Liebert Power Supply 350 Users Manual
350 to the manual 70717a75-7a20-4f2a-a34f-8c432c308e64
2015-02-09
: Liebert Liebert-Liebert-Power-Supply-350-Users-Manual-571381 liebert-liebert-power-supply-350-users-manual-571381 liebert pdf
Open the PDF directly: View PDF .
Page Count: 2
Download | |
Open PDF In Browser | View PDF |
DISCONTINUED PRODUCT PowerSure™ PSA Quick-Start Guide for 350-1000VA; 120V WHAT’S IN THE BOX • • • • • • • * Power ON/OFF/ Alarm Silence Quick-Start guide PowerSure family user manual on CD (also at www.liebert.com) Warranty card MultiLink™ software CD MultiLink serial cable (M3LS9P9S), 10 ft. (3m) RJ-11 cord, 7 ft. (2.1 m) USB cable, 6 ft. (1.8m) DIP switches ** *** DB-9 port Data Line *** Protection Connectors ** Orange output receptacles (battery backup and surge protection) (4 receptacles on 350, 500 and 650VA models) Battery Indicator * (Green/Amber) * Fault Indicator (Red/Green) ** Black output receptacles (surge protection only) For details, see : * Controls and Indicators ** Installation *** Communications For more details, refer to the PowerSure user manual on CD. Para una información más detallada, consulte el manual del usuario de la familia PowerSure en el CD. Site Wiring Fault * Indicator (Red) *** USB port * Utility Indicator (Green) PowerSure PSA Battery cover plate (on bottom for 650&1000VA models) (on rear of 350&500VA models) 6-ft. (1.8m) power cord INSTALLATION Plug computers, monitors & network hubs into orange receptacles Read all safety, installation and operating instructions in the PowerSure family user manual on the included CD or at www.liebert.com before operating the UPS. Adhere to all warnings on the unit and in the manual. 1. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C). 2. Plug the PSA’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated, refer to the Troubleshooting section. 3. Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black receptacles, which provide surge protection only. 4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors. 5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green). 6. Turn on connected equipment. CONTROLS AND INDICATORS Scanners Fax machines COMMUNICATIONS The PowerSure PSA will communicate with your computer in either of two ways: over its DB-9 port through Liebert’s MultiLink™ software or by USB through Microsoft® Windows® operating system features. • Turns the PowerSure PSA ON • Turns the PowerSure PSA OFF • Silences PowerSure PSA alarms MultiLink supplies useful monitoring data, such as input voltage and battery level, and will perform an orderly shutdown of the computer system. Microsoft Windows XP and 2000 operating system utilities supply UPS status information and will perform an orderly computer shutdown. Check your computer’s OS features to determine whether it has power management capability. TURN THE UPS OFF: When the PSA is ON, hold the main ON/OFF button down for more than 2 seconds to shut it down. An audible alarm will sound briefly. SILENCE AN ALARM: When a UPS alarm is active, press and release the main ON/OFF button to silence the audible alarm (Exceptions: low battery, overload and overtemperature). DO NOT hold the button down for more than 2 seconds or the PSA will shut down. CHECK THE PSA’S CONDITION: Three status indicators on the front of the UPS illuminate to specify the status of the UPS (see Troubleshooting section for details). Utility Indicator Green: Normal operation Amber: Buck/Boost mode SPECIFICATIONS Model Number PSA350MT-120 PSA500MT-120 PSA650MT-120 PSA1000MT-120 Power Rating VA/W Unit WxDxH Battery Indicator Green: On battery Amber: Battery warning Shipping WxDxH Rear of UPS DIP Switches 500VA/300W 650VA/390W 1000VA/600W Operating Temperature +32°F to +104°F (0°C to +40°C) 4.6x7.7x8.7 4.6x7.7x8.7 4.6x14.1x8.7 (116x358x222) 4.6x14.1x8.7 (116x358x222) Storage Temperature +5°F to +104°F (-15°C to +40°C) 7.7x12.2x11.5 7.7x12.2x11.5 9.5x19.7x12.4 9.5x19.7x12.4 (242x500x316) Relative Humidity 0% to 95%, noncondensing Operating Elevation Up to 10,000 ft. (3000m) at 86°F (30°C) without derating (116x196x222) (196x310x293) (196x310x293) (242x500x316) Unit 16.8 (7.6) 17.2 (7.8) 20.7 (9.4) 29.7 (13.5) Shipping 18.1 (8.2) 18.5 (8.4) 22.9 (10.4) 31.9 (14.5) INPUT AC PARAMETERS Voltage Range Without Battery Operation 78VAC - 150VAC, DIP switch selectable (see “DIP switch settings” on page 1) Frequency Range 46.5 - 63.5 Hz (±0.1 Hz) Input Power Cord 6 ft. (1.8m) attached, w/ NEMA 5-15 P OUTPUT AC PARAMETERS The two-position DIP switch control on the rear panel, shown above, allows the operator to select the utility transfer voltage at which the UPS will switch to battery power. The factory default settings are 100VAC - 135VAC. DIP switch positions for each voltage setting are: Output Receptacles ↑ Up ↑ Up ↑ Up ↓ Down Nominal Utility Setting 120VAC 85 - 145VAC (default) 110VAC 78 - 138VAC ↓ Down ↑ Up 127VAC 90 - 150VAC ↓ Down ↓ Down 120VAC 85 - 145VAC CAUTION Never change the voltage settings while the UPS is ON and powering connected loads. Change DIP switches only when the UPS is OFF. CAUTION (4) NEMA 5-15R (orange) Battery backup + surge protection; (2) NEMA 5-15R (black) Surge protection Voltage (Normal mode) DIP switch settings Right To ensure protection of the connected equipment, the DIP switch settings should match the nominal utility input voltage. DIP switch settings not matching the nominal utility could potentially damage connected equipment. Output Current (6) NEMA 5-15R (orange) Battery backup + surge protection; (2) NEMA 5-15R (black) Surge protection Nominal (110, 120, 127VAC) ±10% Voltage (Battery mode) 120VAC ±8% 2.9 A 4.2 A Waveform (Battery mode) 5.4 A 8.3 A Stepped Sinewave Frequency 50 Hz or 60 Hz; auto sensing Overload Warning (Normal & Battery modes) >100% Overload Shutdown >110% QuantityxVoltagexRating Transfer Time Backup Time: (1)x12Vx9Ah (1)x12Vx9Ah (2)x12Vx7.5Ah 4 - 6 ms typical At 77°F (25°C), resistive loading, with fully charged batteries: Full Load 8 minutes 8 minutes 5 minutes 5 minutes Half Load 26 minutes 24 minutes 16 minutes 18 minutes Recharge Time UL 1778, c-UL Listed Surge ANSI C62.41, Category A, Level 3 (IEEE 587, Category A); EN61000-4-5, Level 3, Criteria A ESD EN61000-4-2, Level 3, Criteria A Susceptibility EN61000-4-3, Level 3, Criteria A Electrical Fast EN61000-4-4, Level 4, Transient/Burst Criteria A Emissions FCC Part 15, Subpart B, Class B Conducted Immunity EN61000-4-6, Level 3, Criteria A Harmonics EN61000-3-2 Transportation Valve-regulated, nonspillable, lead acid (1)x12Vx7Ah < 40 dBA, at 1 meter Safety Flicker BATTERY PARAMETERS Type Audible Noise AGENCY 570J TRANSFER VOLTAGE SELECTORS (DIP SWITCHES) Left (116x196x222) Surge Protection Site Wiring Fault Indicator (Red) ENVIRONMENTAL (ALL MODELS) 350VA/210W WEIGHT: lbs (kg) SITE WIRING FAULT INDICATOR (RED) The Site Wiring Fault Indicator on the rear panel, as shown, illuminates red when the UPS detects a line-neutral reversal or a poor neutral-ground. (See Troubleshooting Chart if indicator is illuminated.) For MultiLink Serial Communications • Connect the provided MultiLink serial cable to the DB-9 ports on the rear of the UPS and on the rear of your computer. • Install the MultiLink software—the software, installation instructions and the user manual are on the CD included in the PowerSure PSA package. For USB Communications (with operating system power management) • Connect the USB cable provided with the UPS to the USB ports on the PSA and your computer. The PSA will work automatically with the built-in power management software on Windows XP and 2000 or later. • All USB models are compatible with Microsoft Windows 2000, Windows XP and Macintosh® OS 10.2 or later. DIMENSIONS: in. (mm) Fault Indicator Green: Overload/ Overtemperature Red: UPS fault ! Inkjet printers This button controls output power to the connected load and has three functions: TURN THE UPS ON: Press and release the main ON/OFF button to start the UPS. An audible alarm will sound briefly. ! Plug this type of equipment into black receptacles ONLY 6 hours to 90% of rated capacity, after full discharge into resistive load EN61000-3-3 ISTA Procedure 1A TROUBLESHOOTING TROUBLESHOOTING CHART The information below indicates various symptoms a user may encounter in the event the PowerSure PSA experiences a problem. Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy. 1. The Fault indicator illuminates, indicating the UPS Utility detected a problem. Indicator 2. An alarm sounds, alerting that the UPS requires Fault Battery attention. The alarm can be silenced except for low Indicator Indicator battery, overload and overtemperature warning conditions. 3. Utility and/or Battery indicators may be illuminated as a diagnostic aid to the operator, as shown below: If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installation section of this manual. If the problem persists, refer to the chart below: Problem UPS will not start GUIDE TO STATUS INDICATORS Fault Indicator Utility Indicator Green ON — — — — — Battery Indicator — — Green Flashing — Green ON Green ON — Green ON — Red Flashing Red ON UPS is operating on battery; beep every 10 seconds. Green ON Battery test has been initiated; no beep. Amber Low battery warning; beep every Flashing half-second. Green ON Green ON Green ON — Overload warning, load is >100%; beep every half-second. — Overload shutdown, load exceeds UPS capacity (110%); continuous beep. — Overtemperature (overtemp) warning; beep every 5 seconds (Normal mode). Green ON Green ON — UPS starts on battery, but will not switch to AC Overtemperature (overtemp) warning; beep every 5 seconds (Battery mode). — Overtemperature (overtemp) shutdown; long beep every 5 seconds. — UPS is on, fault warning; continuous beep. — UPS has failed & shut down; continuous beep. Solution Overload/Short Circuit Check the circuit protector on the rear of the UPS. If it is tripped, reset it and restart the UPS. For further help, call your local dealer, Liebert representative or the Liebert Worldwide Support Group. Battery disconnected or is completely discharged Check for proper connection of battery or batteries. UPS not plugged in Plug in the power cord securely. Circuit protector tripped Reset the circuit protector and restart the UPS. Power not available at utility receptacle Have the utility checked by a qualified electrician. Input voltage below threshold Wait until the voltage rises to an appropriate level or have the utility checked by a qualified electrician. AC overvoltage Wait until voltage lowers to an appropriate level or have the utility checked by a qualified electrician. Overload/Short Circuit Amber Battery needs to be replaced; long Flashing beep every minute. — Green Flashing Normal operation with utility power present; no beep. — Green ON Diagnosis/ Audible Alarm Cause UPS shuts down, Fault Indicator lit Site Wiring Fault Indicator illuminated UPS not providing expected back-up time Check the circuit protector on the rear of the UPS. If it is tripped, reset it and restart the UPS. If the problem persists, disconnect some of the equipment from your UPS—the total wattage of your equipment must not exceed the capacity of the UPS. For further help, call your local dealer, Liebert representative or the Liebert Worldwide Support Group. Internal UPS fault High temp shutdown Make sure that the UPS is operating in 32°F to 104°F (0°C to 40°C) and that it has adequate ventilation. MultiLink shutdown Consult the MultiLink user manual or contact your LAN administrator. Line-neutral reversal, Poor ground connection Have the utility checked by a qualified electrician. Overload Reduce load. Battery not charged due to a recent outage Recharge battery. Battery needs to be replaced Replace battery. MAINTENANCE BATTERY REPLACEMENT The PowerSure PSA UPS requires very little maintenance. Follow these practices to prevent problems. Replacement requires removing the battery cover plate on the bottom of the UPS. No tools are needed. CLEANING THE UPS To replace the batteries: The following will help ensure trouble-free operation for years: • Vacuum dust from the ventilation intake occasionally. • Wipe the cover periodically with a dry cloth. MAINTAINING BATTERIES The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The UPS continuously charges the batteries when connected to the utility supply, even while the UPS is switched off. When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries. 1. Remove the battery cover plate on the back/bottom of the UPS (Figure 1). 2. Pull the white tabs towards you to remove the battery from the UPS (Figure 2). Figure 1 Figure 2 3. Disconnect the insulated connectors from the battery terminals (Figure 3). 4. Insert a new battery pack, and push the connectors onto the battery terminals (black to black & red to red) (Figure 4). Figure 3 Figure 4 BATTERY REPLACEMENT CAUTION A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries: • Remove rings, watches, and other metal objects. • Do not lay tools or other metal objects on top of the batteries. • If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately. • Do not dispose of batteries in a fire. The batteries may explode. • Dispose of old batteries according to local codes. This UPS is equipped with internal “hot swappable” batteries that the user can replace without shutting down the UPS or connected loads. NOTE Caution should be exercised when replacing the batteries because the load is unprotected from disturbances and power outages during this procedure. NOTE: There may be a small spark at the battery terminals when reconnecting the connectors. This is normal and will not harm you or the UPS. 5. Push the battery pack into the UPS (Figure 5). 6. Reattach the battery cover plate (Figure 6). Figure 5 Figure 6 DISCONTINUED PRODUCT ! PRODUCT WARRANTY REGISTRATION To register for warranty protection: • Visit the Quick Links section of our Web site at: http://www.liebert.com • Click on Product Warranty Registration and fill in the form. If you have any questions, please contact us at: US: 800-222-5877 Outside the US: 614-841-6755 upstech@liebert.com SL-23270QS (9/03) Rev. 0
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : Adobe XMP Core 5.2-c003 61.141987, 2011/02/22-12:03:51 Creator Tool : Adobe InDesign CS5.5 (7.5) Create Date : 2013:05:28 10:00:46-06:00 Metadata Date : 2013:05:28 10:00:49-06:00 Modify Date : 2013:05:28 10:00:49-06:00 Instance ID : uuid:3959fff6-0892-f641-b3dd-d27666a94922 Document ID : xmp.did:8AD188980D2068118DBBBDDE4A0BDB84 Original Document ID : xmp.did:8AD188980D2068118DBBBDDE4A0BDB84 Rendition Class : proof:pdf History Action : created History Instance ID : xmp.iid:8AD188980D2068118DBBBDDE4A0BDB84 History When : 2013:05:28 09:54:52-06:00 History Software Agent : Adobe InDesign 7.5 Format : application/pdf Producer : Adobe PDF Library 9.9 Trapped : False Page Count : 2 Creator : Adobe InDesign CS5.5 (7.5)EXIF Metadata provided by EXIF.tools