Lenox Air Conditioner Elite Series Xp16 Units Heat Pumps Users Manual 506640a

Lenox Air Conditioner Elite Series XP16 Units Heat Pumps Lennox_XP16_IOM

Elite Series XP16 Units Heat Pumps to the manual 4a0ca56a-af7f-4082-a8f4-4c8427d7732c

2015-02-09

: Lenox Lenox-Lenox-Air-Conditioner-Elite-Series-Xp16-Units-Heat-Pumps-Users-Manual-571122 lenox-lenox-air-conditioner-elite-series-xp16-units-heat-pumps-users-manual-571122 lenox pdf

Open the PDF directly: View PDF PDF.
Page Count: 43

12/10 506640−01
*2P1210* *P506640-01*
Page 1
E20 Lennox Industries Inc.
Dallas, Texas, USA
These instructions are intended as a
general guide and do not supersede
local codes in any way. Consult
authorities having jurisdiction before
installation.
RETAIN THESE INSTRUCTIONS FOR FUTURE
REFERENCE
NOTICE TO INSTALLER
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting on
page 11 to avoid damaging the service valve’s internal seals.
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HFCs, and HCFCs) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration
may be levied for noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox XP16 Engineering Handbook.
Coils previously charged with HCFC−22 must be
flushed.
CAUTION
Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working near these areas during installation or while
servicing this equipment.
INSTALLATION
INSTRUCTIONS
Elite® Series XP16 Units
HEAT PUMPS
506640−01
12/10
Supersedes 11/10
TABLE OF CONTENTS
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification 2. . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . .
Caps and Fasteners Torque Requirements 3. . . . . . . .
Operating Gauge Set and Service Valves 3. . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . .
New Outdoor Unit Placement 6. . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 8. . . . . . . . . . . . . . . . .
Line Set Requirements 9. . . . . . . . . . . . . . . . . . . . . . . . .
Brazing Connections 11. . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Refrigerant Metering Device Removal and
Flushing Line Set and Indoor Coil 14. . . . . . . . . . . . . . . .
Installing New Indoor Metering Device 15. . . . . . . . . . . .
Leak Test Line Set and Indoor Coil 16. . . . . . . . . . . . . . .
Evacuating Line Set and Indoor Coil 17. . . . . . . . . . . . .
Electrical Connections 18. . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing and Weighing In Refrigerant for Units
Delivered Void of Charge 24. . . . . . . . . . . . . . . . . . . . . . .
Optimizing System Refrigerant Charge 26. . . . . . . . . . .
System Operation 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two−Stage Modulation Compressors Checks 40. . . . . .
Maintenance 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checklists 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List
Check unit for shipping damage. Consult last carrier
immediately if damage is found.
1 − Assembled outdoor unit
General
The XP16 outdoor unit uses HFC−410A refrigerant. This
unit must be installed with a matching indoor blower coil
and line set as outlined in the XP16 Lennox Engineering
Handbook. Elite® Series outdoor units are designed for
use in check / expansion valve (CTXV) systems only and
are not to be used with other refrigerant flow control
devices. An indoor coil check / expansion valve approved
for use with HFC−410A must be ordered separately and
installed prior to operating the unit.
Litho U.S.A.
Page 2
Model Number Identification
P 16 036− −
Unit Type
P = Heat Pump
Series
Nominal Cooling Capacity
024 = 2 tons
036 = 3 tons
048 = 4 tons
060 = 5 tons
Minor Revision Number
230
Voltage
230 = 208/230V−1ph−60hz
Refrigerant Type
X = R−410A
X05
Unit Dimensions − inches (mm)
ELECTRICAL
INLETS
SIDE VIEW
DISCHARGE AIR
VAPOR LINE
CONNECTION
LIQUID LINE
CONNECTION
4−1/4
(108)
4−3/4
(121)
1 (25)
2 (51)
SIDE VIEW
CB
A
UNIT SUPPORT
FEET
8−1/2
(216) D
G
K
J
E
F
XP16−024 BASE SECTION
8−3/4
(222)
5−1/2
(140)
9−1/2
(241)
8−1/4
(210)
13−1/2
(343)
UNIT SUPPORT FEET
XP16 BASE WITH LEGS
H
Mode Number A B C D E F G H J K
XP16−024−230 35 (889) 27 (686) 28 (711) −−−−−−−
XP16−036−230 39 (991) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
XP16−048−230 35 (889) 35−1/2 (902) 39−1/2
(1003)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
XP16−060−230 45 (1143 35−1/2 (902) 39−1/2
(1003)
Page 3
XP16 SERIES
Typical Unit Parts Arrangement
CHECK /
EXPANSION
VALVE
VAPOR VALVE AND GAUGE PORT /
SUCTION LINE CONNECTIONS
EXPANSION VALVE
SENSING BULB
LOW PRESSURE
SWITCH (S87)
LIQUID LINE
BI−FLOW FILTER
DRIER
HIGH PRESSURE
SWITCH (S4)
COMPRESSOR
LIQUID VALVE AND GAUGE
PORT / LIQUID LINE
CONNECTIONS
REVERSING
VALVE (L1)
DEMAND DEFROST
CONTROL (A108)
SINGLE POLE
CONTACTOR
(K1)
GROUND
LUG AMBIENT
TEMPERATURE
SENSOR (RT13)
TRUE SUCTION
PORT
DISCHARGE LINE
SENSOR (RT28)
XP16−024
COIL SENSOR −THIRD
HAIRPIN DOWN FROM
THE TOP ON INSIDE
ROW.
XP16−036
COIL SENSOR − NINTH
HAIRPIN UP FROM THE
BOTTOM ON INSIDE
ROW.
XP16−048
COIL SENSOR − EIGHT HAIRPIN
UP FROM THE BOTTOM ON
INSIDE ROW.
XP16−060
COIL SENSOR −
SIXTH HAIRPIN UP
FROM THE BOTTOM
ON INSIDE ROW.
DUAL RUN CAPACITOR (C12)
(−024, −036 AND −048 ONLY)
DETAIL A
FOR COIL SENSOR (RT21)
LOCATION SEE DETAIL A
SINGLE RUN CAPACITOR (C1)
(−060 ONLY)
Figure 1. Unit Parts Arrangement
Caps and Fasteners Torque Requirements
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc −
Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for
small valves, to 25 ft−lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using an
Allen wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.
See the Lennox Service and Application Notes
Corp.0807−L5 (C−08−1) for further details and
information.
When servicing or repairing HVAC equipment and
components, ensure the fasteners are appropriately
tightened. Table 1 list torque values for various caps and
fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
Page 4
Operating Gauge Set and Service Valves
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for
refrigerant recovery, flushing, leak testing, evacuating,
weighing in refrigerant and optimizing system charge.
Each valve is equipped with a service port which has a
factory−installed valve core. Figure 2 provides information
on how to access and operate both angle− and ball−type
service valves.
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold
gauge set that features low−loss anti−blow back fittings.
Manifold gauge set used for HFC−410A refrigerant
systems must be capable of handling the higher system
operating pressures. The manifold gauges should be rated
for:
SHigh side  Pressure range of 0 − 800 pound−force per
square inch gauge (psig)
SLow side  Use with 30" vacuum to 250 psig with
dampened speed to 500 psig
SManifold gauge set hoses must be rated for use to 800
psig of pressure with a 4000 psig burst rating.
INSERT HEX−HEAD
EXTENSION HERE
SERVICE PORT CORE
SERVICE PORT CAP
SERVICE PORT
CORE
TO OUTDOOR UNIT STEM CAP
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
TO INDOOR
UNIT
BALL (SHOWN CLOSED)
SERVICE PORT CORE
TO INDOOR UNIT
TO OUTDOOR UNIT
ATo open rotate stem
counterclockwise
90°.
BTo close rotate stem
clockwise 90°.
SERVICE PORT
SERVICE PORT CAP
REMOVE
STEM CAP
VALVE STEM
Operating Angle−Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16"
for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open
the service valve.
Operating Ball−Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open.
1
2
3
4
5
6
7
8
9
10
11 12
1/12 TURN
To Access Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized
wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and
tighten as follows:
SWith torque wrench: Finger tighten and torque cap per table 1.
SWithout torque wrench: Finger tighten and use an appropriately sized
wrench to turn an additional 1/6 turn clockwise.
12
3
4
5
6
7
8
9
10
11 12
1/6 TURN
When service valve stem is in the CLOSED position,
the service port is open to the line set and indoor unit.
When service valve is OPEN, the service port is open to line set,
indoor and outdoor unit.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and
serves as the primary seal. Replace the stem cap and
tighten as follows:
SWith Torque Wrench: Finger tighten and then
torque cap per table 1.
SWithout Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise.
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
TO INDOOR
UNIT
TO OUTDOOR
UNIT
REMOVE
STEM CAP
1
2
VALVE STEM
SHOWN
CLOSED
1
2
Figure 2. Angle and Ball−Type Service Valves
Page 5
XP16 SERIES
Recovering Refrigerant from Existing System
Disconnect all power to the existing outdoor unit at the disconnect
switch and/or main fuse box/breaker panel.
DISCONNECT POWER CONNECT MANIFOLD GAUGE SET
MANIFOLD GAUGES
RECOVERY MACHINE
CLEAN RECOVERY
CYLINDER
OUTDOOR UNIT
HIGH
LOW
Connect a manifold gauge set, clean recovery cylinder and a
recovery machine to the service ports of the existing unit..
METHOD 1:
Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or
if the unit is not operational and you plan to use the existing HCFC−22 to flush
the system.
Recover all HCFC−22 refrigerant from the existing system using a recovery
machine and clean recovery cylinder. Check gauges after shutdown to confirm
that the entire system is completely void of refrigerant.
METHOD 2:
Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves,
and you plan to use new HCFC−22 refrigerant to flush the system.
Perform the following task:
A Start the existing HCFC−22 system in the cooling mode and close the liquid line
valve.
B Use the compressor to pump as much of the existing HCFC−22 refrigerant into
the outdoor unit until the outdoor system is full. Turn the outdoor unit main power
OFF and use a recovery machine to remove the remaining refrigerant from the
system.
NOTE  It may be necessary to bypass the low pressure switches (if equipped) to
ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve.
D Check gauges after shutdown to confirm that the valves are not allowing
refrigerant to flow back into the low side of the system.
Remove existing HCFC−22 refrigerant using one of the following procedures:
RECOVERING REFRIGERANT
12
3
DISCONNECT
SWITCH
MAIN FUSE
BOX/BREAKER
PANEL
NOTE  Use the recovery machine instructions to make
the correct manifold gauge set connections for recovery
refrigerant. The illustration below is a typical connection.
NOTE  When using Method 2, the listed devices
below could prevent full system charge recovery into
the outdoor unit:
SOutdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycle the
compressor OFF.
SCompressor can stop pumping due to tripped
internal pressure relief valve.
SCompressor has internal vacuum protection that
is designed to unload the scrolls (compressor
stops pumping) when the pressure ratio meets a
certain value or when the suction pressure is as
high as 20 psig. (Compressor suction
pressures should never be allowed to go into
a vacuum. Prolonged operation at low suction
pressures will result in overheating of the
scrolls and permanent damage to the scroll
tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower
pressure due to any of the above mentioned system
conditions, shut off the vapor valve. Turn OFF the main
power to unit and use a recovery machine to recover
any refrigerant left in the indoor coil and line set.
