NORDYNE Package Units(both Units Combined) Manual L0612184

User Manual: NORDYNE NORDYNE Package Units(both units combined) Manual NORDYNE Package Units(both units combined) Owner's Manual, NORDYNE Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 16

DownloadNORDYNE  Package Units(both Units Combined) Manual L0612184
Open PDF In BrowserView PDF
10 and 12 SEER
Single Package Air Conditioner

Single Package

Air Conditioner

Read this owner information to become familiar with the capabilities and use of
your appliance. Keep this with literature on other appliances where you have easy
access to it in the future. If a problem occurs, check the instructions and follow
recommendations
given. If these suggestions don't eliminate your problem, call
your installing contractor or distributor in your area.

INTRODUCTION
Most any air conditioner will keep you cool. Our air conditioner was designed to
do it efficiently. Efficiency means less cost to you while keeping you comfortable.
WHY

YOUR

AIR CONDITIONER

WORKS

SO WELL,

SO QUIETLY

1.

Air is cooled by a large evaporator
this same coil.

coil. Moisture is also removed from the air by

2.

Air is then delivered through the main duct, via registers, into your home.

3.

Return air is drawn through the return register.

4.

This air enters the unit, passes through the evaporator coil, is cooled and dehumidified. Then the cycle begins again.

SECTION t.

OWNER INFORMATION

OPERATING

INSTRUCTIONS

To Turn On Air Conditioner
If you have a heating/cooling thermostat:
1. Set the system switch to "Cool."
2. Set the thermostat at the temperature level
you desire.
3. Turn the power on. Your air conditioner
should start as soon as room temperature
rises above the setting on the thermostat.
If you have one thermostat for heating and
another for cooling, they must be interlocked to prevent simultaneous operation
(See Figure 1):
1. Turn the heating thermostat to its lowest
possible setting.
2. If the cooling thermostat has an "On/Off"
switch, turn it "On."
3. Set the cooling thermostat to the desired
temperature.
4. Turn the power on. Your air conditioner
should start when room temperature exceeds the thermostat setting.
To Shut Off Air Conditioner

In addition, follow these simple rules:
1. Never run your system without filter. If you
do, the cooling coils will get dirty and may
become dogged.
2. Set your thermostat at the comfort level
you wish -- and then leave it alone. Let it
control the operation of the air conditioning
system. Ifyou get chilly, turn it up a degree
at a time until comfort is restored.
3. It takes longer for an air conditioner to cool
your dwelling than it does for your furnace
to heat it. So... don't turn the unit on and
expect a dramatic drop in temperature, at
least not dght away. Ifyour home is hot and
humid, the temperature will drop slowly.
4. Check your filters every ten days in summer to see if they are dirty. To keep them
clean, use a mild solution of detergent and
water on washable types. Replace non
washable filters.
5.

If your air conditioner isn't working:
1. Make sure the fuses are not blown or that
your circuit breakers are on.
2. See that your thermostat is set at the
desired temperature and that your system's
switch is on "Cool."
3.

If you have a heating/cooling thermostat:
1. Turn the system switch to "Heat" or "Off."
2. Turn the thermostat to the desired heating
temperature setting.
3. If you are turning your air conditioner offfor
the winter or an extended period, shut off
the power to the air conditioner.

Keep your outdoor condenser coil clean.
You can hose it down when it gets dirty.

4.

For free air flow, make sure your return
register is not covered and that the filter is
clean.
Check the outdoor condenser coil and
make sure it is clean and not clogged with
grass or leaves.

if your air conditioner still isn'tworking, call you r
nearest distributor.

If you have one thermostat for heating
and another for cooling, they must be
interlocked to prevent simultaneous
operation (See Figure I):
1.
2.
3.

Turn your cooling thermostat "Off" or to its
highest setting.
Turn the heating thermostat to the desired
temperature.
If you are turning your air conditioner off for
the winter or aM extended period, shut off
the power to the air conditioner.

BEFORE YOU CALL A SERVICEMAN
Let your serviceman check your system at the
start of each air conditioning season. He will
make sure it's working right, clean or change
filters and make any needed adjustments.

2

Cooling
Thermostat

Furnace
Thermos1

Double
Throw
Double
Po_ Switch

3"o Air Conditio

TM

To Furnace

Figure 1. Thermostat Interlock System

SECTION 2. INSTALLER
IN FORMATION
GENERAL
Read the following instructions completely
before performing the installation,
These instructions are for the use of qualified
personnel specially trained and experienced in
the installation of this type of equipment and
related system components. Some states require installation and service personnel to be
licensed. Unqualified individuals should not
attempt to interpret these instructions or install
this equipment.
The single packaged air conditioners are designed for outdoor installationonly and can be
readily connected into the high static duct
system of a home. The only connections
needed for installation are the supply and return
ducts, the line voltage, and thermostat wiring.
A complete air conditioning system typically
consists of:
•
•
•
•

Single Package Air Conditioner
Home Fittings Kit
Unit Fittings Kit
Thermostat

The single package air conditioner is completely assembled, factory wired, and factory
run tested. The units are ready for easy and
immediate installation.

PRE-INSTALLATION

CHECK

Before any installationis attempted, the cooling
load of the area to be conditioned must be
calculated and a system of the proper capacity
selected. It is recommended that the area to be
conditioned be completely insulated and vapor
sealed.
The installer should comply with all local codes
and regulations which govern the installationof
this type of equipment.
Local codes and
regulations take precedence over any recommendations contained in these instructions.
Consult local building codes and the National
Electrical Code (ANSI Cl) for special installation requirements.
The electrical supply should be checked to
determine if adequate power is available. If
there is any question concerning the power
supply, contact the local power company.

Inspecting Equipment: All units are securely
packed at the time of shipment and, upon
arrival, should be carefully inspected for damage. Claims for damage (apparent or concealed) should be filed immediately with the
carrier.

INSTALLATION
1.

SELECT THE BEST LOCATION
THE AIR CONDITIONING UNIT

FOR

IMPORTANT: DO NOT PLACE UNIT UNDER
THE HOME.
• Select a solid, level position, preferably on a
concrete slab, slightly above the grade level,
and parallel to the home.
• The hot condenser air must be discharged
up and away fi'om the home, and if possible,
in a direction with the prevailing wind.
• De not place the unit in a confined space.
• If practical, place the air conditioner where it
and the ducts will be shaded from the afternoon sun when the heat load is greatest.
• Try to select a site for the unitthat is as close
as possible to the proposed return grille
location.
• Keep in mind that the length ofthe supply and
return ducts should be kept to a minimum with
no sharp radiused bends.
2.

UNPACK THE UNIT

It is recommended that the unit be unpacked at
the installation site to minimize damage due to
handling.

CAUTION:
Do not tip the unit on its side. Oil may
enter the compressor
cylinders and
cause starting trouble. If unit has been
set on its side, restore to upright position and do not run for several hours.
Then run unit for a few seconds.
Do
this three or four times with five minutes between

runs.

a. Remove the bands from around the unit.
b. Unfold the top and bottom cap flanges.
c. Carefully remove the top cap and tube.

6ft.

Figure 2. Minimum Unit Clearances
3.

INSTALL THE RETURN AND SUPPLY
AIR FITTINGS ON THE UNIT
The supply and return fittings are included with
select models. If supplied, the duct fittings are
shipped in the supply duct. They attach to the
unit openings with a flange and bead arrangement, secured with two sheet metal screws.
Note: For ease of access, install fitting before
positioning unit in final location.
SUPPLY

DUCT

Positionthe supplyduct collar, ifsupplied,so the
edge of the unit opening fits between the flange
and the bead. Overlap the collar ends keeping
the small screw holes underneath. Align the
holes in the crimped area and install one screw.
Note: It may be necessary to loosen the four
screws that hold the transition duct in order to
install the supply fitting. Re-tighten when installation is complete.
Tap collar as necessary to ensure engagement
with unit opening and install second screw.
Tighten first screw. Rotate collar clockwise so
joint is near three o'clock position.

RETURN DUCT
The 12" return duct is installed in the same
manner as the supply duct. Ifthe unit has a 14"
return, follow these instructions.
10 SEER

Return

12 SEER

Return

Model
2 Ton
2 1/2 Ton

eia. (in)
12
12

Model
2 Ton
2 1/2 Ton

Dia. (in)
12
12

3 Ton
3 1/2 Ton

12
12

3 Ton
3 1/2 Ton

12
14

4 Ton
5 Ton

14
14

4 Ton

14

Align the slots with the holes in the collar and
install two screws. Position the collar over the
opening and align the four notches in the collar
with the four dimples in the panel. Using selfddlling screws (10-16x.5) attach the collar to
the rear panel.
4.

LOCATING AND INSTALLING THE RETURN AIR ASSEMBLY

To avoid complications, locate and install the
return air assembly first. The return air box with
grille and filter (Figure 4) should not be located
in heavy traffic areas like hallways or center of
rooms. A good spot is in a corner or under a
table, if a minimum two inch clearance is available. If desired, the return opening can be
located inside a closet with Iouvered doors that
have an open area equal to or greater than the
12"x 20" grille furnished. The return air grille can
be placed in the wall of a closet and the air ducted
into the filter box through a boxed-in area at the
closet floor level. Make sure the filter is readily
accessible.
After determining the location of the return air
opening, start the installation from under the
home by cutting a small hole in the fiber
underboard to determine hew the floor joist

:ILTER

CUT

Supply Air

FLOOR

Return Air

Figure 3. Return and Supply Air Fittings
4

Figure

4. Return Air Box

location will affect cutting the opening needed
for the box. Floor joists generally are located on
16" centers, leaving 14-3/8" between joists.
After measuring the return air box (approximately 12-1/4" x 14-1/4"), cut the hole through
the floor so that the box will fit between the floor
joists. Careshould betakenwhen cuttingthrough
carpeting to avoid snags. In most installations
it will be necessary to cut a similar hole in the
fiberboard directly under the hole in the floor.
However, if the floor is more than ten inches
deep, it will only be necessary to cut a hole for
the collar on the return air box orforthe insulated
duct.
Set the box into the opening and fasten with
screws or nails. Put the filter and return air grille
in place.
5.

LOCATING
AND INSTALLING
SUPPLY DAMPER(S)

THE

CAUTION:

Figure

5. Supply Damper

nearest register. The round supply opening in
the slanted side of the damper should face the
side of the home where the air conditioner is
located. To locate the center of the heat duct,
first cut a small hole in the fiberboard below the
duct at the desired location. After locating the
duct center, cut a hole approximately 3/4" larger
than the damper opening in the fiberboard. Cut
a 9-1/8" x 13-1/8" hole in the duct and bend over
all tabs flat on the inside of the heat duct. After
inserting the damper into the duct, bend over all
tabs flat on the inside of the heat duct. Seal the
opening between the fiberboard and damper or
flexible duct.

When a home is not equipped with a
make-ready
kit means must be pro-

DUCTINGSYSTEM

vided to prevent simultaneous
operation of the heating and cooling units. A
heat/cool thermostat
is available for

DUCT REQUIREMENTS
The supply duct system, including the number
and type of registers, will have much more
effect on the performance of an air conditioning
system than any other factor. The duct must
be sufficiently large to conduct an adequate
amount of air to each register.

this purpose.

When installing this air conditioning
system in conjunction with a furnace,
a damper must be installed in the furnace base assembly to prevent cold
air being discharged around the heat
exchanger.
Damage to the heat exchanger and asphyxiation
may occur
ifa damper is not installed.
Check with the furnace

manufacturer

for damper requirements.
Failure to
install the required furnace damper
may invalidate code agency listing and
limited warranty on the furnace.

When locating the supply damper(s), carefully
check floor joists and frame members that
could interfere with the installation of the damper
or flexible duct. Ideally, the damper should be
located in the bottom of the main duct, forward
of center of the home, at least three feet from the

THE AIR CONDITIONING OUTPUT OF THE
SYSTEM WILL NOT COOL THE HOME IF
THE AiR IS LOST TO THE OUTSIDE
THROUGH LEAKS IN THE DUCT SYSTEM.
ALSO, DUCTS WHICH ARE COLLAPSED OR
RESTRICTED BY FOREIGN OBJECTS WILL
PREVENT ADEQUATE AIR FLOW.
Note: For highly resistive duct systems it may
be necessary to add an additional return air duct
and or supply to achieve maximum performance and prevent coil icing and refrigerant
flood back.
CONNECTING THE RETURN AND SUPPLY
AIR FLEXIBLE DUCTS
a.

The supply duct for all units istwelve inches
in diameter. The return duct may be 12" or
14" diameter depending on unit size. (See
Table on page 4).
5

TYPICAL

APPLICATIONS

SINGLE DUCTAPPLICATION

Ref. No.

MULTIPLE

Description

(_

12" x 20" Return

Air

(_

16" x 20" Air Filter

(_

12" x 20" Grille

(_

Supply

(_

12" or 14" Diameter

(_

12" Diameter

(_

12" x t2" x 12" "Y"

Damper
Flex Return

Flex Supply

Duct

Fitting

Figure 6. Typical Applications

6

DUCTAPPLICATION

Duct

b.

The flexible ducts can be connected to the

to bundle the remaining motor lead up and
out of the way.

corresponding fittings with the clamps provided with the ducts. Note: All connections

c.

d.

e.

f.

should be leak tight or a loss in cooling
capacity will result.
The flexible ducts may be cut to the required length, see instructions packed with
duct. Keep all ducts as short and straight
as possible. Avoid sharp bends.
Ducts may be spliced with sheet metal
sleeves and clamps. (See Ducting Installation Accessories below.)
Once the inner duct is connected to the
proper fitting, the insulation and plastic
sleeve should be pulled over the connection and clamped.
For homes with multiple supply ducts or for
special applications, a Y fitting is available
to divide the supply air so it can be ducted
to different areas of the home for more
efficient cooling. Note: The Y fitting should
be insulated for maximum performance.

A2 CAUTION:
To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
any uninsulated
the unit.

CONDENSATE DRAIN
A 3/4" condensate fitting extends out of the side
of the unit. The drain trap, shipped in the
electrical compartment, must be installed to
prevent water from collecting inside the unit.
Thread the elbow provided with the unit into the
drain connection until hand tight. Install the trap
into the fitting and seal the joint. Make sure it is
level. Route the condensate from the trap to a
suitable drain. Any connecting tubing or hose
must have the outlet below the trap level for
proper drainage.

WARNING:
Turn
vicing

Black
Wire
RedColor

High
MotorLow
Speed

Figure 7. Motor Lead Connection

of

Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connections to be sure none loosened during shipping
or installation.

Blower Speed -- The blower speed is preset at
the factory for operation at the same speed for
heating and cooling.
For optimum system
performance and comfort, it may be necessary
to change the factory set speed. To change the
blower speed:
1. Disconnect all electrical power to the unit
and remove the service panel.
2. See Figure 7 for wire color vs. motor speed
guide.
3. Place the desired heating blower speed
lead on the "NO" terminal of the blower
relay. Use another wire tie (field supplied)

J

metal components

I

off electrical

power

controls.

Severe

before

ser-

electrical

turned off. Unit must be installed in
shock may result unless power is
compliance
with the National Electrical Code (NEC) and local codes.

Elbow

High Voltage
_

P-Tra p

Figure 8. Drain Trap

Low Voltage
Figure 9. Power Entry
7

ELECTRICAL
1.

ELECTRICAL

CON NECTIONS

Connect the red and yellow wires from the
unit to the R and Y terminals respectively
on the thermostat subbase. Connect the
green wire to the yellow wire at the unit. See
the instruction sheet packed with the thermostat for detailed methods of mounting.

SERVICE

High Voltage
a. Install a branch circuit disconnect of adequate size per NEC. Locate the disconnect within sight of the unit.
b. Extend leads through power wiring hole
provided. Connect L1 and L2 directly to the
contactor. (See Figure 9).
c. Ground the air conditioning unit using the
green grounding screw provided in the
control panel.

Note: The cooling-only thermostat must
be connected to an interlock switch to
prevent simultaneous operation of the furnace and the air conditioner. (See Figure 1,
Page 2.)
b,

Low Voltage
a. Route 24v control wires through the sealing grommet near the power entrance.
b. Connect the control wires to the leads in the
low voltage area. (See Figure 10).
2.

OVERCURRENT

PROTECTION

Connect the red, yellow, green and brown
tow voltage wires to the R or RC, Y, G and
W terminals respectively on the thermostat base. The black wire is the 24 volt
common required on some thermostats.
See thermostat instruction sheet for more
detailed information.

In general, the best fuse or breaker for any air
conditioner is the smallest size that will permit
the equipment to run under normal use and
service without nuisance trips. Such a device,
sized properly, gives maximum equipment protection. The principal reason for specifying a
time delay type is to prevent nuisance trips
when the unit starts.
In the event that a fuse does blow or a breaker
trips, always determine the reason. Do not
arbitrarily put in a larger fuse or breaker and do
not, in any case, exceed the maximum size
listed on the data label of the unit.
3.

LOCATING

Do not locate near a lamp, kitchen range, direct
sunlight, or in line with air flow from supply
registers.
Connect Cooling Thermostat:
The
cooling thermostat available for use with
this system is equipped with a selector
switch. To shut down the air conditioner,
set the selector switch to the OFF position.

a.

8

Refer to furnace installationinstructionsfor
required connections and proper heat anticipator setting when installing unit with an
external furnace.
Co

THE THERMOSTAT

Locate the thermostat away from drafts and
slamming doors and place it where there is a
free flow of air. Mount on an inside wall approximately five feet from the floor.

Connect the Heat-Cool Thermostat:
The heat-cool thermostat is equipped with
a system HEAT-COOL switch, which provides a positive means of preventing simultaneous operation of the heating and cooling units. The thermostat is also equipped
with an ON-AUTO fan switch which allows
the home owner to operate the indoor
blower when air circulation is desired.

4,

If two stage heating is desired, an
optional outdoor thermostat may be
installed: Connect the thermostat to the
orange low voltage wire and the W terminal
on the indoor thermostat base (See Figure
10). See the thermostat instructions for
details on setting the outdoor thermostat.
ELECTRIC
TIONAL)

HEAT

PACKAGE

(OP-

The air conditioner is shipped without an auxiliary electric heat kit installed. If electric heat is
desired, an accessory Heater Kit must be field
installed. See Specifications Sheet for available
kits and their applications.
Select the correct size heat package for
the installation.

Control

Wire

4 Wire Heat/CoolThermostat

Leuend

Single Stage Electric

Green - Blower Relay
Red - Transformer
24V
Yellow - Cooling
Stage

1st

Brown - Heating
Stage

1st

Orange

- Heating
Stage

- - -_

2 Wire CoolinqThermostat

Heat

YELL_

2nd

BROWN
ORANGE
Two Stal e Electric

Heat

---_RED

I
i......

- - -_

YELLOW

_ _ __L_

GREEN

_ _ __L_

BR(_N N

--

ORANGE

I

Outdoor

Thermostat
Optional
(Field Supplied)

•: __

Figure 10. Low Voltage Connections
Follow installation instructions provided
with each heater kit.
Installation is most easily accomplished
before making duct or electrical connections.
The blower must be set to high speed for
electdc heat operation.

SYSTEM
1.

OPERATION

[]

Is the thermostat wired correctly?
installed in a proper location?

2.

START-UP

a.
b.
c.

Set the system switch to the OFF position.
Dial thermostat setting as high as it will go.
Turn on power supply at the disconnect
switch.
Set the system switch to ON or COOL. Set
the temperature setting to below room
temperature. Verify that the indoor blower,
outdoor fan, and compressor are energized and the cooling function starts.
Verify that the discharge air grilles are
adjusted and the system is balanced.
Verify that there are no air leaks in the duct
work.

d.

PRE-START CHECK LIST

The following check list should be observed
prior to starting the unit.
[]

[]

Is the unit level? It should be level or
slightly slanted toward the d rain for proper
condensate drainage.
Is the unit installed with the proper clearances (See Figure 2)?

[]

Is the wiring correct according to the
wiring diagram and electrical codes?

[]

Are all the wiringconnections tight? Check
the condenser fan to make sure it turns
freely.

[]

Is the overcurrent
sized?

protection

properly

e.
f.
g.
h.
i.

j.
k.

Is it

PROCEDURE

Verify that the condensate drain is propedy
installed and that it functions correctly.
Dial the thermostat higher than room temperature. The unit should stop.
If using a combination heating-cooling thermostat, set to the HEAT position. Proceed
to check for correct furnace operation.
Verify that the furnace controls and burners or heating elements operate correctly.
Instruct the owner on unit operation, filter
servicing, and proper thermostat operation.

10 SEER - Refrigerant Charging Tables
2 Ton

OUTDOOR
70
5ucL Press Dis Press.!

75

_is. Temp.

Dis. Press

80

Dis. Temp

DIS Press.

TEMPERATURE

Dis. Temp

3s

Press.

90

Dis Temp

243

160

1_
tB8

245
247

18_
169

261

170 _ i_'_:_

176

254

177

266

179

278

180

_ i_

257

181

270

183

282

184

_ _;_4_J:_. _ _!i:_

273

187

286

188

299

189

289

193

302

194

305

198

72

183

141

196

142

74

185

146

198

147

212

149

76

185

155

201

152

2!4

153

228

155

78

189

158

201

159

216

158

230

z05

162

218
221

1_
167

232
234
241

88
90

)is. Temp

92

Dis. Press.

105

159

136

Dis. Press•

100

Dis Temp•

180

86

95

3is. Press.

70

80
82

!°F!

85

Dis. Temp.

Dis. Press•

94

Dis. Temp,

" _
_

96

2-1/2 Ton
OUTDOOR
70
Suet. Press

Dis. Press

)is

75
Temp.

Dis

Press

80
Dis. Temp.

Dis. Press

TEMPERATURE

('F)

85

Dis Temp.

DIS. Press

90

Dis, Temp

Dis. Press.

95

Dis Temp.

100

Dis. Press.

Dis. Temp.

_ !_!!!!_!

!_i;_;_i_i_!!_

Dis. Press

105

_)is Temp.

DIS, Press.

Dis. Temp.

69

190

147

71

193

152

207

152

73

195

157

209

157

223

156

75

196

165

211

162

225

161

239

161

77

199

168

212

168

227

166

241

166

255

165

216

171

229

171

243

170

257

170

232

175

246

175

259

174

273

174

252

182

266

182

279

182

291

181

269

186

282

186

295

186

286

190

299

190

312

190

302

194

315

194

319

199

79
81

85
87
89
91

:_7

93

_

95
* Note;

All pressures

are listed

in psig. and

-Shaded
flooded

Boxesindicate
conditions

all temperatures
I

in °F.
J

I

- Rated Design
flow, entering

Values.
dry bulb,

Suction
Pressure
will be lower than design value if indoor
or entering wet bulb temperatures
a re lower than d esign,

air

- Discharge
temperaturesgreater
values indicate an undercharged

thancharted
system.

10 SEER - Refrigerant

Charging Tables

3 Ton
OUTDOORTEMPERATURE('F)
70
Suct. Pres_ D_

Press,

75

Dis Temp.

De.

Press.

80

D_.Temp.

Oh. Press.

85

D_.Temp

Dis. Press

90

Dis Temp.

Dis. Press.

95
)_.Temp

DIS. Press,

100

Dis,Temp.

DIS. Press

105

)is. Temp

Dis,Press.

Dis. Temp.

68

177

156

70

180

161

198

161

72

182

166

20(I

166

218

165

74

184

173

202

171

220

170

238

170

76

187

175

204

176

222

175

240

174

258

t74

208

179

224

179

242

179

260

178

228

183

245

183

262

183

280

182

82

248

187

265

187

282

186

84

252

190

269

191

285

190

302

190

272

194

289

195

306

194

292

199

309

199

326

198

313

203

329

203

333

207

78
80

86
88

_

...... _

90

_,4_, i_i_!%

92

_ii_18_,_!
_!i_
ii_i_

i _4_;_

94

3-1/2 Ton
OUTDOOR
70
_uct

Press

D=s. p tess

75

3is Temp

Dis. Press.

80

Dis Temp

DIS Press.

TEMPERATURE

('F)

85

Dis. Temp.

Dis. Press,

90

Dis Temp.

Dis. Press.

g5

Dis. Temp

100

_is. Press.

Dis. Temp.

Dis. Press.

105

Dis. Temp.

DIS Press

Dis. Temp.

68

195

148

70

!97

153

213

155

72

199

159

216

160

232

161

74

200

167

218

1_5

234

166

250

_68

76

204

170

219

172

236

_71

252

172

268

t74

222

175

238

176

254

177

270

178

241

180

256

182

272

183

288

184

82

260

185

275

187

290

188

84

263

189

279

191

294

192

308

282

195

297

197

313

198

_ _!;_,i

301

201

316

202

331

204

31g

207

335

208

338

213

78
80

86
88
90
92

!_!_;

:_ ......

194

94

* Note: All pressures

are listed in psig. and all temperatures
-Shaded Boxesicdicate
flooded condilion s

I

in °F.
I

I -RatedDesignValues.
SuctionPressurewillbelowerthandesignvalueifindoorair
flow, entering d_ bulb, o r entering wet bulb temperatures a re lower th an design,

- Discharge temperatures g rearer than charted
values indicate an undercharged system.

10 SEER - Refrigerant

Charging Tables

4 Ton

OUTDOOR
70
)uct

Press

Dis, Press

75

Dis Temp.

Dis. Press.

80

Dis. Temp.

Dis. Press.

TEMPERATURE

('F}

85

Dis Temp

Dis Press,

90

Dis Temp.!3=s.

Press.

95

Dis Temp,

Dis Press.

!00

Dis. Temp.

D_s. Press.

105
)is. Temp

Dis,Press

)is. Temp.

68

195

148

70

197

153

213

155

72

199

159

216

160

232

161

74

200

167

218

165

234

166

250

168

76

204

170

219

172

236

171

252

172

268

174

222

175

238

176

254

177

270

!78

2,,,1

_

256

182

272

183

2s8

1_

82

260

185

275

187

290

!B8

84

263

189

279

191

294

192

308

194

_

_

282

195

297

197

313

198

! !_:_!

_

301

201

316

202

331

204

319

207

335

208

338

213

78

80

86
88
90

ii:_

_

92

_i_
t_t_ _

94

5 Ton
OUTDOOR
70
Suct. Press Dis Press.

75

Dis. Temp.

80

Dis. Press. l )is. Temp

Dis Press

TEMPERATURE

(=F)

85

D_s, Temp

Dis. PreSs.

90

Dis Temp.

)m. Press.

95

Dis, Temp

)is

Press.

100

Dis. Temp.

Dis. Press.

105

Dis. Temp.

Dis. Press

)is. Temp.

63

207

155

65

209

160

224

161

67

211

165

226

166

241

166

69

211

175

228

171

243

171

259

172

71

215

177

229

178

246

176

261

176

276

177

233

18!

247

181

263

181

278

181

ii_i_93ii!ii_
.... i ,, ,ri,,

251

185

265

185

280

185

295

_86

7:

268

18o

2B3

190

297

19o

79

272

193

286

193

300

194

314

194

3_7

202

322

203

336

204

325

207

339

208

343

212

73
75

83
85
87

!;_!_t'%! i';_m'_'
_! _

_

89

* Note: All pressures

are listed in psig, and all temperatures
-Shaded Boxesindicate
flooded conditions

I

in °F.
I

I

-RatedDesignValues.
SuctionPressurewillbelowerthandesignvalueifindoorair
flow, entering dry bulb, or entedng wet bulb temperatures are lower than design,

- Discharge temperaturesgreater
values indicate an undercharged

than chaded
system.

12 SEER - Refrigerant

Charging Tables

2 Ton
TEMPERATURE

OUTDOOR
70
Suct

Press

Dis. Press.

75

DIS, Temp.

DIS Press.

80

Dis. Temp.

DIS. Press.

I"FI

85

)is. Temp

Dis. Press.

90

Dis. Temp.

Dis. Press

95

Dis, Temp.

100

3is Press.

Dis. Temp.

)isPress.

105

Dis. Temp.!

DIS. Press.

D_Temp

72

170

123

74

172

129

186

132

76

174

134

189

137

203

140

78

175

142

1gl

142

205

145

219

149

80

179

144

192

148

207

150

221

153

236

157

196

151

209

155

224

158

23B

161

213

158

226

162

240

165

254

169

B6

229

188

243

189

256

173 iiii_!

88

233

169

246

173

260

177

272

180

250

177

263

1B1

276

184

266

185

280

189

293

283

193

297

197

300

201

B2
B4

90
92
94

;-_;it

96

_i_ _B_'_!
_i_1_

_ii_ ii!i_!_8_:
192

98

2-1/2 Ton
OUTDOOR
70

75

Ois. Temp,

Dis. Temp.

)is. Press

73

172

125

75

174

131

189

132

77

175

136

191

137

206

139

79

176

146

193

142

208

B1

180

148

194

150

210

197

153

85

Dis. Press

TEMPERATURE

(=F)

85

Suct. Pres!

83

)is, Press

BO
Dis. Temp

90
Dis. Press.

95

Dis Press

]is, Temp.

Dis Temp,

!44

223

145

14B

225

150

240

151

212

154

227

154

242

155

215

157

100

Dis Press.

Dis. Temp.

Dis Press,

105

Dis,Temp.

)is. Press.

Dis Temp,

22_

ls9

2,_

180

2s9

161

B7

233

162

247

164

261

165

89

236

166

251

168

265

169

27B

170

254

172

26B

173

282

175

272

177

286

179

300

180

289

183

304

185

307

189

91
93
95
97

_" '_}_ii!

_

99
* Note:
c_a

All pressures

are listed in psig.

and all temperatures

-ShadedBoxesindicate
flooded conditions

I

in °F.
I

I -RatedDesignValues.
flow, entering
dry

bulb,

SuctionPressurewillbelowerthandesignvalueifirldoorair
or entering
wet bulb tern peratures
are lower

than design,

-Dischargetemperaturesgreaterthanchaded
values indicate an undercharged
system.

12 SEER - Refrigerant Charging Tables
3 Ton
OUTDOOR
70

75

Dis. Temp

Dis Press.

80
3_s. Temp

D=s,Press

90

Dis. Temp.

Dis. Press

95
Dis. Press.

Dis. Temp.

)is

Press,

105

70

172

130

72

174

135

1B9

134

74

176

140

191

139

206

139

76

175

152

193

144

208

143

223

143

78

179

154

193

153

210

148

225

147

240

196

156

211

155

227

152

242

151

214

158

228

157

244

155

258

154

84

232

161

246

159

261

158

86

235

164

250

163

264

162

277

161

253

167

267

166

282

1B6

271

171

285

170

299

169

288

174

303

173

306

178

88

Dis,Temp

100

3is Press.

82

Dis. Press.

I'F)

Suct. PresJ

B0

Dis Temp.

TEMPERATURE
85

Dis. Tgmp.

)is.

Press.

Dis,Temp

146

90
92

!:_

_i_

94

;

96

3-1/2 Ton
OUTDOOR
70
Suct

Pres=

]is

Press

75

Dis. Temp

)is

Press.

80

DIS Temp,

Dis. Press.

TEMPERATURE

('F)

85

Dis Temp.

Dis. Press.

90
)is. Temp.

Dis. Press

95

3is Temp.

100

Dis. Press.

Dis. Temp.

Dis. Press

105

Dis,Temp

)is. Press.

Ois. Temp

69

169

137

71

171

143

186

142

73

174

148

188

147

204

146

75

175

155

191

152

206

151

221

150

77

179

_57

193

157

208

156

223

155

238

154

196

160

210

_61

225

160

240

159

214

164

228

164

242

163

257

162

83

231

167

245

167

259

167

85

235

171

249

171

263

171

276

17o

252

175

266

175

280

174

269

179

283

179

297

178

287

183

301

182

304

187

79
81

_i_ _
t

87
89
91
93

P_
ff

_i_:_,_,_
;_ _?

95

* Note: All pressures

are listed in psig. and all temperatures
-Shaded Boxesindicate
flooded conditions

I

in °F.
I

I - Rated Design Values. Suction Pressure will belower than design value if indoor air
flow, entedng dry bulb, or entering wet bulb temperatures
are lower than d esign,

- Discharge temperatures greater than charted
values indicate an undercharged system,

12 SEER - Refrigerant

Charging Tables

4 Ton
OUTDOOR
70

75

Dis. Temp.

Dis. Temp

(°F)

]is

Temp.

Dis. Press.

]is. Temp.

Dis. Press.

100

135

70

175

140

191

141

72

178

146

193

146

208

146

74

178

155

195

151

211

151

226

151

76

181

158

196

158

213

156

228

156

243

156

199

161

214

161

230

160

246

161

218

165

232

165

248

165

263

165

82

236

169

250

169

265

169

84

239

172

254

173

268

173

282

173

_

257

177

272

177

286

178

_,;_:_

275

181

290

182

305

182

293

186

308

187

311

191

_2_

Dis. Temp.

Dis. Press

105

173

88

DIS. Press.

95

68

86

]is, Temp

90

)is. Press

80

Dis. Press.

TEMPERATURE
85

Suct. Pres!

78

]is. Press.

80

)is. Temp.

Dis. Press.

Dis. Temp.

1_

90
92

_;;
_

;
?"

94

* Note: All pressures
_

_::

I _,

]

are listed in psig. and all temperatures
-Shad_lBoxesindicate
flooded conditions

I

'

in °F.
]

I -RatedDesignValues.
SuctionPressurewillbelowerthandesignvalueifindoorair
flow, entering dry bulb, or entering wet bulb tern peratures are lower than design,

-Dischargetemperaturusgreaterthanchaded
values indicate an undercharged system.

INSTALLER
PLEASE LEAVE THESE
INSTALLATION
INSTRUCTIONS
WITH THE HOMEOWNER.

IIIIIIIIIIIIIIIIIIII

708298A(Replaces 7082980)

Specifications and illustrations subject to change
without notice and without incurring obligations.

708298A

Prlnted
inU.S.A.(11/03)



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 16
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Thu Apr 05 10:19:28 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu