NORDYNE Package Units(both Units Combined) Manual L0612184
User Manual: NORDYNE NORDYNE Package Units(both units combined) Manual NORDYNE Package Units(both units combined) Owner's Manual, NORDYNE Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 16
| Download | |
| Open PDF In Browser | View PDF |
10 and 12 SEER
Single Package Air Conditioner
Single Package
Air Conditioner
Read this owner information to become familiar with the capabilities and use of
your appliance. Keep this with literature on other appliances where you have easy
access to it in the future. If a problem occurs, check the instructions and follow
recommendations
given. If these suggestions don't eliminate your problem, call
your installing contractor or distributor in your area.
INTRODUCTION
Most any air conditioner will keep you cool. Our air conditioner was designed to
do it efficiently. Efficiency means less cost to you while keeping you comfortable.
WHY
YOUR
AIR CONDITIONER
WORKS
SO WELL,
SO QUIETLY
1.
Air is cooled by a large evaporator
this same coil.
coil. Moisture is also removed from the air by
2.
Air is then delivered through the main duct, via registers, into your home.
3.
Return air is drawn through the return register.
4.
This air enters the unit, passes through the evaporator coil, is cooled and dehumidified. Then the cycle begins again.
SECTION t.
OWNER INFORMATION
OPERATING
INSTRUCTIONS
To Turn On Air Conditioner
If you have a heating/cooling thermostat:
1. Set the system switch to "Cool."
2. Set the thermostat at the temperature level
you desire.
3. Turn the power on. Your air conditioner
should start as soon as room temperature
rises above the setting on the thermostat.
If you have one thermostat for heating and
another for cooling, they must be interlocked to prevent simultaneous operation
(See Figure 1):
1. Turn the heating thermostat to its lowest
possible setting.
2. If the cooling thermostat has an "On/Off"
switch, turn it "On."
3. Set the cooling thermostat to the desired
temperature.
4. Turn the power on. Your air conditioner
should start when room temperature exceeds the thermostat setting.
To Shut Off Air Conditioner
In addition, follow these simple rules:
1. Never run your system without filter. If you
do, the cooling coils will get dirty and may
become dogged.
2. Set your thermostat at the comfort level
you wish -- and then leave it alone. Let it
control the operation of the air conditioning
system. Ifyou get chilly, turn it up a degree
at a time until comfort is restored.
3. It takes longer for an air conditioner to cool
your dwelling than it does for your furnace
to heat it. So... don't turn the unit on and
expect a dramatic drop in temperature, at
least not dght away. Ifyour home is hot and
humid, the temperature will drop slowly.
4. Check your filters every ten days in summer to see if they are dirty. To keep them
clean, use a mild solution of detergent and
water on washable types. Replace non
washable filters.
5.
If your air conditioner isn't working:
1. Make sure the fuses are not blown or that
your circuit breakers are on.
2. See that your thermostat is set at the
desired temperature and that your system's
switch is on "Cool."
3.
If you have a heating/cooling thermostat:
1. Turn the system switch to "Heat" or "Off."
2. Turn the thermostat to the desired heating
temperature setting.
3. If you are turning your air conditioner offfor
the winter or an extended period, shut off
the power to the air conditioner.
Keep your outdoor condenser coil clean.
You can hose it down when it gets dirty.
4.
For free air flow, make sure your return
register is not covered and that the filter is
clean.
Check the outdoor condenser coil and
make sure it is clean and not clogged with
grass or leaves.
if your air conditioner still isn'tworking, call you r
nearest distributor.
If you have one thermostat for heating
and another for cooling, they must be
interlocked to prevent simultaneous
operation (See Figure I):
1.
2.
3.
Turn your cooling thermostat "Off" or to its
highest setting.
Turn the heating thermostat to the desired
temperature.
If you are turning your air conditioner off for
the winter or aM extended period, shut off
the power to the air conditioner.
BEFORE YOU CALL A SERVICEMAN
Let your serviceman check your system at the
start of each air conditioning season. He will
make sure it's working right, clean or change
filters and make any needed adjustments.
2
Cooling
Thermostat
Furnace
Thermos1
Double
Throw
Double
Po_ Switch
3"o Air Conditio
TM
To Furnace
Figure 1. Thermostat Interlock System
SECTION 2. INSTALLER
IN FORMATION
GENERAL
Read the following instructions completely
before performing the installation,
These instructions are for the use of qualified
personnel specially trained and experienced in
the installation of this type of equipment and
related system components. Some states require installation and service personnel to be
licensed. Unqualified individuals should not
attempt to interpret these instructions or install
this equipment.
The single packaged air conditioners are designed for outdoor installationonly and can be
readily connected into the high static duct
system of a home. The only connections
needed for installation are the supply and return
ducts, the line voltage, and thermostat wiring.
A complete air conditioning system typically
consists of:
•
•
•
•
Single Package Air Conditioner
Home Fittings Kit
Unit Fittings Kit
Thermostat
The single package air conditioner is completely assembled, factory wired, and factory
run tested. The units are ready for easy and
immediate installation.
PRE-INSTALLATION
CHECK
Before any installationis attempted, the cooling
load of the area to be conditioned must be
calculated and a system of the proper capacity
selected. It is recommended that the area to be
conditioned be completely insulated and vapor
sealed.
The installer should comply with all local codes
and regulations which govern the installationof
this type of equipment.
Local codes and
regulations take precedence over any recommendations contained in these instructions.
Consult local building codes and the National
Electrical Code (ANSI Cl) for special installation requirements.
The electrical supply should be checked to
determine if adequate power is available. If
there is any question concerning the power
supply, contact the local power company.
Inspecting Equipment: All units are securely
packed at the time of shipment and, upon
arrival, should be carefully inspected for damage. Claims for damage (apparent or concealed) should be filed immediately with the
carrier.
INSTALLATION
1.
SELECT THE BEST LOCATION
THE AIR CONDITIONING UNIT
FOR
IMPORTANT: DO NOT PLACE UNIT UNDER
THE HOME.
• Select a solid, level position, preferably on a
concrete slab, slightly above the grade level,
and parallel to the home.
• The hot condenser air must be discharged
up and away fi'om the home, and if possible,
in a direction with the prevailing wind.
• De not place the unit in a confined space.
• If practical, place the air conditioner where it
and the ducts will be shaded from the afternoon sun when the heat load is greatest.
• Try to select a site for the unitthat is as close
as possible to the proposed return grille
location.
• Keep in mind that the length ofthe supply and
return ducts should be kept to a minimum with
no sharp radiused bends.
2.
UNPACK THE UNIT
It is recommended that the unit be unpacked at
the installation site to minimize damage due to
handling.
CAUTION:
Do not tip the unit on its side. Oil may
enter the compressor
cylinders and
cause starting trouble. If unit has been
set on its side, restore to upright position and do not run for several hours.
Then run unit for a few seconds.
Do
this three or four times with five minutes between
runs.
a. Remove the bands from around the unit.
b. Unfold the top and bottom cap flanges.
c. Carefully remove the top cap and tube.
6ft.
Figure 2. Minimum Unit Clearances
3.
INSTALL THE RETURN AND SUPPLY
AIR FITTINGS ON THE UNIT
The supply and return fittings are included with
select models. If supplied, the duct fittings are
shipped in the supply duct. They attach to the
unit openings with a flange and bead arrangement, secured with two sheet metal screws.
Note: For ease of access, install fitting before
positioning unit in final location.
SUPPLY
DUCT
Positionthe supplyduct collar, ifsupplied,so the
edge of the unit opening fits between the flange
and the bead. Overlap the collar ends keeping
the small screw holes underneath. Align the
holes in the crimped area and install one screw.
Note: It may be necessary to loosen the four
screws that hold the transition duct in order to
install the supply fitting. Re-tighten when installation is complete.
Tap collar as necessary to ensure engagement
with unit opening and install second screw.
Tighten first screw. Rotate collar clockwise so
joint is near three o'clock position.
RETURN DUCT
The 12" return duct is installed in the same
manner as the supply duct. Ifthe unit has a 14"
return, follow these instructions.
10 SEER
Return
12 SEER
Return
Model
2 Ton
2 1/2 Ton
eia. (in)
12
12
Model
2 Ton
2 1/2 Ton
Dia. (in)
12
12
3 Ton
3 1/2 Ton
12
12
3 Ton
3 1/2 Ton
12
14
4 Ton
5 Ton
14
14
4 Ton
14
Align the slots with the holes in the collar and
install two screws. Position the collar over the
opening and align the four notches in the collar
with the four dimples in the panel. Using selfddlling screws (10-16x.5) attach the collar to
the rear panel.
4.
LOCATING AND INSTALLING THE RETURN AIR ASSEMBLY
To avoid complications, locate and install the
return air assembly first. The return air box with
grille and filter (Figure 4) should not be located
in heavy traffic areas like hallways or center of
rooms. A good spot is in a corner or under a
table, if a minimum two inch clearance is available. If desired, the return opening can be
located inside a closet with Iouvered doors that
have an open area equal to or greater than the
12"x 20" grille furnished. The return air grille can
be placed in the wall of a closet and the air ducted
into the filter box through a boxed-in area at the
closet floor level. Make sure the filter is readily
accessible.
After determining the location of the return air
opening, start the installation from under the
home by cutting a small hole in the fiber
underboard to determine hew the floor joist
:ILTER
CUT
Supply Air
FLOOR
Return Air
Figure 3. Return and Supply Air Fittings
4
Figure
4. Return Air Box
location will affect cutting the opening needed
for the box. Floor joists generally are located on
16" centers, leaving 14-3/8" between joists.
After measuring the return air box (approximately 12-1/4" x 14-1/4"), cut the hole through
the floor so that the box will fit between the floor
joists. Careshould betakenwhen cuttingthrough
carpeting to avoid snags. In most installations
it will be necessary to cut a similar hole in the
fiberboard directly under the hole in the floor.
However, if the floor is more than ten inches
deep, it will only be necessary to cut a hole for
the collar on the return air box orforthe insulated
duct.
Set the box into the opening and fasten with
screws or nails. Put the filter and return air grille
in place.
5.
LOCATING
AND INSTALLING
SUPPLY DAMPER(S)
THE
CAUTION:
Figure
5. Supply Damper
nearest register. The round supply opening in
the slanted side of the damper should face the
side of the home where the air conditioner is
located. To locate the center of the heat duct,
first cut a small hole in the fiberboard below the
duct at the desired location. After locating the
duct center, cut a hole approximately 3/4" larger
than the damper opening in the fiberboard. Cut
a 9-1/8" x 13-1/8" hole in the duct and bend over
all tabs flat on the inside of the heat duct. After
inserting the damper into the duct, bend over all
tabs flat on the inside of the heat duct. Seal the
opening between the fiberboard and damper or
flexible duct.
When a home is not equipped with a
make-ready
kit means must be pro-
DUCTINGSYSTEM
vided to prevent simultaneous
operation of the heating and cooling units. A
heat/cool thermostat
is available for
DUCT REQUIREMENTS
The supply duct system, including the number
and type of registers, will have much more
effect on the performance of an air conditioning
system than any other factor. The duct must
be sufficiently large to conduct an adequate
amount of air to each register.
this purpose.
When installing this air conditioning
system in conjunction with a furnace,
a damper must be installed in the furnace base assembly to prevent cold
air being discharged around the heat
exchanger.
Damage to the heat exchanger and asphyxiation
may occur
ifa damper is not installed.
Check with the furnace
manufacturer
for damper requirements.
Failure to
install the required furnace damper
may invalidate code agency listing and
limited warranty on the furnace.
When locating the supply damper(s), carefully
check floor joists and frame members that
could interfere with the installation of the damper
or flexible duct. Ideally, the damper should be
located in the bottom of the main duct, forward
of center of the home, at least three feet from the
THE AIR CONDITIONING OUTPUT OF THE
SYSTEM WILL NOT COOL THE HOME IF
THE AiR IS LOST TO THE OUTSIDE
THROUGH LEAKS IN THE DUCT SYSTEM.
ALSO, DUCTS WHICH ARE COLLAPSED OR
RESTRICTED BY FOREIGN OBJECTS WILL
PREVENT ADEQUATE AIR FLOW.
Note: For highly resistive duct systems it may
be necessary to add an additional return air duct
and or supply to achieve maximum performance and prevent coil icing and refrigerant
flood back.
CONNECTING THE RETURN AND SUPPLY
AIR FLEXIBLE DUCTS
a.
The supply duct for all units istwelve inches
in diameter. The return duct may be 12" or
14" diameter depending on unit size. (See
Table on page 4).
5
TYPICAL
APPLICATIONS
SINGLE DUCTAPPLICATION
Ref. No.
MULTIPLE
Description
(_
12" x 20" Return
Air
(_
16" x 20" Air Filter
(_
12" x 20" Grille
(_
Supply
(_
12" or 14" Diameter
(_
12" Diameter
(_
12" x t2" x 12" "Y"
Damper
Flex Return
Flex Supply
Duct
Fitting
Figure 6. Typical Applications
6
DUCTAPPLICATION
Duct
b.
The flexible ducts can be connected to the
to bundle the remaining motor lead up and
out of the way.
corresponding fittings with the clamps provided with the ducts. Note: All connections
c.
d.
e.
f.
should be leak tight or a loss in cooling
capacity will result.
The flexible ducts may be cut to the required length, see instructions packed with
duct. Keep all ducts as short and straight
as possible. Avoid sharp bends.
Ducts may be spliced with sheet metal
sleeves and clamps. (See Ducting Installation Accessories below.)
Once the inner duct is connected to the
proper fitting, the insulation and plastic
sleeve should be pulled over the connection and clamped.
For homes with multiple supply ducts or for
special applications, a Y fitting is available
to divide the supply air so it can be ducted
to different areas of the home for more
efficient cooling. Note: The Y fitting should
be insulated for maximum performance.
A2 CAUTION:
To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
any uninsulated
the unit.
CONDENSATE DRAIN
A 3/4" condensate fitting extends out of the side
of the unit. The drain trap, shipped in the
electrical compartment, must be installed to
prevent water from collecting inside the unit.
Thread the elbow provided with the unit into the
drain connection until hand tight. Install the trap
into the fitting and seal the joint. Make sure it is
level. Route the condensate from the trap to a
suitable drain. Any connecting tubing or hose
must have the outlet below the trap level for
proper drainage.
WARNING:
Turn
vicing
Black
Wire
RedColor
High
MotorLow
Speed
Figure 7. Motor Lead Connection
of
Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connections to be sure none loosened during shipping
or installation.
Blower Speed -- The blower speed is preset at
the factory for operation at the same speed for
heating and cooling.
For optimum system
performance and comfort, it may be necessary
to change the factory set speed. To change the
blower speed:
1. Disconnect all electrical power to the unit
and remove the service panel.
2. See Figure 7 for wire color vs. motor speed
guide.
3. Place the desired heating blower speed
lead on the "NO" terminal of the blower
relay. Use another wire tie (field supplied)
J
metal components
I
off electrical
power
controls.
Severe
before
ser-
electrical
turned off. Unit must be installed in
shock may result unless power is
compliance
with the National Electrical Code (NEC) and local codes.
Elbow
High Voltage
_
P-Tra p
Figure 8. Drain Trap
Low Voltage
Figure 9. Power Entry
7
ELECTRICAL
1.
ELECTRICAL
CON NECTIONS
Connect the red and yellow wires from the
unit to the R and Y terminals respectively
on the thermostat subbase. Connect the
green wire to the yellow wire at the unit. See
the instruction sheet packed with the thermostat for detailed methods of mounting.
SERVICE
High Voltage
a. Install a branch circuit disconnect of adequate size per NEC. Locate the disconnect within sight of the unit.
b. Extend leads through power wiring hole
provided. Connect L1 and L2 directly to the
contactor. (See Figure 9).
c. Ground the air conditioning unit using the
green grounding screw provided in the
control panel.
Note: The cooling-only thermostat must
be connected to an interlock switch to
prevent simultaneous operation of the furnace and the air conditioner. (See Figure 1,
Page 2.)
b,
Low Voltage
a. Route 24v control wires through the sealing grommet near the power entrance.
b. Connect the control wires to the leads in the
low voltage area. (See Figure 10).
2.
OVERCURRENT
PROTECTION
Connect the red, yellow, green and brown
tow voltage wires to the R or RC, Y, G and
W terminals respectively on the thermostat base. The black wire is the 24 volt
common required on some thermostats.
See thermostat instruction sheet for more
detailed information.
In general, the best fuse or breaker for any air
conditioner is the smallest size that will permit
the equipment to run under normal use and
service without nuisance trips. Such a device,
sized properly, gives maximum equipment protection. The principal reason for specifying a
time delay type is to prevent nuisance trips
when the unit starts.
In the event that a fuse does blow or a breaker
trips, always determine the reason. Do not
arbitrarily put in a larger fuse or breaker and do
not, in any case, exceed the maximum size
listed on the data label of the unit.
3.
LOCATING
Do not locate near a lamp, kitchen range, direct
sunlight, or in line with air flow from supply
registers.
Connect Cooling Thermostat:
The
cooling thermostat available for use with
this system is equipped with a selector
switch. To shut down the air conditioner,
set the selector switch to the OFF position.
a.
8
Refer to furnace installationinstructionsfor
required connections and proper heat anticipator setting when installing unit with an
external furnace.
Co
THE THERMOSTAT
Locate the thermostat away from drafts and
slamming doors and place it where there is a
free flow of air. Mount on an inside wall approximately five feet from the floor.
Connect the Heat-Cool Thermostat:
The heat-cool thermostat is equipped with
a system HEAT-COOL switch, which provides a positive means of preventing simultaneous operation of the heating and cooling units. The thermostat is also equipped
with an ON-AUTO fan switch which allows
the home owner to operate the indoor
blower when air circulation is desired.
4,
If two stage heating is desired, an
optional outdoor thermostat may be
installed: Connect the thermostat to the
orange low voltage wire and the W terminal
on the indoor thermostat base (See Figure
10). See the thermostat instructions for
details on setting the outdoor thermostat.
ELECTRIC
TIONAL)
HEAT
PACKAGE
(OP-
The air conditioner is shipped without an auxiliary electric heat kit installed. If electric heat is
desired, an accessory Heater Kit must be field
installed. See Specifications Sheet for available
kits and their applications.
Select the correct size heat package for
the installation.
Control
Wire
4 Wire Heat/CoolThermostat
Leuend
Single Stage Electric
Green - Blower Relay
Red - Transformer
24V
Yellow - Cooling
Stage
1st
Brown - Heating
Stage
1st
Orange
- Heating
Stage
- - -_
2 Wire CoolinqThermostat
Heat
YELL_
2nd
BROWN
ORANGE
Two Stal e Electric
Heat
---_RED
I
i......
- - -_
YELLOW
_ _ __L_
GREEN
_ _ __L_
BR(_N N
--
ORANGE
I
Outdoor
Thermostat
Optional
(Field Supplied)
•: __
Figure 10. Low Voltage Connections
Follow installation instructions provided
with each heater kit.
Installation is most easily accomplished
before making duct or electrical connections.
The blower must be set to high speed for
electdc heat operation.
SYSTEM
1.
OPERATION
[]
Is the thermostat wired correctly?
installed in a proper location?
2.
START-UP
a.
b.
c.
Set the system switch to the OFF position.
Dial thermostat setting as high as it will go.
Turn on power supply at the disconnect
switch.
Set the system switch to ON or COOL. Set
the temperature setting to below room
temperature. Verify that the indoor blower,
outdoor fan, and compressor are energized and the cooling function starts.
Verify that the discharge air grilles are
adjusted and the system is balanced.
Verify that there are no air leaks in the duct
work.
d.
PRE-START CHECK LIST
The following check list should be observed
prior to starting the unit.
[]
[]
Is the unit level? It should be level or
slightly slanted toward the d rain for proper
condensate drainage.
Is the unit installed with the proper clearances (See Figure 2)?
[]
Is the wiring correct according to the
wiring diagram and electrical codes?
[]
Are all the wiringconnections tight? Check
the condenser fan to make sure it turns
freely.
[]
Is the overcurrent
sized?
protection
properly
e.
f.
g.
h.
i.
j.
k.
Is it
PROCEDURE
Verify that the condensate drain is propedy
installed and that it functions correctly.
Dial the thermostat higher than room temperature. The unit should stop.
If using a combination heating-cooling thermostat, set to the HEAT position. Proceed
to check for correct furnace operation.
Verify that the furnace controls and burners or heating elements operate correctly.
Instruct the owner on unit operation, filter
servicing, and proper thermostat operation.
10 SEER - Refrigerant Charging Tables
2 Ton
OUTDOOR
70
5ucL Press Dis Press.!
75
_is. Temp.
Dis. Press
80
Dis. Temp
DIS Press.
TEMPERATURE
Dis. Temp
3s
Press.
90
Dis Temp
243
160
1_
tB8
245
247
18_
169
261
170 _ i_'_:_
176
254
177
266
179
278
180
_ i_
257
181
270
183
282
184
_ _;_4_J:_. _ _!i:_
273
187
286
188
299
189
289
193
302
194
305
198
72
183
141
196
142
74
185
146
198
147
212
149
76
185
155
201
152
2!4
153
228
155
78
189
158
201
159
216
158
230
z05
162
218
221
1_
167
232
234
241
88
90
)is. Temp
92
Dis. Press.
105
159
136
Dis. Press•
100
Dis Temp•
180
86
95
3is. Press.
70
80
82
!°F!
85
Dis. Temp.
Dis. Press•
94
Dis. Temp,
" _
_
96
2-1/2 Ton
OUTDOOR
70
Suet. Press
Dis. Press
)is
75
Temp.
Dis
Press
80
Dis. Temp.
Dis. Press
TEMPERATURE
('F)
85
Dis Temp.
DIS. Press
90
Dis, Temp
Dis. Press.
95
Dis Temp.
100
Dis. Press.
Dis. Temp.
_ !_!!!!_!
!_i;_;_i_i_!!_
Dis. Press
105
_)is Temp.
DIS, Press.
Dis. Temp.
69
190
147
71
193
152
207
152
73
195
157
209
157
223
156
75
196
165
211
162
225
161
239
161
77
199
168
212
168
227
166
241
166
255
165
216
171
229
171
243
170
257
170
232
175
246
175
259
174
273
174
252
182
266
182
279
182
291
181
269
186
282
186
295
186
286
190
299
190
312
190
302
194
315
194
319
199
79
81
85
87
89
91
:_7
93
_
95
* Note;
All pressures
are listed
in psig. and
-Shaded
flooded
Boxesindicate
conditions
all temperatures
I
in °F.
J
I
- Rated Design
flow, entering
Values.
dry bulb,
Suction
Pressure
will be lower than design value if indoor
or entering wet bulb temperatures
a re lower than d esign,
air
- Discharge
temperaturesgreater
values indicate an undercharged
thancharted
system.
10 SEER - Refrigerant
Charging Tables
3 Ton
OUTDOORTEMPERATURE('F)
70
Suct. Pres_ D_
Press,
75
Dis Temp.
De.
Press.
80
D_.Temp.
Oh. Press.
85
D_.Temp
Dis. Press
90
Dis Temp.
Dis. Press.
95
)_.Temp
DIS. Press,
100
Dis,Temp.
DIS. Press
105
)is. Temp
Dis,Press.
Dis. Temp.
68
177
156
70
180
161
198
161
72
182
166
20(I
166
218
165
74
184
173
202
171
220
170
238
170
76
187
175
204
176
222
175
240
174
258
t74
208
179
224
179
242
179
260
178
228
183
245
183
262
183
280
182
82
248
187
265
187
282
186
84
252
190
269
191
285
190
302
190
272
194
289
195
306
194
292
199
309
199
326
198
313
203
329
203
333
207
78
80
86
88
_
...... _
90
_,4_, i_i_!%
92
_ii_18_,_!
_!i_
ii_i_
i _4_;_
94
3-1/2 Ton
OUTDOOR
70
_uct
Press
D=s. p tess
75
3is Temp
Dis. Press.
80
Dis Temp
DIS Press.
TEMPERATURE
('F)
85
Dis. Temp.
Dis. Press,
90
Dis Temp.
Dis. Press.
g5
Dis. Temp
100
_is. Press.
Dis. Temp.
Dis. Press.
105
Dis. Temp.
DIS Press
Dis. Temp.
68
195
148
70
!97
153
213
155
72
199
159
216
160
232
161
74
200
167
218
1_5
234
166
250
_68
76
204
170
219
172
236
_71
252
172
268
t74
222
175
238
176
254
177
270
178
241
180
256
182
272
183
288
184
82
260
185
275
187
290
188
84
263
189
279
191
294
192
308
282
195
297
197
313
198
_ _!;_,i
301
201
316
202
331
204
31g
207
335
208
338
213
78
80
86
88
90
92
!_!_;
:_ ......
194
94
* Note: All pressures
are listed in psig. and all temperatures
-Shaded Boxesicdicate
flooded condilion s
I
in °F.
I
I -RatedDesignValues.
SuctionPressurewillbelowerthandesignvalueifindoorair
flow, entering d_ bulb, o r entering wet bulb temperatures a re lower th an design,
- Discharge temperatures g rearer than charted
values indicate an undercharged system.
10 SEER - Refrigerant
Charging Tables
4 Ton
OUTDOOR
70
)uct
Press
Dis, Press
75
Dis Temp.
Dis. Press.
80
Dis. Temp.
Dis. Press.
TEMPERATURE
('F}
85
Dis Temp
Dis Press,
90
Dis Temp.!3=s.
Press.
95
Dis Temp,
Dis Press.
!00
Dis. Temp.
D_s. Press.
105
)is. Temp
Dis,Press
)is. Temp.
68
195
148
70
197
153
213
155
72
199
159
216
160
232
161
74
200
167
218
165
234
166
250
168
76
204
170
219
172
236
171
252
172
268
174
222
175
238
176
254
177
270
!78
2,,,1
_
256
182
272
183
2s8
1_
82
260
185
275
187
290
!B8
84
263
189
279
191
294
192
308
194
_
_
282
195
297
197
313
198
! !_:_!
_
301
201
316
202
331
204
319
207
335
208
338
213
78
80
86
88
90
ii:_
_
92
_i_
t_t_ _
94
5 Ton
OUTDOOR
70
Suct. Press Dis Press.
75
Dis. Temp.
80
Dis. Press. l )is. Temp
Dis Press
TEMPERATURE
(=F)
85
D_s, Temp
Dis. PreSs.
90
Dis Temp.
)m. Press.
95
Dis, Temp
)is
Press.
100
Dis. Temp.
Dis. Press.
105
Dis. Temp.
Dis. Press
)is. Temp.
63
207
155
65
209
160
224
161
67
211
165
226
166
241
166
69
211
175
228
171
243
171
259
172
71
215
177
229
178
246
176
261
176
276
177
233
18!
247
181
263
181
278
181
ii_i_93ii!ii_
.... i ,, ,ri,,
251
185
265
185
280
185
295
_86
7:
268
18o
2B3
190
297
19o
79
272
193
286
193
300
194
314
194
3_7
202
322
203
336
204
325
207
339
208
343
212
73
75
83
85
87
!;_!_t'%! i';_m'_'
_! _
_
89
* Note: All pressures
are listed in psig, and all temperatures
-Shaded Boxesindicate
flooded conditions
I
in °F.
I
I
-RatedDesignValues.
SuctionPressurewillbelowerthandesignvalueifindoorair
flow, entering dry bulb, or entedng wet bulb temperatures are lower than design,
- Discharge temperaturesgreater
values indicate an undercharged
than chaded
system.
12 SEER - Refrigerant
Charging Tables
2 Ton
TEMPERATURE
OUTDOOR
70
Suct
Press
Dis. Press.
75
DIS, Temp.
DIS Press.
80
Dis. Temp.
DIS. Press.
I"FI
85
)is. Temp
Dis. Press.
90
Dis. Temp.
Dis. Press
95
Dis, Temp.
100
3is Press.
Dis. Temp.
)isPress.
105
Dis. Temp.!
DIS. Press.
D_Temp
72
170
123
74
172
129
186
132
76
174
134
189
137
203
140
78
175
142
1gl
142
205
145
219
149
80
179
144
192
148
207
150
221
153
236
157
196
151
209
155
224
158
23B
161
213
158
226
162
240
165
254
169
B6
229
188
243
189
256
173 iiii_!
88
233
169
246
173
260
177
272
180
250
177
263
1B1
276
184
266
185
280
189
293
283
193
297
197
300
201
B2
B4
90
92
94
;-_;it
96
_i_ _B_'_!
_i_1_
_ii_ ii!i_!_8_:
192
98
2-1/2 Ton
OUTDOOR
70
75
Ois. Temp,
Dis. Temp.
)is. Press
73
172
125
75
174
131
189
132
77
175
136
191
137
206
139
79
176
146
193
142
208
B1
180
148
194
150
210
197
153
85
Dis. Press
TEMPERATURE
(=F)
85
Suct. Pres!
83
)is, Press
BO
Dis. Temp
90
Dis. Press.
95
Dis Press
]is, Temp.
Dis Temp,
!44
223
145
14B
225
150
240
151
212
154
227
154
242
155
215
157
100
Dis Press.
Dis. Temp.
Dis Press,
105
Dis,Temp.
)is. Press.
Dis Temp,
22_
ls9
2,_
180
2s9
161
B7
233
162
247
164
261
165
89
236
166
251
168
265
169
27B
170
254
172
26B
173
282
175
272
177
286
179
300
180
289
183
304
185
307
189
91
93
95
97
_" '_}_ii!
_
99
* Note:
c_a
All pressures
are listed in psig.
and all temperatures
-ShadedBoxesindicate
flooded conditions
I
in °F.
I
I -RatedDesignValues.
flow, entering
dry
bulb,
SuctionPressurewillbelowerthandesignvalueifirldoorair
or entering
wet bulb tern peratures
are lower
than design,
-Dischargetemperaturesgreaterthanchaded
values indicate an undercharged
system.
12 SEER - Refrigerant Charging Tables
3 Ton
OUTDOOR
70
75
Dis. Temp
Dis Press.
80
3_s. Temp
D=s,Press
90
Dis. Temp.
Dis. Press
95
Dis. Press.
Dis. Temp.
)is
Press,
105
70
172
130
72
174
135
1B9
134
74
176
140
191
139
206
139
76
175
152
193
144
208
143
223
143
78
179
154
193
153
210
148
225
147
240
196
156
211
155
227
152
242
151
214
158
228
157
244
155
258
154
84
232
161
246
159
261
158
86
235
164
250
163
264
162
277
161
253
167
267
166
282
1B6
271
171
285
170
299
169
288
174
303
173
306
178
88
Dis,Temp
100
3is Press.
82
Dis. Press.
I'F)
Suct. PresJ
B0
Dis Temp.
TEMPERATURE
85
Dis. Tgmp.
)is.
Press.
Dis,Temp
146
90
92
!:_
_i_
94
;
96
3-1/2 Ton
OUTDOOR
70
Suct
Pres=
]is
Press
75
Dis. Temp
)is
Press.
80
DIS Temp,
Dis. Press.
TEMPERATURE
('F)
85
Dis Temp.
Dis. Press.
90
)is. Temp.
Dis. Press
95
3is Temp.
100
Dis. Press.
Dis. Temp.
Dis. Press
105
Dis,Temp
)is. Press.
Ois. Temp
69
169
137
71
171
143
186
142
73
174
148
188
147
204
146
75
175
155
191
152
206
151
221
150
77
179
_57
193
157
208
156
223
155
238
154
196
160
210
_61
225
160
240
159
214
164
228
164
242
163
257
162
83
231
167
245
167
259
167
85
235
171
249
171
263
171
276
17o
252
175
266
175
280
174
269
179
283
179
297
178
287
183
301
182
304
187
79
81
_i_ _
t
87
89
91
93
P_
ff
_i_:_,_,_
;_ _?
95
* Note: All pressures
are listed in psig. and all temperatures
-Shaded Boxesindicate
flooded conditions
I
in °F.
I
I - Rated Design Values. Suction Pressure will belower than design value if indoor air
flow, entedng dry bulb, or entering wet bulb temperatures
are lower than d esign,
- Discharge temperatures greater than charted
values indicate an undercharged system,
12 SEER - Refrigerant
Charging Tables
4 Ton
OUTDOOR
70
75
Dis. Temp.
Dis. Temp
(°F)
]is
Temp.
Dis. Press.
]is. Temp.
Dis. Press.
100
135
70
175
140
191
141
72
178
146
193
146
208
146
74
178
155
195
151
211
151
226
151
76
181
158
196
158
213
156
228
156
243
156
199
161
214
161
230
160
246
161
218
165
232
165
248
165
263
165
82
236
169
250
169
265
169
84
239
172
254
173
268
173
282
173
_
257
177
272
177
286
178
_,;_:_
275
181
290
182
305
182
293
186
308
187
311
191
_2_
Dis. Temp.
Dis. Press
105
173
88
DIS. Press.
95
68
86
]is, Temp
90
)is. Press
80
Dis. Press.
TEMPERATURE
85
Suct. Pres!
78
]is. Press.
80
)is. Temp.
Dis. Press.
Dis. Temp.
1_
90
92
_;;
_
;
?"
94
* Note: All pressures
_
_::
I _,
]
are listed in psig. and all temperatures
-Shad_lBoxesindicate
flooded conditions
I
'
in °F.
]
I -RatedDesignValues.
SuctionPressurewillbelowerthandesignvalueifindoorair
flow, entering dry bulb, or entering wet bulb tern peratures are lower than design,
-Dischargetemperaturusgreaterthanchaded
values indicate an undercharged system.
INSTALLER
PLEASE LEAVE THESE
INSTALLATION
INSTRUCTIONS
WITH THE HOMEOWNER.
IIIIIIIIIIIIIIIIIIII
708298A(Replaces 7082980)
Specifications and illustrations subject to change
without notice and without incurring obligations.
708298A
Prlnted
inU.S.A.(11/03)
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 16 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Thu Apr 05 10:19:28 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools