NORDYNE Furnace/Heater, Gas Manual L0523341
M3RL Series L0523341
User Manual: NORDYNE NORDYNE Furnace/Heater, Gas Manual NORDYNE Furnace/Heater, Gas Owner's Manual, NORDYNE Furnace/Heater, Gas installation guides
Open the PDF directly: View PDF .
Page Count: 36
Download | ![]() |
Open PDF In Browser | View PDF |
Direct Vent (SeaHed Combustion) M3RL Series 90+ Downfiow For installation in: I. Manufactured Forced Air Gas Furnaces Condensing Furnace Homes 2. Park Models and Manufactured 3. Modular Homes/Buildings Buildings WARNING: FiRE OR EXPLOSION HAZARD Failure to fol!ow safety warnings e×actly could result in serious injury, death or property damage. - Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. -WHAT TO DO mFYOU SMELL GAS o Do not try to light any appliance. o Do not touch any electrical switch; do not use any phone in your building. , Leave the building immediately. o Immediately call your gas supplier from a neighbor s phone. Follow the gas supplier's instructions. , If you cannot reach your gas supplier, call the fire department. -installation and service must be performed by a qualified installer, service agency, or the gas supplier. BW Models BWT Models RISQUE D'INCENDmE OU D'EXPLOSmON Le non-respect des avertissements de s_curit_ pourrait entra_ner des blessutes graves, la mort ou des dommages mat_rieJs. - Ne pas entreposer ni utiliser de I'essence ni d'autres vapeurs ou liquides inflammables dans Ic voisinage de cet appareil, ni de tout autre apparei -QUE FAmRE S'IL YA UNE ODEUR DE GAZ o Ne pas tenter d'allumer aucun appareil. ,Ne toucher a aucun interrupteur 61ectdque; n'utiliser aucun t616phone dans le b_timent. o E_vacuer I'immeuble immCdiatement. , Appeler immCdiatement le foumisseur de gaz en employant le t616phone d'un voisin. Respecter la lettre les instructions du foumisseur de gaz. o Si personne ne repond, appeler le service des incendies. - Uinstallation et I'entretien doivent Ctre effectues par un installateur qualifie, un organisme de service ou le fournisseur de gaz. WARNING: Shoumd overheating occur, or the gas suppty fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply. Improper installation, adjustment, amteration, service or maintenance or property this manual. additional a qualified agency can cause injury damage. Refer For assistance information consult installer, service or the gas supplier. LEAVE THESE mNSTRUCTmONS WroTHTHE HOMEOWNER. to or TABLE Generam ...................................................... Unit Dimensions .................................. Shipping Weights ................................ Furnace Specification ........................ Air Flow Data ..................................... Owner's hformation ................................ OF CONTENTS 4 4 4 4 4 5 Installation Requirements ...................... Location .............................................. Clearance ........................................... 6 7 7 Circumating ............................ 7 .............................. 8 Return Air Air Supply Air Provisions Distribution Duct Connector Duct Installation Systems ........................ 9 .................... 10 Selection Conversion .............................................. 21 Lighting and Adjustment of the Appliance .............................. 23 ElectdcaIWiring ...................................... Line Voltage Wiring ........................... Low Voltage Wiring ........................... 24 24 26 Ventilation 26 ................................................ Start-up and Adjustment ........................ Start-Up Procedure ........................... Shut Down Procedure ....................... 26 26 27 Verifying and Adjusting Firing Rate ... 27 Temperature Rise ............................. 27 Verifying and Adjusting Verifying Burner Operation .............. 28 Verifying Operation of the Supply Air Limit Switch ................. 28 .................................... 10 and Combustion Requirements ........................... 13 Description Venting Requirements .......................... Vent Table ........................................ Vent Pipe Material ............................ Vent Pipe Length and Diameter ....... Vent Pipe installation ........................ Pipe Routing & Support .................... Location of Outdoor Termination ..... Horizontal Venting ............................ Vertical Venting ................................ Vent Freezing Protection ................. Concentric Vent Termination ........... 14 15 16 16 16 16 16 18 18 19 19 Furnace Drainage of Condensate From Furnace ................................ 19 Gas Supply and Piping ......................... Leak Check ....................................... 20 21 Wiring Diagram ....................................... 33 High Altitude Derate ......................... Pressure Switch .............................. 21 21 instaliationlPerformance CheckJist ......................................... 35 Venting Air Maintenance Application ........................................... Furnace Series Comfort Mode! RL - Condensing 29 29 Condensate Drain Assembly ........... 30 Blower Compartment ....................... 30 Heat Exchanger and Burner Maintenance .................................. 30 System Operation Information ............. 30 Sequence of Operation .................... 30 Furnace Fails to Operate ................. 31 of Major Components .......... 32 060 A - A W c°°,,°°,°t,°° 1 M-Manufactured ................ 29 ............................. Combustion Air and Vent System .... 29 Air Filter(s) ....................................... 29 Lubrication ........................................ 30 Location M3RL- of Components Accessories Home W - White G - Gray Cabinet Dimensions A - 56" x 19-3/4" x 23-3/4" B - w/Coil Cavity, 76" x 19-3/4" x 23-3/4" m Downflow Heating Capacity input, BTUH (000') Tabte 1. Model Electricam Code A - IPH, 60 Hz, 120 VAC identification 3 I£_7/8 -- %1#2 -317132 COMBUSTION ® i i 24_5/8 -AiR INTAKE 1-1/118 EXHAUST VENT 18 1#2 KNOCKOUTS •I-- I_r2 fl 56!/16 (W/C_EBOX} 7_!_ (W/O CoilBo_) /32 2"37116 917132 , 1 19F32 21 157/6 -- Cooling Coil Box 1_3/!6 _-- Figure 1. Furnace 24_t4 -- Dimensions Top Return Knockouts _12.000_ _J 1000 , Shipping Weight \ 21000 = O © Furnace Model M3RL 060A AW (Ibs) 15O M3RL 060A BW* 170 M3RL 080A AW 155 M3RL 080A BW* 175 * May include Top Top View (AW and BW Models) Furnace Furnace Model No. M3 RL-060 M3 RL-080 Note: Specifications Furnace Furnace Input Btuh Output Btuh 60,000 80,000 54,000 72,000 Returr_ Opening (BWT Models) / Airflow 35- 65 I/2 35 - 65 I/2 3. Weight External 0.1 Static Pressure ( Inches Water 0.2 0.3 0.4 Speed High* CFM 1660 CFM I599 CFM I544 CFM 1474 CFM I410 Ton 4 Med-High Med-Low 1512 1340 I467 I304 I416 I261 1363 1217 I304 II58 3 2.-I/2 Low** 1176 II42 I108 1025 966 2 High* 1660 I599 I544 1474 I410 4 Med-High Med-Low** 1512 1340 I467 I304 I416 I261 1363 1217 I304 II58 Low 1176 II42 I108 1025 966 Factory Wired Heating Tap Table Shipping Motor Data is for Operation with Filter, * Factory Wired Cooling Tap ** 2. Data Temp. Rise @ Motor .3"WC °F HP Table suffix - T Furnace SpecificationslAirflow Data Column) 0.5 Recommended A/C 3 2.-I/2 2 5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leak to check all connections. 6. Always install furnace to operate within the furnace's intended temperature rise range with a duct system that has an external static pressure within the allowable range, as specified in page 4 of these instructions. See furnace rating plate. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. Note: This section only applies to furnaces installed with side or top return air. A gas-fired furnace for installation in a residential garage must be installed as specified in page 7 of these instructions. The furnace is not to be used for temporary heat of buildings or structures under construction. WARNmNG: Do not use this appmiance has been submerged mediatemy nician camsa quamified to inspect if any underwater. service the appmiance part Imtech- and to repmace any part of the controm system and any submerged gas controm that has been underwater. 7. NOTICE TO iNSTALLER Installer is advised to follow carefully all instructions and warnings in this manual to insure maximum performance, safety, and operating efficiency of these appliances. Improper installation may create hazardous conditions, and will void the appliance warranty. 8. GENERAL General Description The M3 series gas furnaces are listed direct vent (sealed combustion) forced air furnaces for use with both natural and propane gases. The M3 series is a Category IV and type FSP furnace. The M3 furnace series has been certified to the ANSi Z21.47/CSA2.%2001 for use in the United States and Canada and to the UL307B --1995 for use in the United States. 9. These furnaces may be installed in: I. Manufactured Homes. OWNER 2. Park Models and Manufactured 3. Modular Homes/Buildings buildings The following are safety guidelines with references to their specific sections or pages in the manual. I. 2. 3. 4. Use only type of gas approved for this furnace. Refer to the furnace rating plate. Install this furnace only in location and position as specified in pages 7 - 13 of these instructions. Provide adequate combustion and ventilation air to the furnace space as specified in pages 13 - 20 of these instructions. Combustion products must be discharged outdoors, connect this furnace to an approved vent system only, as specified in pages 14-19 of these instructions. M3 series furnaces are air conditioning ready as shipped. The furnace cooling capacities of the blower motor speed taps are shown in Table 3. Table 2 lists the shipping weights for the M3 series furnaces. NFORMATION NORDYNE has been involved in the design of products for the manufactured home industry since the first manufactured home or trailer was built. NORDYNE originated the sealed combustion system, which separates the furnace combustion system from the living area of the home, now a standard for the manufactured home industry. NORDYNE engineers developed the first central heating system and the first central air conditioner for manufactured homes. NORDYNE is dedicated to bringing to its customers the finest heating and cooling comfort possible. NORDYNE constantly seeks to further refine its products to continuously provide exceptional comfort. Followthe instructionsin this bookletcarefully andthis appliancewill providemanyyearsof superiorperformance. 6. Providinginstructionaltrainingon how to lightandoperatethefurnace. 7. Furnaceproblemscausedbyinstallationof an air conditioner,heatpumpor otherair comfortdevices. if you wish to cool your homeautomatically witha centralair conditioningsysteminvesti- 8. Revisinginstallationof the furnaceflue gatetheexcellentNORDYNEcoolingsystems assembly. availablefromyour heatingand coolingcon- 9. Adjustingor calibratingof thermostat. tractor.Thesesystemsare designedto work 10.Any constructiondebris which falls into best with your NORDYNEfurnaceand have theflue system. beencarefullyengineeredto deliveroptimum performancewhen mated with NORDYNE Carefullyreviewtheseresponsibilities withyour manufacturedhomefurnaces. manufactured housingdealer,servicecompany or gas supplierso therewill be no misunderNORDYNE alsoofferswaterheaters,fireplaces standingat a latertime. and ventilatingsystemsspecificallydesigned for manufactured housingapplications.Check CAUTmON'. with your manufacturedhomeretailer,your heating and cooling contractor or your Never attempt to alter or modify this distributorfor information. Writedirectlyto the furnace or any of its components. factory(POBox8809,O'Fallon,MO63366)if Never attempt to repair damaged or youarenotabletolocatea sourceforNORDYNE inoperable components. Such action manufactured housingproductsin yourarea. could MANUFACTURER WARRANTY,OWNER'S RESPONSIBILITIES it isthesoleresponsibility ofthehomeowner to makecertainthegasfurnacehasbeencorrectly setupandconvertedtotheproperfuel(UP.gas or Naturalgas)andadjustedto operateproperly. All gas furnacesare manufacturedfor Naturalgasandmustbefieldconvertedwhen usingUP.gas. Awarrantycertificate withfulldetailsisincluded with theseinstructions.However,NORDYNE willnotberesponsible foranycostsfoundnecessaryto correctproblemsdue to improper setup,improper installation, furnaceadjustments, improperoperatingprocedureonthepartofthe user, etc. Somespecificexamplesof servicecallswhich cannotbe includedinwarrantypaymentsare: I. Converting thefurnacetouseanothertype ofgas. 2. Repairing ductworkinthehomefoundtobe faulty. 3. Correctingwiringproblemsin theelectrical circuitsupplyingthefurnace. 4. Resettingcircuitbreakers,blownfusesor otherswitches. 5. Correctingproblemsdueto impropergas supplypressuretothefurnace. cause plosion, unsafe fire and/or • If a malfunction you ating operation, has occurred, feel that the furnace as it should, service agency sistance. iNSTALLATiON ex- asphyxiation. contact or gas or if is not opera qualified utility for as- STANDARDS Installer shall be familiar with and comply with all codes and regulations applicable to the installation of these heating appliances and related equipment. In lieu of local codes, the installation shall be in accordance with the current provisions of one or more of the following standards. a. Federal Manufactured Home Constructions & Safety Standard (H.U.D. Title 24, Part 3280.707[a][2]) b. The Standard for Manufactured Home Installations (Manufactured Home Sites, Communities, and Set-Ups) ANSI A225.1 and/or CAN/CSA-2240 MH Series). c. American National Standard (ANS1-119.2/ NFPA-501C) for all recreational vehicle installations. d. American National Standard (ANSI-Z223.1/ NFPA-54) and/or CAN/CGA B149 for all gasfired furnace models. e. American National Standard (ANSI-C1iNFPA70) and/or CSA 22. I Canadian Electric Code Part I for all electrical field wiring. CE gen6rateurd'air chauddoit 6tre installe conformement aux instructionsdu fabricantet auxcodesIocaux.EnI'absencede codelocal, respecterla normeANSIZ223.,I,instituleNationalFuelGasCodeoulescodesd'installation CAN/GCA-B149. The NationalFuelGas Codeis availableby writing: AmericanNationalStandardsinstitute,inc. 1430 Broadway NewYork,NY 10018 NFPApublicationsare availableby writing: NationalFireProtectionAssociation Batterymarch Park Quincy,ME02269 bustible material other than wood flooring. The furnace may be installed on combustible flooring when installed on a Nordyne duct connector (see Table 5). The ductwork within 3 feet of the furnaces without the A/C coil box must be installed such that surfaces are at least I/4" from combustible materials. When installed in a residential garage, the furnace must be positioned so the burners and the source of the ignition are located no less than 18 inches above the floor and protected from physical damage by vehicles. CiRCULATiNG LOCATION WARNmNG: The furnace must be installed on a level suF face, and as close to the center of the air distribution system as possible. See Figure I for overall dimensions to determine the required clearances in hallways, doorways, stairs, etc. to allow the furnace to be moved to the installation point. The furnace must be installed so that all electrical components are protected from water. Minimum clearances to combustible materials are listed in Table 4. Access for positioning and servicing must be considered when locating the unit. This furnace is certified for use on wood flooring. The furnace must be installed on a solid surface and must be level front4o-back and side-to-side. This furnace must not be installed directly on carpeting, tile, or any comALL MODELS Front Back Sides Vent Top Duct (Plenum) w/Coil Box w/o Coil Box (within 3 feet) CLOSET ALCOVE Inches Inches 1" 1" 0 0 0 6 0 0 0 6 0 1/4 0 1/4 *Note: For 1"clearance, use a fullylouvered door with at least 400 square inches of free airflow area. Table 4. Minimum Clearances AiR SUPPLY Products of combustion allowed of to enter the must the return furnace or the not be air openings circulating air supply. Failure to prevent products of combustion from being circulated into the living hazardous space can conditions poisoning monoxide personal The iniury floor furnace physical gaps, furnace create potentially including carbon or that could or death. platform on result which in the is mounted must provide sound support of the furnace with no cracks, or sagging and the floor The circulating be connected between the or platform. air ductwork must not to any other heat producing device insert, stove, etc. such as a fireplace GENERAL Plenums and air ducts must be installed in accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems (NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning Systems (NFPA No. 90B). RETURN AiR PROViSiONS U.S.A. home manufacturers shall comply with aft of the following conditions to have accept= able return air systems for closet installed forced air heating appliances: a. Regardless of the location, the return air opening into the closet shall not be less than specified in the appliance's listing. b. Means shall be provided to prevent inadverb ent closure by a flat object placed over the return air opening when it is located in the floor of the closet (versus the vertical front or side wall). c. Closet installations must use a Iouvered door having a minimum free area of 235 sq. in. when located 6" from furnace. For clear= ance between I" and 6" from furnace, requirements are a Iouvered door with minimum of 235 sq. in. free area, with the open= ings in closet door directly inJine with the Iouvered openings in the furnace door. For I" clearance from furnace, use a fully Iouvered door with at least 400 sq. in. of free airflow area. d. The cross-sectional area of the return duct in the floor or ceiling shall not be less than 235 square inches. e. The total free area of openings in the floor or ceifing registers serving the return air duct system must be at least 352 sq. in. At least one register should be located where it is not likely to be covered by carpeting, boxes and other objects. f. Materials located in the return duct system must have a flame spread classification of 200 or less. This includes a closet door if the furnace is in a closet. g. Noncombustible pans having I" upturned flanges are located beneath openings in a floor duct system. h. Wiring materials located in the return duct system shall conform to Articles 300=22 of the National Electrical Code (ANSI CI/ NFPA=70). 19"_ k Top View system leading into the closet, when located I_13 A Single , trunk I 10 1/4" 1/4'_ I duct Figure If "X" (Floor I I Transition duct C pw/branches _ U U Figure 2. Non=Platinum Supply Duct System English Cavity) Metric 7/8" 2" 4 1/4" 6 1/4" 8 1/4" 10 1/4" 12 1/4" is: I 4. Part Tab Number: Screw 901987 901988 901989 901990 901991 901992 901993 Table 5. Duct Connectors (depth equal to "X" in Figure 5 and Table 5) i, "1 I:/ Connector Model 22 51 108 150 210 260 311 / X "_ (mm I Finger FLOOR CAVITY Z of Duct Use Duct Connector I / Dual trunk duct B w/crossover connector _, SUPPLY AIR DUCT Figure 3. / ( Down 904008 904009 904010 904011 904012 904013 904014 ( )OPENING TO DUCT (1) WITH PLATE (C) REMOVED OPENING BECOMES 13-1/4" x 13-1/4" (2) WITH PLATE (C) REMOVED OPENING BECOMES 13"X 13" WITH REDUCER ITIS 13"X 10-1/8" SPACERS (1) FINGER (2) SCREW m . E • I • I • TAB DUCT CONNECTOR DOWN DUCT CONNECTOR I A X y •- SEE TABLE 5 ONLY ONLY Figure 5. ALTFUEL FUEL HOLE Figure 6. Closet i. Gas piping is not run in or through the return duct system. j. Test the negative pressure in the closet with the air-circulating fan operating at high speed and the closet closed. The negative pressure is to be no more negative than minus 0.05 inch water column. k. For floor return systems, the manufactured home manufacturer shall affix a prominent marking on or near the appliance where it can be easily read when the closet door is open. The marking shall read: HAZARD cover OF ASPHY×IATmON: or restrict return Do not air opening. I. Air conditioning systems may require more duct register and open louver area to ob- or Alcove tain necessary airflow. Use NORDYNE's certiduct program to determine proper duct size for AiC. DUCTED RETURN AIR M3 furnaces with model numbers ending in AW or BW are factory configured for the return air to flow through the front Iouvered door. The return air may also be attached to either side or the top of the furnace cabinet using a field installed kit. Refer toTable 12 for the NORDYNE ducted return kit PiN number. The location and size of the side and top return air connections are shown in Figure I. The filter size for the side return air is 20" x 20" x I". For top return the filter size is 24" x 16" x I". M3 furnaces with model numbers ending in BWT are factory configured for the return air to enter the top of the furnace. I I 2-1/4 FLOOR CUT-OUT FOR DUCT CONNECTIONS 17-29/32 14-1/2 21-3/4 21-7/16 8-19/32 1-3/4 f 3-I14 VENT COMBUSTION AiR INTAKE FUEL LINE ENTRY I 1-1/4 ALT FUEL LINE 1-3/4 12-7/8 ENTRY OUTER DOOR 15-1/2 FLOOR CUT-OUT FOR OPTIONAL COOLING COIL FOR NON-PLATINUM SERIES Figure NR DiSTRiBUTiON 7. Cut-Out SYSTEMS For proper air distribution, the supply duct system must be designed so that the static pressure measured external to the furnace does not exceed the listed static pressure rating shown on the furnace rating plate. Three typical distribution systems are illustrated in Figure 2. Location, size, and number of registers should be selected on the basis of best air distribution and floor plan of the home. UNITS Locations cavity. To maximize air delivery, remove reducer "C" (see Figure 5) to obtain the largest open area that will fit the duct/floor construction. DUCT iNSTALLATiON Required floor, ceiling, and roof cut-out openings must be carefully located to avoid misalignment of the furnace (see Figures 6 & 7). installation procedures are suggested for typical furnace installations and need not be followed in the exact listed sequence. DUCT CONNECTOR PLATINUM SELECTION SERES a. For Platinum ready construction use the 14" round plenum, pin: 903896. NON-PLATINUM SERIES a. Determine depth of floor cavity from surface of floor to top of supply air duct (See Figure 3). b. Select appropriate model from Table 5 which matches X-dimension of the floor I0 CUT OUT FLOOR OPENING HOLE & FUEL LINE a. Determine center of closet or alcove (Figures 7 & 8). b. Locate center of the floor opening, measured 10" from the rear wall, and mark cutout measuring approximately 14-I/2" by 14I/2" (+ I") for model duct connector used (refer to Figures 4 & 5). c. Locate center of gas line hole, measured 23I/4" from the rear wall and 6-5/8" to the left of center of the floor cut-out (See Figure 6) or 5-I/4"totheleftofcenterofthefloorcut-out, or for entry throughright-sideof furnace measured9"totherightofcenterofthefloor cut-out. d. Cutoutflooropeningandonegaslinehole. INSTALLING PLATINUM SERIES 14" ROUNDDUCT CONNECTOR a. Placeductconnectorthroughtheflooropening.(SeeFigure9). b. Secureductconnectorto floor. CUT DUCTOPENING(FINGERTABBED ONLY) a. Placeductconnectorthroughtheflooropening with bottomtabs restingon top of the supplyair duct. b. Centerductconnector andpushbackagainst rearedgeofflooropening. c. Markcut-outlocation(tabarea)andremove duct connector. d. Cutout ductopening1/16"largerthanarea marked. INSTALLINGSCREWDOWNDUCTCONNECTOR a.Applya beadof caulking,mastic,or other approvedsealantaroundbottomsideof I/2" flangeandrestrictorplate,whenapplicable. b. Locatethe duct connectorover duct and carefullylowerscrewdownduct connector intoplace. c. Once duct connectoris locatedon duct, temporarily holdinplacewhilefasteningduct connectorto thefloorusingflatheadscrews or nails.Be sureflangesof ductconnector stayin contactwith the duct. d. Screwplenumto ductmakingsurea sealis madebetweenthe duct andthe duct con- INSTALLFURNACEMOUNTINGPLATE a. Placemountingplate(suppliedwithinduct connector)at rearof theflooropening(See Figure9). MOUNTING REARWALL FUEL LINE HOLES Figure 8. Mounting Plate SCREWS BEND UNDER CONNEC DUCT _OR MOUNTING TABS OPENING CONNECTION Finger Tabbed Duct Connectors Screw Duct Figure Down Connectors Platinum Series 9. Duct Connector 11 nector.Additionalscrewsmay be addedif required. e. Cutawayalongedgeof flangeallowingthe centertodropintotheduct.Removesection ofductwithcaution,asedgeswill besharp. INSTALLINGFINGERTABBEDDUCTCONNECTORS a. Placeductconnectorthroughtheflooropeningwith bottomtabsextendingthroughthe ductopening.(SeeFigure9) b. Secureduct connectorto floor. c. Bendbottomtabsunderanduptightlyagainst the supplyair duct (SeeFigure10). attachedtothesidesoftheductbyusingsheet metalscrewsor othersuitablefasteners.(See Figure11). if sealant,mastic,or tapeis usedto providea betterseal,itshouldbeapprovedbyapplicable nationalor localcodes. ALTERNATEATTACHMENTMETHODS This proceduremay alsobe usedto installa furnace duct connector to narrow metal ductworkwhereinsufficientclearanceprevents bendingof the duct connectortabs at the side(s)of the duct.(SeeFigure12). NOTE:Theductconnectorisdesignedforuse I. Scoreandcutthe top of the metalduct as onducts12"inwidth.Whenusingtheconnec= indicatedin StepI or Step2. WithStep I toron 12"wideducts,theremaybeinsufficient choice,alsocutoutthemetalfromtheshaded clearanceto bendthe tabsontwosidesof the area"A'. ductconnector,insuchcasesthetabsmaybe 2. Foldthe ductflap "B"up,(SeeStep3). TABS TABS DUCT _ DUCT 1. INSERT DUCTPLBNUM CONNECTOR INTO DUCT CUT-OUT. Figure 2. BEND BOTTOM TABS OVER AND ONTO THE UNDERNEATH DUCTBERVtCE. 10. Installation of Duct Connector Duct Connector i_ I _) Figure Duct 11. Narrow _ Duct Narrow Duct Installation STEP 2. STEP 1. Fold Back Flap "B" Fold Back Flap"B" Cut Cut- Out Cut- Out Area"A" Top of Duct -- Fold Back Flap "B" Staple Folded Duct Flap (typ) to side of Duct Connector Bend Duct Connector Tabs Up and Over- (along length of duct) , ,/ // \, "_k_ . , !LtC t _L_ STEP 4. Figure 12 Fold Back Flap"B" 12. Alternate Installation Duct _--'_ NOTE:Additionalfastenersmay be usedat rear,sidesor throughdoorframe,as desired, to securefurnaceto closetor alcoveframing. VENTING AND COMBUSTION AiR CAUTmON'. Snow block Figure 13. "A', "g', & Platinum Cabinet Furnaces must not be allowed to restrict or the combustion air intake or vent pipes. General SLIDE ALL THE ONTO SECURE FURNACE WFH 2 FASTENERS • [, ' ,', AT FRONT CORNER _ q, ' WAY MTG BACK PLATE , HOLES FURNACE , ' HOLES Figure 14. "A" Cabinet Furnace on 911969 Coil Cabinet (NonoPmatinum Series) 3. At the front-to-back of duct run (Area "A'), bend the duct tabs and secure them directly to the duct. 4. At Area "B", bend the duct tabs up and back over, around the duct connector, (See Step 3). 5. Fold/form the duct flap against the side of the duct connector and attach as shown, (See Step 4). Use three (3) staples (minimum) on each duct flap OR, if a 2X block/joist is not provided, use two (2) sheet metal screws (minimum) on each duct flap. An alternate attachment method is acceptable, as long as the plenum is securely attached. 6. Tape the duct flap edges with an approved tape for a leak-free joint. _NSTALL FURNACE a. Remove furnace outer door(s) and bottom fuel line knockout. b. Place furnace onto duct connector and center with floor opening. c. Slide onto mounting plate. (Bottom rear slots on furnace should engage with mounting plate tabs.) d. Secure front with one (1) fastener at each corner (See Figure 13 or 14). NORDYNE condensing furnaces must be installed with outdoor combustion air piped directly to the furnace. Codes refer to this type of installation as direct vent, or two pipe installation. Provisions must be made for adequate supply of air for combustion and ventilation. For United States installations, the adequacy of air provisions can be determined by consulting the current version of the National Fuel Gas Code (ANSI Z223.1iNPFA-54). For Canadian installations, requirements are specified in the National Standard of Canada (CAN/CGA B149.1 & .2). Consult local codes for special requirements. NOTE: If the furnace is operated without adequate air for combustion and ventilation, it may not perform properly. Furnace components may be strained by high temperature and could fail prematurely. G: The combustion blocked air piping or restricted must not be in any manner. WARNmNG: Furnace installation other than those using described methods in the following National sections Fuel must complywith Gas Code and the all applicable sufficient local codes to provide combustion air for the furnace. 13 that there is no blockage striction, leakage, other deficiencies Do not allow nace. tion debris This could and voids to fail into the fur- cause unsafe the furnace opera- cause 3. So all VENTING as building warranty. is practical, FURNACE VENTED MUST WiTH NOT OTHER BE Follow the APPLIANCES. 5. Genera_ Turn in are located instructions. appliance in thermostat operate and space of the building. lighting inspected all connected system spaces the Place COMMON the the appliance(s) and other WARNmNG: close and windows between to the venting 4. and could condition. doors doors which REQUIREMENTS corrosion which an unsafe far or re- being operation. so Adjust appliance shall continuously. on clothes dryers and any This section specifies installation requirements for 2-pipe combustion air piping. The capacity table provided in this section applies to the maximum equivalent lengths of vent and combustion air intake pipe. other appliance not connected to the venting system. Turn on any These condensing furnaces are classified as "Category IV" appliances, which require special venting materials and installation procedures. Category tV appliances operate with positive vent pressure and therefore require vent systems which are thoroughly sealed. They also produce combustion condensate, which is slightly acidic and can cause severe corrosion of ordinary venting materials. Furnace operation can be adversely affected by restrictive vent and combustion air piping. Therefore, vent and combustion air piping lengths must conform completely to the requirements of Table 6. Do not operate fan. exhaust exhausts, shall operate at maximum Close 7. Test for spillage hood opening 8. if improper 1. Seal any 2. venting inspect unused system the venting proper size as required system and horizontal in the National in the for pitch, Fuel Gas Code, ANSI Z223.1 or the CAN/OGA Bt49 mnstallation Codes and these instructions. Determine 14 draft after 5 minutes venting is observed Fuel Gas Code, ANSt Z223.1/NFPA 54 a n d/or CSA B I49.1, Natural Gas and Propane Installation Codes. After it has been determined that return openings hood during any of the above tests, the venting system must be corrected in accordance with the National when HAZARD draft at the of main burner operation. Use the flame of a match or candle. 9. POiSONmNG from appliance appliance venting MONOXmDE speed. exhaust dampers. equipped relief hoods so they a summer fireplace each CARBON as range bathroom 6. The furnace must be vented to the outdoors. WARNmNG: fans, such and fans, other their connected system tested doors, gas properly as fireplace outlined windows, dampers burning previous to the vents above, exhaust and any appliance to conditions of use. It must not be vented in common with any other appliance, even if that appliance is of the condensing type. Common venting can result in severe corrosion of other appliances or their venting and can allow combustion gases to *NOTES 1. Subtract 3.5 ft. for each additional 3" 90 degree elbow. 2. Two45degree elbowsare equivalent toone 90degree elbow 3 One short radius elbow is equivalent to two long radiu,_ elbows. 4. Do not include terrnination elbows incalculation of vent length 5 This table is applicable for elevations from sea levelto 400( ft. Forhigher elevations, decreasevent pipe lengthsby 8% pe 1000 ft. of altitude 6 Only the above pipe materialsare approved for usewith thes( condensing furnaces. MAXIMUM DIRECT VENT, DUAL APPLICATION PIPE LENGTH PVC,CPVC (ft.)* Inlet/Outlet or ABS SCH. 40 Pipe Size Model M3RL 060 3" 3" 50 50 Model M3RL 080 50 50 Tabie 6. Vent Tabie / / / / _J VENT / / TERMINAL (_ AiR SUPPLY INLET [] Canadian Installations AREA WHERE TERMINAL 1 iS NOT PERMITTED US Installations 2 A = Clearance above grade, veranda, porch, deck, or balcony 12 inches (30 cm) 12 inches (30 cm) B = Clearance to window or door that may be opened 6 inches (15 cm)for appliances -< 10,000 Btuh (3 kW), 12 inches (30 cm) for appliances > 10,000 Btuh (3 kW) and -< 100,00 Btuh (30 kW), 36 inches (91 cm) for appliances >100,00 Btuh (30 kW) 6 inches (15 cm)for appliances -<10,000 Btuh (3 kW), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kW) and -< 50,000 Btuh (15 kW), 12 inches (30 cm) fol appliances > 50,000 Btuh (15 kW) C = Clearance to permanently closed window D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61 cm) from the center tine of the terminal E F G H = = = = Clearance Clearance Clearance Clearance to to to to unventilated soffit outside corner inside corner each side of center tine 3 feet (91 cm) within a height 15 feet above the meter/regulator assembly 3 feet (1.83 m) extended above meter/regulator assembly I = Clearance to service regulator vent outlet J = Clearance to nonmechanicaI air supply inlet to building or the combustion air inlet to any other appliance K = Clearance to a mechanical air supply inlet 6 inches (15 cm)for appliances -< 10,000 Btuh (3 kW), 12 inches (30 cm)for appliances > 10,000 Btuh (3 kW) and -< 100,00 Btuh (30 kW), 36 inches (91 cm) for appliances >100,00 Btuh (30 kW) 6 inches (15 cm)for appliances -<10,000 Btuh (3 kW), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kW) and -< 50,000 Btuh (15 kW), 12 inches (30 cm) fol appliances > 50,000 Btuh (15 kW) 6 feet (1.83 m) 3 feet (91 cm) above if within 10 feet (3 m) horizontally L = Clearance above paved sidewatk or paved driveway located on public property 7 feet (2.13 m) 1 M = Clearance under veranda, porch deck, or balcony 12 inches (30 cm) $ 2 In accordance In accordance 1 A vent dwellings _: Permitted * For shall with with not and only the the current current terminate CSA ANSI directly B149.1 Z223.1 above serves both dweltings if veranda, porch, deck, clearances not specified "Clearance in accordance Figure in ANSI with Natural / NFPA Gas and Propane 54 National Fuel a sidewalk or balcony Z223.! or paved is fully / NFPA local installation manufacturer's 15. Vent Termination 54 Installation Gas Code driveway open or CSA on that codes, and installation Clearances is located a minimum B149.1, the Code of two following the requirements instructions." between sides beneath statement of the two gas shall supplier single the family floor. be included: and the for Direct Vent Furnaces 15 escapethroughsuchappliancesor vents. Do not ventthefurnaceto a fireplacechimneyor buildingchase. if removingan existingfurnacein a venting system,theventingsystemmaynotbeproperly sized.Totesttheventsystemwiththeremaining appliances,followthe test outlinedbelow. Combustion The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in The quality of outdoor air must also be considered. Be sure that the combustion air intake is not located near a source of solvent fumes or other chemicals which can cause operation: corrosion Vent Pipe Material Vent and combustion air pipe and fittings must be one of the following materials and must conform to the indicated ANSI/ASTM standards: Piping must be mechanically supported so that its weight does not bear down on the furnace. Supports must be at intervals no greater than five feet, and at smaller intervals if necessary to ensure that there are no sagging sections to trap water (See Figures 16 & 17). Material Schedule 40 PVC PVC-DWV SDR-21 & SDR-26 ABS-DWV Schedule 40 ABS Foam/Cellular Core PVC Standard D1785 D2665 D2241 D2661 F628 F891 Cement and primer must conform to ATSM Standard D2564 for PVC and Standard D2235 for ABS. When joining PVC piping to ABS, use an appropriate solvent cement and procedure per the piping manufacturer's recommendation and ASTM Standard D3138. Vent Pipe Installation Pipe Routing and Support Route piping as directly as possible between the furnace and the outdoors and remember that routing affects pipe length limitations per Table 6. Locate the combustion air intake and the vent exhaust in the same atmospheric pressure zone - i.e. both must exit the building though the same portion of exterior wall or roof. Vent piping must be sloped upwards not less than 1/4" per foot in the direction from the furnace to the terminal. This is to ensure that any condensate flows back to the furnace where it can be disposed of through the condensate disposal system. CAUTmON'. occupied air must spaces not be drawn and from a corrosive atmosphere. of the furnace combustion system. These condensing furnaces have been certified for installation with zero clearance between vent piping and combustible surfaces. However, it is good practice to allow space for convenience in installation and service. Location of Outdoor Terminations Vent and combustion air intake terminations must be located to ensure proper furnace operation and to conform to applicable codes. Figure 15 illustrates necessary distances from the vent termination to windows and building air intakes. In Canada, the Canadian Fue! Gas Code takes precedence over these instructions. Specifically, all minimum distance requirements with respect to term!nation of the vent piping listed below. The following list is a summary of vent terminal location requirements: I. The termination must be 12 inches above snow level or grade level whichever is higher. See Figure 18 for alternate method to achieve 12" above snow level. 2. The minimum distance for a direct vent 3. (2-pipe) installation from any door, openable window, or air gravity inlet is I ft. below, 1 ft. horizontally, or 1 ft. above. The vent termination shall be a minimum of 4. 3 ft. above any forced air inlet within 10 ft. The vent termination shall be located at least 4 ft. horizontally from any electric meter, gas meter, regulator and any relief equipment. These distances apply ONLY to U.S. installations, in Canada, the Canadian Fuel Gas Code takes precedence. 16 Downflow Furnace Vent _ _!3 9/1E"_ ÷i Combustion Al ,oto,oO,po l Seal/Cat_lk Around Pipe at Building I_ \ \ _ Supports at Minimum of 5 ft. Intervals Straps or Other Suitable \ \ 90 ° Elbow 7,8 i i \ \ \ _ _-_j _ ___Z \ ' \ Top View Offset iq with Vent for Adequate Dirnensiona_ C}eara#ce Exhaust Vent PVC or ABS pipe f Normal Snow Combustion Level Intake Figure Air Pipe 16. Horizontal Venting Support System on Vertical Rise Below Joints First support close ¢//_ should to furnace Vent be as es possible Vent Upward Pitch t/4" per foot Figure . 17. Vertical Avoid areas where condensate drainage may cause problems by dropping on plant_ ers or patios, etc. Also ensure that ex_ haust gases will not impinge on windows or building surfaces, which may be com_ promised or damaged by condensation. Do not install the vent terminal such that exhaust is directed into window wells, stairwells, under decks or into alcoves or similar recessed areas, and do not terminate above any public walkways. 6. Venting Select the point of wall penetration where the minimum I/4 inch per foot of slope up can be maintained. CAUTmON'. For optimal performance vent furnace through wall which experiences the least exposure to winter winds. 17 Horizontal Venting Vent and combustion air intake terminations must be as shown in Figure 19 unless the concentric vent termination kit is used. NG: Ensure the that the combustion exhaust shown in termination vent Fig. t9. can cause the flue gases. vibration, are configured Improper recirculation cases, If you note these oscillations check the vent configuration. that the exhaust vent does degree vent of in furnace contact sensor. occurring, Make sure not have a 90 termination. For horizontal venting, either the Horizontal Exterior Vent Mounting Kit or the Concentric Vent Termination Kit may be used (See Table 12). For Canadian installations please refer to the Canadian Installation Code (CAN/CGA-B149.1 or 2) and/or local codes. The HorizontaJ Exterior Vent Mounting Kit consists of two face plates and an insulating gasket to seal the exterior surface. A hole sized closely to the pipe diameter must first be cut through the wall. A short length of pipe is then cut such that it can penetrate the wall and be held in place by closely fitting standard couplings. The face plates are retained on both sides of the waJJ by the couplings, and the gasket is retained against the wail by the outer face plate. Face plates must be fastened to the walJ and the outside one must be flashed as appropriate to prevent entry of water. When the above kits are not used the following steps are required: I. Check the hole size cut through the exterior wall. Insure that the hole diameter is less than the diameter of the couplings to be used. 18 Extend the vent pipe through the wall approximately I" and seal the area between the wall and pipe. Apply couplings to the vent pipe on the interior and exterior sides of the wall to insure the pipe can not be pushed or pulled through the wall. Insure the combustion air inlet pipe has a 90 degree termination elbow, and is pointing downward as shown in Figures 19 & 20. as the furnace will cycle, due to the intermittent between the flame and the flame 3. 