REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599 REV 12/11
REV 4
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
PAGE 1/6
STANDARD FEATURES
TANDEM COMPRESSORS - Scroll with a suction gas cooled motor, vibration isolators, thermal overloads, manual reset high-pressure switch and pump
down low-pressure switch.
REFRIGERATION SYSTEM - Dual R-407C refrigeration circuits each including liquid line filter dryers, refrigerant sight glass with moisture indicator,
electronic control valve, adjustable externally equalized expansion valves and liquid line solenoid valves.
HEAT EXCHANGER - Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.
PUMPS - Centrifugal type. Uses R-134a.
STANDARD CONTROL PROCESSOR - The standard control system is microprocessor-based with an external LCD numerical display to allow
observation of specified settable functions. Normal operating conditions are indicated on the LCD display panel, which is mounted to the unit. The control
system also monitors unit operation and activates an alarm when any of the specified factory preset conditions are exceeded.
CABINET AND FRAME - Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a protected
enclosure for all high voltage components. Frame is constructed of 14 gauge heli-arc welded tubular steel and painted using an auto-deposition coating
system.
CANBUS ISOLATOR - Electrically isolates external CANBUS from internal CANBUS. Allows for greater total length of external CANBUS cables.
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599 REV 12/11
REV 4
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
PAGE 2/6
B
Overall
F
Height of Unit
A
Overall
SHADED AREAS INDICATE A RECOMMENDED
CLEARANCE OF 36in (914mm) BE PROVIDED FOR
COMPONENT ACCESS.
C
UNIT DIMENSIONAL DATA
D
Unit Base
E
Unit Base
FLOOR CUTOUT DIMENSIONS
5in
127 mm
RECOMMENDED MINIMUM
HOT GAS SUPPLY &
LIQUID RETURN
PIPING OPENING
D
1in
25.4mm
2in
50.8mm
17in
431.8mm
* Dimension Does Not Include the Bezel of the Disconnect Switch or iCOM Display.
MODEL
50/60 HZ A B * C D E F DOM. EXPORT
XDC160 74 (1880) 34 (864) 33-1/8 (841) 33 (838) 72 (1829) 78 (1981) 1975 (896) 2109 (957)
DIMENSIONAL DATA inches (mm)
SHIPPED WEIGHT
lbs (kg)
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599 REV 12/11
REV 4
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
PAGE 3/6
DIMENSIONS ARE SUBJECT
TO CHANGE WITHOUT NOTICE.
44in
1118 mm
~
47in
1194 mm
6in
152 mm
23in
584 mm
Install Replaceable Filter Drier Assembly
in Liquid Supply Line
Orientation
Defined by
Installer.*
To First Cooling Module or
Bypass Flow Controller **
* Allow 8in (204mm) Of Clearance For Filter Replacement.
Filter assembly may be positioned horizontally.
** To Ensure All Refrigerant Flow is Filtered, Install the Filter
Drier Assembly Between the Discharge Line of the Liebert
XDC and the first Bypass Flow Controller or the first
Liebert XD Cooling Module.
21in
533mm
8in
203mm *
22in
559mm
3 1/4in
83mm
Liquid Supply Line
To Cooling Units
Hot Gas Refrigerant Lines Liquid Refrigerant Lines
CD
XDC160 2-1/8 1-1/8 1-3/8 7/8
MODEL
50/60 HZ
UNIT PIPING OUTLET CONNECTION SIZES, inches
A
OD CU
B
OD CU
C
OD CU
D
OD CU
Return Line From
Cooling Units
(line is spin closed)
(elbow customer provided)
A
B
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599 REV 12/11
REV 4
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
PAGE 4/6
LIEBERT XDC
RETURN SUPPLY
LIEBERT
XD
COOLING
MODULE
Install Replaceable
Filter Drier Assembly
in liquid supply line
Flow Direction
Must be toward
Return Main.
Replaceable
Filter Drier
Assembly
RETURN
SUPPLY
Factory Piping
Field Piping
Bypass Flow Control Assembly
Return Main
Supply Main
Bypass Flow Controller
Factory Supplied and
Field Installed
Field Supplied and
Field Installed
Field Supplied and
Field Installed
Install Bypass Flow Control Assembly
between the Liebert XDC and first
Liebert XD Cooling module. See System
Design Manual SL-16655 for quantity
required.
Ball Valve
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599 REV 12/11
REV 4
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
PAGE 5/6
Three phase electric
service not provided
by Liebert.
Field supplied disconnect
switch may not be required,
check local codes.
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
60HZ COMPONENTS SHOWN
Factory installed disconnect switch
EARTH GROUND CONNECTION
Connection terminal for field supplied
earth grounding wire.
HEAT REJECTION CONNECTION (R-407C Side)
Field supplied 24V. Class 1 wiring to
interlock heat rejection from pigtails:
70A & 71A - Compressor 1 circuit
70B & 71B - Compressor 2 circuit
70C & 71C - Dual Cool relay (optional)
THREE PHASE CONNECTION
Electric service connection terminals
Electrical handy box factory
installed with cover.
Factory wired to components
on electric panel
EARTH GROUND BAR (50Hz only)
Connection terminal with factory
ground from each high voltage
component
Three phase electric service
not by Liebert.
ELECTRIC CONDUIT KNOCKOUTS
On top of electric box. Knockout size
2 in (51 mm)
ALARM AND WARNING OUTPUT RELAYS
Field supplied 24V Class 2 wire for
special alarms.
(Not to exceed 1.0A @ 24v each.)
REMOTE UNIT SHUTDOWN
Replace existing jumper between terminals
37 & 38 with normally closed switch having
a minimum 50VA rating. Use field supplied
24V Class 2 wire.
INTELLISLOTS
Two Liebert Intellislots for optional
OCWEB-LBDS or OC485-LBDS card.
®
®
iCOM display
Factory installed unit
disconnect switches
CANBUS ISOLATOR
REFER TO SL-16655, LIEBERT XTREME DENSITY SYSTEM DESIGN MANUAL, AND SL-16674, LIEBERT XDC USER MANUAL FOR ADDITIONAL DETAIL.
DPN001599 REV 12/11
REV 4
LIEBERT XD CHILLER (XDC) WITH iCOM CONTROLS
PAGE 6/6
NOTES:
1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).
2. REQUIRES SHIELDED CABLE.
K11COM
COMMON WARNING OUTPUT
K11NO K11NC
K11
TO REMOTE ALARM
CIRCUIT BY OTHERS
K11
N.O. CONTACT BY OTHERS
FOR INDICATION OF ALARM, WIRE
N.O. CONTACTS FROM REMOTE
ALARM DEVICE AS SHOWN.
24 50
INPUT: REMOTE ALARM DEVICE
N.O. CONTACTS REQUIRED
5424
ALARM WHEN CLOSED.
INPUT: FAN BREAKER STATUS
N.O. CONTACTS REQUIRED
5124
ALARM WHEN CLOSED.
INPUT: CONDENSATION
DETECTION
FOR SHUTDOWN OF CONTROL
CIRCUIT, REMOVE JUMPER
BETWEEN TERMINALS 37 & 38
AND REPLACE WITH N.C. CONTACT
3837
INPUT: REMOTE SHUTDOWN
N.C. CONTACTS BY OTHERS
K3COM
COMMON ALARM OUTPUT
K3NO K3NC
K3
TO REMOTE ALARM
CIRCUIT BY OTHERS
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
K3
FOR CONTACTS INDICATING AN
ALARM CONDITION.
(MAX) 1.0AMP @ 24V
FACTORY WIRED
TEMPERATURE SENSOR.
1
1
21
Liebert XDC Extra Low Voltage field connection points
TO REMOTE T/H SENSOR A
P67
DO NOT
USE
UNIT DISPLAY (REAR VIEW)
TO OPTIONAL
EXTERNAL
CONNECTIONS
TO LIEBERT XD COOLING
MODULE AND REMOTE
T/H SENSOR B
P64 P67P66
TO P64 ON ICOM CONTROL BOARD
RED ETHER NET CABLE
TO P66 ON ICOM CONTROL BOARD
TERMINATION PLUG