NORDYNE Package Units(both Units Combined) Manual L0809124

User Manual: NORDYNE NORDYNE Package Units(both units combined) Manual NORDYNE Package Units(both units combined) Owner's Manual, NORDYNE Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 16

DownloadNORDYNE  Package Units(both Units Combined) Manual L0809124
Open PDF In BrowserView PDF
13 SEER
Single Package Air Conditioner

Single Package Air Conditioner

Read this owner information to become familiar with the capabilities and use
of your appliance. Keep this with literature on other appliances where you
have easy access to it in the future. If a problem occurs, check the instructions
and follow recommendations
given. If these suggestions don't eliminate your
problem, call your installing contractor or distributor in your area.

INTRODUCTION
Most any air conditioner will keep you cool. Our air conditioner was designed to do
it efficiently. Efficiency means less cost to you while keeping you comfortable.
WHY YOUR

AIR CONDITIONER

WORKS

SO WELL,

coil. Moisture

SO QUIETLY

1.

Air is cooled by a large evaporator
this same coil.

is also removed from the air by

2.

Air is then delivered through the main duct, via registers, into your home.

3.

Return air is drawn through the return register.

4.

This air enters the unit, passes through the evaporator coil, is cooled and dehumidified. Then the cycle begins again.

SECTION 1.
OWNER iNFORMATiON

make sure it's working right, clean or change
filters and make any needed adjustments.

OPERATING

In addition, follow these simple rules:
1. Never run your system without filter. If you
do, the cooling coils will get dirty and may
become clogged.
2. Set your thermostat at the comfort level you
wish -- and then leave it alone. Let it control

iNSTRUCTiONS

ToTurn On Air Conditioner
ff you have a heating/cooling
thermostat:
1. Set the system switch to "Cool."
2. Set the thermostat at the temperature level
you desire.
3. Turn the power on. Your air conditioner
should start as soon as room temperature
rises above the setting on the thermostat.
ff you have one thermostat
for heating
and another for cooling, they must be
interlocked
to prevent
simultaneous
operation (See Figure 1):
1.
2.
3.
4.

Turn the heating thermostat to its lowest
possible setting.
If the cooling thermostat has an "On/Off"
switch, turn it "On."
Set the cooling thermostat to the desired
temperature.
Turn the power on. Your air conditioner
should start when room temperature exceeds the thermostat setting.

the operation of the air conditioning system.
If you get chilly, turn it up a degree at a time
until comfort is restored.
3.

4.

5.

ff you have one thermostat
for heating
and another for cooling, they must be
interlocked
to prevent
simultaneous
operation (See Figure 1):
1.
2.
3.

Turn your cooling thermostat "Off" or to its
highest setting.
Turn the heating thermostat to the desired
temperature.
If you are turning your air conditioner off for
the winter or an extended period, shut off
the power to the air conditioner.

BEFORE YOU CALL A SERVICEMAN
Let your serviceman check your system at the
start of each air conditioning season. He will
2

expect a dramatic drop in temperature, at
least not right away. If your home is hot and
humid, the temperature will drop slowly.
Check your filters every ten days in summer
to see if they are dirty. To keep them clean,
use a mild solution of detergent and water
on washable types. Replace non washable
filters.
Keep your outdoor condenser coil clean.
You can hose it down when it gets dirty.

ff your air conditioner
isn't working:
1. Make sure the fuses are not blown or that
2.

To Shut Off Air Conditioner
ff you have a heating/cooling
thermostat:
1. Turn the system switch to "Heat" or "Off."
2. Turn the thermostat to the desired heating
temperature setting.
3. If you are turning your air conditioner off for
the winter or an extended period, shut off
the power to the air conditioner.

It takes longer for an air conditioner to cool
your dwelling than it does for your furnace
to heat it. So... don't turn the unit on and

3.

4.

your circuit breakers are on.
Seethatyourthermostatissetatthedesired
temperature and that your system's switch
is on "Cool."
For free air flow, make sure your return
register is not covered and that the filter is
clean.
Checkthe outdoor condenser coil and make
sure it is clean and not clogged with grass
or leaves.

If your air conditioner still isn't working, call your
nearest distributor.

Cooling
Thermostat

Furnace
Thermostat

f

)

4_

R()_

R()

()

Double Throw
Double Pole Switch

To Air Conditioner

Figure 1. Thermostat

To Furnace

interlock

System

SECTION

2.

iNSTALLER

Inspecting Equipment: All units are securely
packed at the time of shipment and, upon arrival,
shou Id be carefully inspected for damage. Claims
for damage (apparent or concealed) should be
filed immediately with the carrier.

iNFORMATiON

GENERAL
Read the following
before performing

instructions completely
the installation.

These instructions are for the use of qualified
personnel specially trained and experienced
in the installation of this type of equipment
and related system components. Some states
require installation and service personnel to
be licensed. Unqualified individuals should not
attempt to interpret these instructions or install
this equipment.
The single packaged air conditioners are designed for outdoor installation only and can be
readily connected into the high static duct system
of a home. The only connections needed for
installation are the supply and return ducts, the
line voltage, and thermostat wiring. A complete
air conditioning system typically consists of:
.
.
.
.

Single Package Air Conditioner
Home Fittings Kit
Unit Fittings Kit
Thermostat

SELECTTHE BEST LOCATION FORTHE
AIR CONDITIONING UNIT

iMPORTANT:
THE HOME.
,

DO NOT PLACE UNiT UNDER

Select a solid, level position, preferably on a
concrete slab, slightly above the grade level,
and parallel to the home.
The hot condenser air must be discharged
up and away from the home, and if possible,
in a direction with the prevailing wind.
Do not place the unit in a confined space.
if practical, place the air conditioner where it
and the ducts will be shaded from the after-

.

.

noon sun when the heat load is greatest.
Try to select a site for the unit that is as close
as possible to the proposed return grille location.
Keep in mind that the length of the supply and
return ducts should be kept to a minimum with
no sharp radiused bends.

2.

UNPACKTHE

UNIT

It is recommended that the unit be unpacked
at the installation site to minimize damage due
to handEing.

CHECK

Before any installation is attempted, the cooling load of the area to be conditioned must be
calculated and a system of the proper capacity
selected. It is recommended that the area to
be conditioned
vapor sealed.

1.

.

The single package air conditioner is completely
assembled, factory wired, and factory run tested.
The units are ready for easy and immediate
installation.

PRE-INSTALLATION

INSTALLATION

be completely

insulated

and

The installer should comply with all local codes
and regulations which govern the installation
of this type of equipment. Local codes and
regulations take precedence over any recommendations contained in these instructions.
Consult local building codes and the National
Electrical Code (ANSI CI) for special installation
requirements.
The electrical supply should be checked to determine if adequate power is available. If there
is any question concerning the power supply,
contact the local power company.

CAUTION:
Do not tip the unit on its side. Oil
may enter the compressor
cylinders
and cause starting trouble, if unit has
been set on its side, restore to upright
position
and do not run for several
hours.Then run unit for a few seconds.
Do this three or four times with five
minutes between runs.
a. Remove the bands from around the unit.
b. Unfold the top and bottom cap flanges.
c. Carefully remove the top cap and tube.

DUCT REQUIREMENTS
The supply duct system, including the number
and type of registers, will have much more effect on the performance of an air conditioning
system then any other factor. The duct must be
sufficiently large to conduct an adequate amount
of air to each register.
4.

Figure 2. Minimum
3.

The supply and return fittings are included with
select modeEs. If supplied, the duct fittings are
shipped in the supplyduct.They attach tothe unit
openings with a flange and bead arrangement,
secured with two sheet metal screws. Note: For

Unit Clearances

ease of access, install fitting before positioning
unit in final location.

CLEARANCES

Minimum clearances, as specified in Figure
2, MUST be maintained from adjacent structures to provide room for proper servicing
and air circulation.
Do NOT install unit in a confined

or recessed

area that will allow discharge air from the unit
to re-circulate
into the condenser
air inlet,
through the coil.
Service Access

Clearance:

Blower access panel side .......................... 24"
Electrical compartment access panel side... 12"
Clearance
between overhang
and top of
unit .........................................................
72"
Clearance around condenser coil area to wall
or shrubs (excludes duct panel side) .......... 12"
Minimum clearance to combustible

materials:

Combustible Base (Wood or Class A, B, or
roof Covering material) ...............................
Supply and Return Air Ducts .......................
Duct Connection side ..................................

INSTALLTHE RETURN AND SUPPLYAIR
FITTINGS ON THE UNiT

C
0"
0"
0"

SUPPLY DUCT
Position the supply duct collar, if supplied, so the
edge of the unit opening fits between the flange
and the bead. Overlap the collar ends keeping the
small screw holes underneath. Align the holes in
the crimped area and install one screw.
Note: It may be necessary to loosen the four
screws that hold the transition duct in order to
install the supply fitting. Re-tighten when installation is complete.
Tap collar as necessary to ensure engagement
with unit opening and install second screw.
Tighten first screw. Rotate collar clockwise so
joint is near three o'clock position.
RETURN DUCT
Align the 14" return duct slots with the holes in
the collar and install two screws. Position the

7 RETURN AiR

CUT

Tran

Figure 3. Return and Supply
4

_

FLOOR

_

Air Fittings

Figure 4. Return Air Box

collarovertheopeningandalignthefournotches
in thecollarwiththefourdimplesin the panel.
Usingself-drillingscrews(10-16x.5)attachthe
collarto therearpanel.
5. LOCATINGAND

iNSTALLING
TURN AIR ASSEMBLY

REGISTER
/

AUTOMATIC
WHEN

Figure 5. Supply

Damper

When installing this air conditioning
system in conjunction
with a furnace,

that have an open area equal to or greater than
the 12"x 20" grille furnished. The return air grille
can be placed in the wall of a closet and the air
ducted into the filter box through a boxed-in area
at the closet floor level. Make sure the filter is

a damper

readily accessible.

changer
and asphyxiation
if a damper is not installed.

After determining the location of the return air
opening, start the installation from under the
home by cutting a small hole in the fiber underboard to determine how the floor joist location
will affect cutting the opening needed for the box.
Floor joists generally are located on 16"centers,
leaving 14-3/8" between joists. After measuring
the return air box (approximately 12-1/4" x 141/4"), cut the hole through the floor so that the
box will fit between the floor joists. Care should
be taken when cutting through carpeting to avoid
snags. In most installations it will be necessary to
cut a similar hole in the fiberboard directly under
the hole in the floor. However, if the floor is more
than ten inches deep, it will only be necessary
to cut a hole for the collar on the return air box
or for the insulated duct.
Set the box into the opening and fasten with
screws or nails. Put the filter and return air
grille in place.
LOCATING

AND

iNSTALLING

THE

SUPPLY DAMPER(S)

CAUTION:
When a home is not equipped
with
a make-ready
kit means must be
provided to prevent simultaneous
operation
of the heating and cooling
units. A heat/cool
thermostat
is
available for this purpose.

IS CLOSED
iS OFF

THE RE-

To avoid complications, locate and install the
return air assembly first. The return air box
with grille and filter (Figure 4) should not be
located in heavy traffic areas like hallways or
center of rooms. A good spot is in a corner or
under a table, if a minimum two inch clearance
is available. If desired, the return opening can
be located inside a closet with Iouvered doors

6.

DAMPER
A/C UNiT

nace

base

must

be installed

assembly

air being discharged
exchanger.
Damage

in the fur=

to prevent
around
to the

cold

the heat
heat ex=
may occur

Check with the furnace manufacturer
for damper requirements.
Failure to
install the required furnace damper
may i nvalidate code agency listing and
limited warranty on the furnace.
When locating the supply damper(s), carefully
check floor joists and frame members that could
interfere with the installation of the damper or
flexible duct. Ideally, the damper should be
located in the bottom of the main duct, forward
of center of the home, at least three feet from
the nearest register. The round supply opening
in the slanted side of the damper should face
the side of the home where the air conditioner
is located. To locate the center of the heat duct,
first cut a small hole in the fiberboard below the
duct at the desired location. After locating the
duct center, cut a hole approximately 3/4" larger
than the damper opening in the fiberboard. Cut
a 9-1/8" x 13-1/8" hole in the duct and bend
over all tabs flat on the inside of the heat duct.
After inserting the damper into the duct, bend
over all tabs flat on the inside of the heat duct.
Sea! the opening between the fiberboard
damper or flexible duct.

DUCTING

and

SYSTEM

DUCT REQUIREMENTS
The supply duct system, including the number
and type of registers, will have much more ef-

TYPICAL

APPLiCATiONS

\

SINGLE

DUCT APPLiCATiON

Ref. No.

MULTIPLE

DUCT APPLiCATiON

Description

(_

12"x 20" Return Air

(_

16" x 20" Air Filter

(_)

12" x 20" Grille

(_)

Supply Damper

(_)

14" Diameter Flex Return Duct

(_)

12" Diameter Flex Supply Duct

(_

12" x 12" x 12" "Y" Fitting

Figure 6. Typical Applications

fect on the performance of an air conditioning
system than any other factor. The duct must be
sufficiently large to conduct an adequate amount
of air to each register.
Air ducts should be installed in accordance with
the standards of the National Fire Protection
Association "Standard for Installation of Air
Conditioning and Ventilation Systems" (NFPA
90A), "Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning
Systems" (NFPA 90B), these instructions, and
all applicable codes.

THE AiR CONDITiONiNG
OUTPUT OF THE
SYSTEM WiLL NOT COOLTHE HOME IFTHE
AiR iS LOST TO THE OUTSIDE THROUGH
LEAKS INTHE DUCT SYSTEM. ALSO, DUCTS
WHICH ARE COLLAPSED OR RESTRICTED
BY FOREIGN OBJECTS WiLL PREVENT
ADEQUATE AIR FLOW.
Note: For highly resistive duct systems it may
be necessary to add an additional return air duct
and or supply to achieve maximum performance
and prevent coil icing and refrigerant flood
back.

CONNECTING THE RETURN
AIR FLEXIBLE DUCTS
a.

b.

AND SUPPLY

The supply duct for all units is 12" in diameter. The return duct is 14" diameter for all
air conditioning units.
The flexible ducts can be connected

_ Elbow

to the

corresponding fittings with the clamps provided with the ducts. Note: All connections

c.

d.

e.

f.

should be leak tight or a loss in cooling
capacity will result.
The flexible ducts may be cut to the required
length, see instructions packed with duct.
Keep all ducts as short and straight as possible. Avoid sharp bends.
Ducts may be spliced with sheet metal
sleeves and clamps. (See Ducting Installation Accessories page 6.)
Once the inner duct is connected to the
proper fitting, the insulation and plastic
sleeve should be pulled over the connection
and clamped.
For homes with multiple supply ducts or for
special applications, a Y fitting is available
to divide the supply air so it can be ducted
to different areas of the home for more efficient cooling. Note: TheY fitting should be
insulated for maximum performance.
Model
P3RD

Wire Color/
Speed Tap

Motor
Speed

Air Flow
(0.3 in.WC)

2Ton

2.5 Ton

3Ton

Red

Low

760

Black

High*

1000

Red

Low

760

Black

High*

1000

Red

Low

760

Black

High*

1000

T1

Low

T2
3.5 Ton

1,000

Orange / T3

Medium*

1,140

Red / T4

Med/High*

1,300

T5

High

1,350

T1

Low

1,340

Orange / T2

Med/Low*

1,450

Red / T3

Medium*

1,650

T4

Med/High

1,750

T5

High

1,965

T1

Low

1,340

4 Ton

5 Ton

750

Med/Low

T2

Med/Low

1,450

Orange / T3

Medium*

1,650

Red / T4

Med/High*

1,750

T5

High

1,965

* Factory Setting

Figure 7. Standard Motor Lead Connection

_""

P-Trap

Figure 8. Drain Trap

Blower
Speed
-- For optimum
system
performance and comfort, it may be necessary
to change the factory set speed. See figure 7 for
factory settings. To change the blower speed:
If Standard Motor (2, 2.5 and 3 Ton):
1. Disconnect
all electrical
power to the
unit and remove the service panel.
2. Place the desired blower speed lead on the
"COM" terminal. Use another wire tie (field
supplied) to bundle the remaining motor
leads.
If High Efficiency Motor (3.5, 4, and 5 Ton):
1. Disconnect all electrical power to the unit
and remove the blower panel.
2. Locate the orange and red wires terminated
to the blower motor. The orange wire controls
cooling operation while the red wire controls
heating operation.
3. Verify the required speed from the airflow
data found in figure 7. Place appropriate
wire on the appropriate motor speed tap for
the required airflow point.
Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connections to be sure none loosened during shipping
or installation.

CAUTION'.
To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
any uninsulated
of the unit.

metal

components

Low Voltage
a. Route 24vcontrol wires through the sealing
grommet near the power entrance.
b. Connect the control wires to the leads in
the low voltage area. (See Figure 10).
2.

Figure 9. Power Entry

DRAIN

A 3/4" condensate fitting extends out of the side
of the unit.The drain trap, shipped in the electrical
compartment, must be installed to prevent water
from collecting inside the unit.Thread the elbow
provided with the unit into the drain connection
until hand tight. Install the trap into the fitting and
seal the joint. Make sure it is level. Route the
condensate from the trap to a suitable drain. Any
connecting tubing or hose must have the outlet
below the trap level for proper drainage.

WARNING:
Turn off electrical power before servicing controls. Severe electrical shock
may result unless power is turned off.
Unit must be installed in compliance
with the National Electrical Code (NEC)
and

local

1.

c.

3.

ELECTRICAL

Do not locate near a lamp, kitchen range, direct
sunlight, or in line with air flow from supply
registers.
a.

SERVICE

of ad-

equate size per NEC. Locate the disconnect
within sight of the unit.
Extend leads through power wiring hole
provided. Connect L1 and L2 directly to the
contactor. (See Figure 9).
Ground the air conditioning unit using the
green grounding screw provided in the
control panel.

LOCATING THE THERMOSTAT

Locate the thermostat away from drafts and
slamming doors and place it where there is a free
flow of air. Mount on an inside wall approximately
five feet from the floor.

CONNECTIONS

High Voltage
a. Install a branch circuit disconnect

b.

In the event that a fuse does blow or a breaker
trips, always determine the reason. Do not arbitrarily put in a larger fuse or breaker and do not,
in any case, exceed the maximum size listed on
the data label of the unit.

codes.

ELECTRICAL

PROTECTION

In general, the best fuse or breaker for any air
conditioner is the smallest size that will permit
the equipment to run under normal use and
service without nuisance trips. Such a device,
sized properly, gives maximum equipment
protection. The principal reason for specifying
a time delay type is to prevent nuisance trips
when the unit starts.

Low Voltage

CONDENSATE

OVERCURRENT

Connect Cooling Thermostat:
The cooling thermostat available for use with this
system is equipped with a selector switch.
To shut down the air conditioner, set the
selector switch to the OFF position. Connect the red and yellow wires from the unit
to the R and Y terminals respectively on
the thermostat subbase. Connect the green
wire to the yellow wire at the unit. See the
instruction sheet packed with the thermostat
for detailed methods of mounting.
Note: The cooling-only thermostat must be
connected to an interlock switch to prevent
simultaneous operation of the furnace and
the air conditioner. (See Figure 1, Page 2.)

b.

Connect

the Heat-CooIThermostat:

The

heat-cool thermostat is equipped with a
system H EAT-COOL switch, which provides

4 Wire Heat/Cool Thermostat

Control Wire Leqend
Green

- BJower

2 Wire Cooling Thermostat

SingleStageElectricHeat

ReJay

Red - Transformer
24V
Yellow-

Cooling
Stage

1st

Brown - Heating
Stage

1st

Orange

- Heating
Stage

---_-RED
---_YELLOW

YELLOW

---_GREEN

GREEN

2rid

BROWN

BROWN

ORANGE
Two Stage Electric Heat
---_-RED
---_-YELLOW
---_-GREEN
---_--BROWN
--ORANGE
I

Optional
Outdoor Thermostat
(Field Supplied)

[_

Figure 10. Low Voltage Connections

a positive means of preventing simultaneous operation of the heating and cooling
units. The thermostat is also equipped with
an ON-AUTO fan switch which allows the
home owner to operate the indoor blower
when air circulation is desired.

4.

The air conditioner is shipped without an auxiliary electric heat kit installed. If electric heat is
desired, an accessory Heater Kit must be field
installed. See Specifications Sheet for available
kits and their applications.

Connect the red, yellow, green and brown
low voltage wires to the R or RC, Y, G and
W terminals respectively on the thermostat
base. The black wire is the 24 volt common

Select the correct size heat package for the
installation.
Follow installation instructions provided with
each heater kit.

required on some thermostats. See thermostat instruction sheet for more detailed
information.
Refer to furnace

installation

C.

Installation is most easily accomplished
before making duct or electrical connections.

instructions

for required connections and proper heat
anticipator setting when installing unit with
an external furnace.
if two stage heating is desired,
an
optional outdoor thermostat
may be
installed: Connect the thermostat to the
orange low voltage wire and the W terminal
on the indoor thermostat base (See Figure
10). See the thermostat instructions for
details on setting the outdoor thermostat.

ELECTRIC HEAT PACKAGE (OPTIONAL)

The blower must be set to high speed for
electric heat operation.

SYSTEM
1.

OPERATION

PRE-START

CHECK LIST

The following check list should be observed prior
to starting the unit.
[]

Is the unit level? It should be level or slightly
slanted toward the drain for proper condensate drainage.

[]

Is the unit installed with the proper clearances (See Figure 2)?

[]

Is the wiring correct according to the wiring
diagram and electrical codes?

[]

Are all the wiring connections tight? Check
the condenser fan to make sure it turns

c.

Turn on power supply at the disconnect
switch.

d.

Set the system switch to ON or COOL.
Set the temperature setting to below room
temperature. Verify that the indoor blower,
outdoor fan, and compressor are energized
and the cooling function starts.
Verify that the discharge air grilles are
adjusted and the system is balanced.
Verify that there are no air leaks in the duct
work.

e.

freely.
f.

[]

Is the overcurrent
sized?

[]

protection

properly
g.

Is the thermostat wired correctly?
installed in a proper location?

Is it

h.
i.

.

STAR.UP

PROCEDURE

a.

Set the system
tion.

switch to the OFF posi-

j.

b.

Dial thermostat
go.

setting

k.

10

as high as it will

Verify that the condensate drain is properly
installed and that it functions correctly.
Dial the thermostat higher than room temperature. The unit should stop.
If using a combination heating-cooling thermostat, set to the HEAT position. Proceed
to check for correct furnace operation.
Verify that the furnace controls and burners
or heating elements operate correctly.
Instruct the owner on unit operation, filter
servicing, and proper thermostat operation.

13 SEER - Charging
2
TON
Suct.

70
Dis.

75
Dis.

Dis.

Charts

80
Dis.

Dis.

Dis.

Press, Press. Temp. Press. Temp. Press. Temp.
75
142
133

OUTDOOR TEMPERATURE/°F)
85
90
95
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Press. Temp.

Press. Temp.

Press. Temp.

100
Dis.

105
Dis.

Press. Temp.

Dis.

Dis.

Press. Temp.

77
79

144
147

138
144

157
159

136
141

171

138

81

150

147

161

146

173

143

186

141

83

153

149

164

149

176

148

188

146

200

144

168

152

179

152

190

150

202

148

182

155

193
197

154
158

205
208

152
156

217
219

150
155

200

161

211

160

222

159

233

157

215

164

226

163

237

161

229

167

240

165 _ 251

I 163

244

258
170 I 255

172
I 168

85
87
89
91
93
95
99
97
101

2-1_
TON
Suct.

70
Dis.

75
Dis.

Dis.

80
Dis.

Press. Press. Temp. Press. Temp.
75
143
126

Dis.

OUTDOOR TEMPERATURE/°F)
85
90
Dis.
Dis.
Dis.
Dis.
Dis.

Press. Temp.

Press. Temp.

Press. Temp.

I

95
Dis.

100
Dis.

Press. Temp.

Dis.

105
Dis.

Dis.

Dis.

Press. Temp. Press. Temp.

77

145

131

158

130

79

148

137

161

135

174

134

81
83

149
153

143
146

163
165

140
146

176
178

139
144

189
191

138
143

204

142

168

149

180

148

193

147

206

146

184

152

196
199

151
155

208
211

151
155

221
223

150
154

203

159

215
218

158
162

227
230

158
162

238
242

157
161

234

166

246

166 _ 258

165

249

265
170 I 261

174
169

85
87
89
91
93
95
99
97
101

Refrigerant

Charging

Chart Legend for Cooling

I

Mode of Operation

* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate
flooded conditions

- Rated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

- Discharge temperatures greater than charted
values indicate an undercharged system.

11

13 SEER - Charging Charts - Continued
3
TON
Suct.

70
Dis.

Dis.

Press. Press. Temp.
69
147
140

75
Dis.

Dis.

Press. Temp.

80
Dis.

OUTDOOR TEMPERATURE/°F)
85
90
Dis.
Dis.
Dis.
Dis.
Dis.

Press. Temp.

95
Dis.

Dis.

Press. Temp. Press. Temp. Press. Temp.

100
Dis.

Dis.

Press. Temp.

71

149

145

163

144

73
75

152
152

150
159

166
168

149
154

180
182

147
152

196

151

77

156

161

169

160

184

157

198

155

212

154

173

163

186

162

200

160

215

159

189

166

203
206

165
168

217
219

163
167

231
233

161
166

210

172

223

171

236

170

249

168

226

175

240
243

174
178

253
256

172
177

260

181

100
Dis.

Dis.

79
81
83
85
87
89
91
93

105
Dis.

Dis.

Press. Temp.

I

270

175

273
276

180
184

105
Dis.

Dis.

95

3-1/2
TON
Suct.

70
Dis.

Dis.

Press. Press. Temp.
72
162
127
74
164
133

75
Dis.

Dis.

80
Dis.

OUTDOOR TEMPERATURE/°F)
85
90
Dis.
Dis.
Dis.
Dis.
Dis.

Press. Temp. Press. Temp.

95
Dis.

Dis.

Press. Temp. Press. Temp. Press. Temp. Press. Temp. Press. Temp.

179

135

76

167

138

182

140

196

141

78
80

167
170

148
150

184
184

145
152

199
201

146
151

213
216

148
153

230

154

188

155

202

157

218

157

232

159

206

160

220
223

162
166

235
237

163
167

249
251

165
169

227

169

241

171

255

173

268

175

244

175

258

177

272

179

262

181

276

183 _ 290

185

279

297
188 I 293

194
189

82
84
86
88
90
92
96
94
98

Refrigerant

Charging

Chart Legend for Cooling

I

Mode of Operation

* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate
flooded conditions

--

Rated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

- Discharge temperatures greater than charted
values indicate an undercharged system.

12

13 SEER - Charging Charts - Continued
4

TgN
Suct.

70
Dis.

Dis.

Press. Press. Temp.
71
151
147

75
Dis.

Dis.

Press. Temp.

80
Dis.

OUTDOOR TEMPERATURE (°F)
85
90
95
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.

Press. Temp.

Press. Temp.

Press. Temp.

Dis.

Press. Temp.

100
Dis.

Dis.

Press. Temp.

105
Dis.

Dis.

Press. Temp.

73
75

153
156

152
157

169
171

151
156

187

156

77

157

164

173

161

189

161

204

160

79

160

167

175

167

191

165

206

165

222

164

179

170

193

170

209

169

224

169

197

174

211
215

174
177

226
229

173
177

242
244

173
177

218

181

233

181

247

181

261

180

236

185

251

185

265

185

254

189

269

189 _ 283

I 189

272

290
193 I 287

198
I 193

100
Dis.

Dis.

105
Dis.

Dis.

81
83
85
87
89
91
95
93
97

5
TON
Suct.

70
Dis.

Dis.

Press. Press. Temp.
68
151
151
70
154
156

75
Dis.

Dis.

80
Dis.

OUTDOOR TEMPERATURE/°F)
85
90
Dis.
Dis.
Dis.
Dis.
Dis.

Press. Temp. Press. Temp. Press. Temp.

Press. Temp.

95
Dis.

Dis.

Press. Temp.

I

Press. Temp.

Press. Temp.

168

155

72

156

162

170

160

184

159

74
76

157
161

168
171

172
174

165
171

186
189

164
169

201
203

163
168

217

167

178

174

191

173

205

172

219

171

194

177

208
211

176
180

221
224

175
179

236
238

174
179

215

184

228
231

183
187

241
244

183
187

254
258

182
186

248

191

261

190

274 I

189

265

194

281
278 I

198
194

78
80
82
84
86
88
92
90
94

Refrigerant

Charging

Chart Legend for Cooling

I

Mode of Operation

* Note: All pressures are listed in psig. and all temperatures in °F.

- Shaded Boxes indicate
flooded conditions

Rated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

- Discharge temperatures greater than charted
values indicate an undercharged system.

13

NOTES:

1.
2.
3.
4.

Disconnect all power before servicing.
For supply connections use copper conductors only.
Not suitable on systems that exceed 150 V to ground.
For replacement wires use conductors suitable for 105° C.

1.
2.
3.

Couper le courant avant de faire letretien.
Employez
uniquement
des conducteurs
en cuivre
Ne convient pas aux installations
de plus de 150V

RED

3 AMP
FUSE

Legend
--

Field Wiring
Factory Wiring:
Low Voltage
High Voltage

O

a la terre.

O
L_R_d!

\

BROWN=

COM

PACITOR

RED_"

RELAY

CONTROL

3

BOARD

"13
(Q
c

BLOWER
MOTOR

L_WBITE

m _GREEN---_
YELLOW

S

mWHITE

=_-

BLUEm_-

TRANSFORMER

_--

RED
WHITE_

i

THERMOSTAT

_

REDi

_

m_
m

--Z

5"
(Q

RED
WHITE

BLACK _

L2

COMPRESSORI (
THERMOSTAT--GREEN--

(Q

CONTACTOR

_):,

OUTDOOR

THERMOSTAT

iyELLOW

III

.o .

TTTBLUE_

_J

___

===L

o
el
el
4_

_BROWN--Lj
ORANGE

--

liii_:L_OR

YELLOW

_BLACK_

ORANGE=_-_j

FANMOTOR

-'3

1

Packaged Air Conditioner
NOTES:

=Single Phase

1,
2.
3.
4.

Disconnect all power before servicing,
For supply connections
use copper conductors
only.
Not suitable on systems
that exceed 150 V to ground,
For replacement
wires use conductors
suitable for l05°

5.

See installation

instructions

for blower

motor

airflow

1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs
en cuivre
3. Ne convient pas aux installations de plus de 150 V a la terre.

Legend
Field Wiring

C.

settings.

OUTDOOR
MOTOR

Factory Wiring:
Low Voltage
High Voltage

FAN

r_
ORANGE'_

BLACK
/

LOAD
RELAY

BLOWER
MOTOR
--

--

RED

___

RED

1

ORANGE_:

...... _

GREEN/YELLOW

_/

BLACK '%-

(£:2
¢.==_
FO

FRANSFORMER I

(Q

'

THERMOSTAT--

(Q

THERMOSTAT--

GREEN

RED

24V

_

ACK--

/

COMPRESSOR
CONTACTOR

--

_-

BLUE
RED_

3 AMP
FUSE
\._-_

--

RED-

THERMOSTAT--YELLOW

LOW

-.4
..=_
0

PRESSURE
SWITCH

COMPRESSOR

O0

CAPACITOR
YELLOW
_

DUAL
BLACK'

..=_
O1

WB'TE
--1

RED
F

iNSTALLER
PLEASE LEAVE THESE
iNSTALLATiON
iNSTRUCTiONS
WiTH THE HOMEOWNER.

III
IIIIIllllllllilllll
IllII!

708548B (Replaces 708548A)

O'Fallon, MO

NOR_IE

708548B

Specifications and illustrations subject
to change without notice and without
incurring obligations.
Printed in U.S.A. (01/07)



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 16
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Thu Sep 18 04:25:10 2008
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu