LUTRONControl Unit Quick Installation and Operation Guide®Please ReadThe GRAFIK Eye® QS control unit allows for control of both lights and shades, without interfaces, using a single control unit. Features include pushbutton scene recall, info screen that displays energy savings and status, IR receiver, astronomic timeclock, contact closure input, and engravable backlit buttons that are easy to find and operate.Model Numbers:  QSGRJ-3P, QSGRJ-4P, QSGRJ-6P QSGR-3P, QSGR-4P, QSGR-6P120 V50/60 Hz 220 - 240 V50/60 HzUnit Capacity (watts) 2000 W 3000 W MLV 2000 VA 1600 W 3000 VA 2400 WZone Capacity (watts) 25 – 800 W 40 – 1200 W MLV 25 – 800 VA25 – 600 W 40 – 1200 VA40 – 960 WSee page 6 for IEC PELV/NEC® Class 2 ratings.For California residents only:The batteries in these devices contain  Perchlorate Material – special handling may apply.For more information visit  www.dtsc.ca.gov/hazardouswaste/perchlorateContentsFeatures and Functions of the GRAFIK Eye® QS Control Unit .................2Wiring the GRAFIK Eye® QS Control UnitOverview of Line Voltage/Mains Wiring . . . . . . . . . 3Line Voltage Wiring Details. . . . . . . . . . . . . . . . . . . 4Overview of IEC PELV/NEC® Class 2 Wiring . . . . . 6QS Link Control Wiring Details. . . . . . . . . . . . . . . . 7Power Group Wiring Example  . . . . . . . . . . . . . . . .8Completing Installation of the  GRAFIK Eye® QS Control Unit  . . . . . . . . . . . . . 9Programming ModeEntering and Exiting Programming Mode . . . . . . 10Navigating Menus in Programming Mode . . . . . . 10Wireless Mode.........................11FCC Information ..........................11Zone SetupAssigning Load Types. . . . . . . . . . . . . . . . . . . . . . 12Assigning Non-Dim Load Type. . . . . . . . . . . . . . . 12Setting Load Types........................13Scene SetupSetting Zone Levels, Fade Rates,  and Shade Group Actions  . . . . . . . . . . . . . . . . . 14Occupancy Sensor Setup. . . . . . . . . . . . . . . . 15Scene Mode .............................16Configuring Occupancy Sensor Settings  (optional) ...............................17Pico® Wireless Control Setup:Associating with a GRAFIK Eye® QS  Wireless Control Unit . . . . . . . . . . . . . . . . . . . . . 18Troubleshooting .......................19Warranty .............................20Contact Information  . . . . . . . . . . . . . . . . . . . . 20For additional features and advanced functions,  see the complete installation and operation guide at www.lutron.com/qsEnglish Español Français
OK®Info screenDisplays status or programming functionsScene buttonsWith integral scene indicator LEDsOptional Shade  button groupsPreset and raise/lower buttons with integral LEDs (maximum of 3 button groups)Zone numbersZone raise/lower buttonsZone LEDs display current lighting zone levelsTimeclock buttonDisplays current  timeclock infoOK buttonUsed for programmingInfrared receiverFor handheld remote useMaster buttonsTemporarily raise and lower lighting levels on unitUSB type mini BFor programming via PC{Hinged faceplateHinged faceplateFeatures and Functions of the GRAFIK Eye® QS Control UnitFor additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   2
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   3Wiring the GRAFIK Eye® QS Control Unit:Overview of Line Voltage/Mains Wiring12341 2 ABC123456LN 12 AWG (4.0 mm2) each terminal120 - 127 Vor 220 - 240 V Distribution PanelLine Voltage/Mains Cables and Load Wiring123456LNIncandescent loadLoad controlled by power module or interfaceTerminal labels:L: Hot/LiveN: Neutral : Ground1-6:  Dimmed/Switched line voltage outputsPower module or interface
®Wiring the GRAFIK Eye® QS Control Unit:Line Voltage Wiring Details• Useproperlycertifiedcableforalllinevoltage/mains cables.• Propershort-circuitandoverloadprotection must be provided at thedistribution panel. You can use up to a20 A circuit breaker for your installation.• Installinaccordancewithalllocalandnational electrical codes.• IECPELV/NEC® Class 2 terminals maybe temporarily unplugged for ease of IR,occupancy sensor, and control wiring.•Notice: Risk of damage to unit. Do notconnect line voltage/mains cable to IECPELV/NEC® Class 2 terminals.Step 1: Install wallbox. Mount a 3½ in (89 mm) deep 4-gang U.S. wallbox on a dry, flat indoor surface that is accessible and allows for system programming and operation. Allow at least 4½ in (110 mm) clearance above and below the faceplate to ensure proper heat dissipation. Allow  1 in (25 mm) for faceplate overhang on all sides. Note:  4-gang wallbox available from Lutron;P/N241400.Step 2: Test load wiring.• TurnpowerOFFatthecircuitbreakerorfuse box.• Connectastandardlightswitchbetweenthe live lead and load wire to test thecircuit.• TurnpowerONandcheckforshortoropen circuits. If load does not operate,the circuit is open. If the circuit breakertrips (fuse blows or opens), a load shortmay exist. Correct short or open circuitsand test again.Step 3: Check control unit wiring.•Earth/ground terminal connection mustbe made as shown in line voltage wiringdiagrams.•Do not mix different load types on thesame zone.•Follow all local and national electricalcodes when installing IEC PELV/NEC® Class 2 wiring with line voltage/mains wiring.WARNING! Shock hazard. May result in serious injury or death. Always turn off circuit breaker or remove main fuse from power line before doing any work. Before connecting the loads to the GRAFIK Eye® QS control unit, test the loads for short-circuits.NeutralHot/Live SwitchLoadLUTRONLUTRONFaceplate overhangs wallbox on all sides;  allow 1 in (25 mm)4` in (110 mm)For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   4
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   5Wiring the GRAFIK Eye® QS Control Unit:Line Voltage Wiring Details (continued)Step 4: Connect line voltage and loads to control unit.• Strip9 in (8 mm) of insulation off the line voltage/mains cables in the wallbox.• Connectthelinevoltage/mains,ground,and load wires to the appropriate terminals on the back of the control unit.  L: Hot/Live N:Neutral      : Ground  Terminals 1-6:  Dimmed/Switched  line voltage outputs   9 in (8 mm)  The recommended installation torque is 5.0 in∙lb(0.6N∙m) for line voltage/mains connections and 5.0 in∙lb(0.6N∙m) for the earth/ground connection. Note:  See the zone setup section for a list of compatible load types and instructions for programming the GRAFIK Eye® QS control unit to properly recognize them.Notice: Risk of damage to unit. GRAFIK Eye® QS control units must be in stalled by a qual i fied electrician in accordance with all applica ble reg u la tions and building codes. Im prop er  wiring can result in dam age to control units or oth er equipment.Note: To avoid over heat ing and pos si ble damage to  equipment, do not install control units to dim re cep ta cles, mo tor-op erated ap pli ances, or flu o res cent lighting not equipped with Lutron Hi-lume®, Eco-10®, Tu-Wire®, electron ic dim ming ballasts, or other devices approved for your location. In dimmed mag net ic low-voltage cir cuits, you can pre vent trans former  overheating and failure by avoid ing excessively high cur-rent flow. Do not op erate control units with any lamps re moved or burned out; re place any burned out lamps imme di ate ly; use only transform ers that in cor po rate ther mal pro tection or fused pri ma ry wind ings. Control units are de signed for res i den tial and commercial use, for indoor use only.
12341 2 ABC123456LNContact Closure Input Wiring24 V   50 mA For settings, see the full installation and operation guide at  www.lutron.com/qs.®1 2 ABCNH123456123412341 2ABC123456LN12341 2ABC123456LNNote:  Use appropriate wire connecting devices as specified by local codes.Example:  Occupancy sensor(maximum 1)1: COM2: 24 V *3: MUX4: MUXQS Link Control Wiring24 V   100 mAWiring the GRAFIK Eye® QS Control Unit:Overview of IEC PELV/NEC® Class 2 WiringIR WiringFrom external IR connection (by others)18 AWG (1.0 mm2) each terminal18 AWG (1.0 mm2) each terminal1: IR DATA2: IR COMA: CCI SIGB: 24 VC: CCI COMTo control stations, shades, or other GRAFIK Eye® QS control unitsData (terminals 3 and 4):  Twisted, shielded pair 22 AWG (0.5 mm2) each terminalCommon and power (terminals 1 and 2):  Two 18 AWG (1.0 mm2) each terminal (for link <500 ft/153 m)Two 12 AWG (4.0 mm2) each terminal (for link 500-2000 ft/153-610 m)* Do not connect terminal 2between any GRAFIK Eye® QScontrol unit and any other power supply, including another GRAFIK Eye® QS control unit.See “Power Group Wiring” for a detailed wiring example.12341 2ABC123456LNExample:  Emergency lighting interface (maximum 1)Note:  The GRAFIK Eye® QS control unit mustbepoweredbyaNormal/Emergency distribution panel for proper ELI operation. Refer to the LUT-ELI-3PH Installation Guide for the complete wiring diagram.A: CCI SIGB: 24 VC: CCI COMLUT-ELI-3PHSignal+V InputCircuit CommonFor additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   6
• SystemcommunicationusesIECPELV/NEC® Class 2 wiring.• FollowalllocalandnationalelectricalcodeswheninstallingIECPELV/NEC® Class 2 wiring with line voltage/mains wiring.• Eachterminalacceptsuptotwo18AWG(1.0mm2) wires.• Totallengthofcontrollinkmustnotexceed 2000 ft (610 m).• Makeallconnectionsinthecontrolunit’swallbox.• WiringcanbeT-tappedordaisy-chained.• IECPELV/NEC® Class 2  24 V   150 mA.System Limits  The QS wired communication link is limited to 100 devices or 100 zones.  The GRAFIK Eye® QS control unit supplies 3 Power Draw Units (PDUs) on the QS link. Refer to the QS Link Power Draw Units specification submittal (LutronPN369405)formoreinformationconcerningPower Draw Units.®Wiring the GRAFIK Eye® QS Control Unit:QS Link Control Wiring DetailsQS smart power  panel LUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONT-Tap Wiring Example GRAFIK Eye® QS control unitSivoia® QS shade/drapeseeTouch® QS wallstationLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRONLUTRON LUTRON LUTRONLUTRONGRAFIK Eye® QS control unitSivoia® QS shade/drapeseeTouch® QS wallstationsDaisy-Chain Wiring Example QS smart  power panel GRAFIK Eye® QS control unitFor additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   7Wire Sizes (check compatibility in your area)QS Link Wiring Length Wire Gauge Lutron Cable Part NumberLess than 500 ft (153 m) Power (terminals 1 and 2)1 pair 18 AWG (1.0 mm2) GRX-CBL-346S (non-plenum)GRX-PCBL-346S (plenum)Data (terminals 3 and 4)1 twisted, shielded pair 22 AWG (0.5 mm2)500 to 2 000 ft (153 to 610 m) Power (terminals 1 and 2)1 pair 12 AWG (4.0 mm2) GRX-CBL-46L (non-plenum)GRX-PCBL-46L (plenum)Data (terminals 3 and 4)1 twisted, shielded pair 22 AWG (0.5 mm2)
Wiring the GRAFIK Eye® QS Control Unit: Power Group Wiring Example®On the QS link, there are devices that supply power and devices that consume power. Each device has a specic number of Power Draw Units (PDUs) it either supplies or consumes. A Power Group consists of one device that supplies power and one or more devices that consume power; each Power Group may have only one power-supplying device. Refer to the QS Link Power Draw Units specificationsubmittal(LutronPN369405)formoreinformationconcerningPDUs. Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the diagram. Between devices on theQSlinkthatsupplypower,connectonlyterminals1,3,and4(NOTterminal2),shownbytheletterBonthediagram.Wiring can be T-tapped or daisy-chained.For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   8LUTRONLUTRON LUTRONLUTRONLUTRONLUTRONPower Group 1Power Group 2Power Group 3AABB(Do not connect terminal 2: 24 V )(Do not connect terminal 2: 24 V )GRAFIK Eye® QScontrol unit  Supplies PDUsQS Power SupplySupplies PDUsEnergi Savr NodeTMunit Supplies PDUsControl Interfaces Consume PDUsControl Interfaces Consume PDUsWallstations Consume PDUsWallstations Consume PDUsWallstations Consume PDUsQS Sensor Module with Occupancy SensorConsumes PDUsConnect all 4 terminals within a power group:1: Common 2: 24 V3 and 4: DataConnect only 3 terminals between power groups:1: Common 3 and 4: DataDo not connect  Terminal 2: 24 VABQuantum® panelSupplies PDUsBA
®Completing Installation of the GRAFIK Eye® QS Control Unit1. Mount the control unit in the wallbox asshown using the four screws pro vid ed.Note:  Follow all local and nationalelectrical codes when installing IEC PELV/NEC® Class 2 wiring with line voltage/mains wiring.2. Verify installation:•Restore power.•Press the top scene button. The LED willlight.•Press the zone raise and lower buttons.Make sure the control unit is dimming allconnected loads.3. Apply the protective overlay to the controlunit.Note: When tightening mounting screws, make sure that the hinged cover and faceplate will open fully, as shown. Wall7.9 in (200 mm)3.5 in (87 mm) 3.75 in (95 mm)Protective overlay  (apply after installation)For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   9
Entering and Exiting Programming ModeEntering programming mode:Press and hold the top and bottom scene buttons simultaneously for 3 seconds. The LEDs in the scene buttons will scroll from top to bottom, confirming that you are in programming mode, and the info screen will display the main menu.Exiting programming mode:Press and hold the top and bottom scene buttons simultaneously for 3 seconds. The info screen will go to Scene 1.Navigating Menus in Programming ModeMaster ButtonsThe Master buttons allow you to move through the menu choices. The current choice is highlighted on the info screen.OK ButtonThe OK button chooses the current highlighted menu choice. This will either take you to the next menu or accept a setting you haveselected.WhenthescreendisplaysaYes/Noquestion,theOK button is “Yes”.Timeclock ButtonThe timeclock button functions as a “back” button during programming mode. Pressing the timeclock button takes you back one step in the current menu. Pressing it repeatedly will eventually return you to the main menu, but will not exit programmingmode.WhenthescreendisplaysaYes/Noquestion,theTimeclockbuttonis“No”.®Programming ModeOK123456Press and hold the top and bottom buttons for 3 seconds to enter or exit programming modeMaster buttonsOK buttonTimeclock (back) buttonMain menuScene setupTimeclockScene 1Fade time 3 secondsFor additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   10
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   11Wireless ModeMany models of the GRAFIK Eye® QS control unit support wireless communication with other Lutron products. This feature allows for easy integration of wireless sensors, keypads, remotes, and shades for single-room wireless applications, as well as compatibility with other Lutron wireless systems such as RadioRA® 2. (See the RadioRA®SetupGuide;LutronPN044254.)Units supporting wireless communication are labeled “GRAFIK Eye® QS Wireless” on the front label of the unit.The wireless feature of the GRAFIK Eye® QS Wireless control unit has three (3) modes of operation.•Disabled: Use for wired-only systems.•Enabled: The GRAFIK Eye® QS Wireless control unit will respond to any programmingcommands from nearby Lutron QS wireless (and compatible) products.•Ignore Programming (default): The GRAFIK Eye® QS Wireless control unit will onlyrespond to normal operation commands from wireless devices associated while inEnabled mode. Changing the wireless mode of the GRAFIK Eye® QS Wireless control unit:1.  Enter programming mode.2.  Use the Master buttons to highlight “Wireless Mode” and pressthe OK button to accept.3.  Use the Master buttons to highlight the desired wireless mode,and press the OK button to accept.4.  The info screen will display a confirming “Saved” message.5.  Exit programming mode.Notes• The wireless signal has a range of 30 ft (9 m) through standardconstruction or 60 ft (18 m) line of sight.• WhenusedwithinaRadioRA® 2 system, the wired QS link on theGRAFIK Eye® QS control unit is disabled, and certain featuresthat do not pertain to RadioRA® 2 are not accessible.Wireless ModeEnabledSavedSavedMain menuShade labelsWireless ModeFCC InformationChanges or modifications not expressly approved by Lutron Electronics Co. could void the user’s authority to operate this equipment. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules and Industry Canada license-exempt RSS standard(s) . Operation is subject to the following: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. These limits are designed to provide reasonable protection against harmful interference in a residential and commercial installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio or television reception. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:•Reorientorrelocatethereceivingantenna.•Increasetheseparationbetweentheequipmentand receiver.•Connecttheequipmentintoanoutletonacircuit different from that to which the receiver isconnected.•Consultthedealeroranexperiencedradio/TVtechnician for help.OKMaster buttonsOK buttonTimeclock (back) button
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   12Assigning Load Types1.  Enter programming mode.2.  Use the Master buttons to highlight“Zone setup” and press theOK button to accept.3.  Use the Master buttons to highlight“Load type”. Press the OK button toaccept. See “Setting Load Types”table on the next page.4.  Use the zone raise/lower buttons tochoose the load type for that zone.See the list on the next page forsupported load types. Press the OKbutton to accept.5.  The info screen will confirm thatyour load type has been saved.6.  Exit programming mode.Zone SetupOK123456Master buttonsOK buttonMain menuCCI SetupZone setupOK123456Use the zone raise/lower buttons to choose the load type for that zone.Zone SetupNon-Dim Load TypeLoad Type Set zonesSavedLoad TypeAssigning Non-Dim Load TypeZones assigned to non-dim loads have three available configurations:•LOFO: Last On, First Off•FOFO: First On, First Off•FOLO: First On, Last Off Scenes made up of both dim and non-dimload types will toggle the non-dim loadsbefore the dim loads in a “First” on/offconfiguration, and after the dim loads in a“Last” on/off configuration.1.  Enter programming mode.2.  Use the Master buttons to highlight “Zonesetup” and press the OK button to accept.3.UsetheMasterbuttonstohighlight“Non-DimLoad type”. Press the OK button to accept.See “Setting Load Types” table on the nextpage.4.  Use the zone raise/lower buttons to choosethe non-dim load type for that zone. (Zonesnot programmed as non-dim will be displayedas Unaffected.) Press the OK button toaccept.5.  The info screen will confirm that your loadtype has been saved.6.  Exit programming mode.Main menuCCI SetupZone setupZone SetupLoad TypeLoad Type Set zonesSavedNon-Dim Load Type
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   13Zone Setup (continued)Load Type Notes• Allelectroniclow-voltage(ELV) lighting used with an interface must be rated for reverse phase control dimming. Before installing an ELV light source, verify with the manufacturer that their transformer can be dimmed. When dimming, an ELV interface (such as the PHPM-PA-DV-WH) must be used with the control unit.• ForallDMXorRGB/CMYDMXlighting,anexternalDMXinterface(suchastheQSE-CI-DMX)mustbe used with the control unit.• MaximumtotallightingloadforLutron® Tu-Wire® and Advance MarkX® electronic dimming ballasts (120 to 127 V  only) must not exceed 6 A per zone or 16 A per unit.Zone ratings:• Notallzonesmustbeconnected;however, connected zones must have a minimum load:120 - 127 V : 25 W 220 - 240 V : 40 W• Maximumzoneloads:120 - 127 V : 800 W220 - 240 V : 1200 W• Maximumtotallightingloadformagnetic low-voltage (MLV) variesby input voltage:120 - 127 V : 800 VA / 600 W220 - 240 V : 1200 VA / 960 WLUTRONLUTRONLUTRONLUTRONSetting Load TypesDirect control via GRAFIK Eye® QS control unitControl via  power module or interfaceFixture load type Choose this load type from the menu on the GRAFIK Eye® QS control unit:Zones 1 – 6Incandescent Incandescent Power moduleMLV (magnetic low-voltage) MLV Power moduleELV (electronic low-voltage) — Power moduleHi-Lume®/Eco-10®— Fluorescent module0-10 V — Fluorescent moduleNon-dim lighting loads Non-dim Non-dimNeon/Cold cathode Neon, CC Neon, CCTu-Wire®Tu-Wire Tu-WireAdvance Mark X®Tu-Wire Tu-WireDMX — DMXRGB/CMY DMX — RGB/CMY DMXCree LR4/LR6 LED Cree LR4/LR6 LED Fluorescent modulePower module or interface
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   14Scene SetupSetting Zone Levels, Fade Rates, and Shade Group Actions1.  Enter programming mode.2.  Use the Master buttons to highlight “Scene setup” and pressthe OK button to accept.3.  Use the Master buttons to highlight “Levels” to adjust lightingand/or shade levels. Press the OK button to accept. Use theMaster buttons to highlight the scene number of your desiredscene. Press the OK button to accept.4.  Set each zone to the desired light level for this scene usingthe zone raise/lower buttons. The info screen will display thezone and percentage as you adjust it. To set a zone as unaffected, lower the light levels all the wayto off, then hold the zone lower button for 3 seconds. Thescreen will display “---” and the three middle LEDs for thezone will be lit to indicate this zone is unaffected by the scene(the zone will not change when this scene is initiated). When all zones are at the desired level, press the OK button toaccept.5.  Use the Master buttons to set the fade time for this scene.Press the OK button to accept.6.  Note: This step is applicable only if you have shades on yoursystem. If you do not have or do not wish to set shade groupsfor this scene, press the OK button to skip this step.Set each shade group to the desired level for this scene.When all shade groups are at the desired level, press the OKbutton to accept.For shade programming, see the full installation and operationguide at www.lutron.com/qs.7.  The info screen will confirm that your scene has been saved.8.  Exit programming mode.Main menuTimeclockScene setupScene setupLabelsLevelsScene 1Adjust fade       secondsScene 1 Set shade Groups 3   secondsScene 1 Set zonesScene setupScene 1Saved3Shade button groupOKOKZone raiseZone lowerOKMaster buttonsOK buttonTimeclock (back) button
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   15Associating wireless occupancy sensors and GRAFIK Eye® QS Wireless control units (for wireless enabled units only):1.  Make sure the wireless mode of the GRAFIK Eye® QS control unit is “Enabled”.2.  Enter programming mode.3.  Use the Master buttons to highlight “Sensor setup” and press the OK button to accept. 4.  Use the Master buttons to highlight “Add wireless sensors” and press the OK button to accept. 5.  Press and hold the “Lights Off” button (  on some sensors) on the occupancy sensor for 6 seconds. The lens will start flashing and the info screen on the GRAFIK Eye® QS Wireless control unit willdisplaythesensor’sserialnumber.6.  Press the OK button on the GRAFIK Eye® QS control unit. A screen will confirm that the sensor has been assigned.  (To disassociate a wireless occupancy sensor from the GRAFIK Eye® QS control unit, Refer to the Radio Powr SavrTM occupancy sensor install guide to return the sensor to its “out-of-box” functionality. Doing so will remove its programming from the GRAFIK Eye® QS control unit.)7. Repeat the above steps for all desired sensors.8. Exit programming mode.Associating wireless occupancy sensors through  QS Sensor Modules (QSM):1.  Press and hold the Program button on the QSM for 3 seconds to enter programming mode. There will be 1 audible beep and the Status LED will begin flashing. The info screen on the GRAFIK Eye® QS control unit will display that the QSM is in programming mode.2.  Press and hold the “Lights Off” button (  on some sensors) on the occupancy sensor for 6 seconds. There will be 3 audible beeps from the QSM to verify association.3.  Press and hold the Program button on the QSM for 3 seconds to exit programming mode. Note:  The wireless signal has a range of 30 ft (9 m) through standard construction or 60 ft (18 m) line of sight.Occupancy Sensor SetupOK1 2 34569 10 11 12 13 14 7815169-161-8Master buttonsOK  buttonTimeclock (back) buttonMain menuZone SetupSensor SetupOccupancyxxxx-xxxxPress OK to SaveAdd wireless sensorsInitiate association  of sensorsSaved*Assigned*Sensor SetupDaylightAdd wireless sensorsProgram buttonPress and hold “Lights Off” or   button to associate/disassociateQS Sensor Module (QSM)Radio Powr SavrTM Occupancy Sensors
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   16Occupancy Sensor SetupScene Mode   This step allows you to assign up to four occupancy sensors to the GRAFIK Eye® QS control unit.   Selecting Sensors1.  If not already done, associate occupancy sensors and set to “Scene Mode”.2.  Use the Master buttons to highlight “Setup” and press the OK button to accept. The info screen will display “Searching” while the unit detects available occupancy sensors.3.  Use the Master buttons to scroll through the list of available occupancy sensors. When the desired sensor is displayed, press the OK button to select it. Then choose “Assign” or “Unassign” from the following menu and press OK. Once a sensor has been assigned, it will appear with an asterisk (*) in the sensor list. Repeat for additional sensors. Note:  If wireless sensors are not found, verify that they are associated correctly.   Setting the Sensor Action1.  Press the Timeclock (back) button to return to the Occ Sensor screen. Use the Master buttons to highlight “Actions” and press the OK button. By default, the occupied scene is set to “NoAction”andtheunoccupiedsceneissetto“SceneOff”.2.  Use the Master buttons to highlight the scene you wish to use for occupied status and press the OK button to accept. Repeat for the scene you wish to use for unoccupied status. Press the OK button to accept.3.  Exit programming mode.SavedSaved   3   secondsOcc SensorSetupActionsOccupied SceneScene 1Unoccupied SceneScene OffOcc SensorLabelsSetupSensor          x/yxxxx-xxxxRFSensor         *x/yxxxx-xxxxRFAssignmentUnassignAssignSaved*Assigned*SavedSearchingOKMaster buttonsOK  buttonTimeclock (back) button
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   17Occupancy Sensor SetupConfiguring Occupancy Sensor Settings (optional)Occupancy Sensor SettingsNote:  These settings affect all sensors assigned to the GRAFIK Eye® QS control unit.Grace Period: If the GRAFIK Eye® QS control unit is transitioning to an unoccupied state, motion detected within the grace period will return the lights to the previously occupied level. Range: 15 – 30 seconds (default 15 seconds).Vacancy Delay: An additional time delay after vacancy is detected and before unoccupied action occurs. Use when occupancy sensor does not provide sufficient delay.  Range: 0 – 30 minutes (default 0 minutes).Auto Turnoff: If lights assigned to an occupancy sensor are turned on manually without the sensor reporting occupancy, the GRAFIK Eye® QS control unit can be set to automatically turn off the lights after a set time delay. Disable this feature by setting the time delay to 0 (disabled). Range: Disabled or 1 – 30 minutes (default Disabled).Zone Fade: When in Zone Mode, lights can be set to fade to the unoccupied levels over this period of time. Range: 0 – 59 seconds; 1 – 10 minutes (default 10 seconds).Configuring the Sensor Settings:1.  Enter programming mode.2.   Use the Master buttons to highlight “Sensor Setup” and press the OK button to accept.3.  Use the Master buttons to highlight “Occupancy” and press the OK button to accept.4.  Use the Master buttons to highlight “Settings” and press the OK button to accept.5.  Use the Master buttons to highlight the setting you wish to configure. Press the OK button to accept.6.  Use the Master buttons to adjust the value of the selected setting. Press the OK button to accept. 7.  The info screen will confirm that your setting has been saved.8.  Exit programming mode.Auto Turnoff5 minutesSavedSavedMain menuZone SetupSensor SetupOcc SensorDiagnosticsSettingsSettingsZone FadeAuto TurnoffOKMaster buttonsOK  buttonTimeclock (back) buttonSensor SetupDaylightOccupancy
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   18Associating the Pico® wireless control with a GRAFIK Eye® QS Wireless control unit:(for wireless enabled GRAFIK Eye® QS control units only)1.  Make sure the wireless mode of the GRAFIK Eye® QS control unit is“Enabled”.2.  On the Pico® wireless control, press and hold the top (on) and bottom (off)buttons for 3 seconds. The info screen on the GRAFIK Eye® QS control unit will display the Pico® options. Press the OK button on the GRAFIK Eye® QS control unit to select the desired operation type for the Pico®.3a.   To assign the Pico® wireless control as a zone controller, use the Master buttons to select “Zone” and press the OK button to accept. Use the zone raise/lower buttons for a zone to select a desired preset level, and then press the zone raise and lower buttons simultaneously for 1 second (until the zone LEDs flash at the programmed preset level). Repeat for all zones you wish to control with the Pico® wireless control.OR3b.  To assign the Pico® wireless control as a scene controller, use the Master buttons to select “Scene” and press the OK button to accept. Press and hold the top scene button on the GRAFIK Eye® QS control unit for 3 seconds (until the scene LEDs flash).4.  On the Pico® wireless control, press and hold the top and bottom buttons for3 seconds until the LEDs on the GRAFIK Eye® QS control unit stop flashing.Note:Thewirelesssignalhasarangeof30ft(9m)throughstandardconstruction or 60 ft (18 m) line of sight.Change type?ZoneChange type?SceneSavedSavedPicoChange type?Press OKPico® Wireless Control SetupOKZone LEDsZone RaiseZone LowerOROK1 2 34569 10 11 12 13 14 7815 169-161-8Press and hold the top scene button for 3 seconds to assign Pico® as a scene controller.Master buttonsOK buttonTop/On buttonBottom/Off buttonPico® Wireless Control
®For additional information, see the complete installation and operation guide at www.lutron.com/qsGRAFIK Eye® QS Control Unit Quick Installation and Operation Guide   19TroubleshootingSymptom Possible Causes SolutionUnit does not power upUnit does not control loadsCircuit breaker is trippingCircuit Breaker is off Switch circuit breaker onMiswire Verify wiring to unit and loadsSystem short circuited Find and correct shortsSystem overload Verify zone/unit loading is within ratings (see Zone Setup section)Zone control does not workZone control yields incorrect resultsMiswire Make sure loads are connected to the right zonesLoose or disconnected wire Connect zone wires to loadsBurned out lamps Replace bad lampsIncorrect load type selected Assign the zone to the appropriate load type (see Zone Setup section)Dimming limits set incorrectly Adjust High End/Low End values  (see Zone Setup section)One or more zones are always “full on” and zone intensity is not adjustableZone control affects more than one zoneMiswire Make sure loads are connected to the right zonesShorted line output Check wiring; if wiring is correct, call Lutron Technical SupportFaceplate is warm Normal operation Solid-state controls dissipate about 2% of the connected load as heat.  No action is requiredUnit does not allow scene change or zone adjustments Unit is in wrong save mode Change to correct save modeQS device in system has locked the unit Check programming and state of QS devicesCannot program fade time from “Scene Off” Fade time from “Scene Off” is not programmable; can only program fade time to “Scene Off”Fade time from “Scene Off” is always 3 secondsIntegral (direct-wired) contact closure input does not work Miswire Check wiring on contact closure inputInput CCI signal is not received Verify the input device is operating properlyUnit is in wrong CCI mode and/or type Change to correct CCI mode and/or type for your applicationQS devices on link are not working Miswire or loose connection on QS link Verify QS link wiring to all devicesQS device is not associated Place the QS device into programming mode, and hold the “Scene 1” button on the GRAFIK Eye® QS control unit to associate the two devicesQS device programming is incorrect Verify the functionality and programming on the QS devicesTimeclock events do not occurSunrise or sunset events do not occur at the correct timeTimeclock is disabled Enable the timeclockTime/date is not set correctly Set the time/dateLocation is not set correctly Set the latitude and longitude of the unit’s locationHoliday schedule is in effect Normal schedule will resume when the holiday ends
®Lutron Electronics Co., Inc.One Year Limited Warranty  For a period of one year from the date of purchase, and subject to the exclusions and restrictions described below, Lutron warrants each new unit to be free from manufacturing defects.  Lutron will, at its option, either repair the defective unit or issue a credit equal to the purchase price of the defective unit to the Customer against the purchase price of comparable replacement part purchased from Lutron.  Replacements for the unit provided by Lutron or, at its sole discretion, an approved vendor may be new, used, repaired, reconditioned, and/or made by a different manufacturer.    If the unit is commissioned by Lutron or a Lutron approved third party as part of a Lutron commissioned lighting control system, the term of this warranty will be extended, and any credits against the cost of replacement parts will be prorated, in accordance with the warranty issued with the commissioned system, except that the term of the unit’s warranty term will be measured from the date of its commissioning.EXCLUSIONS AND RESTRICTIONS This Warranty does not cover, and Lutron and its suppliers are not responsible for:1.   Damage, malfunction or inoperability diagnosed by Lutron or a Lutron approved third party as caused by normal wear and tear, abuse, misuse, incorrect installation, neglect, accident, interference or environmental factors, such as (a) use of incorrect line voltages, fuses or circuit breakers; (b) failure to install, maintain and operate the unit pursuant to the operating instructions provided by Lutron and the applicable provisions of the National Electrical Code and of the Safety Standards of Underwriter’s Laboratories; (c) use of incompatible devices or accessories; (d) improper or insufficient ventilation; (e) unauthorized repairs or adjustments; (f) vandalism; or (g) an act of God, such as fire, lightning, flooding, tornado, earthquake, hurricane or other problems beyond Lutron’s control.2.   On-site labor costs to diagnose issues with, and to remove, repair, replace, adjust, reinstall and/or reprogram the unit or any of its components.3.   Equipment and parts external to the unit, including those sold or supplied by Lutron (which may be covered by a separate warranty).4.   The cost of repairing or replacing other property that is damaged when the unit does not work properly, even if the damage was caused by the unit.  EXCEPT AS EXPRESSLY PROVIDED IN THIS WARRANTY, THERE ARE NO EXPRESS OR IMPLIED WARRANTIES OF ANY TYPE, INCLUDING ANY IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY.  LUTRON DOES NOT WARRANT THAT THE UNIT WILL OPERATE WITHOUT INTERRUPTION OR BE ERROR FREE.    NO LUTRON AGENT, EMPLOYEE OR REPRESENTATIVE HAS ANY AUTHORITY TO BIND LUTRON TO ANY AFFIRMATION, REPRESENTATION OR WARRANTY CONCERNING THE UNIT.  UNLESS AN AFFIRMATION, REPRESENTATION OR WARRANTY MADE BY AN AGENT, EMPLOYEE OR REPRESENTATIVE IS SPECIFICALLY INCLUDED HEREIN, OR IN STANDARD PRINTED MATERIALS PROVIDED BY LUTRON, IT DOES NOT FORM A PART OF THE BASIS OF ANY BARGAIN BETWEEN LUTRON AND CUSTOMER AND WILL NOT IN ANY WAY BE ENFORCEABLE BY CUSTOMER.  IN NO EVENT WILL LUTRON OR ANY OTHER PARTY BE LIABLE FOR EXEMPLARY, CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF PROFITS,  CONFIDENTIAL OR OTHER INFORMATION, OR PRIVACY; BUSINESS INTERRUPTION; PERSONAL INJURY; FAILURE TO MEET ANY DUTY, INCLUDING OF GOOD FAITH OR OF REASONABLE CARE; NEGLIGENCE, OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER), NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON’S WRITTEN CONSENT ARISING OUT OF OR IN ANY WAY RELATED TO THE INSTALLATION, DEINSTALLATION, USE OF OR INABILITY TO USE THE UNIT OR OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY, OR ANY AGREEMENT INCORPORATING THIS WARRANTY, EVEN IN THE EVENT OF THE FAULT, TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY, BREACH OF CONTRACT OR BREACH OF WARRANTY OF LUTRON OR ANY SUPPLIER, AND EVEN IF LUTRON OR ANY OTHER PARTY WAS ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.  NOTWITHSTANDING ANY DAMAGES THAT CUSTOMER MIGHT INCUR FOR ANY REASON WHATSOEVER (INCLUDING, WITHOUT LIMITATION, ALL DIRECT DAMAGES AND ALL DAMAGES LISTED ABOVE), THE ENTIRE LIABILITY OF LUTRON AND OF ALL OTHER PARTIES UNDER THIS WARRANTY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, USE, REPAIR, OR REPLACEMENT OF THE UNIT, OR ANY AGREEMENT INCORPORATING THIS WARRANTY, AND CUSTOMER’S SOLE REMEDY FOR THE FOREGOING, WILL BE LIMITED TO THE AMOUNT PAID TO LUTRON BY CUSTOMER FOR THE UNIT. THE FOREGOING LIMITATIONS, EXCLUSIONS AND DISCLAIMERS WILL APPLY TO THE MAXIMUM EXTENT ALLOWED BY APPLICABLE LAW, EVEN IF ANY REMEDY FAILS ITS ESSENTIAL PURPOSE. TO MAKE A WARRANTY CLAIM  To make a warranty claim, promptly notify Lutron within the warranty period described above by calling the Lutron Technical Support Center at (800) 523-9466. Lutron, in its sole discretion, will determine what action, if any, is required under this warranty.  To better enable Lutron to address a warranty claim, have the unit’s serial and model numbers available when making the call. If Lutron, in its sole discretion, determines that an on-site visit or other remedial action is necessary, Lutron may send a Lutron Services Co. representative or coordinate the dispatch of a representative from a Lutron approved vendor to Customer’s site, and/or coordinate a warranty service call between Customer and a Lutron approved vendor.  This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.  NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.  Advance Mark X is a registered trademark of the Advance Transformer Company.  Lutron, ®, Sivoia, Hi-lume, Eco-10, Tu-Wire, Radio RA, Pico, seeTouch, Quantum, and GRAFIK Eye are registered trademarks and Radio Powr Savr and Energi Savr Node are trademarks of Lutron Electron-ics Co., Inc.    © 2012 Lutron Electronics Co., Inc.Internet: www.lutron.comE-mail: product@lutron.comWORLD HEADQUARTERSUSALutron Electronics Co., Inc.7200 Suter Road, Coopersburg, PA 18036-1299TEL +1.610.282.3800FAX+1.610.282.1243Toll-Free1.888.LUTRON1Technical Support 1.800.523.9466North and South America Technical HotlinesUSA, Canada, Caribbean: 1.800.523.9466Mexico: +1.888.235.2910Central/South America: +1.610.282.6701EUROPEAN HEADQUARTERSUnited KingdomLutron EA Ltd.6 Sovereign Close, London, E1W 3JF United KingdomTEL +44.(0)20.7702.0657FAX+44.(0)20.7480.6899FREEPHONE(UK)0800.282.107Technical support +44.(0)20.7680.4481ASIAN HEADQUARTERSSingaporeLutron GL Ltd. 15 Hoe Chiang Road, #07-03, Tower 15, Singapore 089316TEL +65.6220.4666FAX+65.6220.4333Asia Technical HotlinesNorthernChina:10.800.712.1536Southern China: 10.800.120.1536Hong Kong: 800.901.849Indonesia: 001.803.011.3994Japan: +81.3.5575.8411Macau: 0800.401Singapore: 800.120.4491Taiwan: 00.801.137.737Thailand: 001.800.120.665853Other countries: +65.6220.4666WarrantyLutron Electronics Co., Inc.P/N032-402Rev.A02/2012Contact Information