PEERLESS Boiler Manual L0308199
User Manual: PEERLESS PEERLESS Boiler Manual PEERLESS Boiler Owner's Manual, PEERLESS Boiler installation guides
Open the PDF directly: View PDF
.
Page Count: 61
| Download | |
| Open PDF In Browser | View PDF |
LC/LCE
Gas/Off
Boilers
- Steam
Installation,
Operation
Maintenance
Manual
PEERLESS
CAST IRON BOILERS
°
22
Sizes
4-24
Forced
Draft
• Only
Sections
a Three
Efficiency
• Choice
Cast
• Adds
Rear
Iron
Outlet
on
Flue
• Includes
Locking
Damper
Base
Safety
Up to
Power
Operating
LC,
Top
Section
Design
with
Heating
Surface
Flame
or Webster
Outlet
on
for Increased
Tubular
LCE
Efficiency
Heat
for Optimum
Exchanger
Heat
Transfer
Type
Low
Water
Cut OffAvailable
Coils
• For Domestic
Unique
Hot Water
Flex-Seal
• Injection
Molded
• Assures
a Water
Individual
Insulated
Port
for Superior
Tight
on Hot Water
Gaskets
Performance
Seal
Boilers
Between
and
Flexibility
Sections
Rods
of Assembly
Enameled
• Reduces
Production
Flow
Draw
• For Ease
Bo_er
Heat
Steel
Jacket
Loss
• Honeywell
• Manual
• LWCO
still
Efficiency
Noise
Flue
Gas Travel
Additional
or Float
Tankless
lTlul'ci¢l{
Combustion
Controls
• Probe
Peerless
cast
i1oll
83.7%
Collector
Reduces
Optimum
• Provides
Input
the Roof
Gordon-Piatt,
Flue
and
• Provides
Wet
GPH
Burners
Carlin,
Durability
Flue
Foot Vent Above
Power
ofBeckett,
Integral
to 32.5
Venting
Requires
High
4.75
Boilers
boil_'rs
]tol
Pt'erlt,ss
It!¢ll_'l
is pleased
to qlTer
irlclude
a filll,
one
CJlICI sleanl
[Joilera.lot
complete
one
year
boilers.
of
the most
it_atTatlty.
Fivt_
tv(trratlly
Peerless
(lll(_
lell
comptz,h_,nsive
A limitt_¢t,
tell
year
¢'.k'I¢'llc'l¢!¢l
Operating
Reset
High
on Packaged
• Tankless
Coils
• Various
Burner
• FM and
IRI Control
wantruly
programs
year
tt!Cllwa_ll[j
Oil lilt;
it;(lrl(ltl{i¢'s
Controls
Limit Control
Boilers
Opliol_s
and
Voltages
Syslems
irl the indttstl
y. All Peerless
commercial
¢'(ISl ir_)tl ._('cIioIIs
is provided.lbr
(111 col_l
Oil 11(111.% (llld
!¢llx)l
¢1r€" iiott_
available,.
/)l¢'(lst'
¢'¢._tt
it{lbrmaliotl,
Boilers
• 610-367-2153
* www.peerless-heater.com
FA6 LC R3 i3031MI
Pr_n_o_J irl U S A
Series
pr=-r=-RLESS o
Large Commercial
•
CAST
LC/LCE
Boilers
Packaged, Assembled Block or
Individual Sections
o Forced Draft Venting
Power Burners
IRON BOILERS
•
Oil, Gas, Gas/Oil
Q Steam or Hot Water Boilers
Optional
Tankless Coils
Series LC
Series LCE
Net I=B=R
....
Ratings 4
Efficiency
5
Oil
Model
Output
Boiler
Oil Input
Number
LC-O4
MBH
547
H,P.
16.3
GPH 1
4.75
Gas
Input
MBH
686
l Steam
Sq. Ft.
1,708
Steam3
Water 2
MBH
410
MBH
476
,0.05,_,9 19.4 5.60 80_ 2.029,7
Comb.
%
83.7
Water
Gas
Therm.
%
82.2
Comb.
Therm.
%
81.2
%
79.8
I
Content
Steam
40.57
I
Water
50,65
m
mm
56, _.7 62.561.290._ 47.29 69.0,
m
LC-05
707
21.1
6.10
881
2,208
530
615
83.7
82.8
81.2
803
47.29
59.05
II
LC-06
866
25.9
7.59
1,077
2,713
651
755
83.7
83,1
81,1
80.8
54.01
67.45
I
LC-07
1029
30.7
8.80
1,273
3,217
772
895
83.6
83.3
61.1
806
60.79
75.55
I
LC-08
1189
35.5
10.20
1,469
3,717
892
1,034
83.6
835
61.1
81.0
67.46
84.25
I
LC-09
1350
40.3
11.60
1,864
4,250
1,020
1,174
83,6
83.6
811
81.1
74.17
91.65
I
LC-10
1511
45.1
12.80
1,860
4,804
1,153
1,314
83.6
83.7
81.1
81.2
80.88
101,05
I
LC-11
1872
48.9
14.26
2,056
5,367
1,288
1,454
63.6
83.8
811
81.3
87,61
109,45
I
LC-12
1832
54,7
15.60
2,252
5,917
1,420
1,593
83.6
83.9
811
814
94.33
117,65
I
LCE-13
1966
58.7
17,00
2,464
6,358
1,526
1,710
83,5
822
61.0
79,8
101.05
126,25
I
LCE-14
2128
83.5
18.40
2,657
6,875
1,650
1,848
83.5
625
810
80.0
107.77
134,65
•
LCE-15
2284
66,2
19.80
2,850
7,388
1,773
1,986
83.5
826
510
80.2
114.49
143,05
I
LCE-16
2444
73,0
21.00
3,043
7,908
1,896
2,125
83.5
82.8
610
80.3
121.21
151.45
I
LCE-17
2603
77.8
22.50
3,236
8,421
2,021
2,283
83.5
629
81.0
80.4
t 27.93
15985
I
LCE-18
2763
82.5
24.00
3,429
6,938
2,145
2,403
83.5
83.1
810
80.6
134.65
168.25
I
LCE-19
2922
87.3
2500
3,622
9,454
2,289
2,541
83,5
83.2
81.0
80.7
141.37
176.65
I
LCE-80
3082
92.1
2650
3,815
9,971
2,393
2,680
83.5
833
810
806
148,09
18505
I
LCE-21
3256
97.3
2800
4,027
10,533
2,528
2,831
83.6
63 3
81 1
809
15481
19345
I
LCE-22
3430
102.5
29.80
4,239
11,096
2,663
2,983
83.6
834
8t 1
808
161.53
20185
•
LCE-23
3604
107.7
31.00
4,451
11,658
2,798
3,134
83.7
835
812
81.0
168.25
210.25
•
LCE-24
3777
1128
32,50
4,663
12,217
2,932
3,284
83.7
835
812
81.0
174.97
218.65
I
1
2
3
4
5
Burner input based on No. 2 fuel oit with a beating value of 140,000 Btu per garlon
Net I_B-R water ratings based on allowance of 1.15.
Net I=B-R steam ratings based on an allowance for LC-04 to LC-05 1.333, LC-09 1.323, LC-10-1.310, LC-11=1.298, LC-12 1.290, LCE-13 to LCE-24=1.288.
Consult factory before selecting a boiler for installation having unusual piping and pickup requirements, such as intermitlent system operation, extensive piping systems, etc
Combustion and thermal efficiency determined in accordance with The Hydronics Institute's Testing and Rating Standard for Heating Boilers
SERIES LC SPECIFICATIONS
F_[o]llll=l_ I_]]_r_l_J_.-][o_[,."]F_1Lqi]
If.'1_
Jacket
][e[_
_[,,.'!1
Boiler
Model
Number
Width
"A"
Length
"B"
Top to Floor
Left of
Jacket to
C/L of
Flue
LC-04
37"
25_%#'
63"
18W'
54W'
9"
LC-05R
37"
31"
63"
181/4 "
54W'
9"
21_A#'
LC-05
37"
31"
63"
18V4"
54W'
9"
219/_6"
LC-06
37"
36¼s"
63"
18_ ,,
541/8 `'
10"
265/8"
LC-07
37"
41W'
63"
18V4"
54W'
10"
31"/_e"
LC-08
37"
46%6"
63"
18V4"
54W'
10"
36_3/_#'
15_¾6"
LC-09
37"
513/."
63"
181/4"
541/8 ''
12"
417/_"
20_%6"
LC-10
37"
56%#'
63"
18V4"
54W'
12"
46_5/_e
"
20_¾8"
LC-11
37"
61½"
63"
18W'
54W'
12"
52"
26"
LC-12
37"
66%s"
63"
18_A,,
54W'
12"
57W'
26"
Distance Between Tappings*
Floor to
C/L of
Flue
"E"
Flue
Size
"F"
liG_l
"GI"
16_/_"
Apply Prefix "O" for oil--"G" for gas--"GO"
for gas-oil
* Dimensions are approximate
The manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation,
extensive piping, etc. For forced hot water heating systems where the boiler and all the piping are within the area to be heated, the boiler may be selected on the
basis of its Gross Output.
SERIES LC/LCE SPECIFICATIONS
STEAM
PIPING
Pipe the return line to a Hartford Loop, with the return nipple located from 2 to 4 inches below the normal water line.
Model
Number
Riser
Minimum
Header
Size
Equalizer
Model
Number
Riser
Minimum
Header
Size
Equalizer
LC-04
14"
4"
2"
LCE-13
2_4",
1_3"
6"
3"
LC-O5R
2--3"
5"
2"
LCE-14
2_",
2--3"
8"
3"
LCE-15
2_4",
2--3"
8"
3 '=
LCE-16
2---4", 2--3"
8"
3"
LCE-17
24",
_"
8"
4"
LCE-18
2_",
3_3"
8"
4"
LCE-19
24",
3--3"
6"
4"
LC-05
2--3"
5"
2"
LC-06
24"
5"
2"
LC-07
24"
5"
21/2"
LC-08
24"
6"
21/2"
LC-09
24"
6"
21/2'
LCE-20
24",
4_3"
8"
4"
LC-IO
24"
6"
21/2"
LCE-21
24",
4---3"
8"
4"
LC- 11
24"
1--3"
6"
3"
LCE-22
2_4",
4---3"
8"
4"
LCE-23
24",
4--3"
6"
4"
LC-12
2_"
6.
3.
6"
14"
4"
WATER
Model
Number
Supply
Return
Minimum
Header
Size
LC-64, 85R, 65
1--2W'
1--2Vz"
21/2,,
LC-06 and LC-07
1--3"
1--3"
3"
LC-68 and LC-09
2--3"
2--3"
3"
LCqO thru LCE-16
2--4"
2--3"
4"
LCE-17 thru LCE*20
2_"
2--3"
6"
LCE-21 thru LCE*24
24"
3-3"
5"
PIPING
Size the supply and return headers to meet the system flow requirement.
SERIES LC/LCE SPECIFICATIONS
Large, Integral
Cast Iron Flue Collector
Unique Flex-Seal Gaskets
--
Tubular Heat Exchanger
--
Large Combustion Chamber
613/4"
Individual Draw Rods
--
--_
345,46,,
_
HEATER
LOCATION
#1
HEATER
LOCATION
#2
_:m
- _
E
_i
Series LCE Includes
LOCATION
Cast lron Rear Cover Plate
FRONT
I
Heater No.
X-1020
Boiler
Number
Model
LC-04
LC-O5R
LC-05
LC-06
LC-07
LC-08
LC-09
LC-10
LC-11
LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24
Heater No.
X-1021
Location**
GPM
Stea
5.5
5.62
5.75
6.25
6.5
7.0
7.25
7.5
8.0
1
t
1
1
1
1
1
1
1
mT
water
2
2
2
2
2
2
2
2
2
Heater No.
X-1022
Location**
GPM
SteamlWater
Two Heaters
No. Xo1020
Location**
GPM
Steam Water
Two Heaters
No. X-1021
Location**
GPM
8.0
6.5
7.0
7.75
8.5
1
1
1
1
2
2
2
2
13.0
1
2
9.25
10.0
10.75
11.56
12.25
13,00
13.00
13.00
13.00
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
13.75
14.5
15.5
16.5
17.5
18.0
18.75
19.5
20.0
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
13.00
13.00
13.00
13.00
1
1
1
1
2
2
2
2
20.0
20,0
20.0
20.0
20.0
1
1
1
1
22
2
2
2
.....
.....
.....
13.00
13.00
1
1
2
2
20.0
20.0
1
I
2
2
--
13.00
1
2
20.0
1
2
Steam Water
-1 &2
Two Heaters
No. X-1022
Location**
Location**
GPM ,Steam
Water
GPM
Steam Wate!
9.0
10.0
12.0
13.0
-----
1& 2
1&2
1&2
1&2
9,5
10.5
13.0
15.5
-----
1&2
1&2
1&2
1&2
15.5
--
14.0
14.5
15,9
16.0
.....
-1&3
1&3
1&3
1 &2
1&2
1&2
1&2
17.5
20.0
21.5
23.5
24.5
26,0
26.0
26.0
26.0
--1&3
1&3
1&3
1&3
1&3
1&3
1&3
1& 2
1&2
1&2
1&2
1&2
1&2
1&2
1&2
1&2
18.0
20.0
22.5
24.5
27.0
29.0
31.5
33.5
35.5
-------1&3
1&3
1 &2
1&2
1&2
1&2
1&2
1&2
1&2
1&2
1&2
__
--
26.0
26.0
26.0
26.0
1&3
1&3
1&3
1&3
1&2
1&2
1&2
1&2
37.5
39.8
40.0
40.0
40.0
1&3
1&3
1&3
1&3
1&2
1&2
1&2
1&2
26.0 11&3
i
26.0 11&3
26.0 I 1&3
1&2
1&2
40.0
40:0
40.0
1&3
1&3
1&3
1&2
1&2
1&2
.....
.....
-
IZI
,
I
--
'
--
" Water heater rahngs are based on intermittent deman_O
° P to 140 ° F Rise with 200 ° F boiler water
** Water beater locations may be found on the drawing above.
When two (2) tankless water heaters are used in a steam boiler, a special rear section is furnished at no extra charg_when
Caution: Water mixing valve should always be installed in the hot water supply to prevent injury.
1 & 2
ordered with boiler,
1&2
SERIES LCE SPECIFICATIONS
\
Rear Flue
Cover
R
E
A
R
Cast Iron Block Assembly-Top
Butterfly Flue Damper (Series LCE)
Mounted Horizontally or Vertically
Flue Outlet
4_/,_
" • .*
G
_l_
]-
_
4,_,_¢
:
16'_1(_
f_
O"
I
F
R
R
E
< o
A
N
R
_:
T
_I
1:,.',_'_€,.][9_,'_€"1:=1,_]
i:{*]llq_:
2.
Remove lifting frame and hardware.
1.
3.
Proceed to Section D: Install Coils or PLates
Remove crate top and sides. Remove any loose
cartons. Remove burner support pedestal and
nipple, if supplied.
2.
Lift boiler off crate pallet. Move to location
determined in Chapter I: Preinstallation.
3.
Remove lifting frame and hardware.
4.
Re-install burner support
[,.)q 114i_[.I1,,][4mlmlh_lk'_l
i=(,,]l!_:
].
2.
3.
Place the Back Section on the floor as shown in
Figure 7.
Proceed to Chapter 3: Piping the Boiler.
4.
I:_N V;l.$'I_vJI:]l_.)
i.
Open the Section Assembly Kit cartons. These
cartons contain the parts needed for assembly of the
sections.
pedestal and nipple if
necessary.
5.
Place channel rails as shown in Figure 4.
:]I[.lN[4I:{o]II::i-"
Move block to location determined
Preinstallation.
in Chapter
I:
The Back Section combustion chamber area is lined
with a ceramic fiber blanket liner. Make sure the liner
is in good condition. Minor tears are not a problem,
but there should be no holes in the insulation.
Lay sections
on
floor
as SohOw
with
maChined
groove
Figure 7:
12
Lay Sections
on Floor and Apply
Rope Seal and Gaskets
side
up.
i
Flat'_
Machined
o?:eo
Ji
Recess
Machined
Face
The sections are heavy and must be supported
securely.
I0. Lift up the Rear Section and move into position
the steel channels on the boiler foundation.
on
11. Screw a 3" pipe at least 30 inches long into the
lower 3" tapping on the back of the Rear Section as
shown in Figure I0. Place a block under the pipe as
shown in the figure and use as a brace during
assembly.
i.°°°2°
Flow Port
Gasket
12. Place a Plain Intermediate Section on the floor and
prepare as above.
13. Carefully place the Intermediate Section against the
Rear Section and visually line up the flow ports as
closely as possible.
14. Insert a tie rod with one nut and washer applied into
each of the four tie rod lugs. See Figures 5 and 6.
15. Place the nut and washer on the other end of the tie
rod and draw finger light.
\
\
\.
Figure 8:
Flow Port
Machining
b Gasket
Gaskets will be damaged by petroleum or its
derivatives. Completely remove all solvent residue
before placing gaskets.
Do not use petroleum based compounds
boiler.
5.
6.
in the
Clean the area around the flow ports and in the seal
recess. Use solvent and a clean cloth to thoroughly
clean all of the sealing surfaces. Remove all foreign
matter to assure a water fight seal when the sections
are drawn together.
Place a Flow Port Gasket in each of the three flow
port recesses as shown in Figures 7 and 8.
7. Apply rope adhesive in the rope groove around the
perimeter of the section.
chined
silicone
8. Place the sealing rope completely around the rope
groove, being careful not to stTetch the rope. Extend
the rope from 1/4" to 1/2" past the end of the groove
on both sides of the cleanout opening on top of the
section. This will assure a gas tight seal when the
cleanout cover plate is applied.
9,
groove.
about
ide of
Do not get sealant
"face of gasket.
Apply a bead of silicone sealant around each flow
port as shown in Figure 9. Do not get sealant on the
flow port gaskets.
Figure 9:
Apply
Silcone
Sealant
13
SECTIONS ARE TOP HEAVY.
HANDLE WITH CARE TO
AVOID
TIPPING
OR FALLING.
Intermediate
tion
Level Each Section:
Place the first intermediate
section next to the rear section
as shown. Use a spirit level to
make sure the sections are
Spirit
.=vel
plumb. Check the level as each
additional intermediate section
is added.
Rear
Section
Temporary Support Pipe
Screw a 3" pipe at least 30 inches
long into the lower (return) tapping
in the rear section.
Support
Figure
14
10: Install
Block
Additional
Sections.
Use level on each section
as tie rod bolts are drawn
up.
I "]av_..]_ ii'l_
16. To propedy assemble LC/LCE sections in the field.
the following steps must be followed to ensure that
no damage occurs to the tie rod lugs. A 0-I00 ftdbs
torque wrench is required•
a, Use a spirit level as shown in Figure I0 to check
the alignment of the sections as the nuts are
drawn up Keep the sections plumb•
b.
17 Repeat with the remaining sections.
a. Save the LWCO Intermediate with two I"
tappings (for level control) for use as the section
closest to the front section.
b.
Draw the sections together evenly, in three
rotations. Torque each port to 20 ft-lbs for the
first rotation, then to 40 ftdbs for the second
rotation, then to 60 ft-lbs for the third rotation
Use the following sequence until all three ports
touch metal-to-metal at 60 ft-lbs. See Figure 11
for port reference
i)
Place the Intermediate Section with 3" top
tapping (Tapped Intermediate) in the position
given in Figure 13
LCE ONLY. Save the (3) Top Flue Outlet
Intermediates (with wide opening in top of the
flue collector) for use as the sections closest to
the LWCO Intermediate Section• See Figure 13.
C,
The sequence from Front to Rear is:
• Front Section
• I" Low Water Cut-off Intermediate
First: Lower Top Port
ii) Second:
• Three (3) Top Flue Outlet Intermediates
BO_LOmPort
it) The remaining intermediate sections are 3"
Tapped Intermediates or Plain Intermediates
as shown in Figure 12 and Figure 13.
iii) Third: Upper Top Port
c.
Tighten these (3) three locations only to a torque
value of 60 ft-lbs. DO NOT EXCEED.
d.
After the three ports have been tightened to 60
ft-lbs, tighten the draw rod at the bumping pads
until metal-to-metal contact is reached. This will
assure a proper gas tight seal and prevent the
products of combustion from migrating into the
boiler room.
Front
Do not exceed the manufacturer's
recommendations.
12 11 10 9
TOP PORT
I
8
7
6
5
4 3
13 12 11 10 9
8
7
6
5
2 1 Rear
torque
iiiii
Front
,LOWER
[:7_]TI :I;1
UPPER TOP PORT
4 3
2 1 Rear
I
/
Figure
Table
12: Section
9:
Section
Positioning
Numbering
Numbering
Sequence
Model
Place
a Tapped Intermediate
Section at Position
(Numbered Rear to Front)
LC-04
LC-05
LC-06
LC-07
LC-08
NA
NA
NA
NA
NA
LC-09
LC-10
LC-II
LC-12
NA
NA
6
6
LCE-14
I
/
i ouMP,.OP.O
i I +ooPO.T
I
Figure
11: Torque
Specification/Procedure
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24
5, 9
.
6, I0
6, II
5, 9, 12
5, 9, 13
5, 9, 14
5, 9, 12, 15
5, 9, 13, 16
5, 9, 13, 17
6, I0, 14, 18
6, I0, 14, 19
15
l_nP_j
:I=I I_[o_
SERIES
LC
SERIES
LCE
LCE
-13
LC
-04
Fron_
4 3
Z
I
Aear
Front
LC
-05
Front
5 4
3 Z
I
e
S 4
3 2
LCE
-14
iiill
LCE
-15
iiii
_ 6
5 4 3
_ _ Rear
Rear
LC
-06
Front
13 IZ H 10 9 e
1
Rear
Fro_t
_ I_ 13 12 _1 _0 9
Fron_
16 15 _
n 7 6
5 _ 3
Z I
Rea_
s 2
q
LCE
-16
LC
-07
LC
-08
LCE
-17
Front
8
7
6 _ 4
3 2
I
Rear
LC
-09
I_ 1_ _1 _0 9 a
_ 5
_ 4
R_ar
iiill
Fro_
19 I_ I_ _4 13 _2 I_ 10 g e 7
6 5 4
_ Z I
Rear
Front
I$ I_ 16 16 14 13 12 II 10 9 B
7 6
6 4 3
Z I
Front
19 19 17 IS 15 14 13 12 II 10 9
6 7
6 5 4
3 2 T
Rear
Front
N
19 19 17 IB 15 14 I_ II
1
Fron_
zl
_1 19 18 I_ _1_ 15 14 _Z _2 II l0 9
_ront
z2 Zl 2O 19 le
Front
Z3 _
LCE
-18
Front
_ s
7 6
5 4 3
2
_
Rear
_e_r
LCE
-19
/C
-10
Front
10 9
S 7
6 5
4 _
2
I
Rear
LC
-11
LCE
-20
Front
II
Io 9 _
7 6
5 4
3
2 I
Rear
LC
-12
I) I_ _
_
_
_
I
I
l
I
Ftear
S _
6
6
4
3
2
I
?
_
6
4
3
Z I
Rear
B _
e
_
_
3
_
LCE
-21
Fron_
Iz II 10 9
e 7
E 6
4
_ 2 I
Rear
Rear
LCE
-22
I_ _1_ 15 14 13 _2 II _0 9
S
LCE
-23
Zl _1 19 _
19 15 16 14 _
12 II 10 9
2
Rear
LCE
-24
i
Figure
16
i
,_
Burner
13: LC/LCE
'! i
_
I
1" LWCO
Tapped
Interm.
Section
Boiler Section
Assembly
Front
Section
Top Flue
Interm.
Section
Sequence
Tapped
Interm.
Section
I
Plain
Interm.
Rear
_ Section
Section
_
Flue
j Rear
Cover
III:(_i
JR ILl'_[_ Ir'.._UH
NIl{_o]lNl_,,_[o];| I_IIF,.._IUI:::F_
=I
i/.l-, :_']f!_"
lii'i.];{o]_lL'l|[@/1511/II1:1.]1111
1+
Remove the coil cover plates, gaskets and mounting
hardware, located in the Flue Box Carton•
1.
Install a drain valve in the Rear Section, Tapping 13
See Figure 29.
2.
Place the cover plates and gaskets over any unused
heater openings• Place the cover plate with two 3/4"
NPT tappings on the upper flow port opening
(Position #2) of the Front Section•
2.
Provide a water supply line to the boiler
3.
Plug all open tappings in the boiler
4.
Provide a means to vent air as the boiler fills.
5.
Fill the boiler with water, venting air as water level
3.
Install tankless heaters, if used, in openings
#3, (Optional on Rear Section)
#i and
rises.
4. See Figure 14
6.
5. Steam boilers may have up to two coils installed
when supplied with special tankless coil rear section•
6, Standard Rear Sections do not have a tankless
opening (Position #3). This is available only as
optional constroction. This special rear section is
needed to install two coils on a steam boiler
FRONT VIEW
Figure
14: Tankless
Pressurize boiler to:
• 45 psig
• DO NOT EXCEED
THIS PRESSURE.
a) Maintain pressure while checking all joints and
fittings for leaks•
7.
After inspection is complete, drain the boiler and
remove plugs from tappings that are to be used.
REAR VIEW
Coil Openings
17
Table
10:
Taokless
Coil
Ratings
Heater No.
X-1020
Heater No.
X-1021
Heater No.
X-1022
Two Heaters No.
X-1020
Two Heaters
X-1021
No.
Two Heaters No.
X-1022
Model
GPM
LC-04
LC_05R
LC 05
LC-06
LC-07
LC-08
LC-09
LC_10
LC-11
LC-12
LCE 13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE 21
LCE 22
LCE-23
LCE-24
5 5
562
575
6.25
6.5
7.0
7.25
75
8.0
Location
I
i
I
I
i
I
i
i
I
-
GPM
Location
65
70
7.75
8.5
9.25
10.0
10.75
11.50
12.25
13
13
13
13
13
13
13
13
13
13
13
13
Above heater ratings are based on intermittent
demand
18
Location
i
1
1
1
I
1
I
1
I
I
I
I
I
I
130
1375
145
15.5
16.5
17.5
18.0
18.75
19.5
20
20
I
I
i
i
i
I
1
1
I
I
I
1
I
1
i
1
1
I
20
20
20
20
20
20
20
I
I
I
I
I
I
1
GPM
14.5
15.0
16.0
-
Location
I &3
I &3
1&3
.
GPM
Location
21.5
23.5
24.5
26
26
26
26
26
1&3
I&3
1&3
I&3
1&3
1&3
1&3
1&3
l&3
1&3
1&3
26
26
26
26
26
26
26
I&3
I&3
l&3
1&3
:
GPM
Location
33.5
35.5
37.5
i &3
1&3
1&3
39.5
40
40
40
40
40
40
t
I&3
1 &3
l&3
l&3
I & 3
1 &3
1 &3
for water from 40°F to 140°F with 200°F boiler water.
Steam boilers require a special rear section with col! opening
DANGER:
GPM
in order to use two tankless heaters.
Install mixing valve in hot water supply piping, Water temperature
over 125°F can cause severe burns instantly or death from scalds.
I_I'_"]51k117=I .l.l_.]Ir:l_
;IN r±_'.l;,,lN_"ie,]il_±_L_[olnnluu_e_v,a:l;
_I'.lW'.._und=l
',
I.
Apply the Cleanout Cover Plates on the tops of the
section joints as shown in Figure 15.
2.
Pre-assemble a steel fiat washer and steel nut on the
carriage bolts. Place a carriage bolt into each side of
the cleanout opening as shown in the figure.
3.
Tighten the lower nut securely.
4.
Press the Cleanout Plate with insulation over the
protruding carriage bolts until the insulation lays
flush against the cast iron.
5.
Apply a fiat washer and brass nut to the carriage
bolt. Draw the brass nuts down until the insulation
presses firmly against the iron.
Cleanout Cover Plate
With Insulation
Brass
J
Steel Hex Nut _
1.
(LC) Remove the Flue Collar and Rear Observation
Door Assembly from the LC Rear Flue Box Carton.
(LCE)Remove the Top Flue Outlet Plate. the Rear
Flue Cover Plate and the Rear Observation Door
Assembly from the LCE Top Flue Outlet Carton.
2.
(LC) Attach the Flue Collar to the Back Section with
5/16" x 11/2'' studs, fiat washers and hex nuts
supplied. See Figure 16.
(LCE) Attach the Rear Flue Cover Plate to the Rear
Section with 5/16" x 1172'' studs, fiat washers and nuts
supplied.
3.
(LCE) Apply high tack adhesive (supplied in Section
Assembly Kits) to the rope groove on the bottom of the
Top Flue Outlet Plate. Place the high temperature rope
seal in the groove, overlapping at the ends for a good
seal.
a) Place the plate over the opening provided by the
three top flue intermediate sections at the front of
the boiler. NOTE: Top flue outlet plate is marked
"FRONTV" for proper orientation.
Carriage Bolt
%6" UNC x 13/4'' Long
/
\
Flat Washers
SIDE VIEW
Figure
15: Install
Cleanout
Cover
Plates
d) The correct Top Flue Outlet Plate for the LCE
boiler is:
• LCE-13 thru
part number
• LCE-18 thru
part number
4.
LCE 17 use the 14" flue opening,
LCE-5007, Carton D
LCE 24 use the 16" flue opening,
LCE-5007-1, Carton E
Attach the Rear Observation Door to the Rear
Section with four (4) 5/16"-18 x 3/4" hex head bolts
provided.
b) Secure the plate and compress using the 3/8" tie
down assembly, nuts and washers provided. See
Figure 17.
c) Inspect the finished seal, particularly
plate crosses the section joints.
Figure
16: Rear Flue Collar
Attachment
where the
Figure
17: Top Flue Collar Attachment
19
II: _
h__'_ ir_,_tl m etUJ ::It:f_,!-t ;l l:_
ii _
1
Remove the Front Cleanout
Section.
2.
Open Baffles carton Remove Baffles. For LC Only Save Ceramic Fiber Liner for Section I Save Rating
Label for Chapter 4. Models LCE 13 through
LCE-20 do not require baffles
3.
Place baffles as shown in Figure 18. Three of these
are special stainless steel baffles, identified with a
i/4" hole punched in each end These baffles must
be placed in the lowest row of tubes.
4.
Install the Front Cleanout
Front Cleanout
Aluminized
Plate from Front
h,_F:-IIf:'_ I! ql_ : F,__/_
I :] ::h| III i'll_ i
1.
(LCE) Remove ceramic fiber liner from jacket
carton E. (LC/LCE) Place the liner on the floor of the
combustion chamber, Place the front end of the liner
flush with the inside of the Front Section. The liner is
24 inches wide, It will not extend all the way to the
rear of the boiler on all boiler sizes. No adhesive is
required, just press the liner down firmly.
Plate.
Plate
Steel Baffle
Aluminized Steel Baffles
Stainless Steel Baffles
Must be in Bottom Row
Have 1/4" Hole As Shown
Figure
2O
18: Flue Baffle
Locations
,m
;,]1fl::1i_
_!
IiI; t _1",I:I -'!:!1/ [*] L_
5,
i.
The boiler must be pressure tested as outlined in the
chapter "Place the Boiler Sections" of this manual.
2.
The Supply and Return piping can be installed
before the jacket is applied. Use nipples long enough
to extend through the jacket.
6.
;N
t-"llll,,ll,
lli'd
I:,ll:JIL_[€
7.
1.
See Figure 21 for piping illustration.
2.
Install Top connections sized per Table 11.
a) Model LC-04 requires one riser off the Rear
Section. Plug the 4" tapping in the top of the
Front Section.
8.
9.
d) LCE models require three or more risers.
3.
4.
Size the Header per Table 11. Pipe the header at
least 24 inches above the normal boiler water line.
See Figure 19. This is required to prevent water from
carrying over into the header and then to the
system.
Figure 21 shows the Supply and Return piping for
Parallel Flow Gravity systems and all Pumped Return
Systems.
Counterflow Gravity systems require the boiler steam
line to enter the top of the steam main. See
Figure 20 for this special case.
Do not reduce the size or number of risers
shown. These are required for reliable operation of
the boiler. If the risers are undersized or incorrectly
placed, a sloped water line can occur in the boiler,
causing possible overheating of some sections.
Pipe the Header with an offset as shown in the
drawings. This offset prevents the expansion and
contraction of the Header from damaging the boiler
sections.
b) Models LC-05 through LC-10 require two risers,
one off the Front and one off the Rear Section.
c) Models LC-11 and LC-12 require three risers,
one each off the Front and Rear Sections plus
one off the Tapped Intermediate Section.
:1:1:1_,]]1[_-
Always locate the Steam Supply take-off
between the Equalizer and the last Boiler
Riser. (See Peerless Heater Company's "Steam
Installation Survey" for discussion). Locating the
steam supply between the risers will cause water
carryover to the system.
Do not use a bull head tee to provide steam supply
and equalizer connections, this will cause water level
bounce and carryover.
Jel! I it 11ill ltl'_l fJI iI h:_lc
I.
The use of a Hartford loop is recommended in all
installations. See Figure 19. The loop provides
additional reliability for the system.
2.
A check valve must still be installed on the pump
discharge of all pumped return systems.
Steam
Steam Supply should always
be piped between
last boiler
riser and equalizer.
Supply
BOILER HEADER Pipe with offset
to allow for header
expansion
I
24"
Min.
x
To
." Use close
i
4" " Hartford
, Loop
I
!
Blowdown
/"
Valve
.
/+
Figure
19: Supply
and Return
Positions,
Skim Piping,
Hartford
Loop
21
3.
Boiler Riser Piping
enters TOP of main
on Counterflow
System
_
4
Steam Main
6.
Pitch T
2" Skim
Connection
Header,
Model
LC-04
LC-05R
LC-05
LC-O6
LC-O7
LC-08
LC-09
LC-10
LC-11
LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE 21
LCE-22
LCE-23
LCE-24
22
1.
Figure 22 shows typical piping for multiple boiler
Gravity Return systems. Figure 23 show typical
piping for multiple boiler Pumped Return Systems•
2.
Provide separate feed lines for multiple boiler
pumped return systems. Use either separate feed
pumps or solenoid or motorized valves to isolate
feeding of the boilers. This is needed to provide
reliable level control and avoid nuisance
performance problems.
3.
Condensate return units are not effective for multiple
boiler installations since they do not respond to the
needs of the boilers• always use Boiler Feed Units.
4.
Install a Float and Thermostatic trap at the boiler
water level on each of the mufltple boilers on a
pumped return system• This prevents flooding of idle
boilers due to condensation of steam•
20: Supply and Return Piping Counterflow
Gravity Systems
11:
Risers r: Equalizer
I=B=R
Gross
Output
MBH
547
649
707
868
1029
1189
1350
1511
1672
1832
1966
2125
2284
2444
2603
2763
2922
3082
3256
3430
3604
3777
If the pump discharge is looped overhead, above the
boiler water line, install spring loaded check valves at
both the pump discharge and the connection to the
boiler return.
I)]q I fldaJ allll:J ii=l I:{e] lit :I:llL_LL't IL,11iW_'_lll[O]t_
_
ualizer
Table
Size the equalizer per Table 11. Models LC II, LC12 and LCE-13 through LCE 24 require two return
connections to the boiler off of the equalizer line.
Pipe the Hartford loop tee so the inside top of the
close nipple is 2 to 4 inches below the normal boiler
water line. See Figure 19.
Counterflow
Figure
On pumped return systems, install a boiler cock after
the pump to allow throttling of the pump discharge.
The pressure after the boiler cock should be no more
than 5 psig above the boiler operating pressure.
Pumping the water into the boiler too fast will cause
collapse of the water level and level control problems.
Sizing
!!
;
!
End Section
Risers
Size
Number
(Inches)
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
4
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Intermediate Section
Risers
Size
Number
(Inches)
7
Equalizer
(inches)
2
2
2
2
21/2
2½
21/2
1
1
1
2
2
2
3
3
3
4
4
4
4
4
_
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
Header
Size
(Inches)
4
5
5
5
5
6
6
6
6
6
6
8
8
8
8
8
8
8
8
8
8
8
I ;1I_ _ _
-i-i-i-i-i-i-i-i-i_
_ _I
LCE-13 THRU LCE-24
TWO
END RISERS
ONE OR MORE INTERMEDIATE
RISERS
TWO RETURN CONNECTIONS
Figure
21: Supply
and Return
Piping - Pumped
Return
and Parallel
Flow Gravity
Systems
23
l_1_llill_ I;I.]TI-_;t
Steam
Supply
Stop
Valve
Pipe All Headers
24" Above Boiler
Minimum
Water Line
Stop
Valve
Blowdown
Valve
Figure
22: Piping
Multiple
Boilers,
Typical,
Gravity
Return
Systems
Steam
Stop
Valve
Pipe All Headers Minimum
24" Above Boiler Water Line
Supply
Stop
Valve
_f_\_
receiver
F/I- Drip
Trap
) Valve
_'_.
;olenoid or Motorized
Valve
Boiler Cock for Throttling
Pump Pressure to Boilers
Check
Valve
Valve
To
Pump
Alternate Piping: Use two separate pumps, separate return lines and no solenoid valves
Figure 23:
24
Piping Multiple
Boilers, Typical,
Pumped
Return
Systems
"_1 "J,| :1_:_ H _ //'l:I
_:! ;| |
Collect all the jacket cartons: Jacket
Front & Back
Carton plus Jacket Side & Top Cartons. See
the Shipping List in the front of this manual for the
jacket cartons required. The cartons contain the
jacket parts and screws• The jacket panels are preinsulated.
Remove all needed knockouts
before beginning assembly,
2.
2.
Attach the Middle Front
in the same manner.
Panel
and Lower
Front
Rail
3.
Position the Jacket Assembly with the front panels
pushed up against the front section. You will need
the jacket in this position to install the Burner Front
Plate•
le]i Ir:q"] "]k'd IqiL'Te.][4:il / IH :I_,I :g :I_,1L_1:1
from the jacket parts
1.
Attach the Rear Jacket Panel to the Jacket Side
Panels with #10 x 1/2" sheet metal screws.
I:R F-'N']'.Jk'd qY_'To.]
[4:ill _"lle] :(,:] r,_lL_le][e.[e];]_l:4:[,:
I_q V*-N']:,lk'd [qY:Te'][4:il/ll[e]:.i__,NLH:tl_
1.
See Figure 25 for details.
2.
The Side Panels can be used on either side of the
boiler.
3.
Place the Jacket Side Panels on each side leaned
against the Boiler Sections.
4.
On Models LC-08 through LC-12, each side uses
two panels. Place the panels so the seam is centered
on the Tapped Intermediate Section. On LCE
models, place panels in the sequence shown in Table
12.
On boilers with two or more Jacket Side Panels per
side, join the panels together with #I0 x I/2" sheet
metal screws. Also attach the Jacket Side Panel
Reinforcing Angle inside the jacket at the bottom of
the seam.
5.
i.
Attach the Top Front Panel to the Sides and Upper
Front Panel with #I0 x 1/2" sheet metal screws.
2.
Models LC-08 through LC-12 use two Jacket Top
Panels. Place them on top with the seam at the same
point as the side panels• Join them at their seam
with #10 x 1/2" sheet metal screws. On LCE models,
place panels in the sequence shown in Table 12.
3.
Attach the Jacket Top Panel to the Jacket Top Front
Panel with #I0 x 1/2" sheet metal screws•
4.
Attach the Top Rear Panel to the Jacket Top Panel
with #I0 x 1/2" sheet metal screws.
5.
Finish by placing #10 x i,,'2" sheet metal screws in
the remaining holes along the Jacket Top Panel
flanges, into the Jacket Side Panels.
Attach the Left Front Corner Panel to the Left Side
Panel with # i0 x 1/2" sheet metal screws.
6.
7. Attach the Right Front Corner Panel to the Right
Side Panel with #10 x i/2" sheet metal screws.
I=1 r_W_l_Jk"4I'.,,IW'.._Ii::(-_
F;1L'_IO]
lir_,l:]::ll_
i.
Mount Boiler Rating Plates and Agency Plates on the
Upper Jacket Front Panel as shown in Figure 24.
2.
Secure metal plates with #6 x 1/4" sheet metal
screws. Apply all adhesive-backed
labels.
[o46r_,'q-.,l:JiVdPlr±Te.][4::illiH
:l:{e]b,'1|l i_._I_1:ii(_
1.
Attach the Upper Front Panel to the Right and Left
Front Corner Panels with #i0 x 1/2" sheet metal
SCreWS.
Table
12:
Jacket
Top b Side Panel Placement
Locate Jacket Top and Side Panels in
the Position Below
(Numbers are from Rear to Front)
Model
5 T
(Front) I
2
4
1
i (Rear)
I
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24
-
E
I
B
E
A
B
C
0
€
T
1
E
E
E
E
E
E
E
E
A
A
B
B
C
[
A
B
C
A
B
B
B
B
B
B
B
B
B
B
B
B
C
C
0
Figure 24:
Location of Rating, Agency and
Instruction
Plates on Jacket Front
Top Panel
25
Jacket
Top Panel
Jacket Top Panel
Jacket Top
Rear Panel
I
I
Jacket
Rear Panel
• I
Jacket Top
Rear Panel
Jacket Top
Front Panel
Jacket
Side
Panel
Jacket Front
Top Panel
Jacket Front
Middle
Panel
Jacket Left
Front
Corner Panel
Jacket Front
Lower Rail /
Figure 25: Jacket
26
Assembly
Jacket
Side
Panel
Side Panel
Support
Angle
Jacket Right Front
Corner Panel
Refer to Chapter I, preinstallation, Section D. Chimney,
or Vent for installation requirements. Refer to
Chapter 9. Startina the Boiler, Section C. Run Burner
Check Out for damper settings and draft requirements.
r:!
I:{II:|L_I:I;t
3_
r:1:J'Jl[l'Y:_li[e]{
1.
Refer to Burner Spec and Data Sheets for the Oil
and Gas/Oil Burners pre-tested with Series LC
boilers.
2.
Make sure the nozzle sizing and spray pattern match
those given in the spec and data sheets.
3.
See Figure 26 and Table 13 for combustion
dimensions.
4.
I.
2.
chamber
Remove the Burner Mounting Plate and Hardware
Bag from the crate.
I1:1:
I:|II:|LII=I_
Remove the Burner from its crate. Read the burner
instructions.
2.
Insert (4) 3/8"-16 x II/4'' studs supplied with Burner
Mounting Plate into the front plate holes.
3.
Place the high temperature gasket on the burner
front plate and secure the burner to the front plate
with 3/8" fiat washers and hex nuts.
I_v_[_l|JL_illlh_[Cl
I;.lff-_lll
The Burner Mounting Plate is made to fit the burner
being used. Burners vary in bolt pattern for the
flange, burner tube diameter, insertion length and
near-tube configuration. Make sure the front plate is
correct for your burner if purchased separately from
the boiler.
Secure the Burner Mounting Plate to the front
section with the fiat washers and hex nuts.
[I,_ hVA[ellJL_ll
1.
I:_ IIL_-"]llr±!llli:]lJ-'_,_l=l;!
Screw (7) 3/8"-16 x 21/4"studs into the holes in the
front section around the chamber opening.
4.
If the burner is supplied with a pedestal, install it to
the burner per the Burner Manufacturer's
Instructions. The pedestal provides additional
support and prevents the burner from sagging.
27
:I
Figure 26:
Combustion
Chamber
Layout
Table
Combustion
Chamber
Dimensions
13:
Model
LC-04
LC-05R
LC-05
LC-06
LC-07
LC-08
LC-09
LC-IO
LC-11
LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE 19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24
28
Chamber
Length
"A"
(Inches)
18%
23W16
23_5Ao
29
34¼€
39V_
44¾,3
49V4
54_A6
59%
647A0
69V2
749A€
79%
84_¼6
89%
941¾_
99%
104'5A6
110
1151/16
1201/8
- See Table
13 for Dimensions
Burner
Beckett
6%
6%
6%
6V8
6_
11/8
1%
IYs
11/8
11/_
11/8
1%
11/8
1%
1%
11/_
1%
1%
1%
N/A
N/A
Front
Plate
Extension
Carlin
61/s
6%
6%
6%
6Vs
61/8
i%
II/8
1%
1%
IVs
II/8
11/_
1%
1%
I%
1Vs
U/s
1%
I%
NIA
i
i
Past Jacket
(Inches)
GordonPiatt
Power
Flame
6gs
I%
ll/s
1%
I%
11/8
1%
IV8
11/8
1%
1%
I%
II/8
IV8
11/8
6%
6%
6%
6Va
6_×_
1%
I_/8
I%
I%
IVa
IV_
1Vs
1V8
1%
1%
1%
I%
IV8
IV_
i%
6%
6%
6%
6Vs
6V8
I%
I%
I%
IV8
IV8
IV8
1Vo
1%
IVs
1%
IV_
1%
1%
1%
1%
IV8
1%
1Ve
11/_
I%
1%
I%
1%
11/8
I%
i'/8
Webster
[_o]_ h'_
1:(..inuI _LIJ=lml["_1"J_c7
I
].
2.
Read the Burner Instruction Manual, supplied with
the boiler or with the burner if purchased separately.
Review applicable code requirements for burner and
fuel piping installations.
To Gas Supply --_
Install piping to allow removal of burner and access
to combustion chamber for cleaning or service.
Service Valve -1_
I=J IIL_l_"]llr'-l!ll:llJ =lll0]ll
-_
",JI_IL_[,
1.
Place the fuel oil tank and install the piping in
accordance with the National Board of Fire
Underwriters and all other applicable codes.
2.
General Guidelines for Oil Piping
a) Follow the guidelines in the Burner Manual for
sizing oil lines. Never use smaller than I/2" OD
copper tubing.
Ground_
b) Install manual shut-off valves on the suction line
at the burner and at the oil line entrance to the
building. When installing a shut-off valve on the
return line, an oil pressure relief valve piped
ahead of the shut-off valve and discharged to the
tank must be provided to prevent over-pressure
conditions.
c)
Install a two-pipe oil distribution system when
possible. It will improve the reliability of the oil
delivery to the burner.
d)
e)
Use flare fittings when using copper tubing.
To Boiler Gas Control Train
Sediment Trap
Figure 27:
Provide an oil line filter in the suction line. Size
the filter for the suction gear capacity of the
burner oil pump if running a two-pipe system.
If burner is above the top of the fuel oil tank,
install a check valve on the oil suction line at the
burner to prevent oil from evacuating the line. If
burner is below the top of the tank, install an
anti-siphon device to prevent oil flow should the
oil line break.
t!
ion Ih.'_[.-"lllr'_llIIc'f_'l,-"] [.'.llJ'J'Jli'd
2.
3.
The standard gas train is designed for a maximum
pressure of 1/2 psig (14 inches water column). Make
sure the system regulator will not allow a higher
pressure to the Gas Control Train under any
conditions.
The minimum gas supply pressure is listed on the
Burner Rating Plate. Make sure the system regulator
and the piping are sized and adjusted properly to
provide this pressure under all conditions.
to Boiler
Install a Service Valve, Sediment Trap and Ground
Joint Union at the supply connection to the Gas
Control Train as shown in Figure 27. These are not
supplied with the boiler. Install them in accordance
with local codes.
5.
Use only pipe joint compounds
Liquefied Petroleum Gases.
II_-I
".,]I'ilh,'1[€
Size the piping as required by the National Fuel Gas
Code, ANSI Z223.1 or as required by local codes.
a) Use Table 14 for sizing of natural gas for a
system pressure drop of 0.3 inch water column.
Connection
4.
I.
1,
Gas Supply
Icf:!-I
rated for use with
[--"].ll"J_k'dN _l:,,,lh,'_[_
ISOLATE THE BOILER GAS CONTROL TRAIN
FROM THE SYSTEM DURING TES_
a) Test pressure 1/2 psig or less - Close the Manual
Shut-Off Valve on the Boiler Gas Control Train.
b) Test pressure over 1/2 psig - Disconnect the gas
supply piping upstream of the Boiler Manual
Shut-Off Valve.
Do not expose the Gas Control Train to excessive
pressure.The gas valves can be damaged.This could
result in explosion hazard and severe personal injury
or death.
Do not test gas supply piping with open flame. Use a
soap suds mixture brushed onto the pipe joints to
test for leaks.
29
Table
14:
Capacity of Gas Supply
0.3 inch Water Column,
Pipe in Cubic Feet Per Hour of Natural
Gas for Pressure
Drop of
Pipe Length
(Feet)
1-1/4"
Pipe
1-1/2"
Pipe
2"
Pipe
2-1/2"
Pipe
3"
Pipe
4"
Pipe
Pipe
10
1050
1600
3050
4800
8500
17500
44OO0
20
730
1100
2100
3300
5900
12000
31000
30
590
890
1650
2700
4700
9700
25000
40
500
760
1450
2300
4100
8300
22000
50
440
670
1270
2000
3600
7400
20000
60
400
610
1150
1850
3250
6800
18OOO
70
350
560
1050
1700
3000
6200
17OOO
90
320
490
930
1500
2600
5400
15OOO
I00
305
460
870
1400
2500
5100
14OO0
150
250
380
710
1130
2000
4100
11500
Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance
pipe fittings. Use the following multipliers on above capacities for specific gravity other than 060:
Specific
Multiply
3O
Gravity
Capacity
by:
0.50
0.55
060
1.10
104
1 O0
6 t,
is needed
0.65
0.70
0962
0.926
for
r,l
Ih_[..'_lf;11lll _',]r;1;;l::illk'4LVl;1IkvJ=[..
i.
ID31 IIs_[_"]llr;!llt!I;,l:?:k."_'_lJ:|::l[I,[i]_//:(t]l_
Pipe the discharge of the Safety Relief Valve away
from any traffic area, preferably to a floor drain. This
is necessary to prevent injury should the valve
discharge.
Make sure that the ignition system components,
electrical controls, junction boxes and electrical
panels are protected from water (dripping, spraying,
rain, etc.) during boiler operation and service (trap
servicing, control replacements or other).
Pipe the discharge full size of valve outlet.
2.
3. Pipe the Steam Pressure Gauge and Boiler Limit and
Operating Pressure Controls as shown in Figure 30.
Connect the control assembly to the I/2" tapping in
the front section.
Pipe the Pop Safety Valve on a tee mounted in the
2]/2'' tapping located on the upper ]eft side of the
Rear Section. Make sure the relief valve sizing meets
local code requirements.
Install a 2" ball valve for skimming off the end of the
tee as shown in the piping drawings in this manual.
1:11 -,JI "]:11it_,1
t_I [41 =k'_l:
1.
I;]tl I h,_[,,:"Jr
It_'111 1:] Ko]I,_I| tp[ol r,_|_,'_
I kVl'_1IkvJ=[-;
1.
Install a IL/Z"full port ball valve off of the return
connection as shown in the "Pipe the Boiler" section
of this manual. See Figure 28.
2.
Pipe the valve discharge to a floor drain if available
or apply a nipple and cap to close off when not in
I:q
I:f_,t /: :ll_
Connect piping to any installed tankless heaters. See
Figure 35 for suggested piping for single coils and
Figure 36 for suggested piping for dual coils.
[Ke]L_h_l:[_l/[,."J.uJ:,l:,llk'dLrAVJlHh_[€
1.
Install all wiring in accordance with local codes, the
National Electrical Code and other controlling
agencies or governing bodies.
USe.
tel! Ih,'ql,,,_
Ir_'lll! lU(ol_l_ir_,rr_'_lti=l-"l
_l,,]ljl[O]-I:r,{___
1. Mount a float type Low Water Cutoff and Gauge
Glass in the tappings provided in the side of the front
section or the side and top of the first intermediate
section.
2.
3.
4.
Do not apply piping which would raise or lower the
location of the cutoff relative to the tappings in the
boiler. Raising the water level over the design height
will cause water carryover to the system.
For correct location of typical low water cutoff/feeder
or low water cutoff/pump control, see Figures 31
through 34.
See Figure 29 for the location of control connection
tappings.
The boiler/burner must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction, or in the absence of such
requirements, with the current edition of the National
Electrical Code, ANSI/NFPA Number 70.
2.
Use #14 gauge or heavier wire for supply wiring.
Protect the circuit with a fused disconnect switch (by
others) and a grounded neutral.
3.
Mount an electrical junction box on the boiler Front
Panel for connection of supply wiring and
distribution to the boiler controls.
4.
5.
Provide each float low water cutoff with a blowdown
valve. Pipe the blowdown away from traffic to a floor
drain if available. The blowdown valve is required
for proper maintenance of the control.
6.
Maintain a height of 461/2" from boiler foundation
the normal water level.
7.
When using Multiple Float Type Controls: Always
pipe the controls off of the same tappings to the
boiler. Do not mount on different ends of the boiler
or in different tappings. This can cause erratic
operation and nuisance problems with the controls.
Follow the instructions in the Burner Manual and the
Wiring Diagrams supplied with the burner and the
boiler.
to
31
¢H
h_l.."l Ih_1
I! IKa,(o] _ilII; {o] INr_,_i
I; i h_[_.
3
Install all line voltage wiring in conduit
I.
Wire the boiler according to the wiring diagrams
supplied with the burner and the boiler (in the Boiler
Envelope)
4.
Do not install single pole switches, including safely
controls, in a grounded line.
2.
Low Energy Safety Control Wiring, if used, must
follow the contour of the boiler. Some local codes
may require that all wiring, even low voltage, be
routed in conduit.
Steam
Supply
Install Boiler
off of 21/2"tapp,ng
as shown. Pi
full size
preferably
in_End Section
a
Install a 2"
valve piping
Install
a 11/2
'' Blowdown
Valve
off of the
Return
Piping As
Show n_
Figure 28: Blowdown
32
Valve,
Safety
Valve
and Skim Valve
Return
Piping
i
6
4
9
1
2
16;
15
11;<
10
8
f
14
e
7
FRONT
REAR
1
4" NPT Supply Tapping, Front Section
8
Not Used On Steam, 3/4" NPT - Plug
2
4" NPT Supply Tapping, Rear Section
9
Pressure Ctrl/Gauge
3/4" NPT Tapping
3
3" NPT Return Tapping, Rear Section
10
Secondary Probe LWCO Tapping, 3/4" NPT
4
Not Used On Steam,
1/2" NPT Tapping - Plug
11
12
Not Used On Steam,
1" NPT Tapping - Plug
5
(2) 1/2" NPT Gauge Glass or
LWCO Tapping
13
Drain Tapping, 3/4" NPT
6
Tankless Coil Temp Control Tapping,
3/4" NPT, Only with Tankless Coil Installed
14
NOt Shown - 1" NPT Tapping in Side and
Top of First Intermediate - for LWCO
7
Relief Valve and Skim Tapping, 21/2" NPT
15
Not Used On Steam,
(2) 3/4" NPT Tapping - Plug
16
Assembly,
Tankless Coil Temp Control Tapping, 3/4" NPT, Only with Optional Tankless Coil Back Section
Figure 29:
Control
and Pipe Tapping
Locations
33
. ]_[--_t'_] _ ['_k'i]_ o_I_]_],
_J;th'_l [:1_JIfll_[_
P
Option 1
J
(Right Hand Shown,
Left Hand WouEd Be Reversed)
E
F
P
E
C
I
Option
2
C
P
A
3/4" X 3/4" X 1/4" Reducing
B
3/4" Cross,
C
3/4" Plug, Malleable
D
3/4" x 1/4" Hex Bushing,
E
1/4" x 3" Nipple,
Brass
F
3/4" x 3" Nipple,
Black Iron
34
Tee, Malleable
Malleable
(NOTE:
Figure 30: Control
A
Malleable
Some
and Pipe Tapping
local codes may require
Locations
G
3/4" x4" Nipple,
Black Iron
H
3/4" x 5" Nipple,
Black Iron
J
3/4" x 6" Nipple, Black Iron
K
Steam Gauge
P
Steam
larger
Pressure
piping)
Control
!
--
Burner Cut-Off
Level
/>
1/2" Brass
Union
/-1/2" X 4" Brass Nipples
Figure
31: Optional
Model
(2 Req'd)
67PE2
1/2" Brass Close
Nipples (2 Req'd)
Float Low Water
Conduit
Connection
Cutoff
Normal
Water Line
81/2 ''
t
Burner
Cut-Off
Level
Feeder Closing Level
(Mark on Casting)
Figure
32: Optional
Model
47-2 Low
Water Cutoff/Feeder
- Use only up to Model
LC-O7
35
74;,]
Ii;1177f4lTffitI 4
C
C
B
H
A
A
G
Burner Cut-Off Level
Casting)
J
Normal
Water Line
=_
LWCO Intermediate
Section (First from
F
E
B
12"
Install 1" Blowdown
Boiler Foundation
Valve
A
1" Cross
B
1" Ground Joint
Union
D
I" x 3" Nipple
G
1" x 12" Nipple
E
I" x 4" Nipple
N
1" x 61/d' Nipple
C
J
The connected
fittings shown on this drawing
to be supplied
by the installer.
Figure
36
33: Optional
Float Type Pump Control/Low
Water Cutoff,
Model
are
157
'.
V
*
1
C
B
A
Burner Cut-Off Level is 1V2" Below
Center Line on 51-2 and 51-S-2 Controls
(23/4" Below Normal Water Line)
Feeder Closing Level
(Mark on Castingj
J
Normal
Water Line
Control
Center
Line
LWCO Intermediate
Section (
E
B
/
Install 1" Blowdown
f
y_Bo!le[
Valve
SUGGESTED
FITTINGS
Foundation
LIST
A
1" Cross
D
1" x 4" Nipple
G
1" x 12" Nipple
B
1"GroundJointUnion
E
l"x4"Nipple
H
1"x61/2"Nipple
C
1" Plug
F
I" x _' Nipple
d
1" x 19" Nipple
Always
Figure 34:
use a pump control
Optional
and boiler feed system
Feeder/Low
Water
Cutoff,
The connected fittings shown on this drawing are
to be supplied by the installer.
Type 51-2
37
3/4" Control
Tapping
High Temperature
Hot Water
Provide anti-scald
devices in the system
Mixed Water
Tankless
where
needed.
Failure to control water
Heater
temperature
or other usage areas
NE
Flow
to showers
where a scald risk exists
can result in severe
personal injury,
Cold
Water
Inlet
Figure 35:
Suggested
Water
Mixer
Piping - Single Tankless
Coil Installation
High Temperature
Mixed
Tankless
Hot Water
Heaiers
_4_
Rear
"
Water
Front
,
V
Water
Is
Mixer
Cold
Watel
Tapping
Inlet
Flow Control
Figure
38
36: Suggested
Piping - Dual Tankless
Coil Installation
"-!1 [_:l_[li:l;
I.
When a barometric draft regulator is installed in the
venting system, adjust the boiler damper for 0" wc
pressure reading at the damper. Adjust the draft
regulator for -005" wc draft between the boiler
damper and the draft regulator.
I']l'J h_[4
Steam Piping
a) The Boiler must have been hydrostatically
b) Check the attached
tested.
piping for joint tightness.
4.
c) Continue
start up.
2.
monitoring
as you proceed through
Gas Piping
a) Make sure the gas system piping and the
connections to the Boiler Gas Control Train(s)
have been leak tested.
Adjust the burner as needed for a CO 2 reading of:
a) Oil burners: CO 2 approximately 12.5% or I%
less than the level at which the smoke reading
goes above a trace on the Bacharach scale.
b) Gas burners: 9% to 10% with CO less than 50 ppm.
5.
b) After the boiler is in operation, check the
tightness of all joints in the boiler gas piping with
a soap suds solution.
Inspect al[ flue gas joints (sections, attachments,
breeching and vent) for gas tightness. Remove the
jacket panels in order to thoroughly inspect all rope
seal joints between the sections.
c) Purge the gas piping of all air up to the boiler
Gas Control Train.
3.
Oil Piping
a) Check the oil piping visually. Make sure all joints
are tight.
b) When the burner is firing, check the suction line
and return line pressures.
c) If the pressure exceeds the allowable pressure in
the Burner Manual or if the suction line vacuum
is higher than allowable, correct the piping as
needed to bring the suction line and return line
pressures within acceptable range.
On installations with high draft, do not leave the
boiler with a negative draft reading at the rear flue
box or draft damper. High negative draft can pull the
flame up into the boiler crown sheet and overheat the
iron.This can result in cracked sections or shortened
boiler life.
I_
[_'I:[*,]H
1.
d) Excess pressure can cause pump seal failures.
Excess vacuum will cause fuel flow problems
with the burner oil pump.
I:{o]ll_:l(t]L_ll;lo]_
Limit and Operating
Pressure Controls
a) Lower the setting of each control until the burner
shuts down.
2. Low Water Cutoffs
:tl
I=11 II i :l:l I:{*]lllq;
a) Test probe type controls by using the Push4o-Test
Button.
i.
b) Test float type conb'ols.
Fill the boiler to the normal water line.
a) Gravity Systems and Pumped Return with
Condensate Units - Fill to 461/2" above the boiler
foundation (center of gauge glass).
3.
4
b) Pumped Return with Boiler Feed Unit - Fill the
boiler using the boiler feed unit. Fill level will
depend on the control being used, but should be
461/2" above the boiler foundation (just below
center of gauge glass) when the pump stops.
;_l
I ;tlJ L_I :t.ll 1| L_1:1it lit : I :[_ [_.11
II
i.
l_fore firing the burner, slide the Slide Gate Damper
on the rear flue box all the way down (full open) on
LC's or open the LCE Draft Damper until the handle
is parallel to the vent pipe (full open).
2.
Follow the instructions in the Burner Manual for
starting the burner, adjusting air openings and fuel
rates. Perform ignition system and flame supervisory
control test and checkout as described in the manual.
3.
After burner is set at rate, close the damper until the
pressure reading at the test opening in the rear flue box
or draft damper is between 0" wc and 0.1" wc positive.
See Table 15 for typical overfire pressure (measured at
the burner front plate) and boiler draft loss.
Follow additional instructions in the Burner Manual
for proving the burner component operation.
Check all controls to make sure they function
correctly.
5. After all controls have been proven, set the
Operating and High Limit Temperature Controls to
the pressures desired.
I_
[_I_:IL_Ii/:I
I.
_n :[o]llq;
Clean the boiler as described below no later than
one week after the initial start-up. Cleaning will be
more effective if the boiler operates a day or two to
loosen sediment and impurities in the system.
Cleaning the boiler requires the use of very hot water
and corrosive chemicals. Use care when handling to
prevent injury.
39
2.
3.
4.
5.
The boiler must be cleaned to remove any
accumulation of oil, grease, sludge, etc. that may be
in the system. These substances can cause foaming
and surging of the boiler water, producing unstable
water line and water carryover to the system.
9.
10. Continue skimming the boiler until the water flowing
from the skim tapping flows clear. This will take
some time, possibly several hours for a dirt_ system.
The piping for a 2" Skim Valve must be done as
shown in this manual, with the skim valve mounted
off the Pop Safety Valve tee on the rear of the boiler
11. After skimming is complete,
turn off the boiler.
Connect a 2 inch drain line off of the skim valve, run
to a point of safe discharge.
12. Close the make-up
blowdown valves.
Close all valves to the system. Provide a means of
continuous fresh water to the boiler for the cleaning
Open the skim valve. Fill the boiler until water begins
to flow out of the valve.
Table
15. Note: If the gauge glass becomes dirty again, this
indicates more contaminants have worked loose in
the system. Repeat the cleaning and skimming
process as needed to clean the system.
Turn burner on and allow the boiler water to heat up
to just below steaming (180 ° to 200 ° F). Cycle the
burner to maintain temperature during skimming. Do
not allow the boiler to steam. Steaming mixes up the
contaminants in the water instead of floating them at
the surface.
15:
Typical
Model
LC-04
LC-05R
LC-05
LC-06
LC-07
LC-08
LC-09
LC-10
LC-11
LC 12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24
Combustion
Chamber
Pressure
water valve and open the boiler
14. Restore piping to normal. Pipe a nipple and cap in
the skim valve.
7. Use common washing soda (such as Arm and
Hammer Super Washing Soda). Mix the soda with
water in a 10 quart pail and pour into the boiler
through the safety valve tapping. Use a proportion of
one (1) pound of washing soda for each 800 square
feet EDR net boiler rating.
8.
close the skim valve and
13. Drain the boiler completely, then refill and drain
again one or two times to make sure all of the soda
has been washed out.
process.
6.
Open the make-up water valve to coninuously feed
water to the boiler, Allow water to flow out the skim
tapping.
Do not leave the boiler unattended while firing.
Take great care not to allow the water level to drop
below the bottom of the gauge glass or to allow fresh
water make-up to flow in too fast.This will avoid the
possibility of causing the boiler sections to fracture.
and Boiler Draft
Loss
Combustion Chamber Pressure
with 0.1" w.c. at Rear Flue Box Test Port
(Inches w.c.)
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
0,22
0.22
0.24
0.26
0.27
028
029
0.30
0.31
0,32
0.24
0.25
0.26
0,27
0.28
+
+
+
+
+
+
+
0.29
0.30
031
0.31
0.31
0.32
0.32
Boiler Draft Loss
(Inches w.c,)
I
0.12
0.12
0.14
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0,14
0.15
.
0.16
0.17
0.18
0.19
0.20
0.21
0.21
0.21
0.22
0.22
NOTE: Actual chamber pressure and draft loss readings may vary with each boiler and installation due to variation in the heat exchanger,
deposits in the flueways, actual burner firing rate and excess air conditions, Use the above numbers as a general guide only. If the measured
loss is considerably higher than the above, check the flueways for deposits and confirm the burner firing rate
4O
draft
c) Do not use ethylene glycol antifreeze in a steam
boiler or system.
Do not store or allow combustible or flammable
materials near the boiler. Substantial fire or explosion
hazard could result, causing risk of personal injury,
death or property damage.
Do not use this boiler if any part of it has been under
water. Immediately call a qualified service technician
to inspect the boiler. Any part of the control system,
any gas control or any burner or gas component
which has been under water must be replaced.
Should overheating occur or the fuel supply fail to
shut off: Shut off the fuel supply at a location
external to the boiler. Do not turn off or disconnect
the electrical supply to the pump. Immediately call a
qualified service technician to inspect the boiler for
damage and defective components.
f.*1 I'=llF_*l_]l=_
[e I:[*]ll:l:f
Ih_l [*]',I=I;__'_I[*]L_
I.
Start up the Burner/Boiler per the Burner Manual
and the instructions in this manual on starting the
boiler.
2.
Prove the correct operation of all controls on the
boiler and burner as outlined below.
3.
Check the operation of the ignition and flame
proving controls as described in the Burner Manual.
4.
Test the limit and operating
are operating correctly.
controls to assure they
Before servicing the boiler:
• Turn off all electrical power to the boiler.
• Close the Gas Service Valve and Oil Shut-Off Valve.
• Allow the boiler to cool if it has been operating.
• Label all
servicing
improper
operation
loll
wires prior to disconnection when
controls. Wiring errors can cause
and dangerous operation, Verify proper
after servicing,
hVjr:lh_//_L_rI, IL_[_l_
1.
2.
,V:IL_h_IlY:I
Before the start of each heating season, inspect
and make all necessary adjustments to insure proper
boiler and burner operation. Use the maintenance
and inspection procedures following.
Inspect the Venting System
a) Check the chimney or vent to make sure it is
clean and free from cracks or potential leaks.
5.
Inspect and test all low water cutoffs.
6.
Test the pop safety valve(s) using the procedure
given by the valve manufacturer on the valve tag.
7.
Visually inspect the burner and pilot flames (if
applicable).
I:H b(e] _:LIiIlllol_,_lb,'lli:l_
d) Be certain that the boiler and system are refilled
before returning to service. Follow the
Instructions in the manual and the Lighting
instructions to operate.
b) All joints must be tight and sealed.
c) The vent connector must extend into, but not
beyond the inside edge of the chimney or vent.
3.
I:{o]llq;
1.
Turn off Burner.
2.
Open main line power disconnect
boiler/burner.
Inspect the Boiler Area
a) The boiler area must be clean and free from
combustible materials, gasoline or any other
flammable liquids or vapors.
b) The combustion air openings and the area
around the boiler must be unobstructed.
switch to
3.
Close fuel shut-off valves.
4.
To take boiler out of service if the boiler and system
are not to be used when temperatures are below
freezing:
a) Drain the boiler and system completely and shut
off make-up water supply.
b) Open main line power disconnect switch to
boiler/burner. Remove the fuses or secure the
switch so that the power cannot be turned on
accidentally.
4.
Inspect boiler flueways and burner for cleanliness.
cleaning is required, use the following procedure.
a) Turn off all electrical power to the boiler.
If
b) Remove Jacket Middle Front Panel and Jacket
Top Panels. Remove Front Cleanout Plate and
Cleanout Cover Plates on each flueway. On LCE
boilers, remove the top flue outlet plate and vent
piping as necessary to access the top of the
sections.
e) Brush the boiler tube spaces both horizontally
(through cleanout openings on ends) and
vertically (from top of boiler through cleanout
openings at flueways).
41
d_ Remove the Burner and Burner Mounting Plate.
Remove any scale or soot from the combustion
chamber by means of vacuum cleaning or other
available means. Take care not to damage the
chamber floor liner or target wall liner.
!::lq I e7,_11k"m LvjF±I I L_/ | _ L__:1 _ [o4
i.
Inspect the boiler area to make sure the area is free
from combustible or flammable materials and that
there are not obstructions to the flow of air to the
boiler or combustion air openings to the room.
2.
Make sure there are no signs of abnormal
such as overfilling or leakage.
e) Replace the Front Cleanout Plate, Burner
Mounting Plate, Burner and all Cleanout Cover
Plates on top of the sections. Make sure all
sealing rope and seals are in good condition.
Replace sealing rope if necessary.
f)
Replace all Jacket
Panels.
5.
Inspect the boiler and piping for signs of leaks.
Check to see if there are signs of heavy make-up
water addition to the system.
Be very careful when adding water to a hot boiler,
Add very slowly or, if possible, allow the boiler to
cool naturally before adding water.
6.
When placing boiler into operation, follow Burner
Manual, all instructions supplied with the boiler and
the instructions in this chapter.
If an excessive loss of water occurs, check for a leak
in the piping and correct the problem. Excessive
make-up water will cause corrosion and damage to
the boiler.
7.
Test the operation of all limit controls, float controls
and ignition components as described in Part A,
"Placing Boiler in Operation", of this chapter.
!e]q hVj[o]L_||'lk'd
42
operation,
ILVJF_,Ih_i|_L1F_,IL_[a4
1.
Inspect the burner and pilot flames as for the annual
inspection.
2.
Inspect the boiler and system for any signs of
leakage or excessive make-up water usage.
3.
Inspect and check the operation
system.
of the venting
Table
16:
Series
LC/LCE Boiler
Ratings
-'1_ :11_.'II I(l_J Kil =1 :(011i 1 :tl :q:_ | I_[€_
Gross
l B
Boiler
Model
Number
I=B=R
Output
Mbh
LC-04
547
LC-O5R
LC=05
649
707
LC-06
LC-07
868
1029
LC-08
1189
LC-09
1350
i 4o:3
LC-10
1511
;
LC-11
R Burner Capacity
I B
R Net Ratings
Combustion
Efficiency
Boiler
H.P
Oil
GPH
Gas
MBH
Steam
Sq. Ft
Steam
MBH
Water
MBH
Oil
Gas
16.3
19.4
475
686
1708
410
476
837
81.2
560
808
2029
487
564
83.7
81.2
21.1
6.10
881
2208
530
615
83.7
81.2
25_9
7.50
1077
2713
651
755
83.7
81.1
30.7
35.5
8.80
1273
3217
772
895
83.6
81.1
1020
1469
3717
892
1034
83.6
811
II.60
1664
4250
1020
1174
83.6
81.1
45.1
12.80
1860
4804
1153
1314
83.6
81.1
1672
49.9
14.20
2056
5367
1288
1454
83.6
811
LCd2
1832
54.7
15.60
2252
5917
1420
1593
83.6
811
LCE 13
1966
LCE-14
2125
1700
18.40
2464
2657
6358
6875
1526
1650
1710
1848
83.5
83.5
81.0
81.0
t
i
:
58.7
LCE-15
2284
63,5
68.2
19.80
2850
7388
1773
1986
83.5
81.0
LCE-16
2444
73.0
21.00
3043
7908
1898
2125
83.5
810
LCE 17
2603
77.8
22.50
3236
8421
2021
2263
83.5
81.0
LCE-18
2763
82.5
24.00
3429
8938
2145
2403
83.5
810
LCE-19
2922
87.3
25.00
3622
9454
2269
2541
83.5
81.0
LCE-20
3082
92.1
26.50
3815
9971
2393
2680
83.5
81 0
LCE 21
3256
97.3
LCE-22
3430
4027
4239
10533
11096
2528
2663
2831
2983
836
83.6
81.1
811
LCE-23
3604
1025
107.7
2800
29.50
31.00
4451
11658
2798
3134
83.7
812
LCE 24
3777
112.8
32.50
4663
12217
2932
3284
83.7
812
I Burner input based on No 2 fuel oil with a heating
2 Net I=B-R
water ratings based
3 Net I-B-R
steam ratings based
LCE-13 to LCE-24-1 288.
value of 140,000
of 1.15.
on an allowance
for LC-04 to LC-08=
4 Consult factory before selecting a boiler for installations
systems,etc.
5 Combustion
efficiency
Blu per gallon.
on an allowance
determined
in accordance
1.333, LC-09=1.323,
LC-10=I.310,
having unusual piping and pickup requirements,
with The Hydronics
Instgute's
LC 11-1.298,
such as intermitient
Testing and Rating Standard
for Heating
6O
5O
LC-12-1
290,
system operation,
extensive
piping
Boilers
/
i..
.
J
I
Q..
4O
o
a 30
==
/
/
10
//
//
I
2
6
8
10
12
14
16
18
2O
Coil Flow Rate, GPM
Figure
37: Tankless
Coil Pressure
Drops
43
-IT[,]IIII ::1;] IT_'__
dT_[_._ [_ t_bSl :l_-_]J[O]_
_-_]
Flue
Connection
(_)
4" Supply
(_)
3" Rear
Tappings
Return
(_
3"
Tapping
Intermediate
(_)
3"
(_
Rear
Observation
Tap,
when
Supply
Side
Return,
when
required
Port
required
TOP
®
Maximum
Burner
PowerFlame:
Gordon-piat_:
Length
C = 36"
$4 = 32"
J
R
= 29 =
= 37 _
Webster:
Becket t = J26"= 31"
Cartin
= 26"
Z = t 1f_ excep_whe,e e_eqd=d plate _d
Z
E_end_Flate J_S6 i_ Se_Burne[info_ationmMan_al
t
C
FRONT
Figure
RIGHT SIDE
38: Series LC Dimensional
(_
4" Supply
(_)
3" Rear Return Tapping
(_
3" Side Return Tapping(s)
(_
Rear Observation
(_
REAR
Diagram
Tappings
3" Intermediate
Maximum Burner Length
F
Beckett = 26"
Carlin = 26"
Port
Supply
•
•
Tappings
PowerFlame:
C = 36"
Gordon-Piatt:
R - 37"
Webster:
J = 31"
TOP
G
C
Line
B
FRONT
Figure
44
39:
Series
LCE
RIGHT SIDE
Dimensional
Diagram
REAR
J = 29"
Table 17:
Series
LC/LCE Boiler Dimensions
1-1iI I ,,t-i ,_-TI,%wlI *|',| l ¶ ? t| -d•u , -'*"." LO]_h"
I
Jacket
Boiler
Model
Number
Width
",K'
LC-04
37"
LC-05R
Supply
i Length
i
Height
"C"
"B"
I
'251_d
37"
'
1
31"
63"
2
2
LC-05
37"
31"
63"
LC-06
37"
36¼g'
63"
2
LC-07
37"
41½"
63"
2
LC-08
37"
46%d"
63"
63"
37"
51%"
37"
56%d"
63"
2
37"
61½"
63"
2,1
l
T
LC-12
LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE18LCE-19
LCE 20
LCE-21
LCE-23
LCE-24
37"
37"
37"
37"
37"
37"
37"_
37"
66_0"
_71¾"
_61_6"
T 81%"
L
i 861%6"
! 92½"
97¾d'
' 102¼ _
3T_107Vm"
37"
37"
37"
_
I 122%' _,_
!127_¼_"
*Dimensions
areapproximate
63 _
63"
63"
:
!
63"
63"
63"
63"
63"
63"
3"
i
_
4"
4"
4"
i
2,2
_
2,4
2,4
2,4
2,4
2,4
i
i
T
,
4",3"
4",3"
4",3"
4",3"
4",3"
4",3"
4",3"
4",3"
4",3"
4",3"
s"
5"
5"
6"
6"
6"
6"
, Riser Tapping
End
Sect. I_
Tappings
_
i
I
Locations*
Intermediate
,t
) 21'/1."
]
I_
i
[
i
2"
2½"
2½"
2½"
i
26%"
6"
i
_
i
3"
3"
3"
3"
57%"
62aAa"
I 67¼"
, 72:A_:', _
I 77V,#
!
-
_
_
_
,
_
-
Z
!
=
7
-
-
36V_d'
2015A6 "
26"
26"
] 205A6"
ii 2o_/,o",
25¼g ' _
4"
82½
20 5/16 i 20_Ad ' i
8"
8"
4"
4"
87%0"
92%"
20_Y,o" I 2_Ad' _ 20_Ad" "
20 ¼_•;'
20_Ad ' ] 25Vld'
8"
8"
8"
8"
8"
4"
4"
4"
4"
4"
97:k7'
102:V./'
107%"
112_%."
118¼#
2@_A_('
20'V_d'
20'aA/'
26"
26"
1 18_'_" i
=
I !8'/_"
-
18t/2
,
_
-
q
]
I
18W'
18½"
18W"
18½"
:
181/2,,
20_A6"
20V_d'
20SAd'
20rV_"
20%_"
v
-
20"%_"
20 _/,_"
20V.('
20.%J
18½"
18½"
18½"
Minimum
Height
9,,
31
9.
3,
_812o" p4v_"
9"
3'
18/4
l
10"
3'
10"
3'
!
_8¼"
E"
54w'
54%"
54/81-
181/,*"
18¼"
18¼"
18¼"
18¼"
54V/'
541//'
541/d '
54_"
54_"
10"
3'
12"
3'
12"
3'
12"
3'
18¼"
16"
54¼"
20½"
12"
3'
14"
14"
3'
3'
16" i 20½"
16"
_ 20½"
14"
3'
16"
16"
20½"
20½"
14"
3'
14"
3'
16"
20½"
16"
3,
-
18½"
16"
20V_"
16"
3'
15¼"
18///'
16"
201/z"
16"
3'
15¼"
20 sad'
18½"
16"
20Vz"
16"
3'
181/2 "
16"
20V/'
16"
3'
20_7_d'
26"
18'//'
16"
20V/'
16"
3'
18½"
16"
20½"
16"
3'
-
15¼"
15W'
.
,
Vent
Diameter
'rF'
"D....
18¼"
i
8"
"
_
26"
26"
Location
Burner
Center
G3" i "G4" Line
t
i 18½"
-
7
-
i 31hAd'
! 36'Ym"
41%"
2%,
46_V,d '
/ 3" (2 R_t) I
52"
[ 3" 12net.)
7
Vent
Section Tapping
i
2" ] t! °/1¢'
6"
8"
8"
8"
4",3"
4",3"
4",3"
.
_ _2'_
4"
4",3"
i
2,3
23
Lp iping
t,
3" T
4"
2,1
2,1
_
2,2
2,3
63 H
63"
63"
,t
2
LC-IO
_
Size HeaderEqualizer"0" l "Gr' I "02....
4 / 4
2
16_ + -
2
LC-09
LC-I1
tan
i
Return
Recom.
'
: Risers
63"
Piping
18½"
18½"
181/2"
18½"
'7
o
..
0_
_o_
_-_
'-_
_._.
o-
g
3
.
0
.
g
_
0
25
I
_3i
.
_.-©
21
o
o
z
_
__
_
_5'
ca- r
8
.f
_.('3
L_:I;/-_ If] i_-,_'ii-"]Table
18A:Series
LC Repair
I
Front Section
2
Intermediate Section
3
Intermediate Section
4
Back Section
5
Tapped
Parts
See Table 3 for Stock Code
Intermediate
w/1 '_Tapping
Section
i
' Upper Flow Port Gasket
Lower Flow Port Gasket
2 Required
per Flueway
51671
I Required
per Flueway
51672
4 Required
per Flueway
51721
I
6
[ Tie Rod
I 5/8" Diameter High Temp Rope
13 Feet Required
[ Ceramic
Models LC-04 through
t
i
8
: Ceramic
_ 9
Fiber Base Liner
.
55723
per Flueway
50862
LC-12
.
50854
Fiber Target Wall
51162
I Front € eanou! P!a!e !c.I.
I0
] 5/16" 18 x 11/4"Studs w/Brass Nuts
11
I Steel Cover Plate
12
4 Required
51776
Steel Cover Plate
51777
I
13
I Tankless Heater
Location
I
Specif_ Heater Model Number
16
Rubber Gasket
Specify Quantity
17
3/8"-16 x 3/4" SS Hex Head Cap Screw
Specify Quantity
18
Rear Observation
19
5/16" 18 x 3/41' Hex Head Cap Screw
51800
90923
Assembly
Specify Quantity
Specdy Burner Model
20
I Burner Mounting
21
: 3/8"-16 x 21/4.' Studs with Nuts
Plate
22
i Flame Observation
7 R_'guirQd
90922
Assembly
±
23
24
3 8 -16 x I Studs for Burner Mounting
[ I/4'-20
4 Required
x I/2" Hex Head Machine Screw
4 Required
I
25
I Cleanout
Cover Plate (Steel)
I Required
per Flueway
51772
J
26
0
t
Models LC-06
Rear Flue Box w/12" Flue Outlet
27
, Rear Flue Box Stud 5/16"-18
28
29
Models LC-09. LC-10
x 11/2''
Rear Flue Box Hi Temp Rope, I/4" Diameter
LC-07 and LC-08
LC-II
86041
and LC-12
86042
7 Required
x 65" Long
Side Jacket Panel LC 6000
For Models LC-04 and LC-08
Side Jacket Panel LC-6001
For Models LC-05
Side Jacket Panel LC-6002
For Models LC-06, LC-10. LC-II
Side Jacket Panel LC-6003
For Models LC 07 and LC 12
+
LC-08. LC-09 and LC-10
and LC 12
F
30
[ Left Front Jacket Corner
Panel LC-6011
i
_
Right Front Jacket Corner Panel LC-6010
_2_Upper
Front Jacket Pane! LC-6007
33
! Middle Front Jacket Panel LC-6008
34
i Lower Front Jacket Rail LC 6009
)
35
! Back Jacket Panel LC-6012
36
Side Jacket Panel Support
37
Front Top Jacket Panel LC-6005
Angle LC-6014
47
I;1=]_'-_I.qI ",7_'_
;tl_'_
Table
18B: Series LC Repair
38
Top Jacket Panel LC 6004
Top Jacket
39
48
Panel LC6004
Parts (continued)
For Models LC-04 and LC 08
1
For Modds LC 05. LC 08, LC-09 and LC 10
Top Jacket Panel LC 6004 2
For Models LC-06, LC 10. LC 11 and LC-12
Top Jacket Panel LC-6004-3
For Models LC-07 and LC-12
Rear Top Jacket Panel LC-6006
Single Rib Flue Baffle, Aluminized Steel LC-I018
Specify Boiler Model Number
Triple Rib Flue Baffle, Aluminized Steel LC-I019
Specify Boiler Model Number
Single Rib Flue Baffle, Stainless Steel LC 1020
Specify Boiler Model Number
Triple Rib Flue Baffle, Stainless
Specify Boiler Model Number
Steel LC 1021
t_
II
I-'
Im
O I
l'l
,,.i
m
3
_3t
30
/
4_
_.0
Table
19A:Series
LCE Repair
Parts
See Table 3 for Stock Code
Front Section
2
4
Top Flue Outl#t
intermediate
Sechon
[ntermedlate
Section
Back Sertlon
6
Tapped
_/Tankless
Intermediate
Tapping
Cod Opening
Section
Upper Flow Port Gasket
2 Required per Flueway
51671
Lower Flow Port Gasket
i Required per Flueway
51672
Tie Rod
4 Required per Flueway
51721
13 Feet Required
55723
5/8" Diameter
High Temp Rope
7
Ceramic
Fiber Base Liner
8
Ceramic
Fiber Target Wall
per Flueway
For All LCE Boilers
50862
50854
9
Fiont Cleanout
I0
5/161'-18 x ii/4 Studs w Brass Nuts
11
Steel Cover Plate
12
Steel Cover Plate
13
Tankless Heater Location
I
Specify Heater Model Number
15
Tankless Heater Location
3
Specify Heater Model Number
Plate (C.I,
51162
4 Required
51776
L
16
Rubber Gaskel
Specify Quantity
17
3 8'-16 x 3,4' SS Hex Head Cap Screw
Specify Quantity
18
Rein Obs_rvatlon
]9
5116
18 x 34'
Assembly
Hex Head
90923
Ca]; Screw
Specdy Quantity
Burn_1 Mounting
21
3/8"-16 x 21/4'' Studs with Nuts
22
Front Observation
23
3/8"-16 x I' Studs for Burner Mounting
4 Required
24
1/4"-20 x I/2' Hex Head Machine Screw
4 Required
25
Cleanout
I Required
26
Rear Flue Cover Plate
For All LCE Boilers
27
Real Flue Covel Stud 5 16"-18 x lY2'
5 Required
28
Rear F _e Cover Hi Temp Rope. I 4" Dia. x 65" Long
29
Side Jacket
Panel LC-6000
For Models LCE-13
Bide Jacket
Panel LC-6001
For Models LCE-13 to LCE-15. LCE-17 to LCE-24
Side Jacket
Panel LC-6002
For All LCE Boilers
Plate
Specify Burner Model
7 Required
Assembly
Cover Plate
51777
51800
20
Steell
30
Left Front Jacket Corner Panel LC 6011
31
Right Front Jacket Corner Panel LC-601O
32
Upper Front Jacket Panel LC-6007
33
Middle Front Jacket Panel LC 6008
34
5O
w/1
S_'ctlon
Closed Back
Back Section
5
Inteml#dlat¢,
90922
per Flueway
51772
51131
-17. 20 & -21
I
1__
. Lower Front Jacket Rail LC-6009
35
Rack Jacket Panel LC-6012
36
Side Jacket Panel Support
37
Front Tol: Jacket
38
ToI_ Jacket Panel LC-6004
For Models LCE-12
Top Jacket Panel LC-6004-I
For Models LCE-13 to LCE-15, LCE-17 to LCE-24
Angle LC-6014
Panel LC-6005
-17. -20 & -21
Table
19B:
Series
LCE
Repair
Parts
(continued)
For Models LCE-15, -16, -19, 23 & 24
38
Top Jacket
Panel LC-6004-2
40
Top ,Jacket Panel with Flue Opening
39
Rear Top Jacket Panel LC-6006
41
Top Flue Outlet Plate (14" Flue)
For Models LCE-13 through
Top Flue Outlet Plate (16" Flue)
For Models LCE 18 and Larger
51133
For Top Flue Outlet Plate, 6 Feet
55723
Rope
For All LCE Boilers
LCE-17
51132
42
5/8" Diameter
43
3/81' Diameter Tie Down Assembly
For Top Flue Outlet Plate, 4 Required
51604
44
Draft Damper,
14"
For Models LCE-13 through
90523
Draft Damper,
16"
For Models LCE-18 and Larger
90524
Models LCE-21 through
86113
Baffles
High T_,mperature
LC-6022
LCE 17
LCE-24 Only
51
Series
LC/LCE
Oil,
Gas/Oil
Steam
Gas
Boilers
Installation,
Operation
Maintenance
Manual
TO THE
INSTALLER:
This manua/ is the property
of the owner and must
be affixed
near the boifer for future reference,
TO THE
OWNER:
This
boiler
should
Quafiffed
Service
member
HI Division
be
inspected
annuafly
by
a
Agency.
gama
ASME
of gama
PEERLESS
CAST
PEERLESS
IRON
°
BOILERS
HEATER
COMPANY
231 NORTH WALNUT STREET • BOYERTOWN, PA 19512-1021 • PHONE 610 367 2153
www, peerless-heater.oom
THE
@2002
Peerless
Heater
Company
PREFERRED
HEATING
CHOICE
LC8046 R1 (12/02-1M)
Printed in U.S.A.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 61 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Tue Apr 03 15:23:13 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools