Norton Master (PTDO) Or Support (PTO) Units, Push Pull Side 80 9377 0716 020

User Manual: Norton Master (PTDO) or Support (PTO) Units, Push or Pull Side Installation

Open the PDF directly: View PDF PDF.
Page Count: 4

Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9377-0716-020 (04-14)
1
Installation Instructions
Combination Door Closer-Holder and
Releasing Device WITH and WITHOUT
Integral Smoke Detector
An incorrectly installed or improperly
adjusted door closer can cause property
damage or personal injury. These instructions
should be followed to avoid the possibility
of misapplication or misadjustment.
CAUTION ®
Power Track Series
Master Unit – PTDO (with detector)
Support Unit - PTO (without detector)
Models
Hinge (Pull) Side of
Door Application
Stop (Push) Side of
Door Application
7705PTDO
7705PTO
P7705PTDO
P7705PTO
7705PTDO
PULL SIDE
illustrated
LH – Left Hand Door
RHR – Right Hand Reverse
P7705PTDO
PUSH SIDE
illustrated
LH – Left Hand Door
RHR – Right Hand Reverse
Components:
®
NOTES: - For wiring of PTDO models, see "PowerTrack "
"Wiring Instructions" No. 80-9342-0902-021 (01-09)
- When used with a PTDO model, PTO unit must
be a 24V unit
* This cover is only available for PULL SIDE applications.
ASSA ABLOY
PTO UNITS NOT SHOWN
Arm Assembly
7700ST-1A
9/64"
Hex Drive
Socket Screw
Metal Cover
with Clips
7700M *
Power Adjustment Nut
Delayed
Action Option
7705LAP-DA
Standard
7705LAP
BC
P
D
S
L
BC
P
S
L
Plastic Cover
(Standard)
7700P
2 Cover Screws
Push (Stop) Side
Pull (Hinge) Side
PTO Hook-Up Box
PTOHB24
PTOHB120
PTO Track
PTO24
PTO120
PPTO Track
PPTO24
PPTO120
PPTO Hook-Up Box
PPTOHB24
PPTOHB120
PPTDO Hook-Up Box
PPTDOHB24
PPTDOHB120
Smoke
Detector
PTDO Hook-Up Box
PTDOHB24
PTDOHB120
Smoke
Detector
9/32” (7 mm);
3/8” (9.5 mm) dia. x
3/8” (9.5 mm) deep on
door opposite to closer
Standard
Optional
Through-bolts and
grommet-nuts
All
Preparation for Fasteners
Door or Frame
Fasteners Drill-Sizes
Self-Drilling Screw
Wood 3/16” (4.30 mm)
Pilot hole required
1/4” - 20 machine
screw Metal Drill: #7 (0.201” dia.)
Tap: 1/4” - 20
Sleeve nuts and
bolts
Hollow
Metal
9/32” (7 mm) through;
3/8” (9.5 mm) door face
opposite to closer
Aluminum
or Wood
3/8” (9.5 mm) through
Aluminum
or Metal No drill required
NOTE:
For special applications a separate door and frame
preparation template is packed with these instructions.
Use this instruction sheet for installation sequence and
closer adjustments only.
Use of an auxiliary door stop is always recommended.
Unit must be mounted on interior of building in dry
environment, maximum humidity of 95%.
See NFPA70 for wiring requirements and NFPA72 for alarm
system requirements.
Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9377-0716-020 (04-14)
2
9
8
7
6
5
3
12
4
Cover
Optional
Latch
Sweep
Parts
Caution:
Don't completely
close cushion valve
Optional Cover
Hinge (Pull) Side Application
Right Hand Shown
Mark and Drill Holes
Installation Sequence
!
19
(483)
3-5/8
(92)
A
B
5
(127)
6-3/4
(171)
C
L
Closing Force
7700M
7700P
A
C
After installed,
bend out tabs
to secure.
D
G
See Page 4 for
wiring instructions.
2
1
H
Pinion Flat
RH Door LH Door
F
Power Track
PTO
PTDO
31-1/16
(788)
34-11/16
(881)
Dim. "A”
32-1/8
(816)
35-3/4
(908)
Dim. "B”
Hold Open Angle
(Between 85° and 110° only)
A
Lock into
hold-open
C Open door to
desired angle
BD
Use holes
that align
in arms
I
7/8 (22) Conduit
hole for concealed
wiring only
1/2
(13)
B
7705PTO/7705PTDO Series
Closer
Valves
Up
Closer
Valves
Down
E
-
+
-
+
Backcheck
-
+
-
+
Cushion
Position
Self-Drilling
Screw Wood
(see Note)
No drill required
3-16” (4.3mm)
Drill #7 (.201” dia)
Tap 1/4”-20
Metal
Fasteners Door or
Frame Drill Sizes
Preparation for Fasteners
Note: Wood doors/frames MUST have pilot
hole when using Self-Drilling Screws.
1/4”-20
machine screw
Aluminum
or Metal
3/4
(19)
1-7/16
(37)
1-1/4
(32)
2-3/8
(60)
Solenoid wire
coiled inside
end of track
+_
Product shipped
with closing force
set at the middle of
the power range.
DO NOT use a power drill or driver
to turn adjustment nut. This will
damage closer and void warranty.
Install closer per instructions with the
proper pre-load applied to the arm
then adjust spring power. The
power adjustment will not work
properly if the closer spring is
not pre-loaded.
Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9377-0716-020 (04-14)
3
Optional
3
Parts
Stop (Push) Side Application
2
Left Hand Shown
Mark and Drill Holes
Installation Sequence
12
(305)
3-1/8
(79)
AB
C
L
A
F
D
G
Power Track
PTO
PTDO
30-9/16
(776)
34-3/16
(868)
Dim. "A”
31-11/16
(805)
35-5/16
(897)
Dim. "B”
H
19
(486)
Used for 7788
Drop Plate
1
(25)
1-1/8 (29) hole
for Conduit
Bottom of Frame Stop
4
(102)
4-3/4
(121)
1-1/8
(29)
5/16
(8)
2-5/8
(67)
2-3/8
(60)
1/2
(13)
See Page 4 for
wiring instructions.
B
5
C
P7705PTO/P7705PTDO Series
9
6
4Latch
Sweep
Caution:
Don't completely
close cushion valve
Optional Cover
!
Closing Force 8
7700M
7700P
-
+
-
+
Backcheck
-
+
-
+
Cushion
Position
Hold Open Angle
(Between 85° and 110° only)
A
Lock into
hold-open
C Open door to
desired angle
BD
Use holes
that align
in arms
E
Self-Drilling
Screw Wood
(see Note)
No drill required
3-16” (4.3mm)
Drill #7 (.201” dia)
Tap 1/4”-20
Metal
Fasteners Door or
Frame Drill Sizes
Preparation for Fasteners
Note: Wood doors/frames MUST have pilot
hole when using Self-Drilling Screws.
1/4”-20
machine screw
Aluminum
or Metal
Cover
4-1/4
(108)
6-3/4
(171)
4
(102)
4
(102)
1
2
1
Pinion Flat
RH DoorLH Door
Closer
Valves
Down
Closer
Valves
Up
Solenoid wire
coiled inside
end of track
+_
Product shipped with
closing force set at the
middle of the power
range.
DO NOT use a power drill or driver
to turn adjustment nut. This will
damage closer and void warranty.
Install closer per instructions with the
proper pre-load applied to the arm then
adjust spring power. The power
adjustment will not work properly if
the closer spring is not pre-loaded.
Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9377-0716-020 (04-14)
4
PTO Support Unit Wiring Diagram
(24VAC/DC Input)
PTO Support Unit Wiring Diagram
(120VAC Input)
(Do not use a 120VAC PTO unit when power is
supplied from a PTDO unit)
2-Pin Jumper SOL
1
2
3
4
3
2
1
24VAC/DC Circuit Board 4-Pin
Jumper
2-Pin Jumper SOL
1
2
3
4
3
2
1
120VAC Circuit Board 4-Pin
Jumper
Test Switch
Header for Solenoid
Connection
Openings for surface
wiring shown Fuse (PTO125V)
125V / 1/2A
Terminal Strip for
Power Input Connection Test Switch
Openings for surface
or concealed wiring
Terminal Strip for
Power Input Connection
ELECTRICAL DATA
NOTES:
Maximum wire size is 14AWG.
All wiring and connections use standard wiring practice conforming with
local wiring codes.
For PTDO Models:
Refer to Wiring Instructions
No. 80-9342-0902-021 (01-09)
for making wiring connections.
Earth
(+)
(-)
Earth
(+)
(-)
Input
Power
Input
Power
Again, open door to the hold-open position.
Depress “Test Switch” button on the hook-up
board (accessible through cover)...door should
close. If arm does not release, see previous step.
Installation of Cover:
Plastic Cover (7700P): Slide cover insert into the
un-used cutout in cover. Install cover using
screws provided.
Metal Cover (7700M): Fasten cover to mounting
clips with screws provided.
IMPORTANT:
Remove solenoid wire from end of track before
installing track to frame. Do not pinch or crimp wire.
Once track and hook-up box are installed, solenoid
wire must be plugged into Header on circuit board
shown above.
After making all wiring connections:
Turn power to unit “ON”. (On Master (PTDO) unit
only, red LED should illuminate once every 15
sec.).
Track’s hold open force is preset at the factory.
Open door to hold-open position. Manually pull
door out of hold-open and release...door should
close. If arm does not release from hold-open,
increase the releasing force by turning the screw
accessible thru the end cap of the track using the
9/64” hex wrench provided.
120VAC 24VAC 24VDC
Voltage
Current
120V 24V 24V
132V Max
102V Min
26.4V Max
20.4V Min
26.4V Max
20.4V Min
.036 Amps .059 Amps .074 Amps
Detector
26.4V Max
20.4V Min
0.034 Amps
24V
Header for Solenoid
Connection
Fuse (PTO125V)
125V / 1/2A
3000 Highway 74 East • Monroe, NC 28112
Tel: (877)- • Fax: (800)-338-0965974-2255
www. no r to nd oo rc ont rol s. co m
ASSA ABLOY

Navigation menu