PEERLESS Boiler Manual L0308199

User Manual: PEERLESS PEERLESS Boiler Manual PEERLESS Boiler Owner's Manual, PEERLESS Boiler installation guides

Open the PDF directly: View PDF PDF.
Page Count: 61

DownloadPEERLESS  Boiler Manual L0308199
Open PDF In BrowserView PDF
LC/LCE
Gas/Off

Boilers

- Steam

Installation,
Operation
Maintenance
Manual
PEERLESS
CAST IRON BOILERS

°

22

Sizes

4-24

Forced

Draft

• Only

Sections

a Three

Efficiency

• Choice

Cast

• Adds
Rear

Iron

Outlet

on
Flue

• Includes

Locking

Damper

Base

Safety

Up to

Power

Operating

LC,

Top

Section

Design

with

Heating

Surface

Flame

or Webster

Outlet

on

for Increased

Tubular

LCE

Efficiency

Heat

for Optimum

Exchanger

Heat

Transfer

Type

Low

Water

Cut OffAvailable

Coils

• For Domestic
Unique

Hot Water

Flex-Seal

• Injection

Molded

• Assures

a Water

Individual

Insulated

Port

for Superior
Tight

on Hot Water
Gaskets

Performance

Seal

Boilers

Between

and

Flexibility

Sections

Rods

of Assembly
Enameled

• Reduces

Production

Flow

Draw

• For Ease

Bo_er

Heat

Steel

Jacket

Loss
• Honeywell
• Manual
• LWCO

still

Efficiency

Noise

Flue

Gas Travel

Additional

or Float

Tankless

lTlul'ci¢l{

Combustion

Controls

• Probe

Peerless
cast
i1oll

83.7%

Collector

Reduces

Optimum

• Provides

Input

the Roof

Gordon-Piatt,

Flue

and

• Provides

Wet

GPH

Burners

Carlin,

Durability
Flue

Foot Vent Above

Power

ofBeckett,

Integral

to 32.5

Venting

Requires

High

4.75

Boilers
boil_'rs
]tol

Pt'erlt,ss

It!¢ll_'l

is pleased
to qlTer
irlclude
a filll,
one
CJlICI sleanl

[Joilera.lot

complete

one
year

boilers.

of

the most
it_atTatlty.

Fivt_

tv(trratlly

Peerless

(lll(_

lell

comptz,h_,nsive
A limitt_¢t,
tell
year

¢'.k'I¢'llc'l¢!¢l

Operating
Reset

High

on Packaged

• Tankless

Coils

• Various

Burner

• FM and

IRI Control

wantruly
programs
year
tt!Cllwa_ll[j
Oil lilt;
it;(lrl(ltl{i¢'s

Controls
Limit Control
Boilers

Opliol_s

and

Voltages

Syslems

irl the indttstl
y. All Peerless
commercial
¢'(ISl ir_)tl ._('cIioIIs
is provided.lbr
(111 col_l

Oil 11(111.% (llld

!¢llx)l

¢1r€" iiott_

available,.

/)l¢'(lst'

¢'¢._tt

it{lbrmaliotl,

Boilers

• 610-367-2153

* www.peerless-heater.com
FA6 LC R3 i3031MI
Pr_n_o_J irl U S A

Series

pr=-r=-RLESS o

Large Commercial
•

CAST

LC/LCE
Boilers

Packaged, Assembled Block or
Individual Sections

o Forced Draft Venting
Power Burners

IRON BOILERS

•

Oil, Gas, Gas/Oil

Q Steam or Hot Water Boilers
Optional

Tankless Coils

Series LC

Series LCE

Net I=B=R

....

Ratings 4

Efficiency

5

Oil

Model

Output

Boiler

Oil Input

Number
LC-O4

MBH
547

H,P.
16.3

GPH 1
4.75

Gas

Input

MBH
686

l Steam
Sq. Ft.
1,708

Steam3

Water 2

MBH
410

MBH
476

,0.05,_,9 19.4 5.60 80_ 2.029,7

Comb.
%
83.7

Water
Gas

Therm.
%
82.2

Comb.

Therm.

%
81.2

%
79.8

I

Content

Steam
40.57

I

Water
50,65

m
mm

56, _.7 62.561.290._ 47.29 69.0,
m

LC-05

707

21.1

6.10

881

2,208

530

615

83.7

82.8

81.2

803

47.29

59.05

II

LC-06

866

25.9

7.59

1,077

2,713

651

755

83.7

83,1

81,1

80.8

54.01

67.45

I

LC-07

1029

30.7

8.80

1,273

3,217

772

895

83.6

83.3

61.1

806

60.79

75.55

I

LC-08

1189

35.5

10.20

1,469

3,717

892

1,034

83.6

835

61.1

81.0

67.46

84.25

I

LC-09

1350

40.3

11.60

1,864

4,250

1,020

1,174

83,6

83.6

811

81.1

74.17

91.65

I

LC-10

1511

45.1

12.80

1,860

4,804

1,153

1,314

83.6

83.7

81.1

81.2

80.88

101,05

I

LC-11

1872

48.9

14.26

2,056

5,367

1,288

1,454

63.6

83.8

811

81.3

87,61

109,45

I

LC-12

1832

54,7

15.60

2,252

5,917

1,420

1,593

83.6

83.9

811

814

94.33

117,65

I

LCE-13

1966

58.7

17,00

2,464

6,358

1,526

1,710

83,5

822

61.0

79,8

101.05

126,25

I

LCE-14

2128

83.5

18.40

2,657

6,875

1,650

1,848

83.5

625

810

80.0

107.77

134,65

•

LCE-15

2284

66,2

19.80

2,850

7,388

1,773

1,986

83.5

826

510

80.2

114.49

143,05

I

LCE-16

2444

73,0

21.00

3,043

7,908

1,896

2,125

83.5

82.8

610

80.3

121.21

151.45

I

LCE-17

2603

77.8

22.50

3,236

8,421

2,021

2,283

83.5

629

81.0

80.4

t 27.93

15985

I

LCE-18

2763

82.5

24.00

3,429

6,938

2,145

2,403

83.5

83.1

810

80.6

134.65

168.25

I

LCE-19

2922

87.3

2500

3,622

9,454

2,289

2,541

83,5

83.2

81.0

80.7

141.37

176.65

I

LCE-80

3082

92.1

2650

3,815

9,971

2,393

2,680

83.5

833

810

806

148,09

18505

I

LCE-21

3256

97.3

2800

4,027

10,533

2,528

2,831

83.6

63 3

81 1

809

15481

19345

I

LCE-22

3430

102.5

29.80

4,239

11,096

2,663

2,983

83.6

834

8t 1

808

161.53

20185

•

LCE-23

3604

107.7

31.00

4,451

11,658

2,798

3,134

83.7

835

812

81.0

168.25

210.25

•

LCE-24

3777

1128

32,50

4,663

12,217

2,932

3,284

83.7

835

812

81.0

174.97

218.65

I

1
2
3
4
5

Burner input based on No. 2 fuel oit with a beating value of 140,000 Btu per garlon
Net I_B-R water ratings based on allowance of 1.15.
Net I=B-R steam ratings based on an allowance for LC-04 to LC-05 1.333, LC-09 1.323, LC-10-1.310, LC-11=1.298, LC-12 1.290, LCE-13 to LCE-24=1.288.
Consult factory before selecting a boiler for installation having unusual piping and pickup requirements, such as intermitlent system operation, extensive piping systems, etc
Combustion and thermal efficiency determined in accordance with The Hydronics Institute's Testing and Rating Standard for Heating Boilers

SERIES LC SPECIFICATIONS

F_[o]llll=l_ I_]]_r_l_J_.-][o_[,."]F_1Lqi]
If.'1_

Jacket

][e[_

_[,,.'!1

Boiler
Model
Number

Width
"A"

Length
"B"

Top to Floor

Left of
Jacket to
C/L of
Flue

LC-04

37"

25_%#'

63"

18W'

54W'

9"

LC-05R

37"

31"

63"

181/4 "

54W'

9"

21_A#'

LC-05

37"

31"

63"

18V4"

54W'

9"

219/_6"

LC-06

37"

36¼s"

63"

18_ ,,

541/8 `'

10"

265/8"

LC-07

37"

41W'

63"

18V4"

54W'

10"

31"/_e"

LC-08

37"

46%6"

63"

18V4"

54W'

10"

36_3/_#'

15_¾6"

LC-09

37"

513/."

63"

181/4"

541/8 ''

12"

417/_"

20_%6"

LC-10

37"

56%#'

63"

18V4"

54W'

12"

46_5/_e
"

20_¾8"

LC-11

37"

61½"

63"

18W'

54W'

12"

52"

26"

LC-12

37"

66%s"

63"

18_A,,

54W'

12"

57W'

26"

Distance Between Tappings*
Floor to
C/L of
Flue
"E"

Flue
Size
"F"

liG_l

"GI"

16_/_"

Apply Prefix "O" for oil--"G" for gas--"GO"
for gas-oil
* Dimensions are approximate
The manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation,
extensive piping, etc. For forced hot water heating systems where the boiler and all the piping are within the area to be heated, the boiler may be selected on the
basis of its Gross Output.

SERIES LC/LCE SPECIFICATIONS

STEAM

PIPING

Pipe the return line to a Hartford Loop, with the return nipple located from 2 to 4 inches below the normal water line.

Model
Number

Riser

Minimum
Header
Size

Equalizer

Model
Number

Riser

Minimum
Header
Size

Equalizer

LC-04

14"

4"

2"

LCE-13

2_4",

1_3"

6"

3"

LC-O5R

2--3"

5"

2"

LCE-14

2_",

2--3"

8"

3"

LCE-15

2_4",

2--3"

8"

3 '=

LCE-16

2---4", 2--3"

8"

3"

LCE-17

24",

_"

8"

4"

LCE-18

2_",

3_3"

8"

4"

LCE-19

24",

3--3"

6"

4"

LC-05

2--3"

5"

2"

LC-06

24"

5"

2"

LC-07

24"

5"

21/2"

LC-08

24"

6"

21/2"

LC-09

24"

6"

21/2'

LCE-20

24",

4_3"

8"

4"

LC-IO

24"

6"

21/2"

LCE-21

24",

4---3"

8"

4"

LC- 11

24"
1--3"

6"

3"

LCE-22

2_4",

4---3"

8"

4"

LCE-23

24",

4--3"

6"

4"

LC-12

2_"

6.

3.
6"

14"

4"

WATER

Model
Number

Supply

Return

Minimum
Header
Size

LC-64, 85R, 65

1--2W'

1--2Vz"

21/2,,

LC-06 and LC-07

1--3"

1--3"

3"

LC-68 and LC-09

2--3"

2--3"

3"

LCqO thru LCE-16

2--4"

2--3"

4"

LCE-17 thru LCE*20

2_"

2--3"

6"

LCE-21 thru LCE*24

24"

3-3"

5"

PIPING

Size the supply and return headers to meet the system flow requirement.

SERIES LC/LCE SPECIFICATIONS
Large, Integral
Cast Iron Flue Collector
Unique Flex-Seal Gaskets

--

Tubular Heat Exchanger

--

Large Combustion Chamber

613/4"

Individual Draw Rods
--

--_

345,46,,

_

HEATER
LOCATION
#1

HEATER
LOCATION
#2

_:m

- _

E

_i

Series LCE Includes

LOCATION

Cast lron Rear Cover Plate

FRONT

I

Heater No.
X-1020
Boiler
Number
Model
LC-04
LC-O5R
LC-05
LC-06
LC-07
LC-08
LC-09
LC-10
LC-11
LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24

Heater No.
X-1021

Location**
GPM

Stea

5.5
5.62
5.75
6.25
6.5
7.0
7.25
7.5
8.0

1
t
1
1
1
1
1
1
1

mT
water
2
2
2
2
2
2
2
2
2

Heater No.
X-1022

Location**
GPM

SteamlWater

Two Heaters
No. Xo1020

Location**
GPM

Steam Water

Two Heaters
No. X-1021

Location**
GPM
8.0

6.5
7.0
7.75
8.5

1
1
1
1

2
2
2
2

13.0

1

2

9.25
10.0
10.75
11.56
12.25
13,00
13.00
13.00
13.00

1
1
1
1
1
1
1
1
1

2
2
2
2
2
2
2
2
2

13.75
14.5
15.5
16.5
17.5
18.0
18.75
19.5
20.0

1
1
1
1
1
1
1
1
1

2
2
2
2
2
2
2
2
2

13.00
13.00
13.00
13.00

1
1
1
1

2
2
2
2

20.0
20,0
20.0
20.0
20.0

1
1
1
1

22
2
2
2

.....
.....
.....

13.00
13.00

1
1

2
2

20.0
20.0

1
I

2
2

--

13.00

1

2

20.0

1

2

Steam Water
-1 &2

Two Heaters
No. X-1022

Location**

Location**

GPM ,Steam

Water

GPM

Steam Wate!

9.0
10.0
12.0
13.0

-----

1& 2
1&2
1&2
1&2

9,5
10.5
13.0
15.5

-----

1&2
1&2
1&2
1&2

15.5

--

14.0
14.5
15,9
16.0
.....

-1&3
1&3
1&3

1 &2
1&2
1&2
1&2

17.5
20.0
21.5
23.5
24.5
26,0
26.0
26.0
26.0

--1&3
1&3
1&3
1&3
1&3
1&3
1&3

1& 2
1&2
1&2
1&2
1&2
1&2
1&2
1&2
1&2

18.0
20.0
22.5
24.5
27.0
29.0
31.5
33.5
35.5

-------1&3
1&3

1 &2
1&2
1&2
1&2
1&2
1&2
1&2
1&2
1&2

__
--

26.0
26.0
26.0
26.0

1&3
1&3
1&3
1&3

1&2
1&2
1&2
1&2

37.5
39.8
40.0
40.0
40.0

1&3
1&3
1&3
1&3

1&2
1&2
1&2
1&2

26.0 11&3
i
26.0 11&3
26.0 I 1&3

1&2
1&2

40.0
40:0
40.0

1&3
1&3
1&3

1&2
1&2
1&2

.....
.....

-

IZI

,

I

--

'

--

" Water heater rahngs are based on intermittent deman_O
° P to 140 ° F Rise with 200 ° F boiler water
** Water beater locations may be found on the drawing above.
When two (2) tankless water heaters are used in a steam boiler, a special rear section is furnished at no extra charg_when
Caution: Water mixing valve should always be installed in the hot water supply to prevent injury.

1 & 2

ordered with boiler,

1&2

SERIES LCE SPECIFICATIONS

\
Rear Flue
Cover

R
E
A
R

Cast Iron Block Assembly-Top

Butterfly Flue Damper (Series LCE)
Mounted Horizontally or Vertically

Flue Outlet

4_/,_
" • .*

G
_l_

]-

_

4,_,_¢

:

16'_1(_

f_

O"
I

F
R

R
E

< o

A

N

R

_:

T

_I

1:,.',_'_€,.][9_,'_€"1:=1,_]
i:{*]llq_:

2.

Remove lifting frame and hardware.

1.

3.

Proceed to Section D: Install Coils or PLates

Remove crate top and sides. Remove any loose
cartons. Remove burner support pedestal and
nipple, if supplied.

2.

Lift boiler off crate pallet. Move to location
determined in Chapter I: Preinstallation.

3.

Remove lifting frame and hardware.

4.

Re-install burner support

[,.)q 114i_[.I1,,][4mlmlh_lk'_l
i=(,,]l!_:
].

2.

3.

Place the Back Section on the floor as shown in
Figure 7.

Proceed to Chapter 3: Piping the Boiler.
4.

I:_N V;l.$'I_vJI:]l_.)
i.

Open the Section Assembly Kit cartons. These
cartons contain the parts needed for assembly of the
sections.

pedestal and nipple if

necessary.

5.

Place channel rails as shown in Figure 4.

:]I[.lN[4I:{o]II::i-"

Move block to location determined
Preinstallation.

in Chapter

I:

The Back Section combustion chamber area is lined
with a ceramic fiber blanket liner. Make sure the liner
is in good condition. Minor tears are not a problem,
but there should be no holes in the insulation.

Lay sections
on
floor
as SohOw
with
maChined
groove
Figure 7:

12

Lay Sections

on Floor and Apply

Rope Seal and Gaskets

side

up.

i

Flat'_
Machined

o?:eo
Ji

Recess
Machined
Face

The sections are heavy and must be supported
securely.

I0. Lift up the Rear Section and move into position
the steel channels on the boiler foundation.

on

11. Screw a 3" pipe at least 30 inches long into the
lower 3" tapping on the back of the Rear Section as
shown in Figure I0. Place a block under the pipe as
shown in the figure and use as a brace during
assembly.

i.°°°2°

Flow Port
Gasket

12. Place a Plain Intermediate Section on the floor and
prepare as above.
13. Carefully place the Intermediate Section against the
Rear Section and visually line up the flow ports as
closely as possible.
14. Insert a tie rod with one nut and washer applied into
each of the four tie rod lugs. See Figures 5 and 6.
15. Place the nut and washer on the other end of the tie
rod and draw finger light.

\
\

\.

Figure 8:

Flow Port

Machining

b Gasket

Gaskets will be damaged by petroleum or its
derivatives. Completely remove all solvent residue
before placing gaskets.
Do not use petroleum based compounds
boiler.

5.

6.

in the

Clean the area around the flow ports and in the seal
recess. Use solvent and a clean cloth to thoroughly
clean all of the sealing surfaces. Remove all foreign
matter to assure a water fight seal when the sections
are drawn together.
Place a Flow Port Gasket in each of the three flow
port recesses as shown in Figures 7 and 8.

7. Apply rope adhesive in the rope groove around the
perimeter of the section.

chined
silicone

8. Place the sealing rope completely around the rope
groove, being careful not to stTetch the rope. Extend
the rope from 1/4" to 1/2" past the end of the groove
on both sides of the cleanout opening on top of the
section. This will assure a gas tight seal when the
cleanout cover plate is applied.
9,

groove.
about
ide of

Do not get sealant
"face of gasket.

Apply a bead of silicone sealant around each flow
port as shown in Figure 9. Do not get sealant on the
flow port gaskets.
Figure 9:

Apply

Silcone

Sealant

13

SECTIONS ARE TOP HEAVY.
HANDLE WITH CARE TO
AVOID

TIPPING

OR FALLING.

Intermediate
tion

Level Each Section:
Place the first intermediate
section next to the rear section
as shown. Use a spirit level to
make sure the sections are

Spirit
.=vel

plumb. Check the level as each
additional intermediate section
is added.

Rear
Section

Temporary Support Pipe
Screw a 3" pipe at least 30 inches
long into the lower (return) tapping
in the rear section.

Support

Figure

14

10: Install

Block

Additional

Sections.

Use level on each section

as tie rod bolts are drawn

up.

I "]av_..]_ ii'l_
16. To propedy assemble LC/LCE sections in the field.
the following steps must be followed to ensure that
no damage occurs to the tie rod lugs. A 0-I00 ftdbs
torque wrench is required•
a, Use a spirit level as shown in Figure I0 to check
the alignment of the sections as the nuts are
drawn up Keep the sections plumb•
b.

17 Repeat with the remaining sections.
a. Save the LWCO Intermediate with two I"
tappings (for level control) for use as the section
closest to the front section.
b.

Draw the sections together evenly, in three
rotations. Torque each port to 20 ft-lbs for the
first rotation, then to 40 ftdbs for the second
rotation, then to 60 ft-lbs for the third rotation
Use the following sequence until all three ports
touch metal-to-metal at 60 ft-lbs. See Figure 11
for port reference
i)

Place the Intermediate Section with 3" top
tapping (Tapped Intermediate) in the position
given in Figure 13
LCE ONLY. Save the (3) Top Flue Outlet
Intermediates (with wide opening in top of the
flue collector) for use as the sections closest to
the LWCO Intermediate Section• See Figure 13.

C,

The sequence from Front to Rear is:
• Front Section
• I" Low Water Cut-off Intermediate

First: Lower Top Port

ii) Second:

• Three (3) Top Flue Outlet Intermediates

BO_LOmPort

it) The remaining intermediate sections are 3"
Tapped Intermediates or Plain Intermediates
as shown in Figure 12 and Figure 13.

iii) Third: Upper Top Port
c.

Tighten these (3) three locations only to a torque
value of 60 ft-lbs. DO NOT EXCEED.

d.

After the three ports have been tightened to 60
ft-lbs, tighten the draw rod at the bumping pads
until metal-to-metal contact is reached. This will
assure a proper gas tight seal and prevent the
products of combustion from migrating into the
boiler room.
Front

Do not exceed the manufacturer's
recommendations.

12 11 10 9

TOP PORT

I

8

7

6

5

4 3

13 12 11 10 9

8

7

6

5

2 1 Rear

torque

iiiii
Front

,LOWER

[:7_]TI :I;1

UPPER TOP PORT

4 3

2 1 Rear

I

/

Figure
Table

12: Section
9:

Section

Positioning

Numbering

Numbering

Sequence

Model

Place

a Tapped Intermediate
Section at Position
(Numbered Rear to Front)

LC-04
LC-05
LC-06
LC-07
LC-08

NA
NA
NA
NA
NA

LC-09
LC-10
LC-II
LC-12

NA
NA
6
6

LCE-14

I

/

i ouMP,.OP.O
i I +ooPO.T
I
Figure

11: Torque

Specification/Procedure

LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24

5, 9
.

6, I0
6, II
5, 9, 12
5, 9, 13
5, 9, 14
5, 9, 12, 15
5, 9, 13, 16
5, 9, 13, 17
6, I0, 14, 18
6, I0, 14, 19

15

l_nP_j

:I=I I_[o_

SERIES

LC

SERIES

LCE

LCE
-13

LC
-04
Fron_

4 3

Z

I

Aear

Front

LC
-05
Front

5 4

3 Z

I

e

S 4

3 2

LCE
-14

iiill

LCE
-15

iiii

_ 6

5 4 3

_ _ Rear

Rear

LC
-06
Front

13 IZ H 10 9 e

1

Rear

Fro_t

_ I_ 13 12 _1 _0 9

Fron_

16 15 _

n 7 6

5 _ 3

Z I

Rea_

s 2

q

LCE
-16

LC
-07

LC
-08

LCE
-17
Front

8

7

6 _ 4

3 2

I

Rear

LC
-09

I_ 1_ _1 _0 9 a

_ 5

_ 4

R_ar

iiill
Fro_

19 I_ I_ _4 13 _2 I_ 10 g e 7

6 5 4

_ Z I

Rear

Front

I$ I_ 16 16 14 13 12 II 10 9 B

7 6

6 4 3

Z I

Front

19 19 17 IS 15 14 13 12 II 10 9

6 7

6 5 4

3 2 T

Rear

Front

N

19 19 17 IB 15 14 I_ II

1

Fron_

zl

_1 19 18 I_ _1_ 15 14 _Z _2 II l0 9

_ront

z2 Zl 2O 19 le

Front

Z3 _

LCE
-18
Front

_ s

7 6

5 4 3

2

_

Rear

_e_r

LCE
-19

/C
-10
Front

10 9

S 7

6 5

4 _

2

I

Rear

LC
-11

LCE
-20
Front

II

Io 9 _

7 6

5 4

3

2 I

Rear

LC
-12

I) I_ _

_

_

_

I

I

l

I

Ftear

S _

6

6

4

3

2

I

?

_

6

4

3

Z I

Rear

B _

e

_

_

3

_

LCE
-21
Fron_

Iz II 10 9

e 7

E 6

4

_ 2 I

Rear

Rear

LCE
-22
I_ _1_ 15 14 13 _2 II _0 9

S

LCE
-23
Zl _1 19 _

19 15 16 14 _

12 II 10 9

2

Rear

LCE
-24

i

Figure

16

i
,_

Burner

13: LC/LCE

'! i
_
I

1" LWCO
Tapped
Interm.
Section

Boiler Section

Assembly

Front
Section

Top Flue
Interm.
Section

Sequence

Tapped
Interm.
Section

I

Plain
Interm.

Rear
_ Section

Section

_

Flue
j Rear
Cover

III:(_i
JR ILl'_[_ Ir'.._UH
NIl{_o]lNl_,,_[o];| I_IIF,.._IUI:::F_

=I

i/.l-, :_']f!_"

lii'i.];{o]_lL'l|[@/1511/II1:1.]1111

1+

Remove the coil cover plates, gaskets and mounting
hardware, located in the Flue Box Carton•

1.

Install a drain valve in the Rear Section, Tapping 13
See Figure 29.

2.

Place the cover plates and gaskets over any unused
heater openings• Place the cover plate with two 3/4"
NPT tappings on the upper flow port opening
(Position #2) of the Front Section•

2.

Provide a water supply line to the boiler

3.

Plug all open tappings in the boiler

4.

Provide a means to vent air as the boiler fills.

5.

Fill the boiler with water, venting air as water level

3.

Install tankless heaters, if used, in openings
#3, (Optional on Rear Section)

#i and
rises.

4. See Figure 14
6.
5. Steam boilers may have up to two coils installed
when supplied with special tankless coil rear section•
6, Standard Rear Sections do not have a tankless
opening (Position #3). This is available only as
optional constroction. This special rear section is
needed to install two coils on a steam boiler

FRONT VIEW

Figure

14: Tankless

Pressurize boiler to:
• 45 psig
• DO NOT EXCEED

THIS PRESSURE.

a) Maintain pressure while checking all joints and
fittings for leaks•
7.

After inspection is complete, drain the boiler and
remove plugs from tappings that are to be used.

REAR VIEW

Coil Openings

17

Table

10:

Taokless

Coil

Ratings

Heater No.
X-1020

Heater No.
X-1021

Heater No.
X-1022

Two Heaters No.
X-1020

Two Heaters
X-1021

No.

Two Heaters No.
X-1022

Model
GPM
LC-04
LC_05R
LC 05
LC-06
LC-07
LC-08
LC-09
LC_10
LC-11
LC-12
LCE 13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE 21
LCE 22
LCE-23
LCE-24

5 5
562
575
6.25
6.5
7.0
7.25
75
8.0

Location
I
i
I
I
i
I
i
i
I

-

GPM

Location

65
70
7.75
8.5
9.25
10.0
10.75
11.50
12.25
13
13
13
13
13
13
13
13
13
13
13
13

Above heater ratings are based on intermittent

demand

18

Location

i
1
1
1
I
1
I
1
I
I
I
I
I
I

130
1375
145
15.5
16.5
17.5
18.0
18.75
19.5
20
20

I
I
i
i
i
I
1
1
I
I
I

1
I
1
i
1
1
I

20
20
20
20
20
20
20

I
I
I
I
I
I
1

GPM

14.5
15.0
16.0
-

Location

I &3
I &3
1&3

.

GPM

Location

21.5
23.5
24.5
26
26
26
26
26

1&3
I&3
1&3
I&3
1&3
1&3
1&3
1&3
l&3
1&3
1&3

26
26
26
26
26
26
26

I&3
I&3
l&3
1&3

:

GPM

Location

33.5
35.5
37.5

i &3
1&3
1&3

39.5
40
40
40
40
40
40

t

I&3
1 &3
l&3
l&3
I & 3
1 &3
1 &3

for water from 40°F to 140°F with 200°F boiler water.

Steam boilers require a special rear section with col! opening
DANGER:

GPM

in order to use two tankless heaters.

Install mixing valve in hot water supply piping, Water temperature

over 125°F can cause severe burns instantly or death from scalds.

I_I'_"]51k117=I .l.l_.]Ir:l_
;IN r±_'.l;,,lN_"ie,]il_±_L_[olnnluu_e_v,a:l;
_I'.lW'.._und=l
',
I.

Apply the Cleanout Cover Plates on the tops of the
section joints as shown in Figure 15.

2.

Pre-assemble a steel fiat washer and steel nut on the
carriage bolts. Place a carriage bolt into each side of
the cleanout opening as shown in the figure.

3.

Tighten the lower nut securely.

4.

Press the Cleanout Plate with insulation over the
protruding carriage bolts until the insulation lays
flush against the cast iron.

5.

Apply a fiat washer and brass nut to the carriage
bolt. Draw the brass nuts down until the insulation
presses firmly against the iron.

Cleanout Cover Plate
With Insulation

Brass

J

Steel Hex Nut _
1.

(LC) Remove the Flue Collar and Rear Observation
Door Assembly from the LC Rear Flue Box Carton.
(LCE)Remove the Top Flue Outlet Plate. the Rear
Flue Cover Plate and the Rear Observation Door
Assembly from the LCE Top Flue Outlet Carton.

2.

(LC) Attach the Flue Collar to the Back Section with
5/16" x 11/2'' studs, fiat washers and hex nuts
supplied. See Figure 16.
(LCE) Attach the Rear Flue Cover Plate to the Rear
Section with 5/16" x 1172'' studs, fiat washers and nuts
supplied.

3.

(LCE) Apply high tack adhesive (supplied in Section
Assembly Kits) to the rope groove on the bottom of the
Top Flue Outlet Plate. Place the high temperature rope
seal in the groove, overlapping at the ends for a good
seal.
a) Place the plate over the opening provided by the
three top flue intermediate sections at the front of
the boiler. NOTE: Top flue outlet plate is marked
"FRONTV" for proper orientation.

Carriage Bolt
%6" UNC x 13/4'' Long
/

\

Flat Washers

SIDE VIEW
Figure

15: Install

Cleanout

Cover

Plates

d) The correct Top Flue Outlet Plate for the LCE
boiler is:
• LCE-13 thru
part number
• LCE-18 thru
part number
4.

LCE 17 use the 14" flue opening,
LCE-5007, Carton D
LCE 24 use the 16" flue opening,
LCE-5007-1, Carton E

Attach the Rear Observation Door to the Rear
Section with four (4) 5/16"-18 x 3/4" hex head bolts
provided.

b) Secure the plate and compress using the 3/8" tie
down assembly, nuts and washers provided. See
Figure 17.
c) Inspect the finished seal, particularly
plate crosses the section joints.

Figure

16: Rear Flue Collar

Attachment

where the

Figure

17: Top Flue Collar Attachment

19

II: _

h__'_ ir_,_tl m etUJ ::It:f_,!-t ;l l:_

ii _

1

Remove the Front Cleanout
Section.

2.

Open Baffles carton Remove Baffles. For LC Only Save Ceramic Fiber Liner for Section I Save Rating
Label for Chapter 4. Models LCE 13 through
LCE-20 do not require baffles

3.

Place baffles as shown in Figure 18. Three of these
are special stainless steel baffles, identified with a
i/4" hole punched in each end These baffles must
be placed in the lowest row of tubes.

4.

Install the Front Cleanout

Front Cleanout

Aluminized

Plate from Front

h,_F:-IIf:'_ I! ql_ : F,__/_
I :] ::h| III i'll_ i
1.

(LCE) Remove ceramic fiber liner from jacket
carton E. (LC/LCE) Place the liner on the floor of the
combustion chamber, Place the front end of the liner
flush with the inside of the Front Section. The liner is
24 inches wide, It will not extend all the way to the
rear of the boiler on all boiler sizes. No adhesive is
required, just press the liner down firmly.

Plate.

Plate

Steel Baffle

Aluminized Steel Baffles
Stainless Steel Baffles
Must be in Bottom Row
Have 1/4" Hole As Shown

Figure

2O

18: Flue Baffle

Locations

,m

;,]1fl::1i_

_!

IiI; t _1",I:I -'!:!1/ [*] L_

5,

i.

The boiler must be pressure tested as outlined in the
chapter "Place the Boiler Sections" of this manual.

2.

The Supply and Return piping can be installed
before the jacket is applied. Use nipples long enough
to extend through the jacket.

6.

;N

t-"llll,,ll,

lli'd

I:,ll:JIL_[€

7.

1.

See Figure 21 for piping illustration.

2.

Install Top connections sized per Table 11.
a) Model LC-04 requires one riser off the Rear
Section. Plug the 4" tapping in the top of the
Front Section.

8.

9.

d) LCE models require three or more risers.

3.

4.

Size the Header per Table 11. Pipe the header at
least 24 inches above the normal boiler water line.
See Figure 19. This is required to prevent water from
carrying over into the header and then to the
system.
Figure 21 shows the Supply and Return piping for
Parallel Flow Gravity systems and all Pumped Return
Systems.

Counterflow Gravity systems require the boiler steam
line to enter the top of the steam main. See
Figure 20 for this special case.
Do not reduce the size or number of risers
shown. These are required for reliable operation of
the boiler. If the risers are undersized or incorrectly
placed, a sloped water line can occur in the boiler,
causing possible overheating of some sections.
Pipe the Header with an offset as shown in the
drawings. This offset prevents the expansion and
contraction of the Header from damaging the boiler
sections.

b) Models LC-05 through LC-10 require two risers,
one off the Front and one off the Rear Section.
c) Models LC-11 and LC-12 require three risers,
one each off the Front and Rear Sections plus
one off the Tapped Intermediate Section.

:1:1:1_,]]1[_-

Always locate the Steam Supply take-off
between the Equalizer and the last Boiler
Riser. (See Peerless Heater Company's "Steam
Installation Survey" for discussion). Locating the
steam supply between the risers will cause water
carryover to the system.
Do not use a bull head tee to provide steam supply
and equalizer connections, this will cause water level
bounce and carryover.

Jel! I it 11ill ltl'_l fJI iI h:_lc
I.

The use of a Hartford loop is recommended in all
installations. See Figure 19. The loop provides
additional reliability for the system.

2.

A check valve must still be installed on the pump
discharge of all pumped return systems.

Steam

Steam Supply should always
be piped between
last boiler
riser and equalizer.

Supply
BOILER HEADER Pipe with offset
to allow for header
expansion

I
24"

Min.
x

To

." Use close

i

4" " Hartford
, Loop
I

!
Blowdown

/"

Valve

.
/+

Figure

19: Supply

and Return

Positions,

Skim Piping,

Hartford

Loop
21

3.

Boiler Riser Piping
enters TOP of main
on Counterflow

System

_

4

Steam Main

6.

Pitch T

2" Skim
Connection

Header,

Model

LC-04
LC-05R
LC-05
LC-O6
LC-O7
LC-08
LC-09
LC-10
LC-11
LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE 21
LCE-22
LCE-23
LCE-24

22

1.

Figure 22 shows typical piping for multiple boiler
Gravity Return systems. Figure 23 show typical
piping for multiple boiler Pumped Return Systems•

2.

Provide separate feed lines for multiple boiler
pumped return systems. Use either separate feed
pumps or solenoid or motorized valves to isolate
feeding of the boilers. This is needed to provide
reliable level control and avoid nuisance
performance problems.

3.

Condensate return units are not effective for multiple
boiler installations since they do not respond to the
needs of the boilers• always use Boiler Feed Units.

4.

Install a Float and Thermostatic trap at the boiler
water level on each of the mufltple boilers on a
pumped return system• This prevents flooding of idle
boilers due to condensation of steam•

20: Supply and Return Piping Counterflow
Gravity Systems

11:

Risers r: Equalizer
I=B=R
Gross
Output
MBH
547
649
707
868
1029
1189
1350
1511
1672
1832
1966
2125
2284
2444
2603
2763
2922
3082
3256
3430
3604
3777

If the pump discharge is looped overhead, above the
boiler water line, install spring loaded check valves at
both the pump discharge and the connection to the
boiler return.

I)]q I fldaJ allll:J ii=l I:{e] lit :I:llL_LL't IL,11iW_'_lll[O]t_
_

ualizer

Table

Size the equalizer per Table 11. Models LC II, LC12 and LCE-13 through LCE 24 require two return
connections to the boiler off of the equalizer line.
Pipe the Hartford loop tee so the inside top of the
close nipple is 2 to 4 inches below the normal boiler
water line. See Figure 19.

Counterflow

Figure

On pumped return systems, install a boiler cock after
the pump to allow throttling of the pump discharge.
The pressure after the boiler cock should be no more
than 5 psig above the boiler operating pressure.
Pumping the water into the boiler too fast will cause
collapse of the water level and level control problems.

Sizing

!!

;

!

End Section
Risers
Size
Number
(Inches)
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

4
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

Intermediate Section
Risers
Size
Number
(Inches)

7

Equalizer
(inches)
2
2
2
2
21/2
2½
21/2

1
1
1
2
2
2
3
3
3
4
4
4
4
4

_

3
3
3
3

3
3
3
3

3
3
3
3
3
3
3
3
3
3

3
3
4
4
4
4
4
4
4
4

Header
Size
(Inches)
4
5
5
5
5
6
6
6
6
6
6
8
8
8
8
8
8
8
8
8
8
8

I ;1I_ _ _

-i-i-i-i-i-i-i-i-i_
_ _I

LCE-13 THRU LCE-24
TWO

END RISERS

ONE OR MORE INTERMEDIATE
RISERS
TWO RETURN CONNECTIONS

Figure

21: Supply

and Return

Piping - Pumped

Return

and Parallel

Flow Gravity

Systems

23

l_1_llill_ I;I.]TI-_;t
Steam

Supply

Stop
Valve

Pipe All Headers
24" Above Boiler

Minimum
Water Line

Stop
Valve

Blowdown
Valve

Figure

22: Piping

Multiple

Boilers,

Typical,

Gravity

Return

Systems

Steam
Stop
Valve

Pipe All Headers Minimum
24" Above Boiler Water Line

Supply

Stop
Valve

_f_\_

receiver

F/I- Drip
Trap

) Valve
_'_.

;olenoid or Motorized

Valve

Boiler Cock for Throttling
Pump Pressure to Boilers
Check

Valve

Valve

To

Pump

Alternate Piping: Use two separate pumps, separate return lines and no solenoid valves
Figure 23:

24

Piping Multiple

Boilers, Typical,

Pumped

Return

Systems

"_1 "J,| :1_:_ H _ //'l:I

_:! ;| |

Collect all the jacket cartons: Jacket
Front & Back
Carton plus Jacket Side & Top Cartons. See
the Shipping List in the front of this manual for the
jacket cartons required. The cartons contain the
jacket parts and screws• The jacket panels are preinsulated.
Remove all needed knockouts
before beginning assembly,

2.

2.

Attach the Middle Front
in the same manner.

Panel

and Lower

Front

Rail

3.

Position the Jacket Assembly with the front panels
pushed up against the front section. You will need
the jacket in this position to install the Burner Front
Plate•

le]i Ir:q"] "]k'd IqiL'Te.][4:il / IH :I_,I :g :I_,1L_1:1

from the jacket parts
1.

Attach the Rear Jacket Panel to the Jacket Side
Panels with #10 x 1/2" sheet metal screws.

I:R F-'N']'.Jk'd qY_'To.]
[4:ill _"lle] :(,:] r,_lL_le][e.[e];]_l:4:[,:
I_q V*-N']:,lk'd [qY:Te'][4:il/ll[e]:.i__,NLH:tl_
1.

See Figure 25 for details.

2.

The Side Panels can be used on either side of the
boiler.

3.

Place the Jacket Side Panels on each side leaned
against the Boiler Sections.

4.

On Models LC-08 through LC-12, each side uses
two panels. Place the panels so the seam is centered
on the Tapped Intermediate Section. On LCE
models, place panels in the sequence shown in Table
12.
On boilers with two or more Jacket Side Panels per
side, join the panels together with #I0 x I/2" sheet
metal screws. Also attach the Jacket Side Panel
Reinforcing Angle inside the jacket at the bottom of
the seam.

5.

i.

Attach the Top Front Panel to the Sides and Upper
Front Panel with #I0 x 1/2" sheet metal screws.

2.

Models LC-08 through LC-12 use two Jacket Top
Panels. Place them on top with the seam at the same
point as the side panels• Join them at their seam
with #10 x 1/2" sheet metal screws. On LCE models,
place panels in the sequence shown in Table 12.

3.

Attach the Jacket Top Panel to the Jacket Top Front
Panel with #I0 x 1/2" sheet metal screws•

4.

Attach the Top Rear Panel to the Jacket Top Panel
with #I0 x 1/2" sheet metal screws.

5.

Finish by placing #10 x i,,'2" sheet metal screws in
the remaining holes along the Jacket Top Panel
flanges, into the Jacket Side Panels.

Attach the Left Front Corner Panel to the Left Side
Panel with # i0 x 1/2" sheet metal screws.

6.

7. Attach the Right Front Corner Panel to the Right
Side Panel with #10 x i/2" sheet metal screws.

I=1 r_W_l_Jk"4I'.,,IW'.._Ii::(-_
F;1L'_IO]
lir_,l:]::ll_
i.

Mount Boiler Rating Plates and Agency Plates on the
Upper Jacket Front Panel as shown in Figure 24.

2.

Secure metal plates with #6 x 1/4" sheet metal
screws. Apply all adhesive-backed
labels.

[o46r_,'q-.,l:JiVdPlr±Te.][4::illiH
:l:{e]b,'1|l i_._I_1:ii(_
1.

Attach the Upper Front Panel to the Right and Left
Front Corner Panels with #i0 x 1/2" sheet metal
SCreWS.

Table

12:

Jacket

Top b Side Panel Placement
Locate Jacket Top and Side Panels in
the Position Below
(Numbers are from Rear to Front)

Model

5 T
(Front) I

2

4

1
i (Rear)

I
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24

-

E

I

B

E

A
B
C

0

€
T

1
E
E
E
E
E

E
E
E
A
A
B
B
C

[

A
B
C
A
B
B
B
B

B
B

B
B
B
B
B
B
C
C

0

Figure 24:

Location of Rating, Agency and
Instruction
Plates on Jacket Front
Top Panel

25

Jacket

Top Panel

Jacket Top Panel
Jacket Top
Rear Panel
I

I

Jacket

Rear Panel

• I

Jacket Top
Rear Panel

Jacket Top
Front Panel

Jacket
Side
Panel

Jacket Front
Top Panel
Jacket Front
Middle
Panel
Jacket Left
Front
Corner Panel

Jacket Front
Lower Rail /
Figure 25: Jacket

26

Assembly

Jacket
Side
Panel

Side Panel
Support
Angle
Jacket Right Front
Corner Panel

Refer to Chapter I, preinstallation, Section D. Chimney,
or Vent for installation requirements. Refer to
Chapter 9. Startina the Boiler, Section C. Run Burner
Check Out for damper settings and draft requirements.

r:!

I:{II:|L_I:I;t

3_

r:1:J'Jl[l'Y:_li[e]{

1.

Refer to Burner Spec and Data Sheets for the Oil
and Gas/Oil Burners pre-tested with Series LC
boilers.

2.

Make sure the nozzle sizing and spray pattern match
those given in the spec and data sheets.

3.

See Figure 26 and Table 13 for combustion
dimensions.

4.

I.

2.

chamber

Remove the Burner Mounting Plate and Hardware
Bag from the crate.

I1:1:

I:|II:|LII=I_

Remove the Burner from its crate. Read the burner
instructions.

2.

Insert (4) 3/8"-16 x II/4'' studs supplied with Burner
Mounting Plate into the front plate holes.

3.

Place the high temperature gasket on the burner
front plate and secure the burner to the front plate
with 3/8" fiat washers and hex nuts.

I_v_[_l|JL_illlh_[Cl
I;.lff-_lll

The Burner Mounting Plate is made to fit the burner
being used. Burners vary in bolt pattern for the
flange, burner tube diameter, insertion length and
near-tube configuration. Make sure the front plate is
correct for your burner if purchased separately from
the boiler.

Secure the Burner Mounting Plate to the front
section with the fiat washers and hex nuts.

[I,_ hVA[ellJL_ll
1.

I:_ IIL_-"]llr±!llli:]lJ-'_,_l=l;!

Screw (7) 3/8"-16 x 21/4"studs into the holes in the
front section around the chamber opening.

4.

If the burner is supplied with a pedestal, install it to
the burner per the Burner Manufacturer's
Instructions. The pedestal provides additional
support and prevents the burner from sagging.

27

:I
Figure 26:

Combustion

Chamber

Layout

Table

Combustion

Chamber

Dimensions

13:

Model

LC-04
LC-05R
LC-05
LC-06
LC-07
LC-08
LC-09
LC-IO
LC-11
LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE 19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24

28

Chamber
Length
"A"
(Inches)
18%
23W16
23_5Ao
29
34¼€
39V_
44¾,3
49V4
54_A6
59%
647A0
69V2
749A€
79%
84_¼6
89%
941¾_
99%
104'5A6
110
1151/16
1201/8

- See Table

13 for Dimensions

Burner
Beckett
6%
6%
6%
6V8
6_
11/8
1%
IYs
11/8
11/_
11/8
1%
11/8
1%
1%
11/_
1%
1%
1%
N/A
N/A

Front

Plate

Extension

Carlin
61/s
6%
6%
6%
6Vs
61/8
i%
II/8
1%
1%
IVs
II/8
11/_
1%
1%
I%
1Vs
U/s
1%
I%
NIA

i
i

Past Jacket

(Inches)

GordonPiatt

Power
Flame

6gs
I%
ll/s
1%
I%
11/8
1%
IV8
11/8
1%
1%
I%
II/8
IV8
11/8

6%
6%
6%
6Va
6_×_
1%
I_/8
I%
I%
IVa
IV_
1Vs
1V8
1%
1%
1%
I%
IV8
IV_
i%

6%
6%
6%
6Vs
6V8
I%
I%
I%
IV8
IV8
IV8
1Vo
1%
IVs
1%
IV_
1%
1%
1%
1%

IV8
1%

1Ve
11/_

I%
1%
I%
1%
11/8
I%
i'/8

Webster

[_o]_ h'_
1:(..inuI _LIJ=lml["_1"J_c7
I

].

2.

Read the Burner Instruction Manual, supplied with
the boiler or with the burner if purchased separately.
Review applicable code requirements for burner and
fuel piping installations.

To Gas Supply --_

Install piping to allow removal of burner and access
to combustion chamber for cleaning or service.

Service Valve -1_
I=J IIL_l_"]llr'-l!ll:llJ =lll0]ll

-_

",JI_IL_[,

1.

Place the fuel oil tank and install the piping in
accordance with the National Board of Fire
Underwriters and all other applicable codes.

2.

General Guidelines for Oil Piping
a) Follow the guidelines in the Burner Manual for
sizing oil lines. Never use smaller than I/2" OD
copper tubing.

Ground_

b) Install manual shut-off valves on the suction line
at the burner and at the oil line entrance to the
building. When installing a shut-off valve on the
return line, an oil pressure relief valve piped
ahead of the shut-off valve and discharged to the
tank must be provided to prevent over-pressure
conditions.

c)

Install a two-pipe oil distribution system when
possible. It will improve the reliability of the oil
delivery to the burner.

d)
e)

Use flare fittings when using copper tubing.

To Boiler Gas Control Train
Sediment Trap

Figure 27:

Provide an oil line filter in the suction line. Size
the filter for the suction gear capacity of the
burner oil pump if running a two-pipe system.
If burner is above the top of the fuel oil tank,
install a check valve on the oil suction line at the
burner to prevent oil from evacuating the line. If
burner is below the top of the tank, install an
anti-siphon device to prevent oil flow should the
oil line break.
t!

ion Ih.'_[.-"lllr'_llIIc'f_'l,-"] [.'.llJ'J'Jli'd

2.

3.

The standard gas train is designed for a maximum
pressure of 1/2 psig (14 inches water column). Make
sure the system regulator will not allow a higher
pressure to the Gas Control Train under any
conditions.
The minimum gas supply pressure is listed on the
Burner Rating Plate. Make sure the system regulator
and the piping are sized and adjusted properly to
provide this pressure under all conditions.

to Boiler

Install a Service Valve, Sediment Trap and Ground
Joint Union at the supply connection to the Gas
Control Train as shown in Figure 27. These are not
supplied with the boiler. Install them in accordance
with local codes.

5.

Use only pipe joint compounds
Liquefied Petroleum Gases.

II_-I

".,]I'ilh,'1[€

Size the piping as required by the National Fuel Gas
Code, ANSI Z223.1 or as required by local codes.
a) Use Table 14 for sizing of natural gas for a
system pressure drop of 0.3 inch water column.

Connection

4.

I.

1,

Gas Supply

Icf:!-I

rated for use with

[--"].ll"J_k'dN _l:,,,lh,'_[_

ISOLATE THE BOILER GAS CONTROL TRAIN
FROM THE SYSTEM DURING TES_
a) Test pressure 1/2 psig or less - Close the Manual
Shut-Off Valve on the Boiler Gas Control Train.
b) Test pressure over 1/2 psig - Disconnect the gas
supply piping upstream of the Boiler Manual
Shut-Off Valve.

Do not expose the Gas Control Train to excessive
pressure.The gas valves can be damaged.This could
result in explosion hazard and severe personal injury
or death.
Do not test gas supply piping with open flame. Use a
soap suds mixture brushed onto the pipe joints to
test for leaks.

29

Table

14:

Capacity of Gas Supply
0.3 inch Water Column,

Pipe in Cubic Feet Per Hour of Natural

Gas for Pressure

Drop of

Pipe Length
(Feet)

1-1/4"
Pipe

1-1/2"
Pipe

2"
Pipe

2-1/2"
Pipe

3"
Pipe

4"
Pipe

Pipe

10

1050

1600

3050

4800

8500

17500

44OO0

20

730

1100

2100

3300

5900

12000

31000

30

590

890

1650

2700

4700

9700

25000

40

500

760

1450

2300

4100

8300

22000

50

440

670

1270

2000

3600

7400

20000

60

400

610

1150

1850

3250

6800

18OOO

70

350

560

1050

1700

3000

6200

17OOO

90

320

490

930

1500

2600

5400

15OOO

I00

305

460

870

1400

2500

5100

14OO0

150

250

380

710

1130

2000

4100

11500

Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance
pipe fittings. Use the following multipliers on above capacities for specific gravity other than 060:

Specific

Multiply

3O

Gravity

Capacity

by:

0.50

0.55

060

1.10

104

1 O0

6 t,

is needed

0.65

0.70

0962

0.926

for

r,l

Ih_[..'_lf;11lll _',]r;1;;l::illk'4LVl;1IkvJ=[..
i.

ID31 IIs_[_"]llr;!llt!I;,l:?:k."_'_lJ:|::l[I,[i]_//:(t]l_

Pipe the discharge of the Safety Relief Valve away
from any traffic area, preferably to a floor drain. This
is necessary to prevent injury should the valve
discharge.

Make sure that the ignition system components,
electrical controls, junction boxes and electrical
panels are protected from water (dripping, spraying,
rain, etc.) during boiler operation and service (trap
servicing, control replacements or other).

Pipe the discharge full size of valve outlet.

2.

3. Pipe the Steam Pressure Gauge and Boiler Limit and
Operating Pressure Controls as shown in Figure 30.
Connect the control assembly to the I/2" tapping in
the front section.

Pipe the Pop Safety Valve on a tee mounted in the
2]/2'' tapping located on the upper ]eft side of the
Rear Section. Make sure the relief valve sizing meets
local code requirements.

Install a 2" ball valve for skimming off the end of the
tee as shown in the piping drawings in this manual.

1:11 -,JI "]:11it_,1
t_I [41 =k'_l:
1.

I;]tl I h,_[,,:"Jr
It_'111 1:] Ko]I,_I| tp[ol r,_|_,'_
I kVl'_1IkvJ=[-;

1.

Install a IL/Z"full port ball valve off of the return
connection as shown in the "Pipe the Boiler" section
of this manual. See Figure 28.

2.

Pipe the valve discharge to a floor drain if available
or apply a nipple and cap to close off when not in

I:q

I:f_,t /: :ll_

Connect piping to any installed tankless heaters. See
Figure 35 for suggested piping for single coils and
Figure 36 for suggested piping for dual coils.

[Ke]L_h_l:[_l/[,."J.uJ:,l:,llk'dLrAVJlHh_[€
1.

Install all wiring in accordance with local codes, the
National Electrical Code and other controlling
agencies or governing bodies.

USe.

tel! Ih,'ql,,,_
Ir_'lll! lU(ol_l_ir_,rr_'_lti=l-"l
_l,,]ljl[O]-I:r,{___
1. Mount a float type Low Water Cutoff and Gauge
Glass in the tappings provided in the side of the front
section or the side and top of the first intermediate
section.
2.

3.

4.

Do not apply piping which would raise or lower the
location of the cutoff relative to the tappings in the
boiler. Raising the water level over the design height
will cause water carryover to the system.
For correct location of typical low water cutoff/feeder
or low water cutoff/pump control, see Figures 31
through 34.
See Figure 29 for the location of control connection
tappings.

The boiler/burner must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction, or in the absence of such
requirements, with the current edition of the National
Electrical Code, ANSI/NFPA Number 70.

2.

Use #14 gauge or heavier wire for supply wiring.
Protect the circuit with a fused disconnect switch (by
others) and a grounded neutral.

3.

Mount an electrical junction box on the boiler Front
Panel for connection of supply wiring and
distribution to the boiler controls.

4.

5.

Provide each float low water cutoff with a blowdown
valve. Pipe the blowdown away from traffic to a floor
drain if available. The blowdown valve is required
for proper maintenance of the control.

6.

Maintain a height of 461/2" from boiler foundation
the normal water level.

7.

When using Multiple Float Type Controls: Always
pipe the controls off of the same tappings to the
boiler. Do not mount on different ends of the boiler
or in different tappings. This can cause erratic
operation and nuisance problems with the controls.

Follow the instructions in the Burner Manual and the
Wiring Diagrams supplied with the burner and the
boiler.

to

31

¢H

h_l.."l Ih_1
I! IKa,(o] _ilII; {o] INr_,_i
I; i h_[_.

3

Install all line voltage wiring in conduit

I.

Wire the boiler according to the wiring diagrams
supplied with the burner and the boiler (in the Boiler
Envelope)

4.

Do not install single pole switches, including safely
controls, in a grounded line.

2.

Low Energy Safety Control Wiring, if used, must
follow the contour of the boiler. Some local codes
may require that all wiring, even low voltage, be
routed in conduit.

Steam
Supply

Install Boiler
off of 21/2"tapp,ng
as shown. Pi
full size
preferably

in_End Section

a

Install a 2"
valve piping

Install
a 11/2
'' Blowdown
Valve
off of the
Return
Piping As
Show n_

Figure 28: Blowdown

32

Valve,

Safety

Valve

and Skim Valve

Return
Piping

i

6

4

9

1

2

16;

15

11;<
10
8

f

14

e

7

FRONT

REAR

1

4" NPT Supply Tapping, Front Section

8

Not Used On Steam, 3/4" NPT - Plug

2

4" NPT Supply Tapping, Rear Section

9

Pressure Ctrl/Gauge
3/4" NPT Tapping

3

3" NPT Return Tapping, Rear Section

10

Secondary Probe LWCO Tapping, 3/4" NPT

4

Not Used On Steam,
1/2" NPT Tapping - Plug

11
12

Not Used On Steam,
1" NPT Tapping - Plug

5

(2) 1/2" NPT Gauge Glass or
LWCO Tapping

13

Drain Tapping, 3/4" NPT

6

Tankless Coil Temp Control Tapping,
3/4" NPT, Only with Tankless Coil Installed

14

NOt Shown - 1" NPT Tapping in Side and
Top of First Intermediate - for LWCO

7

Relief Valve and Skim Tapping, 21/2" NPT

15

Not Used On Steam,
(2) 3/4" NPT Tapping - Plug

16

Assembly,

Tankless Coil Temp Control Tapping, 3/4" NPT, Only with Optional Tankless Coil Back Section

Figure 29:

Control

and Pipe Tapping

Locations

33

. ]_[--_t'_] _ ['_k'i]_ o_I_]_],
_J;th'_l [:1_JIfll_[_

P

Option 1

J
(Right Hand Shown,
Left Hand WouEd Be Reversed)

E

F
P
E

C

I

Option

2
C
P

A

3/4" X 3/4" X 1/4" Reducing

B

3/4" Cross,

C

3/4" Plug, Malleable

D

3/4" x 1/4" Hex Bushing,

E

1/4" x 3" Nipple,

Brass

F

3/4" x 3" Nipple,

Black Iron

34

Tee, Malleable

Malleable

(NOTE:

Figure 30: Control

A

Malleable

Some

and Pipe Tapping

local codes may require

Locations

G

3/4" x4" Nipple,

Black Iron

H

3/4" x 5" Nipple,

Black Iron

J

3/4" x 6" Nipple, Black Iron

K

Steam Gauge

P

Steam

larger

Pressure

piping)

Control

!

--

Burner Cut-Off

Level

/>
1/2" Brass
Union
/-1/2" X 4" Brass Nipples

Figure

31: Optional

Model

(2 Req'd)

67PE2

1/2" Brass Close
Nipples (2 Req'd)

Float Low Water

Conduit
Connection

Cutoff

Normal
Water Line

81/2 ''

t

Burner

Cut-Off

Level

Feeder Closing Level
(Mark on Casting)

Figure

32: Optional

Model

47-2 Low

Water Cutoff/Feeder

- Use only up to Model

LC-O7

35

74;,]

Ii;1177f4lTffitI 4

C

C

B
H

A

A

G

Burner Cut-Off Level
Casting)
J

Normal

Water Line

=_

LWCO Intermediate
Section (First from

F

E

B
12"

Install 1" Blowdown

Boiler Foundation

Valve

A

1" Cross

B

1" Ground Joint

Union

D

I" x 3" Nipple

G

1" x 12" Nipple

E

I" x 4" Nipple

N

1" x 61/d' Nipple

C

J

The connected
fittings shown on this drawing
to be supplied
by the installer.

Figure

36

33: Optional

Float Type Pump Control/Low

Water Cutoff,

Model

are

157

'.

V

*

1

C

B

A

Burner Cut-Off Level is 1V2" Below
Center Line on 51-2 and 51-S-2 Controls
(23/4" Below Normal Water Line)

Feeder Closing Level
(Mark on Castingj

J

Normal

Water Line
Control
Center
Line

LWCO Intermediate
Section (

E

B

/
Install 1" Blowdown

f
y_Bo!le[

Valve

SUGGESTED

FITTINGS

Foundation

LIST

A

1" Cross

D

1" x 4" Nipple

G

1" x 12" Nipple

B

1"GroundJointUnion

E

l"x4"Nipple

H

1"x61/2"Nipple

C

1" Plug

F

I" x _' Nipple

d

1" x 19" Nipple

Always

Figure 34:

use a pump control

Optional

and boiler feed system

Feeder/Low

Water

Cutoff,

The connected fittings shown on this drawing are
to be supplied by the installer.

Type 51-2

37

3/4" Control
Tapping

High Temperature
Hot Water
Provide anti-scald
devices in the system

Mixed Water

Tankless

where

needed.

Failure to control water

Heater

temperature

or other usage areas

NE

Flow

to showers

where a scald risk exists
can result in severe
personal injury,

Cold
Water
Inlet

Figure 35:

Suggested

Water
Mixer

Piping - Single Tankless

Coil Installation

High Temperature

Mixed

Tankless

Hot Water

Heaiers

_4_

Rear

"

Water

Front

,
V

Water

Is

Mixer

Cold
Watel

Tapping

Inlet

Flow Control
Figure

38

36: Suggested

Piping - Dual Tankless

Coil Installation

"-!1 [_:l_[li:l;
I.

When a barometric draft regulator is installed in the
venting system, adjust the boiler damper for 0" wc
pressure reading at the damper. Adjust the draft
regulator for -005" wc draft between the boiler
damper and the draft regulator.

I']l'J h_[4

Steam Piping
a) The Boiler must have been hydrostatically
b) Check the attached

tested.

piping for joint tightness.
4.

c) Continue
start up.
2.

monitoring

as you proceed through

Gas Piping
a) Make sure the gas system piping and the
connections to the Boiler Gas Control Train(s)
have been leak tested.

Adjust the burner as needed for a CO 2 reading of:
a) Oil burners: CO 2 approximately 12.5% or I%
less than the level at which the smoke reading
goes above a trace on the Bacharach scale.
b) Gas burners: 9% to 10% with CO less than 50 ppm.

5.

b) After the boiler is in operation, check the
tightness of all joints in the boiler gas piping with
a soap suds solution.

Inspect al[ flue gas joints (sections, attachments,
breeching and vent) for gas tightness. Remove the
jacket panels in order to thoroughly inspect all rope
seal joints between the sections.

c) Purge the gas piping of all air up to the boiler
Gas Control Train.
3.

Oil Piping
a) Check the oil piping visually. Make sure all joints
are tight.
b) When the burner is firing, check the suction line
and return line pressures.
c) If the pressure exceeds the allowable pressure in
the Burner Manual or if the suction line vacuum
is higher than allowable, correct the piping as
needed to bring the suction line and return line
pressures within acceptable range.

On installations with high draft, do not leave the
boiler with a negative draft reading at the rear flue
box or draft damper. High negative draft can pull the
flame up into the boiler crown sheet and overheat the
iron.This can result in cracked sections or shortened
boiler life.

I_

[_'I:[*,]H
1.

d) Excess pressure can cause pump seal failures.
Excess vacuum will cause fuel flow problems
with the burner oil pump.

I:{o]ll_:l(t]L_ll;lo]_

Limit and Operating

Pressure Controls

a) Lower the setting of each control until the burner
shuts down.
2. Low Water Cutoffs

:tl

I=11 II i :l:l I:{*]lllq;

a) Test probe type controls by using the Push4o-Test
Button.

i.

b) Test float type conb'ols.

Fill the boiler to the normal water line.
a) Gravity Systems and Pumped Return with
Condensate Units - Fill to 461/2" above the boiler
foundation (center of gauge glass).

3.

4

b) Pumped Return with Boiler Feed Unit - Fill the
boiler using the boiler feed unit. Fill level will
depend on the control being used, but should be
461/2" above the boiler foundation (just below
center of gauge glass) when the pump stops.
;_l

I ;tlJ L_I :t.ll 1| L_1:1it lit : I :[_ [_.11

II

i.

l_fore firing the burner, slide the Slide Gate Damper
on the rear flue box all the way down (full open) on
LC's or open the LCE Draft Damper until the handle
is parallel to the vent pipe (full open).

2.

Follow the instructions in the Burner Manual for
starting the burner, adjusting air openings and fuel
rates. Perform ignition system and flame supervisory
control test and checkout as described in the manual.

3.

After burner is set at rate, close the damper until the
pressure reading at the test opening in the rear flue box
or draft damper is between 0" wc and 0.1" wc positive.
See Table 15 for typical overfire pressure (measured at
the burner front plate) and boiler draft loss.

Follow additional instructions in the Burner Manual
for proving the burner component operation.
Check all controls to make sure they function
correctly.

5. After all controls have been proven, set the
Operating and High Limit Temperature Controls to
the pressures desired.
I_

[_I_:IL_Ii/:I
I.

_n :[o]llq;

Clean the boiler as described below no later than
one week after the initial start-up. Cleaning will be
more effective if the boiler operates a day or two to
loosen sediment and impurities in the system.

Cleaning the boiler requires the use of very hot water
and corrosive chemicals. Use care when handling to
prevent injury.

39

2.

3.

4.

5.

The boiler must be cleaned to remove any
accumulation of oil, grease, sludge, etc. that may be
in the system. These substances can cause foaming
and surging of the boiler water, producing unstable
water line and water carryover to the system.

9.

10. Continue skimming the boiler until the water flowing
from the skim tapping flows clear. This will take
some time, possibly several hours for a dirt_ system.

The piping for a 2" Skim Valve must be done as
shown in this manual, with the skim valve mounted
off the Pop Safety Valve tee on the rear of the boiler

11. After skimming is complete,
turn off the boiler.

Connect a 2 inch drain line off of the skim valve, run
to a point of safe discharge.

12. Close the make-up
blowdown valves.

Close all valves to the system. Provide a means of
continuous fresh water to the boiler for the cleaning

Open the skim valve. Fill the boiler until water begins
to flow out of the valve.

Table

15. Note: If the gauge glass becomes dirty again, this
indicates more contaminants have worked loose in
the system. Repeat the cleaning and skimming
process as needed to clean the system.

Turn burner on and allow the boiler water to heat up
to just below steaming (180 ° to 200 ° F). Cycle the
burner to maintain temperature during skimming. Do
not allow the boiler to steam. Steaming mixes up the
contaminants in the water instead of floating them at
the surface.

15:

Typical

Model

LC-04
LC-05R
LC-05
LC-06
LC-07
LC-08
LC-09
LC-10
LC-11
LC 12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24

Combustion

Chamber

Pressure

water valve and open the boiler

14. Restore piping to normal. Pipe a nipple and cap in
the skim valve.

7. Use common washing soda (such as Arm and
Hammer Super Washing Soda). Mix the soda with
water in a 10 quart pail and pour into the boiler
through the safety valve tapping. Use a proportion of
one (1) pound of washing soda for each 800 square
feet EDR net boiler rating.
8.

close the skim valve and

13. Drain the boiler completely, then refill and drain
again one or two times to make sure all of the soda
has been washed out.

process.

6.

Open the make-up water valve to coninuously feed
water to the boiler, Allow water to flow out the skim
tapping.

Do not leave the boiler unattended while firing.
Take great care not to allow the water level to drop
below the bottom of the gauge glass or to allow fresh
water make-up to flow in too fast.This will avoid the
possibility of causing the boiler sections to fracture.

and Boiler Draft

Loss

Combustion Chamber Pressure
with 0.1" w.c. at Rear Flue Box Test Port
(Inches w.c.)
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+

0,22
0.22
0.24
0.26
0.27
028
029
0.30
0.31
0,32
0.24
0.25
0.26
0,27
0.28

+
+
+
+
+
+
+

0.29
0.30
031
0.31
0.31
0.32
0.32

Boiler Draft Loss
(Inches w.c,)
I

0.12
0.12
0.14
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0,14
0.15

.

0.16
0.17
0.18
0.19
0.20
0.21
0.21
0.21
0.22
0.22

NOTE: Actual chamber pressure and draft loss readings may vary with each boiler and installation due to variation in the heat exchanger,
deposits in the flueways, actual burner firing rate and excess air conditions, Use the above numbers as a general guide only. If the measured
loss is considerably higher than the above, check the flueways for deposits and confirm the burner firing rate

4O

draft

c) Do not use ethylene glycol antifreeze in a steam
boiler or system.
Do not store or allow combustible or flammable
materials near the boiler. Substantial fire or explosion
hazard could result, causing risk of personal injury,
death or property damage.
Do not use this boiler if any part of it has been under
water. Immediately call a qualified service technician
to inspect the boiler. Any part of the control system,
any gas control or any burner or gas component
which has been under water must be replaced.
Should overheating occur or the fuel supply fail to
shut off: Shut off the fuel supply at a location
external to the boiler. Do not turn off or disconnect
the electrical supply to the pump. Immediately call a
qualified service technician to inspect the boiler for
damage and defective components.

f.*1 I'=llF_*l_]l=_
[e I:[*]ll:l:f

Ih_l [*]',I=I;__'_I[*]L_

I.

Start up the Burner/Boiler per the Burner Manual
and the instructions in this manual on starting the
boiler.

2.

Prove the correct operation of all controls on the
boiler and burner as outlined below.

3.

Check the operation of the ignition and flame
proving controls as described in the Burner Manual.

4.

Test the limit and operating
are operating correctly.

controls to assure they

Before servicing the boiler:
• Turn off all electrical power to the boiler.
• Close the Gas Service Valve and Oil Shut-Off Valve.
• Allow the boiler to cool if it has been operating.
• Label all
servicing
improper
operation

loll

wires prior to disconnection when
controls. Wiring errors can cause
and dangerous operation, Verify proper
after servicing,

hVjr:lh_//_L_rI, IL_[_l_
1.

2.

,V:IL_h_IlY:I

Before the start of each heating season, inspect
and make all necessary adjustments to insure proper
boiler and burner operation. Use the maintenance
and inspection procedures following.
Inspect the Venting System
a) Check the chimney or vent to make sure it is
clean and free from cracks or potential leaks.

5.

Inspect and test all low water cutoffs.

6.

Test the pop safety valve(s) using the procedure
given by the valve manufacturer on the valve tag.

7.

Visually inspect the burner and pilot flames (if
applicable).

I:H b(e] _:LIiIlllol_,_lb,'lli:l_

d) Be certain that the boiler and system are refilled
before returning to service. Follow the
Instructions in the manual and the Lighting
instructions to operate.

b) All joints must be tight and sealed.
c) The vent connector must extend into, but not
beyond the inside edge of the chimney or vent.
3.

I:{o]llq;

1.

Turn off Burner.

2.

Open main line power disconnect
boiler/burner.

Inspect the Boiler Area
a) The boiler area must be clean and free from
combustible materials, gasoline or any other
flammable liquids or vapors.
b) The combustion air openings and the area
around the boiler must be unobstructed.

switch to

3.

Close fuel shut-off valves.

4.

To take boiler out of service if the boiler and system
are not to be used when temperatures are below
freezing:
a) Drain the boiler and system completely and shut
off make-up water supply.
b) Open main line power disconnect switch to
boiler/burner. Remove the fuses or secure the
switch so that the power cannot be turned on
accidentally.

4.

Inspect boiler flueways and burner for cleanliness.
cleaning is required, use the following procedure.
a) Turn off all electrical power to the boiler.

If

b) Remove Jacket Middle Front Panel and Jacket
Top Panels. Remove Front Cleanout Plate and
Cleanout Cover Plates on each flueway. On LCE
boilers, remove the top flue outlet plate and vent
piping as necessary to access the top of the
sections.

e) Brush the boiler tube spaces both horizontally
(through cleanout openings on ends) and
vertically (from top of boiler through cleanout
openings at flueways).

41

d_ Remove the Burner and Burner Mounting Plate.
Remove any scale or soot from the combustion
chamber by means of vacuum cleaning or other
available means. Take care not to damage the
chamber floor liner or target wall liner.

!::lq I e7,_11k"m LvjF±I I L_/ | _ L__:1 _ [o4

i.

Inspect the boiler area to make sure the area is free
from combustible or flammable materials and that
there are not obstructions to the flow of air to the
boiler or combustion air openings to the room.

2.

Make sure there are no signs of abnormal
such as overfilling or leakage.

e) Replace the Front Cleanout Plate, Burner
Mounting Plate, Burner and all Cleanout Cover
Plates on top of the sections. Make sure all
sealing rope and seals are in good condition.
Replace sealing rope if necessary.
f)

Replace all Jacket

Panels.

5.

Inspect the boiler and piping for signs of leaks.
Check to see if there are signs of heavy make-up
water addition to the system.

Be very careful when adding water to a hot boiler,
Add very slowly or, if possible, allow the boiler to
cool naturally before adding water.

6.

When placing boiler into operation, follow Burner
Manual, all instructions supplied with the boiler and
the instructions in this chapter.

If an excessive loss of water occurs, check for a leak
in the piping and correct the problem. Excessive
make-up water will cause corrosion and damage to
the boiler.

7.

Test the operation of all limit controls, float controls
and ignition components as described in Part A,
"Placing Boiler in Operation", of this chapter.

!e]q hVj[o]L_||'lk'd

42

operation,

ILVJF_,Ih_i|_L1F_,IL_[a4

1.

Inspect the burner and pilot flames as for the annual
inspection.

2.

Inspect the boiler and system for any signs of
leakage or excessive make-up water usage.

3.

Inspect and check the operation
system.

of the venting

Table

16:

Series

LC/LCE Boiler

Ratings
-'1_ :11_.'II I(l_J Kil =1 :(011i 1 :tl :q:_ | I_[€_

Gross

l B

Boiler
Model
Number

I=B=R
Output
Mbh

LC-04

547

LC-O5R
LC=05

649
707

LC-06
LC-07

868
1029

LC-08

1189

LC-09

1350

i 4o:3

LC-10

1511

;

LC-11

R Burner Capacity

I B

R Net Ratings

Combustion

Efficiency

Boiler
H.P

Oil
GPH

Gas
MBH

Steam
Sq. Ft

Steam
MBH

Water
MBH

Oil

Gas

16.3
19.4

475

686

1708

410

476

837

81.2

560

808

2029

487

564

83.7

81.2

21.1

6.10

881

2208

530

615

83.7

81.2

25_9

7.50

1077

2713

651

755

83.7

81.1

30.7
35.5

8.80

1273

3217

772

895

83.6

81.1

1020

1469

3717

892

1034

83.6

811

II.60

1664

4250

1020

1174

83.6

81.1

45.1

12.80

1860

4804

1153

1314

83.6

81.1

1672

49.9

14.20

2056

5367

1288

1454

83.6

811

LCd2

1832

54.7

15.60

2252

5917

1420

1593

83.6

811

LCE 13

1966

LCE-14

2125

1700
18.40

2464
2657

6358
6875

1526
1650

1710
1848

83.5
83.5

81.0
81.0

t

i

:

58.7

LCE-15

2284

63,5
68.2

19.80

2850

7388

1773

1986

83.5

81.0

LCE-16

2444

73.0

21.00

3043

7908

1898

2125

83.5

810

LCE 17

2603

77.8

22.50

3236

8421

2021

2263

83.5

81.0

LCE-18

2763

82.5

24.00

3429

8938

2145

2403

83.5

810

LCE-19

2922

87.3

25.00

3622

9454

2269

2541

83.5

81.0

LCE-20

3082

92.1

26.50

3815

9971

2393

2680

83.5

81 0

LCE 21

3256

97.3

LCE-22

3430

4027
4239

10533
11096

2528
2663

2831
2983

836
83.6

81.1
811

LCE-23

3604

1025
107.7

2800
29.50
31.00

4451

11658

2798

3134

83.7

812

LCE 24

3777

112.8

32.50

4663

12217

2932

3284

83.7

812

I Burner input based on No 2 fuel oil with a heating
2 Net I=B-R

water ratings based

3 Net I-B-R
steam ratings based
LCE-13 to LCE-24-1 288.

value of 140,000
of 1.15.

on an allowance

for LC-04 to LC-08=

4 Consult factory before selecting a boiler for installations
systems,etc.
5 Combustion

efficiency

Blu per gallon.

on an allowance

determined

in accordance

1.333, LC-09=1.323,

LC-10=I.310,

having unusual piping and pickup requirements,

with The Hydronics

Instgute's

LC 11-1.298,

such as intermitient

Testing and Rating Standard

for Heating

6O

5O

LC-12-1

290,

system operation,

extensive

piping

Boilers

/
i..

.

J

I
Q..

4O

o
a 30
==

/

/

10

//

//
I

2

6

8

10

12

14

16

18

2O

Coil Flow Rate, GPM

Figure

37: Tankless

Coil Pressure

Drops

43

-IT[,]IIII ::1;] IT_'__
dT_[_._ [_ t_bSl :l_-_]J[O]_
_-_]
Flue
Connection

(_)

4" Supply

(_)

3" Rear

Tappings
Return

(_

3"

Tapping
Intermediate

(_)

3"

(_

Rear

Observation

Tap,

when

Supply

Side

Return,

when

required

Port

required

TOP

®

Maximum
Burner

PowerFlame:
Gordon-piat_:

Length

C = 36"
$4 = 32"

J
R

= 29 =
= 37 _

Webster:
Becket t = J26"= 31"
Cartin
= 26"
Z = t 1f_ excep_whe,e e_eqd=d plate _d
Z
E_end_Flate J_S6 i_ Se_Burne[info_ationmMan_al

t

C

FRONT

Figure

RIGHT SIDE

38: Series LC Dimensional
(_

4" Supply

(_)

3" Rear Return Tapping

(_

3" Side Return Tapping(s)

(_

Rear Observation

(_

REAR

Diagram

Tappings

3" Intermediate

Maximum Burner Length

F

Beckett = 26"
Carlin = 26"

Port
Supply

•

•

Tappings

PowerFlame:

C = 36"

Gordon-Piatt:

R - 37"

Webster:

J = 31"

TOP

G

C

Line

B
FRONT

Figure

44

39:

Series

LCE

RIGHT SIDE
Dimensional

Diagram

REAR

J = 29"

Table 17:

Series

LC/LCE Boiler Dimensions
1-1iI I ,,t-i ,_-TI,%wlI *|',| l ¶ ? t| -d•u , -'*"." LO]_h"
I

Jacket
Boiler
Model
Number

Width
",K'

LC-04

37"

LC-05R

Supply

i Length
i

Height
"C"

"B"

I
'251_d

37"

'

1

31"

63"

2
2

LC-05

37"

31"

63"

LC-06

37"

36¼g'

63"

2

LC-07

37"

41½"

63"

2

LC-08

37"

46%d"

63"
63"

37"

51%"

37"

56%d"

63"

2

37"

61½"

63"

2,1

l
T

LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE18LCE-19
LCE 20
LCE-21
LCE-23
LCE-24

37"
37"
37"
37"
37"
37"
37"_
37"

66_0"
_71¾"
_61_6"
T 81%"
L
i 861%6"
! 92½"
97¾d'
' 102¼ _

3T_107Vm"
37"
37"
37"

_
I 122%' _,_
!127_¼_"

*Dimensions
areapproximate

63 _
63"
63"

:
!

63"
63"

63"
63"
63"
63"

3"
i

_

4"
4"
4"
i

2,2

_

2,4
2,4
2,4
2,4
2,4

i

i
T

,

4",3"
4",3"
4",3"
4",3"
4",3"

4",3"
4",3"
4",3"
4",3"
4",3"

s"
5"
5"
6"
6"
6"
6"

, Riser Tapping

End
Sect. I_
Tappings

_

i

I

Locations*

Intermediate

,t

) 21'/1."

]
I_
i
[

i

2"
2½"
2½"
2½"

i

26%"

6"

i
_
i

3"
3"
3"
3"

57%"
62aAa"
I 67¼"
, 72:A_:', _
I 77V,#

!

-

_
_

_

,

_

-

Z

!

=

7
-

-

36V_d'
2015A6 "

26"
26"

] 205A6"

ii 2o_/,o",
25¼g ' _

4"

82½

20 5/16 i 20_Ad ' i

8"
8"

4"
4"

87%0"
92%"

20_Y,o" I 2_Ad' _ 20_Ad" "
20 ¼_•;'
20_Ad ' ] 25Vld'

8"
8"
8"
8"
8"

4"
4"
4"
4"
4"

97:k7'
102:V./'
107%"
112_%."
118¼#

2@_A_('
20'V_d'
20'aA/'
26"
26"

1 18_'_" i

=

I !8'/_"

-

18t/2
,

_
-

q
]
I

18W'
18½"
18W"
18½"

:

181/2,,

20_A6"
20V_d'
20SAd'
20rV_"
20%_"

v
-

20"%_"
20 _/,_"
20V.('
20.%J

18½"
18½"
18½"

Minimum
Height

9,,

31

9.

3,

_812o" p4v_"

9"

3'

18/4
l

10"

3'

10"

3'

!

_8¼"

E"
54w'
54%"
54/81-

181/,*"
18¼"
18¼"
18¼"
18¼"

54V/'
541//'
541/d '
54_"
54_"

10"

3'

12"

3'

12"

3'

12"

3'

18¼"
16"

54¼"
20½"

12"

3'

14"
14"

3'
3'

16" i 20½"
16"

_ 20½"

14"

3'

16"
16"

20½"
20½"

14"

3'

14"

3'

16"

20½"

16"

3,

-

18½"

16"

20V_"

16"

3'

15¼"

18///'

16"

201/z"

16"

3'

15¼"
20 sad'

18½"

16"

20Vz"

16"

3'

181/2 "

16"

20V/'

16"

3'

20_7_d'
26"

18'//'

16"

20V/'

16"

3'

18½"

16"

20½"

16"

3'

-

15¼"

15W'

.
,

Vent
Diameter
'rF'

"D....
18¼"

i

8"
"

_

26"
26"

Location

Burner
Center

G3" i "G4" Line
t
i 18½"

-

7

-

i 31hAd'
! 36'Ym"
41%"

2%,
46_V,d '
/ 3" (2 R_t) I
52"
[ 3" 12net.)

7

Vent

Section Tapping

i

2" ] t! °/1¢'

6"

8"
8"
8"

4",3"

4",3"
4",3"

.

_ _2'_

4"
4",3"

i

2,3
23

Lp iping

t,

3" T
4"

2,1
2,1
_

2,2
2,3

63 H

63"
63"

,t

2

LC-IO

_

Size HeaderEqualizer"0" l "Gr' I "02....
4 / 4
2
16_ + -

2

LC-09
LC-I1

tan

i

Return
Recom.

'
: Risers

63"

Piping

18½"
18½"
181/2"
18½"

'7

o
..

0_

_o_
_-_

'-_

_._.
o-

g

3

.

0

.

g

_

0

25

I
_3i

.

_.-©
21

o

o

z

_

__

_

_5'

ca- r
8

.f

_.('3

L_:I;/-_ If] i_-,_'ii-"]Table

18A:Series

LC Repair

I

Front Section

2

Intermediate Section

3

Intermediate Section

4

Back Section

5

Tapped

Parts

See Table 3 for Stock Code

Intermediate

w/1 '_Tapping

Section

i

' Upper Flow Port Gasket
Lower Flow Port Gasket

2 Required

per Flueway

51671

I Required

per Flueway

51672

4 Required

per Flueway

51721

I

6

[ Tie Rod
I 5/8" Diameter High Temp Rope

13 Feet Required

[ Ceramic

Models LC-04 through

t

i

8

: Ceramic

_ 9

Fiber Base Liner
.

55723

per Flueway

50862

LC-12

.

50854

Fiber Target Wall

51162

I Front € eanou! P!a!e !c.I.

I0

] 5/16" 18 x 11/4"Studs w/Brass Nuts

11

I Steel Cover Plate

12

4 Required
51776

Steel Cover Plate

51777

I

13

I Tankless Heater

Location

I

Specif_ Heater Model Number

16

Rubber Gasket

Specify Quantity

17

3/8"-16 x 3/4" SS Hex Head Cap Screw

Specify Quantity

18

Rear Observation

19

5/16" 18 x 3/41' Hex Head Cap Screw

51800

90923

Assembly
Specify Quantity
Specdy Burner Model

20

I Burner Mounting

21

: 3/8"-16 x 21/4.' Studs with Nuts

Plate

22

i Flame Observation

7 R_'guirQd
90922

Assembly

±

23
24

3 8 -16 x I Studs for Burner Mounting
[ I/4'-20

4 Required

x I/2" Hex Head Machine Screw

4 Required

I

25

I Cleanout

Cover Plate (Steel)

I Required

per Flueway

51772

J

26

0

t

Models LC-06

Rear Flue Box w/12" Flue Outlet
27

, Rear Flue Box Stud 5/16"-18

28
29

Models LC-09. LC-10

x 11/2''

Rear Flue Box Hi Temp Rope, I/4" Diameter

LC-07 and LC-08
LC-II

86041

and LC-12

86042

7 Required
x 65" Long

Side Jacket Panel LC 6000

For Models LC-04 and LC-08

Side Jacket Panel LC-6001

For Models LC-05

Side Jacket Panel LC-6002

For Models LC-06, LC-10. LC-II

Side Jacket Panel LC-6003

For Models LC 07 and LC 12

+

LC-08. LC-09 and LC-10
and LC 12

F

30

[ Left Front Jacket Corner

Panel LC-6011

i

_

Right Front Jacket Corner Panel LC-6010

_2_Upper

Front Jacket Pane! LC-6007

33

! Middle Front Jacket Panel LC-6008

34

i Lower Front Jacket Rail LC 6009
)

35

! Back Jacket Panel LC-6012

36

Side Jacket Panel Support

37

Front Top Jacket Panel LC-6005

Angle LC-6014

47

I;1=]_'-_I.qI ",7_'_
;tl_'_
Table

18B: Series LC Repair

38

Top Jacket Panel LC 6004
Top Jacket

39

48

Panel LC6004

Parts (continued)

For Models LC-04 and LC 08
1

For Modds LC 05. LC 08, LC-09 and LC 10

Top Jacket Panel LC 6004 2

For Models LC-06, LC 10. LC 11 and LC-12

Top Jacket Panel LC-6004-3

For Models LC-07 and LC-12

Rear Top Jacket Panel LC-6006
Single Rib Flue Baffle, Aluminized Steel LC-I018

Specify Boiler Model Number

Triple Rib Flue Baffle, Aluminized Steel LC-I019

Specify Boiler Model Number

Single Rib Flue Baffle, Stainless Steel LC 1020

Specify Boiler Model Number

Triple Rib Flue Baffle, Stainless

Specify Boiler Model Number

Steel LC 1021

t_
II
I-'

Im
O I

l'l
,,.i

m

3
_3t

30
/

4_
_.0

Table

19A:Series

LCE Repair

Parts

See Table 3 for Stock Code

Front Section
2

4

Top Flue Outl#t
intermediate

Sechon

[ntermedlate

Section

Back Sertlon

6

Tapped

_/Tankless

Intermediate

Tapping

Cod Opening

Section

Upper Flow Port Gasket

2 Required per Flueway

51671

Lower Flow Port Gasket

i Required per Flueway

51672

Tie Rod

4 Required per Flueway

51721

13 Feet Required

55723

5/8" Diameter

High Temp Rope

7

Ceramic

Fiber Base Liner

8

Ceramic

Fiber Target Wall

per Flueway

For All LCE Boilers

50862
50854

9

Fiont Cleanout

I0

5/161'-18 x ii/4 Studs w Brass Nuts

11

Steel Cover Plate

12

Steel Cover Plate

13

Tankless Heater Location

I

Specify Heater Model Number

15

Tankless Heater Location

3

Specify Heater Model Number

Plate (C.I,

51162
4 Required
51776
L

16

Rubber Gaskel

Specify Quantity

17

3 8'-16 x 3,4' SS Hex Head Cap Screw

Specify Quantity

18

Rein Obs_rvatlon

]9

5116

18 x 34'

Assembly
Hex Head

90923
Ca]; Screw

Specdy Quantity

Burn_1 Mounting

21

3/8"-16 x 21/4'' Studs with Nuts

22

Front Observation

23

3/8"-16 x I' Studs for Burner Mounting

4 Required

24

1/4"-20 x I/2' Hex Head Machine Screw

4 Required

25

Cleanout

I Required

26

Rear Flue Cover Plate

For All LCE Boilers

27

Real Flue Covel Stud 5 16"-18 x lY2'

5 Required

28

Rear F _e Cover Hi Temp Rope. I 4" Dia. x 65" Long

29

Side Jacket

Panel LC-6000

For Models LCE-13

Bide Jacket

Panel LC-6001

For Models LCE-13 to LCE-15. LCE-17 to LCE-24

Side Jacket

Panel LC-6002

For All LCE Boilers

Plate

Specify Burner Model
7 Required

Assembly

Cover Plate

51777

51800

20

Steell

30

Left Front Jacket Corner Panel LC 6011

31

Right Front Jacket Corner Panel LC-601O

32

Upper Front Jacket Panel LC-6007

33

Middle Front Jacket Panel LC 6008

34

5O

w/1

S_'ctlon

Closed Back

Back Section
5

Inteml#dlat¢,

90922

per Flueway

51772
51131

-17. 20 & -21

I
1__

. Lower Front Jacket Rail LC-6009

35

Rack Jacket Panel LC-6012

36

Side Jacket Panel Support

37

Front Tol: Jacket

38

ToI_ Jacket Panel LC-6004

For Models LCE-12

Top Jacket Panel LC-6004-I

For Models LCE-13 to LCE-15, LCE-17 to LCE-24

Angle LC-6014

Panel LC-6005
-17. -20 & -21

Table

19B:

Series

LCE

Repair

Parts

(continued)

For Models LCE-15, -16, -19, 23 & 24

38

Top Jacket

Panel LC-6004-2

40

Top ,Jacket Panel with Flue Opening

39

Rear Top Jacket Panel LC-6006

41

Top Flue Outlet Plate (14" Flue)

For Models LCE-13 through

Top Flue Outlet Plate (16" Flue)

For Models LCE 18 and Larger

51133

For Top Flue Outlet Plate, 6 Feet

55723

Rope

For All LCE Boilers

LCE-17

51132

42

5/8" Diameter

43

3/81' Diameter Tie Down Assembly

For Top Flue Outlet Plate, 4 Required

51604

44

Draft Damper,

14"

For Models LCE-13 through

90523

Draft Damper,

16"

For Models LCE-18 and Larger

90524

Models LCE-21 through

86113

Baffles

High T_,mperature

LC-6022

LCE 17

LCE-24 Only

51

Series

LC/LCE

Oil,

Gas/Oil
Steam

Gas

Boilers

Installation,
Operation
Maintenance
Manual
TO THE

INSTALLER:

This manua/ is the property
of the owner and must
be affixed
near the boifer for future reference,
TO THE

OWNER:

This

boiler

should

Quafiffed

Service

member
HI Division

be

inspected

annuafly

by

a

Agency.

gama

ASME

of gama

PEERLESS
CAST

PEERLESS

IRON

°

BOILERS

HEATER

COMPANY

231 NORTH WALNUT STREET • BOYERTOWN, PA 19512-1021 • PHONE 610 367 2153
www, peerless-heater.oom
THE

@2002

Peerless

Heater

Company

PREFERRED

HEATING

CHOICE

LC8046 R1 (12/02-1M)
Printed in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 61
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Tue Apr 03 15:23:13 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu