Lochinvar Power Fin 1002 Users Manual PBX PFX USER Rev B.qxp
1002 to the manual ec733567-2cc3-48f9-8264-cc23fef3f4f3
2015-02-09
: Lochinvar Lochinvar-Power-Fin-1002-Users-Manual-575692 lochinvar-power-fin-1002-users-manual-575692 lochinvar pdf
Open the PDF directly: View PDF .
Page Count: 16
Download | |
Open PDF In Browser | View PDF |
User Manual Models: 502, 752, 1002, 1302, 1501, 1701, and 2001 Up To 5:1 Turndown WARNING If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. • If you cannot reach your gas supplier, call the fire department. • Installation and service must be performed by a qualified installer, service agency, or the gas supplier. Save this manual for future reference. User’s Information Manual Contents Hazard definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Please read before proceeding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1. Maintenance schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Maintenance procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2. Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3. SMART SYSTEM control module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Access modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Saving parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Parameter table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Viewable and changeable control parameters . . . . . . . . . . . . . . . . . . . . . . 11 Status display screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Revision Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Back Cover Hazard definitions The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product. DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or CAUTION moderate injury. CAUTION CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage. NOTICE NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage. 2 User’s Information Manual Please read before proceeding NOTICE This is a gas appliance and should be installed by a licensed electrician and/or certified gas supplier. Service must be performed by a qualified service installer, service agency or the gas supplier. WARNING If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death. This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors. What to do if you smell gas – • Do not try to light any appliance. • Do not touch any electric switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbors phone. Follow the gas supplier’s instructions. • If you cannot reach your gas supplier, call the fire department. installation, adjustment, WARNING Improper alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or additional information, consult a qualified installer, service agency or the gas supplier. Checking equipment – Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the appliance which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on the packing slip with those actually received. In case there is damage or a shortage, immediately notify the carrier. Do not use this appliance if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced. Owner warning – The information contained in this manual is intended for use by qualified professional installers, service technicians, or gas suppliers. Consult your local expert for proper installation or service procedures. NOTICE Installation and service must be performed by a qualified installer, service agency, or the gas supplier. Warranty – Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated. Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems. 1. 2. Excessive water hardness causing a lime/scale build-up in the copper tube is not the fault of the equipment and is not covered under the manufacturer’s warranty (see Water Treatment and Water Chemistry in the Power-fin Installation and Operation Manual). Excessive pitting and erosion on the inside of the copper tube may be caused by too much water velocity through the tubes and is not covered by the manufacturer’s warranty (see Boiler Flow Rates and Temperature Rise for flow requirements in the Power-fin Installation and Operation Manual). Consult and follow all local Building and Fire Regulations and other Safety Codes that apply to this installation. Consult a local gas utility company to authorize and inspect all gas and flue connections. Your conventionally vented gas appliance must have a supply of fresh air circulating around it during burner operation for proper gas combustion and proper venting. WARNING Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, turn off the manual gas control valve to the appliance at a location external to the appliance. Prevention of freezing – Heat exchangers and headers damaged by freezing are not covered by warranty. See Section 7, Startup - Freeze Protection in the Power-fin Installation and Operation for more information. 3 User’s Information Manual Please read before proceeding WARNING To minimize the possibility of serious personal injury, fire, or damage to your appliance, never violate the following safety rules: 1. Boilers and water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the appliance or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the appliance and vent-air intake components. 2. Never cover your appliance, lean anything against it, store trash or debris near it, stand on it or in any way block the flow of fresh air to your appliance. 3. UNDER NO CIRCUMSTANCES must flammable materials such as gasoline or paint thinner be used or stored in the vicinity of this appliance, vent-air intake system or any location from which fumes could reach the appliance or vent-air intake system. 4 Codes – The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1. All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where required by the authority having jurisdiction, the installation must comply with the Canadian Gas Association Code, CAN/CGA-B149.1 and/or B149.2 and/or local codes. This appliance meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI standards for gasfired units, ANSI Z21.13. User’s Information Manual 1 Maintenance schedule Service technician Owner maintenance (see the Power-fin Service Manual for instructions) (see the following pages for instructions) General: • Check appliance area • Address reported problems • Inspect interior; clean and vacuum if necessary; • Check pressure/temperature gauge Daily • Inspect condensate system and flush with fresh water • Check for leaks (water, gas, flue, condensate) ANNUAL START-UP • Examine venting system • Check system water pressure/system piping/expansion tank • Check vent piping • Check control settings Monthly • Check igniter • Check wiring and connections • Check air piping • Check relief valve • Check flue gas passageways • Check condensate drain system • Flame inspection (stable, uniform) • Inspect and clean the burner • Check manifold gas pressure • Clean the heat exchanger if flue temperature is more than 54°F (12.2°C) above return water temperature. • Perform start-up checkout and performance verification per Section 7 in the Power-fin Installation and Operation Manual. Periodically • Test low water cutoff (if used) • Reset button (low water cutoff) Every 6 months • Check appliance piping (gas and water) for leaks • Operate relief valve If combustion indicate need: or performance • Clean heat exchanger • Remove and clean compressed air only • Clean the blower wheel WARNING burner using End of season months • Shut appliance down (unless boiler used for domestic hot water) Follow the maintenance procedures given throughout this manual. Failure to perform the service and maintenance or follow the directions in this manual could result in damage to the appliance or system, resulting in severe personal injury, death, or substantial property damage. 5 User’s Information Manual 1 Maintenance schedule Maintenance procedures Appliance must be serviced and maintained WARNING NOTICE The appliance must be inspected and started annually at the beginning of the heating season by a qualified service technician. In addition, the maintenance and care of the pool heater designated on page 5 of this manual and explained on pages 6 and 7 must be performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the appliance and system could result in equipment failure, causing possible severe personal injury, death, or substantial property damage. The following information provides detailed instructions for completing the maintenance items listed in the maintenance schedule on page 5. In addition to this maintenance, the appliance must be serviced and started up at the beginning of each heating season by a qualified service technician. Check vent piping 1. WARNING Failure to inspect the vent system as noted above and have it repaired by a qualified service technician can result in vent system failure, causing severe personal injury or death. Check pressure/temperature gauge 1. Make sure the pressure reading on the boiler pressure/ temperature gauge does not exceed 24 PSI. Higher pressure may indicate a problem with the expansion tank. 2. Contact a qualified service technician if problem persists. Check vent piping 1. Check appliance area WARNING To prevent potential of severe personal injury, death, or substantial property damage, eliminate all materials discussed below from the boiler/water heater vicinity and the vicinity of the boiler/water heater combustion air inlet. If contaminants are found: Remove products immediately from the area. If they have been there for an extended period, call a qualified service technician to inspect the appliance for possible damage from acid corrosion. If products cannot be removed, immediately call a qualified service technician to re-pipe vent and air piping and locate vent termination/air intake away from contaminated areas. 1. Combustible/flammable materials -- Do not store combustible materials, gasoline or any other flammable vapors or liquids near the appliance. Remove immediately if found. 2. Air contaminants -- Products containing chlorine or fluorine, if allowed to contaminate the appliance intake air, will cause acidic condensate in the appliance. This will cause significant damage to the appliance if allowed to continue. 6 Visually inspect the flue gas vent piping for any signs of blockage, leakage, or deterioration of the piping. Notify your qualified service technician at once if you find any problems. Visually inspect the flue gas vent piping for any signs of blockage, leakage, or deterioration of the piping. Notify your qualified service technician at once if you find any problems. WARNING Failure to inspect the vent system as noted above and have it repaired by a qualified service technician can result in vent system failure, causing severe personal injury or death. Check air piping 1. Visually inspect the air inlet elbow to be sure it is unobstructed. Inspect the entire length of air piping to ensure piping is intact and all joints are properly sealed. 2. Call your qualified service technician if you notice any problems. Check relief valve 1. Inspect the appliance relief valve and the relief valve discharge pipe for signs of weeping or leakage. 2. If the relief valve often weeps, immediately contact your qualified service technician to inspect the appliance and system. User’s Information Manual 1 Maintenance schedule (continued) Inspect condensate system WARNING 1. Inspect the condensate drain line, condensate PVC fittings, and condensate trap on an annual basis. Flush condensate trap with water 3. Have leaks fixed at once by a qualified service technician. Failure to comply could result in severe personal injury, death, or substantial property damage. Replace the front access door. 1. Remove the four (4) screws securing the top cover to the condensate trap and remove the cover (reference FIG. 1-1). Operate relief valve 2. Locate the plastic ball inside the float tube. Verify there is nothing under the ball causing it to not seat properly. 1. 3. If necessary, flush with fresh water until the water begins to pour out of the drain. WARNING 4. Replace the top cover on the condensate trap. 5. Replace the four (4) screws removed in Step 1. Figure 1-1_Condensate Trap If the system is equipped with a low water cutoff, test the low water cutoff periodically during the heating season, following the low water cutoff manufacturer’s instructions. Read the boiler pressure/temperature gauge to make sure the system is pressurized. Lift the relief valve top lever slightly, allowing water to relieve through the valve and discharge piping. 3. If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the seat again to attempt to clean the valve seat. If the valve continues to weep afterwards, contact your qualified service technician to inspect the valve and system. 4. If water does not flow from the valve when you lift the lever completely, the valve or discharge line may be blocked. Immediately shut down the appliance, following the operating instructions on page 8 of this manual. Call your qualified service technician to inspect the appliance and system. Reset button (low water cutoff) 1. Testing the low water cutoff shuts the unit off. Press the RESET button on the low water cutoff bracket to turn the unit back on. Check appliance piping (gas and water) 1. 2. Remove the appliance front access door and perform a gas leak inspection per steps 1 through 7 of the Operating Instructions on page 8. If gas odor or leak is detected, immediately shut down the appliance following the procedures on page 8. Call a qualified service technician. Visually inspect for leaks around water piping. Also inspect the circulators, relief valve, and fittings. Immediately call a qualified service technician to repair any leaks. To avoid water damage or scalding due to valve operation, a metal discharge line must be connected to the relief valve outlet and run to a safe place of disposal. This discharge line must be installed by a qualified heating installer or service technician in accordance with the instructions in the Power-fin Installation and Operation Manual. The discharge line must be terminated so as to eliminate possibility of severe burns or property damage should the valve discharge. 2. Test low water cutoff (if installed) 1. Before proceeding, verify that the relief valve outlet has been piped to a safe place of discharge, avoiding any possibility of scalding from hot water. Shut appliance down (unless boiler is used for Domestic Water) 1. Follow “To Turn Off Gas to Appliance” on page 8 of this manual. 2. Do not drain the system unless exposure to freezing temperatures will occur. 3. Do not drain the system if it is filled with an antifreeze solution. 4. DO NOT shut down appliances used for domestic water heating, they must operate year-round. 7 User’s Information Manual 2 Operating instructions 8 User’s Information Manual 3 SMART SYSTEM control module Power-fin control module Use the control panel (FIG. 3-1) to set temperatures, operating conditions, and monitor appliance operation. Figure 3-1_ Control Panel Access modes User The user can adjust the space heating target temperature and the tank target temperature (if a tank sensor is used) by using the UP and DOWN buttons (FIG. 3-1) at any time during normal operation. By entering the USER code (0704), the user can also change temperature units, time and date, and night setback settings. In User Mode, the following parameters can be viewed but not changed: • Boiler outlet water target temperature in DHW Mode • Appliance model number • Software version • Total operating hours • Total cycles Installer Most parameters are available only to the installer, accessible only by entering the installer access code, see the Power-fin Service Manual. Saving parameters (reference the Parameter Table in the Power-fin Service Manual) To save parameters and exit programming: Press the ENTER/RESET button, then the MENU/EXIT button 3 times. To keep parameter settings only for a current operating cycle: Press the MENU/EXIT button 3 times after making all desired parameter changes. To enter a programming: parameter and continue Press the MENU/EXIT button 1 time to return to the parameter listings; press again to return to the menu listings. Remember to press the ENTER/RESET button when finished programming in order to save the changes made. See the Power-fin Service Manual for a detailed description of parameters and access modes. 9 User’s Information Manual 3 SMART SYSTEM control module Parameter table Table 3A_This table lists SMART SYSTEM control module parameters and where to access them GENERAL MENU OUTDOOR AIR RESET DHW SETTINGS DATA LOGGING TEMPERATURE SETTING A B C E SUB ITEM DESCRIPTION USER ACCESS SEE PAGE DISPLAY INSTALLER ACCESS MODIFY DISPLAY MODIFY 1 Heater Model 11 Yes No Yes No 2 User Code 11 Yes Yes Yes Yes 3 Date and Time 11 Yes Yes Yes Yes 4 Software Version 11 Yes No Yes No 5 Temperature Units 11 Yes Yes Yes Yes 6 Night Setback Temperature 11 Yes Yes Yes Yes 7 Night Setback Times 11 Yes Yes Yes Yes 1 SH Set Point User 11 Yes Yes Yes Yes 1 Hours Running SH 11 Yes No Yes No 2 Hours Running DHW 11 Yes No Yes No 3 Ignition Attempts 11 Yes No Yes No 4 Show Last 10 Errors 11 Yes No Yes No 1 DHW Tank Set Point 12 Yes Yes Yes Yes 2 DHW Boiler Set Point 12 Yes Yes Yes Yes 3 SH/DHW Switching Time 12 Yes Yes Yes Yes 5 Outdoor Air Shutdown 12 Yes Yes Yes Yes 6 Outdoor Air Shutdown Differential 12 Yes Yes Yes Yes 8 Boost Temperature 12 Yes Yes Yes Yes 9 Boost Time 12 Yes Yes Yes Yes F 10 User’s Information Manual 3 SMART SYSTEM control module (continued) Viewable and changeable control parameters CAUTION Before changing parameters, note the settings so that the unit can be returned to its original operating parameters. A: General Heater model The control will display “LOCHINVAR” as the model number because the same control is used on several models. This will be displayed when parameter A1 has been accessed. This parameter is not changeable. User code The User Code allows the user to access and change a limited number of control parameters. The access code can be changed by the user or the installer to a code of their choosing. To change the code, parameter A2 must be accessed. The default code is 0704. The code can be changed one digit at a time by using the arrow keys on the display. Night setback temperature Once the internal clock has been set correctly, the night setback feature can be used to program a lower water temperature set point for space heating or tank. This parameter can be changed by the user or the installer by accessing parameter A6. The temperature range for this parameter is 32°F (0°C) to 140°F (60°C). The feature is turned off with a setting of 32.0°F (0°C). The default value is 32.0°F (0°C). Night setback times If parameter B6 is set to anything other than 32.0°F (0°C), the night setback feature becomes active. This will require start and stop times to be programmed for the days that reduced temperatures are required. These times can be changed by the user or the installer by accessing parameter A7. Each day of the week (Monday through Sunday) will have an on and off time. Example: Monday ON: 22:30, Tuesday OFF: 6:45. If you wish to skip a day and have no night setback, leave the on and off times the same. The default times for each day will be 08:00 (OFF) and 18:00 (ON). B: Temperature settings (boiler only) Date and time The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the unit is first installed or any time the unit has been powered off for more than 30 days. To set the clock, parameter A3 must be accessed. The date and time are displayed as “YY:MM:DD W hh:mm”. YY = year, MM = month, DD = date, W = day (1 = Monday, 2 = Tuesday, etc.), hh = hour (24 hour time; 2:00 PM = 14:00), mm = minutes. SH Set point user The SH set point user sets the water temperature set point for fixed operation or the maximum temperature set point when the outdoor air sensor is used. This parameter can be changed by the user or the installer by accessing parameter B1. The temperature range of this parameter is 60°F (15°C) to 230°F (110°C). The default value is 120°F (49°C). C: Data logging The internal clock does not adjust for Daylight Savings Time and therefore, will require a manual adjustment. Hours running SH The hours running SH parameter shows the total number of hours the unit has been in the SH firing position. This parameter can be viewed by the user and the installer by accessing parameter C1. The software version allows the user to view the software version in use by the control. This software controls the operation of the unit. When a new software version becomes available, the existing control can be replaced with a new control to update the software. Hours running DHW The hours running DHW parameter shows the total number of hours the unit has been in the DHW firing position. This parameter can be viewed by the user and the installer by accessing parameter C2. Temperature units Ignition attempts The ignition attempts parameter shows the total number of times the unit has attempted to fire. This parameter can be viewed by the user and the installer by accessing parameter C3. NOTICE Software version The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing parameter A5. The default is °F. Show last 10 errors The control will log the 10 most current errors with the date and time the error occurred. This parameter can be viewed by the user and the installer by accessing parameter C4. 11 User’s Information Manual 3 SMART SYSTEM control module E: DHW settings F: Outdoor air reset (boiler only) DHW tank set point When a temperature sensor is installed in the DHW tank, the DHW tank set point sets the target temperature of the water in the tank. The user or installer can adjust this set point by accessing parameter E1. The temperature range of this parameter is 60°F (15°C) to 190°F (88°C). The default value is 120°F (49°C). Outdoor air shutdown DHW boiler set point (boiler only) When a DHW call for heat becomes active, the control will use the DHW boiler set point to determine the firing rate of the unit based on the actual outlet water temperature. This parameter can be changed by the installer by accessing parameter E2. The temperature range of this parameter is 60°F (15°C) to 200°F (93°C). The default value is 180°F (82°C). SH/DHW switching time (boiler only) The SH/DHW switching time parameter sets the length of time the control will stay in DHW Mode when a space heating (SH) call has been received. After this time period has expired the control will revert to SH Mode. If a DHW call is still active the timer will reset. After the time period has expired the control will revert back to DHW Mode. This will continue until one of the demands has been satisfied. This parameter can be changed by the installer by accessing parameter E3. The time range of this parameter is 10 minutes to 240 minutes. The default value is 30 minutes. When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). This parameter can be changed by the user or the installer by accessing parameter F5. The temperature range of this parameter is 0°F (-18°C) to 120°F (49°C). The default value is 80°F (27°C). Outdoor air shutdown differential The outdoor air shutdown differential parameter is the number of degrees below parameter F5 the outdoor air temperature must go before the unit will respond to a SH demand. This parameter can be changed by the user or the installer by accessing parameter F6. The temperature range of this parameter is 0°F (0°C) to 90°F (50°C). The default value is 10°F (5°C). Boost temperature If a SH demand lasts longer than the programmed time delay setting (F9) and there have been no DHW demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or the maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting. The boost temperature can be changed by the installer by accessing parameter F8. The temperature range of this parameter is 0°F (0°C) to 45°F (25°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C). Boost time The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature set point will be increased. This parameter can be changed by the installer by accessing parameter F9. The time range for this parameter is 1 minute to 60 minutes. The default value is 20 minutes. 12 User’s Information Manual 3 SMART SYSTEM control module (continued) Status display screens Status Display Screens By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the nine (9) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display: Screen Display shows: Description HTR: OFF The unit has been turned OFF by the Enter/Reset button on the SMART SYSTEM display panel. Standby The unit has not received a call for heat from a remote thermostat nor has it received a call for heat from a DHW thermostat. Set Point Met The unit has met the water temperature set point, but is still receiving a call for heat from either a remote thermostat or a DHW thermostat. Prepurge The unit has initiated the 10 second purge and 15 second HSI warmup periods on a call for heat. Ignition The unit has begun a 5 second trial for ignition. SH***% Rate DHW***% Rate The unit has fired and is running at the displayed percentage. Postpurge The call for heat has been satisfied and the unit runs the fan for an additional 10 seconds to clear the combustion chamber and vent system of residual flue products. Service The unit has been placed in a temporary mode that will allow the unit to fire for the purpose of combustion analysis. OUT: ***F(***) When the outlet sensor has been selected as the control sensor (default), the control will display the outlet temperature as well as the set point in parenthesis. ***F If the outlet sensor has not been selected as the control sensor or a system supply sensor is connected, only the outlet temperature will be displayed. Open The control does not detect the outlet sensor. Shorted The outlet sensor wires or the sensor itself has become shorted. #1 Press the Next arrow key on the SMART SYSTEM display to access Screen #2. IN: ***F If the inlet sensor has not been selected as the control sensor or a system return sensor is installed, only the inlet temperature will be displayed. ***F (***) When the inlet sensor has been selected as the control sensor, the control will display the inlet temperature as well as the set point in parenthesis. Open The control does not detect the inlet sensor. Shorted The inlet sensor wires or the sensor itself has become shorted. RISE: ***F The difference between the inlet temperature and the outlet temperature. #2 Press the Next arrow key on the SMART SYSTEM display to access Screen #3. 13 User’s Information Manual 3 SMART SYSTEM control module Status Display Screens (cont’d) By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the nine (9) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display: Screen #3 Display shows: Description SYS: ***F If the system supply sensor has not been selected as the control sensor, only the system temperature will be displayed. ***F (***) When the system supply sensor has been selected as the control sensor, the control will display the system temperature as well as the set point in parenthesis. Open The control does not detect the system supply sensor. Shorted The system supply sensor wires or the sensor itself has become shorted. OUTDOOR: ***F The control will display the outdoor air temperature as sensed by the outdoor air sensor. Open The control does not detect the outdoor air sensor. Shorted The outdoor air sensor wires or the sensor itself has become grounded. Press the Next arrow key on the SMART SYSTEM display to access Screen #4. SYSRT: *** The control will display the system return temperature if the system return sensor is connected. If not connected, the display will skip this screen and display screen #5. VALVE: ***% The control will display the position of the 3-way valve; 100% indicates that no outlet water is being bypassed into the inlet. #4 Press the Next arrow key on the SMART SYSTEM display to access Screen #5. #5 FLUE: ***F The control will display the flue temperature. Open The control does not detect the flue sensor. Shorted The flue sensor wires or the sensor itself has become shorted. AUX: ***F The control will display the temperature. Open The control does not detect the auxiliary sensor. Shorted The auxiliary sensor wires or the sensor itself has become shorted. Press the Next arrow key on the SMART SYSTEM display to access Screen #6. #6 FAN SPD: ****RPM The control will display the actual fan motor RPM. FLAME SIG: **.*uA The control will display the flame signal in dc microamps. Press the Next arrow key on the SMART SYSTEM display to access Screen #7. 14 User’s Information Manual 3 SMART SYSTEM control module (continued) Status Display Screens (cont’d) By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the nine (9) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display: Screen Display shows: Description SH CFH: OFF The control has not received a call for heat from a SH remote thermostat. ON The control has received a call for heat from a SH remote thermostat. DHW CFH: OFF The control has not received a call for heat from a tank sensor or tank thermostat. ON The control has received a call for heat from a tank sensor or tank thermostat. #7 Press the Next arrow key on the SMART SYSTEM display to access Screen #8. DHW PUMP: OFF The control has not received a DHW call for heat and has not powered the DHW pump. ON The control has received a DHW call for heat and has powered the DHW pump. Delay The DHW call for heat has been satisfied and the DHW pump is running for a fixed time to remove any residual heat. 0-10V IN: **.VDC The control will display a 0-10 VDC signal received from a Building Management System (BMS) connected to the unit. #8 Press the Next arrow key on the SMART SYSTEM display to access Screen #9. #9 SYS PUMP: OFF The control has not received a call for heat from a remote thermostat and has not powered the system pump. ON The control has received a call for heat from a remote thermostat and has powered the system pump. Delay The system call for heat has been satisfied and the system pump is running for a fixed time to remove any residual heat. BLR PUMP: OFF The control has either not received a call for heat from a remote thermostat, a remote thermostat is not connected to the unit and the water temperature has not dropped below the temperature set point of the control to initiate a call for heat, or the control has received a DHW call for heat from a DHW thermostat. ON The control has received a call for heat from a remote thermostat or a remote thermostat is not connected and the water temperature has dropped below the temperature set point of the control to initiate a call for heat. Delay The call for heat has been satisfied and the boiler pump is running for a fixed time to remove any residual heat. Press the Next arrow key on the SMART SYSTEM display to roll back to Screen #1. At any point if you wish to access an earlier screen, press the Previous arrow key on the SMART SYSTEM display. 15 Revision Notes: Revision B (PBX-PFX-USER-Rev B) reflects the addition of Models 502 - 1302 to the manual. PBX-PFX-USER-Rev B CP-2M-8/07
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0 (Windows) Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2007:08:28 08:43:20-05:00 Create Date : 2007:08:28 08:43:20-05:00 Format : application/pdf Title : PBX-PFX-USER-Rev B.qxp Creator : yroberts Document ID : uuid:4dc39ba9-624c-4d9f-a10d-1e730cae2cb9 Instance ID : uuid:2380c8ad-3528-4176-94a8-98bd5339d1a9 Page Count : 16 Author : yrobertsEXIF Metadata provided by EXIF.tools