Nedap N V SF-USB USB Light Controller Transmitter User Manual manual

N. V. Nederlandsche Apparatenfabriek NEDAP USB Light Controller Transmitter manual

manual

Download: Nedap N V SF-USB USB Light Controller Transmitter User Manual manual
Mirror Download [FCC.gov]Nedap N V SF-USB USB Light Controller Transmitter User Manual manual
Document ID1177120
Application IDyIuEnb4r2yw1GHRSh9ua4A==
Document Descriptionmanual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize72.99kB (912411 bits)
Date Submitted2009-09-29 00:00:00
Date Available2009-09-30 00:00:00
Creation Date2009-06-29 11:02:38
Producing SoftwareGPL Ghostscript 8.15
Document Lastmod2009-06-29 11:02:38
Document TitleMicrosoft Word - Printed_Documentation_SenzaFil_English.doc
Document CreatorPScript5.dll Version 5.2
Document Author: martin.gotink

SenzaFil Manual
info@nedaplightcontrols.com
℡ +31 544 471 888
Table of Contents
SenzaFil Manual ................................................................................................................................................................ 1
Welcome....................................................................................................................................................................... 1
Introduction................................................................................................................................................................. 2
Project Configuration ................................................................................................................................................. 3
Screen Appearance .................................................................................................................................................... 4
Installation...................................................................................................................................................................... 7
Hardware Installation ............................................................................................................................................. 7
Software Installation .............................................................................................................................................. 8
Configuration.................................................................................................................................................................. 9
Getting Started........................................................................................................................................................ 9
Importing Floorplan .............................................................................................................................................. 10
Drag and Drop Control Unit................................................................................................................................. 11
Extend license........................................................................................................................................................ 12
Locating Lamps...................................................................................................................................................... 13
Drag and Drop Lamps .......................................................................................................................................... 14
Creating Groups .................................................................................................................................................... 15
Uploading to Control Unit .................................................................................................................................... 16
Tips.............................................................................................................................................................................. 17
Setting Auto Toggle Time .................................................................................................................................... 17
Auto Toggle ............................................................................................................................................................ 18
Adjusting Range .................................................................................................................................................... 19
Devices vs. Lamps ................................................................................................................................................ 20
Properties (Device Status)................................................................................................................................... 21
Group view ............................................................................................................................................................. 23
Icons........................................................................................................................................................................ 24
Functional grouping .............................................................................................................................................. 26
More than One Control Unit................................................................................................................................. 27
Naming devices/groups........................................................................................................................................ 28
Restore backup...................................................................................................................................................... 29
Switching On and Assigning per Circuit............................................................................................................. 30
Recognizing Assigned Lamps .............................................................................................................................. 31
Menu............................................................................................................................................................................ 32
File Menu ................................................................................................................................................................ 32
View Menu .............................................................................................................................................................. 33
Select Menu............................................................................................................................................................ 34
Device Menu........................................................................................................................................................... 35
Control Unit Menu ................................................................................................................................................. 36
Menu Tools ............................................................................................................................................................. 37
SenzaFil Manual V2.3.4 ........................................................................................................................................... 38
Index ............................................................................................................................................................................... 39
iii
SenzaFil Manual
Welcome
SenzaFil Help provides assistance on SenzaFil, a control unit and configuration tool for wireless control
of HID lamps. SenzaFil allows you to switch lamps on and off, to dim them and to monitor their status.
Each control unit can control a maximum of 200 HID lamps that can be subdivided into a maximum of
8 groups. Creating groups allows you to control the settings of separate groups.
The SenzaFil control unit has dimming capability, enabling it to dim the brightness of HID lamps in 5%
increments to a maximum of 50% of their full voltage.
SenzaFil Manual
Introduction
In order to use the SenzaFil control unit, you need:
1.
HID lamps;
2.
Nedap SenzaFil lamp drivers;
3.
One SenzaFil control unit for every 200 lamps (in max. 8 groups);
4.
SenzaFil USB key;
5.
Laptop or handheld PC with Microsoft Windows XP / Vista;
6.
CD with configuration software (included with the SenzaFil USB key);
7.
A license if you want to configure more than 5 lamps;
SenzaFil Manual
Project Configuration
When configuring a new project, you must take the following steps in sequence (see also Getting
Started):
1.
Import Floorplan
2.
Drag and drop Control Unit
3.
Extend license
4.
Locate lamps
5.
Drag and drop lamps
6.
Create groups
7.
Upload to Control Unit
SenzaFil Manual
Screen Appearance
The default SenzaFil screen consists of three parts.
1.
2.
Left: 'Devices within range'
•
a slide to adjust the computer's range (see Adjusting Range);
•
the unassigned control unit(s) and lamps the PC detects;
•
the number of lamps and control units;
•
Refresh button to update the status of the control unit and the lamps;
•
two checkboxes: Show assigned (x) and Show ignored (x);
•
Reset option to restore ignored lamps to their normal (unassigned) status.
Middle: Floorplan
•
the floorplan onto which lamps are dragged to assign them to a position).
SenzaFil Manual
3.
Right: 'Control unit'
This window is used to assign lamps to groups.
•
Individual pane for each group, containing:
on the left: Add lamp to group
on the right: the number of lamps assigned to this group;
assigned lamps represented by small orange squares;
selected assigned lamps are represented by small blue squares;
button;
at the bottom of the 'Control unit' window: total number of assigned lamps;
Upload to control unit button to upload the configuration to the control unit and the
lamps.
SenzaFil Manual
SenzaFil Manual
Installation
Hardware Installation
•
Connect lamps
Hang the lights and connect the lamps to allow them time (20 minutes) to warm up.
Connect the HID lamps and the SenzaFil lamp driver. The lamp's factory default setting is to
burn at full voltage (100%) when the power supply is turned on. This is necessary for
locating and assigning the lamps.
TIP : Switching on and assigning per circuit
•
Control Unit installation
Install the SenzaFil Control Unit and connect the wires. For more information and the wiring
schedule, see the SenzaFil Control Unit Manual.
Note: The control unit must never be installed in a metal power cabinet. This would
impede wireless communication.
SenzaFil Manual
Software Installation
1. SenzaFil CD
Install SenzaFil configuration software from the CD that comes with the USB key. Follow the
instructions on the screen.
Note: Only place the USB key in the USB port after you have installed the software!
2. SenzaFil USB key
Place the SenzaFil USB key in a USB port.
The Windows Found New Hardware Wizard will install the driver.
SenzaFil Manual
Configuration
Getting Started
It is recommended that you assign lamps to a particular spot on a floor plan. This will make it easier to
create groups and select certain lamps to dim. The SenzaFil software saves this configuration, making
it easier to assign lamps to groups and to work with these. To get started, you need to:
1.
Import a Floorplan
2.
Drag and drop the Control Unit
3.
Extend license
4.
Locate lamps
5.
Drag and drop lamps
6.
Create groups
7.
Upload configuration to Control Unit
Click on the shortcut to start the configuration program.
The lamps and the control unit are shown as icons in the 'Devices within range' window (left).
If you see too many or too few lamps, you can adjust the PC's range (see Adjusting Range)..
SenzaFil Manual
Importing Floorplan
The middle window on the screen displays a white field (emptyimage.bmp) by default. You can either
use this or import an existing or newly created floor plan in *.bmp format.
To import a floorplan:
10
•
Click the Import Floorplan button in the toolbar; or
•
Go to File -> Import Floorplan.
SenzaFil Manual
Drag and Drop Control Unit
Place the laptop or handheld PC with the SenzaFil software within 20 metres of the control unit to
ensure that the PC can 'find' and show the control unit on the screen.
Select the control unit in the 'Devices within range' window; drag and drop onto the floor plan.
TIP : More than one Control Unit
11
SenzaFil Manual
Extend license
After assigning the control unit the project will work as a limited version by default. If you received a
license with the control unit, or did request a license you can enter the license by choosing Control
unit > Extend license.
In this screen you are also able to request an extended license if you don't have a license, or if the
current license allows too few lamps. By clicking the link under the 'Request extended license' heading
an e-mail will be created, in this e-mail you only have to enter the number of lamps you need. In case
the e-mail isn't being created you can send an e-mail to support@nedap-lightcontrols.com yourself
with the required number of lamps, the Device ID and the Network ID of the control unit (which can be
found in this screen).
12
SenzaFil Manual
Locating Lamps
To locate a particular lamp, you can make it blink by toggling the lamp icon in the ('Devices within
range') window.
Note: Always check whether the lamps are fully warmed up. As long as either the warming-
up
or cooling-down icon
is visible, you cannot turn on Toggle or Auto toggle.
To start Auto Toggle:
•
click the button on the toolbar or go to Tools -> Start auto toggle.
The top left lamp icon in the 'Devices within range' window will start toggling. You can identify the
corresponding lamp because it will be blinking.
TIP : Auto Toggle settings
In order to make one specific lamp blink (toggle):
1.
Select the corresponding lamp icon;
2.
Right-click to start Toggle.
13
SenzaFil Manual
Drag and Drop Lamps
Drag the blinking icon to the correct location on the floor plan and drop it there (assign).
An assigned lamp is either dimmed to 50%
or switched off
If Auto toggle is switched on, the next lamp icon (and corresponding lamp) will automatically start
blinking.
Drag and drop this lamp onto the floor plan.
Repeat until all lamps are in the correct position and the 'Devices within range' window is empty.
TIP : Functional grouping
In order to find more lamps, you need to move the laptop/handheld PC within range of other lamps.
Repeat the toggle, drag and drop sequence.
If you do not want to assign the lamps to a particular position on a floor plan, you can also select all
the lamps in the 'Devices within range' window. Drag and drop them onto the white field in the middle
window.
TIP : Naming Devices/Groups
14
SenzaFil Manual
Creating Groups
Allot the assigned lamps to groups.
TIP : How to recognize assigned lamps
There are three ways to create groups:
1.
Use the mouse to select the lamps and click the Add to Group button of the appropriate
group. The group pane will display a number of small orange squares representing the
lamps. Selected lamps are represented by small dark blue squares.
2.
Select the lamps and drag them to the appropriate group.
3.
Select the lamps and right-click to select Assign to group
 and the appropriate group
number (Group 1, etc.).
Lamps that have been assigned to a group are represented by this icon:
. The number
indicates the group the lamp has been assigned to. See also Icons.
TIP : Group view
15
SenzaFil Manual
Uploading to Control Unit
In order to upload the project to the control unit and the lamp drivers, you must place your PC within a
20 metre range of the control unit.
To upload:
1.
Click on the Upload to control unit button on the bottom right of your screen. You will be
asked to save the settings (project).
2.
Give the project a name. By default, projects are given a .szf extension (SenzaFil project file)
and are saved to the SenzaFil directory.
3.
Wait until the connection between the lamps and the control unit has been established.
Depending on the number of lamps this can take up to several minutes. You can monitor
progress in the progress pane.
Note: Uploading a new project automatically overwrites the previous one.
16
SenzaFil Manual
Tips
Setting Auto Toggle Time
To change the length of time the icon toggles and the lamp blinks:
1.
Go to Tools -> Options.
2.
Fill in the number of seconds in the 'Toggle time-out' field.
17
SenzaFil Manual
Auto Toggle
Turning on Auto toggle makes the icons blink in sequence for a (freely definable) duration, starting
with the top left icon in the 'Devices within range' window. The objective is to identify the
corresponding lamp so you can drag the icon to the correct location on the floor plan.
TIP: Setting Auto toggle time
The default setting for Auto toggle is 30 seconds. After 30 seconds the blinking stops, but the lamp
remains selected. If you drag the lamp onto the floor plan within 30 seconds, the next lamp icon will
automatically start to toggle.
To disable the Auto toggle function:
•
18
Go to Tools -> Auto toggle enable and uncheck.
SenzaFil Manual
Adjusting Range
You can adjust the PC's range by moving the slide at the top of the 'Devices within range' window. The
slide controls the number of lamps detected by the PC.
If you are working with large numbers of lamps:
1.
Assign the lamps within range;
2.
Move the PC within range of remaining lamps and assign those;
If you see lamps that you do not wish to assign to this control unit:
1.
Select the lamps you wish to ignore.
2.
Go to Device -> Ignore to hide these lamps. The number of ignored lamps (Show ignored
(x)) is shown at the bottom left of the pane.
To make the ignored lamps visible:
•
Check the (Show ignored (x)) box. This icon
represents an ignored lamp.
To reactivate ignored lamps:
•
Go to Device -> Unignore
or
•
Click Reset, to the right of Show ignored (x).
19
SenzaFil Manual
Devices vs. Lamps
There are various types of device:
•
Lamp driver
•
Switch
•
Lux sensor
•
Movement sensor
•
etc.
Lamps or lamp drivers are referred to as 'devices' in the software, and as either 'lamps' or 'devices' in
the manual.
See also Device status
20
SenzaFil Manual
Properties (Device Status)
Control Unit
1.
To view the status of a control unit:
•
Go to Control Unit -> Properties
or
•
select a control unit, right-click and select Properties.
Name: Control Unit's custom name (see Naming devices/groups)
Type: Type of device, e.g. control unit
Status: Active or Suspended
Notes: field for entering extra information on the control unit.
Lamp error level: Specifies the number of lamps in each group that will generate a lamp error
message.
21
SenzaFil Manual
2.
Device
To view the status of an individual lamp:
•
Go to Device -> Properties
or
•
select a lamp, right-click and select Properties.
Name: Custom name of the lamp (see Naming devices/groups)
Type: Type of device, e.g. Lamp driver, Switch, Lux sensor, Movement sensor, etc.
Power level: Off, 50%, 55%, etc.
Status: Standby, Verifying startup, Ignition, Cooling down, Warming up, Error, Defective lamp
or Unknown
22
SenzaFil Manual
Group view
To switch from Map View to Group View:
•
Click on the Group view button in the toolbar
or
•
Go to View -> Group.
Group View expands the group window to the left, showing individual lamps (including their numbers
or names) instead of squares.
To switch back to the floor plan:
•
Click on the Map View button in the toolbar
or
•
Go to View -> Map.
23
SenzaFil Manual
Icons
Control unit active
Control unit
suspended
Control unit memory
Memory corrupt, control unit has to be replaced
corrupt
Factory default
Lamp will start to burn at full capacity when the
setting (100%)
power is switched on.
Ignored
In 'Devices within range' window. Visible only
when 'Show ignored' checkbox has been
checked.
Assigned: off
The number represents the group to which the
lamp has been assigned.
Assigned: 50%
The number represents the group to which the
lamp has been assigned.
Assigned: 100%
The number represents the group to which the
lamp has been assigned.
24
SenzaFil Manual
Warming up
Cooling down
Ignition
Lamp is being ignited
Add lamp to group
Defective lamp
Lamp needs replacing.
Driver error
25
SenzaFil Manual
Functional grouping
Assign the lamps to functional groups or use the builder's or architect's specifications.
Note: These are functional groups, not circuits on the distribution board.
26
SenzaFil Manual
More than One Control Unit
If you are working in an environment with more than one control unit, you need to verify that the
control unit detected by your PC is the correct one. Select Toggle and check whether the LEDs on your
control unit are blinking.
To toggle the control unit:
•
Select and right-click to select Toggle or
•
Go to Control Unit -> toggle
27
SenzaFil Manual
Naming devices/groups
Control units and lamp drivers have a unique number (Device ID), which is printed on their labels. This
number is also displayed under the lamp icon on the floor plan.
For ease of use, you can name the devices:
1.
Select the lamp or control unit.
2.
Right-click and open Properties
or
Go to Device / Control Unit -> Properties.
3.
Give the lamp/control unit a name. This name now appears under the lamp/control unit icon
on your screen. The internal ID remains the same and can be viewed in Properties.
You can choose to display the names on your screen or to turn them off:
•
Go to View -> Show lamp names and click to check or uncheck.
You can also name groups:
•
28
Type a name in the  field in the 'Control Unit' window.
SenzaFil Manual
Restore backup
Should the project become corrupt or contain invalid settings for some other reason, there is the
possibility to restore a backup.
For this option go to File> Restore backup...
In this screen you can choose which backup you want to restore, the existing project will be
overwritten by the backup!
Two backups are kept, the last backup is the backup which is created when the project is saved for the
first time since opening it, the other backup is being created up to one time per day.
29
SenzaFil Manual
Switching On and Assigning per Circuit
If you are working with large numbers of lamps in a large space, it is recommended to switch on and
assign the lamps per circuit.
30
SenzaFil Manual
Recognizing Assigned Lamps
Lamps assigned to the floor plan are represented by a lamp icon (either off or burning at 50%
capacity) with a green radio symbol.
The corresponding lamp is switched off or dimmed to half brightness.
To set output level after assigning:
1.
Go to Tools -> Level after assigning.
2.
Select Off. Assigned lamps are switched off
or
Select 50%. Assigned lamps are dimmed to 50%
•
A lamp assigned to a group is represented by this icon:
. The number indicates the
group to which the lamp has been assigned.
31
SenzaFil Manual
Menu
File Menu
Aside from the familiar options like Open and Save, the File menu also gives you access to:
•
Import Floorplan: to import a floor plan (see Importing Floorplan).
•
Restore backup...: if the project file is corrupted you can use this option to restore a
backup (se Restore backup).
•
32
Exit: to shut down the SenzaFil configuration tool.
SenzaFil Manual
View Menu
The View menu allows you to switch between Map View and Group View.
•
Map: displays the floor plan and a small version of the groups window (lamps are shown as
small squares).
•
Group: the floor plan disappears, while the group window expands to the left. Lamps are
represented by lamp icons.
•
Show lamp names: click to show or hide names.
33
SenzaFil Manual
Select Menu
In the Select menu you can select groups and defective lamps or lamp drivers:
34
•
Group 1 ... Ctrl+1; Group 2 ... Ctrl+2; etc.): selects a single group.
•
Lamp error: selects all defective lamps.
•
Lamp driver error: selects all defective lamp drivers.
•
Select all ... Ctrl + A: selects all groups.
•
Clear selections ... Esc: to deselect.
SenzaFil Manual
Device Menu
The Device menu allows you to control a selected device (e.g. a lamp):
•
Toggle: toggles the icon and makes the corresponding lamp blink.
•
Toggle off: turns toggle off for the selected device.
•
Assign to group : assign this lamp or these lamps to one of the groups listed.
•
Unassign ... Del: removes lamp(s) from group.
•
Ignore: ignore lamp(s).
•
Unignore: reactivates ignored lamp(s).
•
Update all: updates the status of all devices in the project.
•
Update: updates the status of the selected device(s).
•
Properties...: to view and change the properties of a device (see Device status).
35
SenzaFil Manual
Control Unit Menu
The Control Unit menu allows you to control a selected control unit:
•
Change status: to change the status of the control unit.
•
Toggle: toggles the control unit icon (and makes the LEDs on the selected unit blink).
•
Toggle off: turns toggle off.
•
Assign: assigns the selected unit to the project.
•
Unassign: removes the control unit, moving it back to the 'Devices within range' window.
•
Upload to control unit... F9: saves the project and uploads the settings.
•
Extend license...: with this option the window to extend the license, or request an
extended license is being shown (see Extend license).
•
36
Properties...: to view and change the control unit's properties (see Device status).
SenzaFil Manual
Menu Tools
In the Tools menu you can turn auto toggle on/off and view the Options task pane.
•
Auto toggle enable: must be selected (checked) for Auto Toggle to work.
•
Start auto Toggle: starts auto toggle.
•
Stop auto toggle: stops auto toggle.
•
Level after assigning: sets the output level of the lamp (either Off or 50%) after
assigning lamp to floor plan.
•
Language: change the language
•
Options: to see or change which COM port the USB key uses; to view the COM port status;
to set Toggle time-out.
37
SenzaFil Manual
SenzaFil Manual V2.3.4
Nedap Light Controls
PO Box 101
NL-7140 AC Groenlo
Netherlands
http://www.nedaplightcontrols.com/
info@nedaplightcontrols.com
Phone: +31 544 471 888
Fax: +31 544 466 008
FCC Declarations
Compliance statement (part 15.19)
This device complies with part 15 of the FCC Rules and to RSS210 of Industry Canada.
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause
undesired operation.
Warning (part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void
the user’s authority to operate the equipment.
RF Exposure (OET Bulletin 65)
To comply with FCC RF exposure requirements for mobile transmitting devices, this transmitter
should only be used or installed at locations where there is at least 20cm separation distance
between the antenna and all persons.
FCC ID: CGD-SF-USB
IC ID: 1444A-SF-USB
Copyright ©
by
N.V. Nederlandse
Apparatenfabriek
- NEDAP
-.
No part of this document may be reproduced or distributed in any form or by any means, or
stored in a database or retrieval system, without the prior written permission of NEDAP.
38
Index
Configuration ...............................................................3
Lamps.............................. 14, 15, 16, 22, 23, 30, 32, 33
Project......................................................................3
Assign per Circuit .................................................. 32
Control Unit.............................................. 12, 17, 29, 38
Assign to Floorplan................................................ 15
Assign ....................................................................12
Assign to Group..................................................... 16
Drag-and-drop........................................................12
Drag-and-drop ....................................................... 15
Extend license........................................................13
Locating Lamps ..................................................... 14
Menu......................................................................38
Naming.................................................................. 30
More than One .......................................................29
Properties.............................................................. 23
Range, adjust.........................................................21
Recognizing Assigned Lamps................................ 33
Toggle....................................................................29
Status .............................................................. 23, 37
Device ..................................................... 22, 23, 30, 37
Devices vs. Lamps .................................................22
vs. Devices ............................................................ 22
Menu............................................ 34, 35, 36, 37, 38, 39
Menu......................................................................37
Control Unit ........................................................... 38
Naming ..................................................................30
Device ................................................................... 37
Properties...............................................................23
File ........................................................................ 34
Status.....................................................................23
Select .................................................................... 36
Disclaimer and contact information ............................40
Tools ..................................................................... 39
Floorplan ...................................................................11
View ...................................................................... 35
Project Configuration................................................... 3
Getting Started ............................................................9
Upload................................................................... 17
Groups..................................................... 16, 25, 28, 30
Creating Groups.....................................................16
Functional Grouping ...............................................28
Group View ............................................................25
Naming ..................................................................30
Restore backup......................................................... 31
Screen Appearance .................................................... 4
Toggle................................................................. 19, 20
Icons..........................................................................26
Auto Toggle ........................................................... 20
Installation ...............................................................7, 8
Conrol Unit ............................................................ 29
Hardware .................................................................7
Toggle time-out...................................................... 19
Software...................................................................8
Introduction..................................................................2
Welcome..................................................................... 1
39

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
Page Count                      : 43
Producer                        : GPL Ghostscript 8.15
Create Date                     : 2009:06:29 11:02:38
Modify Date                     : 2009:06:29 11:02:38
Title                           : Microsoft Word - Printed_Documentation_SenzaFil_English.doc
Creator                         : PScript5.dll Version 5.2
Author                          : martin.gotink
EXIF Metadata provided by EXIF.tools
FCC ID Filing: CGD-SF-USB

Navigation menu