PS902

44487023
Power Supply

Installation Instructions

DANGER
To avoid risk of electric shock, turn off AC power before
installing or servicing PS902 power supply

These instructions cover the following parts:

900-KL Keylock (optional) - Page 2
:

NING

!

WAR

:

NING

!

WAR

!

ER
NG
DA

F1

:

ER

NG

!

DA

900-BB Battery Backup (optional) - Page 3

PS902 Power Supply - Pages 1-3

PS902 Power Supply Specifications:
Input

120/240 VAC, 1.1 A, 50/60Hz, High Voltage Class 1 Wiring Required

Output

2 Amp DC @ 12/24 VDC

Enclosure

14” H x 12” W x 4” D (8 knockouts, 1/2” or 3/4” )

Temperature Range

32°-120° F (0°- 49° C)

Fuse

F1, T3.15A
250VAC

CAUTION
For protection against risk of fire, replace fuse with same
type and rating

Compliance

UL 294, ULC-S318, RoHS, & FCC Part 15, Class 2 Output

Compatible Boards

900-2RS

INST. INSTRUCTIONS - 24125007

(Optional, 1 board maximum)

900-2Q

INST. INSTRUCTIONS - 44487098

900-4R

INST. INSTRUCTIONS - 44487106

900-4RL

INST. INSTRUCTIONS - 44487080

900-8F

INST. INSTRUCTIONS - 44487106

900-8P
Fire Alarm Input Board (Optional)

900-FA

INST. INSTRUCTIONS - 44487106
INST. INSTRUCTIONS - 44487072

Battery Backup Board (Optional)

900-BB

INST. INSTRUCTIONS - 44487064

Mounting notes
The PS902 must be installed in accordance with the article 760 of the National Electrical Code or NFPA 72, Canadian Electrical Code, or
any other applicable codes.
Install the PS902 indoors within the protected premises.
Check national and local codes for additional installation requirements.
Enclosure must be firmly mounted to a solid surface using hardware suitable for the surface.

1

Mount power supply

1a

Mark 2 Top Holes

1b

Secure Enclosure with 4 Screws

x

x

Board not shown for
clarity

2

Secure enclosure door
If No Keylock

If Keylock

Enclosure will be secured with 2
screws as shown (done as last step)

Remove knockout and insert key cylinder, then slide in clip

OR

a

b

3
3a
3a

PS902 setup and testing
Connect AC Wiring

DANGER

AC Input

Ensure AC breaker is turned off

Green (Ground)
White (Neutral)
Black (Hot)

NEU LINE

AC (In)
120/240
VAC

900-BB Connector
!

DANGER

High Voltage

3b

24 VDC
Output Setting

12 VDC
Output Setting

24

If main board must be
removed, turn off AC power
and wait 8 minutes before
removal

Use Jumper to Select 24 VDC or 12
VDC Output

12

Do not remove this cover, no
serviceable parts

F1

OR

NC C NO

Note:

4
4a

4b

Minimum of 1/4” separation
between AC and DC wiring as
well as power limited and nonpower limited.

AC Input
(Green LED)

DANGER

AC Monitor
Active when AC present
and F1 fuse not open
(Form C dry contacts)

If AC LED is
off, turn AC
breaker prior
to checking F1
fuse

12/24 VDC
Output
Terminals

900-FA
Connector

DC Output
(Red LED)

Refer to 900-BB instructions for additional info

Install 900-BB battery backup (If Included)

Battery Supervision Terminals
(Form C Dry Contacts)

Place Batteries in Box with Terminals to
the left

NO
C
NC

Attach Wire from Battery Board
Red wires = (+)
Black wire = (-)

(Shown
AC Off)

Active

Inactive

AC On

AC Off

BB LED
(Amber)

Red Wires = (+)

+

Note: allow 24 hours for batteries
to fully charge

Fire Alarm Jumper
Remove when
900-FA installed

ry

tte

Ba

2
On-Blinking

AC On

AC Off

Batteries
Charging

Batteries
Supplying
Power

+

On-Solid

ry

tte

Ba

1

Black Wires = (-)

5

•
•
•

Turn on AC breaker to test power supply
Verify AC LED is On = GREEN
Verify DC LED is On = RED
Verify BB LED (if applicable) is On = AMBER

6

Refer to 900-FA instructions
for additional info

Wire 900-FA (fire alarm board) if included

Terminal Definitions

NC

C

NO

Supervision Output
Contacts Shown FA Active (open)

One 900-FA Board - Automatic Reset
NC

C

NO

FA1

FA1

Note: If FA is installed on PS902:

FA2

•
•

Fire Alarm Input

Verify jumper J13 is removed
Power will be removed from
PS902 when fire alarm is active

One 900-FA Board - Manual Reset
NC

FA2

C

NO

FA1

FA2

Manual Reset
(Temporarily close to reset)

Fire Alarm Contact
Closed = no fire
Open = fire

Fire Alarm Contact
Closed = no fire
Open = fire

Refer to appropriate instructions if any board
shown below is factory-installed

Option Boards

Option 1

Option Board to be Plugged
into Option Connector

• See option board installation instructions
for wiring info

Notes:
1. When powering (2) QEL’s with a PS902, both cannot be
activated at the same time, they must be sequenced.
2. Latchbolt retraction of (2) sequenced QEL’s requires more
than 1 second to complete.
3. For double door QEL applications with auto operators, it is
recommended to use a PS904, 906, or 914 power supply.

Available option boards:

900-2RS
(2 Relay)

900-2Q
(2 Relay w/com)

900-4R
(4 Relay)

900-4RL
(4 Relay w/logic)

900-8F
(8 Zone
Distribution-fuse)

900-8P
(8 Zone
Distribution-PTC)

NOTE: When installation is complete, secure enclosure door with screws (provided) or keylock

Customer Service
1-877-671-7011

www.allegion.com/us

© Allegion 2014
Printed in U.S.A.
44487023 Rev. 01/14-c



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Create Date                     : 2013:12:19 10:56:23-05:00
Creator                         : Adobe InDesign CS6 (Windows)
Modify Date                     : 2016:02:11 12:44:05-05:00
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2016:02:11 12:44:05-05:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:90fcd14e-a672-4796-872e-3abb6c36bf70
Original Document ID            : xmp.did:31E29F5C3D5CDF11BB6AEFFDF511A3FD
Document ID                     : xmp.id:AC0A8415C668E311A82AD68785E9E205
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:AB0A8415C668E311A82AD68785E9E205
Derived From Document ID        : xmp.did:59DEE055BE68E311A82AD68785E9E205
Derived From Original Document ID: xmp.did:31E29F5C3D5CDF11BB6AEFFDF511A3FD
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2013:12:19 10:56:23-05:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 4
EXIF Metadata provided by EXIF.tools

Navigation menu