LENNOX Package Units(both Units Combined) Manual L0806711
User Manual: LENNOX LENNOX Package Units(both units combined) Manual LENNOX Package Units(both units combined) Owner's Manual, LENNOX Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 9
Download | |
Open PDF In Browser | View PDF |
I STALLATIO AN NTENANC iNSTRUCTiONS (2,4)SA13 Series lectric Coolin Package Unit TABLE iNSTALLATiON OPERATION OF CONTENTS ...................................... .......................................... MAINTENANCE WiRiNG ..................................... DIAGRAM WARRANTY ................................ ........................................ 2 7 8 9 10 Manufactured By A.A.C. A Lennox International Inc. Company 421 Monroe Street Bellevue, OH 44811 [ A, CAUTION I The installation of this appliance must conform to the requirements of the National Fire Protection Association; the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual. # 48392M005 Save these instructionsfor future reference Page 1 INSTALLATION These instructions, and any instructions packaged with mating components and/or accessories, should be carefully read prior to beginning installation. Note particularly any CAUTIONS or WARNINGS in these instructionsand all labels on the units. These instructionsare intended as a general guide only, for use by qualified personnel and do not supersede any national or local codes in any way. Compliance with all local, state, provincial, or national codes pertaining to this type of equipment should be determined prior to installation. These instructions explain the recommended method of installation of the SA electric cooling unit and associated electrical wi ring. Location The unit is designed to be located outdoors with sufficient clearance for free entrance to the air inlet and discharge air openings. The location must also allow for adequate service access. The unit must be installed on a solid foundation that will not settle or shift. Adequate structural support must be provided. Maintain minimum clearances as shown in Table 1 and install the unit in level position, isolate the base from the building structure to avoid possible transmission of sound or vibration into the conditioned space. Minimum Clearance Requirements The SA unit is designed and approved for use as a selfcontained ai r-to-ai r ai r conditioning system. The unit is factory equipped with a transformer and blower control for applications without auxiliary heat. An electric heat accessory kit (PHK) can be ordered for field installation of additional heat where required. IMPORTANT: This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer's refrigerant charging and air flow instructions. Failure to confirm proper charge and airflow may reduce energy efficiency and shorten equipment life. inspection of Shipment Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier's freight bill. Take special care to examine the unit inside the carton if the carton is damaged. File a claim with the transportation company. Front Rear 0" 48" 3" 3" . 0". 24' Condenser End 0" 24" 3" Top 0" 36" 36" Table 1 If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT, as claim may be denied. Avoid placing the unit near quiet areas such as sleeping quarters or study rooms. Normal operating sound levels may be objectionable if the unit is placed near certain rooms. Check the unit rating plate to confirm specifications are as ordered. Do not permit overhanging structures or shrubs to obstruct condenser air discharge inlet or outlet. Limitations For improved start-up performance, the indoor coil should be washed with suitable detergent to remove any residue from manufacturing processes. The unit should be installed in accordance with all national and local safety codes. Limitations of the unit and appropriate accessories must also be observed. The unit must not be installed with any ductwork in the outdoor air stream. The outdoor fan is not designed to operate against any additional static pressure. Page 2 Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. An accessory lift kit can be purchased to aid in rigging (see Figure 1). Spreaders whose length exceed the largest dimension across the unit must be used across the top of the unit. Recommended spreader length: 3 ton and smaller package units - 44", 3.5 ton and larger units - 54". # 48392M005 Clearances Using Accessory Lift Kit Spreaders (Field Supplied) All units require certain clearances for proper operation and service. Refer to Table 1 for the minimum clearances to combustibles as well as minimum clearances necessary for servicing and proper unit operation. In the U.S., units may be installed on combustible floors made from wood or class A, B, or C roof covering material. In Canada, units may be installed on combustible floors. Service Access To avoid possible damage to unit panels from lifting clevis, place packing material between clevis and panels before lifting unit, Figure Access to all serviceable components is provided by four removable panels: filter compartment, blower compartment, heater compartment, and top panel. Condensate Drain The SA package unit is equipped with a 3/4" FPT coupling for condensate line connection. Plumbing must conform to local codes. Use a sealing compound on male pipe threads. 1 Units may also be moved or lifted with a forklift while still in the factory-supplied packaging. The lengths of the forks of the forklift must be a minimum of 42". The condensate drain line must be properly trapped and routed to a suitable drain. See Figure 3 for proper drain arrangement. The drain line must pitch to an open drain or pump to prevent clogging of the line. Seal around the drain connection with suitable material to prevent air leakage into the return air system. Typical Condensate Drain Connection Roof Curb Installation Unit /-- Drain Connection / If a roof curb is used, follow the manufacturer's Installation Instructions and be sure that all required clearances are observed (see following Clearances section). 1.00" Min. t2.oo '- Roof Curb Assembly Max. °' _\ Positive Liquid Seal Required _ Figure 3 Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA). Figure 2 A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. It is recommended that supply and return duct connections at the unit be made with flexible joints. # 48392M005 Page 3 ThesupplyandreturnairductsystemsshouldbedesignedfortheCFMandstaticrequirements ofthejob. They should not be sized by matching of the duct connections on the unit. Outdoor ductwork airflow of the unit. Filters should be sized in accordance with Table 2. the dimensions Minimum Required for Disposable must be insulated and waterproofed. Equipment is shipped for side ductwork connection. The unit can be converted to bottom ductwork connection by removing the duct covers located over the bottom duct openings and placing these covers over the side duct openings (see Figure 4). Surface Filters 24,000 2.67 36,000 4.00 Area To remove the bottom duct cover over supply opening: 1. Remove screw on cover nearest side opening. 42,000 2. Lift end of cover slightly and push to slide back screw/ pin free from duct flange. 3. Slide duct cover out the side duct opening. Removing Bottom Electrical (D 1. Remove screw and lift. 2. Slide cover to free back pin. 4.67 5.33 Table 2 ® Figure 48,000 Duct Covers 41111 . Wiring J Base_ 4 All wiring should be done in accordance with the National Electrical Code, ANSI/NFPA No. 70 (latest edition); Canadian Electrical Code Part 1, CSA C22.1 (latest edition); or local codes where they prevail. Use wiring with a temperature limitation of 75°C minimum. Run the 208 or 230 volt, 60 hertz electric power supply through a fused disconnect switch to the connection box of the unit and connect as shown in the wiring diagram located on the inside of the control access panel. Filters Air filters are to be used with this heating/cooling unit. Filters are not factory supplied in the unit. However, a filter frame accessory is available from the manufacturer that allows filters to be installed within the unit. If the filter frame accessory is not used, a filter must be installed in the duct work by the installer. Filters must always be installed ahead of the evaporator coil and must be kept clean or replaced. Dirty filters will reduce the Page 4 # 48392M005 Electrical Access Heater Power Thermostat _Q_ Powersupplytotheunitmustcomplywithallapplicable codesandtheNational ElecticalCode(NEC)orCanadian Electrical Code(CEC).Afuseddisconnect switchshouldbe fieldprovided fortheunit.Theswitchmustbeseparate from allothercircuits. Entry Line Voltage Entry Ifanyofthewiresupplied withtheunitmustbereplaced, replacement wiremustbeofthetypeshownonthewiring diagram. Electrical wiringmustbesizedtocarryminimum circuitampacity markedontheunit.Usecopperconductorsonly.Eachunitmustbewiredwithaseparate branch circuitandbeproperly fused. Figure 5 Thermostat The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow the Typical THERMOSTAT E_------ OUTDOOR UNIT [] [_------ ECONOMIZER NOT INSTALLED [_-- Connections THERMOSTAT OUTDOOR UNIT E_------ -----[] [] Wiring -----[] [] ] [_-- -----[_ WHITE ] - -except required by the indoor thermostat. thermostat installation YELLOW [_---- _CAUTION [CJeonnections BLUE ---- -- -- [_---- Do not connect -- [_ GREEN when - -- Refer to the --d_--- BLACK instructions. (_ _' GROUND @ POWER WIRING 208/230=1-60 POWER WIRING POWER 24V CONTROL WIRING 24V CONTROL 2) * W1, W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 15 & 20 KW MODELS. * 5 & 10 KW HEATER ACCESSORY FUNCTION OFFW1 ONLY. TYPICAL WIRING CONNECTI©N 1 PHASE except when to the POWER WIRING 200/230-3-60, 460/575-3=60 (90°C MIN.WIRE) (gO°C MIN. WIRE) CLASS [CJconnections required by the indoor thermostat. Refer thermostat installation instructions. GROUND SCREW I SCREW (NED AOAUTION Do not connect @ (NED WIRING CLASS ............ WIRING 2) Wl, W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 15 & 20 KW MODELS. 10 KW HEATER ACCESSORY FUNCTION OFF Wl ONLY. TYPICAL WIRING CONNECTION 3 PHASE Figure # 48392M005 ECONOMIZER 6 Page 5 manufacturer's instructions enclosed withthermostat for generalinstallation procedure. Color-coded insulated wires (#18AWG)shouldbeusedtoconnectthermostat tounit. Fourwiresarerequired forcooling. Heater Kit Accessory Compressor I Units are shipped with compressor mountings factoryadjusted and ready for operation. Caution: Do not loosen compressor mounting bolts. Heater Kit Accessory (if used) Installation Blockoff Heater , = _!_i ent Panel The unit is fully equipped for cooling operation without auxiliary heat. A heater kit accessory may also be used. Heater Kit To install the heater kit accessory (see Figure 7): 1. Disconnectthe powerand remove the heatercompartment access panel. 2. Disconnect the plug separating the high voltage wire harness. Remove the high voltage wire harness plug and discard. 3. Remove the heater blockoff by removing the four screws holding it in place. 4. insert the heater into the control panel and fasten in the same mounting holes. Plug the heater wiring harness into the wire harness on the control assembly. Field wiring of the auxiliary heater is separate from the unit power supply. Wire the power supply wiring for the heater to the appropriate connections on the heater kit. 6. Replace the heater compartment access panel and reconnect the power. Removal of Unit from Common Venting 2. 3. Seal any unused openings in the common venting system. 7 are located and other spaces in the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. 4. Following the lighting instructions, place the unit being inspected in operation. Adjust the thermostat so the appliance will operate continuously. 5. Test for spillage at the draft control relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. 6. Follow the preceding steps for each appliance connected to the common venting system. 7. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other fuel burning appliance to their previous condition of use. System When an existing indoor furnace is removed from a common venting system serving other appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted with each appliance while the other appliances connected to the common venting system are not in operation. 1. Figure 8. If improper venting is observed during any of the above tests, the common venting system must be corrected. See National Fuel Gas Code, ANSI Z223.1 (latest edition)or CAN/CGA B149.1 & .2 Canadian installation Codes to correct improper operation of common venting system. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition. insofar as is practical, close all building doors and windows between the space in which the appliances remaining connected to the common venting system Page 6 # 48392M005 OPERATION Sequence of Operation CooHng Upon cooling demand, the thermostat closes circuit R and Y. Closing R and Y closes the unit contactor, starting the compressor and outdoor fan. The thermostat automatically closes R to G circuit which also brings on the indoor blower at the same time. Upon satisfying cooling demand, the thermostat will open the above circuits and open the main contactor, stopping the compressor and outdoor fan. (f the un(t is equipped with a delay timer, the blower will continue to operate for 90 seconds wh(ch improves system efficiency. Circulating Air Blower The circulating air blower is controlled by a timing circuit in the blower control. Timings are not adjustable. There is no blower "on" delay after a call for heating or cooling. Blower "off" delay is 90 seconds after the thermostat is satisfied. Cooling System Performance For maximum performance of the cooling system, operating temperatures and pressure should be checked. Superheat should be determined at Standard AR( test conditions of 82°F outdoor and 80°F indoor dry bulb/67°F wet bulb. (f superheat measured deviates from values found in Table 3, refrigerant charge should be adjusted accordingly for maximum performance. Suction 48,60 Superheat 22 ° 15 ° 20 ° 12 ° 20 ° 10 ° Table 3 # 48392M005 Page 7 MAINTENANCE Owner Record Model # Serial # Installation Date Installed by: Dealer Address Telephone # License # At the beginning of each heating season, system should be checked as follows by a qualified service technician: Periodic inspection and maintenance normally consists of changing or cleaning the filters and cleaning the outdoor coil. On occasion, other components may also require cleaning. Filters Filters should be checked at least every 6 weeks. Disposable filters should be replaced when dirty, and cleanable filters should be cleaned regularly. It is important to keep the air filters clean, as dirty filters can restrict airflow and the blower motor depends upon sufficient air flowing across and through it to keep from overheating. Motors indoor and outdoor fan and vent motors are permanently lubricated and require no maintenance. Outdoor Coil Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure the power to unit is shut off prior to cleaning. Care should be used when cleaning the coil so that the coil fins are not damaged. Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs. Page 8 # 48392M005 N 05 d w d3 ±HM 0 ii NN9 i ii o o oJ LO N78 Z o co >- o co z o 0 < L£ LL 09 W > "qcd o w Z -£:: 1- © Z d w o9 LU 7- 0 eO ¢D cO 04 _- CO ,q- C_ _0 > 0 o2 w w @ _IO { _ow CC--D 0 d 09 w _J d D w 09 rr w z -I23 >- z N7g _S w_ II O w ol_ o _ _ ko b2 w z _AOP8 M7g I u-_x _Ng_NOgSNV£11 I 08 o-_axj N7g n78 73A E mo _ IHM w_ _w Z_ w _ 8 w_ Ow D "_ Z o M78 -- w W_Z D_ N_ _o Z © _z # 48392M005 __ ZI/_ OI So Z_ o_ o_ _ ::/ o I _o ss _ _8 _cc -- -ZZ _ < @_ _o 2° > O omZ Z-- _ oo oo 73A cc o:: o9 ccO 08 @ co { _ o o Figure 8 Page 9
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 9 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Jul 20 21:04:43 2008 Author : Title : Subject :EXIF Metadata provided by EXIF.tools