Lifebreath Rnc10 Users Manual
RNC120D c7ec2756-8b9b-1924-451e-1ba2cdf7fd7a
RNC5-TPD to the manual c7ec2756-8b9b-1924-451e-1ba2cdf7fd7a
2015-02-09
: Lifebreath Lifebreath-Rnc10-Users-Manual-571807 lifebreath-rnc10-users-manual-571807 lifebreath pdf
Open the PDF directly: View PDF .
Page Count: 36
Download | |
Open PDF In Browser | View PDF |
Installation Instructions for Heat Recovery Ventilators with 2 Speed RNC Electronics RNC Series Models RNC95 RNC155 RNC200 RNC10 RNC20 RNC120D RNC5-TPD Residential Heat Recovery Ventilators (HRV) Manufactured with 2 Speed RNC Electronics TI-RNC 0108 Table of Contents Introduction Introduction.........................................................................2 The Lifebreath HRV (Heat Recovery Ventilator) is designed to introduce fresh outdoor air into a building while exhausting an equal amount of stale indoor air. Engineering Data - RNC95 .............................................3-4 Engineering Data - RNC155...............................................5 During the heating season, heat energy from the stale exhausting air is transferred to the fresh, incoming air via Lifebreath's patented aluminum core. Engineering Data - RNC200...............................................6 Engineering Data - RNC10.................................................7 Engineering Data - RNC20.................................................8 During the air conditioning season, the HRV will help cool the incoming fresh air with the cooler stale exhausting air. Engineering Data - RNC5-TPD..........................................9 Engineering Data - RNC120D ....................................10-11 RNC Electronics Remote Control Devices...................................................12 Locating and Suspending the HRV ..................................13 RNC electronics offers standard 2-speed operation of low/high. There is also an installer selectable 2-speed operation of medium low/high (refer to "Increasing Low Speed to Medium Low" in this manual). Locating and Suspending the RNC120D..........................14 Drain Connection..............................................................15 Installation Methods .........................................................16 The RNC circuit board also includes an interlock relay which is used to Interlock the HRV to an Air Handler/Furnace. Refer to "Interlocking HRV Operation to an Air Handler/Furnace Blower" in this manual. Simplified Installation ......................................................17 Partially Dedicated Installation.........................................18 Fully Dedicated Installation..............................................19 We recommend using one of the Optional Main Controls (refer to "Remote Control Devices" in this manual) for normal operation. Grilles and Weatherhoods.................................................20 Electrical ...........................................................................21 Changing OFF to Standby/ Increasing Low Speed to Medium....................................21 CAUTION Mode DIP Switch Settings................................................21 Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflows of the HRV (Heat Recovery Ventilator) by using the balancing procedure found in this manual. NEVER install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment. Wiring the Controls ..........................................................22 Defrost Operation .............................................................23 Defrost Cycle DIP Switch Settings...................................23 Air Flow Balancing .....................................................24-27 Interlocking HRV Operation to an Air Handler/Furnace Blower ............................................28 Wiring Diagrams .........................................................29-31 Troubleshooting................................................................32 Maintenance......................................................................33 IMPORTANT NOTE Please read this manual before installing the HRV (Heat Recovery Ventilator). Due to ongoing research and product development, specifications, ratings and dimensions are subject to change without notice. Leave this Manual for the Homeowner TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION Installing Contractor _________________________________________Telephone / Contact _____________________ Serial Number______________________________________________Installation Date ________________________ Model _________________________________________________________________________________________ 2 Engineering Data - HRV Model RNC95 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE HRV Four threaded inserts at corners of the cabinet designed to accept PVC reinforced polyester straps that are supplied with the unit. DEFROST Recirculating defrost system. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD. WEIGHT 52 lbs. (23.6 kg) Shipping Weight 56 lbs. (25.4 kg) Performance (HVI certified) Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) @ 0.1" (25 Pa) 76 (36) @ 0.2" (50 Pa) 73 (34) @ 0.3" (75 Pa) 70 (33) @ 0.4" (100 Pa) 66 (31) @ 0.5" (125 Pa) 60 (29) Max. Temperature Recovery Sensible Effectiveness @ 60 cfm (28 L/s) *Sensible Efficiency @ 60 cfm (28 L/s) CONTROLS - HRV System Control HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV. Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available. *Sensible Efficiency @ 61 cfm (29 L/s) OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.) 99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch. The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch. The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length (max.) OPTIONAL TIMERS 99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge wire (min.) 100’ length 99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length 99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100' length (max.) WARRANTY Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty. DIMENSIONS RNC95 18.5" (470 mm) 24.5" (622 mm) inches (mm) knockout for side mounting of EXHAUST return port 6" round collar converted to oval Hanging straps (4) Drain Pan Drain spout FRONT SIDE 16" (406 mm) 32°F (0°C) 88% 32°F (0°C) 75% -13°F (-25°C) 68% 120 WATTS / Low speed. 60 WATTS / High speed 150 Amp rating 0.9 *Sensible Efficiency – thermal **Latent Efficiency – moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs 80 5 - High Speed 5 75 Air Flow (cfm) 70 65 60 55 50 0 0.1 0.2 0.3 0.4 0.5 0.6 Static Pressure (in w.g.) All units conform to CSA and UL standards Threaded inserts (4) at corners 18.5" (470 mm) minimum 18 inches (459 mm) required for service access 88% VAC @ 60HZ SUPPLY Fresh air from outside 5" round collar Removable Heat Recovery Core [cfm (L/s)] EXHAUST Stale Air to outside 5" round collar EXHAUST Return air from building SUPPLY Fresh air to building 6" round (conv. to oval) collar TOP Choice of port location Knockouts on top and side of unit (use 1 only) 6" round (conv. to oval) collar supplied Date: _______________________________________________ Contractor: __________________________________________ Tag: __________________________Qty:__________________ Supplier: ____________________________________________ Project: _____________________________________________ Quote#: _____________________________________________ Engineer:____________________________________________ Submitted by: ________________________________________ 3 SP-RNC95 Port Configuration and Airflow Model RNC95 In order to make the RNC95 as space efficient as possible, the INDOOR supply and return ports are converted from round to oval shape. Overall size of the port remains the same. Simply bend a standard duct fitting to the correct shape, and attach to the oval port using the same method as for a round port. RNC95 Specifications The RNC95 HRV (Heat Recovery Ventilator) has been designed to allow the installer to choose between two possible positions on the cabinet for the Stale Air Exhaust (from building) port. Illustrations in this manual show standard (side mounted) port location. The same specifications apply to both RNC95 setups, regardless of which port position is selected. SIDE MOUNTED PORT standard location Round port bent to oval RNC95 Air Flow Stale air enters the FRONT RIGHT side port. The air will pass down the front half of the core, then up the back half of the core and out the RIGHT REAR port. TOP MOUNTED PORT alternate location Fresh outdoor air will enter the LEFT REAR port and pass down the back half of the core. It will then pass up the front half of the core, and out the LEFT FRONT port. Variable Port Location / Installation (Model RNC95 only) The exhaust return port collar is not factory installed. Installer may choose either side mounted or alternate top mounted port by simply removing one of the two knock-out plates and attaching a port collar (supplied). To remove knock-out plate, insert a utility knife into the knock-out slits and trace them completely to puncture protective film underneath. Then, cut the solid tabs between the slits, using tin snips or side cutters, and remove the knock-out plate. If any protective film still blocks the opening, remove it now. 4 Engineering Data - HRV Model RNC155 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit. DEFROST Recirculating damper defrost system. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD. WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg) CONTROLS - HRV System Control HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV. Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available. Performance (HVI certified) Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) [cfm (L/s)] @ 0.1" (25 Pa) 150 (71) @ 0.2" (50 Pa) 146 (69) @ 0.3" (75 Pa) 134 (63) @ 0.4" (100 Pa) 121 (57) @ 0.5" (125 Pa) 106 (50) @ 0.6" (150 Pa) 92 (43) Max. Temperature Recovery Sensible Effectiveness @ 65 cfm (31 L/s) *Sensible Efficiency @ 65 cfm (31 L/s) *Sensible Efficiency @ 68 cfm (32 L/s) 78% 32°F (0°C) 76% 32°F (0°C) 64% -13°F (-25°C) 66% VAC @ 60HZ 120 WATTS / Low speed. 49 OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) WATTS / High speed 120 99-116 Amp rating 1.4 99-RECIRC 99-130 OPTIONAL TIMERS *Sensible Efficiency – thermal **Latent Efficiency – moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs 160 3 - High Speed *2 - Medium Low Speed *1 - Low speed 3 140 * Manufacturers Data 120 Air Flow (cfm) 99-2040 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.) 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch. The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.) Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch. The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.) Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length (max.) 100 80 2 99-132 99-104 99-101 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge wire (min.) 100’ length Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100' length (max.) WARRANTY Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty. inches (mm) 0 0.1 0.2 0.3 0.4 0.5 Static Pressure (in w .g.) 0.6 0.7 All units conform to CSA and UL standards FILTERS BLOWERS CORE MOTOR STALE AIR TO OUTSIDE CONDENSATE DRAINS 20 STALE AIR FROM INSIDE FRESH AIR FROM OUTSIDE RECIRCULATING DEFROST DAMPER 1 40 *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit. 19" (483) DIMENSIONS RNC155 60 *All Duct Connections 6" (150mm) FRESH AIR TO INSIDE 33 5/8" (850mm) BALANCING DAMPER 14 3/4" (375) Date: _______________________________________________ Contractor: __________________________________________ Tag: __________________________Qty:__________________ Supplier: ____________________________________________ Project: _____________________________________________ Quote#: _____________________________________________ Engineer:____________________________________________ Submitted by: ________________________________________ 5 SP-RNC155 Engineering Data - HRV Model RNC200 CONTROLS - HRV System Control HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV. Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available. OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.) 99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch. The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch. The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length (max.) OPTIONAL TIMERS 99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge wire (min.) 100’ length 99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length 99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100' length (max.) Performance (HVI certified) Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) [cfm (L/s)] @ 0.1" (25 Pa) @ 0.2" (50 Pa) @ 0.3" (75 Pa) @ 0.4" (100 Pa) @ 0.5" (125 Pa) @ 0.6" (150 Pa) @ 0.7" (175 Pa) @ 0.8" (200 Pa) 207 (97) 200 (94) 184 (87) 171 (80) 152 (71) 130 (61) 116 (55) 86 (40) Max. Temperature Recovery Sensible Effectiveness @ 66 cfm (31 L/s) *Sensible Efficiency @ 66 cfm (31 L/s) *Sensible Efficiency @ 109 cfm (51 L/s) 74% 32°F (0°C) 74% 32°F (0°C) 64% -13°F (-25°C) 62% VAC @ 60HZ 120 WATTS / Low speed. 87 WATTS / High speed 164 Amp rating 1.4 *Sensible Efficiency – thermal **Latent Efficiency – moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs 220 3 - High Speed *2 - Medium Low Speed *1 - Low speed 3 200 180 Air Flow (cfm) THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit. DEFROST Recirculating damper defrost system. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD. WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg) * Manufacturers Data 160 140 120 2 100 1 80 60 40 0 0.1 0.2 0.3 0.4 0.5 0.6 Static Pressure (in w.g.) 0.7 0.8 0.9 WARRANTY Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty. All units conform to CSA and UL standards inches (mm) FRESH AIR FROM OUTSIDE RECIRCULATING DEFROST DAMPER STALE AIR FROM INSIDE FILTERS BLOWERS CORE MOTOR STALE AIR TO OUTSIDE CONDENSATE DRAINS *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit. 19" (483 mm) Dimensions RNC200 *All Duct Connections 6" (150 mm) FRESH AIR TO INSIDE 33 5/8" (850 mm) BALANCING DAMPER 14 3/4" (375 mm) Date: _______________________________________________ Contractor: __________________________________________ Tag: __________________________Qty:__________________ Supplier: ____________________________________________ Project: _____________________________________________ Quote#: _____________________________________________ Engineer:____________________________________________ Submitted by: ________________________________________ 6 SP-RNC200 Engineering Data - HRV Model RNC10 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four PVC reinforced polyester straps that are supplied with the unit. DEFROST Damper defrost system; defrosts automatically as the outdoor temperature falls. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD. WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 67 lbs. (30.4 kg) Performance (HVI certified) Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) 164 (77) @ 0.3" (75 Pa) 156 (73) @ 0.4" (100 Pa) 143 (67) @ 0.5" (125 Pa) 123 (58) @ 0.6" (150 Pa) 100 (47) @ 0.7" (175 Pa) 38 (18) Sensible Effectiveness @ 67 cfm (32 L/s) *Sensible Efficiency @ 67 cfm (32 L/s) *Sensible Efficiency @ 68 cfm (32 L/s) 78% 32°F (0°C) 76% 32°F (0°C) 66% -13°F (-25°C) 60% VAC @ 60HZ OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.) 99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch. The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length (max.) WARRANTY Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty. 177 (83) @ 0.2" (50 Pa) Max. Temperature Recovery CONTROLS - HRV System Control HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV. Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available. 120 WATTS / Low speed. 63 WATTS / High speed 173 Amp rating 1.4 *Sensible Efficiency - thermal **Latent Efficiency - moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs 200 180 3 - High Speed *2 - Medium Low Speed *1 - Low speed 3 160 *Manufacturer’s Data 140 Air Flow (cfm) OPTIONAL TIMERS 99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge wire (min.) 100’ length 99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length 99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100' length (max.) [cfm (L/s)] @ 0.1" (25 Pa) 120 2 100 1 80 60 40 20 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Static Pressure (in w.g.) All units conform to CSA and UL standards Dimensions RNC10 inches (mm) FRESH AIR FROM OUTSIDE DEFROST DAMPER STALE AIR TO OUTSIDE BLOWERS FILTERS FRESH AIR TO INSIDE STALE AIR FROM INSIDE *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit. * All Duct Connections 6"(150mm) 14 3/4" (375) 33-5/8" CONDENSATE DRAINS 19" (483) DEFROST PORT BALANCING DAMPER Date: _______________________________________________ Contractor: __________________________________________ Tag: __________________________Qty:__________________ Supplier: ____________________________________________ Project: _____________________________________________ Quote#: _____________________________________________ Engineer:____________________________________________ Submitted by: ________________________________________ 7 SP-RNC10 Engineering Data - HRV Model RNC20 CONTROLS - HRV System Control HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV. Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available. OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.) 99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch. The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length (max.) OPTIONAL TIMERS 99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge wire (min.) 100’ length 99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length 99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100' length (max.) WARRANTY Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty. Performance (HVI certified) Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) [cfm (L/s)] @ 0.1" (25 Pa) 214 (101) @ 0.2" (50 Pa) 206 (97) @ 0.3" (75 Pa) 193 (91) @ 0.4" (100 Pa) 184 (87) @ 0.5" (125 Pa) 170 (80) @ 0.6" (150 Pa) 155 (73) @ 0.7" (175 Pa) 137 (65) Max. Temperature Recovery Sensible Effectiveness @ 119 cfm (56 L/s) *Sensible Efficiency @ 119 cfm (56 L/s) *Sensible Efficiency @ 117 cfm (55 L/s) 69% 32°F (0°C) 67% 32°F (0°C) 60% -13°F (-25°C) 60% VAC @ 60HZ 120 WATTS / Low speed. 70 WATTS / High speed 182 Amp rating 1.4 *Sensible Efficiency - thermal **Latent Efficiency - moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs 240 220 3 - High Speed *2 - Medium Low Speed *1 - Low speed 3 200 *Manufacturer’s data 180 Air Flow (cfm) THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four PVC reinforced polyester straps that are supplied with the unit. DEFROST Damper defrost system; defrosts automatically as the outdoor temperature falls. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections two - 1/2" (12mm) OD. WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 67 lbs. (30.4 kg) 160 140 120 2 100 1 80 60 40 20 0 0.1 0.2 0.3 0.4 0.5 Static Pressure (in w.g.) 0.6 0.7 0.8 All units conform to CSA and UL standards Dimensions RNC20 inches (mm) FRESH AIR FROM OUTSIDE DEFROST DAMPER STALE AIR TO OUTSIDE BLOWERS FILTERS FRESH AIR TO INSIDE STALE AIR FROM INSIDE *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit. * All Duct Connections 6"(150mm) 14 3/4" (375) 33-5/8" CONDENSATE DRAINS 19" (483) DEFROST PORT BALANCING DAMPER Date: _______________________________________________ Contractor: __________________________________________ Tag: __________________________Qty:__________________ Supplier: ____________________________________________ Project: _____________________________________________ Quote#: _____________________________________________ Engineer:____________________________________________ Submitted by: ________________________________________ 8 SP-RNC20 Engineering Data - HRV Model RNC5-TPD CONTROLS- HRV System Control HRV defaults to user selected speed from switch on top of cabinet when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV. OFF(Standby)/LOW or OFF/HIGH speed operation is also available. OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.) 99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch. The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch. The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length (max.) OPTIONAL TIMERS 99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge wire (min.) 100’ length 99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length 99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100' length (max.) WARRANTY Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty. Dimensions RNC5-TPD Performance (H.V.I. certified) Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) @ 0.1" (25 Pa) @ 0.2" (50 Pa) @ 0.3" (75 Pa) @ 0.4" (100 Pa) @ 0.5" (125 Pa) @ 0.6" (150 Pa) @ 0.7" (175 Pa) @ 0.8" (200 Pa) @ 0.9" (225 Pa) @ 1.0" (250 Pa) [cfm (L/s)] 169 (80) 156 (73) 149 (70) 136 (64) 126 (59) 116 (54) 103 (48) 89 (42) 77 (36) 58 (27) Max. Temperature Recovery Sensible Effectiveness @ 66 cfm (31 L/s) 32°F (0°C) *Sensible Efficiency @ 66 cfm (31 L/s) 32°F (0°C) *Sensible Efficiency @ 76 cfm (36 L/s) 78% 74% 61% -13°F (-25°C) 63% VAC @ 60HZ 120 WATTS / Low speed. 69 WATTS / High speed 147 Amp rating 1.7 *Sensible Efficiency - thermal **Latent Efficiency - moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs 180 3 - High Speed *2 - Medium Low Speed *1 - Low speed 3 160 140 * Manufacturers Data 120 Air Flow (cfm) THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has an independent motorized impeller. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. DEFROST Recirculating damper defrost system. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 1/2" (12 mm) OD. MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit. DUCT CONNECTIONS 4 - 5” (127 mm) duct connections. WEIGHT 61 lbs. (28 kg) SHIPPING WEIGHT 64 lbs. (29 kg) 100 80 2 1 60 40 20 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 Static Pressure (in w.g.) All units conform to CSA and UL standards 15” (378 mm) inches (mm) 27” (690 mm) 2-1/4” (57 mm) SPEED SELECTION SWITCH 18-3/4” (475 mm) Date: _______________________________________________ Contractor: __________________________________________ Tag: __________________________Qty:__________________ Supplier: ____________________________________________ Project: _____________________________________________ Quote#: _____________________________________________ Engineer:____________________________________________ Submitted by: ________________________________________ 9 SP-RNC5-TPD Engineering Data - HRV Model RNC120D OPTIONAL TIMERS 99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire) 20 gauge wire (min.) 100’ length 99-104 Digital Electronic Timer- initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length 99-101 60 Minute Crank Timer - initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100' length (max.) WARRANTY Units carry a lifetime warranty on the heat recovery core and a 5 year replacement parts warranty. Dimensions RNC120D STALE AIR TO OUTSIDE FRESH AIR FROM OUTSIDE Performance (HVI certified) Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) @ 0.1" (25 Pa) @ 0.2" (50 Pa) @ 0.3" (75 Pa) @ 0.4" (100 Pa) @ 0.5" (125 Pa) @ 0.6" (150 Pa) @ 0.7" (175 Pa) @ 0.8" (200 Pa) @ 0.9" (225 Pa) @ 1.0" (250 Pa) [cfm (L/s)] 142 (67) 137 (64) 131 (62) 128 (60) 123 (58) 115 (54) 113 (53) 105 (49) 102 (48) 96 (45) Max. Temperature Recovery Sensible Effectiveness @ 70 cfm (33 L/s) *Sensible Efficiency @ 70 cfm (33 L/s) *Sensible Efficiency @ 67 cfm (32 L/s) 72% 32°F (0°C) 68% 32°F (0°C) 59% -13°F (-25°C) 56% VAC @ 60HZ 120 WATTS / Low speed. 70 WATTS / High speed 160 Amp rating 1.5 *Sensible Efficiency - thermal **Latent Efficiency - moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs 160 3 - High Speed *2 - Medium Low Speed *1 - Low speed 3 140 * Manufacturers Data 120 Air Flow (cfm) THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has an independent motorized impeller. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit. DEFROST Recirculating damper defrost system. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections- 1/2" (12 mm) OD. DUCT CONNECTIONS 5” duct connections. WEIGHT 42 lbs. (19 kg.) SHIPPING WEIGHT 45 lbs. (20.5 kg.) CONTROLS - HRV System Control HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV. Standard LOW SPEED SETTING can be increased to medium low. Off (Standby)/Low or OFF/HIGH speed operation is also available. OPTIONAL MAIN CONTROLS (only one main control can be installed on the system) 99-116 Dehumidistat Ventilation Control - Dehumidistat Dial, ON/OFF Switch and LOW/HIGH Switch (3 wire) 20 gauge wire (min.) 100' length (max.) 99-2040 20/40 ON/OFF Dehumidistat - Dehumidistat Dial, ON/OFF Switch and 20/40 Switch. The 20/40 Switch will toggle from continuous low speed ventilation to intermittent low speed ventilation of 20 minutes fan ON and 40 minutes fan OFF. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-RECIRC Recirculation Control - Dehumidistat Dial, ON/OFF Switch and Recirculation Switch. The Recirculation Switch will toggle from continuous low speed ventilation to continuous low speed recirculation. (4 wire) 20 gauge wire (min.) 100' length (max.) 99-130 Remote Dehumidistat - Dehumidistat Dial only. (2 wire) 20 gauge wire (min.) 100' length (max.) 100 80 2 1 60 40 20 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 Static Pressure (in w.g.) All units conform to CSA and UL standards All duct collars are 5” diameter (127 mm) inches (mm) STALE AIR FROM BUILDING 9 1/8” (232 mm) 22” (559 mm) FRESH AIR TO BUILDING 25 1/8” (637 mm) Front View (if mounting vertically) Bottom View (if mounting horizontally) Date: _______________________________________________ Contractor: __________________________________________ Tag: __________________________Qty:__________________ Supplier: ____________________________________________ Project: _____________________________________________ Quote#: _____________________________________________ Engineer:____________________________________________ Submitted by: ________________________________________ 10 SP-RNC120D Engineering Data - HRV Model RNC120D Option 1 - Horizontal Duct Configuration Dimensions inches FRESH AIR STALE FROM AIR TO OUTSIDE OUTSIDE HANGING STRAPS 22” (559 mm) STALE AIR FROM BUILDING FRESH AIR TO BUILDING 25 1/8” (637 mm) BOTTOM VIEW FOR HORIZONTAL MOUNT SERVICE CLEARANCE FROM BOTTOM OF UNIT IS MINIMUM 3’0” STALE AIR TO OUTSIDE FRESH AIR TO BUILDING 9-1/8” (232 mm) FRESH AIR FROM OUTSIDE STALE AIR FROM BUILDING ALL DUCT COLLARS ARE 5” DIAMETER ACCESS DOOR SIDE VIEW FOR HORIZONTAL MOUNT Connect drain hose to spout located in door. Option 2 - Vertical Duct Configuration Dimensions STALE AIR TO OUTSIDE FRESH AIR FROM OUTSIDE STALE AIR TO OUTSIDE inches HANGING STRAPS STALE AIR FROM BUILDING 22” (559 mm) “L” BRACKETS (not included) May be installed if wall mounting is desired for the vertical installation. FRESH AIR TO BUILDING FRESH AIR FROM OUTSIDE 25 1/8” (637 mm) STALE AIR FROM BUILDING 9-1/8” (232 mm) SIDE VIEW FOR VERTICAL MOUNT SERVICE CLEARANCE FROM BOTTOM OF UNIT IS MINIMUM 3’0” ALL DUCT COLLARS ARE 5” (127 mm) DIAMETER ACCESS DOOR FRESH AIR TO BUILDING TOP VIEW FOR VERTICAL MOUNT Connect drain hose to the two field installed spouts located on the bottom of the unit. The HRV can be installed horizontally or vertically as illustrated on the following pages. The unit should be suspended using the provided hanging straps. The unit must be level for proper condensate drainage. Sufficient clearance below the access door is required for servicing the air filters and core. A minimum of 25" (635mm) clearance is recommended so the door can be removed. Four PVC reinforced polyester hanging straps are provided for hanging the HRV. 11 Remote Control Devices Optional Main Control Features The Dehumidstat The amount of ventilation required in your home will fluctuate according to the activity level in the house. Higher activity levels require more ventilation. Main controls can be mounted in a central location of the home (i.e. beside the furnace thermostat) which will provide the user with complete control over their ventilation system from a convenient location. Main controls feature a dehumidistat which is used to reduce high indoor humidity levels during the heating season. The control has a selector knob with setpoints ranging from 20% to 80% relative humidity (RH). Most people are comfortable when indoor relative humidity levels are in a range from 30% to 45%. The dehumidistat switches the HRV to high speed ventilation when the moisture level in the home exceeds the desired setpoint. The dehumidistat should only be used during the heating season. It must be set to the OFF position throughout the rest of the year. The ON/OFF Switch The ON/OFF Switch will turn the HRV ON or OFF. Controls with an ON/OFF switch can be modified to ON/Standby by adjusting the circuit board DIP Switches (Refer to "Mode DIP Switch Settings"). Ventilation Dehumidistat Recirculation Control PART NO. 99-RECIRC High/Low Speed Switch PART NO. 99-116 The High/Low Speed Switch initiates High or Low speed ventilation. This control also has an ON/OFF Switch and a Dehumidistat Dial. The Recirculation Switch will toggle from continuous low speed ventilation to recirculation mode (closes the fresh air damper and circulates the building air). Dehumidistat The Dehumidistat Dial will Dial initiate High Speed ventilation when the indoor humidity level exceeds the set point (regardless position of the RECIRC Switch.). This control also has an ON/OFF Switch and a Dehumidistat Dial. T DEHUMIDISTA ON/OFF Switch 20/40 ON/OFF Dehumidistat PART NO. 99-2040 20/40 Switch The 20/40 Switch will toggle from continuous low speed ventilation to an intermittent mode of 20 minutes fan ON (in low speed) and 40 minutes fan OFF. The Dehumidistat Dial will initiate High Speed ventilation when the indoor humidity level exceeds the set point (regardless position of the 20/40 Switch.). This control also has an ON/OFF Switch. Recirculation Switch ON/OFF Switch Dehumidistat Dial Remote Dehumidistat Dehumidistat Dial PART NO. 99-130 White The Remote Dehumidistat activates high speed ventilation when the indoor humidity level exceeds the set point. ON/OFF Switch Dehumidistat Dial Optional Timers Install timers at each exhaust location of your system. 20 Minute Timer Crank Timer PART NO. 99-132 PART NO. 99-101 20 Minute Status Lights The 20 Minute Status Light indicates high speed operation is activated. Off 10 20 Crank Dial Rotate the dial for up to 60 minutes high speed operation. 30 60 50 40 Touch Pad The Touch Pad initiates high speed operation. • Connects to RED, BLACK and GREEN (LED drive) terminals. • Use a minimum of three 20 gauge low voltage wires. • Connect up to 4 on 100 ft (91 m) wire max. • Mounts in a 2 x 4 box. • Initiates high speed ventilation for up to 60 minutes. • Requires 2 lead low voltage (20 gauge) wire. • Mounts in a 2" x 4" box. 12 Locating and Suspending the HRV Location Selection The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted. If a basement area is not convenient or does not exist, a utility or laundry room may be used. Suspending the HRV The hanging straps should be attached to the unit at the top end corners (mounting screws are already located on the HRV case). Securely fasten the other end of the straps to the floor joists with wide head nails (not supplied), making sure the UNIT IS LEVEL. The straps are designed to reduce the possibility of noise, resonance or harmonics; therefore using the full length of the strap between the HRV and the floor joists is recommended. Attic installations are not normally recommended due to: A) the complexity of work to install Suspending the HRV using the Provided Hanging Straps B) freezing conditions in the attic C) difficulty of access for servicing Wide Head Nails WIDE HEAD (not supplied) CAUTION NAILS (not supplied) Unit must be installed level to ensure proper condensate drainage. Due to the broad range of installation and operational conditions, consideration must be given for the possibility of condensation forming on the unit or connecting ducting. Objects below the installation may be exposed to condensate. STRAPS AND SCREWS (supplied) 19" (483) 31" (787) DETAIL *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit. 4" 3/ ) 14 375 ( WARNING All models except the RNC120D are designed for horizontal installation only as shown. Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. Using full length hanger straps is recommended for vibration control, but can be shorter if required. A minimum of 25" (635mm clearance is recommended so the door can be opened. WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency. 13 Suspending the RNC120D Horizontal Installation ATTENTION The unit must be mounted level for proper drainage of the condensate pans. JOIST FASTENERS (not supplied) STRAPS AND SCREWS (supplied) DETAIL Using full length hanger straps is recommended for vibration control, but can be shorter if required. Vertical Installation Wall Mounting the HRV "L" BRACKETS (not included) may be installed if wall mounting is desired for the vertical installation. Suspending the RNC120D The hanging straps should be attached to the unit at the top end corners (mounting screws are already located on the HRV case). Securely fasten the other end of the straps to the ceiling making sure the UNIT IS LEVEL. The straps are designed to reduce the possibility of noise, resonance or harmonics; therefore using the full length of the strap between the HRV and the floor joists is recommended. It is important to isolate the "L" BRACKET from the attached surface to minimize vibration. Use the hanging strap hardware to attache the brackets. Do not drill additional holes in the HRV. 14 Drain Connections Drain Connection (HRV Only) During a defrost cycle, the HRV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. "P" Trap (HRV only) DRAIN HOSE PLUMBING PRE-PUNCHED HOLES (2) DRAIN PAN CAUTION DRAIN PAN DRAIN SPOUT The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point or freeze protection must be provided. DRAIN SPOUT ZIP TIE TEE CONNECTOR 1/2 " I.D. DRAIN HOSE TO DRAIN The HRV cabinet has prepunched holes for the drain (see below). Insert the drain spout through the hole in the drain pan. Do not forget the “O ring” which seals each spout to the pan REMEMBER TO HAND TIGHTEN ONLY the washer and lock nut which hold the drain spout in place. HARD PIPE PLUMBING PRE-PUNCHED HOLES (2) DRAIN PAN Construct a P-Trap using the plastic tee connector. Cut two lengths of hose and connect each piece to an end of the “T” fitting, then connect the other ends to the two drain spouts. Position the “T” fitting to point upward and connect the drain line. Tape or fasten base to avoid any kinks. Pour a cup of water into the drain pan of the HRV after the drain connection is complete. This creates a water seal which will prevent odors from being drawn up the hose and into the fresh air supply of the HRV. DRAIN SPOUT DRAIN PAN 1/2" HARD PIPE TEE JOINT DRAIN SPOUT TO DRAIN Model RNC120D Drain Set-up for Vertical Installation CAUTION Drain trap and tubing MUST be below bottom of door with 1/4" per foot downwards slope away from unit. 1/2” I.D. condensate line Note: Secondary drain pan may be required to protect from condensate leakage. Do not remove cap from drain spout Use “T” between drain pans to create a “P Trap”. “P” trap must be at least 6” (152 mm) below unit. Drain Set-up for Horizontal Installation Do not remove these drain plugs Use drain spout provided in door. “P” trap must be at least 6” (152 mm) below unit. 15 1/2” I.D. condensate line Installation Methods The Three Methods of Installation The three methods of installation for the HRV system are the Simplified, Partially Dedicated and Fully Dedicated Installations. Refer to the installation illustrations in this manual. Air Duct Design and Installation A well designed and installed ducting system will allow the HRV to operate at its maximum efficiency. Always try to keep duct runs as short and straight as possible. See Installation Diagrams for various installation options. The inner and outer liners of the flexible insulated duct must be clamped to the sleeve of the weatherhoods (as close to the outside as possible) and the appropriate port on the HRV. It is very important that the fresh air intake line be given special attention to make sure it is well sealed. A good bead of high quality caulking (preferably silicone sealant) will seal the inner flexible duct to both the HRV port and the weatherhood prior to clamping with a large zip tie. To minimize air flow restriction, the flexible insulated duct that connects the two outside weatherhoods to the HRV should be stretched tightly and be as short as possible. Twisting or folding the duct will severely restrict air flow. Simplified Installations The Simplified Installation draws stale air from the cold air return duct of the air handler/furnace and introduces an equal amount of fresh air farther downstream into the cold air return. Refer to "The Simplified Installation" in this manual. The air handler/furnace blower must be running when the unit is operating for this system to be effective. Refer to "Interlocking HRV Operation to an Airhandler/Furnace Blower". Partially Dedicated Installations The Partially Dedicated Installation draws stale air from specific points in the house and introduces an equal amount of fresh air into the cold air return. Refer to "The Partially Dedicated Installation" in this manual. Stale air ducts should be installed where the worst air quality problems occur (bathroom, kitchen, and laundry room). Each location with a stale air duct should have a timer which will initiate high speed ventilation. Refer to "Optional Timers" in this manual. The air handler/furnace blower should be running when the HRV is operating to evenly distribute the fresh air throughout the house. Refer to "Interlocking HRV Operation to an "Airhandler/Furnace Blower". Installing the Ducting Between the HRV & Living Areas in the House To maximize airflow in the duct system, all ducts should be kept short and have as few bends or elbows as possible. Forty-five degree elbows are preferred to 90° elbows. Use “Y” tees instead of 90° elbows whenever possible. All duct joints must be fastened with screws, rivets or duct sealant and wrapped with mastic or a quality duct tape to prevent leakage. Mastic is preferred but if duct tape is used, we recommend aluminum foil duct tape. Galvanized ducting from the HRV to the living areas in the house is recommended whenever possible, although flexible duct can be used in moderation if necessary. To avoid possible noise transfer through the duct system, a short length (approximately 12 inches or 300mm) of non-metallic flexible insulated duct should be connected between the HRV and the supply/exhaust duct system. The main supply and return lines to/from the HRV must be 6 inches (150mm) minimum. Branch lines to the individual rooms may be as small as 4 inches (100mm), but 5 inch (125mm) lines are preferred . All ducts running through attics and unheated spaces must be sealed and insulated to code. Fully Dedicated Installations The Fully Dedicated Installation draws stale air from specific points in the house and introduces an equal amount of fresh air to specific locations of the house. This system is not connected to an air handler/furnace. Refer to "The Fully Dedicated Installation" in this manual. Stale air ducts should be installed where the worst air quality problems occur (bathroom, kitchen, and laundry room). Each location with a stale air duct should have a timer which will initiate high speed ventilation. Refer to "Optional Timers" in this manual. Fresh air ducts should be installed to all bedrooms and living areas, excluding bathrooms, kitchen and utility areas. Grilles should be located high on a wall or in ceiling locations. Grilles that diffuse the air comfortably such as the Round Diffuser are recommended. If the floor is the only option available, then special care should be taken in locating grilles. Areas such as under baseboard heaters will help to temper the air. Also, optional inline duct heaters are available for mounting in the supply duct work to add heat if required. WARNING Include a short length of fabric, flex duct or other non-metallic connector in the “Fresh Air to Building” hard ducted line in order to keep the HRV separately grounded (electrically) from the air handler. This will avoid a possible shock hazard to service people if a short to ground develops in one of the devices. Applications such as greenhouses, atriums, swimming pools, saunas, etc. have unique ventilation requirements which should be addressed with an isolated ventilation system. 16 The Simplified Installation (Return/Return Method) • It is mandatory that the furnace run continuously or HRV WARNING operation be interlocked with the furnace. • Check local codes/authority having jurisdiction for acceptance. HRV must be balanced. Refer to “Airflow Balancing” in this manual. FOUR PORT MODELS RETURN AIR DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN 40" (1m) MINIMUM 3' (1 m) min. recommended Outdoors Cool Air Return Forced Air Furnace NOTES: 1. Furnace blower is required to operate when ventilation from HRV is required. The furnace must be set to run continuously or interlocked with HRV. 2. A minimum separation of 40 inches (1 m) is required between the two direct connections. 3. The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air. 4. Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required. Eighteen inches (460 mm) above grade minimum. 5. Due to the differences in pressure between the HRV and the equipment it is being connected to, the HRV's airflow must be confirmed on site, using the balancing procedure found in the installation manual. *Unit is normally balanced on HIGH speed with air handler blower ON. FIVE PORT MODELS - Simplified Installation for Models RNC10/RNC20 Return Air Outdoors 40" (1m) MINIMUM 3' (1 m) min. recommended Stale Air To Outside Fresh Air From Outside Cool Air Return Fresh Air To House Stale Air From Building Field-supplied Balancing Damper (optional) WARNING Defrost air port needs to be drawn from clean area without combustion appliances. To avoid backdrafting of combustion products, never draw defrost air from a room with a naturally aspirated appliance, i.e. furnace, hot water heater, gas dryer, stove, fire place etc. High efficiency filter or electronic air cleaner Air Handler *Unit is normally balanced on HIGH speed with air handler blower ON. CAUTION Weatherhood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) clearance above grade or anticipated snow level. 17 The Partially Dedicated Installation • Stale air drawn from key areas of home WARNING (bathroom, kitchen, laundry) • Fresh air supplied to return air duct of air handler HRV must be balanced. Refer to “Airflow Balancing” in this manual. FOUR PORT MODELS DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN (Stale air drawn from key areas of home) EXHAUST AIR from various parts of home. i.e. bathrooms (if required), kitchens (if required). Return Air Outdoors 3' (1 m) min . recommended * Unit is normally balanced on HIGH speed with furnace blower ON. Cool Air Return NOTES: 1. Furnace blower is recommended to operate when HRV is on to provide good air distribution. 2. Weatherhood arrangement is for drawing purposes only. 6' (2 m) minimum separation required. 18" (460 mm) above grade minimum. 3. Due to the differences in pressure between the HRV and the equipment it is being connected to, the HRV's airflow must be confirmed on site, using the balancing procedure found in the installation manual. 4. The duct port configuration (Fresh Air from Outside, Stale Air to Outside, etc.) varies from model to model. Check specifications for the duct configuration on your model. Forced Air Furnace FIVE PORT MODELS - Partially Dedicated Installation for Models RNC10/RNC20 Outdoors Return Air Stale Air To Outside 3' (1 m) min . recommended Fresh Air From Outside Cool Air Return STALE AIR from various parts of home. i.e. bathrooms (if required), kitchens (if required). Field-supplied Balancing Damper (optional) WARNING Defrost air port needs to be drawn from clean area without combustion appliances. To avoid backdrafting of combustion products, never draw defrost air from a room with a naturally aspirated appliance, i.e. furnace, hot water heater, gas dryer, stove, fire place etc. High efficiency filter or electronic air cleaner Air Handler * Unit is normally balanced on HIGH speed with furnace blower ON. CAUTION Weatherhood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) clearance above grade or anticipated snow level. 18 The Fully Dedicated Installation • Stale air drawn from key areas of home WARNING (bathroom, kitchen, laundry) • Fresh air supplied to main living areas of house HRV must be balanced. Refer to “Airflow Balancing” in this manual. FOUR PORT MODELS - Models RNC155/RNC200 Stale Air from various parts of home. i.e. bathrooms (if required) kitchens (if required) Outdoors Fresh air to house main living areas... bedrooms, living room, rec. room etc. *Unit is normally balanced on HIGH speed with air handler blower ON. NOTES: 1. Weatherhood arrangement is for drawing purposes only. 6' (2m) minimum separation required. 18" (460mm) above grade minimum or above anticipated snow level . 2. The HRV air flow must be confirmed on site, using the balancing procedure found in the installation manual. FIVE PORT MODELS - Fully Dedicated Installation for Models RNC10/RNC20 Outdoors Stale Air To Outside * Unit is normally balanced on HIGH speed with furnace blower ON. Fresh Air From Outside Fresh air to house main living areas... bedrooms, living room, rec. room etc. STALE AIR from various parts of home. i.e. bathrooms (if required), kitchens (if required). Field-supplied Balancing Damper (optional) WARNING Defrost air port needs to be drawn from clean area without combustion appliances. To avoid backdrafting of combustion products, never draw defrost air from a room with a naturally aspirated appliance, i.e. furnace, hot water heater, gas dryer, stove, fire place etc. CAUTION Weatherhood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) clearance above grade or anticipated snow level. 19 Grilles and Weatherhoods Lifebreath Kitchen Grille Grilles REMOVABLE FILTER 6” x 10” Kitchen Grille Part No. 10-002 Replacement Grease Filter Part No. 10-002-2 Adjustable grilles should be used to balance the flow rates into and out of various rooms. Grilles or diffusers should be positioned high on the wall or in the ceiling. Kitchen exhaust grilles must never be connected to a range hood. They should be installed at least 4 feet (1.2m) horizontally away from the stove. This grille includes a removable grease filter. Canadian building codes require that kitchen grilles be equipped with washable filters. Lifebreath Techgrille Field-supplied balancing dampers should be installed external to the unit to balance the amount of stale air being exhausted with the amount of fresh air being brought into the house. Refer to Air flow Balancing section. 4" (100mm) Part No. 99-140 5" (125mm) Part No. 99-145 6" (150mm) Part No. 99-141 8" (200mm) Part No. 99-148 CAUTION Weatherhood Clearances Intake Weatherhood Requirements • Should be located upstream (if there are prevailing winds) from the exhaust outlet. OUTSIDE CORNER 36" (1m) recommended min. 36" (1m) recommended min. INSIDE CORNER • At least 6' (2m) from the exhaust weatherhood. • At least 6' (2m) away from dryer vents and air handler exhaust. • A minimum of 6' (2m) from driveways, oil fill pipes, gas meters, swimming pools or garbage containers. 6' (2m) recommended min. • At least 18" (460mm) above the ground, or above the depth of expected snow accumulation. EXHAUST INTAKE • At least 3' (1m) from the inside/outside corner of the building. 18" (460mm) min. 18" (460mm) min. • Do not locate in a garage, attic, or crawl space. Exhaust Weatherhood Requirements Lifebreath Weatherhoods • At least 6' (2m) from the ventilation air intake. 5" (125mm) Part No. 99-185 6" (150mm) Part No. 99-186 7" (200mm) Part No. 99-187 • At least 18" (460mm) above ground or above the depth of snow accumulation. • At lease 3' (1m) away from the corner of the building. Weatherhood Installation • At least 3' away from gas meter, electric meter or a walkway where fog or ice could create a hazard. COLLARISSUPPLIEDTO ENSUREVAPOURBARRIER IS100%SEALEDTO WALLPLATE SCREEN (sideview) • not into a garage, workshop or other unheated space. When installing the weatherhood, its outside perimeter must be sealed with exterior caulking. 12"galvanized pipesupplied Local codes may require greater distances. CAUTION 1/4"(6mm)SCREEN (frontview) EXTERIOR WALL 1. ThermalCollarslidesovergalvanized sleeveofWeatherhood. 2. FastenThermalCollartoBelt. 3. SlidetheInsulatedFlexibleDuctingover theWeatherhood'sgalvanizedsleeveand fastenittotheThermalCollar. 4. Hoodishingedtoallowforeasyaccess forcleaningofbirdscreen. Weatherhood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) clearance above the higher of the grade or anticipated snow level. 20 Electrical The HRV unit should be plugged into a standard designated (120VAC) electrical outlet with a ground. The outlet should be serviced by a separate 15 amp/120V circuit. An extension cord should not be used with this appliance. A qualified service technician should make any required electrical connections. WARNING In order to prevent electric shock when cleaning or servicing the HRV, it is extremely important to confirm the polarity of the power line that is switched by the safety (disconnect) switch. The hot line (black) is the proper line to be switched. To confirm the proper polarity, use a voltmeter or test lamp to ensure there is no power after the switch when the door is open. Check between that point and ground (on the cabinet). Always make sure that the HRV is properly grounded. Remote Control Connections Prior to connecting remote devices, it is advisable to run self test on the HRV/ERV. Low voltage connections between the remote controls, the dehumidistat, or the fan timer should be made by a qualified service technician. Low voltage wires from the remote controls are connected to the HRV micro-processor board. Changing OFF to STANDBY Figure 1 - Factory DIP Switch Settings Figure 2-DIP Switch Settings for Standby (When using a Remote Control Device that has an ON/OFF Switch) The factory setting of the DIP switches (located on the circuit board) provides continuous low speed ventilation. Optional Remote Controls will initiate high speed ventilation. This DIP Switch Setting can be adjusted when using a system control that has an ON/OFF switch (refer to "Remote Control Devices" in this manual). "STANDBY" is achieved when the Remote Control Switch is in the "OFF" position. The Dehumidistat and Timers will initiate high speed ventilation regardless of the "ON/OFF" switch position when this DIP switch configuration is used. Remote controls with an ON/OFF switch (refer to "Remote Control Devices" in this manual) will shut the entire system down when the remote control is in the OFF position. Changing the remote control from OFF to STANDBY can be achieved by Setting the DIP Switch as per Figure 2. Figure 1 - Factory setting for OFF Figure 2 - Contractor adjusted setting for STANDBY ON ON ATTENTION HS REMOTE DFR2 DFR3 Figure 2 may not meet building code conformance in certain geographical areas. Check with your local building authority. HS REMOTE DFR2 DFR3 Increasing Low Speed to Medium Low the autotransformer inside the electrical box. Whether or not this change is made, the HRV will only be able to access a single selected low speed. The ventilator automatically operates on its lowest speed when plugged in or switched on. This setting is factory supplied from an autotransformer with two selectable low speeds. To switch to a continuous medium low speed, an installing contractor must interchange the red and blue wires from High speed is available with the use of optional remote controls connected to the appropriate terminals inside the electrical box. 21 Wiring the Controls Dehumidistat Ventilation Control 2040 ON/OFF Dehumidistat Part No. 99-116 Part No. 99-2040 Red to Red Orange to Orange Black to Black Remove factory installed jumper when installing this control DEHUMIDISTAT Red to Red Remove factory installed jumper when installing this control Orange to Orange Black to Black Low Fan to Blue Circuit Board Terminal Strip Circuit Board Terminal Strip Remote Dehumidistat Recirculation Control Part No. 99-130W Part No. 99-RECIRC Red to Red Factory installed jumper Black to Black Red to Red Remove factory installed jumper when installing this control Orange to Orange Black to Black Recirculate to Blue Circuit Board Terminal Strip Circuit Board Terminal Strip 20 Minute Timer Crank Timer (shown in a Decora cover plate)* Part No. 99-101 Red to Red Factory installed jumper Black to Black Red to Red Factory installed jumper Black to Black Off 10 20 Green LED Drive to Green 30 60 50 Circuit Board Terminal Strip Circuit Board Terminal Strip * The Decora cover plate (Part No. 99-107W) is a standard switch plate. Digital Electronic Timer (DET) Part No. 99-104 ATTENTION Red to Red Factory installed jumper Controls will use 2, 3 or 4 lead 20 gauge wire. Note the number of leads required for each control (refer to the above illustrations). Green Ground to Green Comms to Yellow Circuit Board Terminal Strip 22 40 Defrost Operation Recirculating Damper Defrost (4 port models) The recirculating damper defrost HRV has an electronically controlled damper defrost mechanism. The defrost timer is activated when the outside temperature drops below 27°F (3°C). A motor driven damper door mechanism closes off the supply air from outside allowing the exhaust air to recirculate through the unit. After the defrost period, the damper operates in the opposite direction to reopen the fresh air port. Defrost cycle repeats until the temperature again rises above 27°F (-3°C). STALE AIR FROM INSIDE FRESH AIR FROM OUTSIDE FILTERS RECIRCULATING DEFROST DAMPER BLOWERS CORE MOTOR STALE AIR TO OUTSIDE Damper Defrost (5 port models) The damper defrost HRV has a fifth port for defrost. An electronically controlled damper defrost mechanism activates the defrost timer when the outside temperature drops below 27°F (-3°C). A motor driven damper door mechanism closes off the supply air from outside allowing room air to enter through the fifth port of the unit. After the defrost period, the damper operates in the opposite direction to reopen the fresh air port. Defrost cycle repeats until the temperature again rises above 27°F (-3°C). FRESH AIR TO INSIDE FRESH AIR FROM OUTSIDE DEFROST DAMPER STALE AIR TO OUTSIDE DEFROST PORT BLOWERS FILTERS FRESH AIR TO INSIDE STALE AIR FROM INSIDE Defrost Cycle DIP Switch Settings - Increasing the Run Time Defrost DIP Switch Settings (located on the circuit board) can be adjusted to increase the unit’s run (ventilation) time. The three minute defrost time cannot change. Factory Setting 3 minute defrost time 17 minute run time CAUTION Lengthening the run time may result in ice buildup on the core. Option 1* 3 minute defrost time 25 minute run time ON Option 2* 3 minute defrost time 30 minute run time ON ON HS HS HS REMOTE REMOTE REMOTE DFR2 DFR2 DFR2 DFR3 DFR3 OFF SW1 ON SW1 OFF DFR3 ON SW1 *Lengthening the run time may result in ice build-up on the core. 23 Air Flow Balancing The first step is to operate all mechanical systems on high speed, which have an influence on the ventilation system, i.e. the HRV itself and the air handler, if applicable. This will provide the maximum pressure that the HRV will need to overcome, and allow for a more accurate balance of the unit. It is necessary to have balanced air flow in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flow is not properly balanced, then: • The HRV may not operate at its maximum efficiency • A negative or positive air pressure may occur in the house Drill a small hole in the duct (about 3/16"), three feet downstream of any elbows or bends, and one foot upstream of any elbows or bends. These are recommended distances but the actual installation may limit the amount of straight duct. • The unit may not defrost properly • Failure to balance HRV properly may void warranty The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0.25 in. (0-62 Pa) of water, preferably to 3 digits of resolution. The tube coming out of the end of the Pitot is connected to the high pressure side of the gauge. The tube coming out of the branch of the Pitot is connected to the low pressure or reference side of the gauge. CAUTION Ensure balanced air flow in HRV. Excessive positive pressure may drive moist indoor air into the external walls of the building where it may condense (in cold weather) and degrade structural components. May also cause key holes to freeze up. Insert the Pitot tube into the duct; pointing the tip into the air flow. For general balancing it is sufficient to move the Pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other (supply or return) duct. Determine which duct has the highest air flow (highest reading on the gauge). Then damper that air flow back to match the lower reading from the other duct. The flow should now be balanced. Excessive negative pressure may have several undesirable effects. In some geographic locations, soil gases such as methane and radon gas may be drawn into the home through basement/ground contact areas. Read the Application Warning in Clearances & Requirements section of this manual! Actual air flow can be determined from the gauge reading. The value read on the gauge is called the velocity pressure. The Pitot tube comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will be in either feet per minute or meters per second. To determine the actual air flow, the velocity is multiplied by the cross sectional area of the duct being measured. WARNING Ensure balanced air flow in HRV/ERV. Excessive negative pressure may also cause the backdrafting of vented combustion equipment. This is an example for determining the air flow in a 6" duct. The Pitot tube reading was 0.025 inches of water. Prior to balancing, ensure that: From the chart, this is 640 feet per minute. 1. All sealing of the duct system has been completed. The 6" duct has a cross sectional area of 2. All of the HRV’s components are in place and functioning properly. = [3.14 x (6"÷12)2]÷4 = 0.2 square feet 3. Balancing dampers are fully open. The air flow is then: 4. Unit is on HIGH speed. 640 ft./min. x 0.2 square feet = 128 cfm 5. Air flow in branch lines to specific areas of the house should be adjusted first prior to balancing the unit. A smoke pencil used at the grilles is a good indicator of each branch line's relative air flow. For your convenience, the cross sectional area of some common round duct is listed below: DUCT DIAM. (inches) 6. After taking readings of both the stale air to the HRV duct and fresh air to the house duct, the duct with the lower CFM ([L/s] velocity) reading should be left alone, while the duct with the higher reading should be dampered back to match the lower reading. 5 6 7 CROSS SECTION AREA (sq. ft.) 0.14 0.20 0.27 The accuracy of the air flow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature supplied with the Pitot tube. 7. Return unit to appropriate fan speed for normal operation 8. A field-supplied balancing damper for the stale air side is required for system balancing. Balancing Procedure The following is a method of field balancing an HRV using a Pitot tube, which is advantageous in situations when flow stations are not installed in the duct system. Procedure should be performed with the HRV on high speed. 24 Air Flow Balancing Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit Part No. 99-167 1 - magnehelic gauge 1 - Pitot Tube and hose 1 - Carry Case DUCT AIR FLOW ATTENTION Pitot tube Apply use of balancing dampers as required. Magnehelic gauge High Pressure Side LIC MAGNEHE NOTE Graphic is for illustrative purposes only. Duct connection ports may vary. Low Pressure Side Placement of Pitot Tube HRV Place pitot tube a minimum of 18" from blower or elbows Outdoors Pitot tube Magnehelic gauge MAGNEHELIC Note: Duct connections may vary, depending on model. Pitot tube Magnehelic gauge Additional dampers may be required MAGNEHELIC Balancing Collar Instructions Often the “Fresh Air to House” ducting will have the heaviest air flow which must be dampered down. A Balancing Damper is located in the “Fresh Air to House” collar. The Balancing Collar feature is not available on all models. Hard/Rigid ducting Insulated flexible ducting Push and turn with slotted screwdriver. Damper automatically locks when pressure is released. Installations where the HRV is ducted directly to the return of a furnace may require additional dampening on the fresh air to building duct. This is due to the high return static pressures found in some furnace installations. 25 1/2” When connecting ductwork to the collar, take note where screws are located. Screws should be located no further than 1/2” from outside edge of collar, so as not to impede operation of the damper. Air Flow Balancing using AccuFlow Gauge Part No. 99-170 Models RNC155 and RNC200 Only AccuFlow Gauge Kit 1 - Accu-Flow Balancing Gauge 2 - Connection Hoses 4 - Rubber Fittings 1 - Instruction Page Lifebreath Accu-Flow is designed to quickly and accurately balance the airflows on units equipped with balancing ports. Normally the HRV/ERV would be balanced on high speed. If the HRV/ERV is connected to a forced air system, both systems should be set to run at the highest operational speed when balancing is performed. Procedure: Step 1 Remove balancing port covers. Step 2 Insert rubber fittings into balancing ports on door. (Use light pressure until fitting is snug). Step 3 Attach tubes to balancing gauge. Step 4 Place gauge on metal door (gauge is equipped with a magnetic strip). Ensure gauge is level/plumb. Step 5 Connect tubes to door ports as illustrated in step 5 (record readings). Step 6 Connect tubes to door ports as illustrated in Step 6. (record readings). Fresh Air Stale Air Step 6 Measuring Fresh Air Side (Always connect left side port first). Measuring Stale Air Side (Always connect left side port first). 0 0 10 10 20 20 30 30 40 40 70 70 60 60 70 70 80 80 90 90 10 0 10 0 Step 5 Note: It is normal practice to lightly tap gauge if reading is non-responsive. Step 7 Damper airflows as required. Step 8 Repeat Steps 5 and 6 as required to confirm airflows 26 Air Flow Balancing using the Door Ports Models RNC155 and RNC200 Only The door ports ( MODELS RNC155 & RNC 200) are designed to quickly and measure the airflows for balancing. Magnehelic Door Port Balancing Kit Normally the HRV would be balanced on high speed. If the HRV is connected to a forced air system, both systems should be set to run at the highest operational speed when balancing is performed. Use the Magnehelic Gauge Kit (Part No. 99-206) for door port balancing. Part No. 99-206 1 - Pressure Gauge 2 - Connection Hoses Balancing Procedure Step 1 Remove balancing port covers. Step 2 Insert one end of each connection hose into a rubber fitting. (Use light pressure until fitting is snug). Step 3 Attach the connection hoses to pressure gauge Step 4 Fresh Air - Connect hoses to door ports as illustrated (record reading). Step 5 Stale Air - Connect hoses to door ports as illustrated (record reading). Step 6 Refer to the Airflow Reference Chart for the conversion of gauge reading to airflow reading. Step 7 Damper the airflows as required to balance the system. The fresh airflow must equal the stale airflow. Step 8 Repeat steps 4 to 7 as required to confirm airflows. Airflow Reference Chart Fresh Air Step 4 Measuring Fresh Air Side (Connect to both ports at the same time). Pressure Gauge ELIC MAGNEH Stale Air Step 5 Measuring Stale Air Side (Connect to both ports at the same time). ELIC MAGNEH 4 - Rubber Fittings 1 - Instruction Page Pressure Gauge Pressure Gauge Reading Fresh Air Stream Flow Stale Air Stream Flow (in w.g.) (cfm) (cfm) 0.070 0.080 0.090 0.100 0.110 0.120 0.130 0.140 0.150 0.160 0.170 0.180 0.190 0.200 0.210 0.220 0.230 0.240 0.250 0.260 0.270 0.280 0.290 0.300 0.310 0.320 0.330 0.340 75 80 84 89 93 98 102 106 111 115 120 124 128 133 137 142 146 151 155 159 164 168 173 177 181 186 190 195 54 59 65 70 75 81 86 91 97 102 114 118 123 128 133 138 143 148 153 158 163 167 172 177 182 187 192 197 Door port balancing is only available for Models RNC155 and RNC200. 27 Interlocking HRV Operation to an Airhandler/Furnace Blower When using the Interface relay contacts to initiate blower operation on a furnace, certain thermostats will initiate the outdoor cooling condenser when R and G are closed. Use this wiring configuration to prevent the Interface relay contacts from initializing the condenser unit. This problem can occur at the thermostat because the Y terminal is connected to the G terminal internal to the stat. When R and G are closed at the furnace (by dehumidistat or relay) 24 Volts is sent to G at thermostat. 24 Volts is then sent through Y which will initiate outdoor condenser. Wire Connector 28 Wiring Diagrams Model RNC5-TPD RED BLUE TO MOTORS INTERFACE RELAY CONTACTS DEFROST DETAILS Model RNC5 (Only) PCB PLUG - IN 1 2 P1 PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MOTOR BLACK BLACK ORANGE ORANGE RED RED 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SPARE 29 RNC120D HRV Control Box TO MOTORS BLUE Wiring Diagrams INTERFACE RELAY CONTACTS DEFROST DETAILS PCB PLUG - IN 1 2 P1 PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MOTOR BLACK BLACK ORANGE ORANGE RED RED 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SPARE 60-120D-WIRING 30 Wiring Diagrams RNC95/RNC10/RNC20/RNC155/RNC200 RNC3WIRINGDIAGRAM LEGEND HIGHVOLTAGE 12VLOWVOLTAGE AUTO TRANSFORMER 120V POWER SUPPLY RED BLACK BLUE WHITE WHITE FANMOTORDETAILS INTERFACE RELAYCONTACTS BLACK FIELDINSTALLED 12VLOWVOLTAGE TO MOTOR BLACK T6 T9 GREEN GREEN AUTOTRANS ORANGE YELLOW CAPACITOR T2 ITE WH D RE T3 T4 T5 T6 SPARE NEUTRAL T7 LINE T8 T9 FAN O/P N/C COMMON N/O T10 T11 T12 8 K4 T1 C4 SEE DEFROST DETAIL C5 GROUND P1 VDR2 DIRECTMOUNTEDCAPACITOR VDR3 K1 ModelRNC5(Only) PCBPLUG-IN 1 3/4AMPFUSE DEFROSTDETAILS BLACK ORANGE ORANGE RED BLACK DEHUMIDISTAT - + C1 2 BI-DIRECTIONAL DAMPERMOTOR 3 GREEN LEDDRIVE 4 BLUE P3 THERMISTOR RECIRCULATE CR1 LOWFAN ON 12VAC P4 PIN1-RED PIN2-ORANGE PIN3-BLACK PIN4-SPARE RED +12V ORANGE OBCS VDR1 P1 BLACK K3 FACTORY INSTALLED JUMPER PLUGIN CONNECTOR RED K2 RED GREEN GROUND HS REMOTE DFR2 DFR3 P2 DEHUMIDISTAT NONFUNCTIONAL FUTURE USE TERMINALS COMMS 1 P5 SW1 PCBPLUG-IN 1 2 P1 PLUGIN CONNECTOR BI-DIRECTIONAL DAMPERMOTOR BLACK BLACK ORANGE ORANGE RED RED 3 4 INTERNAL DEHUMIDISTAT (IFAPPLICABLE) PIN1-BLACK PIN2-ORANGE PIN3-RED PIN4-SPARE 98-RNC3-001 INSHRV 0104 31 Troubleshooting Symptom Cause Solution Poor Air Flow • • • • • • • • • • clean exterior hoods or vents • remove and clean filter • remove and clean core • check and open grilles • open and adjust dampers • have electrician check supply voltage at house • check duct installation • increase the speed of the HRV • have contractor balance HRV Supply air feels cold • poor location of supply grilles, the air flow may irritate the occupant 1/4” (6mm) mesh on the outside hoods is plugged filters plugged core obstructed house grilles closed or blocked dampers are closed if installed poor power supply at site duct is restricting HRV improper speed control setting HRV air flow improperly balanced • outdoor temperature extremely cold • locate the grilles high on the walls or under the baseboards, install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant (eg. over a sofa) • turn down the HRV supply speed. A small duct heater (1kw) could be used to temper the supply air • placement of furniture or closed doors is restricting the movement of air in the home • if supply air is ducted into air handler return, the air handler fan may need to run continuously to distribute ventilation air comfortably Dehumidistat is not Operating • improper connection to ventilator • external low voltage is shortened out by a staple or nail • check dehumidistat setting it may be on OFF • check that the correct terminals have been used • check external wiring for a short • set the dehumidistat at the desired setting Humidity Levels are too High in Winter Condensation is appearing on the windows • dehumidistat is set too high .• lifestyle of the occupants • HRV is set at too low a speed • set dehumidistat lower • avoid hanging clothes to dry, storing wood and venting clothes dryer inside. Heating wood may have to be moved outside • vent crawl space and place a vapor barrier on the floor of the crawl space • ducts from the washroom/bathroom should be sized to remove moist air as effectively as possible, use of a washroom/bathroom fan for short periods will remove additional moisture • timer or fan can be added to washroom/bathroom exhaust • on humid days, as the seasons change, some condensation may appear but the home’s air quality will remain high with some HRV use • increase speed of the HRV • • • • • • • • • moisture coming into the home from an unvented or unheated crawl space • moisture is remaining in the washroom/bathroom and kitchen areas • condensation seems to form in the spring and fall Humidity Levels are too Low dehumidistat control set too low blower speed of HRV is too high lifestyle of occupants HRV air flow may be improperly balanced HRV and / or Ducts Frosting up • HRV air flow is improperly balanced • malfunction of the HRV defrost system set dehumidistat higher decrease HRV blower speed humidity may have to be added through the use of humidifiers have a contractor balance HRV air flow • Note: minimal frost build-up is expected on cores before unit initiates defrost cycle functions • have HVAC contractor balance the HRV • ensure working properly. Condensation or Ice Build Up in Insulated Duct to the Outside • incomplete vapor barrier around insulated duct • a hole or tear in outer duct covering • tape and seal all joints • tape any holes or tears made in the outer duct covering • ensure that the vapor barrier is completely sealed Water in the bottom of the HRV • • • • • • ensure O-Ring on drain nozzle sits properly • look for kinks in line • check water drain connections • make sure water drains properly from pan 20 Minute Timer Not Working • Wiring • Faulty control • Faulty circuit board drain pans plugged improper connection of HRV drain lines HRV is not level drain lines are obstructed HRV heat exchange core is not properly installed • disconnect external controls and run unit through self test. If the unit runs through self test successfully, then the circuit board is okay. • check wiring connection. • make sure wires are connected to proper terminals. • test 20 Minute Timer, press and hold the button for 10 seconds then release. The unit should run on high speed and then return to normal operation when the button is released. 32 Maintenance HRV 1. Inspect Exterior Hoods at least once a month. 4. Motors - Maintenance Free 5. Drain (condensate) Line - Clean Once a Year Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen). Inspect drain line, drain spout and “P” trap for blockage, mold or kinks. Flush with warm soapy water and replace if worn, bent or unable to clean. WARNING: Blockage of hoods may cause an imbalance. 6. Clean Duct System if Required 2. Clean Air Filters - Twice a Year The standard filters equipped with your HRV are removable and washable. The duct system running to and from the HRV may accumulate dirt. Wipe and vacuum the duct once every year. You may wish to contact a Heating/Ventilation company to do this. a) simply open access door and slide core out 7. General Maintenance - Twice a Year b) remove filter clips Wipe down the inside of the cabinet with a damp cloth to remove dirt, bugs and debris that may be present. c) once clips are removed filters can be taken off the core to be rinsed with water or a combination of mild soap and water. Do not clean in the dishwasher 8. Cleaning the Fans e) slide core back into its original position Fans may accumulate dirt causing an imbalance and/or excessive vibration of the HRV. A reduction in the air flow may also occur. In new construction this may result within the first year due to heavy dust and may occur periodically after that over time depending on the outdoor conditions. 3. Clean Core - Twice a Year • unplug the HRV and open the service door a) open access door • remove the core b) carefully grip ends of core and pull evenly outward. -core may be snug, but will slide out of the channel c) once removed from the cabinet remove filters • remove ducting (metal and/or flexible insulated type) from the red and/or blue ports which are connected immediately inline with the fan assembly d) wash core in warm soapy water (do not use dishwasher) • use a small brush, such as a toothbrush or pipe cleaner, and insert first d) to re-assemble, place clean filter(s) (wet or dry) back into their positions against the core and return clips to their original position e) install the clean filters (a) through the large opening of the fan assembly and then f) install clean core (b) through the smaller opening in the end of the fan assembly • scrub individual fan blades until clean. Avoid moving or damaging balancing flat weight, clip is usually found on one or more of the fan blades Note: Core installation label on the outer end of the core. To install the clean core: a) first mount the bottom flange of the core guide into the bottom H channel approximately 1/4” (6mm) • vacuum and wipe b) mount the left or right side flange of the core guide approximately 1/4” (6mm) followed by the other side • reassemble making sure ducting is reattached firmly and insulation and moisture barrier are sealed and taped c) mount the top flange of the core guide into the top H channel approximately 1/4” (6mm) Before attempting this task, thought should be given to having a qualified service technician complete the service work. d) with all four corners in place and the core straight and even, push hard in the center of the core until the core stops on the back of the cabinet NOTE: Core will appear to stick out from cabinet approximately 1/8” (3mm). This is designed this way so that the access door will fit tight against the core. 33 34 35 36
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Page Count : 36 XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:387b6c2f-4161-479f-9ffc-4317d7b57e3c Producer : Acrobat Distiller 6.0.1 (Windows) Create Date : 2008:01:22 11:49:49-05:00 Modify Date : 2008:01:22 11:49:49-05:00 Document ID : uuid:92a97d7e-0110-412e-9dc0-eb2946460111 Format : application/pdf Title : untitledEXIF Metadata provided by EXIF.tools