Mercury Networks QUANTUM1000 Quantum 1000 Base Station User Manual Part 2

Mercury Networks, LLC Quantum 1000 Base Station Users Manual Part 2

Contents

Users Manual Part 2

   Quantum 1000 Base Station User 3. Grounding and Lightning Requirements Proper lightning protection requires tprotection built into the PureWave equipment. The primary protectors offer the surge currents a direct path to earth ground versus the undesirable “sneak” paths it may find through the equip Properly installed and grounded primary protectors will dramatically increase the surge withstanding capabilities of the PureWave equipment. Surges that exceed the maximum ratings of the primary protector devices will eventually cause them to fail,short or open, as the application warrants, such that further surges will not damage the end equipment. While a failed primary protector still results in a service outage, it does prevent further damagemore expensive end equipment.  A Base Station that is installed outdoor on the tower or mast (ODU) is especially vulnerable to lightning surges. Good surge mitigation practice starts with the lightning rod and its connection to a proper sized down conductor.  The ground down conductor should be as straight as possible and avoid incidental contact with other conductors such that it represents the path of least resistance to earth ground from the lightning rod. The tower/mast is also earth grounded tosafety, and generally presents a less desirable path to ground to surge currents. ODU equipment and external primary protection devices are mounted to the tower/mast and should be bonded tat the same point on the down conductor. This practice is intended to avoid ground loop currents that may flow from differences in potential between the tower/mast structure and down conductor while large surge currents are flowing in them respectively. Good surge mitigation practice also makes use of shielded cables with peripheral shield grounding to minimize potentials induced on circuit conductors. These cables should also be secured to the tower/mast at regular intervals to create from conductors which are carrying surge currents. This practice avoids incidental contact or possible insulation breakdown from high surge potentials. A Base Station that is installed indoor units (IDU) requires similar protection as (ODU). Primary protection devices are installed on all cables just prior to entry of the facility and bonded to an earth ground stake. Likewise, the cable shields are grounded at the entry panel which should be bonded to the same earth ground stake. IDU equipment may also be vulnerable to surges entering via the AC power connection and steps should be taken to install a proper AC Surge Suppressor device to complete a well protected installation. 3.1 Lightning Protection Installation  The following are considered to be the main elements that constitute the components of a lightning protection scheme.     Lightning Rod   Base Station and Antenna Grounding   Down Conductor   Coaxial and/or Cat 5 Cable Shield Grounding   Quantum 1000 Base Station User Guide   Rev 1.1, Page Grounding and Lightning Requirements Proper lightning protection requires the use of external primary protectors to complement the secondary protection built into the PureWave equipment. The primary protectors offer the surge currents a direct path to earth ground versus the undesirable “sneak” paths it may find through the equipProperly installed and grounded primary protectors will dramatically increase the surge withstanding capabilities of the PureWave equipment. Surges that exceed the maximum ratings of the primary protector devices will eventually cause them to fail, however these devices are generally designed to fail short or open, as the application warrants, such that further surges will not damage the end equipment. While a failed primary protector still results in a service outage, it does prevent further damageA Base Station that is installed outdoor on the tower or mast (ODU) is especially vulnerable to lightning surges. Good surge mitigation practice starts with the lightning rod and its connection to a proper sized The ground down conductor should be as straight as possible and avoid incidental contact with other conductors such that it represents the path of least resistance to earth ground from the lightning rod. The tower/mast is also earth grounded to keep its conductive elements at earth potential (0V) for personnel safety, and generally presents a less desirable path to ground to surge currents. ODU equipment and external primary protection devices are mounted to the tower/mast and should be bonded tat the same point on the down conductor. This practice is intended to avoid ground loop currents that may flow from differences in potential between the tower/mast structure and down conductor while large surge espectively. Good surge mitigation practice also makes use of shielded cables with peripheral shield grounding to minimize potentials induced on circuit conductors.These cables should also be secured to the tower/mast at regular intervals to create physical separation from conductors which are carrying surge currents. This practice avoids incidental contact or possible insulation breakdown from high surge potentials. A Base Station that is installed indoor units (IDU) requires similar protection as the outdoor installation (ODU). Primary protection devices are installed on all cables just prior to entry of the facility and bonded to an earth ground stake. Likewise, the cable shields are grounded at the entry panel which should be arth ground stake. IDU equipment may also be vulnerable to surges entering via the AC power connection and steps should be taken to install a proper AC Surge Suppressor device to complete a well protected installation.Lightning Protection Installation Components The following are considered to be the main elements that constitute the components of a lightning Base Station and Antenna Grounding Coaxial and/or Cat 5 Cable Shield Grounding  Rev 1.1, Page 38 of 70 he use of external primary protectors to complement the secondary protection built into the PureWave equipment. The primary protectors offer the surge currents a direct path to earth ground versus the undesirable “sneak” paths it may find through the equipment. Properly installed and grounded primary protectors will dramatically increase the surge withstanding  capabilities of the PureWave equipment. Surges that exceed the maximum ratings of the primary however these devices are generally designed to fail short or open, as the application warrants, such that further surges will not damage the end equipment. While a failed primary protector still results in a service outage, it does prevent further damage to the A Base Station that is installed outdoor on the tower or mast (ODU) is especially vulnerable to lightning surges. Good surge mitigation practice starts with the lightning rod and its connection to a proper sized The ground down conductor should be as straight as possible and avoid incidental contact with other conductors such that it represents the path of least resistance to earth ground from the lightning rod. The keep its conductive elements at earth potential (0V) for personnel safety, and generally presents a less desirable path to ground to surge currents. ODU equipment and external primary protection devices are mounted to the tower/mast and should be bonded to earth ground at the same point on the down conductor. This practice is intended to avoid ground loop currents that may flow from differences in potential between the tower/mast structure and down conductor while large surge espectively. Good surge mitigation practice also makes use of shielded cables with peripheral shield grounding to minimize potentials induced on circuit conductors. physical separation from conductors which are carrying surge currents. This practice avoids incidental contact or possible the outdoor installation (ODU). Primary protection devices are installed on all cables just prior to entry of the facility and bonded to an earth ground stake. Likewise, the cable shields are grounded at the entry panel which should be IDU equipment may also be vulnerable to surges entering via the AC power connection and steps should be taken to install a proper AC Surge Suppressor device to complete a well protected installation. The following are considered to be the main elements that constitute the components of a lightning
   Quantum 1000 Base Station User Figure 41, demonstrates graphically how these elements are applied to an overall lightning design. Please note that this is simply a generic diagram and that each individual installation may have its own specific requirements which may differ from the diagram. The key The main items will be outlined in more detail in the following sections.    Figure  3.2  Lightning Rod  The Lightning Rod must be welded to the mast constructed of a steel pointed tip and is in general installed at the highest point of the tower. It operates to intercept the downward moving lightning strike by launching an upward going attachment spark.attachment is achieved, the bulk of the lightning current follows the ionized path. In this way, the lightning rod diverts the lightning away from equipment on the tower. If the lightning rod is not installed at the highest point on the tower, thighest point (usually a radio) is the most likely attachment point.   A Class I lightning rod (air terminal) is 3/8inch copper or 5/8-inch aluminum. Con(stranded  or  strips)  and  materials  (aluminum  or  copper).  Since  most  soils  contain  acid  or  alkaloid compounds  that  react  with  aluminum,  any  aluminum  used  must  not  come  in  contact  with  the  soLightning rods (air terminals) 24 inches or higher should be used.  Quantum 1000 Base Station User Guide   Rev 1.1, Page emonstrates graphically how these elements are applied to an overall lightning design. Please note that this is simply a generic diagram and that each individual installation may have its own specific requirements which may differ from the diagram. The key point to note is the overall concept.The main items will be outlined in more detail in the following sections.  Figure 41 - A Typical Lightning Protection Design The Lightning Rod must be welded to the mast structure and to a down conductor. This should beconstructed of a steel pointed tip and is in general installed at the highest point of the tower. It operates to intercept the downward moving lightning strike by launching an upward going attachment spark.attachment is achieved, the bulk of the lightning current follows the ionized path. In this way, the lightning rod diverts the lightning away from equipment on the tower. If the lightning rod is not installed at the highest point on the tower, the equipment that is connected to the highest point (usually a radio) is the most likely attachment point.   A Class I lightning rod (air terminal) is 3/8-inch copper or 1/2-inch aluminum, while Class II calls for 1/2inch aluminum. Conductor sizes vary accordingly, also depending on their composition (stranded  or  strips)  and  materials  (aluminum  or  copper).  Since  most  soils  contain  acid  or  alkaloid compounds  that  react  with  aluminum,  any  aluminum  used  must  not  come  in  contact  with  the  soLightning rods (air terminals) 24 inches or higher should be used.  Rev 1.1, Page 39 of 70 emonstrates graphically how these elements are applied to an overall lightning design. Please note that this is simply a generic diagram and that each individual installation may have its own point to note is the overall concept.  structure and to a down conductor. This should be constructed of a steel pointed tip and is in general installed at the highest point of the tower. It operates to intercept the downward moving lightning strike by launching an upward going attachment spark. Once the attachment is achieved, the bulk of the lightning current follows the ionized path. In this way, the lightning he equipment that is connected to the inch aluminum, while Class II calls for 1/2-ductor sizes vary accordingly, also depending on their composition (stranded  or  strips)  and  materials  (aluminum  or  copper).  Since  most  soils  contain  acid  or  alkaloid compounds  that  react  with  aluminum,  any  aluminum  used  must  not  come  in  contact  with  the  soil.
   Quantum 1000 Base Station User  Referring to figure 41 above, the “Height Above Antenna” above the highest item of equipment (generally the antenna) must  be at least twice  the distance  (2 x d)  between the outer surfatower. This  will ensure  a “protection cone” of 60 degrees around the  tower (30  degrees each side from the lightning rod). In areas of high lightning activity, the “Height Above Antenna” should be increased to up 5 times the distance.  3.3  Down Conductor  The purpose of the Down conductor is to provide the shortest and most direct path to the earth. grounding of the down conductor to earth must be of ground resistance no more than 5 ohms. 3.4  Co-axial and/or Cat 5 Cable Shield Grounding The purpose of the Shield grounding is to minimize the potentials induced on circuit conductors plus keep the cable shields at earth potential (0V) for personnel safety. All ground lugs must be properly bonded to the grounding system of the protected compall Antenna cables. Prior to entry into any facility, the cables must be properly grounded to the building primary ground system at the building entrance panel.  In case of an indoor installed Base Station then this will apply to the coStation to the Antenna. This is because these cothe indoor and the outdoor.   In the case of an outdoor installed Base Station, then this will apply to the Cat 5 cabconnection to the Base Station. In the case of an installation of the Base Station, it is the Cat 5 cable and the power that provide the inter-connections between the indoor and the outdoor. 3.5 Grounding and Bonding The National Electric Code requires that any accessible metallic surface of electronic equipment be connected to earth ground for personnel safety. Earth ground connections are achieved by direct connections to the AC power ground at the IDU and by a grounding lug on the ODU. A Craftattach a proper size wire to the ODU ground lug during installation, else the ODU chassis will float at whatever potential appears at the shield connection of the coax.  3.6 Recommended Connection of a Bonded Ground We will now examine the concept of a bonded ground. Bonded connections for reliable, gas tight joints between conductors require removal of all paint from both contact surfaces and holding them together under high pressure such as with a bolt or screw. The use of toothed washers is alcause the conductive surfaces to bite into each other for improved connectivity and eliminate movement of the conductors due to vibration.    Quantum 1000 Base Station User Guide   Rev 1.1, Page above, the “Height Above Antenna” above the highest item of equipment (generally the antenna) must  be at least twice  the distance  (2 x d)  between the outer surface of the item and the tower. This  will ensure  a “protection cone” of 60 degrees around the  tower (30  degrees each side from the lightning rod). In areas of high lightning activity, the “Height Above Antenna” should be increased to The purpose of the Down conductor is to provide the shortest and most direct path to the earth. grounding of the down conductor to earth must be of ground resistance no more than 5 ohms.axial and/or Cat 5 Cable Shield Grounding The purpose of the Shield grounding is to minimize the potentials induced on circuit conductors plus keep the cable shields at earth potential (0V) for personnel safety. All ground lugs must be properly bonded to the grounding system of the protected compall Antenna cables. Prior to entry into any facility, the cables must be properly grounded to the building primary ground system at the building entrance panel.  