Lenox Air Conditioner Elite Series Xp16 Units Heat Pumps Users Manual 506640a
Lenox Air Conditioner Elite Series XP16 Units Heat Pumps Lennox_XP16_IOM
Elite Series XP16 Units Heat Pumps to the manual 4a0ca56a-af7f-4082-a8f4-4c8427d7732c
2015-02-09
: Lenox Lenox-Lenox-Air-Conditioner-Elite-Series-Xp16-Units-Heat-Pumps-Users-Manual-571122 lenox-lenox-air-conditioner-elite-series-xp16-units-heat-pumps-users-manual-571122 lenox pdf
Open the PDF directly: View PDF .
Page Count: 43
Download | |
Open PDF In Browser | View PDF |
INSTALLATION INSTRUCTIONS E20 Lennox Industries Inc. Dallas, Texas, USA Elite® Series XP16 Units HEAT PUMPS These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE NOTICE TO INSTALLER BRAZING LINE SET TO SERVICE VALVES It is imperative to follow the brazing technique illustrated starting on page 11 to avoid damaging the service valve’s internal seals. WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency. IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HFCs, and HCFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance. 506640−01 12/10 Supersedes 11/10 TABLE OF CONTENTS Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Model Number Identification . . . . . . . . . . . . . . . . . . . . Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Parts Arrangement . . . . . . . . . . . . . . . . . . . . . . Caps and Fasteners Torque Requirements . . . . . . . . Operating Gauge Set and Service Valves . . . . . . . . . Recovering Refrigerant from Existing System . . . . . New Outdoor Unit Placement . . . . . . . . . . . . . . . . . . . Removing and Installing Panels . . . . . . . . . . . . . . . . . Line Set Requirements . . . . . . . . . . . . . . . . . . . . . . . . . Brazing Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil . . . . . . . . . . . . . . . . Installing New Indoor Metering Device . . . . . . . . . . . . Leak Test Line Set and Indoor Coil . . . . . . . . . . . . . . . Evacuating Line Set and Indoor Coil . . . . . . . . . . . . . Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . Unit Start−Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Servicing and Weighing In Refrigerant for Units Delivered Void of Charge . . . . . . . . . . . . . . . . . . . . . . . Optimizing System Refrigerant Charge . . . . . . . . . . . System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Defrost System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two−Stage Modulation Compressors Checks . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IMPORTANT This unit must be matched with an indoor coil as specified in Lennox XP16 Engineering Handbook. Coils previously charged with HCFC−22 must be flushed. CAUTION Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment. 12/10 *2P1210* Litho U.S.A. 1 1 2 2 3 3 3 5 6 8 9 11 14 15 16 17 18 23 24 26 30 34 40 40 42 Shipping and Packing List Check unit for shipping damage. Consult last carrier immediately if damage is found. 1 − Assembled outdoor unit General The XP16 outdoor unit uses HFC−410A refrigerant. This unit must be installed with a matching indoor blower coil and line set as outlined in the XP16 Lennox Engineering Handbook. Elite® Series outdoor units are designed for use in check / expansion valve (CTXV) systems only and are not to be used with other refrigerant flow control devices. An indoor coil check / expansion valve approved for use with HFC−410A must be ordered separately and installed prior to operating the unit. Page 1 506640−01 *P506640-01* Model Number Identification X P 16 −036 − 230 −05 Refrigerant Type X = R−410A Minor Revision Number Voltage 230 = 208/230V−1ph−60hz Unit Type P = Heat Pump Nominal Cooling Capacity 024 = 2 tons 036 = 3 tons 048 = 4 tons 060 = 5 tons Series Unit Dimensions − inches (mm) C B DISCHARGE AIR LIQUID LINE CONNECTION ELECTRICAL INLETS A VAPOR LINE CONNECTION 2 (51) 4−3/4 (121) 4−1/4 (108) SIDE VIEW SIDE VIEW 1 (25) UNIT SUPPORT FEET UNIT SUPPORT FEET 8−1/2 (216) 9−1/2 (241) 8−3/4 (222) D 8−1/4 (210) E 13−1/2 (343) 5−1/2 (140) K J H G F XP16 BASE WITH LEGS XP16−024 BASE SECTION Mode Number A B C D E F G H J K XP16−024−230 35 (889) 27 (686) 28 (711) − − − − − − − XP16−036−230 39 (991) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524) XP16−048−230 35 (889) 35−1/2 (902) 39−1/2 (1003) 16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683) XP16−060−230 45 (1143 35−1/2 (902) 39−1/2 (1003) Page 2 Typical Unit Parts Arrangement FOR COIL SENSOR (RT21) LOCATION SEE DETAIL A COMPRESSOR DUAL RUN CAPACITOR (C12) (−024, −036 AND −048 ONLY) SINGLE RUN CAPACITOR (C1) (−060 ONLY) DEMAND DEFROST CONTROL (A108) DISCHARGE LINE SENSOR (RT28) REVERSING VALVE (L1) TRUE SUCTION PORT HIGH PRESSURE SWITCH (S4) EXPANSION VALVE SENSING BULB CHECK / EXPANSION VALVE LIQUID VALVE AND GAUGE PORT / LIQUID LINE CONNECTIONS GROUND LUG SINGLE POLE CONTACTOR (K1) AMBIENT TEMPERATURE SENSOR (RT13) LIQUID LINE BI−FLOW FILTER DRIER LOW PRESSURE SWITCH (S87) VAPOR VALVE AND GAUGE PORT / SUCTION LINE CONNECTIONS DETAIL A XP16−048 XP16−036 COIL SENSOR − EIGHT HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW. COIL SENSOR − NINTH HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW. XP16−060 COIL SENSOR − SIXTH HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW. XP16−024 COIL SENSOR −THIRD HAIRPIN DOWN FROM THE TOP ON INSIDE ROW. Figure 1. Unit Parts Arrangement Caps and Fasteners Torque Requirements IMPORTANT Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess. Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess. See the Lennox Service and Application Notes Corp.0807−L5 (C−08−1) for further details and information. When servicing or repairing HVAC equipment and components, ensure the fasteners are appropriately tightened. Table 1 list torque values for various caps and fasteners. Table 1. Torque Requirements Parts Recommended Torque Service valve cap 8 ft.− lb. 11 NM Sheet metal screws 16 in.− lb. 2 NM Machine screws #10 28 in.− lb. 3 NM Compressor bolts 90 in.− lb. 10 NM Gauge port seal cap 8 ft.− lb. 11 NM Page 3 XP16 SERIES Operating Gauge Set and Service Valves USING MANIFOLD GAUGE SET When checking the system charge, only use a manifold gauge set that features low−loss anti−blow back fittings. IMPORTANT To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening. Manifold gauge set used for HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The manifold gauges should be rated for: S High side Pressure range of 0 − 800 pound−force per square inch gauge (psig) S Low side Use with 30" vacuum to 250 psig with dampened speed to 500 psig S Manifold gauge set hoses must be rated for use to 800 psig of pressure with a 4000 psig burst rating. OPERATING SERVICE VALVES The liquid and vapor line service valves are used for refrigerant recovery, flushing, leak testing, evacuating, weighing in refrigerant and optimizing system charge. Each valve is equipped with a service port which has a factory−installed valve core. Figure 2 provides information on how to access and operate both angle− and ball−type service valves. Operating Angle−Type Service Valve: 1. Remove stem cap with an appropriately sized wrench. HEX−HEAD 2 INSERT EXTENSION HERE 2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open the service valve. SERVICE PORT CAP TO INDOOR UNIT SERVICE PORT CORE SERVICE PORT CORE (VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE TO INDOOR UNIT TO OUTDOOR UNIT TO OUTDOOR UNIT VALVE STEM SHOWN CLOSED When service valve stem is in the CLOSED position, the service port is open to the line set and indoor unit. STEM CAP When service valve is OPEN, the service port is open to line set, indoor and outdoor unit. Operating Ball−Type Service Valve: To Access Service Port: A service port cap protects the service port core from contamination and serves as the primary leak seal. 1. Remove stem cap with an appropriately sized wrench. 1. Remove service port cap with an appropriately sized wrench. 2. Use an appropriately sized wrenched to open. 2. Connect gauge set to service port. A B To open rotate stem counterclockwise 90°. To close rotate stem clockwise 90°. TO INDOOR UNIT 2 VALVE STEM SERVICE PORT SERVICE PORT CORE 1 REMOVE STEM CAP 11 12 10 9 8 7 6 1 2 3 4 Without torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise. 1/12 TURN Reinstall Stem Cap: Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows: S SERVICE PORT CAP 1/6 TURN 5 3. When testing is completed, replace service port cap and tighten as follows: S With torque wrench: Finger tighten and torque cap per table 1. S BALL (SHOWN CLOSED) TO OUTDOOR UNIT 1 REMOVE STEM CAP S With Torque Wrench: Finger tighten and then torque cap per table 1. 11 12 1 2 10 9 3 4 8 7 6 5 Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise. NOTE A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque. Figure 2. Angle and Ball−Type Service Valves Page 4 Recovering Refrigerant from Existing System 1 DISCONNECT POWER Disconnect all power to the existing outdoor unit at the disconnect switch and/or main fuse box/breaker panel. 2 CONNECT MANIFOLD GAUGE SET Connect a manifold gauge set, clean recovery cylinder and a recovery machine to the service ports of the existing unit.. NOTE Use the recovery machine instructions to make the correct manifold gauge set connections for recovery refrigerant. The illustration below is a typical connection. MAIN FUSE BOX/BREAKER PANEL MANIFOLD GAUGES DISCONNECT SWITCH RECOVERY MACHINE LOW 3 CLEAN RECOVERY CYLINDER RECOVERING REFRIGERANT HIGH OUTDOOR UNIT Remove existing HCFC−22 refrigerant using one of the following procedures: METHOD 2 LIMITATIONS METHOD 1: Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system. Recover all HCFC−22 refrigerant from the existing system using a recovery machine and clean recovery cylinder. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant. S S METHOD 2: Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system. Perform the following task: A Start the existing HCFC−22 system in the cooling mode and close the liquid line valve. B Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system. NOTE It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation. C D NOTE When using Method 2, the listed devices below could prevent full system charge recovery into the outdoor unit: When the low side system pressures reach 0 psig, close the vapor line valve. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF. Compressor can stop pumping due to tripped internal pressure relief valve. S Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.) Once the compressor can not pump down to a lower pressure due to any of the above mentioned system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set. Figure 3. Refrigerant Recovery IMPORTANT The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed. WARNING Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death. Page 5 XP16 SERIES New Outdoor Unit Placement If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) schedule 40 female threaded adapter. CAUTION In order to avoid injury, take proper precaution when lifting heavy objects. Remove existing outdoor unit prior to placement of new outdoor unit. See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements. POSITIONING CONSIDERATIONS Consider the following when positioning the unit: S Some localities are adopting sound ordinances based on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line. S When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A. The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2 inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit. NOTE Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights. ROOF MOUNTING Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications. See figure 5, detail F for other roof top mounting considerations. PLACING UNIT ON SLAB When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B. NOTE If necessary for stability, anchor unit to slab as described in figure 5, detail D. ELEVATING THE UNIT Units are outfitted with elongated support feet as illustrated in figure 5, detail C. NOTICE Roof Damage! This system contains both refrigerant and oil. Some rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface. CLEARANCE ON ALL SIDES INCHES (MILLIMETERS) 6 (152) ACCESS PANEL CONTROL PANEL ACCESS LOCATION 30 (762) 12 (305) MINIMUM CLEARANCE ABOVE UNIT NOTES: S S Clearance to one of the other three sides must be 36 inches (914mm). Clearance to one of the remaining two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm). LINE SET CONNECTIONS 36 (914) MINIMUM CLEARANCE BETWEEN TWO UNITS 24 (610) Figure 4. Installation Clearances Page 6 48 (1219) DETAIL A Outside Unit Placement Install unit away from windows. DETAIL B Slab Mounting at Ground Level Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure. BUILDING STRUCTURE MOUNTING SLAB TWO 90° ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION. Elevated Slab Mounting DETAIL C using Feet Extenders GROUND LEVEL DETAIL D Slab Side Mounting #10 1/2" LONG SELF−DRILLING SHEET METAL SCREWS COIL STABILIZING BRACKET (18 GAUGE METAL 2" WIDTH; HEIGHT AS REQUIRED) BASE PAN #10 1−1/4" LONG HEX HD SCREW AND FLAT WASHER CORNER POST BASE Concrete slab use two plastic anchors (hole drill 1/4") Wood or plastic slab no plastic anchor (hole drill 1/8") Stabilizing bracket (18 gauge metal 2" (50.8mm) width; height as required); bend to form right angle as exampled below. LEG DETAIL 2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER DETAIL F Roof Top Mounting If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated. 2" (50.8MM) SCH 40 MALE THREADED ADAPTER PREVAILING WINTER WINDS Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit. WIND BARRIER INLET AIR DETAIL E Deck Top Mounting MINIMUM ONE One bracket per side PER SIDE (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner. SAME FASTENERS AS SLAB SIDE MOUNTING. INLET AIR INLET AIR FOR EXTRA STABILITY INLET AIR Figure 5. Placement, Slab Mounting and Stabilizing Unit Page 7 XP16 SERIES Removing and Installing Panels LOUVERED PANEL REMOVAL Remove the louvered panels as follows: 1. Remove two screws, allowing the panel to swing open slightly. 2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in detail B. 3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in detail A. IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL. PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL. SCREW HOLES LIP LOUVERED PANEL INSTALLATION Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as possible. Then, in a continuous motion: 1. Slightly rotate and guide the lip of top tab inward as illustrated in detail A and C; then upward into the top slot of the hinge corner post. 2. Rotate panel to vertical to fully engage all tabs. 3. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes. 4. When panel is correctly positioned and aligned, insert the screws and tighten. Detail A Detail B ROTATE IN THIS DIRECTION; THEN DOWN TO REMOVE PANEL Detail C ANGLE MAY BE TOO EXTREME HOLD DOOR FIRMLY TO THE HINGED SIDE TO MAINTAIN FULLY−ENGAGED TABS PREFERRED ANGLE FOR INSTALLATION Detail D MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL. Figure 6. Removing and Installing Panels WARNING To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following: While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched). While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered. Page 8 Line Set Requirements This section provides information on: installation of new or replacement line set. S Adding Polyol ester oil requirements S New or replacement line set installation S Using existing line set. S Model (XP16) and size of unit (e.g. −036). S Line set diameters for the unit being installed as listed in table 2 and total length of installation. S Number of elbows vertical rise or drop in the piping. USING EXISTING LINE SET ADDING POLYOL ESTER OIL REQUIREMENTS IMPORTANT Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol Ester oil. The compressor is charged with sufficient Polyol Ester oil (POE) for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. Systems with 20 pounds or less of refrigerant required no oil to be added. For systems over 20 pounds − add one ounce for every five (5) pounds of HFC−410A refrigerant. Things to consider: S Liquid line that meter the refrigerant, such as RFC1 liquid line, must not be used in this application. S Existing line set of proper size as listed in table 2 may be reused. S If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing Line Set and Indoor Coil on page 14). If existing line set is being used, then proceed to Brazing Connections on page 11. Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF. NEW OR REPLACEMENT LINE SET INSTALLATION Field refrigerant piping consists of both liquid and vapor lines from the outdoor unit to the indoor coil. Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as specified in table 2. If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 7 for recommended installation practices. IMPORTANT Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing Line Set and Indoor Coil on page 13. IMPORTANT If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty. NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following information: Table 2. Refrigerant Line Set Inches (mm) Model XP16−024−230 Field Connections Recommended Line Set Liquid Line Suction Line Liquid Line Suction Line L15 Line Set 3/8" (10 mm) 3/4" (19 mm) 3/8" (10 mm) 3/4" (19 mm) L15−41 15 ft. − 50 ft. (4.6m − 15 m) 3/8" (10 mm) 7/8" (22 mm) 3/8" (10 mm) 7/8" (22 mm) L15−65 15 ft. − 50 ft. (4.6 m − 15 m) 3/8" (10 mm) 1−1/8" (29 mm) 3/8" (10 mm) 1−1/8" (29 mm) Field Fabricated XP16−036−230 XP16−048−230 XP16−060−230 NOTE Some applications may required a field provided 7/8" to 1−1/8" adapter Page 9 XP16 SERIES Line Set Isolation The following illustrations are examples of proper refrigerant line set isolation: REFRIGERANT LINE SET INSTALLING VERTICAL RUNS (NEW CONSTRUCTION SHOWN) REFRIGERANT LINE SET TRANSITION FROM VERTICAL TO HORIZONTAL ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE MUFFLER-TYPE HANGER NOTE Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig. AUTOMOTIVE MUFFLER-TYPE HANGER OUTSIDE WALL LIQUID LINE VAPOR LINE WALL STUD WIRE TIE INSIDE WALL STRAP WOOD BLOCK BETWEEN STUDS STRAP LIQUID LINE TO VAPOR LINE NON−CORROSIVE METAL SLEEVE WIRE TIE LIQUID LINE NON−CORROSIVE METAL SLEEVE WOOD BLOCK VAPOR LINE − WRAPPED IN ARMAFLEX WIRE TIE STRAP REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS SLEEVE To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties. WIRE TIE (AROUND VAPOR LINE ONLY) VAPOR LINE WRAPPED WITH ARMAFLEX 8 FEET (2.43 METERS) STRAPPING MATERIAL (AROUND VAPOR LINE ONLY) OUTSIDE WALL FLOOR JOIST OR ROOF RAFTER LIQUID LINE TAPE OR WIRE TIE 8 FEET (2.43 METERS) PVC PIPE NON−CORROSIVE METAL SLEEVE TAPE OR WIRE TIE CAULK FIBERGLASS INSULATION STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE. NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall. FLOOR JOIST OR ROOF RAFTER Figure 7. Line Set Installation Page 10 Brazing Connections Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves. WARNING IMPORTANT Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections. Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals. IMPORTANT WARNING Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture − Check the high and low pressures before applying heat. WARNING When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa). Use silver alloy brazing rods with 5% minimum silver alloy for copper−to−copper brazing. Use 45% minimum alloy for copper−to−brass and copper−to−steel brazing. WARNING Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an explosion, that could result in property damage, personal injury or death. CAUTION Brazing alloys and flux contain materials which are hazardous to your health. Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas. Wear gloves and protective goggles or face shield to protect against burns. Wash hands with soap and water after handling brazing alloys and flux. Page 11 XP16 SERIES 1 CUT AND DEBUR Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line. 2 CAP AND CORE REMOVAL Remove service cap and core from both the suction / vapor and liquid line service ports. CUT AND DEBUR SERVICE PORT CAP SERVICE PORT CORE LINE SET SIZE MATCHES SERVICE VALVE CONNECTION SERVICE PORT CORE SERVICE VALVE CONNECTION SERVICE PORT CAP COPPER TUBE STUB LIQUID LINE SERVICE VALVE REDUCER LINE SET SIZE IS SMALLER THAN CONNECTION SUCTION / VAPOR LINE SERVICE VALVE DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS SMALLER THAN CONNECTION REFRIGERANT LINE 3 ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve. A Connect gauge set low pressure side to liquid line service valve (service port). USE REGULATOR TO FLOW B Connect gauge set center port to bottle of nitrogen with regulator. C Remove core from valve in suction / vapor line service port to allow nitrogen to escape. SUCTION / VAPOR SERVICE PORT MUST BE OPEN TO ALLOW EXIT POINT FOR NITROGEN C LOW HIGH NITROGEN AT 1 TO 2 PSIG. ATTACH GAUGES B SUCTION / VAPOR LINE SERVICE VALVE VAPOR LINE OUTDOOR UNIT INDOOR UNIT NITROGEN LIQUID LINE LIQUID LINE SERVICE VALVE A WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME AWAY FROM SERVICE VALVE. Figure 8. Brazing Procedures WARNING When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa). Page 12 4 5 6 WRAP SERVICE VALVES To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use additional water saturated cloths underneath the valve body to protect the base paint. FLOW NITROGEN Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections BRAZE LINE SET Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water saturated cloths must remain water saturated throughout the brazing and cool−down process. LIQUID LINE SERVICE VALVE WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME AWAY FROM SERVICE VALVE. IMPORTANT Allow braze joint to cool. Apply additional water saturated cloths to help cool brazed joint. Do not remove water saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals. WATER SATURATED CLOTH LIQUID LINE WARNING SUCTION / VAPOR LINE SERVICE VALVE 1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE may result if you do not wrap a water saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat. 2. Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated. Refer to procedures provided in this supplement. WHEN BRAZING LINE SET TO SERVICE VALVES, POINT FLAME AWAY FROM SERVICE VALVE. SUCTION / VAPOR LINE WATER SATURATED CLOTH 7 PREPARATION FOR NEXT STEP After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both service valves to cool piping. Once piping is cool, remove all water saturated cloths. Figure 9. Brazing Procedures (continued) Page 13 XP16 SERIES Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 15. 1A TYPICAL EXISTING FIXED ORIFICE REMOVAL PROCEDURE (UNCASED COIL SHOWN) 1B TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN) OR TWO PIECE PATCH PLATE (UNCASED COIL ONLY) DISTRIBUTOR TUBES LIQUID LINE ORIFICE HOUSING DISTRIBUTOR TUBES STUB END LIQUID LINE ORIFICE HOUSING CHECK EXPANSION VALVE TEFLON® RING TEFLON® RING FIXED ORIFICE BRASS NUT TEFLON® RING DISTRIBUTOR ASSEMBLY DISTRIBUTOR ASSEMBLY REMOVE AND DISCARD WHITE TEFLON® SEAL (IF PRESENT) A B C D E LIQUID LINE ASSEMBLY WITH BRASS NUT CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE D E INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING. F A 1 GAUGE MANIFOLD LOW OPENED EXISTING INDOOR UNIT VAPOR LIQUID D CLOSED B LIQUID LINE SERVICE VALVE RECOVERY CYLINDER G H HIGH NEW OUTDOOR UNIT VAPOR LINE SERVICE VALVE INLET DISCHARGE RECOVERY MACHINE A B C D MALE EQUALIZER LINE FITTING SENSING BULB Inverted HCFC−22 cylinder with clean refrigerant to the vapor service valve. HCFC−22 gauge set (low side) to the liquid line valve. HCFC−22 gauge set center port to inlet on the recovery machine with an empty recovery tank to the gauge set. Connect recovery tank to recovery machines per machine instructions. VAPOR LINE FLUSHING LINE SET The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding. A Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line B set and indoor unit coil. B Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine. C After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull down to 0 the system. D Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off. Figure 10. Removing Indoor Refrigerate Metering Device and Flushing Procedures Page 14 LIQUID LINE On fully cased coils, remove the coil access and plumbing panels. Remove any shipping clamps holding the liquid line and distributor assembly. Disconnect the equalizer line from the check expansion valve equalizer line fitting on the vapor line. Remove the vapor line sensing bulb. Disconnect the liquid line from the check expansion valve at the liquid line assembly. Disconnect the check expansion valve from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process. Remove and discard check expansion valve and the two Teflon® rings. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing. 3 TANK RETURN C EQUALIZER LINE LIQUID LINE ASSEMBLY (INCLUDES STRAINER) On fully cased coils, remove the coil access and plumbing panels. Remove any shipping clamps holding the liquid line and distributor assembly. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process. Remove and discard fixed orifice, valve stem assembly if present and A Teflon® washer as illustrated above. B Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing. C 2 SENSING LINE Installing New Indoor Metering Device This outdoor unit is designed for use in HFC−410A systems that use a check / expansion valve metering device (purchased separately) at the indoor coil. See the Lennox XP16 Engineering Handbook for approved check / expansion valve kit match−ups. The check / expansion valve device can be installed either internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the check / expansion valve in a manner that will provide access for field servicing of the check / expansion valve (see figure 11). INDOOR EXPANSION VALVE INSTALLATION TWO PIECE PATCH PLATE (UNCASED COIL ONLY) DISTRIBUTOR TUBES A (Uncased Coil Shown) LIQUID LINE ORIFICE HOUSING STUB END B CHECK / EXPANSION VALVE TEFLON® RING TEFLON® RING DISTRIBUTOR ASSEMBLY SENSING LINE C D E EQUALIZER LINE LIQUID LINE ASSEMBLY WITH BRASS NUT SENSING BULB INSTALLATION A MALE EQUALIZER LINE FITTING (SEE EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS) VAPOR LINE Sensing bulb insulation is required if mounted external to the coil casing. 1/2 Turn Remove the field−provided fitting that temporarily reconnected the liquid line to the indoor unit’s distributor assembly. 11 12 1 2 Install one of the provided Teflon® rings around the 10 3 stubbed end of the check / expansion valve and lightly 9 4 lubricate the connector threads and expose surface of 8 7 6 5 the Teflon® ring with refrigerant oil. Attach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft−lb. Place the remaining Teflon® washer around the other end of the check / expansion valve. Lightly lubricate connector threads and expose surface of the Teflon® ring with refrigerant oil. Attach the liquid line assembly to the check / expansion valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb. Attach the vapor line sensing bulb in the proper orientation as illustrated to the right using the clamp and screws provided. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right. BULB FLARE NUT OR ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION. VAPOR LINE EQUALIZER LINE INSTALLATION FLARE SEAL CAP 1/8 Turn NOTE Confirm proper thermal contact between vapor line 11 12 1 and expansion bulb before insulating the sensing bulb once 10 2 LIQUID LINE installed. 9 3 4 B Connect the equalizer line from the check / expansion 8 7 5 6 valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below. 12 BULB VAPOR LINE COPPER FLARE SEAL BONNET MALE BRASS EQUALIZER LINE FITTING ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE. 12 BULB BULB NOTE NEVER MOUNT ON BOTTOM OF LINE. VAPOR LINE Figure 11. Installing Indoor Check / Expansion Valve Page 15 XP16 SERIES Leak Test Line Set and Indoor Coil IMPORTANT Leak detector must be capable of sensing HFC refrigerant. CONNECT GAUGE SET A B Connect an HFC−410A manifold gauge set high pressure hose to the vapor valve service port. LOW NOTE Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. HIGH MANIFOLD GAUGE SET OUTDOOR UNIT NOTE Later in the procedure, the HFC−410A container will be replaced by the nitrogen container. A B TO VAPOR SERVICE VALVE NITROGEN HFC−410A Figure 12. Manifold Gauge Set Connections for Leak Testing TEST FOR LEAKS After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks: 1. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (vapor only). 2. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure Page 16 side of the manifold gauge set. Disconnect the HFC−410A cylinder. 3. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set. 4. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit. 5. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector. 6. After leak testing disconnect gauges from service ports. Evacuating Line Set and Indoor Coil Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts. CONNECT GAUGE SET 1 NOTE Remove cores from service valves (if not already done). A Connect low side of manifold gauge set with 1/4 SAE in−line tee to vapor line service valve B Connect high side of manifold gauge OUTDOOR set to liquid line service valve UNIT C Connect micron gauge available connector on the 1/4 SAE in−line tee. A D Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC−410A and nitrogen containers. LOW MANIFOLD GAUGE SET A34000 1/4 SAE TEE WITH SWIVEL COUPLER 500 MICRON GAUGE C TO VAPOR SERVICE VALVE NITROGEN HFC−410A HIGH B VACUUM PUMP TO LIQUID LINE SERVICE VALVE D 2 EVACUATE THE SYSTEM A B C NOTE The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following: S S S S S S D E F G RECOMMEND MINIMUM 3/8" HOSE Open both manifold valves and start the vacuum pump. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure. Close manifold gauge valves Close valve on vacuum pump and turn off vacuum pump Disconnect manifold gauge center port hose from vacuum pump Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open manifold gauge valves to break the vacuum in the line set and indoor unit. Close manifold gauge valves. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit. 1/6 TURN Perform the following: S S S S Close manifold gauge valves. 11 Shut off HFC−410A cylinder. Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core tool while maintaining a positive system pressure. Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated. 10 9 8 12 1 2 4 7 6 3 5 Figure 13. Evacuating Line Set and Indoor Coil Page 17 XP16 SERIES Electrical Connections IMPORTANT Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns. WARNING Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty. SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH 1 Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch. In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. 24VAC TRANSFORMER Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum) 2 INSTALL THERMOSTAT Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts. THERMOSTAT MAIN FUSE BOX/ BREAKER PANEL DISCONNECT SWITCH 5 FEET (1.5M) NOTE Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground. NOTE 24VAC, Class II circuit connections are made in the control panel. WARNING Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes. Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. Page 18 3 HIGH VOLTAGE FIELD WIRING LOW VOLTAGE CONNECTIONS LOW VOLTAGE (24V) FIELD WIRING AWG# INSULATION TYPE LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM. NOTE − For proper voltages, select thermostat wire (control wires) gauge per table above. NOTE − Do not bundle any excess 24VAC control wires inside control box. A Run 24VAC control wires through cutout with grommet. B Run 24VAC control wires through wire tie. C Make 24VAC control wire connections. D Tighten wire tie to security 24V control wiring. C A WIRE RUN LENGTH NOTE − Wire tie provides low voltage wire strain relief and to maintain separation of field installed low and high voltage circuits. CUTOUT WITH GROMMET 24V CONTROL WIRES D B TIGHTEN WIRE TIE Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated. See figures 14 and 15 for typical field connections when connecting unit to either a CBX32MV or CBX40UHV in non−communicating mode. For connections to other Lennox air handlers or furnaces, see the ComfortSense® 7000 installation instruction for further match component wiring illustrations. 4 HIGH VOLTAGE POWER SUPPLY CONNECTIONS GROUND NOTE − Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. OUTDOOR UNIT CONTROL BOX G L1 L2 NOTE − To facilitate a conduit, a cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. CONDUIT CUTOUT CONDUIT Page 19 XP16 SERIES HEAT PUMP UNIT (TWO−STAGE) CBX32MV OR CBX40UHV COMFORTSENSET 7000 R R R W3 H W2 W2 1 2 W1 W1 O O 3 1 W1 X2658 OUTDOOR SENSOR IS REQUIRED FOR OUTDOOR TEMPERATURE DISPLAY, DEW POINT CONTROL, HEAT PUMP AND DUAL FUEL BALANCE POINTS. CONNECTED ON UNIT WITH LSOM. RESISTOR KIT (CAT # 47W97) IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000 WITH THE LSOM 2. FIELD PROVIDED JUMPER BETWEEN Y2 OUT BL ON HEAT PUMP TO Y2 ON CBX40UHV. O. D. SENSOR (X2658) O AIR HANDLER CONTROL 2 L L Y1 Y1 Y1 Y2 Y2 DS D Y2 B C C T R−O HEAT PUMP CUT ON−BOARD LINK R −O. T C R−DS DEHUM OR HARMONY CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION TERMINAL IS USED. CUT FOR OPTION 3 Y1−Y2 2−STAGE COMPR CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE HP G G Y2 OUT BL IMPORTANT − USE CARE WHEN CUTTING LINKS TO PREVENT DAMAGE TO CONTROL. SEE CBX40UHV INSTALLATION INSTRUCTION FOR FURTHER DETAILS. Figure 14. Typical Field Wiring Heat Pump Application with CBX32MV or CBX40UHV CBX32MV OR CBX40UHV OUTDOOR UNIT COMFORTSENSEt 7000 THERMOSTAT RED FAN RELAY (NOT REQUIRED WITH SINGLE−SPEED OUTDOOR FAN) PURPLE RED OUTDOOR SENSOR BLACK T PURPLE T (X2658) BLACK YELLOW BLUE BROWN (NOT USED FOR APPLICATIONS WITHOUT LSOM BLUE (NOT REQUIRED FOR SINGLE STAGE) AIR HANDLER CONTROL IMPORTANT − USE CARE WHEN CUTTING LINKS TO PREVENT DAMAGE TO CONTROL. SEE CBX40UHV INSTALLATION INSTRUCTION FOR FURTHER DETAILS. CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE A/C ONLY CUT ON−BOARD LINK R −O. CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION TERMINAL IS USED. Y1−Y2 2−STAGE COMPR R−O HEAT PUMP R−DS DEHUM OR HARMONY Figure 15. Heat Pump Application Humiditrol ® and Second−Stage Outdoor Fan Relay Wiring with CBX32MV or CBX40UHV Page 20 CUT FOR OPTION RESISTOR KIT (CAT # 47W97) IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000 WITH THE LSOM 2. Figure 16. Typical Unit Wiring Diagram (−024, −036 and −048 Only) Page 21 XP16 SERIES Figure 17. Typical Unit Wiring Diagram (−060 Only) Page 22 Figure 18. Typical Factory Wiring Diagram (No Field Modifications) Unit Start−Up IMPORTANT If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging. have consulted with the power company and the voltage condition has been corrected. 6. Open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system. 7. Use figure 19 to determine next step in system preparation. OPEN BOTH VAPOR AND LIQUID SERVICE VALVE STEMS TO RELEASE REFRIGERANT FROM OUTDOOR UNIT TO SYSTEM. UNIT START−UP 1. Rotate fan to check for binding. 2. Inspect all factory− and field−installed wiring for loose connections. 3. Verify that the manifold gauge set is connected as illustrated in figure 21. Use a temperature sensor positioned near the liquid line service port as illustrated in figure 21 which will be required later when using the subcooling method for optimizing the system refrigerant charge. 4. Replace the stem caps and tighten to the value listed in table 1. 5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you NO REFRIGERANT PRESENT GO TO SERVICE AND WEIGH IN REFRIGERANT CHARGE FOR OUTDOOR UNITS DELIVERED VOID OF CHARGE ON PAGE 24. YES GO TO OPTIMIZING SYSTEM REFRIGERANT CHARGE ON PAGE 26. Figure 19. Outdoor Unit Factory Charge Page 23 XP16 SERIES Service and Weigh In Refrigerant for Outdoor Units Delivered Void of Charge The following procedures are only required if it has been determine that the new outdoor unit is void of charge. Skip to the next section if refrigerant charge is present. LEAK CHECK, REPAIR AND EVACUATE If the outdoor unit is void of refrigerant, clean the system using the procedure described below. 2. Connect the manifold gauge set’s low pressure side to the true suction port. 3. Connect the manifold gauge set’s high pressure side to the liquid line service port. 1. Leak check system using procedures provided on page 16. Repair any leaks discovered during leak test. 4. Connect the center hose of the gauge set to a cylinder of HFC−410A and purge the hose. Then, place the cylinder upside down on a scale. 2. Evacuate the system using procedure provided in figure 13. 5. Check that fan rotates freely. 3. Use nitrogen to break the vacuum and install a new filter drier in the system. 6. Inspect all factory− and field−installed wiring for loose connections. 4. Evacuate the system again using procedure in figure 12. 7. Open the high side manifold gauge valve and weigh in liquid refrigerant. Use figure 20 in calculating the correct weigh−in charge. CONNECT MANIFOLD GAUGE SET AND WEIGH IN CHARGE After the evacuation procedure, reconnect the manifold gauge set as illustrated in figure 21. 8. Close manifold gauge valves. 9. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the bi−flow filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future. 10. Continue to Optimizing System Refrigerant Charge on page 26 to optimize the system charge using subcooling method. NOTE − Temperature sensor illustrated in figure 21 is not required for initial system weigh in charging. 1. Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging. WEIGH−IN CHARGING CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge: Amount specified on nameplate Additional charge specified per indoor unit match listed on page 28. Adjust amount. for variation in line set length listed on line set length table below. + Total Charge = + Refrigerant Charge per Line Set Length LIQUID LINE SET DIAMETER OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET (4.6 M) LINE SET* 3/8" (9.5 MM) 3 OUNCE PER 5’ (85 G PER 1.5 M) *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount. NOTE Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig. NOTE The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information. Figure 20. Using HFC−410A Weigh In Method Page 24 GAUGE SET MANIFOLD GAUGE SET HIGH LOW CONNECTIONS FOR OPTIMIZING SYSTEM CHARGE SUCTION PORT B TRUE CONNECTION OUTDOOR UNIT NOTE Refrigerant tank should be turned right−side−up to deliver vapor during charge optimizing procedure. REFRIGERANT TANK A CHARGE IN LIQUID PHASE DIGITAL SCALE TO LIQUID LINE SERVICE VALVE TEMPERATURE SENSOR (LIQUID LINE) C D TEMPERATURE SENSOR (USE FOR SUBCOOLING METHOD) INSIDE OUTDOOR UNIT A Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging. B Connect the manifold gauge set’s low pressure side to the true suction port. C Connect the manifold gauge set’s high pressure side to the liquid line service port. D Position temperature sensor on liquid line near liquid line service port (use only for subcooling method). Figure 21. Gauge Set Connections for Adding Refrigerant DISTRIBUTOR OUTDOOR UNIT NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW REVERSING VALVE CHECK / EXPANSION VALVE OUTDOOR COIL INDOOR UNIT BI−FLOW FILTER / DRIER MUFFLER TRUE SUCTION PORT LIQUID LINE SERVICE PORT VAPOR SERVICE PORT COMPRESSOR CHECK / EXPANSION VALVE NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use true suction port to measure vapor pressure during charging. INDOOR COIL Figure 22. Heat Pump Cooling Cycle Page 25 XP16 SERIES Optimizing System Refrigerant Charge This section provides instructions on optimizing the system charge. This section includes: S Optimizing procedure S Adjusting indoor airflow S Using subcooling method S Approved matched components, targeted subcooling (SC) values and add charge values S Normal operating pressures S Temperature pressures OPTIMIZING PROCEDURE 1. Move the low−side manifold gauge hose from the vapor line service valve to the true suction port (see figure 21). 2. Set the thermostat for either cooling or heating demand. Turn on power to the indoor unit and close the outdoor unit disconnect switch to start the unit. efficiency. Make any air flow adjustments before continuing with the optimizing procedure. 5. Use subcooling method to optimize the system charge (see figure 24). Adjust charge as necessary. ADJUSTING INDOOR AIRFLOW Heating Mode Indoor Airflow Check (Only use when indoor unit has electric heat) Indoor blower airflow (CFM) may be calculated by energizing electric heat and measuring: S Temperature rise between the return air and supply air temperatures at the indoor coil blower unit, S Measuring voltage supplied to the unit, S Measuring amperage being drawn by the heat unit(s). Then, apply the measurements taken in the following formula to determine CFM: Amps x Volts x 3.41 3. Allow unit to run for five minutes to allow pressures to stabilize. 4. Check the airflow as instructed under Adjusting Indoor Airflow to verify or adjust indoor airflow for maximum CFM = 1.08 x Temperature rise (F) Cooling Mode Indoor Airflow Check Check airflow using the Delta−T (DT) process using figure 23. ADJUSTING INDOOR AIRFLOW Temp. of air entering indoor coil ºF DT 24 23 22 21 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 Wet−bulb ºF 19 19 18 18 17 17 16 15 15 14 13 12 11 10 57 58 59 60 61 62 63 64 65 66 67 68 69 70 A Dry−bulb 80 78 76 74 24 23 22 21 24 23 22 21 23 22 21 20 23 22 21 19 22 21 20 19 22 21 19 18 22 20 19 17 20 19 18 16 19 18 17 16 18 17 16 15 17 16 15 14 16 15 14 13 15 14 13 12 B C 53º A 72º TDrop 19º air flow air flow DRY BULB B 64º DRY BULB 1. Determine the desired DTMeasure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle). 2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (TDrop) = A minus C. 3. Determine if fan needs adjustmentIf the difference between the measured TDrop and the desired DT (TDrop–DT) is within +3º, no adjustment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions: Cº TDrop – DT = ºF ACTION 53º 58º 62º All temperatures are expressed in ºF INDOOR COIL WET BULB 19 14 10 – – – 15 15 15 = = = 4 Increase the airflow −1 (within +3º range) no change −5 Decrease the airflow 4. Adjust the fan speedSee indoor unit instructions to in- crease/decrease fan speed. Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º. Figure 23. Checking Airflow over Indoor Coil Using Delta−T Formula Page 26 OPTIMIZE CHARGE USING SUBCOOLING METHOD 1. Check liquid and vapor line pressures. Compare pressures with either second−stage heat or cooling mode normal operating pressures listed in table 7. Table 7 is a general guide and expect minor pressures variations. Significant pressure differences may indicate improper charge or other system problem. USE COOLING MODE 60ºF (15ºC) 2. Decide whether to use cooling or heating mode based on current outdoor ambient temperature: A Use COOLING MODE when: S S Outdoor ambient temperature is 60°F (15.5°C) and above. Indoor return air temperature range is between 70 to 80°F (21−27°C). This temperature range is what the target subcooling values are base upon in tables 3 through 6. If indoor return air temperature is not within reference range, set thermostat to cooling mode and a setpoint of 68ºF (20ºC). This should place the outdoor unit into second−stage (high−capacity) cooling mode. When operating and temperature pressures have stabilized, continue to step 3. USE HEATING MODE B Use HEATING MODE when: S S Outdoor ambient temperature is 59°F (15.0°C) and below. Indoor return air temperature range is between 65−75°F (18−24°C). This temperature range is what the target subcooling values are base upon in tables 3 through 6. If indoor return air temperature is not within reference range, set thermostat to heating mode and a setpoint of 77ºF (25ºC). This should place the outdoor unit into second−stage (high−capacity) heating mode. When operating and temperature pressures have stabilized, continue to step 3. 3. Read the liquid line pressure; then find its corresponding temperature pressure listed in table 8 and record it in the SATº space to the left. 4. Read the liquid line temperature; record in the LIQº space to the left. SATº 5. Subtract LIQº temperature from SATº temperature to determine subcooling; record it in SCº space to the left.. LIQº – SCº = 6. Compare SCº results with tables 3 through 6 (either Heating or Cooling mode column), also consider any additional charge required for line set lengths longer than 15 feet and/or unit matched component combinations (Add Charge column). 7. If subcooling value is: A B GREATER than shown for the applicable unit match component, REMOVE refrigerant; LESS than shown for the applicable unit match component, ADD refrigerant. 8. If refrigerant is added or removed, repeat steps 3 through 6 to verify charge. 9. Close all manifold gauge set valves and disconnect gauge set from outdoor unit. 10. Replace the stem and service port caps and tighten as specified in Operating Service Valves on page 2. 11. Recheck voltage while the unit is running. Power must be within range shown on the nameplate. Figure 24. Using HFC−410A Subcooling Method Second Stage (High Capacity) Page 27 XP16 SERIES APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND ADD CHARGE VALUES Listed below are the approved matched system components (air handlers and indoor coils), targeted subcooling and add charge values for the XP16. This information is also listed on the unit charging sticker located on the outdoor unit access panel. Subcooling values listed in the following tables are based on outdoor ambient air temperature of: S 60°F (15.5°C) and above for cooling mode S 59°F (15.0°C) and below for heating mode. Table 3. XP16−024−230 Indoor Air Handers and Coils Heating Mode +5ºF Cooling Mode +1ºF Subcooling *Add Charge lb. oz. Table 5. XP16−048−230 Indoor Air Handers and Coils Heating Mode +5ºF CBX26UH−048−230 10 CBX27UH−048−230 CBX27UH−060−230 Cooling Mode +1ºF Subcooling *Add Charge lbs. oz. 8 1 4 19 9 1 4 13 14 3 3 CBX32M−048 19 9 1 4 CBX26UH−024 45 6 0 15 CBX32M−060 14 9 1 11 CBX27UH−024−230 20 7 0 9 CBX32MV−048 19 9 1 4 CBX27UH−030−230 17 7 1 3 CBX32MV−060 14 9 1 11 CBX32MV−024/030 20 7 0 9 CBX32MV−068 9 8 1 11 CBX32MV−036 17 7 1 3 CBX40UHV−048 19 9 1 4 CBX40UHV−024 17 7 1 3 CBX40UHV−060 14 9 1 11 CBX40UHV−030 17 7 1 3 CH23−68 24 10 1 12 CBX40UHV−036 17 7 1 3 CH33−49C 19 9 2 5 CH33−31B 31 8 1 12 CH33−50/60C 19 9 2 5 CR33−30/36A/B/C 45 4 0 0 CH33−60D 13 8 0 0 CX34−31A/B 24 7 1 11 CH33−62D 11 9 1 4 CX34−38A/B 18 8 1 10 CR33−50/60C 15 7 0 10 CR33−60D 15 7 0 10 CX34−60D 14 8 1 0 CX34−62D 9 9 1 6 CX34−62C 8 9 1 9 Table 4. XP16−036−230 Indoor Air Handers and Coils Heating Mode +5ºF Cooling Mode +1ºF Subcooling *Add Charge lbs. oz. CBX26UH−036 50 5 0 0 CBX27UH−036−230 22 7 0 9 CBX27UH−042−230 24 11 3 0 CBX32M−036 22 7 0 9 CBX32MV−036 22 7 0 9 CBX32MV−048 24 11 3 0 CBX40UHV−030 22 7 0 9 CBX40UHV−036 22 7 0 9 CBX40UHV−042 24 11 3 0 CBX40UHV−048 24 11 3 0 CH33−43B 13 10 2 7 CH33−48C 37 11 2 11 CH33−43C 37 11 2 11 CR33−48B/C 49 7 0 9 CX34−43B/C 29 9 2 11 CX34−50/60C 29 9 2 11 Table 6. XP16−060−230 Indoor Air Handers and Coils Heating Mode +5ºF Cooling Mode +1ºF Subcooling *Add Charge lbs. oz. CBX26UH−060 20 9 4 13 CBX27UH−060−230 10 6 2 3 CBX32M−060 17 6 1 12 CBX32MV−060 17 6 1 12 CBX32MV−068 15 7 2 1 CBX40UHV−060 17 6 1 12 CH23−682 37 9 2 10 CH33−50/60C 33 8 1 0 CH33−62D 15 7 1 4 CR33−50/60C 24 7 0 0 CR33−60D 24 7 0 0 CX34−62C 21 9 2 16 CX34−62D 13 7 1 4 *Amount of charge required in additional to charge shown on unit nameplate. (Remember to consider line set length difference.) Page 28 NORMAL OPERATING PRESSURES Use the following tables to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system. TEMPERATURE PRESSURES Compute subcooling by determining saturated condensing temperature from temperature pressure chart. Subtract from liquid temperature entering TXV. Table 8. HFC−410A Temperature (°F) − Pressure (Psig) °F Psig °F Psig °F Psig °F Psig 32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8 Table 7. Normal Operating Pressures* 34 105.0 65 184.3 96 299.4 127 457.6 Normal Operating Pressures − Cooling 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 481.6 39 115.8 70 200.6 101 321.8 132 487.8 Typical pressures only, expressed in psig (liquid +/− 10 and vapor +/− 5 psig); matched indoor component (air handler or coil), indoor air quality, and indoor load will cause the pressures to vary. XP16 F (C)** −024 Liq −036 Vap Liq −048 Vap Liq −060 Vap Liq Vap First Stage (Low Capacity) Pressure 65 (18.3) 226 144 220 141 224 143 230 137 75 (23.9) 260 145 254 144 259 143 267 139 40 118.0 71 203.9 102 326.4 133 494.0 85 (29.4) 301 148 295 148 302 147 311 141 41 120.3 72 207.2 103 331.0 134 500.2 95 (35.0) 346 151 340 150 346 149 357 144 42 122.6 73 210.6 104 335.7 135 506.5 105 (40.6) 396 153 389 153 396 152 398 147 43 125.0 74 214.0 105 340.5 136 512.9 115 (46.1) 44 127.3 75 217.4 106 345.3 137 519.3 451 156 444 156 450 155 453 149 45 129.7 76 220.9 107 350.1 138 525.8 46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 110 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3 Second Stage (High Capacity) Pressure 65 (18.3) 241 140 232 129 238 138 232 131 75 (23.9) 279 142 269 136 278 140 276 133 85 (29.4) 321 144 312 140 321 142 320 136 95 (35.0) 369 146 346 142 372 144 367 138 50 142.2 81 239.0 112 375.1 143 559.1 105 (40.6) 421 148 409 145 424 147 421 141 51 144.8 82 242.7 113 380.2 144 565.9 115 (46.1) 480 151 465 148 481 149 479 144 52 147.4 83 246.5 114 385.4 145 572.8 53 150.1 84 250.3 115 390.7 146 579.8 54 152.8 85 254.1 116 396.0 147 586.8 55 155.5 86 258.0 117 401.3 148 593.8 56 158.2 87 262.0 118 406.7 149 601.0 57 161.0 88 266.0 119 412.2 150 608.1 58 163.9 89 270.0 120 417.7 151 615.4 59 166.7 90 274.1 121 423.2 152 622.7 60 169.6 91 278.2 122 428.8 153 630.1 61 172.6 92 282.3 123 434.5 154 637.5 62 175.4 93 286.5 124 440.2 155 645.0 Normal Operating Pressures − Heating First Stage (Low Capacity) Pressure 50 (10) 312 112 350 115 336 114 385 108 60 (15.5) 330 130 372 136 363 135 414 126 Second Stage (High Capacity) Pressure 20 (−7.0) 299 64 321 61 289 57 332 59 30 (−1.0) 312 79 347 74 294 69 349 67 40 (4.4) 325 93 367 90 321 80 361 75 50 (10) 344 110 387 110 341 110 383 85 60 (15.5) 358 128 395 131 361 128 425 122 ** Temperature of air entering outdoor coil. Page 29 XP16 SERIES UNIT COMPONENTS System Operation IMPORTANT Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRESSOR. This section addresses: S Unit components (sensors, temperature switch, pressure switches and demand defrost control) S Second−stage operation Demand Defrost Control (A108) The demand defrost control measures differential temperatures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates when the defrost system starts and after each system defrost cycle. The demand defrost control’s: components are shown in figure 25. S Demand defrost control connections, jumpers and LED locations are shown in figure 25. S Demand defrost control connections, jumpers and LED descriptions are listed on table 9. S Demand defrost control status, fault and lockout LEDs are listed in table 10. TEST PINS (P1) LOW AMBIENT THERMOSTAT PINS (P3) DEFROST TERMINATION PIN SETTINGS (P1) SENSOR PLUG IN (COIL AND AMBIENT SENSORS) (P4) DIAGNOSTIC LEDS (DS1 AND DS2) DELAY PINS (P5) 24V TERMINAL STRIP CONNECTIONS (P2) REVERSING VALVE (O OUT) PRESSURE SWITCH CIRCUIT CONNECTIONS Note − Component locations vary by board manufacturer. Figure 25. Demand Defrost Control (A108) Page 30 Table 9. Demand Defrost Control (A108) Inputs, Outputs and Configurable Settings Control Locations Control Label or Description Purpose Function P1 TEST Test Mode See Test Mode on page 39 for further details. 50, 70, 90, 100 Defrost Temperature Termination Shunt (Jumper) Pins The demand defrost control as illustrated in figure 25 has valid selections which are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C). W1 24VAC Thermostat Input / Output 24VAC input / output from indoor thermostat to indoor unit. C 24VAC Common 24VAC common L Thermostat Service Light Thermostat service light connection. R 24VAC 24VAC Y2 Thermostat Input Controls the second stage operation of the unit. O Thermostat Input Reversing valve solenoid. Y1 Thermostat Input Controls the operation of the unit. 55, 50, 45, 40 Low Ambient Thermostat Provides selection of the Y2 compressor lock−in temperature. Valid Pins options are 40, 45, 50 and 55 degrees Fahrenheit. DIS−YEL Coil Sensor (P4−5) Ground connection for outdoor coil temperature sensor. (P4−6) Connection for outdoor coil temperature sensor. AMB−BLACK Ambient Sensor (P4−3) Ground connection for outdoor ambient temperature sensor. (P4−4) Connection for outdoor ambient temperature sensor. COIL−BROWN Discharge Sensor No discharge sensor is used; replaced by 10K resistor. P1 P2 P3 P4 P5 DELAY The demand defrost control has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins. Delay Mode NOTE − The 30 second off cycle is NOT functional when TEST pins on P1 are jumpered. P6 TST, PS DF, C, R, O, Y1, Y2 DS1 RED LED Factory Test Connectors No field use. Diagnostic LED Valid states for demand defrost control two LEDs are OFF, ON and FLASHING which indicate diagnostics conditions that are described in table 10. DS2 GREEN LED FAN TWO CONNECTORS Condenser Fan Operation These two connections provide power for the condenser fan. O OUT O OUT 24 VAC output 24 VAC output connection for reversing valve. When the low pressure switch trips, the demand defrost control will cycle off the compressor, and the strike counter in the demand defrost control will count one strike. The low pressure switch is ignored under the following conditions: LO−PS LO−PS Low−Pressure Switch S S S S during the defrost cycle and 90 seconds after the termination of defrost when the average ambient sensor temperature is below 0°F (−18°C) for 90 seconds following the start up of the compressor during TEST mode Y2 OUT Y2 OUT 24 VAC Output 24 VAC output for second stage compressor solenoid. Y1 OUT Y1 OUT 24 VAC Common Output 24 VAC common output, switched for enabling compressor contactor. HS−PS HS−PS High−Pressure Switch When the high pressure switch trips, the demand defrost control will cycle off the compressor, and the strike counter in the demand defrost control will count one strike. L L Service Light Output 24VAC service light output. 24V 24V 24 Volt output 24VAC typically used to supply power to the Lennox System Operation Monitor (LSOM). Not used in this system. Page 31 XP16 SERIES DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS The state (Off, On, Flashing) of two LEDs on the demand defrost control (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 10. Table 10. Demand Defrost Control (A108) Diagnostic LEDs DS1 and DS2 System Status, Fault and Lockout Codes DS2 Green DS1 Red Condition/Code Possible Cause(s) Status Power problem No power (24V) to demand defrost control terminals R and C or demand defrost control failure. Simultaneous SLOW Flash Status Normal operation Unit operating normally or in standby mode. None required. Alternating SLOW Flash Status 5−minute anti−short cycle delay Initial power up, safety trip, end of room thermostat demand. None required (jumper TEST pins to override) Simultaneous FAST Flash Fault Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Demand defrost control will revert to time/temperature defrost operation. (System will still heat or cool). Alternating FAST Flash Fault Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Demand defrost control will not perform demand or time/temperature defrost operation. (System will still heat or cool). ON ON Fault Demand Defrost Control Failure Indicates that demand defrost control has internal component failure. Cycle 24VAC power to demand defrost control. If code does not clear, replace demand defrost control. OFF SLOW Flash Fault Low Pressure Fault 1 OFF ON Lockout Low Pressure Lockout SLOW Flash OFF Fault High Pressure Fault ON OFF Lockout High Pressure Lockout SLOW Flash ON Fault FAST Flash ON Lockout OFF Fast Flash Fault Fast Flash OFF Lockout OFF OFF Type Solution 1 2 Check control transformer power (24V). If power is available to demand defrost control and LED(s) do not light, replace demand defrost control. 1 Restricted air flow over indoor or outdoor coil. 2 Improper refrigerant charge in system. 3 Improper metering device installed or incorrect operation of metering device. 4 Incorrect or improper sensor location or connection to system. Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws. 2 Check system charge using subcooling method. 3 Check system operating pressures and compare to unit subcooling tables in this instruction or located on unit access panel. 4 Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements. Discharge Line Temperature This code detects shorted sensor or high discharge temperatures. If the discharge Fault line temperature exceeds a temperature of 285ºF (140ºC) during compressor operation, the demand defrost control will de−energize the compressor contactor Discharge Line Temperature output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC). Lockout Discharge Sensor Fault Discharge Sensor Lockout The demand defrost control detects open sensor or out of temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the demand defrost control will count one fault. After 5 faults, the demand defrost control will lockout. (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT) Page 32 High Pressure Switch (S4) When the high pressure switch trips, the demand defrost control will cycle off the compressor, and the strike counter in the demand defrost control will count one strike. High Pressure (auto reset) − trip at 590 psig, reset at 418. Low Pressure Switch (S87) When the low pressure switch trips, the demand defrost control will cycle off the compressor, and the strike counter in the demand defrost control will count one strike. Low pressure switch (auto reset) − trip at 25 psig, reset at 40 psig. The low pressure switch is ignored under the following conditions: S During the defrost cycle and 90 seconds after the termination of defrost S When the average ambient sensor temperature is below 15° F (−9°C) S For 90 seconds following the start up of the compressor S During test mode Ambient Sensor (RT13) The ambient sensor considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the demand defrost control will not perform demand defrost operation. The demand defrost control will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition. Coil Sensor (RT21) Coil SensorThe coil temperature sensor considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the demand defrost control will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition. High Discharge Temperature Sensor (RT28) If the discharge line temperature exceeds a temperature of 285°F (140°C) during compressor operation, the demand defrost control will de−energize the compressor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute anti−short cycle delay has been satisfied. This sensor has two fault and lockout codes: 1. If the demand defrost control recognizes five high discharge line temperature faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. This code detects shorted sensor or high discharge temperatures. Code on demand defrost control is Discharge Line Temperature Fault and Lockout. 2. If the demand defrost control recognizes five temperature sensor range faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. The demand defrost control detects open sensor or out-of-temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the demand defrost control will count one fault. After five faults, the demand defrost control will lockout. Code on demand defrost control is Discharge Sensor Fault and Lockout. The discharge line sensor, which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a ½" refrigerant discharge line. NOTE − Within a single room thermostat demand, if 5−strikes occur, the demand defrost control will lockout the unit. demand defrost control 24 volt power R must be cycled OFF or the TEST pins on demand defrost control must be shorted between 1 to 2 seconds to reset the demand defrost control. Crankcase Heater (HR1) and Crankcase Thermostat Switch (S40) The reference models are equipped with a 70 watt, belly band type crankcase heater. HR1 prevents liquid from accumulating in the compressor. HR1 is controlled by a thermostat located on the liquid line. When liquid line temperature drops below 50° F the thermostat closes energizing HR1. The thermostat will open, de−energizing HR1 once liquid line temperature reaches 70° F . Liquid Line Bi−Flow Filter Drier The unit is equipped with a large−capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity. The replacement filter drier must be suitable for use with HFC−410A refrigerant. The replacement filter drier must be suitable for use with HFC−410A refrigerant. SECOND−STAGE OPERATION If the demand defrost control (A108) receives a call for second−stage compressor operation Y2 in heating or cooling mode and the first-stage compressor output is active, the second-stage compressor solenoid output will be energized. If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock−in temperature, the second-stage compressor solenoid output will be energized without the Y2 input. If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock−in temperature of 40°F (4.5°C) will be used. The demand defrost control de−energizes the second-stage compressor solenoid output immediately when the Y2 signal is removed or the outdoor ambient temperature is 5°F above the selected compressor lock−in temperature, or the first-stage compressor output is de−energized for any reason. Page 33 XP16 SERIES Defrost System This section addresses: S Emergency Heat S Defrost System Overview S Defrost Control Connections, Jumper Settings and Features S Operational Mode Overview (Calibration, Normal and Defrost) S Defrost Cycle Actuation EMERGENCY HEAT (AMBER LIGHT) An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode. Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging. DEFROST SYSTEM OVERVIEW The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation. NOTE − The demand defrost control accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the demand defrost control initiates defrost cycles. DEFROST CONTROL CONNECTIONS, JUMPERS SETTINGS AND FEATURES Pressure Switch 5−Strike Lockout The internal control logic of the demand defrost control counts the pressure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition. The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the demand defrost control or by shorting the TEST pins between 1 to 2 seconds. All timer functions (run times) will also be reset. If a pressure switch opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes. Demand Defrost Control Pressure Switch Connections The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the demand defrost control on the LO−PS and HI−PS terminals, respectively. Demand Defrost Control Sensors Sensors connect to the demand defrost control through a field-replaceable harness assembly that plugs into the demand defrost control as illustrated in figure 1. Through the sensors, the demand defrost control detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Testing Demand Defrost Control Sensors Sensor resistance values can be checked by ohming across pins shown in table 11. Table 11. Sensor Temperature /Resistance Range Pins/W ire Color Sensor Temperature Range °F (°C) Resistance values range (ohms) Outdoor −35 (−37) to 120 (48) 280,000 to 3750 3&4 (Black) Coil −35 (−37) to 120 (48) 280,000 to 3750 5&6 (Brown) Discharge (if applicable) 24 (−4) to 350 (176) 41,000 to 103 1&2 (Yellow) Note: Sensor resistance increases as sensed temperature decreases. Tables 12 and 13 shows how the resistance varies as the temperature changes for various types of sensors. NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 11, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced. Defrost Temperature Termination Jumper Settings (P1) The demand defrost control selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If temperature shunt is not installed, default termination temperature is 90°F (32°C). Test Pins (P1) Function Placing the jumper on the field test pins (P1) allows the technician to: S Clear short cycle lockout S Clear five−strike fault lockout S Cycle the unit in and out of defrost mode S Place the unit in defrost mode to clear the coil See figure 27 for flowchart of test pin (P1) operations. Page 34 Compressor Delay Mode (P5) The demand defrost control has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins. NOTE − The 30 second off cycle is NOT functional when jumpering the TEST pins. 1. Frost Detection If the compressor runs longer than 30 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the demand defrost control, a defrost cycle will be initiated. 2. Time If six hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle. OPERATIONAL MODE OVERVIEW The demand defrost control has three basic operational modes. Those modes are: 1. Calibration Mode The demand defrost control is considered uncalibrated when power is applied to the demand defrost control, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode (see figure 26 for further details). 2. Normal Mode The demand defrost control monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required. Calibration of the demand defrost control occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle. 3. Defrost Mode The following paragraphs provide a detailed description of the defrost system operation. Actuation When the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the demand defrost control logs the compressor run time. If the demand defrost control is not calibrated, a defrost cycle will be initiated after 30 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all other) defrost cycle(s). DEFROST CYCLE ACTUATION The demand defrost control initiates a defrost cycle based on either frost detection or time. Calibration success depends on stable system temperatures during the 20−minute calibration period. If the demand defrost control fails to calibrate, another defrost cycle will be initiated after 45 minutes of heating mode compressor run time. Once the demand defrost control is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control or after six hours of heating mode compressor run time has been logged since the last defrost cycle. Termination The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 30 minutes of run time. Page 35 XP16 SERIES DEFROST CONTROL (A108) CALIBRATION MODE SEQUENCE Occurs after power up and cooling operation, or if the coil temperature exceeds the termination temperature while in Heat Mode. Demand defrost control defaults to 30 minute Time / Temperature Mode Reset Compressor Runtime / Reset Three / Five Strike Counter DEMAND MODE Accumulate compressor runtime of more than 30 minutes while coil temperature is below 35° F (2°C). When the accumulated compressor time exceeds six (6) hours or if the coil sensor indicates frost is present on coil, go to Defrost. THIRTY (30) MINUTE TIME / TEMPERATURE MODE 45 MINUTE TIME/TEMPERATURE MODE Accumulate compressor runtime while coil temperature is below 35° F (2°C). When the accumulated compressor time exceeds 30 minutes go to Defrost. Accumulate compressor runtime while coil temperature is below 35° F (2°C). When the accumulated compressor time exceeds 45 minutes go to Defrost. DEFROST S S S Outdoor Fan OFF Reversing Valve ON W1 line ON Monitor coil temperature and time in defrost mode. HOW DID DEFROST TERMINATE? Coil temperature was above 35°F (2°C) for four (4) minutes. of the 14−minute defrost OR reached defrost termination temperature. Defrosted for 14−minute without the coil temperature going above 35°F (2°C) for four (4) minutes and coil did not reach termination temperature. DEFROST TERMINATION DEFROST TERMINATION S S S S S S S S Compressor runtime counter RESET Outdoor Fan ON Reversing Valve OFF W1 line OFF Compressor runtime counter RESET Outdoor Fan ON Reversing Valve OFF W1 line OFF Attempt to Calibration Temperature measurements are not taken for the first few minutes of each heat demand. This is to allow coil temperatures to stabilize. demand defrost control has a maximum of 20 minutes of accumulated compressor runtime in heat mode to calibrate demand defrost control This may involve more than one heating demand. YES Calibration occurred Was stable coil temperature attained within 20 minutes? Figure 26. Defrost Calibration Page 36 NO Demand defrost control reverts to 45 minute time / temperature. Table 12. Ambient (RT13) and Coil (RT21) Sensors Temperature / Resistance Range Degrees Fahrenheit 136.3 133.1 130.1 127.3 124.7 122.1 119.7 117.5 115.3 113.2 111.2 109.3 107.4 105.6 103.9 102.3 100.6 99.1 97.6 96.1 94.7 93.3 92.0 90.6 89.4 88.1 86.9 85.7 84.5 83.4 82.3 81.2 80.1 79.0 78.0 77.0 76.0 75.0 74.1 73.1 72.2 71.3 70.4 69.5 68.6 67.7 66.9 66.0 65.2 64.4 63.6 62.8 62.0 61.2 60.5 59.7 59.0 58.2 57.5 Resistance 2680 2859 3040 3223 3407 3592 3779 3968 4159 4351 4544 4740 4937 5136 5336 5539 5743 5949 6157 6367 6578 6792 7007 7225 7444 7666 7890 8115 8343 8573 8806 9040 9277 9516 9757 10001 10247 10496 10747 11000 11256 11515 11776 12040 12306 12575 12847 13122 13400 13681 13964 14251 14540 14833 15129 15428 15730 16036 16345 Degrees Fahrenheit 56.8 56.0 55.3 54.6 53.9 53.2 52.5 51.9 51.2 50.5 49.9 49.2 48.5 47.9 47.3 46.6 46.0 45.4 44.7 44.1 43.5 42.9 42.3 41.7 41.1 40.5 39.9 39.3 38.7 38.1 37.5 37.0 36.4 35.8 35.2 34.7 34.1 33.5 33.0 32.4 31.9 31.3 30.7 30.2 29.6 29.1 28.6 28.0 27.5 26.9 26.4 25.8 25.3 24.8 24.2 23.7 23.2 22.6 22.1 Resistance 16657 16973 17293 17616 17942 18273 18607 18945 19287 19633 19982 20336 20695 21057 21424 21795 22171 22551 22936 23326 23720 24120 24525 24934 25349 25769 26195 26626 27063 27505 27954 28408 28868 29335 29808 30288 30774 31267 31766 32273 32787 33309 33837 34374 34918 35471 36031 36600 37177 37764 38359 38963 39577 40200 40833 41476 42130 42794 43468 Degrees Fahrenheit 21.6 21.0 20.5 20.0 19.4 18.9 18.4 17.8 17.3 16.8 16.3 15.7 15.2 14.7 14.1 13.6 13.1 12.5 12.0 11.5 11.0 10.4 9.9 9.3 8.8 8.3 7.7 7.2 6.7 6.1 5.6 5.0 4.5 3.9 3.4 2.8 2.3 1.7 1.2 0.6 0.0 −0.5 −1.1 −1.7 −2.2 −2.8 −3.4 −4.0 −4.6 −5.2 −5.7 −6.3 −6.9 −7.5 −8.2 −8.8 −9.4 −10.0 −10.6 Resistance 44154 44851 45560 46281 47014 47759 48517 49289 50074 50873 51686 52514 53356 54215 55089 55979 56887 57811 58754 59715 60694 61693 62712 63752 64812 65895 67000 68128 69281 70458 71661 72890 74147 75431 76745 78090 79465 80873 82314 83790 85302 86852 88440 90068 91738 93452 95211 97016 98870 100775 102733 104746 106817 108948 111141 113400 115727 118126 120600 Degrees Fahrenheit −11.3 −11.9 −12.6 −13.2 −13.9 −14.5 −15.2 −15.9 −16.5 −17.2 −17.9 −18.6 −19.3 −20.1 −20.8 −21.5 −22.3 −23.0 −23.8 −24.6 −25.4 −26.2 −27.0 −27.8 −28.7 −29.5 −30.4 −31.3 −32.2 −33.2 −34.1 −35.1 −36.1 −37.1 −38.2 −39.2 Resistance 123152 125787 128508 131320 134227 137234 140347 143571 146913 150378 153974 157708 161588 165624 169824 174200 178762 183522 188493 193691 199130 204829 210805 217080 223677 230621 237941 245667 253834 262482 271655 281400 291774 302840 314669 327343 Page 37 XP16 SERIES Table 13. High Discharge Sensor (RT28) Temperature / Resistance Range Degrees Fahrenheit 303.1 298.1 293.4 289.0 284.8 280.9 277.1 273.6 270.2 267.0 263.9 260.9 258.1 255.3 252.7 250.1 247.7 245.3 243.0 240.8 238.6 236.5 234.4 232.4 230.5 228.6 226.7 224.9 223.2 221.5 219.8 218.1 216.5 214.9 213.4 211.9 210.4 208.9 207.5 206.0 204.6 203.3 201.9 200.6 199.3 198.0 196.8 195.5 194.3 193.1 191.9 190.7 189.5 188.4 187.2 Resistance 183 195 207 220 232 245 258 270 283 297 310 323 336 350 364 378 391 405 420 434 448 463 478 492 507 523 538 553 569 584 600 616 632 649 665 682 698 715 732 750 767 785 803 821 839 857 876 894 913 932 952 971 991 1011 1031 Degrees Fahrenheit 186.1 185.0 183.9 182.8 181.8 180.7 179.6 178.6 177.6 176.6 175.5 174.6 173.6 172.6 171.6 170.6 169.7 168.7 167.8 166.9 165.9 165.0 164.1 163.2 162.3 161.4 160.5 159.7 158.8 157.9 157.1 156.2 155.3 154.5 153.6 152.8 152.0 151.1 150.3 149.5 148.7 147.9 147.1 146.2 145.4 144.6 143.8 143.0 142.3 141.5 140.7 139.9 139.1 138.3 137.6 Resistance 