Napoleon Fireplaces Quality Bgd40 N Users Manual W415 0299 BGD40.pmd

BGD40-N to the manual 8344b49d-2afc-41fb-9a47-e41bdd7caa7d

2015-02-05

: Napoleon-Fireplaces Napoleon-Fireplaces-Quality-Fireplaces-Bgd40-N-Users-Manual-493348 napoleon-fireplaces-quality-fireplaces-bgd40-n-users-manual-493348 napoleon-fireplaces pdf

Open the PDF directly: View PDF PDF.
Page Count: 36

DownloadNapoleon-Fireplaces Napoleon-Fireplaces-Quality-Fireplaces-Bgd40-N-Users-Manual- W415-0299 - BGD40.pmd  Napoleon-fireplaces-quality-fireplaces-bgd40-n-users-manual
Open PDF In BrowserView PDF
1
INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS

GAS FIRED - DIRECT VENT MILLIVOLT SYSTEM
INSTALLATION AND OPERATION INSTRUCTIONS FOR
MULTI-VIEW DECORATIVE FIREPLACE
NATURAL GAS MODEL
PROPANE GAS MODEL

BGD40-N
BGD40-P

CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS

WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Immediately call your gas supplier from
• Do not try to light any appliance.
a neighbor's phone. Follow the gas sup• Do not touch any electrical switch.
plier's instructions.
• Do not use any phone in your building.
• If you cannot reach your gas supplier,
call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.

R-2000

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.napoleonfireplaces.com • ask@napoleon.on.ca
W415-0299 / C / 03.12.03

2
Pg 3-5

INTRODUCTION

TABLE of CONTENTS
Vertical Venting Installation
Flexible Vent Components
Fireplace Vent Connection
Rigid Vent Components
Gas Supply Connection

Warranty
General Instructions
General Information
Care of Glass & Plated Parts
Dimensions

6-13

14-15

22-25

VENTING

Framing
Bar / Countertop Installation
Brick Panel Installation
Facing

16

OPEN END INSTALLATION PROCEDURE
Framing
Brick Panel Installation
Facing

17

Mantle Height Locations
Log Placement
Logo Placement
Louvre Installation
Door & Louvre Installation
End Door Installation

Vent Lengths
Air Terminal Installation
Venting Application Flow Chart
Typical / Special Vent Installations
Venting Options

PENINSULA INSTALLATION PROCEDURE

SEE-THRU INSTALLATION PROCEDURE
Framing
Brick Panel Installation
Facing

18

VENT FRAMING DIMENSIONS

19-22

VENTING SPECIFICS
Wall and Ceiling Protection
Horizontal Venting Installation

FINISHING

26

OPTIONAL BLOWER INSTALLATION

27

OPERATION / MAINTENANCE
Operating Instructions
Maintenance

28

ADJUSTMENTS
Pilot Burner Adjustment
Venturi Adjustments
Restricting Vertical Vents

29-30 REPLACEMENTS

31

Ordering Replacement Parts
Replacement Parts
Vent Kits
Terminal Kits

ACCESSORIES

32-33 TROUBLE SHOOTING GUIDE

PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
WARNING
• Do not burn wood or other materials in this fireplace.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay
away to avoid burns or clothing ignition. Supervise young children when they are in the same room as the
fireplace.
• Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
• Clothing or other flammable material should not be placed on or near the fireplace.
• Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the fireplace
and venting system are kept clean. The fireplace and its venting system should be inspected before use and at
least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. The fireplace area must be kept clear and free from combustible materials,
gasoline and other flammable vapours and liquids.
• Under no circumstances should this fireplace be modified.
• This fireplace must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect
the fireplace and to replace any part of the control system and any gas control which has been under water.
• Do not operate the fireplace with the glass door removed, cracked or broken. Replacement of the glass should be
done by a licensed or qualified service person.
• Do not strike or slam shut the fireplace glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
W415-0299 / C / 03.12.03

3
NAPOLEON gas fireplaces are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certificate.
NAPOLEON products are designed with superior components and materials, assembled by trained craftsmen
who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test
station. The complete fireplace is thoroughly inspected by a qualified technician before packaging to ensure that
you, the customer, receives the quality product that you expect from NAPOLEON.
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY

The following materials and workmanship in your new NAPOLEON gas fireplace are warranted against defects for as long as you own the fireplace. This covers: combustion chamber,
heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakage
only), gold plated parts against tarnishing, porcelainized enamelled components and aluminum
extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are
covered and NAPOLEON will provide replacement parts free of charge during the first year of
the limited warranty.
Labour related to warranty repair is covered free of charge during the first year. Repair work,
however, requires the prior approval of an authorized company official. Labour costs to the
account of NAPOLEON are based on a predetermined rate schedule and any repair work must
be done through an authorized NAPOLEON dealer.

CONDITIONS AND LIMITATIONS
NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the
warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with the
product and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify this
warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel
parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.
NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will replace
or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated in
accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President's Limited Lifetime Warranty, NAPOLEON may, at its discretion, fully discharge all obligations with respect to this warranty by refunding
to the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not
covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event
extend to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product,
its components or accessories are excluded.
NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible for:
over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging
chemicals or cleaners will not be the responsibility of NAPOLEON.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card
must be returned within fourteen days to register the warranty.
NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.

ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED
TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD.
W415-0299 / C / 03.12.03

4
INTRODUCTION
GENERAL INSTRUCTIONS

GENERAL INFORMATION

THIS GAS FIREPLACE SHOULD BE INSTALLED AND
SERVICED BY A QUALIFIED INSTALLER to conform with
local codes. Installation practices vary from region to region and it is important to know the specifics that apply to
your area,
for example: in Massachusetts State:

FOR YOUR SATISFACTION, ALL BURNER ASSEMBLIES
HAVE BEEN TEST-FIRED TO ASSURE THEIR OPERATIONS AND QUALITY! Maximum input is 30,000 BTU/h
for natural gas and propane. When the fireplace is installed
at elevations above 4,500ft, and in the absence of specific
recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be reduced
at the rate of 4% for each additional 1,000ft. Maximum output for natural gas is 20,400 BTU/hr at an efficiency of 68%
with the fan on.
Minimum inlet gas supply pressure is 4.5 inches water
column for natural gas and 11 inches water column for
propane. Maximum inlet gas pressure is 7 inches water
column for natural gas and 13 inches water column for
propane. Manifold pressure under flow conditions is 3.5
inches water column for natural gas and 10 inches water
column for propane.
This fireplace is approved for bathroom, bedroom and bedsitting room installations and is suitable for mobile home
installation
NO EXTERNAL ELECTRICITY (110 VOLTS OR 24 VOLTS) IS
REQUIRED FOR THE GAS SYSTEM OPERATION. Expansion / contraction noises during heating up and cooling
down cycles are normal and are to be expected.
If utilizing one of Wolf Steel's trim or surround kits, follow
the framing instructions on page 14 and the finishing instructions on page 23, for removal of the top extension.

• The fireplace damper must be removed or welded in the open
position prior to installation of a fireplace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or
bathroom unless the unit is a direct vent sealed combustion
product.
• WARNING: This product must be installed by a licensed plumber
or gas fitter when installed within the commonwealth of
Massachusetts.

In absence of local codes, install to the current CAN/CGA B149 Installation Code in Canada or to the National Fuel
Gas Code, ANSI Z223.1, and NFPA 54 in the United States.
Mobile home installation must conform with local codes.
In the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA Z240 MH
Series in Canada or the manufactured home construction
and safety standard, Title 24 CFR, part 3280, or the Fire
Safety Criteria for manufactured home installations, Sites
and Community Standard ANSI/NFPA 5OIA in the United
States.
Purge all gas lines with the glass door of the fireplace
open. Assure that a continuous gas flow is at the burner
before closing the door.
Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition.
The fireplace and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated
from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal to or
less than 1/2 psig (3.5 kPa).
When the fireplace is installed directly on carpeting, vinyl
tile or other combustible material other than wood flooring,
the fireplace shall be installed on a metal or wood panel
extending the full width and depth.
If the optional heat circulating blower is installed, the blower
must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use
the current CSA C22.1 CANADIAN ELECTRICAL CODE in
Canada or the ANSI/NFPA 70 NATIONAL ELECTRICAL
CODE in the United States.
Minimum clearance to combustible construction from fireplace and vent surfaces:
sides, back, bottom, and top
0 inches
vent pipe
1 inch
recessed depth (corner installation) 25¼ inches

W415-0299 / C / 03.12.03

CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean these parts. Buff
lightly with a clean dry cloth. The glass is 3/16" tempered
glass available from your Napoleon / Wolf Steel Ltd. dealer.
Do not substitute materials.
If the door glass should crack or break, do not operate the
fireplace. Replace only with a door assembly certified with
the fireplace. See DOOR, LOUVRE AND TRIM INSTALLATION for removal and replacement details. Clean the glass
after the first 10 hours of operation with a recommended
gas fireplace glass cleaner. Thereafter clean as required.
Do not clean glass when hot!
If the glass is not kept clean permanent discolouration
and / or blemishes may result.

Provide adequate ventilation air. Provide adequate
accessibility clearance for servicing and operating
the fireplace. Never obstruct the front opening of
the fireplace.
For safe and proper operation of the fireplace follow
the venting instruction exactly.
Deviation from the minimum vertical vent length can
create difficulty in burner start-up and/or carboning.
Provide a means for visually checking the vent connection to the fireplace after the fireplace is installed.
In order to avoid the possibility of exposed
insulation or vapour barrier coming in contact
with the fireplace body, it is recommended that
the walls of the fireplace enclosure be “finished”
(ie: drywall/sheetrock), as you would finish any
other outside wall of a home. This will ensure
that clearance to combustibles is maintained
within the cavity.

5
Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated
with the insulation wrapped in a protective sleeve
to minimize condensation.

Objects placed in front of the fireplace must be kept
a minimum of 48" away from the glass front faces of
the unit.

DIMENSIONS
PENINSULA
FIGURE 1a

OPEN-END
FIGURE 1b

SEE-THRU
FIGURE 1c

W415-0299 / C / 03.12.03

6
VENTING
VENTING LENGTHS
Use only Wolf Steel or Simpson Dura-Vent Model DV-GS
venting components. Minimum and maximum vent lengths,
for both horizontal and vertical installations, and air terminal locations for either system are set out in this manual
and must be adhered to. For Simpson Dura-Vent, follow
the installation procedure provided with the venting components.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / flexible components with the following termination kits: WALL TERMINAL KIT GD422, or
1/12 TO 7/12 PITCH ROOF TERMINAL KIT GD410, 8/12 TO
12/12 ROOF TERMINAL KIT GD411, FLAT ROOF TERMINAL KIT GD412 or PERISCOPE KIT GD401 (for wall penetration below grade). With flexible venting, in conjunction
with the various terminations, use either the 5 foot vent kit
GD420 or the 10 foot vent kit GD430.
Wolf Steel rigid and flexible venting systems must not
be combined.
Wolf Steel and Simpson Dura-Vent venting systems
must not be combined.
These vent kits allow for either horizontal or vertical venting
of the fireplace. The maximum allowable horizontal run is
20 feet. The maximum allowable vertical vent length is 40
feet. The maximum number of 5" vent connections is two
horizontally or three vertically (excluding the fireplace and
the air terminal connections) when using aluminum flexible venting.
For optimum flame appearance and fireplace performance, keep the vent length and number of elbows to a
minimum.

W415-0299 / C / 03.12.03

The air terminal must remain unobstructed at all times.
Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged.
Purge all gas lines with the glass door of the fireplace
open. Assure that a continuous gas flow is at the burner
before closing the door.
Under extreme vent configurations, allow several minutes
(5-15) for the flame to stabilize after ignition.
Nine (9") inches is the minimum bend radius allowed
for the 8" diameter flexible liner.
For optimum performance it is recommended that all
horizontal runs have a 1 inch rise per foot when using
Napoleon flexible vent components.
A terminal shall not terminate directly above a sidewalk
or paved driveway which is located between two single family dwellings and serves both dwellings. Local
codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or
vertical runs and elbows. Keep it pulled tight. A 1¼" air
gap all around between the inner liner and outer liner is
required for safe operation. Use a firestop when penetrating interior walls, floor or ceiling.
Horizontal runs may have a 0 inch rise per foot in all
cases using SIMPSON DURA-VENT or NAPOLEON
RIGID OR FLEXIBLE venting components when venting.
A clearance to combustibles of 1" all around the vent
pipe is required.

7
AIR TERMINAL INSTALLATIONS

FIGURE 2

INSTALLATIONS

CANADIAN

U.S.A.

A

12 INCHES

12 INCHES

B

12 INCHES

9 INCHES

C

12 INCHES*

12 INCHES*

D

18 INCHES**

Vertical clearance to ventilated soffit located above the terminal within
18 INCHES** a horizontal distance of 2 feet from the centerline of the terminal.

E

12 INCHES**

12 INCHES** Clearance to unventilated soffit.

F

0 INCHES

0 INCHES

0 INCHES***

0 INCHES***

Clearance to an inside non-combustible corner wall or protruding
non-combustible obstructions (chimney, etc.).

2 INCHES***

2 INCHES***

Clearance to an inside combustible corner wall or protruding combustible obstructions ( vent chase, etc.).

H

3 FEET

3 FEET****

Clearance to each side of the centerline extended above the meter
/ regulator assembly to a maximum vertical distance of 15ft.

I

3 FEET

3 FEET****

Clearance to a service regulator vent outlet.

J

12 INCHES

9 INCHES

Clearance to a non-mechanical air supply inlet to the building or a
combustion air inlet to any other appliance.

K

6 FEET

3 FEET†

L

7 FEET‡

7 FEET****

M

12 INCHES††

N

16 INCHES

O

2 FEET†*

G

*
**
***
****
****
†
‡
††
†*

Clearance above grade, veranda porch, deck or balcony.
Clearance to windows or doors that open.
Clearance to permanently closed windows.

Clearance to an outside corner wall.

Clearance to a mechanical air supply inlet.
Clearance above a paved sidewalk or paved driveway located on
public property unless fitted with a heat shield kit GD-301.

12 INCHES**** Clearance under a veranda, porch, deck or balcony.
Clearance above the roof.
16 INCHES
2 FEET†*

Clearance from an adjacent wall including neighbouring buildings.

Recommended to prevent condensation on windows and thermal breakage
It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.
The periscope GD-201 requires a minimum 18 inches clearance from an inside corner.
This is a recommended distance. For additional requirements check local codes.
Three feet above if within 10 feet horizontally.
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single fa
dwellings and serves both dwellings.
Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
Recommenced to prevent recirculation of exhaust products. For additional requirements check local codes
W415-0299 / C / 03.12.03

8
VENTING APPLICATION FLOWCHART

HORIZONT
AL
HORIZONTAL
ATION
TERMINA
TERMIN

vertical rise
is equal to
or greater
than the
horizontal
run

horizontal
run + vertical rise to
maximum
of 40 feet

vertical rise
is less than
horizontal
run

horizontal
run + vertical rise to
maximum of
24.75 feet

4.2 times
the vertical
rise equal to
or greater
than
the
horizontal
run

W415-0299 / C / 03.12.03

VER
TICAL
VERTICAL
ATION
TERMINA
TERMIN

vertical rise
is equal to
or greater
than the
horizontal
run

horizontal
run + vertical rise to
maximum
of 40 feet

vertical
rise is less
than horizontal run

horizontal
run + vertical rise to
maximum
of 40 feet

3 times the
vertical rise
equal to or
greater
than
the
horizontal
run

9
TYPICAL VENT INSTALLATIONS
When terminating
vertically, the vertical
rise is a minimum 34
inches and a maximum 40 feet above
the fireplace. FIGURE
3b.

FIGURE 3a

When venting, the horizontal run must be kept to a minimum of 10 inches or a maximum of 20 feet. If a 20 foot
horizontal run is required, the fireplace must have a minimum vertical rise immediately off the fireplace of 57 inches.
FIGURE 3a.

FIGURE 3b

SPECIAL VENT INSTALLATIONS
PERISCOPE TERMINATION
Use the GD401 periscope kit to locate the air termination
above grade. The periscope must be installed so that when
final grading is completed, the bottom air slot is located a
minimum of 12 inches above grade. The maximum allowable vent length depends on the model of fireplace, as
illustrated.

FIGURE 4

W415-0299 / C / 03.12.03

10
DEFINITIONS
for the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT - total of both horizontal vent lengths (HR) and offsets (HO) in feet
HR - combined horizontal vent lengths in feet
*) in
HO - offset factor: .03(total degrees of offset - 135°*
feet
VT - combined vertical vent lengths in feet

ELBOW VENT LENGTH VALUES
feet
0.03
0.45
0.9
1.35
2.7

1°
15°
30°
*
45°*
*
90°*

inches
0.5
6.0
11.0
16.0
32.0

* the first 45º and 90° offset has a zero value and is
shown in the formula as -45° and -90º respectively or
-135º when combined.

HORIZONTAL TERMINATION
when (HT) < (VT)
Simple venting configuration (only one 45º and 90° elbow)

90°

For vent configurations requiring more than one 45º and
90° elbow, the following formulas apply:

Formula 1: HT < VT
Formula 2: HT + VT < 40 feet
Example 1:

90°

FIGURE 5

45º

H2

V1
FIGURE 6

45º
H1

90°

HT - total of both horizontal vent lengths (HR) and offsets
(HO) in feet

REQUIRED
VERTICAL
RISE IN FEET
(VT)

CALCULATED HORIZONTAL VENT RUN
PLUS OFFSETS IN FEET (HT)
The shaded area within the lines represents acceptable
values for HT and VT .

V1 = 8 ft
VT = V1 = 8 ft
H1 = 2.5 ft
H2 = 2 ft
HR = H1 + H2 = 2.5 + 2 = 4.5 ft
HO = .03(one 45º elbow + two 90º elbows - 135º)
=0.3(225-135º) = 2.7ft
HT = HR + HO = 4.5 + 2.7 = 7.2 ft
HT + VT = 7.2 +8 =15.2ft
Formula 1:
Formula 2:

HT < VT
7.2 < 8
HT + VT < 40 feet
15.2 < 40

Since both formulas are met, this vent configuration is acceptable.

W415-0299 / C / 03.12.03

11
HORIZONTAL TERMINATION
when (HT) > (VT)
Simple venting configuration (only one 45º and 90° elbow)

FIGURE 7

Example 2:

90°
FIGURE 8

See graph to determine the required vertical rise VT for the required
horizontal run HT.

H4

H3
45°
H1

V1

H2

90°

90°

REQUIRED
VERTICAL
RISE IN
INCHES (VT)

V1
VT
H1
H2
H3
H4
HR
HO
HT
HT + VT

= 4 ft
= V1 = 4 ft
= 2 ft
= 1 ft
= 1 ft
= 1.5 ft
= H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1. 5 = 5.5 ft
= .03(one 45º elbow + three 90º elbow -135º)
=.03(315-135)=5.4ft
= HR + HO = 5.5 +5.4 = 10.9 ft
= 10.9 + 4 = 14.9 ft

Formula 1: HT < 4.2 VT

4.2 VT = 4.2 x 4 = 16.8 ft

10.9 < 16.8

Formula 2: HT + VT < 24.75 feet
14.9 < 24.75
HORIZONTAL VENT RUN PLUS OFFSETS IN FEET (HT)

The shaded area within the lines represents acceptable
values for HT and VT .

Since both formulas are met, this vent configuration is acceptable.

For vent configurations requiring more than one 45º and
90° elbow the following formulas apply:

Formula 1: HT < 4.2 VT
Formula 2: HT + VT < 24.75 feet

W415-0299 / C / 03.12.03

12
VERTICAL TERMINATION
when (HT) < (VT)

Example 3:

Simple venting configurations

FIGURE 9

V2

FIGURE10

H2

90°
45°

45°

H1

V1

90°

90°
See graph to determine the required vertical rise VT for the
required horizontal run HT.
V1
V2

= 5 ft
= 10 ft

VT
H1
H2
HR
HO

= V1 + V2 = 5 + 10 = 15 ft
= 3 ft
= 2.5 ft
= H1 + H2 = 3 + 2.5 = 5.5 ft
= .03(one 45º elbow + three 90º elbows - 135º)
= .03(45+90+90+90-135)=5.4
HT
= HR + HO = 5.5 + 5.4 = 10.9 ft
HT + VT = 10.9 + 15 = 25.9 ft

REQUIRED VERTICAL RISE IN
FEET (VT)

HT < V T
10.9 < 15
Formula 2: HT + VT < 40 feet
25.9 < 40
Since both formulas are met, this vent configuration is acceptable.
Formula 1:

HORIZONTAL VENT RUN
PLUS OFFSETS IN FEET (HT)

The shaded area within the lines represents acceptable
values for HT and VT.
For vent configurations requiring more than one 45º and
one 90° elbow , the following formulas apply:

Formula 1: HT < VT
Formula 2: HT + VT < 40 feet

W415-0299 / C / 03.12.03

13
VERTICAL TERMINATION
when (HT) > (VT)
Simple venting configurations

V1
V2

= 1 ft
= 1.5 ft

VT
H1
H2
HR
HO

= V1 + V2 = 1 + 1.5 = 2.5 ft
= 6 ft
= 2 ft
= H1 + H2 = 6 + 2 = 8 ft
= .03(one 45º elbow + three 90º elbow - 135º)
= .03(45 + 90 + 90 + 90 - 135) = 5.4 ft
HT
= HR + HO = 8 + 5.4 = 13.4 ft
HT + VT = 13.4 + 2.5 = 15.9 ft

FIGURE 11

HT < 3VT
3VT = 3 x 2.5 = 7.5 ft
13.4 > 7.5
Since this formula is not met, this vent configuration is
unacceptable.
Formula 2:
HT + VT < 40 feet
15.9 < 40
Since only formula 2 is met, this vent configuration is unacceptable and a new fireplace location or vent configuration
will need to be established to satisfy both formulas.
Formula 1:

See graph to determine the required vertical rise VT for the
required horizontal run HT.
REQUIRED
VERTICAL
RISE
IN
FEET (VT)

Example 5:

90°

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (HT)

45°

The shaded area within the lines represents acceptable
values for HT and VT.

V1
V2

Example 4:

45°

90°
H1

V1

H2

90°
FIGURE 12

V2
90°

V1
90°

For vent configurations requiring more than one 45º and
one 90° elbow , the following formulas apply:

Formula 1: HT < 3VT
Formula 2: HT + VT < 40 feet

H1

V2

H2

H3
90°

45°
FIGURE 13

= 1.5 ft
= 8 ft

VT
H1
H2
H3
HR
HO

= V1 + V2 = 1.5 + 8= 9.5 ft
= 1 ft
= 1 ft
= 10.75 ft
= H1 + H2 + H3 = 1 + 1 + 10.75 = 12.75 ft
= .03(three 90° elbows + two 45° elbow - 135°)
= .03(90 + 90 + 90 + 45 + 45 - 135) = 6.75 ft
HT
= HR + HO = 12.75 + 6.75 = 19.5 ft
HT + VT = 19.5 + 4.5= 29 ft

HT < 3VT
3VT = 3 x 9.5 = 28.5 ft
19.5 < 28.5
Formula 2:
HT + VT < 40 feet
29 < 40
Since both formulas are met, this vent configuration is acceptable.
Formula 1:

W415-0299 / C / 03.12.03

14
PENINSULA INSTALLATION PROCEDURE
VENTING

COUNTERTOP / BAR INSTALLATION

fer to pages 6-13. All venting must have a minimum clearance of 1" to combustible.

When finishing the fireplace, combustible material may
rest directly on of the top extension. In order to achieve a
countertop or bar type appearance with the minimum height
allowed, framing must be non-combustible and may be
done with metal studding attached to the top extension
sides or the upper frame of the fireplace.

FRAMING
See Page 18 for additional framing dimensions.
Note: In order to avoid the possibility of exposed
insulation or vapour barrier coming in contact with the
fireplace body, it is recommended that the walls of the
fireplace enclosure be “finished” (ie: drywall/sheetrock),
as you would finish any other outside wall of a home. This
will ensure that clearance to combustibles is maintained
within the cavity.
It is best to frame your fireplace after it is positioned and
the vent system is installed. Use 2x4's and frame to local
building codes.

FIGURE 14

A
FIGURE 16

*
A = 22 " minus finishing material thickness each side.
To install the fireplace face flush with the finished wall,
position the framework to accommodate the thickness
of the finished wall.

FIGURE 15

The top extension may be removed if non-combustible
framing is faced with a non-combustible material placed
flush with the front face of the unit and extending from the
top of the unit. (Example: cement board) (not supplied).
Combustible counter / bar tops must maintain a minimum
of 38 inches from the base of the fireplace to the underside
of the top.

FIGURE 17
TOP EXTENTION
TOP OF THE UNIT

NOTE: Wolf Steel trim and/or surround kits will not totally cover the top extension of the fireplace. In order to
obtain a smooth transition from the trim / surround to the
wall, it is recommended that the top extension be removed and the unit be installed following the above procedure.

Care should be taken to maintain sufficient clearance for
the vent installation. A horizontal vent installation requires
a minimum height of 39½" using rigid or 43" using flexible
vent pipe. (including the 1" clearance to combustibles).
W415-0299 / C / 03.12.03

15
BRICK PANEL INSTALLATION

FACING

Install the base panels as illustrated in steps 1-4 . The
side panel sits under the bracket tab. Holding the side
panel in position, bend down the tab to secure. DETAIL 5.

Combustible materials may be installed flush with the front
of the fireplace but must not cover any of the black faceareas of the fireplace. Non-combustible material (brick,
stone or ceramic tile) may protrude in these areas.
It is not necessary to install a hearth extension with this
fireplace system.
When roughing in the fireplace, raise the fireplace to accommodate for the thickness of the finished floor materials, i.e. tile, carpeting, hard wood, which if not planned for
will interfere with the opening of the lower access door and
the installation of many decorative flashing accessories.

FIGURES 18a-e

STEP 1

Objects placed in front of the fireplace should be
kept a minimum of 48" away from the glass front
faces.
FIGURE 19
DRYWALL

DRYWALL

STEP 2

STEP 3

5" MIN

FINISHING
Refer to pages 22-25 for complete instructions regarding
mantle requirements and installations, log placement,
glass door and upper and lower louvre attachments.

STEP 4

RETAINER

STEP 5

DETAIL5
W415-0299 / C / 03.12.03

16
OPEN-END INSTALLATION PROCEDURE
VENTING
Refer to pages 6-13. All venting must have a minimum
clearance of 1" to combustible.

FIGURES 21a-c

FRAMING
See Page 18 for additional framing dimensions.
Note: In order to avoid the possibility of exposed
insulation or vapour barrier coming in contact with the
fireplace body, it is recommended that the walls of the
fireplace enclosure be “finished” (ie: drywall/sheetrock),
as you would finish any other outside wall of a home. This
will ensure that clearance to combustibles is maintained
within the cavity.
It is best to frame your fireplace after it is positioned and
the vent system is installed. Use 2x4's and frame to local
building codes.

STEP 5

RETAINER

FIGURE 20
DETAIL6

STEP 6

FACING

A
A = 25¼" minus finishing material thickness each side.
NOTE: LEFT CORNER UNIT ILLUSTRATED
To install the fireplace face flush with the finished wall,
position the framework to accommodate the thickness
of the finished wall.

BRICK PANEL INSTALLATION
Install the base panels as illustrated in steps 1-4 on page
15. The side panel sits under the bracket tab. Holding the
side panel in position, bend down the tab to secure. DETAIL 6.

Combustible materials may be installed flush with the front
of the fireplace but must not cover any of the black faceareas of the fireplace. Non-combustible material (brick,
stone or ceramic tile) may protrude in these areas.
It is not necessary to install a hearth extension with this
fireplace system.
When roughing in the fireplace, raise the fireplace to accommodate for the thickness of the finished floor materials, i.e. tile, carpeting, hard wood, which if not planned for
will interfere with the opening of the lower access door and
the installation of many decorative flashing accessories.

Objects placed in front of the fireplace should be
kept a minimum of 48" away from the glass front
faces.

FINISHING
Refer to pages 22-25 for complete instructions regarding
mantle requirements and installations, log placement,
glass door and upper and lower louvre attachments.

FIGURE 22

DRYWALL

DRYWALL

5" MIN
W415-0299 / C / 03.12.03

17
SEE-THROUGH INSTALLATION PROCEDURE
VENTING

FACING

Refer to pages 6-13. All venting must have a minimum
clearance of 1" to combustible.

Combustible materials may be installed flush with the front
of the fireplace but must not cover any of the black faceareas of the fireplace. Non-combustible material (brick,
stone or ceramic tile) may protrude in these areas.
It is not necessary to install a hearth extension with this
fireplace system.

FRAMING
See Page 18 for additional framing dimensions.
Note: In order to avoid the possibility of exposed
insulation or vapour barrier coming in contact with the
fireplace body, it is recommended that the walls of the
fireplace enclosure be “finished” (ie: drywall/sheetrock),
as you would finish any other outside wall of a home.
This will ensure that clearance to combustibles is
maintained within the cavity.

FIGURE 23

When roughing in the fireplace, raise the fireplace to accommodate for the thickness of the finished floor materials, i.e. tile, carpeting, hard wood, which if not planned for
will interfere with the opening of the lower access door and
the installation of many decorative flashing accessories.

Objects placed in front of the fireplace should be
kept a minimum of 48" away from the glass front
faces.

FINISHING
Refer to pages 22-25 for complete instructions regarding
mantle requirements and installations, log placement,
glass door and upper and lower louvre attachments.

FIGURE 25

A

DRYWALL
DRYWALL

A = 22" minus finishing material thickness, each side.

BRICK PANEL INSTALLATION
Install the base panels as illustrated in steps 1-4 on page
15. Both side panels sit under the bracket tab. Holding the
side panel in position, bend down the tab to secure. DETAIL 6.
FIGURES 24a-c
5" MIN
RETAINER

STEP 5

DETAIL 5 & 6

RETAINER

STEP 6
W415-0299 / C / 03.12.03

18
VENT FRAMING DIMENSIONS
There must be a minimum of 1" clearance to combustibles
when framing around all venting options. See pages 14-17.

FIGURE 26

FIGURE 27
Horizontal Vent Off Fireplace

A = 42" using flexible vent components.
A = 38½" using Wolf Steel rigid vent components.

W415-0299 / C / 03.12.03

Vertical Vent Off Fireplace

B = 45" using flexible vent components.
B = 42½" using Wolf Steel rigid vent components.

19
INSTALLATION
WALL AND CEILING PROTECTION
For optimum performance it is recommended that all
horizontal runs have a minimum 1 inch rise per foot using flexible venting.
For safe and proper operation of the fireplace, follow the
venting instructions exactly.

HORIZONTAL INSTALLATION
This application occurs when
venting through an exterior wall.
Having determined the air terminal location, cut and frame a hole
in an exterior wall with a minimum square or round opening
* . (As an alternative to
of 10½"*
framing, a vent pipe shield may
be installed, ensuring a 1" clearance to combustibles.

10½"*

FIGURE 28

Mark and cut the vent pipe shield to the determined depth
of the combustible wall. Apply a bead of caulking (not supplied) to the framework or to the shield plate (in the case of
a finished wall) and secure the shield through the opening
to the interior wall. The final location of the vent pipe shield
should maintain the required clearance to the 8" vent
pipe / liner. Do not fill this cavity with any type of material.
Apply a bead of caulking all around and place a firestop
spacer over the vent shield to restrict cold air from being
drawn into the room or around the fireplace. Ensure that
both spacer and shield maintain the required clearance to
combustibles. Once the vent pipe / liner is installed in its
final position, apply sealant between the pipe / liner and
the firestop spacer.

OR

FIGURE 29

VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for various roof pitches are available from
your Napoleon dealer.
See Accessories to order the specific kit reFIGURE 30
quired.
1. Determine the air terminal location, cut and
frame 10½ inch openings in the ceiling and
the roof to provide the
minimum clearance between the fireplace pipe
/ liner and any combustible material. Try to center the exhaust pipe location midway between two joist to prevent having to cut them. Use a
plumb bob to line up the center of the openings.
DO NOT FILL THIS
SPACE WITH ANY
TYPE OF MATERIAL.
A vent pipe shield will
FIGURE 31
prevent any materials such as insulation, from filling up
the 1" air space
around the pipe. Nail headers between the joist for extra
support.
2. Apply a bead of caulking (not supplied) to the framework
or to the Wolf Steel vent pipe shield plate or equivalent (in
the case of a finished ceiling), and secure over the opening in the ceiling. A firestop must be placed on the bottom
of each framed opening in a roof or ceiling that the venting
system passes through. Apply a bead of caulking all around
and place a firestop spacer over the vent shield to restrict
cold air from being drawn into the room or around the fireplace. Ensure that both spacer and shield maintain the
required clearance to combustibles. Once the vent
VENT
pipe / liner is installed in its
PIPE
final position, apply sealant
COLLAR
between the pipe / liner and
the firestop spacer.
VENT PIPE
3. In the attic, after the pipe /
SHIELD
liner has been installed,
slide the vent pipe collar
down to cover up the open
FIGURE 32
end of the shield and tighten.
This will prevent any materials, such as insulation, from
filling up the 1" air space around the pipe.

W415-0299 / C / 03.12.03

20
USING FLEXIBLE VENT COMPONENTS
Use only approved aluminum flexible liner kits marked:

FIGURE 33

For optimum performance, it is recommended that
horizontal runs have a minimum ¼ inch rise per
foot .

"Wolf Steel Approved Venting" as identified by the stamp only on the 8” outer liner.
5. From outside, apply a bead of the high temperature sealant to the inside of both liners, approximately 1" from the
end of each liner.
HORIZONTAL AIR TERMINAL INSTALLATION
5. Holding the air terminal (lettering in an upright, readable
position), insert into both liners with a twisting motion to
1. Stretch the 5" diameter aluminum flexible liner to the
ensure that both the terminal sleeves engage into the linrequired length taking into account the additional length
ers / sealant. Secure the terminal to the exterior wall and
needed for the finished wall surface. Apply a heavy bead of
make weather tight by sealing with caulking (not supplied).
the high temperature sealant, supplied with the unit, to the
inside of the 5" liner approximately 1" from the end. Slip the 6. If more liner needs to be used to reach the fireplace,
liner a minimum of 2" over the fireplace vent collar and couple them together as illustrated. The vent system must
be supported approximately every 3 feet for both vertical
secure with 3 #8 screws.
and horizontal runs. Use Napoleon support ring assembly
2. Using the 8" diameter flexible aluminum liner, apply sealW010-0380 or equivalent noncombustible strapping to
ant, slide a minimum of 2" over the fireplace combustion
maintain the minimum 1" clearance to combustibles.
air collar and secure with 3 #8 screws.

For safe and proper operation of the fireplace, follow
the venting instructions exactly.

VERTICAL AIR TERMINAL INSTALLATION

FIGURE 34
The air teminal may be recessed into the exterior wall
or siding by 1½", the depth of the return flange.

FIGURE 35

3. Insert the liners through the firestop. Position and secure the fireplace using the nailing tabs (2 per side) and/or
secure to the floor using screws inserted through the two
¼" diameter holes in the front left and right corners of the
base. The liners should be flush with the exterior wall.

FIGURE 36
1. Fasten the roof support
to the roof using the
screws provided. The roof
support is optional. In this
case the venting is to be
adequately supported using either an alternate
method suitable to the authority having jurisdiction
or the optional roof support.
2. Stretch the 5" diameter alumiFIGURE 37 num flexible liner to the required
length. Slip the liner a minimum
of 2" over the inner sleeve of the
air terminal and secure with 3 #8
screws. Seal using a heavy bead
of the high temperature sealant.
3. Repeat using 8" diameter aluminum flexible liner.
5. Thread the air terminal pipe
assembly down through the roof.
The air terminal must be located
vertically and plumb. Attach the air terminal assembly to
the roof support, ensuring that a minimum 16" of air terminal will penetrate the roof when fastened.
DO NOT CLAMP THE
FLEXIBLE ALUMINUM
LINER.

FIGURE 38
W415-0299 / C / 03.12.03

21
5. Remove nails from the shingles, above and to the sides
of the chimney. Place the flashing over the air terminal and
slide it underneath the sides and upper edge of the
shingles. Ensure that the air terminal is properly centered
within the flashing, giving a 3/5" margin all around. Fasten
to the roof. Do not nail through the lower portion of the
flashing. Make weather-tight by sealing with caulking.
Where possible, cover the sides and top edges of the flashing with roofing material.
6. Apply a heavy bead of weatherproof caulking 2 inches
above the flashing. Slide the storm collar around the air
terminal and down to the caulking. Tighten to ensure that a
weather-tight seal between the air terminal and the collar
is achieved. Attach the other storm collar centered between
the air intake and the air exhaust slots onto the air terminal. Tighten securely. Attach the vertical rain cap.
Spacers are attached to the 5" inner flex liner at predetermined intervals to maintain a 1-1/5" air gap to the 8"
outer liner. These spacers must not be removed.

7. If more liner needs to be used to reach the fireplace,
couple them together as illustrated. The vent system must
be supported approximately every 3 feet for both vertical and
horizontal runs. Use Wolf Steel support ring assembly W0100370 or equivalent noncombustible strapping to maintain a
clearance to combustibles of 1".

FIREPLACE VENT CONNECTION
1. Install the 5 inch diameter
aluminum flexible liner to the fireplace. Secure with 3 screws and
flat washers. Seal
the joint and screw
holes using the high
temperature sealant
provided.
2. Install the 8 inch
diameter aluminum
flexible liner to the
fireplace. Attach and
seal the joints.

FIGURE 39

USING RIGID VENT COMPONENTS
For optimum performance it is recommended that all
horizontal runs have a ¼ inch rise per foot.
For safe and proper operation of the fireplace, follow
the venting instructions exactly.
The vent system must be supported approximately every 3
feet for both vertical and horizontal runs. Use Napoleon
vent spacers W615-0033 every 3 feet and on either side of
each elbow to maintain the minimum 1¼" clearance between the outer and inner vent pipes. Use Napoleon support ring assembly W010-0380 or equivalent noncombustible strapping to maintain the minimum 1" clearance to
combustibles for both vertical and horizontal runs.
HORIZONTAL AIR TERMINAL INSTALLATION
1. Move the fireplace into position. Measure the vent
length required between terminal and fireplace taking into
account the additional length needed for the finished wall
surface and any 1¼" overlaps between venting components.
2. Apply high temperature sealant to the outer edge of the
5" inner collar of the fireplace. Attach the first vent component and secure using 3 self tapping screws. Repeat using 8" piping.
3. Holding the air terminal (lettering in an upright, readable
position), insert into both vent pipes with a twisting motion
to ensure that both the terminal sleeves engage into the
vent pipes and the sealant. Secure the terminal to the exterior wall and make weather tight by sealing with caulking
(not supplied). The air teminal may be recessed into the
exterior wall or siding by 1½", the depth of the return
flange.

FIGURE 40

VERTICAL AIR TERMINAL INSTALLATION
1. Move the fireplace into position.
2. Fasten the roof support to the roof using the screws
provided. The roof support is optional. In this case the venting is to be adequately supported using either an alternate
method suitable to the authority
FIGURE 41
having jurisdiction or the optional
roof support.
3. Apply high temperature sealant
to the outer edge of the inner sleeve
of the air terminal. Slip a 5" diameter coupler a minimum of 2" over
the sleeve and secure using 3
screws.
5. Apply high temperature sealant
to the outer edge of the of the outside sleeve of the air terminal. Slip
a 8" diameter coupler over the sleeve and secure as
before.Trim the 8" coupler even with the 5" coupler end.
5. Thread the air terminal pipe assembly down through the
roof support and attach, ensuring that a minimum 16" of
air terminal will penetrate the roof when fastened. If the
attic space is tight, we recommend threading the Wolf
Steel vent pipe collar or equivalent loosely onto the air
terminal assembly as it is passed through the attic.
The air terminal must be located vertically and plumb.
6. Remove nails from the shingles, above and to the sides
of the chimney. Place the flashing over the air terminal and
slide it underneath the sides and upper edge of the
shingles. Ensure that the air terminal is properly centered
within the flashing, giving a 3/5" margin all around. Fasten
to the roof. Do NOT nail through the lower portion of the
flashing. Make weather-tight by sealing with caulking. Where
possible, cover the sides and top edges of the flashing
with roofing material.

W415-0299 / C / 03.12.03

22

O

O I

PI L OT

3

ON

FIGURE 42

IH

1. Move the fireplace into position and secure to the floor
using #10 hex head screws (not supplied).
2. Route a 3/8" N.P.T. black iron gas line, 1/2" type-L
copper tubing or equivalent to the fireplace.
3. For ease of accessibility, an optional remote wall
switch or millivolt thermostat may be installed in a convenient location. Route 2-strand (solid core) millivolt wire
through the electrical hole located at the bottom left side of
the unit.
The recommended maximum lead length depends on
wire size:
WIRE SIZE
MAX. LENGTH
14 gauge
100 feet
16 gauge
60 feet
18 gauge
40 feet

2

P L T

GAS INSTALLATION

1
LO

It is best to frame your fireplace after it is positioned and
the vent system is installed. Use 2x4's and frame to local
building codes.
See PAGE 14 for bar type / countertop installation.

Do not connect either the wall switch, thermostat or
gas valve to electricity (110 volts).
Attach the two leads to terminals 1 and 3 located on the
gas valve.

FF

8. Apply a heavy bead of waterproof caulking 2 inches above
the flashing. Slide the storm collar around the air terminal
and down to the caulking. Tighten to ensure that a weathertight seal between the air terminal and the collar is
achieved. Attach the other storm collar centered between
the air intake and air exhaust slots onto the air terminal.
Tighten securely. Attach the rain cap.
8. Continue adding rigid venting sections, sealing and
securing as above. Attach a 5" collapsed telescopic pipe
to the last section of rigid piping. Secure with screws and
seal. Repeat using a 8" telescopic pipe.
9. Run a bead of high temperature sealant around the
outside of the 5" elbow. Pull the adjustable pipe a minimum 2" onto the elbow. Secure with 3 screws. Repeat with
the 8" telescopic pipe.
10. In the attic, slide the vent pipe collar down to cover up
the open end of the shield and tighten. This will prevent
any materials, such as insulation, from filling up the 1" air
space around the pipe.

4. Install the rigid black pipe, ½" type-L copper tubing or,
if local codes permit, a 3/8" flex connector and shutoff valve
to the gas line and the fireplace gas valve. Seal and tighten
securely. An adapter fitting is required between the gas
valve and the copper tubing or flex connector.

FIGURE 43
Do not kink flexible connector.
5. Check for gas leaks by brushing on a soap and water
solution.
Do not use open flame.
6. Mark the appropriate boxes on the rating plate label to
indicate the model type.

FIGURE 44

FINISHING
MANTLE INSTALLATION
Combustible mantle clearance can vary according to the
mantle depth. Use the graph to help evaluate the clearance needed. The three-sided top extension piece may be
removed if non-combustible framing is faced with a noncombustible material.
FIGURES 45 a-b
* SEE FIGURE 16.

Dashed lines are suitable mantle sizes and clearances
when a non-combustible facing is used.

7" MANTLE
3" MANTLE
*

TOP EXTENTION
TOP OF THE UNIT

W415-0299 / C / 03.12.03

23
LOG PLACEMENT

E

PHAZER logs, glowing and charcoal embers, exclusive
to Napoleon fireplaces, provide a unique and realistic glowing effect that is different in every installation. Take the time
to carefully position the embers for a maximum glowing
effect. Figures 46 A - H.
TM

A

#1

LOCATING PINS

#3

LOCATING PINS

5. When pieces #3a and #3b are attached to create log
#3, the upper end of log #3 should rest in the groove, on
top of log # 2.

F

1. Looking at the unit from the valve side, place log #1
diagonally across the textured burner cover onto the pins.
The texture is designed to cradle the underside of the log.

B

#4

#2

6. As with log # 1, log #4 is also cradled by the texture of the
burner cover and the pin in the base. Position log #4 so that
the lower end fits onto the pin. The upper end rests against
the moulded locater on the top of log # 1.

G

#5

b
2. Depending on the type of installation, the view of the log
positioning will reverse. Here the lower end of log #2 rests
near the back left corner of the firebox on the locating pin.
The upper end sits on top of log #1, inside the groove on
log #2.

C

7. Like log #3, log #5
also comes in two
pieces. The base
(#5a) slopes
outwards between
logs #2 and #4.
As with pieces #3a
& b, piece #5b fits
over piece #5a.
Place the end of
piece #5b onto the
pin.

a

#3a

H

#2
#5
#3

D

#3

b
a

3. Log # 3 is made up of
two pieces, a and b. Piece
#3a is the base of log #3.
The base sits diagonally in
the designated area located between logs #1 and
fits tight up against #2.

#1

#4

8. The upper end of log #5 rests in the groove, on top of
log #4 and creates the final appearance of log set.

4. The slot in the underside of piece #3b fits over
#3a. Place the end of
piece #3b onto the pin.
W415-0299 / C / 03.12.03

24
DOOR INSTALLATION

GLOWING EMBERS
Tear the embers into small pieces and place on the ported
area of the burner. Care should be taken to shred the
embers into thin, small irregular pieces as only the exposed edges of the fibre hairs will glow. The ember material will only glow when exposed to direct flame; however,
care should be taken to not block the burner ports. Blocked
burner ports can cause an incorrect flame pattern, carbon
deposits and delayed ignition. PHAZERT M logs glow when
exposed to direct flame.

FLANGE
HOOD

UPPERLOUVRE
DOOR LATCH

49

CHARCOAL EMBERS
Randomly place the embers around the bottom brick panels in a realistic manner but not in contact with the flames.
Keep ember dust away from burner ports to avoid plugging
them.

CLIP

DOOR OPENING AND
CLOSING: The upper louvres must be removed to
allow the door to be
opened or closed. To access the lower door latch,
open the valve control door.
Release the top and bottom door latches, located
at the right side of the door.

UPPER LOUVRE BRACKETS & HOOD
FIGURE 50

Fine dust found in bottom of bag not to be used. PHAZERTM
logs, and embers glow when exposed to direct flame. Use
only certified PHAZERT M logs, glowing embers and charcoal embers available from your Napoleon / Wolf Steel Ltd.
dealer.

GLOWING EMBERS
Attach the hood with louvre brackets by pressing the top
flange of the bracket into the clips along the top of the
louvre opening with louvre securing tabs facing out.

LOWER LOUVRE BRACKETS & HINGE SCREEN
FIGURES 51 a-b

A

47

B

LOGO PLACEMENT
Remove
the
backing of the
logo supplied and
place on the glass
viewing door, as
indicated.

½"

Using 6 screws, attach the lower louvre brackets and hinge
screen as illustrated. Be sure to install the louvre brackets over the hinge screen.

LOGO

GVFL INSTALLATION

½"

HOOD
BRACKET
SLOT

FIGURE 48

52

LOUVRE

53
LOWER LOUVRES
(VALVE CONTROL DOOR)
W415-0299 / C / 03.12.03

TO INST ALL THE UPPER LOUVRES: Insert
the upper louvres into the
slots on both brackets.
Press the top flange of
the hood into the four
clips located along the
top of the unit as shown.
TO INSTALL THE LOWER
LOUVRE ASSEMBLY: Attach each hinge to the firebox with 2 screws.

Optional plated door trim, and arched door facia are available at your local Napoleon dealer.

25
L36 LOUVRE INSTALLATION
FIGURE 54 a-c

A

B

END DOOR INSTALLATION
Ensure that the
door is properly
clipped onto the
steel lip to prevent overheating, glass breakage and / or discolouration of
the upper trim.
FIGURE 56

FIGURE 55

STEEL LIP

DOOR

To install the door(s),
hook it over the steel lip
located above the door
opening.

C

A

CLIPS

FLANGE

HOOD
Attach the hood by pressing the
top flange into the clips along
the top of the louvre opening.
Secure using a screw through
the centre slot.

Secure with screws
along the bottom of
the door. Tighten
screws snugly. Do not
over-tighten.

FIGURE 57

CENTRE
SLOT

SLOT

UPPER LOUVRES
Insert the louvre tabs into the
slots located at the top left and
right corners of the unit.

TAB

B
C
HINGE
CLIP

SLOT

LOWER LOUVRES
Insert the hinge clips into the
slots located at the bottom left
and right corners of the unit.
To remove the louvres, pull the
back tabs of the clips forward,
while pushing the louvre assembly back. Lift the clip.

W415-0299 / C / 03.12.03

26
OPTIONAL BLOWER INSTALLATION

blac

INSTALLATION TO BE DONE BY A QUALIFIED INSTALLER and must be electrically connected and grounded
in accordance with local codes. In the absence of local
codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE
in Canada or the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the
United States.
Remove
the
blower from its
mounting bracket
r ed
and attach to the
bracket supplied
with the fireplace.
white
FIGURE 58
This bracket is
found secured on
the mounting stud
located at the bottom of the vent
side wall.
k

Remove the "Z" shaped
mounting bracket secured
to the burner, by the pilot.
Remove the thermodisc
from the bracket supplied in
the blower kit and attach to
the mounting bracket. Attach
the connectors from the
black and white wires to the
FIGURE 62
thermodisc.
Do not overtighten thermodisc or distort housing.
Attach the connectors from the
black and red wires to the
blower. Attach and secure the
variable speed switch using the
nut provided. Plug the harness
cord into the receptacle.

FIGURE 63

FIGURE 59

FIGURE 60

The blower bracket contains two holes that allow the blower
to be positioned away from the intended gas supply hole.
Position the vibration reducing pad, centred, onto the
threaded stud, piercing a hole into the pad. The blower
must be able to be positioned entirely onto the pad.
Tilt the blower onto its side and slide it past the controls.
Position the blower under the clip and onto the stud. Secure with a wing nut.

FIGURE 61

W415-0299 / C / 03.12.03

The wire harness provided in this kit is a universal harness. When installed, ensure that any excess wire is
contained, preventing it from making contact with moving or hot objects.
Drywall dust will penetrate into the blower bearings,
causing irreparable damage. Care must be taken to
prevent drywall dust from coming into contact with the
blower or its compartment. Any damage resulting from
this condition is not covered by the warranty policy.
Because the blower is thermally activated, when turned
on, it will automatically start approximately 10 minutes
after lighting the fireplace and will run for approximately
30 - 45 minutes after the fireplace has been turned off.
Use of the fan increases the output of heat.

27
OPERATION / MAINTENANCE

When lit for the first time, the fireplace will emit a slight
odour for a few hours. This is a normal temporary condition caused by the curing of the logs and the "burn-in" of
internal paints and lubricants used in the manufacturing
process and will not occur again. Simply open a window to
sufficiently ventilate the room.

After extended periods of non-operation such as following
a vacation or a warm weather season, the fireplace may
emit a slight odour for a few hours. This is caused by dust
particles in the heat exchanger burning off.
Purge the gas line with a glass door open. Assure that
a continuous gas flow is at the burner before re-installing the door.

FOR YOUR SAFETY READ BEFORE LIGHTING:

WHAT TO DO IF YOU SMELL GAS:
•
•
•
•

Turn off all gas to the fireplace.
PL T
Open windows.
Do not try to light any appliance.
Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier from GAS KNOB
a neighbour's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
FLAME
ADJUSTMENT
PILOT
KNOB
ON/OFF
KNOB

FF

O I

ON

O

P I LOT

PL T

IH

O

FF

O I

ON

A. This fireplace is equipped with a pilot which must be lit
by hand while following these instructions exactly.
B. Before operating smell all around the fireplace area for
gas and next to the floor because some gas is heavier
than air and will settle on the floor.
C. Use only your hand to turn the gas control knob. Never
use tools. If the knob will not turn by hand, do not try to
repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service technician to
inspect the fireplace and replace any part of the control
system and any gas control which has been under water.

LO

LIGHTING INSTRUCTIONS
WARNING: The gas valve has an interlock device which
will not allow the pilot burner to be lit until the thermocouple has cooled. Allow approximately 60 seconds for the
thermocouple to cool.
When lighting and re-lighting, the gas knob cannot be
turned from pilot to off unless the knob is depressed
slightly.
1. Stop! Read the above safety information on this label.
2. Turn off all electric power to the fireplace.
3. Turn the gas knob clockwise to off.
4. Wait five (5) minutes to clear out any gas. If you smell
gas including near the floor. Stop! Follow "B" in the
above safety information on this label. If you don't smell
gas go the next step.

5. Turn gas knob counter-clockwise to pilot.
6. Depress slightly and hold gas knob while lighting the
pilot with the push button ignitor. Keep knob depressed
for one minute, then release. If pilot does not continue
to burn, repeat steps 3 through 5.
7. With pilot lit, depress and turn gas knob counter-clockwise to on.
8. If equipped with remote on-off switch/thermostat, main
burner may not come on when you turn valve to on.
Remote switch must be in the on position to ignite
burner.
9. Turn on all electric power to the fireplace.

TO TURN OFF GAS
1. Turn off all electric power to the fireplace if service is to be
performed.
2. For a complete shut-down procedure: push in gas control
knob slightly and turn clockwise to off. Do not force.

3. For a temporary shut-down procedure: set thermostat to
lowest setting or remote switch to off. Press and turn the
gas knob clockwise to pilot.

MAINTENANCE
Turn off the gas and electrical power before servicing the
fireplace.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing. This fireplace
and its venting system should be inspected before use and at
least annually by a qualified service person. The fireplace area
must be kept clear and free of combustible materials, gasoline
or other flammable vapours and liquids. The flow of combustion and ventilation air must not be obstructed.
1. In order to properly clean the burner and pilot assembly,
remove the logs to expose both assemblies.
2. Keep the control compartment, logs, burner, air shutter opening and the area surrounding the logs clean by vacuuming or
brushing, at least once a year.

3. Check to see that all burner ports are burning. Clean out any
of the ports which may not be burning or are not burning properly.
4. Check to see that the pilot flame is large enough to engulf
the thermocouple and thermopile and reaches toward the
burner with the third jet.
5. Replace the cleaned logs.
6. Check to see that the main and runner burners ignite completely on all openings when the gas knob for the burners is
turned on. A 5 to 10 second total light-up period is satisfactory. If
ignition takes longer, consult your Napoleon dealer / distributor.
7. Check that the gasketing on the sides, top and bottom of
the door is not broken or missing. Replace if necessary.
W415-0299 / C / 03.12.03

28
ADJUSTMENTS
PILOT BURNER ADJUSTMENT

VENTURI ADJUSTMENT

Adjust the pilot screw to provide properly sized flame. Turn
in a clockwise direction to reduce the gas flow.

Natural gas models have air shutters set at 1/4 (.250") inch
open. Propane gas models have air shutters set at 7/16
(.437) inch open. Closing the air shutter will cause a more
yellow flame, but can lead to carboning. Opening the air
shutter will cause a more blue flame, but can cause flame
lifting from the burner ports. The flame may not appear
yellow immediately; allow 15 to 30 minutes for the final
flame colour to be established.

FIGURE 64

FIGURE 66
FIGURE 65
WARNING: This is a fast acting thermocouple. It is an integral safety component.
Replace only with a fast acting thermocouple supplied
by Wolf Steel Ltd.

AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A
QUALIFIED GAS INSTALLER!

RESTRICTING VERTICAL VENTS
Vertical installations may display a very active flame.If this
appearance is not desirable,the vent exit must be restricted
using the optional restrictor vent kit, RP40-KT. This will
reduce
the velocity of the exhaust gases,slowing down the flame
pattern and creating a more traditional gentle appearance.
Specific instructions are included with the kit.

W415-0299 / C / 03.12.03

29
REPLACEMENTS

Contact your dealer or the factory for questions concerning
prices and policies on replacement parts. Normally all parts
can be ordered through your Napoleon dealer or distributor.

* WARNING: This is a fast acting thermocouple. It is an
integral safety component. Replace only with a fast
acting thermocouple supplied by Wolf Steel Ltd.

When ordering replacement parts always give the following information:
1. MODEL & SERIAL NUMBER OF FIREPLACE
2. INSTALLATION DATE OF FIREPLACE
3. PART NUMBER
4. DESCRIPTION OF PART
5. FINISH
6. TOP OR REAR VENT

COMPONENTS COMMON TO ALL UNITS
#

PART No. DESCRIPTION

1*
2*
3
4
5*
6*
7*
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23

W361-0016
W550-0001
W562-0009
W010-0454
W500-0028
W385-0245
W573-0008
GL-634
W135-0153
W135-0154
W135-0155
W135-0156
W135-0157
W135-0158
W135-0159
W475-0265
W475-0259
W475-0260
W475-0261
W475-0262
W080-0519
W500-0193
N010-0279

GLOWING EMBERS
CHARCOAL EMBERS
DOOR GASKET (100 INCHES)
GLASS W/ GASKET
FIRESTOP - FLEXIBLE VENTING
NAPOLEON LOGO
HIGH TEMP SEALANT
BGD40 LOGSET
LOG#1
LOG#2
LOG#3 - PIECE A
LOG#3 - PIECE B
LOG#4
LOG#5 - PIECE A
LOG#5 - PIECE B
END FIBRE BRICK PANEL - FOR WALL
END FIBRE BRICK PANEL - FOR BURNER
END FIBRE BRICK PANEL - FOR BURNER
SIDE FIBRE BRICK PANEL - FOR BURNER
SIDE FIBRE BRICK PANEL - FOR BURNER
BOTTOM LOUVRE BRACKET
BRICK PANEL RETAINER
SIDE LOUVRE HOOD W/ LOUVRE BRACKETS

W200-0114
N010-0327
W300-0057
W010-0873
W562-0009
W475-0263
N010-0310
W500-0192

SIDE DOOR COVER
SIDE DOOR HEAT SHIELD
END DOOR TEMPERED GLASS ONLY
END DOOR TEMPERED GLASS C/W GASKET
DOOR GASKET (100 INCHES)
SIDE BRICK PANEL - FOR WALL
END LOUVRE HOOD W/ LOUVRE BRACKETS
END BRICK PANEL RETAINER

W562-0009
W475-0265
N010-0326
W200-0117
W500-0192
W010-0516

DOOR GASKET (100 INCHES)
END FIBRE BRICK PANEL - FOR
END DOOR HEAT SHIELD
END DOOR COVER
END BRICK PANEL RETAINER
BLACK SIDE DOOR c/w GLASS

24
25
26
27
3
28
29
30
3
16
31
32
30
33

COMPONENTS UNIQUE TO OPEN END UNIT

COMPONENTS UNIQUE TO SEE-THRU UNIT

BURNER COMPONENTS
34
35
35
36
36
37*
38
39
40
41
42
42
43
43

W010-0871
W010-0801
W010-0800
W455-0069
W455-0067
W660-0005
W680-0004
W680-0005
W240-0006
W357-0001
N455-0003
W455-0072
W725-0026
W725-0025

REPLACEMENT BURNER
NATURAL GAS PILOT ASSEMBLY
PROPANE GAS PILOT ASSEMBLY
NATURAL GAS PILOT INJECTOR
PROPANE GAS PILOT INJECTOR
BURNER ON/OFF SWITCH
THERMOPILE
THERMOCOUPLE
ELECTRODE W / WIRE
PIEZO IGNITER
MAIN BURNER ORIFICE - PROPANE
MAIN BURNER ORIFICE - NATURAL
PROPANE GAS VALVE
NATURAL GAS VALVE

GAS

VENT KITS

GD420 (5 FOOT)
44*
45*

W010-0772
W730-0012

5" FLEXIBLE ALUMINIUM LINER - (5 FT.) C/W SPACERS
8" FLEXIBLE ALUMINIUM LINER - (5FT .)

46*
47*
48*

W730-0013
W010-0773
W010-0810

8" FLEXIBLE ALUMINIUM LINER -(10FT.)
5" FLEXIBLE ALUMINIUM LINER-(10 FT.) C/W SPACERS
WALL SUPPORT ASSEMBLY

GD430 (10 FOOT)

ROOF TERMINAL KITS

49*
50*
51*

1/12 TO 7/12 PITCH 8/12 TO 12/12 PITCH FLAT ROOF
-

GD410
GD411
GD412

52*
53*
54*
55*

W120-0036
VERTICAL CAP
W170-0063
STORM COLLAR
W010-0453
ROOF SUPPORT
W263-0054 /W263-0055 / W263-00056 ROOF FLASHING

TERMINAL KITS

WALL

56*
57*

PERISCOPE
WALL TERMINAL KIT -

GD401
GD422

COMPONENTS UNIQUE TO PENINSULA UNIT
28

W010-0873

33
30

W010-0516
N010-0310

END DOOR TEMPERED GLASS
C / W GASKET
BLACK SIDE DOOR c/w GLASS
END LOUVRE HOOD W/ LOUVRE BRACKETS

W415-0299 / C / 03.12.03

30

W415-0299 / C / 03.12.03

* WARNING:

This is a fast acting thermocouple. It is an integral safety component.
Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.

31
#

PART No. DESCRIPTION

1
2
3*
4*
5
6*
7*
8*
8*
9*
10*
10*
11
11
11
11
12*
12*
12*
12*
13
13
13
13
14*
14*
14*
14*
15
15
15
15
16*
16*
16*

W690-0001
GD501
W573-0008
W010-0370
GZ-550-1KT
W175-0170
W500-0033
W660-0010
W660-0011
W660-0013
W175-0166
W175-0002
GVFLK
GVFLPB
GVFLAB
GVFLSS
BGDELK
BGDELPB
BGDELAB
BGDELSS
L36K
L36AB
L36PB
L36SS
ELB40K
ELB40PB
ELB40AB
ELB40SS
HOIG-1
HOIKG-1
HOIBC-1
HOIBG -1
EHOIG -1
EHOIKG-1
EHOIBC-1

ACCESSORIES

MILLIVOLT THERMOSTAT
HEAT GUARD
HI-TEMP SEALANT
WALL SUPPORT ASSEMBLY
BLOWER KIT
DURA-VENT ZERO CLEARANCE ADAPTOR
VARIABLE SPEED SWITCH WALL MOUNTING PLATE
REMOTE CONTROL - ADVANTAGE
REMOTE CONTROL - ADVANTAGE PLUS
MODULATING REMOTE - CONTROLS FLAME & BLOWER
5" COUPLER
8" COUPLER
LOUVRE KIT - BLACK
LOUVRE KIT - POLISHED BRASS
LOUVRE KIT - ANTIQUE BRASS
LOUVRE KIT - STAINLESS STEEL
END LOUVRE KIT - BLACK
END LOUVRE KIT - POLISHED BRASS
END LOUVRE KIT - ANTIQUE BRASS
END LOUVRE KIT - STAINLESS STEEL
LOUVRE KIT - UPPER & LOWER - BLACK
LOUVRE KIT - UPPER & LOWER - ANTIQUE BRASS
LOUVRE KIT - UPPER & LOWER - POLISHED BRASS
LOUVRE KIT - UPPER & LOWER - BRUSHED STAINLESS STEEL
END LOUVRE KIT - BLACK
END LOUVRE KIT - POLISHED BRASS
END LOUVRE KIT - ANTIQUE BRASS
END LOUVRE KIT - STAINLESS STEEL
HERITAGE ORNAMENTAL INSET-GOLD PLATED
HERITAGE ORNAMENTAL INSET-BLACK GOLD PLATED
HERITAGE ORNAMENTAL INSET-BRUSHED COPPER PLATED
HERITAGE ORNAMENTAL INSET-BRUSHED GOLD PLATED
END HERITAGE ORNAMENTAL INSET-GOLD PLATED
END HERITAGE ORNAMENTAL INSET-BLACK GOLD PLATED
END HERITAGE ORNAMENTAL INSET
- BRUSHED COPPER PLATED

16*
17
17
17
17
18*
18*
18*
18*
19
19
19
19
20*
20*
20*
20*
21
21
21
21
22*
22*
22*
22*
23
23
23
23
24*
24*
24*
24*
32*
33*
41*
42*
42*

EHOIBG -1
DOIG-1
DOIKG-1
DOIBC-1
DOIBG-1
EDOIG-1
EDOIKG-1
EDOIBC-1
EDOIBG-1
GOIG-1
GOIKG-1
GOIBC-1
GOIBG-1
EGOIG-1
EGOIKG-1
EGOIBC-1
EGOIBG-1
SOIG-1
SOIKG-1
SOIBC-1
SOIBG-1
ESOIG-1
ESOIKG-1
ESOIBC-1
ESOIBG-1
EOIG-1
EOIKG-1
EOIBC-1
EOIBG-1
EEOIG-1
EEOIKG-1
EEOIBC-1
EEOIBG-1
GD825N
GD825P
RP40-KT
W175-0205
W175-0206

END HERITAGE ORNAMENTAL INSET - BRUSHED GOLD PLATED
DIAMOND ORNAMENTAL INSET - GOLD PLATED
DIAMOND ORNAMENTAL INSET - BLACK GOLD PLATED
DIAMOND ORNAMENTAL INSET - BRUSHED COPPER PLATED
DIAMOND ORNAMENTAL INSET - BRUSHED GOLD PLATED
END DIAMOND ORNAMENTAL INSET - GOLD PLATED
END DIAMOND ORNAMENTAL INSET - BLACK GOLD PLATED
END DIAMOND ORNAMENTAL INSET - BRUSHED COPPER PLATED
END DIAMOND ORNAMENTAL INSET - BRUSHED GOLD PLATED
GOTHIC ORNAMENTAL INSET - GOLD PLATED
GOTHIC ORNAMENTAL INSET - BLACK GOLD PLATED
GOTHIC ORNAMENTAL INSET - BRUSHED COPPER PLATED
GOTHIC ORNAMENTAL INSET - BRUSHED GOLD PLATED
END GOTHIC ORNAMENTAL INSET - GOLD PLATED
END GOTHIC ORNAMENTAL INSET - BLACK GOLD PLATED
END GOTHIC ORNAMENTAL INSET - BRUSHED COPPER PLATED
END GOTHIC ORNAMENTAL INSET - BRUSHED GOLD PLATED
SEASHELL ORNAMENTAL INSET - GOLD PLATED
SEASHELL ORNAMENTAL INSET - BLACK GOLD PLATED
SEASHEL ORNAMENTAL INSET - BRUSHED COPPER PLATED
SEASHELL ORNAMENTAL INSET - BRUSHED GOLD PLATED
END SEASHELL ORNAMENTAL INSET - GOLD PLATED
END SEASHELL ORNAMENTAL INSET - BLACK GOLD PLATED
END SEASHEL ORNAMENTAL INSET - BRUSHED COPPER PLATED
END SEASHELL ORNAMENTAL INSET - BRUSHED GOLD PLATED
ECLIPSE ORNAMENTAL INSET - GOLD PLATED
ECLIPSE ORNAMENTAL INSET - BLACK GOLD PLATED
ECLIPSE ORNAMENTAL INSET - BRUSHED COPPER PLATED
ECLIPSE ORNAMENTAL INSET - BRUSHED GOLD PLATED
END ECLIPSE ORNAMENTAL INSET - GOLD PLATED
END ECLIPSE ORNAMENTAL INSET - BLACK GOLD PLATED
END ECLIPSE ORNAMENTAL INSET - BRUSHED COPPER PLATED
END ECLIPSE ORNAMENTAL INSET - BRUSHED GOLD PLATED
VALVE REGULATOR FOR W660-0013 - NATURAL GAS
VALVE REGULATOR FOR W660-0013 - PROPANE
RESTRICTOR VENT KIT
CONVERSION KIT - NG - LP
CONVERSION KIT - LP - NG

W415-0299 / C / 03.12.03

32
TROUBLE SHOOTING GUIDE
BEFORE

ATTEMPTING TO TROUBLESHOOT, PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR OPEN.

SYMPTOM
Main burner flame
is a blue, lazy,
transparent
flame.

PROBLEM

TEST SOLUTION

Blockage in vent.

- remove blockage. In really cold conditions, ice buildup may occur
on the terminal and should be removed as required.

Incorrect installation.

- refer to Figure 34 to ensure correct location of storm collars.
(vertical vent)

Flames are con- Unit is over-fired or undersistently too large fired.
or too small.
Carboning occurs.
A

B

O

LO

ON

FF
PL T

IH

O I

- check pressure readings:
Inlet pressure can be checked by turning screw (A) counter-clockwise 2 or 3 turns and then placing pressure gauge tubing over the
test point. Gauge should read 8" (minimum 4.5") water column for
natural gas or 13" (11" minimum) water column for propane. Check
that main burner is operating on "HI".
Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5" water column for natural gas or 10" water
column for propane. Check that main burner is operating on "HI".
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN
SCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOT
OVERTORQUE.
Leak test with a soap and water solution.

PI LOT

Carbon is being
deposited
on
glass, logs or
combustion
chamber
surfaces.

Air shutter has become - ensure air shutter opening is free of lint or other obstructions.
blocked

White / grey film
forms.

Sulphur from fuel is being
deposited on glass, logs or
combustion chamber surfaces.

Exhaust fumes
smelled in room,
headaches.

Fireplace is spilling.

Pilot goes out
when the gas knob
is released.
The gas valve has
an interlock device which will not
allow the pilot
burner to be lit
until the thermocouple
has
cooled. Allow approximately 60
seconds for the
thermocouple to
cool.
W415-0299 / C / 03.12.03

Flame is impinging on the - check that the logs are correctly positioned.
logs or combustion cham- - open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifice size
ber.
as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that the
seal is tight.
- check that both 5" and 8" vent liners are free of holes and well
sealed at all joints.
- check that minimum rise per foor has been adhered to for any
horizontal venting.
- clean the glass with a recommended gas fireplace glass cleaner.
Do not clean glass when hot!
If deposits are not cleaned off regularly, the glass may become permanently marked.

System is not correctly purged.

check door seal and relief flap seal.
check for chimney blockage
check that chimney is installed to building code.
room is in negative pressure; increase fresh air supply.
purge the gas line with a glass door open.

Out of propane gas.

- fill the tank.

Pilot flame is not large
enough

- turn up the pilot flame.

Pilot flame is not engulfing
the thermocouple.

- gently twist the pilot head to improve the flame pattern around the
thermocouple.

Thermocouple shorting / faulty.
Faulty valve.

loosen and tighten thermocouple.
clean thermocouple and valve connection.
replace thermocouple.
replace valve.

- replace.

33
SYMPTOM
Pilot burning; no
gas
to
main
burner; gas knob
is on 'HI'; wall
switch / thermostat is on.

PROBLEM

TEST SOLUTION

Themostat or switch is defective.

- connect a jumper wire across the wall switch terminals; if main
burner lights, replace switch / thermostat.

Wall switch wiring is defective.

- disconnect the switch wires from the valve & connect a jumper wire
across terminals 1 & 3; if the main burner lights, check the wires for
defects and / or replace wires.

Main burner
plugged.

orifice

is - remove stoppage in orifice.

Faulty valve.

- replace.

Pilot goes out
while standing;
Main burner is in
'OFF' position.

Gas piping is undersized.

- turn on all gas appliances and see if pilot flame flutters, diminishes or extinguishes, especially when main burner ignites. Monitor
appliance supply working pressure.
- check if supply piping size is to code. Correct all undersized piping.

Pilot will not light.

No spark at pilot burner

-

Main burner goes
out; pilot stays on.

check if pilot can be lit by a match
check that the wire is connected to the push button ignitor.
check if the push button ignitor needs tightening.
replace the wire if the wire insulation is broken or frayed.
replace the electrode if the ceramic insulator is cracked or broken.
replace the push button ignitor.

Out of propane gas

- fill the tank.

Spark gap is incorrect

- spark gap should be 0.150" to 0.175" (5/32" to 11/65" approx.) from
the electrode tip and the pilot burner. To ensure proper electrode
location, tighten securing nut (finger tight plus 1/4 turn).

No gas at the pilot burner

-

Pilot flame is not large
enough or not engulfing the
thermopile

- turn up pilot flame.
- replace pilot assembly.

Thermopile shorting

- clean thermopile connection to the valve. Reconnect.
- replace thermopile / valve.

check that the manual valve is turned on.
check the pilot orifice for blockage.
replace the valve.
call the gas distributor.

Remote wall switch wire is - shorten wire to correct length or wire gauge.
too long; too much resistance in the system.
Faulty thermostat or switch.

- replace.

Main burner goes Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"
out; pilot goes out.
- check for vent blockage.
Vent is blocked
Vent is re-circulating

- check joint seals and installation.

5" flexible vent has become - re-attach to fireplace.
disconnected from fireplace.
Remote
wall
switch is in "OFF"
position;
main
burner comes on
when gas knob is
turned to "ON" position.

Wall switch is mounted up- - reverse.
side down
Remote wall switch is - replace.
grounding.

Flames are very
aggressive.

Door is ajar

Remote wall switch wire is - check for ground (short); repair ground or replace wire.
grounding.
- replace.
Faulty valve.
Venting action is too great.

-tighten door clamps
-restrict vent exit with restrictor vent kit, RP40-KT.
W415-0299 / C / 03.12.03

34

W415-0299 / C / 03.12.03

Wolf Steel Fireplace Service History
This fireplace must be serviced annually depending on usage.

Date

Dealer Name

Service Technician
Name

Service Performed

Special Concerns

35
NOTES

W415-0299 / C / 03.12.03

36
NOTES

W415-0299 / C / 03.12.03



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2003:03:12 15:14:04-05:00
Modify Date                     : 2003:03:12 15:28:28-05:00
Page Count                      : 36
Creation Date                   : 2003:03:12 20:14:04Z
Mod Date                        : 2003:03:12 20:14:04Z
Producer                        : Acrobat Distiller 5.0 (Windows)
Author                          : joannaf
Metadata Date                   : 2003:03:12 20:14:04Z
Creator                         : joannaf
Title                           : W415-0299 - BGD40.pmd
EXIF Metadata provided by EXIF.tools

Navigation menu