Schneider Electric DIGEST 175 Metering Equipment Brochure
551171-Brochure 551171-Brochure 551171-Brochure 785901 Batch5 unilog cesco-content
102577-Brochure 102577-Brochure 102577-Brochure 785901 Batch6 unilog cesco-content
648220-Attachment 648220-Attachment 648220-Attachment 785901 Batch5 unilog cesco-content
2014-06-03
: Pdf 102621-Brochure 102621-Brochure 785901 Batch4 unilog
Open the PDF directly: View PDF .
Page Count: 16
- Metering_Equipment.pdf
- Table of Contents
- Metering Equipment
- Meter Sockets
- Meter Sockets
- Meter Sockets
- MP Meter-PakTM Meter Centers
- EZ Meter-Pak® Meter Centers
2-1
© 2009 Schneider Electric
All Rights Reserved
2METERING EQUIPMENT
Table of Contents
Section 2
Metering Equipment
Individual Meter Socket
Page 2-2
MP Meter-Pak Metering Equipment
Page 2-5
EZ Meter-Pak Metering Equipment
Page 2-8
Meter Sockets
Ring and Ringless Type Individual Meter Sockets 2-2
Horizontal Ganged, Test Block Bypass Sockets and Accessories 2-3
Dimensions 2-4
MP Meter-PakTM Meter Centers
Ring and Ringless Devices 2-5
Tenant Circuit Breakers and Accessories 2-6
Dimensions 2-7
EZ Meter-Pak® Meter Centers
Indoor/Rainproof Meter Center Information 2-8
Selection Information 2-9
Indoor/Rainproof Meter Center 2-10
Branch Devices 2-11
Main Devices 2-12
Branch Devices 2-13
EZM Main Devices 2-14
EZ Meter-Pak® Meter Centers and Accessories 2-15
Dimensions 2-16
New!
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2-2 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
2METERING EQUIPMENT
Meter Sockets Ring and Ringless Type Individual Meter Sockets
Class 4131
•Available single or three phase, 600 Vac max., with and without horn or lever bypass, overhead and underground
service feed.
•10 kA short circuit current rating (or higher with utility approval).
•UL Listed, NEMA 3R enclosure.
•Units supplied with bonded neutral.
•Units supplied with hub opening in top endwall require the use of a bolt-on hub, or closing plate.
•Units supplied with solid top are for underground feed only.
•Accessories, refer to page 2-3.
This metering is generally utility specific. Always check with local utility company before installing. Contact
your nearest Field Sales Office for additional catalog numbers, if required by utility.
aDevice requires approval from the serving utility, consult your nearest Square D/Schneider Electric sales office.
bOrder appropriate bolt-on hub or closing plate separately and install on TOP endwall.
cDevice supplied with 1-1/4 in. bolt-on hub (Cat.No. A125) mounted on TOP endwall.
dDevice supplied with solid top endwall (without hub opening).
eWhen unit is installed for underground feed, the appropriate closing plate must be ordered separately and installed over hub opening in TOP endwall of
device.
fDevice supplied with closing plate ACP mounted on TOP endwall.
gDevice supplied with two closing plates ACP mounted in TOP endwall.
hContains “Duquesne Light Co.” approved label.
iOrder lugs separately, refer to accessories, page 2-3.
jRating is continuous.
Table 2.1: Individual Meter Sockets
Ampere
RatingjJaw
Qty. Service
Type Cat. No.a$ Price
Lug Wire Range (Al/Cu) Enclosure Information Box No.
see
page 2-4
Line, Load,
and Neutral
(AWG/kcmil)
Wire
Binding Gnd.
(AWG) Material
Top Endwall Conf.
Hub
OpeningbClosing
Plateb
Ringless Type, 1Ø3W 600 Vac Max., Without Bypass or Jaw Release
125 4 UG UTZRS101Ad123.00 8–2/0 1/2 in. Hex 14–2 Steel Solid Topd—1R
125 4 OH UTRS101B 123.00 8–2/0 Slotted 14–2 Steel Series A ACP 1R
125 4 OH UATRS101B 137.00 8–2/0 Slotted 14–2 Aluminum Series A ACPA 1R
125 4 OH URS101BCPL 135.00 8–2/0 Slotted 14–2 Steel Series A ACP 1R
125 5 OH/UG 1003880Ae161.00 8–2/0 Slotted 14–2 Steel Series A ACP 1R
200 4 OH UTRS202B 177.00 8–250 1/2 in. Hex 14–2 Steel Series A ACP 3R
200 4 OH UATRS202B 195.00 8–250 1/2 in. Hex 14–2 Aluminum Series A ACPA 3R
200 4 UG UTRS213Ad212.00 1/0–350 1/2 in. Hex 14–2 Steel Solid Topd—5R
200 4 OH/UG UTRS213Be212.00 1/0–350 1/2 in. Hex 14–2 Steel Series A ACP 5R
200 4 OH/UG UATRS213Be225.00 1/0–350 1/2 in. Hex 14–2 Aluminum Series A ACPA 5R
200 4 OH/UG U92197CCCPLg240.00 1/0–350 1/2 in. Hex 14–2 Steel (2)Series A (2)ACPg7R
Ringless Type, 1Ø3W 600 Vac Max., With Horn Bypass, Without Jaw Release
125 4 OH/UG UHTRS101B 161.00 8–2/0 Slotted 14–2 Steel Series A ACP 1R
125 5 OH UGHTRS101Lc161.00 8–2/0 Slotted 14–2 Steel A125 c —1R
125 4 OH URS101BDQh138.00 8–2/0 1/2 in. Hex None Steel Series A ACP 1R
125 5 OH/UG UGHTRS111Cf207.00 8–2/0 Slotted 14–2 Steel Series A ACP f4R
200 4 OH/UG UBHMRS212Be210.00 8–250 1/2 in. Hex None Steel Series A ACP 4R
200 4 OH UHTRS202B 206.00 8–250 1/2 in. Hex 14–2 Steel Series A ACP 3R
200 4 OH/UG UHTRS212Be206.00 8–250 1/2 in. Hex 14–2 Steel Series A ACP 4R
200 4 OH/UG UHTRS213Be213.00 1/0–350 1/2 in. Hex 14–2 Steel Series A ACP 5R
200 4 UG UHTRS223Ad272.00 1/0–350 1/2 in. Hex 14–2 Steel Solid Topd—2R
200 4 UG URS212ADQdh 203.00 8–250 1/2 in. Hex None Steel Solid Topd—4R
Ringless Type, 1Ø3W 600 Vac Max., With Lever Bypass and Jaw Release
200 4 OH UTH4203T 465.00 6–350 1/2 in. Hex 14–2 Steel Series A-L ACPL 8R
200 4 OH/UG UTH4213Te479.00 6–350 1/2 in. Hex 14–2 Steel Series A-L ACPL 9R
200 5 OH UTH5203T 494.00 6–350 1/2 in. Hex 14–2 Steel Series A-L ACPL 8R
200 5 OH/UG UTH5213Te564.00 6–350 1/2 in. Hex 14–2 Steel Series A-L ACPL 9R
320 4 OH/UG UTH4330Tei 749.00 Studs Only 3/8 in. dia. studs 14–1/0 Steel Series A-L ACPL 11R
Ringless Type, 3Ø4W 600 Vac Max., With Lever Bypass and Jaw Release
200 7 OH/UG UTH7213Te666.00 6–350 1/2 in. Hex 14–2 Steel Series A-L ACPL 9R
320 7 OH UTH7300Ti830.00 Studs Only 3/8 in. dia. studs 14–1/0 Steel Series A-L ACPL 10R
Ringless Type, 3Ø4W 600 Vac Max., Bolt-On Socket Without Bypass
400 7 OH/UG UK7T ei 2423.00 Studs Only 1/2 in.–20
dia. studs 1/2 in.–20
dia. studs Steel Series A-L ACPL 12R
400 7 OH/UG UAK7Tei 2678.00 Studs Only 1/2 in.–20
dia. studs 1/2 in.–20
dia. studs Aluminum Series A-L ACPLA 12R
Ring Type, 1Ø3W 600 Vac Max., Without Bypass or Jaw Release
125 4 OH/UG URTRS101Be123.00 8–2/0 Slotted 14–2 Steel Series A ACP 1R
200 4 OH/UG URTRS213Be212.00 1/0–350 1/2 in. Hex 14–2 Steel Series A ACP 5R
UTRS101B
UTRS202B
(cover not shown)
UTH5203T
(cover not shown)
URTRS213B
DE4 Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
© 2009 Schneider Electric
All Rights Reserved 2-3
Meter Sockets Horizontal Ganged, Test Block Bypass Sockets and Accessories
Class 4131
Horizontal Ganged Meter Sockets
•1Ø, 600 Vac max., main lugs only, 2 through 6 meter positions, with and without
horn or lever bypass, end or center feed, overhead and underground service feeds.
•10 kA short circuit current rating (or higher with utility approval).
•UL Listed, NEMA 3R enclosure.
•Supplied with ground lugs.
•Supplied with hub opening in top endwall, requires the use of a bolt-on hub, or closing plate.
This metering is generally utility specific. Always check with local utility company before installing. Contact
your nearest Field Sales Office for additional catalog numbers, if required by utility.
Meter Mains with Test Block Bypass (Meets EUSERC Requirements)
Meter Socket Accessories
Table 2.2: Ringless Type, 1Ø3W, 600 Vac Max., Without Bypass or Jaw Release
Branch Ratings Mains
Rating
(A) Cat. No. $ Price
Main Lugs
Phase and
Neutral
Al/Cu
(AWG/kcmil)
Branch Lugs
Phase and
Neutral
Al/Cu (AWG)
Top Endwalla
Box No.
See Page 2-4
AmperescNo. of
Positions
Socket
Jaw
Qty.b
Service
Type
Hub Type
(Order
Separately)
Closing Plate
(Order
Separately)
100 A
2
4 OH/UG
200 UT2R1121B 453.00 6–250
8–2/0 Series A ACP
13R
3205UT3R1121B 560.00 6–250 13R1
4205UT4R1131B 660.00 6–350 14R
5250UT5R1131B 908.00 6–350 15R
6300UT6R1131B 1157.00 6–350 16R
200 A
2
4 OH/UG
205 UT2R2122B 647.00 6–250
8–250
Series A ACP 17R
4360UT4R2352T 1106.00 1/0–500 Series A-L ACPL 18R
5500UT5R2392TU 1383.00 1/0–500 or Series A-L ACPL 19R
(2)1/0–350
6620UT6R2392TU 1548.00 1/0–500 or Series A-L ACPL 20R
(2)1/0–350
aFor hubs and closing plates, see Accessories table below.
bFifth jaw kit available to convert 4-jaw socket to a 5-jaw socket. See Accessories table below.
cRating is continuous.
Table 2.3: Ring Type, 1Ø3W and 3Ø4W, Meter Main with Test Block Bypass (Meets EUSERC Requirements)
Supplied with bondable neutral, suitable for use as service equipment. Suitable for overhead or underground service. UL Listed File E6294.
System (Incoming)
and
Service (Outgoing)
Meter
Socket
Type
Ampere
Rating
(Max.)
Short Circuit
Current Rating Cat. No.f$ Price Main Circuit Breaker Type
(Order Separately)d
120/240 Vac 1Ø3W 5-Jaw 225 A 100 kA max. EMT1225CB 4095.00 2P Type QB, QD, QG, QJ, QOe, QO-VHe or QOHe
208Y/120 Vac 3Ø4Wg
or
240/120 Vac 3Ø4W Delta 7-Jaw 225 A 65 kA max. EMT3225CB 5355.00 3P Type QB, QD, QG or QJ
dRefer to page 2-15 to select main circuit breaker.
eRequires use of EZM125QOA adapter (order separately), when using QO (40 A–125 A, 2-pole) 10kA max. SCCR, QO-VH (40 A–60 A, 2-pole) 22kA
max. SCCR, or QOH (40 A–60 A, 2-pole) 42kA max. SCCR. Refer to page 2-15 for pricing.
fRefer to page 2-4 for box dimensions.
g100 kA max.
Table 2.4: EMT Terminal Wire Size h
Line Phase Lug Line Neutral Lug Service Ground Lug Equipment Ground Lug Load Neutral Lug
6 AWG–300 kcmil Al/Cu 6 AWG–350 kcmil Al/Cu 4 AWG–300 kcmil Al/Cu 6 AWG–300 kcmil Al/Cu 4 AWG–300 kcmil Al/Cu
hRefer to circuit breaker listings for usable load lug wire sizes.
Table 2.5: Meter Socket Accessories
Accessory Description Cat. No. $ Price
Fifth-Jaw Kit Converts a 4-jaw meter socket to a 5-jaw meter socket.
For use on meter sockets supplied without lever bypass or jaw release only. A5J 14.90
Closing Plates
(to seal hub openings)
For Series A (steel) ACP 13.40
For Series A (aluminum) ACPA 11.90
For Series A-L (steel) ACPL 18.30
For Series A-L (aluminum) ACPLA 16.50
Hubs
(listed by conduit size)
Series A
1.00 inch A100 33.90
1.25 inch A125 33.90
1.50 inch A150 33.90
2.00 inch A200 47.90
2.50 inch A250 61.00
Series A-L
2.00 inch A200L 83.00
2.50 inch A250L 87.00
3.00 inch A300L 111.00
3.50 inch A350L 114.00
4.00 inch A400L 119.00
Series B 3.00 inch B300i186.00
Adapter Plate To allow the use of a Series A Hub on a device that is setup for a series A-L Hub. AAP 33.80
Lug Kits
For use on meter sockets supplied with Line, Load, and Neutral Studs only. Be sure
to order enough lugs for each device (a typical 1Ø device requires 6 lugs).
Includes one, two-barrel lug (6-250 kcmil) ARP00118 38.10
Includes one, single barrel lug (4-600 kcmil) ARP00129 55.00
Includes three, two-barrel lugs (6-350 kcmil) ARP00427 135.00
Sealing Ring
Snap-on Aluminum (Standard) 2920910001 8.00
Snap-on Stainless Steel (Non-standard) ARP00026 16.70
Screw Type Aluminum (Non-standard) 29008W 20.10
iDE1A Discount.
UT2R1121B
EMT3225CB
EMT1225CB
Without Covers
DE4 DE1A Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
2-4 © 2009 Schneider Electric
All Rights Reserved
Meter Sockets Dimensions
Class 4131
aRefer to page 2-3 for closing plates and hubs.
bKnockout for grounding conductor.
Table 2.6: Enclosure Dimensions
Dimensions (Inches)
Box
No. HWD Hub Opening
(Max. Conduit Size) a
1R 10.88 8.00 3.50 Series A
2R 13.00 13.00 4.94 Solid Top
3R 14.00 8.00 4.38 Series A
4R 14.00 11.00 4.38 Series A
5R 15.00 11.00 4.38 Series A
6R 15.50 8.00 4.36 Series A
7R 17.13 13.00 4.94 (2) Series A
8R 19.00 10.50 4.94 Series A-L
9R 19.00 13.00 4.94 Series A-L
10R 34.50 15.00 5.68 Series A-L
11R 36.62 15.00 5.68 Series A-L
12R 43.00 20.25 6.00 Series A-L
13R 14.12 24.31 4.50 Series A
13R1 14.12 32.50 4.50 Series A
14R 14.12 40.62 4.50 Series A
15R 14.12 48.75 4.50 Series A
16R 14.12 57.00 4.50 Series A
17R 14.12 24.31 5.38 Series A
18R 14.12 40.62 5.38 Series A-L
19R 14.12 54.75 5.38 (2) Series A-L
20R 14.12 63.00 5.38 (2) Series A-L
Table 2.7: Knockout Information
Knockouts
SymbolS ABCDEFGH I J
Conduit
Size (in.) 5/16
b1/23/4 11-1/41-1/222-1/233-1/24
DW
H
S
Hub
Opening
3R, 6R
Meter
Socket
A
E,F,G
DW
H
F,G,H
S
8R
Meter
Socket
F,G,H
A
A,B
A,B
Hub
Opening
DW
H
F,G,H,I
S
11R
Meter
Socket
Offset
F,G,H,I
A
Hub
Opening
DW
H
F,G,H
Solid
Top
2R
C,D,E,F,G
Meter
Socket
Offset
SA
DW
H
A,B,C,D,E
S
C,D,E,F
A,B,C,D
Hub
Opening
1R
A,B,C,D
Meter
Socket
DW
H
D,E,F,G
S
7R
Meter
Socket
Offset
F,G,H
A
Hub
Opening
DW
H
C,D,E,F,G
S
D,E,F,G
4R, 5R
Meter
Socket
A
Hub
Opening
DW
H
F,G,H,I
S
10R
Meter
Socket
F,G,H,I
A
Hub
Opening
DW
H
F,G,H
S
9R
Meter
Socket
F,G,H
A
A,B A,B
Hub
Opening
Hub
Opening
DW
H
G,H,I,J
12R
Meter
Socket
A,B
DW
Hub Opening
H
Main
Lugs
Meter
Socket
SA
C,D,E,F,G (13R)
F,G,H (17R)
C,D,E,F,G
(13R, 17R)
C,D,E,F,G
(13R, 17R)
13R and 17R
Hub Opening
Meter
Socket
DW
H
Main
Lugs
SA
C,D,E,F,G
(14R, 18R)
14R and 18R
C,D,E,F,G (14R)
F,G,H (18R)
C,D,E,F,G
(14R, 18R)
Hub Opening
Meter
Socket
DW
H
Main
Lugs
SA
C,D,E,F,G
13R1
C,D,E,F,G C,D,E,F,G
EMT1225CB and EMT3225CB
Supplied with (2)
ACP Closing Plates.
Order A-Hubs
separately for
overhead service
feed.
7.50
191
C,D,E (3 Locations)
E,F,G,H (8 Locations)
A,B
22.44
570
30.00
762
DW
H
Main
Lugs
SA
C,D,E,F,G
15R and 16R
Hub Opening
C,D,E,F,G C,D,E,F,G
Meter Socket
Left position omitted on
5-Gang unit (15R)
Meter Socket
Left position omitted on
5-Gang unit (19R)
DW
H
Main
Lugs
SA
C,D,E,F,G
(19R, 20R)
C,D,E,F,G
(19R, 20R)
19R and 20R
F,G,H
(19R, 20R)
Hub Opening (2 Locations)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
© 2009 Schneider Electric
All Rights Reserved 2-5
MP Meter-PakTM Meter Centers Ring and Ringless Devices
Class 4141
Ring and Ringless Type Devices
•Consult local utility for approval before installation.
•120/240 Vac 1Ø3W.
•Main lugs only—two to six meter sockets.
•Enclosures are indoor/rainproof NEMA 3R construction.
•Suitable only for use as service equipment.
•Swingable mounting feet supplied at bottom of device.
•Factory-installed mechanical lugs, alternate lugs and NEMA/EUSERC lug landing kits available.
•Surface mount, convertible to semi-flush with field installed flange kit.
•Ring type devices supplied with 4-jaw meter sockets (5th jaw kits available, order separately).
•Ringless type devices supplied with 5-jaw meter sockets, available with and without horn or lever bypass.
•Provisions for mounting 2-pole circuit breaker for each meter socket position (order circuit breakers separately).
•Mounting channel supplied, except for box 1R (125 A, 2-position).
•Combination overhead/underground feed.
MP44125
Table 2.8: Ring Type MP Meter-Pak Metering Equipment with 125 A (42 kA Maximum SCCR) or
200 A (22 kA Maximum SCCR) Meter Socket Positions
Amperes
per Pole No. of
Poles
Factory-Installed
Main Lug Ampacity
(See page 2-6 for
alternate lugs)
Main Bus
Ampacity
(A) Cat. No. $ Price Line Lug Wire
Size Al/Cu
AWG/kcmil
Circuit
Breaker Type
(2P) Hub Prov.aSemi-Flush
Flange Kit Wt Lbs Box No.
125
2 200 200 MP22125 b977.00 (1) 4–250
QO,
QO-VH,
QOH
A/B300 MPSF12 46 1R
3 300 300 MP33125 c1187.00 (1) 1/0–600 or
(2) 1/0–250 A-L MPSF14 95 2R
4 400 400 MP44125 c1730.00 (1) 1/0–600 or
(2) 1/0–250 A-L MPSF14 97 2R
5400 Al
500 Cu 500 MP55125 c2079.00 (1) 1/0–600 or
(2) 1/0–250 (4) A-L MPSF16 130 3R
6400 Al
500 Cu 600 MP66125 c2415.00 (1) 1/0–600 or
(2) 1/0–250 (4) A-L MPSF16 132 3R
200
2 400 400 MP42200 c1274.00 (1) 1/0–600 or
(2) 1/0–250
QOM2-MM,
QOM2-MVH (4) A-L
MPSF23 99 4R
3 400 400 MP43200 c2151.00 (1) 1/0–600 or
(2) 1/0–250 MPSF23 99 4R
4 400 600 MP64200 c2814.00 (1) 1/0–600 or
(2) 1/0–250 MPSF24 135 5R
5 600 Al, 750 Cu 800 MP85200 c3377.00 (2) 3/0–500 MPSF26 173 6R
6 600 Al, 750 Cu 800 MP86200 c4040.00 (2) 3/0–500 MPSF26 173 6R
aFor A and A-L Hubs see page 2-3, for B Hubs see page 3-9.
bMeets EUSERC standards.
cMeets EUSERC standards with addition of lug landing kit, MMSK2.
Table 2.9: Ringless Type MP Meter-Pak Metering Equipment with 125 A (42 kAMaximum SCCR) or
200 A Type MPR, MPH (22 kA Maximum SCCR) or 225 A Type MPL (100 kA Maximum SCCR) Meter Socket Positions
Amperes
Per
Pos.
No.
of Pos.
Factory-Installed
Main Lugs
Ampacity
(See page 2-6 for
alternate lugs)
Main Bus
Ampacity No. Bypass
Cat. No. $ Price Horn
Bypass
Cat. No. $ Price Lever
Bypass
Cat. No. $ Price
Line Lug
Wire Size
Al/Cu
AWG/kcmil
Circuit Breaker
Type
(2P)
(See page 2-6)
Hub
Prov. dSemi-Flush
Flange Kit Wt
Lbs Box
No.
125
2 200 200 MPR22125 995.00 MPH22125 1002.00 — — (1) 4–250
QO,
QO-VH,
QOH
A/B300 MPSF12 46 1R
3 300 300 MPR33125 1220.00 MPH33125 1253.00 — — (1) 1/0–600 or
(2) 1/0–250 A-L
MPSF14 95 2R
4 400 400 MPR44125 1781.00 MPH44125 1830.00 ——
(1) 1/0–600 or
(2) 1/0–250 MPSF14 97 2R
5400 Al
500 Cu 500 MPR55125 2246.00 MPH55125 2330.00 ——
(1) 1/0–600 or
(2) 1/0–250 (2) A-L
MPSF16 130 3R
6400 Al
500 Cu 600 MPR66125 2615.00 MPH66125 2715.00 ——
(1) 1/0–600 or
(2) 1/0–250 MPSF16 132 3R
200
2 400 400 MPR42200 1290.00 MPH42200 1299.00
——
(1) 1/0–600 or
(2) 1/0–250 QOM2-MM,
QOM2-MVH
(2) A-L
MPSF23 99 4R
3 400 400 MPR43200 2186.00 MPH43200 2219.00 MPSF23 99 4R
4 400 600 MPR64200 2865.00 MPH64200 2916.00 MPSF24 135 5R
225
2 350 350 — — — — MPL32225 1739.00
(1) 1/0–600 or
(2) 1/0–250
QBP-TM,
QDP-TM,
QGP-TM or
QJ-TM
QOe, QO-VHe
or QOHe
N/A 105 7R
3 400 500 — — — — MPL53225 2741.00 N/A 147 8R
4 400 600 — — — — MPL64225 3656.00 N/A 200 9R
200 5 600 Al, 750 Cu 800 MPR85200 3545.00 MPH85200 3627.00 — — (2) 3/0–500 QOM2-MM,
QOM2-MVH
MPSF26 173 6R
6 600 Al, 750 Cu 800 MPR86200 4241.00 MPH86200 4341.00 — — (2) 3/0–500 MPSF26 173 6R
dFor A and A-L Hubs see page 2-3, for B Hubs see page 3-9.
eRequires use of EZM125QOA adapter (order separately). Refer to oage 2-15 for pricing.
UL Listed short circuit current rating depends on lowest interrupting rating of circuit breaker installed.
DE4 Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2-6 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
2METERING EQUIPMENT
MP Meter-PakTM Meter Centers Tenant Circuit Breakers and Accessories
Class 4141
Tenant Circuit Breakers
UL Listed Short Circuit Current Rating depends on lowest interrupting rating of circuit breaker installed. (Refer to the
table on the bottom of page 2-9 for Square D certified ratings for downstream panelboards and load centers.)
aOrder only. Not stocked in PDS. Order Point: Lincoln.
bRequires use of EZM125QOA adapter (order separately). Refer to page 2-15 for pricing.
cQO-VH tenant circuit breakers are rated 22 kAIR at 120/240 Vac.
dQOH tenant circuit breakers are rated 42 k AIR at 120/240 Vac.
Accessories
eThe meter center short circuit current rating is 10 kA when manual circuit closing is used. Not rated for continuous duty.
fStandard lug for 3 through 6 position 125 A and 2 through 4 position 200 A devices.
gCannot be installed on 2 position 125 A device.
hOrder only. Not stocked in PDS. Order point: Lexington.
For hubs and closing plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2-3
Table 2.10: Tenant Circuit Breakers
Amperes 10 k AIR
120/240 Vac $ Price
(DE2A) 22 k AIR
120/240 Vac $ Price
(DE2A) 42 k AIR
120/240 Vac $ Price
(DE2A) 100 k AIR
120/240 Vac $ Price
(DE2A)
For use in 125 A Max. Type MP, MPR and MPH Meter-Pak Metering Equipment
40 QO240 67.00 QO240VHa146.00 QOH240 317.00 ——
50 QO250 67.00 QO250VHa146.00 QOH250a317.00 ——
60 QO260 67.00 QO260VH 146.00 QOH260a317.00 ——
70 QO270 134.00 QO270VH 224.00 QOH270a528.00 ——
80 QO280 189.00 QO280VH 315.00 QOH280a651.00 ——
90 QO290 189.00 QO290VH 315.00 QOH290 651.00 ——
100 QO2100 189.00 QO2100VH 315.00 QOH2100 651.00 ——
125 QO2125 428.00 QO2125VH 1034.00 QOH2125 1389.00 ——
For use in 200 A Max. Type MP, MPR and MPH Meter-Pak Metering Equipment
100 QOM2100MM 474.00 QOM2100MVH 1143.00 ————
125 QOM2125MM 474.00 QOM2125MVH 1143.00 ————
150 QOM2150MM 474.00 QOM2150MVH 1143.00 ————
175 QOM2175MM 474.00 QOM2175MVH 1143.00 ————
200 QOM2200MM 474.00 QOM2200MVH 1143.00 ————
For use in 225 A MPL Lever Bypass Meter-Pak Metering Equipment
Amperes 10 k AIR
120/240 Vac $ Price
(DE2A) 25 k AIR
120/240 Vac $ Price
(DE2A) 65 k AIR
120/240 Vac $ Price
(DE2A) 100 k AIR
120/240 Vac $ Price
(DE2A)
40 QO240b67.00 QO240VHacb 146.00 QOH240bd 317.00 ——
50 QO250b67.00 QO250VHacb 146.00 QOH250bda 317.00 ——
60 QO260b67.00 QO260VHacb 146.00 QOH260bda 317.00 ——
70 QBP22070TM 474.00 QDP22070TM 1143.00 QGP22070TM 1521.00 QJP22070TM 1890.00
80 QBP22080TM 474.00 QDP22080TM 1143.00 QGP22080TM 1521.00 QJP22080TM 1890.00
90 QBP22090TM 474.00 QDP22090TM 1143.00 QGP22090TM 1521.00 QJP22090TM 1890.00
100 QBP22100TM 474.00 QDP22100TM 1143.00 QGP22100TM 1521.00 QJP22100TM 1890.00
110 QBP22110TM 474.00 QDP22110TM 1143.00 QGP22110TM 1521.00 QJP22110TM 1890.00
125 QBP22125TM 474.00 QDP22125TM 1143.00 QGP22125TM 1521.00 QJP22125TM 1890.00
150 QBP22150TM 474.00 QDP22150TM 1143.00 QGP22150TM 1521.00 QJP22150TM 1890.00
175 QBP22175TM 474.00 QDP22175TM 1143.00 QGP22175TM 1521.00 QJP22175TM 1890.00
200 QBP22200TM 474.00 QDP22200TM 1143.00 QGP22200TM 1521.00 QJP22200TM 1890.00
225 QBP22225TM 474.00 QDP22225TM 1143.00 QGP22225TM 1521.00 QJP22225TM 1890.00
Table 2.11: Accessories
Accessory Description Cat. No. $ Price
Fifth Jaw Kit Fifth Jaw Kit 5J 18.30
Horn Bypass Kit For MPR and MPH only MMHB 16.70
QO Adapter For Bolt-on Q2M tenant circuit breakers (40–125 A, 2P) EZM125QOA 273.00
Slider Type Manual Circuit Closing: 125 A Ring Style 2 Position Top Meter (Only) MM125MBe171.00
125 and 200 A Ring Style MM200MBe171.00
Sealing Rings:
Snap-on Aluminum 2920910001 8.00
Screw Type Aluminum 29008W 20.10
Snap-on Type Stainless Steel ARP00026 16.70
Meter Cover-Lexan®Meter Cover-Lexan®29007 10.10
Optional Lug Kits:
(1) 1/0–600 AWG/kcmil or
(2) 1/0–250 AWG/kcmil per phase MMLK250fg 150.00
(2) 3/0–500 AWG/kcmil per phase MMLK500g200.00
(2) 2–600 AWG/kcmil per phase MMLK600g233.00
Semiflush Kits:
125 A 2 Position MPSF12 101.00
125 A 3–4 Position MPSF14 134.00
125 A 5–6 Position MPSF16 218.00
200 A 2–3 Position MPSF23 144.00
200 A 4 Position MPSF24 171.00
200 A 5–6 Position MPSF26 255.00
NEMA/EUSERC Lug Landing Kit: For 3 through 6 position 125 A and 200 A devices. Each pad rated 600 A maximum and
includes (2) 1/2-13 studs and mounting hardware. MMSK2g185.00
NEMA Lug Landing Kit: For use ONLY on MPL43225, MPL53225 and MPL64225 with optional lugs. See wiring
diagram of each device for optional lugs. MMSK4 276.00
MP Meter-Pak Wireway:
(Wall Mount Pedestal)
125 A 2 Position ONLY MP43X8PED 441.00
125 A 3–6 Position MP43X11PED 504.00
200 A 2–6 Position MP43X11PED 504.00
MPL32-225 MP35X11PEDh504.00
MPL53-225 MP43X11PED 504.00
MPL64-225 MP35X11PEDh504.00
MP Meter-Pak Wireway Extensions: Used ONLY with MP43X8PED MP12X8PEDEXTh102.00
Used with MP43X11PED and MP35X11PED MP12X11PEDEXTh126.00
QO2100VH
2P, Plug-on Type
Circuit Breaker
QDP22200TM
2P, Bolt-on Type
Circuit Breaker
QOM2200MVH
MMLK500
DE4 DE2A Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
© 2009 Schneider Electric
All Rights Reserved 2-7
MP Meter-PakTM Meter Centers Dimensions
Class 4141
Dimensions and Knockouts
A Hub Opening Supplied
with ACP Closing Plate
18.50
470
37.50
953
12.28
312
9.00
229
7.28
185
A
D,F,G and A or
B300 Hub Provision
C,D,F
C,D,F
Mounting Holes
(4) Locations
(Supplied without
Mounting Channel)
Box 1R
7.28
185
C,D,F
E,F,G,H,I,J and
A-L Hub Provision
48.12
1222
24.34
618
9.00
229
Typ.
11.19
284
Top Position
Omitted on
3-Gang Unit
Box 2R
C,D,F
A-L Hub Opening Supplied
with ACPL Closing Plate
A,B
7.28
185
36.46
926
9.00
229
Typ.
C,D,F
Top Left
Position
Omitted on
5-Gang Unit
42.37
1076
11.19
284
C,D,F
A
Box 3R
A-L Hub Opening Supplied
with ACPL Closing Plates
A,B
E,F,G,H,I,J and
A-L Hub Provision
C,D,F
43.41
1103
9.00
229
Typ.
12.22
310
Top Position
Omitted on
2-Gang Unit
8.28
210
29.44
748
A-L Hub Opening Supplied
with ACPL Closing Plates
Box 4R
C,D,E,F
A,B
E,F,G,H,I,J and
A-L Hub Provision
C,D,F
52.00
1321
9.00
229
Typ.
12.22
310
Box 5R
29.44
748
8.28
210
A-L Hub Opening Supplied
with ACPL Closing Plates
C,D,E,F
A,B
E,F,G,H,I,J and
A-L Hub Provision
C,D,F
9.00
229
Typ.