1052 1072 1093 1114 1135 1157 1179 1201 1223 1245 1268 1291 1315 1338 1362 1386 1411 1435 1460 1486 1511 1537 1563 1590 1617 1644 1672 1699 1728 1756 1785 1815 1845 1875 1905 1936 1968 1999 2032 2064 2098 2131 2165 2200 2235 2270 2306 2343 2380 2418 2456 2495 2534 2574 2615 Degrees Fahrenheit 136.8 136.0 135.2 134.5 133.7 132.9 132.2 131.4 130.6 129.9 129.1 128.4 127.6 126.8 126.1 125.3 124.6 123.8 123.1 122.3 121.6 120.8 120.1 119.3 118.5 117.8 117.0 116.3 115.5 114.8 114.0 113.2 112.5 111.7 111.0 110.2 109.4 108.7 107.9 107.1 106.4 105.6 104.8 104.0 103.3 102.5 101.7 100.9 100.1 99.3 98.5 97.7 96.9 96.1 95.3 Page 38 Resistance 2656 2698 2740 2783 2827 2872 2917 2963 3010 3057 3105 3154 3204 3255 3307 3359 3413 3467 3523 3579 3637 3695 3755 3816 3877 3940 4005 4070 4137 4205 4274 4345 4418 4491 4567 4644 4722 4802 4884 4968 5054 5141 5231 5323 5416 5512 5610 5711 5814 5920 6028 6139 6253 6370 6489 Degrees Fahrenheit 94.5 93.6 92.8 92.0 91.2 90.3 89.5 88.6 87.8 86.9 86.0 85.2 84.3 83.4 82.5 81.6 80.7 79.8 78.8 77.9 76.9 76.0 75.0 74.1 73.1 72.1 71.1 70.0 69.0 68.0 66.9 65.8 64.7 63.6 62.5 61.3 60.2 59.0 57.8 56.6 55.3 54.0 52.7 51.4 50.0 48.6 47.2 45.7 Resistance 6613 6739 6869 7002 7139 7281 7426 7575 7729 7888 8051 8220 8394 8574 8759 8951 9149 9354 9566 9786 10013 10250 10495 10749 11014 11289 11575 11873 12184 12509 12848 13202 13573 13961 14368 14796 15246 15719 16218 16744 17301 17891 18516 19180 19887 20641 21448 22311 TEST Placing the jumper on the field test pins (P1) allows the technician to: S S S S Clear short cycle lockout Clear five−strike fault lockout Cycle the unit in and out of defrost mode Place the unit in defrost mode to clear the coil When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal operation. The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied. Y1 Active Place a jumper on TEST pins for longer than one second but less than two seconds. Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating. Place a jumper on TEST pins for more than two seconds. Clears any short cycle lockout and five strike fault lockout function, if applicable. ACTIVE INACTIVE O Line Status If in COOLING Mode If in DEFROST Mode If in HEATING Mode No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied. The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 45 minute test. If no ambient or coil sensor fault exist, unit will go into DEFROST MODE. If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE. NOTE Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Control. If jumper on TEST pins remains in place for more than five seconds. If jumper on TEST pins is removed before a maximum of five seconds. The unit will return to HEAT MODE un−calibrated with defrost timer set for 34 minutes. The unit will remain in DEFROST MODE until termination on time or temperature. Figure 27. Test Pin (P1) Functions Page 39 XP16 SERIES 12. After testing is complete, return unit to original set up. Two−Stage Modulation Compressors Checks Maintenance Use this checklist on page 42 to verify part-load and full-load capacity operation of two-stage modulation compressors. TOOLS REQUIRED S Refrigeration gauge set S Digital volt/amp meter S Electronic temperature thermometer S On-off toggle switch DEALER Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows: Outdoor Unit 1. Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning. 2. Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed. 3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks. 4. Check all wiring for loose connections. 5. Check for correct voltage at unit (unit operating). 6. Check amp draw on outdoor fan motor. Motor Nameplate:_________ Actual:__________. IMPORTANT This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant charge. All components in the system must be functioning proper to correctly perform compressor modulation operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings). PROCEDURE NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing). 1. Turn main power OFF to outdoor unit. 2. Adjust room thermostat set point 5ºF above the room temperature. 3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor. 7. Inspect drain holes in coil compartment base and clean if necessary. NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked. Outdoor Coil It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts) S S 4. Turn toggle switch OFF and install switch in series with Y2 wire from room thermostat. 5. Cycle main power ON. 6. Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes). 7. Record all of the readings for the Y1 demand. 8. Close switch to energize Y2 demand. Verify power is going to compressor solenoid. 9. Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes). 10. Record all of the readings with the Y1 and Y2 demand. 11. If temperatures and pressures change in the direction noted in Two−Stage Modulation Compressor Field Operational Checklist on page 42, the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is performed, the compressor is not modulating between low and high capacity and replacement is necessary). Page 40 Outdoor Coil The outdoor coil may be flushed with a water hose. Outdoor Coil (Sea Coast) Moist air in ocean locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract. Indoor Unit 1. Clean or change filters. 2. Lennox blower motors are prelubricated and permanently sealed. No more lubrication is needed. 3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure. 4. Belt Drive Blowers − Check belt for wear and proper tension. 5. Check all wiring for loose connections. 6. Check for correct voltage at unit. (blower operating) 7. Check amp draw on blower motor. Motor Nameplate:_________ Actual:__________. Indoor Coil 1. Clean coil if necessary. 2. Check connecting lines, joints and coil for evidence of oil leaks. 3. Check condensate line and clean if necessary. HOMEOWNER Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner. IMPORTANT Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit. Outdoor Coil The outdoor unit must be properly maintained to ensure its proper operation. S Please contact your dealer to schedule proper inspection and maintenance for your equipment. S Make sure no obstructions restrict airflow to the outdoor unit. S Grass clippings, leaves, or shrubs crowding the unit can cause the unit to work harder and use more energy. S Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit. Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. Routine Maintenance In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. 1. Air Filter Ask your Lennox dealer to show you where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed. 2. Disposable Filter Disposable filters should be replaced with a filter of the same type and size. NOTE If you are unsure about the filter required for your system, call your Lennox dealer for assistance. 3. Reusable Filter Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille. NOTE The filter and all access panels must be in place any time the unit is in operation. 4. Indoor Unit The indoor unit’s evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.) Thermostat Operation See the thermostat homeowner manual for instructions on how to operate your thermostat. Heat Pump Operation Your new Lennox heat pump has several characteristics that you should be aware of: S Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space. S Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45F (7C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost. S During the defrost cycle, you may notice steam rising from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle. Extended Power Outage The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation. If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the EMERGENCY HEAT setting to obtain temporary heat without the risk of serious damage to the heat pump. In EMERGENCY HEAT mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume. Preservice Check If your system fails to operate, check the following before calling for service: S Verify room thermostat settings are correct. S Verify that all electrical disconnect switches are ON. S Check for any blown fuses or tripped circuit breakers. S Verify unit access panels are in place. S Verify air filter is clean. S If service is needed, locate and write down the unit model number and have it handy before calling. Page 41 XP16 SERIES Accessories For update−to−date information, see any of the following publications: S S S Lennox XP16 Engineering Handbook Lennox Product Catalog Lennox Price Book Checklists Two−Stage Modulation Compressors Field Operational Checklist Unit Readings Y1 − First-Stage Expected results during Y2 demand (Toggle switch On) COMPRESSOR Voltage Same Amperage Higher OUTDOOR UNIT FAN MOTOR Amperage Same or Higher TEMPERATURE Ambient Same Outdoor Coil Discharge Air Higher Compressor Discharge Line Higher Indoor Return Air Same Indoor Coil Discharge Air Lower PRESSURES Suction (Vapor) Lower Liquid Higher Page 42 Y2 − Second-Stage XP16 Start−Up and Performance Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial Notes: START UP CHECKS Refrigerant Type: 1st Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts 2nd Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts Outdoor Unit Fan Full Load Amps Actual Amps: 1st Stage 2nd Stage COOLING MODE Suction Pressure: 1st Stage: 2nd Stage: Liquid Pressure: 1st Stage: 2nd Stage: Supply Air Temperature: 1st Stage: 2nd Stage: Temperature: Ambient: Return Air: System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach temperatures.) A Subcooling: B Saturated Condensing Temperature (A) minus Liquid Line Temperature (B) A Approach: Indoor Coil Temperature Drop (18 to 22°F) = B Liquid Line Temperature (A) minus Outdoor Air Temperature (B) A APPROACH = B Return Air Temperature (A) minus Supply Air Temperature (B) SUBCOOLING COIL TEMP DROP = Page 43 XP16 SERIES
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes Author : LWM02 Create Date : 2010:12:17 08:25:42-06:00 Modify Date : 2010:12:17 08:25:42-06:00 XMP Toolkit : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04 Creator Tool : BroadVision, Inc. Format : application/pdf Title : 506640a Creator : LWM02 Producer : Acrobat Distiller 9.4.0 (Windows) Document ID : uuid:8a8d7f41-173f-49c7-a78e-8b567dfdd58b Instance ID : uuid:9deded30-9ae4-4498-906f-31d77646bb1f Page Count : 43EXIF Metadata provided by EXIF.tools