Neptune Technology Group R450DC DATA COLLECTOR User Manual IM R450 Rack Mount DC
Neptune Technology Group Inc. DATA COLLECTOR IM R450 Rack Mount DC
Contents
- 1. 450-Rack Mount DC Manual 2
- 2. User Manaul Rack Mount DC
450-Rack Mount DC Manual 2
Chapter 4: Uninterruptible Power Supply Connecting the UPS This section provides information on what tools, materials and procedures are needed to connect the UPS. Tools and Materials Required The following list describes the tools and materials needed to connect the UPS. Slotted-tip screwdrivers for tightening screws on terminal blocks. AC/DC voltmeter. Procedures Complete the following steps. Step 1: Wiring the Input and Output Connectors 1. Remove the two screws that secure the UPS cover. 2. Remove the UPS cover. Figure 34 – Wire Input and Output Connectors The UPS contains a vent on the upper right side of the case; do not remove this. Step 2: Installing and Wiring the Batteries 1. Install Liquid-Tight Flexible Non-Metallic Conduit from the disconnect switch to the lower 1/2' conduit hole on the side of the UPS. 2. Install the black, white, and green wires through the conduit and terminate to the terminal block inside the UPS. 40 R450 Rack Mount DC Installation and Maintenance Guide Chapter 4: Uninterruptible Power Supply Powering ON the UPS 1. Install the DC cord grip in the upper 1/2" conduit hole on the side of the UPS; just above the conduit. 2. Route the open pigtail end of the DC power cable through the cord grip and terminate to the DC terminal block inside the UPS. 3. Tighten the DC cord grip using pliers or a wrench. 4. Attach the power cord to the bottom of the R450 RM DC. 5. Turn the UPS power switch on. 6. Re-install the UPS cover and secure it with the two screws. Servicing the UPS This section provides information on servicing the UPS. CAUTION: Before attempting to service the UPS, verify that the disconnect device is turned OFF. Also verify that the UPS switch is turned OFF. Checking UPS Status LEDs This section provides information on checking and troubleshooting the UPS. Complete the following steps to check the UPS status if the R450 RM DC will not power up. 1. Remove the power plug from the bottom of the R450 RM DC. 2. Measure between pin-1 (+) and pin-2 (-) on the plug. The voltage should measure 13.5-14.4 VDC. See Figure 35. Figure 35 – R450 RM DC Power Plug If the voltage measures okay, then there is a problem with the R450 RM DC. Refer to "Potential R450 RM DC Problems" on page 46. R450 Rack Mount DC Installation and Maintenance Guide 41 Chapter 4: Uninterruptible Power Supply If the voltage is negative, there is a problem with the UPS wiring. Complete the following steps. 1. Remove the UPS cover . 2. Correct the wiring issue. 3. Recheck wiring. If there is no voltage present or the voltage is low (< 10.5V DC), complete the following steps. 1. Remove the two screws that secure the UPS cover. 2. Remove the cover. 3. Verify the internal power switch is on. 4. Check the status LEDs inside the UPS. See Table 8 below. Table 8 – UPS Status LEDs LED Indicators Green Description Solid on = AC okay Off = AC failure Yellow Solid on = battery fully charged Blinking slowly = battery charging Blinking rapidly = battery is discharging (possible AC input voltage failure) Red DC output is faulty (fuse may be blown) 5. Verify the UPS is producing the correct voltage at the output terminals by measuring across DC+ (red) and DC- (black). The voltage should measure 13.5-14.4 VDC. This assumes the AC input voltage is present and the UPS internal switch is on (i.e., battery should be charging). If the AC input is not present, then the voltage across DC+ (red) and DC- (black) should measure 10.5-12.8 VDC. 42 R450 Rack Mount DC Installation and Maintenance Guide Chapter 4: Uninterruptible Power Supply If the voltage is less than 10.5 VDC, this indicates a fully discharged battery and must be recharged. Complete the following steps. 1. Measure the AC input voltage across L1 and N1. The voltage should measure 100-140 VAC. 2. Verify the UPS's internal switch is On. 3. Check the UPS status LEDs. See Table 8. Checkup Complete After the UPS diagnostics has been completed, perform the following steps. 1. Re-install the UPS cover. 2. Secure cover with two screws. R450 Rack Mount DC Installation and Maintenance Guide 43 Chapter 4: Uninterruptible Power Supply This page intentionally left blank. 44 R450 Rack Mount DC Installation and Maintenance Guide Chapter 5: Troubleshooting This section provides information for possible symptoms, areas of focus, and actions that can be taken to resolve problems that could arise with your R450 Rack Mount Data Collector (R450 RM DC). Equipment Required The following items are required in order to troubleshoot the R450 RM DC. Keys to access the site and open the R450 RM DC cabinet. Digital volt - Ohm multimeter Voltage Standing Wave Ration (VSWR) meter Socket and open-end wrenches to install/remove the R450 RM DC Small, medium, and large slot style screw drivers #1 and #2 Phillips Head screw drivers Electrical tape and wire ties Backup R450 RM DC, if one fails R450 RM DC configuration USB flash drive The USB flash drive must be configured for the specific R450 RM DC. Anti-static wrist strap and ground lead with alligator clip for attaching wrist strap to the R450 RM DC cabinet MIU configured for site Magnet to swipe MIU R450 System Field Service Tool R450 Rack Mount DC Installation and Maintenance Guide 45 Chapter 5: Troubleshooting PC Notebook Configuration In order to use a notebook computer, consider the following. The CalAmp modem requires an Ethernet cable to connect to the network port of the computer. The CalAmp modem uses an online application for configuration. It does not require software to be installed to configure the modem. Refer to the cellular modem's Quick Start Guide for log on and setup instructions. WARNING: Neptune does not recommend servicing an R450 RM DC during inclement weather. Potential R450 RM DC Problems The following sections describe problems that can arise and how to handle these potential problems. Multiple R450 DCs Not Syncing with Host Database Consider the following. Host database server is down or not connected to the Internet. Remote Internet, phone, cable, or cell service provider is either down or experiencing degraded service. Multiple power outages affecting several sites. Storm Damage Affecting Multiple Sites One R450 RM DC is not syncing with the host database. Troubleshooting this problem requires going to the R450 RM DC site. First Steps Before leaving for the site, assess the health of the R450 RM DC using the host system. For instructions on how to assess the health of the R450 RM DC, refer to "Using System Health" in the "System Health" chapter of the N_SIGHT® R450 Online Help. 46 R450 Rack Mount DC Installation and Maintenance Guide Chapter 5: Troubleshooting If the R450 RM DC is offline, this indicates that they power, power supply, CPU, or backhaul modem may not be functioning. Some sites are configured so that an operator can log on the R450 RM DC remotely and look at the logs and watch the system activity. If the R450 RM DC is offline but it is still possible to log on the system, this indicates that the computer and backhaul modem are both functional. Initial Site Activities Open the R450 RM DC and inspect the equipment. Make sure that there is no obvious physical damage to the system, such as evidence of burned components or wires, which may indicate a lightning strike. If there is any evidence of physical damage, the R450 RM DC should be replaced with the spare and returned to Neptune's repair facility. CAUTION: The ground wrist strap must be clipped to the box. Do not touch the computer circuit board or any of the components if you are not wearing the wrist strap. Failure to use the strap could cause damage to the computer due to static electricity. Checking the General Health of Each of the Modules Visual Check of CPU Board Power There are three Ethernet Status Light Emitting Diodes (LEDs) to the left of the Ethernet RJ45 connector. The red LED closest to the connector should be lit if there is power being supplied to the CPU board. See Figure 36. Figure 36 – Ethernet Status LED R450 Rack Mount DC Installation and Maintenance Guide 47 Chapter 5: Troubleshooting Visual Check of Radio Power The radio has several indicator LEDs on the front panel. The green Power indicator should be on. See Figure 37. If the amber ALM LED is on, the radio is malfunctioning. Figure 37 – Radio LEDs on Front Panel Visual Check of Backhaul Modem Power and Connectivity Cal Amp Vanguard Modem Look at the indicator lights on the modem to verify if the modem is working. See Figure 38. If the RSSI and SVC lights are on, this indicates that the modem is connected. If the RSSI and SVC lights are not on, this indicates that there is a power problem with the modem. Verify that the main power is on. If the SVC light is solid, the modem is connected to the cellular network. See Table 9 on the facing page. If the SVC light is flashing, the modem is trying to connect to the network. See Table 9 on the facing page. Figure 38 – Modem Indicator Lights 48 R450 Rack Mount DC Installation and Maintenance Guide Chapter 5: Troubleshooting The LEDs behavior is different than the table below at boot. The sequence is: all read, all amber, all green, and all flash green Table 9 – Modem Status LEDs Function Off Green RSSI Strong SVC (cellular network connection) 36/4G NET No connectivity GPS Disabled Fix AUX Disabled Good Flash Green Red Flash Red Weak/None Flash Amber Medium 3G/4G/NC NC Rx data Tx data Search Amber 2G 2G/NC Rx/Tx no fix Failed Additional Detail Checks If any of the previous checks failed, the following detail checks should be performed. Power supply voltage checks should be made one at a time so that a load remains on the power supply. This is especially true of the CPU and modem voltage checks. With no load on the power supply, erroneous values may be measured. Verify Main Power Usually, it is a good practice to check the main power and make sure it is within specification. If there are no power indications on in the R450 RM DC, this must be checked. The circuit breaker should be in the ON position. Verify that it has not tripped. Using the voltmeter, verify that there is 120V AC on both the AC feed and the power supply sides of the circuit breaker. R450 Rack Mount DC Installation and Maintenance Guide 49 Chapter 5: Troubleshooting If voltage is not present on the AC feed side of the circuit breaker or is less than 110V, there is something wrong with the supply voltage. Repairing this is outside of the scope of this manual The R450 RM DC is capable of functioning on voltages as low as 90V. If voltage is not present on the power supply side of the circuit breaker and the circuit breaker is not tripped, the breaker is damaged. If the circuit breaker is damaged, it is recommended that the R450 RM DC be returned for repair. Verifying CPU Board Power Neptune recommends checking the voltage levels going to the computer. 1. Put on your wrist strap and attach the alligator clip to the cabinet. 2. Turn off the circuit breaker. 3. Remove the 10-pin connector located in the upper left corner of the CPU Board. There is a locking tab on the bottom side of the connector. 4. Turn the circuit breaker back on. Figure 39 – Red and Black Leads 50 R450 Rack Mount DC Installation and Maintenance Guide Chapter 5: Troubleshooting 5. Use the Digital Volt-Ohm-Multimeter to measure the voltage. The red leads are positive; the black leads are negative. 6. The voltage must be between 4.9V and 5.2V. Turn off the R450 RM DC circuit breaker. If the voltage is above or below these values, it indicates that the power supply is defective. Return the R450 RM DC to Neptune's repair facility. 7. Reconnect CPU power. Verifying Radio Power 1. Turn off the circuit breaker if it is not already off. 2. Remove the BATT connector on the radio. The locking ring unscrews. 3. Turn the circuit breaker back on. 4. On the power cable connector, measure the voltage across pins X and Y as shown. 5. The voltage should be between 14.5V and 15.5V. If the voltage is above or below these values, the power supply is defective and the R450 RM DC should be returned to Neptune's repair facility. 6. If the voltage is within specifications, turn the circuit breaker off and replace the connector. Make sure that the connector locking ring is finger tight. Verifying Cellular Modem Power Cal Amp Vanguard Modem Approximately 12.0 V should be present between the two pins shown as illustrated in the following figure. Figure 40 – R450 Rack Mount DC Installation and Maintenance Guide Vanguard Three Wires 51 Chapter 5: Troubleshooting Verifying Cellular Modem Connectivity Cal Amp Vanguard Modem To verify connectivity and signal levels, complete the following. 1. Locate the RSSI LED light on the modem. 2. Identify how the light is lit. Solid = indicates signal strength is strong Blinking = indicates signal strength is medium Off = indicates signal strength is poor or no signal at all Figure 41 – CalAmp Vanguard Modem with RSSI LED 3. If the signal strength is poor or if there is no signal at all, there is something wrong with the antenna, or it is possible that the local cell service is not working. For more detailed information on your wireless connection status, connect to the modems configuration application. Refer to "Securing the R450 RM DC" on page 27. Ethernet If Ethernet backhaul is used, then check the status lights on the CPU board. Refer to "Testing the Connections" on page 24. 52 R450 Rack Mount DC Installation and Maintenance Guide Chapter 5: Troubleshooting Verifying Radio Functionality Using an MIU To verify that the system is functioning properly, complete the following steps. For this test to be valid, there must be regular time beacon transmissions sent by the R450 RM DC. This is indicated by the TX indicator flashing every ten seconds. See Figure 37 on page 48. If the R450 RM DC is not sending out time beacons, this test will automatically fail. 1. Obtain a magnet and an MIU. 2. Swipe the MIU with a magnet so that it will send out a configuration packet. 3. Watch for the radio's Busy light to turn on. This should happen within a minute of swiping the MIU. If the Busy light turns on, it should be followed by an immediate flash of the TX indicator. See Figure 41 on page 52. If the Busy indicator is not immediately followed by a flash of the TX indicator, then there is an internal problem with the R450 RM DC that may include its configuration, the radio, NTG modem, or the computer. R450 RM DC is Syncing but Not Supplying MIU Data If the R450 RM DC is online, this indicates that the computer and the backhaul modem are both working. If no readings are being collected by the R450 RM DC, this indicates that there is a potential problem with the radio and modem. Troubleshooting this problem requires going to the R450 RM DC site. Initial Observations After opening the cabinet, assess the following. The R450 RM DC sends out a time beacon every 10 seconds. The transmit light on the radio should flash every 10 seconds. See Figure 37 on page 48. Only the red transmit light should turn on. If the amber ALM indicator turns on at the same time, this indicates that there is a problem between the transmitter and the antenna. If the transmit indicator does not flash, this indicates that there is a potential problem with the modem or possibly the computer's serial port. R450 Rack Mount DC Installation and Maintenance Guide 53 Chapter 5: Troubleshooting Transmitter Transmits but ALM Indicator Flashes This requires measuring the Voltage Standing Wave Ratio of the antenna system. If the VSWR is greater than 1.5:1, that indicates that there is a problem with the feed line or the antenna. Measuring the VSWR To measure the VSWR (MFJ-269 SWR Analyzer), complete the following steps. 1. Make sure the red Power button is off. The red button is extended outward. 2. Press the UHF button to be sure it is extended outward. 3. Turn the Frequency knob fully counter-clockwise. This knob points to 114-170/UHF. 4. Connect the 2-inch long attenuator pad to the Antenna Connector. Leave the other end open. 5. Press and lock the red Power button and the black UHF button. 6. Adjust the Tune knob for desired frequencies. Sweep the entire 450 - 470 MHz range. 7. Observe the indicated VSWR. It should read 3.0 ± 0.2 This indicates that the unit is calibrated correctly and the batteries are good. If the reading is outside this range, then try replacing the batteries (eight AA batteries). If this does not improve the readings, the unit needs to be recalibrated. 8. Power off the unit. 9. Remove the attenuator pad and connect the antenna from the bottom of the collector. 10. Press and lock the red Power button and the black UHF button. 11. Adjust the Tune knob for desired frequencies. Look at both the collector receive and transmit frequencies. 12. Observe the indicated VSWR. The value should be 1.5 or less. A value of 1.0 is ideal but not practical. Usually values are 1.1 or 1.2. If a flashing SLP indication appears in the bottom-right corner of the display, this indicates Sleep mode. Simply turn the unit off and then on again. 54 R450 Rack Mount DC Installation and Maintenance Guide Chapter 5: Troubleshooting 13. When finished, power off the unit. The Radio Never Transmits The simplest test is to cycle power on the R450 RM DC to see if the radio starts transmitting. It can take up to 10 minutes for the R450 RM DC to be fully functional. If radio starts transmitting, this indicates that there was a soft failure in one of the serial ports possibly related to the side effects of a storm. If this does not fix the problem, then the R450 RM DC has an internal problem, either with the computer or the Neptune modem. It is recommended that you return the R450 RM DC for repair. Reduction in Amount of Data Collected If the R450 RM DC is not collecting as much data as before, but it is still collecting some MIU data, this usually indicates that there is a problem with the antenna and feedline system or possibly an internal problem. To determine the cause of the problem, complete the following steps. 1. Check all the system voltages as outlined above. 2. Check the VSWR of the system using the technique previously described. If the VSWR is high, the feedline and antenna should be checked out and certified by qualified radio personnel. 3. Check the VSWR again, if the power output is low, by placing the wattmeter between the duplexer and the surge protector. If the VSWR measures much higher before the surge suppressor, the suppressor may be damaged. If the above tests pass, most likely there is s problem with the duplexer or radio, and it is recommended that you contact Customer Support R450 Rack Mount DC Installation and Maintenance Guide 55 Chapter 5: Troubleshooting Contacting Customer Support Within North America, Neptune Customer Support is available Monday through Friday, 7:00 AM to 5:00 PM Central Standard Time by telephone, email, or fax. By Phone To contact Neptune Customer Support by phone, complete the following steps. 1. Call (800) 647-4832. 2. Select one of the following options: Press 1 if you have a Technical Support Personal Identification Number (PIN). Press 2 if you do not have a Technical Support PIN number. 3. Enter the six-digit PIN number and press #. 4. Select one of the following options. Press 2 for Technical Support. Press 3 for maintenance contracts or renewals. Press 4 for Return Material Authorization (RMA) for Canadian accounts. You are directed to the appropriate team of Customer Support Specialists. The specialists are dedicated to you until the issue is resolved to your satisfaction. When you call, be prepared to give the following information. Your name and utility or company name. A description of what occurred and what you were doing at the time. A description of any actions taken to correct the issue. By Fax To contact Neptune Customer Support by fax, send a description of your problem to (334) 283-7497. Please include on the fax cover sheet the best time of day for a customer support specialist to contact you. By Email To contact Neptune Customer Support by email, send your message to support@neptunetg.com. 56 R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation RF Antenna Overview There are a number of critical items you must consider when placing and installing the antenna. The following list contains items that can influence the antenna placement and installation. Mounting the Antenna Consider the following when mounting the antenna. 1. Mount the antenna as high as possible with an unobstructed view of the coverage area. The supporting structure, if the antenna is not mounted above it, can cause specific areas of limited coverage. Water towers in particular can severely limit coverage where the signal must pass directly through the tank. When mounting the antenna on a water tower, it is recommended that they be mounted on top as close to the center as possible. When mounting the antenna on a traditional three-leg or four-leg tower, the standoff mount for the antenna must position the antenna at least five feet away from the tower to minimize coverage area problems. 2. Avoid making the R450 Data Collector's (R450 RM DC) antenna the tallest point in the surrounding area. This may be unavoidable but it increases the potential of the antenna being damaged by lightning. Mounting the Antenna Mast Consider the following. CAUTION: The antenna mast and stand must be grounded to the same grounding electrode used for the building's electrical system to ensure that all exposed, non-currentcarrying metal parts are the same potential. Refer to NEC Article 810. When mounting the antennas and antenna mast, it is important to maximize the line-of-sight relationship between the RF 450 MHz Antenna and R450 MIUs for optimum RF communications. R450 Rack Mount DC Installation and Maintenance Guide 57 Appendix A: RF Antenna Installation WARNING: Antenna contact with high voltage wires may result in death. Watch for overhead electric power lines when erecting the antenna and mast. WARNING: Do not mount antennas on utility poles, electric service masts, or other structures carrying electric light or power wires. Coaxial cables must maintain clearance of at lease 2 feet (.61 M) from power or light wires of less than 250V, or at least 10 feet (3.048 M) from power wires of more than 250V, per N.E.C., Article 810, C.E.C. Section 54. Site Recommendations The following are recommendations for sites with multiple transmitters, receivers, and antennas. These sites require extra care when determining a location to install the antenna. 58 Avoid mounting the R450 RM DC antenna so that it is at the same height as another antenna on the site, regardless of the frequencies. For sites that have multiple antennas, if possible, mount the antennas one above the other, separating each by at least 10 feet vertically. This will minimize the interference between the systems. The exception to the previous rule is for cellular antennas. As long as the R450 RM DC antenna is either above, below, or in the middle of the ring of cell antennas, the two systems can coexist without interference. Antenna sites that must share space with multiple transmitting systems may require additional equipment to protect the systems from interfering with each other. These sites may also require additional engineering to make them perform well. R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation If there are radio systems at the site that are already operating on the 450 - 470 MHz band, it may be advantageous to combine the signals into one antenna system using the appropriate equipment. This often works better than attempting to protect the individual systems from interfering with each other. Managed antenna sites may require additional equipment and may dictate how an installation is to be performed. As long as the installation meets Neptune's minimum requirements, following the site's requirements is recommended. Feed Line and Antenna Recommendations CAUTION: Neptune recommends that you consult with a qualified installer on the design and installation of the antenna systems. If the installer is already familiar with the sites and the existing equipment, this can make the installation go more smoothly. Feed Line The feed line is a significant contributor to both good and poor system performance. A properly installed feed line is critical to optimal system performance. Testing the antenna while it is on the ground can ensure the system is working properly. Installation of the connectors is best done with the proper tools and a trained installer. With the proper tools and jigs, installing coaxial (coax) connectors takes only a few minutes each. Not using the proper tools as recommended by the manufacturer could potentially cause problems, either immediately or after several years of apparently proper operation. Feed Line Requirements Consider the following. The antenna and feed line system installation must be certified by the installer after it is completed to perform according to specifications. Maximum loss for the feed line and connectors must be less than 3 dB. The feed line must be bonded at the top of the tower and at the base of the tower. Andrew grounding kits and procedures should be used for all bonds. R450 Rack Mount DC Installation and Maintenance Guide 59 Appendix A: RF Antenna Installation For towers over 150 feet tall, the feed line should be bonded at regular intervals down the tower. The general recommendation is that the feed line be bounded by a minimum of 200 feet. Site requirements and standard practices should dictate the configuration. An optional surge protector may be installed on the tower near the antenna to help protect the feed line but is not required. For the AVA5-50 cable or larger, jumpers should be used to go between the larger cable and the R450 RM DC and antenna connectors. Andrew provides installation instructions for Heliax Coaxial Cable. See Bulletin 17800B Revision C. Neptune can supply a PDF copy by request through Customer Support. Cable Guidelines Prepare the cable for installation and check for damage. You will need the following materials to install the cable. Table 10 – Material Needed for Cable Installation Action Hoisting the Cable Anchoring Cable Grounding Horizontal Cable Runs Cable Connections Measurements 60 Material Needed Hoist lines Pulleys Cable reel Hoisting grips Cable hangers (standard, snap-in) 3 to 4 ft. intervals Coax ground kits (top, bottom, building entrance) Above ground - ice bridge Buried cable - conduit or sand below the frost line or one meter Connector installation instructions Connector torque Weatherizing kits Return Loss (VSWR) Distance to Fault (DTF) R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation Neptune Part Numbers The following tables provides Neptune part numbers for cable and connectors. Table 11 – Neptune Part Numbers for Cable and Connectors Neptune Part Number Andrew Part Number Coax Diameter Loss per 100' Minimum Bend Radius Weight per Foot Maximum Length Notes 10046-119 LDF4-50A 1/2" 1.45 dB 5" 0.15 150' Recommended antenna cable for 150' cable runs or less 10046-118 AVA5-50 7/8" 0.74 dB 10" 0.30 400' Recommended antenna cable for runs over 150' The following tables contain the Neptune part numbers for connectors and accessories. Table 12 – Connectors and Accessories Cable Type Neptune Part Number Andrew Part Number Coax Diameter Notes 10046-117 F4A-PNMDM-6USA Pre-made Coax 6' Jumper DIN Male on one end, N Male on the other Used as jumper from feed line to R450 RM DC or antenna 8138-200 L4TNM-PS Coax Connector, N Male Mates with R450 RM DC and antenna connectors SG12-12B2U SureGround Grounding Kit for 1/2 " coax ALDF-PS Coax Connector, 7/16" DIN Female FSJ4-50B LDF4-50A AVA5-50 8138-190 Used to connect to FSJ4 jumper cable For the long-term protection of all RF connections, use the appropriate Andrews weatherproofing kit (Andrews P/N 245171) on all coaxial connectors. R450 Rack Mount DC Installation and Maintenance Guide 61 Appendix A: RF Antenna Installation Antenna General specifications for the supplied antenna are shown in the table below. Neptune P/N 12896-001 Andrew P/N DB636-C Frequency Range 450-482MHz Maximum Input Power (Watts) 500 Gain 8.1 dBi (6 dBd) Bandwidth > 1.5VSWR 32 MHz Vertical Bean Width (-3 db) 20 Degrees Lightning Protection Direct Ground Termination N Female Overall Length 9.3 Feet Element Housing Length 6.8 Feet Support Pipe Diameter 2.5 inches Support Pipe Length 26 Inches Wind Load 1.61 Square Feet Rated Wind Velocity 225 MPH Weight 30 lbs Mounting Hardware Included DB365 Clamps Requirements 62 The antenna, if mounted on the side of a tower or other supporting structure, must be mounted so that it is at least five feet away from the structure. The components to offset the antenna are specific to the installation and are not included by Neptune with the R450 RM DC package. The antenna is large and care must be taken when hoisting it up a tower so that it is not damaged. The feed line should not be attached to the antenna while it is being hoisted up the tower or other supporting structure. The feed line should be attached after the antenna is in place. There have been reports of damage to the antenna's N connector where the center pin has become bent and shorts out the antenna system. Care must be taken not to damage the connector. R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation System Certification The Andrews antenna supplied with the R450 RM DC is specified as having a VSWR of 1.5:1 or better over the 450 - 470 MHz range. Measuring VSWR at the R450 RM DC must take into account losses in the feed line. For instructions, see “Measuring the VSWR” on page 68. The easiest approach is to use return loss instead of VSWR. The 1.5:1 VSWR translates into a return loss of 13.98dB. Refer to Table 13 below, Table 14 on the next page and Table 16 on page 70 to assist with the calculation. It is recommended that the feed line be certified as a separate step. This is best performed by putting a known amount of power into one end of the cable and verifying that, after correcting for the cable losses, the correct amount of power is coming out the other end. Power Measurement Table 13 – Power Measurement to Return Loss and VSWR Conversion Table -Part I Input Power 1W 5W 10W Reflected Power Reading Return Loss VSWR 0.001 0.005 0.01 30.0 1.07 0.002 0.010 0.02 27.0 1.09 0.003 0.015 0.03 25.2 1.12 0.004 0.020 0.04 24.0 1.14 0.005 0.025 0.05 23.0 1.15 0.006 0.030 0.06 22.2 1.17 0.007 0.035 0.07 21.5 1.18 0.008 0.040 0.08 21.0 1.20 0.009 0.045 0.09 20.5 1.21 0.010 0.050 0.10 20.0 1.22 0.020 0.100 0.20 17.0 1.33 0.030 0.150 0.30 15.2 1.42 0.040 0.200 0.40 14.0 1.50 0.050 0.250 0.50 13.0 1.58 R450 Rack Mount DC Installation and Maintenance Guide 63 Appendix A: RF Antenna Installation Table 13 – Power Measurement to Return Loss and VSWR Conversion Table -Part I (continued) Input Power 1W 5W 10W Reflected Power Reading Return Loss VSWR 0.060 0.300 0.60 12.2 1.65 0.070 0.350 0.70 11.5 1.72 0.080 0.400 0.80 11.0 1.79 0.090 0.450 0.90 10.5 1.86 0.100 0.500 1.00 10.0 1.92 0.110 0.550 1.10 9.59 1.99 0.120 0.600 1.20 9.21 2.06 0.130 0.650 1.30 8.86 2.13 0.140 0.700 1.40 8.54 2.20 0.150 0.750 1.50 8.24 2.26 0.160 0.800 1.60 7.96 2.33 0.170 0.850 1.70 7.70 2.40 0.180 0.900 1.80 7.45 2.47 0.190 0.950 1.90 7.21 2.55 0.200 1.000 2.00 6.99 2.62 Table 14 – Power Measurement to Return Loss and VSWR Conversion Table -Part II Input Power 1W 5W 10W Reflected Power Reading 64 Return Loss VSWR 0.20 1.05 2.10 6.78 2.69 0.22 1.10 2.20 6.58 2.77 0.23 1.15 2.30 6.38 2.84 0.24 1.20 2.40 6.20 2.92 R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation Table 14 – Power Measurement to Return Loss and VSWR Conversion Table -Part II (continued) Input Power 1W 5W 10W Reflected Power Reading Return Loss VSWR 0.25 1.25 2.50 6.02 3.00 0.26 1.30 2.60 5.85 3.08 0.27 1.35 2.70 5.69 3.16 0.28 1.40 2.80 5.53 3.25 0.29 1.45 2.90 5.38 3.33 0.30 1.50 3.00 5.23 3.42 0.31 1.55 3.10 5.09 3.51 0.32 1.60 3.20 4.95 3.60 0.33 1.65 3.30 4.81 3.70 0.34 1.70 3.40 4.69 3.80 0.35 1.75 3.50 4.56 3.90 0.36 1.80 3.60 4.44 4.00 0.37 1.85 3.70 4.32 4.11 0.38 1.90 3.80 4.20 4.21 0.39 1.95 3.90 4.09 4.33 0.40 2.00 4.00 3.98 4.44 0.41 2.05 4.10 3.87 4.56 0.42 2.10 4.20 3.77 4.68 0.43 2.15 4.30 3.67 4.81 0.44 2.20 4.40 3.57 4.94 0.45 2.25 4.50 3.47 5.08 0.46 2.30 4.60 3.37 5.22 0.47 2.35 4.70 3.28 5.36 0.48 2.40 4.80 3.19 5.51 0.49 2.45 4.90 3.10 5.67 R450 Rack Mount DC Installation and Maintenance Guide 65 Appendix A: RF Antenna Installation Coax Cable Loss Table 15 – Coax Cable Loss Table Coax Type FSJ4-50B LDF4-50A AVA5-50 Coax Type FSJ4-50B LDF4-50A AVA5-50 Loss 100 ft. 2.31 dB 1.45 dB 0.744 dB Loss 100 ft. 2.31 dB 1.45 dB 0.744 dB Length (ft.) Loss in dB Length (ft.) Loss in dB 10 0.231 0.145 0.074 210 4.851 3.045 1.562 20 0.462 0.290 0.149 220 5.082 3.190 1.637 30 0.693 0.435 1.223 230 5.313 3.335 1.711 40 0.924 0.580 0.298 240 5.544 3.480 1.786 50 1.155 0.725 0.372 250 5.775 3.625 1.860 60* 1.386 0.870 0.446 260 6.006 3.770 1.934 70* 1.617 1.015 0.521 270 6.237 3.915 2.009 80* 1.848 1.160 0.595 280 6.468 4.060 2.083 90* 2.079 1.305 0.670 290 6.699 4.205 2.158 100* 2.310 1.450 0.744 300 6.930 4.350 2.232 110 2.541 1.595 0.818 310 7.161 4.495 2.306 120 2.772 1.740 0.893 320 7.392 4.640 2.381 130 3.003 1.885 0.967 330 7.623 4.785 2.455 140 3.234 2.030 1.042 340 7.854 4.930 2.530 150 3.465 2.175 1.116 350 8.085 5.075 2.604 160 3.696 2.320 1.190 360 8.316 5.220 2.678 170 3.927 2.465 1.265 370 8.547 5.365 2.753 180 4.158 2.610 1.339 380 8.778 5.510 2.827 190 4.389 2.755 1.414 390 9.009 5.655 2.902 200 4.620 2.900 1.488 400 9.240 5.800 2.976 * Acceptable Range 66 R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation VSWR Calculation Neptune recommends the following method of computing VSWR. Taking the reading at the R450 RM DC end of the feed line without compensating for cabling losses may give a false impression of the antenna and feed line performance. Using a Wattmeter and a Handheld 450MHz Radio The recommended procedure is to use a handheld commercial grade transceiver that is tuned to the R450 RM DC's transmitter frequency and an inline wattmeter, such as a Bird Model 43 Wattmeter with the appropriate element (slug) for the frequency range and power output of the transceiver. The Bird Model 43 Wattmeter uses elements to set the frequency and power ranges that the meter will read. The wattmeter element should be a 400 - 1000 MHz model sized so that the forward power reading is close to full scale. For a 5W output handheld, the Bird 5E element is recommended. If the radio puts out more than 5W, a Bird 10E or higher power element may be required. Complete the following steps to use a Wattmeter and handheld to calculate VSWR. 1. Connect the wattmeter and transceiver to the feed line in place of the R450 RM DC. 2. Measure both the forward and reflected power. 3. Find the return loss value using Table 13 on page 63 and Table 14 on page 64. 4. Find the loss attributed to the coax using Table 15 on the previous page based on the coax type and feed line length. The adjusted return loss is calculated by the following formula. Return Loss (from Table) - (2 x Cable Loss) = Corrected Return Loss 5. Find the VSWR using Table 13 on page 63 and Table 14 on page 64 using the Corrected Return Loss value. 6. Change the frequency on the handheld transceiver to the R450 RM DC's receive frequency. 7. Measure the power and calculate VSWR using the procedure just used for calculating transmitter VSWR. 8. Record both transmit and receive frequencies' VSWR values. In order for the antenna system to pass, both readings must be less than 1.5.1. R450 Rack Mount DC Installation and Maintenance Guide 67 Appendix A: RF Antenna Installation Using the AEA 140-525 Antenna Analyzer Complete the following steps to configure the analyzer. This procedure assumes that the analyzer has not been configured prior to use. 1. Turn the analyzer ON. 2. Type the frequency: 46000. 3. Press Enter. 4. Set the value next to WID on the screen to 20 using the width buttons. 5. Set the reading to return loss by pressing F1 three times. (Press it slowly; the unit should beep each time.) Taking the Reading and Calculating VSWR 1. Connect the analyzer to the feed line in place of the R450 RM DC. 2. Configure the analyzer using the preceding procedure. Be sure that there is not a vertical line running through the display in the plot area. If there is, press EXAM PLOT and it should go away. 3. Allow the analyzer reading to stabilize, between 10 and 20 seconds. 4. Press EXAM PLOT to freeze the display. 5. Move the cursor (the vertical line in the middle of the screen) using the FREQ arrows to approximately the R450 RM DC's frequency. (It moves to within 100KHz of a frequency.) 6. Read the value next to RETL on the display. This is the return loss value. 7. Find the loss attributed to the coax (based on the coax type and feed line length) using Table 15 on page 66. 8. Calculate the adjusted return loss using the following formula. Return Loss (from Table 5) - (2 x Cable Loss) = Corrected Return Loss. 9. Find the VSWR (using the Corrected Return Loss value) Table 13 on page 63 or Table 14 on page 64 68 R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation 10. Move the cursor to within 100KHz of the R450 RM DC's receive frequency. 11. Calculate VSWR using the new return loss value. 12. Record both values. They must be less than 1.5.1 for the antenna and feed line to pass the test. General Installation Guidelines Unpacking As with all precision electronic instruments, the RF 450 MHz antenna should be handled with care; however, no additional special handling is required. After unpacking the RF 450 MHz antenna, inspect it for damage. If any parts of the R450 MHz antenna appear to be damaged or prove to be defective upon installation, notify your Neptune sales representative. If the unit or item requires reshipment, use the original cardboard box and packing material. In particular, check to be sure that the N connector at the base of the antenna is not damaged. This is much easier to check while the antenna is on the ground than after it is installed. RF Antenna Installation Kit The RF 450 MHz antenna and the basic accessories are included with the R450 RM DC. The mounting brackets that are included are designed to mount on the top of a mast or similar structure. If the installation requires offsetting the antenna from the supporting structure, this must be ordered separately. Neptune does not sell it. Figure 42 – RF 450 MHz Antenna R450 Rack Mount DC Installation and Maintenance Guide 69 Appendix A: RF Antenna Installation Tools and Materials Table 16 shows the recommended tools and materials you need to successfully install the RF antenna. Table 16 – Recommended Tools and Materials Item Took Kit Description/Recommendation Contains standard tools including: Use Various installation procedures performed by the installer Assorted screwdrivers (medium, flat head) Cordless electric drill/assorted bits Adjustable wrench Standard socket wrench set Standard box-end wrench set Hammer Channel locks UV-Stable Cable Ties 8" and 12" (20.32 cm and 30.48 cm) Secure coax cable Cable Clips Various sizes Securing coax cable Weatherizing Kit PolyPhasor P/N: WK-1 Weatherproofing coax cable connections - or Times Microwave P/N: WK-S-2 - or Andrews P/N: 245171 Electrical Tape Scotch® Heavy Duty Vinyl Electrical Tape 22 -or Weatherproofing coax cable connections and other connections as required Scotch® Super 88 70 R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation Installing the RF Antenna This section contains the instructions for the RF antenna installation. Mounting the RF 450 MHz Antenna The RF 450 MHz antenna must be installed by professionals in accordance with the FCC site license before you begin the installation of the R450 RM DC. WARNING: Mounting and wiring the RF 450 MHz antenna must be done by a trained professional. Be sure to subcontract this work, so it is completed properly. CAUTION: The cable, connectors, and the antenna installation must be checked with the VSWR meter. To mount the RF 450 MHz antenna, complete these steps. 1. Assemble the RF 450 MHz antenna, per the instructions included with the antenna kit See Figure 43. 2. Use the mounting hardware included with the antenna to mount the antenna per the supplied instructions. 3. Install the antenna in accordance with the FCC site license (per the antenna mounting instructions contained in this appendix). 4. Weatherize the antenna coaxial connector using the weatherizing kit. See Table 16 on the previous page. Figure 43 – RF 450 MHz Antenna to be Mounted Mounting the Antenna Mast to the Building With a wall-mount installation, it is necessary to mount the 450MHz and cellular antenna on the exterior of the building. Complete the following steps to mount the antenna mast to the building. Use manufacturer installation instructions provided with mounting hardware. R450 Rack Mount DC Installation and Maintenance Guide 71 Appendix A: RF Antenna Installation 1. Use antenna pole brackets to install the pole to the building. See Appendix A. 2. With a drill, pre-drill your holes for the first pole bracket. 3. Secure the pole bracket in one of the following ways: If mounting to a wood-constructed wall, use wood screws rated at minimum of 20 pounds loading. If mounting to sheet metal or masonry, use appropriate sheet metal screws or masonry anchors rated at a minimum of 20 pounds loading. Figure 44 – Securing the Pole Bracket 4. Place the antenna mast pole within the bracket. 5. Using a level to make sure the pole is vertical, line up a second bracket a minimum of 2 feet (2') from the bracket you just installed. 6. Secure the second bracket similarly to the first one, following steps 2 and 3. 7. Line up the pole in the two brackets. See Appendix A. 8. Secure the pole with the bolts provided. Figure 45 – Lining Up Second Bracket Attaching the RF 450 MHz Antenna Cable To attach the RF 450 MHz antenna cable to the RF antenna R450 RM DC, complete the following steps. 1. Locate the RF 450 MHz antenna cable that extends from the RF 450 MHz antenna cable conduit. See Figure 46. 2. Connect the RF 450 MHz antenna cable to the RF 450 MHz antenna connector located on the bottom of the R450 RM DC. See Appendix A. Tighten the coaxial connector to: Type N: 15 to 20 lbf in (1.7 - 2.3 N m) Type 7 - 16 DIN: 220 - 265 lbf in (25 - 3 N m) Figure 46 – RF 450 MHz Antenna Connection 72 R450 Rack Mount DC Installation and Maintenance Guide Appendix A: RF Antenna Installation WARNING: Special consideration should be given when the RF antenna R450 RM DC is installed inside a building. The screen (shield) of the coaxial cable must be connected to the earth (grounded) at the entrance to the building. This should be done in accordance with applicable national electrical installation codes (Section 820.93 of the National Electrical Code, ANSI/NFPA 70). Weatherizing the Cable Connections Complete the following instructions to weatherproof the cables with the Scotch Wireless Wk101 Kit or equivalent. 1. Using the weatherizing kit, start the tape at the top of the RF antenna connection as illustrated in Figure 47. 2. Wrap the tape around the connection several times; slowly work your way downward to weatherize your connection at the base. Figure 47 – Weatherizing the RF Antenna Connection Troubleshooting the RF Antenna This section provides a table of possible symptoms, areas of focus, and actions that can be taken to try to resolve problems that could arise with your RF antenna. Equipment Required The following items are required in order to troubleshoot the R450 RM DC. Keys to access the site and open the R450 RM DC cabinet Digital volt - Ohm multimeter Socket and open-end wrenches to install and remove the R450 RM DC Small, medium, and large slot-style screw drivers #1 and #2 Phillips head screw drivers Electrical tape and wire ties Spare R450 RM DC in order to swap if one fails R450 Rack Mount DC Installation and Maintenance Guide 73 Appendix A: RF Antenna Installation R450 RM DC configuration memory stick Anti-static wrist strap and ground lead with alligator clip for attaching wrist strap to the R450 RM DC cabinet MIU configured for the site Magnet to swipe the MIU Conduct a test by hooking up the wattmeter to the coaxial connector at the R450 RM DC end to measure the VSWR for the antenna and feed line combined. The R450 RM DC's transmitter cannot be used to certify the antenna system. The transmitter only transmits short packets approximately 50ms in length, so taking an accurate reading of forward or reflected power cannot be done with standard equipment. 74 R450 Rack Mount DC Installation and Maintenance Guide Appendix B: USB Flash Drive Configuration for R450 RM DC Overview This appendix provides information and the steps for creating an R450 Rack Mount Data Collector (R450 RM DC) and configuring the USB flash drive using the N_SIGHT PLUS host software. Creating a Collector The Collector tab in the N_SIGHT PLUS host software provides valuable information about the R450 RM DCs in your R450 System. On this tab you can search for or create a R450 RM DC. Using the Collector tab, you can do the following: Create collector Search collectors Creating a New Collector To create a new R450 RM DC, complete the following steps. 1. Open the N_SIGHT PLUS host software on the PC. 2. Select the Collector tab, and click Create Collector. The Create a New Collector window appears similar to Figure 48. All required fields display a red *. Figure 48 – Create a New Collector Window R450 Rack Mount DC Installation and Maintenance Guide 75 Appendix B: USB Flash Drive Configuration for R450 RM DC Table 17 – Collector Details Field Description Collector ID Indicates the unique identifier for the data collector which can be a street, location, or a neighborhood. Collector Name Indicates the name of the data collector, for example the street, neighborhood, tower name, and so forth. Host IP Address Displays the static IP address for the host database. Time Zone Indicates the unique identifier for the time zone in which the R450 RM DC is located; offset is from UTC: Atlantic Time is -4; Eastern Time is -5; and so forth. Sync Interval (minutes) Indicates, in number of minutes, the time between synchronizations between the collector and the database. Usually it is 60 minutes for cellular system, and 30 minutes for an Ethernet system. Transmit Frequency Indicates the frequency used to transmit data. Receive Frequency Indicates the frequency used to receive data. Latitude Indicates the actual latitude of the R450 RM DC. Longitude Indicates the actual longitude of the R450 RM DC. Power Indicates the power used by the R450 RM DC. Antenna Height Indicates the actual height of the RF antenna. Daily Reboot Indicates if the R450 RM DC requires a daily reboot. Start Time Displays the beginning time in hh:mm format for the quiet time period when the R450 RM DC is not transmitting or receiving. End Time Displays the ending time in hh:mm format for the quiet time period when the R450 RM DC is not transmitting or receiving. On this tab, remember the following: 76 All fields with an * are required. All white fields are available fields. All fields with gray text are read-only fields R450 Rack Mount DC Installation and Maintenance Guide Appendix B: USB Flash Drive Configuration for R450 RM DC 3. Complete all the required and available information that applies, and click Save. The Collector Network Settings tab appears similar to Figure 49. Figure 49 – Collector Network Setting Tab Table 18 – Collector Network Settings Field WAN Connection Type Description Indicates the type of Wide Area Network (WAN) used by the R450 RM DC. The options include the following: Cellular Cellular_Ethernet Network_DHCP Network_Static_IP Mobile NTP Server Indicates a server that uses NTP (Network Time protocol). Its purpose is to keep the clock accurate. Primary DNS Server Indicates the primary server, the first DNS (Domain Name System) server queried when trying to resolve a server name. You can supply the name rather than the IP address, for example, Chicago rather than 10.10.10.10. Secondary DNS Server Indicates the secondary server, the second DNS (Domain Name System) server. R450 Rack Mount DC Installation and Maintenance Guide 77 Appendix B: USB Flash Drive Configuration for R450 RM DC On this tab, remember the following: All fields with an * are required. All white fields are available fields. All fields with gray test are read-only fields. 4. Complete all the required and available information that applies, and click Save. The R450 RM DC just created appears in the list of R450 DCs on the Collector tab, and the detail appears in the lower half of the page. Editing Collector Information To edit information for an R450 RM DC, complete the following steps. 1. On the Collector tab, select the R450 RM DC for which you want to edit the information. The Edit Collector window appears with the existing information for the collector. 2. Edit and change the appropriate information on both the Collector Details tab and the Collector Network Settings tab. 3. When complete, click Save to display the new information for the collector. The changes you made are saved for the selected collector. Deleting a Collector To delete a collector, complete the following steps. 1. On the Collector tab, select the collector you want to delete. 2. Click Delete. A delete confirmation message appears similar to the following. Figure 50 – Delete Confirmation Dialog Box 3. Click OK. The R450 RM DC is now deleted from the list of collectors on the Collector tab. 78 R450 Rack Mount DC Installation and Maintenance Guide Appendix B: USB Flash Drive Configuration for R450 RM DC Using Collector Search To use the Search function to locate an R450 RM DC, complete the following steps. 1. Click Search Collectors on the Collector tab. The following page appears. Figure 51 – Collector Search On this page, there is a drop-down selection list for you to select how you want to search for the R450 RM DC. Collector Name Synchro User Collector ID 2. Type all or part of the search criteria you selected in the previous step in the search area provided. See Figure 51. Everything matching your search criteria appears in the collector list on the Collector tab with the detailed information for the collector appearing in the lower-half of the page. See Figure 52 on page 80. R450 Rack Mount DC Installation and Maintenance Guide 79 Appendix B: USB Flash Drive Configuration for R450 RM DC Figure 52 – Collector Search Results 3. Select one of the following options. Create another R450 RM DC. Edit information for the selected R450 RM DC. Delete the selected R450 RM DC. Build a USB drive for the R450 RM DC. Building a USB Drive for Collector Configuration This feature adds the ability to build a USB drive that can be inserted into a replacement collector for automatic configuration in order to mimic an old collector. R450 Collector configuration application must be installed on a local PC to extract files to the USB drive. Make sure only the desired USB drive is on the computer. 80 R450 Rack Mount DC Installation and Maintenance Guide Appendix B: USB Flash Drive Configuration for R450 RM DC Complete the following steps to add an USB drive. 1. Select the R450 RM DC to upload data to the USB drive from the Collector tab 2. Click Build USB. A confirmation message appears similar to the following. 3. Click OK to build the drive. 4. Double-click the downloaded file (*.ntg). The application formats and extracts files to the USB drive. A message similar to the following will appear. R450 Rack Mount DC Installation and Maintenance Guide 81 Appendix B: USB Flash Drive Configuration for R450 RM DC This page intentionally left blank. 82 R450 Rack Mount DC Installation and Maintenance Guide Appendix C: Ethernet Termination Straight-Through Ethernet Cable For most installations, the Straight-Through Ethernet Cable is used. Terminate the Ethernet cable according to the diagram below using the T-568B wiring standard for both ends. One end should already be pre-terminated to the switch or hub. Figure 53 – Straight-Through Ethernet Cable RJ-45 Crossover Ethernet Cable On some occasions, a Crossover Ethernet Cable is required. If you require a cable to connect two Ethernet devices directly together without a hub or when you connect two hubs together, you will need to use a crossover cable instead. Figure 54 – RJ-45 Crossover Ethernet Cable R450 Rack Mount DC Installation and Maintenance Guide 83 Appendix C: Ethernet Termination Determining if You Need a Crossover Cable One method of determining if you need a crossover cable is to plug the Ethernet cable from the hub or modem into your laptop computer's Ethernet port. If the laptop computer can communicate through the Ethernet port, then the site probably requires a Crossover Ethernet Cable to be compatible with the R450 Data Collector (R450 RM DC). Table 19 – Cable Color Code Table Symbol 84 Wire Color White with orange stripe Solid orange White with green stripe Solid blue White with blue Solid green br White with brown stripe BR Solid brown R450 Rack Mount DC Installation and Maintenance Guide Glossary ALM Alarm indicator. AMI Advance Metering Infrastructure. System that captures, stores, and provides to the utility at frequent intervals detailed consumption and other information, such as, usage, leak, and flow status, in order to support advanced applications. These data can then be used to support a onsumer portal. Furthermore, the mass of data generated by the system can feed an advanced analytics system to convert it into actionable information that supports the efficient management of the utility. AMR Automatic Meter Reading. The automated process of reading meters. APN Access Point Name. ballast Heavy material used to secure the stability of the equipment stand. For the R450 System, concrete blocks are used for the ballast. CDMA Code Division Multiple Access. A channel-access method used by various radio commumication technologies tha allows multiple users to be connected over the same channel. R450 Rack Mount DC Installation and Maintenance Guide 85 Glossary Data Collector R450 Data Collector (R450 DC). The physical equipment that houses Neptune's N_SIGHT PLUS host software. The R450 DC is a device that collects meter reading data from Neptune's absolute encoder register interfacing with Neptune's R450 MIU and transmits the data for collection. This unit receives the data for collection. This unit receives the data and stores data to be downloaded through the host software. DHCP Dynamic Host Configuration Protocol. IMEI International Mobile Equipment Identifier. LED Light Emitting Diode. MEID Mobile Equipment Identifier. MHz Abbreviation for megahertz. One MHx represents one million cycles per second. MIU Meter Interface Unit. 86 R450 Rack Mount DC Installation and Maintenance Guide Glossary R450 System R450 System is a fixed network AMI system for targeted applications allowing a utility to conduct meter reading operations automatically ensuring maximum collection of the data. serial number A unique identification number given to each product at the factory. VSWR Voltage Standing Wave Ratio. The ratio of the amplitude of a partial standing wave at an antinode (maximum) to the amplitude at an adjacent node (minimum) in an electrical transmission line. R450 Rack Mount DC Installation and Maintenance Guide 87 Glossary This page intentionally left blank. 88 R450 Rack Mount DC Installation and Maintenance Guide Index backhaul AC modem 48 power box 21 modem connectivity 52 power source 21 type 2 activating light 25 battery 35 activating, R450 DC 21 safety checklist 36 ALM spill kit 36 indicator 53 LED 48 antenna 62 accessories 12 bonded 59 cable analyzer 68 clips 13 attaching 16, 18 Ethernet 83 cable 16 Cal Amp, landcell modem 48, 51 commerical broadcast 7 calculating VSWR 68 connection 16 cellular antenna 58 external 4 certification 63 GPRS 8 circuit breaker 49 installing 71 CIS 1 mast 3 coax cable 8, 12-13, 60 placement 6 coax cable loss 66 RF 57 collector assembly accessories building USB drive 80 Ethernet 9 create 75 GPRS 8 deleting 78 AWG 17 details 76 edit information 78 network settings 77 R450 Rack Mount DC Installation and Maintenance Guide 89 Index using search 79 flash drive configuring collector, USB flash drive 24 connectivity 52 configuration 75 frequencies 1 connectors 61 conversion table 63-64 GPRS CPU board 24-25, 47, 50 modem 2 creating collector 75 parts list 8 customer support 56 ground wire 17 component 16 connecting 17 Digital Volt-Ohm-Multimeter 51 host software 26 electrical codes 21 encoder register 1 Ethernet 9 90 installation backhaul 25 common problems 7 cable 22 completing 24 cable, RJ-45 crossover 83 four types 2 cable, straight-through 83 instructions 15 kit 9 kits 12 parts list 9 pole 5 port 84 R450 DC 3 termination 83 site selection 3 external ground lug 17 interference 6 FCC 1 lightning arrestors 8 feed line 59 link integrity light 25 R450 Rack Mount DC Installation and Maintenance Guide Index site 15 pole mounting magnet 14, 26, 53 steel or concrete 39 materials 13 power measurement 63 MIU 1 power supply 33 placement 7 primary DNS server 77 swipe 26 modem Cal Amp 46 R450 DC 1 GPRS 2, 8 kit 8 mounting mounting 4 antenna 17, 57 performance issues 6 pole 39 potential problems 46 RF 450 antenna 71 product description 1 UPS 39 securing 27 mounting brackets 69 stand 5 transmitter 73 R450 MIU NTP server 77 performance issues 6 radio power 48 part numbers 61 receiver sensitivity 7 parts list Ethernet 9 GPRS modem 8 RF 450, antenna connection 72 RF antenna installation kit 69 performance maintaining 8 optimizing 6 RF antenna, installation 57 pole secondary DNS server 77 installation 5 server mount 15 NTP 77 R450 Rack Mount DC Installation and Maintenance Guide 91 Index primary DNS 77 troubleshooting 45 secondary DNS 77 equipment required 45 signal strenght 52 PC Notebook Configuration 46 SIM card 9 storm damage 46 site voltage checks 49 preparation 38 tune knob 54 surveys 7-8 site, recommendations 58 SLP 54 unlicensed equipment 6 specifications 11 unpacking 12 electrical 11 upacking 69 environmental conditions 11 UPS 33 spectrum analyzer 7 checklist 35 stable ties 13 connecting 40 stand, R450 DC 5 mounting 39 storage 12 USB storm activity 8 building for collector configuration 80 structure 57 flash drive 24-25 strut ports 24 channels 18 clamp 8 syncing 53 testing connections 24 tool kit 13 tools 13 tools and materials 70 tower 57 transceiver 67 VSWR 54, 63, 67 wall mounting 39 WAN connection 77 wattmeter 67 weatherizing antenna connection 21 cable connections 20, 73 kit 13 92 R450 Rack Mount DC Installation and Maintenance Guide Index wiring connectors 40 R450 Rack Mount DC Installation and Maintenance Guide 93 Neptune Technology Group Inc. 1600 Alabama Highway 229 Tallassee, AL 36078 USA Tel: (800) 633-8754 Fax: (334) 283-7293 Neptune Technology Group (Canada) Ltd. 7275 West Central Ave. Mississauga, Ontario L5N 5M9 Canada Tel: (905) 858-4211 Fax: (905) 858-0428 Neptune Technology Group Inc. Ejèrcito Nacional No. 418 Piso 12, Desp. 1201-1202 Col. Chapultepec Morales Delegación Miguel Hidalgo 11570 Mèxico, Distrito Federal T: (525) 55203 5294 / (525) 55203 5708 IM R450 RM DC 12.17 Part No. 12835-001 © Copyright 2006 - 2017, Neptune Technology Group Inc. Neptune is a registered trademark of Neptune Technology Group Inc.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Author : vguy Create Date : 2018:01:04 13:58:47-05:00 Modify Date : 2018:01:04 13:58:59-05:00 Has XFA : No XMP Toolkit : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03 Metadata Date : 2018:01:04 13:58:59-05:00 Format : application/pdf Title : IM R450 Rack Mount DC Creator : vguy Document ID : uuid:e0d5f12f-5c07-4185-8657-74452c477e4e Instance ID : uuid:b988721c-14b8-45c3-95d5-d2a080ebccc2 Producer : madbuild Page Count : 55EXIF Metadata provided by EXIF.tools