Liebert Libert Xd Chiller Xdc With Icom Controls Dpn001599 Rev 12 11 Users Manual SUBTL XDC160 UNIT

DPN001599 REV 1211 to the manual 3da95c1b-0553-4ac0-994b-9762a971557e

2015-02-09

: Liebert Liebert-Libert-Xd-Chiller-Xdc-With-Icom-Controls-Dpn001599-Rev-12-11-Users-Manual-571444 liebert-libert-xd-chiller-xdc-with-icom-controls-dpn001599-rev-12-11-users-manual-571444 liebert pdf

Open the PDF directly: View PDF PDF.
Page Count: 6

DownloadLiebert Liebert-Libert-Xd-Chiller-Xdc-With-Icom-Controls-Dpn001599-Rev-12-11-Users-Manual- SUBTL XDC160 ICOM UNIT  Liebert-libert-xd-chiller-xdc-with-icom-controls-dpn001599-rev-12-11-users-manual
Open PDF In BrowserView PDF
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS

STANDARD FEATURES
TANDEM COMPRESSORS - Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, manual reset high-pressure switch and pump
down low-pressure switch.
REFRIGERATION SYSTEM - Dual R-407C refrigeration circuits each including liquid line filter dryers, refrigerant sight glass with moisture indicator,
electronic control valve, adjustable externally equalized expansion valves and liquid line solenoid valves.
HEAT EXCHANGER - Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.
PUMPS - Centrifugal type. Uses R-134a.
STANDARD CONTROL PROCESSOR - The standard control system is microprocessor-based with an external LCD numerical display to allow
observation of specified settable functions. Normal operating conditions are indicated on the LCD display panel, which is mounted to the unit. The control
system also monitors unit operation and activates an alarm when any of the specified factory preset conditions are exceeded.
CABINET AND FRAME - Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a protected
enclosure for all high voltage components. Frame is constructed of 14 gauge heli-arc welded tubular steel and painted using an auto-deposition coating
system.
CANBUS ISOLATOR - Electrically isolates external CANBUS from internal CANBUS. Allows for greater total length of external CANBUS cables.

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 1/6

REV 12/11
REV 4

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
B
Overall

A
Overall

C
F
Height of Unit

SHADED AREAS INDICATE A RECOMMENDED
CLEARANCE OF 36in (914mm) BE PROVIDED FOR
COMPONENT ACCESS.
E
Unit Base

D
Unit Base

UNIT DIMENSIONAL DATA

1in
25.4mm

RECOMMENDED MINIMUM
HOT GAS SUPPLY &
LIQUID RETURN
PIPING OPENING
D

17in
431.8mm

5in
127 mm

2in
50.8mm

FLOOR CUTOUT DIMENSIONS
SHIPPED WEIGHT
lbs (kg)

DIMENSIONAL DATA inches (mm)
MODEL
50/60 HZ
XDC160

A

B*

74 (1880) 34 (864)

C
33-1/8 (841)

D

E

F

DOM.

EXPORT

33 (838) 72 (1829) 78 (1981) 1975 (896) 2109 (957)

* Dimension Does Not Include the Bezel of the Disconnect Switch or iCOM Display.
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 2/6

REV 12/11
REV 4

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
To First Cooling Module or
Bypass Flow Controller **
Install Replaceable Filter Drier Assembly
in Liquid Supply Line
22in
559mm

21in
533mm

Orientation
Defined by
Installer.*

3 1/4in
83mm

Return Line From

A Cooling Units

(line is spin closed)
(elbow customer provided)

Supply Line
B Liquid
To Cooling Units

DIMENSIONS ARE SUBJECT
TO CHANGE WITHOUT NOTICE.
47in
1194 mm

8in
203mm *

~ 44in
1118 mm

6in
152 mm
23in
584 mm

* Allow 8in (204mm) Of Clearance For Filter Replacement.
Filter assembly may be positioned horizontally.
** To Ensure All Refrigerant Flow is Filtered, Install the Filter
Drier Assembly Between the Discharge Line of the Liebert
XDC and the first Bypass Flow Controller or the first
Liebert XD Cooling Module.

C Hot Gas Refrigerant Lines

D Liquid Refrigerant Lines

UNIT PIPING OUTLET CONNECTION SIZES, inches
MODEL
A
B
C
D
50/60 HZ
OD CU OD CU OD CU OD CU
XDC160

2-1/8

1-1/8

1-3/8

7/8

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 3/6

REV 12/11
REV 4

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Bypass Flow Control Assembly
Return Main
Field Supplied and
Field Installed

LIEBERT
XD
COOLING
MODULE

Bypass Flow Controller
Factory Supplied and
Field Installed
Field Supplied and
Field Installed

Ball Valve

Supply Main

RETURN

Flow Direction
Must be toward
Return Main.

Install Bypass Flow Control Assembly
between the Liebert XDC and first
Liebert XD Cooling module. See System
Design Manual SL-16655 for quantity
required.

SUPPLY
Replaceable
Filter Drier
Assembly

Install Replaceable
Filter Drier Assembly
in liquid supply line

RETURN

SUPPLY

LIEBERT XDC

Factory Piping
Field Piping

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 4/6

REV 12/11
REV 4

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Three phase electric
service not provided
by Liebert.

Factory installed unit
disconnect switches

iCOM display
Field supplied disconnect
switch may not be required,
check local codes.

HEAT REJECTION CONNECTION (R-407C Side)
Field supplied 24V. Class 1 wiring to
interlock heat rejection from pigtails:
70A & 71A - Compressor 1 circuit
70B & 71B - Compressor 2 circuit
70C & 71C - Dual Cool relay (optional)

Three phase electric service
not by Liebert.
ELECTRIC CONDUIT KNOCKOUTS
On top of electric box. Knockout size
2 in (51 mm)

EARTH GROUND CONNECTION
Connection terminal for field supplied
earth grounding wire.

Electrical handy box factory
installed with cover.
THREE PHASE CONNECTION
Electric service connection terminals
CANBUS ISOLATOR
ALARM AND WARNING OUTPUT RELAYS
Field supplied 24V Class 2 wire for
special alarms.
(Not to exceed 1.0A @ 24v each.)

Factory wired to components
on electric panel

REMOTE UNIT SHUTDOWN
Replace existing jumper between terminals
37 & 38 with normally closed switch having
a minimum 50VA rating. Use field supplied
24V Class 2 wire.

Factory installed disconnect switch

EARTH GROUND BAR (50Hz only)
Connection terminal with factory
ground from each high voltage
component

INTELLISLOTS®
Two Liebert Intellislots® for optional
OCWEB-LBDS or OC485-LBDS card.
60HZ COMPONENTS SHOWN

NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 5/6

REV 12/11
REV 4

LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
Liebert XDC Extra Low Voltage field connection points
TO P66 ON ICOM CONTROL BOARD

TO P64 ON ICOM CONTROL BOARD
RED ETHER NET CABLE

TERMINATION PLUG

TO LIEBERT XD COOLING
MODULE AND REMOTE
T/H SENSOR B
TO REMOTE T/H SENSOR A

COMMON WARNING OUTPUT

TO OPTIONAL
EXTERNAL
CONNECTIONS

FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
P64

P66 P67

K11
K11
K11NO K11COM K11NC
TO REMOTE ALARM
CIRCUIT BY OTHERS

INPUT: REMOTE ALARM DEVICE
FOR INDICATION OF ALARM, WIRE
N.O. CONTACTS FROM REMOTE
ALARM DEVICE AS SHOWN.

UNIT DISPLAY (REAR VIEW)

24

FACTORY WIRED
TEMPERATURE SENSOR.

50

N.O. CONTACT BY OTHERS

INPUT: CONDENSATION
DETECTION

P67

ALARM WHEN CLOSED.

DO NOT
USE

24

51

N.O. CONTACTS REQUIRED

1

INPUT: FAN BREAKER STATUS
ALARM WHEN CLOSED.
24

54

N.O. CONTACTS REQUIRED

COMMON ALARM OUTPUT
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V

K3NO

TO REMOTE ALARM
CIRCUIT BY OTHERS

1

INPUT: REMOTE SHUTDOWN

NOTES:
1.

CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).

2.

REQUIRES SHIELDED CABLE.

K3
K3
K3COM K3NC

FOR SHUTDOWN OF CONTROL
CIRCUIT, REMOVE JUMPER
BETWEEN TERMINALS 37 & 38
AND REPLACE WITH N.C. CONTACT
37

38

N.C. CONTACTS BY OTHERS

1

2

REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.

DPN001599

PAGE 6/6

REV 12/11
REV 4



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Producer                        : GPL Ghostscript RELEASE CANDIDATE 9.01
Keywords                        : 
Modify Date                     : 2011:12:13 12:52:02-05:00
Create Date                     : 2011:12:02 09:26:11+01:00
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2011:12:13 12:52:02-05:00
Document ID                     : ca37866f-1f1a-11e1-0000-0dbbd2fc6e54
Instance ID                     : uuid:997a5318-d777-4acf-b4eb-86404114e0c1
Format                          : application/pdf
Title                           : SUBTL XDC160 ICOM UNIT
Creator                         : adolphb3354
Description                     : 
Page Count                      : 6
Subject                         : 
Author                          : adolphb3354
EXIF Metadata provided by EXIF.tools

Navigation menu