Locks Fire Lite MS9200UDLS User Manual
User Manual: Locks Fire Lite MS9200UDLS User Manual Security Product Manuals - Northeast Security SolutionsNortheast Security Solutions
Open the PDF directly: View PDF .
Page Count: 228
Download | |
Open PDF In Browser | View PDF |
PN: 52750:E1 ECN 09-062 Addressable Fire Alarm Control Panel MS-9200UDLS MS-9200UDLSE IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this manual when installing or servicing the Fire Alarm Control Panel. Document #52750 01/27/09 Revision: PN: 52750:E1 E1 D ECN 09-062 Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. age of flammable materials, etc.). The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire. Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because: • Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. • Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located. • Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before reaching the detector. The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor- Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that: • Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. • Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. • In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. PrecauLarge.PMD 02/26/2007 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F and at a relative humidity of 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F. Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense. PrecauLarge.PMD 02/26/2007 Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. This Class A digital apparatus complies with Canadian ICES-003. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. Cet appareil numerique de la Classe A est conforme a la norme NMB-003 du Canada. Notes 4 MS-9200UDLS PN 52750:E1 01/27/09 Table of Contents Product Description ................................................................................................................................................14 Features and Options .........................................................................................................................................14 Specifications ....................................................................................................................................................16 Current Availability ....................................................................................................................................17 Controls and Indicators .....................................................................................................................................18 Circuits ..............................................................................................................................................................19 Digital Alarm Communicator/Transmitter ........................................................................................................19 Components .......................................................................................................................................................20 Intelligent Addressable Detectors: Newer Series .......................................................................................20 Intelligent Addressable Modules: Newer Series ........................................................................................20 300 Series Intelligent Addressable Devices ...............................................................................................21 Addressable Device Accessories ................................................................................................................21 Optional Modules ..............................................................................................................................................21 Accessories ........................................................................................................................................................22 PS-Tools Programming Utility ...................................................................................................................22 DP-9692 Dress Panel .................................................................................................................................22 Trim Ring ...................................................................................................................................................22 Battery Box ................................................................................................................................................22 Battery Charger ..........................................................................................................................................23 CHG-75 Battery Charger ....................................................................................................................23 CHG-120F Battery Charger ................................................................................................................23 IPDACT- Internet Protocol DACT .............................................................................................................23 ANN-BUS Annunciators/Modules ............................................................................................................24 ANN-BUS Wiring ...............................................................................................................................24 Calculating Wiring Distance for ANN-BUS Modules .......................................................................24 Wiring Configuration ..........................................................................................................................26 Powering ANN-BUS Devices from Auxiliary Power Supply ............................................................27 ANN-BUS Device Addressing ...........................................................................................................27 ANN-80 Remote Fire Annunciator .....................................................................................................28 Specifications ......................................................................................................................................28 Installation ...........................................................................................................................................28 Mounting .............................................................................................................................................28 Opening/Closing Annunciator ............................................................................................................28 Wiring ANN-80 to FACP ...................................................................................................................29 ANN-S/PG Serial/Parallel Interface Installation ................................................................................31 Specifications ......................................................................................................................................31 PRN-6F Printer Installation ................................................................................................................31 ANN-I/O LED Driver Module ............................................................................................................33 ANN-I/O Board Layout ......................................................................................................................33 Specifications ......................................................................................................................................33 ANN-I/O Connection to FACP ...........................................................................................................34 ANN-I/O Module LED Wiring ...........................................................................................................34 ANN-LED Annunciator Module ........................................................................................................35 ANN-LED Board Layout ....................................................................................................................36 Specifications ......................................................................................................................................36 Mounting/Installation ..........................................................................................................................36 ANN-LED Connection to FACP ........................................................................................................37 ANN-RLY Annunciator Module ........................................................................................................38 ANN-RLY Board Layout ....................................................................................................................38 Specifications ......................................................................................................................................38 Mounting/Installation ..........................................................................................................................38 ANN-RLY Connection to FACP ........................................................................................................39 ANN-BUS Audio Panel Control .........................................................................................................39 Legacy ACS Series LED Zone Type Annunciators ...................................................................................41 Getting Started ...................................................................................................................................................41 MS-9200UDLS P/N: 52750:E1 01/27/09 5 Telephone Requirements and Warnings ............................................................................................................42 Telephone Circuitry ....................................................................................................................................42 Digital Communicator ................................................................................................................................42 Telephone Company Rights and Warnings ................................................................................................43 For Canadian Applications .........................................................................................................................44 Installation ...............................................................................................................................................................45 Mounting Backbox ............................................................................................................................................45 Mounting Optional Transformer/Remounting Chassis .....................................................................................46 Power .................................................................................................................................................................49 AC Power and Earth Ground Connection ..................................................................................................49 Battery Power .............................................................................................................................................49 Special Application DC Power Output Connection ...................................................................................49 Relays ................................................................................................................................................................50 Notification Appliance Circuits .........................................................................................................................50 Configuring NACs .....................................................................................................................................51 Style Y (Class B) NAC Wiring ..................................................................................................................51 Style Z (Class A) NAC Wiring ..................................................................................................................52 Remote Synchronization Output .......................................................................................................................52 UL Power-limited Wiring Requirements ...........................................................................................................53 Digital Communicator .......................................................................................................................................54 Optional Module Installation .............................................................................................................................55 4XTMF Transmitter Module Installation ...................................................................................................56 Printer .........................................................................................................................................................57 Programming .........................................................................................................................................................59 Programming Data Entry ...................................................................................................................................59 User Programming .............................................................................................................................................60 Initial Power-up .................................................................................................................................................61 Programming Screens Description ....................................................................................................................61 Programming and Passwords .............................................................................................................................62 Master Programming Level ...............................................................................................................................63 Autoprogram ..............................................................................................................................................64 Point Program .............................................................................................................................................65 Detector Programming ........................................................................................................................65 Add Detector .......................................................................................................................................65 Delete Detector ....................................................................................................................................66 Edit Detector .......................................................................................................................................66 Module Programming .........................................................................................................................75 Add Module ........................................................................................................................................75 Delete Module .....................................................................................................................................76 Edit Module Screen for Monitor Module ............................................................................................76 Edit Module Screen for Control Modules ...........................................................................................85 Zone Setup ..................................................................................................................................................92 Enable ..................................................................................................................................................92 Disable .................................................................................................................................................93 Zone 97, 98 and 99 ..............................................................................................................................93 Zones Installed ....................................................................................................................................94 Zones Enabled .....................................................................................................................................94 Zones Disabled ....................................................................................................................................94 Zone Type ...........................................................................................................................................95 Zones Available ..................................................................................................................................96 Zone Message ......................................................................................................................................96 Loop Setup .................................................................................................................................................96 Style .....................................................................................................................................................96 Loop Protocol ......................................................................................................................................97 System Setup ..............................................................................................................................................97 6 MS-9200UDLS P/N: 52750:E1 01/27/09 Table of Contents Trouble Reminder ...............................................................................................................................98 Banner .................................................................................................................................................98 Time-Date ...........................................................................................................................................100 Time ....................................................................................................................................................100 Date .....................................................................................................................................................101 Clock Format .......................................................................................................................................101 Daylight Savings Time ........................................................................................................................101 Timers .................................................................................................................................................102 PAS (Positive Alarm Sequence) Delay ...............................................................................................102 Pre-signal Delay ..................................................................................................................................103 Waterflow Delay .................................................................................................................................103 AC Loss Delay ....................................................................................................................................104 NAC (Notification Appliance Circuit) ................................................................................................104 Enabled ................................................................................................................................................105 Type ....................................................................................................................................................106 Silenceable ..........................................................................................................................................106 Auto Silence ........................................................................................................................................107 Coding (only for NACs not programmed as Sync Strobe Type) ........................................................107 Zone ....................................................................................................................................................109 Silence Inhibited .................................................................................................................................109 Sync Type ...........................................................................................................................................109 Relays ..................................................................................................................................................110 Canadian Option .................................................................................................................................111 Waterflow Silenceable ........................................................................................................................111 Verify Loop ................................................................................................................................................111 History ........................................................................................................................................................112 View Events ........................................................................................................................................112 Erase History .......................................................................................................................................112 Walktest ......................................................................................................................................................113 Option Modules .........................................................................................................................................115 Annunciators .......................................................................................................................................115 Term Options ......................................................................................................................................115 ACS Options .......................................................................................................................................116 ANN-BUS Options .............................................................................................................................118 Onboard DACT ...................................................................................................................................131 Onboard DACT Enable .......................................................................................................................131 Primary Phone .....................................................................................................................................131 Secondary Phone .................................................................................................................................132 Service Terminal .................................................................................................................................132 Central Station .....................................................................................................................................133 Trouble Call Limit (Dialer Runaway Prevention) ..............................................................................134 Supervised Phone Line ........................................................................................................................141 Printer/PC ............................................................................................................................................142 Password Change .......................................................................................................................................143 Clear Program ............................................................................................................................................144 Program Check ...........................................................................................................................................145 Maintenance Programming Level .....................................................................................................................147 Disable Point ..............................................................................................................................................148 History ........................................................................................................................................................149 Program Check ...........................................................................................................................................150 Walktest ......................................................................................................................................................151 System ........................................................................................................................................................153 Zone Setup ..................................................................................................................................................154 Operating Instructions ...........................................................................................................................................156 Panel Control Buttons .......................................................................................................................................156 MS-9200UDLS P/N: 52750:E1 01/27/09 7 Acknowledge/Step ......................................................................................................................................156 Alarm Silence .............................................................................................................................................156 Drill/Hold 2 Sec ..........................................................................................................................................156 Reset ...........................................................................................................................................................156 LED Indicators ..................................................................................................................................................157 Normal Operation ..............................................................................................................................................158 Trouble Operation ..............................................................................................................................................158 Alarm Operation ................................................................................................................................................160 Supervisory Operation .......................................................................................................................................161 Process Monitor Operation ................................................................................................................................162 Hazard/Tornado Condition Operation ...............................................................................................................162 Medical Alert Condition Operation ...................................................................................................................162 NAC Operation ..................................................................................................................................................162 Programmed Zone Operation ............................................................................................................................163 Disable/Enable Operation ..................................................................................................................................163 Waterflow Circuits Operation ............................................................................................................................163 Detector Functions .............................................................................................................................................163 Time Functions: Real-Time Clock ....................................................................................................................163 Synchronized NAC Operation ...........................................................................................................................164 Coded Operation ................................................................................................................................................164 Presignal ............................................................................................................................................................164 Positive Alarm Sequence ...................................................................................................................................165 Special System Timers ......................................................................................................................................166 Silence Inhibit Timer ..................................................................................................................................166 Autosilence Timer ......................................................................................................................................166 Trouble Reminder .......................................................................................................................................166 Waterflow Retard Timer .............................................................................................................................166 Alarm Verification (None or One Minute) .................................................................................................166 Walktest .............................................................................................................................................................167 Read Status ........................................................................................................................................................168 System Point ...............................................................................................................................................169 Zones ..........................................................................................................................................................170 Power ..........................................................................................................................................................171 Trouble Reminder .......................................................................................................................................172 Timers .........................................................................................................................................................172 NAC ............................................................................................................................................................173 Relays .........................................................................................................................................................173 Program Check ...........................................................................................................................................174 History ........................................................................................................................................................174 Annunciators ..............................................................................................................................................174 Phone Line ..................................................................................................................................................176 Central Station ............................................................................................................................................176 Service Terminal .........................................................................................................................................177 Printer/PC ...................................................................................................................................................177 Print ............................................................................................................................................................178 Time-Date ...................................................................................................................................................180 Central Station Communications ..........................................................................................................................181 Transmittal Priorities .........................................................................................................................................182 Remote Site Upload/Download ..............................................................................................................................184 Remote Download .............................................................................................................................................184 Transferring a Program ......................................................................................................................................185 Security Features ........................................................................................................................................186 Power Supply Calculations ....................................................................................................................................187 Overview ...........................................................................................................................................................187 Calculating the AC Branch Circuit ....................................................................................................................187 8 MS-9200UDLS P/N: 52750:E1 01/27/09 Table of Contents Calculating the System Current Draw ...............................................................................................................188 Overview ....................................................................................................................................................188 How to Use Table 7.3 on page 189 to Calculate System Current Draw ....................................................188 Calculating the Battery Size ..............................................................................................................................190 NFPA Battery Requirements ......................................................................................................................190 Selecting and Locating Batteries ................................................................................................................190 Software Zones ........................................................................................................................................................191 Correlations .......................................................................................................................................................191 Default Programming .............................................................................................................................................197 NFPA Standard-Specific Requirements ...............................................................................................................198 Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts ...........................................202 MBT-1 Municipal Box Trip - Silenceable ........................................................................................................203 FACP with Keltron .................................................................................................................................................204 Wire Requirements .................................................................................................................................................205 NAC Wiring ......................................................................................................................................................207 HVAC Control ........................................................................................................................................................208 Control Module Operation ................................................................................................................................208 HVAC SHUTDN .......................................................................................................................................208 Monitor Module Operation ...............................................................................................................................208 HVAC RESTART ......................................................................................................................................208 HVAC OVRRIDE ......................................................................................................................................209 Ademco Contact ID Format Event Code Descriptions .......................................................................................210 Transmission Format Between DACT and Receiver ........................................................................................210 Ademco Contact ID Typical Printout ................................................................................................................210 Central Station Points ............................................................................................................................................215 MS-9200UDLS P/N: 52750:E1 01/27/09 9 Software Downloads In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application. 10 MS-9200UDLS PN 52750:E1 01/27/09 It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • • • Underwriters Laboratories Standards NFPA 72 National Fire Alarm Code CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents. NFPA Standards NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code Underwriters Laboratories Documents: UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems Other: EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ) Fire-Lite Documents: Fire-Lite Device Compatibility SLC Wiring Manual ACS Series Annunciators CHG-120F Battery Charger CHG-75 Battery Charger LDM Series Lamp Driver Modules LCD-80F Remote Fire Annunciator ACM-8RF Relay Control Module IPDACT Communicator/Transmitter ANN-80 Product Installation Document ANN-(R)LED Product Installation Doc. ANN-I/O Product Installation Document ANN-RLY Product Installation Document ANN-S/PG Product Installation Document ACC-25/50(ZS/T) Manual Document #15384 Document #51309 Document #51480 Document #50888 Document #51315 Document #50055 Document #51338 Document #50362 Document #53109 Document #52749 Document #53032 Document #151416 Document #53033 Document #151417 Document #52750 This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ). MS-9200UDLS PN 52750:E1 01/27/09 11 12 2 1 TRANSFORMER 1 MS-9200UDLS PN 52750:E1 HIGH VOLTAGE J10 4 3 3 2 1 JP4 CAUTION! CAUTION! 2 1 J11 TRANSFORMER 2 Transformer 1 Connector Transformer 2 Connector Important! Removing Ground Fault Disable Jumper JP7 voids UL/NFPA Style/Class identifications for circuits. Remove jumper JP7 only with the approval of the AHJ (Authority Having Jurisdiction) Nonresettable or Resettable Power Jumper selectable by JP4, 24 VDC filtered, power-limited (0.300 amps maximum) Supervision required. Nonresettable Power suitable for powering annunciators, Resettable Power suitable for powering smoke detectors.. Resettable Power - 24 VDC filtered, power-limited (0.300 amps maximum) to smoke detectors (IDC). Supervision required. Nonsupervised, power-limited circuits Supervise with a power supervision relay A77-716B + - J1 + + + NAC #4 + + + 120 VAC, 60 HZ, 3.0 amps 220/240 VAC, 50 Hz, 1.5 amps - + BATTERY J9 24 VDC, supervised, nonpower-limited 18 Amp Hour maximum Battery J4 Remove this jumper to disable the FACP battery charger when using external charger. To disable ground fault detection, remove jumper/shunt from JP7 JP7 REMOVE TO DISABLE GND. FLT. Configure NACs for Class A or Class B wiring using NACKEY card. Factory default is Class B. B+ A+ A- B2B+ 4B+ 4B- 2BNAC 2 CLASS A NAC 2 & 4 CLASS B NC C Alarm* Trouble JP2 RELAY 2 NC NO C NC NO C TB6 NC C RELAY 1 TB5 NO NO NC C TB8 KISSOFF + - 4XTMF CUT TO MONITOR 4XTMF JP3 J6 PH15 B (Nonpower-Limited) J12 SEC. ACTIVE DACT Phone Line Jacks SEC. PHONE LINE PH16 A shield SHIELD J7 A+ B- A- SLC SLC SLC B A B A A B + + - TB10 SLC B+ Cut this jumper to supervise the 4XTMF module when installed (see J5 & J6) J5 PRI. PHONE LINE PRI. ACTIVE TB9 (supervised) Refer to the SLC Wiring Manual for detailed information on wiring addressable devices for Style 4, 6 and 7. SLC Loop Cut this jumper to enable Supervisory relay when 4XTMF module is installed IN+ IN- OUT+ OUT- O O I I U U N N T T + - + - PS2 Keyboard Interface MINI DIN KEYBOARD CONN. J3 KEYPAD I/F SW1 Flash Memory Load Enable Switch. UP is normal position for switch. DOWN position allows loading of factory software upgrades. RELAY 3 TB7 NO NO NC C Supervisory* (*Factory default relay programming) OR (nonsupervised) For EDP-listed equipment or personal computer with FACP Upload/Download Utility. 50 foot maximum within same room. EIA-232 to printer or personal computer ACS/ANN-BUS (EIA-485) to Annunciators (power-limited, supervised) TERM (EIA-485) to LCD annunc. Contacts shown below in normal condition (AC power with no alarm, trouble or supervisory activity). Nonsupervised relay contacts Contact Ratings: 2.0 amps @ 30 VDC (resistive) 0.5 amps @ 30 VAC (resistive) 2 Programmable Relays & 1 Fixed Trouble Relay ELRs 4.7K, ½W A Fail Safe Trouble NC NO C relay switches to the NO position during trouble conditions and under loss of all power. NAC #2 B B B B + + - NAC 2 4 4 2 Number TB4 B+ A+ A- B1B+ 3B+ 3B- 1BNAC 1 CLASS A NAC 1 & 3 CLASS B TB3 - B B B B + + - 1 3 3 1 + + + NAC #3 LCD DISPLAY JP6 HOT NEUT EARTH TB11 - + - + + + + NAC #1 REMOTE PWR SUPPLY SYNC TB2 JP5 + 24V - + 24V NON-RST RST POWER POWER TB1 + Notification Appliance Circuits NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited) (Special Application) 2.5 amps max. per circuit. JP6 configured for Class B using NACKEY card. (See Style Z illustrated near right edge of board). Special Application DC Power Outputs (24 VDC) Special Application Power 24 VDC filtered, supervised and power-limited. 0.040 amps maximum, follows NAC1 control circuit. Requires 4.7kohm End-of-Line resistor. Remote Synchronization Output Basic System Connections HIGH VOLTAGE 01/27/09 OR T R D G X C T N V R D 5 4 3 2 1 TR D G XC T N V R D Notification Appliance Circuits TB3 B A A B + + - - + + + TB4 92udLSlayo.cdr B A A B + + - - + + NAC #2 + NAC #1 & #2 Style Z (Class A) (Supervised, Power Limited) 2.5 amps max. per circuit. JP6 configured for Class A using NACKEY card. NAC #1 TB8 TB8 (option to DB-25) 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 TB8 USB Port J12 for local programming using a personal computer and programming utility. Red White Green Black DB9F 9 8 7 6 5 4 3 2 1 Peripheral Devices and Their Documents: ANN Audio Control for ACC-25/50(ZS/T) Doc. #51889 ANN-(R)LED LED Display Doc. #53032 ANN-RLY 10 Form-C Relay Card Doc. #53033 ANN-I/O LED Driver Doc. #151416 ANN-80 LCD Text Annunciator Doc. #52749 ANN-S/PG Printer Driver Doc. #151417 IPDACT Internet Communicator Doc. #53109 ANN-BUS - TB9 PH15 & PH16 Telephone Connections J5 & J6 4XTMF Reverse Polarity Module SLC Loop - TB10 Addressable Devices and SLC Wiring Doc. #51309 9200udLSannperi.cdr Battery Connector - J9 CHG-75 Charger Doc. # 51315 CHG-120F Charger Doc. #50888 MS-9200UDLS PN 52750:E1 01/27/09 13 Product Description Product Description SECTION 1 The Fire-Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features.The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection technology. The power supply and all electronics are contained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software and remote power expansion. The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone network. Local programming and interrogation is also possible using the PS-Tools and the USB port (J12) on the FACP. Any personal computer with Windows™ XP or greater, and compatible modem with a speed of 2400 baud or faster and PS-Tools software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS (120 VAC version) and the MS-9200UDLSE (240 VAC version) FACPs. Inventory When MS-9200UDLS shipment is received, check that all parts have been included in shipment. The MS-9200UDLS shipment consists of one of each of the following: main circuit board with display backbox with door plastic bag containing screws, cables, key, etc. manual 1.1 Features and Options • • • • • • • • • • • • • 14 New LiteSpeed™ polling protocol for faster SLC response time SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire (refer to "Wire Requirements" on page 205) Built-in DACT (Digital Alarm Communicator/Transmitter) Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements 198 addressable device capacity (99 detectors and 99 control/relay/monitor modules) 99 software zones Onboard NACs (Notification Appliance Circuits) which can be configured as four Style Y (Class B) or two Style Z (Class A) circuits - special application 3.0 amps total power for NACs and 24 VDC special application auxiliary power outputs expandable to 6.0 amps 3.6 amps total system power (includes battery charger) expandable to 6.6 amps Two programmable relay outputs and one fixed trouble relay Synchronization output for remote power supply applications (special application) Built-in Programmer Telephone Line Active LEDs MS-9200UDLS PN 52750:E1 01/27/09 Product Description • • • • • • • • • • • • • • • • • • • • • • • • • Optional 4XTMF module (conventional reverse polarity/city box transmitter) • ANN-BUS for connection to following optional modules (cannot be used if ACS annunciators are used): ANN-80 Remote Annunciator ANN-I/O LED Driver ANN-S/PG Printer Module ANN-RLY Form-C Relay Module ANN-LED Annunciator Module annunciates alarm, trouble and supervisory ANN-RLED Annunciator Module annunciates alarms only Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center Legacy ACS/TERM Annunciators (cannot be used if ANN annunciators are used): ACS Series-LED Zone Annunciators LDM Graphic Annunciator Series LCD-80F Liquid Crystal Display point annunciator ACM-8RF Relay Module • • MS-9200UDLS PN 52750:E1 Communication Confirmation (Kissoff) LED Touchtone/Rotary dialing Programmable Make/Break Ratio EIA-232 Printer/PC interface (variable baud rate) 80-character LCD display (backlit) Real-time clock/calendar with daylight savings time control History file with 1,000 event capacity Advanced fire technology features: Automatic drift compensation Maintenance alert Detector sensitivity test capability (NFPA 72 compliant) Automatic device type-code verification Point trouble identification Waterflow selection per module point Alarm verification selection per detector point Walktest, silent or audible PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant) Silence inhibit timer option per NAC Autosilence timer option per NAC Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability Selectable strobe synchronization per NAC Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, ACS annunciators or ANN-80 Remote annunciator Auto-program (learn mode) reduces installation time. Reports two devices set to the same address Password and key-protected nonvolatile memory User programmable password Fully programmable from local keypad or optional keyboard Optional PK-CD (contains PS-Tools utility) for local or remote Upload/ Download of program and data Compatible with Fire-Lite’s newer series devices in LiteSpeed and CLIP mode (refer to SLC Wiring Manual for a list of compatible addressable devices) Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC Wiring Manual for a list of compatible addressable devices) 01/27/09 15 Product Description 1.2 Specifications Refer to Illustration on page 10 for terminal locations and connections. AC Power - TB11 MS-9200UDLS: 120 VAC, 60 Hz, 3.0 amps MS-9200UDLSE: 240 VAC, 50 Hz, 1.5 amps Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation Battery (Lead Acid Only) - J9 Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. For greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box). Minimum Battery Size: 7 Amp Hour Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the FACP battery charger when using an external battery charger. Communication Loop - TB10 24 VDC nominal, 27.6 VDC maximum Maximum length - refer to "Wire Requirements" on page 205) Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit Refer to SLC Loop manual for wiring information Notification Appliance Circuits - TB3 & TB4 Each Terminal Block provides connections for two Style Y (Class B) or one Style Z (Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs Style is configured using NACKEY card plugged into JP6 on main board Special Application full-wave rectified power Power-limited circuitry NAC wiring requirements refer to "NAC Wiring" on page 207 Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 17) End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC Refer to the Device Compatibility Document for listed compatible devices Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7 Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.6 on page 50 for information on power-limited relay circuit wiring Nonresettable or Resettable Special Application Power (24 VDC Nominal) TB1, Terminals 1 (+) & 2 (-) Jumper selectable (JP4) for conversion to resettable power output Maximum ripple voltage: 10mVRMS Total DC current available from each output is up to 0.300 amps (see Figure 1.1) Power-limited circuit Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal) - TB1, Terminals 3 (+) & 4 (-) Maximum ripple voltage: 10 mVRMS Up to 0.300 amps is available for powering 4-wire smoke detectors (see Figure 1.1) Power-limited circuit Refer to the Device Compatibility Document for listed compatible devices 16 MS-9200UDLS PN 52750:E1 01/27/09 Product Description Remote Sync Output - TB2 Remote power supply synchronization output 24 VDC nominal special application power Maximum current is 40 mA End-of-Line Resistor: 4.7KΩ Output linked to NAC 1 control Supervised and power-limited circuit EIA-485 (TERM) or EIA-232 Serial - TB8 EIA-485 Terminal Mode annunciator connections: Terminal 1 (In +), 2 (In -), 3 (Out +), 4 (Out -) EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 3 (DTR) 4 (Ground) EIA-485 ACS or ANN-BUS - TB9 ACS/ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B) 1.2.1 Current Availability The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP with optional second transformer. Refer to the battery calculations section for additional information. Figure 1.1 Current Availability MS-9200UDLS PN 52750:E1 01/27/09 6.0 amps with optional second XRM-24B(E) transformer. 3.0 amps max. with only standard transformer installed. powerdist9200ud.cdr Note: If NACs are configured as two Style Z (Class A) circuits, each circuit can handle 2.5 amps maximum. 17 Product Description 1.3 Controls and Indicators LCD Display The FACP uses an 80-character HONEYWELL (4 lines X 20 characters) high LIFE SAFETY viewing angle LCD display. The SYSTEM ALL NORMAL display includes a long life LED 10:00A 012102 backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries. LED Indicators LED indicators are provided to annunciate the following conditions: • • • • • • • • • AC Power (green) Fire Alarm (red) Supervisory (yellow) Trouble (yellow) Maintenance/presignal (yellow) Alarm Silenced signals (yellow) Disabled (yellow) Battery fault (yellow) Ground fault (yellow) Key Panel Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad. Function keys: Acknowledge/Step Alarm Silence Drill Reset (lamp test) Service/program keys: • • • • • • • • • • AC POWER MAINTENANCE FIRE ALARM ALARM SILENCED SUPERVISORY DISABLED TROUBLE BATTERY GROUND 2 1 4 5 ACK/STEP 1st 3 DEF ABC 6 EVENT ALARM SILENCE CLR Keys labeled 1 to 9 7 8 9 * key # key 0 # * -/. 0 (recall) key 1st Event key Figure 1.2 Membrane/Display Panel Clear key Escape key Mode key Four cursor keys (up, down, left and right) Enter key GHI JKL MNO PRS TUV WXY ENTER ESC DRILL HOLD 2 SEC MODE RESET QZ RECALL 9600kypd.cdr • • • • Local Piezo Sounder A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions. 18 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.4 Circuits SLC Communication Loop One SLC loop is provided standard on the FACP main circuit board. The SLC loop, configurable for NFPA Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the SLC Wiring manual for information on wiring devices. Reference Manual Output Circuits The following output circuits are available on the FACP: • • Special Application Power 24 VDC Resettable (smoke detector power) output - 0.300 amps maximum 24 VDC Nonresettable or Resettable power output - 0.300 amps maximum 24 VDC Battery Charger (up to 18 AH batteries) NAC (Notification Appliance Circuits) NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY card in JP6, are provided with various programmable features. Relays One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following operations: • • • • • • • • • • fire alarm trouble supervisory supervisory auto-resettable DACT communication failure process monitor process monitor auto-resettable hazard alert medical alert AC loss 1.5 Digital Alarm Communicator/Transmitter Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions: • • • • • • MS-9200UDLS PN 52750:E1 Line Seizure: takes control of the phone lines disconnecting any premises phones Off/On Hook: performs on and off-hook status to the phone lines Listen for dial tone: 440 Hz tone typical in most networks Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly. Communicate in the following formats: Ademco Contact ID SIA DCS 8 SIA DCS 20 01/27/09 19 Product Description 1.6 Components Main Circuit Board The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main circuit board. See Page Cabinet The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for Canadian installations). Transformer Assembly One 100VA transformer is provided standard with the panel (3.6 amps maximum). An optional 100 VA transformer XRM-24B (XRM-24BE for the MS-9200UDLSE) is Standard available to provide maximum system and XRM-24B(E) accessory power (6.6 amp total). Note that the XRM-24B and XRM-24BE are only suitable for use with MS-9200UDLS(E) with main circuit board number 03611. This circuit board can also be identified by using the software revision of #9200UDV4.0 (meaning version 4.0) or later. 9200xfor.cdr Optional XRM-24B(E) + - 9200batt.cdr Battery Cable P/N 75287 + The MS-9200UDLS cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour require an external charger such as the CHG-75 or CHG-120F and a UL listed battery box such as the BB-55F. Batteries must be ordered separately. - Batteries 1.6.1 Intelligent Addressable Detectors: Newer Series Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The maximum address cannot exceed address 99. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel. These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable detectors. 1.6.2 Intelligent Addressable Modules: Newer Series Reference Manual 20 The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 99. Note that a blinking LED on an addressable module indicates communication between the module and the control panel. MS-9200UDLS PN 52750:E1 01/27/09 Product Description These devices (i.e., MMF-300, MMF-301, MMF-302, CMF-300, CRF-300) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable modules. Refer to the Device Compatibility Document for a list of approved conventional notification and initiating devices. 1.6.3 300 Series Intelligent Addressable Devices Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC Wiring Manual for a list of compatible addressable devices. 1.6.4 Addressable Device Accessories End-of-Line Resistor Assembly The End-of-Line resistors are included with each module. Refer to the specific module documentation for specific information. Power Supervision Relay The UL listed End-of-Line power supervision relay is used to supervise the power to 4wire smoke detectors and notification appliances. EOL-C(R/W) Mounting Plate The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which are required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used for the supervision of a monitor and control module circuit. 1.7 Optional Modules The MS-9200UDLS main circuit board includes option module connectors for the following module: 4XTMF Transmitter Module The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circuit board, must be cut to allow supervision of the module. MS-9200UDLS PN 52750:E1 01/27/09 21 Product Description 1.8 Accessories 1.8.1 PS-Tools Programming Utility The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible computers (PC), running Windows™ XP (or newer). FACP program files can also be created and stored on the PC and then downloaded later to the control panel. The PK-CD Kit includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of the PC to the USB port J12 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem. Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "Remote Site Upload/Download" on page 184). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option. 1.8.2 DP-9692 Dress Panel dp9200udls.cdr An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress panel and the ground stud in the backbox. An optional DP9692-LED dress panel is available for use with the ANN-LED annunciator module. 1.8.3 Trim Ring An optional Trim Ring (P/N TR-CE) is available for the FACP backbox. The Trim Ring provides a finished appearance for a semi-flush mounted panel. 1.8.4 Battery Box BB-26 The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger. The battery box, which is red and is provided with knockouts, was designed specifically to compliment mounting below the FACP. BB-55F The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box. 22 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.8.5 Battery Charger 1.8.5.1 CHG-75 Battery Charger The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information. 1.8.5.2 CHG-120F Battery Charger Reference Manual The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information. 1.8.6 IPDACT- Internet Protocol DACT The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter designed to allow FACP status communication to a Central Station via the internet. No telephone lines are required when using the IPDACT. Using Contact ID protocol from the FACP, the IPDACT converts the standard DACT phone communication to a protocol that can be transmitted and received via the internet. It also checks connectivity between the FACP and Central Station. Refer to the IPDACT Product Installation Document P/N 53109 for additional information. MS-9200UDLS PN 52750:E1 01/27/09 23 Product Description 1.8.7 ANN-BUS Annunciators/Modules WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring. The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due to incompatible serial communication protocols. A variety of optional devices can be connected to the FACP ANN-BUS communication circuit. ANN Series devices can be connected to the ACS (EIA-485) terminals on TB-9. Compatible devices include the following: • ANN-80 LCD Annunciator • ANN-S/PG Serial/Parallel Printer Interface Module • ANN-I/O LED Driver Module • ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs) • ANN-RLED Annunciator Module (red alarm LEDs only) • ANN-RLY Relay Module 1.8.7.1 ANN-BUS Wiring This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B). 1.8.7.1.1 Calculating Wiring Distance for ANN-BUS Modules The following instructions will guide the installer in determining the type of wire and the maximum wiring distance that can be used with FACP ANN-BUS accessory modules. To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the following table: Model Number Worst Case Current Draw ANN-80 LCD Annunciator 0.040 amps ANN-S/PG Serial/Parallel Printer Interface Module 0.040 amps ANN-I/O LED Driver Module 0.200 amps ANN-(R)LED Annunciator Module 0.068 amps ANN-RLY Relay Module 0.075 amps Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp. If current draw exceeds 0.5 amps, refer to "Powering ANN-BUS Devices from Auxiliary Power Supply" on page 27. 24 MS-9200UDLS PN 52750:E1 01/27/09 Product Description After calculating the total worst case current draw, Table 1.1 specifies the maximum distance the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is shown in the note below. Wiring Distance: ANN-BUS Modules to FACP Total Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0.100 1,852 ft. 4,688 ft. * 6,000 ft. *6,000 ft. 0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft. 0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft. 0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft. 0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft. Table 1.1 Wiring Distances Note: The following formulas were used to generate the wire distance chart: Maximum Resistance (Ohms) = Maximum Wire Length (feet) (6,000 feet maximum) 6.0 Volts Total Worst Case Current Draw (amps) Maximum Resistance (Ohms) Rpu *500 where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below) Wire Gauge 22 18 16 14 Ohms per 1,000 feet (Rpu) 16.2 6.4 4.02 2.54 Exception: When using the ANN-RLY module, the installer must ensure that the maximum 24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations: Wire Gauge 18 16 14 12 MS-9200UDLS PN 52750:E1 01/27/09 Maximum Wire Length 312 feet 497 feet 787 feet 1,250 feet 25 Product Description Wiring Distance Calculation Example: Suppose a system is configured with the following ANN-BUS modules: • 3 ANN-80 Remote Fire Annunciators • 1 ANN-S/PG Serial/Parallel Printer Interface Module The total worst case current is calculated as follows: ANN-80 Current Draw = 3 X 0.040 amps = 0.120 amps ANN-S/PG Current Draw = 1 X.0.040 amps = 0.040 amps Total Worst Case Current Draw = 0.160 amps Using this value and referring to the Wiring Distance Table 1.1 on page 25, it can be found that the available options are: 926 feet maximum using 22 Gauge wire 2,344 feet maximum using 18 Gauge wire 3,731 feet maximum using 16 Gauge wire 5,906 feet maximum using 14 Gauge wire 1.8.7.1.2 Wiring Configuration Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices. 24 VDC nonresettable ANN-BUS Device ANN-BUS/ACS BUS 92udlstoann80.cdr ANN-BUS and power wiring are supervised and power-limited MS-9200UDLS Figure 1.3 FACP wiring to ANN-BUS Device 26 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.8.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply Figure 1.4 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as the FCPS-24FS6/8, when the total ANN-BUS power requirements exceed the panel’s DC Power Output capability. Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults) ANN-BUS and power wiring are supervised and power-limited ANN-BUS -24 VDC +24 VDC nonresettable ANN-BUS/ACS BUS FCPS-24FS6/8 92udlstofcptoann.cdr ANN-80 MS-9200UDLS Figure 1.4 Powering ANN-BUS Devices from FCPS-24FS6/8 1.8.7.2 ANN-BUS Device Addressing Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the FACP. A 5-position DIP switch on each device is used to set this address. The address set for these devices must also be programmed at the FACP for the specific device (refer to the programming section titled "ANN-BUS Options" on page 118). A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device addresses do not need to be sequential and can be set to any number between 01 and 08. Note that 00 is not a valid address. The following table shows the DIP switch setting for each address. Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions. Unless otherwise specified in the documentation supplied with each device, switch positions 6 and above must be set to OFF. Address not valid 01 02 03 04 05 06 07 08 Switch 5 OFF OFF OFF OFF OFF OFF OFF OFF OFF Switch 4 OFF OFF OFF OFF OFF OFF OFF OFF ON Switch 3 OFF OFF OFF OFF ON ON ON ON OFF Switch 2 OFF OFF ON ON OFF OFF ON ON OFF Switch 1 OFF ON OFF ON OFF ON OFF ON OFF Note: Switch 5 must be set to OFF for ANN-BUS devices to be recognized. MS-9200UDLS PN 52750:E1 01/27/09 27 Product Description 1.8.7.3 ANN-80 Remote Fire Annunciator The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics the display on the control panel and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the annunciator is capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, filtered, power supply. The function buttons, keyswitch and piezo sounder may be individually enabled and disabled through the FACP software. Refer to "ANN-80 Options" on page 130 for a description of this feature and programming information. Note that if the keyswitch is enabled and remains in the unlocked position for more than two minutes without any buttons being pressed on the annunciator, a trouble indication will be annunciated. 1.8.7.3.1 Specifications • Operating Voltage Range: 18 VDC to 28 VDC • Current Consumption @ 24 VDC nominal (filtered and nonresettable): Normal/Standby (no activity): 37.0 mA Trouble: 39.0 mA Alarm: 40.0 mA AC Fail ( not backlit): 15.0 mA • For use indoors in a dry location 1.8.7.3.2 Installation Ensure that all power (AC and DC) has been removed from the FACP before installing the annunciator. 1.8.7.3.3 Mounting The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box. Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and mount the annunciator in or on the wall depending on the type of installation desired. The ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator to the electrical box/wall. The cover cannot be reattached or removed after the annunciator has been mounted. 1.8.7.3.4 Opening/Closing Annunciator The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to figure below): 1. Turn the key switch to the ON (Unlocked) position by turning the key counterclockwise 2. Push in the snap latch located on the right side of the unit while pulling the cover open 3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut 4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key 28 MS-9200UDLS PN 52750:E1 01/27/09 Product Description Annunciator cover with LCD display Annunciator backplate Press in latch and pull annunciator cover open Key switch shown in ON position 1.8.7.3.5 Wiring ANN-80 to FACP The following steps can be used as a guide to wire the annunciator. Make certain all power has been removed from the FACP prior to annunciator installation. 1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal block TB1 wiring channel wires TB1 2. Remove appropriate amount of wire insulation 3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B). Make certain to connect A to A and B to B 4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals 3 & 4. Make certain to connect A to A and B to B 5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+). Make certain to observe proper polarity 6. If appropriate, connect the power wiring going to the next device to terminals 1 (-) & 2 (+). Make certain to observe proper polarity 7. After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any excess wire pushed back through hole into electrical box MS-9200UDLS PN 52750:E1 01/27/09 29 Product Description ANN-BUS and power wiring are supervised and power-limited ANN-BUS 24 VDC nonresettable 92udlstoann80.cdr ANN-BUS/ACS BUS ANN-80 FACP Figure 1.5 ANN-80 Wiring to FACP The following table shows the ANN-80 connections to the MS-9200UDLS MS-9200UDLS Terminal GND (-) on TB1 Terminal PWR (+)TB1 Terminal ACS on TB9 Terminal ACS on TB9 ANN-80 (TB1) Terminal 1 (-) Terminal 2 (+) Terminal 3 (A) Terminal 4 (B) Programming Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must added to the system via FACP programming. Refer to the programming section titled "ANN-BUS Options" on page 118 in this manual for detailed programming information. Select the LCD option for programming. Trouble Response If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN80 will indicate a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will provide no indication of an ANN80 trouble. To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the ANN-80 at the FACP. 30 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.8.7.4 ANN-S/PG Serial/Parallel Interface Installation The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mounting. Proceed with the installation as described in the following: 1. Ensure that all power (AC and DC) has been removed from the FACP. 2. Connect the ANN-S/PG to the FACP as illustrated in Figure 1.6 Parallel ANN-BUS and power wiring are supervised and power-limited Cable Connectors for connection to printer Serial ANN-S/PG Module 24 VDC nonresettable MS-9200UDLS Figure 1.6 ANN-S/PG Connection to FACP 92udlstospg.cdr ANN-BUS/ACS BUS 3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module 4. Select the address and configuration options for the ANN-S/PG module as described in the Programming section of this manual (refer to "ANN-BUS Options" on page 118) Note that the Auto-configure feature allows the programmer to quickly bring all installed ANN-BUS modules online (refer to "Auto-Configure" on page 128) 5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 1.6). Only one printer can be connected. 1.8.7.4.1 Specifications • Operating Voltage: 24 VDC • Current (Alarm and Standby): 45 mA • Ambient Temperature: 32oF to 120oF (0oC to 49oC) • Max. Wiring Distance from FACP: 6,000 ft. (1,800 m) • Mounting: Surface • Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D) • For indoor use in a dry location only 1.8.7.4.2 PRN-6F Printer Installation When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes within the control panel and time-stamps the printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section contains information on connecting a printer to the control panel and setting the printer options. MS-9200UDLS PN 52750:E1 01/27/09 31 Product Description 1.8.7.4.2.1 Connecting PRN-6F Printer Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as a standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may be used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details. Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the same time. 1.8.7.4.2.2 Setting Printer Options Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer menu controls. Set the printer options (under the menu area) as shown in the following table: Table 1.2 PRN Setup Options Option Font LPI ESC Character Bidirectional Copy CG-TAB Country Auto CR Color Option Formien Lines Standard 32 Setting HS Draft 6 LPI ESC ON Graphic E-US ASCII OFF Not Installed 6LPI=60 Exec 10.5 Option CPI Skip Emulate I/O Buffer Serial Baud Format Protocol Character Set SI.Zero Auto LF PAPER BIN 1 BIN 2 SINGLE PUSH TRA PULL TRA PAP ROLL Setting 10CPI 0.5 Epson FX-850 40K 9600 or 2400 7 Bit, Even, 1 Stop XON/XOFF Standard On On 12/72” 12/72” 12/72” 12/72” 12/72” 12/72” MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.8.7.5 ANN-I/O LED Driver Module The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic enclosure for mounting inside the annunciator or accessory box. The following sections describe hardware installation. Refer to the section titled "ANN-BUS Options" on page 118 for programming information. 1.8.7.5.1 ANN-I/O Board Layout Figure 1.7 illustrates the ANN-I/O board showing locations of screw terminals for connection to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID number. Terminals not used (future) ann-IObrd.cdr ANN-BUS (ID#) Address DIP switch ANN-BUS Connector Figure 1.7 ANN-I/O Board Layout 1.8.7.5.2 Specifications • Max. ANN-BUS Voltage: 28 VDC • Max. Current: Alarm: 200 mA Standby: 35 mA Each LED: 10 mA MS-9200UDLS PN 52750:E1 • Operating Temperature: 32oF to 120oF (0oC to 49oC) • For indoor use in a dry location only 01/27/09 33 Product Description 1.8.7.5.3 ANN-I/O Connection to FACP The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 1.8. After the ANN-I/O is connected to the panel, it must be added to the system via FACP programming. Refer to the section titled "ANN-I/O Options" on page 120. ANN-I/O Module ANN-BUS/ACS BUS ANN-BUS and power wiring are supervised and power-limited 92udlstoannio.cdr 24 VDC nonresettable MS-9200UDLS Figure 1.8 ANN-I/O Connection to FACP 1.8.7.5.4 ANN-I/O Module LED Wiring There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10 LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so that there is approximately 10 mA of current for each LED. No series resistors are required. LED outputs can be mapped to output circuits. Refer to the programming section titled "ANN-I/O Options" on page 120 of this manual. The LEDs are wired as illustrated in Figure 1.9. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40). 34 MS-9200UDLS PN 52750:E1 01/27/09 Figure 1.9 ANN-I/O Board Layout annI-Oleds.cdr Product Description 1.8.7.6 ANN-LED Annunciator Module The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general system faults and input zones/points when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. The ANN-LEDR provides alarm (red) indication for up to 30 input zones or addressable points. Multiple ANN-(R)LED modules may be used for full system coverage. MS-9200UDLS PN 52750:E1 01/27/09 35 Product Description 1.8.7.6.1 ANN-LED Board Layout Figure 1.10 illustrates the ANN-LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number. ANN-BUS (ID#) Address DIP switch ANN-BUS Connector Figure 1.10 ANN-LED Board Layout 1.8.7.6.2 Specifications • Max. ANN-BUS Voltage: 24 VDC • Max. Current: Alarm: 68 mA Standby: 28 mA • Operating Temperature: 32o F to 120o F (0o C to 49o C) • For indoor use in a dry location only 1.8.7.6.3 Mounting/Installation The ANN-LED Module is supplied mounted to the DP-9692LED Dress Panel. Install the dress panel as described in the documentation supplied with the DP9692LED. 36 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.8.7.6.4 ANN-LED Connection to FACP Figure 1.10 illustrates the ANN-LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number. ANN-LED ANN-BUS and power wiring are supervised and power-limited +24 VDC -24 VDC ANN-BUS/ACS BUS MS-9200UDLS Figure 1.11 ANN-LED Connection to FACP MS-9200UDLS PN 52750:E1 01/27/09 37 Product Description 1.8.7.7 ANN-RLY Annunciator Module The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP. 1.8.7.7.1 ANN-RLY Board Layout Figure 1.10 illustrates the ANN-RLY board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number. ANN-BUS (ID#) Address DIP switch ANN-BUS Connector Figure 1.12 ANN-RLY Board Layout 1.8.7.7.2 Specifications • Operating Voltage: 24 VDC • Max. Current: Alarm: 75 mA Standby: 15 mA • Operating Temperature: 32o F to 120o F (0o C to 49o C) • For indoor use in a dry location only 1.8.7.7.3 Mounting/Installation The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis. Refer to documentation supplied with the relay module. 38 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.8.7.7.4 ANN-RLY Connection to FACP Figure 1.13 illustrates the ANN-RLY board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number. ANN-RLY ANN-BUS and power wiring are supervised and power-limited ANN-BUS/ACS BUS +24 VDC -24 VDC FACP Figure 1.13 ANN-RLY Connection to FACP 1.8.7.8 ANN-BUS Audio Panel Control WARNING! Disconnect all sources of power (AC and DC) before installing or removing any wiring. The FACP is capable of providing automated activation of the ACC-25/50(ZS/T) zoned system speaker circuits. To do this, the FACP must be enabled to communicate with the ACC-25/50ZS Audio Panel over the ANN-BUS (refer to "ANN-BUS Enabled" on page 118). This is accomplished by programming the Audio Panel ANN-BUS address into the FACP (refer to "Modules Installed" on page 118). For details on setting the ANN-BUS address and programming the audio panel, refer to the ACC-25/50ZS Series Audio Panel manual (document #51889). The ACC-25/50ZS Series audio panel connects to the FACP via the ACS/ANNBUS communication circuit. Zones 33 - 56 on the FACP correspond to the ACC25/50ZS Series audio circuits 1 - 24. Zone 32 on the FACP serves as the All-Call zone and will activate all audio panel output circuits. The programmer can select which of the five audio messages at the audio panel will play when an FACP input zone goes into alarm (refer to "Zone Message" on page 96). The message will play over the corresponding audio panel output circuit. MS-9200UDLS PN 52750:E1 01/27/09 39 Product Description Examples: • • • • FACP Input programmed to Zone 33 goes into alarm, the programmed message for Zone 33 [Message 1, 2, 3, 4 or 5] will play over the ACC-25/50ZS Series output circuit 1 which corresponds to FACP Zone 33. FACP Input programmed to Zone 1 and Zone 34 (Zone 1 is programmed for a Message [1, 2, 3, 4 or 5] and Zone 34 is programmed for No Message) goes into alarm, the programmed message for Zone 1 will play over the ACC-25/50ZS Series output circuit 2 which corresponds to FACP Zone 34. If two or more input zones are active at the same time, the highest priority message will turn on (Message 1 is highest priority and Message 5 is lowest) and play over the corresponding audio panel output circuit(s). Zone 32 is an All-Call zone. All audio panel output circuits will turn on if Zone 32 is activated and its programmed message will play (or the highest priority message currently being played). A fault at the ACC-25/50ZS Series panel will cause the FACP to indicate a System Trouble and the display will indicate a Voice Evac Fault. The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of communication wires connected between the A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals 2 & 3 of the ACC-ZPMK module on the audio panel. ACC-ZPMK on ACC-25/50ZS Series A (+) B (-) ANN-BUS FACP Figure 1.1 FACP Connection to ACC-25/50ZS Series Audio Panel 40 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.8.8 Legacy ACS Series LED Zone Type Annunciators WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring. The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due to incompatible serial communication protocols. The legacy ACS Series Annunciators remotely display alarm and trouble status as well as system status. In addition, they can provide remote Acknowledge, Silence, Reset and Drill functions. For more detailed information, refer to the appropriate annunciator manual. Following is a list of annunciators which can be used with the MS9200UDLS. Reference Manual • • • • ACM-16ATF* Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs ACM-32AF* Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32 red LEDs * In Canada, the color red must be used to indicate active alarm inputs. Yellow indicates supervisory, burglary or trouble signals. Green indicates the presence of power, or an activated output. LCD-80F Remote Fire Annunciator Reference Manual The LCD-80F annunciator is an 80-character backlit LCD remote fire annunciator that is capable of displaying English language text. Communications between the control panel and the annunciator is accomplished over a serial interface employing the EIA485 communication standard. Up to 32 LCD-80F annunciators may be connected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote UL listed filtered power supply such as the FCPS Series. For more detailed information, refer to the LCD-80F manual. LDM Series Lamp Driver Modules (Graphic Annunciator) The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. Legacy ACM-8RF Relay Control Module Reference Manual The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps. 1.9 Getting Started The following is a brief summary of the minimal steps involved in bringing an MS9200UDLS on-line: MS-9200UDLS PN 52750:E1 • Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page 45) • Address and Install Intelligent Devices (refer to the SLC Wiring Manual) • Enter Autoprogramming (refer to "Autoprogram" on page 64) • Resolve Programming Conflicts • Go to Point Program to Enter Specific Data (refer to "Point Program" on page 65). Use the right and left arrow keys to navigate between devices. 01/27/09 41 Product Description 1.10 Telephone Requirements and Warnings 1.10.1 Telephone Circuitry Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area. 1.10.2 Digital Communicator Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact: Manufacturer: Fire•Lite Alarms, Inc. One Fire-Lite Place Northford, CT 06472 (203) 484-7161 Product Model Number: MS-9200UDLS FCC Registration Number: US:1W6AL11B9200UDLS Ringer Equivalence: 1.1B Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company. Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to "Digital Communicator" on page 54 for an illustration of the proper installation of this equipment. Important! The DACT must not be used to dial a phone number that is call-forwarded . 42 MS-9200UDLS PN 52750:E1 01/27/09 Product Description 1.10.3 Telephone Company Rights and Warnings The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions. If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary. DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES. When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line. The control panel must be connected to the public switched telephone network upstream (as first device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant. MS-9200UDLS PN 52750:E1 01/27/09 43 Product Description 1.10.4 For Canadian Applications The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the users’s satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas. CAUTION Users should not attempt to make such connections themselves, but should contact the appropriate electric inspections authority, or electrician. “The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.” DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.” Representative: NOTIFIER/FIRE•LITE, CANADA 10 Whitmore Road Woodbridge, Ontario L4L 7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687 IC Certificate Number: Ringer Equivalence Number (REN): 1.3B Load Number: 2 44 MS-9200UDLS PN 52750:E1 01/27/09 Installation Installation SECTION 2 The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems. 2.1 Mounting Backbox ! The circuit board contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies. To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly inside the supplied anti-static bag and store in a safe location until it can be reinstalled in the backbox. Mark and predrill hole in the wall for the center top keyhole mounting bolt using the dimensions illustrated in Figure 2.3 on page 47 See Page Install center top fastener in the wall with the screw head protruding Place backbox over the top screw, level and secure Mark and drill the left and right upper and lower mounting holes Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting Install remaining fasteners and tighten Main Circuit Board on chassis mounting studs 92udchassisinbox.cdr mounting slots grounding stud Backbox Figure 2.1 MS-9200UDLS Chassis Removal MS-9200UDLS PN 52750:E1 01/27/09 45 Installation 2.2 Mounting Optional Transformer/Remounting Chassis One XRM-24B(E) transformer is supplied standard with the control panel. An optional second XRM-24B(E) transformer can be ordered and installed to provide maximum system power. Install the transformers in the locations indicated in the following illustration. 6. The standard transformer is premounted to the chassis. If the optional second transformer has been ordered, mount it to the chassis as illustrated below. The chassis does not need to be removed to install the optional transformer. 7. When the location is dry and free of construction dust, install the chassis/ transformer/circuit board assembly. 8. Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the backbox, then position the two mounting hole tabs over the studs with nuts located in the upper portion of the backbox. 9. Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by pressing the chassis down. 10. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top, and to ensure proper grounding, use a 3/8” nut driver or socket. 11. If the main circuit board is not already attached to the chassis, install it by positioning the ten mounting holes over the studs on the chassis and secure with the supplied screws. 12. Connect the Standard XRM-24B(E) Transformer plug to Transformer 1 Connector J10 on the FACP main circuit board 13. Connect the Optional XRM-24B(E) Transformer plug to Transformer 2 Connector J11 on the FACP main circuit board. 14. Complete the installation as detailed in the following sections. Optional XRM-24B(E) Transformer Installation Optional XRM-24B(E) Transformer mounting slot Slide top flange of XRM-24B(E) into slot at top left of chassis. Standard XRM-24B(E) Transformer Mounting Studs Slide bottom flange of XRM-24B(E) into transformer mounting slot. Mounting Slot XRM-24B(E) will remain securely in place after bottom flange has been seated. Figure 2.2 MS-9200UDLS Main Board/Chassis Installation 46 MS-9200UDLS PN 52750:E1 01/27/09 Installation Semi-Flush Mounting Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box. Hinge Slot for optional Dress Panel Mounting slots for optional Trim Ring Semi-flush mounting hole 9050udencl.cdr Hinge Slot for optional Dress Panel Figure 2.3 MS-9200UDLS Cabinet Mounting MS-9200UDLS PN 52750:E1 01/27/09 47 9050udcab.cdr Installation Figure 2.4 MS-9200UDLS Cabinet Dimensions An optional Trim Ring (P/N TR-CE-) is also available for semi-flush mount installations. 48 MS-9200UDLS PN 52750:E1 01/27/09 Installation 2.3 Power WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized. 2.3.1 AC Power and Earth Ground Connection Primary power required for the FACP is 120 VAC, LCD DISPLAY J4 J1 60 Hz, 3.0 amps for the MS-9200UDLS or 240 VAC, 50 Hz, 1.5 amps for the MS-9200UDLSE. TB11 Overcurrent protection for this circuit must comply J9 with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00 - + HOT NEUT EARTH BATTERY mm2) or larger wire with 600 volt insulation rating. Make certain that the AC mains circuit breaker is off before wiring any connections between the mains and the control panel. Connect wiring from the AC mains to TB11 on the FACP, being careful to observe proper connections. Connect a wire from the grounding stud in the cabinet to a known solid earth ground in the building. Refer to Figure 2.1 on page 45 for location of the stud. This connection is vital for maintaining the control panel’s immunity to unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be applied to the panel before installing the battery interconnect cable (refer to the following section). 2.3.2 Battery Power Interconnect Cable Before connecting the batteries to the FACP, make + certain that the interconnect cable between the batteries is not connected. Do not connect the interconnect cable until the system is completely installed. Observe polarity when connecting the batteries. Connect the battery cable to J9 on the main circuit board. Refer "Power Supply Calculations" on page 187, for calculation of the correct battery rating. - + See Page WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention. 2.3.3 Special Application DC Power Output Connection All Special Application DC power outputs are power-limited (refer to "UL Powerlimited Wiring Requirements" on page 53). Power-limited Resettable or Nonresettable Power 0.300 amperes max., 24 VDC nominal filtered, resettable or nonresettable power can be drawn from TB1 Terminals 1(+) and 2(-) JP4 TB1 92udtb1.cdr JP4 is used to configure TB1, Terminals 1 & 2 for: • Nonresettable Power - jumper pins 1 and 2 of JP4 as shown • Resettable Power - jumper pins 2 & 3 of JP4 Power-limited Resettable Power 0.300 amperes max., 24 VDC nominal filtered, resettable power can be drawn from TB1 Terminals 3(+) and 4(-) Figure 2.5 Special Application Power Outputs - 24 VDC MS-9200UDLS PN 52750:E1 01/27/09 49 Installation 2.4 Relays The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive). Note that relay connections may be power-limited or nonpower-limited, provided that 0.25” spacing is maintained between conductors of power-limited and nonpowerlimited circuits. Refer to UL Power-limited wiring requirements. TB7 TB5 TB6 92udreyp.cdr Note that the programmable relay labeled as Relay 1 is factory default programmed as Alarm and programmable Relay 3 is factory default programmed as Supervisory. The relay labeled Relay 2 is fixed as a Trouble relay and cannot be changed. It is a fail-safe relay which will transfer on any trouble or total power failure. Relay contacts shown with power applied to panel and no active troubles, alarms or supervisories Figure 2.6 Relay Terminals 2.5 Notification Appliance Circuits See Page Reference Manual The control panel provides four Style Y (Class B) or two Style Z (Class A) NACs (Notification Appliance Circuits). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to "Calculating the System Current Draw" on page 188). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device Compatibility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be expanded via the FCPS Series field charger/power supplies. The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the MS-9200UDLS main circuit board. The NACs are configured for Style Y (Class B) from the factory. Refer to "Configuring NACs" on page 51 for information on changing the NAC configuration to Style Z (Class A). 50 MS-9200UDLS PN 52750:E1 01/27/09 Installation 2.5.1 Configuring NACs The Notification Appliance Circuits on the main circuit board are configured for Style Y (Class B) or Style Z (Class A) by properly orienting the NACKEY card in JP6 which is located at the top of the main circuit board near the NAC terminal blocks TB3 and TB4. The default configuration is for Style Y (Class B). Refer to Figure 2.7 for information on installing the NACKEY card. • Style Z (Class A) - install NACKEY into JP6 with Class A pointing down toward circuit board as illustrated to the right. • Style Y (Class B) - install NACKEY into JP6 with Class B pointing down toward circuit board . NACKEY Card NACKEY -PCA CLASS B Key CLASS A NACKEY -PCA Key-slot 92nackey.cdr NACKEY must be inserted with text side facing in toward center of main circuit board and key into keyslot as illustrated to the right. It is keyed to prevent incorrect insertion. JP6 Top edge of MS-9200UDLS Main Circuit Board TB3 TB4 NACKEY card slot JP6 Figure 2.7 NAC Configuration Using NACKEY 2.5.2 Style Y (Class B) NAC Wiring 4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7 kΩ, ½ watt P/N:71252 UL listed NAC 4 NAC 3 NAC 2 Polarized Bells + + + + Polarized Strobes + + + + Polarized Horns + + + + Notification Appliance Circuit polarity shown in alarm state circuit number TB3 B B B B + + - 1 3 3 1 B B B B + + - 2 4 4 2 Polarized Bells Polarized Strobes Polarized Horns Dummy Load all unused circuit 9200nacy.cdr NAC 1 TB4 Figure 2.8 NAC Style Y (Class B) Wiring MS-9200UDLS PN 52750:E1 01/27/09 51 Installation 2.5.3 Style Z (Class A) NAC Wiring 2 Style Z (Class A) Notification Appliance Circuits, supervised and power-limited Polarized Bell + + Polarized Strobe + + + + Polarized Horn NAC 1 Polarized Bell Polarized Strobe Polarized Horn B A A B + + - - B A A B + + - - NAC 2 9200nacz.cdr Notification Appliance Circuit polarity shown in alarm state TB4 TB3 Figure 2.9 NAC Style Z (Class A) Wiring 2.6 Remote Synchronization Output Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard to individuals. Devices connected directly to the control panel’s NACs can be synchronized as described in "Type" on page 106. Notification appliances connected to remote power sources may require synchronization with the FACP’s devices. This can be accomplished by connecting the Remote Synchronization Output from TB2 of the MS-9200UDLS to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics, the signal on NAC1. This allows the devices connected to the power supply to be synchronized with the devices connected to NAC1 on the FACP. The Remote Synchronization Output is power-limited and supervised (refer to "UL Power-limited Wiring Requirements" on page 53). A 4.7 kΩ ELR resistor must be connected to the end of the wiring at the remote power supply. Remote Power Supply Sync Input Remote Sync Output 4.7 kΩ ELR TB3 TB2 TB1 TB4 JP4 FACP main circuit board 1 2 3 + 24V - + 24V NON-RST RST POWER POWER + - REMOTE PWR SUPPLY SYNC B+ A+ A- B1B+ 3B+ 3B- 1B- B+ A+ A- B2B+ 4B+ 4B- 2B- Figure 2.10 Remote Sync Output 52 MS-9200UDLS PN 52750:E1 01/27/09 Installation 2.7 UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-9200UDLS is shown below. Figure 2.11 Typical UL Power-limited Wiring Requirements Power-limited Circuits (Class 2) Power-limited Circuits (Class 2) Nonpower-limited Circuits Nonpower-limited Circuits Power-limited Circuits (Class 2) maintain minimum 0.25” between power-limited and nonpower-limited circuits wiring AC Power Ground Strap Nonpower-limited Circuits Grounding Stud 92udulpw.cdr To Batteries MS-9200UDLS PN 52750:E1 01/27/09 53 Installation 2.8 Digital Communicator Two independent telephone lines can be connected to the control panel. Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the panel's digital communicator be located as the first device on the incoming telephone circuit to properly function. Important! The DACT must not be used to dial a phone number that is call-forwarded. Customer Premises Equipment and Wiring Network Service Provider’s Facilities Computer RJ31X Jack Unused RJ-11 Jack FACP with DACT Telephone Line Telephone Network Demarcation Point Unused RJ-11 Jack Fax Machine Answering System Telephone actadact.cdr Telephone Figure 2.12 DACT Installation The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone lines is required as shown below. Figure 2.13 Wiring Phone Jacks 54 MS-9200UDLS PN 52750:E1 01/27/09 Installation 2.9 Optional Module Installation WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring. MS-9200UDLS Keypad/Display Removal Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to replace the keypad/display or access jumpers JP5 and JP7 or switch SW1, the Keypad/Display can be removed by inserting a Phillips screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and loosening the three mounting screws. Note that it is not necessary to disconnect the cables between the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/Display and rest the unit at the bottom of the main circuit board. Mounting Screw Access Holes 92udbdky.cdr Mounting Screw Access Hole Figure 2.14 Keypad/Display Removal MS-9200UDLS PN 52750:E1 01/27/09 55 Installation 2.9.1 4XTMF Transmitter Module Installation The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service. Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems): Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings: Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9200UDLS. In addition, the System Trouble LED will turn on to indicate the Disconnect condition. Note: The 4XTMF Module is not directly suitable for transmitting a reverse polarity supervisory signal. For applications using reverse polarity of a supervisory signal, refer to "FACP with Keltron" on page 204. }Remote Alarm (power-limited)* }Remote Trouble (power-limited)* } + - + 1 2 3 4 5 + 6 7 * Wiring from these terminals can exit the protected premises. Dummy load terminals No connection 6 and 7 (4.7kΩ, ¼ watt resistor) if Municipal Municipal Box (nonpower-limited)* Box is not connected. Polarities are shown for module activation 4xtmfl.cdr Disconnect LED Disconnect Switch shown in disconnect position TBL Jumper Connect to FACP J10 & J11 Figure 2.15 4XTMF Transmitter Module 56 MS-9200UDLS PN 52750:E1 01/27/09 Installation The following steps must be followed when installing the 4XTMF module: 1. Remove all power (Primary and Secondary) from the FACP before installing 4XTMF 2. Cut jumper JP3 on the main circuit board to allow the control panel to supervise the 4XTMF module 3. Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 on the MS-9200UDLS main circuit board, being careful not to bend any pins 4. Secure 4XTMF module to standoffs with supplied screws. 5. Reapply power to the FACP 6. For proper 4XTMF operation, the output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3 7. When the installation has been complete, enable the 4XTMF module by sliding the disconnect switch to the left 8. Test system for proper operation Standoff Standoff J5 & J6 Connectors FACP main circuit board 92udls4xtm.cdr Cut Jumper JP3 4XTMF Figure 2.16 4XTMF Connectors to MS-9200UDLS Connectors NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module. Relay 3 at TB5 must be programmed as a supervisory relay. Cutting JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens Leaving JP2 in will prevent generation of a trouble if the supervisory contact opens 2.9.2 Printer A serial printer may be connected to TB8 Terminals 1 - 4 on the FACP. The printer can be used to provide a hard-copy printout of real-time events, history file and walktest data. Installation the device requires panel programming to allow the FACP to communicate with the device. MS-9200UDLS PN 52750:E1 01/27/09 57 Installation A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel Interface Module. Refer to "ANN-S/PG Serial/Parallel Interface Installation" on page 31 for installation details. Refer to "ANN-BUS Options" on page 118 for programming information. ! CAUTION! Do not connect a printer or PC to the MS-9200UDLS FACP if a ground fault (zero impedance to ground) exists on the control panel. Circuit damage may result. Remove all power (Primary and Secondary) before installing or removing any wiring. Installation Remote printers and PCs require separate primary power. Also required is the PRT/ PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/ PK-CABLE to TB8 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25 adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines. Apply power to the FACP and printer or PC. Note that a ground fault (zero impedance to ground) may occur on the FACP, dependent on the printer or PC being used, due to this connection. For this reason, it is important that there be no preexisting ground fault on the panel. Note that the printer may or may not be supervised as determined by user programming. Refer to "Printer/PC" on page 142. Figure 2.17 Serial Printer and Computer Connections 92udlstb8.cdr PRT/PK-CABLE Printer Configuration Refer to the documentation supplied with the printer for pertinent information about printer setup. Set the printer’s options as listed in the following table: COMMUNICATION SETUP BUFFER: DATA BITS: PARITY: STOP BIT: BAUD RATE: AUTOMATIC LINE FEED AUTOMATIC CARRIAGE RETURN 58 LARGE 7 EVEN 1 STOP 2400/4800/9600 NO NO MS-9200UDLS PN 52750:E1 01/27/09 Programming Programming SECTION 3 NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below: Program feature Permitted in Settings permitted Possible settings or option UL 864? (Y/N) in UL 864 Refer to "Trouble Call Limit (Dialer Runaway Prevention)" on page 134. Trouble Call Limit Trouble Call Limit N Trouble Call Limit = 0 (factory default): unlimited calling to Central Station for any trouble condition Trouble Call Limit = 1 - 99: limits call for each unique trouble to from 1 to 99 within a 24 hour period Refer to "Remote Site Upload/Download" on page 184. Remote Download Y Remote Download - Proprietary No Remote Download - Proprietary Yes = 0 for unlimited Central Station trouble calls Remote Download Proprietary Yes for Proprietary system intended to protect only contiguous properties 3.1 Programming Data Entry Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the control panel main circuit board. The information presented in this section refers to programming the MS-9200UDLS via the onboard keypad. If an optional computer keyboard is connected to the MS-9200UDLS main circuit board, the following table describes the keyboard keys which correspond to the onboard keypad keys. Keypad Keys 1st Event CLR ESC RECALL * # A-Z 0-9 (on QZ key) — / • ENTER ACK/STEP SILENCE DRILL RESET MS-9200UDLS PN 52750:E1 01/27/09 Computer Keyboard Keys Home Delete Esc Insert * # A-Z 0-9 Space bar — / • Enter F1 F2 F3 F4 59 Programming 3.2 User Programming !! The MS-9200UDLS is completely field programmable and requires no special software skills. While programming the MS-9200UDLS, the fire protection capabilities of the control panel are enabled. Site-specific programming may be accomplished in any of the following ways: • Autoprogramming Feature - This is a convenient method for quickly bringing the FACP addressable SLC devices on-line without the necessity of programming each device individually. Refer to "Autoprogram" on page 64 for a detailed description of Autoprogramming • Manual programming or editing, using the FACP keypad or a PC keyboard • Remote Programming and Editing Feature - allows creation and editing of sitespecific custom programs using a Windows-based computer and modem. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming CD-ROM can be ordered for this purpose • Local Programming and Editing Feature - allows creation and editing of sitespecific custom programs using a Windows-based computer and the FACP USB connection. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming CD-ROM can be ordered for this purpose The System All Normal screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated below: SYSTEM ALL NORMAL 10:00A 012106 Read Status mode can be entered while the panel is in any mode of operation. If an alarm or supervisory event exists at the panel, the event must be cleared before entering Programming mode. To access any of the programming or read status features, the Enter or Mode key must be pressed, which will cause the LCD to display the following: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD See Page Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status Mode which allows the user to view the programmed features and status of the control panel The Read Status feature is not password protected. Refer to "Read Status" on page 168 for a detailed description of this feature. Pressing 2 will select user Programming Mode which may only be accomplished by an authorized person. After pressing 2, a screen will prompt for a password. After entering the correct password, the user may select from a list of programming options. Pressing 3 will select Remote Download which allows the user to enable the remote programming option. Refer to "Remote Site Upload/Download" on page 184. 60 MS-9200UDLS PN 52750:E1 01/27/09 Programming Exit Programming, Read Status The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Note that the data which is entered during Programming mode is not saved until the programmer exits this mode by repeatedly pressing the ‘ESC’ key. If the Reset key is pressed or power is lost before exiting Programming mode, all data just entered will be lost. User Programming Levels There are two user programming levels: • • User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc. User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change. 3.3 Initial Power-up The following sections describe the initial programming procedures for a new system. The same procedures are used to modify programming in an existing system. After completing the wiring of addressable devices to the SLC, apply power to the control panel. If the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and the following trouble message will be displayed. TROUBL IN SYSTEM NO DEVICES INSTALLED 09:03A 012106 3.4 Programming Screens Description See Page The options available when the Enter key is pressed are: Read Status, Programming. The Read Status and Programming options have multiple functions or features which may be chosen. To view all of the choices, it is necessary that the programmer scroll through a number of additional subscreens. These selections are displayed on multiple screens to make them more readable for the programmer. Refer to "Master Programming Level" on page 63, for additional information on the various screens. The title of the main option screen will always be displayed at the top of the subscreens for the programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in the upper right corner of the screen being viewed. The programmer can then press the keypad Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the programmer presses the keypad numerical key corresponding to the desired choice. Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the previous paragraphs, is followed to view all option choices. MS-9200UDLS PN 52750:E1 01/27/09 61 Programming 3.5 Programming and Passwords See Page There are two factory set programming passwords which will access the Programming screens as indicated in the following examples. From either of the screens, access to specific system and device features or programming may be obtained. All user programming entries are stored in nonvolatile memory. The factory set passwords can be changed by the user as described in "Password Change" on page 143. If an invalid password is entered, the blinking cursor will return to the first password character position. To exit Programming or Read Status mode at any time, press the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved. To access user Programming mode, press the Enter or Mode key. The LCD will display the following: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD To enter the user Programming mode, press 2. The display will read as follows: PROGRAMMING ENTER PASSWORD ***** Entering the Master level password (default 00000) will cause the following screen to appear: PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP If the Maintenance level password (default 11111) is entered, the following screen will appear: PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. 62 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6 Master Programming Level When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited. The following display will appear: PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP Programming Screen #1 The down arrow which appears in the display indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen. PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP Programming Screen #2 PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Programming Screen #3 PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK Programming Screen #4 MS-9200UDLS PN 52750:E1 01/27/09 63 Programming 3.6.1 Autoprogram PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP Programming Screen #1 Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which prompts the control panel to poll all devices installed on the SLC loop. The primary purpose of autoprogramming is to allow the installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is poweredup, it should be autoprogrammed. If the system is already programmed and Autoprogram is initiated, the system will only add default values for newly installed devices. When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device installed on the SLC loop. While autoprogramming, the panel will display the following: AUTOPROGRAM AUTOPROGRAMMING! PLEASE WAIT Autoprogram Progress Screen When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop similar to the following display: # OF DET LOOP1 055 # OF MON LOOP1 035 # OF CON LOOP1 030 Autoprogram Result Screen #1 In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control modules installed. Pressing the ESC key will return the display to Programming Screen #1. 64 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6.2 Point Program PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP Programming Screen #1 The Point Program option allows the programmer to add a new addressable device to an SLC loop, delete an existing device from a loop or change the programming for an existing device. Pressing 2, while viewing Programming Screen #1, will select the Point Program option and display the following screen: POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE Point Program Screen 3.6.2.1 Detector Programming Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete or change the programming of an addressable detector. The following screen will be displayed by the control panel: DETECTOR 1=ADD 2=DELETE 3=EDIT Detector Screen 3.6.2.1.1 Add Detector Pressing 1 while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector address to programming: ADD DETECTOR ENTER DETECTOR# *** Add Detector Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005. When the last digit is keyed-in, the following screen will be displayed: DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE(ION) Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the newly added detector. MS-9200UDLS PN 52750:E1 01/27/09 65 Programming When the type has been selected, the following screen will be displayed: ADD DETECTOR DETECTOR# 005 IS ADDED The programmer can continue adding detectors by pressing the ESC key which will return the display to the Add Detector Screen. DETECTOR 1=ADD 2=DELETE 3=EDIT Detector Screen 3.6.2.1.2 Delete Detector Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the programmer to delete a specific detector: DELETE DETECTOR ENTER DETECTOR# *** Delete Detector Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005. When the last digit is keyed-in, the following screen will be displayed: DELETE DETECTOR DETECTOR# 005 IS DELETED The programmer can continue deleting detectors by pressing the ESC key which will return the display to the Delete Detector Screen. 3.6.2.1.3 Edit Detector The programmer can change a detectors existing or factory default programming by pressing 3 in the Detector Screen. The following screen will be displayed: EDIT DETECTOR ENTER POINT ADDRESS *** Edit Detector Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 017. When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device that is installed with a lower address, closest to the selected address, will be displayed. 66 MS-9200UDLS PN 52750:E1 01/27/09 Programming If no detectors have been installed on the loop, the following will be displayed: NO DETECTOR INSTALLED Edit Detector Screen #1 If the selected address has been added to programming, device summary screens will be displayed. These screens allow the programmer to view all device settings at a single glance. Pressing the left or right arrow keys will allow the programmer to rapidly view the devices at the previous or next address (if installed). If a detector (such as a photoelectric detector) with the selected address is not physically installed on the SLC or has a communication fault but the address is programmed in the system, the following screen will be displayed: TROUBL SMOKE(PHOTO)ZNNN * 1D017 Edit Detector Screen #1 If the selected address has been added to programming and a detector (such as a photoelectric detector) with the selected address is physically installed on the SLC and is communicating with the control panel, the following will be displayed: NORMAL SMOKE (PHOTO) ZNNN V 1D017 Edit Detector Screen #1 To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to view the Edit Detector screens. In the preceding example: Normal - indicates that the detector with the selected address is physically installed on the SLC and communicating with the control panel (enabled) - represents the adjective and noun, which have been programmed, describing the location of the displayed device ZNNN - represents the first of five possible software zones that the detector is assigned to (NNN = the three digit zone number from 000 - 099) V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification disabled) 1D017 - represents the Loop, Device type and Device address (1 = SLC Loop, D=Detector and 017 = Detector Address 017) MS-9200UDLS PN 52750:E1 01/27/09 67 Programming The following examples show the editing of a photoelectric smoke detector with address 017, located on the SLC loop: EDIT DETECTOR 1D017 1=ENABLED YES 2=TYPE SMOKE(PHOTO) 3=VERIFICATION OFF Edit Detector Screen #2 EDIT DETECTOR 1D017 1=WALKTEST NO 2=PAS NO 3=PRE-SIGNAL NO Edit Detector Screen #3 EDIT DETECTOR 1D017 1=ZONE ASSIGNMENT 00 ** ** ** ** Edit Detector Screen #4 EDIT DETECTOR 1D017 1=NOUN/ADJECTIVE 2=DESCRIPTION ******************** Edit Detector Screen #5 Enable/Disable Detector EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION Edit Detector Screen #2 68 To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the detector will not be polled by the control panel, preventing the detector from reporting alarms and troubles to the panel. The control panel will display the device type and address which has been disabled and will turn on the Trouble LED and Disable LED. MS-9200UDLS PN 52750:E1 01/27/09 Programming Type EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION To select the type of detector being programmed, press the 2 key while viewing the Edit Detector Screen #2. This will cause the control panel to display the following Detector Type Screens: DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE (ION) Edit Detector Screen #2 Detector Type Screen #1 Pressing the down arrow key will display additional detector types as indicated in the following table. Detector Type Smoke Photo User-Defined-1 Smoke Ion User-Defined-2 Heat Detect User-Defined-3 Smoke DuctP User-Defined-4 Photo w/Heat User-Defined-5 Duct-Superv User-Defined-6 Photo-SupervAR User-Defined-7 ADAPT User-Defined-8 Beam User-Defined-9 Action When Activated Fire Alarm same as previous (Smoke Photo) Fire Alarm same as previous (Smoke Ion) Fire Alarm same as previous (Heat Detect) Fire Alarm same as previous (Smoke DuctP) Fire Alarm same as previous (Photo w/Heat) Supervisory, latching same as previous (Superv DuctP) Supervisory, nonlatching (works only in LiteSpeed) same as previous (Photo-SupervAR) Fire Alarm same as previous (ADAPT) Fire Alarm same as previous (Beam) While viewing either Detector Type screen, select the type of detector being programmed by pressing the corresponding keyboard number key. The display will return to Edit Detector Screen #2 and indicate the selection next to the Type option. Note: If a detector is selected to be a SUPERV DUCTP type, it will function like a supervisory point not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire alarm LED or alarm relay, if the detector senses smoke. Verification See Page Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2 so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle between Verification On and Verification Off. For a detailed description, refer to "Alarm Verification (None or One Minute)" on page 166. Walktest EDIT DETECTOR 1=WALKTEST 2=PAS 3=PRE-SIGNAL Edit Detector Screen #3 MS-9200UDLS PN 52750:E1 The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable a device for the Walktest feature, press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 167. 01/27/09 69 Programming PAS See Page The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation (including alarm relay and communicator) for a period of 15 seconds plus a programmable time of up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose). To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the display reads PAS Yes. Each press of the 2 key will cause the display to toggle between PAS Yes and PAS No. Refer to "Positive Alarm Sequence" on page 165. For example, if a detector with address 005 is to be configured for PAS operation: Select PAS Yes when editing the detector set to address 005 Program the desired zone or zones to be activated by this detector, in this example Z001 Program an output, such as a control module that is to be activated by detector 005 by assigning the same zone to it; in this example Z001 Program an output, such as a control module, for PAS activation by assigning zone Z97 to it. This control module may be connected to a signaling device used to indicate a PAS condition (do not use a Notification Appliance Circuit for this purpose) Enable zones Z001 and Special Purpose Zone PAS 97 and set the PAS delay timer to some value With the preceding program settings, when the detector with address 005 is activated, zone Z97 will cause its associated control module to activate immediately, sounding the connected PAS signaling device. Following the PAS delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition. Note that a detector can be enabled for either PAS or Pre-signal but not both Pre-signal EDIT DETECTOR 1=WALKTEST 2=PAS 3=PRE-SIGNAL Edit Detector Screen #3 See Page The Pre-signal option programs the detector to delay panel activation for a preprogrammed time delay of up to three minutes while allowing for visual verification by a person. Note that the alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be programmed to a control module which may be used to activate a sounder or indicator which the installer designates as a Presignal indication (do not use a Notification Appliance Circuit for this purpose). To enable the Pre-signal feature, press 3 while viewing Edit Detector Screen #3 until the display reads Pre-signal Yes. Each press of the 3 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to "Presignal" on page 164. For example, if a detector with address 005 is to be configured for Pre-Signal operation: Select Pre-signal Yes when editing the detector set to address 005 Program the desired zone or zones to be activated by this detector, in this example Z001 Program an output, such as a control module that is to be activated by detector 005 by assigning the same zone to it; in this example Z001 Program an output, such as a control module, for Pre-signal activation by assigning zone Z98 to it. This control module may be connected to a signaling device used to indicate a Pre-signal condition (do not use a Notification Appliance Circuit for this purpose) 70 MS-9200UDLS PN 52750:E1 01/27/09 Programming Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Presignal delay timer to some value With the preceding program settings, when the detector with address 005 is activated, zone Z98 will cause its associated control module to activate immediately, sounding the connected signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition. Note that a detector can be enabled for either PAS or Pre-signal but not both Zone Assignment EDIT DETECTOR 1=ZONE ASSIGNMENT 00 ** ** ** ** A maximum of five zones can be programmed to each addressable detector. Pressing 1 while viewing Edit Detector Screen #4 displays the following screen: ZONE ASSIGNMENT Z00 Z** Z** Z** Z** Edit Detector Screen #4 Zone Assignment Screen See Page Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zone Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate through the zones and the CLEAR key can be used to quickly clear a zone. Noun/Adjective EDIT DETECTOR 1=NOUN/ADJECTIVE 2=DESCRIPTION ***************** The Noun/Adjective selection allows the programmer to enter specific descriptors about the detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will cause the following screen to be displayed: Edit Detector Screen #5 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9200UDLS PN 52750:E1 01/27/09 71 Programming 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the detector currently being programmed. When an adjective has been selected, it will appear at the top of the display as indicated by the asterisks. ********************** 1=NORTH 2=SOUTH 3=EAST ********************** 1=3RD 2=4TH 3=5TH Adjective Screen #1 Adjective Screen #5 ********************** 1=WEST 2=FRONT 3=CENTER ********************** 1=FLOOR1 2=FLOOR2 3=FLOOR3 Adjective Screen #2 Adjective Screen #6 ********************** 1=REAR 2=UPPER 3=LOWER Adjective Screen #3 ********************** 1=FLOOR4 2=FLOOR5 3=ROOM Adjective Screen #7 ********************* 1=MAIN 2=FIRST 3=2ND Adjective Screen #4 72 MS-9200UDLS PN 52750:E1 01/27/09 Programming 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the detector currently being programmed. When a noun has been selected, it will appear at the top of the display as indicated by the asterisks. ********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM Noun Screen #1 ********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM Noun Screen #2 ********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR Noun Screen #3 ********************** 1=GARAGE 2=HALLWAY 3=HVAC RM Noun Screen #4 MS-9200UDLS PN 52750:E1 01/27/09 ********************** 1=KITCHEN 2=LOBBY 3=OFFICE Noun Screen #5 ********************** 1=PATIENT 2=RESTROOM 3=ROOM Noun Screen #6 ********************** 1=STAIRWAY 2=STOREROOM 3=WING Noun Screen #7 ********************** 1=ZONE Noun Screen #8 73 Programming Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns which have been programmed into the control panel using the PS-Tools utility. These descriptors are selected as described in the previous sections. 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Description EDIT DETECTOR 1=NOUN/ADJECTIVE 2=DESCRIPTION The Description selection allows the programmer to enter additional information about the detector currently being programmed. This information will be displayed as part of the device label on the display. Pressing 2 while viewing Edit Detector Screen #5 will cause the following screen to be displayed: Edit Detector Screen #5 DESCRIPTION 1D002 NOUN/ADJECTIVE ******************** Adjective/Noun Screen A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the display along with the standard device label information. A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 2, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Detector Screen #5, displaying the new information at the bottom of the screen. Recall/Increment Function In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Description, Adjective or Noun field as follows: 74 • If the zero key is pressed, a 0 is placed in the first letter position • If the zero key is then pressed a second time with no intervening key actions, the entire field is replaced with the field entered for the previous device programmed, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by-letter • If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one. If the last character is a letter, it changes to a 0. If the last character is 9 it goes to 0 • The above increment function may be repeated with each press of the zero key MS-9200UDLS PN 52750:E1 01/27/09 Programming As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows: 1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3 2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field 3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305 4. Press the right arrow key to advance the zone field 5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones 3.6.2.2 Module Programming POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or change the programming of an addressable module. The following screen will be displayed by the control panel: Point Program Screen #2 MODULES 1=ADD 2=DELETE 3=EDIT Modules Screen 3.6.2.2.1 Add Module Pressing 1 while viewing the Modules Screen will display the following screen which allows the programmer to add a new module address to programming: ADD MODULE ENTER MODULE# *** Add Module Screen #1 A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 005. When the last digit is keyed-in, the following screen will be displayed: ADD MODULE 1=CONTROL 2=MONITOR Add Module Screen #2 Pressing 1 for Control Module or 2 for Monitor Module will cause the following MS-9200UDLS PN 52750:E1 01/27/09 75 Programming screen to be displayed: ADD MODULE MODULE# 005 IS ADDED Add Module Screen #3 The programmer can continue adding modules by pressing the ESC or left arrow key which will return the display to the Add Module Screen #1. MODULES 1=ADD 2=DELETE 3=EDIT Modules Screen 3.6.2.2.2 Delete Module Pressing 2 in the Modules Screen will display the Delete Module Screen which allows the programmer to delete a specific module: DELETE MODULE ENTER MODULE# *** Delete Module Screen A flashing cursor will appear in the position of the first asterisk to the left. Using the panel keypad, key in the module address such as 005. When the last digit is keyed in, the following confirmation that the module has been deleted will be displayed: DELETE MODULE MODULE# 005 IS DELETED 3.6.2.2.3 Edit Module Screen for Monitor Module The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed: EDIT MODULE ENTER MODULE ADDRESS *** Edit Module Screen 76 MS-9200UDLS PN 52750:E1 01/27/09 Programming A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 012. When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device that is installed with a lower address, closest to the selected address, will be displayed. If no modules are installed on the loop, the following screen will be displayed: NO MODULE INSTALLED Edit Module Screen If the selected address has been added to programming but a module (such as a monitor module) with the selected address is not physically installed on the SLC or has a communication fault, the following screen will be displayed: TROUBL MONITOR ZNNN * 1M012 If the selected address has been added to programming and a module (such as a monitor module) with the selected address is physically installed on the SLC and is communicating with the control panel, the following screen will be displayed: NORMAL MONITOR ZNNN W 1M012 To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Monitor screens. In the preceding example: Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the control panel (enabled) - represents the adjective and noun, which have been programmed, describing the location of the displayed device ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the two digit zone number from 000 - 099) 1M012 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module and 012 = Module Address 012) W or * - indicates whether or not the device is programmed for Walktest (W = programmed for walktest, * = not programmed for walktest). MS-9200UDLS PN 52750:E1 01/27/09 77 Programming See Page If the selected address corresponds to a control module, a screen displaying information about the control module with the selected address will be displayed as shown in "Edit Module Screen for Control Modules" on page 85. If the selected address corresponds to a monitor module, a screen displaying information about the module with the selected address will be displayed as illustrated in the following: NORMAL MONITOR ZNNN 1M012 EDIT MONITOR 1M012 1=ENABLED YES 2=TYPE MONITOR Edit Monitor Screen #2 EDIT MONITOR 1=PRE-SIGNAL 1M012 NO Edit Monitor Screen #3 EDIT MONITOR 1M012 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** ** Edit Monitor Screen #4 EDIT MONITOR 1M012 1=ADJECTIVE/NOUN 2=DESCRIPTION ******************** Edit Monitor Screen #5 78 MS-9200UDLS PN 52750:E1 01/27/09 Programming Enable/Disable Module To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from reporting alarms and troubles to the panel. The control panel will indicate a system trouble condition and the Disable LED with turn on if any devices are disabled. EDIT MONITOR 1=ENABLED 2=TYPE MONITOR Edit Monitor Screen #2 Type Monitor Using the PK-CD Upload/Download utility program, unique user-defined monitor types can be created and loaded into the FACP for later use. The FACP response to the activation of a user-defined type is the same as most previous standard types in the list, thus allowing a variety of user-defined types and responses. To select the type of monitor module being programmed, press the 2 key while viewing the Edit Monitor Screen #2. This will cause the control panel to display the following Monitor Type Screens: MONITOR TYPE 1=PULL-STATION 2=USER-DEFINED-1 3=WATERFLOW Monitor Type Screen #1 Pressing the down arrow key will display additional Monitor Type screens. While viewing one of the Monitor Type screens, select the type of monitor module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which will show the new type selection. Table 3.1 on page 80 lists the Monitor Types and their respective functions. MS-9200UDLS PN 52750:E1 01/27/09 79 Programming Monitor module type selection will affect the function of the point as follows: Table 3.1 Monitor Types Monitor Type Pull-Station User-Defined-1 Waterflow User-Defined-2 Monitor User-Defined-3 Future Future Smoke-Conventional User-Defined-5 Heat-Conventional User-Defined-6 Medic-Alert 3 User-Defined-7 Hazard-Alert3 User-Defined-8 Tornado-Alert3 User-Defined-9 Phone User-Defined-10 Tamper User-Defined-11 Supervisory User-Defined-12 Supervisory-AR1 User-Defined-13 HVAC OVRRIDE2 Power-Monitor User-Defined-14 Trouble-Monitor User-Defined-15 Process-Monitor3 User-Defined 16 Process-Monitor-AR1, 3 User-Defined-17 Future Future Ack-Switch Sil-Switch Reset-Switch Drill-Switch PAS-Bypass HVAC RESTART2 Drill-Switch-AR1 Action When Activated Fire Alarm same as previous (Pull-Station) Fire Alarm Delayed same as previous (Waterflow) Fire Alarm same as previous (Monitor) not used not used Fire Alarm same as previous (Smoke-Conventional) Fire Alarm same as previous (Heat-Detector) Supervisory, latching same as previous (Medic-Alert) Supervisory, latching same as previous (Hazard-Alert) Supervisory, latching same as previous (Tornado-Alert) Active Phone (LCD display only) same as previous (Phone) Supervisory, nonlatching (tracking) same as previous (Tamper) Supervisory, latching same as previous (Supervisory) Supervisory, nonlatching (tracking) same as previous (Supervisory-AR) Switch Supervisory, nonlatching (tracking) Power Fault same as previous (Power Monitor) Trouble same as previous (Trouble Monitor) Piezo same as previous (Process-Monitor) Piezo, nonlatching (tracking) same as previous (Process-Monitor-AR) not used not used Acts like panel Acknowledge Key Acts like panel Silence Key Acts like panel Reset Key Acts like panel Drill Key PAS Disable Switch (see note 2) Acts like panel Drill Key, nonlatching (tracking) Note: 1. For entries ending in AR, AR refers to AutoResettable 2. For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor Module Operation" on page 208 3. Combination systems employing these non-fire monitor types require the SLC loop to be programmed by the installer for Style 4 operation and isolator modules must be employed on each non-fire branch of the SLC as per Figure 13 in the SLC Wiring Manual (document number 51309). Fire and non-fire devices must not be used on the same SLC branch. 80 MS-9200UDLS PN 52750:E1 01/27/09 Programming Pre-signal EDIT MONITOR 1=PRE-SIGNAL Edit Monitor Screen #3 See Page EDIT MONITOR 1=WALKTEST 2=ZONE ASSIGNMENT 00 ** ** ** ** Edit Monitor Screen #4 To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to "Presignal" on page 164 for additional information. Walktest The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable devices, which are connected to a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 167 for additional information. Zone Assignment A maximum of five zones can be programmed to each addressable monitor module. Pressing 2 while viewing Edit Monitor Screen #4 displays the following screen: MON ZONE ASSIGN Z00 Z** Z** Z** Z** Zone Assignment Screen Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Monitor Screen #4. EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION ***************** Edit Monitor Screen #5 Noun/Adjective The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will cause the following screen to be displayed: 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen MS-9200UDLS PN 52750:E1 01/27/09 81 Programming 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the monitor module currently being programmed. ********************** 1=NORTH 2=SOUTH 3=EAST ********************** 1=3RD 2=4TH 3=5TH Adjective Screen #1 Adjective Screen #5 ********************** 1=WEST 2=FRONT 3=CENTER ********************** 1=FLOOR 1 2=FLOOR 2 3=FLOOR 3 Adjective Screen #2 Adjective Screen #6 ********************** 1=REAR 2=UPPER 3=LOWER Adjective Screen #3 ********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM Adjective Screen #7 ********************** 1=MAIN 2=FIRST 3=2ND Adjective Screen #4 82 MS-9200UDLS PN 52750:E1 01/27/09 Programming 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the monitor module currently being programmed. ********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM Noun Screen #1 ********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM Noun Screen #2 ********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR Noun Screen #3 ********************** 1=GARAGE 2=HALLWAY 3=HVAC RM Noun Screen #4 ********************** 1=KITCHEN 2=LOBBY 3=OFFICE Noun Screen #5 ********************** 1=PATIENT 2=RESTROOM 3=ROOM Noun Screen #6 ********************** 1=STAIRWAY 2=STOREROOM 3=WING Noun Screen #7 ********************** 1=ZONE Noun Screen #8 Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PS-Tools utility. MS-9200UDLS PN 52750:E1 01/27/09 83 Programming Description EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION ***************** The Description selection allows the programmer to enter additional information about the monitor module currently being programmed. This information will be displayed as part of the device label on the LCD display. Pressing 2 while viewing Edit Monitor Screen #5 will cause the following screen to be displayed: Edit Monitor Screen #5 DESCRIPTION 1M012 NOUN/ADJECTIVE ******************** Noun/Adjective Screen A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the LCD display along with the standard device label information. A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 2, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Monitor Screen #4, displaying the new information at the bottom of the screen. Recall/Increment Function In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as follows: 84 • If the zero key is pressed, a 0 is placed in the first letter position • If the zero key is then pressed a second time with no intervening key actions, the entire Adjective field is replaced with the field entered for the previous device programmed, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-byletter • If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one. If the last character is a letter, it changes to a 0. If the last character is 9 it goes to 0 • The above increment function may be repeated with each press of the zero key MS-9200UDLS PN 52750:E1 01/27/09 Programming As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows: 1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3 2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field 3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305 4. Press the right arrow key to advance the zone field 5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones MODULES 1=ADD 2=DELETE 3=EDIT 3.6.2.2.4 Edit Module Screen for Control Modules The programmer can change a module’s existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed: EDIT MODULE ENTER MODULE ADDRESS *** Modules Screen Edit Module Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 002. When the last digit is keyed-in, if the selected address corresponds to a control module, a screen displaying information about the control module with the selected address will be displayed as illustrated in the following: NORMAL CONTROL ZNNN SW 1M002 Edit Control Screen #1 In the preceding example: Normal - indicates that the module with the selected address is physically installed on the SLC and communicating with the control panel (enabled) - represents the adjective and noun, which have been programmed, describing the location of the displayed device Control - indicates that the selected module is a control module S or * - represents Silenceable (S) or Nonsilenceable (*) W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * = Waterflow Timer Delay disabled) ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from 000 - 099) 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module and 002 = Module Address 02) MS-9200UDLS PN 52750:E1 01/27/09 85 Programming To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Control screens: EDIT CONTROL 1=ENABLED 2=TYPE CONTROL 3=SILENCEABLE YES YES Edit Control Screen #2 EDIT CONTROL 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** ** Edit Control Screen #3 EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION ******************** Edit Control Screen #4 EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE Edit Control Screen #2 86 Enable/Disable Module To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from activating its output devices. The control panel will indicate a system trouble condition and the Disable LED will turn on if any devices are disabled. MS-9200UDLS PN 52750:E1 01/27/09 Programming EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE Edit Control Screen #2 Type To select the type of control module being programmed, press the 2 key while viewing the Edit Control Screen #2. This will cause the control panel to display the following Control Type Screens. Press the down arrow key to view additional screens and selections. CONTROL TYPE 1=BLANK 2=BELL-CIRCUIT 3=HORN-CIRCUIT Control Type Screen #1 While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Control Screen #2 and indicate the new type selection. Note: A control relay module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control relay module is disabled. The following table contains control module type codes and their functions which are displayed in the Control Type screens: Control Type Special Function Bell Circuit NAC Type - supervised Horn Circuit NAC Type - supervised Sounders NAC Type - supervised Relay Ignore Open Circuit Strobe Circuit NAC Type - supervised Control NAC Type - supervised Power 1 Relay Type - Ignore Open Circuit SHUTDN 2 Relay Type - Ignore Open Circuit Resettable HVAC Note: 1. When using a control relay module to supply resettable power to conventional 2wire smoke detectors, the addressable monitor module must be programmed for Smoke-Conventional operation 2. For HVAC SHUTDN description, refer to "Control Module Operation" on page 208 MS-9200UDLS PN 52750:E1 01/27/09 87 Programming EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE Edit Control Screen #2 EDIT CONTROL 1=WALKTEST 2=ZONE ASSIGNMENT 00 ** ** ** ** Edit Control Screen #3 Silenceable The Silenceable selection allows the programmer to select whether output devices connected to the control module can be silenced, either by pressing the Alarm Silence key or by enabling Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable feature causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable No. Walktest The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable devices, which are connected to a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 167 for additional information. Zone Assignment A maximum of five zones can be programmed to each addressable control module. Pressing 2 while viewing Edit Control Screen #3 displays the following screen: ZONE ASSIGNMENT Z00 Z** Z** Z** Z** Zone Assignment Screen Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Control Screen #3. EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION Edit Control Screen #4 Noun/Adjective The Noun/Adjective selection allows the programmer to enter specific descriptors about the control module currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause the following screen to be displayed: 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen 88 MS-9200UDLS PN 52750:E1 01/27/09 Programming 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the control module currently being programmed. ********************** 1=NORTH 2=SOUTH 3=EAST ********************** 1=3RD 2=4TH 3=5TH Adjective Screen #1 Adjective Screen #5 ********************** 1=WEST 2=FRONT 3=CENTER ********************** 1=FLOOR 1 2=FLOOR 2 3=FLOOR 3 Adjective Screen #2 Adjective Screen #6 ********************** 1=REAR 2=UPPER 3=LOWER Adjective Screen #3 ********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM Adjective Screen #7 ********************** 1=MAIN 2=FIRST 3=2ND Adjective Screen #4 MS-9200UDLS PN 52750:E1 01/27/09 89 Programming 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the control module currently being programmed. ********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM Noun Screen #1 ********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM Noun Screen #2 ********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR Noun Screen #3 ********************** 1=GARAGE 2=HALLWAY 3=HVAC RM Noun Screen #4 ********************** 1=KITCHEN 2=LOBBY 3=OFFICE Noun Screen #5 ********************** 1=PATIENT 2=RESTROOM 3=ROOM Noun Screen #6 ********************** 1=STAIRWAY 2=STOREROOM 3=WING Noun Screen #7 ********************** 1=ZONE Noun Screen #8 Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PS-Tools programming utility. 90 MS-9200UDLS PN 52750:E1 01/27/09 Programming Description EDIT CONTROL 1=ADJECTIVE/NOUN 2=DESCRIPTION The Description selection allows the programmer to enter additional information about the control module currently being programmed. This information will be displayed as part of the device label on the display. Pressing 2 while viewing Edit Control Screen #4 will cause the following screen to be displayed: Edit Control Screen #4 DESCRIPTION 1M002 NOUN/ADJECTIVE ******************** Adjective/Noun Screen A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the display along with the standard device label information. A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Control Screen #4, displaying the new information at the bottom of the screen. Recall/Increment Function In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as follows: • • • • If the zero key is pressed, a 0 is placed in the first letter position If the zero key is then pressed a second time with no intervening key actions, the entire Adjective field is replaced with the field entered for the previous device programmed, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-byletter If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one. If the last character is a letter, it changes to a 0. If the last character is 9 it goes to 0 The above increment function may be repeated with each press of the zero key As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows: 1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3 2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field 3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305 4. Press the right arrow key to advance the zone field 5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones MS-9200UDLS PN 52750:E1 01/27/09 91 Programming PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP 3.6.3 Zone Setup Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated below: Programming Screen #2 ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99 Zone Setup Screen #1 ZONE SETUP 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED Zone Setup Screen #2 ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=ZONE MESSAGE Zone Setup Screen #3 ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99 3.6.3.1 Enable Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen: Zone Setup Screen #1 ZONE TO ENABLE Z Enable Screen This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z. Another zone can then be enabled. 92 MS-9200UDLS PN 52750:E1 01/27/09 Programming ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99 3.6.3.2 Disable Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following: ZONE TO DISABLE Zone Setup Screen #1 Z Disable Screen This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second digit is entered, the zone will be disabled and the cursor will return to the original position next to the Z. Another zone can then be disabled. 3.6.3.3 Zone 97, 98 and 99 Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will display the following screen: SPEC PURPOSE ZONE 1=PAS 97 OFF 2=PRESIGNAL 98 OFF 3=TWO STAGE 99 OFF Zone 97, 98 and 99 Screen Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose applications. In the above illustration, the three zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning them to input and output devices in the Programming Zone Assignment Screen. Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 97 to activate. By assigning Zone 97 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a PAS condition in the control panel. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software checks. Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is programmed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning Zone 98 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal condition. Attempting to do so will generate an error message and will be prevented by software checks. Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 108 for a description of this feature. MS-9200UDLS PN 52750:E1 01/27/09 93 Programming ZONE SETUP 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED 3.6.3.4 Zones Installed Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to the following: Zone Setup Screen #2 ZONES INSTALLED 00 01 02 03 04 05 Zones Installed Screen This display will show all of the zones that have been programmed into the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones. 3.6.3.5 Zones Enabled Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to the following: ZONES ENABLED 00 01 02 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 Zones Enabled Screen This display will show all of the zones that are enabled in the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones. 3.6.3.6 Zones Disabled Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar to the following: ZONES DISABLED 03 Zones Disabled Screen This display will show all of the zones that are disabled in the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones. 94 MS-9200UDLS PN 52750:E1 01/27/09 Programming ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=ZONE MESSAGE Zone Setup Screen #3 3.6.3.7 Zone Type Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a screen similar to the following: ZONE 1=Z00 2=Z01 3=Z02 TYPE PROG MONITOR MONITOR MONITOR Zones Installed Screen This display will show the system zones (default and user programmed) and their associated types. Note that an up and/or down arrow will appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view zones Z00 through Z99. Zone types can be changed by pressing the keypad number key corresponding to the zone in each Zones Installed Screen. Available zone types will be displayed in the resultant screens. For example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following screens will be displayed: ZONE TYPE PROG 1=MONITOR 2=SMOKE PHOTO 3=WATERFLOW Zone Type Program Screen #1 ZONE TYPE PROG 1=HEAT 2=PULL STATION 3=DUCT Zone Type Program Screen #2 ZONE TYPE PROG 1=MEDICAL 2=HAZARD 3=TAMPER Zone Type Program Screen #3 ZONE TYPE PROG 1=SUPERVISORY 2=PROC. MON 3=SMOKE ION Zone Type Program Screen #4 To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure for each zone to be changed. IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow silenceable zone type to the selected zone. Any signaling devices programmed to the same zone can be silenced by pressing the Alarm Silence key or by using the auto-silence feature. To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page 97. Note: Zone Types are only relevant for Central Station reporting. Changing a zone type will only change how it is reported to the Central Station. MS-9200UDLS PN 52750:E1 01/27/09 95 Programming ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=ZONE MESSAGE Zone Setup Screen #3 3.6.3.8 Zones Available Pressing 2 while viewing Zone Setup Screen #3 will display the following screen: ZONES AVAILABLE 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 The display will show all of the zones that are still available for programming. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow key to view additional screens. 3.6.3.9 Zone Message Pressing 3 while viewing Zone Setup Screen #3 will display the following screen: ZONE MESSAGE 1=Z00 NO MESSAGE 2=Z01 MESSAGE 1 3=Z02 NO MESSAGE Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number key corresponding to the Zone to be programmed. Screens will be displayed allowing the programmer to select Audio Messages 1 through 5. When an audio message is selected, the display will return to the Zone Message screen, showing the message selected for that particular zone. In the example above, Zone 01 has been programmed for Audio Message 1. PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP Programming Screen #2 3.6.4 Loop Setup Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 wiring and to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the following screen to be displayed: LOOP SETUP 1=STYLE 4 2=PROTOCOL LITESPEED Loop Setup Screen 3.6.4.1 Style To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as indicated by the 4 to the right of Style in the display. To change the wiring style, press 1 to toggle the display to read Style 6. Each press of the 1 key will cause the display to toggle between Style 4 and Style 6. Note that, when programming the Loop Style, the programmer can only select between Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop Setup for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each addressable device on the loop must have a pair of isolator modules, one on each side. 96 MS-9200UDLS PN 52750:E1 01/27/09 Programming Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for Style 6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear the SLC trouble. 3.6.4.2 Loop Protocol Loop Protocol refers to the SLC loop mode of operation. Refer to "Wire Requirements" on page 205 for wire specifications based upon SLC protocol. There are two Loop Protocols available: • CLIP (Classic Loop Interface Protocol) - which is used for the older legacy addressable devices such as the M300 Series modules and detectors. • LiteSpeed (factory default setting) - used for the 350 Series or newer addressable devices for quicker response times. Note that the legacy devices can operate only in CLIP mode while the newer devices are compatible with CLIP and LiteSpeed modes of operation. Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed Protocols. Device Addressing It is important to note that the MS-9200UDLS addressable device capacity is 99 detectors and 99 control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses will not function with the MS-9200UDLS. Note that It is permissible to mix old and new devices on the same loop but the FACP must be set for CLIP mode when older devices are installed. 3.6.5 System Setup System Setup allows the programmer to configure the following control panel features: • • • • • • • • MS-9200UDLS PN 52750:E1 Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or trouble still exists on the FACP after the control panel has been silenced. The control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If the trouble condition is not cleared within 24 hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the central station if connected. Banner: This option allows the user to change the top two lines of the LCD display from the blank factory default readout to a user defined readout when the control panel is in Normal condition. Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr), date and daylight savings time feature into the FACP memory Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal time delay and Waterflow time delay. NACs: This feature allows the programmer to configure the control panel Notification Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable, autosilence, coding, silence inhibit, zone assignment and enable/disable. Relays: This option allows programming of two onboard relays for activation by various control panel events, such as alarm, trouble, supervisory, etc. Canadian Option: This option allows the automatic programming of ionization smoke detector sensitivity thresholds to Canadian specifications. Waterflow Silenceable: This option provides the ability to silence any output circuit activated by a monitor module programmed as a waterflow type. 01/27/09 97 Programming PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP Programming Screen #2 Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be displayed: SYSTEM SETUP 1=TROUBLE REM OFF 2=BANNER 3=TIME-DATE System Setup Screen #1 SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS System Setup Screen #2 SYSTEM SETUP 1=CANADIAN OPT. 2=WATERFLOW SIL. OFF NO System Setup Screen #3 3.6.5.1 Trouble Reminder See Page The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 97, for a detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will cause the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will cause the display to toggle between Trouble Rem On and Trouble Rem Off. 3.6.5.2 Banner The top line of the display, which appears when the control panel is in normal mode, can be changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be displayed: BANNER 1=FACTORY 2=USER DEFINED Banner Screen BANNER 1=FACTORY 2=USER DEFINED Pressing 1 while viewing the Banner Screen will select the blank factory default banner setting and display the following screen: Banner Screen FACTORY BANNER Factory Banner Screen 98 MS-9200UDLS PN 52750:E1 01/27/09 Programming Pressing the Enter key will store this selection in nonvolatile memory and return the display to the Banner Screen. Pressing 2 while viewing the Banner Screen will cause the following screens to be displayed: USER DEFINED BANNER PRESS ENTER IF OK User Defined Banner Screen #1 USER BANNER - LINE 2 PRESS ENTER IF OK ************ User Defined Banner Screen #2 These screens allow the programmer to enter a two line custom banner. A flashing cursor will appear in the bottom left corner of each display. A maximum of 20 characters (including spaces) can be entered into each screen for a total of two lines with 40 characters. After entering up to 20 characters in the first screen, press Enter to view the second screen. Enter up to 20 characters in the second screen in the same manner or just press Enter if a second banner line is not being entered. To quickly clear the current banner, press the CLR key. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times to place a blank in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Banner Screen. MS-9200UDLS PN 52750:E1 01/27/09 99 Programming SYSTEM SETUP 1=TROUBLE REM 2=BANNER 3=TIME-DATE 3.6.5.3 Time-Date The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen #1. The following screen will be displayed: System Setup Screen #1 TIME 1=TIME 2=DATE 3=CLOCK AND DATE 10:00 AM 04-07-2006 FORMAT 12HR Time-Date Screen #1 TIME AND DATE 1=DAYLIGHT SAVINGS Time-Date Screen #2 3.6.5.3.1 Time To change the time, press 1 while viewing the Time-Date Screen. The following screen will be displayed: ENTER TIME 10:00 AM 1=AM 2=PM Time Screen A flashing cursor is located toward the top left of the display. Below the cursor is the current time. To change the time, enter the two-digit hours followed by the twodigit minutes. The cursor will move one position to the right each time a digit is entered. After the last minutes digit is entered, the cursor will again move one position to the right. At this point enter 1 for AM or 2 for PM. The display will then return to the Time-Date Screen which will show the new time entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again. 100 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6.5.3.2 Date To change the date, press 2 while viewing the Time-Date Screen. The following screen will be displayed: ENTER DATE MONTH DAY YEAR 04-07-2006 Date Screen A flashing cursor is located toward the top left of the display. Below the cursor is the current date. To change the date, enter the two-digit month followed by the twodigit day and then the two-digit year (01 for 2001, 02 for 2002, etc.). The cursor will move one position to the right each time a digit is entered. After the last year digit is entered, the display will return to the Time-Date Screen which will show the new date entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again. 3.6.5.3.3 Clock Format The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display. Note: If the clock is changed to 24 hour (military) format, the date will change to the European standard of Day-Month-Year (for display purposes only). TIME AND DATE 1=DAYLIGHT SAVINGS 3.6.5.3.4 Daylight Savings Time Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed: Time & Date Screen #2 DAYLIGHT SAVINGS 1=ENABLED YES 2=START MONTH MAR 3=START WEEK WEEK-2 Daylight Savings Screen #1 DAYLIGHT SAVINGS 1=END MONTH NOV 2=END WEEK WEEK-1 Daylight Savings Screen #2 Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between Enabled Yes and Enabled No. The control panel will automatically update the time for daylight savings time when Enabled Yes is selected. Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April and 3 will select May. MS-9200UDLS PN 52750:E1 01/27/09 101 Programming Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will begin. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third week, while in the second subscreen, pressing 1 will select the fourth week and 2 will select the last week of the selected month. Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1 will select September, 2 will select October and 3 will select November. Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will end. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third week, while in the second subscreen, pressing 4 will select the fourth week and 5 will select the last week of the selected month. SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS System Setup Screen #2 3.6.5.4 Timers Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while viewing System Setup Screen #2. The following screen will be displayed: TIMERS 1=PAS DELAY 2=PRE SIGNAL 3=WATERFLOW 000 000 000 Timer Screen #1 TIMERS 1=AC LOSS DELAY 000 Timer Screen #2 TIMERS 1=PAS DELAY 2=PRE SIGNAL 3=WATERFLOW Timer Screen #1 000 000 000 3.6.5.4.1 PAS (Positive Alarm Sequence) Delay The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear: PAS DELAY RANGE 0-180 SECONDS PAS Delay Screen A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. 102 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6.5.4.2 Pre-signal Delay The factory default setting for Pre-signal delay is 000 for no delay. To select a Presignal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed: PRESIGNAL DELAY RANGE 0-180 SECONDS Pre-signal Delay Screen A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. Note that the FACP allows programming for PAS and Pre-signal timers, but a detector can only be programmed for either PAS or Pre-signal operation. Refer to "Edit Detector" on page 66 for programming details. TIMER 1=PAS DELAY 2=PRE SIGNAL 3=WATERFLOW 000 000 000 Timer Screen #1 3.6.5.4.3 Waterflow Delay A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing Timer Screen #1. The following screen will be displayed: WATERFLOW DELAY RANGE 0-90 SECONDS Waterflow Delay Screen A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time. MS-9200UDLS PN 52750:E1 01/27/09 103 Programming TIMER 1=AC LOSS DELAY 3.6.5.4.4 AC Loss Delay The reporting of a loss of AC power to a central station can be delayed by programming the length of the desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2 to display the following: Timer Screen #2 AC LOSS DELAY 1=NO DELAY 2=ENTER DELAY AC Loss Delay Screen #1 Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central station. Pressing 2 while viewing AC Loss Delay Screen #1 will display the following: AC LOSS DELAY RANGE 00-23 AC Loss Delay Screen #2 A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1. Note: Upon the loss of AC power at the control panel, relays programmed for ‘AC Loss’ will transfer immediately, regardless of the AC Loss Delay setting. If no trouble exists at the panel other than AC Loss, the System Trouble relay will delay its activation for the duration of the AC Loss Delay setting. SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS System Setup Screen #2 3.6.5.5 NAC (Notification Appliance Circuit) The options for the NACs on the control panel main circuit board can be configure by pressing 2 while viewing System Setup Screen #2. The following screens will be displayed: NACS 1=NAC 1 2=NAC 2 3=NAC 3 4=NAC 4 NAC Selection Screen The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2 for NAC 2, 3 for NAC 3 or 4 for NAC 4. Note that 3=NAC 3 and 4=NAC 4 will be displayed, and can be programmed, regardless of how the NACKEY card is installed. Their programming, however, will have no effect if the NACKEY card is installed for Class A operation. 104 MS-9200UDLS PN 52750:E1 01/27/09 Programming The following screens will be displayed for each selection: NAC # 1=ENABLED 2=TYPE 3=SILENCEABLE YES BELL YES NAC Screen #1 NAC # 1=AUTO SILENCE 00 2=CODING TEMPORAL NAC Screen #2 NAC # 1=ZONE 00 00 00 00 00 2=SIL INHIBITED NO NAC Screen #3 NAC # 1=SYNC TYPE S NAC Screen #4 3.6.5.5.1 Enabled Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No. Note: The programming for NAC 1 will determine the operation of the remote power supply sync. MS-9200UDLS PN 52750:E1 01/27/09 105 Programming NAC # 1=ENABLED 2=TYPE 3=SILENCEABLE 3.6.5.5.2 Type The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1. The following screen will be displayed. Press the down arrow key to view additional screens: NAC Screen #1 NAC TYPE 1=BELL 2=HORN 3=STROBE Type Screen #1 Select the NAC device type by pressing the number corresponding to the type in the appropriate screen. When the selection is made, the display will return to NAC Screen #1. The following table contains NAC type codes and their functions: NAC Type Code Bell Horn Strobe Synced Strobe Strobe Sil Sync Future Use Future Use Future Use Blank Special Function None None None Synchronized to manufacturer Same as Synced Strobe but Silence turns off audible & visual devices None None None None 3.6.5.5.3 Silenceable Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This will prevent the selected main circuit board NAC from being silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable No. Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the Synced Strobe feature is selected, only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence or Autosilence will turn off both audible and visual devices. 106 MS-9200UDLS PN 52750:E1 01/27/09 Programming NAC # 1=AUTO SILENCE 2=CODING TEMPORAL NAC Screen #2 3.6.5.5.4 Auto Silence The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notification appliances after a programmed length of time. To enable this feature and program the time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following screens will be displayed: AUTO SILENCE 1=NO 2=5 MINUTES 3=10 MINUTES Auto Silence Screen #1 AUTO SILENCE 1=15 MINUTES 2=20 MINUTES 3=25 MINUTES Auto Silence Screen #2 AUTO SILENCE 1=30 MINUTES Auto Silence Screen #3 To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To enable the Auto Silence feature, press the number corresponding to the time delay which will elapse before Auto Silence activates. This information will be stored in memory and the display will return to NAC Screen #2. Note: All silenceable control modules as well as the remote power supply sync will be controlled by the Autosilence timer for NAC 1. 3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type) The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear: CODING 1=STEADY 2=MARCH TIME 3=CALIFORNIA Coding Screen #1 CODING 1=TEMPORAL 2=TWO STAGE 3 MIN 3=TWO STAGE 5 MIN Coding Screen #2 MS-9200UDLS PN 52750:E1 01/27/09 107 Programming The programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding selections are: • • • • • Steady - a continuous output with no coding March Time - 120 ppm (pulse-per-minute) output California - 10 seconds on and 5 seconds off Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off Two Stage - refer to "Two Stage Operation" on page 108 for a description Selection of one of the above options will cause the control panel to store the information in memory and return the display to NAC Screen #2, which will display the new coding choice. 3.6.5.5.5.1 Two Stage Operation Two Stage operation consists of the following: • 1st stage output - 20 ppm (pulse-per-minute) coding • 2nd stage output - Temporal coding as described above If Two Stage operation is programmed as the Coding option, the following sequence of events will occur during an alarm. 1. The on-board NACs which are programmed to General Alarm Zone 0 will activate with a 1st stage output upon activation of any alarm point 2. If the activated alarm point is directly mapped to a zone which is programmed to an on-board NAC, that NAC will go directly to 2nd stage coding output. All other NACs not directly mapped to the activated alarm point’s zone but assigned to Zone 0 will activate with a 1st stage output 3. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not been pressed, all NACs presently in 1st stage activation will go to 2nd stage activation 4. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in 2nd stage activation 5. If another alarm point is activated and the countdown timer is counting, the alarm point will have no effect on the NACs unless the alarm point’s zones are directly mapped to one of the NACs, in which case it will follow the procedure outlined in step 2 6. If another alarm point is activated and the countdown timer has stopped counting due to the Acknowledge switch being pressed, the countdown timer will restart and the NACs will respond as outlined in step 2. NACs already in 2nd stage activation will not be affected 7. Any control modules assigned to special Zone 99 will be activated either by direct mapping of an input device programmed to Zone 99 or if the timer counts down to zero or when any NAC goes into 2nd stage coding 8. Control modules that are programmed to the same zone as the activated input device will not be delayed for activation 108 MS-9200UDLS PN 52750:E1 01/27/09 Programming NAC # 1=ZONE 00 00 00 00 00 2=SIL INHIBITED NO 3.6.5.5.6 Zone A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while viewing NAC Screen #3 displays the following screen: NAC Screen #3 ZONE ASSIGNMENT Z00 Z** Z** Z** Z** Zone Screen Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this NAC. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zone Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the NAC Screen #3 which will show the zone assignments just entered. 3.6.5.5.7 Silence Inhibited The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board NAC for a period of one minute. Resetting the FACP will also be prevented for one minute while the NAC programmed for silence inhibit is activated. Pressing 2 while viewing NAC Screen #3 will cause the display to change from the factory default of Silence Inhibit No to Silence Inhibit Yes. Each press of the 2 key will cause the display to toggle between the two options. NAC # 1=SYNC TYPE NAC Screen #4 3.6.5.5.8 Sync Type If synchronized strobes were selected as the Type of device installed, the type of synchronization must be selected in this option. Pressing 1 while viewing NAC Screen #4 will cause the following screen to be displayed: NAC SYNC TYPE 1=SYSTEM SENSOR 2=WHEELOCK 3=GENTEX Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Wheelock and 3 will select Gentex. 3.6.5.5.8.1 Maximum Number of Strobes for Synchronization The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the manufacturer’s documentation supplied with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded. To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following is a list of the strobes that have been tested with this FACP and the maximum number that can be connected to each NAC. Make sure that the NAC maximum current is not exceeded: System Sensor: 40 Strobes Wheelock: 25 Strobes Gentex: 23 Strobes MS-9200UDLS PN 52750:E1 01/27/09 109 Programming SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS 3.6.5.6 Relays Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two main circuit board Form-C relays from the following screen: System Setup Screen #2 RELAYS 1=RELAY 1 2=RELAY 2 3=RELAY 3 Relays Selection Screen To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The following screen will appear for each relay to be programmed: RELAY # 1=TYPE ALARM Relay Type Screen Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be displayed: RELAY 1=ALARM 2=SUPERVISORY 3=SUPERVISORY AR Relay Screen #1 Relay Screen #3 RELAY 1=MEDICAL 2=SILENCEABLE ALARM RELAY 1=TROUBLE 2=COMM FAIL 3=PROCESS-MON Relay Screen #2 RELAY 1=PROCESS MON AR 2=AC LOSS 3=HAZARD Relay Screen #4 While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice. Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays. Notes: 1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the Supervisory and/or Process Monitor type code, when activated, will automatically reset when the corresponding condition is cleared. 2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and deactivate when the FACP Alarm Silenced LED is illuminated. 110 MS-9200UDLS PN 52750:E1 01/27/09 Programming SYSTEM SETUP 1=CANADIAN OPT. OFF 2=WATERFLOW SIL. NO System Setup Screen #3 3.6.5.7 Canadian Option Pressing 1 while viewing System Setup Screen #3 will allow the programmer to configure the system to automatically monitor addressable ionization smoke detector sensitivity using Canadian specifications. The display will change to Canadian Opt. On. Each press of the 1 key will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.: SYSTEM SETUP 1=CANADIAN OPT. OFF 2=WATERFLOW SIL. NO Relays Selection Screen 3.6.5.8 Waterflow Silenceable Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the system for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the display between Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all output devices associated with a waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is selected, all output devices associated with a waterflow type input device, will be silenceable. 3.6.6 Verify Loop PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP Programming Screen #2 Pressing 3 while viewing Programming Screen #2, will select the Verify Loop option. During loop verification, the FACP polls each device on the SLC to determine if the device is communicating and whether or not it responds with the proper type identification. The following screen will be displayed while verification is in progress: VERIFYING LOOPS PLEASE WAIT Verification Progress Screen When Loop verification has been completed, the display will indicate that the system is OK or, if problems have been detected, any device type programming errors. Use the up and down arrow keys to view all detected errors. MS-9200UDLS PN 52750:E1 01/27/09 111 Programming 3.6.7 History PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES The History option allows an authorized user to view or erase events which have occurred in the control panel. Pressing 1 while viewing Programming Screen #3 will display the History options as shown in the following display: Programming Screen #3 HISTORY 1=VIEW EVENTS 2=ERASE HISTORY History Screen HISTORY 1=VIEW EVENTS 2=ERASE HISTORY History Screen 3.6.7.1 View Events Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as illustrated in the following: HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS View Events Screen While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3 to view other events. Use the up and down arrow keys to scroll through all of the displayed events. 3.6.7.2 Erase History The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history file to track future events. Pressing 2 while viewing the History Screen will display the following screen: ERASE HISTORY PROCEED ? 1=YES 2=NO Erase History Screen Pressing 1 while viewing the Erase History Screen will erase all events from the History file. During this process, the display will read as follows: ERASING HISTORY PLEASE WAIT Erase History Wait Screen After the History file has been erased, the display will return to the History Screen. 112 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6.8 Walktest PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Walktest allows an individual to test the fire alarm system without the necessity to reset the control panel after each device activation. Pressing 2 while viewing the Programming Screen #3 will cause the following Walktest options to be displayed: Programming Screen #3 WALKTEST 1=SILENT 2=AUDIBLE 3=VIEW RESULT Walktest Screen To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the following screen will be displayed:: UNIT IN WALKTEST 1=VIEW WALKTEST LOG 2=VIEW POINTS 3=VIEW SUMMARY Unit In Walktest Screen From this screen, it is possible to view the walktest log, untested system points or a summary of the addressable devices tested during the current walktest. The user can select between any of these screens without interrupting the current walktest session. The walktest session will not end until the Unit In Walktest screen is exited by pressing the Escape key. Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen similar to one of the following two screens to be displayed: NO EVENTS IN WALKTEST LOG OR ALARM: MONITOR NORTH CLASSROOM Z001 10*15A 012308 1M006 If there are no events in the current walktest session, the first screen will be displayed, indicating no events have been stored in the walktest log. If any events have been stored, a screen similar to the second will be displayed indicating the latest event. As walktest events occur, the display will change to indicate the latest event. All stored events can be scrolled on the screen by pressing the up or down arrow keys. To return to the first event, press the 1st Event key. MS-9200UDLS PN 52750:E1 01/27/09 113 Programming Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the following screens: NO POINTS IN SYSTEM OR UNTESTED POINTS 010 1D001 SMOKE (PHOTO) ********************* NOT TESTED If the system has no points installed, the first screen will be displayed. If points are installed, the second screen will be displayed, which allows the viewing of all untested system points and their status relating to the current walktest session. The up and down arrow keys will allow viewing of all untested points. If a point is tested while it is being displayed, the screen will update and display the next untested point. The first line indicates the total number of untested points. The second line displays information about an untested point. A description on the bottom of the screen will indicate if the displayed point has been disabled, if the Walktest option has been disabled for that point or if the point is not yet tested. The up and down arrow keys allow the user to scroll through all untested points. Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen which will show a total of the tested detectors, tested modules, untested detectors and untested modules for the current walktest session. The user can perform a one-person walktest by activating devices throughout the system. As each device is activated, the information about the activated device is stored in the Walktest Log. The information can be viewed by choosing one of the options from the Unit In Walktest screen. To end the Walktest session, press the Escape key to return to the Walktest screen. Pressing 3 for View Results while viewing the Walktest screen, after a walktest session has been completed, will allow the operator to view the final results of the most recent walktest. The following screen will be displayed: WALKTEST RESULTS View Result Screen Use the up and down arrow keys to view all of the walktest results which will be displayed. Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed. 114 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6.9 Option Modules PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES Programming Screen #3 Options available for the MS-9200UDLS include ACS Series, Graphic and LCD annunciators, printer connection for acquiring hardcopy printouts of panel data and PC (Personal Computer) connection for uploading and downloading panel data. Pressing 3 while viewing Programming Screen #3 will display the following screen: OPTION MODULES 1=ANNUNCIATORS 2=ONBOARD DACT 3=PRINTER/PC PR4800 Options Screen Note that PR4800 in the display indicates that a supervised printer, configured for 4800 baud, has been previously programmed into the system. 3.6.9.1 Annunciators Pressing 1 while viewing the Options Screen will cause the control panel to display the following screens: ANNUNCIATORS 1=TERM ENABLED 2=ACS OPTIONS 3=ANN-BUS OPTIONS NO A Terminal Mode annunciator, ACS Mode annunciator or ANN-BUS annunciator/ module can be installed in the MS-9200UDLS system. Do not use a mix of ACS annunciators and ANN annunciators since they use different communication protocols. ACS or ANN annunciators use the same TB9 terminal block connection. To install any of these devices, press the number corresponding to the desired device shown in the Annunciator Screen. 3.6.9.1.1 Term Options While viewing the Annunciators screen, each press of the 1 key for Term Enabled, will cause the display to toggle between Term Enabled No and Term Enabled Yes. Notes: 1. *The LCD-80F is a Terminal Mode annunciator. To enable the MS-9200UDLS for LCD-80F operation, press 1 for Term Enabled Yes. 2. The Terminal Mode annunciator (LCD-80F) and the Printer/PC use the same TB8 terminal block on the MS-9200UDLS main circuit board. Only one device can be connected at one time, therefore, enabling an annunciator in the Term Option will disable any Printer/PC communications. MS-9200UDLS PN 52750:E1 01/27/09 115 Programming ANNUNCIATORS 1=TERM ENABLED 2=ACS OPTIONS 3=ANN-BUS OPTIONS 3.6.9.1.2 ACS Options Pressing 2 for ACS Options while viewing the Annunciators screen, will display the following screen: ACS OPTIONS 1=ACS ENABLED 2=ACS INSTALLED NO Pressing 1 while viewing the ACS Options screen will cause the display to toggle between ACS Enabled Yes and ACS Enabled No. To install an ACS annunciator, the display must read ACS Enabled Yes. If ACS has been enabled, press 2 while viewing the Annunciator Screen to select addresses for the ACS annunciators. The following screen will be displayed: ANNUNCIATOR 1=ADDRESS 1 2=ADDRESS 2 3=ADDRESS 3 YES NO NO ACS Installed Screen Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1 -31. Each screen will indicate if an address has been used for an installed ACS annunciator. To select one or more addresses for the installed ACS annunciator(s), press the number key corresponding to the address in each screen. The display for the selected address will change from No to Yes. Each press of the number key will cause the display to toggle between No and Yes. The address of each installed annunciator must be enabled to allow communication between the FACP and annunciator. 116 MS-9200UDLS PN 52750:E1 01/27/09 Programming Annunciator addressing is specific to the MS-9200UDLS control panel. The following table describes the annunciator addresses and the corresponding addressable devices that will be annunciated at each annunciator address. ACS Annunciator Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Annunciator Displays the Following Points 8 General System Status Points & Zones 1 - 56 Zones 57 - 99 & 4 NACs SLC Loop, Module Addresses 1 - 64 not used SLC Loop, Module Addresses 65 - 99 not used not used SLC Loop, Detector Addresses 1 - 64 not used SLC Loop, Detector Addresses 65 - 99 not used not used not used not used not used not used not used not used not used 8 General System Status Points & Zones 1 - 56 Zones 57 - 99 & 4 NACs SLC Loop, Module Addresses 1 - 64 not used SLC Loop, Module Addresses 65 - 99 not used not used SLC Loop, Detector Addresses 1 - 64 not used SLC Loop, Detector Addresses 65 - 99 not used not used not used The MS-9200UDLS must be programmed for the annunciators installed on the system. Refer to "Annunciators" on page 115 for information on annunciator programming. Make certain to program the annunciator addresses that have been physically installed on the system. Note: The 8 General System Status Points include the following: • General Alarm • General Trouble • General Supervisory MS-9200UDLS PN 52750:E1 01/27/09 • Alarm Silenced • System Off Normal • AC Loss • Battery Fault • NAC Fault 117 Programming 3.6.9.1.3 ANN-BUS Options Pressing 3 for ANN-BUS Options, while viewing the Annunciators screen, will cause the following screens to be displayed:. ANN-BUS 1=ENABLED NO 2=MODULES INSTALLED 3=AUTO-CONFIGURE ANN-BUS Screen #1 ANN-BUS 1=ANN-S/PG OPTIONS 2=ANN-80 OPTIONS ANN-BUS Screen #2 A printer module, graphic annunciator module, LCD annunciator module, LED annunciator module and relay module can be programmed into the MS-9200UDLS system. These devices communicate with the FACP over the ANN-BUS terminals on the control panel. 3.6.9.1.3.1 ANN-BUS Enabled The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-BUS Enabled Yes and ANN-BUS Enabled No. 3.6.9.1.3.2 Modules Installed If an ANN-BUS module is installed, press 2 for Modules Installed while viewing ANN-BUS screen #1 to select ANN-BUS addresses for the module(s). The following screen will be displayed. ANN-BUS MODULES 1=ADDR. 1 NONE 2=ADDR. 2 NONE 3=ADDR. 3 NONE ANN-BUS Modules Screen #1 Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1-8. To select one or more addresses for the installed module(s), press the number key corresponding to the module address in each screen. The following screen will be displayed for each address: ANN-BUS MODULES ANN-BUS ADDRESS # 1=TYPE NONE ANN-BUS Address Screen 118 MS-9200UDLS PN 52750:E1 01/27/09 Programming Pressing 1 for Type will display the following screens: ANN-BUS MODULE TYPE 1=NOT INSTALLED 2=ANN-80 MODULE 3=ANN-I/O MODULE Module Type Screen #1 ANN-BUS MODULE TYPE 1=ANN-S/PG MODULE 2=ANN-LED MODULE 3=ANN-RLY MODULE Module Type Screen #2 ANN-BUS MODULE TYPE 1=ANN-AUDIO Module Type Screen #3 Press the number corresponding to the module/device type that is installed with the selected address. Note: If the module type selected is the ANN-80, ANN-S/PG or ANN-AUDIO or if Not Installed is selected, the ANN-BUS Address Screen shown on the previous page will be displayed following the module selection. The options selected for each of these modules will be the same for all modules of the same type (refer to "ANN-S/PG (Print) Options" on page 129 and "ANN-80 Options" on page 130). If ANN-I/O, ANN-LED or ANN-RLY is the selected module type, the following ANN-BUS Address Screen will be displayed: ANN-BUS MODULES ANN-BUS ADDRESS # 1=TYPE ANN-I/O 2=MODULE OPTIONS ANN-BUS Address Screen Since the options for each of these module types can be individually set, pressing 2 for Module Options, while viewing the ANN-BUS Address Screen will display the available options as described below. MS-9200UDLS PN 52750:E1 01/27/09 119 Programming ANN-I/O Options Pressing 2 for Module Options while viewing ANN-BUS Address screen when the ANN-I/O option is selected will display the following screen: ANN-I/O ADDR 1 LOOP1 DET 1-30 ACTIVE LEDS ONLY ANN-I/O Address Screen #1 ANN-I/O ADDR 1 1=POINT/ZONE ANN-I/O Address Screen #2 ANN-I/O ADDR 1 1=RANGE 2=DET/MOD ANN-I/O Address Screen #3 The first screen indicates that the ANN-I/O at ANN-BUS address 1 is programmed to annunciate SLC Loop #1 addressable Detectors with addresses 1 through 30. The programming can be changed using ANN-I/O Address Screens 2 and 3. Pressing 1 while viewing ANN-I/O Address Screen #2 will program the annunciator module to annunciate either Point (addressable device address) information or Zone information. Pressing 1 while viewing ANN-I/O Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in "ANN-I/O Zone Option" on page 121 and "ANN-I/O Point Option" on page 122). Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable detectors or addressable modules to be annunciated. 120 MS-9200UDLS PN 52750:E1 01/27/09 Programming ANN-I/O Zone Option If Zone is selected as the module option, the first ten LEDs on the first ANN-I/O module will display the system status information. The remaining 30 LEDs on the first module and 40 LEDs on the remaining modules will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assignments for each ANN-I/O module will be as follows. Module LED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 MS-9200UDLS PN 52750:E1 01/27/09 Zone Range 0-29 AC Fault Fire Alarm Supervisory Trouble Alarm Silenced Earth Fault Battery Fault Charger Fault NAC Fault Disabled Zone 00 Zone 01 Zone 02 Zone 03 Zone 04 Zone 05 Zone 06 Zone 07 Zone 08 Zone 09 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Zone 25 Zone 26 Zone 27 Zone 28 Zone 29 Zone Range 30-69 Zone 30 Zone 31 Zone 32 Zone 33 Zone 34 Zone 35 Zone 36 Zone 37 Zone 38 Zone 39 Zone 40 Zone 41 Zone 42 Zone 43 Zone 44 Zone 45 Zone 46 Zone 47 Zone 48 Zone 49 Zone 50 Zone 51 Zone 52 Zone 53 Zone 54 Zone 55 Zone 56 Zone 57 Zone 58 Zone 59 Zone 60 Zone 61 Zone 62 Zone 63 Zone 64 Zone 65 Zone 66 Zone 67 Zone 68 Zone 69 Zone Range 70-99 Zone 70 Zone 71 Zone 72 Zone 73 Zone 74 Zone 75 Zone 76 Zone 77 Zone 78 Zone 79 Zone 80 Zone 81 Zone 82 Zone 83 Zone 84 Zone 85 Zone 86 Zone 87 Zone 88 Zone 89 Zone 90 Zone 91 Zone 92 Zone 93 Zone 94 Zone 95 Zone 96 Zone 97 Zone 98 Zone 99 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used 121 Programming ANN-I/O Point Option If Point is selected as the module option, the first ten LEDs on the first ANN-I/O module will display the system status information. The remaining 30 LEDs on the first module and 40 LEDs on each additional module will display the active/alarm status of each point in the Point Range programmed for that particular module. The points that will be annunciated on a particular ANN-I/O module depend on the programming options selected as far as the device type (detector or module) to be annunciated. The LED assignments for each ANN-I/O module will be as follows. Module LED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 122 Point Range 1-30 AC Fault Fire Alarm Supervisory Trouble Alarm Silenced Earth Fault Battery Fault Charger Fault NAC Fault Disabled Point 01 Point 02 Point 03 Point 04 Point 05 Point 06 Point 07 Point 08 Point 09 Point 10 Point 11 Point 12 Point 13 Point 14 Point 15 Point 16 Point 17 Point 18 Point 19 Point 20 Point 21 Point 22 Point 23 Point 24 Point 25 Point 26 Point 27 Point 28 Point 29 Point 30 Point Range 31-70 Point 31 Point 32 Point 33 Point 34 Point 35 Point 36 Point 37 Point 38 Point 39 Point 40 Point 41 Point 42 Point 43 Point 44 Point 45 Point 46 Point 47 Point 48 Point 49 Point 50 Point 51 Point 52 Point 53 Point 54 Point 55 Point 56 Point 57 Point 58 Point 59 Point 60 Point 61 Point 62 Point 63 Point 64 Point 65 Point 66 Point 67 Point 68 Point 69 Point 70 Point Range 71-99 Point 71 Point 72 Point 73 Point 74 Point 75 Point 76 Point 77 Point 78 Point 79 Point 80 Point 81 Point 82 Point 83 Point 84 Point 85 Point 86 Point 87 Point 88 Point 89 Point 90 Point 91 Point 92 Point 93 Point 94 Point 95 Point 96 Point 97 Point 98 Point 99 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used MS-9200UDLS PN 52750:E1 01/27/09 Programming PROGRAMMING 1=ANN-RLY OPTIONS 2=ANN-LED OPTIONS ANN-LED Options Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-LED option is selected, will display the following screen: ANN-BUS Screen #3 ANN-LED ADDR # LOOP1 DET 1-10 ALARM,SUPERV,TBL ANN-LED Address Screen #1 ANN-LED ADDR # 1=POINT/ZONE 2=ALARM/ATS ANN-LED Address Screen #2 ANN-LED ADDR # 1=RANGE 2=DET/MOD 3=LOOP# ANN-LED Address Screen #3 The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Supervisories and Troubles for SLC Loop #1 addressable Detectors with addresses 1 through 10. The programming can be changed using ANN-LED Address Screens 2 and 3. Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable device address) information or Zone information. Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms for addressable device addresses 130 or Alarms, Supervisories and Troubles for addressable device addresses 1-10. Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated - refer to the tables in "ANN-LED Zone Option Alarm Only (for use with ANN-RLED module)" on page 124 and "ANN-LED Point Option - Alarm Only (for use with ANN-RLED module)" on page 126. Pressing 2 while viewing ANN-LED Address Screen #3 will select either addressable detectors or addressable modules to be annunciated. MS-9200UDLS PN 52750:E1 01/27/09 123 Programming ANN-LED Zone Option - Alarm Only (for use with ANN-RLED module) If Zone is selected as the module option, and the module is programmed to annunciate alarms only, the first ten LEDs on the first ANN-LED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the remaining modules will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assignments for each ANN-LED module will be as follows. ANN-RLED Module #1 Alarm Silenced NAC 1 Fault NAC 2 Fault NAC 3 Fault NAC 4 Fault Earth Fault Battery Fault Charger Fault Disabled Maintenance Zone 00 Active/Alarm Zone 01 Active/Alarm Zone 02 Active/Alarm Zone 03 Active/Alarm Zone 04 Active/Alarm Zone 05 Active/Alarm Zone 06 Active/Alarm Zone 07 Active/Alarm Zone 08 Active/Alarm Zone 09 Active/Alarm Zone 10 Active/Alarm Zone 11 Active/Alarm Zone 12 Active/Alarm Zone 13 Active/Alarm Zone 14 Active/Alarm Zone 15 Active/Alarm Zone 16 Active/Alarm Zone 17 Active/Alarm Zone 18 Active Alarm Zone 19 Active/Alarm Zone 20 Active/Alarm Zone 21 Active/Alarm Zone 22 Active/Alarm Zone 23 Active/Alarm Zone 24 Active/Alarm Zone 25 Active/Alarm Zone 26 Active/Alarm Zone 27 Active/Alarm Zone 28 Active/Alarm Zone 29 Active/Alarm ANN-RLED Module #2 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Zone 30 Active/Alarm Zone 31 Active/Alarm Zone 32 Active/Alarm Zone 33 Active/Alarm Zone 34 Active/Alarm Zone 35 Active/Alarm Zone 36 Active/Alarm Zone 37 Active/Alarm Zone 38 Active/Alarm Zone 39 Active/Alarm Zone 40 Active/Alarm Zone 41 Active/Alarm Zone 42 Active/Alarm Zone 43 Active/Alarm Zone 44 Active/Alarm Zone 45 Active/Alarm Zone 46 Active/Alarm Zone 47 Active/Alarm Zone 48 Active Alarm Zone 49 Active/Alarm Zone 50 Active/Alarm Zone 51 Active/Alarm Zone 52 Active/Alarm Zone 53 Active/Alarm Zone 54 Active/Alarm Zone 55 Active/Alarm Zone 56 Active/Alarm Zone 57 Active/Alarm Zone 58 Active/Alarm Zone 59 Active/Alarm The LED assignments for the modules annunciating Zone Ranges 60 - 89 and 90 - 99, will follow the same pattern as the second ANN-RLED module. 124 MS-9200UDLS PN 52750:E1 01/27/09 Programming ANN-LED Zone Option - Alarm, Trouble and Supervisory If Zone is selected as the module option, and the module is programmed to annunciate alarms, troubles and supervisories, the first ten LEDs on the first ANN-LED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the remaining modules will display the alarm, trouble and supervisory status for each of the ten zones in the Zone Range programmed for that particular module. The LED assignments for each ANN-LED module will be as follows. ANN-LED Module #1 Alarm Silenced NAC 1 Fault NAC 2 Fault NAC 3 Fault NAC 4 Fault Earth Fault Battery Fault Charger Fault Disabled Maintenance Zone 00 Active/Alarm Zone 01 Active/Alarm Zone 02 Active/Alarm Zone 03 Active/Alarm Zone 04 Active/Alarm Zone 00 Trouble Zone 01 Trouble Zone 02 Trouble Zone 03 Trouble Zone 04 Trouble Zone 00 Supervisory Zone 01 Supervisory Zone 02 Supervisory Zone 13 Supervisory Zone 04 Supervisory Zone 05 Active/Alarm Zone 06 Active/Alarm Zone 07 Active/Alarm Zone 08 Active Alarm Zone 09 Active/Alarm Zone 05 Trouble Zone 06 Trouble Zone 07 Trouble Zone 08 Trouble Zone 09 Trouble Zone 05 Supervisory Zone 06 Supervisory Zone 07 Supervisory Zone 08 Supervisory Zone 09 Supervisory ANN-LED Module #2 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Zone 10 Active/Alarm Zone 11 Active/Alarm Zone 12 Active/Alarm Zone 13 Active/Alarm Zone 14 Active/Alarm Zone 10 Trouble Zone 11 Trouble Zone 12 Trouble Zone 13 Trouble Zone 14 Trouble Zone 10 Supervisory Zone 11 Supervisory Zone 12 Supervisory Zone 13 Supervisory Zone 14 Supervisory Zone 15 Active/Alarm Zone 16 Active/Alarm Zone 17 Active/Alarm Zone 18 Active/Alarm Zone 19 Active/Alarm Zone 15 Trouble Zone 16 Trouble Zone 17 Trouble Zone 18 Trouble Zone 19 Trouble Zone 15 Supervisory Zone 16 Supervisory Zone 17 Supervisory Zone 18 Supervisory Zone 19 Supervisory The LED assignments for the modules annunciating Zone Ranges 20 - 29, 30 - 39, 40 49, 50 - 59, 60 - 69, 70 - 79, 80 - 89 and 90 - 99, will follow the same pattern as the second ANN-LED module. MS-9200UDLS PN 52750:E1 01/27/09 125 Programming ANN-LED Point Option - Alarm Only (for use with ANN-RLED module) If Point is selected as the module option and the module is programmed to annunciate alarms only, the first ten LEDs on the first ANN-LED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on each additional module will display the active/alarm status of each point in the Point Range programmed for that particular module. The points that will be annunciated on a particular ANN-LED module depend on the programming options selected as far as which SLC loop and the device type (detector or module) to be annunciated. The LED assignments for each ANN-LED module will be as follows. ANN-RLED Module #1 (Point Range 01 - 30) Alarm Silenced NAC 1 Fault NAC 2 Fault NAC 3 Fault NAC 4 Fault Earth Fault Battery Fault Charger Fault Disabled Maintenance Point 03 Active/Alarm Point 04 Active/Alarm Point 05 Active/Alarm Point 01 Active/Alarm Point 02 Active/Alarm Point 06 Active/Alarm Point 07 Active/Alarm Point 08 Active/Alarm Point 09 Active/Alarm Point 10 Active/Alarm Point 11 Active/Alarm Point 12 Active/Alarm Point 13 Active/Alarm Point 14 Active/Alarm Point 15 Active/Alarm Point 16 Active/Alarm Point 17 Active/Alarm Point 18 Active/Alarm Point 19 Active/Alarm Point 20 Active/Alarm Point 21 Active/Alarm Point 22 Active/Alarm Point 23 Active/Alarm Point 24 Active/Alarm Point 25 Active/Alarm Point 26 Active/Alarm Point 27 Active/Alarm Point 28 Active/Alarm Point 29 Active/Alarm Point 30 Active/Alarm ANN-RLED Module #2 (Point Range 31 - 60) Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Point 33 Active/Alarm Point 34 Active/Alarm Point 35 Active/Alarm Point 31 Active/Alarm Point 32 Active/Alarm Point 36 Active/Alarm Point 37 Active/Alarm Point 38 Active/Alarm Point 39 Active/Alarm Point 40 Active/Alarm Point 41 Active/Alarm Point 42 Active/Alarm Point 43 Active/Alarm Point 44 Active/Alarm Point 45 Active/Alarm Point 46 Active/Alarm Point 47 Active/Alarm Point 48 Active/Alarm Point 49 Active/Alarm Point 50 Active/Alarm Point 51 Active/Alarm Point 52 Active/Alarm Point 53 Active/Alarm Point 64 Active/Alarm Point 55 Active/Alarm Point 56 Active/Alarm Point 57 Active/Alarm Point 58 Active/Alarm Point 59 Active/Alarm Point 60 Active/Alarm The LED assignments for the modules annunciating Point Ranges 61 - 90 and 91 99, will follow the same pattern as the second ANN-RLED module. 126 MS-9200UDLS PN 52750:E1 01/27/09 Programming ANN-LED Point Option - Alarm, Trouble and Supervisory If Point is selected as the module option, and the module is programmed to annunciate alarms, troubles and supervisories, the first ten LEDs on the first ANN-LED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the remaining modules will display the alarm, trouble and supervisory status for each of the ten zones in the Point Range programmed for that particular module. The LED assignments for each ANN-LED module will be as follows. ANN-LED Module #1 (Point Range 01 - 10) Alarm Silenced NAC 1 Fault NAC 2 Fault NAC 3 Fault NAC 4 Fault Earth Fault Battery Fault Charger Fault Disabled Maintenance Point 01 Active/Alarm Point 02 Active/Alarm Point 03 Active/Alarm Point 04 Active/Alarm Point 05 Active/Alarm Point 01 Trouble Point 02 Trouble Point 03 Trouble Point 04 Trouble Point 05 Trouble Point 01 Supervisory Point 02 Supervisory Point 03 Supervisory Point 04 Supervisory Point 05 Supervisory Point 06 Active/Alarm Point 07 Active/Alarm Point 08 Active/Alarm Point 09 Active/Alarm Point 10 Active/Alarm Point 06 Trouble Point 07 Trouble Point 08 Trouble Point 09 Trouble Point 10 Trouble Point 06 Supervisory Point 07 Supervisory Point 08 Supervisory Point 09 Supervisory Point 10 Supervisory ANN-LED Module #2 (Point Range 11 - 20) Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Point 11 Active/Alarm Point 12 Active/Alarm Point 13 Active/Alarm Point 14 Active/Alarm Point 15 Active/Alarm Point 11 Trouble Point 12 Trouble Point 13 Trouble Point 14 Trouble Point 15 Trouble Point 11 Supervisory Point 12 Supervisory Point 13 Supervisory Point 14 Supervisory Point 15 Supervisory Point 16 Active/Alarm Point 17 Active/Alarm Point 18 Active/Alarm Point 19 Active/Alarm Point 20 Active/Alarm Point 16 Trouble Point 17 Trouble Point 18 Trouble Point 19 Trouble Point 20 Trouble Point 16 Supervisory Point 17 Supervisory Point 18 Supervisory Point 19 Supervisory Point 20 Supervisory The LED assignments for the modules annunciating Point Ranges 21 - 30, 31 - 40 and 41 - 50, 51 - 60, 61 - 70, 71 - 80, 81 - 90 and 91 - 99, will follow the same pattern as the second ANN-LED Module. MS-9200UDLS PN 52750:E1 01/27/09 127 Programming ANN-RLY Options Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-RLY option is selected, will cause the following screen to be displayed: ANN-RLY - ADDR. # 1=RELAY 1 ZONE 00 2=RELAY 2 ZONE 01 3=RELAY 3 ZONE 02 ANN-RLY Options Screen The ANN-RLY module provides ten Form-C relays which can be programmed for various functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will display the remaining relays for this module. To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key corresponding to the relay to be programmed. Following is a list of the available programming options for each relay: • Alarm • Supervisory • Supervisory AR • Trouble • Comm Fail • Process Mon • Process Mon AR • AC Loss • Hazard • Medical • Silenceable Alarm • Zone Active XX 3.6.9.1.3.3 Auto-Configure The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically program the device type and address into the system. For the Auto-Configure to work, the ANN-BUS must be enabled, the annunciators must be connected/powered and a unique address must be set on each annunciator. Pressing 3 while viewing ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to be displayed: ANN-BUS AUTO-CONGFIGURE IN PROGRESS PLEASE WAIT Auto-Configure Screen 128 MS-9200UDLS PN 52750:E1 01/27/09 Programming ANN-BUS 1=ANN-S/PG OPTIONS 2=ANN-80 OPTIONS 3.6.9.1.3.4 ANN-S/PG (Print) Options The Print option allows the programmer to configure the optional printer. Pressing 1 while viewing ANN-BUS screen #2 will display the following screens: ANN-S/PG OPTIONS 1=PORT 2=PRINTER SUPV 3=OFFLINE TIMER ANN-BUS Screen #2 PAR NO 60 ANN-S/PG Options Screen #1 ANN-S/PG OPTIONS 1=BAUD RATE N/A 2=DATA BITS N/A 3=PARITY N/A ANN-S/PG Options Screen #2 ANN-S/PG OPTIONS 1=STOP BITS N/A ANN-S/PG Options Screen #3 Pressing 1 for Port while viewing ANN-S/PG Options screen #1 will allow the programmer to select between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that the interface selected determines which options are available to the user. If the Parallel Port option is selected, the user has the option to supervise the printer and select an offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print Options screen #1. Each press of the 2 key will cause the display to toggle between Printer Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option is not selectable if the Serial Port option has been selected. If the Parallel Port option is selected, the user has the ability to select an Offline Timer by pressing 3 while viewing Print Options screen #1. The resultant screen allows the programmer to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer supervision is reported as a trouble. If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be available. The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port option has been selected. Pressing 1 for Baud Rate while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allow the user to select a Baud Rate of 19200, 9600 or 2400. Pressing 2 for Data Bits while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select 7 or 8 Data Bits. MS-9200UDLS PN 52750:E1 01/27/09 129 Programming Pressing 3 for Parity while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select between No Parity, Even Parity or Odd Parity. Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear which allows the user to select between 1.0 or 2.0 Stop Bits. 3.6.9.1.3.5 ANN-80 Options Pressing 2 while viewing ANN-BUS screen #2 will display the following screen: ANN-80 OPTIONS 1=PIEZO ENABLE 2=LOCK ENABLE 3=ACK BTN ENABLE ANN-80 Options Screen #1 ANN-80 OPTIONS 1=SIL BTN ENABLE 2=RST BTN ENABLE 3=DRL BTN ENABLE ANN-80 Options Screen #2 The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No. The Lock Enable option allows the programmer to select whether or not any installed ANN-80 annunciator must be unlocked by its key before any annunciator key presses will function. Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock position is ignored). The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select whether the Ack/Step button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step button never functions). The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the Silence button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never functions). The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the Reset button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never functions). 130 MS-9200UDLS PN 52750:E1 01/27/09 Programming The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the Drill button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never functions). OPTION MODULES 1=ANNUNCIATORS 2=ON BOARD DACT 3=PRINTER/PC 3.6.9.2 Onboard DACT The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a central station. Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed: Option Module Screen ON BOARD DACT 1=ENABLED YES 2=PRIMARY PHONE 3=SECONDARY PHONE On Board DACT Screen #1 ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=SUPERV PHONE LINE On Board DACT Screen #2 3.6.9.2.1 Onboard DACT Enable To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1 until the display reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press of the key. 3.6.9.2.2 Primary Phone Press 2 while viewing On Board DACT Screen #1 to program the type of primary phone line being connected to the DACT. The following screen will be displayed: ON BOARD DACT PRIMARY PHONE LINE 1=TYPE TOUCHTONE Primary Phone Line Screen To select the type, press 1 while viewing the Primary Phone Line screen. The following screen will be displayed: PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38 Primary Phone Type Screen Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38. MS-9200UDLS PN 52750:E1 01/27/09 131 Programming ON BOARD DACT 1=ENABLED 2=PRIMARY PHONE 3=SECONDARY PHONE On Board DACT Screen #1 3.6.9.2.3 Secondary Phone Press 3 while viewing On Board DACT Screen #1 to program the type of secondary phone line being connected to the DACT. The following screen will be displayed: ON BOARD DACT SECONDARY PHONE LINE 1=TYPE TOUCHTONE Secondary Phone Line Screen To select the type, press 1 while viewing the Secondary Phone Line screen. The following screen will be displayed: PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38 Secondary Phone Type Screen Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38. ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=SUPERV PHONE LINE On Board DACT Screen #2 3.6.9.2.4 Service Terminal The FACP can be programmed remotely from a PC using a modem and telephone line. Information can also be retrieved from the FACP using the same method. The Upload/Download option allows an operator to set the necessary parameters to allow the uploading and downloading of data between the FACP and PC. The Service Terminal selection provides the means for entering these parameters. Pressing 1 while viewing On Board DACT Screen #2 will cause the following screen to appear: SERVICE TERMINAL 1=RING COUNT 0 Service Terminal Screen 132 MS-9200UDLS PN 52750:E1 01/27/09 Programming SERVICE TERMINAL 1=RING COUNT Service Terminal Screen #2 3.6.9.2.4.1 Ring Count The ring count designates the number of rings allowed on the phone line prior to answering an incoming call from a service terminal. The factory default is 0 which means the control panel will not answer an incoming call. This entry may be programmed for 1 to 25 rings. To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The following screen will be displayed: RING COUNT RANGE 0-25 RANGE Ring Count Screen A flashing cursor will appear in the lower left corner of the display. Enter the twodigit ring count which can be a value between 00 and 25. After the second digit is entered, the display will return to the Service Terminal screen. ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=SUPERV PHONE LINE 3.6.9.2.5 Central Station Central Station programming configures the control panel DACT for contacting the central station. Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens to be displayed: On Board DACT Screen #2 CENTRAL STATION 1=REPORTING DISABLED 2=REPORT BACKUP 3=CALL LIMIT Central Station Screen #1 CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE Central Station Screen #2 3.6.9.2.5.1 Reporting Enable To enable the DACT for reporting FACP activity to the central station, press 1 while viewing Central Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will toggle the display between Reporting Disabled and Reporting Enabled. MS-9200UDLS PN 52750:E1 01/27/09 133 Programming 3.6.9.2.5.2 Backup Reporting The DACT can be programmed to transmit reports to primary and/or secondary central station phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the following screen: BACKUP REPORTING 1=BACKUP ONLY 2=FIRST AVAILABLE Backup Reporting Screen Press 1 to have all reports transmitted to the central station secondary phone number as a backup only if the primary phone line fails. Press 2 to send reports to the first available phone number. 3.6.9.2.6 Trouble Call Limit (Dialer Runaway Prevention) The Call Limit option limits the number of DACT trouble calls to the Central Station, to a programmed amount between 0 and 99, for each unique trouble within a 24 hour period. Separate limit counters keep track of each unique type of trouble. Note that the number of phone line (communication) faults called to the Central Station are not limited by this feature. No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose call limit has been reached. Local DACT annunciation will still track the particular trouble and restoral. To set the Trouble Call Limit, press 3 while viewing Central Station Screen #1. The following screen will be displayed. TROUBLE CALL LIMIT 00-99 RANGE * Backup Reporting Screen Enter a value between 00 and 99, then press Enter to set the Call Limit to this value. Note: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the Central Station an unlimited number of times. 134 MS-9200UDLS PN 52750:E1 01/27/09 Programming CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE 3.6.9.2.6.1 Central Station Primary and Secondary Phone Numbers Pressing 1 for Primary or 2 for Secondary will display the following screens. Note that the following information must be entered for both the Primary and Secondary Central Station Phone Numbers. Central Station Screen #2 CENTRAL STATION # 1=TEST TIME INT 24 2=ACCOUNT CODE 0000 3=24HR TST TIME 0021 Primary/Secondary Screen #1 CENTRAL STATION 1=PHONE NUMBER Primary/Secondary Screen #2 CENTRAL STATION 1=COMM FORMAT ADEMCO-CONTACT-ID Primary/Secondary Screen #3 CENTRAL STATION 1=EVENT CODES Primary/Secondary Screen #4 MS-9200UDLS PN 52750:E1 01/27/09 135 Programming Test Time Interval CENTRAL STATION 1=TEST TIME INT 2=ACCOUNT CODE 3=24HR TST TIME Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be displayed: Primary/Secondary Screen #1 TEST TIME INTERVAL 1=24 HOURS 2=12 HOURS 3=8 HOURS Test Time Interval Screen #1 TEST TIME INTERVAL 1=6 HOURS Test Time Interval Screen #2 The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24 hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens shown above. Account Code Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed: ACCOUNT CODE 4 CHAR RANGE 0-F Account Codes Screen The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will have a flashing cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F keys. 136 MS-9200UDLS PN 52750:E1 01/27/09 Programming 24 Hour Test Time CENTRAL STATION 1=TEST TIME INT 2=ACCOUNT CODE 3=24HR TST TIME Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed: 24 HOUR TEST TIME Primary/Secondary Screen #1 RANGE 0000-2359 24 Hour Test Time Screen Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time (0000 = midnight and 2359 = 11:59PM). Phone Number CENTRAL STATION 1=PHONE NUMBER Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be displayed: PHONE NUMBER Primary/Secondary Screen #2 20 NUMBERS MAXIMUM Phone Number Screen The Phone Number screen is used to enter the Central Station phone number that the DACT will be contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9 and A - C where A = *, B = # and C = 2 seconds pause. A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press the right arrow key to move the cursor to the right one position. Enter the second digit and repeat the process until all digits are entered. Press the Enter key to store the phone number in memory. Enter the digits as you would like the number to be dialed. For example, if it’s necessary to dial 9 before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9 followed by D for a three second pause or E for a five second pause then the phone number followed by an F to indicate the end of the number. MS-9200UDLS PN 52750:E1 01/27/09 137 Programming Communication Format CENTRAL STATION 1=COMM FORMAT Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be displayed: COMM FORMAT 1=ADEMCO CONTACT ID 2=SIA 8 3=SIA 20 Primary/Secondary Screen #3 The Communication Format is determined by the type of receiver that the DACT is transmitting to. Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes. Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen. The following table describes each format: Table 3.2 Communication Formats Screen Selection ADEMCO CONTACT ID SIA 8 SIA 20 Communication Format Description Contact ID, DTMF, 1400/2300 ACK Security Industry Association, 8 messages per call Security Industry Association, 20 messages per call Event Codes CENTRAL STATION 1=EVENT CODES Primary/Secondary Screen #4 Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be displayed: EVENT CODES 1=PULL STATION 2=MON-USER-DEF-1 3=WATERFLOW Event Code Screen Pressing the down arrow key allows viewing of all Events associated with the selected Communication Format. Pressing the number corresponding to the event displayed in each screen will display its default event code which can be customized by the programmer. For example, pressing 1 for Pull Station will display the following screen which allows the Event Code to be changed from the default value. PULL STATION ALARM 000 Event Code Screen The tables on the following pages list all of the Events and their default Event Codes for the various Communication Formats. 138 MS-9200UDLS PN 52750:E1 01/27/09 Programming Ademco Contact ID & SIA Formats The information shown in Table 3.3 is automatically programmed for the Central Station phone number Event Codes when the Ademco Contact ID or SIA Format is selected. Enter 0s for an Event Code Setting to disable the report. Disabled reports will not get called to the Central Station. The programmer may enable the Event Types in programming as described on the previous page. Table 3.3 Event Codes Event Description PULL STATION MON-USER-DEF-1 WATERFLOW MON-USER-DEF-2 SMOKE (PHOTO) DET-USER-DEF-1 SMOKE (ION) DET-USER-DEF-2 HEAT DETECT DET-USER-DEF-3 SMOKE DUCT-P DET-USER-DEF-4 PHOTO W/HEAT DET-USER-DEF-5 DUCT SUPERVISORY DET-USER-DEF-6 PHOTO SUPERV DET-USER-DEF-7 PHOTO ADAPT DET-USER-DEF-8 PHOTO BEAM DET-USER-DEF-9 not used not used not used not used not used not used not used not used not used not used MONITOR MON-USER-DEF-3 not used not used SMOKE CONVEN MON-USER-DEF-5 HEAT CONVENTIONAL MON-USER-DEF-6 MEDIC ALERT MON-USER-DEF-7 HAZARD ALERT MON-USER-DEF-8 TORNADO ALRT MON-USER-DEF-9 MON-PHONE MON-USER-DEF-10 TAMPER MON-USER-DEF-11 MON SUPERVISORY MON-USER-DEF-12 MON SUPERV AUTO MS-9200UDLS PN 52750:E1 01/27/09 Ademco Contact ID Active 115 115 113 113 111 111 111 111 114 114 116 116 111 111 200 200 200 200 111 111 111 111 000 000 000 000 000 000 000 000 000 000 110 110 000 000 111 111 114 114 100 100 150 150 150 150 000 000 144 144 200 200 200 SIA Active FA FA SA SA FA FA FA FA KA KA FA FA FA FA FS FS FS FS FA FA FA FA 00 00 00 00 00 00 00 00 00 00 FA FA 00 00 FA FA KA KA MA MA PA PA PA PA 00 00 TA TA FS FS FS Restoral FH FH SH SH FH FH FH FH KH KH FH FH FH FH FV FV FV FV FH FH FH FH 00 00 00 00 00 00 00 00 00 00 FH FH 00 00 FH FH KH KH MH MH PH PH PH PH 00 00 TH TH FV FV FV 139 Programming Table 3.3 Event Codes (continued) MON-USER-DEF-13 HVAC OVRRIDE POWER MON MON-USER-DEF-14 TROUBLE MON MON-USER-DEF-15 PROCESS MON MON-USER-DEF-16 PROCMON AR MON-USER-DEF-17 not used not used POINT_FAULT POINT_DISABLE AC_FAIL DRILL SLC 1 OPEN FAULT SLC 1 SHORT FAULT not used not used GROUND FAULT LOW BATTERY NO_BATTERY TELCO LINE 1 TELCO LINE 2 COMM FAULT 1 COMM FAULT 2 TOTAL COMM FLT PRINTER FAULT NAC 1 FAULT NAC 2 FAULT NAC 3 FAULT NAC 4 FAULT 24 VDC FAULT VOICE EVAC FAULT ACS/ANN-BUS FAULT LCD_80F FAULT NAC 1 DISABLE NAC 2 DISABLE NAC 3 DISABLE NAC 4 DISABLE CS CALC FAULT CHARGER FAULT OPTION CARD 1 FAULT REMOTE SYNC FAULT not used ZONE DISABLE NAC_KEY_FLT NO_DEVICES_INSTLLD OFF_NORMAL_MESSAGE 24_HOUR_TEST 24 HOUR ABNORMAL TES UPDOWN REQUEST UPLOAD SUCCESS DOWNLOAD SUCCESS UPDOWN FAILURE GENERAL_ALARM GENERAL_SUPERVISORY 140 200 FS FV 200 FS FV 330 AT AR 330 AT AR POINT_FAULT code will always be transmitted POINT_FAULT code will always be transmitted 000 00 00 000 00 00 000 00 00 000 00 00 000 00 00 000 00 00 380 FT FJ 570 FB FU 301 AT AR 604 FI FK 371 ET1 ER1 372 ET1 ER1 000 00 00 000 00 00 310 ET ER 302 YT YR 311 YT YR 351 LT LR 352 LT LR 354 YC YK 354 YC YK 000 00 00 336 VT VR 321 YA YR 322 YA YR 326 YA YR 327 YA YR 300 YP YQ 330 ET ER 333 EM EN 330 EM EN 521 ET ER 522 ET ER 526 ET ER 527 ET ER 304 YF 300 YP YQ 331 ET ER 332 OU OV 000 00 00 570 FB FU 300 ET ER 380 ET ER 308 LB LX 602 RP 608 RY 411 RB 416 RS 412 RS 413 RR 000 00 00 000 00 00 MS-9200UDLS PN 52750:E1 01/27/09 Programming Report Style CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE POINT Central Station Screen #2 Pressing 3 while viewing Central Station Screen #2 will cause the Report Style display to toggle between Point and Zone. Setting the Report Style to Point will program the DACT to report individual point status to the Central Station. The control panel is capable of monitoring a total of 198 addressable devices. Setting the Report Style to Zone will program the DACT to report zone status to the Central Station. The control panel is capable of monitoring a total of 99 individual zones. Notes: 1. Detector Address 01 will be reported to the Central Station as Point 01, Detector Address 02 as Point 02, with reports continuing in a similar fashion all the way up to Detector Address 99 which will be reported as Point 99. 2. Module Address 01 will be reported to the Central Station as Point 160, Module Address 02 will be reported to the Central Station as Point 161, with reports continuing in a similar fashion all the way up to Module Address 99 which will be reported as Point 258. ON BOARD DACT 1=FUTURE USE 2=CENTRAL STATION 3=SUPERV PHONE LINE On Board DACT Screen #2 3.6.9.2.7 Supervised Phone Line The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2 by the DACT when using an alternate means of secondary transmission path. The factory default setting is Phone Line 2 supervised. Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the following screen to be displayed: SUPERVISE PHONE LINE 1=PHONE LINE 2 YES Panel ID Screen Each press of the 1 key while viewing this screen will toggle the option between Supervise Phone Line 2 Yes and No. MS-9200UDLS PN 52750:E1 01/27/09 141 Programming 3.6.9.3 Printer/PC OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ON BOARD DACT 3=PRINTER/PC NO Option Module Screen A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option Module Screen will cause the following screen to appear: PRINTER-PC 1=PRINTER NO SU 2=PRINTER SU 3=PC NO YES NO Printer-PC Screen Pressing 1 while viewing the Printer-PC Screen will program the control panel for an unsupervised (NO SU) printer. The display will change to the Printer Baud Rate Screen as shown below. Pressing 2 while viewing the Printer-PC Screen will program the control panel for a supervised (SU) printer. Printer supervision, when enabled, will typically detect the removal of the printer cable and will detect when the printer power has been turned off. Depending upon the brand of printer, other errors such as paper empty or printer off-line may be detected. The following screen will appear, which allows the programmer to select the baud rate for the printer communication: PRINTER BAUD RATE 1=2400 BAUD 2=4800 BAUD 3=9600 BAUD Printer Baud Rate Screen Pressing the number key corresponding to the desired baud rate (2 for 4800 Baud for example) will program the control panel for the selected baud rate and return the display to the Option Module Screen which will indicate Printer/PC PR4800 for a supervised printer installed at 4800 baud rate. Pressing 3 while viewing the Printer-PC Screen will program the control panel for a PC connection. The display will return to the Option Module Screen which will indicate Printer/PC PC for personal computer installed. Note: The LCD-80F and the Printer/PC use the same TB8 terminal block. Only one device can be used at any one time. Setting any option in the Printer/PC screen to Yes will disable communications with the LCD-80F. The printer must be installed in the same room and within 50 feet of the FACP. 142 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6.10 Password Change PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK The factory set passwords, which have been programmed into the control panel, can be changed by selecting the Password Change option. Pressing 1 while viewing Programming Screen #4 will cause the following screen to be displayed: Programming Screen #4 PASSWORD CHANGE 1=MASTER 2=MAINTENANCE 3=REMOTE DOWNLOAD Password Change Screen Press 1 to change the Master Programming Level password, 2 to change the Maintenance Level password or 3 to change the Remote Download password. Note that the passwords will not be displayed on LCD annunciators. The following screen will appear when any change option is selected: ENTER NEW FIVE DIGIT PASSWORD Enter Password Screen A flashing cursor will appear in the center of the display. Enter a new five digit password (such as 10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed: VERIFY NEW PASSWORD Password Change Screen Re-enter the new password to accept the change. The display will return to the initial Password Change Screen. MS-9200UDLS PN 52750:E1 01/27/09 143 Programming 3.6.11 Clear Program PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK Programming Screen #4 Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will cause the LCD to display the following screen: CLEAR PROGRAM 1=WHOLE SYSTEM 2=ALL POINTS Clear Program Screen #1 See Page Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all general system programming options and all programmed addressable devices from the nonvolatile memory of the FACP. This function is useful when the control panel is first installed, prior to autoprogramming. Note that it is necessary to autoprogram after using the Clear Whole System function. Pressing 2, for ALL POINTS while viewing the Clear Program Screen #1, will clear all programming related to the SLC loop and connected addressable devices. Before executing any of the Clear commands listed above, the control panel will provide a warning to the user by prompting with the following display: WARNING! SYSTEM CHANGE PROCEED? 1=YES 2=NO Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will prevent programming from being cleared. 144 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.6.12 Program Check PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK Programming Screen #4 The Program Check feature allows the programmer to view the zones which have been programmed to the Notification Appliance Circuits on the control panel but have not been programmed to Initiating Devices as well as other circuits with no input or output correlations. Pressing 3 while viewing Programming Screen #4 will cause the following screen to be displayed: PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT PROGRAMCHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT Pressing 1 while viewing the Program Check screen will display an NAC screen similar to the following. Program Check Screen NACS NO INPUT NAC 1 25 31 44 55 67 The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but no input devices have been programmed to any of these zones. Use the up and down arrow keys to view all the NAC zones without input assignments for NAC 1, NAC2, NAC 3 and NAC 4. Note: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC 2 will display test information. NAC 3 and NAC 4 will display asterisks (*) and will not be included in the test. MS-9200UDLS PN 52750:E1 01/27/09 145 Programming Pressing 2 while viewing the Program Check screen will display a screen similar to the following: ZONES NO INPUT 05 07 09 10 11 1M001 The Zone No Input screen allows the programmer to view the zones which have not been programmed to at least one input device (not including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an addressable module (control module in this example) with an address of 001 on loop 1 but have not been programmed to any input devices. Use the up and down arrow keys to view all the zones without input assignments. Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be displayed: ZONES NO OUTPUT 05 07 09 10 11 1D001 The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow keys to view all the zones without output assignments. 146 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.7 Maintenance Programming Level To access Maintenance Programming mode, press the Enter key. The LCD will display the following: 1=READ STATUS 2=PROGRAMMING 3=REMOTE DOWNLOAD To enter the Maintenance Programming mode, press 2. The display will read as follows: PROGRAMMING ENTER PASSWORD When the Maintenance level password (default 11111) is entered, the following screen will appear: PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key, as shown in the following screen. PROGRAMMING 1=WALKTEST 2=SYSTEM 3=ZONE SETUP MS-9200UDLS PN 52750:E1 01/27/09 147 Programming 3.7.1 Disable Point PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Maintenance Screen #1 Pressing 1 for Point Program, while viewing Maintenance Screen #1 will cause the following screens to be displayed: POINT PROGRAM 1=DETECTOR 2=MODULE Device Select Screen Select the device type by pressing 1 for an addressable detector or 2 for an addressable module. The operator will be prompted to enter the three digit device address as shown in the following example for a detector: EDIT DETECTOR ENTER POINT ADDRESS *** Address Select Screen A flashing cursor will appear in the bottom left corner of the display, prompting for the three digit device address. When the third digit is enter, 001 for example, a screen will appear which will allow enabling or disabling of the selected point, as illustrated in the following example: EDIT DETECTOR 1D001 1=ENABLED YES Enable/Disable Select Screen Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No. 148 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.7.2 History PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed: HISTORY 1=VIEW EVENTS 2=ERASE HISTORY Maintenance Screen #1 History Screen The History feature allows the operator to view control panel events which have been stored in a history file in memory and erase the contents of the history file Pressing 1 while viewing the History screen will cause the following screen to be displayed: HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS Events Screen To view all the events which have occurred in the control panel since the history file was last erased, press 1 while viewing the Events screen. To view only alarms which have occurred, press 2 while viewing the Events screen. To view events other than alarms, press 3. The most recent event will be displayed on the screen. To view all of the selected events, press the up or down arrow keys to scroll through the list of events. If no events have occurred, the display will read NO EVENTS IN HISTORY. Pressing 2 while viewing the History Screen will cause the following screen to be displayed: ERASE HISTORY PROCEED ? 1=YES 2=NO Erase History Screen Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY, PLEASE WAIT to be displayed. The display will then return to the History Screen. Pressing 2 will cause the display to return to the History Screen without erasing the History file. MS-9200UDLS PN 52750:E1 01/27/09 149 Programming 3.7.3 Program Check PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK Maintenance Screen #1 Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be displayed: PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT Program Check Screen The Program Check feature allows the programmer to view the zones which have been programmed to the Notification Appliance Circuits on the control panel but have not been programmed to Initiating Devices as well as other circuits with no input or output correlations. Pressing 1 while viewing Program Check screen will cause a screen similar to the following to be displayed. NACS NO INPUT NAC 1 25 31 44 55 67 The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but no input devices have been programmed to any of these zones. Use the up and down arrow keys to view all the NAC zones without input assignments for both NAC 1, NAC 2, NAC 3 and NAC 4. Note: If the NACs have been configured for Class A in the Setup option, only NAC 1 and NAC2 will display test information. NAC 3 and NAC 4 will display asterisks (*) and will not be included in the test. Pressing 2 while viewing the Program Check screen will display a screen similar to the following: ZONES NO INPUT 05 07 09 10 11 1M001 The Zone No Input screen allows the programmer to view the zones which have not been programmed to at least one input device (not including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an addressable module (control module in this example) with an address of 001 on loop 1 but have not been programmed to any input devices. Use the up and down arrow keys to view all the zones without input assignments. 150 MS-9200UDLS PN 52750:E1 01/27/09 Programming Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be displayed: ZONES NO OUTPUT 05 07 09 10 11 1D001 The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow keys to view all the zones without output assignments. 3.7.4 Walktest PROGRAMMING 1=WALKTEST 2=SYSTEM 3=ZONE SETUP To perform a walktest, press 1 while viewing Maintenance Screen #2. The following screen will be displayed: WALKTEST 1=SILENT 2=AUDIBLE 3=VIEW RESULT Maintenance Screen #2 Walktest Screen The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. Pressing 1 or 2 will cause the control panel to enter Walktest Mode and will display the following screen: UNIT IN WALKTEST 1=VIEW WALKTEST LOG 2=VIEW POINTS 3=VIEW SUMMARY Unit In Walktest Screen From this screen, it is possible to view the walktest log, untested system points or a summary of the addressable devices tested during the current walktest. The user can select between any of these screens without interrupting the current walktest session. The walktest session will not end until the Unit In Walktest screen is exited by pressing the Escape key to return to the Walktest Screen. MS-9200UDLS PN 52750:E1 01/27/09 151 Programming Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen similar to one of the following two screens to be displayed: NO EVENTS IN WALKTEST LOG OR ALARM: MONITOR NORTH CLASSROOM Z001 10*15A 012308 1M006 If there are no events in the current walktest session, the first screen will be displayed, indicating no events have been stored in the walktest log. If any events have been stored, a screen similar to the second will be displayed indicating the latest event. As walktest events occur, the display will change to indicate the latest event. All stored events can be scrolled on the screen by pressing the up or down arrow keys. To return to the first event, press the 1st Event key. Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the following screens: NO POINTS IN SYSTEM OR UNTESTED POINTS 010 1D001 SMOKE (PHOTO) ********************* NOT TESTED If the system has no points installed, the first screen will be displayed. If points are installed, the second screen will be displayed, which allows the viewing of all untested system points and their status relating to the current walktest session. The up and down arrow keys will allow viewing of all untested points. If a point is tested while it is being displayed, the screen will update and display the next untested point. The first line indicates the total number of untested points. The second line displays information about an untested point. A description on the bottom of the screen will indicate if the displayed point has been disabled, if the Walktest option has been disabled for that point or if the point is not yet tested. The up and down arrow keys allow the user to scroll through all untested points. Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen which will show a total of the tested detectors, tested modules, untested detectors and untested modules for the current walktest session. To end the Walktest session, press the Escape key to return to the Walktest screen. Pressing 3 for View Results while viewing the Walktest screen, after a walktest session has been completed, will allow the operator to view the final results of the most recent walktest. 152 MS-9200UDLS PN 52750:E1 01/27/09 Programming 3.7.5 System To program the time and date into the control panel, press 2 while viewing Maintenance Screen #2. The following display will appear: SYSTEMS 1=TIME/DATE System Screen Pressing 1 while viewing the System Screen will cause the following screen to be displayed: TIME AND DATE 1=TIME 01:00 AM 2=DATE 01-01-2006 12HR Time and Date Screen To change the time, press 1 to display the following screen: ENTER TIME 01:00 AM 1=AM 2=PM Time Screen A flashing cursor will appear on the left side of the display. Enter the four digit number corresponding to the time (0000 - 1259). When the fourth digit is entered, the cursor will move one position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will return to the Time and Date Screen displaying the new time. To change the date, press 2 while viewing the Time and Date Screen. The following screen will be displayed: ENTER DATE MONTH DAY YEAR 01-01-2006 Date Screen A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit day and four digit year. The cursor will move one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and Date Screen which will show the new date. MS-9200UDLS PN 52750:E1 01/27/09 153 Programming 3.7.6 Zone Setup PROGRAMMING 1=WALKTEST 2=SYSTEM 3=ZONE SETUP Maintenance Screen #2 Pressing 3 while viewing Maintenance Screen #2 will display the following screen: ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99 Zone Setup Screen Pressing 1 while viewing Zone Setup screen will display the following screen: ZONE TO ENABLE Z Enable Screen A flashing cursor appears to the right of the Z. To enable a zone, enter the two digit zone number (00 - 99). After the second digit is entered, the zone will be enabled and the cursor will return to the original position. The next zone to be enabled can then be entered. Press Esc (Escape) to return to the previous screen. Pressing 2 while viewing Zone Setup screen will display the following screen: ZONE TO DISABLE Z Disable Screen A flashing cursor appears to the right of the Z. To disable a zone, enter the two digit zone number (00 - 99). After the second digit is entered, the zone will be disabled and the cursor will return to the original position. The next zone to be disabled can then be entered. Press Esc (Escape) to return to the previous screen. 154 MS-9200UDLS PN 52750:E1 01/27/09 Programming Pressing 3 while viewing Zone Setup screen will display the following screen: SPEC PURPOSE ZONE 1=PAS 97 OFF 2=PRE-SIGNAL 98 OFF 3=TWO STAGE 99 OFF Disable Screen Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose applications. In the above illustration, the three zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning them to input and output devices in the Programming Zone Assignment Screen. Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 97 to activate. By assigning Zone 97 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a PAS condition in the control panel. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition. Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is programmed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning Zone 98 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal condition. Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 108 for a description of this feature. MS-9200UDLS PN 52750:E1 01/27/09 155 Operating Instructions SECTION 4 Operating Instructions 4.1 Panel Control Buttons 4.1.1 Acknowledge/Step The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to steady and also changes the status field on the LCD display from capital letters to small letters. When the piezo is silenced, an acknowledge message is sent to the printer and the history file. Acknowledge also sends a silence piezo command to the optional annunciators connected to the FACP. When more than one event exists, the first press of the Acknowledge/Step key functions as described in the preceding paragraph. Subsequent pressing of the key steps through each off-normal active event, with alarm events having a higher priority than trouble and supervisory events. 4.1.2 Alarm Silence The Alarm Silence key performs the same functions as Acknowledge/Step. In addition, if an alarm exists, it turns off all silenceable NACs (Notification Appliance Circuits) and causes the Alarm Silenced LED to turn on. It also sends an ‘alarm silenced’ message to the printer, history file and optional annunciators. A subsequent new alarm will resound the system NACs. Note that the Alarm Silenced LED is turned off by pressing the Reset key, the Drill key or subsequent activation of the NACs. 4.1.3 Drill/Hold 2 Sec When the Drill key is held for a minimum of two seconds (time required to prevent accidental activations), the FACP turns on both main panel NAC outputs and all silenceable circuits such as control modules that are programmed as silenceable, and turns off the Alarm Silenced LED if it was previously on. The EVAC IN SYSTEM message is shown on the LCD display. The same message is sent to the printer and history file. The Alarm Silence key can be used to turn off all silenceable NAC outputs following activation by the Drill key. 4.1.4 Reset Pressing and releasing the Reset key turns off all control modules and NACs, temporarily turns off resettable power to 4-wire detectors, causes a RESET IN SYSTEM message to be displayed on the LCD and sends the same message to the printer and history file. It also performs a lamp test by turning on all LEDs (except the Ground LED), piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that exists after a reset will resound the system. 156 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions 4.2 LED Indicators The nine LED indicators, which are located on the front panel, operate as follows: AC Power This is a green LED which illuminates if AC power is applied to the FACP. A loss of AC power will turn off this LED Fire Alarm This red LED flashes when one or more alarms occur. It illuminates steady when the Acknowledge/Step or Alarm Silence key is pressed. The Fire Alarm LED turns off when the Reset key is pressed. The LED will remain off if all alarms have been cleared. Supervisory This is a yellow LED that flashes when one or more supervisory conditions occur, such as a sprinkler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm Silence key is pressed. It turns off when the Reset key is pressed and remains off if all supervisory alarms have been cleared. Trouble This is a yellow LED that flashes when one or more trouble conditions occur. It stays on steady when the Acknowledge/Step or Alarm Silence key is pressed. The LED turns off when all trouble conditions are cleared. This LED will also illuminate if the microprocessor watchdog circuit is activated. Maintenance This is a yellow LED that flashes to indicate that a smoke detector requires cleaning or replacement due to an invalid chamber reading or excessive drift. Alarm Silenced This is a yellow LED that turns on after the Alarm Silence key is pressed while an alarm condition exists. It turns off when the Drill or Reset key is pressed. Disabled This is a yellow LED that flashes to indicate that a zone, NAC, detector or module has been temporarily disabled in programming by the user. Battery This is a yellow LED that flashes to indicate a low battery voltage condition. Ground This is a yellow LED that flashes to indicate a ground fault condition (zero impedance from the FACP to ground). Primary Line Active This is a red LED that indicates the primary phone line is active. Secondary Line Active This is a red LED that indicates the secondary phone line is active Kiss-off This is a green LED that blinks when a Central Station has acknowledged receipt of each transmitted message or when a portion of upload or download data has been accepted from a Service Terminal MS-9200UDLS PN 52750:E1 01/27/09 157 Operating Instructions 4.3 Normal Operation With no alarms or troubles in the system, the display message is System All Normal along with the current time and date as shown below. To set the time and date, refer to the appropriate section in this manual. HONEYWELL LIFE SAFETY SYSTEM ALL NORMAL 10:00A 012106 The MS-9200UDLS performs the following functions at regular intervals while in Normal mode: Monitors AC input voltage and battery voltage Monitors and reports status of SLC loop, option cards and control panel Polls all devices on the SLC loop and flashes each device LED while checking for valid replies, alarms, troubles, etc. Refreshes LCD display and updates time Scans control panel keypad for key presses Performs autotest for all SLC devices Tests memory Updates and reads all communications busses (EIA-485, EIA-232, etc.) 4.4 Trouble Operation With no alarms in the system, the detection of a trouble will cause the following: • The piezo to pulse 1 second On and 1 second Off • The system Trouble LED to flash one second On and one second Off • The trouble relay to activate • TROUBL with device type, noun/adjective, address and trouble description will appear on the LCD display • The same message, along with the time and date, is sent to the optional printer and the history buffer. • Communicate the trouble conditions to the Central Station • Terminate upload or download communications Note that specific troubles will initiate additional actions; for example, loss of AC power will turn off the AC Power LED, a ground fault will turn on the Ground LED, etc. 158 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions Addressable Smoke Detectors, Monitor Modules and Control Modules For addressable devices connected to the SLC loop, the following is a typical message that could appear on the LCD display for a device trouble: TROUBL SMOKE (PHOTO) INVREP 10:00A 010806 1D001 The information displayed in the above example provides the following information: • First line in display: The type of event; in this example TROUBL indicating a device trouble Device type identifier; in this example, SMOKE (PHOTO) indicates a Photoelectric smoke detector. Other device type identifiers which can be displayed include SMOKE (ION) for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc. Refer to "Edit Detector" on page 66, "Edit Module Screen for Monitor Module" on page 76 and "Edit Module Screen for Control Modules" on page 85 for information on additional device types. • Second line in display: ; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC. ; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC. • Third line in display: INVREP indicates an invalid reply from the addressable device. Other possible troubles include: U SHORT - indicating a shorted circuit on an addressable device U OPEN - indicating an open circuit on an addressable device U DIRTY1 - maintenance alert indicating that a detector is near but below the allowed alarm limit and is in need of maintenance before the performance is compromised U DIRTY2 - maintenance alert indicating that a detector needs immediate maintenance since it has been within 80% of its alarm threshold for 24 hours U INVREP - maintenance alert indicating a hardware problem in the detector U TEST F - indicating a detector has failed the automatic test operation which functionally checks its sensing chamber and electronics U INV ID - indicating that an incorrect device code (Type ID) has been programmed for an installed device (for example, Photo has been programmed but an Ion detector has been installed) • U SW TBL - indicating a module has failed the testing of its Class A switching relay Fourth line in display: Time; the current time in this example is 10:00A which represents 10:00 AM Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 Device Address; 1D001 in this example 1 represents SLC Loop, D represents a detector and 001 represents device address 001 MS-9200UDLS PN 52750:E1 01/27/09 159 Operating Instructions Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the system Trouble LED to change from flashing to on steady. This block acknowledgment occurs regardless of the number of troubles, alarms and supervisory events active in the system. When the Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the ‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or after the Acknowledge/ Step key is pressed, the ‘clear trouble’ message is sent to the printer and history file. If all troubles clear and there are no supervisory or fire conditions active in the system, the system returns to normal mode operation and the System All Normal message is shown on the LCD display and sent to the history and printer files. The auto-restore feature will restore cleared troubles even if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only troubles exist in the system will have the same effect as pressing the Acknowledge/Step key except the Alarm Silenced LED will light. 4.5 Alarm Operation Alarm operation is similar to trouble operation with the following differences: • • • • • • • • • • • • The piezo sounder produces a steady output as opposed to a pulsed output The Fire Alarm LED flashes 1 second On and 1 second Off The LCD displays Alarm along with the device name, type, address, adjective/noun, associated zones and time/date Communicate the alarm to the Central Station Alarms latch and are not allowed to clear automatically Alarms activate software zones if so programmed Timers for Silence Inhibit, Autosilence and Trouble Reminder are started Alarms activate the general alarm relay and general alarm zone Z00 The trouble relay is not activated Store event in history buffer Terminate upload or download communications Alarms must be Acknowledged before the FACP can be reset A typical alarm display would be as illustrated below: ALARM PULL STATION Z000 10:00A 010806 1M001 Note that the device type, which in this example is PULL STATION, can be any other programmable alarm type. The information displayed in the above example provides the following information: • First line in display: • The type of event; in this example ALARM indicating an alarm condition Device type identifier; in this example, PULL STATION indicates a manual pull box. Other device type identifiers which can be displayed include SMOKE (ION) for Ionization Detector, HEAT for Heat Detector, CONTROL for Control Module and MONITOR for Monitor Module, PULL STATION for a manual pull box, etc. Refer to "Edit Detector" on page 66, "Edit Module Screen for Monitor Module" on page 76 and "Edit Module Screen for Control Modules" on page 85 for information on additional device types. Second line in display: ; refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC. ; refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC. 160 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions • Third line in display: Z000 indicates the zone programmed to this device which, in this example, is general alarm Zone 000. Note that a single device can be programmed to five different zones but only the first zone will be displayed. • Fourth line in display: Time; the current time in this example is 10:00A which represents 10:00 AM Date; the current month, day and year in this example is 01 for January, 08 for the 8th day of the month and 01 for the year 2001 Device Address; 1M001 in this example 1 represents SLC Loop, M represents a module and 001 represents device address 001 4.6 Supervisory Operation Supervisory operation is similar to alarm operation but with the following differences: • The piezo sounder pulses ½ second On and ½ second Off • The Supervisory LED flashes ½ second On and ½ second Off • The LCD displays the status label Active Supervisory along with the device name, type, address, adjective/noun, associated zones and time/date • Communicate the supervisory condition to the Central Station • The supervisory relay is activated • The alarm relay is not activated • NACs will not activate • Silenced alarms are not resounded • Timers are not started • Store event in history buffer • Terminate upload or download communications • Supervisory condition must be Acknowledged before the FACP can be reset A typical Supervisory event would be displayed as illustrated in the following: ACTIVE SUPERVISORY Z000 10:00A 010806 1M001 Note that, like alarms, supervisory signals latch (except when programmed for supervisory autoresettable) and can be assigned to software zones. Supervisory events do not cause resound as do other alarm conditions. Open circuits in supervisory wiring are processed by the control panel the same way as other trouble conditions. Refer to "Alarm Operation" on page 160, for a description of the information displayed on the control panel LCD. MS-9200UDLS PN 52750:E1 01/27/09 161 Operating Instructions 4.7 Process Monitor Operation Process Monitor operation will initiate the following events: • • • • • • • • • • The piezo sounder pulses ¼ second On and ¼ second Off The LCD displays a process monitor message along with the device name, type, address, adjective/noun, associated zones and time/date Communicate the process monitor condition to the Central Station Relays programmed for process monitoring will be activated The alarm relay is not activated NACs will not activate Silenced alarms are not resounded Timers are not started Store event in history buffer Process Monitor condition must be Acknowledged before the FACP can be reset Note that, like supervisories, process monitor signals latch (except when programmed for process monitor autoresettable) and can be assigned to software zones. 4.8 Hazard/Tornado Condition Operation Hazard/Tornado Condition operation will initiate the following events: • • • • • • • • • • • The piezo sounder pulses ½ second On, ½ second Off The LCD displays a hazard message along with the device name, type, address, adjective/noun, associated zones and time/date Communicate the hazard condition to the Central Station Relays programmed for hazard will be activated The alarm relay is not activated NACs will not activate Silenced alarms are not resounded Timers are not started Store event in history buffer Supervisory LED flashes ½ second On, ½ second Off Hazard/Tornado Condition must be Acknowledged before FACP can be reset Hazard conditions latch. They can be assigned to software zones. 4.9 Medical Alert Condition Operation Medical Alert Condition operation will initiate the following events: • • • • • • • • • • • The piezo sounder ½ second On, ½ second Off The LCD displays a medical alert message along with the device name, type, address, adjective/noun, associated zones and time/date Communicate the medical alert condition to the Central Station Relays programmed for medical alert will be activated The alarm relay is not activated NACs will not activate Silenced alarms are not resounded Timers are not started Store event in history buffer Supervisory LED flashes ½ second On, ½ second Off Medical Alert condition must be Acknowledged before FACP can be reset Medical Alert conditions latch. They can be assigned to software zones. 4.10 NAC Operation There are four Style Y (Class B) or two Style Z (Class A) programmable NACs (Notification Appliance Circuits) resident on the MS-9200UDLS main circuit board. All NACs may be programmed as silenceable or nonsilenceable and may also be programmed for steady or coded operation. Coded operation provides a choice between March Time, Temporal or California coding. 162 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions 4.11 Programmed Zone Operation Each addressable detector and monitor module can be assigned to a maximum of five software alarm zones. A general alarm zone Z00 may be listed for output (control) points, but it is not necessary to list Z00 for input points, since this is the default zone for all alarm input devices. Zone Z00 is not activated by supervisory points. When an input device alarms and is not disabled, it activates all software zones assigned to it. An output device that is not disabled is turned on when any of the software zones to which it is programmed become active. Only alarms, hazards/ tornado alerts can turn on any of the four main NACs. 4.12 Disable/Enable Operation Input points which are disabled do not cause an alarm or any zone activation. Disabled output points are held in the off state. All disabled points are treated as if they were in trouble, with the exception being the status label that will be displayed is DISABL. 4.13 Waterflow Circuits Operation If an alarm exists from a monitor module point that has a waterflow type code and its mapped NAC control module outputs are programmed for nonsilenceable operation, the Alarm Silence key will not function. Also, any output zone activated by a waterflow device will not be silenceable if the Waterflow Silenceable option is set to NO in system programming. 4.14 Detector Functions Maintenance Alert Each addressable detector is monitored by the control panel for its maintenance status. If a detector is near but below the allowed alarm limit, a ‘maintenance alert’ message will automatically be displayed, signaling that the detector is in need of servicing. Automatic Test Operation An automatic test of an addressable detector is performed each minute, resulting in a complete SLC loop test in approximately 5 hours (if the loop has the maximum number of devices installed). The detector’s sensing chamber and electronics are functionally tested for normal, safe operation. A trouble message is displayed upon failure of this test. A System Reset will clear this trouble. Type Code Supervision The FACP monitors addressable hardware device codes at slow intervals. Mismatch of any type code, compared to the system program, will cause a device trouble. System Alarm Verification The control panel may be programmed to perform alarm verification to help eliminate the nuisance of false alarms. Alarm verification applies to smoke detectors only. Smoke Detector Data Smoke detector data is monitored by the FACP, eliminating the need to test the sensitivity of each detector at its location. A printout of each detector’s data can be retrieved from the FACP using an optional printer or Windows© HyperTerminal. Detector sensing ability can decrease with age and should be monitored as part of a system’s routine maintenance. 4.15 Time Functions: Real-Time Clock The MS-9200UDLS includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time change-over is programmable and automatic. If both AC and battery are lost, the time must be reset. MS-9200UDLS PN 52750:E1 01/27/09 163 Operating Instructions 4.16 Synchronized NAC Operation Synchronization is a panel feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s devices. NAC synchronization can only be supported properly by the Remote Power Supply Sync Terminal, which follows NAC 1 programming. Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the synchronization feature is selected, only the audible devices will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to operate. 4.17 Coded Operation The NAC circuits resident on the control panel main circuit board can be programmed for coded operation. The available pulse rates which can be programmed for coded operation are as follows: • • • Continuous: March Time: Temporal Code: • • California Code: Two-Stage (depending on Steady output with no pulsing Pulses at 120 ppm (pulses per minute) Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off 10 seconds On, 5 seconds Off Pulses at 20 ppm (pulses per minute) for 3 or 5 minutes programming) and then changes to Temporal 4.18 Presignal Presignal option programs an initiating device to delay the activation of NACs and/or control modules while allowing visual verification by a person. Once a detector or monitor module triggers an alarm, the onboard piezo sounds immediately, but the NACs are not activated for a user programmed time duration of up to three minutes. Note that the alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be programmed to a control module which may be used to activate a sounder or indicator which the installer designates as a Presignal indication. Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal condition. After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs during the programmed time delay, the alarm will be processed immediately, causing activation of the appropriate output zones. The events which occur upon Presignal activation are as follows: onboard piezo sounds immediately control panel LCD display will indicate a presignal event and the active point control points programmed to Zone 98 will activate annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED outputs (NACs and control modules) of associated zones will be inhibited from activating for a user programmed time delay of up to three minutes second alarm occurring anytime during the time delay will cause immediate activation of all associated outputs Presignal does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. Presignal operation requires the approval of the local Authority Having Jurisdiction. 164 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions 4.19 Positive Alarm Sequence PAS (Positive Alarm Sequence) option will program a smoke detector to delay panel activation (including alarm relay and communicator) for a period of 15 seconds. Zone 97, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition. When a detector triggers an alarm, the onboard piezo sounds immediately, but the NACs are prevented from activating for 15 seconds. This inhibit time is factory set and cannot be changed. Pressing the Alarm Silence or Acknowledge/Step key during the 15 second inhibit time will silence the piezo sounder and start a timer which prevents activation of NACs for an additional time duration which can be user programmed for up to three minutes. After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note that if a second alarm occurs during either time delay, the alarm will be processed immediately, causing activation of the appropriate output zones. The events which occur upon PAS activation are as follows: onboard piezo sounds immediately control panel LCD display will indicate a presignal event and the active point control points programmed to Zone 97 will activate ACS annunciators (if enabled) will pulse the Zone 97 PAS LED immediately upon PAS activation. They will sound the local piezo, and pulse the alarm, associated zone and detector address point LEDs after 15 seconds of an unacknowledged PAS activation. Note that if the Alarm Silence or Acknowledge/Step button is pressed, the annunciators will be inhibited from activating for an additional time delay outputs (NACs and control modules) of associated zones will be inhibited from activating for a factory set duration of 15 seconds pressing the Alarm Silence or Acknowledge/Step key will start a timer which inhibits output activation for additional time delay of up to three minutes which is user programmable second alarm occurring anytime during either time delay will cause immediate activation of all associated outputs PAS operation requires the approval of the local Authority Having Jurisdiction. Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS capability until the PAS BYPASS monitor is deactivated. While PAS is inhibited, signaling devices will immediately place the control panel into alarm. This feature may be employed by wiring a normally open device, such as a switch, to a monitor module which has been programmed for PAS BYPASS. MS-9200UDLS PN 52750:E1 01/27/09 165 Operating Instructions 4.20 Special System Timers 4.20.1 Silence Inhibit Timer This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds following an alarm. A new alarm during the initial 60 second period will not cause the timer to restart with a new 60 seconds. Silence Inhibit operation requires the approval of the local Authority Having Jurisdiction. 4.20.2 Autosilence Timer If Autosilence is selected, the notification appliances, programmed as silenceable, will automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the Drill key will restart the timer. Autosilence operation requires the approval of the local Authority Having Jurisdiction. 4.20.3 Trouble Reminder If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the Alarm Silence key is pressed) and every two minutes during a trouble condition (after the Acknowledge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard piezo sounder will occur until the alarm or fault is cleared. Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating that the trouble condition still exists. 4.20.4 Waterflow Retard Timer If selected, this option will delay the activation of a waterflow type alarm for a programmable time duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow device. This feature requires the approval of the local Authority Having Jurisdiction. 4.20.5 Alarm Verification (None or One Minute) If alarm verification is selected, an addressable smoke detector's alarm is ignored for a retard time of 13 seconds and the detector's alarm condition is automatically reset. There will be no alarm indication at the FACP during the Retard period. A confirmation period of 60 seconds follows, during which a subsequent alarm from the same detector will cause the panel to immediately activate the appropriate outputs and indicate the alarm condition at the FACP. If a different detector alarms any time during the first detector's verification period, the panel will immediately activate all appropriate outputs and indicate the alarm condition at the FACP. If no additional detector alarms occur within 73 seconds of the first alarm (13 second retard plus 60 second confirmation), the timer resets and the panel is ready to verify any new detector alarms which may occur. The following is a graphic representation of Alarm Verification. 166 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions 13 sec. 0 sec. CONFIRMATION (60 seconds) RETARD Detector Alarm Verification (Retard + Confirmation) Detector Goes Into Alarm 73 sec. Alarm Ignored Control Panel Processes Alarm if Same Detector is Still in Alarm Control Panel Immediately Processes Alarm Different Detector Alarms During First Detector's Verification Period Note: Alarm Verification is available only for addressable smoke detectors, not conventional smoke detectors. 4.21 Walktest Walktest is a feature which allows one person to test the fire alarm system. An audible walktest will momentarily sound the Notification Appliance Circuits in the building and store the walktest information in a file at the panel. A silent walktest will not sound the NACs but will store the walktest information in a file which can be viewed at the panel. Disabled NAC devices will not activate during walktest. Alarm/Shorted Condition When in audible Walktest, the panel responds to each new alarm and activates its programmed control outputs for four seconds, if those outputs have been programmed for silenceable activation. It also stores each alarm in the walktest history file which can be sent to an optional printer. The stored display will be the same as if the device actually activated except the colon (:) in the time stamp is replaced with an asterisk (*). Note that if the system under test includes one or more enabled MMF-302 monitor modules, the following may apply: If the MMF-302 monitor module is used for a supervised, 2-wire smoke zone, alarming any monitor module in the system will result in the activation of programmed control outputs for an additional eight seconds or less. This is caused by the temporary removal of 24 VDC resettable power from the MMF-302. The MMF-302 reports this loss of power as an open condition in addition to the alarm condition. Open Condition Addressable devices are monitored for fault conditions during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs and control modules programmed for Walktest and mapped to the faulty device, then shut them off after eight seconds. While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change operations). The alarm relay is not activated. MS-9200UDLS PN 52750:E1 01/27/09 167 Operating Instructions 4.22 Read Status Read Status functions do not require a password. The control panel will continue to provide fire protection while in Read Status mode. This mode can be entered while the control panel is in alarm or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to prevent confusion. Read Status Entry When the operator presses the control panel Enter key, the LCD will display the following: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status mode which allows the user to view and print the programmed features and status of the control panel. The following screens will be displayed: READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Read Status Screen #1 READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NACS Read Status Screen #2 READ STATUS 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Read Status Screen #3 168 READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION Read Status Screen #4 READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT Read Status Screen #5 READ STATUS 1=TIME-DATE Read Status Screen #6 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions 4.22.1 System Point READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed: Read Status Screen #1 READ SYSTEM POINT SELECT TYPE 1=DETECTOR 2=MODULE The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for Module. If 1 is pressed, the display will change to the following screen: READ SYSTEM POINT ENTER DETECTOR# *** Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a detector with address 001 on the SLC loop is entered, a display similar to the following will appear: NORMAL SMOKE(PHOTO) NORTH CLASSROOM Z005 V 1D001 The information in the preceding display includes: MS-9200UDLS PN 52750:E1 • NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.) • SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector) • NORTH CLASSROOM - the Adjective/Noun label for this device • Z005 - the first of five possible assigned software zones • 1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001 • V - Alarm Verification Enabled (V = Yes, * = No) • S - Silenceable for control modules (S = Yes, * = No) • W - Walktestable for control and monitor modules (W = Yes, * = No) 01/27/09 169 Operating Instructions Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming information about the selected device, such as: • Enable/Disable Status • Device Type • Alarm Verification On/Off (for detectors) • Walktest Yes/No • PAS (Positive Alarm Sequence) Yes/No (for detectors only) • Pre-Signal Yes/No (for detectors and monitor modules) • Zone Assignments (five maximum) • Chamber Value • Adjective/Noun descriptor • Silenceable Yes/No (for control modules) 4.22.2 Zones READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed: Read Status Screen #1 ZONES 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED Zones Screen #1 ZONES 1=SPECIAL PURPOSE 2=ZONE TYPE 3=ZONE MESSAGE Zones Screen #2 From the preceding screens, the control panel operator can view: 170 • Zones Installed - all software zones programmed into the system (99 maximum) • Zones Enabled - all software zones that are enabled • Zones Disabled - all software zones that have been disabled • Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98 reserved for Pre-signal and 99 reserved for Two Stage • Zone Type - the Type assigned to each installed zone (default is Alarm) • Zone Message - the Message assigned to each installed zone MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions 4.22.3 Power Pressing 3 while viewing Read Status Screen #1 will cause the following screens to be displayed: POWER BATTERY 24 V RST 27.21V 25.31 Power Screen #1 POWER CHARGER NAC 1 NAC 2 28.36V -1.49V -1.49V Power Screen #2 POWER NAC 3 NAC 4 -1.49V -1.49V Power Screen #3 A real-time display of the control panel voltages can be used to determine if a problem exists in the system. Note that Power Screen #3 will only be displayed if the NACKEY NAC option card is installed, in JP8 of the main circuit board, for Class B operation. The following table lists the circuit being measured, possible conditions and their respective voltage ranges: Circuit Condition Voltage Range Normal Battery (nominal) 27.05 to 28.15 VDC Low Battery 20.0 to 20.8 VDC No Battery 0 to 18.36 VDC 24V Resettable Normal 21.25 to 27.50 VDC 24V Nonresettable Normal 21.25 to 27.50 VDC Charger Normal 21.87 to 29.84 VDC Normal -1.3 to -1.6 VDC Open Circuit -2.3 to -2.5 VDC Short Circuit 0 to 1.0 VDC Battery NAC 1 or NAC 2 MS-9200UDLS PN 52750:E1 01/27/09 171 Operating Instructions 4.22.4 Trouble Reminder READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NAC Pressing 1 while viewing Read Status Screen #2 will display the following screen: Read Status Screen #2 TROUBLE REMINDER TROUBLE REM ON The screen indicates whether the Trouble Reminder feature is On or Off. 4.22.5 Timers Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be displayed: TIMERS PAS DELAY PRE SIGNAL WATERFLOW TIMERS AC LOSS DELAY 000 000 000 4 These screens will indicate the delay time, in seconds, for each of the first three possible delay options. The AC Loss Delay time is displayed in hours. 172 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions 4.22.6 NAC Pressing 3 while viewing Read Status Screen #2 will display the following screen: NAC 1=NAC 1 2=NAC 2 3=NAC 3 4=NAC 4 Note that 3=NAC 3 and 4=NAC 4 will always be displayed regardless of how the NACKEY NAC option card is installed. The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed options for NAC 2, 3 to view the programmed options for NAC 3 or 4 to view the programmed options for NAC 4. The resulting screens will display the following information: • Enable/Disable Status • Circuit Type (Bell, Strobe, etc.) • Silenceable/Nonsilenceable • Auto Silence Enable/Disable and time delay (in minutes) • Coding Selection (Temporal, Steady, etc.) • Zone Assignments • Silence Inhibit Enabled/Disabled • Synchronization Type (System Sensor, Wheelock or Gentex) 4.22.7 Relays READ STATUS 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Pressing 1 while viewing Read Status Screen #3 will display the following screen: Read Status Screen #3 RELAY 1=RELAY 1 2=RELAY 2 3=RELAY 3 The operator can view the programmed option for each relay by pressing the corresponding number key. MS-9200UDLS PN 52750:E1 01/27/09 173 Operating Instructions 4.22.8 Program Check Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be displayed: PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed to one of the Notification Appliance Circuits. Use the up and down arrow keys to view all NACs. Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any output zones have not been programmed to at least one input zone. Use the up and down arrow keys to view all zones. Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any input zones have not been programmed to at least one output zone. Use the up and down arrow keys to view all zones. 4.22.9 History Pressing 3 while viewing Read Status Screen #3 will display the following screen: HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS The operator can view all events which have been stored in the history file, only alarms or other events, such as troubles or supervisories, by pressing the corresponding number key. 4.22.10 Annunciators READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION Read Status Screen #4 Pressing 1 while viewing Read Status Screen #4 will display the following screens: ANNUNCIATORS TERM ENABLED YES 2=ACS OPTIONS 3=ANN-BUS OPTIONS Annunciator Screen 174 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions The Annunciator Screen indicates if Terminal mode options are enabled or disabled. Pressing 2 for ACS Options while viewing the Annunciator Screen allows the operator to view the ACS Options screen: ACS OPTIONS ACS ENABLED 2=ACS ADDRESSES UDACT ENABLED NO NO ACS Options Screen The ACS Options screen indicates if the ACS option has been enabled YES or disabled NO. Pressing 2 for ACS Addresses while viewing the ACS Options screen will display screens with ACS addresses 1 -31 and whether a device is installed at that address YES or not installed NO. The ACS Options screen indicates if a UDACT is installed YES or if a UDACT is not installed NO. Pressing 3 for ANN-BUS Options while viewing the Annunciator Screen will display the following screens: ANN-BUS ENABLED NO 2=MODULES INSTALLED 3=ANN-S/PG OPTIONS ANN-BUS Screen #1 ANN-BUS 1=ANN-80 OPTIONS ANN-BUS Screen #2 The ANN-BUS Screen #1 indicates if the ANN-BUS has been enabled YES or disabled NO. Pressing 2 for Modules Installed while viewing ANN-BUS Screen #1 will display screens for ANN-BUS Addresses 1 -8 and the devices installed at each address. Subscreen will display the options that have been programmed for each device. Pressing 3 for ANN-S/PG Options while viewing ANN-BUS Screen #1 will display the options selected for the installed serial or parallel printer. Pressing 1 for ANN-80 Options while viewing ANN-BUS Screen #2 will display the options selected for the installed ANN-80 annunciators. MS-9200UDLS PN 52750:E1 01/27/09 175 Operating Instructions 4.22.11 Phone Line Pressing 2 while viewing Read Status Screen #4 will display the following screen: PHONE LINE PRIMARY TOUCHTONE SECONDARY TOUCHTONE 3=SUPERV PHONE LINE The second and third lines of this screen indicate that both the Primary and Secondary phone lines have been configured for touchtone dialing operation. Pressing 3 while viewing the Phone Line screen will cause the following screen to be displayed: SUPERVISE PHONE LINE PHONE LINE 2 NO This screen indicates whether or not Phone Line 2 is being supervised. In this example, Phone Line 2 No indicates the phone line is not being supervised. 4.22.12 Central Station READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION Read Status Screen #4 Pressing 3 while viewing Read Status Screen #4 will display the following screens: CENTRAL STATION REPORTING ENABLED REPORT BOTH CALL LIMIT 10 Central Station Screen #1 CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=REPORT STYLE Central Station Screen #2 Central Station Screen #1 indicates whether the Central Station Reporting is enabled or disabled, if the Reports will be sent to one or both the Primary and Secondary Central Station phone numbers and the Call Limit for DACT trouble calls within a 24 hour period. 176 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions Central Station Screen #2 provides information on the Primary and Secondary Central Station programming which includes: • Test Time Interval • Account Code • 24 Hour Test Time • Phone Number • Communication Format • Event Codes 4.22.13 Service Terminal READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT Pressing 1 while viewing Read Status Screen #5 will display the following screens: Read Status Screen #5 SERVICE TERMINAL RING COUNT Service Terminal Screen The Panel ID number is displayed as the first item in Service Terminal Screen #1. To view the phone number for each Service Terminal, press 2 for Terminal 1 or 3 for Terminal 2 while viewing Service Terminal Screen #1. The Ring Count is displayed in Service Terminal Screen #2. 4.22.14 Printer/PC Pressing 2 while viewing Read Status Screen #5 will display the following screen: PRINTER PC PRINTER PC PR4800 Printer/PC Screen The display will inform the operator as to whether the control panel is configured for a printer or a PC. In the example above, PR4800 indicates that the panel is configured for a printer with a baud rate of 4,800. MS-9200UDLS PN 52750:E1 01/27/09 177 Operating Instructions 4.22.15 Print READ STATUS 1=FUTURE USE 2=PRINTER/PC 3=PRINT To print program data or control panel status, press 3 while viewing Read Status Screen #5. The following screens will be displayed: Read Status Screen #5 PRINT 1=HISTORY 2=WALKTEST LOG 3=DETECTOR DATA Print Screen #1 PRINT 1=EXIT PRINTING Print Screen #2 Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail all of the system activities since the file was last cleared from memory. Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on page 113 for additional information on the display. Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each addressable smoke detector connected to the system. A printout, similar to the following example, will be generated if an optional printer is connected to the FACP. DEVICE# DEVICE TYPE 1D001 1D002 1D003 1D004 1D005 1D006 1D007 1D008 1D009 SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) %DRIFT COMP 20 20 21 20 21 20 20 20 20 CHAMBER 1281 1281 1259 1309 1281 1322 1280 1215 1310 TIME/DATE 12:01AM 01-08-2001 12:01AM 01-08-2001 12:01AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 12:02AM 01-08-2001 Chamber Value The Chamber value should be within the indicated range for the following smoke detectors: • SD350(T), D350P(R) and SD300(T) Addressable Photoelectric Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.) • CP350 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration of 0.50%/ft. to 1.44%/ft.) If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the detector and check the Chamber value again. If the reading is still not within the acceptable range, immediately replace the detector. 178 MS-9200UDLS PN 52750:E1 01/27/09 Operating Instructions Drift Compensation Drift compensation uses software algorithms that identify and compensate for longterm changes in the data readings from each addressable smoke detector. These longterm changes in detector data readings are typically caused by dirt and dust accumulation inside the smoke chamber. Drift compensation performs the following functions: • Samples photoelectric smoke detectors every 6 seconds and ionization smoke detectors every 3 seconds • Allows a smoke detector to retain its original ability to detect actual smoke and resist false alarms, even as dirt and dust accumulate • Reduces maintenance requirements by allowing the control panel to automatically perform the periodic sensitivity measurements required by NFPA Standard 72 The FACP software also provides filters to remove transient noise signals, usually caused by electrical interference. Maintenance Alert The software determines when the drift compensation for a detector reaches an unacceptable level that can compromise detector performance. When a detector reaches an unacceptable level, the control panel indicates a maintenance alert. Table 4.1 summarizes the three levels of maintenance alert: Maintenance Level FACP Status Displays Indicates Low Chamber Value INVREP A hardware problem in the detector Maintenance Alert DIRTY1 Dust accumulation that is near but below the allowed limit. DIRTY 1 indicates the need for maintenance before the performance of the detector is compromised Maintenance Urgent DIRTY2 Dust accumulation above the allowed limit. Table 4.1 Maintenance Alert Levels Figure 4.1 illustrates a graphic representation of the maintenance levels: Maintenance Urgent DIRTY Maintenance Alert Acceptable Range Low Chamber Reading LOW VALUE Figure 4.1 Diagram of Maintenance Levels MS-9200UDLS PN 52750:E1 01/27/09 179 Operating Instructions 4.22.16 Time-Date READ STATUS 1=TIME-DATE The operator can view the daylight savings time and the month and week when daylight savings time will begin and end. Pressing 1 while viewing Read Status Screen #6 will display the following screens: Read Status Screen #6 DAYLIGHT SAVINGS ENABLED YES START MONTH MAR START WEEK WEEK-2 DAYLIGHT SAVINGS END MONTH NOV END WEEK WEEK-1 180 MS-9200UDLS PN 52750:E1 01/27/09 Central Station Communications Central Station Communications SECTION 5 The control panel transmits zone and system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two optional 7 foot telephone cords are available for this purpose and can be purchased separately. The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound, the yellow trouble LED will blink, the LCD display will indicate the phone line trouble and the trouble condition will be reported to the Central Station over the remaining operational phone line. The control panel comes with line seizure capability provided for both the primary and secondary telephone line interfaces. Any time that the control panel needs to make a call to a Central Station, line seizure will disconnect any local premises phones sharing the same telephone line. All transmissions to the Central Stations will be sent over the primary phone line. In the event of noisy phone lines, transmissions will be sent over the backup secondary phone line. Two phone numbers must be programmed, the primary Central Station phone number and the secondary Central Station phone number. All system reports will be transmitted to the primary Central Station phone number. Reports will automatically be sent to the secondary Central Station phone number if attempts to transmits to the primary Central Station phone number are unsuccessful. If 10 total attempts to communicate are unsuccessful, a Communicator Failure report will be displayed. Note that as an option, all reports may also be sent to the secondary Central Station phone number. The MS-9200UDLS meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. The general priority reporting structure is: 1. Zone Alarms and Restores 2. Zone Troubles and Restores 3. System Troubles and Restores 4. 24-hour Test MS-9200UDLS PN 52750:E1 01/27/09 181 Central Station Communications 5.1 Transmittal Priorities The integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in descending order: 1. Alarms (highest priority level) Pull stations Waterflow Smoke detector Other alarm types 2. Supervisory Zone 3. System Troubles Zone disabled Fire drill AC fail (after delay) Zonal faults Earth fault Low battery Telephone line fault Notification Appliance Circuits fault Communication trouble Annunciator trouble System off normal 4. Restoral Reports Zone alarm Supervisory Zone(s) enabled Fire drill AC Zone fault Earth Battery Telephone line Notification Appliance Circuits Communication Annunciator trouble System off normal 5. 24 Hour Test (lowest priority) Red LEDs are provided on the circuit board to identify which telephone line is activated. Also, a green LED labeled Kissoff will turn on whenever the control panel has successfully transmitted reports to the Central Station. The Kissoff LED may turn on several times during communications with a Central Station. 182 MS-9200UDLS PN 52750:E1 01/27/09 Central Station Communications The table below shows UL listed receivers which are compatible with the MS-9200UDLS. FBI CP220FB (10) SurGard MLR-2000 (9) SurGard System III (8) Silent Knight 9800 (4) SIA-DCS-8 1 SIA-DCS-20 2 Ademco Contact ID Radionics 6600 (6) Format SurGard MLR2 (7) Silent Knight 9500 (3) 0 Ademco 685 (1) Ademco MX8000 (2) Osborne Hoffman 2000E (5) Table 5.1 Compatible UL Listed Receivers 1. With 685-8 Line Card with Rev. 4.4d software 2. With 124060V206B and 124063 Line Card Rev. B 3. With version V2.4 Receiver and 126047 Line Card Rev. G 4. With 124077V2.00 Receiver and 126047 Line Card Rev. M 5. With V.7301 Receiver S/W 6. With 01.01.03 Receiver S/W and Line Card 01.01.03 7. With software V1.86 8. With software V1.72 9. With DSP4016 and V1.6 Line Card 10. With software V3.9 IMPORTANT! It is the installer’s responsibility to ensure that the Digital Alarm Communicator/ Transmitter is compatible with the Central Station Receiver, utilized by the monitoring service, prior to installation. The Compatibility Table provides a list of compatible receivers and associated software versions for the receivers. Changes in the hardware and/or software by the receiver manufacturers may affect the receiver compatibility with the FACP DACT. After completing the installation, communication between the DACT and Central Station Receiver must be tested and verified. MS-9200UDLS PN 52750:E1 01/27/09 183 Remote Site Upload/Download SECTION 6 Remote Site Upload/Download Important! The FACP will automatically reset 2 minutes after completion of a user program download via the PS-Tools programming utility. To prevent program corruption, the operator must wait until this panel reset occurs before performing any panel operations. The control panel may be programmed or interrogated off-site via the public switched telephone network or locally using a USB cable. Any personal computer with Windows™ XP or NEWER, with a 2400 baud compatible modem and Upload/Download software PS-Tools, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status, system voltages, time and date. The control panel may also communicate to a local PC at the job-site. The PC must be connected to the USB connector J12 on the FACP main circuit board. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required. Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "Remote Site Upload/Download" on page 184). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option. CAUTION: After successfully downloading a program, make certain to perform the following steps: 1. Print out all programmed data via Print Mode or manually view programmed entries and compare to intended program data 2. Test all affected panel operations 3. Immediately correct any problems found 6.1 Remote Download NFPA 72 requirements state that a technician be on-site and at the control panel whenever the PKPlus Programming Utility is used to download any information to the FACP. This applies to local and remote programming. For this reason, a new option has been added to the FACP which allows an individual at the FACP to enter a password and either enable the proprietary mode where downloading will be allowed at any time or access a specific password protected screen where downloading will be allowed regardless of the current proprietary setting. The Remote Download option can be selected from the main menu screen as shown below: 1=READ STATUS MODE 2=PROGRAMMING MODE 3=REMOTE DOWNLOAD Pressing 3 for Remote Download while viewing the main menu will cause the following screen to be displayed: REMOTE DOWNLOAD ENTER PASSWORD ***** 184 MS-9200UDLS PN 52750:E1 01/27/09 Remote Site Upload/Download The Remote Download password (default 00000) must be entered to access the Remote Download feature. Note that the default password can be changed using the Password Change option (refer to "Password Change" on page 143). Entering the correct password will cause the following screen to be displayed: REMOTE DOWNLOAD 1=PROPRIETARY 2=ACCEPT DOWNLOAD NO Pressing 1 for Proprietary No (factory default setting), while viewing the Remote Download screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the 1 key will cause the display to toggle between Proprietary No and Proprietary Yes. Selecting Proprietary Yes will program the FACP to allow remote programming downloads from the PK-Plus programming utility at all times without the need to access the Remote Download screen. Pressing 2 for Accept Download will cause the following screen to be displayed: *ALLOWING DOWNLOADS* IF YOU EXIT THIS SCREEN DOWNLOADS WILL BE DISABLED! While this screen is displayed, remote programming downloads are allowed regardless of the Proprietary setting. Exiting this screen will disable any further downloads to the FACP. Also, following 30 minutes of inactivity (including up/downloading), the Accept Download screen will time-out, causing the display to return to the System All Normal screen. 6.2 Transferring a Program The first time that the control panel is downloaded (whether initiated at the jobsite or remotely), a secret code is loaded in by a Service Terminal. Future upload or download requests cause verification of the secret code by the control panel before processing of data is allowed. If the secret code is not verified, the control panel will terminate the request. While the control panel is communicating with the Service Terminal, one of the DACT’s red phone line active LEDs and the green Kissoff LED will turn on steady. In order to download the panel (whether initiated at the jobsite or remotely), the following must be true: The control panel must be in the Normal Mode of operation. Downloading is not possible if the panel is in any other mode There cannot be any active communications ongoing with a Central Station receiver All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be in a standby state with no new information waiting to be transmitted to a Central Station MS-9200UDLS PN 52750:E1 01/27/09 185 Remote Site Upload/Download 6.2.1 Security Features Upload and download with the control panel have been carefully designed to include key security features to ensure proper functionality. Any time a transfer is initiated, the control panel and the Service Terminal will communicate and transfer data before contacting a Central Station. When the data transfers are completed and the control panel disconnects from the Service Terminal, the control panel will call the Central Station and report one of the following conditions: • Upload/Download request received • Upload and/or Download request successful • Upload/Download failed The key features are listed and explained in the following sections. Secret Code Verification A secret code is stored in the control panel by a Service Terminal to prevent unauthorized access. The secret code is created at the Service Terminal by the master user and cannot be viewed or changed by anyone other than a master user. Viewing of the secret code is prohibited at the control panel. Prior to allowing an upload or download of data, the control panel will verify the secret code transmitted by the Service Terminal. Time-out at Control Panel Upon answering an incoming call on either the primary or secondary Central Station phone line, the control panel will listen for a modem connection signal. If this signal is not received within 50 seconds, the control panel will disconnect the call. Upon successful connection (secret code verified), if no communication occurs within 30 minutes, the panel will disconnect the call. Upon time-out, transfer activity will be reported to the Central Station (if enabled) and the connection will be terminated. Error Checking As each block of data is received by the control panel, it is checked for accuracy. If an error is detected, the block is retransmitted until correct, up to a maximum of four times. If the Secret Code is not verified and four errors occur, the call is disconnected and the report that the upload/ download was not successful is called to the Central Station(s). Central Station Data Protection The primary and secondary Central Station phone numbers, communications format, account code, test time and programmable event codes are vital Central Station information. These blocks of data are protected from partial programming due to faulty phone connections, line noise and other errors. This prevents the panel from being confused due to a wrong phone number, account code, test time and most critical formatting errors. 186 MS-9200UDLS PN 52750:E1 01/27/09 Power Supply Calculations Power Supply Calculations SECTION 7 7.1 Overview This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: 1. Calculating the total amount of AC branch circuit current required to operate the system 2. Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load 3. Calculating the size of batteries required to support the system if an AC power loss occurs 4. Selecting the proper batteries for your system 7.2 Calculating the AC Branch Circuit The control panel requires connection to a separate, dedicated AC branch circuit, which must be labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm branch circuit. The branch circuit wire must run continuously, without any disconnect devices, from the power source to the control panel. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2) wire with 600 volt insulation for this branch circuit. Use Table 7.1 , to determine the total amount of current, in AC amperes (A), that must be supplied to the system. Table 7.1 AC Branch Circuit Requirements Device Type Number of Devices MS-9200UDLS or MS-9200UDLSE 1 Current Draw (AC amps) Total Current per Device X 3.00 or 1.50 = CHG-75 [ ] X 2.05 = CHG-120F [ ] X 2.00 = [ ] X [ ] Sum Column for AC Branch Current Required MS-9200UDLS PN 52750:E1 01/27/09 = = 187 Power Supply Calculations 7.3 Calculating the System Current Draw 7.3.1 Overview The control panel must be able to power all internal and external devices continuously during the non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when primary power is applied, use Calculation Column 1 in Table 7.3 on page 189. The control panel must support a larger load current during a fire alarm condition. To calculate the fire alarm load on the power supply, use Calculation Column 2 in Table 7.3 on page 189. The secondary power source (batteries) must be able to power the system during a primary power loss. To calculate the non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7.3 on page 189. When calculating current draw and the battery size, note the following: • ‘Primary’ refers to the main power source for the control panel • ‘Secondary’ refers to the control panel’s backup batteries • All currents are given in amperes (A). Table 7.2 shows how to convert milliamperes and microamperes to full amperes. Table 7.2 Converting to Full Amperes To convert... Multiply Milliamperes (mA) to amperes (A) mA x 0.001 Microamperes (µA) to amperes (A) µA x 0.000001 Example 3 mA x 0.001 = 0.003A 300 µA x 0.000001 = 0.0003 A 7.3.2 How to Use Table 7.3 on page 189 to Calculate System Current Draw Use Table 7.3 on page 189 to calculate current draws as follows: 1. Enter the quantity of devices in all three columns 2. Enter the current draw where required. Refer to the Device Compatibility Document for compatible devices and their current draw 3. Calculate the current draws for each in all columns 4. Sum the total current for each column 5. Copy the totals from Column 2 and Column 3 to Table 7.4 on page 190 Following are the types of current that can be entered into Table 7.3 on page 189: Calculation Column 1 - The primary supply current load that the control panel must support during a non-fire alarm condition, with AC power applied. Calculation Column 2 - The primary supply current load that the control panel must support during a fire alarm condition, with AC power applied. Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm condition during a loss of AC power. 188 MS-9200UDLS PN 52750:E1 01/27/09 Power Supply Calculations Table 7.3 contains columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 7.4 on page 190. Table 7.3 System Current Draw Calculations Device Type Main Circuit Board ANN-80 ANN-LED ANN-RLY ANN-I/O ANN-S/PG ACM-8RF ACM-16ATF ACM-32AF AEM-16ATF AEM-32AF AFM-16ATF AFM-32AF AFM-16AF LDM-32F LDM-E32F LCD-80F 4XTMF 4-wire Detector Heads Power Supervision Relays6 CP350 & CP355 SD350 & SD355 SD350T & SD355T AD350 & AD355 H350 & H355 H350R & H355R H355HT D350P & D350PL D350RP & D350RPL B501BH & B501BHT7 B224RB Relay Base B224BI Isolator Base MMF-300 MMF-300-10 MDF-300 MMF-301 MMF-302 MMF-302-6 BG-12LX CMF-300 CMF-300-6 CRF-300 CRF-300-6 I300 NAC #18 NAC #2 NAC #3 NAC #4 Current Draw from TB3 (nonalarm9) Sum each column10 for totals Calculation Column 1 Primary, Non-Fire Alarm Current (amps) [ [ [ [ [ [ Qty 1 ] ] ] ] ] ] X[current draw]= X[0.340]= X[0.037]= X[0.028]= X[0.015]= X[0.035]= X[0.045]= X[0.030]= [ ] [ ] Calculation Column 2 Primary, Fire Alarm Current (amps) Total 0.340 [ [ [ [ [ [ Qty 1 ] ] ] ] ] ] X [current draw] = X[0.360]= X[0.040]= X[0.068]= X[0.075]= X[0.200]= X[0.045]= X[0.158]1= X[0.040]= [ ] X[0.002]= [ ] Calculation Column 3 Secondary, Non-Fire Alarm Current (amps) Total 0.360 [ [ [ [ [ [ ] ] ] ] ] ] X[current draw]= X[0.137]= X[0.015]= X[0.028]= X[0.015]= X[0.035]= X[0.045]= X[0.030]= X[0.056]2= [ ] X[0.040]= X[0.018]2= [ ] X[0.002]= 2 Qty 1 [ ] X[0.040]= [ ] X[0.056] = [ ] X[0.040]= [ [ [ [ [ [ ] ] ] ] ] ] X[0.025]= X[0.040]= X[0.002]= X[0.064]= X[0.005]= X[ ]5= [ [ [ [ [ [ ] ] ] ] ] ] X[0.065]2= X[0.056]3= X[0.018]= X[0.064]= X[0.011]4= X[ ]= [ [ [ [ [ [ ] ] ] ] ] ] X[0.025]= X[0.040]= X[0.002]= X[0.025]= X[0.005]= X[ ]= [ ] X[0.025]= [ ] X[0.025]= [ ] X[0.025]= [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.001]= X[0.00050 ]= X[0.00045]= X[0.00040]= X[0.00350]= X[0.00075]= X[0.000375]= X[0.00027]= X[0.00200]= X[0.00030]= X[0.00039]= X[0.00225]= X[0.00027]= X[0.00145]= X[0.00040]= [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ [ ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] ] X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.00030]= X[0.001]= X[0.00050 ]= X[0.00045 ]= X[0.00040]= X[0.00350]= X[0.00075]= X[0.000375]= X[0.00027]= X[0.00200]= X[0.00030]= X[0.00039]= X[0.00225]= X[0.00027]= X[0.00145]= X[0.00040]= [ ] [ ]= Primary Non-Alarm = maximum alarm draw for all devices [ [ [ [ ] ] ] ] X[ X[ X[ X[ [ ] [ Primary Alarm = 0.400 Total 0.137 ]= ]= ]= ]= ]= [ ]= Secondary Non-Alarm = Table Footnote 1. 2. 3. 4. All eight ACM-8RF relays activated on a single module. All annunciator LEDs on LDM-32F with LEDs on If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005 amps. 5. Refer to the Device Compatibility Document for standby current. 6. Must use compatible listed Power Supervision Relay. 7. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source. 8. Current limitation of Terminal TB3 & TB4 circuits is 2.5 amps per NAC. 9. The total standby current must include both the nonresettable/resettable (TB1 Terminals 1 & 2) and resettable (TB1 Terminals 3 & 4) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. Current limitations of TB3 & TB4 circuits is 2.5 amps per NAC output and 0.3 amps per special application auxiliary power output 10.Total current draw listed above cannot exceed 6.0 amps. MS-9200UDLS PN 52750:E1 01/27/09 189 Power Supply Calculations 7.4 Calculating the Battery Size Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 7.4 as follows: 1. Enter the totals from Table 7.3 on page 189, Calculation Columns 2 and 3 where shown 2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below) 3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours 4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH) 5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet door Table 7.4 Total Secondary Power Requirements at 24 VDC Secondary Standby Load (total from Table 7.3 Calculation Column 3) [ ] Required Standby Time (24 hours) Primary Alarm Load (total from Table 7.3 Calculation Column 2) Required Alarm Time (for 5 min., enter 0.084, for 10 min., enter 0.168) [ X[ = AH = AH Sum of Standby and Alarm Ampere Hours = AH Multiply by the Derating Factor X 1.2 Battery Size, Total Ampere Hours Required = ] X[ ] ] AH 7.4.1 NFPA Battery Requirements • NFPA 72 Local, Proprietary, Central, Auxiliary and Remote Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm 7.4.2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calculated in Table 7.4 . The control panel can charge batteries in the 7 AH to 18 AH range. The control panel cabinet is capable of housing batteries up to 18 AH. Batteries larger than 18 AH require a UL listed external battery charger and cabinet such as the BB-26, BB-55F or other UL listed external battery cabinet. 190 MS-9200UDLS PN 52750:E1 01/27/09 Software Zones Software Zones APPENDIX A A.1 Correlations Setup and configuration of an addressable system is different than a conventional system. In a conventional system, assignment of input devices (smoke detectors, pull stations, heat detectors, etc.) to zones is accomplished through wiring. The wiring is direct from clearly marked panel terminals to any device assigned to a particular zone. Connection of output devices (horns, bells, strobes, etc.) in a conventional system is accomplished by direct wiring of the output devices to Notification Appliance Circuit terminals. In an addressable system, a minimum of a single pair of wires (SLC communication loop) is used to connect all addressable input and output devices. Communications between the FACP (Fire Alarm Control Panel) and all addressable devices takes place over the wire pair which originates from the FACP. Software programming is used to configure the system as opposed to direct wiring. Zone assignments are created via software means, hence the term software zones. Setup of an MS-9200UDLS software zone is accomplished by panel programming. Each addressable device can be assigned to a maximum of five software zones. Each software zone, however, may have from 1 to 99 addressable input devices assigned to it and from 1 to 99 addressable output devices assigned to it. Monitor and control modules comprise one group of 99 addresses, with each module having a unique address from 1 to 99. Detectors comprise a separate group of 99 addresses, each detector having a unique address from 1 to 99 in its group. Be careful not to duplicate addresses within any one group (modules and detectors). Refer to the following page for an example of zoning. In the example on the following page: • Zone 01 has the following addressable devices assigned to it: SD350 smoke detectors with addresses 01 and 02 MMF-300 monitor module with address 01 MMF-302 monitor module with address 02 and 03 CMF-300 control modules with addresses 05, 06, 07, 09 and 13 • Zone 02 has the following addressable devices assigned to it: MMF-302 monitor module with addresses 02 and 03 CP350 smoke detectors with addresses 03 and 04 CMF-300 control modules with addresses 08, 09 and 10 • Zone 03 has the following addressable devices assigned to it: SD350 smoke detectors with addresses 05, 06 and 07 MMF-302 control module with address 04 CMF-300 control modules with addresses 09, 11 and 12 The example points out some of the key assignment features of the MS-9200UDLS. Addresses of detectors are not duplicated. Addresses of monitor and control modules are not duplicated. The control module with address 09 is assigned to three software zones (providing floor above and floor below). Be careful to properly plan the installation prior to installing any devices. MS-9200UDLS PN 52750:E1 01/27/09 191 Software Zones Correlation of Input and Output Zones Input Devices Zones SD350 01 Output Devices CMF-300 13 SD350 02 CMF-300 05 ZONE 01 MMF-300 01 CMF-300 06 MMF-302 02 CMF-300 07 CMF-300 09 MMF-302 03 CP350 03 ZONE 02 CMF-300 08 CMF-300 10 CP300 04 SD350 05 CMF-300 11 SD350 06 SD350 07 MMF-302 04 ZONE 03 CMF-300 12 The zone correlations which are shown graphically above are also presented in Table A.1 on page 193 and Table A.2 on page 194. 192 MS-9200UDLS PN 52750:E1 01/27/09 Software Zones Table A.1 Detector Programming Sheet Example Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Device Type SD350 SD350 CP350 CP350 SD350 SD350 SD350 Zone Number 1 1 2 2 3 3 3 MS-9200UDLS PN 52750:E1 01/27/09 DETECTOR ZONE ASSIGNMENT ADJ/NOUN Address Device Type FIRST HALL 51 ELEV. LOBBY 52 2ND FLOOR 53 ROOM 210 54 3RD FLOOR 55 MEZZANINE 56 MECH. ROOM 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 Zone Number ADJ/NOUN 193 Software Zones Table A.2 Module Programming Sheet Example Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 194 Device Type MMF-300 MMF-302 MMF-302 MMF-302 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 CMF-300 MONITOR/CONTROL MODULE ZONE ASSIGNMENT Zone ADJ/ Address Device Zone Number NOUN Type Number 1 51 1, 2 52 1, 2 53 3 54 1 55 1 56 1 57 2 58 1, 2, 3 59 2 60 3 61 3 62 1 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 ADJ/NOUN MS-9200UDLS PN 52750:E1 01/27/09 Software Zones Table A.3 Blank Detector Programming Sheet - 1 of 2 Address Device Type Zone Number 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 MS-9200UDLS PN 52750:E1 DETECTOR ZONE ASSIGNMENT ADJ/ Address Device NOUN Type 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 01/27/09 Zone Number ADJ/NOUN 195 Software Zones Table A.4 Blank Module Programming Sheet - 1 of 2 Address 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 196 Device Type MONITOR/CONTROL MODULE ZONE ASSIGNMENT Zone ADJ/ Address Device Zone Number NOUN Type Number 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 ADJ/NOUN MS-9200UDLS PN 52750:E1 01/27/09 Default Programming Default Programming APPENDIX B The following table provides a list of the programming options and their factory default settings. Program Option Detector Programming Detector Type Detector Verification Detector Walktest Detector PAS Detector Presignal Detector Zone Assign. Detector Adj/Noun Module Programming Module Type Module Walktest (not used) Module Presignal Module Zone Assign. Module Adj/Noun Zone 0 Enable Zone 1 Enable Zone 2 Enable Zone 3 Enable .........................through.......... Zone 96 Enable Zones 97, 98 & 99 (future) Loop Style Loop Protocol Trouble Reminder Banner Time Format Hours Setting Minutes Setting Second Settings AM-PM Setting Month Setting Day Setting Year Setting Daylight Savings Month Start Daylight Savings Week Start Daylight Savings Month End Daylight Savings Week End Daylight Savings Verification PAS Timer Presignal Timer Waterflow Retard Timer NAC 1, 2, 3 & 4 Enable NAC 1, 2, 3 & 4 Silenceable NAC 1, 2, 3 & 4 Type NAC 1, 2, 3 & 4 Sync Type NAC 1, 2, 3 & 4 Autosilence NAC 1, 2, 3 & 4 Coding NAC 1, 2, 3 & 4 Zones NAC 1, 2, 3 & 4 Silence Inhibit MS-9200UDLS PN 52750:E1 Factory Default Not Installed Smoke-Photo Off Yes No No 000 only none Not Installed Monitor Yes No 000 only none Enabled Enabled Enabled Enabled ..................... Enabled Enabled Style 4 LITESPEED Off 12 Hr 12 00 AM 01 01 00 Enabled March Week 2 November Week 1 OFF 0 0 0 Enabled Yes Bell System Sensor 0 Steady Zone 000 only No 01/27/09 Program Option Relay 1 Relay 2 Relay 3 Annunciator Terminal Mode Annunciator ACS Mode UDACT ACS Installed Onboard DACT Printer-PC Printer Baud Service Terminal Panel ID Ring Count Primary Phone Type Secondary Phone Type DACT Communication AC Loss Delay Backup Reporting Primary Reporting Style Secondary Reporting Style Primary Account Code Secondary Account Code Primary 24 Hour Test Time Secondary 24 Hour Test Time Primary Phone Number Secondary Phone Number Primary DACT Format Secondary DACT Format ANN Enabled ANN-BUS Modules Addr. 1 - 8 ANN-S/PG Port ANN-S/PG Baud ANN-S/PG Data Bits ANN-S/PG Parity ANN-S/PG Stop Bits ANN-S/PG Offline Timer ANN-S/PG Printer Supervision ANN-80 Piezo Enabled ANN-80 Lock Enabled ANN-80 Acknowledge Button Enabled ANN-80 Silence Button Enabled ANN-80 Reset Button Enabled ANN-80 Drill Button Enabled ANN-I/O Point/Zone ANN-I/O Range ANN-I/O Active LEDs Only ANN-RLY Relay 1 ................through....................... ANN-RLY Relay 10 ANN-LED Point/Zone ANN-LED Alarms/ATS (Alarm, Trbl, Supv) ANN-LED Range Factory Default Alarm Trouble (fixed) Supervisory No No No No No No 9600 0000 0 Touchtone Touchtone OFF 2 First Available Report Point Report Point 0000 0000 0100 0200 Ademco Contact ID Ademco Contact ID No None Parallel 9600 7 Even 1 60 No Yes Yes Yes Yes Yes Yes Zone 00-29 Zone 1 ............ Zone 10 Zone ATS 0-9 197 NFPA Standard-Specific Requirements APPENDIX C NFPA Standard-Specific Requirements The MS-9200UDLS has been designed for use in commercial, industrial and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix. The minimum system components required for compliance with the appropriate NFPA standard are listed below: MS-9200UDLS Control Panel Contains the main control board, cabinet (backbox and door), main power supply transformer and power supply. Batteries Refer to "Power Supply Calculations" on page 187, for Standby Power Requirements. Initiating Devices Connected to one of the control panel's Initiating Device Circuits. Notification Appliances Connected to the control panel's Notification Appliance Circuits via a control module. The following additional equipment is needed for compliance with the NFPA 72 standards listed below: NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR: NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed Central Station DACR or Protected Premises Receiving Unit. This unit must be installed as outlined in "Digital Alarm Communicator/Transmitter" on page 19. OR 4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver. See Figure C.2, “Remote Station Connection Using 4XTMF Module,” on page 200, for installation instructions for this unit. NFPA 72 Auxiliary Fire Alarm System F Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit must be installed as illustrated in the section titled "4XTMF Transmitter Module Installation" on page 56 and as outlined in Figure C.1, “Municipal Box Connected to F Transmitter Module,” on page 199. NFPA 72 Proprietary Fire Alarm System MS-9200UDLS Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.3, “Proprietary Protective Signaling System,” on page 201, for installation instructions for this unit. 198 MS-9200UDLS PN 52750:E1 01/27/09 NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm System All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions. Notes: 1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box. 2. Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module and circuit. 3. Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory relay. 4. Refer to "4XTMF Transmitter Module Installation" on page 56 for detailed information. Figure C.1 Municipal Box Connected to F Transmitter Module FIRE + Municipal Box Circuit Gamewell Model M34-56 Local Energy Municipal Box Polarities shown in alarm condition Nonpower-limited + - F Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module MS-9200UDLS PN 52750:E1 01/27/09 199 NFPA Standard-Specific Requirements NFPA 72 Remote Station Protective Signaling System Notes: 1. Cut Jumper JP3 on the MS-9200UDLS main circuit board to supervise placement of the 4XTMF module. 2. Refer to "4XTMF Transmitter Module Installation" on page 56 for detailed information. RS82 Remote Station Receiver UL listed. Refer to Instruction Manual for Remote Station Receiver Model RS82. + - Polarity Shown is Normal Standby + Power-limited (Dummy load with a 4.7KΩ, ¼ watt resistor when no connection is made) Cutting TBL Jumper allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. 4XTMF Transmitter Module Figure C.2 Remote Station Connection Using 4XTMF Module 200 MS-9200UDLS PN 52750:E1 01/27/09 NFPA Standard-Specific Requirements NFPA 72 Proprietary Protective Signaling Systems MS-9200UDLS Addressable Fire Control Panel MS-9200UDLS Main Board Form-C Alarm contact programmed to activate on General Alarm. Form-C Trouble contact which will automatically activate on any Trouble condition. Form-C relay contact programmed to activate on Supervisory condition. Notes: 1. Connection between the MS-9200UDLS and the transmitter are supervised by the transmitter. 2. This MS-9200UDLS/Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System. Figure C.3 Proprietary Protective Signaling System MS-9200UDLS PN 52750:E1 01/27/09 201 NFPA Standard-Specific Requirements C.1 Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/ Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter manufacturer’s manual for details. Typical Central Station/Remote Station Transmitter Module *Note: The Trouble Relay is a fail-safe relay. With power applied to the FACP and no troubles in the panel, the wiring should be connected to the NO and C contacts as indicated in the illustration. ms9200udlsdryxmit.cdr Trouble* Alarm Supervisory Typical Input Zone Triggers FACP Main Circuit Board Figure C.4 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter 202 MS-9200UDLS PN 52750:E1 01/27/09 NFPA Standard-Specific Requirements C.2 MBT-1 Municipal Box Trip - Silenceable The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the FACP and a Local Energy Municipal Box. The use of an addressable control module programmed for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the panel or box. The addressable Control Module must be programmed as Silenceable and General Alarm. Connect wires to two red terminals on box. Note: 10Ω maximum loop resistance due to wiring from power supply to Municipal Box. Gamewell Model M34-56 Local Energy Municipal Box (All contacts shown in energized position). white wire MBT-1 - To next device + on SLC Loop Braided-shield/Drain Wire brown wire EOLR-1 Power Supervision Relay red black + CMF-300 Control Module* Alarm polarity shown! + - SLC Loop B+ 24 VDC, Nonresettable -B Shield 92udls-MBT1new.cdr FACP Main Circuit Board *If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion charts for legacy and newer versions of the modules. Figure C.5 MBT-1 Silenceable MS-9200UDLS PN 52750:E1 01/27/09 203 FACP with Keltron FACP with Keltron APPENDIX D The following figure illustrates the connections between the FACP and Keltron Receiver/ Transmitter. CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron modules are not shown in actual order. Follow Keltron manual and module markings for exact terminal locations to prevent severe module damage! IMPORTANT! All connections between the FACP and Keltron modules must be made within 20 feet and enclosed within conduit or equivalently protected against mechanical injury. Keltron 95M3158 TTM-RPS 1. Terminals 7 and 8: Remote station alarm/trouble inputs. 2. Terminals 9 and 10: Sprinkler supervisory input. *Note: For more information, refer to Keltron manual. Sprinkler Supervisory Signal Alarm/Trouble Signal 24 VDC nonresettable power 4XTMF Module Note: Cut TBL jumper on 4XTMF module to send alarm/trouble signal from the same pair or terminals. Fire Alarm Control Panel (terminal blocks are not shown in their actual positions in order to clarify wiring connections. 204 MS-9200UDLS PN 52750:E1 01/27/09 Wire Requirements APPENDIX E Wire Requirements T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot exceed 10,000 feet (3,000 m). Connecting external system accessories to the MS-9200UDLS main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, gauge and run length for each MS-9200UDLS circuit. Reference the chart below to specify wire requirements and limitations for each MS-9200UDLS circuit. Note: 1. If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by exclusively employing electronic sounders instead of more electronically noisy notification appliances such as electromechanical bells or horns. 2. The SLC can be programmed to operate in LiteSpeed mode (factory default setting) for a quicker device response time. While shielded wire is not required in LiteSpeed mode, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Use the following table to determine the specific wiring requirements for the SLC when unshielded wire is used: Refer Table E.1 on page 206 and Table E.2 on page 207 for wiring requirements. MS-9200UDLS PN 52750:E1 01/27/09 205 Wire Requirements Table E.1 FACP Wire Specifications CIRCUIT CONNECTIONS WIRE REQUIREMENTS Circuit Type Circuit Function Wire Type and Limitations SLC loop (power-limited) Connects to Addressable Devices Twisted, shielded pair 40 ohms maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops CLIP MODE Recommended Max. Distance Feet (meters) 10,000 (3,000 m) 8,000 (2,400 m) 4,875 (1,450 m) 3,225 (980 m) LITESPEED MODE Twisted, unshielded pair 40 ohms maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops 10,000 (3,000 m) 8,000 (2,400 m) 4,875 (1,450 m) 3,225 (980 m) Wire Gauge and Compatible Brands 12 AWG (3.25 mm2): Genesis 4410, Signal 98230, Belden 9583, WPW999 14 AWG (2.00 mm2):Genesis 4408 & 4608 Signal 98430, Belden 9581, WPW995 16 AWG (1.30 mm2): Genesis 4406 & 4606 Signal 98630, Belden 9575, WPW991 Direct Burial Cable Isotec NP713110VNQ-S 18 AWG (0.75 mm2): Genesis 4402 & 4602 Signal 98300, Belden 9574, WPW975 Direct Burial Cable Isotec NP714110VNQ-S 12 AWG (3.25 mm2): Belden 5020UL & 6020UL, Genesis WG-4315 & WG-4515 14 AWG (2.00 mm2):Belden 5120UL & 6120UL, Genesis WG-4313 & WG-4513 16 AWG (1.30 mm2): Belden 5220UL & 6220UL, Genesis WG-4311 & WG-4511 18 AWG (0.75 mm2): Belden 5320UL & 6320UL, Genesis WG-4306 & WG-4506 Untwisted, unshielded pair1 3,000 (900 m) 12-18 AWG (3.25 - 0.75 mm2) using listed wire ACS-BUS (EIA-485) (power-limited) Connects to annunciator modules Twisted pair with a characteristic impedance of 120 ohms 6,000 (1,800 m) 12 AWG (0.75 mm2) ANN-BUS (EIA-485) (power-limited) Connects to annunciator modules Twisted pair 6,000 (1,800 m) Refer to "ANN-BUS Wiring" on page 24 for information on device wiring EIA-232 (power-limited) connects to remote PC computer Twisted, shielded pair 50 (15 m) 18 AWG (0.75 mm2) minimum MMF-300 and MMF-301 (power-limited) Initiating Device Circuit Maximum loop wire resistance is 40 ohms for the MMF-300 and 20 ohms for the MMF-301 2,500 (760 m) 12-18 AWG (3.25 - 0.75 mm2) MMF-302 (power-limited) Initiating Device Circuit No more than a 2.4 volt drop allowed at end of circuit. Maximum loop wire resistance is 25 ohms 2,500 (760 m) 12-18 AWG (3.25 - 0.75 mm2) CMF-300 (power-limited) Notification Appliance Circuit In alarm, no more than a 1.2 volt drop allowed at end of circuit Distance limitation set by 1.2 volt maximum line drop 12-18 AWG (3.25 - 0.75 mm2) Remote Sync Output Provides strobe and normal sync for remote NAC power supplies Untwisted, unshielded pair wire Distance set by 295 ohm resistance limitation 12-18 AWG (3.25 - 0.75 mm2) Table Footnote 1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection. 206 MS-9200UDLS PN 52750:E1 01/27/09 Wire Requirements E.1 NAC Wiring The following table lists NAC wiring requirements for the FACP. Table E.2 NAC Wiring Requirements for FACP CLASS-A Max. allowable wire pair length (feet) CLASS-B Max. allowable wire pair length (feet) NAC Load (Amps) Max. allowable total loop resistance (ohms) AWG 12 solid AWG 14 solid AWG 16 solid AWG 18 solid AWG 12 solid AWG 14 solid AWG 16 solid AWG 18 solid 0.25 12.72 3295 2072 1301 819 1648 1036 650 409 0.5 6.36 1648 1036 650 409 824 518 325 205 0.75 4.24 1098 691 434 273 549 345 217 136 1 3.18 824 518 325 205 412 259 163 102 1.25 2.54 659 414 260 164 330 207 130 82 1.5 2.12 549 345 217 136 275 173 108 68 1.75 1.82 471 296 186 117 235 148 93 58 2 1.59 412 259 163 102 206 129 81 511 2.25 1.41 366 230 145 91 183 115 72 45 2.5 1.27 330 207 130 82 165 104 65 41 Notes: 1. Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2005 Edition) Table 8, Conductor Properties. MS-9200UDLS PN 52750:E1 01/27/09 207 HVAC Control APPENDIX F HVAC Control The FACP can be programmed to shut down a building’s HVAC fans in the event of a fire. The fans cannot be restarted until the fire alarm condition has been cleared and the FACP has been reset to a normal (non-alarm) condition. IMPORTANT! This HVAC feature is not to be used for smoke control. It is only designed to shut down fans during a fire alarm condition. F.1 Control Module Operation F.1.1 HVAC SHUTDN The HVAC SHUTDN type code can be assigned to any addressable control relay module for the purpose of shutting down HVAC fans during a fire alarm condition. Devices connected to a module with this type code are unsupervised. To program this feature in the FACP: • • • Program the HVAC SHUTDN type code to the control module which will be used to shut down the fans (refer to Type under the section titled "Edit Module Screen for Control Modules" on page 85). Program the control module to a software zone and program alarm input devices which, when activated are to cause fan shutdown, to the same software zone (refer to Zone Assignment under the section titled "Edit Module Screen for Control Modules" on page 85). Monitor the control module using an addressable monitor module programmed for Trouble Monitor. The monitor module label should be programmed to indicate HVAC SHUTDOWN. When the control module is active (HVAC SHUTDN), the monitor module will indicate a trouble condition at the FACP and the display should indicate the HVAC is shut down. Once activated, the HVAC SHUTDN control module remains activated, even if the FACP is silenced or reset. After the alarm condition on the FACP has been cleared and the panel reset, the HVAC SHUTDN control module remains activated and the fans remain off. The monitor module programmed for Trouble Monitor which is being used to supervise the control module, will indicate a trouble condition at the control panel and the LCD should display that the HVAC is shut down. The fans can only be restarted when the HVAC SHUTDN control module is deactivated by the HVAC RESTART module. F.2 Monitor Module Operation F.2.1 HVAC RESTART The HVAC RESTART type code can be assigned to any addressable monitor module for the purpose of resetting (deactivating) the HVAC SHUTDN control module and turning the fans back on. The HVAC RESTART monitor module acts globally throughout the FACP system and therefore is not programmed to a particular software zone. To program this feature in the FACP: • Program the HVAC RESTART type code to the monitor module which will be used to deactivate the HVAC SHUTDN control module and restart the fans (refer to Type Monitor under the section titled "Edit Module Screen for Monitor Module" on page 76). The HVAC RESTART monitor module does not latch when activated. Pressing a switch connected to the monitor module will deactivate the HVAC SHUTDN control relay module only if there are no alarm conditions. The HVAC SHUTDN control relay module can be deactivated if trouble conditions exist on the FACP. 208 MS-9200UDLS PN 52750:E1 01/27/09 HVAC Control F.2.2 HVAC OVRRIDE The HVAC OVRRIDE type code can be assigned to any addressable monitor module for the purpose of overriding or preventing the HVAC SHUTDN control modules from activating. The HVAC OVRRIDE monitor module acts globally throughout the FACP system and therefore is not programmed to a particular software zone. To program this feature in the FACP: • Program the HVAC OVRRIDE type code to the monitor module which will be used to override the HVAC SHUTDN control module and prevent the fans from turning off (refer to Type Monitor under the section titled "Edit Module Screen for Monitor Module" on page 76). The HVAC OVRRIDE monitor module does not latch when activated. Activating a switch connected to the monitor module will override all HVAC SHUTDN control relay modules in the system, preventing the HVAC SHUTDN modules from activating and causing the FACP LCD to display an active HVAC OVRRIDE module and turn on the Supervisory LED. Releasing the switch will allow the HVAC SHUTDN control relay modules to activate with subsequent alarms, turning off the fans. As an example, pressing the HVAC OVRRIDE switch with no alarms in the system will prevent the fans from being turned off when an alarm does occur. As long as the switch is activated, the fans will not shutdown for any alarms. If the system is still in alarm when the switch is released, the fans will not shutdown unless another alarm occurs after the switch is released. Important! If an alarm exists in the system and HVAC Shutdown has already occurred, HVAC OVRRIDE will have no effect on the HVAC SHUTDN control relay modules. HVAC OVRRIDE will prevent HVAC Shutdown from occurring only if it is initiated prior to an alarm condition. Note: Activation of the HVAC OVRRIDE module causes a supervisory event that will be communicated to the Central Station if enabled. MS-9200UDLS PN 52750:E1 01/27/09 209 Ademco Contact ID Format Event Code Descriptions Ademco Contact ID Format Event Code Descriptions APPENDIX G This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format. G.1 Transmission Format Between DACT and Receiver The transmission string for the Ademco Contact ID Format is as follows: SSSS 18 QXYZ GG CCC where SSSS = Four digit Subscriber ID Account Code 18 = Identifies transmission as Contact ID to the receiver at the Central Station Q = Event Qualifier where 1 = New Event and 3 = New Restore XYZ = Event code GG = Group number CCC = Zone/Point number Notes: 1. 18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the alarm and trouble report. 2. GG Group Number is fixed at '00' and cannot be changed. 3. CCC for Zone or Point Number: Zone Number is transmitted as ‘01’ for zone 1 up to ‘99’ for zone 99 Point Number is transmitted as ‘01’ for point/address 1 up to ‘99’ for point/address 99 G.2 Ademco Contact ID Typical Printout A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows: Time Date 11:28 11:28 11:28 11:28 11:28 11:28 11:28 11:28 11:28 11:28 03/25 03/25 03/25 03/25 03/25 03/25 03/25 03/25 03/25 03/25 Rcvr/Line ID 11 11 11 11 11 11 11 11 11 11 SSSS QXYZ GG CCCC 7777 7777 7777 7777 7777 7777 7777 7777 7777 7777 E110 E111 E380 E570 R110 R111 R380 R570 E158 E151 00 00 00 00 00 00 00 00 00 00 C001 - general fire alarm on zone one C002 - smoke detector alarm on zone two C003 - fault on zone three C009 - Zone nine disabled C001 - Zone one alarm restored C002 - smoke detector zone two restored C003 - zone three fault restored C009 - zone nine reenabled C006 - high temperature, zone six C007 - gas detected, zone seven Notes: 1. 11 is an example of a Receiver/Line Card, showing which receiver and line card the message was transmitted to. 2. Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or R for New Restore. 210 MS-9200UDLS PN 52750:E1 01/27/09 Ademco Contact ID Format Event Code Descriptions EVENT CODE CLASSIFICATIONS 100 ALARMS Medical Fire Panic Burglary General 24 Hour 200 SUPERVISORY Fire 300 TROUBLES 400 OPEN/CLOSE REMOTE ACCESS System Sounder/ Relay System Peripheral Communication Protective Loop Sensor Open/Close Remote Access Access Control EVENT 500 DISABLES/ BYPASSES System Sounder/ Relay System Peripheral Communication 600 TEST/ MISC. Test MESSAGE Medical Alarms - 100 100 Medical 101 Pendant transmitter 102 Fail to report in EMERG - Personal Emergency - # EMERG - Personal Emergency - # EMERG - Fail to Check-in - # Fire Alarms - 110 110 Fire Alarm 111 Smoke 112 Combustion 113 Waterflow 114 Heat 115 Pull station 116 Duct 117 Flame 118 Near Alarm FIRE - Fire Alarm - # FIRE - Smoke Detector - # FIRE - Combustion - # FIRE - Waterflow - # FIRE - Heat Sensor - # FIRE - Pull Station - # FIRE - Duct Sensor - # FIRE - Flame Sensor - # FIRE - Near Alarm - # Panic Alarms - 120 120 Panic Alarm 121 Duress 122 Silent 123 Audible PANIC - Panic - # PANIC - Duress PANIC - Silent Panic - # PANIC - Audible Panic - # Burglar Alarms - 130 130 Burglary 131 Perimeter 132 Interior 133 24-Hour 134 Entry/Exit 135 Day/Night 136 Outdoor 137 Tamper 138 Near AlarmBURG - Near Alarm - # BURG - Burglary - # BURG - Perimeter - # BURG - Interior - # BURG - 24-Hour - # BURG - Entry/Exit - # BURG - Day/Night - # BURG - Outdoor - # BURG - Tamper - # General Alarms - 140 140 General AlarmALARM - General Alarm - # 141 Polling loop open ALARM - Polling Loop Open - # 142 Polling loop short ALARM - Polling Loop Short - # 143 Expansion module failure ALARM - Exp. Module Fail - # 144 Sensor tamper ALARM - Sensor Tamper - # 145 Expansion module tamper ALARM - Exp. Module Tamper - # MS-9200UDLS PN 52750:E1 01/27/09 211 Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE 24 Hour Non-Burglary - 150 and 160 150 24-Hour Non-Burg ALARM - 24-Hr. Non-Burg - # 151 Gas detected ALARM - Gas Detected - # 152 Refrigeration ALARM - Refrigeration - # 153 Loss of heat ALARM - Heating System - # 154 Water leakage ALARM - Water Leakage - # 155 Foil break ALARM - Foil Break - # 156 Day trouble ALARM - Day Zone - # 157 Low bottled gas level ALARM - Low Gas Level - # 158 High temp ALARM - High Temperature - # 159 Low temp ALARM - Low Temperature - # 161 Loss of air flow ALARM - Air Flow - # Fire Supervisory - 200 and 210 200 Fire supervisory 201 Low water pressure 202 Low CO2 203 Gate valve sensor 204 Low water level 205 Pump activated 206 Pump failure SUPER. - Fire Supervisory - # SUPER. - Low Water Pressure - # SUPER. - Low CO2 SUPER. - Gate Valve - # SUPER. - Low Water Level - # SUPER. - Pump Activation - # SUPER. - Pump Failure - # System Troubles - 300 and 310 300 System trouble 301 AC loss 302 Low system battery 303 RAM checksum bad 304 ROM checksum bad 305 System reset 306 Panel program changed 307 Self-test failure 308 System shutdown 309 Battery test failure 310 Ground fault 311 No battery TROUBLE - System Trouble TROUBLE - AC Power TROUBLE - System Low Battery TROUBLE -RAM Checksum (restore not applicable) TROUBLE -ROM Checksum (restore not applicable) TROUBLE - System Reset (restore not applicable) TROUBLE - Prog. Change (restore not applicable) TROUBLE - Self Test Failure TROUBLE - System Shutdown TROUBLE - Battery Test Failure TROUBLE - Ground Fault - # TROUBLE - No Battery Sounder/Relay Troubles - 320 320 Sounder/Relay 321 Bell 1 322 Bell 2 323 Alarm relay 324 Trouble relay 325 Reversing 326 Bell 3 327 Bell 4 TROUBLE - Sounder Relay - # TROUBLE - Bell/Siren #1 TROUBLE - Bell/Siren #2 TROUBLE - Alarm Relay TROUBLE - Trouble Relay TROUBLE - Reversing Relay TROUBLE - Bell/Siren #3 TROUBLE - Bell/Siren #4 System Peripheral Troubles - 330 and 340 330 System peripheral TROUBLE - Sys. Peripheral - # 331 Polling loop open TROUBLE - Polling Loop Open 332 Polling loop short TROUBLE - Polling Loop Short 333 Expansion module failure TROUBLE - Exp. Module Fail - # 334 Repeater failure TROUBLE - Repeater Failure - # 335 Local printer paper out TROUBLE - Printer Paper Out 336 Local printer failure TROUBLE - Local Printer 212 MS-9200UDLS PN 52750:E1 01/27/09 Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE Communication Troubles - 350 and 360 350 Communication TROUBLE - Communication Trouble 351 Telco 1 fault TROUBLE - Phone Line #1 352 Telco 2 fault TROUBLE - Phone Line #2 353 Long range radio xmitter faultTROUBLE - Radio Transmitter 354 Fail to communicate TROUBLE - Fail to Communicate 355 Loss of radio supervision TROUBLE - Radio Supervision 356 Loss of central polling TROUBLE - Central Radio Polling Protection Loop Troubles - 370 370 Protection loop TROUBLE - Protection Loop - # 371 Protection loop open TROUBLE - Protection Loop Open - # 372 Protection loop short TROUBLE - Protection Loop Short - # 373 Fire Trouble TROUBLE - Fire Loop - # Sensor Troubles - 380 380 Sensor trouble TROUBLE - Sensor Trouble - # 381 Loss of supervision - RF TROUBLE - RF Sensor Supervision - # 382 Loss of supervision - RPMTROUBLE - RPM Sensor Supervision - # 383 Sensor tamper TROUBLE - Sensor Tamper - # 384 RF transmitter low battery TROUBLE - RF Sensor Batt. - # Open/Close - 400 400 Open/Close 401 Open/Close by user 402 Group Open/Close 403 Automatic Open/Close 404 Late Open/Close 405 Deferred Open/Close 406 Cancel 407 Remote arm/disarm 408 Quick arm 409 Keyswitch Open/Close OPENING OPENING - User # OPENING - Group User # OPENING - Automatic OPENING - Late Opening not used OPENING - Cancel OPENING - Remote Opening not applicable OPENING - Keyswitch CLOSING CLOSING - User # CLOSING - Group User # CLOSING - Automatic CLOSING - Late Closing not used Closing not used CLOSING - Remote CLOSING - Quick arm CLOSING - Keyswitch Remote Access - 410 411 Callback request made REMOTE - Callback Requested (restore not applicable) 412 Success - download/accessREMOTE - Successful Access (restore not applicable) 413 Unsuccessful access REMOTE - Unsuccessful Access (restore not applicable) 414 System shutdown REMOTE - System Shutdown 415 Dialer shutdown REMOTE - Dialer Shutdown 416 Success - upload/access REMOTE - Successful Access (restore not applicable) Access Control - 420 421 Access denied 422 Access report by user ACCESS - Access Denied - User # (restore not used) ACCESS - Access Gained - User # (restore not used) System Disables - 500 and 510 MS-9200UDLS PN 52750:E1 01/27/09 213 Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE Sounder/Relay Disables - 520 520 Sounder/Relay disable DISABLE - Sounder/Relay - # 521 Bell 1 disable DISABLE - Bell/Siren - #1 522 Bell 2 disable DISABLE - Bell/Siren - #2 523 Alarm relay disable DISABLE - Alarm Relay 524 Trouble relay disable DISABLE - Trouble Relay 525 Reversing relay disable DISABLE - Reversing Relay 526 Bell 3 disable DISABLE - Bell/Siren - #3 527 Bell 4 disable DISABLE - Bell/Siren - #4 System Peripheral Disables - 530 and 540 Communication Disables - 550 and 560 551 Dialer disabled DISABLE - Dialer Disable 552 Radio transmitter disabledDISABLE - Radio Disable 214 Bypasses - 570 570 Zone bypass 571 Fire bypass 572 24-Hour zone bypass 573 Burglar bypass 574 Group bypass BYPASS - Zone Bypass - # BYPASS - Fire Bypass - # BYPASS - 24-Hour Bypass - # BYPASS - Burg. Bypass - # BYPASS - Group Bypass - # Test Misc. - 600 601 Manual trigger test 602 Periodic test report 603 Periodic RF transmission 604 Fire test 605 Status report to follow 606 Listen-in to follow 607 Walk test mode 608 System abnormal test TEST - Manually Triggered (restore not applicable) TEST - Periodic (restore not applicable) TEST - Periodic Radio (restore not applicable) TEST - Fire Test (restore not used) STATUS - Status Follows (restore not applicable) LISTEN - Listen-in Active (restore not applicable) TEST - Walk Test Mode TEST - System Abnormal Test MS-9200UDLS PN 52750:E1 01/27/09 Central Station Points Central Station Points APPENDIX H The control panel transmits Central Station Reports in a numerical format which indicates the FACP addressable device address that is reporting. The following table indicates the Central Station Report (CS Report) number that will be transmitted and the addressable device address it represents. Table H.1 Addressable DETECTORS CS Report Detector Address CS Report Detector Address CS Report Detector Address CS Report Detector Address 001 001 033 033 065 065 097 097 002 002 034 034 066 066 098 098 003 003 035 035 067 067 099 099 004 004 036 036 068 068 100 005 005 037 037 069 069 006 006 038 038 070 070 007 007 039 039 071 071 008 008 040 040 072 072 009 009 041 041 073 073 010 010 042 042 074 074 011 011 043 043 075 075 012 012 044 044 076 076 013 013 045 045 077 077 014 014 046 046 078 078 015 015 047 047 079 079 016 016 048 048 080 080 017 017 049 049 081 081 018 018 050 050 082 082 019 019 051 051 083 083 020 020 052 052 084 084 021 021 053 053 085 085 022 022 054 054 086 086 023 023 055 055 087 087 024 024 056 056 088 088 025 025 057 057 089 089 026 026 058 058 090 090 027 027 059 059 091 091 028 028 060 060 092 092 029 029 061 061 093 093 030 030 062 062 094 094 031 031 063 063 095 095 032 032 064 064 096 096 MS-9200UDLS PN 52750:E1 01/27/09 not used through 159 not used 215 Central Station Points Table H.2 Addressable MODULES 216 CS Report Module Address CS Report Module Address CS Report Module Address CS Report Module Address 160 001 192 033 224 065 256 097 161 002 193 034 225 066 257 098 162 003 194 035 226 067 258 099 163 004 195 036 227 068 164 005 196 037 228 069 165 006 197 038 229 070 166 007 198 039 230 071 167 008 199 040 231 072 168 009 200 041 232 073 169 010 201 042 233 074 170 011 202 043 234 075 171 012 203 044 235 076 172 013 204 045 236 077 173 014 205 046 237 078 174 015 206 047 238 079 175 016 207 048 239 080 176 017 208 049 240 081 177 018 209 050 241 082 178 019 210 051 242 083 179 020 211 052 243 084 180 021 212 053 244 085 181 022 213 054 245 086 182 023 214 055 246 087 183 024 215 056 247 088 184 025 216 057 248 089 185 026 217 058 249 090 186 027 218 059 250 091 187 028 219 060 251 092 188 029 220 061 252 093 189 030 221 062 253 094 190 031 222 063 254 095 191 032 223 064 255 096 MS-9200UDLS PN 52750:E1 01/27/09 Index Numerics 24 Hour Test Time 137 300 Series addressable devices 21 4XTMF module 199, 200 coil resistance 56 current 56 installation 56 installation steps 57 see also Transmitter Module 15, 21 supervisory relay config. 57 voltage 56 A AC Branch Circuit calculations 187 AC Loss Delay 104 AC Power 49 current 16 current, maximum 49 voltage 16 wiring 16, 49 Account Code 136 Acknowledge/Step 18, 156 ACM Series see also annunciator 41 ACM-16ATF Annunciator 41 ACM-32AF Annunciator 41 ACM-8RF 15 contact rating 41 see also Relay Control Module 41 ACS 41 ACS LED annunciator 15 add Detector 65 add Module 75 addressable 14 addressable detectors see also detectors 15 Addressable Device Accessories 21 addressable modules 20 see also modules 15 addressing annunciators 117 see also device addressing 97 see also module or detector addressing 20 Ademco Contact ID format 210 Adjective control module 89 list 72 monitor module 82 multiple entries 74 MS-9200UDLS PN 52750:E1 01/27/09 AEM-16ATF Annunciator 41 AEM-32AF Annunciator 41 Alarm 160 Alarm Silence 18, 156 alarm verification 15, 69, 163, 166 ANN-LED 39 ANN-LED Annunciator Module 38 annunciator 24 ACM 15, 117 ACM-8RF 15 LCD-80F 15 LDM Graphic 15 annunciator addressing 117 annunciator, graphic see also LDM Series 41 annunciator, remote see also LCD-80F 41 Automatic Test Operation 163 Autoprogramming 15, 60, 64 Autosilence 15, 166 NAC 107 auxiliary DC power 49 B backbox 20 see also cabinet 48 Backup Reporting 134 Banner 97 setting 98 battery 20 cable connection 49 charger 19 charger capacity 16 Charging Circuit 16 see also secondary power 16, 49 battery box 22 battery charger 23 disable 16 external 23 baud rate 142 BB-55F see also battery box 20, 22 C cabinet dimensions 47, 48 cabinet mounting 45 Calculate System Current Draw 188 Calculating the Battery Size 190 Canadian Applications 44 Canadian Option 97, 111 217 Index Central Station 133, 186 account code 136 communications 181 phone number 137 Phone Numbers 135 point assignments 215 report style 141 Central Station Reports 215 CHG-120F see also battery charger 23 see also remote battery charger 16 CHG-75 see also battery charger 23 see also remote battery charger 16 Clasic Loop Interface Protocol 97 Class A 50 Class B 50 NAC wiring 51 CLIP mode see also Classic Loop Interface Protocol 97 Clock Format 101 Coded Operation 164 Coding NAC 107 coding two stage operation 108 communications format 138 Control Buttons 156 control module 20 description display 91 display 85 edit 85 enable/disable 86 noun 90 noun/adjective 88, 89 silenceable 88 type 87 type codes 87 Correlations 191 current AC Power 49 availability 17 maximum 17 Current Draw Calculations 189 D DACT enable 131 onboard 131 data 218 see also detector data and sensitivity 163 Data Entry via computer keyboard 59 via keypad 59 data values see also detector data and sensitivity 15 Date setting 101 Daylight Savings Time 101 DC power nonresettable 49 resettable 49 see also auxiliary DC power 49 Default Programming 197 Delete Detector 66 Delete Module 76 Description control module 91 detector label 74 monitor module 84 Detector add 65 adding description 71 delete 66 edit 66 enable/disable 68 screen display 67 type 69 verification 69 detector data 163, 178, 179 acceptable range 178 printout 178 Detector Programming 65 device addressing 97 Digital Communicator 42 dimensions cabinet 47 DIRTY1 179 DIRTY2 179 Disable 93 Disable Point Maintenance Level 148 Downloading 185 dress panel 20, 22 drift compensation 15, 179 definition 179 Drill 18, 156 E earth ground 49 edit MS-9200UDLS PN 52750:E1 01/27/09 Index control module 85 detector 66 detector screens 67 module, monitor 76 EIA-232 58 for PC/Printer connection 17 see also Printer/PC interface 15 EIA-485 for ACS annunciators 17 for LCD-80F 17 Enable 92 Enable/Disable control module 86 detector 68 module, monitor 79 End-of-Line Resistor Assembly 21 Enter key 62 Erase History 112 Error Checking 186 event code classification 211 event codes 138 exiting programming 61, 62 Read Status 61, 62 F FACP see also Fire Alarm Control Panel 14 Features 14 Fire Alarm Control Panel see also FACP 14 Form-C relay 19, 41, 50 G general alarm zone 81 see also zone Z00 71 ground fault 58 H Hazard Condition 162 History 112 erase 112 Maintenance Level 149 view events 112 History file 15 HVAC Control 208 HVAC OVRRIDE 209 HVAC RESTART 208 HVAC SHUTDN 208 I Indicators 18 Installation 45 MS-9200UDLS PN 52750:E1 01/27/09 intelligent 14 Internet Protocol DACT 23 Inventory 14 INVREP 179 IPDACT 23 K Key Panel 18 function keys 18 service/program keys 18 keyboard and keypad 59 Keypad/Display removal and installation 55 L lamp test 18 LCD display 15, 18 LCD-80F annunciator 15, 41 LDM Series annunciator 41 LDM-32 Graphic Annunciator 15 LED AC Power 157 Alarm Silenced 157 Battery 157 Disabled 157 Fire Alarm 157 Ground 157 Kiss-off 157 Maintenance 157 Primary Line Active 157 Secondary Line Active 157 see also Indicators 18 Supervisory 157 Trouble 157 LED annunciator 41 Local Energy Municipal Box Service 56 Local Programming 60 Loop Setup 96 M Maintenance Alert 15, 163 levels 179 maintenance alert 179 Maintenance Program Level 2 61, 147 Manual programming 60 Master Program Level 1 61, 63 Medical Alert 162 Mode key 62 Module add 75 addressing 20 delete 76 219 Index edit monitor 76 enable/disable 79 see also addressable modules 20 Module Programming 75 Monitor module 20 adjective 82 enable/disable 79 noun 83 noun/adjective 81 type 79 type action 80 Type list 79 type selection 80 Mounting cabinet 45 main circuit board 45 municipal box transmitter see also 4XTMF module 56 N NAC 16, 19, 104, 106, 162 Auto Silence 107 coded 164 coding 107 current 16 End-of-Line Resistor 16 power 14 see also Notification Appliance Circuit 14, 50 silence inhibit 109 silenceable 106 Style configuration 51 Style Y wiring diagram 51 synchronized 164 type codes 106 voltage drop 16 voltage, operating 16 wiring Style 50 NAC enable/disable 105 NAC options 97 NACKEY card 51 N-ELR Mounting Plate 21 NFPA 72 Auxiliary Fire Alarm System 198, 199 NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service 198 NFPA 72 Proprietary Fire Alarm System 198 NFPA 72 Proprietary Protective Signaling Systems 201 NFPA 72 Remote Station Protective Signaling 220 System 200 NFPA Battery Requirements 190 NFPA Standard 198 nonpower-limited relay connections 50 Nonresettable Power 19 current 16, 49 nonsilenceable waterflow 95, 111 Normal 158 normal display 60 Notification Appliance Circuit 16, 104 see also NAC 14, 50 Noun list 73 monitor module 83 multiple entries 74 Noun/Adjective 71, 73 control module 88 monitor module 81 O Operating Instructions 156 Operation alarm 160 disable/enable 163 hazard condition 162 medical alert 162 NAC 162 normal 158 process monitor 162 programmed zone 163 supervisory 161 trouble 158 waterflow 163 Option Modules 21, 55, 115 annunciators/UDACT 115 Printer/PC 142 Options 14 Output Circuits 19 P PAS 70, 93, 165 see also Positive Alarm Sequence 15, 70 PAS BYPASS 165 PAS timer 102 Password 15, 62 change 143 Maintenance Level 2 62, 147 Master Level 1 62 PC (personal computer) MS-9200UDLS PN 52750:E1 01/27/09 Index ground fault 58 Phone Line 2 supervision 141 Phone Number 137 Piezo see also sounder 18 PK-CD Programming Utility 22 point assignments 215 Point Program 65 Positive Alarm Sequence 70, 165 see also PAS 15 power NAC 14 nonresettable 16 resettable smoke 16 system 14 power supply calculations 187 power-limited relay connections 50 Power-up first time 61 Pre-signal 15, 70, 93 function 164 selection 81 Pre-signal Delay timer 103 Pre-signal timer 102 Primary Phone 131 primary power see also AC Power 49 printer baud rate 142 configuration 58 connection 57 ground fault 58 setup 58 Printer/PC interface 15 Process Monitor 162 PROCMON AR 110 Program check 145 check correlations 145 clear 144 Program Check Maintenance Level 150 program keys see also Key Panel 18 Programming 59, 60 autoprogramming 60 exiting 61 MS-9200UDLS PN 52750:E1 01/27/09 factory default 197 Level 1 61 Level 2 61 manual 60 Master Level 1 63 modules 75 off-line computer 60 via computer keyboard 59 via panel keypad 59 Programming Levels 61 Programming Screens 61 Programming Sheet 193, 194, 195 Programming Utility see also PK-CD 22 Proprietary Yes see also Remote Upload 185 PRT/PK-CABLE for PC/Printer connection 58 R Read Status 60, 168 annunciators 174, 176 exiting 61 history 174 NAC 173 power 171 Print 178 printer/PC 177 program check 174 relay 173 system point 169 Time-Date 180 timers 172 trouble reminder 172 zones 170 Real-Time Clock 163 Recall/Increment Function 74, 84, 91 Receivers 183 Relay 16, 19, 50, 110 connections 50 contact rating 16, 19, 50 fixed 50 Form-C 16, 110 programmable 14, 19, 50 programming 110 selections 110 trouble 14, 19, 50 Relay Control Module see also ACM-8RF 41 Relay options 97 221 Index Remote Download 184 Remote Programming 60 Remote Station Service 56 remote switch functions 15 remote sync output 17 Remote Synchronization 52 REN see also Ringer Equivalence Number 42 Report Style 141 Reporting Enable 133 Reset 18, 156 Resettable Power 19, 49 current 49 see also Smoke Detector Power 16 Ring Count 133 Ringer Equivalence Number 42 S Secondary Phone 132 Secondary Power Requirements 190 Secret Code 186 Security Features 186 sensitivity 163, 179 see also smoke detector sensitivity 163 Service Terminal 132 Signal rate 15 Signaling Line Circuit see also SLC 16 Silence Inhibit 15, 109, 166 Silenceable control module 88 NAC 106 waterflow 111 Silenceable Alarm Relay 110 silenceable circuits synchronized signals 106 Silenceable waterflow 95 SLC 14, 19 current 16 reference manual 16 resistance 16 see also Signaling Line Circuit 14, 16 Style 19 voltage 16 wiring length 16 SLC Loop Protocol 97 SLC Style 96 smoke detector chamber reading 178 data 163, 178 222 sensitivity 15, 163 Smoke Detector Power current 16 Software Zones 14, 191 sounder 18 Specifications 16 strobe synchronization 15 Style 14 Style Y 50 NAC wiring 51 NC configuration 51 Style Z 50 NAC configuration 51 wiring 52 subscreen 61 supervision Phone Line 2 141 Supervisory 161 SUPERVISORY AR 110 supervisory relay configuring for 4XTMF 57 sync programming 105 see also synchronization 109 sync output 17 current 17 End-of-Line resistor 17 voltage 17 synchronization 52, 164, 173 by manufacturer 109 programming 109 see also strobe synchronization 15 synchronized 164 synchronized signals 164 and silenceable circuits 106 System Maintenance Level 153 System Point 169 system power 14 System Setup 97 T Telephone Circuitry 42 Telephone Company Rights and Warnings 43 telephone line 54 Terminal 133 Test Time Interval 136, 137 Time and Date Maintenance Level 153 MS-9200UDLS PN 52750:E1 01/27/09 Index Time setting 100 Time-Date setting 97, 100 Time-out 186 Timers 97 Transformer Assembly 20 Transmittal Priorities 182 Transmitter Module 56 see also 4XTMF module 21 Trouble 158 trouble display 159 trouble relay 14 Trouble Reminder 97, 166, 172 trouble responses 159 Two Stage 93, 155 two stage operation 108 Type control module 87 detector 69 monitor module 79 NAC 106 type code control module 87 supervision 163 verification 15 U UL power-limited wiring requirements 53 see also power-limited and nonpower-limited 50 Upload/Download 184 V Verification detector 69 Verify Loops 111 View Events 112 voltage measurements 171 ranges 171 W Walktest 15, 69, 88, 113 audible 113 Maintenance Level 151 operation 167 selection 81 silent 113 waterflow nonsilenceable 95, 111 silenceable 95, 111 Waterflow Delay timer 102, 103 Waterflow Retard Timer 166 MS-9200UDLS PN 52750:E1 01/27/09 Waterflow Silenceable 97 Wire Requirements 205 wiring AC Power 49 earth ground 49 NAC Style Y 51 NAC Style Z 52 wiring Style 14 X XRM-24 see Transformer Z Z00 71, 81 Z97 PAS zone 70 Z98 71 Zone 97 93 Zone 98 93 Zone Assignment 71, 81, 109 control module 88 Zone Setup 92 Maintenance Level 154 zone type 95 list 95 Zone Z97 70 Zone Z98 pre-signal zone 71 Zones 170, 191 see also software zones 14 Zones Disabled 94 Zones Enabled 94 Zones Installed 94 zones per device 71 223 Notes 224 MS-9200UDLS PN 52750:E1 01/27/09 Notes MS-9200UDLS PN 52750:E1 01/27/09 225 Notes 226 MS-9200UDLS PN 52750:E1 01/27/09 Limited Warranty Honeywell International Inc. warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. Honeywell International Inc. does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than Honeywell International Inc. or as expressly authorized by Honeywell International Inc. in writing, or is serviced by anyone other than Honeywell International Inc. or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department. This writing constitutes the only warranty made by Honeywell International Inc., with respect to its products. Honeywell International Inc., does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Honeywell International Inc., is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident. HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE HONEYWELL INTERNATIONAL INC.’S PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by Honeywell International Inc. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Warn-HL-05-2007.fm World Headquarters 1 Firelite Place Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.firelite.com
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Encryption : Standard V2.3 (128-bit) User Access : Print, Copy, Extract, Print high-res XMP Toolkit : 3.1-702 Producer : Acrobat Distiller 7.0.5 (Windows) Create Date : 2009:01:27 12:54:44-05:00 Modify Date : 2009:03:05 09:39:47-05:00 Metadata Date : 2009:03:05 09:39:47-05:00 Format : application/pdf Title : untitled Document ID : uuid:e3adcb40-6a11-4969-8c88-c7b2bf6de12c Instance ID : uuid:a29eb610-675c-428e-b012-0fcee7cf08c7 Page Count : 228EXIF Metadata provided by EXIF.tools