LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0806498
User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 24
Download | |
Open PDF In Browser | View PDF |
LENNOX ,1,_2003 Lennox industries inc. Dallas, Texas INSTALLATION INSTRUCTIONS HPXB15 SERIES UNITS HEAT PUMP UNITS 504,735M 12/03 Supersedes 07/03 HPXB15 outdoor units use R410A which is an ozone friendly HFC refrigerant. This unit must be installed with a matching indoor coil and line set as outlined in the Lennox Engineering Handbook. HPXB15 outdoor units are designed for use in expansion valve (TXV) systems only. They are not designed to be used with other refrigerant flow control devices. The Lennox Engineering Handbook lists indoor TXV kits that must be ordered separately. A, IMPORTANT _ Technical _z-_j_LL[ i i i Publications Lithe U.S.A. HPXB15 Outdoor Unit ........................... Shipping & Packing List ......................... General Information ............................. Dimensions .................................... Parts Arrangement ............................. Setting the Unit ................................. Electrical ...................................... Refrigerant Piping .............................. Refrigerant Metering Device ..................... Flushing Existing Line Set & Indoor Coil ........... Manifold Gauge Set ............................. Service Valves ................................. Leak Testing ................................... Evacuation ................................... Start-Up ...................................... Charging .................................... System Operation ............................. Defrost System ............................... Maintenance .................................. Optional Accessories ........................... Homeowner Information ........................ HPXB15 Check Points ......................... 1 1 1 2 3 3 4 6 6 7 8 8 9 10 11 11 15 16 18 19 19 20 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 1 - Assembled HPXB15 outdoor unit ,A WARNING 2 - Grommets (for liquid and vapor lines) Check equipment for shipping damage. If you find any damage, immediately contact the last carrier. These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation. ,&,WARNING 12/03 IIIIIIIIIIIIIIIIIIIIIIII1,1111111111111 Page 1 504,735M IIil!111111,111,111,1 inlet _ air inlet 0 air compressor coil drain outlets (around perimeter of base) air Top View electrical inlets C discharge t y air vapor line inlet 4-1/2 (114) liquid line inlet 2 -3/4 (70) 2 (51) 1-3/8 (35) Side View Model No. A B C D JR. 27-7/8 25-7/8 29-7/8 12-1/4 mm 708 657 759 30-7/8 32-1/8 34-1/16 HPXB15-024 HPXB15-030 in. HPXB15-036 mm in. E F G H J K 22-7/16 14-7/16 22-1/8 16-3/4 2-7/8 5-1/2 311 570 367 562 425 730 140 12-3/4 26-5/8 18-5/8 28-1/8 17-1/4 3-7/8 7-1/2 784 816 865 324 676 473 718 438 98 191 34-7/8 32-1/8 34-1/16 13-3/4 26-5/8 18-5/8 28-1/8 18-1/4 3-7/8 7-1/2 886 816 865 349 676 473 718 464 98 191 44-7/8 32-1/8 34-1/16 14-1/4 26-5/8 18-5/8 28-1/8 18-3/4 3-7/8 7-1/2 1140 816 865 362 676 473 718 476 98 191 HPXB15-042 mm HPXB15-048 in. HPXB15-060 mm Page 2 system operation defrost control/timed-off control contactor monitor \ ground lug high pressure sensing bulb switch vaporline service valve and gauge port filter/drier liquid line service valve and gauge port expansion valve with internal defrost thermostat crankcase heater thermostat distributor reversing valve and solenoid compressor terminal plug crankcase heater muffler Figure 1 3 - In heavy snow areas, do not locate unit where drifting will occur. The unit base should be elevated above the depth of average snows. ACAUTION NOTE - Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a support frame is constructed, it must not block drain holes in unit base. XkCAUTION Installation These units operate under a wide range of weather conditions; therefore, several factors must be considered when positioning the outdoor unit. The unit must be positioned to give adequate clearances for sufficient airflow and servicing. A minimum clearance of 24 inches (610 mm) between multiple units must be maintained. Refer to figure 2 for installation clearances. 1 - Place a sound-absorbing material, such as Isomode, under the unit if it will be installed in a location or position that will transmit sound or vibration to the living area or adjacent buildings. NOTE - A service access clearance of 30" (762 mm) must be maintained in front of the service access panel. Clearance to one side must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm). Clearances as noted _* I as noted J 30" (762ram) NOTE - A clearance of 24" (610 mm) must be maintained between two unit& NOTE - 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm). 2 - Mount unit high enough above ground or roof to allow adequate drainage of defrost water and prevent ice build-up. Page 3 Figure 2 4 - When installed in areas where low ambient temperatures exist, locate unit so winter prevailing winds do not blow directly into outdoor coil. 5 - Locateunitawayfromoverhanging rooflineswhich wouldallowwateror icetodropon,orinfrontof,coilor intounit, Rooftop Application Wind Barrier Construction prevailing winter winds 0 Slab Mounting wind barrier When installing unit at grade level, top of slab should be high enough above the grade so that water from higher ground will not collect around unit, See figure 3. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m), This will prevent ice build-up under unit during a defrost cycle. Refer to roof mounting section for barrier construction if unit must face prevailing winter winds. 2 degrees or 2 in. per 5 foot (51 mm per 1.5 m) slope tolerance away from building structure I INLET 0 AIR I I I air i building structure %r IL 24" (610 ram) Slab Mounting discharge ] inlet air 0 inlet air CL- Figure 4 CLIn the U,S,A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC), -T mounting C[- slab Refer to the furnace or blower coil installation instructions ground level Figure for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 3 Roof Mounting WARNING Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit, Consult local codes for rooftop applications, If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. See figure 3, Size barrier at least the same height and width as outdoor unit, Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds. Page 4 1 -Install line voltage power supply to unit from a properly sized disconnect switch, 2 -Ground unit at unit disconnect switch or to an earth ground. side the unit control box cover. NOTE - To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box us 3 - Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be affected ing a proper conduit fitting. NO TE - Units are approved for use only with copper conductors. 24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 5 for field wiring diagram. by sunlight, drafts or vibrations. 4 - Install voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figures 6 and 7. NOTE - A complete unit widn_l dia_lram is located in Typical B4 OUTDOOR FAN (LEADED) Field Wiring SYSTEM OPERATION MONITOR ORANGE-RUN =COMMON Diagram GROUND E _--- WI Ik, AN Y,OUT DEFROST CONTROL PURPLE= CAPACITOR HI -PS LUG,S_ KI COMPRESSOR DONTACTOR z_ L2 L0-PS CI2 DUAL L1 208-230/60/1 main power _ RO D! wo O0 CAPACITOR OUT _0 YI z_NOTEFOR USE WITH COPPER CONDUCTORS ONLY.REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE /_ Figure 5 Page 5 WARNINGELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH.UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES. Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, nonflare) series line sets as shown in table 1 or use field-fabricated refrigerant lines, Valve sizes are listed in table 1. Outdoor Unit and Blower Unit Thermostat Designations (Some connections may not apply. Refer to specific thermostat Thermostat and indoor unit.) Indoor Unit Outdoor Unit Refrigerant Connections HPXB15 Matched with New Indoor Coil and Line Set ® @ If an existing indoor coil which was equipped with an RFCI metering device is being replaced, the liquid line must also be replaced prior to the installation of the HPXB15 unit. power power common common _(__ 1st. stage aux. heat _F 1st. s_e aux. hea_l Table 1 @ Refrigerant Line Sets Valve Field Size Recommended indoor blower @+ reversing @+ compressor Line Set Connections -(b Model valve J L15 Line Sets Liquid Line Vapor Line Liquid Line Vapor Line -024 -030 -036 3/8 in, 10mm 3/4 in, 19mm 3/8 in, 10mm 3/4 in, 19mm L15-41 15 ft. - 50 ft. 4.6 m- 15 m -042 -048 3/8 in. 10mm 7/8 in. 22mm 3/8 in. 10mm 7/8 in. 22mm L15-65 15 ft. - 50 ft. 4.6m15m -060 3/8 in, 10 mm 1-1/8 in, 29 mm 3/8 in. 10 mm 1-1/8 in, 29 mm Field Fabricated Figure 6 Outdoor Unit and Blower Unit Thermostat Designations (with auxiliary heat) (Some connections NOTE - Units are designed for line sets of up to 50 feet (15 m). Select line set diameters from table 1 to ensure that oil returns to the compressor. Installing Refrigerant Line may not apply. Refer to specific thermostat and indoor unit.) Thermostat ® Outdoor Unit Indoor Unit power 1_ common __. ©1 I Q emergency During the installation of any heat pump or a/c system, it is important to properly isolate the refrigerant lines to prevent unnecessary vibration, Line set contact with the structure (wall, ceiling or floor) causes some objectionable noise when vibration is translated into sound, As a result, more energy or vibration can be expected, Closer attention to line set isolation must be observed, ®1 power heat I - he _"cOmmat em'_ _ I I / eutdger t'stat 1st. stage aux. TTeaq-_-st._stTg _. f k ® ® indoor btower @ compressor ®1 _at Following are some points to consider when placing and installing a high-efficiency outdoor unit: @1 ®1 1-Placement - Be aware some localities are adopting sound ordinances based on how noisy the unit is from ®[ ®1 reversinq.vatve Figure the adjacent property not at the original installation. Install the unit as far as possible from the property line, When possible, do not install the unit directly outside a window, Glass has a very high level of sound transmission. 7 If the HPXB15 unit is being installed with a new indoor coil and line set, the refrigerant connections should be made as outlined in this section. If an existing line set and/or indoor coil is going to be used to complete the HPXB15 system, refer to the following section which includes flushing procedures. 2- Line Set Isolation - The following illustrations demonstrate procedures which ensure proper refrigerant line set isolation. Figure 8 shows how to install line sets on vertical runs. Figure 9 shows how to install line sets on horizontal runs, Figure 10 shows how to make a transition from horizontal to vertical, Finally, figure 11 shows how to place the outdoor unit and line set, Page 6 Refrigerant Line Sets How To Install Vertical Runs (new construction shown) NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside waft. Outside Wall \ i r IMPORTANT- Refrigerant lines must not contact wall. Vapor Line Liquid Line Wood Block Between Studs Wire Tie \ Inside Wall -- Strap _ -Vapor LiLn_uid Lin-'_ _- Sleeve Wire Tie (wrapped with --_------- Outside Wall "_ _-------- Wood Block Wire Tie Strap g__Caulk PVC Pipe _" _ Fiberglass Insulation IMPORTANT- Refrigerant lines must not contact structure, j Figure 8 Page 7 Sleeve Refrigerant Line Sets: Installing Horizontal Runs To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties. Wire Tie (around vapor line only) 8 feet I I Floor Joist or Roof Rafter / Tape or Wire Tie / 8 feet Strapping Material (around vapor line only) Metal Sleeve \ Tape or Wire Tie , r Floor Joist or Roof Rafterf_ j/ Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line. Figure 9 Page 8 Refrigerant Line Sets: Transition From Vertical To Horizontal Automotive Muffler-Type Hanger AnchoredHeavy NylonWireTie Wall Stud Wall Stud Strap Liquid Line To Vapor Line Strap Liquid Line To Vapor Line Liquid Line Sleeve Vapor Line Wrapped in Armaflex Metal Sleeve Liquid Line Figure Vapor Line Wrapped in Armaflex 10 Outside Unit Placement and Installation J Install unit away from windows. Two 90 ° elbows installed in line set will reduce line set vibration. Figure 11 Page 9 IsolationGrommets Locatetheprovided isolationgrommets. Usea knifetoslit thewebbingoneachgrommet. Slidelargergrommetonto vaporlineand smallergrommetontoliquidline.Insert grommetsinto mullionto isolaterefrigerantlines from sheetmetaledges. Metering Device Installation distributor o-ring expanston // &WARNING valve o-ring liquid li_ stub Figure 12 Brazing Connection Procedure 1 - The end of the refrigerant line must be cut square and its internal shape must remain round. The line must be free of nicks or dents and must be deburred (I.D. and O.D.) & IMPORTANT 2 - Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the system. 3 - Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper-to-copper brazing or 45 percent &WARNING silver alloy for copper4o-brass or copper4o-steel brazing). Wrap a wet cloth around the valve body and the copper tube stub. Remove light maroon washers from service valves and shield light maroon stickers in order to protect them during brazing. Braze the line set to the service valve. 4 - Quench the joint with water or a wet cloth to prevent heat damage to the valve core and opening port. IMPORTANT - The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity. HPXB15 units are used in check expansion valve systems only. Check expansion valves equipped with Chatleff fittings are available from Lennox. Refer to the Engineering Handbook for applicable expansion valves for use with specific match-ups. If you install a check expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before installing the check expansion valve. See figure 12 for installation of the check expansion valve. Page 10 &IMPORTANT j that the entire system is completely void of refrigerant. Disconnect the liquid and vapor lines from the existing outdoor unit, ACAUTION ff the existing outdoor unit is equipped with manual shut-off valves AND you plan to use NEW R22 refrigerant to flush the system -- Start the existing R22 system in the cooling mode and close the liquid line valve, Pump all of the existing R22 refrigerant back into the outdoor unit, (It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation,) When the low side system pres- IMPORTANT sures reach 0 psig, close the vapor line valve. Disconnect all power to the existing outdoor unit, Refer to gauges after shutdown to confirm that the valves Required You will need the following equipment in order to flush the existing line set and indoor coil: two clean R22 recovery bottles, an oilless recovery machine with a pump down feature, and two sets of gauges (one for use with R22 and one for use with the R410A). Flushing are not allowing refrigerant to flow back into the low side of the system, Disconnect the liquid and vapor lines from the existing outdoor unit, Equipment _ connections. DO NOT install the field-provided R410A check/expansion valve at this time. Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit or open the outdoor unit service valves at this time. Procedure 1 - Remove existing R22 refrigerant using the appropriate procedure below. If the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational AND you plan to use the existing R22 refrigerant to flush the system -- Disconnect all power to the existing outdoor unit. Connect the existing unit, a clean recovery cylinder and the recovery machine according to the instructions provided with the recovery machine, Remove all R22 refrigerant from the existing system. Refer to gauges after shutdown to confirm Page 11 Remove the existing outdoor unit, Set the new R410A unit and follow the brazing connection procedure which begins on the previous page to make line set _ Remove the existing refrigerant flow control orifice or thermal expansion/check valve before continuing with flushing procedures. The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing, Use a field-provided fitting to reconnect the lines. Flushing Connections Inverted R22 Cylinder (Contains clean R22 to be used for flushing) LOW PRESSURE HIGH PRESSURE HPXB15 Unit EXISTING Existinc VAPOR LINE Op{_C:[ENI E:AU EXISTING GE MAN::_: _:_ LIQUID LINE Indoor Coil NOTE - The inverted R22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system. TANK INLET RETURN DISCHARGE RECOVERY CYLINDER Recovery Machine Figure A, IMPORTANT 13 7- After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the R22 vapor is recovered, NOTE- A single system flush should remove all of the mineral oil from the existing refrigerant lines and in- 4- Remove the pressure tap valve cores from the H PXB 15 unit's service valves, Connect an R22 cylinder with clean refrigerant to the vapor service valve. Connect the R22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set, 5 - Set the recovery machine for liquid recovery and start the recovery machine, Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor coil, 6 - Invert the cylinder of clean R22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve, Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine, door coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system is flushed, you must allow the recovery machine to pull a vacuum procedure. on the system at the end of the 8- Close the valve on the inverted R22 drum and the gauge set valves, Pump the remaining refrigerant out of the recovery machine and turn the machine off, 9 - Use nitrogen to break the vacuum on the refrigerant lines and indoor coil before removing the recovery machine, gauges and R22 refrigerant drum, Reinstall pressure tap valve cores into HPXB15 service valves, 10 -Install the provided check/expansion valve (approved for use with R410A refrigerant) in the liquid line at the indoor coil, Page 12 NO TE - Use a 3/16" h ex head extension for liquid line sizes or a 5/16" extension for vapor line sizes. 3 - Replace stem cap and tighten it firmly. Tighten finger tight, then tighten an additional 1/6 turn. To Close Service Valve: A IMPORTANT 1 - Remove stem cap with an adjustable wrench, 2 - Using service wrench and hex head extension, turn stem clockwise to seat valve, Tighten it firmly, NOTE - Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes. 3 - Replace stem cap. Tighten finger tight, then tighten an additional 1/6 turn. Vapor Access the liquid line and vapor line service valves (figures 14 and 15) and gauge ports are used for leak testing, evacuating, charging and checking charge, See table 2 for torque requirements, Each valve is equipped with a service port which has a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the Liquid Service Table 2 Part Type) Valve Vapor line service valves function the same way as the other valves, the difference is in the construction, These valves are not rebuildable. If a valve has failed, you must replace it. A ball valve valve is illustrated in figure 15, The ball valve is equipped with a service port with a factoryinstalled Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leakfree seal, primary leak seal, Torque Line (Ball Valve (Valve Insert Hex Wrench Open) Stem Cap Requirements Recommended Torque Service valve cap 8 ft.- lb. 11 NM Sheet metal screws 16 in.- lb. 2 NM Machine screws #10 28 in.-lb. 3 NM Compressor bolts 90 in.- lb. 10 NM Gauge port seal cap 8 ft.- lb. 11 NM Field Side Schrader Valve Unit Side Service Port Cap Service IMPORTANT Liquid Port Service Valve (Valve Field Side _..----._ Closed) Stem Cap Insert Hex Wrench Here To Access Schrader Port: Service Port 1 - Remove service port cap with an adjustable wrench, 2 - Connect gauge to the service port. 3 - When testing is complete, replace service port cap, Tighten finger tight, then an additional 1/6 turn, To Open Service Valve: 1 - Remove stem cap with an adjustable wrench. 2 - Using service wrench and hex head extension, back the stem out counterclockwise as far as it will go, (Valve Front Seated) Service Port Cap Unit Side Schrader Valve Open To Line Set When Valve Is Page 13 Closed (Front Seated) Figure 14 3 - Open the high pressure side of the manifold to allow the R410A into the line set and indoor unit. Weigh in a trace amount of R410A. [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the valve on the R410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the R410A cylinder. Vapor Line (Ball Type) Service Valve (Valve Open) Use Adjustable Wrench To open: rotate stem counter-clockwise 90 ° . To close: rotate stem clockwise 90 °. cap port service _ unit side 4 - Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge set. S charlavde r_ 5 - Connect the manifold gauge set high pressure hose to the vapor valve service port. (Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.) service port ste m 6 - Adjust the nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit. field side ball (shown open) Figure stem cap 15 After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be checked for leaks. 7 - After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and R410A mixture. Correct any leaks and recheck. ,IMPORTANT WARNING Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts. AWARNING A IMPORTANT WARNING 1 - Connect the manifold gauge set to the service valve ports as follows: • low pressure gauge to vapor line service valve • high pressure gauge to liquid line service valve Using an Electronic Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of R410A. Leak Detector 1 - Connect a cylinder of R410A to the center port of the manifold gauge set. 2 - With both manifold valves closed, open the valve on the R410A cylinder (vapor only). 2 - Connect micron gauge, 3 - Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. 4 - Open both manifold valves and start vacuum pump, Page 14 5 - Evacuate the linesetandindoorunitto anabsolute pressureof23,000microns(29.01inchesof mercury).Duringtheearlystagesof evacuation, it is desirabletoclosethemanifold gaugevalveatleastonceto determine ifthereisa rapidriseinabsolute pressure. IMPORTANT A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure. NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure. 6 - When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves. 1 - Rotate fan to check for frozen bearings or binding. 2 - Inspect all factory- and field-installed connections. wiring for loose 3 - After evacuation is complete, open the liquid line and vapor line service valves (counterclockwise) to release refrigerant charge (contained in outdoor unit) into the system. 4 - Replace stem caps and secure finger tight, then tighten an additional (1/6) one-sixth of a turn. 5- Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit nameplate. If not, do not start the equipment until the power company has been consulted and the voltage condition has been corrected. 6 - Set the thermostat for a cooling demand, turn on power to indoor blower unit and close the outdoor unit disconnect to start the unit. XkWARNING 7 - Recheck voltage while the unit is running. Power must be within range shown on the nameplate. 7 - Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit. 8 - Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves. 9 - When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of R410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the R410A cylinder and remove the manifold gauge set, This system is charged with R410A refrigerant which operates at much higher pressures than R22. The check/expansion valve provided with the unit is approved for use with R410A. Do not replace it with a valve designed for use with R22. This unit is NOT approved for use with coils which include metering orifices or capillary tubes. Processing Procedure The unit is factory-charged with the amount of R410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment. Table 3 Liquid Line Set Diameter 3/8 in. (10 ram) Oz. per 5 ft. (grams per 1.5 m) adjust from 15 ft. (4.6 m) line set* 3 ounces per 5 feet (85g per 1.5 m) *If line length is ,reater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount. Page 15 klMPORTANT The compressor is charged with sufficient polyol ester oil for line set lengths up to 50 ft. The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is determined by the unit's refrigerant metering device and the outdoor ambient temperature. O,ock,n00u,0oor Coi, | | | | r *Outdoor coil should be blocked one side at a time with cardboard or plastic sheet until proper testing pressures are reached. cardboard or plastic sheet Measure the liquid line temperature and the outdoor ambient temperature as outlined below: 1- Connect manifold gauge set to service valves as shown in figure 17: • low pressure gauge to vapor valve service port • high pressure gauge to liquid valve service port Connect the center manifold hose to an upright cylinder of R410A, Close manifold gauge set valves. 2 - Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle. Figure thermometer to record the liquid line temperature, 5 - The outdoor temperature will determine which charging method to use, Proceed with the appropriate charging procedure. Weighing in the Charge Outdoor TXV Systems Temp. < 65°F - 16 1 - With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital thermometer to record the liquid line temperature. 2 - At the same time, record the liquid line pressure reading. 3 - Use a temperature/pressure chart for R410A to determine the saturation temperature for the liquid line pressure reading. See table 7. 4 - Subtract the liquid line temperature from the saturation 3 - Use a digital thermometer to record the outdoor ambient temperature, 4 - When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68_F (20<%). When pressures have stabilized, use a digital *4-sided unit shown temperature (according to the chart) to determine subcooling. (Saturation temperature - Liquid line temperature = Subcooling) 5 - Compare the subcooling value with those in table 4, If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant, Be aware of the R410A refrigerant cylinder. It will be light maroon-colored, Refrigerant should be added through the vapor line valve in the liquid state. Some R410A cylinders are equipped with a dip tube that allows you to draw liquid refrigerant from (18°C) the bottom of the cylinder without turning the cylinder upside-down. The cylinder will be marked if it is equipped with a dip tube. If the system is void of refrigerant, or if the outdoor ambient temperature is cool, the refrigerant charge should be weighed into the unit. Do this after any leaks have been repaired. Table 4 Subcooling Values for Charging 1 - Recover the refrigerant from the unit. Model Number 2 - Conduct a leak check, then evacuate as previously outlined. Conversion 3 - Weigh in the unit nameplate charge. If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other procedures outlined below. Subcooling Outdoor Method HPXB15-024 5 + 1 (2.8 + .5) HPXB15-030 8 + 1 (7.4 + .5) HPXB15-036 5.5 + 1 (3 + .5) HPXB15-042 4.5 + 1 (2.5 + .5) HPXB15-048 2.5 + 1 (1.4 + .5) HPXB15-060 6 + 1 (3.3 + .5) Charging Temp. < 65°F (18°C) Subcooling Values Temp. - Liquid Line Temp. °F (°C) Using Normal Operating and the Approach When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit, It may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 325-375 psig (2240-2585 kPa) range, These higher pressures are necessary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liquid pressure is in the 325-375 psig (2240-2585 kPa) range. See figure 16, Outdoor Temp. Pressures Method _>65°F (18°C) The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C), Monitor system pressures while charging. 1 - Record outdoor ambient temperature using a digital thermometer. 2 - Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize, Page 16 3 - Comparestabilizedpressures withthoseprovidedin table6, <'Normal OperatingPressures."Minorvariationsinthesepressures maybeexpected duetodifferencesin installations, Significantdifferencescould meanthatthesystemisnotproperlychargedorthata problemexistswithsomecomponent in the system. Pressureshigherthanthoselistedindicatethatthe systemis overcharged. Pressureslowerthanthose listedindicatethatthesystemis undercharged, Verify adjustedchargeusingtheapproachmethod. ApproachMethod 4 - Usethesamedigitalthermometer usedtocheckoutdoorambienttemperature tocheckliquidlinetemperature.Verifytheunitchargeusingtheapproach method, 5 - Thedifference between theambientandliquidtemperaturesshouldmatchvaluesgivenintable5.If thevaluesdon'tagreewiththethoseintable5,addrefrigerant to lowerthe approachtemperatureor recover refrigerant fromthesystemto increasetheapproach temperature, (Showing Table 5 Approach Model Number Approach Temperature Liquid Line Temp. - Outdoor Ambient °F (°C) HPXB15-024 13 + 1 (7.2 + .5) HPXB15-030 7 + 1 (3.9 + .5) HPXB15-036 11 + 1 (6.1 + .5) HPXB15-042 12.5 + 1 (6.9 + .5) HPXB15-048 10 + 1 (5.6 + .5) HPXB15-060 11.5 + 1 (6.5 + .5) IMPORTANT HPXB15 Cooling Cycle Gauge Manifold Connections) OUTDOOR DEFROST UNIT DISTRIBUTOR THERM OSTAT-_._._ I I EXPANSION/ Values for Charging NOTE - ARROWS INDICATE DIRECTION OF REFRIGERANT REVERSING VALVE FLOW I CHECK VALVE __ FILTER / LOW PRESSURE OUTDOOR 1_ DR,ER CO,L HIGH PRESSURE INDOOR _X UNIT VAPOR SERVICE / °OAI LINE VALVE DRU= [[ sc y47St -- POR__ -- --I--'_ VAPOR COMPRESSO_ k INDOOR COIL EXPANSION/CHECK VALVE NOTE-Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging. Figure 17 Page 17 L ...... Table 6 Normal Operating Pressures (Liquid +10 and Vapor +5 psig) Outdoor Coil Entering Air Temp. °F (°C) 65 (18.3) 75 (23.9) 85 (29.4) 95 (35.0) 105 (40.6) Outdoor Coil Entering Air HPXB15-024 Liquid 252 291 337 371 421 Cooling Operation HPXB15-036 HPXB15-030 Vapor 131 133 135 140 142 HPXB15-024 Liquid 233 272 314 360 413 Vapor 141 142 143 146 148 Liquid 216 276 298 359 400 Vapor 136 138 139 141 143 Heating Operation HPXB15-036 HPXB15-030 HPXB15-042 Liquid 240 281 325 372 428 Vapor 133 135 137 138 142 HPXB15-042 HPXB15-048 Liquid 228 265 304 348 405 Vapor 137 139 141 142 145 HPXB15-048 HPXB15-060 Liquid 231 269 315 370 415 Vapor 124 126 127 133 136 HPXB15-060 Temp. °F (°C) Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor 20 (-6.6) 30 (-1.1) 40 (4.4) 50 (10.0) 288 306 325 344 60 75 90 105 270 297 325 353 67 84 100 117 234 257 318 322 62 80 93 103 340 350 353 358 65 72 83 101 313 330 346 366 60 73 87 101 245 287 332 347 55 66 82 99 Table 7 R410A Temperature/Pressure Temperature °F Chart Pressure Psig Temperature °F Pressure Psig Temperature °F Pressure Psig 32 33 100.8 102.9 63 64 178.5 181.6 94 95 290.8 295.1 125 126 445.9 451.8 34 105.0 65 184.3 96 299.4 127 457.6 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 481.6 39 115.8 70 200.6 101 321.8 132 487.8 40 118.0 71 203.9 102 326.4 133 494.0 41 120.3 72 207.2 103 331.0 134 500.2 42 122.6 73 210.6 104 335.7 135 506.5 43 125.0 74 214.0 105 340.5 136 512.9 44 127.3 75 217.4 106 345.3 137 519.3 45 129.7 76 220.9 107 350.1 138 525.8 46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 110 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3 50 142.2 81 239.0 112 375.1 143 559.1 51 144.8 82 242.7 113 380.2 144 565.9 52 147.4 83 246.5 114 385.4 145 572.8 53 150.1 84 250.3 115 390.7 146 579.8 54 152.8 85 254.1 116 396.0 147 586.8 55 155.5 86 258.0 117 401.3 148 593.8 56 158.2 87 262.0 118 406.7 149 601.0 57 161.0 88 266.0 119 412.2 150 608.1 58 163.9 89 270.0 120 417.7 151 615.4 59 166.7 90 274.1 121 423.2 152 622.7 60 169.6 91 278.2 122 428.8 153 630.1 61 172.6 92 282.3 123 434.5 154 637.5 62 195.5 93 286.5 124 440.2 155 645.0 Page 18 Temperature °F Pressure Psig When an abnormal condition is detected, the module com- Theoutdoorunitandindoorblowercycleondemandfrom theroomthermostat. Whenthethermostat blowerswitchis intheONposition, theindoorbloweroperatescontinuously. ThermostatOperation Someoutdoorthermostats incorporate isolatingcontacts andanemergency heatfunction(whichincludes anamber indicatinglight).Thethermostat isnotincluded withtheunit andmustbepurchased separately, EmergencyHeat(AmberLight) Anemergency heatfunction isdesigned intosomeroomthermostats. Thisfeatureis applicable whenisolation oftheoutdoorunitis required, orwhenauxiliary electricheatisstaged byoutdoor thermostats, Whentheroomthermostat is placed intheemergency heatposition, theoutdoor unitcontrol drcuit is isolated frompowerandfield-provided relaysbypassthe outdoor thermostats, Anamberindicating lightsimultaneously comesontoremind thehomeowner thatheisoperating inthe emergency heatmode, Emergencyheatis usuallyusedduringan outdoorunit shutdown, butitshouldalsobeusedfollowing a poweroutageif powerhasbeenoffforoveranhourandtheoutdoor temperature is below50°F(10°C).Systemshouldbeleftin theemergency heatmodeatleastsixhoursto allowthe crankcaseheatersufficienttimeto preventcompressor slugging. HighPressureSwitch TheHPXB15 is equipped withanauto-reset highpressure switchwhichis locatedon the liquidline.Thenormally closedswitchopensthe compressorcircuitwhen dischargepressurerisesabove640+ 10psig(4412+ 69 kPa),The switchautomatically closeswhendischarge pressurefallsbelow448+ 10psig(3089+ 69kPa), FilterDrier Theunitis equipped witha large-capacity bifiowfilterdrier whichkeepsthe systemcleananddry.If replacement is necessary, orderanotheroflikedesignandcapacity. The replacement filterdriermustbesuitable forusewithR410A refrigerant, System Operation Monitor The system operation monitor detects the most common fault conditions in the air conditioning system, municates the specific condition through its ALERT and TRIP lights. The monitor is capable of detecting both mechanical and electrical system problems, See figure 18 for the system operation monitor A, IMPORTANT System Operation Monitor LED .y "R LED's Figure 18 LED Functions See table 8 for LED troubleshooting diagnostic codes. Power LED (green) - indicates voltage within the range of 19-28VAC is present at the power connection of the monitor. Alert LED (yellow) - communicates an abnormal system condition through a unique flash code, The alert LED will flash a number of times consecutively, pause and then repeat the process. The number of consecutive flashes, defined as the Flash Code, correlates to a particular abnormal condition, Trip LED (red) - indicates there is a demand signal from the thermostat but no current to the compressor is detected by the module, TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation. Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on, Page 19 System Operation Table 8 Monitor LED Troubleshooting Codes Status LED Status LED Description Status LED Troubleshooting Information Green "Power" Module has power. 24MAC control power is present at the module terminal. Red "Trip" Thermostat demand signal Y1 is present, but the compressor is not running. 1 Compressor protector is open. 2 Outdoor unit power disconnect is open. 3 Compressor circuit breaker or fuse(s) is open. 4 Broken wire or connector is not making contact. 5 Low pressure switch open if present in the system. 6 Compressor contactor has failed to close. Low refrigerant charge. Yellow "Alert" Flash Code 1 (Does not apply to heat pump or to two-stage split systems) Long Run Time Compressor is running tremely long run cycles Yellow "Alert" Flash Code 2 System Pressure Trip Discharge or suction pressure out of limits or compressor overloaded _ High head pressure. 2 Condenser coil poor air circulation (dirty, blocked, damaged). 3 Condenser fan is not running. 4 Return air duct has substantial leakage. 5 If low pressure switch is present, check Flash Code 1 information. Yellow "Alert" Flash Code 3 Short Cycling Compressor is running only briefly I Thermostat demand signal is intermittent. 2 Time delay relay or control board is defective. 3 If high pressure switch is present, check Flash Code 2 information. 4 If low pressure switch is present, check Flash Code 1 information. Yellow ex- "Alert" Flash Code 4 Locked Yellow "Alert" Flash Code 5 Open Circuit Yellow "Alert" Flash Code 6 Yellow "Alert" Flash Code 7 Yellow "Alert" Flash Code 8 Rotor 2 Evaporator blower is not running. 3 Evaporator coil is frozen. 4 Faulty metering device. 5 Condenser coil is dirty 6 Liquid line restriction (filter drier blocked if present) 7 Thermostat is malfunctioning. _ Run capacitor has failed. 2 Low line voltage (contact utility if voltage at disconnect 3 Excessive liquid refrigerant in the compressor. 4 Compressor bearings are seized. Outdoor unit power disconnect is open. 2 Unit circuit breaker or fuse(s) is open. is low). Open Start Circuit Current only in run circuit 3 Unit contactor has failed to close. 4 High pressure switch is open and requires manual reset. 5 Open circuit in compressor supply wiring or connections. 6 Unusually long compressor protector reset time due to extreme ambient temperature. 7 Compressor windings are dama0ed. _ Run capacitor has failed. 2 Open circuit in compressor start wiring or connections. 3 Compressor start windinq is damaqed. Open Run Circuit Current only in start circuit 1 Open circuit in compressor start wiring or connections. 2 Compressor start windinq is damaqed. Welded Contactor Compressor always runs I Compressor contactor failed to open. 2 Thermostat demand siqnal not connected to module. Yellow "Alert" Low Voltage 1 Control circuit transformer is overloaded Flash Code 9 Control circuit < 17VAC 2 Low line volta qe (contact utility if volta qe at disconnect is low.) • Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. • TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation. • Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on. Defrost Control The defrost control board includes the combined funcThe defrost system includes two components: • a defrost thermostat • a defrost control tions of a time/temperature relay, time delay, diagnostic defrost control, defrost LEDs, and a terminal strip for field wiring connections, See figure 19. Defrost Thermostat The control provides automatic switching from normal heating operation to defrost mode and back. During compressor cycle (call for defrost), the control accumulates compressor run times at 30, 60, or 90 minute field adjustable intervals. If the defrost thermostat is closed when the The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor. When the defrost thermostat senses 42°F (5.5°C) or cooler, its contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C), selected compressor run time interval ends, the defrost relay is energized and defrost begins, Page 20 DefrostControlTimingPins Eachtimingpinselectionprovidesa differentaccumulatedcompressorruntimeperiodduringonethermostat runcycle.Thistimeperiodmustoccurbeforea defrost cycleis initiated.Thedefrostintervalcanbeadjustedto 30(T1),60 (T2),or 90 (T3)minutes.Seefigure19,The defrosttimingjumperis factory-installedto providea 90-minutedefrostinterval.Ifthetimingselectorjumperis notin place,the controldefaultstoa 90-minutedefrost interval,Themaximumdefrostperiodis 14minutesand cannotbeadjusted, A TESToptionisprovidedfortroubleshooting, TheTEST modemaybestartedanytimethe unitis in theheating modeandthe defrost thermostatis closedor jumpered.Ifthejumperis intheTESTpositionatpower-up, the controlwillignorethetestpins,Whenthejumperisplaced acrosstheTESTpinsfortwoseconds, thecontrolwillenter thedefrostmode,If thejumperis removedbeforeanadditional5-secondperiodhaselapsed(7secondstotal),the unitwillremainindefrostmodeuntilthedefrostthermostat opensor 14minuteshavepassed.If thejumperis notremoveduntil after the additional5-secondperiodhas elapsed,thedefrostwillterminateandthetestoptionwill notfunctionagainuntilthejumperis removedandreapplied, CompressorDelay The defrost board has a built-in function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode, The compressor will be cycled off for 30 seconds going in and out of the defrost mode. NOTE - The 30 second off cycle is not functional when jumpering the TEST pins. minals to accommodate the addition of a field-provided low pressure or loss of charge pressure switch, See figure 19. This feature is available on all units, During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch that is wired to the control board. In addition, the diagnostic LEDs will indicate a locked out pressure switch after the fifth occurrence of an open pressure switch, See table 9. The unit will remain locked out until power is broken then remade to the control or until the jumper is applied to the TEST pins for 0.5 seconds, NOTE - The defrost control board ignores input from the low pressure switch terminals during the TEST mode, during the defrost cycle, during the 90-second start-up period, and for the first 90 seconds each time the reversing valve switches heat/cool modes. If the TEST pins are jumpered and the 5-minute delay is being bypassed, the LOPS terminal signal is not ignored during the 90-second start-up period. Ambient Thermistor & Service Light Connection The defrost control board provides terminal connections for the ambient thermistor and a service light. The thermistor compensates for changes in ambient temperature which might cause thermostat droop, The service light thermostat provides a signal which activates the room thermostat service light during periods of inefficient operation, Diagnostic LEDs The defrost board uses two LEDs for diagnostics, The LEDs flash a specific sequence according to the diagnosis, Table Defrost Control Board Diagnostic The timed-off delay is five minutes long. The delay helps protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens, The delay is bypassed by placing the timer select jumper across the TEST pins for 0,5 seconds. Pressure Switch Circuits The defrost control includes two pressure switch circuits. The high pressure switch ($4) is factory-connected to the board's HI PS terminals. The board also includes LOPS ter- LED LED 1 Mode Time Delay 9 LED 2 Normal operation / power to board Board failure or no power Board failure Synchronized Flash with LED z Off Synchronized Flash with LED I Off On On High pressure switch open Low pressure switch open Flash On On Flash Pressure switch lockout On Off Anti-short-cycle / 5-minute delay Alternating Flash with IFD2 Alternating Flash with IFD1 Page 21 Defrost FAN Control Board = O U S [] _ HI PS (Factory-wired) Optional Pressure Switch Ambient Thermistor Terminals Optional Pressure Switch Terminals K2 RELAY] (Remove factoryinstalled jumper to install LO PS (Field-provided and installed -jumper Service Light Terminals High Pressure Switch Terminals Pressure Switch Wiring Connections High Pressure Switch ===Wl removed) pressure K3 RELAY DEFROST INTERVAL TIMING PINS HOT switch.) 0 I Defro_ L0-PS Thermostat 24V Terminal Strip D,A NOST,° Reversing Valve LEDs O TST O-0UT o PS_ oDF oC oR o 0 O Figure HOT o YI 19 6 - Check amp-draw on outdoor fan motor. 7- Inspect drain holes in coil compartment base and clean if necessary. AWARNING NOTE - If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction. Indoor Coil 1 - Clean coil if necessary. 2 - Check connecting lines, joints and coil for evidence of oil leaks. Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling or heating season, the system should be checked as follows: 3 - Check condensate line and clean if necessary. Indoor Unit 1 - Clean or change filters, Outdoor Unit 2 - Lennox blower motors are prelubricated and permanently sealed, No more lubrication is needed. 1 - Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning. 3 - Visually inspect all connecting lines, joints and coils for evidence of oil leaks. 3 - Adjust blower speed for cooling, Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure, 4 - Belt Drive Blowers - Check belt for wear and proper tension, 4 - Check all wiring for loose connections. 5 - Check all wiring for loose connections, 5 - Check for correct voltage at unit (unit operating). 6 - Check for correct voltage at unit, 2 - Outdoor unit fan motor is prelubricated and sealed. No further lubrication is needed. Page 22 7 - Checkamp-draw onblowermotor. cause the outdoor unit to work harder and use more ener- RefertotheEngineering Handbook foroptionalaccessoriesthatmayapplytothisunit,Thefollowingmayor may notapply: • Lossof ChargeKit • HighPressureSwitcKit • Compressor Monitor • Compressor Crankcase Heater • HailGuards • Mounting Bases • TimedOffControl • Stand-off Kit • SoundCover • LowAmbientKit • MonitorKit Inordertoensurepeakperformance, yoursystemmustbe properlymaintained. Cloggedfiltersandblockedairflow preventyourunitfromoperating at itsmostefficientlevel, AskyourLennoxdealerto showyouwhereyourindoor unit'sfilteris located.It will be eitherat the indoorunit (installed internalorexternalto thecabinet)orbehinda returnairgrilleinthewallorceiling.Checkthefiltermonthly andcleanorreplaceitas needed, Disposable filtersshouldbereplacedwitha filterof the sametypeandsize,If youareunsureaboutthefilteryou needforyoursystem,callyourLennoxdealerfor assistance. A IMPORTANT gy. Keep shrubbery trimmed away from the unit and periodically check for debris which may have collected around the unit, Heat Pump Operation Your new Lennox heat pump has several characteristics that you should be aware of: Your heat pump satisfies heating demand by delivering large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space, Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost. During the defrost cycle, you may notice steam rising from the outdoor unit, This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle. Your Lennox HPXB15 heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation. If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the "Emergency Heat" setting to obtain temporary heat without the risk of serious equipment damage, In this operating mode, all heating demand will be satisfied by auxiliary heat. Compressor operation is locked out during Emergency Heat operation. After a six-hour compressor crankcase heater warm-up period, the thermostat can be switched to the "Heat" setting and normal operation will resume. Thermostat Many indoor units are equipped with reusable foam filters. These filters can be cleaned with a mild soap and water solution, Rinse the filter thoroughly and let it dry completely before it is returned to the unit or grille, The filter and all access panels must be in place any time the unit is in operation. Your system may be equipped with an electronic air cleaner which will provide respiratory relief by removing up to 90 percent of all airborne particles which pass through it. If it is, ask your dealer to instruct you on its maintenance, Your indoor evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you where the main condensate drain (and auxiliary drain, if applicable) runs and how to check the drain for any obstruction, It is also very important to provide unrestricted airflow to the outdoor unit, Leaves, trash or shrubs crowding the unit Operation Though your thermostat may vary somewhat from the description below, its operation will be similar, Temperature Setting Levers Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling, Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor. Fan Switch In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating, This mode is required when constant air circulation or filtering is desired. Page 23 System Switch Set the system switch for heating, cooling or auto operation, The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings, Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat, Indicating Light and cooling, Refer to the user's information manual provided with your particular thermostat for operation details. Preservice Check If your system fails to operate, check the following before calling for service: • Check to see that all electrical disconnect switches are ON, • Make sure the room thermostat temperature selector is properly set, Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode. • Make sure the room thermostat system switch is properly set. Temperature Indicator The temperature indicator displays the actual room temperature, • Replace any blown fuses, or reset circuit breakers. • Make sure unit access panels are in place. Programmable Thermostats Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating Start-up Job Name Job Location • Make sure air filter is clean, • Locate unit model number and have it handy before calling, and Performance Job No, Check City Installer Unit Model No, List Date State City State Service Technician Serial No. Nameplate Voltage Rated Load Ampacity Maximum Fuse or Circuit Breaker Indoor Filter Clean? [] Electrical Connections Tight? [] Indoor Blower RPM Cooling Liquid Line Pressure Heating Liquid Line Pressure Refrigerant Lines: Outdoor Fan Compressor Supply Voltage (Unit Off) __ S.R Drop Over Indoor (Dry) -- Vapor Pressure Vapor Pressure Leak Checked? [] Properly Insulated? [] Outdoor Coil Entering Air Temp. Refrigerant Charge Checked? [] Refrigerant Charge Checked? Outdoor Fan Checked? [] [] Service Valves Fully Opened? [] Voltage With Compressor Operating -Service Valve Caps Tight? [] Thermostat Sequence of Operation Heating Correct [] Cooling Correct [] Calibrated? [] Properly Set? [] Level? Page 24 []
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 24 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 05:01:41 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools