsorequirecarefulinspection to makesurethechimneyis ingoodshapeandcanaccommodatethe productsof combustion. Thetemperature in theunconditioned spacewillalsoaffectthedraftif longvent connectors areallowedtogettoocold, 2 - OverfireDraft Thistestshouldbetakenwiththeburnerinoperation. Removethescrewfromthecenteroftheinspection door.Insertyourdraftgaugeintothehole, A readingoftheoverfiredraftshouldbe0,02lessthanthe readingfoundintheventconnector. Ifa positivereadingis seenatthispoint,thecombustion fanis pumping toomuch air intothe heatexchanger, Makethe necessaryadjustmentsattheairadjustment dial, 3 - SmokeTest Thesmoketestshouldbetakenattheholedrilledinstep1, Usinga smoketestgunadjusttheairinletshuttersothat youwillhavejusta traceofsmoke.Somewhere between 0 and#1smoke,Thisisthestarting point, Do not stop here. 4 - CO2 Test Again, take the sample at the vent pipe, With the unit firing at a trace of smoke, take a sample of the CO2, From the results of this test, a "window of operation" will be determined, This window of operation establishes some tolerance. The tolerance the installer builds in provides room within the set-up for those things which might affect combustion, Those things which might affect combustion can then do so without causing the unit to start sooting/ smoking. Things which might affect combustion include a nozzle going bad, draft that changes during different climatic conditions, dirty oil, dirt obstructing the air inlet, etc, To build in a "window of operation," set up the burner to be 2% less in CO2. For example, if you find a reading of 12% CO2, adjust the air inlet shutter to increase the air and drop the CO2 to 10%. the room air temperature from the stack temperature. This will give you the net stack temperature. Use the efficiency charts provided in most C02 analyzers to determine furnace efficiency. A - Servicing Filter NOTE - Under no circumstances should the access panels to the blower compartment be left off or left partially open. 1- Throw-Away Type Filters -- Filters should be checked monthly and replaced when necessary to assure proper furnace operation, Replace filters with like kind and size filters, 2- Reusable Type Filters -- Filters should be checked monthly and cleaned when necessary to assure proper furnace operation. Use warm water and a mild detergent. Replace filter when dry. Permanent filters supplied with OF23 furnaces do not require oiling after cleaning. Examine filter label for any for special instructions that may apply, B - Blower Blower motor is pre-lubricated and sealed for extended operation. No further lubrication is required. Disconnect power to unit before cleaning blower wheel for debris, C - Flue Pipe Inspection The flue pipe should be inspected annually by a qualified service technician, Remove and clean any soot or ash found in the flue pipe, Inspect pipe for holes or rusted areas, If replacement is necessary, replace with the same size and type as required by code, Inspect the flue draft control device and replace if found defective, D - Cleaning Heat Exchanger 1- Remove the vent pipe from the furnace, 2- Remove the locking screws and the caps from the clean out tubes, Remove flue access elbow. 3- Using a long spiral wire brush, sweep down the outer drum of the heat exchanger. Then using the hose attachment, vacuum out loose debris, 4- Remove the locking screw and cap from the observation tube and with the spiral wire brush, reach upward toward the rear of the heat exchanger to clean out the crossover tube, 5 - Retest the Smoke With a drop in the CO2 and increase in the air you should see that the smoke has returned to 0, CAUTION 6 - Retest the Overfire Draft This test serves to confirm that you have not increased the air too much, Again you do not want a positive pressure at the test port. It should still be 0.02 less than the draft pressure reading taken at the breach. You may need to increase the stack draft by adjusting the barometric draft control, 5- Replace the clean out caps and flue access elbow, Make sure locking screws are secure, 6- Brush out and vacuum the vent outlet area of the outer drum and replace vent pipe. 7- Clean around burner, blower deck and vestibule area. 7 - Stack Temperature Take a stack temperature reading in the vent pipe, Subtract Page 17 NOTE - A heat exchanger clean-out kit ABRSH380 (35K09) is available from Lennox. Burnerfailureor improper operation canresultfroma numberofdifferentcauses, Oftenthecausecanbepinpointed byobserving thedifferenttypesoffailureor bytheprocessofelimination. Thefol- lowingtroubleshooting chartslist somefailures,causes anda sequenceof stepsto isolatethe pointof failure. Checkthesimplestandmostobviousitemsbeforeprogressingtootheritems. Action Thermostat calls for heat. (W terminal is energized.) System Response ST9103A closes oil primary control T-T connections. Ignition system and oil primary control start the furnace. Oil flows as long as oil primary control senses flame. Burner motor is energized and heat fan on delay timing begins. When timing is complete. the circulating fan is energized at heat speed and warm air is delivered to the controlled space. Thermostat ends call for heat. (W terminal is de-energized.) Oil primary control is de-energized, terminating the burner cycle. Heat fan off delay timing begins. When timing is complete, the circulating fan is de-energized, ST9103A returns to standby mode (oil primary control and circulating fan are off). Burner fails to light. Oil primary control locks out within lockout timing (timing depends on oil primary control). Burner motor is de-energized, If heat fan has started, it continues Established flame fails. Burner motor is de-energized through the selected delay off period. and oil primary control goes into recycle mode. If selected heat fan off delay is longer than the recycle delay timing, the heat fan continues to run through the next trial for ignition. Thermostat begins call for cool. (G and Y terminals are energized.) Circulating fan is energized at the cool speed. Thermostat ends call for cool. (G and Y terminals are de-energized.) Circulating fan and cooling compressor Thermostat Circulating fan is energized immediately begins call for fan. Cooling compressor turns on immediately. (G terminal is energized.) ST9103A may be factory-configured Thermostat ends call for fan. (G terminal is de-energized.) Circulating fan is de-energized. Limit switch string opens. Oil primary control shut off the burner. turn off immediately. at cool speed. to operate heat speed in this mode. Circulating fan is energized immediately at heat speed. ST9103A opens oil primary control T-T connections. Circulating fan runs as long as limit string stays open. If there is a call for cooling or fan, the circulating fan switches from heat speed to cool speed. Limit switch string closes. ST9103A begins heat fan off delay sequence. Circulating fan turns off after the selected heat fan off delay timing. ST9103A closes oil primary control T-T connections. Oil primary control is energized, initiating burner light off. Continuous circulating fan is connected. Circulating fan is energized at low speed when there is no call for heat, cool or fan. (Optional connectors are available for separate circulating fan speed tap.) If fan operation is required by a call for heat, cool, or fan, the ST9103A switches off the continuous fan speed tap before energizing the other fan speed. Electronic air cleaner is connected. (Optional connectors are available for 120 Vac electronic air cleaner.) Electronic air cleaner (EAC) connections are energized when the heat or cool speed of the circulating fan is energized. EAC connections are not energized when the optional continuous fan terminal is energized. Humidity control is connected. (Optional connectors are available for 120 Vac humidifier.) Humidifier connections Page 18 are energized when the burner motor is energized. Source Thermostat Procedure Check thermostat settings. Causes Correction Thermostat in OFF or COOL Switch to HEAT. Thermostat is set too low Turn thermostat perature. Burner motor overload Safety Overloads Power Thermostat Check burner motor, primary safety control, & auxiliary limit switch. Check furnace disconnect switch & main disconnect. Touch jumper wire across thermostat terminals on primary control. If burner starts, then fault is in the thermostat circuit. tripped Reset primary control. Auxiliary safety Reset auxiliary limit. limit switch tripped on Open switch Close switch. Blown fuse or tripped circuit breaker Replace fuse or reset circuit breaker. Broken or loose thermostat wires Repair or replace wires. Loose thermostat nection Tighten connection. Dirty thermostat screw concontacts not level Clean contacts. Level thermostat. Faulty thermostat CAD Cell Push reset button pump motor. Primary control tripped on safety Thermostat Disconnect the flame detector wires at the primary control. If the burner starts, fault is in the detector circuit. to higher tem- Replace thermostat. Flame detector shorted leads are Flame detector exposed to light short circuit in the flame detector Separate leads. Seal off false