METHOD 2 LIMITATIONS
Figure 3. Refrigerant Recovery
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance,
service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
Page 6
New Outdoor Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lift-
ing heavy objects.
Remove existing outdoor unit prior to placement of new
outdoor unit. See Unit Dimensions on page 2 for sizing
mounting slab, platforms or supports. Refer to figure 4 for
mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
SSome localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
SWhen possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 5,
detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in figure 5,
detail B.
NOTE If necessary for stability, anchor unit to slab as
described in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated
in figure 5, detail C.
If additional elevation is necessary, raise the unit by
extending the height of the unit support feet. This may be
achieved by using a 2 inch (50.8mm) schedule 40 female
threaded adapter.
The specified coupling will fit snuggly into the recessed
portion of the feet. Use additional 2 inch (50.8mm)
Schedule 40 male threaded adaptors which can be
threaded into the female threaded adaptors to make
additional adjustments to the level of the unit.
NOTE  Keep the height of extenders short enough to
ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field−fabricated
framework that is sturdy enough for greater heights.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build−up around the unit. Locate
the unit above a load bearing wall or area of the roof that
can adequately support the unit. Consult local codes for
rooftop applications. See figure 5, detail F for other roof top
mounting considerations.
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the
rubber to swell when it comes into contact with oil. The
rubber will then bubble and could cause leaks. Protect
the roof surface to avoid exposure to refrigerant and oil
during service and installation. Failure to follow this
notice could result in damage to roof surface.
CONTROL PANEL
ACCESS
LOCATION
6 (152)
36 (914)
12 (305) 30 (762)
LINE SET
CONNECTIONS
24
(610)
48 (1219)
MINIMUM CLEARANCE BETWEEN TWO UNITS
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
ACCESS PANEL
MINIMUM CLEARANCE
ABOVE UNIT
NOTES:
SClearance to one of the other three
sides must be 36 inches (914mm).
SClearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
Figure 4. Installation Clearances
Page 7
XP16 SERIES
LEG DETAIL
BASE
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
Concrete slab  use two plastic anchors (hole
drill 1/4")
Wood or plastic slab  no plastic anchor (hole
drill 1/8")
COIL
BASE PAN
CORNER POST
STABILIZING BRACKET (18 GAUGE
METAL  2" WIDTH; HEIGHT AS
REQUIRED)
 Slab Side Mounting
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
#10 1−1/4" LONG HEX HD SCREW
AND FLAT WASHER
Stabilizing bracket (18 gauge metal  2" (50.8mm) width; height as required); bend to form
right angle as exampled below.
FOR EXTRA
STABILITY
 Deck Top Mounting
Elevated Slab Mounting
using Feet Extenders
Install unit level or, if on a slope, maintain slope tolerance of two (2)
degrees (or two inches per five feet [50 mm per 1.5 m]) away from
building structure.
MOUNTING
SLAB
BUILDING
STRUCTURE
GROUND LEVEL
 Outside Unit Placement  Slab Mounting at Ground Level
SAME FASTENERS AS
SLAB SIDE MOUNTING.
DETAIL A DETAIL B
DETAIL C DETAIL D
2" (50.8MM) SCH 40
MALE THREADED
ADAPTER
Use additional 2" SCH 40 male threaded adapters which
can be threaded into the female threaded adapters to
make additional adjustments to the level of the unit.
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
Install unit away from windows.
One bracket per side
(minimum). For extra
stability, two brackets per
side, two inches (51mm)
from each corner.
DETAIL E
MINIMUM ONE
PER SIDE
DETAIL F
WIND BARRIER
INLET AIR
INLET AIR INLET AIR
INLET AIR
PREVAILING WINTER WINDS
 Roof Top Mounting
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be
constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24
inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated.
Figure 5. Placement, Slab Mounting and Stabilizing Unit
Page 8
Removing and Installing Panels
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open
slightly.
2. Hold the panel firmly throughout this procedure. Rotate
bottom corner of panel away from hinged corner post until
lower three tabs clear the slots as illustrated in detail B.
3. Move panel down until lip of upper tab clears the top slot in
corner post as illustrated in detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in
detail D with the screw side as close to the unit as possible.
Then, in a continuous motion:
1. Slightly rotate and guide the lip of top tab inward as
illustrated in detail A and C; then upward into the top
slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel’s hinged side firmly in place, close
the right−hand side of the panel, aligning the screw
holes.
4. When panel is correctly positioned and aligned, insert
the screws and tighten.
Detail A
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
PANEL
SCREW
HOLES
LIP
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR
ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR
ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO
PARALLEL WITH THE UNIT AS POSSIBLE) WHILE
INSTALLING PANEL.
PREFERRED ANGLE
FOR INSTALLATION
ANGLE MAY BE TOO
EXTREME
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Detail C
Detail B
Detail D
Figure 6. Removing and Installing Panels
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause
injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g.,
being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause
panels to be blown around and battered.
Page 9
XP16 SERIES
Line Set Requirements
This section provides information on: installation of new or
replacement line set.
SAdding Polyol ester oil requirements
SNew or replacement line set installation
SUsing existing line set.
ADDING POLYOL ESTER OIL REQUIREMENTS
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil
must be added, it must be a Polyol Ester oil.
The compressor is charged with sufficient Polyol Ester oil
(POE) for line set lengths up to 50 feet. Recommend
adding oil to system based on the amount of refrigerant
charge in the system. Systems with 20 pounds or less of
refrigerant required no oil to be added.
For systems over 20 pounds − add one ounce for every five
(5) pounds of HFC−410A refrigerant.
Recommended topping−off POE oils are Mobil EAL
ARCTIC 22 CC or ICI EMKARATEt RL32CF.
NEW OR REPLACEMENT LINE SET INSTALLATION
Field refrigerant piping consists of both liquid and vapor
lines from the outdoor unit to the indoor coil. Use Lennox
L15 (sweat, non−flare) series line set, or field−fabricated
refrigerant line sizes as specified in table 2.
If refrigerant lines are routed through a wall, then seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. See figure 7 for recommended
installation practices.
NOTE  When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, CORP. 9351−L9, or contact
Lennox Technical Support Product Applications for
assistance. To obtain the correct information from Lennox,
be sure to communicate the following information:
SModel (XP16) and size of unit (e.g. −036).
SLine set diameters for the unit being installed as listed
in table 2 and total length of installation.
SNumber of elbows vertical rise or drop in the piping.
USING EXISTING LINE SET
Things to consider:
SLiquid line that meter the refrigerant, such as RFC1
liquid line, must not be used in this application.
SExisting line set of proper size as listed in table 2 may
be reused.
SIf system was previously charged with HCFC−22
refrigerant, then existing line set must be flushed (see
Flushing Line Set and Indoor Coil on page 14).
If existing line set is being used, then proceed to Brazing
Connections on page 11.
IMPORTANT
Lennox highly recommends changing line set when
converting the existing system from HCFC−22 to
HFC−410A. If that is not possible and the line set is the
proper size as reference in table 2, use the procedure
outlined under Flushing Line Set and Indoor Coil on page
13.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil which was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil
and line set must be flushed prior to installation. Take
care to empty all existing traps. Polyol ester (POE) oils
are used in Lennox units charged with HFC−410A
refrigerant. Residual mineral oil can act as an
insulator, preventing proper heat transfer. It can also
clog the expansion device, and reduce the system
performance and capacity.
Failure to properly flush the system per the
instructions below will void the warranty.
Table 2. Refrigerant Line Set  Inches (mm)
Model Field Connections Recommended Line Set
Liquid Line Suction Line Liquid Line Suction Line L15 Line Set
XP16−024−230 3/8" (10 mm) 3/4" (19 mm) 3/8" (10 mm) 3/4" (19 mm) L15−41  15 ft. − 50 ft. (4.6m − 15 m)
XP16−036−230
3/8" (10 mm) 7/8" (22 mm) 3/8" (10 mm) 7/8" (22 mm) L15−65  15 ft. − 50 ft. (4.6 m − 15 m)
XP16−048−230
XP16−060−230 3/8" (10 mm) 1−1/8" (29 mm) 3/8" (10 mm) 1−1/8" (29 mm) Field Fabricated
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter
Page 10
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO
VAPOR LINE
WALL
STUD
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
VAPOR LINE − WRAPPED
IN ARMAFLEX
AUTOMOTIVE
MUFFLER-TYPE HANGER
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
Line Set Isolation  The following illustrations are examples of proper refrigerant line set isolation:
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR
WIRE TIE
WIRE TIE (AROUND
VAPOR LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR
WIRE TIE
To hang line set from joist or rafter, use either metal strapping material
or anchored heavy nylon wire ties.
8 FEET (2.43 METERS)
STRAP THE VAPOR LINE TO THE JOIST
OR RAFTER AT 8 FEET (2.43 METERS)
INTERVALS THEN STRAP THE LIQUID
LINE TO THE VAPOR LINE.
FLOOR JOIST OR
ROOF RAFTER
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
NOTE  Similar installation practices should be used if line set is
to be installed on exterior of outside wall.
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
OUTSIDE
WALL
VAPOR LINE WRAPPED
WITH ARMAFLEX
LIQUID
LINE
OUTSIDE WALL LIQUID LINE
VAPOR LINE
WOOD BLOCK
BETWEEN STUDS
STRAP
WOOD BLOCK
STRAP
SLEEVE
WIRE TIE
WIRE TIE
WIRE TIE
INSIDE WALL
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the
surrounding ambient temperature could become higher than the
temperature of the liquid line or when pressure drop is equal to or greater
than 20 psig.
NON−CORROSIVE
METAL SLEEVE
NON−CORROSIVE
METAL SLEEVE
8 FEET (2.43 METERS)
Figure 7. Line Set Installation
Page 11
XP16 SERIES
Brazing Connections
Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves.
WARNING
Polyol Ester (POE) oils used with HFC−410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture − Check the high and low
pressures before applying heat.
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration
or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well−ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
IMPORTANT
Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver
alloy for copper−to−copper brazing. Use 45% minimum
alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause fire and/or an ex-
plosion, that could result in property
damage, personal injury or death.
Page 12
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE
VALVES
OUTDOOR
UNIT
LIQUID LINE
VAPOR LINE
LIQUID LINE SERVICE
VALVE
SUCTION /
VAPOR LINE
SERVICE
VALVE
ATTACH
GAUGES
INDOOR
UNIT
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
A Connect gauge set low pressure side to
liquid line service valve (service port).
B Connect gauge set center port to bottle of
nitrogen with regulator.
C Remove core from valve in suction / vapor
line service port to allow nitrogen to escape.
NITROGEN
HIGHLOW
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
B
A
C
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction /
vapor line service port valve.
CUT AND DEBUR CAP AND CORE REMOVAL
Cut ends of the refrigerant lines square (free from nicks or dents)
and debur the ends. The pipe must remain round. Do not crimp end
of the line.
Remove service cap and core from
both the suction / vapor and liquid line
service ports.
12
LIQUID LINE SERVICE
VALVE
SERVICE
PORT
CORE
SERVICE PORT
CAP
SERVICE
PORT
CORE
SERVICE
PORT CAP
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
COPPER TUBE
STUB
SERVICE VALVE
CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
REDUCER
3
SUCTION / VAPOR LINE
SERVICE VALVE
LINE SET SIZE IS SMALLER
THAN CONNECTION
Figure 8. Brazing Procedures
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning
system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Page 13
XP16 SERIES
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
LIQUID LINE SERVICE VALVE
LIQUID LINE
BRAZE LINE SET
Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water
saturated cloths must remain water saturated throughout the brazing and cool−down process.
WATER SATURATED
CLOTH
IMPORTANT Allow braze joint to cool. Apply
additional water saturated cloths to help cool brazed
joint. Do not remove water saturated cloths until piping
has cooled. Temperatures above 250ºF will damage
valve seals.
6
SUCTION / VAPOR LINE
WATER SATURATED
CLOTH
SUCTION / VAPOR LINE
SERVICE VALVE
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both
service valves to cool piping. Once piping is cool, remove all water saturated cloths.
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
PREPARATION FOR NEXT STEP
7
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY
DAMAGE may result if you do not wrap a water
saturated cloth around both liquid and suction line
service valve bodies and copper tube stub while
brazing in the line set! The braze, when complete,
must be quenched with water to absorb any residual
heat.
2. Do not open service valves until refrigerant lines and
indoor coil have been leak−tested and evacuated.
Refer to procedures provided in this supplement.
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use
additional water saturated cloths underneath the valve body to protect the base paint.
4
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
5
Figure 9. Brazing Procedures (continued)
Page 14
Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil
Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then
remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 15.
SENSING
LINE
TEFLON® RING
FIXED ORIFICE
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR TUBES
DISTRIBUTOR
ASSEMBLY
REMOVE AND DISCARD
WHITE TEFLON® SEAL
(IF PRESENT)
A On fully cased coils, remove the coil access and plumbing panels.
B Remove any shipping clamps holding the liquid line and distributor as-
sembly.
C Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro-
cess.
D Remove and discard fixed orifice, valve stem assembly if present and
Teflon® washer as illustrated above.
E Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE (UNCASED
COIL SHOWN)
TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
VAPOR
LINE
DISTRIBUTOR
ASSEMBLY
DISTRIBUTOR
TUBES
LIQUID
LINE
MALE EQUALIZER
LINE FITTING
EQUALIZER
LINE
CHECK
EXPANSION
VALVE
TEFLON®
RING
STUB END
TEFLON®
RING
SENSING BULB
LIQUID LINE
ORIFICE
HOUSING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
A On fully cased coils, remove the coil access and plumbing panels.
B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D Remove the vapor line sensing bulb.
E Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
F Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.
G Remove and discard check expansion valve and the two Teflon® rings.
H Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
LOW HIGH
EXISTING
INDOOR
UNIT
GAUGE
MANIFOLD
INVERTED HCFC−22
CYLINDER CONTAINS
CLEAN HCFC−22 TO BE
USED FOR FLUSHING.
LIQUID LINE SERVICE
VALVE
INLET
DISCHARGE
TANK
RETURN
CLOSED
OPENED
RECOVERY
CYLINDER
RECOVERY MACHINE
NEW
OUTDOOR
UNIT
VAPOR LINE
SERVICE VALVE
VAPOR
LIQUID
1
A Inverted HCFC−22 cylinder with clean refrigerant to the vapor service
valve.
B HCFC−22 gauge set (low side) to the liquid line valve.
C HCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
D Connect recovery tank to recovery machines per machine instructions.
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
A
B
C
D
B
OR
FLUSHING LINE SET
A Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
recovery machine to pull a vacuum on the existing system line
set and indoor unit coil.
B Invert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line
valve. Allow the refrigerant to pass from the cylinder and through
the line set and the indoor unit coil before it enters the recovery
machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22
vapor is recovered. Allow the recovery machine to pull down to 0
the system.
D Close the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
The line set and indoor unit coil must be flushed with at least the
same amount of clean refrigerant that previously charged the
system. Check the charge in the flushing cylinder before
proceeding.
1A
2
3
1B
Figure 10. Removing Indoor Refrigerate Metering Device and Flushing Procedures
Page 15
XP16 SERIES
Installing New Indoor Metering Device
This outdoor unit is designed for use in HFC−410A systems that use a check / expansion valve metering device (purchased
separately) at the indoor coil.
See the Lennox XP16 Engineering Handbook for approved check / expansion valve kit matchups. The check / expansion
valve device can be installed either internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the check / expansion valve in a manner that will provide access for field servicing
of the check / expansion valve (see figure 11).
A Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.
NOTE  Confirm proper thermal contact between vapor line
and expansion bulb before insulating the sensing bulb once
installed.
B Connect the equalizer line from the check / expansion
valve to the equalizer vapor port on the vapor line. Finger
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated
below.
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
VAPOR
LINE
LIQUID LINE
ORIFICE
HOUSING
DISTRIBUTOR
TUBES
LIQUID LINE
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING
LINE
EQUALIZER
LINE
CHECK /
EXPANSION
VALVE
TEFLON®
RING
(Uncased Coil Shown)
Sensing bulb insulation is
required if mounted external to
the coil casing.
STUB
END
TEFLON®
RING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
DISTRIBUTOR
ASSEMBLY
A Remove the field−provided fitting that temporarily
reconnected the liquid line to the indoor unit’s distributor
assembly.
B Install one of the provided Teflon® rings around the
stubbed end of the check / expansion valve and lightly
lubricate the connector threads and expose surface of
the Teflon® ring with refrigerant oil.
C Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or 20 ft−lb.
D Place the remaining Teflon® washer around the other
end of the check / expansion valve. Lightly lubricate
connector threads and expose surface of the Teflon®
ring with refrigerant oil.
E Attach the liquid line assembly to the check / expansion
valve. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in the figure above or 20 ft−lb.
ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT ON
BOTTOM OF LINE.
12
ON LINES SMALLER THAN
7/8", MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O’CLOCK POSITION.
12
BULB
VAPOR LINE
VAPOR LINE
NOTE  NEVER MOUNT ON BOTTOM OF LINE.
BULB
BULB
BULB
VAPOR LINE
FLARE NUT
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
FLARE SEAL CAP
OR
1
2
3
4
5
6
7
8
9
10
11 12
1/2 Turn
SENSING BULB INSTALLATION
EQUALIZER LINE INSTALLATION
1
2
3
4
5
6
7
8
9
10
11 12
1/8 Turn
Remove and discard either the flare seal cap or flare nut with
copper flare seal bonnet from the equalizer line port on the vapor
line as illustrated in the figure to the right.
INDOOR EXPANSION VALVE INSTALLATION
Figure 11. Installing Indoor Check / Expansion Valve
Page 16
Leak Test Line Set and Indoor Coil
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
TO VAPOR
SERVICE VALVE
HFC−410A
MANIFOLD GAUGE SET
OUTDOOR UNIT
HIGHLOW
NITROGEN
A Connect an HFC−410A manifold gauge set high pressure hose to the
vapor valve service port.
NOTE  Normally, the high pressure hose is connected to the liquid
line port. However, connecting it to the vapor port better protects the
manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of HFC−410A
refrigerant to the center port of the manifold gauge set.
NOTE  Later in the procedure, the
HFC−410A container will be replaced by
the nitrogen container.
CONNECT GAUGE SET
A
B
Figure 12. Manifold Gauge Set Connections for Leak Testing
TEST FOR LEAKS
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks. Use the following procedure to test for leaks:
1. With both manifold valves closed, connect the cylinder
of HFC−410A refrigerant to the center port of the
manifold gauge set. Open the valve on the HFC−410A
cylinder (vapor only).
2. Open the high pressure side of the manifold to allow
HFC−410A into the line set and indoor unit. Weigh in
a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three
pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure
side of the manifold gauge set. Disconnect the
HFC−410A cylinder.
3. Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold
gauge set.
4. Adjust dry nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
5. After a few minutes, open one of the service valve
ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
6. After leak testing disconnect gauges from service
ports.
Page 17
XP16 SERIES
Evacuating Line Set and Indoor Coil
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any
gas that will not condense under temperatures and pressures present during operation of an air conditioning system.
Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and
compressor parts.
A Open both manifold valves and start the vacuum pump.
B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
SClose manifold gauge valves
SClose valve on vacuum pump and turn off vacuum pump
SDisconnect manifold gauge center port hose from vacuum pump
SAttach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
SOpen manifold gauge valves to break the vacuum in the line set and indoor unit.
SClose manifold gauge valves.
D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and
indoor unit.
G Perform the following:
OUTDOOR
UNIT
TO VAPOR
SERVICE VALVE
TO LIQUID LINE
SERVICE VALVE
MICRON
GAUGE
VACUUM PUMP
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
500
MANIFOLD
GAUGE SET
HFC−410A
RECOMMEND
MINIMUM 3/8" HOSE
AConnect low side of manifold gauge set
with 1/4 SAE in−line tee to vapor line
service valve
BConnect high side of manifold gauge
set to liquid line service valve
CConnect micron gauge available
connector on the 1/4 SAE in−line tee.
DConnect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port
line will be used later for both the
HFC−410A and nitrogen containers.
HIGHLOW
1
2
3
4
5
6
7
8
9
10
11 12
1/6 TURN
NITROGEN
1CONNECT GAUGE SET
A
B
C
D
2EVACUATE THE SYSTEM
NOTE  Remove cores from service valves (if not already done).
SClose manifold gauge valves.
SShut off HFC−410A cylinder.
SReinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
SReplace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.
Figure 13. Evacuating Line Set and Indoor Coil
Page 18
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum
operation. Do not use compressors to evacuate a
system. Extremely low vacuums can cause internal
arcing and compressor failure. Damage caused by
deep vacuum operation will void warranty.
Electrical Connections
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air
handler for low-voltage control power (24VAC − 40 VA
minimum)
Refer to the unit nameplate for minimum circuit ampacity, and
maximum fuse or circuit breaker (HACR per NEC). Install power
wiring and properly sized disconnect switch.
NOTE  Units are approved for use only with copper conductors.
Ground unit at disconnect switch or to an earth ground.
SIZE CIRCUIT AND INSTALL DISCONNECT
SWITCH
1
NOTE  24VAC, Class II circuit connections are made in the control
panel.
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet
(1.5m) from the floor. It should not be installed on an outside wall
or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
INSTALL THERMOSTAT
2
DISCONNECT
SWITCH
MAIN FUSE BOX/
BREAKER PANEL
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and
local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors.
Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power
supplies.
Page 19
XP16 SERIES
ARun 24VAC control wires through cutout with grommet.
BRun 24VAC control wires through wire tie.
CMake 24VAC control wire connections.
DTighten wire tie to security 24V control wiring.
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE (24V) FIELD WIRING
CUTOUT WITH
GROMMET
NOTEFor proper voltages, select thermostat wire (control wires)
gauge per table above.
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
24V CONTROL WIRES TIGHTEN WIRE TIE
LOW VOLTAGE CONNECTIONS
NOTEDo not bundle any excess 24VAC control wires inside
control box.
NOTE − Wire tie provides low voltage wire strain relief and to maintain
separation of field installed low and high voltage circuits.
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated. See figures 14 and 15 for typical field
connections when connecting unit to either a CBX32MV or CBX40UHV in non−communicating mode. For connections to other Lennox air handlers
or furnaces, see the ComfortSense® 7000 installation instruction for further match component wiring illustrations.
3
A
B
C
D
NOTE − Any excess high voltage field wiring
should be trimmed and secured away from
any low voltage field wiring.
GROUND
L2
NOTE − To facilitate a conduit, a cutout is lo-
cated in the bottom of the control box. Connect
conduit to the control box using a proper con-
duit fitting.
CONDUIT
CONDUIT
CUTOUT
OUTDOOR UNIT
CONTROL BOX
G
L1
HIGH VOLTAGE POWER SUPPLY CONNECTIONS
4
Page 20
CBX32MV
OR
CBX40UHV
HEAT PUMP UNIT
(TWO−STAGE) X2658 OUTDOOR SENSOR IS REQUIRED FOR OUTDOOR
TEMPERATURE DISPLAY, DEW POINT CONTROL, HEAT PUMP AND
DUAL FUEL BALANCE POINTS.
COMFORTSENSET
7000
RRR
W3 H
W2
W2
W1 W1 W1
O
OO
L
L
Y1
Y1
Y1
Y2Y2
G
G
CCC
T
T
D
B
Y2
DS
O. D.
SENSOR
(X2658)
Y2
OUT
BL
1
1
CUT ON−BOARD LINK R −O.
CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION TERMINAL IS USED.
CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE HP
2
2
3
3FIELD PROVIDED JUMPER BETWEEN Y2 OUT BL ON HEAT PUMP
TO Y2 ON CBX40UHV.
CONNECTED ON UNIT WITH LSOM. RESISTOR KIT (CAT # 47W97)
IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000
WITH THE LSOM 2.
Y1−Y2
2−STAGE
COMPR
R−O
HEAT
PUMP
R−DS
DEHUM
OR
HARMONY
CUT FOR OPTION
AIR
HANDLER
CONTROL
IMPORTANT − USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE CBX40UHV
INSTALLATION INSTRUCTION FOR FURTHER DETAILS.
Figure 14. Typical Field Wiring  Heat Pump Application with CBX32MV or CBX40UHV
YELLOW
BLUE (NOT REQUIRED FOR SINGLE STAGE)
RED
BLACK
PURPLE
PURPLE
BLACK
BLUE
RED
FAN RELAY (NOT REQUIRED
WITH SINGLESPEED
OUTDOOR FAN)
OUTDOOR
SENSOR
(X2658)
COMFORTSENSEt
7000 THERMOSTAT
OUTDOOR UNIT
CUT ON−BOARD LINK R −O.
CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE A/C ONLY
CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION
TERMINAL IS USED.
T
T
BROWN (NOT USED FOR APPLICATIONS WITHOUT LSOM
Y1−Y2
2−STAGE
COMPR
R−O
HEAT
PUMP
R−DS
DEHUM
OR
HARMONY
CUT FOR OPTION
RESISTOR KIT (CAT # 47W97) IS REQUIRED
WHEN CONNECTING THE COMFORTSENSE
7000 WITH THE LSOM 2.
IMPORTANT − USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE CBX40UHV
INSTALLATION INSTRUCTION FOR FURTHER DETAILS.
CBX32MV OR
CBX40UHV
AIR
HANDLER
CONTROL
Figure 15. Heat Pump Application  Humiditrol ® and Second−Stage Outdoor Fan Relay Wiring with
CBX32MV or CBX40UHV
Page 21
XP16 SERIES
Figure 16. Typical Unit Wiring Diagram (−024, −036 and −048 Only)
Page 22
Figure 17. Typical Unit Wiring Diagram (−060 Only)
Page 23
XP16 SERIES
Figure 18. Typical Factory Wiring Diagram (No Field Modifications)
Unit Start−Up
IMPORTANT
If unit is equipped with a crankcase heater, it should be
energized 24 hours before unit start−up to prevent
compressor damage as a result of slugging.
UNIT START−UP
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose
connections.
3. Verify that the manifold gauge set is connected as
illustrated in figure 21. Use a temperature sensor
positioned near the liquid line service port as illustrated
in figure 21 which will be required later when using the
subcooling method for optimizing the system
refrigerant charge.
4. Replace the stem caps and tighten to the value listed
in table 1.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted with the power company and the
voltage condition has been corrected.
6. Open both the liquid and vapor line service valves to
release the refrigerant charge contained in outdoor
unit into the system.
7. Use figure 19 to determine next step in system
preparation.
REFRIGERANT
PRESENT
OPEN BOTH VAPOR AND LIQUID SERVICE
VALVE STEMS TO RELEASE
REFRIGERANT FROM OUTDOOR UNIT TO
SYSTEM.
YESNO
GO TO SERVICE AND WEIGH
IN REFRIGERANT CHARGE
FOR OUTDOOR UNITS
DELIVERED VOID OF CHARGE
ON PAGE 24.
GO TO OPTIMIZING SYSTEM
REFRIGERANT CHARGE ON
PAGE 26.
Figure 19. Outdoor Unit Factory Charge
Page 24
Service and Weigh In Refrigerant for Outdoor Units Delivered Void of Charge
The following procedures are only required if it has been determine that the new outdoor unit is void of charge. Skip to the
next section if refrigerant charge is present.
LEAK CHECK, REPAIR AND EVACUATE
If the outdoor unit is void of refrigerant, clean the system
using the procedure described below.
1. Leak check system using procedures provided on
page 16. Repair any leaks discovered during leak test.
2. Evacuate the system using procedure provided in
figure 13.
3. Use nitrogen to break the vacuum and install a new
filter drier in the system.
4. Evacuate the system again using procedure in figure
12.
CONNECT MANIFOLD GAUGE SET AND WEIGH IN
CHARGE
After the evacuation procedure, reconnect the manifold
gauge set as illustrated in figure 21.
NOTE − Temperature sensor illustrated in figure 21 is not
required for initial system weigh in charging.
1. Close manifold gauge set valves and connect the
center hose to a cylinder of HFC−410A. Set for liquid
phase charging.
2. Connect the manifold gauge set’s low pressure side to
the true suction port.
3. Connect the manifold gauge set’s high pressure side
to the liquid line service port.
4. Connect the center hose of the gauge set to a cylinder
of HFC−410A and purge the hose. Then, place the
cylinder upside down on a scale.
5. Check that fan rotates freely.
6. Inspect all factory− and field−installed wiring for loose
connections.
7. Open the high side manifold gauge valve and weigh in
liquid refrigerant. Use figure 20 in calculating the
correct weigh−in charge.
8. Close manifold gauge valves.
9. Monitor the system to determine the amount of
moisture remaining in the oil. It may be necessary to
replace the bi−flow filter drier several times to achieve
the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
10. Continue to Optimizing System Refrigerant Charge
on page 26 to optimize the system charge using
subcooling method.
WEIGH−IN CHARGING
LIQUID LINE SET DIAMETER OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET
(4.6 M) LINE SET*
3/8" (9.5 MM) 3 OUNCE PER 5’ (85 G PER 1.5 M)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract
this amount.
Refrigerant Charge per Line Set Length
NOTE  The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature
of the liquid line or when pressure drop is equal to or greater than 20 psig.
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total
refrigerant charge:
Amount specified on
nameplate
Adjust amount. for variation in line set
length listed on line set length table below.
Additional charge specified per indoor
unit match listed on page 28. Total Charge
++=
Figure 20. Using HFC−410A Weigh In Method
Page 25
XP16 SERIES
TO LIQUID
LINE SERVICE
VALVE
TEMPERATURE SENSOR (USE FOR
SUBCOOLING METHOD)
DIGITAL SCALE
REFRIGERANT
TANK
TEMPERATURE SENSOR
(LIQUID LINE)
MANIFOLD GAUGE SET
AClose manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.
BConnect the manifold gauge set’s low pressure side to the true suction port.
CConnect the manifold gauge set’s high pressure side to the liquid line service port.
DPosition temperature sensor on liquid line near liquid line service port (use only for subcooling method).
OUTDOOR UNIT
CHARGE IN
LIQUID PHASE
CONNECTIONS FOR OPTIMIZING SYSTEM CHARGE
GAUGE SET
A
C
D
LOW HIGH
B
INSIDE OUTDOOR UNIT
TRUE SUCTION PORT
CONNECTION
NOTE  Refrigerant tank should be
turned right−side−up to deliver vapor
during charge optimizing procedure.
Figure 21. Gauge Set Connections for Adding Refrigerant
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and
indoor coil. Use true suction port to measure vapor pressure during charging.
OUTDOOR
COIL
CHECK / EXPANSION
VALVE
BI−FLOW FILTER / DRIER
COMPRESSOR
REVERSING VALVE
MUFFLER
NOTE − ARROWS INDICATE DIRECTION
OF REFRIGERANT FLOW
SERVICE
PORT
VAPOR
CHECK / EXPANSION VALVE
INDOOR UNIT
OUTDOOR UNIT
LIQUID LINE
SERVICE PORT
DISTRIBUTOR
INDOOR
COIL
TRUE SUCTION
PORT
Figure 22. Heat Pump Cooling Cycle
Page 26
Optimizing System Refrigerant Charge
This section provides instructions on optimizing the
system charge. This section includes:
SOptimizing procedure
SAdjusting indoor airflow
SUsing subcooling method
SApproved matched components, targeted subcooling
(SC) values and add charge values
SNormal operating pressures
STemperature pressures
OPTIMIZING PROCEDURE
1. Move the low−side manifold gauge hose from the
vapor line service valve to the true suction port (see
figure 21).
2. Set the thermostat for either cooling or heating
demand. Turn on power to the indoor unit and close
the outdoor unit disconnect switch to start the unit.
3. Allow unit to run for five minutes to allow pressures to
stabilize.
4. Check the airflow as instructed under Adjusting Indoor
Airflow to verify or adjust indoor airflow for maximum
efficiency. Make any air flow adjustments before
continuing with the optimizing procedure.
5. Use subcooling method to optimize the system
charge (see figure 24). Adjust charge as necessary.
ADJUSTING INDOOR AIRFLOW
Heating Mode Indoor Airflow Check
(Only use when indoor unit has electric heat)
Indoor blower airflow (CFM) may be calculated by
energizing electric heat and measuring:
STemperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
SMeasuring voltage supplied to the unit,
SMeasuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in the following
formula to determine CFM:
CFM =
Amps x Volts x 3.41
1.08 x Temperature rise (F)
Cooling Mode Indoor Airflow Check
Check airflow using the Delta−T (DT) process using figure
23.
1. Determine the desired DTMeasure entering air temper-
ature using dry bulb (A) and wet bulb (B). DT is the intersect-
ing value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry
bulb entering and leaving air temperatures (A and C). Tem-
perature Drop Formula: (TDrop) = A minus C.
3. Determine if fan needs adjustmentIf the difference between
the measured TDrop and the desired DT (TDropDT) is within
+3º, no adjustment is needed. See examples: Assume DT =
15 and A temp. = 72º, these C temperatures would necessi-
tate stated actions:
T
Drop DT=ºF ACTION
53º 19 15 =4Increase the airflow
58º 14 – 15 =−1 (within +3º range) no change
62º 10 – 15 =−5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck tempera-
tures to confirm that the temperature drop and DT are within
+3º.
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15
78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
Temp.
of air
entering
indoor
coil ºF
INDOOR
COIL
DRY
BULB
DRY
BULB
WET
BULB
B
TDrop
19º
A
Dry−bulb
Wet−bulb ºF
A
72º
B
64º
C
53º
air flowair flow
All temperatures are
expressed in ºF
ADJUSTING INDOOR AIRFLOW
Figure 23. Checking Airflow over Indoor Coil Using Delta−T Formula
Page 27
XP16 SERIES
1. Check liquid and vapor line pressures. Compare pressures with either second−stage
heat or cooling mode normal operating pressures listed in table 7. Table 7 is a general
guide and expect minor pressures variations. Significant pressure differences may
indicate improper charge or other system problem.
