MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
50Hz/1500 rpm/380V
POWER RATING (0.8 P.F.) MODEL CODE
STAND-BY 690 kVA 5S-H5F
PRIME 625 kVA 5P-H5F
MGS0500B with typical options
Voltage Variation
Standard Voltage 3Phase 4 Wires
380V
Voltages Available 3Phase 4 Wires
380, 400, 415, 440, 190, 200, 208 and 220V
Note: Outputs for optional voltages may differ from standard output mentioned above.
CONDITIONS & DEFINITIONS
Stand-by: Code: S
Applicable for supplying emergency power at varying load in the event of the normal utility power interruption.
Fuel stop power in accordance with ISO15550, ISO3046/1, JISB8002-1, DIN6271 and BS5514.
Overload: not allowed
Prime: Code: P
Applicable for supplying emergency power at varying load in the event of normal utility power interruption. + 10% overload
in accordance with ISO3046/1. Overload power in accordance with ISO15550, ISO3046/1, JIS8002-1, DIN6271 and
BS5514.
Conditions:
Engine ratings are based on SAE J1349 standard conditions and also apply at ISO3046/1, DIN6271 & BS5514 standard
conditions.
Fuel rates: based on ASTM D975, BS2869 and on fuel oil of 35° API (16°C or 60° F) gravity having a LHV of 42,780 kJ/kg
(18,390 Btu/lb.) when used at 29°C (85° F) and weighing 838.9 g/liter (7.001lbs./U.S. gal.).
Note: * For conditions of prime power (P.R.P.) and additional rating requirements, please consult your nearest Mitsubishi
MGS dealer.
DIMENSION (Reference Data)
Overall dimensions
L : Length
mm
3600
W : Width
mm
1710
H : Height mm 1935
Total Weight (Dry)
kg
5000
Total Weight (Wet)
kg
5300
M
MG
GS
S0
05
50
00
0B
B
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
MGS0500B
L-6, 4 stroke-cycle water-cooled, turbocharged and aftercooled
ENGINE SPECIFICATIONS & TECHNICAL DATA
Bore
mm
Stroke
mm
Displacement
L
Piston speed
m/sec.
Compression ratio
Lubricating oil capacity
L
Coolant capacity without radiator
L
Coolant pump external resistance
m water
Coolant pump flow rate
L/min
Cooling fan airflow rate
m3/min
Cooling fan air flow restriction
kPa
Ambient air temperature 40
Allowable exhaust back pressure
kPa
Exhaust flange size (internal diameter)
mm
ENGINE OPERATING DATA
Gross Engine Power*
kWm
584
529
Brake mean effective pressure
MPa
2.0
1.8
Regenerative absorption
kW
53
53
Noise Level at 1 m
dB(A)
107
105
(excluding: intake, exhaust & fan)
Fuel consumption load 100%*
L/hr.
147
132
Fuel consumption load 75%*
L/hr.
109
100
Combustion air inlet flow rate
m3/min
51
46
Exhaust gas flow rate
m3/min
133
120
Exhaust gas temperature 520 510
Heat rejection to coolant
kW
366
329
Heat rejection to exhaust
kW
454
402
Heat rejection to atmosphere from engine
kW
44
39
Heat rejection to atmosphere from generator
kW
34
30
* WITH FAN basis.
Deration for engine
Altitude: 2.5% per 300m (1000ft) above 1,500m
Temperature: 2% per 5 (9°F) above 40
ENGINE STANDARD EQUIPMENT
Aftercooler
Turbocharger filter
Structure steel base
Crankcase breather
Charging alternator
Lubricating oil cooler
Fuel filters, full flow paper element
Fuel transfer pump, gear driven, plunger type
Electronic type governor
Jacket water pump, gear driven
Lubricating oil filter, full flow paper element
Lubricating oil pump, gear driven
Exhaust dry manifold
Radiator, blower fan, fan drive
Manual shutoff
24V DC electric starting motor
STAND-BY
690 kVA
PRIME
625 kVA
MGS SERIES DIESEL ENGINE: MITSUBISHI S6R-PTA-S
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
MGS0500B
Type & Design
MGS standard 7310 programmable microprocessor control-automatic start/stop panel, generator breaker control,
indicating the operational status and fault conditions; automatically shutting down the engine and indicating the engine
failure by means of LCD display and LEDs on the front panel.
Controls & Monitoring
Mode selection & start engine button with interlock key switch system
Menu navigation button
LCD display for: AC amperage-each phase and earth current, AC voltage-each phase and neutral, Frequency Hz,
Operation hours run, Lub. Oil pressure, Cooling water temperature, Generator Load kW/kVA/kVar, Generator Load
kWh/kVAh/kVarh
Operation status LED indicators
CB control buttons
Mute/Lamp test button
Voltage adjuster
Speed adjuster
Emergency stop pushbutton
Provided 5 outputs for status as standard equipment (Programmable 8 outputs available as option)
Safety Shutdown Protection and LED Indicators
High engine temperature, Low oil pressure, Fail to start, Generator Over Speed/Frequency,
Generator Under Speed/Frequency
Generator High Voltage, Generator Low Voltage, Oil pressure sender circuit, Loss of Speed signal , Emergency stop,
Mounting
Fabricated cubicle mounted on individual bracket with anti-vibration isolator
Electrical Design
In accordance with BS EN 60950 Low Voltage Directive, BS EN 61006-2 and 61006-4 EMC Directive. The optional
interface can provide real time diagnostic facilities.
Generator Control Panel Description
3 position operation mode control key switch
(ACTIVE, PANEL LOCK, STOP/RESET)
Manual button Stop/Reset button (Manual only)
Auto button Mute/Lamp test button (Manual only)
CB open button (Manual only) Voltage adjusting trimmer
CB close button (Manual only) Speed adjusting trimmer
Start engine button (Manual only) Emergency stop pushbutton
LCD display accessed by scroll pushbutton
Generator volts L1-N, L2-N, L3-N
Engine cooling water temperature (°C & °F)
Generator volts L1-L2, L2-L3, L3-L1
Battery volts
Generator amps L1, L2, L3
Engine hours run
Generator Earth Current
Generator Load kW, kVA, kVar
Generator Frequency Hz
Generator Load kWh, kVAh, kVarh
Engine speed RPM
Power Factor
Engine oil pressure (PSI & Bar)
Generator Phase Sequence
Visual indicators on LCD display
Shutdown alarm
Generator high current
Warning alarm
Over voltage (AC)
High coolant temperature
Under voltage (AC)
Low oil pressure
Over voltage (DC)
Charge fail
Under voltage (DC)
Over-speed
Auxiliary indication
Under-speed
Auxiliary alarm (warning or shutdown)
Electrical trip
Common alarm
Fail to stop
Over frequency
Under frequency
Visual indication alarm and automatically shutdown
High engine temperature
Over frequency
Low oil pressure
Under frequency
Fail to start
Oil pressure sender open circuit
Over-speed
Loss of speed signal
High voltage
High Crankcase internal pressure (MGS-C Continuous only)
Low voltage
Emergency Stop
Operation status indicated by LED
Remote start present
Lubrication oil filter clogged
Generator ready
Electrical trip
Pre-Programmed Starting Unit
Automatic start/stop sequence timing and delay systems configured
via MS-Windows based software.
MGS SERIES 7310 GENERATOR CONTROL PANEL
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
MGS0500B
Type & Design
MGS original design, single bearing, 4 pole, screen protected, selfexciting, self regulating and brushless with fully
connected damper windings, salient pole rotors, A.C. exciter and rotating rectifier unit. Direct coupled to engine and
pre-lubricated maintenance free bearing, direct drive centrifugal blower.
Enclosure: Drip-proof IP23
Winding System
Standard 12 wire reconnectable winding provides a wide range of 3 phase voltage. All windings are impregnated in
vacuum pressure impregnated with a special polyester resin.
Overspeed capability: 125% for 2 minutes
Insulation: Class 'H' of IEC
Temperature rise: Class 'H'
Voltage Regulator
Fully sealed, RMS sensing AVR with built-in protection against sustained over-excitation. This de-excites the generator
after a minimum of 5 seconds.
Voltage regulation: Less than +/- 0.5% from no load to full load at any power factor between 0.8 lagging and 1.0
allowing for a 4% engine speed variation
Voltage adjustment: +/- 6%
Wave form: Less than 5% deviation
Permanent Magnet Generator (PMG)
Electrically isolated from the main alternator stator windings powers AVR - sustaining approx. 250300% of short circuit
current at the AC generator output terminals for not more than 10 seconds by means of excitation voltage via AVR
Electrical Design
In accordance with BS5000 Part 3, VDE0530, UTE51100, NEMA MG1-22, CEMA, IEC34-1, CSA22.2, AS1359 and
JEC2100.
Telephone Influence Factor (TIF): Less than 50
Telephone Harmonic factor (THF): Less than 2%
Radio interference: Suppression is in line with the provision of BS800 and VDE Class G and N
Gen Set Option Features
ENGINE
Air Cleaner, paper element dry type
Battery Kit
Battery Charger
Anchor Bolts
FUEL
Fuel Day Service Tank
COOLING
Oversize radiator
Heat Exchanger
Expansion Tank
Jacket Water Heater
Removal STD Radiator, Fan & Fan Drive
LUBRICATION
Lub. Oil Priming Pump
EXHAUST
Exhaust Silencer
Exhaust Flexible Pipe
GENERATOR
Space Heater
1 phase Sensing Auto Voltage Regulator
Power Factor Regulator
CONTROL PANEL
Diesel Generator Integrated Communication Synthesizer (DGICS-MII)
Auxiliary Control Panel
Remote Monitor Interface
SWITCHGEAR
Circuit Breaker MCCB & ACB
Reverse Power Relay
Power Systems Engine Section, Engine Sales Department
16-5, KONAN 2-CHOME, MINATO-KU, TOKYO 108-8215 JAPAN
TEL: 81-3-6716-4771 FAX: 81-3-6716-5854
Mitsubishi Heavy Industries, Ltd. serves for the customers with improved products continually.
Therefore specification and some materials will be changed without notice.
The International System of units (SI) is used in this publication.
MGS SERIES AC GENERATOR MODEL: MG-HC5F