LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0806498
User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 24
LENNOX
,1,_2003Lennox industries inc.
Dallas, Texas
INSTALLATION
INSTRUCTIONS
HPXB15 SERIES UNITS
HEAT PUMP UNITS _ Technical
504,735M i i i_z-_j_LL[Publications
12/03
Supersedes 07/03 Lithe U.S.A.
HPXB15 outdoor units use R410A which is an ozone
friendly HFC refrigerant. This unit must be installed with a
matching indoor coil and line set as outlined in the Lennox
Engineering Handbook. HPXB15 outdoor units are de-
signed for use in expansion valve (TXV) systems only.
They are not designed to be used with other refrigerant flow
control devices. The Lennox Engineering Handbook lists
indoor TXV kits that must be ordered separately.
A, IMPORTANT
HPXB15 Outdoor Unit ........................... 1
Shipping & Packing List ......................... 1
General Information ............................. 1
Dimensions .................................... 2
Parts Arrangement ............................. 3
Setting the Unit ................................. 3
Electrical ...................................... 4
Refrigerant Piping .............................. 6
Refrigerant Metering Device ..................... 6
Flushing Existing Line Set & Indoor Coil ........... 7
Manifold Gauge Set ............................. 8
Service Valves ................................. 8
Leak Testing ................................... 9
Evacuation ................................... 10
Start-Up ...................................... 11
Charging .................................... 11
System Operation ............................. 15
Defrost System ............................... 16
Maintenance .................................. 18
Optional Accessories ........................... 19
Homeowner Information ........................ 19
HPXB15 Check Points ......................... 20
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
1 - Assembled HPXB15 outdoor unit
2 - Grommets (for liquid and vapor lines)
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
,A WARNING
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
,&,WARNING
12/03
IIIIIIIIIIIIIIIIIIIIIIII1,1111111111111
Page 1
504,735M
IIil!111111,111,111,11111111111111111111111
inlet _ air
compressor
inlet
0
air
electrical
inlets
vapor
line inlet
liquid
line inlet
4-1/2 (114)
2-3/4
(70)
2 1-3/8
(51) (35)
coil drain outlets
air (around perimeter
Top View of base)
C y
discharge tair
Side View
Model No.
JR.
HPXB15-024
mm
HPXB15-030 in.
HPXB15-036 mm
in.
HPXB15-042 mm
HPXB15-048 in.
HPXB15-060 mm
A B CD E F G HJ
27-7/8 25-7/8 29-7/8 12-1/4 22-7/16 14-7/16 22-1/8 16-3/4 2-7/8
708 657 759 311 570 367 562 425 730
30-7/8 32-1/8 34-1/16 12-3/4 26-5/8 18-5/8 28-1/8 17-1/4 3-7/8
784 816 865 324 676 473 718 438 98
34-7/8 32-1/8 34-1/16 13-3/4 26-5/8 18-5/8 28-1/8 18-1/4 3-7/8
886 816 865 349 676 473 718 464 98
44-7/8 32-1/8 34-1/16 14-1/4 26-5/8 18-5/8 28-1/8 18-3/4 3-7/8
1140 816 865 362 676 473 718 476 98
K
5-1/2
140
7-1/2
191
7-1/2
191
7-1/2
191
Page 2
high pressure
switch
filter/drier
expansion valve
with internal
system operation
monitor \
defrost control/timed-off control
contactor
ground lug
sensing bulb
vaporline
service valve
and gauge port
liquid line
service valve
and gauge port
defrost
thermostat crankcase heater
thermostat
distributor
compressor
terminal plug crankcase
heater
muffler
reversing valve
and solenoid
Figure 1
ACAUTION
XkCAUTION
These units operate under a wide range of weather condi-
tions; therefore, several factors must be considered when
positioning the outdoor unit. The unit must be positioned to
give adequate clearances for sufficient airflow and servic-
ing. A minimum clearance of 24 inches (610 mm) between
multiple units must be maintained. Refer to figure 2 for in-
stallation clearances.
1 - Place a sound-absorbing material, such as Isomode,
under the unit if it will be installed in a location or posi-
tion that will transmit sound or vibration to the living
area or adjacent buildings.
2 - Mount unit high enough above ground or roof to allow
adequate drainage of defrost water and prevent ice
build-up.
3 - In heavy snow areas, do not locate unit where drifting
will occur. The unit base should be elevated above the
depth of average snows.
NOTE -Elevation of the unit may be accomplished by
constructing a frame using suitable materials. If a sup-
port frame is constructed, it must not block drain holes
in unit base.
Installation Clearances
NOTE -A service access
clearance of 30" (762 mm)
must be maintained in front
of the service access panel.
Clearance to one side must
be 36" (914 mm). Clearance
to one of the remaining two 30"
sides may be 12" (304 mm) (762ram)
and the final side may be 6"
(152 mm).
NOTE -A clearance of 24" (610 mm)
must be maintained between two unit&
as noted _*
I as noted J
NOTE -48" (1219 mm) clearance required on top
of unit. Maximum soffit overhang is 36" (914 mm).
Figure 2
4 - When installed in areas where low ambient tempera-
tures exist, locate unit so winter prevailing winds do
not blow directly into outdoor coil.
Page 3
5- Locateunitawayfromoverhangingrooflineswhich
wouldallowwateroricetodropon,orinfrontof,coilor
intounit,
Slab Mounting
When installing unit at grade level, top of slab should be
high enough above the grade so that water from higher
ground will not collect around unit, See figure 3. Slab
should have a slope tolerance away from the building of 2
degrees or 2 inches per 5 feet (51 mm per 1.5 m), This will
prevent ice build-up under unit during a defrost cycle. Refer
to roof mounting section for barrier construction if unit must
face prevailing winter winds.
2 degrees or
2 in. per 5 foot
(51 mm per 1.5 m) discharge air
slope tolerance away
from building structure %r
ground level
Slab Mounting
Figure 3
building
structure
mounting
slab
i
CL-
CL-
-T
C[-
Roof Mounting
Install the unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build-up around the unit. Locate
the unit above a load bearing wall or area of the roof that
can adequately support the unit, Consult local codes for
rooftop applications,
If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed. See figure 3,
Size barrier at least the same height and width as outdoor
unit, Mount barrier 24 inches (610 mm) from the sides of the
unit in the direction of prevailing winds.
Rooftop Application
Wind Barrier Construction
prevailing winter winds
0
wind barrier
inlet air
I
I
I
I0
inlet air
]IL
24"
(610 ram)
INLET
0
AIR
Figure 4
In the U,S,A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC),
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
WARNING
1 -Install line voltage power supply to unit from a properly
sized disconnect switch,
2 -Ground unit at unit disconnect switch or to an earth
ground.
Page 4
NOTE -To facilitate conduit, a hole is in the bottom of
the control box. Connect conduit to the control box us
ing a proper conduit fitting.
NO TE -Units are approved for use only with copper
conductors.
24V, Class II circuit connections are made in the low
voltage junction box. Refer to figure 5 for field wiring
diagram.
NOTE -A complete unit widn_l dia_lram is located in
side the unit control box cover.
3 - Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be affected
by sunlight, drafts or vibrations.
4 - Install voltage wiring from outdoor to indoor unit and
from thermostat to indoor unit. See figures 6 and 7.
Typical Field Wiring Diagram
B4
OUTDOOR FAN
(LEADED) ORANGE-RUN
=COMMON
PURPLE=
CAPACITOR
CI2
DUAL
CAPACITOR
SYSTEM
OPERATION
MONITOR E _--- WI
AN DEFROST
Y,OUT CONTROL
HI -PS
L0-PS
_ RO
D! wo
O0
OUT Y I
_0
GROUND
LUG,S_
KI
COMPRESSOR
DONTACTOR
Ik,
z_
L2 L1
208-230/60/1
main power
z_NOTE-
FOR USE WITH COPPER CONDUCTORS
ONLY.REFER TO UNIT RATING
PLATE FOR MINIMUM CIRCUIT
AMPACITY AND MAXIMUM OVER-
CURRENT PROTECTION SIZE
/_ WARNING-
ELECTRIC SHOCK HAZARD,CAN CAUSE INJURY
OR DEATH.UNIT MUST BE GROUNDED IN
ACCORDANCE WITH NATIONAL AND LOCAL CODES.
Figure 5
Page 5
Outdoor Unit and Blower Unit
Thermostat Designations
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat Indoor Outdoor
Unit Unit
@+
@+
power
common _(__
1st. stage aux. heat _F
@
indoor blower -(b
reversing valve
power
common
1st. s_e aux. hea_l
compressor
®
@
J
Figure 6
Outdoor Unit and Blower Unit
Thermostat Designations
(with auxiliary heat)
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat
®
Q
®
®
@
power 1_
common I
emergency heat I -
I
I
1st. stage aux. TTeaq-
f
k
indoor btower
reversinq.vatve
Indoor
Unit
__. power
he_"cOmmat_em'_
/eutdger t'stat
-_-st._stTg _. _at
@1
®1
compressor
Outdoor
Unit
®1
©1
®1
®[
®1
Figure 7
If the HPXB15 unit is being installed with a new indoor coil
and line set, the refrigerant connections should be made as
outlined in this section. If an existing line set and/or indoor
coil is going to be used to complete the HPXB15 system,
refer to the following section which includes flushing proce-
dures.
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, non-
flare) series line sets as shown in table 1 or use field-fabri-
cated refrigerant lines, Valve sizes are listed in table 1.
Refrigerant Connections
HPXB15 Matched with New Indoor Coil and Line Set
If an existing indoor coil which was equipped with an
RFCI metering device is being replaced, the liquid line
must also be replaced prior to the installation of the
HPXB15 unit.
Table 1
Refrigerant Line Sets
Valve Field Size Recommended Line Set
Connections
Model L15
Liquid Vapor Liquid Vapor Line Sets
Line Line Line Line
-024 3/8 in, 3/4 in, 3/8 in, 3/4 in, L15-41
-030 10mm 19mm 10mm 19mm 15 ft. - 50 ft.
-036 4.6 m- 15 m
-042 3/8 in. 7/8 in. 3/8 in. 7/8 in. L15-65
-048 10mm 22mm 10mm 22mm 15 ft. - 50 ft.
4.6m- 15m
3/8 in, 1-1/8 in, 3/8 in. 1-1/8 in, Field
-060 10 mm 29 mm 10 mm 29 mm Fabricated
NOTE -Units are designed for line sets of up to 50 feet (15
m). Select line set diameters from table 1 to ensure that oil
returns to the compressor.
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is
important to properly isolate the refrigerant lines to prevent
unnecessary vibration, Line set contact with the structure
(wall, ceiling or floor) causes some objectionable noise
when vibration is translated into sound, As a result, more
energy or vibration can be expected, Closer attention to
line set isolation must be observed,
Following are some points to consider when placing and
installing a high-efficiency outdoor unit:
1-Placement - Be aware some localities are adopting
sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line,
When possible, do not install the unit directly outside a
window, Glass has a very high level of sound transmis-
sion.
2- Line Set Isolation -The following illustrations demon-
strate procedures which ensure proper refrigerant line
set isolation. Figure 8 shows how to install line sets on
vertical runs. Figure 9 shows how to install line sets on
horizontal runs, Figure 10 shows how to make a transi-
tion from horizontal to vertical, Finally, figure 11 shows
how to place the outdoor unit and line set,
Page 6
Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
NOTE -Similar installation practices should be used if
line set is to be installed on exterior of outside waft.
i
Outside Wall
\
Wood Block
r
Between Studs
-Vapor LiLn_uid Lin-'_
(wrapped with
Outside Wall
g__Caulk
PVC Pipe Fiberglass
Insulation
IMPORTANT- Refrigerant
lines must not contact
structure, j
IMPORTANT- Refrigerant
lines must not contact wall. Vapor Line Liquid Line
Wire Tie
\ Inside Wall
-- Strap
_ Sleeve
_- Wire Tie
--_------- Wood Block
"_ _-------- Wire Tie
Strap
_" _ Sleeve
Figure 8
Page 7
Refrigerant Line Sets:
Installing Horizontal Runs
To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties.
8 feet
Floor Joist or
Roof Rafter
/
/
I
I
8 feet
Wire Tie
(around vapor line only)
Tape or Wire Tie
Strapping Material (around vapor line only)
\
Tape or Wire Tie
Metal Sleeve
r j/
, Floor Joist or Roof Rafterf_
Strap the vapor line to the joist or rafter at 8 ft.
intervals then strap the liquid line to the vapor line.
