GAS KITS & ACCESSORIES
::, 2006 Lennox Industries Inc.
DaIias, Texas, USA

HIGH ALTITUDE KIT

505,247M
09/2006

INSTALLATION
INSTRUCTIONS
FOR HIGH ALTITUDE KIT (59M17) USED WITH ALL G40DF,
G40UH, G43UF, G50DF, G50UH, G51MP, G60 & G61 UNITS FUELED BY NATURAL GAS

I

TABLE 1 (Continued)
Pressure Switch Requirements

Ak WARNING

Pressure Switch
Model Number

Requirements
Altitudes of 7501-10,000 ft,
(2287 - 3048 m)

G6OUH/DF(V)-O7O & 090

Package 1 of I contains the following:
7 - Main burner orifices (0.086)
1 - Gas converter sticker
1 - Nameplate conversion sticker

Pressure Switch

G40DF
G50DF
G40UH
G5OUH
G43UF=045 & =070
G51MP=O45 & -g7g
G43U F-090 & =110
G51MP=090 & -110
G43UF-135
G51MP=135

Requirements
Altitudes of 750140,000
(2287 - 3048 m)

ft.

No Change
56L32

56Mg6
56Mg7

6gM35

09/06

IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

G60UH/DF(V)-110
G6OUH/DF(V)-135

18M61

G61 MP(V)-045
G61 MP-O7O

No Change
56M06

G61MPV-070

56M23

G61MPV-071

26W84

G61MP(V)-090

56M21

G61MPV-091

26W86

G61MP(V)-110

75M22

G61MPV-111

56M23

G61MP(V)-135

56M93

i_ii

High altitude kit (59M17) is used to convert all G40DF,
G40UH, G43UF, G50DF, G50UH, G51MP, G60UH(V),
G60DF(V) and G61MP(V) units which are fueled by
natural gas for operation at altitudes higher than 7500
feet (2286 m) above sea level. Units installed in these
applications
may also require
installation
of a
replacement
pressure
switch, which
is ordered
separately. Refer to table 1 for pressure switch
requirements. All pressure switches are factory-set and
require no adjustment. G51MP and G61MP(V) units
require two pressure switches.
TABLE 1
Pressure Switch Requirements
Model Number

18M64

&CAUTION

1 - Set the thermostat to the lowest setting. Shut off the
gas supply to the furnace, then disconnect the
electrical power.
2- Remove the heating compartment access panel.
Remove burner box cover, if necessary. Turn the
automatic gas valve knob, or switch the gas valve
lever, to the OFF position (figures 3, 4, 5 and 6).
3 - Disconnect the gas supply from the gas valve. Mark
the wires for identification and disconnect the wiring
at the gas valve.
4 - Remove the four manifold securing screws, Remove
the manifold/gas valve assembly, Replace the main
burner orifices with the provided orifices (.086). See
figure 1.
5- Re-install the manifold/valve assembly. Reconnect
wiring to the gas valve.
6- Units installed at altitudes higher than 7500 feet
above sea level may require a replacement pressure
switch assembly. See table 1 for the proper switch
assembly. Refer to figure 2 for pressure switch
location.

505,247M
Page1

IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

a - Remove the tubing from the barbed fitting on the
pressure switch(es).

BURNER BOX ASSEMBLY
(GGOUHV Shown)

b - Remove screw(s) which secure pressure switch
assembly(ies).
Install replacement pressure
switch(es) using existing screw(s),
c-

BURNER
BOX

Securely attach flexible tubing to fitting on
replacement pressure switch assembly(ies).
See figure 2,

=,WARNING
MANIFOLD t
GAS VALVE
ASSEMBLY

ORIFICES

7 - Reconnect the gas supply to the manifold and turn on
gas supply to unit,

Figure

1

PRESSURE SWITCH REPLACEMENT
FLUE
COLLECTOR
BOX

G43UF and G51MP

GASKET

G40DF, G40UH,
G50DF & G50UH

NOTE - G43UF models have only
one pressure switch assembly.
COLLECTOR
BOX

TUBING

TUBING

/
/

./

/

/
GASKET
COMBUSTION
AIR ORIFICE
PRESSURE
SWITCH

/
./
7

_
/

COMBUSTION
AIR INDUCER

COMBUSTION
AIR INDUCER

COMBUSTION AIRPRESSURE
SWITCH ASSEMBLIES

GASKET

G60UH/DF(V)

/

FLUE
COLLECTOR
BOX

G61MP(V)
FLUE
COLLECTOR
BOX

TUBING

/
COMBUSTION
AIR ORIFICE
COMBUSTION
AIR PRESSURE
SWITCH ASSEMBLY
(Two switches)

/
/

COMBUSTION
AIR INDUCER
COMBUSTION
AIR PRESSURE
SWITCH ASSEMBLIES

Figure 2

Page 2

AIRINDUCER

2 - Set the thermostat to its lowest setting,

IMPORTANT

3 - Turn off all electrical power to the furnace,
4-

Do not try to light the burners by hand.

5 - Remove the unit access panel.
6 - Turn the knob on the gas valve clockwise _

A

move the lever) to the OFF position. Do not force,
See figures 3, 4, 5 and 6.

CAUTION

7 - Wait five (5) minutes for any gas to clear out. If you
then smell gas, STOP! Immediately call your gas
supplier from a neighbor's phone, Follow the gas
supplier's instructions. If you do not smell gas, go to
the next step,
8 - Turn the knob on the gas valve counterclockwise

8 - Replace burner box cover, if necessary.

(or move the lever) to the ON position.

9 - Restore the electical power to the unit.
10-Affix
nameplate
nameplate.

conversion

sticker

next to unit

Honeywell VR8205 Series Single-Stage
MANIFOLDGas Valve with On/Off Switch
PRESSURE

11 - Complete the information required on the converter
sticker: date, name, and address. Affix sticker to the
exterior of the unit in a visible area,

SCREW

MANIFOLD
PRESSURE

(under cap)

OUTLET

12 - Follow the steps given in the start-up and adjustment
section.
13 - Energize the thermostat several times to ensure the
ignition control is operating and that the hot surface
ignitor glows.
14 - Replace the heating compartment

(or

GAS VALVE ONtOFF SWITCH SHOWN IN OFF POSITION
FIGURE

3

access panel.
Honeywell VR8205 Series Single-Stage
Gas Valve with Gas Control Knob
MANIFOLD

BEFORE LIGHTING - Smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
Use only your hand to turn the gas control knob or the
control lever. Never use tools. If the knob or lever will not

MANIFOLD

ADJUSTMENT
SCREW

PRESSURE_

turn by hand, do not try to repair it. Call a qualified service
technician. Force or attempted repair may result in a fire
or explosion.

GAS VALVE SHOWN IN OFF POSITION

FIGURE 4

A - Placing the Unit into Operation

White Rodgers 36G Series Gas Valve

IMPORTANT

OUTLET
PRESSURE_

POST

These units are equipped with an automatic hot surface
ignition system. This ignition system automatically lights
the burners each time the thermostat calls for heat.
1 - STOP! Read the safety information at the beginning
of this section.
Page 3

INLET
PRESSURE
POST

MANIFOLD
PRESSURE
ADJUSTMENT
SCREW

J

GAS VALVE SHOWN tN OFF POSITION

FIGURE 5

HONEYWELL
VR8205
Two-Stage

NOTE - Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care to
replace pressure tap plug.
G43UF, G51MP and G61MP(V) Units Only- During this
test procedure, the unit will be overfiring:
• Operate unit only long enough to obtain accurate
reading to prevent overheating heat exchanger.
• Attempts to clock gas meter during this procedure will
be inaccurate. Measure gas flow rate only during
normal unit operation.
7 - G43UF, G51MP and G61MP(V) Units Only -- When
test is complete, return hose to gas valve barbed
fitting.

Gas Valve

HIGH FIRE
ADJUSTING SCREW
(under cap)

MANIFOLD
PRESSURE
TAP

LOW FIRE
(under cap)
RE TAP

GAS VALVE SHOWN IN OFF POSITION

Figure 6
9 - Replace the unit access panel.
10 - Turn on all electrical power to the unit.
11 - Set the thermostat to desired setting.
12-If the furnace will not operate, see the section
"Turning Off Gas to the Unit" and call your service
technician or gas supplier.
B - Turning Off Gas To the Unit
1 - Set the thermostat to its lowest setting.
2 - Turn off all the electrical power to the unit.
3 - Remove the heat section access panel.
4 - Turn the knob on the gas valve clockwise1{_
(or
move the lever) to the OFF position. Do not force.
C - Verifying the Gas Line Pressure
Check the gas line pressure while the unit is operating.
Maintain a minimum of 4.5" w.c. (1.12 kPa) and a
maximum of 10.5" w.c. (2.61 kPa). See figures 3, 4, 5 and
6 for the location of the inlet pressure tap on the gas
valve.
D - Measuring & Adjusting the Manifold Pressure
NOTE - Pressure test adapter kit (10L34) is available from
Lennox to facilitate manifold pressure measurement.
1 - Connect test gauge to outlet tap on gas valve.
2- G43UF, G51MP and G61MP(V) Units Only -Disconnect pressure sensing hose from gas valve.
3 - Start unit on low heat (two-stage units only) and allow
5 minutes for unit to reach steady state.
4- While waiting for the unit to stabilize, notice the
flame. Flame should be stable and should not lift
from burner. Natural gas should burn blue.
5 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to values given in
low-fire columns in table 2.
6 - Repeat steps 3, 4 and 5 on high heat (single-stage
and two stage units). Compare with values given in
high fire columns in table 2.
Table 2
Manifold Pressure (Outlet) in. w.c, (kPa) for Natural Gas
ManifoldPressure_ AllAltitudes
Low Fire
High Fire
in,w,g,
1.7

l

kPa
.42

in,w,g,
3.5

1

XklMPORTANT

E - Verifying the Gas Rate
The gas input must not exceed the amount shown on the
unit's rating plate. In cases where gas is not metered, the
service technician who is performing the conversion will
need to install a temporary meter to perform this
procedure. Check the input by the following method:
Contact the utility company for the heating value of the
gas. Shut offall other appliances during the input check.
Locate the meter just upstream in regulated pressure
[4.5" w.c. to 10.5" w.c. (1.12kPa to 2.61kPa)]. To check the
Btu input rate, time the dial hand on the gas meter for at
least one revolution, using the one cubic foot dial.
To assure accurate measurements, use temperature and
pressure correction factors for the meter.
To determine the number of seconds required for the flow
of one cubic foot of gas, use the following formula:

kPa
.87

Page 4

(BTU Content)
Heating Value Of Gas X 3600
Furnace
Example:

Btuh Input

1000 BTU gas
Furnace input 160,000 BTUH

Seconds for one cubic foot =
1000 X 3600
100,000

= 36 seconds



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 4
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Sun Jul 20 21:11:16 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu