LENNOX Air Conditioner/heat Pump(outside Unit) Manual L0806500
User Manual: LENNOX LENNOX Air conditioner/heat pump(outside unit) Manual LENNOX Air conditioner/heat pump(outside unit) Owner's Manual, LENNOX Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 28
Download | |
Open PDF In Browser | View PDF |
,?c 2008 lennox INSTALLATION INSTRUCTIONS ' ' • Industr_es Inc Datias, Texas, USA S'ClassTM SPB*H4 Units SPB036H4S41, SPB060H4S41 HEAT PUMPS 505,330M SPB048H4S41 and _ Technical LLL[ Publications 02/08 Litho U.S.A. Supersedes 06/07 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Xk WARNING CAUTION IMPORTANT Shipping and Packing List ...................... SPB*H4 Outdoor Unit .......................... Unit Dimensions .............................. General Information ........................... Recovering Refrigerant from Existing System ..... Removing Existing Outdoor Unit ................. Positioning New Outdoor Unit ................... Removing and Installing Panels ................. New or Replacement Line Set ................... Brazing Connections ........................... Removing Indoor Unit Metering Device ........... Flushing the System ........................... Installing New Indoor Unit Metering Device ........ Testing for Leaks .............................. Evacuating the System ......................... Servicing Unit Delivered Void of Charge ........... Electrical Connections ......................... Start-Up and Charging Procedures ............... System Operation ............................. Defrost System ............................... Maintenance .................................. Optional Accessories .......................... Owner Information ............................. Thermostat Operation .......................... Start-Up and Performance Checklist ............. Check unit for shipping damage. Consult immediately if damage is found. 1 -Assembled SPB*H4 outdoor unit IMPORTANT 1 1 2 3 5 6 6 7 9 10 11 12 13 13 15 16 16 18 21 21 26 26 27 28 28 last carrier The SPB*H4 Heat Pumps, which will also be referred to in this instruction as the outdoor unit, uses HFC-410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox SPB*H4 Engineering Handbook. This outdoor unit is designed for use in systems that use check thermal expansion valve (CTXV) refrigerant metering devices. 02/08 IIIHIIIIIIIIIIIHIIIIIIIIIIIIIIIIII Page 1 505,330M IIIIIIIIIIIIIIIIIIIIIIIII RUN CAPACITOR OUTDOORFAN CONTACTOR COMPRESSOR REVERSING VALVE SUCTION LINE • CONNECTION LIQUID LINE CONNECTION DEFROST BOARD HIGH PRESSURE SWITCH FILTER DRIER/ LIQUID LINE CONNECTIONS VAPOR LINE VAPOR VALVE AND GAUGE PORT/SUCTION LINE CONNECTIONS TOP VIEW SPB*H4 PARTS ARRANGEMENT C DISCHARGE AIR t i: D ° :j LIQUID LINE -_ --CONNECTION ELECTRICAL INLETS /V VAPORLINE JCONNECTION 2 (51) i i SIDE VIEW 4_1/4(1 08) 4_8/4 (121) t t \ 1 (25) I I i i SIDE VIEW -T 0N'TSUPPORTFEET\ O __F 13-7/8 (352) @ @ @ 20-5/8 (524) 1 7-3/4 (197) 4-1/2 l (114) --T 3-1/4 (83) 3-5/8 (689) (92) BASE WITH ELONGATED B C D LEGS Model A E F SPB*H4-036 35 (889) 30-1/2 (775) 35 (889) 17-5/8 (448) 8-3/4 (222) 18 (457) SPB*H4-048 45 (1143) 30-1/2 (775) 35 (889) 27-5/8 (702) 8-3/4 (222) 18 (457) 9 (229) 11-1/2 (292) 9 (229) 11-1/2 (292) SPB*H4-060 39 (991) 30-1/2 (775) 35 (889) 27-5/8 (702) 11 (222) 18 (457) 10-1/2 (267) 13-1/2 (343) 10-1/2 (267) 13-1/2 (343) Page 2 505330M 02/08 G 9 (229) H I J 8-1/2 (216) 9 (229) 11-1/2 (292) OPERATING SERVICE VALVES The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging, WARNING Each valve is equipped with a service port which has a factory-installed valve stem. IMPORTANT 1/12 TURN I/6 TURN These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation. 9 8 When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners. Table 1. Torque Requirements Parts Recommended Service valve cap 8 ft.- lb. 11 NM Sheet metal screws 16 in.- lb. 2 NM Machine screws #10 28 in.- lb. 3 NM Compressor bolts 90 in.- lb. 10 NM Gauge port seal cap 8 ft.- lb. 11 NM 4 Figure 1 Cap Tightening Torque Distances IMPORTANT To Access Angle-Type Service Port: A service port cap protects the service port core from contamination and serves as the primary leak seal, USING MANIFOLD GAUGE SETS When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings. See figure 2 for a typical manifold gauge connection setup, 1. Remove service port cap with an appropriately sized wrench. Manifold gauge sets used with HFC-410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating, 3. When testing is completed, replace service port cap and tighten as follows: • With Torque Wrench: Finger tighten and then tighten per table 1, • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1. 2. Connect gauge to the service port, Page 3 SPB*H4 SERIES DISTRIBUTOR CBECK EXPANSION VALVE REV S' :UV E _ \ NOTE - ARROWS OF REFRIGERANT LOW PRESSURE DR,ER O% tOR HIGH INDICATE FLOW. DIRECTION "- MUFFLER PRESSURE ___ ;g2 INDOOR UNIT ] ° V'A;°2 _ CHECK EXPANSION VALVE -INDOOR COIL Figure 2. Typical Manifold Gauge Connection Setup To Open and CloseAngle-TypeService Valve: A valve stem cap protects the valve stem contamination and assures a leak-free seal. from NOTE- To prevent stripping of the cap, the wrench should be appropriately sized and fit snugly over the cap before tightening the cap. 1. Remove stem cap with an appropriately sized wrench. 2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes and 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go. 3. Replace the stem cap and tighten as follows: • With Torque Wrench: Tighten finger tight and then tighten per table 1. • Without Torque Wrench: Finger tighten and use an appropriately sized wrenched to turn an additional 1/12 turn clockwise as illustrated in figure 1. SERVICE SERVICE SERVICE PORT /" _ //_/_ _ _ SERVICE (VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE STEM CAP CLOSED) WRENCH INSERT HEX HERE UNIT Figure 4. Angle-Type Service Valve (Back-Seated Opened) (VALVE STEM SBOWN To Access Bali-Type Service Port: A service port cap protects the service port core from contamination and serves as the primary leak seal. 1. Remove service port cap with an appropriately sized wrench. TO INDOOR UNIT UNIT J J 2. Connect gauge to the service port. 3. When testing is completed, replace service port cap and tighten as follows: CLOSED TO BOTH INDOOR AND OUTDOOR UNITS Figure 3. Angle-Type Service Valve (Font-Seated Closed) NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque. Page 4 02/08 PORT TO INDOOR UNIT PORT FRONT-SEATED 505330M SERVICE AND UNITS TO OUTDOOR CORE TO OUTDOOR PORT CORE PORT _L_ I CAP OPEN TO BOTH INDOOR OUTDOOR CAP_-_ SERVICE PORT • With Torque Wrench: tighten per table 1. Finger tighten and then • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1. TO INDOOR UNIT RECOVERY OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN. TO OPEN ROTATE STEM COUNTERCLOCKWISE 90° . MACHINE MANIFOLD GAUGES BALL (SHOWN CLOSED) TO CLOSE ROTATE STEM CLOCKWISE 90 ° . VALVE STEM CORE SERVICE PORT / CAP OUTDOOR TO OUTDOOR STEM UNIT CAP Figure 6. Typical Refrigerant Recovery (Method 1) Figure 5. Bali-Type Service Valve To Open and Close Bali-TypeService Valve: A valve stem cap protects the valve stem contamination and assures a leak-free seal. from 1. Remove stem cap with an appropriately sized wrench. 2. Use an appropriately sized wrenched to open. To open valve, roate stem counterclockwise 90 °, To close rotate stem clockwise 90 °. 3. Replace the stem cap and tighten as follows: • With Torque Wrench: tighten per table 1. Finger tighten and then • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 1. NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque. NOTE - Use recovery machine instructions for specific setup requirements. METHOD 2: Use this method if the existing outdoor unit is equipped with manual shut-off valves, and plan on using new HCFC-22 refrigerant to flush the system. IMPORTANT: Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning: The following devices could prevent full system charge recovery into the outdoor unit: • Outdoor unit's high or low-pressure switches (if applicable) when tripped can cycled the compressor OFF. • Compressor can stop pumping due to tripped internal pressure relief valve. • Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals). Remove existing HCFC-22 refrigerant using one of the following procedures: METHOD 1 : If the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational and you plan to use the existing HCFC-22 to flush the system. NOTE - Use recovery machine instructions setup requirements. UNIT for specific Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set. Perform the following task: 1. Disconnect all power to the existing outdoor unit. 2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recovery machine on how to setup the connections. 3. Remove all HCFC-22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant. 1. Start the existing HCFC-22 system in the cooling mode and close the liquid line valve. 2. Pump as much of the existing HCFC-22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system. Page 5 SPB*H4 SERIES POSITIONING CONSIDERATIONS Consider the following when positioning the unit: NOTE - It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation. 3, When the low side system pressures reach 0 psig, close the suction line valve, • 4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission, For proper placement of unit in relation to a window see the provided illustration in figure 8, Perform the following task at the existing outdoor unit: • Disconnect line set at the service valves, • Disconnect electrical service at the disconnect switch, • Remove old outdoor unit, Some localities are adopting sound ordinances based on the unit's sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line, ,NSTALL UN,T AWAY FROM II -- CAUTION See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports, Refer to figure 7 for mandatory installation clearance requirements, CONTROL PANEL ACCESS LOCATION Figure 8. Outside Unit Placement PLACING UNIT ON SLAB When installing unit at grade level, the top of the should be high enough above grade so that water higher ground will not collect around the unit. The should have a slope tolerance as described in figure * SEE NOTES BELOW THIS FIGURE FOR FURTHER slab from slab 9, NOTE - If necessary for stability, anchor un# to slab as described in Stabilizing Unit on Uneven Surfaces on page 7, DETAILS. Figure 7. Installation Clearances INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [80 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE. NOTES: • Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box. • Clearance to one of the other three sides must be 36 in. (914 mm). • __L J Clearance to one of the remaining two sides may be 12 in, (305 mm) and the final side may be 6 in, (152 mm)" • 48 in. (1219 mm) clearance required on top of unit. • A clearance of 24 in, (610 mm) must be maintained between two units. 02/08 _ iT Z- . • _ I !_' .m.._l,..._:__--L- Figure 9. Slab Mounting at Ground Level Page 6 505330M BUILDING STRUCTURE ELEVATING THEUNIT Unlikethesmall-base unitswhichuseroundsupportfeet, thelarger-baseunitsareoutfittedwithelongatedsupport feetasillustratedinfigure10whichusesasimilarmethod for elevatingthe unit, If additionalelevationis necessary,raisethe unit by extendingthelengthoftheunitsupportfeet.Thismaybe achievedbyusinga2"SCH40femalethreadedadapter, Thespecifiedcouplingwillfit snugglyintothe recessed portionofthefeet,Useadditional 2"SCH40malethreaded adaptorswhichcanbethreadedintothefemalethreaded adaptorstomakeadditionaladjustments tothelevelofthe unit, NOTE - Keep the height of extenders short enough to ensure a sturdy installation, If it is necessary to extend further, consider a different type of field-fabricated framework that is sturdy enough for greater heights, BASE CAUTION REMOVING PANELS Remove the Iouvered panels as follows: 1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 11, NOTE - Hold the panel firmly throughout this procedure 2. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated in figure 11, detail B. 3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 11, detail A. INSTALLING PANEL Install the Iouvered panels as follows: LEG DETAIL 1. Position the panel almost parallel with the unit as illustrated in figure 12, detail D with the screw side as close to the unit as possible. 2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER 2. With a continuous motion slightly rotate and guide the lip of top tab inward as illustrated in figure 11, details A and C, then upward into the top slot of the hinge corner post. Figure 10. Elevated Slab Mounting using Feet Extenders (Larger Base Units) 3, Rotate panel to vertical to fully engage all tabs, ROOF MOUNTING Install unit at a minimum of four inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended, 4. Holding the panel's hinged side firmly in place, close the right-hand side of the panel, aligning the screw holes. 5. When panel is correctly positioned and aligned, insert the screws and tighten. Page 7 SPB*H4 SERIES PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TOEXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL. LIP STABILIZING UNIT ON UNEVEN SURFACES To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace, Slab Side Mounting DETAIL A / DETAIL B ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL -- DETAIL C Mounting IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL. STABILIZING (18 GAUGE BRACKET METAL2" MINIMUM 1 PER SIDE _ REOD,;BENDTOFORM WIDTH; HEIGHT AS Deck Top Figure 11. Removing/Installing Louvered Panels (Details A, B and C) FOR EXTRA STABILITY ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER. MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE AS POSSIBLE) WHILE INSTALLING PANEL. TO PARALLEL HOLD DOOR X% M AYBE TOO PREFERRED ANGLE WITH THE UNIT Figure 13. Installing Stabilizer FIRMLY TO THE HINGED Brackets __-------__ FOL , %O E NTAT ,,S "__ FOR,NSTALLAT,ON With unit positioned at installation site, remove two side Iouvered panels to expose the unit base pan. Install the brackets as illustrated in figures 11 and 12 using conventional practices; replace the panels after installation is complete. A IMPORTANT Figure 12. Removing/Installing Panels (Detail D) Louvered Page 8 505330M 02/08 This section providesinformationon installationor replacement of existinglineset.If linesetarenot being installed thenproceed to Brazing Connections on page 10. replaced prior to the installation of the SPB*H4 unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper. INSTALLING LINE SET If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings, floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. Also, consider the following when placing and installing a high-efficiency air conditioner. Line Set procedures, isolation: REFRIGERANT LINE SET Isolation--This reference illustrates which ensure proper refrigerant line set • Installation of a transition from vertical is illustrated in figure 14. • Installation of line set illustrated in figure 15, • Installation of line set on vertical runs is illustrated in figure 16. Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or sweat connections). Use Lennox L15 (sweat, non-flare) series line set, or use field-fabricated refrigerant lines as listed in table 2. ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE MUFFLER-TYPE HANGER on horizontal horizontal to runs AUTOMOTIVE MUFFLER-TYPE HANGER \ \ Table 2. Refrigerant Line Set Field Connections Model -018 -024, -036 -048 -060 Recommended Liquid Line Suction Line Liquid Line Suction Line 3/8". (10 ram) 7/8" (22 ram) 3/8" (10 ram) 7/8" (22 ram) 3/8". (10 ram) 1-1/8". (29 ram) 3/8" (10 ram) 1-1/8" (29 ram) Line Set WALL STUD L15 Line Set L15-65 15 ft, - 50 ft, (4.6 m - 15 m) Field Fabricated X STRAP LIQUID LINE TO SUCTION LINE LIQUID LINE METAL SLEEVE kk SUCTION LINE - WRAPPED IN ARMAFLEX NOTE - When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points: • Model (SPB*H4) and size of unit (e.g. -060). • Line set diameters for the unit being installed as listed in table 2 and total length of installation, Figure 14. Refrigerant Line Set: Transition from Vertical to Horizontal WIRE TIE (AROUND SUCTION LINE ONLY) STRAPPING MATERIAL (AROUND SUCTION LINE ONLY) 8 FEET • TAPE OR WIRE TIE Number of elbows and if there is a rise or drop of the piping. STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET METAL SLEEVE The RFCl-metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit, If the SPB*H4 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be TAPE OR WIRE TIE ____'"'"'",',',11 TO HANG LINE SET FROM MATERIAL OR ANCHORED INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE. /\ /\ I HI JOIST OR RAFTER, USE EITHER METAL HEAVY NYLON WIRE TIES. I,,,l STRAPPING Figure 15. Refrigerant Line Set: Installing Horizontal Runs Page 9 SPB*H4 SERIES is IMPORTANT _REFRIGERANT LINES MUST NOT CONTACT WALL. LIQUID LINE OUTSIDE WALL SUCTION LINE Use the following procedure to braze the line set to the new air conditioner unit. Figure 17 is provided as a general guide for preparing to braze the line set to the air conditioner unit. ,WARNING SLEEVE WIRE TIE WOOD BLOCK STRAP WARNING SUCTION LINE WRAPPED WITH ARMAFLEX LIQUID LINE WARNING Figure 16. Refrigerant Line Set: Installing Vertical Runs (New Construction Shown) REMOVE CAP AND CORE FROM BOTH LIQUID AND SUCTION SERVICE PORTS CUT AND DEBUR SERVICE PORT MUST BE OPEN TO ALLOW EXIT POINT FOR NITROGEN INDOOR SERVICE VALVE outdoor UNIT UNIT LIQUtD LINE SERVICEJ VALVE FLOW NITROGEN A SER INSTALL CORE ONLY FOR 3OTH SERVICE PORTS after they have coolED. VALVE Figure 17. Brazing Connections Page 10 505330M 02/08 :RAP 1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends, The pipe must remain round, do not pinch end of the line. • 10 -- Liquid line orifice housings • 10 -- Liquid line assemblies 2. Remove service cap and core from both the suction and liquid line service ports. LIQUID LINE ORIFICE 3. Connect gauge low pressure side to liquid line service valve, / 4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint, Also, shield the light maroon R-410A sticker. 5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve. NOTE- The RFClV or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system,) NOTE - Use silver alloy brazing rods with five or six percent minimum silver afloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper-to-steel brazing. 6. Braze the liquid line to the liquid line service valve, Turn off nitrogen flow. Repeat procedure starting at paragraph 4 for brazing the suction line to the suction service valve. HOUSINGS BRASS (10) NUTS (10) UQU,D L,NE ASSEMBL,ES " (INCLUDES STRAINER) PISTON RETAINER / (10) _j_ .J __C%ER LIQUID LINE ASSEMBLY Figure 18. 69J46 Kit Components TYPICAL FIXED ORIFICE REMOVAL PROCEDURE 1. On fully cased coils, remove the coil access and plumbing panels. 2. Remove any shipping clamps holding the liquid line and distributor assembly, 3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process. 4. Remove and discard fixed orifice, valve stem assembly if present and Teflon washer as illustrated in figure 19. 5. Use a field-provided fitting to temporary reconnect the liquid line to the indoor unit's liquid line orifice housing, 7. After all connections have been brazed, disconnect manifold gauge set the from service ports and remove wrapping. Reinstall the service port core for both of the outdoor unit's service valves. DISTRIBUTOR TUBES LIQUID LINE ORIFICE TEFLON HOUSING RING FIXED Remove and discard slem assembly valve (if present) /ORIFICE/ "" " " Remove the existing HCFC-22 refrigerant flow control orifice or thermal expansion valve from the indoor coil. The existing indoor unit HCFC-22 metering device is not approved for use with HFC-410A refrigerant and may prevent proper flushing, DISTRIBUTO"R " " - " • _ NUT _ " " " ASSEMBL___X_ REPLACEMENT BRASS / LIQUID LINE ASSEMBLY PARTS (INCLUDES If replacement parts are necessary for the indoor unit, order kit 69J46, The kit includes: • 10 -- Brass nuts for liquid line assemblies • 20 -- Teflon rings STRAINER) VA VALVE STEM CAP (Uncased Coil Shown) Figure 19. Typical Fixed Orifice Removal Page 11 SPB*H4 SERIES TYPICAL TXV/CTXV REMOVAL PROCEDURE CAUTION 1, On fully cased coils, remove the coil access and plumbing panels, 2, Remove any shipping clamps holding the liquid line and distributor assembly. A IMPORTANT 3. Disconnect the equalizer line from the TXV/CTXV equalizer line fitting on the suction line. (Uncased Coil Shown) TWO PIECE PATCH PLATE UNCASED COIL ONLY) LIQUID LINE STUB END ORIFICE HOUSING TXV/CTXV DISTRIBUTOR TUBES RING SENSING LINE IMPORTANT LINEEQUALIZER FITTING MALE / SENSING SUCTION LINE BULB LIQUID LINE If the original system used: Figure 20. Typical TXV/CTXV Removal 4, Remove the suction line sensing bulb. • HCFC-22 refrigerant, then flush the system using the procedure provided in this section. • HFC-410A refrigerant, then proceed to Installing New Refrigerant Metering Device, 5, Disconnect the liquid line from the TXV/CTXV at the liquid line assembly, 6, Disconnect the TXV/CTXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process, 7, Remove and discard TXV/CTXV and the two Teflon rings, 8, Use a field-provided fitting to temporary reconnect the liquid line to the indoor unit's liquid line orifice housing, IMPORTANT RECOVERY MACHINE NOTE - THE INVERTED HCFC-22 CYLINDER MUST CONTAIN AT LEAST THE SAME AMOUNT OF REFRIGERANT AS WAS RECOVERED FROM THE EXISTING SYSTEM, Figure 21. Typical Flushing Connection Page 12 505330M 02/08 REQUIRED EQUIPMENT Equipment required to flush the existing line set and indoor unit coil: • Two clean HCFC-22 recovery bottles, • Oilless recovery machine with pump-down feature, • Two gauge sets (one HFC-410A). FLUSHING PROCEDURE 1. Connect the following: for HCFC-22; one 1 -- 1 1/4" wide copper mounting strap for sensing bulb 2 --#10 hex head bolts and nuts for securing sensing bulb for AND NUTS (2) O_TEFLON • HCFC-22 cylinder with clean refrigerant to the suction service valve, • HCFC-22 gauge set to the liquid line valve, Recovery machine with an empty recovery tank to the gauge set, 2. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil. 3. Invert the cylinder of clean HCFC-22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve, Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine. RINGS (2) _ff J • 4. After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC-22 suction is recovered. Allow the recovery machine to pull a vacuum on the system, 5. Close the valve on the inverted HCFC-22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off. _ STRAP (1) Figure 23. CTXV Kit Components TYPICAL CTXV INSTALLATION PROCEDURE The CTXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the CTXV in a manner that will provide access for field servicing of the CTXV, Refer to Figure 24 for reference during installation of CTXV unit, TWO PIECE PATCH PLATE (UNCASED COIL ONLY) DISTRIBUTOR TUBES. - - (Uncased Coil Shown) LIQUID LINE _ OUSING _RIFICE CTXV STUB END .. RING SENSING LINE SPB*H4 units use CTXVfor metering refrigerant only. This section provides instructions on installing CTXV refrigerant metering device. I/2 TURN MALE EQUALIZER LiNE FITTING (SEE FIGURE 26 FOR FURTHER DETAILS) LINE LIQUID LINE SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING SEE FIGURE 25 FOR BULB POSITIONING. Figure 22. Tightening Distance SPB*H4 ENGINEERING HANDBOOK See the SPB*H4 Engineering Handbook for approved indoor/outdoor match-ups, applicable CTXV kits and application information, Figure 24. Typical CTXV Installation 1, Remove the field-provided fitting that temporary reconnected the liquid line to the indoor unit's distributor assembly. 2. Install one of the provided Teflon rings around the stubbed end of the CTXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil, The following is the typical contents of a CTXV kit: 1 -- CTXV 2 -- Teflon rings Page13 SPB*H4 SERIES 3. Attach the stubbed end of the CTXV to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 22, or 20 ft-lb. FLARE SEAL CAP ÷ I I 4. Place the remaining Teflon washer around the other end of the CTXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil. __ I"II_ Figure 26. Copper f BULBt SUCTION LINES SMALLER LINE FITTING SUCTION LINE Flare Seal Bonnet Removal NOTE - To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures. THAN 7#, CKPOSITION After the line set has been con nected to the indoor unit and air conditioner, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks: IMPORTANT LINE ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O'CLOCK BOTTOM P__SITION. OF LINE. NEVER WARNING MOUNT Figure 25. TXV Sensing Bulb Installation 7. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 26. A IMPORTANT Page 14 505330M 02/08 EQUALIZER 8. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated in figure 22. NOTE - Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing. ON MALE BRASS _ 6. Attach the suction line sensing bulb in the proper orientation as illustrated in figure 25 using the clamp and screws provided. FLARE SEAL COPPER BONNET J -- SUCT,ON L,NE -- X V_ I 5. Attach the liquid line assembly to the CTXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 22, or 20 ftqb. FLARE NUT AWARNING ,WARNING Xk WARNING ,& IMPORTANT 1. Connect manifold gauge set to the service valve ports as follows: 1. Connect an HFC-410A manifold gauge set high pressure hose to the suction valve service port. (Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage,) 4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set, 5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit, 6. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector. 7. After leak testing disconnect ports. gauges from service low pressure gauge to suction line service valve • high pressure gauge to liquid line service valve 2. Connect micron gauge. 3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set, 4. Open both manifold valves and start the vacuum pump. 5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29,01 inches of mercury), 2. With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (suction only), 3. Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit, Weigh in a trace amount of HFC-410A, [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure], Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set, Disconnect the HFC-410A cylinder, • NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak, If this occurs, repeat the leak testing procedure. NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure. 6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves. 7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit. Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts. 8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves. 9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the Page15 SPB*H4 SERIES vacuum pump and connect it to an upright cylinder of HFC-410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit. Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 10. Close manifold gauge valves and shut off the HFC-410A cylinder and remove the manifold gauge set. 24VAC TRANSFORMER Use the transformer provided with the furnace or coil blower for low-voltage control power (24VAC - 40 VA minimum) If the system is void of refrigerant, clean the system using the procedure described below. NOTE - The addition of accessories to the system could exceed the 40VAC power requirement of the factory-provided transformer. Measure the system's current and voltage after installation is complete to determine transformer loading. If loading exceeds the factory-provided transformer capacity, a larger field-provided transformer will need to be installed in the system, WIRING CONNECTIONS 1, Install line voltage power supply to unit from a properly sized disconnect switch, 1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks. 2. Evacuate the system to remove as much of the moisture as possible. 3. Use nitrogen to break the vacuum and install a new filter drier in the system. 4. Evacuate the system again. Then, weigh the appropriate amount of HFC-410A refrigerant as listed on unit nameplate into the system. 2. Ground unit at unit disconnect switch or to an earth ground, 5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future. NOTE - Connect condu# to the unit using a proper conduit fitting. Units are approved for use only with copper conductors. Refer to figure 27 for high voltage field wiring diagram, A complete unR wiring diagram is located on the back side of the unit's access panel. AI08 DEFROST I WARNING CONTROL GROUND LOG q _OUND A OUTDOOR FAN 184 Cb}--- BLACK-RUN PURPLECAPACITOR ORANGE-COMMON C_ CAPACITOR L3 KI COMPRESSOR UUN_AUIUM _Llt_ FIELD In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Page 16 505330M 02/08 VOLTAGE INSTALLED NOTE - FOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVER-CURRENT PROTECTION SIZE. Figure 27. Typical Field Wiring RT28 DISCHARGE SENSOR @ T73OOF THERMOSTAT CB31MV o%yMv B4 FAN SB7 LOW PRESSURE _K58- I SWITCH © _ ._'_V (_}C BLACK_A REVERSING VALVE LI RTI3 AMBIENT SENSOR-- -- J%_ _ .... -+-4#I I @ I_ Ill ...................................... _: ..................... I............. RT21 DEFROST COIL SENSOR @ LO-PS K4 $4 HIGH PRESSURE SWITCH © P2 °OUT YB z_ EQUIPMENT GROUND I I I I I I I I OUTr..___ I I I-- = _I _ _!LTUHE oWRIIRMEPED _I _ TERMINAL OUT cc $5 DISCH LIMIT TEMP L_ BICOMPRESSORz_ _DENOTES -- -- OPTIONAL -- COMPONENTS WARNINGZ_ELECTRIC SHOCK HAZARD,CAN CAUSE INJURY OR DEATH,UNIT MUST BE GROUNDEO IN ACCORDANCE WITH NATIONAL AND LOCAL CODES. LINE VOLTAGE FIELD INSTALLED CLASS II VOLTAGE FIELD INSTALLED NOTEZ_FOR USE WITH COPPER CONDUCTORS ONLY,REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPAC]TY AND MAXIMUM OVERCURRENT PROTECTION SIZE _!_REMOVE JUMPER FOR TWO STAGE COOL CRIMPED TO BLUE WIRE USE TERMINAL OR CUT OFF TERMINAL AND SPLICE BLUE WIRE WITH Y2 WIRE TO INDOOR UNIT. /A L$4,SECOND STAGE, SOLENOID IS LOCATED z_IN COMPRESSOR. COIL IS Z¢VDC, DO NOT CONNECT R4VAC TO COIL TERMINALS. I A Z_REPER TO COMPRESSOR IN UNIT FOR ACTUAL TERMINAL ARRANGEMENT. Figure _RTI4 SENSOR,OUTDOOR 28. Typical NOTE - For proper voltages, select thermostat wire gauge per the following chart: Wire run length AWG # Insulation type less than 100' (30m) 18 color-coded, temperature more than lOg' (3Om) 16 rating 35°C minimum 3. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations, TEMP Wiring (OPTIONAL) Z_ SII AND K58 ARE OPTIONAL LOW AMBIENT CONTROLS Diagram THREE-PHASE SCROLL VOLTAGE PHASING Three-phase scroll compressors must be phased sequentially to ensure correct compressor rotation and operation. Incorrect line voltage phasing may cause compressor damage and abnormal unit operation. Power wires are color-coded as follows: Line 1 - red, line 2 - yellow, line 3 - blue, To test for proper rotation and operation: 4, Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit (figure 28), NOTE - 24V, Class II circuit connections are made in the low voltage junction box. 1, Install refrigeration gauges on system, Cycle compressor ON and observe that suction pressure decreases and discharge pressure increases, 2, If pressures do not follow the above conditions, disconnect all power to unit, Reverse any two field-installed main power wires to the line side of the compressor contactor. Make sure connections are tight, Repeat pressure test with system, Page 17 SPB*H4 SERIES Temp. IDT ofair 180 entering._78 indoor _ I _ coilOF _jru 24 23 _ _ 21 24 23 24 23 23 22 23 22 22 21 22 21 22 20 20 19 19 18 18 17 17 16 16 15 15 14 22 21 22 21 21 20 21 20 19 19 19 18 19 17 18 16 17 16 16 15 15 14 14 15 13 12 _72 20 20 19 18 17 17 16Z_15 14 13 12 11 10 _70 19 19 18 18 17 17 16 14 13 12 11 10 _'174 m 15 15 1. Determine the desired ])T--Measure entering air temperature using dry bulb (A) and wet bulb (B). ])T is the intersecting value of A and B in the table (see triangle), 2. Find temperature drop across coil--Measure the coil's dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (TDrop) = A minus C, Wet-bulb°F 57 58 59 60 61 62 63 64 65 66 67 68 69 70 I n A B 19o All temperatures expressed in °F INDOOR are COIL DRY BULB 3. Determine if fan needs adjustment_lf the difference between the measured TDrop and the desired ])T (TDropiDT) is within +3 °, no adjustment is needed. See examples: Assume ])T = 15 and A temp. = 72 °, these C temperatures would necessitate stated actions: C° TDrop- ])T = °F ACTION 530 19 15 = 4 Increase the airflow 58 ° 14 15 = -1 (within +3 ° range) no change 620 10 15 = -5 Decrease the airflow 4. Adjust the fan speed--See crease/decrease fan speed. WET BULB indoor unit instructions to in- Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3 °. Figure 29. Checking Indoor Coil Airflow Guide SETTING UP TO CHECK CHARGE 1, Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC-410A. IMPORTANT 2. Connect the manifold gauge set to the unit's service ports as illustrated in figure 2. • low pressure gauge to vapor service port • high pressure gauge to liquid service port 1. Rotate fan to check for binding. COOLING 2. Inspect all factory- and field-installed wiring for loose connections. 3, After evacuation is complete, open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system, 4, Replace the stem caps and tighten to the value listed in table 1, 5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected, 6, Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit. 7, Recheck voltage while the unit is running. Power must be within range shown on the nameplate, 8, Check system for sufficient refrigerate by using the procedures listed under Testing and Charging System, TESTING AND CHARGING SYSTEM Check airflow using the Delta-T (DT) process using the illustration in figure 29, HEATING MODE INDOOR AIRFLOW CHECK Blower airflow (CFM) may be calculated by energizing electric heat and measuring: • Temperature rise between the return air and supply air temperatures at the indoor coil blower unit, • Measuring voltage supplied to the unit, • Measuring amperage being drawn by the heat unit(s), Then, apply the measurements taken in following formula to determine CFM: CFM = 1.08 x Temperature rise (F) CHARGE If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit, To calculate the total refrigerant charge: Page 18 02/08 Amps x Volts x 3.41 CALCULATING This system uses HFC-410A refrigerant which operates at much higher pressures than HCFC-22. The pre-installed liquid line filter drier is approved for use with HFC-410A only. Do not replace it with components designed for use with HCFC-22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device, 505330M MODE INDOOR AIRFLOW CHECK Amount specified on nameplate + Adjust amount, for variation in line set length listed on table in figure 30. + Additional charge specified per indoor unit match-up listed in tables 3through 5. = Total charge WEIGH 1. Check Liquid and suction line pressures LENNOX Refrigerant Charge per Line Set Length Liquid Line Set Diameter Ounces per 5 feet (g per 1.5 m) adjust from 15 feet (4.6 m) line set* _ a ¢ _5 3t8" (9.5 mm) ;: 2. Compare unit pressures with table Normal Operating Pressures. 7, 3. Conduct leak check; previously outlined. as evacuate 4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet, 3 ounce per 5' (85 g per 1.5 m) NOTE - *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount. HmBl/Jillln| @,::::_, B This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information. Figure 30. Using Weigh In Method Check the airflow as illustrated in figure 29 to be sure the indoor airflow is as required. (Make any air flow adjustments before continuing with the following procedure.) SUBCOOL G' 2 Measure outdoor ambient temperature; determine whether to use cooling heating mode to check charge. 3 Connect gauge set. 4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table 7, (The reference table is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.) USE COOLING MODE Set thermostat for heat/cool demand, depending on mode being used: 60°F (15 °) -- Using cooling mode--When the outdoor ambient temperature is 60°F (15°C) and above. Target subcooling values in table below are based on 70 to 80°F (21-27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68°F (20°C). When pressures have stabilized, continue with step 6. USE HEATING MODE Using heating mode--When the outdoor ambient temperature is below 60°F (15°C). Target subcooling values in table below are based on 65-75°F (18-24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77°F (25°C). When pressures have stabilized, continue with step 6. q;_@i}ii¢ SAT o LIQ o SC o = mode or 6 Read the liquid line temperature; 7 Read the liquid line pressure; then find its corresponding temperature pressure chart listed in table 6 and record it in the SAT° space. record in the LIQ ° space. 8 Subtract LIQ ° temp. from SAT ° temp. to determine subcooling; record it in SC ° space. 9 Compare SC ° results with table below, being sure to note any additional charge for line set and/or match-up. in the temperature/ 10 If subcooling value is greater than shown in tables 3 through 5 for the applicable unit, remove refrigerant; if less than shown, add refrigerant. 11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge. Figure 31. Using Subcooling Method Page 19 SPB*H4 SERIES Table 3. SPB*H4-036 INDOOR Target Subcooling Heat Cool (+5OF) (±1OF) MATCH-UP INDOOR MATCH-UP **Add Target Subcooling Heat Cool (+5°F) (+l°F) CH88_2D 13 12 2 10 8 1 3 30 8 1 3 6F 13 9 1 14 CX34_0D 6F 15 6 1 3 CX34_2C 6F 13 11 2 6 CX34_2D 6F 13 11 2 5 17 7 0 13 CR33 CH23-85 12 8 1 10 CR33_0D_ CBX28UH-030 25 8 1 14 CX34_9C CBX28UH-038 25 8 1 14 CB27UH-036 17 8 2 4 CB27UH-042 17 8 2 4 CB3OU-31 17 6 0 0 CB3OU-41/46 17 8 2 4 CBX32M-030 17 6 0 0 CBX32M-036 17 8 2 4 CBX32MV-024/030 17 6 0 0 CBX32MV-036 17 8 2 4 C33-44C 17 8 1 14 17 7 0 12 8 10 CH33-438 CH33-49C 2F CH33-44/48B CH33-48C 2F 2F CR33_48B/C-F CR33-50/60C 2F 80/80C F Table 6. HFC-410A Temp. (°F) - Pressure (Psig) °F Psig °F Psig °F Psig °F Psig -40 10.1 21 80.5 56 158.2 91 278.2 13 -35 13.5 22 82.3 57 161 92 282.3 1 8 -30 17.2 23 84.1 58 163.9 93 286.5 8 1 6 9 10 1 6 -25 21.4 24 85.9 59 166.7 94 290.8 9 10 1 6 -20 25.9 25 87.8 60 169.6 95 295.1 25 8 2 0 -18 27.8 26 89.7 61 172.6 96 299.4 -16 29.7 27 91.6 62 175.4 97 303.8 25 9 0 14 CX34-38A/B_F Senal No# before 6007K 31 7 1 5 CX34-38A/B_F Senal No# 6007K and after 10 8 1 12 -14 31.8 28 93.5 63 178.5 98 308.2 CX34-43B/C_F 10 8 1 6 -12 33.9 29 95.5 64 181.6 99 312.7 CX34-6OD 9 9 0 14 -10 36.1 30 97.5 65 184.3 100 317.2 -8 38.4 31 99.5 66 187.7 101 321.8 -6 40.7 32 100.8 67 190.9 102 326.4 -4 43.1 33 102.9 68 194.1 103 331 -2 45.6 34 105 69 197.3 104 335.7 0 48.2 35 107.1 70 200.6 105 340.5 1 49.5 36 109.2 71 203.9 106 345.3 **Amount nameplate. F charge 30 CH23-51 CH33-428 **Add charge of charge (Remember required in to consider additional line set to length charge shown difference.) on unit Table 4. SPB*H4-048 INDOOR Target Subcoo]ing Heat Cool (+5OF) (±1OF) MATCH-UP **Add charge CH23-88 15 13 0 7 2 50.9 37 111.4 72 207.2 107 350.1 CB27UH-048 17 7 0 0 3 52.2 38 113.6 73 210.6 108 355 CB27UH-080 17 7 0 0 17 7 0 0 4 53.6 39 115.8 74 214 109 360 17 7 0 0 5 55 40 118 75 217.4 110 365 10 0 3 6 56.4 41 120.3 76 220.9 111 370 7 57.9 42 122.6 77 224.4 112 375.1 CB30U-51, CBX32M _5 048, 080 CBX32MV 088 18 CH33-60D 2F 18 4 0 2 CH33-62D 2F 15 10 0 4 40 4 0 2 8 59.3 43 125 78 228 113 380.2 CX34-60D 6F 18 4 0 2 9 60.8 44 127.3 79 231.6 114 385.4 CX34-62D 6F 18 8 0 2 10 62.3 45 129.7 80 235.3 115 390.7 11 63.9 46 132.2 81 239 116 396 12 65.4 47 134.6 82 242.7 117 401.3 13 67 48 137.1 83 246.5 118 406.7 14 68.6 49 139.6 84 250.3 119 412.2 15 70.2 50 142.2 85 254.1 120 417.7 CR33-60 Table 5. SPB*H4-060 INDOOR Target Subcooling Heat Cool (+5OF) (+1OF) MATCH-UP **Add charge CH23-68 13 14 3 3 CH23-65 18 2 O O 16 71.9 51 144.8 86 258 121 423.2 13 14 3 5 17 73.5 52 147.4 87 262 122 428.8 CB27UH-060 13 10 2 1 CBX32M 13 10 2 1 18 75.2 53 150.1 88 266 123 434.5 77 54 152.8 89 270 124 440.2 78.7 55 155.5 90 274.1 125 445.9 CBX26UH 060 060 CBX32MV 068 13 12 2 9 19 CH33-6OD 2F 15 6 1 3 20 Page 20 505330M 02/08 Table 7. Normal Operating Pressures - Liquid +10 & Vapor +5 PSIG* Model Mode Stage First (Low Capacity) Pressure Cooling Second (High Capacity) Pressure First (Low Capacity) Pressure Heating Second (High Capacity) Pressure *IMPORTANT--These SPB036H4S4 °F (°C)** Liquid SPB048H4S4 Vapor Liquid SPB060H4S4 Vapor Liquid Vapor 65 (18.3) 225 144 235 144 225 138 75 (23.9) 261 147 268 145 264 141 85 (29.4) 302 149 310 147 305 142 95(35.0) 349 151 356 148 352 146 165 (46.6) 397 153 407 150 405 148 115 (46.1) 461 157 466 152 459 150 65 (18.3) 239 139 244 140 241 134 75 (23.9) 278 141 283 141 280 136 85 (29.4) 322 143 326 144 324 137 95(35.0) 367 146 374 147 373 138 165 (46.6) 426 148 427 148 425 142 115 (46.1) 489 151 491 151 486 146 46 (4.4) 328 98 369 75 351 63 50 (10) 333 118 366 114 335 92 26 (-7.6) 296 62 311 58 308 59 36 (-1.6) 309 75 334 72 323 70 46 (4.4) 322 92 354 89 318 69 56 (16) 336 113 381 108 329 82 are most-popular-match-up pressures. Indoor match up and indoor load cause pressures to vary. **Temperature of the air entering the outside coil (outdoor ambient temperature). INSTALLING SERVICE VALVE CAPS Disconnect gauge set and re-install both the liquid and suction service valve caps, INSTALL OUTDOOR UNIT SERVICE VALVES _ placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode. CAPS Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging. / Figure 32. Installing Service Valve Caps FILTER DRIER The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously. THERMOSTAT OPERATION Some indoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light). The thermostat is not included with the unit and must be purchased separately, The unit is equipped with a large-capacity bi-flow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity. The replacement filter drier must be suitable for use with HFC-410A refrigerant. EMERGENCY HEAT (AMBER LIGHT) An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is DEFROST SYSTEM DESCRIPTION The demand defrost controller measures differential temperatures to detect when the system is performing poorly because of ice build-up on the outdoor coil, The controller self-calibrates when the defrost system starts and after each system defrost cycle. The defrost control board components are shown in figure 33, Page21 SPB*H4 SERIES TEST PINS DEFROST TERMINATION PIN SETTINGS SENSOR PLUG IN (COIL AND AMBIENT SENSORS) -- -- O DELAY PINS REVERSING VALVE o J LOW AMBIENT THERMOSTAT PINS DIAGNOSTIC LEDS 24V TERMINAL STRIP CONNECTIONS Low Pressure (auto reset) - trip at 25 psig; reset at 55 psig. PRESSURE SWITCH 5-STRIKE LOCKOUT The internal control logic of the board counts the pressure switch trips only while the Y1 INPUT line is active. If a pressure switch opens and closes four times during a Y1 INPUT, the control logic will reset the pressure switch trip counter to zero at the end of the Y1 INPUT. If the pressure switch opens for a fifth time during the current Y1 INPUT, the control will enter a lockout condition. )o © © NOTE - COMPONENT o o o o o o • o TST P_ OF C _ 0 Y] YZ LOCATIONS VARY BY BOARD O MANUFACTURER. The 5-strike pressure switch lockout condition can be reset by cycling OFF the 24-volt power to the control board or by shorting the TEST pins between 1 to 2 seconds. All timer functions (run times) will also be reset. Figure 33. Outdoor Unit Defrost Control Board (100135-03) The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation. NOTE - The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles. DEFROST BOARD DIAGNOSTIC LEDS The state OFF, ON and FLASHING of two LEDs on the defrost board DS1 [Red] and DS2 [Green] indicate diagnostics conditions that are described in table 9. DEFROST BOARD PRESSURE SWITCH CONNECTIONS The unit's automatic reset pressure switches LO PS-$87 and HI PS-S4 are factory-wired into the defrost board on the LO-PS and HI-PS terminals, respectively. Low Pressure Switch (LO-PS)--When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the following conditions: • • during the defrost cycle and 90 seconds after the termination of defrost when the average below 15 ° F (-9°C) ambient sensor temperature during TEST mode DEFROST BOARD PRESSURE SWITCH SETTINGS High Pressure (auto reset) - trip at 590 psig; reset at 418 psig. )L )R CIRCUIT ..... [_O CONNECTIONS for 90 seconds following the start up of the compressor • High Pressure Switch (HI-PS)--When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. 'i _o-Ps • If a pressure switch opens while the Y1 OUT line is engaged, a 5-minute short cycle will occur after the switch closes. DEFROST SYSTEM SENSORS Sensors connect to the defrost board through a field-replaceable harness assembly that plugs into the board (see figure 35). Through the sensors, the board detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Figure 34 shows how the resistance varies as the temperature changes for both type of sensors. Sensor resistance values can be checking by ohms across pins shown in table 8. NOTE - When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 8, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced. Table 8. Sensor Temperature/Resistance Sensor Temperature Range °F (°C) Resistance values range (ohms) Pins/Wire Color Outdoor -35 (-37) to 120 (48) 280,000 to 3750 3 &4 (Black) Coil -35 (-37) to 120 (48) 280,000 to 3750 5 &6 (Brown) Discharge (if applicable) 24 (-4) to 350 (176) 41,000 to 103 1 & 2 (Yellow) is Note: Sensor resistance increases as sensed temperature decreases. Page 22 505330M 02/08 Range Ambient Sensor--The ambient sensor considers outdoortemperatures below-35°F(-37°C)orabove120°F (48°C)asafault.Iftheambient sensorisdetected asbeing open,shortedor out of the temperaturerangeof the sensor,the board will not performdemanddefrost operation.The board will revert to time/temperature defrostoperationandwill displaythe appropriatefault code.Heatingandcoolingoperation willbeallowedinthis faultcondition. Ambient m demand, it reverts to a lockout mode and displays the appropriate code. This code detects shorted sensor or high discharge temperatures. Code on board is Discharge Line Temperature Fault and Lockout. 2. If the board recognizes five temperature sensor range faults during a single Y1 compressor demand, it reverts to a lockout mode and displays the appropriate code. The board detects open sensor or out-of-temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After five faults, the board will lockout. Code on board is Discharge Sensor Fault and Lockout. and Coil Sensor 7150 19275 11775 _m The discharge line sensor, which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a W' refrigerant discharge line. 15425 _ 19975 26200 m 34375 m 10000 30000 I I 62700 50000 70000 RESISTANCE Dischar NOTE - Within a single room thermostat demand, if 5-strikes occur, the board will lockout the unit. Defrost board 24 volt power R must be cycled OFF or the TEST pins on board must be shorted between I to 2 seconds to reset the board. 46275 85300 I 90000 (OHMS) Second-Stage Operation--If the board receives a call for second-stage compressor operation Y2 in heating or cooling mode and the first-stage compressor output is active, the second-stage compressor solenoid output will be energized. le Sensor D B250 _325 _425 If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock-in temperature, the second-stage compressor solenoid output will be energized without the Y2 input. If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock-in temperature of 40°F (4.5°C) will be used. _600 _825 m_175 700 2025 _500 ;000 3750 4650 1000 2000 3000 4000 5000 5825 6000 RESISTANCE/OHMS/ Figure 34. Temperature/Resistance Charts Coil Sensor--The coil temperature sensor considers outdoor temperatures below -35°F (-37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition. Discharge Line Sensor--If the discharge line temperature exceeds a temperature of 300°F (148°C) during compressor operation, the board will de-energize the compressor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute anti-short cycle delay has been satisfied. This sensor has two fault and lockout codes: 1. If the board recognizes five high discharge line temperature faults during a single Y1 compressor The board de-energizes the second-stage compressor solenoid output immediately when the Y2 signal is removed or the outdoor ambient temperature is 5°F above the selected compressor lock-in temperature, or the first-stage compressor output is de-energized for any reason. Defrost Temperature Termination Shunt (Jumper) Pins--The defrost board selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C). DELAY MODE The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins. NOTE - The 30 second off cycle is NOTfunctional jumpering the TEST pins. when Page 23 SPB*H4 SERIES COIL SENSOR I " DEFROST BOARD DEFROST SENSOR -7 TUBES UP FROM SPB*H4-036 BOTTOM (6-1/2") HARNESS SPB*H4-060 COIL SENSOR - 12 TUBES UP FROM BOTTOM (11-1/2") SENSOR SPB*H4-048 COIL SENSOR - 13 TUBES UP FROM BOTTOM DISCHARGE LINE SENSOR GREASE RETURN SENSOR (12-1/2") BETWEEN BEND AND CLIP COIL TEMPERATURE SENSOR FROM THE DEFROST ON THE RETURN BEND SHOWN. Figure OPERATIONAL 35. Sensor DESCRIPTION The defrost control board has three basic operational modes: normal, defrost, and calibration. • Normal Mode--The demand defrost board monitors Calibration Mode--The board is considered uncalibrated when power is applied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode, Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle. • Defrost Mode--The following paragraphs provide a detailed description of the defrost system operation, DETAILED DEFROST SYSTEM OPERATION The demand defrost control board initiates a defrost cycle based on either frost detection or time. A IMPORTANT Time--If 6 hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle, Actuation--When the reversing valve is de-energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time, The control will attempt to self-calibrate after this (and all other) defrost cycle(s), Calibration success depends on stable system temperatures during the 20-minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 90 minutes of heating mode compressor run Page 24 505330M 02/08 Locations Frost Detection--If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control, a defrost cycle will be initiated, the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required, • BOARD time.Oncethe defrostboardis calibrated,it initiatesa demanddefrostcyclewhenthe differencebetweenthe clear coil and frostedcoil temperatures exceedsthe maximumdifferenceallowedby the controlORafter6 hoursof heatingmodecompressorruntime has been loggedsincethelastdefrostcycle. Termination--Thedefrostcycle endswhen the coil temperature exceedsthetermination temperature or after 14minutesofdefrostoperation. Ifthedefrostisterminated by the 14-minutetimer,anotherdefrostcyclewill be initiatedafter34minutesof runtime. Test Mode--When Y1 is energized and 24V power is Enter the TEST mode by placing a shunt (jumper) across the TEST pins on the board after power-up. (The TEST pins are ignored and the test function is locked out if the shunt is applied on the TEST pins before power-up). Board timings are reduced, the low-pressure switch is ignored and the board will clear any active lockout condition. Each test pin shorting will result in one test event. For each TEST the shunt (jumper) must be removed for at least one second and reapplied. Refer to flow chart (figure 36) for TEST operation. Note: The Y1 input must be active (ON) and the 0 room thermostat terminal into board must be inactive. being applied to the board, a test cycle can be initiated by placing the termination temperature jumper across the TEST pins for 2 to 5 seconds. If the jumper remains across the TEST pins longer than 5 seconds, the control will ignore the test pins and revert to normal operation. The jumper will initiate one cycle per test. Table 9. Defrost Control DEFROST BOARD DIAGNOSTICS See table 9 to determine defrost board operational conditions and to diagnose cause and solution to problems. Board Diagnostic LEDs DS2 DS1 Green Red Condition/Code Possible OFF OFF Power problem No power (24V) to board terminals R & C or board failure. 1 Check control transformer power (24V). 2 If power is available to board and LED(s) do not light, replace board. Simultaneous SLOW Flash Normal operation Unit operating normally or in standby mode. None required. Alternating SLOW Flash 5-minute anti-short cycle delay Initial power up, safety trip, end of room thermostat demand. None required (Jumper TEST pins to override) Simultaneous FAST Flash Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will revert to time/ temperature defrost operation. (System will still heat or cool). Alternating FAST Flash Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not perform demand or time/temperature defrost operation. (System will still heat or cool). ON Circuit Board Failure Indicates that board has internal component failure. Cycle 24 volt power to board. If code does not clear, replace board. FAULT ON & LOCKOUT CODES Cause(s) Solution (Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT) OFF SLOW Flash Low Pressure Fault OFF ON Low Pressure LOCKOUT SLOW Flash OFF High Pressure Fault ON OFF High Pressure LOCKOUT SLOW Flash ON Discharge Line Temperature Fault FAST Flash ON Discharge Line Temperature LOCKOUT OFF Fast Flash Discharge Sensor Fault Fast Flash OFF Discharge Sensor LOCKOUT 1 Restricted air flow over indoor or outdoor coil. 2 Improper refrigerant charge in system. 3 Improper metering device installed or incorrect operation of metering device. 4 Incorrect or improper sensor location or connection to system. 1 Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws. 2 Check system charge using approach and subcooling temperatures. 3 Check system operating pressures and compare to unit charging charts. 4 Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements. This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 300°F (148°C) during compressor operation, the board will de-energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C). The board detects open sensor or out of temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance Is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout. Page25 SPB*H4 SERIES 1 Y1 Active ("0" line inactive) I i, Short test pins for longer than 1 / Short test pins for more than 2.0 seconds second but ess than 2.0 seconds Clear any short cycle lockout or 5-strike fault lockout function, if applicable. Clear any short cycle lockout and/ or 5-strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating. I,finCOO',.G Mode I No further test mode operation will be executed until the test short is removed and Lreapp ed. Mode ] I,fin O .OSZMode The controller will check for ambient and I coil faults (open or shorted). If a fault exists, the unit will remain in Heat Mode and no further test mode operation will be I executed until the test short is removed and re applied. If no fault exists, the unit will go nto Defrost mode. I The unit will terminate defrost and I enter Heat Mode uncalibrated with I defrost timer set for 34 minute test. No further test mode operation will I be executed until the test short is I removed and reapp ed. t Test pins short REMOVED before a Test pin short REMAINS in place for more than 5 seconds max mum of 5 seconds t The unit will return to Heat mode uncalibrated with defrost timer set for 34 minutes. No further test mode operation will be executed until the The unit will remain in Defrost mode until test short s removed and re app ed. termination on time or temperature Figure 36. Test Mode Operation I kWARNING Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance. • Inspect and clean the outdoor and indoor coils. The outdoor coil may be flushed with a water hose. NOTE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, etc.) • Visually inspect the refrigerant lines and coils for leaks. • Check wiring for loose connections. • Check voltage at the indoor and outdoor units (with units operating). • Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate. • Check, clean (or replace) indoor unit filters. • Check the refrigerant charge and gauge the system pressures. Check the condensate drain line for free and unobstructed flow; clean, if necessary. • • Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure. • Check drive belt for wear and proper tension. NOTE - If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction. Refer to the Engineering Handbook for optional accessories that may apply to this unit. The following may or may not apply: • Compressor monitor • • • Compressor crankcase heater Mounting bases Stand-off Kit • • Sound cover Low ambient kit • • Mild ambient kit Monitor kit • Two-stage Lennox Room Thermostat Page 26 505330M 02/08 crowding the unit cause the outdoor unit to work harder and use more energy, Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit, Inordertoensurepeakperformance, yoursystemmustbe properlymaintained. Cloggedfiltersandblockedairflow preventyourunitfromoperating at itsmostefficientlevel. 1, Air Filter--AskyourLennoxdealertoshowyouwhere yourindoorunit'sfilterislocated.It willbeeitheratthe indoorunit(installed internalorexternaltothecabinet) or behinda returnairgrilleinthewallor ceiling.Check thefiltermonthlyandcleanor replaceitas needed, 2, Disposable Filter--Disposablefilters should be replaced witha filterofthesametypeandsize, When removing debris from around the unit, be aware of metal edges on parts and screws, Although special care has been taken to keep exposed edges to a minimum, physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury, Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air conditioning or heat pump system. NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance. IMPORTANT HEAT PUMP OPERATION Your new Lennox heat pump has several characteristics that you should be aware of: • Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space, This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space. • 4. Electronic Air Cleaner--Some systems are equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions. Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost, • 5. Indoor Unit--The indoor unit's evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.) During the defrost cycle, you may notice steam rising from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle, EXTENDED POWER OUTAGE 3, Reusable Filter--Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille. NOTE - The filter and all access panels must be in place any time the unit is in operation. The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation, IMPORTANT If power to your or more, set EMERGENCY without the risk 6, Outdoor Unit--Make sure no obstructions restrict airflow to the outdoor unit, Leaves, trash or shrubs unit has been interrupted for several hours the room thermostat selector to the HEAT setting to obtain temporary heat of serious damage to the heat pump, In Emergency Heat mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume, Page27 SPB*H4 SERIES Though your thermostat may vary somewhat from the description below, its operation will be similar, TEMPERATURE SETTING LEVERS Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor, FAN SWITCH In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling, This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired. INDICATING LIGHT Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode. TEMPERATURE INDICATOR The temperature indicator displays the actual room temperature, PROGRAMMABLE THERMOSTATS Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling, Refer to the user's information manual provided with your particular thermostat for operation details, PRESERVlCE CHECK If your system fails to operate, check the following before calling for service: • Check to see that all electrical disconnect switches are ON. • • SYSTEM SWITCH Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings, Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat, • • • • Make sure the room thermostat temperature selector is properly set. Make sure the room thermostat system switch is properly set, If you discover any blown fuses or tripped circuit breakers, call your Lennox dealer for assistance, Make sure unit access panels are in place, Make sure air filter is clean, Locate unit model number and have it handy before calling, Job Name Job no. Date Job Location City State Installer City State Unit Model No, Serial No. Service Technician Nameplate Voltage Rated Load Ampacity Maximum Fuse or Circuit Breaker Compressor Amperage: 1st Stage Electrical Connections Tight? Indoor Filter clean? Indoor Blower RPM S.P. Drop Over Indoor (Dry) :_] 2nd Stage: Supply Voltage (Unit Off) Outdoor Coil Entering Air Temp. COOLING (2ND STAGE) Liquid Line Pressure: Vapor Pressure: Refrigerant Charge Checked? Liquid Line Pressure: Vapor Pressure: Refrigerant Charge Checked? Vapor Pressure; 1st Stage: 2nd Stage: HEATING (2ND STAGE) Refrigerant Lines: - Leak Checked? Service Valves: --- Fully Opened? SEQUENCE Heating Correct? _ _ Properly Insulated? _1 Caps Tight? 02/08 _1 Voltage With Compressor Operating THERMOSTAT OF OPERATION Calibrated? Cooling Correct? Page 28 505330M Outdoor Fan Checked? Properly Set? _ Level?
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 28 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Mon Jun 30 05:03:25 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools