Nedap N V SFSB Data Transmission System applied with a Sensor Bridge for lamps User Manual 01
N. V. Nederlandsche Apparatenfabriek NEDAP Data Transmission System applied with a Sensor Bridge for lamps 01
Contents
- 1. User manual 01
- 2. User manual 02
User manual 01
Page 1 of 7
Installation Manual
PCB Sensor Bridge
for the application example:
Luxon Sensor Bridge
February 2011
Page 2 of 7
1. Brief product description
With the Luxon Sensor Bridge commercially available sensors can be added to the Nedap Luxon light control system.
During the installation process the Sensor Bridge will become part of the wireless Senzafil Mesh Network, over which
data is transferred. The light controller now can control light levels using data from remote sensors for light, motion and
occupancy detection and from switches and 0-10V controls like electronic potentiometers.
Figure 1. Installation example for the Luxon Sensor Bridge with HID lamps controlled via RF by
a Mesh Network in a building with skylights
Page 3 of 7
2. Assembly overview for the Luxon Sensor Bridge
Figure 2. Overview Sensor Bridge assembly
The Sensor Bridge is fitted in a rugged plastic housing with a sealing to obtain IP67 protection for dust and
moist, see Figure 2.
Cable glands shall be included, they must be mounted for IP67 protection.
The PCB sensor bridge has a small cutout that should fit the notch in the cover to prevent mounting the
PCB the wrong way.
Page 4 of 7
3. Positioning
The Sensor Bridge shall be placed at a maximum distance of 40 meters from the nearest node operating within the
same group. Avoid using a long cable (>>20m) to the sensor.
Note: The Sensor Bridge shall never be installed inside a metal power cabinet. This would impede
wireless communication.
Fig 3 No installation of the Luxon Sensor Bridge inside a metal enclosure
4. Mounting instructions for the Luxon Sensor Bridge
Prior to fixation, assemble the two cable glands to the unit’s enclosure. If only one gland is to be used, close the other
opening with an appropriate plug to maintain IP 67 enclosure protection level if necessary.
The surface or wall mount Sensor Bridge shall be mounted using 2 ball or cylinder head screws with maximum head
diameter of 9 mm, corresponding holes shall be (pre-)drilled 94 mm apart. See also figure 4.
Figure 4. location and pinning of connectors in wall mount bottom part
Page 5 of 7
Overview of inputs and outputs below, see also Fig.4 for locations.
Supply (*) + +12 to +24Vdc +/- 5%
Note that the voltage to be used depends on the used sensor
Input current: 0.3A max.
0V 0V - Gnd
Supply Alternative supply connection via DC-jack with 2mm centre pin,
Centre pin is positive, shield is 0V - Gnd
Sensor Supply Supply for sensor, same level as Supply +
Current 200mA max.
0V 0V - Gnd
Sensor Input Connect to sensor output.
5. Powering the Sensor Bridge system
Fig 5 shows an installation example for the Luxon Sensor Bridge with sensor and mains adapter.
Figure 5. Wiring overview for the Luxon Sensor Bridge system
Powering:
The Sensor Bridge is powered from a mains adapter or similar DC-source supplying 12 to 24V. This
voltage is also available for the sensor, so you can choose the supply voltage depending on the voltage
needed for the sensor to be used.
Power connection via either a standard DC-plug or screw terminals.
Many sensor types can be used:
- Switches;
- 1 to 10V dimmers (resistive and electronic potentiometers);
- Light sensors;
- Sensors for detection of movement and / or room occupancy.
Safety notes: An isolated limited power supply shall be used. For USA/Canada use a UL-listed class 2
limited power supply (E.g. MEAN WELL type GS06U, GS12U)
If a separate supply will be used for the sensor, this supply shall also meet the
requirements for a class 2 limited power supply.
Page 6 of 7
6. Specifications for application Luxon Sensor Bridge
7. FCC and IC Declarations for Luxon Sensor Bridge
English:
This device contains PCB Sensor Bridge p/n 7834802 with
FCC ID: CGDSFSB and IC: 1444A-SFSB
Compliance statement
This device complies with part 15 of the FCC Rules and to RSS210 of Industry Canada.
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation.
Déclaration Conformité
Cet appareil se conforme aux normes RSS exemptés de license du Industry Canada.
L'opération est soumis aux deux conditions suivantes
(1) cet appareil ne doit causer aucune interférence, et
(2) cet appareil doit accepter n'importe quelle interférence, y inclus interférence qui peut causer une opération non pas
voulu de cet appareil.
Warning
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s
authority to operate the equipment.
RF Exposure
To comply with FCC RF exposure requirements for mobile transmitting devices, this transmitter should only be used or
installed at locations where there is at least 20cm separation distance between the antenna and all persons.
Operating temperature
Safety
EMC
/Telecom
-
40 to
+7
0°C
EN60950 ,
UL916
EN301489-1, EN300328 V1.7.1
FCC47 part
15
and IC
RSS210
Wire section range for the
screw connector
Enclosure protection degree
IP67 (with both cable glands assembled
correctly)
Dimensions
Diameter 130mm, height 70mm
Max 1.5sqmm or AWG15
ESKV 16mm gland: 4.5 to 10mm
ESKV 20mm gland: 6 to 13mm
Cable clamp range
Input Supply 10.5 to 28 Vdc, max 300mA
10.5 to 28 Vdc , max 200mA
Sensor Operating
Voltage
Sensor Input Voltage
0 t
o 28 Vdc
Page 7 of 7
8. Label artwork for application Luxon Sensor Bridge
Label artwork for Sensor Bridge Wall Mount
To scale:
This device complies with part 15 of the FCC Rules and to
RSS210 of Industry Canada. Operation is subject to the
following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference
received, including interference that may cause undesired
operation.
Luxon
P/N: 8018669
Input: 12 to 24Vdc max 0.3A
Enclosure IP67 rated – Suitable for wet locations
Model: Sensor Bridge Wall Mount
This device contains PCB Sensor Bridge p/n 7834802
with FCC ID: CGDSFSB IC: 1444A-SFSB
S/N: xxxx xxxx
Output: 12 to 24Vdc max 0.2A
Scale 200%
This device complies with part 15 of the FCC Rules and to
RSS210 of Industry Canada. Operation is subject to the
following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference
received, including interference that may cause undesired
operation.
Luxon
P/N: 8018669
Input: 12 to 24Vdc max 0.3A
Enclosure IP67 rated – Suitable for wet locations
Model: Sensor Bridge Wall Mount
This device contains PCB Sensor Bridge p/n 7834802
with FCC ID: CGDSFSB IC: 1444A-SFSB
S/N: xxxx xxxx
Output: 12 to 24Vdc max 0.2A
Upper Label 50x30mm
Lower Label 50x12.5mm.