Boiler Manual And Installation Instructions for Atmospheric Venting LINEAR 6-12 SECTION BIASI B/40 PAGE 1 Please Read Instructions Carefully Save for Future Reference WARNING If the information in this manual is not followed exactly, a fire explosion may result causing property damage, personal injury or loss of life. DANGER LINEAR BOILER WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance • Do not touch any electric switch; do not use any phone in your building • Immediately call your gas supplier from another location. Follow the gas supplier’s instructions. • If you can not reach your gas supplier call the fire department Manufactured by: Biasi S.p.A. Verona, Italy Distributed By: QHT QUINCY HYDRONIC TECHNOLOGY TECHNOLOGY, NOLOGY, INC. 3560 LAFAYETTE RD PORTSMOUTH, NH 03801 03801 PHONE: 603603-334334-6400 FAX: 603603-334334-6401 REV. H PAGE 2 BIASI B/40 Dear Customer: Thank you for buying a Linear commercial boiler. The Linear is a cast iron, oil or gas fired hot water boiler, using the famous 3-pass design. The boiler is simple, rugged and engineered for maximum heating efficiency. We realize that it is not possible to answer all questions about the Linear series boiler in this manual. Reading this installation manual does not make the reader an expert in all aspects of installation and operation, and does not replace the need for a qualified, licensed heating contractor. We urge you to contact your installing contractor or distributor if you are in question about any aspect of your boiler's performance. Our main concern is that you are satisfied with your boiler and its performance. We require that your contractor complete efficiency tests using instruments. The controls and accessories listed in this manual are intended to serve as guidelines rather than specific recommendations. We realize that other makes and models of such devices are available and can be used as successfully as those we specify. The installing contractor is the best judge of a system's specific requirements, as well as the local availability of certain makes and models of controls and accessories. The preceding does not apply, however, to the equipment that comes with every boiler, such as the overheat control (L4006E) and pressure relief valve. The installation of the specific devices supplied with every boiler is absolutely necessary to the safe operation of the boiler and protection of the heating system. This Linear boiler has a limited warranty, a copy of which is provided with the boiler. Please be sure to return the warranty registration card as the warranty will be void without your boiler's serial numbers, date of installation and the name of your installer being on record in our files. Thank you for purchasing our B-40 Linear series boiler. If you have questions or comments, please don't hesitate to contact us immediately. Our goal is 100% customer satisfaction. PAGE 3 BIASI B/40 TABLE OF CONTENTS BIASI B-40 Linear Series Section Page Important Information 1 4 General Information 2 6 Codes and Regulations 3 6 Combustion Air Supply 4 7 Boiler Location 5 7 Boiler Block Assembly 6 8 Boiler Trim Kit Installation 7 8 Boiler Tapping Diagram - 9 Burner Set-up 8 10 Gas Piping 9 12 Breeching and Chimney 10 14 Piping 11 15 Boiler Jacket Assembly 12 17 Boiler Jacket Explosion Diagram - 18 Wiring B-40 Control Panel Wiring 13 19 20-23 Commissioning 14 24 Maintenance 15 24 Installer Notes 16 25 BIASI B/40 PAGE 4 IMPORTANT INFORMATION Please read this page carefully. ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE AND LOCAL PLUMBING, HEATING AND ELECTRICAL CODES AND ORDINANCES, AS WELL AS THE REGULATIONS OF THE SERVING ELECTRICAL, WATER AND GAS UTILITIES. All systems should be designed by competent contractors, and only persons knowledgeable in the layout and installation of heating systems should attempt the installation of any boiler. It is the responsibility of the installing contractor to see that all controls are correctly installed and operating properly when the installation is completed. Do not burn volatile garbage, gasoline, naphtha or other flammable liquids other than No. 2 fuel oil. All flammable liquids (especially gasoline), chemicals, rags, paper, wood scraps, debris, etc., should be kept away from the boiler at all times. Keep the boiler area clean and free of all fire hazards. Please read the literature and warranties supplied by the manufacturers of the various accessory equipment. This equipment is warranted by the respective manufacturers, not by Quincy Hydronic Technologies, Inc. Each piece of equipment must be installed and used according to the recommendations of the manufacturer. This Linear boiler has a limited lifetime warranty, a copy of which is printed on the back page of this manual. PAGE 5 BIASI B/40 WARNING Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon monoxide (CO). Carbon Monoxide (CO) is a gas which is odorless, colorless and tasteless but is very toxic. If your BIASI B-40 boiler is not working properly, or is not vented properly, dangerous levels of CO may accumulate. CO is lighter than air and thus may travel throughout the building. BRIEF EXPOSURE TO HIGH CONCENTRATIONS OF CO, OR PROLONGED EXPOSURE TO LESSER AMOUNTS OF CO MAY RESULT IN CARBON MONOXIDE POISONING. EXPOSURE CAN BE FATAL AND EXPOSURE TO HIGH CONCENTRATIONS MAY RESULT IN THE SUDDEN ONSET OF SYMPTOMS INCLUDING UNCONSCIOUSNESS. Symptoms of CO poisoning include the following: Dizziness Vision problems Shortness of breath Headache Loss of muscle control Unclear thinking Nausea Weakness Unconsciousness The symptoms of CO poisoning are often confused with those of influenza, and the highest incidence of poisoning occurs at the onset of cold weather or during flu season. A victim may not experience any symptoms , only one symptom, or a few symptoms. Suspect the presence of carbon monoxide if symptoms tend to disappear when you leave your home. The following signs may indicate the presence of carbon monoxide: * Hot gasses from appliance, venting system, pipes or chimney, escaping into the living space. * Flames coming out around the appliance. * Yellow colored flames in the appliance. * Stale or smelly air. * The presence of soot or carbon in or around the appliance. * Very high unexplained humidity inside the building. If any of the symptoms of CO occur, or if any of the signs of carbon monoxide are present, VACATE THE PREMISES IMMEDIATELY AND CONTACT A QUALIFIED HEATING SERVICE COMPANY OR THE GAS COMPANY AND THE FIRE DEPARTMENT. To reduce the risk of CO poisoning, have your heating system "tuned up" by a licensed heating contractor or the gas company - preferably before each heating season. Also have the service company check your chimney or vent pipes for blockage. The building should be adequately ventilated, particularly if you have tightly insulated your home. ONLY QUALIFIED, LICENSED SERVICE CONTRACTORS SHOULD PERFORM WORK ON YOUR BIASI B-40 BOILER. BIASI B/40 PAGE 6 2. General Information: The Linear series are wet base design, sectional, cast-iron boilers for forced hot water heating systems. The Linear boilers are designed for firing with oil and deliver high efficiencies through unique design and construction. The Linear series boilers are shipped from the factory in assembled blocks and each boiler can range from 6 to 12 sections. The sections can then be disassembled before delivery to the jobsite by QHT and then field assembled. The boiler jacket, burner and controls are packed separately for shipping. Note: All equipment should be inspected upon delivery, and any damage or shortage should be reported immediately. Boiler Input Model Number of Heating Oil Number Sections Capacity G.P.H. B40/6 B40/7 B40/8 B40/9 B40/10 B40/11 6 7 8 9 10 11 265 352 437 524 610 696 783 2.20 2.90 3.60 4.30 5.00 5.70 B40/12 12 6.40 Maximum Water Working Pressure 72 psi Water Input Content Length Gas Net Output MBH Efficiency % Gals. (L) inches MBH 308 406 504 602 700 798 896 230 305 380 456 532 607 684 86.0 86.7 86.8 87.0 87.2 87.2 17 20 23 26 28 31 Weight (LBS) 34.8 39.5 44.4 49.2 53.9 58.8 902 1023 1144 1265 1386 1507 87.4 34 63.8 Maximum Relief Valve is 50 psi @ 900 MBH 1628 3. Conforming to Codes and Regulations: Installation of the boiler, burner, oil tank and related equipment must conform to national, state and local regulating agencies and codes applicable to the installation of the equipment. In the absence of local requirements, the following codes apply: • • • ANSI/NFPA - #31 Installation of Oil Burning Equipment ANSI/NFPA - #70 National Electric Code ANSI/NFPA - #211 Chimneys and Vents The above codes are available from: National Fire Protection Association (NFPA) Battery March Park Quincy, Massachusetts, 02269 PAGE 7 BIASI B/40 4. Combustion Air Supply: The boiler location must provide air for proper combustion and ventilation of the surrounding area. To burn efficiently, oil requires 30 CFM/GAL. In general, boiler rooms should incorporate two (2) permanent air supply openings, one commencing within 12 inches of the ceiling, and one commencing within 12 inches of the floor. These openings should freely communicate with the outdoors. OUTSIDE AIR: When combustion air is supplied directly through an outside door or wall, each opening shall have a free area of one square inch per 4,000 BTUH input for the total input of all the appliances in the enclosure. INSIDE AIR: When combustion air is supplied from inside the building, each opening shall have a free area of one square inch per 1,000 BTUH input for the total of all appliances in the enclosure. In no case shall the openings be less than 105 square inches each. In both cases, check manufacturers ratings for louver net free area, and correct for screen resistance to net free area. If the boiler is to be installed where the operation of exhaust fans, attic fans, kitchen ventilation systems, clothes dryers or fireplaces may create severe negative vent pressures causing unsatisfactory combustion and venting, special provisions should be made for additional make-up air to supply the other air requirements. If building is of tight construction, combustion air requirements may not be met and combustion air ducts from outside may be necessary. Please refer to NFPA No. 31. Do not install the boiler until the proper combustion air has been arranged 5. Boiler Location: Locate the boiler to provide sufficient clearance for inspection, servicing and maintenance. Minimum clearance to construction or combustible materials shouldn't be less than six (6) inches from the top, sides and rear of unit, and eighteen (18) inches from the flue pipe in any direction. Front clearance should be at least twenty four (24) inches. When choosing a location for the boiler, take into consideration the 12” supply manifold on the back of the boiler. Adequate space must be given to pipe the manifold in and for the smoke pipe to clear the manifold. Greater distances for ease of access should supersede fire protection clearances. The boiler must be located on a non-combustible floor. A smooth, level concrete floor is recommended. Locate the boiler as close as possible to the chimney. If boiler is installed on combustible flooring, consult local authorities for proper method of covering floor. The boiler must not be installed on carpeting. Caution: Do not store or use flammable materials, chemicals or flammable liquids, especially gasoline, in the vicinity of this heating appliance. BIASI B/40 PAGE 8 6. Boiler Block Assembly: All Linear series boilers are shipped either as an assembled boiler block or a knock-down boiler block. If the block came unassembled, or if the assembled block needs to be split for installation purposes, please read the following: To assemble split blocks, move the sections into a line facing each other. Sections may be slid along boards placed underneath the sections. Inspect nipple ports for damage or burrs. Remove any burrs by brushing the port very lightly. Wipe the push nipples and nipple ports with a clean cloth. Apply a film of nipple compound to both the nipple and port. Install the nipple in the port and then seal it by hitting it with a rubber mallet. Apply section sealant to one section only and slide sections together. If the boiler came in sections, you will want to draw the sections together 2 or three at a time to insure that the blocks are coming together properly. Install the four draw rods and draw the sections together evenly (measure with yardstick). The longer draw rods should be installed on the top of the boiler. The shorter draw rods are installed on the bottom of the boiler. The bottom draw rods should not extend past the front section. Draw the sections together until sections make iron-to-iron contact at a point around the top and bottom ports of each section. Check to insure that the combustion chamber is sealed using a flash light or other lighting device. Place the flashlight into the combustion chamber and look for light on the floor or surrounding walls (this is best done in a dark room). If light appears out of the boiler use a high temperature caulk to fill in the gaps between the block sections. DO NOT OVER TIGHTEN DRAW RODS 7. Installation of Boiler Trim Components: The BIASI B-40 Boiler Trim Kit includes the following components. 1— Honeywell L4006 E Aquastat 1— 3/4” X 3” Nipple 1— 3/4” Elbow 1— 50 PSI Pressure Relief Valve 1— Immersion Well 1— Four Wire Molex Wire Harness 1— Pressure/Temperature Gauge 1— 3/4” Boiler Drain 1— 1/4”X3/4” Bushing 1— 2 1/2” MPT Supply Manifold 1— 2 1/2” MPT Return Manifold The above mechanical components should be installed following the diagram of the boiler tappings on the following page. The installation of the above wiring components (wiring harness) will be described in the wiring portion of this installation manual. PAGE 9 BIASI B/40 Control Panel with operating aquastats 2.5” MPT Supply 8” Breech 2.5” MPT Return Figure 1:Diagram illustrating the location and function of the front and rear boiler tappings. Boiler Model B-40/6 B-40/7 B-40/8 B-40/9 B-4/10 B-4/11 B-4/12 Length (L) 34.8” 39.5” 44.5" 49.2" 53.9" 58.8" 63.9" BIASI B/40 PAGE 10 8. Burner Setup: The following information applies only to the BIASI B-40 series boilers at a maximum output for power venters or lined chimneys only. BURNER MANUFACTURER Boiler Model B-406 P2-KA Burner Model 2.2 GPH Firing Rate FULL Insertion Depth 2.00 X 45 Nozzle solid Spray Pattern 140 psi Pump Pressure 12 Head Position 11.50 Air Setting B-407 P2-K 2.8 GPH FULL 2.25 X 60 solid 170 psi 16 15.00 B-408 P2-K 3.5 GPH FULL 2.75 X 60 solid 175 psi 18 18.00 BURNER MANUFACTURER Boiler Model B-406 F-10 Burner Model 2.4 GPH Firing Rate 4.5" Insertion Depth 2.00X60 Nozzle B Spray Pattern 145 PSI Pump Pressure 3.75 Turbulator 5 Air Gate B-407 F-10 2.6 GPH 4.5" 2.00X60 B 175 PSI 4.5 6 Riello B-408 F-15 3.3 GPH 4.5" 2.50X60 B 175 PSI 1.8 3 B-409 F-15 4.0 GPH 4.5" 3.00X60 B 175 PSI 2.1 4 Beckett B-407 B-408 CF 375 CF 500 2.7 GPH 3.2 GPH 4.5" 4.5" 2.00X45 2.75X45 hollow solid 180 psi 140 psi BURNER MANUFACTURER Boiler Model B-407 Burner Model CF 375 2.1 GPH Firing Rate 4.5" Insertion Depth 1.75X60 Nozzle ES Spray Pattern 140 psi Pump Pressure Head Type 0 Head Position 9/0 Air Setting 2 3/1 3 7/0 Heatwise B-409 B-410 DE-10 DE-10 4.25 GPH 5.0 GPH FULL FULL 3.25 X 60 3.75 X 60 solid solid 175 psi 175 psi 1 1.5 3.5 4.5 B-411 DE-10 5.7 GPH FULL 4.5 X 45 solid 160 psi 2 5.5 B-412 DE-10 6.4 GPH FULL 5.50 X 45 solid 140 psi 2.5 6.75 B-410 F-15 4.6 GPH 4.5" 3.50X60 B 175 PSI 2.8 5.5 B-411 F-20 5.3 GPH 4.5" 4.0X60 B 175 PSI 3.1 4 B-412 F-20 5.9 GPH 4.5" 4.5X60 B 175 PSI 5 6 B-409 CF 500 3.7 GPH 4.5" 2.75X45 solid 180 psi B-410 CF 800 4.3 GPH 4.5" 3.25X45 solid 175 psi B-411 CF 800 4.8 GPH 4.5" 4.0X30 solid 145 psi B-412 CF 800 5.3 GPH 4.5" 4.0X30 solid 180 psi 4.5 10/0 3 7/0 3 8/0 4.5 10/2 Good, reliable operation with a minimum of service starts with attention to the small details: 1. Setting the nozzle position and electrodes "by the book" using the manufacturer's gauges. 2. Installing a quality micron filter at the burner. 3. Making careful/tight flare connections without couplings on oil suction line. 4. Checking fuel pump pressure. 5. Checking draft at the breeching to insure it is adequate to overcome flue gas resistance. 6. Setting the air band properly with well maintained instruments. A good target is 11% to 12.5% of (CO2) or 6.5% to 3.8% of (O2). Note: Oil and Gas burners on B40-series boilers cannot be properly commissioned without instruments and gauges. PAGE 11 BIASI B/40 8. Burner Setup: The following information applies only to the BIASI B-40 series boilers at a maximum output for power venters or lined chimneys only. BURNER MANUFACTURER Boiler Model B-406 SU-3 Burner Model Natural Fuel 315 Input 1" Min. Gas Inlet Size 1.95" Manifold in w.c. 9.5 Air 6 Head B-407 SU-3 Natural 420 1" 3" 14 11 B-408 SU-4 Natural 499 1" 3.5" 21 20 BURNER MANUFACTURER Boiler Model B-406 SU-3 Burner Model Propane Fuel 315 Input 3/4" Min. Gas Inlet Size 1.65" Manifold in w.c. 7.25 Air 6 Head B-407 SU-3 Propane 420 3/4" 2.4" 15 10 B-408 SU-4 Propane 527 1" 2.75" 21.5 18 Heat Wise B-409 SU-5 Natural 577 1" 2" 7.5 2" B-410 SU-5 Natural 672 1" 2.8" 9 2" Heat Wise B-409 B-410 SU-5 SU-5 Propane Propane 634 740 1" 1" 2" 2" B-411 SU-6 Natural 847 1" 1.16" 4.25 2-5/8" B-412 SU-6 Natural 954 1-1/4" 1.4" 5 2-5/8" B-411 SU-6 Propane 847 1" 1" 5.2 2-5/8" B-412 SU-6 Propane 954 1" 1.27" 5.8 2-5/8" Good, reliable operation with a minimum of service starts with attention to the small details: 1. Setting the electrode and flame rod settings against manufacturer's specs to insure proper operation. 2. Installing properly sized gas piping according to BTU input required and length of gas line run. 3. Making sure there is proper manifold pressure before and after the gas valve using a calibrated manometer. 4. Checking draft at the breeching to insure it is adequate to overcome flue gas resistance. 5. Setting the air band properly with well maintained instruments. A good target is 9.5% to 10.5% of (CO2) or 5% to 2.5% of (O2) for natural gas, or 10% to 12% of (CO2) or 5% to 2.5% of (O2) for lp gas Note: Oil and Gas burners on B40-series boilers cannot be properly commissioned To determine how much gas is coming into the burner, or to set the gas meter correctly, the following formula can be used. Ft3/hr = [3600/(sec. Per rev.)]*(Size of gas meter) The chart to the right can be used to determine the flow rate depending upon the time per revolution and the size of the gas meter dial. Seconds per Revolution 20 25 30 35 40 45 50 55 60 without instruments and gauges. 0.5 90 72 60 51 45 40 36 33 30 Size of Gas Meter Dial (Cubic Foot) 1 2 180 360 144 288 120 240 103 206 90 180 80 160 72 144 65 131 60 120 BIASI B/40 PAGE 12 9. Gas Line Piping Gas supply piping is to be sized and installed properly in order to provide a supply of gas sufficient to meet the maximum demand without undue loss of pressure between the meter and the boiler. It is advisable to run a separate gas line from the meter to the gas burner to avoid pressure drops. Consult with the National Fuel Gas Code ANSI Z223.1 for proper sizing of gas piping for various lengths and diameters. Locate a drop pipe adjacent to, but not in front of the boiler. Locate a tee in the drop pipe at the same elevation as the gas inlet connection to the boiler. Extend the drop line with a nipple towards the floor and cap to form a sediment trap. Install a tee handle shut off valve before the tee with sediment trap and a union after the tee before the combination gas valve. When installing the boiler, Use black steel pipe and malleable fittings (do not use cast iron parts) with a suitable pipe dope which is resistant to liquefied petroleum gases. Check piping for leaks. Always check leaks with a water and soap solution. DO NOT USE A FLAME FOR CHECKING GAS LEAKS The boiler and its individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that piping at test pressures in excess of 1/2 psi. INSTALLATION OF SEDIMENT TRAP AND BURNER SUPPLY To check for gas leaks, use a gas detector or apply a soap solution to the joints. DO NOT USE AN Direction of flow Manual Shutoff Valve Height of shutoff valve above ground level to conform to local codes, Pressure Gauge Port (1/8” NPT plugged) Minimum 1” X 1” X 1” Tee 3” MINIMUM Male Union 1” NPT Burner Gas Pipe Cap BIASI B/40 PAGE 13 INSTALLATION OF SEDIMENT TRAP AND BURNER SUPPLY Piping should consist of: 1. A shut off valve approximately 6’ away from the unit. 2. A 1/8” plugged NPT tapping for gas pressure measurement preferably on the manual shut-off valve (as shown or anywhere between the gas valve and the shut off value). Note: The manual shut off valve and tapping are NOT part of the SU-4 Gas Burner. Please make sure you conform to local and state codes. 3. A gas union. 4. A drip pipe. Caution: The gas valve should not be subjected to more than ½” PSIG. Therefore, the burner should be isolated during high-pressure gas leak tests. The appliance and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psig. The appliance must be isolated from the gas supply piping by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig. BIASI B/40 PAGE 14 10. Breeching and Venting: The B-40 Linear boiler is a high efficiency unit that requires proper venting. The boiler must be vented to the outdoors by means of a tile lined masonry or an approved pre-fabricated chimney of the size and height recommended by the manufacturer or by a listed "power venting" unit which provides draft by mechanical venting . The chimney discharge opening must be located at least 24 inches above any part of the building structure within 10 feet of the chimney. Be sure the chimney and smoke pipe don't become obstructed by squirrels, bird nests, soot buildup, chimney liner deterioration, etc. The "power ventor" system should be installed on the leeward side of the building. Very specific requirements must be met concerning clearances from combustibles and distances from doors and windows. Please consult with manufacturer of "power ventor" for this information. In any case, the "ventor" must be installed by a licensed burner mechanic and done in accordance with local codes. The B-40 boiler is a very low stack temperature boiler (between 320 and 400F gross stack temp.) so caution should be used when connecting to an outside built chimney. Should you have concern that the flue gases could condense, then you should consider using a listed, "power venting" unit. If "power venting" is used to discharge flue gases, then the power vent unit should be equipped with a postpurge control as well as delay-off, timing control to prevent problems with fogging and nozzle post drip. Note: 88% steady state efficiency is achieved when flue gas contains over 12.5% CO2 and the gross stack temp. is below 350F. The smoke-pipe connection from the boiler to the chimney should be as short as possible, with a minimum number of elbows. The vent pipe must have a vertical rise of at least 1/4 inch per foot of horizontal run. The vent pipe must be of the same diameter as the flue outlet on the boiler. The chimney connector should have a minimum thickness of 24 gauge, corrosion resistant (galvanized) steel, assembled with a minimum of three (3) sheet-metal screws, and sealed with high temperature silicon at each joint. In most cases a barometric draft control isn't recommended as the B-40 is designed to be pressure-fired. However, one may be needed if the boiler is being used in a high draft situation. PAGE 15 BIASI B/40 10. Blocked Flue Switch: 1. Pierce a 5/8” hole into the vent pipe near the appliance outlet. Remove one of the securing nuts from the pipe of the safety switch. Tighten the other securing nut onto the pipe as far as possible. 2. Insert the threaded pipe end into the pierced hole, then install the securing nut, then install the securing nut, which was removed in step 1, and tighten securely. 3. Please consult the wiring section of this manual for the wiring of the blocked flue switch. 11. Piping: All piping must conform to state and local codes. The supply and return manifolds for B-40 Linear boilers are 2 1/2” male NPT. Be sure to provide unions and gate valves at the manifold inlet and outlet of the boiler, so the boiler may be readily isolated for service. Install the provided pressure relief valve so the discharge is piped directly to a drain, if possible. If not, the discharge should be piped to the floor. In either case, the discharge pipe should be of the same diameter as the outlet of the relief valve, with no valves or obstructions to impede overflow from the boiler. The installation locations on the manifold for the Pressure Relief Valve, the Temperature/Pressure Gauge as well the Honeywell L4006E Aquastat can be seen on the following page. Install manual and/or automatic air venting devices at the high points in the system to eliminate trapped air. The weight of all piping should be supported by suitable hangars and floor stands, not by the boiler. It is recommended that the make-up water line have a backflow preventer and a pressurereducing valve to reduce line pressure to 10 to 15 psi installed adjacent to the boiler. NOTE: If the heating system is to be filled with antifreeze, use only formulations expressly made for hydronic heating systems (such as propylene glycol). Do not use automotive types of antifreeze (ethylene glycol). Use of antifreeze will alter system output and characteristics. Consult factory rep's for details or assistance. Clearance for hot water pipes are 1 inch to combustibles. PAGE 16 BIASI B/40 PAGE 17 BIASI B/40 12. Boiler Jacket Assembly: NOTE: All piping, boiler controls, gauges and valves must be installed before the jacket has been assembled on the boiler. Refer to the following page to clarify these boiler jacket assembly instructions. Insert the separate piece of insulation (# 92) on top of boiler so the entire top and sides of boiler are covered. Use plastic strapping to secure the insulation in place. Mount the panel installation bracket (#82) onto the draw-rods on the upper front of the boiler. Install the six spacers (#86) onto the draw-rods. Two on the upper draw rods in the front and the remaining spacers onto the draw-rods in the back of the boiler. Install the rear insulation (#101) onto the boiler. Place the side panels (#66,52) onto the boiler making sure the draw rod spacers are between the side panels and the boiler casting. Tighten the sides of the casing to the panel installation bracket (#82) using sheet metal screws. Screw two studs (#90) into the bottom front of the boiler and screw on the threaded hex spacers (#87) onto the studs. Attach the lower mounting bracket (#83) to the boiler by using two bolts (#89) and screwing them into the threaded hex spacers. Then using sheet metal screws, attach the lower mounting bracket to the sides of the casing. Slide the control panel (#110) onto the casing from the top and secure it to the control panel support (#82) using sheet metal screws. Attach the rear panels (#84,85) using sheet metal screws. Place the top panel (#76) onto the sides of the casing and assure that the pins on the sides are aligned with the retaining holes on the top casing panel. Finally attach the front panel (#81) onto the casing by aligning the retaining pins with the retaining holes. Push to insure a positive connection. Boiler Components & Parts Vega B40 - Series Boiler Jacket Assembly: Description Part# 84,85 — Rear Jacket Panels*1 92,101— Insulation 52 — Right Jacket Panel 66 — Left Jacket Panel 83 — Front Jacket Supports 110 — Control Panel 82 — Control Panel Support 76 — Top Jacket Panel 81 — Front Jacket Panel*2 *1 *2 Rear insulation not attached, but included with the casing Front insulation attached to the casing 101 76 BIASI B/40 PAGE 18 13. Wiring: The electricity to the boiler shall come from a dedicated breaker in the electric service box. A service switch should be mounted on the side of the boiler so the burner man can service the burner and controls. The electrical wiring should be routed so as not to interfere with normal servicing of the boiler. Wiring done in the field between devices not attached to boiler shall conform with the temperature limitations for type T wire (63F/35C) or other specified wire as applicable when installed in accordance to manufacturer's instructions and wiring diagrams. Please refer to the wiring section of this manual for instructions on wiring the supplied control panel. 1 3 2 6 7 5 4 8 1 On/Off Switch 2 Min. Boiler Temp. Thermostat 3 Max Boiler Temp. Thermostat 4 Thermostat By-Pass Button 5 Circulator Switch 6 Boiler On/Off Signal Lamp 7 Temperature Gauge 8 Manual Reset High Limit 9 Burner Lock Out Signal Lamp 9 * NOTE: If the thermostat test button is closed, the thermostats will be bypassed and the burner will not shutoff until the boiler reaches the manual high limit. PAGE 19 BIASI B/40 CONTROL PANEL DESCRIPTION 1. 2. 3. 4. 5. 6. 7. 8. 9. On/Off Switch — Turns power to control panel on and off and will disable power to the burner assuming the panel is wired correctly. Minimum Boiler Temperature Thermostat — Maintains a minimum boiler temperature between 50 degrees F and 170 degrees F. Maximum Boiler Temperature Thermostat — High limit temperature setting for boiler between 50 degrees F and 205 degrees F. Thermostat Test Button — This button jumps out both thermostats allowing a technician to easily start the burner for testing if there is no call for heat. Warning, with both thermostats disabled the only high limit left will be the manual high limit. Circulator Switch - Supplies power to boiler circulator or relay panel. It is not suggested to use this switch and it is not utilized in any of the suggested wiring diagrams in this manual. Boiler On/Off Signal Lamp — Signal lamp to indicate whether main power switch is turned on or off. Temperature Gauge - Temperature gauge which takes temperature reading from top front of boiler. Manual Reset High Limit - Safety high limit that is set to 214 degrees F. If the manual high limit is tripped, use a flat head screw driver to protective cap on reset button. Then depress reset button making sure that it stays depressed once you have removed your finger. Once the switch is reset replace the protective cover. Burner Lock Out Signal Lamp - Lamp to indicate if the burner has gone out on lockout. 1 6 3 2 7 5 4 8 9 BIASI B/40 PAGE 20 B-40 Control Panel Wiring Diagram for Beckett/Heat Wise Oil Burner 24V BURNER CONTROL CIRCULATOR RELAY B-40 Control Panel Wiring Diagram for Beckett/Heat Wise Oil Burner Line Voltage BIASI B/40 PAGE 21 CIRCULATOR RELAY BURNER CONTROL BIASI B/40 PAGE 22 B-40 Control Panel Wiring Diagram for Riello Oil Burner B-40 Control Panel Wiring Diagram for Heat Wise Gas Burners BIASI B/40 PAGE 23 CIRCULATOR RELAY Burner Primary Control BIASI B/40 PAGE 24 14. Commissioning: After installation of oil/gas-fired boiler, operation and performance tests shall be conducted to make certain that the burner is operating in an acceptable manner and that all safety controls and devices function properly. It is critical that the high limit, low water cutoff and burner "cad cell" relay be checked for normal operation before leaving the job. Refer to the back page of this manual to write down the System Checkout information. 15. Maintenance: Check for fouling or soot buildup in the combustion chamber at least every twelve (12) months. Caution: Black carbon soot in the combustion chamber can, under certain conditions, be ignited by a spark or open flame. To prevent this unlikely occurrence, dampen the soot deposits with a wet brush or a fine water spray before servicing or cleaning the combustion chamber. Fouling or carbon soot buildup on the surfaces in the combustion chamber is caused by incomplete combustion, and is a sign of combustion air and/or venting problems. As soon as any fouling is observed, the cause of the fouling should be corrected and the combustion chamber should be cleaned as follows: Disconnect the electrical power supply to the boiler, burner and controls. Close Fire-O-Matic thermal shutoff valve at burner prior to servicing. Remove the front jacket panel (#9) and the loosen the two (2) front boiler door nuts. Swing the boiler door open. Be careful not to damage the door stud threads or the flexible oil line. Brush and vacuum combustion chamber and flue passages until all deposits are removed. Reassemble components in reverse order, making sure any damaged gaskets are repaired or replaced. Other maintenance requirements are as follows: Inspect wiring and controls for damage. Insure controls are operating correctly. Inspect oil or gas supply lines for damage, corrosion or leaks. Repair any leaks immediately. Inspect, clean or replace oil filter as specified by manufacturer. Inspect vent and fill pipes for any obstruction, damage or corrosion. Clean or replace as necessary. Lubricate the burner motor if necessary during service. Finally, consult burner manual for specific burner maintenance instructions. PAGE 25 BIASI B/40 16. Installer Notes System Checkout: Boiler Model No._________________ Serial No.__________ Original Purchaser: _________________________ Installer: ______________________ _________________________ ______________________ _________________________ ______________________ Burner Manufacturer----------- Type of Oil Burner------------- Burner Model No.-------------- Burner Serial No.-------------- Nozzle Manufacturer------------- Nozzle Spray Angle------------ G.P.H. -------------------- Type ----------------------- Burner Performance Tests: GROSS STACK TEMPERATURE -------------------- ROOM TEMPERATURE (AMBIENT) ------------------NET STACK TEMPERATURE --------------------CO2 ----------------O2---------------SMOKE READING ---------------COMBUSTION EFFICIENCY---------------------COMMENTS PAGE 26 BIASI B/40 BIASI B/40 PAGE 27 BIASI B/40 PAGE 28 Warranty For BIASI B40 Series Commercial Cast-Iron Water Boilers FIRST YEAR through TENTH YEAR-WARRANTY FOR B40 SERIES COMMERCIAL HOT WATER BOILERS: QHT warrants that its cast-iron boiler and casing are free from defects in material and workmanship for ten years from the date of installation at the original installation site to the original owner. If the boiler is found to be defective within this period, QHT will replace the boiler block or casing. ELEVENTH YEAR and BEYOND -WARRANTY FOR THE CAST IRON BOILER SECTIONS OF THE B40 SERIES COMMERCIAL BOILERS: Biasi warrants that the cast-iron sections of the BIASI B40 boilers are free from defects in material and workmanship for the life of the original installation to the original owner. If the B40 boiler section is then found to be defective, QHT and Biasi will replace the defective section of the cast iron boiler block. This warranty is subject to the condition that a heating contractor whose principal occupation is the sale and installation of heating equipment must have installed the boiler. In addition, the boiler must be installed in accordance with the boiler manual supplied by QHT Inc with every boiler. PARTS, WHICH ARE COVERED, consists of all materials supplied by Biasi. Other parts supplied in the trim kit or in the burner pack carry their own warranty and each manufacturer has responsibility for its own products. NOTE: ANY PART, WHICH IS REPLACED UNDER WARRANTY, CARRIES ONLY THE UNEXPIRED PORTION OF THE ORIGINAL WARRANTY. OWNER RESPONSIBILITIES: 1. Provide for proper installation, which includes pressure relief and pressure reducing valves and high limit safety controls on closed systems. 2. Provide qualified periodic service to prolong proper operation and service. 3. Insure that boiler is installed with approved burner and that installation conforms to all codes and ordinances. 4. This warranty does not apply to boilers, which are subject to misuse, abuse, neglect, alteration, accident, excessive temperature, excessive pressure, or corrosive water or atmosphere. 5. Owner will be responsible for return of faulty components to Portsmouth, NH, freight pre-paid. QHT AND BIASI WILL NOT BE RESPONSIBLE FOR: 1. Components that are part of the heating system, but were not manufactured by Biasi or QHT as part of the commercial boiler system. 2. The workmanship of the installers of Biasi B40 Linear boilers. Furthermore, this warranty does not assume any liability for unsatisfactory performance caused by improper installation. 3. Any costs for labor to remove or replace the faulty component. 4. Improper burner application or adjustments, control settings, care or maintenance. 5. Any damage associated with corrosion or leakage due to the use of "non-barrier", plastic pipe in the heating system. *THIS WARRANTY DOES NOT EXTEND TO ANYONE EXCEPT THE FIRST PURCHASER AT RETAIL AND ONLY WHEN THE BOILER IS IN THE ORIGINAL INSTALLATION SITE. *IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THE EXPRESSED WARRANTY. BIASI AND QHT EXPRESSLY DISCLAIM AND EXCLUDE ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY HAVE OTHER RIGHTS THAT VARY FROM STATE TO STATE. For prompt warranty service, notify the installer, who, in turn, will notify the distributor from whom he purchased the boiler. If this does not result in corrective action, contact Biasi through Quincy Hydronic Technology (Address Below) with details in support of the warranty claim. All claims must be processed through proper trade channels. Contact with Biasi directly is not recommended for rapid claim settlement. Quincy Hydronic Technology, 3560 Lafayette Rd Portsmouth, NH, 03801 Tel. (603) 334-6400 ITEM #: B40 REV. H
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Page Count : 28 XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : 6f3cfaa1-ff60-11dd-0000-9b892c22b2ed Producer : Bullzip PDF Printer / www.bullzip.com / Freeware Edition \(not registered\) Modify Date : 2009:02:17 10:09:13-05:00 Create Date : 2009:02:17 10:09:13-05:00 Creator Tool : PScript5.dll Version 5.2.2 Document ID : 6f3cfaa1-ff60-11dd-0000-9b892c22b2ed Format : application/pdf Title : () Creator : Keith Hnatow Author : Keith HnatowEXIF Metadata provided by EXIF.tools