2. Decide whether to use cooling or heating mode based on current outdoor ambient
temperature:
AUse COOLING MODE when:
SOutdoor ambient temperature is 60°F (15.5°C) and above.
SIndoor return air temperature range is between 70 to 80°F (21−27°C). This
temperature range is what the target subcooling values are base upon in
tables 3 through 6.
If indoor return air temperature is not within reference range, set thermostat to
cooling mode and a setpoint of 68ºF (20ºC). This should place the outdoor unit
into second−stage (high−capacity) cooling mode. When operating and
temperature pressures have stabilized, continue to step 3.
BUse HEATING MODE when:
SOutdoor ambient temperature is 59°F (15.0°C) and below.
SIndoor return air temperature range is between 65−75°F (18−24°C). This
temperature range is what the target subcooling values are base upon in
tables 3 through 6.
If indoor return air temperature is not within reference range, set thermostat to
heating mode and a setpoint of 77ºF (25ºC). This should place the outdoor unit
into second−stage (high−capacity) heating mode. When operating and
temperature pressures have stabilized, continue to step 3.
3. Read the liquid line pressure; then find its corresponding temperature pressure listed
in table 8 and record it in the SAspace to the left.
4. Read the liquid line temperature; record in the LIQº space to the left.
5. Subtract LIQº temperature from SA temperature to determine subcooling; record
it in SCº space to the left..
6. Compare SCº results with tables 3 through 6 (either Heating or Cooling mode
column), also consider any additional charge required for line set lengths longer than
15 feet and/or unit matched component combinations (Add Charge column).
7. If subcooling value is:
AGREATER than shown for the applicable unit match component, REMOVE
refrigerant;
BLESS than shown for the applicable unit match component, ADD refrigerant.
8. If refrigerant is added or removed, repeat steps 3 through 6 to verify charge.
9. Close all manifold gauge set valves and disconnect gauge set from outdoor unit.
10. Replace the stem and service port caps and tighten as specified in Operating Service
Valves on page 2.
11. Recheck voltage while the unit is running. Power must be within range shown on the
nameplate.
USE
COOLING
MODE
USE
HEATING
MODE
60ºF
(15ºC)
SA
LIQº –
SCº =
OPTIMIZE CHARGE USING SUBCOOLING METHOD
Figure 24. Using HFC−410A Subcooling Method  Second Stage (High Capacity)
Page 28
APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND
ADD CHARGE VALUES
Listed below are the approved matched system components (air handlers and indoor coils), targeted subcooling and
add charge values for the XP16. This information is also listed on the unit charging sticker located on the outdoor unit
access panel.
Subcooling values listed in the following tables are based
on outdoor ambient air temperature of:
S60°F (15.5°C) and above for cooling mode
S59°F (15.0°C) and below for heating mode.
Table 3. XP16024230
Indoor Air Handers
and Coils
Heating
Mode
+5ºF
Cooling
Mode
+1ºF
*Add Charge
Subcooling lb. oz.
CBX26UH−024 45 6 0 15
CBX27UH−024−230 20 7 0 9
CBX27UH−030−230 17 7 1 3
CBX32MV−024/030 20 7 0 9
CBX32MV−036 17 7 1 3
CBX40UHV−024 17 7 1 3
CBX40UHV−030 17 7 1 3
CBX40UHV−036 17 7 1 3
CH33−31B 31 8 1 12
CR33−30/36A/B/C 45 4 0 0
CX34−31A/B 24 7 1 11
CX34−38A/B 18 8 1 10
Table 4. XP16036230
Indoor Air Handers
and Coils
Heating
Mode
+5ºF
Cooling
Mode
+1ºF
*Add Charge
Subcooling lbs. oz.
CBX26UH−036 50 5 0 0
CBX27UH−036−230 22 7 0 9
CBX27UH−042−230 24 11 3 0
CBX32M−036 22 7 0 9
CBX32MV−036 22 7 0 9
CBX32MV−048 24 11 3 0
CBX40UHV−030 22 7 0 9
CBX40UHV−036 22 7 0 9
CBX40UHV−042 24 11 3 0
CBX40UHV−048 24 11 3 0
CH33−43B 13 10 2 7
CH33−48C 37 11 211
CH33−43C 37 11 211
CR33−48B/C 49 7 0 9
CX34−43B/C 29 9 2 11
CX34−50/60C 29 9 2 11
Table 5. XP16048230
Indoor Air Handers
and Coils
Heating
Mode
+5ºF
Cooling
Mode
+1ºF
*Add Charge
Subcooling lbs. oz.
CBX26UH−048−230 10 8 1 4
CBX27UH−048−230 19 9 1 4
CBX27UH−060−230 13 14 3 3
CBX32M−048 19 9 1 4
CBX32M−060 14 9 1 11
CBX32MV−048 19 9 1 4
CBX32MV−060 14 9 1 11
CBX32MV−068 9 8 1 11
CBX40UHV−048 19 9 1 4
CBX40UHV−060 14 9 1 11
CH23−68 24 10 1 12
CH33−49C 19 9 2 5
CH33−50/60C 19 9 2 5
CH33−60D 13 8 0 0
CH33−62D 11 9 1 4
CR33−50/60C 15 7 0 10
CR33−60D 15 7 0 10
CX34−60D 14 8 1 0
CX34−62D 9 9 1 6
CX34−62C 8 9 1 9
Table 6. XP16060230
Indoor Air Handers
and Coils
Heating
Mode
+5ºF
Cooling
Mode
+1ºF
*Add Charge
Subcooling lbs. oz.
CBX26UH−060 20 9 4 13
CBX27UH−060−230 10 6 2 3
CBX32M−060 17 6 1 12
CBX32MV−060 17 6 1 12
CBX32MV−068 15 7 2 1
CBX40UHV−060 17 6 1 12
CH23−682 37 9 2 10
CH33−50/60C 33 8 1 0
CH33−62D 15 7 1 4
CR33−50/60C 24 7 0 0
CR33−60D 24 7 0 0
CX34−62C 21 9 2 16
CX34−62D 13 7 1 4
*Amount of charge required in additional to charge shown on unit
nameplate. (Remember to consider line set length difference.)
Page 29
XP16 SERIES
NORMAL OPERATING PRESSURES
Use the following tables to perform maintenance checks; it
is not a procedure for charging the system. Minor
variations in these pressures may be due to differences in
installations. Significant deviations could mean that the
system is not properly charged or that a problem exists
with some component in the system.
Typical pressures only, expressed in psig (liquid +/− 10
and vapor +/− 5 psig); matched indoor component (air
handler or coil), indoor air quality, and indoor load will
cause the pressures to vary.
Table 7. Normal Operating Pressures*
Normal Operating Pressures − Cooling
XP16 −024 −036 −048 −060
F
(C)** Liq Vap Liq Vap Liq Vap Liq Vap
First Stage (Low Capacity) Pressure
65
(18.3) 226 144 220 141 224 143 230 137
75
(23.9) 260 145 254 144 259 143 267 139
85
(29.4) 301 148 295 148 302 147 311 141
95
(35.0) 346 151 340 150 346 149 357 144
105
(40.6) 396 153 389 153 396 152 398 147
115
(46.1) 451 156 444 156 450 155 453 149
Second Stage (High Capacity) Pressure
65
(18.3) 241 140 232 129 238 138 232 131
75
(23.9) 279 142 269 136 278 140 276 133
85
(29.4) 321 144 312 140 321 142 320 136
95
(35.0) 369 146 346 142 372 144 367 138
105
(40.6) 421 148 409 145 424 147 421 141
115
(46.1) 480 151 465 148 481 149 479 144
Normal Operating Pressures − Heating
First Stage (Low Capacity) Pressure
50
(10) 312 112 350 115 336 114 385 108
60
(15.5) 330 130 372 136 363 135 414 126
Second Stage (High Capacity) Pressure
20
(−7.0) 299 64 321 61 289 57 332 59
30
(−1.0) 312 79 347 74 294 69 349 67
40
(4.4) 325 93 367 90 321 80 361 75
50
(10) 344 110 387 110 341 110 383 85
60
(15.5) 358 128 395 131 361 128 425 122
** Temperature of air entering outdoor coil.
TEMPERATURE PRESSURES
Compute subcooling by determining saturated
condensing temperature from temperature pressure
chart. Subtract from liquid temperature entering TXV.
Table 8. HFC−410A Temperature (°F) −
Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9
33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 175.4 93 286.5 124 440.2 155 645.0
Page 30
System Operation
IMPORTANT
Some scroll compressor have internal vacuum protector
that will unload scrolls when suction pressure goes
below 20 psig. A hissing sound will be heard when the
compressor is running unloaded. Protector will reset
when low pressure in system is raised above 40 psig. DO
NOT REPLACE COMPRESSOR.
This section addresses:
SUnit components (sensors, temperature switch,
pressure switches and demand defrost control)
SSecond−stage operation
UNIT COMPONENTS
Demand Defrost Control (A108)
The demand defrost control measures differential
temperatures to detect when the system is performing
poorly because of ice build−up on the outdoor coil. The
controller self−calibrates when the defrost system starts
and after each system defrost cycle. The demand defrost
control’s: components are shown in figure 25.
SDemand defrost control connections, jumpers and
LED locations are shown in figure 25.
SDemand defrost control connections, jumpers and
LED descriptions are listed on table 9.
SDemand defrost control status, fault and lockout LEDs
are listed in table 10.
24V TERMINAL STRIP
CONNECTIONS (P2)
DIAGNOSTIC LEDS
(DS1 AND DS2)
PRESSURE SWITCH
CIRCUIT
CONNECTIONS
TEST PINS (P1)
Note − Component locations vary by board manufacturer.
SENSOR PLUG IN
(COIL AND
AMBIENT
SENSORS) (P4)
REVERSING VALVE
(O OUT)
DELAY PINS
(P5)
LOW AMBIENT
THERMOSTAT PINS
(P3)
DEFROST TERMINATION
PIN SETTINGS (P1)
Figure 25. Demand Defrost Control (A108)
Page 31
XP16 SERIES
Table 9. Demand Defrost Control (A108) Inputs, Outputs and Configurable Settings
Control
Locations
Control Label or
Description Purpose Function
P1 TEST Test Mode See Test Mode on page 39 for further details.
P1 50, 70, 90, 100
Defrost Temperature
Termination Shunt (Jumper)
Pins
The demand defrost control as illustrated in figure 25 has valid selections
which are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt
termination pin is factory set at 50°F (10°C). If the temperature shunt is
not installed, the default termination temperature is 90°F (32°C).
P2
W1 24VAC Thermostat Input /
Output 24VAC input / output from indoor thermostat to indoor unit.
C24VAC Common 24VAC common
LThermostat Service Light Thermostat service light connection.
R 24VAC 24VAC
Y2 Thermostat Input Controls the second stage operation of the unit.
OThermostat Input Reversing valve solenoid.
Y1 Thermostat Input Controls the operation of the unit.
P3 55, 50, 45, 40 Low Ambient Thermostat
Pins
Provides selection of the Y2 compressor lock−in temperature. Valid
options are 40, 45, 50 and 55 degrees Fahrenheit.
P4
DIS−YEL Coil Sensor (P4−5) Ground connection for outdoor coil temperature sensor.
(P4−6) Connection for outdoor coil temperature sensor.
AMB−BLACK Ambient Sensor (P4−3) Ground connection for outdoor ambient temperature sensor.
(P4−4) Connection for outdoor ambient temperature sensor.
COIL−BROWN Discharge Sensor No discharge sensor is used; replaced by 10K resistor.
P5 DELAY Delay Mode
The demand defrost control has a field−selectable function to reduce
occasional sounds that may occur while the unit is cycling in and out of
the defrost mode. When a jumper is installed on the DELAY pins, the
compressor will be cycled off for 30 seconds going in and out of the
defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTEThe 30 second off cycle is NOT functional when TEST pins on
P1 are jumpered.
P6 TST, PS DF, C, R, O, Y1, Y2 Factory Test Connectors No field use.
DS1 RED LED
Diagnostic LED
Valid states for demand defrost control two LEDs are OFF, ON and
FLASHING which indicate diagnostics conditions that are described in
table 10.
DS2 GREEN LED
FAN TWO CONNECTORS Condenser Fan Operation These two connections provide power for the condenser fan.
O OUT O OUT 24 VAC output 24 VAC output connection for reversing valve.
LO−PS LO−PS Low−Pressure Switch
When the low pressure switch trips, the demand defrost control will cycle
off the compressor, and the strike counter in the demand defrost control
will count one strike. The low pressure switch is ignored under the
following conditions:
Sduring the defrost cycle and 90 seconds after the termination of
defrost
Swhen the average ambient sensor temperature is below 0°F (−18°C)
Sfor 90 seconds following the start up of the compressor
Sduring TEST mode
Y2 OUT Y2 OUT 24 VAC Output 24 VAC output for second stage compressor solenoid.
Y1 OUT Y1 OUT 24 VAC Common Output 24 VAC common output, switched for enabling compressor contactor.
HS−PS HS−PS High−Pressure Switch
When the high pressure switch trips, the demand defrost control will cycle
off the compressor, and the strike counter in the demand defrost control
will count one strike.
L L Service Light Output 24VAC service light output.
24V 24V 24 Volt output 24VAC typically used to supply power to the Lennox System Operation
Monitor (LSOM). Not used in this system.
Page 32
DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the demand defrost control (DS1 [Red] and DS2 [Green]) indicate diagnostics
conditions that are described in table 10.
Table 10. Demand Defrost Control (A108) Diagnostic LEDs
DS1 and DS2 System Status, Fault and Lockout Codes
DS2
Green
DS1
Red Type Condition/Code Possible Cause(s) Solution
OFF OFF Status Power problem
No power (24V) to demand
defrost control terminals R and C
or demand defrost control failure.
1Check control transformer power (24V).
2If power is available to demand defrost con-
trol and LED(s) do not light, replace demand
defrost control.
Simultaneous
SLOW Flash Status Normal operation Unit operating normally or in
standby mode. None required.
Alternating SLOW
Flash Status 5−minute anti−short cycle delay Initial power up, safety trip, end of
room thermostat demand. None required (jumper TEST pins to override)
Simultaneous
FAST Flash Fault Ambient Sensor Problem
Sensor being detected open or shorted or out of temperature range. Demand defrost
control will revert to time/temperature defrost operation. (System will still heat or
cool).
Alternating
FAST Flash Fault Coil Sensor Problem
Sensor being detected open or shorted or out of temperature range. Demand defrost
control will not perform demand or time/temperature defrost operation. (System will
still heat or cool).
ON ON Fault Demand Defrost Control
Failure
Indicates that demand defrost control has internal component failure. Cycle 24VAC
power to demand defrost control. If code does not clear, replace demand defrost
control.
OFF SLOW
Flash Fault Low Pressure Fault 1Restricted air flow over indoor or
outdoor coil.
2Improper refrigerant charge in
system.
3Improper metering device
installed or incorrect operation
of metering device.
4Incorrect or improper sensor
location or connection to
system.
1Remove any blockages or restrictions from
coils and/or fans. Check indoor and outdoor
fan motor for proper current draws.
2Check system charge using subcooling
method.
3Check system operating pressures and
compare to unit subcooling tables in this
instruction or located on unit access panel.
4Make sure all pressure switches and sensors
have secure connections to system to prevent
refrigerant leaks or errors in pressure and
temperature measurements.
OFF ON Lockout Low Pressure Lockout
SLOW
Flash OFF Fault High Pressure Fault
ON OFF Lockout High Pressure Lockout
SLOW
Flash ON Fault Discharge Line Temperature
Fault This code detects shorted sensor or high discharge temperatures. If the discharge
line temperature exceeds a temperature of 285ºF (140ºC) during compressor
operation, the demand defrost control will de−energize the compressor contactor
output (and the defrost output if active). The compressor will remain off until the
discharge temperature has dropped below 225ºF (107ºC).
FAST
Flash ON Lockout Discharge Line Temperature
Lockout
OFF Fast
Flash Fault Discharge Sensor Fault The demand defrost control detects open sensor or out of temperature sensor range.
This fault is detected by allowing the unit to run for 90 seconds before checking
sensor resistance. If the sensor resistance is not within range after 90 seconds, the
demand defrost control will count one fault. After 5 faults, the demand defrost control
will lockout.
Fast
Flash OFF Lockout Discharge Sensor Lockout
(Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
Page 33
XP16 SERIES
High Pressure Switch (S4)
When the high pressure switch trips, the demand defrost
control will cycle off the compressor, and the strike counter
in the demand defrost control will count one strike. High
Pressure (auto reset) − trip at 590 psig, reset at 418.
Low Pressure Switch (S87)
When the low pressure switch trips, the demand defrost
control will cycle off the compressor, and the strike counter
in the demand defrost control will count one strike. Low
pressure switch (auto reset) − trip at 25 psig, reset at 40
psig.
The low pressure switch is ignored under the following
conditions:
SDuring the defrost cycle and 90 seconds after the
termination of defrost
SWhen the average ambient sensor temperature is
below 15° F (−9°C)
SFor 90 seconds following the start up of the
compressor
SDuring test mode
Ambient Sensor (RT13)
The ambient sensor considers outdoor temperatures
below −35°F (−37°C) or above 120°F (48°C) as a fault. If the
ambient sensor is detected as being open, shorted or out
of the temperature range of the sensor, the demand
defrost control will not perform demand defrost operation.
The demand defrost control will revert to time/temperature
defrost operation and will display the appropriate fault
code. Heating and cooling operation will be allowed in this
fault condition.
Coil Sensor (RT21)
Coil SensorThe coil temperature sensor considers
outdoor temperatures below −35°F (−37°C) or above 120°F
(48°C) as a fault. If the coil temperature sensor is detected
as being open, shorted or out of the temperature range of
the sensor, the demand defrost control will not perform
demand or time/temperature defrost operation and will
display the appropriate fault code. Heating and cooling
operation will be allowed in this fault condition.
High Discharge Temperature Sensor (RT28)
If the discharge line temperature exceeds a temperature of
285°F (140°C) during compressor operation, the demand
defrost control will de−energize the compressor contactor
output (and the defrost output, if active). The compressor
will remain off until the discharge temperature has dropped
below 225°F (107°C) and the 5-minute anti−short cycle
delay has been satisfied. This sensor has two fault and
lockout codes:
1. If the demand defrost control recognizes five high
discharge line temperature faults during a single (Y1)
compressor demand, it reverts to a lockout mode and
displays the appropriate code. This code detects
shorted sensor or high discharge temperatures. Code
on demand defrost control is Discharge Line
Temperature Fault and Lockout.
2. If the demand defrost control recognizes five
temperature sensor range faults during a single (Y1)
compressor demand, it reverts to a lockout mode and
displays the appropriate code. The demand defrost
control detects open sensor or out-of-temperature
sensor range. This fault is detected by allowing the unit
to run for 90 seconds before checking sensor
resistance. If the sensor resistance is not within range
after 90 seconds, the demand defrost control will count
one fault. After five faults, the demand defrost control
will lockout. Code on demand defrost control is
Discharge Sensor Fault and Lockout.
The discharge line sensor, which covers a range of 150°F
(65°C) to 350°F (176°C), is designed to mount on a ½"
refrigerant discharge line.
NOTE − Within a single room thermostat demand, if
5−strikes occur, the demand defrost control will lockout the
unit. demand defrost control 24 volt power R must be
cycled OFF or the TEST pins on demand defrost control
must be shorted between 1 to 2 seconds to reset the
demand defrost control.
Crankcase Heater (HR1) and Crankcase Thermostat
Switch (S40)
The reference models are equipped with a 70 watt, belly
band type crankcase heater. HR1 prevents liquid from
accumulating in the compressor. HR1 is controlled by a
thermostat located on the liquid line. When liquid line
temperature drops below 50° F the thermostat closes
energizing HR1. The thermostat will open, de−energizing
HR1 once liquid line temperature reaches 70° F .
Liquid Line Bi−Flow Filter Drier
The unit is equipped with a large−capacity biflow filter drier
which keeps the system clean and dry. If replacement is
necessary, order another of like design and capacity. The
replacement filter drier must be suitable for use with
HFC−410A refrigerant.
The replacement filter drier must be suitable for use with
HFC−410A refrigerant.
SECOND−STAGE OPERATION
If the demand defrost control (A108) receives a call for
second−stage compressor operation Y2 in heating or
cooling mode and the first-stage compressor output is
active, the second-stage compressor solenoid output will
be energized.
If first-stage compressor output is active in heating mode
and the outdoor ambient temperature is below the selected
compressor lock−in temperature, the second-stage
compressor solenoid output will be energized without the
Y2 input. If the jumper is not connected to one of the
temperature selection pins on P3 (40, 45, 50, 55°F), the
default lock−in temperature of 40°F (4.5°C) will be used.
The demand defrost control de−energizes the
second-stage compressor solenoid output immediately
when the Y2 signal is removed or the outdoor ambient
temperature is 5°F above the selected compressor lock−in
temperature, or the first-stage compressor output is
de−energized for any reason.
Page 34
Defrost System
This section addresses:
SEmergency Heat
SDefrost System Overview
SDefrost Control Connections, Jumper Settings and
Features
SOperational Mode Overview (Calibration, Normal and
Defrost)
SDefrost Cycle Actuation
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of the
outdoor unit is required, or when auxiliary electric heat is
staged by outdoor thermostats. When the room thermostat is
placed in the emergency heat position, the outdoor unit
control circuit is isolated from power and field-provided relays
bypass the outdoor thermostats. An amber indicating light
simultaneously comes on to remind the homeowner that he
is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power
outage if power has been off for over an hour and the
outdoor temperature is below 50°F (10°C). System should
be left in the emergency heat mode at least six hours to
allow the crankcase heater sufficient time to prevent
compressor slugging.
DEFROST SYSTEM OVERVIEW
The control monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a
defrost cycle is required. The coil temperature probe is
designed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
proper defrost operation.
NOTE − The demand defrost control accurately measures
the performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the demand defrost control initiates
defrost cycles.
DEFROST CONTROL CONNECTIONS, JUMPERS
SETTINGS AND FEATURES
Pressure Switch 5−Strike Lockout
The internal control logic of the demand defrost control
counts the pressure switch trips only while the Y1 (Input)
line is active. If a pressure switch opens and closes four
times during a Y1 (Input), the control logic will reset the
pressure switch trip counter to zero at the end of the Y1
(Input). If the pressure switch opens for a fifth time during
the current Y1 (Input), the control will enter a lockout
condition.
The 5−strike pressure switch lockout condition can be reset
by cycling OFF the 24−volt power to the demand defrost
control or by shorting the TEST pins between 1 to 2
seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is
engaged, a 5−minute short cycle will occur after the switch
closes.
Demand Defrost Control Pressure Switch
Connections
The unit’s automatic reset pressure switches (LO PS − S87
and HI PS − S4) are factory−wired into the demand defrost
control on the LO−PS and HI−PS terminals, respectively.
Demand Defrost Control Sensors
Sensors connect to the demand defrost control through a
field-replaceable harness assembly that plugs into the
demand defrost control as illustrated in figure 1. Through
the sensors, the demand defrost control detects outdoor
ambient, coil, and discharge temperature fault conditions.
As the detected temperature changes, the resistance
across the sensor changes.
Testing Demand Defrost Control Sensors
Sensor resistance values can be checked by ohming
across pins shown in table 11.
Table 11. Sensor Temperature /Resistance Range
Sensor
Temperature
Range °F (°C)
Resistance values
range (ohms)
Pins/W
ire
Color
Outdoor −35 (−37) to 120 (48) 280,000 to 3750 3 & 4
(Black)
Coil −35 (−37) to 120 (48) 280,000 to 3750 5 & 6
(Brown)
Discharge (if
applicable)
24 (−4) to 350 (176) 41,000 to 103 1 & 2
(Yellow)
Note: Sensor resistance increases as sensed temperature decreases.
Tables 12 and 13 shows how the resistance varies as the
temperature changes for various types of sensors.
NOTE − When checking the ohms across a sensor, be
aware that a sensor showing a resistance value that is not
within the range shown in table 11, may be performing as
designed. However, if a shorted or open circuit is detected,
then the sensor may be faulty and the sensor harness will
need to be replaced.
Defrost Temperature Termination Jumper
Settings (P1)
The demand defrost control selections are: 50, 70, 90, and
100°F (10, 21, 32 and 38°C). The shunt termination pin is
factory set at 50°F (10°C). If temperature shunt is not
installed, default termination temperature is 90°F (32°C).
Test Pins (P1) Function
Placing the jumper on the field test pins (P1) allows the
technician to:
SClear short cycle lockout
SClear five−strike fault lockout
SCycle the unit in and out of defrost mode
SPlace the unit in defrost mode to clear the coil
See figure 27 for flowchart of test pin (P1) operations.
Page 35
XP16 SERIES
Compressor Delay Mode (P5)
The demand defrost control has a field−selectable function
to reduce occasional sounds that may occur while the unit
is cycling in and out of the defrost mode. When a jumper is
installed on the DELAY pins, the compressor will be cycled
off for 30 seconds going in and out of the defrost mode.
Units are shipped with jumper installed on DELAY pins.
NOTE − The 30 second off cycle is NOT functional when
jumpering the TEST pins.
OPERATIONAL MODE OVERVIEW
The demand defrost control has three basic operational
modes. Those modes are:
1. Calibration Mode The demand defrost control is
considered uncalibrated when power is applied to the
demand defrost control, after cool mode operation, or
if the coil temperature exceeds the termination
temperature when it is in heat mode (see figure 26 for
further details).
2. Normal Mode  The demand defrost control
monitors the O line, to determine the system operating
mode (heat/cool), outdoor ambient temperature, coil
temperature (outdoor coil) and compressor run time to
determine when a defrost cycle is required.
Calibration of the demand defrost control occurs after
a defrost cycle to ensure that there is no ice on the coil.
During calibration, the temperature of both the coil and
the ambient sensor are measured to establish the
temperature differential which is required to allow a
defrost cycle.
3. Defrost Mode  The following paragraphs provide a
detailed description of the defrost system operation.
DEFROST CYCLE ACTUATION
The demand defrost control initiates a defrost cycle based
on either frost detection or time.
1. Frost Detection  If the compressor runs longer than
30 minutes and the actual difference between the clear
coil and frosted coil temperatures exceeds the
maximum difference allowed by the demand defrost
control, a defrost cycle will be initiated.
2. Time  If six hours of heating mode compressor run
time has elapsed since the last defrost cycle while the
coil temperature remains below 35°F (2°C), the
demand defrost control will initiate a defrost cycle.
Actuation
When the reversing valve is de−energized, the Y1 circuit is
energized, and the coil temperature is below 35°F (2°C),
the demand defrost control logs the compressor run time.
If the demand defrost control is not calibrated, a defrost
cycle will be initiated after 30 minutes of heating mode
compressor run time. The control will attempt to
self−calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system
temperatures during the 20−minute calibration period. If
the demand defrost control fails to calibrate, another
defrost cycle will be initiated after 45 minutes of heating
mode compressor run time. Once the demand defrost
control is calibrated, it initiates a demand defrost cycle
when the difference between the clear coil and frosted coil
temperatures exceeds the maximum difference allowed
by the control or after six hours of heating mode
compressor run time has been logged since the last
defrost cycle.
Termination
The defrost cycle ends when the coil temperature exceeds
the termination temperature or after 14 minutes of defrost
operation. If the defrost is terminated by the 14−minute
timer, another defrost cycle will be initiated after 30
minutes of run time.
Page 36
DEFROST CONTROL (A108) CALIBRATION MODE SEQUENCE
Occurs after power up and cooling operation, or if the coil temperature exceeds
the termination temperature while in Heat Mode.
Demand defrost control defaults to 30 minute  Time / Temperature Mode
Reset Compressor Runtime / Reset Three / Five Strike Counter
DEMAND MODE
Accumulate compressor runtime of
more than 30 minutes while coil
temperature is below 35° F (2°C).
When the accumulated compressor
time exceeds six (6) hours or if the
coil sensor indicates frost is present
on coil, go to Defrost.
THIRTY (30) MINUTE TIME /
TEMPERATURE MODE
Accumulate compressor runtime
while coil temperature is below 35° F
(2°C). When the accumulated
compressor time exceeds 30 minutes
go to Defrost.
45 MINUTE
TIME/TEMPERATURE MODE
Accumulate compressor runtime
while coil temperature is below 35°
F (2°C). When the accumulated
compressor time exceeds 45
minutes go to Defrost.
DEFROST
SOutdoor Fan OFF
SReversing Valve ON
SW1 line ON
Monitor coil temperature and
time in defrost mode.
HOW DID DEFROST TERMINATE?
Coil temperature was above 35°F (2°C) for four (4)
minutes. of the 14−minute defrost OR reached
defrost termination temperature.
Defrosted for 14−minute without the coil temperature
going above 35°F (2°C) for four (4) minutes and coil
did not reach termination temperature.
Attempt to Calibration  Temperature measurements are not taken for the first few minutes of each heat demand. This is
to allow coil temperatures to stabilize. demand defrost control has a maximum of 20 minutes of accumulated compressor
runtime in heat mode to calibrate demand defrost control This may involve more than one heating demand.
Was stable coil temperature attained
within 20 minutes?
NO  Demand defrost control
reverts to 45 minute time /
temperature.
DEFROST TERMINATION
SCompressor runtime counter RESET
SOutdoor Fan ON
SReversing Valve OFF
SW1 line OFF
DEFROST TERMINATION
SCompressor runtime counter RESET
SOutdoor Fan ON
SReversing Valve OFF
SW1 line OFF
YES  Calibration occurred
Figure 26. Defrost Calibration
Page 37
XP16 SERIES
Table 12. Ambient (RT13) and Coil (RT21) Sensors Temperature / Resistance Range
Degrees
Fahrenheit Resistance Degrees
Fahrenheit Resistance Degrees
Fahrenheit Resistance Degrees
Fahrenheit Resistance
136.3 2680 56.8 16657 21.6 44154 −11.3 123152
133.1 2859 56.0 16973 21.0 44851 −11.9 125787
130.1 3040 55.3 17293 20.5 45560 −12.6 128508
127.3 3223 54.6 17616 20.0 46281 −13.2 131320
124.7 3407 53.9 17942 19.4 47014 −13.9 134227
122.1 3592 53.2 18273 18.9 47759 −14.5 137234
119.7 3779 52.5 18607 18.4 48517 −15.2 140347
117.5 3968 51.9 18945 17.8 49289 −15.9 143571
115.3 4159 51.2 19287 17.3 50074 −16.5 146913
113.2 4351 50.5 19633 16.8 50873 −17.2 150378
111.2 4544 49.9 19982 16.3 51686 −17.9 153974
109.3 4740 49.2 20336 15.7 52514 −18.6 157708
107.4 4937 48.5 20695 15.2 53356 −19.3 161588
105.6 5136 47.9 21057 14.7 54215 −20.1 165624
103.9 5336 47.3 21424 14.1 55089 −20.8 169824
102.3 5539 46.6 21795 13.6 55979 −21.5 174200
100.6 5743 46.0 22171 13.1 56887 −22.3 178762
99.1 5949 45.4 22551 12.5 57811 −23.0 183522
97.6 6157 44.7 22936 12.0 58754 −23.8 188493
96.1 6367 44.1 23326 11.5 59715 −24.6 193691
94.7 6578 43.5 23720 11.0 60694 −25.4 199130
93.3 6792 42.9 24120 10.4 61693 −26.2 204829
92.0 7007 42.3 24525 9.9 62712 −27.0 210805
90.6 7225 41.7 24934 9.3 63752 −27.8 217080
89.4 7444 41.1 25349 8.8 64812 −28.7 223677
88.1 7666 40.5 25769 8.3 65895 −29.5 230621
86.9 7890 39.9 26195 7.7 67000 −30.4 237941
85.7 8115 39.3 26626 7.2 68128 −31.3 245667
84.5 8343 38.7 27063 6.7 69281 −32.2 253834
83.4 8573 38.1 27505 6.1 70458 −33.2 262482
82.3 8806 37.5 27954 5.6 71661 −34.1 271655
81.2 9040 37.0 28408 5.0 72890 −35.1 281400
80.1 9277 36.4 28868 4.5 74147 −36.1 291774
79.0 9516 35.8 29335 3.9 75431 −37.1 302840
78.0 9757 35.2 29808 3.4 76745 −38.2 314669
77.0 10001 34.7 30288 2.8 78090 −39.2 327343
76.0 10247 34.1 30774 2.3 79465
75.0 10496 33.5 31267 1.7 80873
74.1 10747 33.0 31766 1.2 82314
73.1 11000 32.4 32273 0.6 83790
72.2 11256 31.9 32787 0.0 85302
71.3 11515 31.3 33309 −0.5 86852
70.4 11776 30.7 33837 −1.1 88440
69.5 12040 30.2 34374 −1.7 90068
68.6 12306 29.6 34918 −2.2 91738
67.7 12575 29.1 35471 −2.8 93452
66.9 12847 28.6 36031 −3.4 95211
66.0 13122 28.0 36600 −4.0 97016
65.2 13400 27.5 37177 −4.6 98870
64.4 13681 26.9 37764 −5.2 100775
63.6 13964 26.4 38359 −5.7 102733
62.8 14251 25.8 38963 −6.3 104746
62.0 14540 25.3 39577 −6.9 106817
61.2 14833 24.8 40200 −7.5 108948
60.5 15129 24.2 40833 −8.2 111141
59.7 15428 23.7 41476 −8.8 113400
59.0 15730 23.2 42130 −9.4 115727
58.2 16036 22.6 42794 −10.0 118126
57.5 16345 22.1 43468 −10.6 120600
Page 38
Table 13. High Discharge Sensor (RT28) Temperature / Resistance Range
Degrees
Fahrenheit Resistance Degrees
Fahrenheit Resistance Degrees
Fahrenheit Resistance Degrees
Fahrenheit Resistance
303.1 183 186.1 1052 136.8 2656 94.5 6613
298.1 195 185.0 1072 136.0 2698 93.6 6739
293.4 207 183.9 1093 135.2 2740 92.8 6869
289.0 220 182.8 1114 134.5 2783 92.0 7002
284.8 232 181.8 1135 133.7 2827 91.2 7139
280.9 245 180.7 1157 132.9 2872 90.3 7281
277.1 258 179.6 1179 132.2 2917 89.5 7426
273.6 270 178.6 1201 131.4 2963 88.6 7575
270.2 283 177.6 1223 130.6 3010 87.8 7729
267.0 297 176.6 1245 129.9 3057 86.9 7888
263.9 310 175.5 1268 129.1 3105 86.0 8051
260.9 323 174.6 1291 128.4 3154 85.2 8220
258.1 336 173.6 1315 127.6 3204 84.3 8394
255.3 350 172.6 1338 126.8 3255 83.4 8574
252.7 364 171.6 1362 126.1 3307 82.5 8759
250.1 378 170.6 1386 125.3 3359 81.6 8951
247.7 391 169.7 1411 124.6 3413 80.7 9149
245.3 405 168.7 1435 123.8 3467 79.8 9354
243.0 420 167.8 1460 123.1 3523 78.8 9566
240.8 434 166.9 1486 122.3 3579 77.9 9786
238.6 448 165.9 1511 121.6 3637 76.9 10013
236.5 463 165.0 1537 120.8 3695 76.0 10250
234.4 478 164.1 1563 120.1 3755 75.0 10495
232.4 492 163.2 1590 119.3 3816 74.1 10749
230.5 507 162.3 1617 118.5 3877 73.1 11014
228.6 523 161.4 1644 117.8 3940 72.1 11289
226.7 538 160.5 1672 117.0 4005 71.1 11575
224.9 553 159.7 1699 116.3 4070 70.0 11873
223.2 569 158.8 1728 115.5 4137 69.0 12184
221.5 584 157.9 1756 114.8 4205 68.0 12509
219.8 600 157.1 1785 114.0 4274 66.9 12848
218.1 616 156.2 1815 113.2 4345 65.8 13202
216.5 632 155.3 1845 112.5 4418 64.7 13573
214.9 649 154.5 1875 111.7 4491 63.6 13961
213.4 665 153.6 1905 111.0 4567 62.5 14368
211.9 682 152.8 1936 110.2 4644 61.3 14796
210.4 698 152.0 1968 109.4 4722 60.2 15246
208.9 715 151.1 1999 108.7 4802 59.0 15719
207.5 732 150.3 2032 107.9 4884 57.8 16218
206.0 750 149.5 2064 107.1 4968 56.6 16744
204.6 767 148.7 2098 106.4 5054 55.3 17301
203.3 785 147.9 2131 105.6 5141 54.0 17891
201.9 803 147.1 2165 104.8 5231 52.7 18516
200.6 821 146.2 2200 104.0 5323 51.4 19180
199.3 839 145.4 2235 103.3 5416 50.0 19887
198.0 857 144.6 2270 102.5 5512 48.6 20641
196.8 876 143.8 2306 101.7 5610 47.2 21448
195.5 894 143.0 2343 100.9 5711 45.7 22311
194.3 913 142.3 2380 100.1 5814
193.1 932 141.5 2418 99.3 5920
191.9 952 140.7 2456 98.5 6028
190.7 971 139.9 2495 97.7 6139
189.5 991 139.1 2534 96.9 6253
188.4 1011 138.3 2574 96.1 6370
187.2 1031 137.6 2615 95.3 6489
Page 39
XP16 SERIES
TEST
Placing the jumper on the field test pins (P1) allows the technician to:
SClear short cycle lockout
SClear five−strike fault lockout
SCycle the unit in and out of defrost mode
SPlace the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to
5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal
operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one
second and then reapplied.
NOTE Placing a jumper on the TEST pins will not bring the unit
out of inactive mode. The only way manually activate the heat
pump from an inactive mode is to cycle the 24VAC power to the
Control.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less
than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable. No other functions will be
executed and unit will continue in the
mode it was operating.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable.
If in HEATING Mode
If in DEFROST Mode
No further test mode operation will be
executed until the jumper is removed
from the TEST pins and reapplied.
If no ambient or coil sensor fault
exist, unit will go into DEFROST
MODE.
If ambient or coil faults exist (open or
shorted), unit will remain in HEAT
MODE.
The unit will terminate defrost and
enter HEAT MODE uncalibrated
with defrost timer set for 45 minute
test.
If jumper on TEST pins remains in
place for more than five seconds.
The unit will return to HEAT MODE
uncalibrated with defrost timer set
for 34 minutes.
If jumper on TEST pins is removed
before a maximum of five seconds.
The unit will remain in DEFROST
MODE until termination on time or
temperature.
O Line Status INACTIVE
ACTIVE
If in COOLING Mode
Figure 27. Test Pin (P1) Functions
Page 40
Two−Stage Modulation Compressors
Checks
Use this checklist on page 42 to verify part-load and
full-load capacity operation of two-stage modulation
compressors.
TOOLS REQUIRED
SRefrigeration gauge set
SDigital volt/amp meter
SElectronic temperature thermometer
SOn-off toggle switch
IMPORTANT
This performance check is ONLY valid on systems that
have clean indoor and outdoor coils, proper airflow over
coils, and correct system refrigerant charge. All
components in the system must be functioning proper to
correctly perform compressor modulation operational
check. (Accurate measurements are critical to this test
as indoor system loading and outdoor ambient can affect
variations between low and high capacity readings).
PROCEDURE
NOTE − Block outdoor coil to maintain a minimum of 375
psig during testing).
1. Turn main power OFF to outdoor unit.
2. Adjust room thermostat set point 5ºF above the room
temperature.
3. Remove control access panel. Install refrigeration
gauges on unit. Attach the amp meter to the common
(black wire) wire of the compressor harness. Attach
thermometer to discharge line as close as possible to
the compressor.
4. Turn toggle switch OFF and install switch in series with
Y2 wire from room thermostat.
5. Cycle main power ON.
6. Allow pressures and temperatures to stabilize before
taking measurements (may take up to 10 minutes).
7. Record all of the readings for the Y1 demand.
8. Close switch to energize Y2 demand. Verify power is
going to compressor solenoid.
9. Allow pressures and temperatures to stabilize before
taking measurements (may take up to 10 minutes).
10. Record all of the readings with the Y1 and Y2 demand.
11. If temperatures and pressures change in the direction
noted in Two−Stage Modulation Compressor Field
Operational Checklist on page 42, the compressor is
properly modulating from low to high capacity. (If no
amperage, pressures or temperature readings
change when this test is performed, the compressor
is not modulating between low and high capacity and
replacement is necessary).
12. After testing is complete, return unit to original set up.
Maintenance
DEALER
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:
Outdoor Unit
1. Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed.
No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
7. Inspect drain holes in coil compartment base and
clean if necessary.
NOTE - If insufficient heating or cooling occurs, the unit
should be gauged and refrigerant charge should be
checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more
frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may contain
high levels of corrosive chemicals such as salts)
SOutdoor Coil  The outdoor coil may be flushed with
a water hose.
SOutdoor Coil (Sea Coast)  Moist air in ocean
locations can carry salt, which is corrosive to most
metal. Units that are located near the ocean require
frequent inspections and maintenance. These
inspections will determine the necessary need to wash
the unit including the outdoor coil. Consult your
installing contractor for proper intervals/procedures
for your geographic area or service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and
permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper
tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Page 41
XP16 SERIES
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of
oil leaks.
3. Check condensate line and clean if necessary.
HOMEOWNER
Cleaning of the outdoor unit’s coil should be performed by
a trained service technician. Contact your dealer and set
up a schedule (preferably twice a year, but at least once a
year) to inspect and service your outdoor unit. The
following maintenance may be performed by the
homeowner.
IMPORTANT
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure of the
unit to treated water (i.e., sprinkler systems, soakers,
waste water, etc.) will corrode the surface of steel and
aluminum parts and diminish performance and longevity
of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its
proper operation.
SPlease contact your dealer to schedule proper
inspection and maintenance for your equipment.
SMake sure no obstructions restrict airflow to the
outdoor unit.
SGrass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more
energy.
SKeep shrubbery trimmed away from the unit and
periodically check for debris which collects around the
unit.
Cleaning of the outdoor unit’s coil should be performed by
a trained service technician. Contact your dealer and set
up a schedule (preferably twice a year, but at least once a
year) to inspect and service your outdoor unit.
Routine Maintenance
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
1. Air Filter  Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either
at the indoor unit (installed internal or external to the
cabinet) or behind a return air grille in the wall or
ceiling. Check the filter monthly and clean or replace
it as needed.
2. Disposable Filter Disposable filters should be
replaced with a filter of the same type and size.
NOTE If you are unsure about the filter required for your
system, call your Lennox dealer for assistance.
3. Reusable Filter  Many indoor units are equipped
with reusable foam filters. Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.
NOTE The filter and all access panels must be in place
any time the unit is in operation.
4. Indoor Unit  The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)
Thermostat Operation
See the thermostat homeowner manual for instructions on
how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
SHeat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
SDo not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45F (7C). An electronic control activates a
defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
SDuring the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the
conclusion of the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the
EMERGENCY HEAT setting to obtain temporary heat
without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is
satisfied by auxiliary heat; heat pump operation is locked
out. After a six-hour compressor crankcase warm-up
period, the thermostat can be switched to the HEAT setting
and normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before
calling for service:
SVerify room thermostat settings are correct.
SVerify that all electrical disconnect switches are ON.
SCheck for any blown fuses or tripped circuit breakers.
SVerify unit access panels are in place.
SVerify air filter is clean.
SIf service is needed, locate and write down the unit
model number and have it handy before calling.
Page 42
Accessories
For update−to−date information, see any of the following
publications:
SLennox XP16 Engineering Handbook
SLennox Product Catalog
SLennox Price Book
Checklists
Two−Stage Modulation Compressors Field Operational Checklist
Unit Readings Y1 − First-Stage
Expected results during Y2 demand
(Toggle switch On) Y2 − Second-Stage
COMPRESSOR
Voltage Same
Amperage Higher
OUTDOOR UNIT FAN MOTOR
Amperage Same or Higher
TEMPERATURE
Ambient Same
Outdoor Coil Discharge Air Higher
Compressor Discharge Line Higher
Indoor Return Air Same
Indoor Coil Discharge Air Lower
PRESSURES
Suction (Vapor) Lower
Liquid Higher
Page 43
XP16 SERIES
XP16 Start−Up and Performance
Customer Address
Indoor Unit Model Serial
Outdoor Unit Model Serial
Notes:
START UP CHECKS
Refrigerant Type:
1st Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts
2nd Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts
Outdoor Unit Fan Full Load Amps Actual Amps: 1st Stage 2nd Stage
COOLING MODE
Suction Pressure: 1st Stage: 2nd Stage:
Liquid Pressure: 1st Stage: 2nd Stage:
Supply Air Temperature: 1st Stage: 2nd Stage:
Temperature: Ambient: Return Air:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach tempera-
tures.)
Subcooling: A
B
=
SUBCOOLING
Saturated Condensing Temperature (A) minus Liquid
Line Temperature (B)
Approach: A
B
=
APPROACH
Liquid Line Temperature (A) minus Outdoor Air
Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F) A
B
=
COIL TEMP DROP
Return Air Temperature (A) minus Supply Air
Temperature (B)

Navigation menu