Figure 9
Page 8
AnchoredHeavy
NylonWireTie
Refrigerant Line Sets:
Transition From Vertical To Horizontal
Automotive
Muffler-Type
Hanger
Wall
Stud Strap Liquid Line
To Vapor Line
Wall
Stud
Strap Liquid Line
To Vapor Line
Liquid Line
Sleeve
Vapor Line
Wrapped in
Armaflex Liquid Line
Figure 10
Metal
Sleeve
Vapor Line
Wrapped in
Armaflex
Outside Unit Placement and Installation
Install unit away from windows. J
Two 90° elbows
installed in line set
will reduce line set
vibration.
Figure 11
Page 9
IsolationGrommets
Locatetheprovidedisolationgrommets.Usea knifetoslit
thewebbingoneachgrommet.Slidelargergrommetonto
vaporlineand smallergrommetontoliquidline.Insert
grommetsinto mullionto isolaterefrigerantlinesfrom
sheetmetaledges.
&WARNING
Brazing Connection Procedure
1 - The end of the refrigerant line must be cut square and
its internal shape must remain round. The line must be
free of nicks or dents and must be deburred (I.D. and
O.D.)
2 - Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the sys-
tem.
3 - Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper-to-copper brazing or 45 percent
silver alloy for copper4o-brass or copper4o-steel braz-
ing). Wrap a wet cloth around the valve body and the
copper tube stub. Remove light maroon washers from
service valves and shield light maroon stickers in order
to protect them during brazing. Braze the line set to the
service valve.
4 - Quench the joint with water or a wet cloth to prevent
heat damage to the valve core and opening port.
IMPORTANT -The tube end must stay bottomed in the
fitting during final assembly to ensure proper seating,
sealing and rigidity.
Metering Device Installation
distributor
//
o-ring
o-ring
expanston
valve j
liquid li_
stub
Figure
12
&IMPORTANT
&WARNING
&IMPORTANT
HPXB15 units are used in check expansion valve systems
only. Check expansion valves equipped with Chatleff fit-
tings are available from Lennox. Refer to the Engineering
Handbook for applicable expansion valves for use with
specific match-ups.
If you install a check expansion valve with an indoor coil
that includes a fixed orifice, remove the orifice before
installing the check expansion valve.
See figure 12 for installation of the check expansion valve.
Page 10
ACAUTION
IMPORTANT
Required Equipment
You will need the following equipment in order to flush the
existing line set and indoor coil: two clean R22 recovery
bottles, an oilless recovery machine with a pump down fea-
ture, and two sets of gauges (one for use with R22 and one
for use with the R410A).
Flushing Procedure
1 - Remove existing R22 refrigerant using the appropri-
ate procedure below.
If the existing outdoor unit is not equipped with
shut-off valves, or if the unit is not operational
AND you plan to use the existing R22 refrigerant to
flush the system -- Disconnect all power to the exist-
ing outdoor unit. Connect the existing unit, a clean re-
covery cylinder and the recovery machine according
to the instructions provided with the recovery ma-
chine, Remove all R22 refrigerant from the existing
system. Refer to gauges after shutdown to confirm
_
_
that the entire system is completely void of refrigerant.
Disconnect the liquid and vapor lines from the existing
outdoor unit,
ff the existing outdoor unit is equipped with manu-
al shut-off valves AND you plan to use NEW R22
refrigerant to flush the system -- Start the existing
R22 system in the cooling mode and close the liquid
line valve, Pump all of the existing R22 refrigerant
back into the outdoor unit, (It may be necessary to by-
pass the low pressure switches to ensure complete re-
frigerant evacuation,) When the low side system pres-
sures reach 0 psig, close the vapor line valve.
Disconnect all power to the existing outdoor unit, Re-
fer to gauges after shutdown to confirm that the valves
are not allowing refrigerant to flow back into the low
side of the system, Disconnect the liquid and vapor
lines from the existing outdoor unit,
Remove the existing outdoor unit, Set the new R410A
unit and follow the brazing connection procedure
which begins on the previous page to make line set
connections. DO NOT install the field-provided
R410A check/expansion valve at this time.
Make low voltage and line voltage connections to the
new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this
time.
Remove the existing refrigerant flow control orifice or
thermal expansion/check valve before continuing with
flushing procedures. The existing devices are not ap-
proved for use with R410A refrigerant and may pre-
vent proper flushing, Use a field-provided fitting to re-
connect the lines.
Page 11
Existinc
Indoor Coil
RECOVERY
CYLINDER
Inverted R22 Cylinder
(Contains clean R22 to
be used for flushing)
EXISTING VAPOR LINE
EXISTING LIQUID LINE
Flushing Connections
TANK RETURN
INLET
DISCHARGE
Recovery Machine
HPXB15 Unit
LOW HIGH
PRESSURE PRESSURE
Op{_C:[ENIE:AU GE MAN::_: _:_
NOTE -The inverted R22 cylinder must con-
tain at least the same amount of refrigerant
as was recovered from the existing system.
A, IMPORTANT
Figure 13
7-
4- Remove the pressure tap valve cores from the
H PXB 15 unit's service valves, Connect an R22 cylin-
der with clean refrigerant to the vapor service valve.
Connect the R22 gauge set to the liquid line valve and
connect a recovery machine with an empty recovery
tank to the gauge set,
5 - Set the recovery machine for liquid recovery and start
the recovery machine, Open the gauge set valves to
allow the recovery machine to pull a vacuum on the ex-
isting system line set and indoor coil,
6 - Invert the cylinder of clean R22 and open its valve to
allow liquid refrigerant to flow into the system through
the vapor line valve, Allow the refrigerant to pass from
the cylinder and through the line set and the indoor coil
before it enters the recovery machine,
After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that
all of the R22 vapor is recovered,
NOTE- A single system flush should remove all of the
mineral oil from the existing refrigerant lines and in-
door coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush. Each time the system
is flushed, you must allow the recovery machine
to pull avacuum on the system at the end of the
procedure.
8- Close the valve on the inverted R22 drum and the
gauge set valves, Pump the remaining refrigerant out
of the recovery machine and turn the machine off,
9 - Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery ma-
chine, gauges and R22 refrigerant drum, Reinstall
pressure tap valve cores into HPXB15 service valves,
10 -Install the provided check/expansion valve (approved
for use with R410A refrigerant) in the liquid line at the
indoor coil,
Page 12
AIMPORTANT
Access the liquid line and vapor line service valves (figures
14 and 15) and gauge ports are used for leak testing, eva-
cuating, charging and checking charge, See table 2 for
torque requirements,
Each valve is equipped with a service port which has a fac-
tory-installed Schrader valve. A service port cap protects
the Schrader valve from contamination and serves as the
primary leak seal,
Table 2
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.- lb. 11 NM
Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.-lb. 3 NM
Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
IMPORTANT
To Access Schrader Port:
1 - Remove service port cap with an adjustable wrench,
2 - Connect gauge to the service port.
3 - When testing is complete, replace service port cap,
Tighten finger tight, then an additional 1/6 turn,
To Open Service Valve:
1 - Remove stem cap with an adjustable wrench.
2 - Using service wrench and hex head extension, back
the stem out counterclockwise as far as it will go,
NO TE -Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 - Replace stem cap and tighten it firmly. Tighten finger
tight, then tighten an additional 1/6 turn.
To Close Service Valve:
1 - Remove stem cap with an adjustable wrench,
2 - Using service wrench and hex head extension, turn
stem clockwise to seat valve, Tighten it firmly,
NOTE -Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 - Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
Vapor Line (Ball Type) Valve
Vapor line service valves function the same way as the oth-
er valves, the difference is in the construction, These
valves are not rebuildable. If a valve has failed, you must
replace it. A ball valve valve is illustrated in figure 15,
The ball valve is equipped with a service port with a factory-
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak-
free seal,
Liquid Service Valve (Valve Open)
Insert Hex Stem Cap
Wrench
Field Side
Schrader
Valve
Service Port
Cap
Service Port
Unit Side
Liquid Service Valve (Valve Closed)
Field Side _..----._ Stem Cap
Insert Hex
Wrench Here
Service
Port (Valve Front
Seated)
Service Port Unit Side
Cap
Schrader Valve Open
To Line Set When Valve Is
Closed(FrontSeated)
Figure 14
Page 13
Vapor Line (Ball Type) Service Valve
(Valve Open)
Use Adjustable Wrench
To open: rotate stem counter-clockwise 90 ° .
To close: rotate stem clockwise 90 °.
_service port
cap unit side
Scharlavder_
service
port
ste m
field side ball
(shown open)
Figure 15
stem cap
After the line set has been connected to the indoor and out-
door units, the line set connections and indoor unit must be
checked for leaks.
WARNING
3 - Open the high pressure side of the manifold to allow
the R410A into the line set and indoor unit. Weigh in a
trace amount of R410A. [A trace amount is a maximum
of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.]
Close the valve on the R410A cylinder and the valve
on the high pressure side of the manifold gauge set.
Disconnect the R410A cylinder.
4 - Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 - Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)
6 - Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.
7 - After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R410A
mixture. Correct any leaks and recheck.
,IMPORTANT
AWARNING
WARNING
Using an Electronic Leak Detector
1 - Connect a cylinder of R410A to the center port of the
manifold gauge set.
2 - With both manifold valves closed, open the valve on
the R410A cylinder (vapor only).
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.
AIMPORTANT
1 - Connect the manifold gauge set to the service valve
ports as follows:
• low pressure gauge to vapor line service valve
• high pressure gauge to liquid line service valve
Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of R410A.
2 - Connect micron gauge,
3 - Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 - Open both manifold valves and start vacuum pump,
Page 14
5- Evacuatethelinesetandindoorunitto anabsolute
pressureof23,000microns(29.01inchesof mercu-
ry).Duringtheearlystagesof evacuation,it isdesir-
abletoclosethemanifoldgaugevalveatleastonceto
determineifthereisa rapidriseinabsolute pressure.
A rapid rise in pressure indicates a relatively large leak.
If this occurs, repeat the leak testing procedure.
NOTE -The term absolute pressure means the total
actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.
6 - When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit.
Close the manifold gauge valves.
XkWARNING
7 - Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8 - Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9 - When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set,
IMPORTANT
1 - Rotate fan to check for frozen bearings or binding.
2 - Inspect all factory- and field-installed wiring for loose
connections.
3 - After evacuation is complete, open the liquid line and
vapor line service valves (counterclockwise) to release
refrigerant charge (contained in outdoor unit) into the
system.
4 - Replace stem caps and secure finger tight, then tight-
en an additional (1/6) one-sixth of a turn.
5- Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit
nameplate. If not, do not start the equipment until the
power company has been consulted and the voltage
condition has been corrected.
6 - Set the thermostat for a cooling demand, turn on power
to indoor blower unit and close the outdoor unit discon-
nect to start the unit.
7 - Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
This system is charged with R410A refrigerant which oper-
ates at much higher pressures than R22. The check/ex-
pansion valve provided with the unit is approved for use
with R410A. Do not replace it with a valve designed for use
with R22. This unit is NOT approved for use with coils which
include metering orifices or capillary tubes.
Processing Procedure
The unit is factory-charged with the amount of R410A re-
frigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with a 15
foot (4.6 m) line set. For varying lengths of line set, refer to
table 3 for refrigerant charge adjustment.
Table 3
Liquid Line Set Oz. per 5 ft. (grams per 1.5 m) adjust
Diameter from 15 ft. (4.6 m) line set*
3/8 in. 3 ounces per 5 feet
(10 ram) (85g per 1.5 m)
*If line length is ,reater than 15 ft. (4.6 m), add this amount.
If line length is less than 15 ft. (4.6 m), subtract this amount.
klMPORTANT
Page 15
The compressor is charged with sufficient polyol ester
oil for line set lengths up to 50 ft.
The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. The method of charging is deter-
mined by the unit's refrigerant metering device and the out-
door ambient temperature.
Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:
1- Connect manifold gauge set to service valves as
shown in figure 17:
• low pressure gauge to vapor valve service port
• high pressure gauge to liquid valve service port
Connect the center manifold hose to an upright cylin-
der of R410A, Close manifold gauge set valves.
2 - Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in
the cooling cycle.
3 - Use a digital thermometer to record the outdoor ambi-
ent temperature,
4 - When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68_F
(20<%). When pressures have stabilized, use a digital
thermometer to record the liquid line temperature,
5 - The outdoor temperature will determine which charg-
ing method to use, Proceed with the appropriate charg-
ing procedure.
Weighing in the Charge TXV Systems -
Outdoor Temp. < 65°F (18°C)
If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit. Do this after any leaks have been re-
paired.
1 - Recover the refrigerant from the unit.
2 - Conduct a leak check, then evacuate as previously
outlined.
3 - Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other proce-
dures outlined below.
Subcooling Method
Outdoor Temp. < 65°F (18°C)
When the outdoor ambient temperature is below 65°F
(18°C), use the subcooling method to charge the unit, It
may be necessary to restrict the air flow through the out-
door coil to achieve pressures in the 325-375 psig
(2240-2585 kPa) range, These higher pressures are nec-
essary for checking the charge. Block equal sections of air
intake panels and move obstructions sideways until the liq-
uid pressure is in the 325-375 psig (2240-2585 kPa) range.
See figure 16,
O,ock,n00u,0oorCoi,
| *Outdoor coil should be
| blocked one side
| at a time with cardboard
| or plastic sheet until proper
r testing pressures
are reached.
cardboard or *4-sided
plastic sheet unit shown
Figure 16
1 - With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature.
2 - At the same time, record the liquid line pressure reading.
3 - Use a temperature/pressure chart for R410A to deter-
mine the saturation temperature for the liquid line pres-
sure reading. See table 7.
4 - Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine sub-
cooling. (Saturation temperature - Liquid line tem-
perature = Subcooling)
5 - Compare the subcooling value with those in table 4, If
subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant, Be aware of the R410A refrigerant cylinder. It
will be light maroon-colored, Refrigerant should be
added through the vapor line valve in the liquid state.
Some R410A cylinders are equipped with a dip
tube that allows you to draw liquid refrigerant from
the bottom of the cylinder without turning the cyl-
inder upside-down. The cylinder will be marked if it
is equipped with a dip tube.
Table 4
Subcooling Values for Charging
Model Number Subcooling Values
Conversion Temp. - Liquid Line Temp. °F (°C)
HPXB15-024 5 + 1 (2.8 + .5)
HPXB15-030 8 + 1 (7.4 + .5)
HPXB15-036 5.5 + 1 (3 + .5)
HPXB15-042 4.5 + 1 (2.5 + .5)
HPXB15-048 2.5 + 1 (1.4 + .5)
HPXB15-060 6 + 1 (3.3 + .5)
Charging Using Normal Operating Pressures
and the Approach Method
Outdoor Temp. _>65°F (18°C)
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C),
Monitor system pressures while charging.
1 - Record outdoor ambient temperature using a digital
thermometer.
2 - Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize,
Page 16
3- Comparestabilizedpressureswiththoseprovidedin
table6, <'NormalOperatingPressures."Minorvaria-
tionsinthesepressuresmaybeexpectedduetodiffer-
encesin installations,Significantdifferencescould
meanthatthesystemisnotproperlychargedorthata
problemexistswithsomecomponentinthesystem.
Pressureshigherthanthoselistedindicatethatthe
systemis overcharged.Pressureslowerthanthose
listedindicatethatthesystemisundercharged,Verify
adjustedchargeusingtheapproachmethod.
ApproachMethod
4 - Usethesamedigitalthermometerusedtocheckout-
doorambienttemperaturetocheckliquidlinetempera-
ture.Verifytheunitchargeusingtheapproachmethod,
5- Thedifferencebetweentheambientandliquidtemper-
aturesshouldmatchvaluesgivenintable5.Iftheval-
uesdon'tagreewiththethoseintable5,addrefriger-
ant to lowerthe approachtemperatureor recover
refrigerantfromthesystemto increasetheapproach
temperature,
Table 5
Approach Values for Charging
Approach Temperature
Model Number Liquid Line Temp. -Outdoor Ambient °F (°C)
HPXB15-024 13 + 1 (7.2 + .5)
HPXB15-030 7 + 1 (3.9 + .5)
HPXB15-036 11 + 1 (6.1 + .5)
HPXB15-042 12.5 + 1 (6.9 + .5)
HPXB15-048 10 + 1 (5.6 + .5)
HPXB15-060 11.5 + 1 (6.5 + .5)
IMPORTANT
HPXB15 Cooling Cycle
(Showing Gauge Manifold Connections)
DEFROST THERM OSTAT-_._._ I
I
EXPANSION/ I
CHECK VALVE __
LOW HIGH
PRESSURE PRESSURE
°OAI
DRU=[[ sc y47St
OUTDOOR UNIT
DISTRIBUTOR
FILTER /OUTDOOR
1_ DR,ER CO,L
-- -- --I--'_ COMPRESSO_
k
NOTE-Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines
and indoor coil. Use vapor gauge port to measure vapor pressure during charging.
NOTE - ARROWS INDICATE
DIRECTION OF REFRIGERANT
REVERSING VALVE FLOW
INDOOR UNIT
_X VAPOR
SERVICE
POR__ VAPOR
/LINE
VALVE
INDOOR
EXPANSION/CHECK COIL
VALVE L ......
Figure 17
Page 17
Table 6
Normal Operating Pressures
(Liquid +10 and Vapor +5 psig)
Cooling Operation
Outdoor Coil HPXB15-024 HPXB15-030 HPXB15-036 HPXB15-042 HPXB15-048 HPXB15-060
Entering Air
Temp. °F (°C) Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
65 (18.3) 252 131 233 141 216 136 240 133 228 137 231 124
75 (23.9) 291 133 272 142 276 138 281 135 265 139 269 126
85 (29.4) 337 135 314 143 298 139 325 137 304 141 315 127
95 (35.0) 371 140 360 146 359 141 372 138 348 142 370 133
105 (40.6) 421 142 413 148 400 143 428 142 405 145 415 136
Heating Operation
Outdoor Coil HPXB15-024 HPXB15-030 HPXB15-036 HPXB15-042 HPXB15-048 HPXB15-060
Entering Air
Temp. °F (°C) Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
20 (-6.6) 288 60 270 67 234 62 340 65 313 60 245 55
30 (-1.1) 306 75 297 84 257 80 350 72 330 73 287 66
40 (4.4) 325 90 325 100 318 93 353 83 346 87 332 82
50 (10.0) 344 105 353 117 322 103 358 101 366 101 347 99
Table 7
R410A Temperature/Pressure Chart
Temperature Pressure Temperature Pressure Temperature Pressure Temperature Pressure
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9
33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 195.5 93 286.5 124 440.2 155 645.0
Page 18
Theoutdoorunitandindoorblowercycleondemandfrom
theroomthermostat.Whenthethermostatblowerswitchis
intheONposition,theindoorbloweroperatescontinuously.
ThermostatOperation
Someoutdoorthermostatsincorporateisolatingcontacts
andanemergencyheatfunction(whichincludesanamber
indicatinglight).Thethermostatisnotincludedwiththeunit
andmustbepurchasedseparately,
EmergencyHeat(AmberLight)
Anemergencyheatfunctionisdesignedintosomeroomther-
mostats.Thisfeatureisapplicablewhenisolationoftheout-
doorunitisrequired,orwhenauxiliaryelectricheatisstaged
byoutdoorthermostats,Whentheroomthermostatisplaced
intheemergencyheatposition,theoutdoorunitcontroldrcuit
is isolatedfrompowerandfield-providedrelaysbypassthe
outdoorthermostats,Anamberindicatinglightsimultaneously
comesontoremindthehomeownerthatheisoperatinginthe
emergencyheatmode,
Emergencyheatis usuallyusedduringan outdoorunit
shutdown,butitshouldalsobeusedfollowinga powerout-
ageif powerhasbeenoffforoveranhourandtheoutdoor
temperatureisbelow50°F(10°C).Systemshouldbeleftin
theemergencyheatmodeatleastsixhoursto allowthe
crankcaseheatersufficienttimeto preventcompressor
slugging.
HighPressureSwitch
TheHPXB15isequippedwithanauto-resethighpressure
switchwhichis locatedon theliquidline.Thenormally
closedswitchopensthe compressorcircuitwhendis-
chargepressurerisesabove640+ 10psig(4412+ 69
kPa),Theswitchautomaticallycloseswhendischarge
pressurefallsbelow448+ 10psig(3089+ 69kPa),
FilterDrier
Theunitisequippedwitha large-capacitybifiowfilterdrier
whichkeepsthesystemcleananddry.If replacementis
necessary,orderanotheroflikedesignandcapacity.The
replacementfilterdriermustbesuitableforusewithR410A
refrigerant,
System Operation Monitor
The system operation monitor detects the most common
fault conditions in the air conditioning system,
When an abnormal condition is detected, the module com-
municates the specific condition through its ALERT and
TRIP lights. The monitor is capable of detecting both me-
chanical and electrical system problems, See figure 18 for
the system operation monitor
A, IMPORTANT
System Operation Monitor
LED
.y
"R
LED's
Figure 18
LED Functions
See table 8 for LED troubleshooting diagnostic codes.
Power LED (green) - indicates voltage within the range of
19-28VAC is present at the power connection of the monitor.
Alert LED (yellow) - communicates an abnormal system
condition through a unique flash code, The alert LED will
flash a number of times consecutively, pause and then re-
peat the process. The number of consecutive flashes, de-
fined as the Flash Code, correlates to a particular abnormal
condition,
Trip LED (red) - indicates there is a demand signal from the
thermostat but no current to the compressor is detected by
the module,
TRIP and ALERT LEDs flashing at the same time indicates
that the control circuit voltage is too low for operation.
Reset ALERT flash code by removing 24VAC power from
monitor. Last ALERT flash code will display for 1 minute af-
ter monitor is powered on,
Page 19
Table 8
System Operation Monitor LED Troubleshooting Codes
Status LED Status LED Description Status LED Troubleshooting Information
Green "Power" Module has power. 24MAC control power is present at the module terminal.
1 Compressor protector is open.
Thermostat demand signal 2 Outdoor unit power disconnect is open.
Y1 is present, but the com- 3 Compressor circuit breaker or fuse(s) is open.
Red "Trip" pressor is not running. 4 Broken wire or connector is not making contact.
5Low pressure switch open if present in the system.
6 Compressor contactor has failed to close.
Low refrigerant charge.
Yellow "Alert" 2Evaporator blower is not running.
Flash Code 1 Long Run Time 3Evaporator coil is frozen.
(Does not apply to heat Compressor is running ex- 4 Faulty metering device.
pump or to two-stage tremely long run cycles 5 Condenser coil is dirty
split systems) 6 Liquid line restriction (filter drier blocked if present)
7 Thermostat is malfunctioning.
System Pressure Trip _ High head pressure.
Yellow "Alert" Discharge or suction pres- 2 Condenser coil poor air circulation (dirty, blocked, damaged).
Flash Code 2 sure out of limits or 3Condenser fan is not running.
compressor overloaded 4 Return air duct has substantial leakage.
5 If low pressure switch is present, check Flash Code 1 information.
Short Cycling I Thermostat demand signal is intermittent.
Yellow "Alert" Compressor is 2 Time delay relay or control board is defective.
Flash Code 3 running 3If high pressure switch is present, check Flash Code 2 information.
only briefly 4 If low pressure switch is present, check Flash Code 1 information.
Yellow "Alert" _ Run capacitor has failed.
2 Low line voltage (contact utility if voltage at disconnect is low).
Flash Code 4 Locked Rotor 3 Excessive liquid refrigerant in the compressor.
4 Compressor bearings are seized.
Outdoor unit power disconnect is open.
2 Unit circuit breaker or fuse(s) is open.
Yellow "Alert" 3 Unit contactor has failed to close.
Flash Code 5 Open Circuit 4 High pressure switch is open and requires manual reset.
5 Open circuit in compressor supply wiring or connections.
6 Unusually long compressor protector reset time due to extreme ambient temperature.
7 Compressor windings are dama0ed.
Yellow "Alert" _ Run capacitor has failed.
Flash Code 6 Open Start Circuit 2 Open circuit in compressor start wiring or connections.
Current only in run circuit 3 Compressor start windinq is damaqed.
Yellow "Alert"
Flash Code 7 Open Run Circuit 1 Open circuit in compressor start wiring or connections.
Current only in start circuit 2Compressor start windinq is damaqed.
Yellow "Alert"
Flash Code 8 Welded Contactor I Compressor contactor failed to open.
Compressor always runs 2 Thermostat demand siqnal not connected to module.
Yellow "Alert" Low Voltage 1 Control circuit transformer is overloaded
Flash Code 9 Control circuit < 17VAC 2Low line volta qe (contact utility if volta qe at disconnect is low.)
• Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated.
• TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation.
• Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on.
The defrost system includes two components:
• a defrost thermostat
• a defrost control
Defrost Thermostat
The defrost thermostat is located on the liquid line be-
tween the check/expansion valve and the distributor.
When the defrost thermostat senses 42°F (5.5°C) or cool-
er, its contacts close and send a signal to the defrost con-
trol board to start the defrost timing. It also terminates de-
frost when the liquid line warms up to 70°F (21°C),
Defrost Control
The defrost control board includes the combined func-
tions of a time/temperature defrost control, defrost
relay, time delay, diagnostic LEDs, and a terminal strip
for field wiring connections, See figure 19.
The control provides automatic switching from normal
heating operation to defrost mode and back. During com-
pressor cycle (call for defrost), the control accumulates
compressor run times at 30, 60, or 90 minute field adjust-
able intervals. If the defrost thermostat is closed when the
selected compressor run time interval ends, the defrost
relay is energized and defrost begins,
Page 20
DefrostControlTimingPins
Eachtimingpinselectionprovidesa differentaccumu-
latedcompressorruntimeperiodduringonethermostat
runcycle.Thistimeperiodmustoccurbeforea defrost
cycleisinitiated.Thedefrostintervalcanbeadjustedto
30(T1),60(T2),or90(T3)minutes.Seefigure19,The
defrosttimingjumperis factory-installedto providea
90-minutedefrostinterval.Ifthetimingselectorjumperis
notinplace,thecontroldefaultstoa 90-minutedefrost
interval,Themaximumdefrostperiodis 14minutesand
cannotbeadjusted,
A TESToptionisprovidedfortroubleshooting,TheTEST
modemaybestartedanytimetheunitis intheheating
modeandthe defrostthermostatis closedor jump-
ered.IfthejumperisintheTESTpositionatpower-up,the
controlwillignorethetestpins,Whenthejumperisplaced
acrosstheTESTpinsfortwoseconds,thecontrolwillenter
thedefrostmode,Ifthejumperisremovedbeforeanaddi-
tional5-secondperiodhaselapsed(7secondstotal),the
unitwillremainindefrostmodeuntilthedefrostthermostat
opensor14minuteshavepassed.Ifthejumperisnotre-
moveduntil after the additional5-secondperiodhas
elapsed,thedefrostwillterminateandthetestoptionwill
notfunctionagainuntilthejumperis removedandreap-
plied,
CompressorDelay
The defrost board has a built-in function to reduce occasion-
al sounds that may occur while the unit is cycling in and out
of the defrost mode, The compressor will be cycled off for 30
seconds going in and out of the defrost mode.
NOTE -The 30 second off cycle is not functional when jump-
ering the TEST pins.
Time Delay
The timed-off delay is five minutes long. The delay helps
protect the compressor from short-cycling in case the power
to the unit is interrupted or a pressure switch opens, The
delay is bypassed by placing the timer select jumper across
the TEST pins for 0,5 seconds.
Pressure Switch Circuits
The defrost control includes two pressure switch circuits.
The high pressure switch ($4) is factory-connected to the
board's HI PS terminals. The board also includes LOPS ter-
minals to accommodate the addition of a field-provided low
pressure or loss of charge pressure switch, See figure 19.
This feature is available on all units,
During a single demand cycle, the defrost control will lock
out the unit after the fifth time that the circuit is interrupted
by any pressure switch that is wired to the control board. In
addition, the diagnostic LEDs will indicate a locked out
pressure switch after the fifth occurrence of an open pres-
sure switch, See table 9. The unit will remain locked out un-
til power is broken then remade to the control or until the
jumper is applied to the TEST pins for 0.5 seconds,
NOTE -The defrost control board ignores input from the
low pressure switch terminals during the TEST mode, dur-
ing the defrost cycle, during the 90-second start-up period,
and for the first 90 seconds each time the reversing valve
switches heat/cool modes. If the TEST pins are jumpered
and the 5-minute delay is being bypassed, the LOPS
terminal signal is not ignored during the 90-second
start-up period.
Ambient Thermistor & Service Light Connection
The defrost control board provides terminal connections
for the ambient thermistor and a service light. The thermis-
tor compensates for changes in ambient temperature
which might cause thermostat droop, The service light
thermostat provides a signal which activates the room ther-
mostat service light during periods of inefficient operation,
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics, The
LEDs flash a specific sequence according to the diagnosis,
Table 9
Defrost Control Board Diagnostic
Mode
Normal operation /
power to board
Board failure or no
power
Board failure
High pressure switch
open
Low pressure switch open
Pressure switch lockout
Anti-short-cycle /
5-minute delay
LED 1
Synchronized
Flash with LED
z
Off
On
Flash
On
On
Alternating
Flash with
IFD2
LED
LED 2
Synchronized
Flash with LED
I
Off
On
On
Flash
Off
Alternating
Flash with
IFD1
Page 21
Pressure Switch
Wiring Connections
High
Pressure
Switch
(Factory-wired)
S _
[] HI PS
Optional
Pressure
Switch
(Field-provided
and installed --
jumper removed)
LO PS
High Pressure
Switch
Terminals
Optional
Pressure Switch
Terminals
(Remove factory-
installed jumper
to install
pressure switch.)
Defro_
Thermostat
Reversing
Valve
Defrost Control Board
=O
U ===Wl
K2 RELAY] 0
FAN
HOT I
DEFROST K3 RELAY
INTERVAL
TIMING PINS
L0-PS
D,A NOST,°
LEDs
OTST
O-0UT o PS_
oDF
oC
oR
o 0 HOT
O o YI
Service
Light
Terminals
Ambient
Thermistor
Terminals
24V
Terminal
Strip
Figure
AWARNING
Maintenance and service must be performed by a quali-
fied installer or service agency. At the beginning of each
cooling or heating season, the system should be checked
as follows:
Outdoor Unit
1 - Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2 - Outdoor unit fan motor is prelubricated and sealed. No
further lubrication is needed.
3 - Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4 - Check all wiring for loose connections.
5 - Check for correct voltage at unit (unit operating).
19
6 - Check amp-draw on outdoor fan motor.
7- Inspect drain holes in coil compartment base and
clean if necessary.
NOTE -If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer to
section on refrigerant charging in this instruction.
Indoor Coil
1 - Clean coil if necessary.
2 - Check connecting lines, joints and coil for evidence of
oil leaks.
3 - Check condensate line and clean if necessary.
Indoor Unit
1 - Clean or change filters,
2 - Lennox blower motors are prelubricated and permanent-
ly sealed, No more lubrication is needed.
3 - Adjust blower speed for cooling, Measure the pressure
drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure,
4 - Belt Drive Blowers - Check belt for wear and proper
tension,
5 - Check all wiring for loose connections,
6 - Check for correct voltage at unit,
Page 22
7- Checkamp-drawonblowermotor.
RefertotheEngineeringHandbookforoptionalaccesso-
riesthatmayapplytothisunit,Thefollowingmayormay
notapply:
• Lossof ChargeKit
• HighPressureSwitcKit
• CompressorMonitor
• CompressorCrankcaseHeater
• HailGuards
• MountingBases
• TimedOffControl
• Stand-offKit
• SoundCover
• LowAmbientKit
• MonitorKit
Inordertoensurepeakperformance,yoursystemmustbe
properlymaintained.Cloggedfiltersandblockedairflow
preventyourunitfromoperatingat itsmostefficientlevel,
AskyourLennoxdealerto showyouwhereyourindoor
unit'sfilteris located.It will beeitherat theindoorunit
(installedinternalorexternalto thecabinet)orbehindare-
turnairgrilleinthewallorceiling.Checkthefiltermonthly
andcleanorreplaceitasneeded,
Disposablefiltersshouldbereplacedwitha filterof the
sametypeandsize,Ifyouareunsureaboutthefilteryou
needforyoursystem,callyourLennoxdealerfor assis-
tance.
AIMPORTANT
Many indoor units are equipped with reusable foam filters.
These filters can be cleaned with a mild soap and water
solution, Rinse the filter thoroughly and let it dry completely
before it is returned to the unit or grille,
The filter and all access panels must be in place any
time the unit is in operation.
Your system may be equipped with an electronic air clean-
er which will provide respiratory relief by removing up to 90
percent of all airborne particles which pass through it. If it
is, ask your dealer to instruct you on its maintenance,
Your indoor evaporator coil is equipped with a drain pan to
collect condensate formed as your system removes hu-
midity from the inside air. Have your dealer show you where
the main condensate drain (and auxiliary drain, if applica-
ble) runs and how to check the drain for any obstruction,
It is also very important to provide unrestricted airflow to the
outdoor unit, Leaves, trash or shrubs crowding the unit
cause the outdoor unit to work harder and use more ener-
gy. Keep shrubbery trimmed away from the unit and period-
ically check for debris which may have collected around
the unit,
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
Your heat pump satisfies heating demand by delivering
large amounts of warm air into the living space. This is quite
different from gas- or oil-fired furnaces or an electric fur-
nace which deliver lower volumes of considerably hotter air
to heat the space,
Do not be alarmed if you notice frost on the outdoor coil in
the winter months. Frost develops on the outdoor coil dur-
ing the heating cycle when temperatures are below 45°F
(7°C). An electronic control activates a defrost cycle lasting
5 to 15 minutes at preset intervals to clear the outdoor coil
of the frost. During the defrost cycle, you may notice steam
rising from the outdoor unit, This is a normal occurrence.
The thermostat may engage auxiliary heat during the de-
frost cycle to satisfy a heating demand; however, the unit
will return to normal operation at the conclusion of the de-
frost cycle.
Your Lennox HPXB15 heat pump is equipped with a com-
pressor crankcase heater which protects the compressor
from refrigerant slugging during cold weather operation. If
power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the "Emergen-
cy Heat" setting to obtain temporary heat without the risk
of serious equipment damage, In this operating mode, all
heating demand will be satisfied by auxiliary heat. Com-
pressor operation is locked out during Emergency Heat op-
eration. After a six-hour compressor crankcase heater
warm-up period, the thermostat can be switched to the
"Heat" setting and normal operation will resume.
Thermostat Operation
Though your thermostat may vary somewhat from the de-
scription below, its operation will be similar,
Temperature Setting Levers
Most heat pump thermostats have two temperature selec-
tor levers: one for heating and one for cooling, Set the lev-
ers or dials to the desired temperature setpoints for both
heating and cooling. Avoid frequent temperature adjust-
ment; turning the unit off and back on before pressures
equalize puts stress on the unit compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates
only when the thermostat calls for heating or cooling. This
mode is generally preferred when humidity control is a
priority. The ON or CONT mode provides continuous in-
door blower operation, regardless of whether the compres-
sor or auxiliary heat are operating, This mode is required
when constant air circulation or filtering is desired.
Page 23
System Switch
Set the system switch for heating, cooling or auto opera-
tion, The auto mode allows the heat pump to automatically
switch from heating mode to cooling mode to maintain pre-
determined comfort settings, Many heat pump thermostats
are also equipped with an emergency heat mode which
locks out heat pump operation and provides temporary
heat supplied by the auxiliary heat,
Indicating Light
Most heat pump thermostats have an amber light which in-
dicates when the heat pump is operating in the emergency
heat mode.
Temperature Indicator
The temperature indicator displays the actual room tem-
perature,
Programmable Thermostats
Your Lennox system may be controlled by a programmable
thermostat. These thermostats provide the added feature
of programmable time-of-day setpoints for both heating
and cooling, Refer to the user's information manual pro-
vided with your particular thermostat for operation details.
Preservice Check
If your system fails to operate, check the following before
calling for service:
• Check to see that all electrical disconnect switches
are ON,
• Make sure the room thermostat temperature selector
is properly set,
• Make sure the room thermostat system switch is prop-
erly set.
• Replace any blown fuses, or reset circuit breakers.
• Make sure unit access panels are in place.
• Make sure air filter is clean,
• Locate unit model number and have it handy before
calling,
Start-up and Performance Check List
Job Name Job No, Date
Job Location City State
Installer City State
Unit Model No, Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? []
Indoor Blower RPM
Cooling
Liquid Line Pressure
Heating
Liquid Line Pressure
Refrigerant Lines: Leak Checked? []
Service Valves Fully Opened? []
Sequence of Operation
Heating Correct []
Compressor
Indoor Filter Clean? []
S.R Drop Over Indoor (Dry)
Vapor Pressure
Outdoor Fan
Supply Voltage (Unit Off) __
-- Outdoor Coil Entering Air Temp.
Vapor Pressure
Properly Insulated? []
Service Valve Caps Tight? []
Refrigerant Charge Checked? []
Refrigerant Charge Checked? []
Outdoor Fan Checked? []
Cooling Correct []
Voltage With Compressor Operating --
Thermostat
Calibrated? [] Properly Set? [] Level? []
Page 24