In case of an indoor installed Base Station then this will apply to the co-axial cables that connect the Base Station to the Antenna. This is because these co-axial cables provide the only inter-connection between In the case of an outdoor installed Base Station, then this will apply to the Cat 5 cable and power connection to the Base Station. In the case of an installation of the Base Station, it is the Cat 5 cable and connections between the indoor and the outdoor. Grounding and Bonding equires that any accessible metallic surface of electronic equipment be connected to earth ground for personnel safety. Earth ground connections are achieved by direct connections to the AC power ground at the IDU and by a grounding lug on the ODU. A Craftattach a proper size wire to the ODU ground lug during installation, else the ODU chassis will float at whatever potential appears at the shield connection of the coax. Recommended Connection of a Bonded Ground pt of a bonded ground. Bonded connections for reliable, gas tight joints between conductors require removal of all paint from both contact surfaces and holding them together under high pressure such as with a bolt or screw. The use of toothed washers is also recommended to cause the conductive surfaces to bite into each other for improved connectivity and eliminate movement   Rev 1.1, Page 40 of 70 above, the “Height Above Antenna” above the highest item of equipment (generally ce of the item and the tower. This  will ensure  a “protection cone” of 60 degrees around the  tower (30  degrees each side from the lightning rod). In areas of high lightning activity, the “Height Above Antenna” should be increased to The purpose of the Down conductor is to provide the shortest and most direct path to the earth. The grounding of the down conductor to earth must be of ground resistance no more than 5 ohms. The purpose of the Shield grounding is to minimize the potentials induced on circuit conductors plus keep All ground lugs must be properly bonded to the grounding system of the protected components along with all Antenna cables. Prior to entry into any facility, the cables must be properly grounded to the building axial cables that connect the Base connection between le and power connection to the Base Station. In the case of an installation of the Base Station, it is the Cat 5 cable and equires that any accessible metallic surface of electronic equipment be connected to earth ground for personnel safety. Earth ground connections are achieved by direct connections to the AC power ground at the IDU and by a grounding lug on the ODU. A Craftsperson must attach a proper size wire to the ODU ground lug during installation, else the ODU chassis will float at pt of a bonded ground. Bonded connections for reliable, gas tight joints between conductors require removal of all paint from both contact surfaces and holding them together so recommended to cause the conductive surfaces to bite into each other for improved connectivity and eliminate movement
   Quantum 1000 Base Station User 3.7 Single Point Grounding Concept Extensive analysis and investigation of installations has led to the majority of the failures is likely to be the presence of multiand in the huts. Single point grounding these elements will eliminate ground voltage differentials will dramatically increase the equipment survivability during surges. Single point grounding requires that the grounding leads from the antenna, Base Station and Surge Protection devices for a particular sector, are bonded together at the same point on the tower down conductor. It is not necessary to bond all the sectors togindividual sector have the same ground point on the tower.  In the equipment hut, in the event of an indoor installation of the Base Station then the chassis ground of the Base Station and all the Surge Protectionfigure 42).    Figure  It is important to note that the following ground guidelines are followed during installations: 1. Surge Protection devices generallyground wire length when finished connecting it to the single point earth ground2. Never loop or coil up the ground wire, always connect it straight to ground.3. A good earth ground impedance is less than4. Measure ground impedance at the point where the protector ground wire is connected and not at the ground rod. 5. Avoid sharp bends. Connect the ground wire as straight as possible.6. Connect the protector ground wire and equipment ground (both power gground) to a single common ground.7. Make sure all connections are fastened securely and are tight.8. Never install protectors during a storm and always follow your local safety codes.          Quantum 1000 Base Station User Guide   Rev 1.1, Page Single Point Grounding Concept Extensive analysis and investigation of installations has led to the belief that the root cause at the heart of the majority of the failures is likely to be the presence of multi-point grounding of equipment on the towers and in the huts. Single point grounding these elements will eliminate ground voltage differentials will dramatically increase the equipment survivability during surges. Single point grounding requires that the grounding leads from the antenna, Base Station and Surge Protection devices for a particular sector, are bonded together at the same point on the tower down conductor. It is not necessary to bond all the sectors together but to ensure the components of any individual sector have the same ground point on the tower.  In the equipment hut, in the event of an indoor installation of the Base Station then the chassis ground of the Base Station and all the Surge Protection Devices grounds must be grounded at the same point (see         Figure 42 - Single Point Grounding Concept It is important to note that the following ground guidelines are followed during installations:Surge Protection devices generally connect to ground by using a ground wire. Cut any extra ground wire length when finished connecting it to the single point earth ground Never loop or coil up the ground wire, always connect it straight to ground. A good earth ground impedance is less than 1.0 ohm. Measure ground impedance at the point where the protector ground wire is connected and not at Avoid sharp bends. Connect the ground wire as straight as possible. Connect the protector ground wire and equipment ground (both power ground and telecomm. ground) to a single common ground. Make sure all connections are fastened securely and are tight. Never install protectors during a storm and always follow your local safety codes. Rev 1.1, Page 41 of 70 the belief that the root cause at the heart of point grounding of equipment on the towers and in the huts. Single point grounding these elements will eliminate ground voltage differentials and this Single point grounding requires that the grounding leads from the antenna, Base Station and Surge Protection devices for a particular sector, are bonded together at the same point on the tower down ether but to ensure the components of any In the equipment hut, in the event of an indoor installation of the Base Station then the chassis ground of Devices grounds must be grounded at the same point (see It is important to note that the following ground guidelines are followed during installations: connect to ground by using a ground wire. Cut any extra  Measure ground impedance at the point where the protector ground wire is connected and not at round and telecomm. Never install protectors during a storm and always follow your local safety codes.
   Quantum 1000 Base Station User 3.8 Lightning and Surge Protection PureWave recommends that Surge Protection Devices are installed to protect the Base Station. For an indoor installation of the Base Station these “Surge Protectors” devices would be installed at the entrance to the building that “houses” the Base Station (see fig   Figure 43 - Indoor Installed Base Station Relative to Position of Lightning Protectors  Such a device will provide protection to the Base Station in the event of a “surge event” entering the Base Station through the RF port.  Two recommended devices are:  •  PolyPhaser Model AL-LSXMDC block. This is a uni-directional device.•  Altelicon Model AL-NMNFBbi-directional device.     Quantum 1000 Base Station User Guide   Rev 1.1, Page Lightning and Surge Protection recommends that Surge Protection Devices are installed to protect the Base Station.For an indoor installation of the Base Station these “Surge Protectors” devices would be installed at the entrance to the building that “houses” the Base Station (see figure 43).   Indoor Installed Base Station Relative to Position of Lightning ProtectorsSuch a device will provide protection to the Base Station in the event of a “surge event” entering the Base LSXM-ME (see figure 44). This is a 2GHz to 6GHz in-line surge filter with a directional device. NMNFB-9 (see figure 45). This is a DC to 6GHz in-line surge filter.  Rev 1.1, Page 42 of 70 recommends that Surge Protection Devices are installed to protect the Base Station. For an indoor installation of the Base Station these “Surge Protectors” devices would be installed at the  Indoor Installed Base Station Relative to Position of Lightning Protectors Such a device will provide protection to the Base Station in the event of a “surge event” entering the Base line surge filter with a line surge filter. This is a
   Quantum 1000 Base Station User  Figure 44 - PolyPhaser Model AL    Figure 45 – Altelicon Model AL  Care must be undertaken when installing the surge protectors. Iirrelevant as to the direction of installation. If the device is uniensure that the protected side of the surge protector is connected to the Base Station. In the casePolyphasor the N-type male connection is connected directly to the Base Station output and the Nfemale connection is connected to the Base Station to Antenna cable. The male to female design of the surge protector means that it is very difficground wire is connected to the ground lug that is provided with the surge unit (see figure 4   Quantum 1000 Base Station User Guide   Rev 1.1, Page  PolyPhaser Model AL-LSXM-ME Surge Protector (with ground lug) Altelicon Model AL-NMNFB-9 Surge Protector (with ground lug)Care must be undertaken when installing the surge protectors. If the device is bi-directional then it is irrelevant as to the direction of installation. If the device is uni-directional therefore it must be installed to ensure that the protected side of the surge protector is connected to the Base Station. In the casetype male connection is connected directly to the Base Station output and the Nfemale connection is connected to the Base Station to Antenna cable. The male to female design of the surge protector means that it is very difficult to incorrectly connect. In addition it is recommended that a ground wire is connected to the ground lug that is provided with the surge unit (see figure 4 Rev 1.1, Page 43 of 70 Surge Protector (with ground lug) Surge Protector (with ground lug) directional then it is directional therefore it must be installed to ensure that the protected side of the surge protector is connected to the Base Station. In the case of the type male connection is connected directly to the Base Station output and the N-type female connection is connected to the Base Station to Antenna cable. The male to female design of the ult to incorrectly connect. In addition it is recommended that a ground wire is connected to the ground lug that is provided with the surge unit (see figure 46).
   Quantum 1000 Base Station User  Figure 46 - PolyPhaser Surge Protector Connected to Cable with Ground Cable Attached Actual installation will depend upon the tower specifics. General tower installation practices would have a large ground bar or plate just at the cable entrance to the building and the Surge Protectors would be either attached directly or via the ground wire tdirectly attached to the Base Station and then appropriate ground connections can be made. In the event that the Base Station Radio is installed outside then it is recommended to install the surge protection unit(s) between the Base Station and the Antenna.  Figure 47 - Outdoor Installed Base Station Relative to Position of Lightning Protectors  Quantum 1000 Base Station User Guide   Rev 1.1, Page  PolyPhaser Surge Protector Connected to Cable with Ground Cable Attachedal installation will depend upon the tower specifics. General tower installation practices would have a large ground bar or plate just at the cable entrance to the building and the Surge Protectors would be either attached directly or via the ground wire to this plate/bar. Alternatively the Surge Protectors can be directly attached to the Base Station and then appropriate ground connections can be made.In the event that the Base Station Radio is installed outside then it is recommended to install the surge protection unit(s) between the Base Station and the Antenna.  Outdoor Installed Base Station Relative to Position of Lightning Protectors Rev 1.1, Page 44 of 70 PolyPhaser Surge Protector Connected to Cable with Ground Cable Attached al installation will depend upon the tower specifics. General tower installation practices would have a large ground bar or plate just at the cable entrance to the building and the Surge Protectors would be o this plate/bar. Alternatively the Surge Protectors can be directly attached to the Base Station and then appropriate ground connections can be made. In the event that the Base Station Radio is installed outside then it is recommended to install the surge  Outdoor Installed Base Station Relative to Position of Lightning Protectors
   Quantum 1000 Base Station User  These “RF” surge protection devices will provide the Customer with two advantages (see figure 4 1) To protect the Base Station in the event of a “surge event” entering the BasRF port. 2) It provides a mechanism to effectively “ground” together the Base Station, the RF surge protector and the antenna.  In the case of an outdoor installation, it is recommended that suitable building entry surge protection is considered and the equipment installer may want to consider based upon individual installation requirements.   Note: Please ensure that appropriate weather protection is applied to all outdoor Protection devices.   Surge protection devices for both thebuilt into the unit. No further devices are required to protect the unit. In addition, for an appropriate fee, PureWave provides a RF lightning surge protection kit. This includes the RF surga “ground bar” which acts as a means to ground all the devices. Please refer to figure 4of this kit when installed.   Figure 48 - Installed   Quantum 1000 Base Station User Guide   Rev 1.1, Page These “RF” surge protection devices will provide the Customer with two advantages (see figure 4To protect the Base Station in the event of a “surge event” entering the Base Station through the It provides a mechanism to effectively “ground” together the Base Station, the RF surge protector In the case of an outdoor installation, it is recommended that suitable building entry surge protection is nsidered and the equipment installer may want to consider based upon individual installation Please ensure that appropriate weather protection is applied to all outdoor Surge protection devices for both the Cat 5 and the power connections to the Base Station are already built into the unit. No further devices are required to protect the unit. In addition, for an appropriate fee, PureWave provides a RF lightning surge protection kit. This includes the RF surge protection devices and a “ground bar” which acts as a means to ground all the devices. Please refer to figure 48 Installed PureWave provides a RF lightning surge protection kit    Rev 1.1, Page 45 of 70 These “RF” surge protection devices will provide the Customer with two advantages (see figure 47). e Station through the It provides a mechanism to effectively “ground” together the Base Station, the RF surge protector In the case of an outdoor installation, it is recommended that suitable building entry surge protection is nsidered and the equipment installer may want to consider based upon individual installation Please ensure that appropriate weather protection is applied to all outdoor Surge Cat 5 and the power connections to the Base Station are already built into the unit. No further devices are required to protect the unit. In addition, for an appropriate fee, e protection devices and 8 for an example  PureWave provides a RF lightning surge protection kit
   Quantum 1000 Base Station User 4.  Weather Protection PureWave recommends that appropriate weather protection sealing and the application of an antimaterial is applied to all “outdoor” installed elements of the system. seals the junction between two connprevents vibrations from loosening the interface.  4.1  Weather Sealing  There are a range of commercially available weather protection “kits” that provide all the necessary components in addition to full instructions on “how to” weather protect. A generic weather sealing concept will be adopted rather than a specific one.  The following universal weatherproofing kit was used: Name:   Universal Weatherproofing KitPart #:    488136  Descripton: Weatherproofing tape kit. Each kit contains (6) rolls of 2rolls of 3/4" x 66' black electrical tape & (1) roll of 2" x 20' black electrical tape.Manufacturer: Andrew Networks (P/N 221213)Distributor: Tessco (http  The butyl tape is shown below in figure 4  Figure The general procedure to install is:  1) Completely wrap the connection with the smaller 3/4inch smaller electrical (plastic) tape. Ensure that the tape extends back up the cable to cover the entire connector and that the tape overlays itself by approximately half a width (figures    Quantum 1000 Base Station User Guide   Rev 1.1, Page Protection PureWave recommends that appropriate weather protection sealing and the application of an antimaterial is applied to all “outdoor” installed elements of the system. Weatherproofing tape kits flawlessly seals the junction between two connectors. It not only protects the connection from water damage, it also prevents vibrations from loosening the interface.    There are a range of commercially available weather protection “kits” that provide all the necessary addition to full instructions on “how to” weather protect. A generic weather sealing concept will be adopted rather than a specific one. The following universal weatherproofing kit was used: Universal Weatherproofing Kit  Weatherproofing tape kit. Each kit contains (6) rolls of 2-1/2" x 24" butyl tape, (2) rolls of 3/4" x 66' black electrical tape & (1) roll of 2" x 20' black electrical tape.Andrew Networks (P/N 221213)   Tessco (http://www.tessco.com)  The butyl tape is shown below in figure 49.  Figure 49 - Butyl Tape Weather Protection  Completely wrap the connection with the smaller 3/4inch smaller electrical (plastic) tape. Ensure that the tape extends back up the cable to cover the entire connector and that the tape overlays itself by approximately half a width (figures 50 and 51).  Rev 1.1, Page 46 of 70 PureWave recommends that appropriate weather protection sealing and the application of an anti-seize Weatherproofing tape kits flawlessly ectors. It not only protects the connection from water damage, it also There are a range of commercially available weather protection “kits” that provide all the necessary addition to full instructions on “how to” weather protect. A generic weather sealing concept 1/2" x 24" butyl tape, (2) rolls of 3/4" x 66' black electrical tape & (1) roll of 2" x 20' black electrical tape. Completely wrap the connection with the smaller 3/4inch smaller electrical (plastic) tape. Ensure that the tape extends back up the cable to cover the entire connector and that the tape overlays
   Quantum 1000 Base Station User      Figure      Quantum 1000 Base Station User Guide   Rev 1.1, Page Figure 50 - Connection to Antenna Figure 51 - Plastic (Electrical) Tape Applied  Rev 1.1, Page 47 of 70
   Quantum 1000 Base Station User  2) Cut a length of the butyl such that it will completely cover the connection. Wrap the tape around the connector and press into place. Ensure that there are no gaps  Figure    3) Completely wrap the “wrapped assembly” with the larger 2 inch electrical (plastic) tape. Ensure that the tape extends back up the cable to cover the entireitself by approximately half a width (figure 5  Quantum 1000 Base Station User Guide   Rev 1.1, Page Cut a length of the butyl such that it will completely cover the connection. Wrap the tape around the connector and press into place. Ensure that there are no gaps (figures 52 and 5 Figure 52 - Butyl Tape Being Applied    Figure 53 - Butyl Tape Applied Completely wrap the “wrapped assembly” with the larger 2 inch electrical (plastic) tape. Ensure that the tape extends back up the cable to cover the entire butyl tape and that the tape overlays itself by approximately half a width (figure 54).  Rev 1.1, Page 48 of 70 Cut a length of the butyl such that it will completely cover the connection. Wrap the tape around and 53).   Completely wrap the “wrapped assembly” with the larger 2 inch electrical (plastic) tape. Ensure butyl tape and that the tape overlays
   Quantum 1000 Base Station User   Figure 4.2  Anti-Seize  It is also suggested that a suitable antisuitable lubricant is recommended below. Name:    NEVER-SEEZ® Regular Grade Lubricant 1OZ Part #:    V057940-8A  Descripton:  NEVER-SEEZ® regular grade lubricant is an antipressure lubricantand seizure up to 1800ºF.Distributor: Ellsworth Adhesives (http://www.ellsworth.com)    Quantum 1000 Base Station User Guide   Rev 1.1, Page  Figure 54- Second Plastic Tape Applied It is also suggested that a suitable anti-corrosion lubricant is applied to all exposed metal surfaces. A suitable lubricant is recommended below. SEEZ® Regular Grade Lubricant 1OZ (figure 55)  8A   SEEZ® regular grade lubricant is an anti-seize compound and extreme pressure lubricant in a 1 ounce tube. Protect metal parts against rust, corrosion and seizure up to 1800ºF. Ellsworth Adhesives (http://www.ellsworth.com)  Figure 55 - Anti-Seize Lubricant   Rev 1.1, Page 49 of 70  corrosion lubricant is applied to all exposed metal surfaces. A seize compound and extreme metal parts against rust, corrosion
   Quantum 1000 Base Station User To apply the material then the exposed metal surface is simply “painted” with the lubricant suchexposed metal surfaces are completely covered (see figure 5 Note: These types of lubricants tend to be “messy” and “sticky” their intended application. Always read the labels or instructions provided and take necpre-cautions during application.       Quantum 1000 Base Station User Guide   Rev 1.1, Page To apply the material then the exposed metal surface is simply “painted” with the lubricant suchexposed metal surfaces are completely covered (see figure 56). These types of lubricants tend to be “messy” and “sticky” to apply due to tintended application. Always read the labels or instructions provided and take nec  Figure 56 - Anti-Seize Applied  Rev 1.1, Page 50 of 70 To apply the material then the exposed metal surface is simply “painted” with the lubricant such that all due to the nature of intended application. Always read the labels or instructions provided and take necessary
   Quantum 1000 Base Station User 5. Base Station Bring5.1  Overview  This section describes how the operator may powersystem initialization. The PureWaveand ensure general system integrity 5.2 Connect to the Base Station There are three RJ45 Ethernet ports to connect and hence access the Base Station. RS232: This is the serial interface to the Base Station. This interface will be primarily used for “out of the box” configuration and debug purposes.  E-NET 1: This Gigabit Ethernet port provides the data traffic backhaul interface that should be connecteto the Service Provider’s network equipment. This port allows in E-NET 2: This Gigabit Ethernet port provides an outcan be used for daisy chaining to another basCamera.   The procedure to connect to the Base Station is: • Terminate the antenna ports ANT 1 and ANT 2 as directed.• Connect and Power on the Base Station.• Connect a “straight” Cat 5 Ethernet cabldirectly to your PC or to your switch. • To get access to Base Station CLI (Command Line Interface) you will need the following hardware that come with the install kit. These are as follows:  RJ45 cable.  DB9 male connector (Modem Adapter). DB9 female to DB9 female adapter. Optional: Serial to USB connector. Most laptop nowadays comes with USB connection instead of serial connection. If your PC/laptop has serial connection then you won’t need this adapter. If not, then you will need to get serial to USB adapter to access the             Figure   Quantum 1000 Base Station User Guide   Rev 1.1, Page Base Station Bring-up This section describes how the operator may power-up the PureWave Base Station and verify proper PureWave Base Station CLI (Command Line Interface) will be used to configeneral system integrity.   Connect to the Base Station There are three RJ45 Ethernet ports to connect and hence access the Base Station. RS232: This is the serial interface to the Base Station. This interface will be primarily used for “out of the box” configuration and debug purposes.  NET 1: This Gigabit Ethernet port provides the data traffic backhaul interface that should be connecteto the Service Provider’s network equipment. This port allows in-band management of the Base Station. NET 2: This Gigabit Ethernet port provides an out-of-band management interface. In addition, this port can be used for daisy chaining to another base station or to connect to an external device such as a web The procedure to connect to the Base Station is: Terminate the antenna ports ANT 1 and ANT 2 as directed. Connect and Power on the Base Station. Connect a “straight” Cat 5 Ethernet cable between the E-NET 1 port on the Base Station and the directly to your PC or to your switch.  To get access to Base Station CLI (Command Line Interface) you will need the following hardware that come with the install kit. These are as follows: DB9 male connector (Modem Adapter). DB9 female to DB9 female adapter. Optional: Serial to USB connector. Most laptop nowadays comes with USB connection instead of serial connection. If your PC/laptop has serial connection then you won’t need this adapter. If not, then you will need to get serial to USB adapter to access the BS CLI (figure 57).   Figure 57 – Serial to USB adapter (DB9 Male)  Rev 1.1, Page 51 of 70 up the PureWave Base Station and verify proper will be used to configure RS232: This is the serial interface to the Base Station. This interface will be primarily used for “out of the NET 1: This Gigabit Ethernet port provides the data traffic backhaul interface that should be connected band management of the Base Station.  band management interface. In addition, this port e station or to connect to an external device such as a web NET 1 port on the Base Station and the To get access to Base Station CLI (Command Line Interface) you will need the following Optional: Serial to USB connector. Most laptop nowadays comes with USB connection instead of serial connection. If your PC/laptop has serial connection then you won’t need this adapter. If not, then you will
   Quantum 1000 Base Station User  Plug one end of a “straight” Cat 5 Ethernet cable into the RS232 port on the Base Station and the other end into the RJ45 to Modem adapter. Connect the other end of this Modemand connect this DB9 serial cable to a USB adapter that connect to your laptop. Please refer to figure for the physical layout.   Antenna SectionANT 1ANT 2ANT 3ANT 4POWERGNDQuantum 1000 Base Station Figure 5.3  Configure the Base Station The Base Station can be configured using its CLI. To access the CLI then connection is made via any standard serial communications protocol, such as Hyper Terminal.   To access the Base Station CLI through Hyper Terminal Setup please follow theThis assumes a PC that is operating on Windows 2000/XP. 1) Start HyperTerminal by clicking on ‘>HyperTerminal’. 2) In Hyper Terminal create a "or via the menu within HyperTerminal "3) Type in a name for the connection (for example, test). 4)  Under "connect using" select "the appropriate com port.  5)  Set "Bits per second" to 38400. 6)  Set "Data Bits" to 8.  7)  Set “Parity” to None 8)  Set "Stop Bits" to 1.  9)  Set "Flow control" to Xon / Xoff10)  Click OK - the hyper terminal screen should appear. To login into the Base Station CLI then use the followin Login:    customer Password:  12345    Quantum 1000 Base Station User Guide   Rev 1.1, Page Plug one end of a “straight” Cat 5 Ethernet cable into the RS232 port on the Base Station and the other end into the RJ45 to Modem adapter. Connect the other end of this Modem adapter to a DB9 serial cable and connect this DB9 serial cable to a USB adapter that connect to your laptop. Please refer to figure 4RS232 E-NET 1 E-NET 2GPS ANTDB9 Female to DB9 Female CableRJ 45 Ethernet CableRJ 45 to Male Adapter .Modem DB9 Female to DBFemale CableRJ 45Ethernet CableModem Figure 58 – Base Station Serial Connection   e Station The Base Station can be configured using its CLI. To access the CLI then connection is made via any standard serial communications protocol, such as Hyper Terminal.   To access the Base Station CLI through Hyper Terminal Setup please follow the steps as outlined below. This assumes a PC that is operating on Windows 2000/XP. Start HyperTerminal by clicking on ‘Start -> Programs -> Accessories -> Communications In Hyper Terminal create a "new connection" this can be done by clicking the Hypertrm.exeor via the menu within HyperTerminal "File: NewConnection".  Type in a name for the connection (for example, test).  " select "Direct to Com 6" if the available com port is com 6 otherwise select " to 38400.  " to Xon / Xoff the hyper terminal screen should appear.  To login into the Base Station CLI then use the following information:  Rev 1.1, Page 52 of 70 Plug one end of a “straight” Cat 5 Ethernet cable into the RS232 port on the Base Station and the other adapter to a DB9 serial cable and connect this DB9 serial cable to a USB adapter that connect to your laptop. Please refer to figure 58 Serial to USB AdapterLaptopFemale to DB9 Female CableThe Base Station can be configured using its CLI. To access the CLI then connection is made via any steps as outlined below. > Communications -Hypertrm.exe icon " if the available com port is com 6 otherwise select
   Quantum 1000 Base Station User  After you successfully login, you will see “ Figure 59 - Hyper Terminal Login window to Base Station CLI 1)  Select 1 (CONFIGURATION)Station (figure 60).  Figure  2)  From the 1.1 BASIC CONFIGURATIONStation IP address for Management purposes. You must use “Quotations” when changing the IP address and specify the class of the subnet mask after the slash. The default BS IP Address is 192.168.2.101/24   Quantum 1000 Base Station User Guide   Rev 1.1, Page After you successfully login, you will see “PUREWAVE MANAGEMENT UTILITY” Dialog box (figure  Hyper Terminal Login window to Base Station CLI 1 (CONFIGURATION) from the menu and follow the steps carefully to configure the Base   Figure 60 - Base Station CLI Basic Configuration 1.1 BASIC CONFIGURATION menu, select 2 (DATA PORT IP Addr). TManagement purposes. You must use “Quotations” when changing the IP address and specify the class of the subnet mask after the slash. The default BS IP Address is 192.168.2.101/24  Rev 1.1, Page 53 of 70 ” Dialog box (figure 59).  from the menu and follow the steps carefully to configure the Base  (DATA PORT IP Addr). This is Base Management purposes. You must use “Quotations” when changing the IP
   Quantum 1000 Base Station User For example to change the BS IP address to 192.168.2.113/24, then enter thfigure 61.   Figure   3) The User is free to change the SYSLOG Server Addr (option #6). These will depend upon the Customer’s own networkconfiguration.  4) Please note that you will not be able to change the MAC Addr (option #3) addresses. 5) Hit the <ESC> to return to the “Save” any changes.  6)  Select 2 (WIRELESS PROTOCOLfollowing two settings (figure purposes.  • UL Automatic TX Power Control• Power Control Mode    Quantum 1000 Base Station User Guide   Rev 1.1, Page For example to change the BS IP address to 192.168.2.113/24, then enter the information as Figure 61 - Base Station CLI IP Address Change The User is free to change the Default Gateway (option #3), TFTP Server Addr (option #6). These will depend upon the Customer’s own networkPlease note that you will not be able to change the Base Station ID (option #1) and (option #3) addresses. Hit the <ESC> to return to the 1.1 BASIC CONFIGURATION menu. You will be prompted to WIRELESS PROTOCOL) from the 1.1 BASIC CONFIGURATION menu and verify the following two settings (figure 62). You cannot change the variables so this is simply for verification UL Automatic TX Power Control should be set to 1 (enabled) ontrol Mode should be set to 1 (Open-loop)  Rev 1.1, Page 54 of 70 e information as   (option #5), and (option #6). These will depend upon the Customer’s own network (option #1) and Data Port menu. You will be prompted to menu and verify the ). You cannot change the variables so this is simply for verification
   Quantum 1000 Base Station User  Figure 62 - 7) Hit the <ESC> to return to the “Save” any changes.  8)  Select #3 (ADVANCED CONFIGURATIONverify the following two settings (figure • Auto Default Provisioning• Auto Start is set for 1 (enabled)If these variables are not set as expected then select the relevant option and change these enabled state.    Quantum 1000 Base Station User Guide   Rev 1.1, Page - Base Station CLI IP Wireless Protocol Check Hit the <ESC> to return to the 1.1 BASIC CONFIGURATION menu. You will be prompted to ADVANCED CONFIGURATION) from the 1.1 BASIC CONFIGURATIONverify the following two settings (figure 63).  Auto Default Provisioning is set for 1 (enabled) is set for 1 (enabled) If these variables are not set as expected then select the relevant option and change these  Rev 1.1, Page 55 of 70  menu. You will be prompted to 1.1 BASIC CONFIGURATION menu and If these variables are not set as expected then select the relevant option and change these to the
   Quantum 1000 Base Station User  Figure 63 9) Hit the <ESC> to return to the “Save” any changes.  10)  Select #4 (RADIO) from the parameters. It is important that you set all 4 parameters especially the Frequency (this much match with the CPEs) and the Output Power (figure •  1 (Center Frequency (KHz)).with the CPEs. If the User wishes to change this then please provide the required frequency is KHz.  •  2 (Antenna Gain (dB)•  3 (Cable Loss (dB)). This is a loss of the cable (in dB’s) from the Base Station to the Antenna. •  4 (Output Power (dBm)Maximum output power should be set to 36.   Quantum 1000 Base Station User Guide   Rev 1.1, Page 63 - Base Station CLI Advanced Configuration Hit the <ESC> to return to the 1.1 BASIC CONFIGURATION menu. You will be prompted to ) from the 1.1 BASIC CONFIGURATION menu and assign the parameters. It is important that you set all 4 parameters especially the Frequency (this much match with the CPEs) and the Output Power (figure 64). Center Frequency (KHz)). This is the frequency of the Base Station and it must match with the CPEs. If the User wishes to change this then please provide the required  Antenna Gain (dB)). This is the gain (in dB) for the antenna that is being used. ). This is a loss of the cable (in dB’s) from the Base Station to the Output Power (dBm)). This is the output power in dBm. By default it is set at 6. Maximum output power should be set to 36.  Rev 1.1, Page 56 of 70  menu. You will be prompted to menu and assign the following radio parameters. It is important that you set all 4 parameters especially the Frequency (this much This is the frequency of the Base Station and it must match with the CPEs. If the User wishes to change this then please provide the required ). This is the gain (in dB) for the antenna that is being used.  ). This is a loss of the cable (in dB’s) from the Base Station to the ). This is the output power in dBm. By default it is set at 6.
   Quantum 1000 Base Station User  Figure 64 11) Hit the <ESC> to return to the “Save” any changes.                               Quantum 1000 Base Station User Guide   Rev 1.1, Page  64 - Base Station CLI Radio Configuration Hit the <ESC> to return to the 1.1 BASIC CONFIGURATION menu. You will be prompted to  Rev 1.1, Page 57 of 70  menu. You will be prompted to
   Quantum 1000 Base Station User  Quantum   Quantum 1000 Base Station User Guide   Rev 1.1, Page                  Appendix A  Quantum 1000   Base Station Data Sheet       Rev 1.1, Page 58 of 70
   Quantum 1000 Base Station User   Quantum 1000 Base Station User Guide   Rev 1.1, Page          Rev 1.1, Page 59 of 70
   Quantum 1000 Base Station User 4 (Quad) Antenna Panel                   Quantum 1000 Base Station User Guide   Rev 1.1, Page                Appendix B  4 (Quad) Antenna Panel Data Sheet       Rev 1.1, Page 60 of 70
   Quantum 1000 Base Station User  Electrical Polarization Input Impedance Mechanical Dimensions (LxWxD) Weight Antenna Elements Connectors Radome   Model Frequency (GHz) Peak Gain (per antenna) 2.5A 2.40 2.50 2.63 2.5C 2.40 2.50 2.63 3.5A 3.5 3.6 3.7       Quantum 1000 Base Station User Guide   Rev 1.1, Page  Vertical 50 ohm  25.54” x 20.33” x 1.75” 12.1 lbs 4 N-Type Female x 4 Kydex T Plastic, Light Grey Azimuth ElevationPeak Gain  (per antenna) (dBi) Beamwidth (3 dB) Peak Gain (per antenna) (dBi) Beamwidth14.2  63°  14.4 14.6  68°  14.6 13.9  72°  14.7 14.3  112°   14.0  117°   14.3  117°   17.5  68°  17.4 17.3  71°  17.3 17.2  60°  17.1  Rev 1.1, Page 61 of 70 Elevation Beamwidth (3 dB) 14° 13° 12°    8° 8° 8°
   Quantum 1000 Base Station User  225240255270285300315-130-140-150-160-1701801701601501401302.40 GHz2.48 GHz2.60 GHz  Quantum 1000 Base Station User Guide   Rev 1.1, Page Model 2.5A    Azimuth-25-20-15-10-505101501530456075901051201351501651801952103303452.40 GHz2.50 GHz2.63 GHzElevation-40-30-20-10010209080706050403020100-10-20-30-40-50-60-70-80-90-100-110-120-1301301201102.40 GHz2.48 GHz2.60 GHz Rev 1.1, Page 62 of 70
   Quantum 1000 Base Station User 225240255270285300315  Quantum 1000 Base Station User Guide   Rev 1.1, Page Model 2.5 C Azimuth-35-30-25-20-15-10-505101501530456075901051201351501651801952103303452.40 GHz2.50 GHz2.60 GHz Rev 1.1, Page 63 of 70
   Quantum 1000 Base Station User  225240255270285300315-130-140-150-160-1701801701601501401303.50 GHz3.60 GHz3.70 GHz  Quantum 1000 Base Station User Guide   Rev 1.1, Page Model 3.5 A     Azimuth-50-40-30-20-100102001530456075901051201351501651801952103303453.50 GHz3.60 GHz3.70 GHzElevation-50-40-30-20-10010209080706050403020100-10-20-30-40-50-60-70-80-90-100-110-120-1301301201103.50 GHz3.60 GHz3.70 GHz Rev 1.1, Page 64 of 70
   Quantum 1000 Base Station User Cable Terminations  Quantum 1000 Base Station User Guide   Rev 1.1, Page                   Appendix C  Cable Terminations   Rev 1.1, Page 65 of 70
   Quantum 1000 Base Station User EZ-400-NMH Connector Times Microwave Cable LMRThis installation procedure has been re1. Flush cut the cable squarely.     2. Slide the heat shrink boot and crimp ring onto the prep/strip tool by inserting the cable into End 1 and rotating the tool. Remove any residual plastic from the center conductor.     3. Insert the cable into End 2 of the STplastic jacket.      Quantum 1000 Base Station User Guide   Rev 1.1, Page NMH Connector Installation Procedure on Times Microwave Cable LMR-400  This installation procedure has been re-produced in its entirety from the Times Microwave website. Flush cut the cable squarely.   Slide the heat shrink boot and crimp ring onto the cable. Strip the cable end using the STprep/strip tool by inserting the cable into End 1 and rotating the tool. Remove any residual plastic   Insert the cable into End 2 of the ST-400-EZ prep/strip tool and rotate the tool to remove the   Rev 1.1, Page 66 of 70 produced in its entirety from the Times Microwave website. cable. Strip the cable end using the ST-400-EZ prep/strip tool by inserting the cable into End 1 and rotating the tool. Remove any residual plastic the tool to remove the
   Quantum 1000 Base Station User  4. Debur the center conductor using    5. Flare the braid slightly and push the connector body onto the cable until the connector snaps into place, then slide the crimp ring forward    6. Temporarily slide the crimp ring back, and remove the connector bodyexcess braid at the crease line, then remount theit butts up against the connector body      Quantum 1000 Base Station User Guide   Rev 1.1, Page Debur the center conductor using the DBT-01 deburring tool.  Flare the braid slightly and push the connector body onto the cable until the connector snaps into place, then slide the crimp ring forward creasing the braid.  Temporarily slide the crimp ring back, and remove the connector body from the cable to trim the excess braid at the crease line, then remount the connector and slide the crimp ring forward until connector body   Rev 1.1, Page 67 of 70 Flare the braid slightly and push the connector body onto the cable until the connector snaps into from the cable to trim the connector and slide the crimp ring forward until
   Quantum 1000 Base Station User   7. Position either the heavy duty HX400/300 crimp tool directly behind and adjacent to the connector body, and crimp the connector. The HX-4 crimp tool automatically relea    8. Position the heat shrink boot as far forward on the connector body aswith the coupling nut and use a heat gun to   Quantum 1000 Base Station User Guide   Rev 1.1, Page Position either the heavy duty HX-4 crimp tool with the appropriate dies (.429” hex) or the CT400/300 crimp tool directly behind and adjacent to the connector body, and crimp the connector. 4 crimp tool automatically releases when the crimp is complete.  Position the heat shrink boot as far forward on the connector body as possible, without interfering with the coupling nut and use a heat gun to form a weather tight seal.                 Rev 1.1, Page 68 of 70 (.429” hex) or the CT-400/300 crimp tool directly behind and adjacent to the connector body, and crimp the connector. possible, without interfering
   Quantum 1000 Base Station User   Identifying the RJ-45 Cable Type  To identify the RJ-45 cable type, hold the two ends of the cable next to each other so you can see the colored wires inside the ends, as shown. In a straightsequence at both ends of the cable.    When making a straight-through cable using Cat 5E, it is mandatory that you follow the 568shown below. Otherwise, you risk the possibility of damaging the       Quantum 1000 Base Station User Guide   Rev 1.1, Page Ethernet Cat 5 Cable  45 cable type, hold the two ends of the cable next to each other so you can see the colored wires inside the ends, as shown. In a straight-through cable, the colored wires are in the same both ends of the cable. through cable using Cat 5E, it is mandatory that you follow the 568shown below. Otherwise, you risk the possibility of damaging the equipment.  Rev 1.1, Page 69 of 70 45 cable type, hold the two ends of the cable next to each other so you can see the through cable, the colored wires are in the same  through cable using Cat 5E, it is mandatory that you follow the 568-B standard
   Quantum 1000 Base Station User Termination of the Cat 5E Shielded Cable Please Note:  You must use shielded Cat 5contact with the metal RJ-45 connector.  Quantum 1000 Base Station User Guide   Rev 1.1, Page Termination of the Cat 5E Shielded Cable You must use shielded Cat 5e cables and make certain that the drain wire has a good 45 connector.  Rev 1.1, Page 70 of 70  cables and make certain that the drain wire has a good

Navigation menu