source of light. Replace detector. Check adjustment. maximum setting. Primary Control Place trouble light between the black and white leads. No light indicates that no power is going to the control. Primary or auxiliary switch is open control Set the Jumper terminals; if burner starts, switch is faulty, replace control. Open circuit between disconnect switch and limit control Trace wiring and repair or replace it. Low line voltage or power failure Call the power company. Place trouble light between the orange and white leads. No light indicates faulty control. Defective Replace the control. Place the trouble light between the black and white leads to the burner motor. No light indicates that no power is getting to the motor. Blown fuse Replace the fuse. Binding burner blower wheel Sized fuel pump Turn off power and rotate the blower wheel by hand. If seized, free the wheel or replace the fuel pump. Defective Replace the motor. internal control circuit Burner Place trouble light between the black and white leads to the blower motor. Light indicates power to the motor and burner fault. Page 19 burner motor Source Oil Supply Procedure No oil in tank Fill tank. Coat dip stick with litmus paste and insert into bottom of tank. Water in oil tank If water depth exceeds pump or drain water. Listen for pump whine. Tank shut-off valve closed Open valve. Oil line filter is plugged Replace filter cartridges. Kinks or restriction Repair or replace oil line. in oil line Plugged fuel pump strainer Oil Filters & Oil Line Open bleed valve or gauge port. Start the burner. No oil or milky oil indicates loss or prime. Install pressure gauge on pump and read pressure. Should not be less than 140 psi. Disconnect ignition leads. Observe the oil spray (gun assembly must be removed from unit). Inspect the nozzle for plugged orifice or carbon build-up around orifice. Clean strainer or replace pump. Locate and correct leak. Tighten all connections. Pump is partially or completely frozen. No pressure and the motor locks out on overload. Replace pump. Coupling disengaged - no pressure Re-engage or broken too low or replace coupling. Adjust to 100 psi. Nozzle orifice plugged Nozzle strainer Replace nozzle with the same size, spray angle, and spray type. plugged Poor or off center spray Fouled or shorted electrodes Clean electrode Dirty electrodes Improper electrode Remove gun assembly and inspect electrodes and leads. Improper tips tips gap spacing position of electrode Burner Motor Connect ignition leads to the transformer. Start burner and observe spark. Check line voltage to transformer primary. Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for binding or excessive drag. Clean electrode tips and reset the gap to 5/32 inches and correctly position tips. Bad buss bar connection Retension Cracked or chipped insulators Replace electrode. Cracked tors or burned lead insula- Burned out transformer and realign. Replace electrode leads. Check voltage at power source. Correct cause of voltage drop or call the power company. Low line voltage Ignition Transformer leads. and leads Eroded electrode Ignition Electrodes 1 inch, Air leak in oil supply line Fuel pressure Nozzle Correction Check tank gauge or use dip stick. Listen for pump whine. Oil Pump Causes wind- ings. Replace the transformer. No spark or weak spark Properly ground the transformer case. Low line voltage Check voltage at power source. Correct cause of voltage drop or the call power company. Pump or blower overloading motor Correct cause of overloading. Faulty motor Replace motor. Page 20 Source Procedure Causes Unbalanced If burner continues to run, this may be due to poor fire. Inspect fire. Poor Fire Flame Detector After burner fires, immediately jumper across flame detector terminals at the primary control. If burner locks out on safety, fault is in the primary control. Primary Control Source If fire is good, fault is in the flame detector. Check detector circuit. Flame Detector Oil Supply After burner fires, immediately jumper across flame detector terminals at the primary control, If fire is good, fault is in the flame detector. Check detector circuit. If burner loses flame (does not lock out on safety), fault is in the fuel system. Listen for pump whine Replace nozzle Reduce combustion combustion. Too little air - - long dirty fire Increase combustion combustion. Excessive draft Adjust barometric correct draft. Too little draft or restriction Correct draft or remove tion. Dirty cad cell face Clean cad cell face. Faulty cad cell - exceeds hms Loose or defective wires 15000 cad cell Primary control circuit defective Causes Unbalanced Poor Fire fire Too much air - -lean short fire Procedure If burner continues to run (does not lock out of safety), fault may be due to poor fire. Inspect fire. Correction air - check air - check damper for restric- Replace cad cell. Secure connections or replace cad cell holder and wire leads. Replace primary control. Correction fire Replace nozzle Too much air - - lean short fire Reduce combustion combustion. Too little air - - long dirty fire Increase combustion combustion. Excessive draft Adjust barometric correct d raft. Too little draft or restriction Correct draft or remove tion. Dirty CAD cell face Clean CAD cell face. Faulty CAD cell - - exceeds 15000 h p Replace CAD cell. Loose or defective wires Secure connections or replace cad cell holder and wire leads. cad cell air - check air - check damper for restric- Pump loses prime - air slug Prime pump at bleed port Pump loses prime - air leak in supply line Check supply line for loose connections and tighten fittings. Water slug in line Check oil tank for water (over 1 inch) pump or drain out water. Partially plugged nozzle or nozzle strainer Replace nozzle. Restriction Clear restriction. in oil line Plugged fuel pump strainer Clean strainer or replace pump. Cold oil - outdoor tank Change to number Page 21 1 oil. Source Procedure Causes Heat anticipator Thermostat Limit Control Check thermostat. Connect voltmeter between line voltage connections to primary control (black & white leads). If burner cycles due to power interruption, it is cycling on limit. Vibration Source If voltage fluctuates, fault is in the power source. Recheck voltage at the power source. Thermostat Disconnect thermostat wires at the primary control. Primary control If burner does not turn off, fault is in the primary control. Correct heat anticipator Shield thermostat relocate. Dirty furnace Clean or replace filter. air filters setting. Correct source of vibration. Thermostat in the path of a warm air draft from draft or Burner running too slow Increase blower speed to maintain proper temp. rise. Blower motor seized or burned out Replace motor. Blower bearings Replace bearings seized and shaft. Blower wheel dirty Clean blower wheel. Blower wheel in backward Reverse blower wheel. Wrong motor rotation Replace with properly wheel. Restrictions air system Correct cause of restriction. in return or supply limit control set too Reset limit to maximum setting. rotating stop Loose wiring connection Locate and secure connection. Low or fluctuating Call power company. Procedure If burner turns off, fault is in the thermostat circuit. set too low at thermostat Adjustable low Power Correction line voltage Causes Correction Shorted or welded thermostat contacts Repair or replace the thermostat. Stuck thermostat Clear obstruction thermostat. Thermostat bimetal not level Shorted thermostat or replace Level thermostat. wires Repair short or replace wires. Thermostat out of calibration Replace thermostat. Thermostat in cold draft Correct draft or relocate the thermostat. Defective Page 22 primary control Replace the defective control. primary Source Procedure Causes Too much combustion Low CO 2 less than 10%. Correction air Reduce combustion air. Air leaks into heat exchanger around inspection door, etc. Correct cause of air leak. Excessive Adjust barometric draft control for correct draft. Incorrect ment draft burner head adjust- Correct burner head setting. Clean heat exchanger. Dirty or plugged heat exchanger Combustion Check burner combustion for CO2, stack temperature, and smoke High smoke reading more than a trace. High stack temperature is more than 550"F Net. Readjust burner. Insufficient draft Increase d raft. Incorrect burner head adjustment Correct burner setting. Too little combustion air Increase combustion Too little blower air Increase maintain blower speed to proper temp. rise. Blower belt too loose (if equipped) Tighten blower belt. Dirty or plugged heat exchanger Clean heat exchanger. Dirty blower wheel Clean blower wheel. Dirty furnace Clean or replace filter. Restricted dampers Oil Pressure Inspect fire and check oil pressure. air filters or closed registers or Readjust ers. registers or damp- Partially plugged or defective nozzle Replace nozzle. Oil pressure is too low: less than 100 psi. Increase 100psi. oil pressure Page 23 air. top
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 23 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 04:51:55 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools