Norton 7100SZ Series Safe Zone With External Sensor Installation And Instruction Manual 80 9371 0084 020

User Manual: Norton 7100SZ Series SafeZone with External Sensor Installation and Instruction Manual Installation

Open the PDF directly: View PDF PDF.
Page Count: 6

1
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9371-0084-020 (01-14)
• Allen wrench set (inch)
• Flat blade screwdriver (potentiometer & terminal size)
• Screwdriver (Phillips size 2)
Tape rule
• Power drill
• Center punch
Wire stripper
Tools required:
Mechanical Installation 2
Wiring Diagrams 3
Sensor Settings 4
Sensing Field Settings 5
Trouble Shooting 5
Specifications 6
Safety Precautions 6
Table of Contents:
ASSA ABLOY
Patent Pending
®
7100SZ Series SafeZone
External Sensor
Installation and Instruction Manual
3.14
(79.8)
4.76
(120)
2.0
(50.8)
2
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9371-0084-020 (01-14)
MOUNTING TEMPLATE
DRILL
1/8” HOLE
DRILL
1/8” HOLE
DRILL 1/4” HOLE
THEN INSERT CABLE
PLACE TEMPLATE
AT LEASE 1” ABOVE
BOTTOM OF HEADER
For optional cable routing, notch
cover in one of the areas shown.
10'-0" Max height
Above floor surface
2.0"
Frame Face
1.0" Min.
Above Frame Face
Note:
If frame face is 3.0" or greater,
Sensor can be mounted on frame
face.
1. Apply adhesive backed template, supplied with
sensor, to appropriate surface and aligned with
centerline of door on side of opening opposite
from SafeZone Mount.
2. Drill two 1/8" holes for mounting.
3. Drill one 1/4" hole for cable access.
4. Insert mounting screws into mount surface, but
do not screw them fully in.
5. Route wiring through backplate.
6. Mount sensor backplate and tighten screws.
7. Complete wiring connections and sensor setup
and testing.
8. Secure sensor cover to backplate.
C
LOf Door
Electrical Cable
See page 3 for Wiring Diagrams
See page 4 for Sensor Adjustments
MOUNTING TEMPLATE
DRILL
1/8” HOLE
DRILL
1/8” HOLE
DRILL 1/4” HOLE
THEN INSERT CABLE
PLACE TEMPLATE
AT LEASE 1” ABOVE
BOTTOM OF HEADER
Opening the sensor
Mechanical Installation
*
*
*
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9371-0084-020 (01-14)
3
Wiring Diagram
(Wiring external sensor to SafeZone Unit)
24VDC
Terminal Connection
1 (Red) 24 VDC (+)
2 (Black) 24 VDC (-)
3 (White) Relay Common
4 (Green) Relay N.O.
5 Relay N.C.
Note: Input power tolerance is +/- 10% for
AC, and -10% to +30% for DC power.
12345
12345
SafeZone Unit 24VDC
Closer
Solenoid
Red
Black Green
Jumper Wire
External Sensor
24VDC (-)
24VDC (+)
Wiring Diagram
(Wiring external sensor to SafeZone Unit)
120VAC
SafeZone Unit 120VAC
Red
Black Green
Jumper Wire
External Sensor
Closer
Solenoid
L
N
G
12345
12345
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9371-0084-020 (01-14)
4
Terminal Block
Planner Antenna
(Narrow)
Hold Time Buttons
Lateral and Angular
Antenna Adjustments
Wire
Passage
Increase (+)
Decrease (-) LED
Wire Knockout
(Inside Cover) Cover removal slot
Front Cover
s
Default Factory Settings:
Sensitivity 3
Hold Time 10 seconds
Immunity 2
Detection Mode 1 (Bidirectional)
Door Control Mode 1
Setting Time (Seconds)
1 5
2 6
3 7
4 8
5 (Default) 10
6 14
7 16
8 18
9 20
0 0.5
Recommended Hold Time Settings
Setting 4-6
Setting 1-3 Setting 7-9
Setting Hold Open Time:
Press and release the Increase
(+) or decrease (-) buttons until
desired setting is achieved.
Reset Hold Time to Default:
Holding both buttons depressed
simultaneously for 3 seconds
will set unit at default hold time
of 10 seconds.
Hold Time
Hold open time is defined as the amount of time the door will remain open
AFTER movement in opening is no longer detected.
Sensitivity Setting
Sensitivity is factory set at setting #3. The sensitivity range is (0 - 9). This setting
can be adjusted along with other advanced settings when using the optional
remote.
Optional remote for advanced setting.
List number 7100REM
Sensor Settings
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9371-0084-020 (01-14)
5
Troubleshooting
SYMPTOMS PROBABLE CORRECTIVE
CAUSE ACTION
Door Stops several times in
the same cycle without
sensing presence in the door
way.
Sensitivity is set too high Change sensitivity setting using
optional remote.
Door not closing when cover
installed.
Eye is sensing the closer
cover.
Adjust the sensing field away from
cover edge. (See “Sensing Field
Adjustments” above.
Power switch is off.
Loose wire connection.
Turn power switch to “ON” position.
Inspect wiring for loose connections.
Red LED does not light up.
(No power to sensor)
16" 0
0
16"
16"
32"
48"
32" 32"
Nominal Detection Pattern with Sensor Set as follows:
Mounting Height: 7'-2"
Sensitivity: 3 (factory default)
Immunity: 2 (factory default)
Direction Mode: 1 (Bi-Directional; factory default)
Door Control: 1 (factory default)
Vertical Tilt: 30°
Lateral Tilt:
Altering the lateral tilt angle will shift the detection
pattern left or right of center.
Note:
Always “walk” the opening during senor adjustment to
confirm the detection pattern is adequate for the
opening and application.
Adjusted hole open times as required for application.
See page 4 for hold open time settings.
Sensing Field Adjustments
30º 45º
The position of the sensing field is determined by the vertical and lateral angle of the antenna.
Sensing field as close to the door as possible:
Antenna is set at the position of 0°
Sensing field far from the door:
Antenna is set at the position of 45°
Sensing field close to the door:
Antenna is set at the position of 30°
Vertical Angle Adjustments Lateral Angle Adjustments
+15°-15°
Copyright © 2010, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9371-0084-020 (01-14)
6
Sensor Technical Specifications
DESCRIPTION SPECIFICATION
Frequency: 24.125 GHz
Suppl voltage: y 24 VDC: -10% / +30%:
Mounting height: Normal: 7’; Maximum: 10’-0”
Tilt angle: 0 to 90 vertical
-15 to +15 lateral
Detection area:
Wide
Narrow
13ft (W) x 6.5ft (D)
6.5ft (W) x 8.2ft (D) (supplied as optional)
Minimum detection speed: 2 in/sec. (measured in axis)
Power consumption: < 2 W
Standard output relay:
Max contact voltage
Max contact current
Max s itching po ew w r
60 VDC / 125 VAC
1 A (resistive)
30W (DC / 60V) A (AC)
Hold time: 0.5 sec. to 9 sec. (adjustable)
Temperature range: -4°F to 131°F
Dimensions: 4.75in (W) x 3.15in (H) x 2.0in (D)
Weight: 0.5lbs
Material: ABS
®
SafeZone
Safety Precautions
Shut off all power going to the header before attempting any wiring procedures.
Maintain a clean & safe environment when working in public areas.
Constantly be aware of pedestrian traffic around the door area.
Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by
the door.
Always check placement of all wiring and components before po ering upw to ensure that moving door parts will not
catch an w res and cause damay i ge to equipment.
Ensure compliance w yith all applicable safet standards upon completion of installation.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
Circuit board components are vulnerable to damage by electrostatic discharge
(ESD). ESD can cause immediate or subtle damage to sensitive electronic parts.
An electrostatic charge can build up on the human body and then discharge when
you touch a board. A discharge can be produced when walking across a carpet
and touching a board, for example. Before handling any board, make sure you
dissipate your body’s charge.
CAUTION: In the event a unit needs to be opened, observe the following precautions.
Ground yourself by touching a conductive surface of the door or other element connected to common earth
ground to discharge the static electricity present in your body.
Avoid walking around while replacing items inside the case, especially if you are on carpet or during
conditions of low temperature and low humidity.
Handle the board by the edges only to avoid touching electronic components.
Store a loose board in an anti-static bag.