SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors

■ Overview
Thermistor motor protection devices are used for direct monitoring of the motor winding temperature. For this purpose, the motors are equipped with temperature-dependent resistors (PTC)
that are directly installed in the motor winding and abruptly
change their resistance at their limit temperature.

SIRIUS 3RN1 thermistor motor protection

Order No. scheme
1st - 5th
@@@@@
Thermistor motor protection

6th 7th
@

@

8th 9th 10th 11th 12th
–

@

@

@

@

@

Number and version of the sensor circuits

@

RESET response

@

Connection type

@

Type and number of outputs

@

Control supply voltage

@

Protective separation

@

Behavior in the event of voltage failure
Example

@

3RN10

8

Digit of the Order No.

3RN10

0

0

–

1

A

B

0

0

Note:
The Order No. scheme is presented here merely for information
purposes and for better understanding of the logic behind the
order numbers.
For your orders, please use the order numbers quote in the
catalog in the Selection and ordering data.

■ Benefits
• Thanks to direct motor protection, overdimensioning of the
motors is not necessary
• No settings on the device are necessary
• Solid-state compatible output thanks to versions with hard
gold-plated contacts

• Rapid error diagnosis thanks to versions that indicate openand short-circuit in the sensor circuit
• All versions with removable terminals
• All versions with screw terminals or alternatively with innovative spring-type terminals

■ Application
Direct motor protection through temperature monitoring of the
motor winding offers 100 % motor protection even under the
most difficult ambient conditions, without the need to make adjustments on the device. Versions with hard gold-plated contacts
ensure, in addition, a high switching reliability that is even higher
than an electronic control.

ATEX approval for operation in areas subject to explosion
hazard
The SIRIUS 3RN1 thermistor motor protection relay for PTC sensors is certified according to ATEX Ex II (2) G and GD for gases
and dust see www.siemens.com/industrial-controls/atex

Direct motor protection
• At increased ambient temperatures
• For high switching frequency
• For long start-up and braking procedures
• Used together with frequency converters (low speeds)

Siemens IC 10 · 2011

8/103

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors
Motor protection using current- and temperature-dependent
protective devices

Application

Motor protection
Only currentdependent,
e.g. with
overload relay

Only temperature-dependent,
e.g. with
thermistor motor
protection relay

Currentand
temperaturedependent

Overloading in
uninterrupted duty

✓

✓

✓

Long start-up and braking
operations

❍

✓

✓

Irregular intermittent duty

❍

✓

✓

Excessively high switching
frequency

❍

✓

✓

Single-phase operation and ✓
current unbalance

✓

✓

Voltage and frequency
fluctuations

✓

✓

✓

Stalling of the rotor

EN 60204 and IEC 60204 stipulate that motors must be protected from overheating at a rating of 0.5 kW and higher. The
protection can take the form of overload protection, overtemperature protection or current limiting.
For motors with frequent starting and braking and in environments where cooling may be impaired (e.g. by dust), it is recommended to use the overtemperature protection option in the form
of a protective device coordinated with this mode of operation.
A good choice in this case is the use of 3RN1 thermistor motor
protection devices.
On rotor-critical motors, overtemperature detection in the stator
windings can lead to delayed and hence inadequate protection.
In this case the standards stipulate additional protection, e.g. by
means of an overload relay.
This combination of thermistor motor protection and an overload
relay is recommended for full motor protection in case of frequent starting and braking of motors, irregular intermittent duty
or excessive switching frequency. To prevent premature tripping
of the overload relay in such operating conditions, a higher setting than that normally required for the operational current is chosen. The overload relay then performs the stall protection, and
the 3RN1 thermistor motor protection device monitors the temperature of the motor windings.

Motor protection in case of

✓

✓

✓

Switching on a stalled rotor ✓
of a stator-critical motor

✓

✓

Switching on a stalled rotor ✓
of a rotor-critical motor

❍

✓

Elevated ambient
temperature

--

✓

✓

Impeded cooling

--

✓

✓

✓ Full protection
❍ Conditional protection

8

-- No protection

■ Technical specifications
The 3RN1 tripping units are suitable for use in any climate and
finger-safe according to EN 50274.
They comply with:
• EN 61000-6-2 and EN 61000-6-4
"Electromagnetic compatibility of I&C equipment in industrial
process engineering"
• EN 60947-8
The terminals of the auxiliary contacts are designated in accordance with EN 50005.
The 3RN1 tripping units are suitable for snap-on mounting onto
TH 35 standard mounting rails according to EN 60715 or for
screw mounting using an adapter (Accessories).
Any mounting position is possible.
For devices with the "Manual RESET" function, the test function
can be activated and a trip simulated by pressing the blue
Test/RESET button for > 2 seconds.
If a Type A temperature sensor is connected to a Type A tripping
unit, compliance with the operating temperatures is assured (on
pick-up and reset) according to IEC 60034-11-2 (EN 60947-8).

8/104

Siemens IC 10 · 2011

4000
R

1330
550
250

20
-20°C 0

NSB0_00320

TNF-20 TNF TNF+15 T
TNF-5 TNF+5

Characteristic curve of the 3RN1 release

The characteristic curves of the Type A temperature sensors are
described in EN 60947-8, DIN 44081 and DIN 44082.

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors
Use in areas subject to explosion hazard for gases

Note:

All devices are approved for Equipment Group II, Category (2)
in Area "G" (areas that contain explosive gases, vapor, spray and
air mixtures).

Tripping of the thermistor motor protection relay even in combination with a converter must directly result in disconnection. This
must be implemented with circuitry.

With PTB 01 ATEX 3218 ex II (2) G, compliance with directive
94/9 EC Appendix II is confirmed. The safety devices must be
selected with suitable settings for the safe operation of motors of
the "Increased safety" (EEx e) and "Flameproof enclosure"
(EEx d) degrees of protection and are used outside the area subject to explosion hazard.

Mounting and installation must only be performed by qualified
personnel who observe the applicable regulations! For mounting, use the mounting instructions
Order No.: 3ZX1012-0RN10-1AA1.

The increased danger in areas subject to explosion hazard demands careful analysis of the operator's guide, the safety and
commissioning instructions and the standard (EN 60079-14 /
VDE 0165) for electronic equipment in areas subject to gas explosion hazards.
A risk analysis must be performed for the complete plant or machine. If this risk analysis results in a minimal potential for danger
(Safety Category 1), all 3RN1 TMS releases can be implemented
taking into account the safety notes. In the case of plants or machines with a high potential risk, versions with integrated shortcircuit detection in the sensor circuit are necessary.
Use in areas subject to explosion hazard for dust
PTB 01 ATEX 3218 ex II (2) GD
3RN10 11-.B/-.G, 3RN10 12-.B/-.G and 3RN10 13-...0 tripping
units can be used as protective devices for motors in areas subject to gas explosion hazard for protection against impermissible
overheating due to overload. If the ATEX marking has the extension "D:=Dust", these units can also be used as protective devices for motors in areas subject to dust explosion hazard
(EN 50281-1-1).
Additional information is provided in the EC prototype test certificate which can be obtained from the Internet. The units comply
with the requirements of the following classes:
Device

Class

3RN10 00, 3RN10 10, 3RN10 11-.C,
3RN10 12-.C, 3RN10 22, 3RN10 62

EN 954-1: Category 1

3RN10 11-.B, 3RN10 11-.G,
3RN10 12-.B, 3RN10 12-.G,
3RN10 13

EN 954-1: Category 2

For tripping units with a 24 V AC/DC control voltage, electrical
separation must be secured with a battery network or a safety
transformer to EN 61558.
When releases with Auto-RESET function are used, a reset is
performed automatically after the cooling time has expired. It
must be ensured by means of an external interlock (latching with
a separate ON and OFF button) that the machine to be monitored does not start up again spontaneously.
Units with the "Auto-RESET" function must not be used in applications in which the unexpected restart can lead to personal injury or property damage.
In the case of releases without short-circuit detection, during
commissioning or after modifications or maintenance work (assembly, disassembly) on the equipment, the sensor resistance
must be measured using a suitable measuring device. For resistances of < 50 Ω the sensor circuit must be checked for a
short-circuit.
If 3RN10 00 units are used to protect EEx e motors, separate
monitoring of the control voltage is recommended because there
is no Ready LED to indicate connection to the supply voltage.
If 3RN10 13-.BW01 unit are used to protect EEx e motors,
separate monitoring of the control voltage is recommended because the switching state of the auxiliary contacts does not
change if the control voltage fails (use of a bistable relay is
recommended).
Before commissioning, the effectiveness of the protection function must be checked.

The measuring circuit leads must be routed as separate control
cables. It is not permitted to use cores from the supply line of the
motor or any other main supply cables. If extreme inductive or
capacitive interference is expected as a result of power lines
routed in parallel, shielded control cables must be used.
Cable routing
Maximum cable length for sensor circuit cables
Conductor
cross
section

Cable length for releases
Without short-circuit detection
3RN10 00, 3RN10 10,
3RN10 11-.C, 3RN10 12-.C,
3RN10 22, 3RN10 62

With short-circuit detection1)
3RN10 11-.B/-.G,
3RN10 12-.B/-.G,
3RN10 13

mm2

m

m

2.5

2 x 2800

2 x 250

1.5

2 x 1500

2 x 150

0.5

2 x 500

2 x 50

1)

A short-circuit in the sensor circuit will be detected up to this maximum
cable length.

Siemens IC 10 · 2011

8/105

8

PTB 01 ATEX 3218 ex II (2) G

The 3RN10 is not intended for installation in hazardous areas.
For installation in areas subject to explosion hazards, the 3RN10
must be enclosed in a flameproof casing.

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors
Principle of operation

3RN10 62 releases for multiple motor protection

The 3RN1 releases operate in accordance with the closed-circuit principle and therefore monitor themselves for open circuit
(except: warning output in the case of 3RN10 22). A momentary
voltage failure of less than 50 ms does not change the status of
the auxiliary contacts. The 3RN10 11, 3RN10 12 and 3RN10 13
units with 2 changeover contacts are also equipped with shortcircuit detection in the sensor circuit. The unit will trip in the event
of a short-circuit in the sensor circuit (resistance in sensor circuit
< 20 Ω).

Up to 6 sensor circuits can be connected to the 3RN10 62 release, all of which act on one output relay. The simultaneous protection of several motors (up to 6) is an advantage for multi-motor drives (e.g. if one motor is overloaded, all the other motors of
the drive will be shut down). Apart from the red LED "TRIPPED",
which signals the switching state of the release, a LED is assigned to each sensor circuit which indicates the sensor circuit
that has responded. Unused sensor circuits must be
short-circuited.

All tripping units (except for 24 V AC/DC) feature electrical separation between the control circuit and the sensor circuit.
3RN10 00 compact releases

The reset response of the 3RN10 62 releases can be changed
from Manual RESET to Auto-RESET by linking terminals Y1 and
Y2. Remote-RESET is implemented by connecting an external
pushbutton with a normally-open function.

The compact release is equipped with a red LED (TRIPPED) for
the tripped indicator and a changeover contact.

Response of the releases
in the event of control voltage failure

After the unit has tripped, it is automatically reset once the
thermistors have cooled down. The root of the changeover contact is connected to the control voltage (95 is connected to
terminal A1).
This unit is particularly suitable in circuits in which the control circuit and signaling circuit have the same potential, e.g. in local
control cabinets.

8

3RN10 10, 3RN10 11, 3RN10 12, 3RN10 13 standard releases
The standard devices are equipped with two LEDs (READY and
TRIPPED) for an operating and tripped display and are available
with either 1 NO + 1 NC or with 2 CO contacts. They are available
depending on the version with Auto-RESET (3RN10 10), Manual/Remote-RESET (3RN10 11) or Manual/Auto and RemoteRESET (3RN10 12 and 3RN10 13). Remote-RESET can be
achieved by connecting an external pushbutton with a normallyopen function to terminals Y1 and Y2. If terminals Y1 and Y2 are
bridged, tripping will be followed by an Auto-RESET.

Behavior

Monostable
3RN10 00,
3RN10 10,
3RN10 11

Non-volatile,
monostable
3RN10 12,
3RN10 13-....0,
3RN10 22,
3RN10 62

Bistable
3RN10 13-...01

In case of failure
of the control
voltage

Device trips

Device trips

No change in
switching state of
the auxiliary
contacts

In case of return
of the control
voltage without a
preceding tripping operation

Device resets

Device resets

No change in
switching state of
the auxiliary
contacts

In case of return
of the control
voltage after a
preceding tripping operation

Device resets

The device
remains tripped

No change in
switching state of
the auxiliary
contacts

The 3RN10 11, 3RN10 12 and 3RN10 13 units with 2 COs also
have short-circuit monitoring in the sensor circuit.
The 3RN10 12 and the 3RN10 13 are non-volatile. This means
that even if the control supply voltage fails, a trip preceding it will
be latched.
In the case of the 3RN10 13 release, tripping due to a short-circuit in the sensor circuit will be indicated by a flashing red LED.
The monostable version also indicates open circuit in the sensor
circuit by flashing of the red LED.
3RN10 22 "Warning and disconnection" releases
Two sensor circuits can be connected to one 3RN10 22 release
that acts on one output relay with 1 NO contact for warning and
1 CO for disconnection. Temperature sensors with different rated
response temperatures TNF are used to implement the "Warning" and "Disconnection" functions. When the "Warning" sensor
circuit responds, a yellow LED is lit and when the "Disconnection" circuit responds, a red LED is lit.
The sensor circuits have a different reset response and operating behavior:
• "Warning" (terminals 2T1, T2) only features Auto-RESET and
uses the open-circuit principle.
• "Disconnection" (terminals 1T1, T2) can be changed from
Manual RESET to Auto-RESET by linking terminals Y1 and Y2.
Remote-RESET is implemented by connecting an external
pushbutton with a normally-open function.

8/106

Siemens IC 10 · 2011

Protective separation
All circuits (outputs, control circuits, sensor and RESET circuits)
of the multifunction tripping units 3RN10 13-1BW10 and 3RN10
13-1GW10 (wide voltage range, monostable output relay and
screw connection) are safely isolated from each other up to a
rated voltage of 300 V according to DIN VDE 0100 Part 410
(IEC 60364-4-41 modified) and EN 60947-1.

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors
Function diagrams
3RN10 13-.BW01

3RN10 00, 3RN10 10 (Auto-RESET)

NSB0_00316a
NSB0_00314b

A1/A2
3800
1500
T1/T2
RESET
(Y1/Y2)

A1/A2
3800
1500
T1/T2
K

K

LED Tripped

3RN10 11

LED Tripped

1)

3RN10 13-...00
NSB0_00315c

NSB0_00318a

A1/A2
3800
1500
T1/T2
(Y1/Y2)

A1/A2
3800
1500
T1/T2
RESET
(Y1/Y2)

K

K

LED Tripped

LED Tripped

3RN10 12/3RN10 22/3RN10 62

1)

3RN10 22 only
NSB0_00317a

A1/A2
3800
1500
T1/T2
RESET
(Y1/Y2)

NSB0_00319b

8

3800
1500
2T1/T2
K1

K, K2

LED alarm

LED Tripped
1)

For versions with 2 CO and short-circuit detection in the sensor circuit see
function diagram 3RN10 13.

Compact
units

Standard devices

3RN10 00

3RN10 10

3RN10 11

3RN10 12

Multifunction
units

Warning +
tripping

Multiple motor
protection

3RN10 13

3RN10 22

3RN10 62

mm
mm

22.5 x 83 x 91
22.5 x 84 x 91

45 x 83 x 91
45 x 84 x 91

mm
mm

22.5 x 92 x 91
22.5 x 94 x 91

---

mm
mm

22.5 x 102 x 91
22.5 x 103 x 91

45 x 106 x 91
45 x 108 x 91

D

Dimensions (W x H x D)
• For 2 terminal blocks
- Screw terminals
- Spring-type terminals
• For 3 terminal blocks
- Screw terminals
- Spring-type terminals
• For 4 terminal blocks
- Screw terminals
- Spring-type terminals

H

Type

W

General data
Number of connectable sensor circuits

1

Response in the event of control voltage failure

See page 8/106

Manual RESET

--

✓

Auto-RESET

✓

--

✓

Remote-RESET

--

✓1)

✓

TEST pushbutton

--

✓

Short-circuit detection for sensor circuit

--

✓ (for 2 CO units)

Short-circuit and open-circuit indication

--

Warning and disconnection in one unit

--

Permissible ambient temperature
• During operation

°C

2

✓

--

✓2)

-✓

6

--

-25 ... +60

✓ Function is available

-- Function is not available
1)

Remote-RESET possible by disconnecting control voltage.

2)

Open circuits are only indicated by monostable versions
(3RN10 13-....0).

Siemens IC 10 · 2011

8/107

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors
Type

Compact
units

Standard devices

3RN10 00

3RN10 10

3RN10 11

3RN10 12

Multifunction
units

Warning +
tripping

Multiple motor
protection

3RN10 13

3RN10 22

3RN10 62

Releases
Rated insulation voltage Ui (pollution degree 3)

V

300
Screw terminals

Connection type
•
•
•
•
•

Terminal screw
Solid
Finely stranded with end sleeve
AWG cables, solid or stranded
Tightening torque

mm2
mm2
AWG
Nm

M3 (for standard screwdriver, size 2 and Pozidriv 2)
1 x (0.5 ... 4)/2 x (0.5 ... 2.5)
1 x (0.5 ... 2.5)/2 x (0.5 ... 1.5)
2 x (20 ... 14)
0.8 … 1.2
Spring-type terminals

Connection type
• Solid
• Finely stranded, with end sleeves according to
DIN 46228
• Finely stranded
• AWG cables, solid or stranded

mm2
2

mm

2 x (0.25 ... 1.5)
2 x (0.25 ... 1.5)

mm2
AWG

2 x (0.25 ... 1.5)
2 x (24 ... 16)

Sensor circuit
Measuring circuit load at RF ≤ 1.5 mW

≤5

Voltage in sensor circuit at RF ≤ 1.5 mW

V

≤2

Response temperature (depends on sensor)

°C

60 ... 180

Coupling time (depends on sensor)

s

About 5

Summation PTC resistance RF (per sensor loop)

kΩ

≤ 1.5; response value 3.4 ... 3.8; return value 1.5 ... 1.65

Response tolerance

°C

±6

8

Control circuit
Rated control supply voltage Us

See page 8/110

Operating range
• 110/230 V AC
• 24 ... 240 V AC/DC
• 24 V AC/DC

0,85 ... 1.1 x Us
0,85 ... 1.1 x Us
0.85 ... 1.2 x Us for DC operation, 0.85 ... 1.1 x Us for AC operation

Rated power AC/DC

W

<2

Conventional thermal current Ith

A

5

Rated operational current Ie
• AC-15/240 V
• DC-13/24 V

A
A

3
1

DIAZED fuse

A

61)

V
V

300
300

Auxiliary circuit

CSA and UL rated data, control circuit
Rated control voltage 50/60 Hz
• AC
• DC
Switching capacity

R 300/B 300

Protective separation up to 300 V
according to DIN 60947-1

--

1)

In > 1 kA weld-free according to EN 60947-5-1.

8/108

Siemens IC 10 · 2011

3RN10 131BW10,
3RN10 131GW10

--

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors
Circuit diagrams
Illustrated with Illustrated with
control voltage control voltage
not applied applied

3RN10 00, 1 CO

A1/95

A1(11)

N H2 K
A2

T1 T2

96 98

(14) (12)

NSB0_00322b

3RN10 10, 1 NO + 1 NC

3RN10 10, 2 COs

A1

H1

(13) (21)

A2

96 98

T/R

(14) (22)
NSB0_00323b

3RN10 111), 1 NO + 1 NC

N
T1 T2

95 97

(13) (21)

96 98

(14) (22)

96 98 06 08

H1
T1 T2

NSB0_00323b

3RN10 121), 1 NO + 1 NC

Legend for 3RN10

A1
N

T/R

95

05

(11)

(21)

H2 K

A2

96 98 06 08

95 97

(13) (21)

96 98

(14) (22)

Legend for 3RN10 22

N

T/R

NSB0_00325a

T1 T2

95

05

(11)

(21)

N
T1 T2

96 98 06 08

T/R

(14) (12) (24) (22) K2
NSB0_01399a

1T1 and T2
2T1 and T2

95

05

(11)

(21)

Close unconnected sensor circuits.

96 98 06 08

(14) (12) (24) (22)

Legend for 3RN10 62

NSB0_01400

T/R

H1 to H6
H7
H8
K
1T1, 1T2
to
6T1, 6T2

3RN10 13-...1 (bistable)

Y1 Y2 A1
H1
N
T1 T2

95

05

(11)

(21)

H2 K

A2

96 98 06 08

(14) (12) (24) (22)
. Important!

Close unconnected sensor circuits.

3RN10 22

Y1 Y2 A1
H3
H2
N

K1

LED of the tripped
sensor loop
LED "READY"
LED "TRIPPED"
Output relay
Terminals of the
1st sensor loop
Terminals of the
6th sensor loop

NSB0_00327

T/R

07(23)

LED "READY"
LED "TRIPPED"
LED "ALARM"
Output relay
for warning threshold
(LED "ALARM")
Output relay for disconnect (LED "TRIPPED")
Terminals of the
sensor loop

. Important!

H2 K

A2

H1
H2
H3
K1

H2 K

A2

3RN10 13-...0 (monostable)

Y1 Y2 A1
H1

LED "READY"
LED "TRIPPED"
Output relay
Terminals of
the sensor loop

NSB0_01398

Y1 Y2 A1
H1

H2 K

A2

H1
H2
K
T1, T2

(14) (12) (24) (22)

T/R
3RN10 12, 2 COs

Y1 Y2 A1(A3)
H1
N

05

H2 K

A2

H2 K

A2

T1 T2

N
T1 T2

95

3RN10 11, 2 COs

A1

H1

A1

H1

H2 K

N
T1 T2

95 97

Illustrated with General legend
control voltage
not applied
A1, A2 , A3 Terminals of the
control voltage
N
Amplifier
T/R
TEST/RESET button
Y1, Y2
Terminals for
Remote-RESET
(jumpered =
Auto-RESET)
⇑
The double arrow
indicates an operating
state of the contact
according to
(11)
(21)
DIN 40900, Part 7 which
deviates from the norm
(here: Position of the
contacts when control
voltage is applied to
(14) (12) (24) (22)
NSB0_01397
terminals A1 and A2)

N

08(24) 2T1 1T1 T2

(11)

H1 K2
A2

T/R

95

96 98

(14) (12)

NSB0_00328c

3RN10 62

Y1 Y2
H1 2 3
H4 5 6
1T1 1T2 2T1 2T2 3T1 3T2 4T1 4T2 5T1 5T2 6T1 6T2
T/R
1)

A1

N

H7H8
A2

95 97

(13) (21)

K
96 98

(14) (12)

NSB0_00329a

For units with combination voltages 230/110 V AC (3RN10 11-.CK00 and
3RN10 12-.CK00) A1 and A2 apply: 230 V AC, A3 and A2: 110 V AC.

Siemens IC 10 · 2011

8/109

8

Illustrated with
control voltage
applied

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors

■ Selection and ordering data
• For monitoring the motor winding temperature using temperature-dependent resistors (PTCs, type A) that are directly installed in the motor winding by the manufacturer
• Monostable versions with closed-circuit principle, i.e. relays
respond in the event of control supply voltage failure
• 3RN10 13-.BW01: Bistable version, does not trigger in the
event of control supply voltage failure
• All devices with PTB01 ATEX approval for dust or gas
see www.siemens.com/industrial-controls/atex
• All devices except for 24 V AC/DC feature electrical
separation
• Versions with safe isolation up to 300 V according to EN 61140
• Non-volatile versions
RESET

Contacts

• Versions with short-circuit and open-circuit detection in sensor
circuit
• Versions with solid-state compatible contacts with hard
gold-plating
• Versions for up to 6 sensor circuits
• Versions with Manual-RESET, Remote-RESET, Auto-RESET
and test button
• Terminal labeling according to DIN 50005
• All terminals are removable
• Width 22.5 mm (45 mm on version for several sensor circuits)
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
DT

Rated control supply
voltage Us 50/60 Hz

DT

Screw terminals
Order No.

Price
per PU

V

Spring-type
terminals
Order No.

Price
per PU

Compact signal evaluation units, width 22.5 mm, 1 LED
Terminal A1 is jumpered with the root of the CO contact
Auto
1 CO
24 AC/DC
110 AC
230 AC

}
A
}

3RN10 00-1AB00
3RN10 00-1AG00
3RN10 00-1AM00

A
B
B

3RN10 00-2AB00
3RN10 00-2AG00
3RN10 00-2AM00

Standard evaluation units, width 22.5 mm, 2 LEDs

8

Auto

3RN10 11-1BB00

1 NO + 1 NC

24 AC/DC
110 AC
230 AC
24 … 240 AC/DC

}
}
}
}

3RN10 10-1CB00
3RN10 10-1CG00
3RN10 10-1CM00
3RN10 10-1CW00

}
A
A
A

3RN10 10-2CB00
3RN10 10-2CG00
3RN10 10-2CM00
3RN10 10-2CW00

2 CO

24 AC/DC
110 AC
230 AC

A
A
A

3RN10 10-1BB00
3RN10 10-1BG00
3RN10 10-1BM00

A
C
A

3RN10 10-2BB00
3RN10 10-2BG00
3RN10 10-2BM00

2 CO, hard
gold-plated

24 AC/DC

A

3RN10 10-1GB00

C

3RN10 10-2GB00

24 AC/DC
110/230 AC

}
}

3RN10 11-1CB00
3RN10 11-1CK00

A
A

3RN10 11-2CB00
3RN10 11-2CK00

A
A
A

3RN10 11-1BB00
3RN10 11-1BG00
3RN10 11-1BM00

A
C
A

3RN10 11-2BB00
3RN10 11-2BG00
3RN10 11-2BM00

Manual/Remote1) 1 NO + 1 NC

Short-circuit detection for sensor circuit
Manual/Remote1) 2 CO
24 AC/DC
110 AC
230 AC
2 CO, hard
gold-plated

24 AC/DC

A

3RN10 11-1GB00

A

3RN10 11-2GB00

1 NO + 1 NC

24 AC/DC
110/230 AC

}
}

3RN10 12-1CB00
3RN10 12-1CK00

A
A

3RN10 12-2CB00
3RN10 12-2CK00

A
A
A

3RN10 12-1BB00
3RN10 12-1BG00
3RN10 12-1BM00

C
C
C

3RN10 12-2BB00
3RN10 12-2BG00
3RN10 12-2BM00

A

3RN10 12-1GB00

C

3RN10 12-2GB00

Non-volatile2), short-circuit and open-circuit detection and indication in sensor circuit; wide-range voltage with screw terminal
with safe isolation
Manual/Auto/
2 CO
24 AC/DC
}
Remote
24 … 240 AC/DC
}

3RN10 13-1BB00
3RN10 13-1BW10

A
A

3RN10 13-2BB00
3RN10 13-2BW00

A

3RN10 13-1GW10

C

3RN10 13-2GW00

}

3RN10 22-1DW00

A

3RN10 22-2DW00

}

3RN10 62-1CW00

A

3RN10 62-2CW00

}

3RN10 13-1BW01

A

3RN10 13-2BW01

2)

Non-volatile
Manual/Auto/
Remote

2)
3RN10 13-1BB00 Non-volatile , short-circuit detection in sensor circuit
Manual/Auto/
2 CO
24 AC/DC
Remote
110 AC
230 AC

2 CO, hard
gold-plated

2 CO, hard
gold-plated

3RN10 12-2CK00

24 AC/DC

24 … 240 AC/DC

Evaluation units for 2 sensor circuits, warning and disconnection,
width 22.5 mm, 3 LEDs
Test/RESET button, non-volatile2)
Manual/Auto/
1 NO + 1 CO
Remote

24 … 240 AC/DC

Evaluation units for 6 sensor circuits, multiple motor protection,
width 45 mm, 8 LEDs
Test/RESET button, non-volatile2)
Manual/Auto/
1 NO + 1 NC
Remote

24 … 240 AC/DC

Bistable evaluation units, width 22.5 mm
Test / RESET button, non-volatile2), short-circuit and open-circuit detection and indication in sensor circuit
Manual/Auto/
2 CO
24 … 240 AC/DC
Remote
1)

The unit can be reset with the RESET button or by disconnecting the control supply voltage.

8/110

Siemens IC 10 · 2011

2)

For protection against voltage failure see note on Technical Information on
page 8/1.

* You can order this quantity or a multiple thereof.
Illustrations are approximate

© Siemens AG 2010

SIRIUS 3RN1 Thermistor Motor Protection
For PTC sensors

■ Accessories
Use

Version

DT

Order No.

For 3RN1

Unit labeling plates
For SIRIUS devices

For 3RN1

Inscription labels for sticking
For SIRIUS devices

Price
PU
per PU (UNIT,
SET,
M)

PS*

PG

D

3RT19 00-1SB20

100

340 units

101

19 mm x 6 mm, pastel turquoise
19 mm x 6 mm, zinc yellow

C

3RT19 00-1SB60

100

3060 units

101

C

3RT19 00-1SD60

100

3060 units

101

Push-in lugs
For screw fixing,
2 units are required for each device

}

3RP19 03

1

10 units

101

1

1 unit

101

Blank labels

NSB0_01429b

20 mm x 7 mm, pastel turquoise1)

3RT19 00-1SB20

Push-in lugs
For 3RN1
3RP19 03

Tools for opening spring-type terminals by hand
For auxiliary
circuit
connections

3RA29 08-1A

3.0 mm x 0.5 mm, length approx. 200 mm,
titanium gray/black, partially insulated

Spring-type
terminals
A

3RA29 08-1A

PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
www.murrplastik.de

8

1)

Screwdrivers
For all SIRIUS devices with spring-type
terminals

* You can order this quantity or a multiple thereof.
Illustrations are approximate

Siemens IC 10 · 2011

8/111



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : Siemens AG
Create Date                     : 2012:01:02 12:42:10+02:00
Modify Date                     : 2012:01:02 12:42:18+02:00
Subject                         : SIRIUS Industrial Controls
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Metadata Date                   : 2012:01:02 12:42:18+02:00
Creator Tool                    : PScript5.dll Version 5.2.2
Format                          : application/pdf
Title                           : Catalog IC 10 English 2011
Description                     : SIRIUS Industrial Controls
Creator                         : Siemens AG
Document ID                     : uuid:de931c77-23dc-497d-b76d-c643bb6e396e
Instance ID                     : uuid:c122a34d-78dd-406f-b172-1dea143ea161
Producer                        : Acrobat Distiller 8.2.2 (Windows)
Page Count                      : 9
EXIF Metadata provided by EXIF.tools

Navigation menu