4. air vent and This may result in severe 2. Note that a combustion air intake must be provided with an elbow opening downward. When the vent pipe must exit an exterior wall close to the grade or expected snow level, a riser should be provided as shown in Figure 18. Insulation is required to prevent freezing of this section of pipe. Vertical Venting For verticaJ venting, either the configuration shown in Figure 20 or the Concentric Vent Termination Kit may be used. Vertical venting is one of the shortest routing methods when piping vents for furnaces. The M3 furnace operates trouble-free when the furnace is installed with a shorter vent. o The inlet for the combustion intake pipe must be extended at least one foot above the roofline or snow accumulation level. o The outlet of the vent must be extended at least 10 inches above the inlet of the combustion air intake pipe. , The vent as well as the combustion air intake pipe should be located on the same side of the reel Both pipes must not be closer than 5 inches apart. They should not be separated more than 36 inches. The roof penetration must be properly flashed and waterproofed with a plumbing roof boot or equivalent flashing. Termination spacing requirements from the roof and from each other must be per Figure 20. Concentric Vent Terminatien A concentric vent termination is approved for use with these furnaces (See Table 12). For proper installation of the concentric vent termination, follow the installation instructions provided with the kit. Vent Configuration to Provide 12" Minimum height above Snow Level. <7_ Exhaust \ Vent 12" Min. i Outside _ Support WaEI 12"Above _J i_ I NormaHy Expected Snow 1/2" 19" Nax. // /_ Armaflex f/ 4 S _ Bnsulation or , Level :_ Equivalent '_............................... _ (if required) Figure 18. A_ternate Horizontam Vent Installation Figure 19. DRAINAGE OF CONDENSATE FROM FURNACE Do not install additional condensate drain. The condensate produced by the furnace must be drained. Do not connect awater to the drainage hose of the NOTE: The condensate drain should be protected from freezing when in unheated spaces. The furnace is supplied with an internal condensate drain trap. A= 12" Above Roof or Snow Accumulation Air CAUTION'. NG: suppmy furnace. Exhaust and Combustion Pipe Clearances traps in the The condensate drain may exit through the left side panel, the right side panel, or through the left or right hole on the bottom panel. (See Figure 21). Ensure that the flexible drain hose is not kinked. The condensate should drain from the plastic collector box (location A in Figure 21) as droplets or a small stream. If you notice the furnace has operated for more than 5 minutes without draining or the red status light on the control board is pulsing a 2-blink code follow the steps below. s-Min. 36" l*_ax. Note: If terminations Level meet- ing these vertical requirements exceed the maximum Elbow height for safe transit, the vent and combustion air intakes may be shipped with the home for assembly on site. The furnace must be Bxheust Plumbing Vent Roof Boot labeled to notify the installer/ user not to use the furnace until the vent and combustion air intake terminations are installed. (Typ. Both Pipes) Figure 20. Vertical Vent Termination 19 direction Figure I. Remove 21. Furnace the collector with Condensate box soft tube at location A in Figure 21 and insure the exit from the collector box is clear of any debris or obstructions. 2. 3. Replace this tube and insure the fit to the header spout is air tight. Airwill be drawn into the header if this connection is not tight. Check other tube connections along the drain system, insure that all are air tight. NOTE: Industry research studies indicate that when condensate is routed to an active drain, household detergents, etc., buffer its acidity. If the drain is not actively used or if codes require, obtain a neutralizer kit (See Table 12). Proper drains and connections to the condensate tub= Drain Trap Assembty readily accessible for service and/or emer= gency use. Consult the local utility or gas supplier for additional requirements regarding placement of the manual main gas shut=off. In the absence of local codes, the gas line instal= lation must comply with the provisions stated in the Federal Manufactured Home Standard (H.U.D Title 24, part 280) and the National Fuel Gas Code (ANSI Z223.1!NFPA=54) or (CAN/ CGA B149) installation codes. A drip leg should be installed in the vertical pipe run to the unit. Table 7 lists gas flow capacities for standard pipe sizes as a function of length in typical applications based on nominal pres= sure drop in the line. ing are required as NORDYNE cannot be held responsible for water leakage which occurs due to loose hose connections or improperly sealed drain line pipes. NOTE: Gas piping must not be run in or through air ducts, gas vents, etc. GAS SUPPLY Compounds used on threaded joints of gas piping must be resistant to the actions of Iique= fled petroleum gases. AND PiPiNG General This furnace is equipped for bottom, left, or right side gas entry. Typical gas service hook= ups are shown in Figure 22. When making the gas connection provide clearance between the gas supply line and the entry hole in the furnace casing to avoid unwanted noise and/or damage to the furnace. All gas piping must be installed in compliance with local codes and utility regulations. Some local regulations require the installation of a manual main shut=offvalve and ground joint union exter= hal to the furnace. The shut=off valve should be 2O CAUTmON'. Do not use matches, lighters, or other sources of open flame for gas candles, to check leaks. NOTE: When pressure testing gas supply lines at pressures greater than I/2 psig (14 in. water column), the furnace must be disconnected from the gas supply piping system to prevent damage to the gas control valve. CONVERSION This furnace can be converted from the fac= tory=equipped gas to either natural gas (for LP gas ready models), or LP gas (for natural gas ready models). Conversions must be made by qualified service personnel, using only factory authorized or approved parts. The required conversion orifices are supplied with the fur= Main nace. 0/ / WARNING: \ NOT REMOVE ORIGINAL DO RATING / J !° OR DEFACE THE PLATE. / Floor CAUTION'. The gas suppmy shammbe shut off prior to disconnecting before the proceeding emectricam power, with the conversion. To Gas Supply To Turn Off Fuel Supply Figure 22. Typical Gas Piping I. If the test pressure is less than or equal to I/2 psig (14 in. water column), the furnace must be isolated from the gas supply line by closing the manual shut=off valve. 2. Leak Check 4. After the gas piping to the furnace is complete, all connections must be tested for gas leaks. To check for leaks use only a soap and water solu= tion or other approved method. 3. 5. Set the room thermostat to "OFF" or its lowest temperature setting. Turn OFF the main gas supply to the appli= ance at the manual valve, outside of the appliance casing. Remove the control access panel / Iou= vered door. Move the appliance gasvalve lever/knob to the "OFF" position. Turn OFF the electrical power to the appliance. CAPACITY High Altitude Derate The nameplate input rating for the furnaces apply for elevations up to 4,000 feet above sea level for US and Canada. If the elevation for the furnace location is higher than 4,000 feet above sea level, the furnace input must be derated by using the appropriate orifice size listed in Table 8. NOTE: The density of air decreases with increasing elevation above sea level. This re= duces the quantity of combustion air drawn into the furnace under normal operation and requires the unit be derated by using smaller gas orifices or lower manifold pressure. to the Appliance: OF BLACK FOR NATURAL IRON GAS PIPE GAS (SPECIFIC NOMINAL BLACK (CU. FT, PER HOUR) GRAVITY LENGTH IRON OF PiPE -0.60) RUN (feet) PIPE DIAMETER (in.) 10 20 30 40 50 60 70 80 1/2 130 90 75 65 55 50 45 40 3/4 280 190 150 130 115 105 95 90 1 520 350 285 245 215 195 180 170 1 1/4 1050 730 590 500 440 400 370 350 1 1/2 1600 1100 890 760 670 610 560 530 The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas flow required by the furnace To determine the cubicfeet per hourofgas fie \ _vrequired by the furnace, divide the input rate of the furnace by the heating value of the gas: Cubic Feet Per Hour Required -- hputTo Furnace_ Heating Value of Gas (Btu/Cu. Ft.) Table 7. Capacity of BJack mron Gas Pipe (cu. ft. per hour) for Natural Gas (specific gravity = .60) 21 To Removethe Burner Assembly: I. 2. 3. 4. 5. 6. 7. 8. Followthe instructions"To Turn Off the FuelSupplyto the Appliance." Disconnecttheflamesensorwirefromthe burnerbox. Disconnectthe ignitorwiresat the 2 pin plug.Thisis a lockingquickconnectand bothsidesof the lowersectionmustbe depressedin orderto be separated. Removethe wiresfrom the terminalsof the gas valve. Disconnectthe rubber pressuretubes fromthe gasvalveandthe burnerbox. Removethe burneraccesscover plate from the burnerbox. Removesupplygas pipingfromthe gas valve. Carefullyremovethe burnerassemblyfastenersand removethe burnerassembly fromtheappliance.Keepthefasteners that wereremoved.Notethattheburnerboxmay havehooksnearthetopandontherightand lefthandsides.Toremove thistypeofburner box,lift the burnerbox upwardsandthen removetheboxfromtheunit. CAUTmON'. Caution: If the changed, use only Furnace Plate Rating Input (Btuh) Elevation No. of orifice the size burner must be new orifices. that will be installed into the unit will depend upon the type of conversion (sea level or Hgh altitude; natural gas or LP gas}. To Convert the Unit to the Alternate Gas I. Remove the orifice bag from the manifold of the unit. 2. Install the appropriate gas burner orifices into the gas manifold. Remember if installing at altitudes above 4,000 feet to install the proper orifices, shown in Table 8. When installing the new orifices, DO NOT use pipe joint compound on the orifice threads. Screw the orifices into the manifold by hand until snug to eliminate cross threading, then tighten with a wrench. Before installing an orifice, check the face or side of the orifice for the drill number to ensure that it is the appropriate size. For the conversion to the alternate fuel, the gas valve regulator cap must be turned over, as shown in Figure 23. You will unscrew the cap and reinstall for your in= stallation. After reinstalling the cap, you will be able to read "NAT" for the conversion to 3. natural gas or"LP for the conversion gas. Elevation 2000-4000 0 - 2000 re-drill Note: The size of the new orifices I. Furnace Model Number M3RL - not orifices. To Removethe Burner Orifices: Removethefour(4)fastenersthatsecure the gas manifoldto the burnerbox, as shownin Figure25. Carefullyremovethe gas manifoldassemblyfrom the burner box. Notethatthegasmanifoldassembly consistsofthegasvalve,thegasmanifold, andtheorifices. 2. Carefully removetheburnerorificesfromthe gas manifold,as shownin Figure25. Do Elevation 4000-6000 Elevation 6000-8000 to LP Elevation 8000-10000 Burners Nat LP Nat LP Nat LP Nat LP Nat LP 060A-A/BW 60,000 4 50 57 50 57 51 58 51 58 52 59 080A-A/BW 80,000 5 49 1.15 mm 49 1.15 mm 50 57 50 57 51 58 Table 8. Approximate 22 Orifice Size for Natural and LP Gases Reinstalling I. the Burner Assembly: Reinstal[ the gas manifold assembly to the burner box with the four (4) fasteners, which were removed earlier. 2. Carefully reinstall the burner box into the unit. After installing the burner, inspect the alignment of the burners with the heat exchanger tubes. The center of the burners should be aligned with the center of the tubes. 3. 4. Reconnect the gas piping to the gas valve. Reconnectthewirestothegasvalve terminals. Reconnect the rubber pressure tubes to the gas valve and the burner box. Reinstall the burner access cover plate. Reconnect the ignitor at the 2 position plug. Reconnect the flame sensor wire to the burner box. 5. 6. 7. Pressure Gauge Hoooywo, Valve PRESSURE OTHER SIDE OF CAP REGULATOR Figure 23. Convertible Pressure Regulator Cap installation NOTE: For natural gas installations, the incoming gas line pressure at the gas valve inlet must be between 4.5" WC and 10.0" WC. For Figure LP gas installations, the incoming gas line pressure at the gas valve inlet must be between 11.0" WC and 14.0" WC. This pressure can be checked at the inlet end of the gas valve using a pressure gauge or U-tube manometer, which must be installed according to the manufacturer's supplied instructions. LiGHTiNG AND ADJUSTMENT 24. Burner Inspection OF THE APPLIANCE I. 2. 3. 4. Turn ON the gas at the manual valve, outside of the unit. Check all gas connections for leaks with a soap and water solution. If the solution bubbles there is a gas leak which must be corrected. Do NOT use an open flame to check for gas leaks. Turn ON the electrical power to the appD ance. Move the gas valve lever/knob to the "ON" position. The lever/knob must be moved to the end of its range of motion to insure the valve is completely open. Use only your hand to push in or turn the gas control valve. Never use tools. Burner inlet Box Pressure Tap inlet Gas Valve Cover Plate Figure 25. Typical Installation For Sealed Burner Box With Access Cover Plate 5. 6. Set the room thermostat to a point above room temperature to begin the heating cycle of the unit. Check that the unit ignites and operates properly. Refer to the installation instructions provided with your unit for the normal operating sequence. 23 7. Aftertheflameignites,visuallyinspectthe burnerassemblyto ensurethatthe flame isdrawndirectlyintothecenteroftheheat exchangertube,as shownin Figure23. The end of the flamewill be out of sight aroundthe bend of the heat exchanger tube. Ina properlyadjustedburnerassembly, the flamecolor shouldbe blue with somelightyellowstreaksnearthe outer portionsoftheflame. NOTE: Until all of the air is bled out of the gas line, the hot surface ignitor may not ignite the gas. If the ignition control locks out, turn the thermostat to its lowest setting and wait one minute then turn the thermostat to a point above room temperature and the ignitor will try again to ignite the main burners. This process may have to be repeated several times before the burners will ignite. Once the burners are lit, check all gas connections for leaks again with the soap and water solution. If the solution bubbles there is a gas leak which must be corrected. Do not use an open flame to check for gas leaks. Manifold Pressure The gas valve for the M3 furnace series is equipped with a special conversion pressure regulator cap. The pressure regulator cap is factory set. If the gas valve is converted from natural gas to propane gas or vise versa, the manifold pressure of the gas valve will be set to pressure listed in Table 9. Type of Fuel Manifold 24 avoid electric injury, or death, the disconnect panel before connections. ELECTRICAL shock, personal turn off the power at or the main service making any electrical WIRING Genera! Electrical connections must be made in accoF dance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/NFPA 70). For Canadian installations electrical connec- tions and grounding must be done in accoF dance with the current Canadian Electrical Code (CSA C22.1 Part 1) and/or local codes. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wire having a minimum temperature rating of I05°C. Refer to the furnace nameplate and Table 8 for electrical requirements. Line Voltage Wiring The line voltage (115 volt) to the furnace must be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the furnace. See Table 10. An electrical switch should be readily accessible from and within sight of the furnace. See the Wiring Diagram label in the furnace for more details. 3.5 The furnace Propane (LP) Gas: 10.0 rupted, unbroken ground to minimize injury should an electrical fault condition occur. The COMPLETING 2. To Natural Gas: Table 9. Manifold I. Pressure In.WC CAUTmON'. THE Pressure CONVERSION Affix the gas valve conversion label found in the package with the orifices to the unit rating plate. Run the appliance through a complete cycle to assure proper operation. cabinet must have an uninteF controls used in this furnace require an earth ground to operate properly. Acceptable methods for grounding are electrical wire or conduit approved for electrical ground service. Do not use gas piping as an electrical ground. NOTE: Proper line voltage polarity must be maintained in order for the control system to operate correctly. Verify that the incoming neu- tral lineis connectedto thewhitewireandthe incoming"hot"line is connectedto the black wireinthefurnacejunctionbox.Thefurnacewill not operateunless polarityand groundare properlyconnected.See Figure26. Label all wires prior Low Voltage Wiring install the thermostat per the manufacturer's instructions. The low voltage (24 volt) connec= tions from the thermostat are made at the terminal strip on the control board in the furnace. See Figure 28 for the proper connections for heating only (two=wire) and heating/cooling (four=wire) applications. The recommended minimum wire gauge for thermostat wiring is shown in Table 10. to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. c::_::_ C=_] © 24 V _ BowerOff Til/mg TWIN _1®1 o1®1 _1®=_ Lors des operations d'entretien des tousles Toute files erreur commandes, _tiqueter avant des les d_connecter. de c_blage danger peut _tre une source de et de panne. S'assurer du bon l'appareil apr_s fonctionnement de tout entretien. Figure 27. Blower Speed Tap Location Furnace Cabinet Nominal Maximum Minimum Maximum Minimum Maximum Input (Btuh) Width (in.) Electrical Supply Operating Voltage Operating Voltage Furnace Amperes Wire Gauge Fuse or Circuit Breaker Amps* 60,000 19.75 115-60-1 127 103 9.7 14 15 80,000 19.75 115-60-1 127 103 9.7 14 15 Recommended Thermostat Wire Gauge Thermostat L 2-wire (heating) 24 22 20 55 ft. 90 ft. 140 ft. 225 ft. 18 Wire Length 4 or 5-wire (cooling) 25 ft. 45 ft. 70 ft. 1t0 ft. * Time-delay fuses or HACR-type circuit breakers are required, Table F_/IS ;PerPvliied e 10. Electricam Data p aFnieel' d Snupp/iteodr Panel _ WhltB2aNk_tH_rOtl)_ Black Green_orB_a_rE_ ...... (Ground) _....... _ _ .... _ Black _ ....... _ _ _-] Black ._Ll_',' I _ I I ..... Field Line Voltage Wiring __ Factory Voltage Line Wiring = Ground Ground / Ground Field Supplied Disconnect Within Sight of Furnace Figure 26. Line Voltage Junction Box (may be internal or external to the furnace). These connections can be made in the field supplied disconnect at the furnace. Field Wiring 25 The thermostatmust not be installedon an outsidewaft or any other locationwhere its operationmaybe adverselyaffected.Adverse affectsincluderadiantloadingfromfireplaces, sunlight,or lightingfixtures,and convective loadingfrom warm air registersor electrical appliances. C°"dens'°gun't !- Condensing F i oo E i E::::_::_ Connect R&W For ' C_=M _ 24=V O Blower Off Fuse 3 Amp Room Thermostat NOTB:The "'Y" terminal on the UTEC control board must be connected to the thermostat for proper cooling mode operation. 2. Measurethecurrentflowonthethermostat R-Wcircuitafterthecirculating blowermotor hasstarted. _::= Ventilation must be provided for homes built to HUD Manufactured Homes Safety and Con= struction Standards. This ventilation can be sup= plied by the VentiiAire Ill or VentilAire iV accessories. (See Table 12). Alternate means to pro= vide the ventilation air must meet the requirements of all applicable local and federal codes. (Red) I _ C _ Neutrals Unused Motor . The line voltage power leads are securely connected, that the polarity of the con= nections is correct, and that the furnace is properly grounded. 2. . 26 The thermostat wires (R, W, Y, and G) are securely connected to the correct leads on the terminal strip of the circuit board. The natural gas line service pressure must not exceed 10.0 in. water column (0.36 psig), and must not be less than 4.5 in. water column (0.16 psig). For LP gas the line service pressure must not exceed 14 in. water column (0.51 psig), and must not be less than 11.0 in. W.C. (0.40 psig). m The roll-out and vent safety manual reset switches are closed. If necessary, press the red button to reset a switch. See Figure 26 for location. DO NOT install a jumper wire across a switch to defeat its function. If a switch reopens on start-up, DO NOT reset the switch without identifying and correcting the fault condition which caused the switch to trip. 5. The blower door is in place, closing the door switch in the line voltage circuit. 6. The gas line has been purged connections are leak tight. Prior to start=up, verify that: I. o Figure 28. Low Voltage Field, Four=wire Heating/Cooling Applications AND ADJUSTMENTS General Leads DD_DDD_ For installation of the VentiiAire Ill or IV, follow the instructions provided with the VentilAire kit. START-UP TWIN Status Light 0 u: VENTiLATiON Timing Only Addthe currentdrawof the systemcomponents;or Setthe heatanticipatoraccordingto the thermostat manufacturer'sinstructionsfor heat anticipatorsettings. e_ F,ame Bignal Light 0 (Yellow) Heating To checkthe heatanticipatorsettingeither: I. Unit Start-Up Procedure I. Set the thermostat and all to the lowest setting. 2. Close the disconnect(s) voltage to the furnace. to provide line 3. Follow the procedures given on the operating instructions label attached to the furnace. 4. Set the thermostat above room temperature and verify the sequence of operation. (See the SEQUENCE OF OPERATION.) . After the furnace has run for approximately five minutes, set the thermostat below room temperature and verify steps 9 - 11 of the SEQUENCE OF OPERATION. 6. See the "High Altitude Derate" section for additional information on firing rate at elevations above 4,000 ft. Shut Down Procedure The gas valve regulator is set at a nominal value of 3.5 in. water column for use with natural in the event that the furnace must be shut down, follow this procedure: gas. The manifold pressure must be set at I 0.0 in. water column for use with LP gas. I. Set the room thermostat lowest temperature 2. to "OFF" or its setting. Turn OFF the main gas supply to the appliance at the manual valve outside of the appliance casing. 3. . 5. Remove the control access panel / Iouvered door. Move the appliance gas valve lever/knob to the "OFF" position. Turn OFF appliance. the electrical power to the Verifying Firing Rate The firing rate must be verified for each installation to prevent over-firing the furnace. NOTE: The firing rate must not exceed the rate shown on the furnace rating plate. At altitudes above 4000 ft. it must not exceed that on the rating plate mess 4% for each 1000 ft. Use the following procedure firing rate: to determine the I. Shut off all other gas fired appliances. 2. Start the furnace and allow it to run for at least three minutes. . Measure the time (in seconds) required for the gas meter to complete one revolution. 4. Convert the time per revolution to cubic feet of gas per hour using Table 11. 5. Multiply the gas flow rate in cubic feet per hour by the heating value of the gas in Btu per cubic foot to obtain the firing rate in Btuh. Example: o Time for I revolution of a gas meter with a I cubic foot dial = 60 seconds. o o From Table 11 read 60 cubic feet per hour of gas. Heating value of the gas (obtained from gas supplier) = 1000 Btu per cubic foot. , Fidng rate = I000 x 60 = 60,000 Btuh. Verifying and Adjusting Temperature Rise Verify that the temperature rise through the furnace is within the range specified on the furnace rating plate. Temperature rises outside the specified range could result in premature heat exchanger failure. Place thermometers in the return and supply air stream as close to the furnace as possible. The thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings. Adjust all registers and duct dampers to the desired position and run the furnace for fifteen minutes before taking any temperature readings. The temperature rise is the difference between the supply and return air temperatures. For typical duct systems, the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting. If the temperature rise measured is outside the range specified, it may be necessary to change the blower speed. Lower blower speeds will increase the temperature rise and higher blower speeds will decrease the temperature rise. The furnace is equipped with a multispeed motor. Heating and cooling speed selection is made by moving the leads on the integrated control board located in the furnace. The wiring diagram on the furnace and Figure 30 show the speed taps for adjusting motor speed. If it is desired that the blower operate at the same speed for heating and cooling, tape off the terminal of the unused blower wire. Install the jumper wire, found in the plastic instruction bag, across the HEAT and COOL taps on the control board. Reconnect the desired blower tap to the piggyback quick connect. The blower control is designed to start the circulating air blower 30 seconds after the gas valve is opened. The blower control is factory wired to turn the blower motor off 120 seconds 27 GAS FLOW RATE (CUBIC FEET PER HOUR) TIME FOR ONE REVOLUTION (SECONDSI 24 26 28 3O CUBIC FEET PER REVOLUTION OF METER 1 5 10 150 750 1500 138 692 1385 129 643 1286 120 600 1200 TIME FOR ONE REVOLUTION J (sEcONDs) 8O 82 84 86 CUBIC FEET PER REVOLUTION METER OF 1 45 44 43 42 5 225 220 214 209 10 450 439 429 419 32 34 36 38 4O 113 106 100 95 90 563 529 500 474 450 1125 1059 1000 947 900 88 9O 92 94 96 41 40 39 38 38 205 200 196 191 188 409 400 391 383 375 42 44 46 48 5O 86 82 78 75 72 429 409 391 375 360 857 818 783 750 720 98 100 37 36 35 35 34 184 180 176 173 170 367 360 353 346 340 52 54 56 58 6O 69 67 64 62 60 346 333 321 310 300 692 667 643 621 600 33 33 32 32 31 167 164 161 158 155 333 327 321 316 310 62 64 58 56 290 281 581 563 31 3O 153 150 305 300 102 104 106 108 110 112 114 116 118 120 Table 11. Gas Flow Rate after the gas valve is dosed. This timing can be changed using the BLOWER OFF timing switch opposite the terminal block on the control board (See Figure 27). Verifying Burner Operation To verify operation of the burners, remove front door and ensure that the door switch is in the "on" position (see Figure 29). Set the thermostat above room temperature and observe the ignition sequence. The flame can be observed through the small clearwindow on the burner box. The burner flame should carry over between all burners. The flames should be blue, without yellow tips. Flames should extend from each burner without lifting, curling, or floating. After verifying ignition, set the thermostat below room temperature and verify that the burner flame extinguishes completely. Replace the front door. Verifying Operation Limit Switch of the Supply Air To verify operation of the supply air limit switch, make sure that the blower door is in place and that there is power to the furnace. Completely block the return airflow to the furnace by install= ing a close=off plate in place of or upstream of the filter(s). Set the thermostat above room 28 temperature and verify that the Sequence of Operation is as described in these instructions. The supply air limit switch should function to turn off the gas valve within approximately five minutes. The circulating air and combustion blowers should continue to run when the supply air limit switch opens. Remove the close=off plate immediately after the supply air limit switch opens. If the furnace operates for more than five minutes with no return air, set the thermostat below room temperature, shut off the power to the furnace, and replace the supply air limit switch. DESCRiPTiON OF COMPONENTS Figure 29 shows the location of each of the functional components described below. If any component of the furnace must be replaced, use only factory authorized replacement parts. Contact your distributor for the approved re= placement parts. Flame Sensor - The flame sensor acts to prove that flame has carried over from the ignitor to the opposite end burner. If no flame is sensed, the furnace will be shut down automati= cally. FURNACE ACCESSORY Kit A/C KtTS Order Coil Box Side Number 911969A Return Air Kit 904003 904015 Top Return Air Kit Roof VentilAire Ill Kit 914098 Sloped Roof VentilAire Soffit VentilAire Kit IV Kit 914229 Sloped Concentric Vent Termination (for horizontal and vertical Horizontal Exterior Vent MAINTENANCE It is recommended WARNmNG'. 917201 Kit 903578 To avoid 902375 or death, disconnect ventin,q) Mounting Kit 3"PVC Neutralizer Kit - All Models Table 12. Accessory 902377 that the furnace be checked yearly. At a minimum, this check should include the following items: electric before shock, personal turn off the or the main performing any power service injury, at the panel maintenance. Kits Gas Vamve - The gas valve controls the flow of gas to the burners. When the gas valve is energized it automatically opens and regulates the gas pressure in the manifold. Pressure Switch - The pressure switch vealties that the inducer is drawing the combustion gases through the heat exchanger. It alsosenses a blocked condensate drain condition. WARNING: Holes in the vent pipe or heat exchanger can cause products of combustion to enter the occupied space. vent pipe or heat exchanger found. Failure to prevent products of combustion from being circulated into the occupied Deck Limit Switch (Auxiliary Limit) - The deck limit protects the furnace filter temperature from overheating when the motor has malfunctioned. If the deck switch opens, the power for the furnace will shut down (see Figure 29). Supply Air Limit Switch - The supply air limit switch prevents the air temperature leaving the furnace from exceeding the maximum outlet air temperature. Vent Safety Switch - The vent safety switch shuts the furnace down if the outlet flue gas temperature increases above 145°F. This switch protects the plastic flue system and the inducer from over-temperature conditions. Flame Roll-Out Switch - This switch provides flame roll-out protection to the furnace and combustion air inlet pipe. Replace the if leaks are space tially hazardous carbon monoxide result in personal can crate conditions, poisoning, injury poten- including that could or death. Combustion Air and Vent System Check the combustion air and vent pipe to ensure that it is not damaged, corroded or blocked by debris. Any damaged section of vent pipe must be replaced, and any obstruction or blockage must be removed prior to operating the furnace. Air Filter An air filter is supplied with the furnace as shipped from the factory. Filters should be changed or cleaned monthly during the heating season. New or newly renovated homes may require more frequent changing until the construction dust has been removed. 29 Do not store gasoline or any other flammable vapors and liquids in the vicinity of the furnace. Never operate the furnace without a Change or replace the air filters monthly during any period when the circulating blower is operating regularly. filter Jn pmace. Dust and mintJn the return air can nents, buJmd up on Jntemam comporesumtJng equipment Jn moss of efficiency, damage, and possJbme fire. Always replace the doors on the furnace after servicing. Do not operate the furnace Lubrication without The bearings in the circulating air blower motors are prequbdcated and sealed at the factory. No further oiling of the bearings is required for the life of the motor. Avoid operating the furnace when windows and doors are open. Condensate Drain AssemMy Be sure the condensate lines are free and open (i.e. avoid kinking hoses). Also make sure all hose clamps are tight to avoid drawing air into the system. Blower Compartment The blower compartment should be cleaned monthly during the heating and cooling seasons to remove any dirt and lint that may have accumulated in the compartment or on the blower and motor. Dirt and lint can create excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life. Heat Exchanger and Burner Maintenance The furnace should operate for many years without excessive soot buildup in the flue passageways, however, the flue passageways, the vent system, and the burners should be inspected and cleaned (if required) by a qualified service technician annually to ensure continued safe operation. Particular attention must be given to identify deterioration from corrosion or other sources. SYSTEM OPERATION iNFORMATiON GENERAL Proper maintenance is most important to achieve the best performance from a furnace. Follow these instructions for years of safe, trouble free operation. o Do not place combustible materials on or against the furnace cabinet or the vent pipe. 3O all doors and covers in place. Be sure that the thermostat is propermy installed and is not being affected by drafts or heat from mamps or other appliances. Sequence of Operation Operating sequences for the heating, cooling, and fan modes are described below. Refer to the wiring diagrams (Figures 30) and the low voltage field wiring diagram (Figure 26) for more details. Heating Mode: I. On a call for heat the thermostat closes, applying 24 VAC to the W terminal on the control board. 2. 3. The control board checks on the 24 VAC limit control temperature limit switch, switches and blocked vent for continuity circuit (overflame rollout switch in se- ries). If an open limit is detected the control board will energize the inducer and the conditioned air blower. All other system functions win be inoperable until the limit circuit closes. While the limit is open, the red LED will pulse at a rate of I blink per unit time. The furnace control checks for continuity across the pressure switch (24 VAC). If the pressure switch is closed the heat mode sequence will not continue. If it remains closed for 10 seconds the red LED will blink 3 times repetitively fault condition clears. until the 4. The inducer is energized. 5. The pressure switch win close. If the pressure switch does not close after 10 seconds the fault LED will blink 2 times repetitively and the inducer will continue to run until the switch is closed. 6. The inducer will pre-purge for 30 seconds and then the igniter will start its warm-up as follows: InitialPowerup:After30secondsofigniter warm-upthegasvalve(24VAC)will then open. The igniter circuitwill stay energized for 3 secondsafter the gas valve opens. After InitialPowerup: The controlhas a programmedadaptive ignition feature which variesthe warm-upperiodas follows:Ifignitionissuccessful thewarm-upis reducedby3-seconds oneachsubsequent call for heat until ignitionfailure occurs. Uponignitionfailure,the warm-upis increasedby 3-secondson the nexttry. If successful,thetimingremainsfixedatthis level.Ingeneral,wheneverignitionfailure occursthewarm-upintervalisincreasedby 3-secondsonthe nexttry.Andifsuccessful, it remainsthere.Minimumandmaximumwarm-uptimelimitsareset at6 and 54-seconds, respectively. 7. Thefurnacecontrolmustproveflamevia the flamesensor5 secondsafterthe gas valveopens.If flameis sensed,all burners areon andthe ignitorcoolsoff. If no flame is sensed,the gas valve closes immediatelyandthe inducercontinuesto run. A secondtrial for ignition(step 6) beginsif noflameis sensed.Onthefifth tryforignition,thefurnacecontrolislocked out and the red LEDwill blink 4 times repetitively. The thermostat must be openedfor at leastten secondsto reset the furnacecontrolaftera lockout. Otherwise,the furnacewill attemptanother ignitionsequencein 1 hour. 8. The furnace control energizesthe circulatingair bloweron the heatingspeed 30 secondsafterthe gasvalvecircuitis energized. 9. When the thermostat has been satisfied, gas valve is de-energized. 10. The inducer is de-energized after a 30second postpurge. 11. The furnace control keeps the circulating air blower energized for 120 seconds (factory set) or 60, 90, or 180 seconds (field adjustable). (See Figure 27.) 12. Abnormal conditions: If a limit opens during operation, the inducer and circulating air blower continue to operate. The gas valve is de-energized immediately. The blowers continue to operate until the limit closes. When the limit closes the inducer blower is de-energized immediately. The circulating air blower continues to operate for the specified delay (factory set at 120 seconds). Cooling Mode: I. On a call for cooling the thermostat closes, applying 24 VAC to the G and Y terminals on the furnace control. This closes the 2. 3. 4. compressor contactor. The furnace control energizes the circulating blower (115 VAC) on the cooling speed. When the thermostat is satisfied, the G and Y terminals on the control board are de-energized opening the compressor contactor. The circulating air blower is de-energized after a 90-second delay. Fan Mode: I. On a callforfan operation, the thermostat applies 24 VAC to the G terminal on the furnace control board. . 3. The circulating air blower is energized immediately on the heating speed. If the furnace is operated in the continuous ON position at the thermostat and is then switched to AUTO, the circulating blower will operate for a specified delay (factory set at 120 seconds). Furnace Fails to Operate If the furnace does not operate check the following: I. Is the thermostat operating properly? 2. Is the front door in place? 3. Is the furnace disconnect closed? 4. 5. 6. 7. 8. 9. Has the circuit breaker tripped or the control board fuse burned open? Is the gas turned on? Are any manual reset switches open? Is the filter dirty or plugged? Is the flame sensor coated? (Remove and clean with emery cloth.) Is the deck switch open? If the furnace locks out after 5 attempts for ignition, it will try again every hour if a call for heat remains. If the inducer and circulating air blowers are operating, and items I through 8 have been checked, press the red reset button on the vent safety switch. (See Figure 29.) If the furnace operates after depressing the reset button, contact a qualified service technician to identify and repair the problem. If furnace still fails to operate, depress the red reset buttons on the flame roll-out switch. If the furnace operates after depressing the reset button, contact a qualified service technician to identify and repair the problem. 31 M3 Dewnflow 1 Door Assembly - Louvered Furnace 12 Ignitor Filter Inside Door 13 BurnerView 3 Blower Assembly 14 Main Limit Switch 4 Control Board 15 Coil Cabinet 5 Pressure Switch 16 Flame 6 Flame Rollout Switch 17 Gas Valve "J" Trap Hard Tube 18 Switch, On/Off 8 LowVoltage 19 Blower, Inducer 9 In Line Drain Assembly 20 Orifice(In 21 Aux. 10 Junction Transformer Box 32 Port 29. Location of Major Assembly Sensor Limit Components (Optional) (On Burner BurnerBox) BurnerBox 11 Vent Safety Switch Figure Assembly Box) FAULT CONDmON Power Limit On Circuit (Does STATUS RED LUGHT ON Open not apply or External to Deck Pressure Switch Open Pressure Switch Closed !gn!t!on Fai!ure 115 VAC False Power Off FAULT Low Flame Switch, with (Check & Neutral Flame or Gas or Deck Load with Inducer On On or no Ground Relay Sensor 3 FLASHES 5 FLASHES Continuous OFF Shorted Open FLAME YELLOW LIGHT CONDITION Flame 2 FLASHES 4 FLASHES Ground) Valve I FLASH see below) Inducer Reversed Limit On "W" tf any of the originat wire as supplied with the furnace must be replaced, it must be replaced with wiring materiaJ having a temperature rating of at least 105" C. MOTOR PLUG Factory Wired Heating Speeds Furnace Wire Input, Btuh Cotor 60,000 Red 80,000 Blue Use copper conductors only, Continuous Flash ON Signal Present WD#7i0240B Figure 30. Downflow Furnace Wiring Diagram 33 34 INSTALLATION/PERFORIVlANCE CHECK LIST LOCATION CITY STATE INSTALLER CITY STATE UNIT MODEL NUMBER UNIT SERIAL NUMBER Minimum Clearances Are Flue Connections per Table 3? Electrical Connections tight? tight? Is there Proper Draft? Line Voltage Polarity correct? Is Vent free from restrictions? Volts Supply Voltage: Blower Motor HP: Is the Filter(s) secured in place? Is the Filter(s) clean? FUEL TYPE: Natural Gas LPiPropane Gas Piping Connections leak-tested? Has the Thermostat __ Is the Thermostat Gas Line Pressure: been calibrated? level? Is the Heat Anticipator Setting correct? (in. water column, with furnace operating) Manifold Pressure: Has the Owner's Information (in. water column, with furnace operating) Is there adequate fresh air supply for combustion and ventilation? Furnace Input: (Btuh) Supply Air Temperature: (° F) Return Air Temperature: (° F) Temperature (° F) Rise: been reviewed with the home-owner? Has the Literature Package been left near the furnace? 35 708219D 7082t9D O'Fallon, MO NORDYNE (Replaces 708219C) Specifications and illustrations subject to change without notice and without incurring obligations. Printedin US.A. (04/04)
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 36 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 13:38:23 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools