Liebert Series 600T Users Manual Insms225

SERIES 600T to the manual 938fd302-6969-4739-8e0b-3a343f30bed0

2015-02-09

: Liebert Liebert-Series-600T-Users-Manual-571415 liebert-series-600t-users-manual-571415 liebert pdf

Open the PDF directly: View PDF PDF.
Page Count: 84

DownloadLiebert Liebert-Series-600T-Users-Manual- Insms225  Liebert-series-600t-users-manual
Open PDF In BrowserView PDF
POWER AVAILABILITY

Series 600T™ UPS

INSTALLATION MANUAL

Single Module
Three-Phase
65-225 kVA
60 Hz

The following WARNING applies to all battery cabinets supplied
with UPS systems:

INTERNAL BATTERY STRAPPING MUST BE VERIFIED BY MANUFACTURER PRIOR TO MOVING A BATTERY CABINET.
Battery cabinets contain non-spillable batteries.
Keep units upright.
Do not stack.
Do not tilt.
Failure to heed this warning could result in smoke, fire or electric
hazard. Call 1-800-LIEBERT prior to moving battery cabinets.

INSTALLATION MANUAL
TABLE OF CONTENTS
1.
2.
3.
4.

5.
6.

7.

8.

9.

10.

SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
UNLOADING AND HANDLING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.1.
External Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.2.
Internal Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
EQUIPMENT LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.1.
Battery Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.2
Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6.3
Open-Rack Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CONFIGURING YOUR NEUTRAL AND GROUND CONNECTIONS . . . . . . . . . . . . . . . . . . . . . 7
7.1.
Preferred Grounding Configuration, Isolated Power Distribution Units . . . . . . . . . . . . . . 8
7.2.
Alternative Grounding Configuration, Isolated Power Distribution Units, . . . . . . . . . . . 9
7.3.
Preferred Grounding Configuration, 480 or 600 VAC Input, 208VAC Output . . . . . . . . . 10
7.4.
Preferred Grounding Configuration, 208 VAC Input and Output, Non-Isolated Load . . .11
7.5.
Grounding Configuration, Delta Source or Impedance-Grounded Wye . . . . . . . . . . . . . . 12
7.6.
Preferred Grounding Configuration with Power-Tie™ Switchgear . . . . . . . . . . . . . . . . . 13
7.7.
Preferred Grounding Configuration, Battery Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
WIRING CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8.1.
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8.2.
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.3.
Battery Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.1
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.2
Specific Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
WIRING INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

!
WARNING
LOCATE CENTER OF GRAVITY SYMBOLS
AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET
If you require assistance for any reason, call the toll-free Liebert Global Services number,
1-800-543-2378. Please have the following information available:
Part Number:

________________________________________________________

Serial Number: ________________________________________________________
kVA Rating

________________________________________________________

kW Rating

________________________________________________________

Date Purchased ________________________________________________________
Date Installed

________________________________________________________

Location:

________________________________________________________

Input Voltage

________________________________________________________

Output Voltage ________________________________________________________
Battery Reserve Time: __________________________________________________

i

TABLES
Table 1.
Power Wiring Terminals - Factory Supplied ..............................................................................22
Table 2.
Torque Specifications ...................................................................................................................22
Table 3.
Field-Supplied Lugs .....................................................................................................................23
Table 310-16, NEC Allowable Ampacities of Insulated Conductors............................................................24

FIGURES
Figure 1. Preferred Grounding Configuration, 480 or 600 VAC input and output . . . . . . . . . . . . . . . . . . . 8
Figure 2. Alternative Grounding Configuration, 480 or 600 VAC input and output . . . . . . . . . . . . . . . . . 9
Figure 3. Preferred Grounding Configuration, 480 or 600 VAC input and 208 VAC output . . . . . . . . . . 10
Figure 4. Preferred Grounding Configuration, 208 VAC input and output . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5. Preferred Grounding Configuration with Delta Source Input . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 6. Preferred Grounding Configuration, Power-Tie™ Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 7. Preferred Battery Cabinet Grounding Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 8. Typical One-Line Diagrams for SMS with Standard Dual Input . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 9. Typical One-Line Diagrams of SMS with optional single input. . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 10. Typical One-Line Diagrams of SMS with optional Maintenance Bypass Cabinets . . . . . . . . 18
Figure 11. Outline Drawing Single and Multi Module 65 & 80 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 12. Outline Drawing, 100 through 225 kVA Module with SpaceSaver Top-Entry Configuration 26
Figure 13. Outline Drawing, 100 through 225 kVA Module with Standard Top & Bottom Entry . . . . . . 27
Figure 14. Bypass Transformer Cabinet, 65 & 80 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 15. Bypass Transformer Cabinet, 100-225 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 16. Battery Power Pack, 65 & 80 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 17. Battery Power Pack, Size A, 100-225 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 18. Outline Drawing, 3-Breaker MBC, 65 & 80 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 19. Outline Drawing, 3-Breaker MBC with Bypass Transformer, 65 & 80 kVA . . . . . . . . . . . . . . 33
Figure 20. Outline Drawing, 3-Breaker MBC, 125-350 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 21. Outline Drawing, 3-Breaker MBC, 450 to 800 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 22. Outline Drawing, 3-Breaker MBC, 600-800 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 23. Line-up Detail, 65 & 80 kVA SMS with Bypass Transformer Cabinet . . . . . . . . . . . . . . . . . . 37
Figure 24. Line-up Detail, 100-225 kVA Space Saver with Bypass Transformer Cabinet . . . . . . . . . . . . 38
Figure 25. Line-up Detail, 100-225 kVA Standard SMS with Bypass Transformer Cabinet . . . . . . . . . . 39
Figure 26. Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 27. Line-up Detail, 100-225 kVA Space Saver with Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . 41
Figure 28. Line-up Detail, 100-225 kVA Standard SMS with Battery Cabinets . . . . . . . . . . . . . . . . . . . . 42
Figure 29. Line-up Detail, 65 & 80 kVA with 3-Breaker MBC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 30. Line-up Detail, 65 & 80 kVA with Bypass Transformer and 3-Breaker MBC . . . . . . . . . . . . 44
Figure 31. Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 32. Line-up Detail, 100-225 kVA Space Saver with Bypass Cabinet and 3-Breaker MBC . . . . . . 46
Figure 33. Line-up Detail, 100-225 kVA with 3-Breaker MBC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 34. Line-up Detail, 100-225 kVA with Bypass Transformer Cabinet and 3-Breaker MBC . . . . . 48
Figure 35. Terminal Details, 65 & 80 kVA Single Module Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 36. Terminal Details, 100 & 125 kVA Space Saver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 37. Terminal Details, 150 & 225 kVA Standard SMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 38. Terminal Details, 100 & 125 kVA Standard SMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 39. Terminal Details, 150 & 225 kVA Standard SMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Figure 40. Control Connection Locations, 65 & 80 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 41. Control Connection Locations, 100 through 225 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 42. Standard Control Wiring, Single Module System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 43. Option Wiring, Alarm Status Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 44. Option Wiring, Maintenance Bypass Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 45. Option Wiring, Remote Status Panel Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Figure 46. Option Wiring, Remote Terminal IFM (RS-232 Communications) . . . . . . . . . . . . . . . . . . . . . 60
Figure 47. Option Wiring, SiteScan Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Figure 48. Option Wiring, Customer Alarm Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 49. Option Wiring, Battery Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 50. Option Wiring, SNMP Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 51. Option Wiring, Internal Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 52. Option Wiring, Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 53. Module Battery Disconnect, 65 through 125 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 54. Module Battery Disconnect, 150 & 225 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 55. Remote Status Panel, Surface Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 56. Circuit Breaker Schedule, 65 through 225 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 57. Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 58. Circuit Breaker Schedule, Maintenance Bypass Cabinet, 65 through 225 kVA . . . . . . . . . . .

62
63
64
65
66
67
68
69
70
71
72

iii

INSTALLATION
1. SAFETY PRECAUTIONS
Read this manual thoroughly, paying special
attention to the sections that apply to you, before
working with the UPS. Retain this manual for
use by installing personnel.

when performing the actions described by that
text.
A Danger signals immediate hazards resulting in
severe personal injury or death. For example:

Under typical operation and with all UPS doors
closed, only normal safety precautions are
necessary. The area around the UPS system should
be kept free from puddles of water, excess
moisture, or debris.

DANGER

Special safety precautions are required for
procedures involving handling, installation, and
maintenance of the UPS system or the battery.
Observe all safety precautions in this manual
before handling or installing the UPS system.
Observe all precautions in the Operation and
Maintenance Manual, before and during
performance of all maintenance procedures.
Observe all battery safety precautions before
working on or near the battery.

A Warning signals the presence of a possible
serious, life-threatening condition. For example:

This equipment contains several circuits that
are energized with high voltage. Only test
equipment designated for troubleshooting should
be used. This is particularly true for oscilloscopes.
Always check with an AC and DC voltmeter to
ensure safety before making contact or using tools.
Even when the power is turned Off, dangerously
high potentials may exist at the capacitor banks
and at the batteries.
ONLY qualified service personnel should
perform maintenance on the UPS system.
When performing maintenance with any part of
the equipment under power, service personnel and
test equipment should be standing on rubber mats.
The service personnel should wear insulating
shoes for isolation from direct contact with the
floor (earth ground).
Unless all power is removed from the equipment,
one person should never work alone. A second
person should be standing by to assist and
summon help in case an accident should occur.
Four types of messages are used throughout the
manual to stress important text. Carefully read the
text below each Danger, Warning, Caution, and
Note and use professional skills and prudent care

Liebert Series 600T UPS, 65-225 kVA, Single Module

A DANGER SIGNALS IMMEDIATE
HAZARDS WHICH WILL RESULT IN
SEVERE PERSONAL INJURY OR DEATH.

WARNING
LETHAL VOLTAGES MAY BE PRESENT
WITHIN THIS UNIT EVEN WHEN IT IS
APPARENTLY NOT OPERATING.
OBSERVE ALL CAUTIONS AND
WARNINGS IN THIS MANUAL. FAILURE
TO DO SO COULD RESULT IN SERIOUS
INJURY OR DEATH. DO NOT WORK ON OR
OPERATE THIS EQUIPMENT UNLESS
YOU ARE FULLY QUALIFIED TO DO SO!!
NEVER WORK ALONE.
A Caution indicates a condition that could
seriously damage equipment and possibly injure
personnel. For example:
CAUTION
Extreme care is necessary when removing
shoring braces. Do not strike the cabinet
with hammers or other tools.
A Note emphasizes important text. If the note is
not followed, equipment could be damaged or may
not operate properly. For example:
NOTE
If the UPS system has a blown fuse, the
cause should be determined before you
replace the fuse. Contact Liebert Global
Services.

1

2. INSTALLATION CONSIDERATIONS
Install your Series 600T UPS in accordance
with the submittal drawing package and the
following procedures.
A Liebert authorized representative must
perform the initial system check-out and startup to ensure proper system operation.
Equipment warranties will be voided unless
system start-up is performed by a Liebert
authorized representative. Contact your local
Liebert sales representative or Liebert Global
Services at 1-800-543-2378 to arrange for
system start-up.
CAUTION
Read this manual thoroughly before
attempting to wire or operate the unit.
Improper installation is the most
significant cause of UPS start-up
problems.
Do not install this equipment near gas
or electric heaters. It is preferable to
install the UPS in a restricted location
to prevent access by unauthorized
personnel.
1. Proper planning will speed unloading,
location, and connection of the UPS. Refer
to Figures 11 through 58 and the Site
Planning Data (Appendix A).
2. Be certain that the floor at the final
equipment location and along the route
(inside the facility) to the installation site
can support the cabinet weight and the
weight of any material handling
equipment. The UPS modules can weigh
up to two tons. The battery cabinets weigh
between 2300 and 5000 pounds each.

4. Refer to information later in this manual
regarding the optional Battery Cabinet(s),
Maintenance Bypass Cabinets,
Panelboards and Switchboards. Observe
all battery safety precautions when
working on or near the battery.
5. Use the shortest output distribution cable
runs possible, consistent with logical
equipment arrangements and with
allowances for future additions if planned.
6. Recommended ambient operating
temperature is 25C (77F). Relative
humidity must be less than 95%, noncondensing. Note that room ventilation is
necessary, but air conditioning may not be
required. Maximum ambient operating
temperature for the UPS and switchgear is
40C (104F) without derating. The
batteries should not exceed 25C (77F). At
elevations above 4,000 feet (1219 meters)
temperature derating may be required for
full power output (consult your Liebert
sales representative).
7. Even though your Liebert UPS unit is 92.5
to 94% efficient, the heat output is
substantial. For more specific information,
see the Site Planning Data (Appendix A).
Be sure environmental conditioning
systems can accommodate this BTU load,
even during utility outages.
8. The installer should attempt to balance the
load between the three output phases. The
UPS will operate safely with an unbalanced load, but will give optimum performance if the three output phases are
loaded within 20 percent of each other.

3. Plan the routing to ensure that the unit
can move through all aisle ways, doorways,
and around corners without risking
damage. If the modules and batteries must
be moved by elevator, check the size of the
door openings and the weight-carrying
capacity of the elevator.

2

Installation Manual

3. UNLOADING AND HANDLING
Because the weight distribution in each UPS and
ancillary cabinet is uneven, use extreme care
during handling and transport. Your installation
may also include Battery Cabinets, a Bypass
Transformer Cabinet and a Maintenance Bypass
Cabinet, Panelboard or Switchboard.
WARNING
EXERCISE EXTREME CARE WHEN
HANDLING UPS CABINETS TO AVOID
EQUIPMENT DAMAGE OR INJURY TO
PERSONNEL. THE UPS MODULE CAN
WEIGH UP TO TWO TONS. THE BATTERY
CABINETS WEIGH UP TO 5100 POUNDS.
THE UPS MODULES ARE HEAVIER IN
THE BACK THAN THE FRONT BECAUSE
OF THE WEIGHT OF THE MAGNETICS.
LOCATE CENTER OF GRAVITY SYMBOLS
BEFORE HANDLING CABINET. TEST LIFT
AND BALANCE THE CABINET BEFORE
TRANSPORTING. MAINTAIN MINIMUM
TILT FROM VERTICAL AT ALL TIMES.
WARNING
INTERNAL BATTERY CABINET
STRAPPING MUST BE VERIFIED BY
MANUFACTURER PRIOR TO MOVING
THIS UNIT.
THIS UNIT CONTAINS NON-SPILLABLE
BATTERIES. KEEP UNIT UPRIGHT. DO
NOT STACK. DO NOT TIP.
FAILURE TO HEED THIS WARNING
COULD RESULT IN SMOKE, FIRE OR
ELECTRICAL HAZARD. CALL 1-800LIEBERT PRIOR TO RELOCATING
BATTERY CABINET (AFTER INITIAL
INSTALLATION).

4. INSPECTIONS
4.1. External Inspections
1. While the UPS system is still on the truck,
inspect the equipment and shipping
container(s) for any signs of damage or
mishandling. Do not attempt to install the
system if damage is apparent. If any damage is
noted, file a damage claim with the shipping
agency within 24 hours and contact Liebert
Global Services at 1-800-543-2378 to inform
them of the damage claim and the condition of
the equipment.
2. Locate the bag containing the keys for the front
access door. The bag is attached to the cabinet.
3. Compare the contents of the shipment with the
bill of lading. Report any missing items to the
carrier and to Liebert Global Services
immediately.
4. Check the nameplate on the cabinet to verify
that the model number corresponds with the
one specified. Record the model number and
serial number in the front of this installation
manual. A record of this information is
necessary should servicing become required.

4.2. Internal Inspections
1. Verify that all items have been received.
2. If spare parts were ordered, verify arrival.
3. Open doors and remove cabinet panels to check
for shipping damage to internal components.
4. Check for loose connections or unsecured
components in the cabinet(s).
5. Check for installation of circuit breaker line
safety shields. There should be no exposed
circuit breaker terminals when the cabinet
doors are opened.
6. Remove any orange shipping braces or
brackets from the transformers.
7. Check for any unsafe condition that may be a
potential safety hazard.

Liebert Series 600T UPS, 65-225 kVA, Single Module

3

5. EQUIPMENT LOCATION
1. Handle cabinet(s) in accordance with WARNINGS in Section 3. Use a suitable material
handling device to move each cabinet to its
final location. Exercise extreme care
because of the uneven weight distribution. Carefully lower the cabinets to the floor
and position them for reconnection, if applicable.
2. Verify that the UPS system is installed in a
clean, cool and dry location. Observe the
location of overhead water lines for fire
sprinkler systems. Avoid placing the UPS and
related equipment directly under water lines
or within range of a sprinkler head.
3. Installation and serviceability will be easier if
adequate access is provided on all sides of the
equipment, but only front access is required.

CAUTION
Lead-acid batteries contain hazardous
materials. Batteries must be handled,
transported, and recycled or discarded in
accordance with federal, state, and local
regulations. Because lead is a toxic
substance, lead-acid batteries should be
recycled rather than discarded.
Do not open or mutilate the battery or
batteries. Released electrolyte is harmful
to the skin and eyes. It may be toxic. Do
not dispose of battery or batteries in a fire.
The battery may explode.
A battery can present a risk of electrical
shock and high short-circuit current. The
following precautions should be observed
when working on batteries:

a. Verify that there is adequate clearance to
open cabinet doors (4 feet is recommended).
See drawings and local codes.

1. Remove watches, rings, or other metal
objects.

b. Verify that there is adequate area in front of
circuit breakers to perform maintenance.
Check installation drawings for location of
breakers. Check with local codes.

3. Wear rubber gloves and boots.

c. Verify that there is adequate clearance
above all cabinets to allow exhaust air to
flow without restriction (2 feet minimum,
unobstructed).

5. Disconnect charging source prior to
connecting or disconnecting battery
terminals.

4. Connect the cabinets, internal cables and bus
bars, if applicable.

6. BATTERY INSTALLATION
6.1. Battery Safety Precautions

2. Use tools with insulated handles.
4. Do not lay tools or metal parts on top of
batteries.

6. Determine if the battery is inadvertently grounded. If it is inadvertently
grounded, remove source of ground.
Contact with any part of a grounded
battery can result in electrical shock.
The likelihood of such shock will be
reduced if such grounds are removed
during installation and maintenance.

Battery installation and servicing should be
performed or supervised by personnel
knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away
from batteries.

Lead-acid batteries can present a risk of
fire because they generate hydrogen gas.
The following procedures should be
followed:
1.

DO NOT SMOKE when near batteries.

Be sure to observe the grounding recommendations
in Section 7 when installing batteries. When
replacing batteries, use the same number and type
of batteries.

2.

DO NOT cause flame or spark in
battery area.

3.

Discharge static electricity from body
before touching batteries by first
touching a grounded metal surface.

4

Installation Manual

BATTERY SAFETY PRECAUTIONS IN
FRENCH PER CSA REQUIREMENTS

4. Ne pas déposer les outils ou les pièces
métalliques sur le dessus des accumulateurs.

INSTRUCTIONS IMPORTANES
CONCERNANT LA SÉCURITÉ

5. Interrompre la source de charge avant de
raccorder ou de débrancher les bornes de la
batterie d'accumulateurs.

CONSERVER CES INSTRUCTIONS
AVERTISSEMENT
DES PIECES SOUS ALIMENTATION SERONT
LAISSEES SANS PROTECTION DURANT CES
PROCEDURES D'ENTRETIEN. UN
PERSONNEL QUALIFIE EST REQUIS POUR
EFFECTUER CES TRAVAUX.
LES FUSIBLES A C.C. DE LA BATTERIE
D'ACCUMULATEURS OPERENT EN TOUT
TEMPS A LA TENSION NOMINALE. LA
PRESENCE D'UN FUSIBLE A C.C. BRULE
INDIQUE UN PROBLEME SERIEUX. LE
REMPLACEMENT DE CE FUSIBLE, SANS
AVOIR DETERMINE LES RAISONS DE LA
DEFECTUOSITE, PEUT ENTRAINER DES
BLESSURES OU DES DOMMAGES SERIEUX A
L'EQUIPEMENT. POUR ASSISTANCE,
APPELER LE DEPARTEMENT DE SERVICE A
LA CLIENTELE DE LIEBERT.
DANGER
Les accumulateurs plomb-acide contiennent de la
matière comportant un certain risque. Les
accumulateurs doivent être manipulés, transportés
et recyclés ou éliminés en accord avec les lois
fédérales, provinciales et locales. Parce que le
plomb est une substance toxique, les
accumulateurs plomb-acide devraient être recyclés
plutôt qu'éliminés.
Il ne faut pas brûlé le ou les accumulateurs.
L'accumulateur pourrait alors explosé.
Il ne faut pas ouvrir ou endommager le ou les
accumulateurs. L'électrolyte qui pourrait s'en
échapper est dommageable pour la peau et les
yeux.
Un accumulateur représente un risque de choc
électrique et de haut courant de court-circuit.
Lorsque des accumulateurs sont manipulés, les
mesures préventives suivantes devraient être
observées:
1. Retirer toutes montre, bagues ou autres objets
métalliques.
2. Utiliser des outils avec manchon isolé.

6. Déterminer si l'accumulateur est mis à la terre
par erreur. Si oui, défaire cette mise à la terre.
Tout contact avec un accumulateur mis à la
terre peut se traduire en un choc électrique. La
possibilitié de tels chocs sera réduite si de
telles mises à la terre sont débranchées pour la
durée de l'installation ou de l'entretien.
Les accumulateurs plomb-acide présentent un
risque d'incendie parce qu'ils génèrent des gaz à
l'hydrogène. Les procédures suivantes devront être
respectées.
1. NE PAS FUMER lorsque près des
accumulateurs.
2. NE PAS produire de flammes ou d'étincelles
près des accumulateurs.
3. Décharger toute électricité statique présente
sur votre corps avant de toucher un
accumulateur en touchant d'abord une surface
métallique mise à la terre.
DANGER
L'électrolyte est un acide sulfurique dilué qui est
dangereux au contact de la peau et des yeux. Ce
produit est corrosif et aussi conducteur electrique.
Les procédures suivantes devront être observées:
1. Porter toujours des vêtements protecteurs
ainsi que des lunettes de protection pour les
yeux.
2. Si l'électrolyte entre en contact avec la peau,
nettoyer immédiatement en rinçant avec de
l'eau.
3. Si l'électrolyte entre en contact avec les yeux,
arroser immédiatement et généreusement avec
de l'eau. Demander pour de l'aide médicale.
4. Lorsque l'électrolyte est renversée, la surface
affectée devrait être nettoyée en utilisant un
agent neutralisant adéquat. Une pratique courante est d'utiliser un mélange d'approximativement une livre (500 grammes) de
bicarbonate de soude dans approximativement
un gallon (4 litres) d'eau. Le mélange de bicarbonate de soude devra être ajouté jusqu'à ce
qu'il n'y ait plus apparence de réaction
(mousse). Le liquide résiduel devra être nettoyé à l'eau et la surface concernée devra être
asséchée.

3. Porter des gants set des bottes decautchouc.

Liebert Series 600T UPS, 65-225 kVA, Single Module

5

6.2 Battery Cabinets
Optional battery cabinets are available from
Liebert and other qualified vendors. Consult your
submittal package for details.
The same model battery cabinet may be paralleled
in multiple cabinet strings for additional capacity.
Battery capacity (in minutes) at your installation
will depend on cabinet model, number of cabinets,
and amount of critical load on the UPS.
1. Handling. The Battery Cabinet weighs up to
5100 pounds. Fork lift slots are provided in the
base of 100-225 kVA cabinets for easy
handling. Fork lift forks or a pallet jack can be
used between the casters of the 65 and 80 kVA
battery cabinets.
2. Cabinet Inspection. Remove all panels and
visually inspect the batteries, bus connections,
and cabinet for any damage. If any foam blocks
were placed between shelves to restrain
movement during shipment, remove them now.
Exercise caution; voltage is present
within the Battery Cabinet even before
installation. If there are signs of damage, do
not proceed. Call Liebert Global Services at 1800-542-2378.
3. Battery Storage. The batteries used in the
Battery Cabinet retain their charge well. The
batteries can be stored for up to six months
without any appreciable deterioration. Selfdischarge rate of the batteries is approximately
3% per month when the batteries are stored in
temperatures of 15°C to 25°C (59°F to 77°F). If
the Battery Cabinet must be stored for longer
than six months, contact Liebert Global
Services.
4. Installation. The Battery Cabinet(s) can be
located conveniently to the left side of the 65225 kVA UPS module. The front-access-onlydesign eliminates side and rear service
clearance requirements.

7. Service Clearance. Allow front access to the
Battery Cabinet at all times for maintenance
and servicing. Electrical codes require that the
Battery Cabinet be installed with no less than
3 feet (1 meter) of clearance at the front of the
cabinet when operating. Side and rear panels
do not require service clearance.
8. Side Panels. Remove protective side panels to
connect battery cabinets together. Do not
remove the shield plate, explained below.
9. Shield Plate. The shield plate in 125 kVA
Battery Cabinets should be on the side toward
the UPS system. Move the shield if required by
your Battery Cabinet location.
10. Cables. Cables may be run between battery
cabinets through cutouts in the top of the
cabinets, eliminating the need for external
conduit runs. Route cables before moving
cabinets into final position for bolting
together. Remove top panels for access. Refer
to Figures 16 and 17 or your submittal
drawings for instructions on wiring cabinets in
parallel.
11. Grounding. The battery cabinets have ground
studs near the bus bar connections. Use an
equipment grounding conductor to connect the
lugs of the cabinets together and to connect the
cabinets to the ground bus bar in the UPS
module.
CAUTION
Cables between batteries and modules
should be run in matched pairs, positivewith-negative. Grouping like-polarity
cables together (i.e. positive-with-positive
and negative-with-negative) can cause
stress or damage to the cables, conduit or
buswork.

5. Re-Installation. If it later becomes necessary
to move the Battery Cabinet to another
location, contact Liebert Global Services to
inspect the internal battery hold-down straps.
6. Environment. Locate the Battery Cabinet in
a clean, dry environment. Recommended
temperature range for optimum performance
and lifetime is 20-25°C (68-77°F).

6

Installation Manual

6.3 Open-Rack Batteries
When batteries other than Liebert Battery
Cabinets are used, a remote battery disconnect
switch with overcurrent protection is required per
the National Electrical Code. Refer to Figures 53
and 54. Contact your Liebert sales representative.
1. Install battery racks/cabinets and batteries per
manufacturer's installation and maintenance
instructions.

7. CONFIGURING YOUR NEUTRAL AND
GROUND CONNECTIONS
Improper grounding is the largest single cause of
UPS installation and start-up problems. This is not
an easy subject, since grounding techniques vary
significantly from site to site, depending on several
factors. The questions you should ask are:
•

What is the configuration of the input power
source? Most of the recommended schemes for
UPS grounding require grounded-wye service. The UPS system requires a bypass neutral for sensing and monitoring the quality of
the bypass input. If the building service is
ungrounded delta or corner-grounded delta,
contact your Liebert representative to ensure
your system includes the Artificial Neutral or
Isolated Neutral kit.

•

Does the system have a bypass isolation
transformer? Systems with 480 VAC (or 600
VAC) input and 208 VAC output require a
bypass isolation transformer. In some cases,
it may be necessary to treat that transformer
as a “separately derived source” with its own
grounding electrode. See page 10 for details.

•

What are the UPS input and output voltages?
Systems with 480 VAC input and output have
significantly different needs than systems
with 480/208 VAC or 208/208 VAC.

•

What is the connected load? Does the critical
load consist of one or more Power Distribution Units (PDUs)? Do the PDUs have isolation transformers?

2. Verify battery area has adequate ventilation
and battery operating temperature complies
with manufacturer's specification.
3. Ensure that battery racks are properly
grounded according to code requirements in
your area.
If you have any questions concerning batteries,
battery racks, or accessories, contact Liebert
Global Services at 1-800-543-2378.
CAUTION
Cables between batteries and modules
should be run in matched pairs, positivewith-negative. Grouping like-polarity
cables together (i.e. positive-with-positive
and negative-with-negative) can cause
stress or damage to the cables, conduit or
buswork.

The following sections discuss recommended
grounding procedures for various system
configurations.
NOTE
Some UPS modules are equipped with
input isolation transformers. However,
these transformers have no effect upon any
system grounding considerations. These
modules will be grounded exactly as shown
in the following examples.

Liebert Series 600T UPS, 65-225 kVA, Single Module

7

GROUNDING
ELECTRODE
PER NEC 250-24

Figure 1. Preferred Grounding Configuration, 480 or 600 VAC input and output
The isolation transformers in the PDUs are
7.1. Preferred Grounding Configuration,
considered a separately derived source. Therefore
480 or 600 VAC Input and Output,
the PDU neutral should be bonded to the PDU
Isolated Power Distribution Units,
grounding conductor and connected to a local
Wye-Connected Service
grounding electrode in compliance with NEC 25026.
One of the most-common configurations of the
Series 600T UPS is the Single Module System with
Advantages of this configuration include:
480 VAC input, 480 VAC output, and a connected
•
A measure of common-mode noise attenuaload consisting of multiple Power Distribution
tion, since the isolation (common-mode rejecUnits (PDUs) with isolation transformers in the
tion) occurs as close to the load as practical
PDUs to produce 208 VAC. For Canadian
(i.e. at the PDU).
customers, the UPS modules usually have 600 VAC
input and output. The same principles apply if the
•
The UPS module can be located remotely
connected load is an isolation transformer feeding
from the PDU without compromising comvarious loads. Figure 1 above shows a typical
mon-mode noise performance.
installation.
•
By using UPS modules with 480 VAC input
Notice that the UPS module main input and
and output and creating 208 VAC at the PDU,
bypass input are connected to a grounded-wye
smaller and less costly power feeders can be
service. In this configuration, the UPS module is
used and less voltage drop (as a percent of
not considered a separately derived source. The
nominal) occurs.
UPS module output neutral is solidly connected to
the building service neutral, which is bonded to the
NOTE
grounding conductor at the service entrance
equipment
Impedance-grounded wye sources must be
grounded in accordance with Section 7.5.

8

Installation Manual

Figure 2. Alternative Grounding Configuration, 480 or 600 VAC input and output

7.2 Alternative Grounding
Configuration, 480 or 600 VAC Input
and Output, Isolated Power
Distribution Units, Wye-Connected
Service

This configuration is reserved for those
applications which meet all the following criteria:

This configuration is similar to that shown in
Section 7.1, except that the service entrance
neutral is not brought into the UPS module. In this
configuration, the UPS output transformer is
considered a separately derived source. The UPS
module neutral is bonded to the UPS ground,
which is connected to a local grounding electrode in
accordance with NEC 250-26.
Please note that this configuration represents a
price/performance trade-off. Whenever the UPS
module transfers to or from bypass, two AC sources
(input and bypass) are briefly connected together
and circulating current must flow. In the previous
configuration, the current flows through the
neutral conductor. In this configuration, the
current flows through the ground path, possibly
tripping ground fault interruptors (GFIs) and
distorting the bypass waveform reference. Proper
adjustment of ground fault interrupters is
necessary to avoid unwanted tripping.

Liebert Series 600T UPS, 65-225 kVA, Single Module

•

The facility has Wye-connected service

•

The module rectifier input and bypass input
are fed from the same source

•

The connected load is strictly 3-wire (such as
one or more PDUs) and does not require a
neutral from the UPS

•

Special precautions are taken to prevent tripping the ground fault interruptors. The time
delay should be set to at least 30 cycles to prevent tripping when the UPS performs a
transfer or retransfer operation.

CAUTION
Failure to properly set the ground fault
interruptors could cause loss of power to
the critical load.

9

LOCAL GROUNDING
ELECTRODE
PER NEC 250-30

GROUNDING
ELECTRODE
PER NEC 250-24

Figure 3. Preferred Grounding Configuration, 480 or 600 VAC input and 208 VAC output

7.3. Preferred Grounding Configuration,
480 or 600 VAC Input, 208VAC
Output, and Isolated Bypass
Another configuration in this power range is the
Single Module System with 480 or 600 VAC input,
208 VAC output, a Bypass Isolation Transformer
and a connected load consisting of multiple
distribution panelboards or switchboards. Figure 3
above shows a typical installation.
The Bypass Transformer provides isolation and
steps down the voltage to the bypass inputs. The
Bypass Transformer and the UPS module together
constitute a separately derived system, since there
is no direct electrical connection between the input
(service entrance) circuit conductors and the
output circuit conductors.
NOTE

The bonding of the neutral to the grounding
conductor can theoretically be done at either the
UPS module or the Bypass Transformer. However,
we recommend bonding at the Bypass Transformer
because the UPS module will sometimes be
powered down for maintenance and its output
transformer will be out of the circuit. The neutral
should be bonded to ground and a local grounding
electrode should be installed at the Bypass
Transformer, per NEC 250-30.
Features of this configuration include:
•

The UPS receives its bypass neutral from the
Bypass Transformer

•

The output is isolated from the input circuit
conductors, and

•

Some amount of common-mode noise attenuation can be obtained for sensitive loads if the
UPS module and Bypass Transformer are
located close to sensitive loads.

The illustration above shows a wyeconnected source, but the same grounding
scheme would apply for a delta source at
the service entrance.

10

Installation Manual

GROUNDING
ELECTRODE
PER NEC 250-24

Figure 4. Preferred Grounding Configuration, 208 VAC input and output

7.4. Preferred Grounding Configuration,
208 VAC Input and Output, NonIsolated Load, Wye-Connected
Service
A few applications in this power range have 208
VAC input and output, and a connected load
consisting of multiple Power Distribution Units
(PDUs), panelboards, switchboards or other items
of load equipment which do not have isolation
transformers.

The UPS module output neutral and the load
neutral are solidly connected to the building
service neutral, which is bonded to the grounding
conductor at the service entrance equipment.
This arrangement is typical for systems with 208
VAC input and output. However, it does not
provide any isolation or common-mode noise
attenuation for sensitive loads.

Notice in Figure 4 above that the UPS module
main input and bypass input are connected to a
grounded-wye service. In this configuration, the
UPS module is not considered a separately derived
source.

Liebert Series 600T UPS, 65-225 kVA, Single Module

11

GROUNDING
ELECTRODE
PER NEC 250-24

GROUNDING
ELECTRODE
PER NEC 250-24

LOCAL
GROUNDING
ELECTRODE
PER NEC 250-30

LOCAL
GROUNDING
ELECTRODE
PER NEC 250-30

LOCAL
GROUNDING
ELECTRODE
PER NEC 250-30

Figure 5. Preferred Grounding Configuration with Ungrounded Delta Source Input (top) and
Corner-Grounded Delta (bottom)

7.5. Grounding Configuration, 480 or 600
VAC Input and Output, Delta Source
or Impedance-Grounded Wye
As previously mentioned, Series 600T UPS
modules require a bypass input neutral for sensing
and monitoring. With a wye-connected input
source, the installer should always connect the
building service neutral to the module output
neutral to achieve this. When the building service
is delta-connected, however, the installer must
take special steps to ensure reliable UPS
functioning.

12

If building service is ungrounded delta (and there
is no intent to operate with one corner of the delta
grounded, either on purpose or accidentally), the
UPS requires the Series 600T Artificial Neutral
Kit for proper operation. This kit uses a resistor
network to create a reference point for the bypass
input. In this case, the UPS output neutral must be
bonded to the UPS ground. See Figure 5 above.
If the building service is corner-grounded delta or
an impedance-grounded wye, the UPS requires the
Series 600T Isolated Neutral Kit. This kit uses
control isolation transformers to create a reference
point. For this application, the UPS output neutral
must not be bonded to the UPS ground.

Installation Manual

GROUNDING
ELECTRODE
PER NEC 250-24

GROUNDING
ELECTRODE
PER NEC 250-24

Figure 6. Preferred Grounding Configuration, Power-Tie™ Systems

7.6. Preferred Grounding Configuration,
480 or 600 VAC Input and Output,
with Power-Tie™ Switchgear
Single Module Systems can be used with Power-Tie
switchgear to provide dual critical load busses. The
Power-Tie switchgear permits transferring critical
loads from one critical bus to the other so that one
UPS module and associated breakers can be deenergized for maintenance. Certain configurations
of Power-Tie equipment also permit the operator to
continuously parallel the output of the UPS
modules.

Liebert Series 600T UPS, 65-225 kVA, Single Module

In tied systems, each UPS module must have its
neutral solidly connected to its own building
service neutral and to the Power-Tie switchgear
neutral. See Figure 6 above.
NOTE
It is essential to run a neutral connection
between the tie switchgear and both UPS
modules as shown in the illustration above.

13

TO OUTPUT
DISTRIBUTION

GROUNDING
ELECTRODE
PER NEC 250-24

Figure 7. Preferred Battery Cabinet Grounding Configuration

7.7. Preferred Grounding Configuration,
Battery Systems
Large, open-rack battery systems are normally
either locally grounded or left ungrounded,
depending on local code requirements.

14

Battery cabinet systems, on the other hand, should
be grounded to the UPS ground bus bar. Figure 7
above illustrates how a simple one-cabinet system
would be grounded. For systems with multiple
cabinets, the same configuration would apply.
However, for simplicity the installer can connect all
the battery cabinet grounds together and run a
single ground conductor (in the same conduit as
the phase conductors) to the UPS ground.

Installation Manual

8. WIRING CONSIDERATIONS
8.1. Power Wiring
Refer to Site Planning Data (Appendix A) and the
installation drawings. Determine AC currents for
your system based on kVA, kW, voltage, and
options. Also refer to equipment nameplate for the
model number, rating, and voltage. For wire
termination data, refer to Tables 1-3.
1. Power wiring -- rectifier input, bypass input,
UPS output, and battery cables -- must be run
in individual, separate conduit or cable tray.
Refer to the Outline and Terminal Details
drawings (Figures 11-13 and 35-39) for location
of the various power connections within the
UPS.
CAUTION
Power and control wiring must be
separated!
2. Observe local, state and national electrical
codes. Verify utility power and its overcurrent
protection rating will accommodate the UPS
input rating, including battery recharging.
3. A safety ground wire must be run from
building ground to ground point in the UPS
Module Cabinet, the Battery Cabinet and the
Power-Tie™ switchgear cabinet. See Sections
7.1 through 7.7. The grounding conductor shall
comply with the following conditions of
installation:
a. The insulated grounding conductor must be
sized in accordance with the NEC and local
codes. It must be green (with or without
yellow stripes) and be installed as part of
the branch circuit that supplies the unit or
system.
b. The grounding conductor described above is
to be grounded to earth at the service equipment or, if supplied by a separately derived
system, at the supply transformer or motorgenerator set in accordance with the
instructions in Section 7 of this Manual.
c. The attachment-plug receptacles in the
vicinity of the unit or system are all to be of
a grounding type, and the grounding conductors serving these receptacles are to be

Liebert Series 600T UPS, 65-225 kVA, Single Module

connected to earth ground at the service
equipment.
4. Observe clockwise phase rotation of all power
wiring. Phase A leads Phase B leads Phase C.
A qualified electrician should check the phase
rotation.
5. Power cables must be rated for less than 2 volts
line drop at maximum rated system current.
6. Use 75°C copper wire. Select wire size based on
the ampacities in Table 310-16 and associated
notes of the National Electrical Code (NFPA
70) reprinted on page 24 of this manual.
CAUTION
The weight of power cables must be
adequately supported to avoid stress on
bus bars and lugs. The following
restraining method is recommended to
both to support cable weight and control
cable movement during external fault
conditions: Wrap line cables together at 6
inches and 12 inches from the terminals
with 5 wraps of 3/8 inch nylon rope or
equivalent (tensile strength of 2000
pounds). Support remainder of cable with
5 wraps every 6 inches or 1 wrap every 1
inch.
7. If site equipment includes a backup generator
and automatic transfer switch(es), consult the
manufacturers of those devices for information
on sizing and interfacing to the UPS system.
8. The installing contractor can remove the access
plates from the top left or top right sides of the
UPS in order to cut entry holes for conduit. For
units with bottom-entry cable access, there is a
separate (third) access plate in the base of the
unit, under the cable access wireway.
CAUTION
After cutting holes in the access plates, be
certain that no foreign matter (metal
shavings, sawdust, insulation or wire
fragments, etc.) remains inside the UPS.
Likewise be certain to block any “extra”
holes in the plates through which foreign
matter could later enter the UPS.

15

CB3
CB3

CB3
CB3

Input
InputIso
Iso
Transformer
Transformer
CB1
CB1

CB2
CB2

CB1
CB1

Standard
Standard
SMS,
SMS,
with
with
208/208,
208/208,
480/480
480/480
oror
600/600
600/600
VAC
VAC
input/output.
input/output.

CB2
CB2

SMS
with
input
isolation
transformer
and
208/208,
SMS
with
input
isolation
transformer
and
208/208,
480/480
oror
600/600
VAC
input/output.
480/480
600/600
VAC
input/output.

Bypass
Isolation
Xfmr
CB3

CB1

CB2

600/208 VAC module with external bypass
isolation transformer.

Bypass
Isolation
Xfmr
CB3

Input Isolation
Transformer
CB1

CB2

480/208 or 600/208 VAC module with both
internal input isolation transformer and external
bypass isolation transformer.

Figure 8. Typical One-Line Diagrams for SMS with Standard Dual Input

16

Installation Manual

CB3

CB3

Input Isolation
Transformer

CB1

CB2

Standard single-input SMS with 208/208, 480/480
or 600/600 VAC input/output.

CB1

Single-input SMS with input isolation transformer
and 208/208, 480/480 or 600/600 VAC input/output.

External
Bypass
Isolation
Transformer

Internal
Bypass
Isolation
Xfmr
CB3

CB1

CB2

CB2

480/208 VAC single-input SMS with bypass
isolation transformer. Single-input modules are
not available with both bypass and input isolation
transformers.

CB3

CB1

CB2

600/208 VAC single-input SMS with bypass
isolation transformer. Single-input modules are
not available with both bypass and input isolation
transformers.

Figure 9. Typical One-Line Diagrams of SMS with optional single input.

Liebert Series 600T UPS, 65-225 kVA, Single Module

17

MBB

MBB

MIB

MIB

CB3

CB3

CB1

CB1

CB2

CB2

2-breaker Maintenance Bypass Cabinets for standard (left) and single-input (right) modules.
MBB

MBB

RIB

BIB

MIB

MIB

CB3

CB3

CB1

CB1

CB2

CB2

3-breaker Maintenance Bypass Cabinets for standard (left) and single-input (right) modules.
MBB

MBB

BIB

RIB

BIB

MIB

MIB
BYPASS
ISO XFMR
(OPT.)

BYPASS
ISO XFMR
(OPT.)

CB3

CB3

CB1

CB1

CB2

CB2

3-breaker and 4-breaker Maintenance Bypass Cabinets for stepdown-voltage applications.

Figure 10. Typical One-Line Diagrams of SMS with optional Maintenance Bypass Cabinets
Abbreviations for Circuit Breakers
BIB
MBB
MIB
RIB

18

Bypass Isolation Breaker
Maintenance Bypass Breaker
Maintenance Isolation Breaker
Rectifier Input Breaker

Installation Manual

8.2. Control Wiring

8.3. Battery Wiring

Control wiring must be stranded and tinned and
run in individual separate steel conduit. Control
wiring must be separated from power wiring. In
addition, each control wiring cable group should be
run in a separate conduit to minimize control
signal interference.

Power wiring to the Battery Cabinet connects
positive, negative, and ground power cables from
the Battery Cabinet to the associated UPS.
Connection of the UPS to the Battery Cabinet
serves to both charge and discharge the batteries
(when needed). The battery disconnect (circuit
breaker) requires a control cable. Liebert Battery
Cabinets include power and control cables to join
multiple cabinets together into a system.
Additional (field-supplied) power or control wiring
might be necessary to connect the battery cabinet
system to the UPS. Refer to Figures 16-17.

If your system has any installed options, special
wire lists will be included in your Submittal
Drawing Package. Contact your Liebert Sales
Representative for assistance if the Submittal
drawings have been lost or misplaced.
All control cable groups are connected to different
Interface Modules (IFMs) inside the UPS. Figure
29 shows the typical location of each IFM inside
the UPS. The position of a particular IFM may be
different for your UPS, depending upon the model
and the installed options.
NOTE
The UPS control and communication
wiring are considered Class 2 circuits by
NEC standards. However, NEC Class 1
wiring methods are required for these
circuits to ensure proper operation of the
UPS.

DANGER
A BATTERY INTERCELL CONNECTION
ON EACH TIER IS DISCONNECTED FOR
SAFETY DURING SHIPMENT. DO NOT
COMPLETE THESE CONNECTIONS. THE
LIEBERT GLOBAL SERVICES REPRESENTATIVE WILL COMPLETE THESE CONNECTIONS AS PART OF START-UP. AN IMPROPERLY INSTALLED UNIT CAN
RESULT IN INJURY TO PERSONNEL OR
DAMAGE TO EQUIPMENT.
CAUTION
Be sure polarity is correct when wiring
the Battery Cabinet to the connected
equipment (positive to positive; negative
to negative). If polarity is not correct, fuse
failures or equipment damage can result.
CAUTION
DC power cables should be installed in
conduit with conductors in matched pairs
(positive and negative).
NOTE
Inspection of the battery installation is a
service that can be provided by Liebert. A
Battery Specialist can perform a detailed
inspection of the entire battery system to
ensure it meets current IEEE standards.
This inspection service is recommended
because batteries are a critical part of the
UPS system.

Liebert Series 600T UPS, 65-225 kVA, Single Module

19

9. WIRING CONNECTIONS
9.1 Warnings
DANGER
VERIFY THAT ALL INCOMING HIGH AND
LOW VOLTAGE POWER CIRCUITS ARE
DE-ENERGIZED AND LOCKED OUT
BEFORE INSTALLING CABLES OR
MAKING ELECTRICAL CONNECTIONS.
ALL POWER CONNECTIONS MUST BE
COMPLETED BY A LICENSED
ELECTRICIAN EXPERIENCED IN WIRING
UPS EQUIPMENT, AND IN ACCORDANCE
WITH ALL APPLICABLE NATIONAL AND
LOCAL ELECTRICAL CODES.
IMPROPER WIRING MAY CAUSE DAMAGE
TO THE UPS OR INJURY TO PERSONNEL.

9.2 Specific Connections
Refer to the drawings in this manual and any other
drawings provided by Liebert for this installation.
Make all of the following connections:
a. AC power cables from input power source
circuit breaker to UPS Module Input. Observe
phase rotation.
CAUTION
See Section 7 of this Manual for an
explanation of proper grounding
techniques.
b. AC power cables from bypass power source circuit breaker to UPS Module Bypass input.
Observe phase rotation.
c. AC power cables from UPS Module Output to
critical load. Observe phase rotation.
NOTE

CAUTION
All shielded cables, non-shielded cables,
non-shielded control wires, non-shielded
battery breaker control wires, and nonshielded remote control wires must be
housed in individual, separate, steel
conduits. Placing multiple cables in the
same conduit with other control or power
wiring may cause system failure.

If your installation includes a
Maintenance Bypass Cabinet, Switchboard
or Panelboard, some (or all) power cables
will be terminated in these cabinet(s).
Make sure all required wiring between
UPS module and the optional cabinet(s) is
completed. Observe phase rotation.
d. The UPS Module Output Neutral must be connected to one common point and solidly
grounded per requirements of the National
Electrical Code. See Section 7.
CAUTION
UPS bypass and output neutral must be
connected to only one common point in
the UPS. This neutral line must be
grounded at the source.
e. For Battery Cabinets:
DC power cables and ground from Battery Cabinet to UPS Module, and between Battery Cabinets. Observe polarity. DC power cables
should be installed in matched pairs (positive
and negative).

20

Installation Manual

NOTE
DC power and battery circuit breaker control cables are provided with the Liebert
brand Battery Cabinets. Power cables are
sized for interconnecting Battery Cabinets.
Battery Cabinets specified for bolting up to
the UPS are shipped with power cables to
connect the Battery Cabinet system to the
UPS Module. Field-supplied cabling must be
provided to connect “stand-alone” Battery
Cabinets to the UPS Module.

10. WIRING INSPECTION
1. Verify all power connections are tightened per
the torque specifications in Table 2. Verify all
control wire terminations are tight.
2. Verify all power wires and connections have
proper spacing between exposed surfaces,
phase-to-phase and phase-to-ground.
3. Verify that all control wires are run in steel
conduit, separate from all power wiring.

DANGER
DO NOT MAKE ANY CONNECTIONS
BETWEEN BATTERY TIERS IN THE
BATTERY CABINET. THESE
CONNECTIONS WILL BE MADE BY THE
LIEBERT GLOBAL SERVICES
REPRESENTATIVE DURING START-UP.
f.

For remote battery:
DC power cables (and ground) from battery to
Module Battery Disconnect, and then to UPS
Module DC bus. Observe polarity. DC power
cables should be installed in conduit with conductors in matched pairs (positive and negative).

g. Module Battery Disconnect control wiring to
UPS Module (and between Battery Cabinets, if
applicable).
h. Control wiring to Remote Monitor Panel, if
used. Selected alarm messages are also available for customer use through a set of contacts
on a separate terminal board. Wiring must be
run in individual separate steel conduit.
i.

Emergency Power Off control wiring must be
run in separate steel conduit.

j.

Communications wiring for site monitoring or
for modem must be run in separate steel conduit.

k. Power and control connections required for the
Maintenance Bypass.
l.

Any additional special wiring required at the
customer site.

Liebert Series 600T UPS, 65-225 kVA, Single Module

21

Table 1
Power Wiring Terminals - Factory Supplied
UPS
MODULE
65 & 80 kVA

100-225 kVA

CONNECTION
TYPE
Bypass input wiring is top-entry, to busbars on top of the circuit breaker. Rectifier
input wiring is top-entry, directly to lugs on top of the input circuit breaker. DC link
and critical bus output connections are top entry, to frame-mounted lugs. A bottomentry access plate is standard, to enable the installer to pull AC cables and control
wiring through the module to the connections on top.
For “SpaceSaver” modules in the 48” frame, rectifier and bypass input wiring is topentry, directly to lugs on top of their respective circuit breakers. DC link and critical
bus output connection are top entry, to frame-mounted lugs.
Standard modules with top-and-bottom entry have access plates and a wireway on
the right side of the modules. All power connections are to bus bars in the wireway.

Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 and associated notes of the National
Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Refer to Table 3. Connect
wire to the lug using tool and procedure specified by the lug manufacturer.

Table 2
Torque Specifications

BOLT SHAFT
SIZE
1/4
5/16
3/8
1/2

NUT AND BOLT COMBINATIONS
GRADE 2
ELECTRICAL CONNECTIONS
STANDARD
with Belleville Washers
Lb - in
N-m
Lb-in
N-m
53
6.0
46
5.2
107
12
60
6.8
192
22
95
11
428
22
256
29

CIRCUIT BREAKERS
WITH COMPRESSION LUGS
(For Power Wiring)
Lb-in
N-m
WIRE SIZE
OR
RANGE
#6 - #4
100
11
#3 - #1
125
14
1/0 - 2/0
150
17
3/0 - 200 MCM
200
23
250 - 400 MCM
250
28
500 - 700 MCM
300
34

22

TERMINAL BLOCK
COMPRESSION LUGS
(For Control Wiring)
Lb-in
N-m
AWG WIRE
SIZE
OR RANGE
#22 -#14
3.5 to 5.3
0.4 to 0.6

Installation Manual

Table 3
Field-Supplied Lugs
T & B LUG STYLE
1
2
3
4
5
6
7
8
9
10
11
12
13
14

STAK-ON
COLOR-KEYED
ALUMINUM/
COPPER
COLOR-KEYED
COPPER CABLE
LONG BARREL
NARROW-TONGUE
COPPER CABLE

WIRE SIZE
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
1/0 AWG
2/0 AWG
3/0 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250MCM
350MCM
500MCM

ONE-HOLE LUGS
BOLT SIZE
TONGUE
(INCHES)
WIDTH (IN.)
3/8
0.88
3/8
1.00
3/8
1.10
3/8
1.20
3/8
0.93
3/8
0.97
3/8
1.06
3/8
0.75
3/8
0.81
1/2
0.94
1/2
1.03
1/2
1.09
1/2
1.09
1/2
1.20

T & B P/N

LIEBERT P/N

J973
K973
L973
M973
60130
60136
60142
54909BE
54910BE
54965BE
54970BE
54913BE
55165
55171

12-714255-56
12-714255-66
12-714255-76
12-714255-86

NOTES:
1. Manufacturer: Thomas & Betts (T & B). (800) 862-8324

Liebert Series 600T UPS, 65-225 kVA, Single Module

23

Table 310-16. Allowable Ampacities of Insulated Conductors
Rated 0-2000 Volts, 60 to 90C (140 to 194F)
Not More Than Three Conductors in Raceway or Cable or
Earth (Directly Buried), Based on Ambient Temperature of 30 (86F)
Size

Temperature Rating of Conductor. See Table 310-13.
90°C
60°C
75°C
90°C
(194°F)
(140°)
(167°F)
(194°F)
TYPES
TYPES
TYPES
TYPES
TBS, SA,
TW=
RH=, RHW=,
TBS,
SIS, FEP=
UF=
THHW=,
SA, SIS,
FEPB=, MI,
THW=,
THHN=,
RHH= RHW-2
THWN=,
THHW=,
THHN=, THHW=,
XHHW=,
THW-2, THWN-2,
THW-2, THWN-2,
USE=
RHH==, RHW-2,
USE-2, XHH,
USE-2,
XHHW=
XHH, XHHW=,
XHHW-2, ZW-2
XHHW-2, ZW-2
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM

Size

60oC
(140°F)
TYPES
TW=
UF=

75°C
(167°F)
TYPES
FEPW=,
RH, RHW=,
THHW=,
THW=,
THWN=,
XHHW=,
USE=, ZW=

18
16
14*
12*
10*
8
6
4
3
2
1

......
......
20
25
30
40
55
70
85
95
110

.......
.......
20
25
35
50
65
85
100
115
130

14
18
25
30
40
55
75
95
110
130
150

.......
.......
.......
20
25
30
40
55
65
75
85

.......
.......
.......
20
30
40
50
65
75
90
100

.......
.......
.......
25
35
45
60
75
85
100
115

.......
.......
.......
12*
10*
8*
6
4
3
2
1

1/0
2/0
3/0
4/0

125
145
165
195

150
175
200
230

170
195
225
260

100
115
130
150

120
135
155
180

135
150
175
205

1/0
2/0
3/0
4/0

250
300
350
400
500

215
240
260
280
320

255
285
310
335
380

290
320
350
380
430

170
190
210
225
260

205
230
250
270
310

230
255
280
305
350

250
300
350
400
500

600
700
750
800
900

355
385
400
410
435

420
460
475
490
520

475
520
535
555
585

285
310
320
330
355

340
375
385
395
425

385
420
435
450
480

600
700
750
800
900

1000
1250
1500
1750
2000

455
495
520
545
560

545
590
625
650
665

615
665
705
735
750

375
405
435
455
470

445
485
520
545
560

500
545
585
615
630

1000
1250
1500
1750
2000

1.04
1.00
.96
.91
.87
.82
.76
.71
.58
.41

Ambient
Temp °F
70-77
78-86
87-95
96-104
105-113
114-122
123-131
132-140
141-158
159-176

AWG
kcmil

Ambient
Temp °C
21-25
26-30
31-35
36-40
41-45
46-50
51-55
56-60
61-70
71-80

1.08
1.00
.91
.82
.71
.58
.41
.......
.......
.......

CORRECTION FACTORS
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities
shown above by the appropriate factor shown below.
1.05
1.04
1.08
1.05
1.00
1.00
1.00
1.00
.94
.96
.91
.94
.88
.91
.82
.88
.82
.87
.71
.82
.75
.82
.58
.75
.67
.76
.41
.67
.58
.71
.......
.58
.33
.58
.......
.33
.......
.41
.......
.......

AWG
kcmil

*Unless otherwise specifically permitted in Section 240-3 of this Code, the overcurrent protection for conductor types marked with an asterisk (*) shall not
exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum
and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.
Reprinted with permission from NEC 1999, NFPA 70, the National Electrical Code , Copyright 1998, National Fire Protection Association, Quincy,
MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on the referenced subject which
is represented only by the standard in its entirety.

24

Installation Manual

Figure 11. Outline Drawing Single and Multi Module 65 & 80 kVA

Liebert Series 600T UPS, 65-225 kVA, Single Module

25

Figure 12. Outline Drawing, 100 through 225 kVA Module with SpaceSaver Top-Entry Configuration

26

Installation Manual

Figure 13. Outline Drawing, 100 through 225 kVA Module with Standard Top & Bottom Entry

Liebert Series 600T UPS, 65-225 kVA, Single Module

27

Figure 14. Bypass Transformer Cabinet, 65 & 80 kVA

28

Installation Manual

Figure 15. Bypass Transformer Cabinet, 100-225 kVA

Liebert Series 600T UPS, 65-225 kVA, Single Module

29

Figure 16. Battery Power Pack, 65 & 80 kVA

30

Installation Manual

Figure 17. Battery Power Pack, Size A, 100-225 kVA

Liebert Series 600T UPS, 65-225 kVA, Single Module

31

Figure 18. Outline Drawing, 3-Breaker MBC, 65 & 80 kVA

32

Installation Manual

Figure 19. Outline Drawing, 3-Breaker MBC with Bypass Transformer,
65 & 80 kVA
Liebert Series 600T UPS, 65-225 kVA, Single Module

33

Figure 20. Outline Drawing, 3-Breaker MBC, 125-350 Amps

34

Installation Manual

Figure 21. Outline Drawing, 3-Breaker MBC, 450 to 800 Amps
Liebert Series 600T UPS, 65-225 kVA, Single Module

35

Figure 22. Outline Drawing, 3-Breaker MBC, 600-800 Amps

36

Installation Manual

Figure 23. Line-up Detail, 65 & 80 kVA SMS with Bypass Transformer Cabinet

Liebert Series 600T UPS, 65-225 kVA, Single Module

37

Figure 24. Line-up Detail, 100-225 kVA Space Saver with Bypass Transformer Cabinet

38

Installation Manual

Figure 25. Line-up Detail, 100-225 kVA Standard SMS with Bypass Transformer Cabinet

Liebert Series 600T UPS, 65-225 kVA, Single Module

39

Figure 26. Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets

40

Installation Manual

Figure 27. Line-up Detail, 100-225 kVA Space Saver with Battery Cabinets

Liebert Series 600T UPS, 65-225 kVA, Single Module

41

Figure 28. Line-up Detail, 100-225 kVA Standard SMS with Battery Cabinets

42

Installation Manual

Figure 29. Line-up Detail, 65 & 80 kVA with 3-Breaker MBC

Liebert Series 600T UPS, 65-225 kVA, Single Module

43

Figure 30. Line-up Detail, 65 & 80 kVA with Bypass Transformer and 3-Breaker MBC

44

Installation Manual

Figure 31. Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC

Liebert Series 600T UPS, 65-225 kVA, Single Module

45

Figure 32. Line-up Detail, 100-225 kVA Space Saver with
Bypass Transformer Cabinet and 3-Breaker MBC

46

Installation Manual

Figure 33. Line-up Detail, 100-225 kVA with 3-Breaker MBC

Liebert Series 600T UPS, 65-225 kVA, Single Module

47

Figure 34. Line-up Detail, 100-225 kVA with Bypass Transformer Cabinet and 3-Breaker MBC

48

Installation Manual

Figure 35. Terminal Details, 65 & 80 kVA Single Module Systems

Liebert Series 600T UPS, 65-225 kVA, Single Module

49

Figure 36. Terminal Details, 100 & 125 kVA Space Saver

50

Installation Manual

Figure 37. Terminal Details, 150 & 225 kVA Standard SMS

Liebert Series 600T UPS, 65-225 kVA, Single Module

51

Figure 38. Terminal Details, 100 & 125 kVA Standard SMS

52

Installation Manual

Figure 39. Terminal Details, 150 & 225 kVA Standard SMS

Liebert Series 600T UPS, 65-225 kVA, Single Module

53

Figure 40. Control Connection Locations, 65 & 80 kVA

54

Installation Manual

Figure 41. Control Connection Locations, 100 through 225 kVA

Liebert Series 600T UPS, 65-225 kVA, Single Module

55

Figure 42. Standard Control Wiring, Single Module System

56

Installation Manual

Figure 43. Option Wiring, Alarm Status Contacts

Liebert Series 600T UPS, 65-225 kVA, Single Module

57

Figure 44. Option Wiring, Maintenance Bypass Interlock

58

Installation Manual

Figure 45. Option Wiring, Remote Status Panel Interface

Liebert Series 600T UPS, 65-225 kVA, Single Module

59

Figure 46. Option Wiring, Remote Terminal IFM (RS-232 Communications)

60

Installation Manual

Figure 47. Option Wiring, SiteScan Interface

Liebert Series 600T UPS, 65-225 kVA, Single Module

61

Figure 48. Option Wiring, Customer Alarm Interface

62

Installation Manual

Figure 49. Option Wiring, Battery Temperature Sensor

Liebert Series 600T UPS, 65-225 kVA, Single Module

63

Figure 50. Option Wiring, SNMP Interface

64

Installation Manual

Figure 51. Option Wiring, Internal Modem

Liebert Series 600T UPS, 65-225 kVA, Single Module

65

Figure 52. Option Wiring, Maintenance Bypass Cabinet

66

Installation Manual

Figure 53. Module Battery Disconnect, 65 through 125 kVA

Liebert Series 600T UPS, 65-225 kVA, Single Module

67

Figure 54. Module Battery Disconnect, 150 & 225 kVA

68

Installation Manual

Figure 55. Remote Status Panel, Surface Mount

Liebert Series 600T UPS, 65-225 kVA, Single Module

69

Figure 56. Circuit Breaker Schedule, 65 through 225 kVA

70

Installation Manual

Figure 57. Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA

Liebert Series 600T UPS, 65-225 kVA, Single Module

71

Figure 58. Circuit Breaker Schedule, Maintenance Bypass Cabinet, 65 through 225 kVA

72

Installation Manual

Appendix A: Site Planning Data
65-225 kVA Single Module Systems

Notes
1.

Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current
includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and
noncontinuous current limits are defined in NEC 100. Maximum input current is controlled by current limit setting which
is adjustable. Values shown for maximum setting are 125% of nominal input current. Standard factory setting is 115%.

2.

Nominal AC output current (considered continuous) is based on full rated output load. Maximum current includes
nominal output current and overload current for 10 minutes.

3.

Bypass AC input current (considered continuous) is based on full rated output load.

4.

Feeder protection (by others in external equipment) for rectifier AC input and bypass AC input is recommended to be
provided by separate overcurrent protection devices.

5.

UPS output load cables must be run in separate conduit from input cables.

6.

Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop
(measured at the module) at maximum discharge current.

7.

Grounding conductors to be sized per NEC 250-122. Neutral conductors to be sized for full capacity -- per
NEC 310-15 (b)(4) -- for systems with 4-wire loads and half capacity for systems with 3-wire loads.

8.

Rectifier AC Input:3-phase, 3-wire, plus ground
AC Output to Load: 3-phase, 3 or 4-wire, plus ground
Bypass AC Input:3-phase, 3 or 4-wire, plus ground
Module DC Input from Battery:2-wire, (positive and negative) plus ground

9.

All wiring is to be in accordance with National and Local Electrical Codes.

10. Minimum overhead clearance is 2 feet above UPS.
11. Top and bottom cable entry standard through removable access plates. However, SpaceSaver versions of the 100-225
kVA modules are 8” narrower (48” vs. 56”) and are top-entry only. Tables show SpaceSaver modules, where available.
Cut access plates to suit conduit size.
12. Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors.
13. 7% maximum reflected input harmonic current and 0.92 lagging input power factor at full load with optional input filter.

Liebert Series 600T UPS, 65-225 kVA, Single Module

A-1

Series 600T Single Module Systems
208 Volt Input

UPS Rating
kVA

kW

65
52
65
52
65
52
65
52
80
64
80
64
80
64
80
64
100
80
100
80
100
80
100
80
125 100
125 100
125 100
125 100
150 120
150 120
150 120
150 120
225 180
225 180
225 180
225 180
Applicable
Notes:

A-2

AC
Output
Voltage
VAC

208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208
208

Rectifier AC
Options
Input Current
Input
Input
Filter Xformer Nom
Max

NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
13

NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES

184
229
170
213
187
233
173
216
226
282
209
262
230
287
213
266
282
353
262
327
287
359
266
333
353
441
327
409
359
449
333
416
424
530
393
491
431
538
399
499
635
794
589
736
646
807
599
748
1,4,8,
9,11,12

Inverter Or
Bypass AC
Output
Current
Nom

Max

180
226
180
226
180
226
180
226
222
278
222
278
222
278
222
278
278
347
278
347
278
347
278
347
347
434
347
434
347
434
347
434
416
520
416
520
416
520
416
520
625
781
625
781
625
781
625
781
2,3,5,7,8,
9,11,12

Required Maximum Maximum
Battery
Battery
Heat
DisconCurrent
Dissipanect
At End Of
tion
Rating Discharge BTU/Hr
Amperes Amperes Full Load

175
175
175
175
175
175
175
175
250
250
250
250
250
250
250
250
350
350
350
350
500
500
500
500
6

141
141
141
141
174
174
174
174
217
217
217
217
271
271
271
271
326
326
326
326
488
488
488
488
6,8,9,
11,12

14,390
15,015
17,555
18,200
17,710
18,480
21,600
22,395
22,140
23,100
27,005
27,995
27,675
28,875
33,755
34,995
33,200
34,650
40,500
42,000
49,800
52,000
60,750
63,000

Dimensions
Inches
(WxDxH)

34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
56x33x79
56x33x79
56x33x79
56x33x79
56x33x79
56x33x79
56x33x79
56x33x79
11

Floor
Loading
Approx.
Lb./Sq.ft
Weight
(ConcenLB.
trated
(unpacked) Loading)

1,900
1,950
2,400
2,450
2,100
2,150
2,630
2,680
2,900
2,950
3,270
3,320
3,050
3,100
3,450
3,500
3,320
3,450
4,020
4,150
3,870
4,000
4,510
4,640

251
258
318
324
278
285
348
355
264
268
297
302
277
282
314
318
259
269
313
323
302
312
351
362

Installation Manual

Series 600T Single Module Systems
480 Volt Input

UPS Rating

AC
Output
Voltage

kVA

kW

VAC

65
65
65
65
65
65
65
65
80
80
80
80
80
80
80
80
100
100
100
100
100
100
100
100
125
125
125
125
125
125
125
125
150
150
150
150
150
150
150
150
225
225
225
225
225
225
225
225

52
52
52
52
52
52
52
52
64
64
64
64
64
64
64
64
80
80
80
80
80
80
80
80
100
100
100
100
100
100
100
100
120
120
120
120
120
120
120
120
180
180
180
180
180
180
180
180

480
480
480
480
208
208
208
208
480
480
480
480
208
208
208
208
480
480
480
480
208
208
208
208
480
480
480
480
208
208
208
208
480
480
480
480
208
208
208
208
480
480
480
480
208
208
208
208

Applicable
Notes:

Options
Input
Input
Filter Xformer

NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
13

NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES

Rectifier
AC Input
Current
Nom

Max

78
98
73
91
80
99
74
92
79
98
73
91
80
100
74
93
96
120
89
112
98
122
91
113
97
121
90
112
98
123
91
114
120 151
112 140
122 153
113 142
121 151
112 140
123 154
114 143
151 188
140 174
153 191
142 177
151 189
140 175
154 192
143 178
181 226
167 209
184 229
170 213
182 227
168 210
185 231
171 214
271 339
251 314
275 344
255 319
272 341
253 316
277 346
257 321
1,4,8,
9,11,12

Inverter Or
Bypass AC
Output
Current
Nom

Max

78
98
78
98
78
98
78
98
180 226
180 226
180 226
180 226
96
120
96
120
96
120
96
120
222 278
222 278
222 278
222 278
120 150
120 150
120 150
120 150
278 347
278 347
278 347
278 347
150 188
150 188
150 188
150 188
347 434
347 434
347 434
347 434
180 226
180 226
180 226
180 226
416 520
416 520
416 520
416 520
271 338
271 338
271 338
271 338
625 781
625 781
625 781
625 781
2,3,5,7,8,
9,11,12

Liebert Series 600T UPS, 65-225 kVA, Single Module

Required
Battery
Disconnect
Rating
Amperes

Maximum
Battery
Current At
End Of
Discharge
Amperes

Maximum
Heat
Dissipation
BTU/Hr
Full Load

150
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
225
225
225
225
225
225
225
225
250
250
250
250
250
250
250
250
300
300
300
300
300
300
300
300
500
500
500
500
500
500
500
500
6

140
140
140
140
141
141
141
141
173
173
173
173
174
174
174
174
216
216
216
216
217
217
217
217
270
270
270
270
271
271
271
271
324
324
324
324
326
326
326
326
486
486
486
486
488
488
488
488
6,8,9,
11,12

11,330
11,935
14,390
15,015
12,340
12,950
15,435
16,065
13,945
14,685
17,710
18,480
15,185
15,940
18,995
19,770
17,425
18,360
22,140
23,100
18,980
19,920
23,745
24,715
21,785
22,950
27,675
27,675
23,725
23,725
29,680
29,680
26,140
27,540
33,210
34,650
28,475
29,885
35,615
37,070
39,215
41,305
49,810
41,305
42,710
44,825
53,420
55,605

Floor
Loading
Approx.
Lb./Sq.ft
Dimensions
Weight
(ConcenInches
LB.
trated
(WxDxH)
(unpacked) Loading)

34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
56x33x79
56x33x79
56x33x79
56x33x79
48x33x79
48x33x79
48x33x79
48x33x79
56x33x79
56x33x79
56x33x79
56x33x79
11

1,500
1,550
2,200
2,250
1,700
1,750
2,400
2,450
1,700
1,750
2,430
2,480
1,950
2,000
2,680
2,730
2,300
2,370
3,075
3,145
2,600
2,670
3,375
3,445
2,400
2,470
3,200
3,270
2,700
2,770
3,500
3,570
2,650
2,780
3,550
3,680
3,050
3,180
3,950
4,080
2,990
3,120
4,190
4,320
3,475
3,605
4,675
4,805

281
291
413
422
319
328
450
459
319
328
456
465
366
375
503
512
209
215
280
286
236
243
307
313
218
225
291
297
245
252
318
325
241
253
323
335
238
248
308
318
272
284
381
393
271
281
364
374

A-3

Series 600T Single Module Systems
600 Volt Input

UPS Rating
kVA

kW

65
52
65
52
65
52
65
52
65
52
65
52
65
52
65
52
80
64
80
64
80
64
80
64
80
64
80
64
80
64
80
64
100
80
100
80
100
80
100
80
100
80
100
80
100
80
100
80
125 100
125 100
125 100
125 100
125 100
125 100
125 100
125 100
150 120
150 120
150 120
150 120
150 120
150 120
150 120
150 120
225 180
225 180
225 180
225 180
225 180
225 180
225 180
225 180
Applicable
Notes:

A-4

AC
Output
Voltage
VAC

600
600
600
600
208
208
208
208
600
600
600
600
208
208
208
208
600
600
600
600
208
208
208
208
600
600
600
600
208
208
208
208
600
600
600
600
208
208
208
208
600
600
600
600
208
208
208
208

Options
Input
Input
Filter Xformer

NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
13

NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES
NO
NO
YES
YES

Rectifier AC
Input
Current
Nom

Max

63
79
58
73
64
80
59
74
63
79
59
73
64
80
60
75
77
97
72
90
79
98
73
91
78
97
72
90
79
99
73
92
97
121
90
112
98
123
91
114
97
122
90
113
99
124
92
115
121 151
112 140
123 154
114 143
122 152
113 141
124 155
115 143
145 182
135 168
148 185
137 171
146 183
135 169
148 186
138 172
218 272
202 253
221 277
205 257
219 274
203 254
223 278
206 258
1,4,8,
9,11,12

Inverter Or
Bypass AC
Output
Current
Nom

Max

63
78
63
78
63
78
63
78
180
226
180
226
180
226
180
226
77
96
77
96
77
96
77
96
222
278
222
278
222
278
222
278
96
120
96
120
96
120
96
120
278
347
278
347
278
347
278
347
120
150
120
150
120
150
120
150
347
434
347
434
347
434
347
434
144
180
144
180
144
180
144
180
416
520
416
520
416
520
416
520
217
271
217
271
217
271
217
271
625
781
625
781
625
781
625
781
2,3,5,7,8,
9,11,12

Required
Battery
Disconnect
Rating
Amperes

150
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
225
225
225
225
225
225
225
225
250
250
250
250
250
250
250
250
300
300
300
300
300
300
300
300
500
500
500
500
500
500
500
500
6

Maximum Maxmum
Battery
Heat
Current At DissipaEnd Of
tion
Discharge
BTU/Hr
Amperes Full Load

140
140
140
140
141
141
141
141
173
173
173
173
174
174
174
174
216
216
216
216
217
217
217
217
270
270
270
270
271
271
271
271
324
324
324
324
326
326
326
326
486
486
486
486
488
488
488
488
6,8,9,
11,12

12,340
12,950
15,435
16,065
13,355
13,975
16,490
17,125
15,185
15,940
18,995
19,770
16,445
17,200
20,290
21,075
18,980
18,920
23,745
24,715
20,550
21,500
25,265
26,345
23,725
24,900
29,680
30,895
25,690
26,875
31,705
32,930
28,480
29,880
35,615
37,070
30,825
32,250
38,045
39,520
42,710
44,825
53,420
55,605
46,240
48,380
57,070
59,280

Dimensions
Inches
(WxDxH)

34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
34x32x68
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
48x33x79
56x33x79
56x33x79
56x33x79
56x33x79
48x33x79
48x33x79
48x33x79
48x33x79
56x33x79
56x33x79
56x33x79
56x33x79
11

Floor
Loading
Approx.
Lb./Sq.ft
Weight
(ConcenLB.
trated
(unpacked) Loading)

1,600
1,650
2,200
2,250
1,800
1,850
2,400
2,450
1,800
1,850
2,430
2,480
2,050
2,100
2,680
2,730
2,450
2,520
3,075
3,145
2,750
2,820
3,375
3,445
2,600
2,670
3,200
3,270
2,900
2,970
3,500
3,570
2,920
3,050
3,570
3,700
3,270
3,400
3,920
4,050
3,260
3,390
4,210
4,340
3,660
3,790
4,610
4,740

300
309
413
422
338
347
450
459
338
347
456
465
384
394
503
512
223
229
280
286
250
256
307
313
236
243
291
297
264
270
318
325
265
277
325
336
255
265
305
316
296
308
383
395
285
295
359
369

Installation Manual

Liebert Series 600T UPS, 65-225 kVA, Single Module

A-5

POWER AVAILABILITY

Series 600T™ UPS

INSTALLATION MANUAL

The Company Behind the Products

Technical Support

With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:

United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229

•
•
•

•
•

Environmental systems—close-control air
conditioning from 1 to 60 tons
Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both
environmental and power protection in a
single, flexible package
Monitoring and control—from systems of any
size or location, on-site or remote
Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center

While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
© 2000 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.

SL-30545 (2/00)

Single-Phase UPS
800-543-2378
Outside the United States
614-841-6598
3-Phase UPS
800-543-2378
Environmental Control
800-543-2778
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
FAX: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
FAX: +852 2 831 0114
Web Site
www.liebert.com
E-mail
UPStech@liebert.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Create Date                     : 2000:02:07 14:58:28Z
Creator                         : FrameMaker 5.5.6p145
Modify Date                     : 2002:04:19 14:40:51-03:00
Page Count                      : 84
Page Mode                       : UseOutlines
Has XFA                         : No
Creation Date                   : 2000:02:07 14:58:28Z
Producer                        : Acrobat Distiller 4.0 for Windows
Mod Date                        : 2002:04:19 14:40:51-03:00
Metadata Date                   : 2002:04:19 14:40:51-03:00
Title                           : insms225.book
EXIF Metadata provided by EXIF.tools

Navigation menu