43.41
1103
12.22
310
Top Left
Position
Omitted on
5-Gang Unit
46.68
1186
8.28
210
A-L Hub Opening Supplied
with ACPL Closing Plates
A,B,C
C,D,E,F
E,F,G,H,I,J and A-L Hub Provision
Box 6R
C,D,E,F
A-L Hub Opening Supplied
with ACPL Closing Plates
60.25
1530
14.00
356
34.00
864
Box 7R
9.62
244
19.43
494
E,F,G,H,I,J and
A-L Hub Provision
C,D,E,F
A,B
C,D,E,F
53.12
1349
14.00
356
Typ.
13.43
341
Box 8R
35.37
898
A-L Hub Opening Supplied
with ACPL Closing Plates
9.62
244
E,F,G,H,I,J and
A-L Hub Provision
C,D,E,F
A,B
C,D,E,F
67.37
1711
14.00
356
Typ.
13.43
341
Box 9R
35.37
898
A-L Hub Opening Supplied
with ACPL Closing Plates
9.62
244
E,F,G,H,I,J and
A-L Hub Provision
C,D,E,F
A,B
Knockouts
Symbol ABCDEFGH I J
Conduit Size
(in.) 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
2-8 © 2009 Schneider Electric
All Rights Reserved
EZ Meter-Pak® Meter Centers Indoor/Rainproof Meter Center Information
Class 4141
NEMA 3R Construction
240 Vac Maximum, for use on AC systems, suitable for
use as Service Equipment.
Utility Company Requirements Review local utility
requirements to ensure that metering equipment meets
their standards.
EZ Meter-Pak meter center enclosures meet NEC wire
bending requirements, and are designed for wall mounting
only (not suitable for floor mounting). All unmetered
conductor compartments may be sealed by the utility
company.
EZ Meter-Pak meter centers have UL Listed short circuit
current ratings up to 100 kA at 240 Vac when properly
applied. For three-tier series ratings refer to Data Bulletin
4100DB0301 and Instruction Bulletin 80043-303-22.
Suitable incoming services for an EZM main device
and available outgoing feeder(s) to downstream
panelboards from EZM branch section(s)—
Incoming Service to Main Device 120/240 Vac, 1Ø3W
Available outgoing feeder(s) to downstream panelboards:
•120/240 Vac, 1Ø3W
(4-jaw ring type meter sockets, two-pole circuit breakers)
(5-jaw ringless meter sockets, two-pole circuit breakers).
Incoming Service to Main Device 240/120 Vac, 3Ø4W
Delta
Available outgoing feeder(s) to downstream panelboards:
•120/240 Vac, 1Ø3W (Fed from transformer’s “A-Phase” and
“C-Phase” only.) NOTE: Connection to High-Leg “B-Phase”
not permitted for this service
(4-jaw ring type meter sockets, two-pole circuit breakers)
(5-jaw ringless meter sockets, two-pole circuit breakers)
Standard 3Ø IN/1Ø OUT branch units are not suitable for
use on this Delta System. Special branch units are
available for this System by adding suffix: “CA” to catalog
number (Typical Examples: EZM313125CA,
EZM313125XCA, EZM313125CUXCA, EZM314225CA,
EZM314225XCA, EZM314225CUXCA, EZM315225CA,
EZM314225CUCA, etc.).
•240/120 Vac, 3Ø4W Delta (7-jaw meter sockets, three-pole
circuit breakers).
Incoming Service to Main Device 208Y/120 Vac, 3Ø4W
Available outgoing feeder(s) to downstream panelboards:
•120/208 Vac, 1Ø3W (5-jaw meter sockets, two-pole circuit
breakers)
•208Y/120 Vac, 3Ø4W (7-jaw meter sockets, three-pole circuit
breakers).
Main Devices
•400, 600 and 800 A main disconnects may be end mounted
with branch units having 800 A or 1200 A continuous
horizontal cross bus.
•1000 and 1200 A main disconnect or terminal box must be
center mounted when used with branch devices with main
bus rated 800 A continuous.
•1600 A main disconnect or terminal box must be center
mounted.
•2000 A main disconnect must be center mounted and
requires use of branch units having 1200 A continuous
horizontal cross bus.
•400, 800 and 1200 A Type EZM-TBU tap boxes supplied with
lug landings to meet EUSERC requirements.
Main Circuit Breaker ratings: 400, 600, 800, 1000, 1200,
1600 and 2000 A
Main Fusible Switch ratings: 400, 600, 800, and 1200 A
(1Ø3W only)
Main Lugs Terminal Box ratings:
225, 400, 600, 800, 1200, 1600, and 2000 A
Branch Units
•125 A and 225 A residential branch units are available
in ring type or ringless type construction and are supplied with
800 A continuous aluminum horizontal cross bus as standard
(Example: EZM314125). For optional 1200 A continuous
copper horizontal cross bus with aluminum vertical
connectors, add suffix “X” to catalog number (Example:
EZM314125X). For optional 1200 A continuous all-copper
bussing, add suffix “CUX” to catalog number (Example:
EZM314125CUX). NOTE: 5-gang 225 A EZM, EZMR and
EZMH residential branch units are supplied with 1200 A
continuous Cross Bus as standard, do not add suffix “X” or
“CUX” to these units (Examples: EZMR315225 or
EZMR315225CU). Plug-in style residential meter sockets are
available as ring type EZM without bypass, ringless type
EZMR without bypass, and ringless type EZMH with horn
bypass.
Tenant circuit breakers must be ordered separately for these
branch units. 125 A max. units make use of Type QO, QO-VH
or QO-H two-pole tenant circuit breakers (40–125 A). 225 A
max. units make use of Type QDP-TM, QBP-TM, QGP-TM
and QJP-TM two-pole tenant circuit breakers (70–225 A), and
may also make use of two-pole Type QO (40–125 A at 10 kA
max.), two-pole Type QO-VH (40–60 A at 100 kA max.), or
two-pole Type QO-H (40–60 A at 100 kA max.) tenant circuit
breakers.
•225 A commercial branch units are available in ring type
or ringless type construction and are supplied with 1200 A
copper horizontal cross bus with aluminum vertical
connectors as standard (Example: EZML314225). For
optional 1200 A continuous all-copper bussing, add suffix
“CU” to catalog number (Example: EZML314225CU). Plug-
in style commercial meter sockets are available as ring type
EZMT with test block bypass (meets EUSERC
requirements), ringless type EZMR without bypass, and
ringless type EZML with lever bypass.
225 A max. units make use of type QDP-TM, QBP-TM, QGP-
TM and QJP-TM two-pole or three-pole tenant circuit breakers
(70– 225 A), and may also make use of two-pole type QO
(40–125 A at 10 kA max.), two-pole type QO-VH (40–60 A at
100 kA max.), or two-pole type QO-H (40–60 A at 100 kA
max.) tenant circuit breakers.
Note: QO, QO-VH and QO-H tenant circuit breakers used
in 225 A branch units require the use of adapter
EZM125QOA (purchased separately). Refer to page 2-15
for pricing.
•400 A branch units are available in ringless type
construction only, and are supplied with 1200 A continuous
all-copper bussing as standard (Example: EZML332400).
These branch units are supplied with factory-installed type
DJM tenant circuit breakers that have a field adjustable
ampere rating trip setting from 160 A min. to 400 A max.
A tamper-evident seal kit is available where needed, order
seal kit 29375 (refer to NEC 240-6 [c]). 400 A branch units
are available as Type EZML with plug-in style lever bypass
type meter sockets, or Type EZMK with bolt-on style with
manual bypass type meter sockets.
•Units having 800 A continuous horizontal cross bus
WILL CONNECT with units having 1200 A continuous
horizontal cross bus.
•Single phase units (three bus bars in horizontal cross bus)
WILL NOT CONNECT with three phase units (four bus
bars in horizontal cross bus).
For Load Center Three-Tiered Series Ratings used
downstream from Metering Equipment, refer to Data
Bulletins : 4100DB0301 and 2700DB9901.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
© 2009 Schneider Electric
All Rights Reserved 2-9
EZ Meter-Pak® Meter Centers Selection Information
Class 4141
•Review local utility requirements to ensure that metering
equipment meets their standards.
•Check local utility to determine available fault current at the
meter center.
•Using the SCCR table:
— Select meter center configuration, main lugs only (Six
Disconnect Rule), or remote main, main circuit breaker, or
main fusible switch.
— Read down to select SCCR equal to, or greater than desired
rating.
— Read across to select branch unit tenant circuit breaker type.
— Continue reading across to select EZM main device type.
Table 2.12: UL Listed Meter Center Short Circuit Current Ratings (SCCR)
Tenant circuit breakers of same frame size having higher AIR values may replace tenant circuit breakers as listed in tables below and maintain the series rating.
Figures
Short Circuit
Current Rating
(240 Vac
Maximum)ab
EZM Meter Center Overcurrent Protection Devices
EZM Branch Unit Tenant Circuit Breaker
Types Available (Branch Unit Amperes max.,
Number of Poles, Tenant Circuit Breaker
Amperes Rating Range)
EZM Main Device with Integral Mounted Main,
Remote Mounted Main or without an Upstream Mounted Main
(Six Disconnect Rule)
EZ Meter-Pak (Six Disconnect Rule Applications)—See Figure 1
10 kA QO (125 A, 2P, 40–125 A)
400–2000 A Main Lugs Terminal Box
(Tenant Circuit Breakers used as Service Disconnects—6 maximum)
QO (225 A, 2P, 40–125 A)d
QB (225 A, 2P or 3P, 70–225 A)
22 kA QO-VH (125 A, 2P, 40–125 A )
QO-VH (225 A, 2P, 40–60 A)d
25 kA QD (225 A, 2P or 3P, 70–225 A)
42 kA QOH (125 A, 2P, 40–125 A)
QOH (225 A, 2P, 40–60 A)d
65 kA QG (225 A, 2P or 3P, 70–225 A)
100 kA QJ (225 A, 2P or 3P, 70–225 A) c
DJM (400 A, 2P or 3P, 160–400 A)ec
EZ Meter-Pak 225–2000 A Main Lugs Terminal Box Applications Protected by Remote Main—See Figure 2
10 kA
QO (125 A, 2P, 40–125 A)
Must be protected by an upstream disconnecting means rated 10 k AIR minimum
QO (225 A, 2P, 40–125 A)d
QB (225 A 2P or 3P, 70–225 A)
DJM (400 A, 2P or 3P 160–400 A)e
22 kA QO-VH (125 A, 2P, 40–125 A) Must be protected by an upstream disconnecting means rated 22 k AIR minimumQO-VH (225 A, 2P, 40–60 A)d
DJM (400 A, 2P or 3P, 160–400 A)e
25 kA QD (225 A 2P or 3P, 70–225 A) Must be protected by an upstream disconnecting means rated 25 k AIR minimum
DJM (400 A, 2P or 3P, 160–400 A)e
42 kA
QOH (125 A, 2P, 40–125 A) Must be protected by an upstream disconnecting means rated 42 k AIR minimumQOH (225 A, 2P, 40–60 A)d
DJM (400 A, 2P or 3P, 160–400 A)e
QO-VH (125 A, 2P, 40–125 A) Must be protected by a Square D circuit breaker Type LA (400 A max.) or MA
(1000 A max.) Rated 42 k AIR minimum
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P or 3P, 70–225 A)
65 kA
QG (225 A 2P or 3P, 70–225 A) Must be protected by an upstream disconnecting means rated 65 k AIR minimum
DJM (400 A, 2P or 3P, 160–400 A)e
QO-VH (125 A, 2P, 40–125 A) Must be protected by a Square D circuit breaker Type LH (400 A max.), MH (1000 A max.)
or PA (1600 A max.) rated 65 k AIR minimum
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P or 3P, 70–225 A)
QD (225 A 2P or 3P, 70–225 A) Must be protected by a Square D circuit breaker Type MG (800 A max.), PG (1200 A max.) or
RG (2000 A max.) rated 65 k AIR minimum
100 kA
QJ (225 A 2P or 3P, 70–225 A )cMust be protected by an upstream disconnecting means rated 100 k AIR minimum
DJM (400 A 2P or 3P, 160–400 A)ec
QO-VH (125 A, 2P, 40–125 A) Must be protected by an upstream disconnection means with Class R (600 A max.), or
Class T (300 Vac, 800 A maximum) fuses.QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P only, 70–225 A) Must be protected by an upstream disconnection means with Class J (600 A max.), Class L
(1200 A max.), Class R (600 A max.), Class T (300 Vac, 1200 A max.) or Class T (600 Vac,
800 A maximum) fuses, or be protected by a Square D circuit breaker Type MJ (800 A max.),
PJ (1200 A max.), PH (1600 A max.) or RJ (2000 A max.) rated 100 k AIR minimum.
QD (225 A 3P only, 70–225 A)c
EZ Meter-Pak—Main Circuit Breaker Applications—See Figure 3
10 kA QO (125 A, 2P, 40–125 A)
400–1600 A EZM Main Device with Type LH (400 A Max.), MH (1000 A max.) or PA (1600 A
max.) circuit breaker.
QO (225 A, 2P, 40–125 A)d
QB (225 A 2P or 3P, 70–225 A)
65 kA
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P or 3P, 70–225 A)
DJM (400 A, 2P or 3P, 160–400 A)e
100 kA
QO-VH (125 A, 2P, 40–125 A)
1000–1200 A Main Device with catalog number suffix "CBU" supplied with
Type MHF circuit breaker.
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P only, 70–225 A)
QD (225 A 3P only, 70–225 A)c
DJM (400 A, 2P or 3P, 160–400 A)ec
QD (225 A 2P only, 70–225 A) 2000 A EZM Main Device with Type RJ (2000 A) circuit breakerQD (225 A 3P only, 70–225 A)c
DJM (400 A 2P or 3P, 160–400 A)ec
EZ Meter-Pak—Main Fusible Switch Applications—See Figure 3
10 kA QO (125 A, 2P, 40–125 A) 400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed. 1200 A EZM
Main Device (1Ø only) with Class T (300 Vac) fuses installed.
QO (225 A, 2P, 40–125 A)d
QB (225 A 2P or 3P, 70–225 A)
42 kA QO-VH (125 A, 2P, 40–125 A)
1200 A EZM Main Device (1Ø only) with Class T (300 Vac) fuses installed.
QO-VH (225 A, 2P, 40–60 A)d
100 kA DJM (400 A, 2P, 160–400 A)e
QD (225 A 2P, 70–225 A)
100 kA
QO-VH (125 A, 2P, 40–125 A)
400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed.
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P, only, 70–225 A)
QD (225 A 3P only, 70–225 A)c
DJM (400 A, 2P or 3P, 160–400 A)ec
aMeter center short circuit current rating is equal to the lowest short circuit current rating given in table for any circuit breaker installed in any meter panelboard in the meter center.
bShort circuit current rating is measured at the LINE SIDE terminals of the integral mounted or remote mounted main providing overcurrent protection for the EZM metering equipment lineup.
c3P only tenant circuit breaker(s) are limited to: 100 kA Max. at 208Y/120 Vac or 65 kA Max at 240/120 Vac.
dRequires use of EZM125QOA adapter (order separately). Refer to page 2-15 for pricing.
eSupplied with factory-installed circuit breaker(s), with an adjustable trip range of 160–400 A.
For three-tier series ratings refer to Data Bulletin 4100DB0301 and Instruction Bulletin 80043-303-22.
Load
Centers
(Main Lugs)
Transformer
Service
Disconnects
(6 Max.)
EZM Main Lugs
Terminal Box
EZM Branch Units
Figure 1
Tenant
Circuit
Breakers
Load
Centers
(Main Lugs)
Transformer
EZM Main Lugs Terminal Box
EZM Branch Units
Upstream Disconnection
Means and Overcurrent
Protection as required
Figure 2
Load
Centers
(Main Lugs)
Transformer
EZM Circuit Breaker Main
or EZM Main Fusible Switch
Tenant
Circuit
Breakers
EZM Branch Units
Figure 3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2-10 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
2METERING EQUIPMENT
Select EZM meter center short circuit current rating from Table 2.12 on page 2-9. Using this table as a reference, make
the following selections:
1. Select EZM 1Ø main device from Table 2.13 or 2.14, below, with an equal or higher short circuit rating than the application.
2. Select EZM 1Ø branch units from Tables 2.15, 2.16 or 2.17.
3. Select proper 2P type QO, QO-VH, QOH, QBP-TM, QDP-TM, QGP-TM or QJP-TM branch circuit breakers for use as tenant mains
in branch unit from Table 2.24, page 2-15.
4. Select accessories as required from Table 2.25, page 2-15.
5. Dimensions; page 2-16.
Select Main Devices—NEMA 3R Construction
aAvailable by special order with main circuit breaker supplied with other standard ampere ratings, consult local Field Office (allow 6 weeks for delivery).
bAmpere rating of the PA circuit breaker supplied with this main changed to a LOWER value in the field by ordering a different set of rating columns, refer
to Supplementary Digest, Section 3 for listing.
cSupplied with copper horizontal bus bars and aluminum vertical bus bars.
d225 A tap box supplied with isolated neutral that cannot be bonded.
eFor mechanical lugs (3/0 AWG–600 kcmil) order kit CMELK4, Price $91.00. Kit includes 4 lugs only. Multiple kits may be required, consult factory. For
crimp-type lugs refer to Anderson Electrical Connector Products Catalog AEC-40R.
fHas a 100 kA max. short circuit current rating.
gDoes not meet EUSERC Standards.
hTap box is suitable for use on LINE or LOAD side of service equipment. Supplied with isolated neutral and provided with neutral bonding kit for use as
required. Refer to page 2-9 for appropriate short circuit current ratings.
iFeed-thru lug kit available, see Accessories, page 2-15.
EZM1800CBU
EZM1800CB
Table 2.13: Main Devices, Overhead/Underground Feed
System
Type Ampere
Rating
Horizontal Cross Bus
Rating and Bus Bar
Material Cat. No. Width $ Price
Line Side Lug (Factory-Installed)
(Conductors per Phase and Neutral) Wire
Size
(AWG/kcmil)
Main Circuit Breaker (1Ø Incoming and 1Ø Outgoing)
65 kA Short Circuit Current Rating (400–1600 A Max.), 100 kA Short Circuit Current Rating (2000 A Max.)
1Ø3W
120/240 Vac
400 400 A Al EZM1400CBa18.66 6180.00 (1) 1–600 or (2) 1–250
600 600 A Al EZM1600CBa18.66 8573.00 (3) 3/0–500
800 800 A Al EZM1800CBa18.66 11364.00 (3) 3/0–500
1000 1000 A Al EZM11000CBa18.66 15767.00 (3) 3/0–500
1200 1200 A Al/Cu EZM11200CBbc 30.19 20366.00 (4) 1/0–750
1600 1200 A Al/Cu EZM11600CBbc 30.19 29904.00 (6) 1/0–750
2000 1200 A Al/Cu EZM12000CBc30.19 54518.00 (6) 1/0–750 or (12) 1/0–250
Main Fusible Switches (1Ø Incoming and 1Ø Outgoing)
100 kA Short Circuit Current Rating. Requires 300 Vac Class T Fuses (Order Separately)
1Ø3W
120/240 Vac
400 400 A Al EZM1400FS 18.66 3989.00 (1) 1–600 or (2) 1–250
600 600 A Al EZM1600FS 18.66 6978.00 (3) 3/0–500
800 800 A Al EZM1800FS 18.66 8972.00 (3) 3/0–500
1200 1200 A Al/Cu EZM11200FSc30.19 11564.00 (4) 1/0–750
Main Lugs Terminal Boxes (1Ø Incoming and 1Ø Outgoing)
1Ø3W
120/240 Vac
225 800 A Al EZM1225TBd11.50 798.00 (1) 4–300
400 800 A Al EZM1400TBh17.00 915.00 (2) 3/0–500
600 800 A Al EZM1600TBh17.00 998.00 (2) 1/0–750 or (4) 1/0–300
800 800 A Al EZM1800TBh18.66 1236.00 (4) 3/0–500
800 800 A Cu EZM1800TBCUih 23.93 1658.00 (4) 3/0–500
1600 1200 A Al EZM11600TBcih 22.33 3588.00 (6) 3/0–600
2000 1200 A Cu EZM12000TBh30.19 9600.00 6 (Order Lugs Separately)
Table 2.14: Main Devices, Underground Feed Only
System
Type Ampere
Rating
Horizontal Cross Bus
Rating and Bus Bar
Material
Cat. No.
Meets EUSERC
Requirements Width $ Price
Factory-Installed Lug Landings
for use with Crimp-Type Lugs
(2-Hole Mounting)
Qty. per Phase and Neutral e
Main Circuit Breakers (1Ø Incoming and 1Ø Outgoing)e
65 kA Short Circuit Current Rating (400–800 and 1600 A Max.),
100 kA Short Circuit Current Rating (1000, 1200 and 2000 A Max.)
1Ø3W
120/240 Vac
400 400 A Al EZM1400CBUa20.46 6380.00 1 (Order Lugs Separately)
600 600 A Al EZM1600CBUa20.46 9171.00 2 (Order Lugs Separately)
800 800 A Al EZM1800CBUa20.46 11762.00 2 (Order Lugs Separately)
1000 1000 A Al/Cu EZM11000CBUfc 34.19 16547.00 3 (Order Lugs Separately)
1200 1200 A Al/Cu EZM11200CBUfc 34.19 21332.00 3 (Order Lugs Separately)
1600 1200 A Al/Cu EZM11600CBUbcg 27.69 31658.00 6 (Order Lugs Separately)
2000 1200 A Al/Cu EZM12000CBUfgc 30.19 52755.00 6 (Order Lugs Separately)
Main Fusible Switches (1Ø Incoming and 1Ø Outgoing)e
100, kA Short Circuit Current Rating. Requires 300 Vac Class T Fuses (Order Separately)
1Ø3W
120/240 Vac
400 400 A Al EZM1400FSU 20.46 6180.00 1 (Order Lugs Separately)
600 600 A Al EZM1600FSU 20.46 9369.00 2 (Order Lugs Separately)
800 800 A Al EZM1800FSU 20.46 11564.00 2 (Order Lugs Separately)
1200 1200 A Al/Cu EZM11200FSUc34.19 14154.00 3 (Order Lugs Separately)
Main Lugs Terminal Boxes (1Ø Incoming and 1Ø Outgoing) e
1Ø3W
120/240 Vac
400 800 A Al EZM1400TBUh16.16 1544.00 1 (Order Lugs Separately)
800 800 A Al EZM1800TBUh24.16 1827.00 2 (Order Lugs Separately)
1200 1200 A Al/Cu EZM11200TBUch 32.16 3725.00 3 (Order Lugs Separately)
New!
New!
EZ Meter-Pak® Meter Centers Indoor/Rainproof Meter Centers
Class 4161 1Ø 3W EZ Meter-Pak Meter Centers—1Ø, Indoor/Rainproof, UL Listed
DE4 Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
© 2009 Schneider Electric
All Rights Reserved 2-11
EZ Meter-Pak® Meter Centers Branch Devices
Class 4161
Branch Devices—NEMA 3R Construction
aSnap-on aluminum sealing rings supplied as standard.
bSupplied with removable drip hood and equipped with an indoor top endwall with knockouts provided.
cFor 1200 A main cross bus add suffix “X” to catalog number (Example: EZM314125X). Add 3% adder to list per device. Allow 6 weeks for delivery.
dType QO, QO-VH and QOH branch circuit breakers (40–60 A) may be installed with use of EZM125QOA adapter kits, refer to page 2-15.
e2P Type QO (40–125 A, 10 kA max. meter center SCCR) or QO-VH and QO-H (40–60 A, 100 kA max. meter center SCCR) may be installed using
EZM125QOA adapter kit, refer to page 2-15.
fSupplied with Class 320 lever bypass meter socket. Utilizes anti-inversion clip kit, catalog number MMLRK, if required, refer to page 2-15.
gSupplied with bondable neutral, suitable for use as service equipment. Use main lugs tapbox type EZM-TBU for Six Disconnect Rule applications to feed
this device. Supplied with copper horizontal bus bars and aluminum vertical bus bars.
hSupplied with removable drip hood and equipped with an indoor top endwall with knockouts provided.
iDoes not meet EUSERC 48 in. minImum / 75 in. maximum meter height requirements for outdoor installations. The bottom meter socket is 37 inches above
ground when the device is mounted with the top meter socket at 75 inches above ground. EUSERC indoor requirements are 36 in. minimum / 75 in. maximum.
jDJM circuit breaker has adjustable trip settings from 160–400 A. Use seal kit 29375, if required. DJM circuit breaker terminal lug kit 32508 factory-
installed and accomodates (1) 2 AWG–500 kcmil Al or (1) 2 AWG–600 kcmil Cu per phase. Alternate lug kit 32510 for DJM circuit breaker is available,
see Accessories, page 2-15. Additional field-installed DJ circuit breaker accessories are available, see page 7-35.
kSupplied with Class 320 lever bypass meter socket. Utilizes anti-inversion clip kit MMLRK, if required, refer to page 2-15.
Table 2.15: Branch Units—1Ø Incoming and 1Ø Outgoing
System
Type Width
(in.)
Number
of Meter
Sockets
Horizontal Cross
Bus Rating and
Bus Bar Material
Ring Type
4-Jaw Meter Socketm
without Bypassa
Ringless Type
5-Jaw Meter Socket
without Bypass
Ringless Type
5-Jaw Meter Socket
with Horn Bypass
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
125 A Maximum (Order Type QO, QO-VH or QOH Circuit Breakers Separately) b
1Ø3W
120/240 Vac
2P Branch
Circuit Breakers
12.25
3800 A Al EZM113125c1436.00 EZMR113125c1436.00 EZMH113125c1755.00
1200 A Cu EZM113125CUX 2282.00 EZMR113125CUX 2282.00 EZMH113125CUX 2282.00
4800 A Al EZM114125c1914.00 EZMR114125c1914.00 EZMH114125c2153.00
1200 A Cu EZM114125CUX 3043.00 EZMR114125CUX 3043.00 EZMH114125CUX 3043.00
5800 A Al EZM115125c2354.00 EZMR115125c2354.00 EZMH115125c2910.00
1200 A Cu EZM115125CUX 3742.00 EZMR115125CUX 3742.00 EZMH115125CUX 3742.00
6800 A Al EZM116125c2792.00 EZMR116125c2792.00 EZMH116125c3549.00
1200 A Cu EZM116125CUX 4438.00 EZMR116125CUX 4438.00 EZMH116125CUX 4438.00
225 A Maximum Branch Units (Order Type QBP-TM, QDP-TM, QGP-TM or QJP-TM Circuit Breakers Separately) d
1Ø3W
120/240 Vac
2P Branch
Circuit Breakers
17.38
2800 A Al EZM112225c2273.00 EZMR112225c2273.00 EZMH112225c2474.00
1200 A Cu EZM112225CUX 3615.00 EZMR112225CUX 3615.00 EZMH112225CUX 3615.00
3800 A Al EZM113225c2792.00 EZMR113225c2792.00 EZMH113225c3069.00
1200 A Cu EZM113225CUX 4438.00 EZMR113225CUX 4438.00 EZMH113225CUX 4438.00
4800 A Al EZM114225c3588.00 EZMR114225c3588.00 EZMH114225c4028.00
1200 A Cu EZM114225CUX 5705.00 EZMR114225CUX 5705.00 EZMH114225CUX 5705.00
51200 A Al/Cu EZM115225 4715.00 EZMR115225 4715.00 EZMH115225 4715.00
1200 A Cu EZM115225CU 7090.00 EZMR115225CU 7090.00 EZMH115225CU 7090.00
Table 2.16: Branch Units—225 A Maximum Commercial
(Order Type QBP-TM, QDP-TM, QGP-TM or QJP-TM Circuit Breakers Separately, see page 2-15)e
System
Type
Number
of Meter
Sockets
Horizontal Cross Bus
Ratingand Bus Bar
Material
Ringless Type 5-Jaw Meter Socket
with Lever Bypass and Jaw Releasef
Ring Type 5-Jaw Meter Socket
with Test Block Bypass.
Meets EUSERC Requirements
Cat. No. Width
(in.) $ Price Cat. No. Width
(in.) $ Price
1Ø3W
120/240 Vac
2P Branch
Circuit Breakers
1
1200 A Al/Cu EZML111225
19.44
2453.00 EZMT111225g22.42 3387.00
1200 A Cu EZML111225CU 3901.00 ———
1200 A Al/Cu EZML111225Dh2576.00 ———
2
1200 A Al/Cu EZML112225
19.44
4466.00 EZMT112225g22.42 6143.00
1200 A Cu EZML112225CU 7101.00 ———
1200 A Al/Cu EZML112225Dh4689.00 ———
3
1200 A Al/Cu EZML113225
19.44
6579.00 EZMT113225gi 22.42 9215.00
1200 A Cu EZML113225CU 10461.00 ———
1200 A Al/Cu EZML113225Dh6908.00 ———
4
1200 A Al/Cu EZML114225
19.44
8813.00 ———
1200 A Cu EZML114225CU 14013.00 ———
1200 A Al/Cu EZML114225Dh9254.00 ———
Table 2.17: Branch Units—400 A Maximum Commercial
System
Type
Number
of Meter
Sockets
Main
Cross Bus
Rating
and Bus Bar
Material
Ringless Type 5-Jaw Meter Socket
with Lever Bypass and Jaw Release.
Includes Factory-Installed 400 A Type DJM
Circuit Breaker jk
Ringless Type K Bolt-on
4-Jaw Meter Socket with Manual Bypass.
Includes Factory-Installed 400 A Type DJM
Circuit Breaker j
Cat. No. Width
(in.) $ Price Cat. No. Width
(in.) $ Price
1Ø3W
120/240 Vac
2P Branch
Circuit Breakers
1 1200 A Cu EZML111400 23.21 5981.00 EZMK111400 27.56 7424.00
2 1200 A Cu EZML112400 23.21 11963.00 EZMK112400 27.56 14531.00
EZMT111225
EZMH114125
EZML113225
DE4 Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2-12 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
2METERING EQUIPMENT
EZ Meter-Pak® Meter Centers Main Devices
Class 4162
3Ø4W EZ Meter-Pak Meter Centers—3Ø Indoor/Rainproof, UL Listed
Select EZM meter center short circuit current rating from Table 2.12 on page 2-9. Using this table as a reference, make
the following selections:
1. Select 3Ø EZM main device below with an equal or higher short circuit rating than the application from Tables 2.18 and 2.19.
2. Select EZM 3Ø branch units from Tables 2.20, 2.21 and 2.22.
3. Select proper 2P type QO, QO-VH, QOH, QBP-TM, QDP-TM, QGP-TM or QJP-TM or 3P QBP-TM, QDP-TM, QGP-TM or QJP-TM
branch circuit breakers for use as tenant mains in branch unit; from Table 2.24.
4. Select accessories as required, from Table 2.25.
5. Dimensions, page 2-16.
Main Devices—NEMA 3R Construction
aAvailable by special order with main circuit breaker supplied with other standard ampere ratings, consult your nearest Field Sales Office (allow 6 weeks
for delivery).
bAmpere rating of the PA circuit breaker supplied with this main can be changed to a LOWER value in the field by ordering a different set of rating columns,
refer to Supplementary Digest, Section 3, for listing.
cSupplied with copper horizontal bus bars and aluminum vertical bus bars.
d225 A tap box supplied with isolated neutral that cannot be bonded.
eFor mechanical lugs (3/0 AWG–600 kcmil) order kit CMELK4, Price $91.00. Kit includes 4 lugs only. Multiple kits may be required, consult factory. For
crimp-type lugs refer to Anderson Electrical Connector Products Catalog AEC-40R.
fHas a 100 kA short circuit current rating.
gDoes not meet EUSERC requirements.
hTap box is suitable for use on LINE or LOAD side of service equipment. Supplied with isolated neutral and provided with neutral bonding kit for use as
required. Refer to page 2-9 for appropriate short circuit current ratings.
iFeed-thru lug kit available, see Accessories, page 2-15.
Table 2.18: Main Device, Overhead/Underground Feed
System
Type Ampere
Rating
Horizontal Cross Bus
Rating and Bus Bar
Material Cat. No. Width
(in.) $ Price
Factory-Installed Line Side Lug
(Conductors per Phase and Neutral)
Wire Size
(AWG–kcmil)
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing)
65 kA Short Circuit Current Rating (400–1600 A Max.), 100 kA Short Circuit Current Rating (2000 A Max.)
3Ø4W 208Y/120 Vac
or
240/120 Vac Delta
400 400 A Al EZM3400CBa18.66 6620.00 (1) 1–600 or (2) 1–250
600 600 A Al EZM3600CBa18.66 10247.00 (3) 3/0–500
800 800 A Al EZM3800CBa18.66 13650.00 (3) 3/0–500
1000 1000 A Al EZM31000CBa18.66 17027.00 (3) 3/0–500
1200 1200 A Al/Cu EZM31200CBbc 30.19 23127.00 (4) 1/0–750
1600 1200 A Al/Cu EZM31600CBbc 30.19 35288.00 (6) 1/0–750
2000 1200 A Al/Cu EZM32000CBc30.19 57518.00 (6) 1/0–750 or (12) 1/0–250
Main Fusible Switches (3Ø Incoming and 3Ø Outgoing)
100 kA Short Circuit Current Rating, Requires 300 Vac Class T Fuses (Order Separately)
3Ø4W 208Y/120 Vac
or
240/120 Vac Delta
400 400 A Al EZM3400FS 18.66 4466.00 (1) 1–600 or (2 )1–250
600 600 A Al EZM3600FS 18.66 8373.00 (3) 3/0–500
800 800 A Al EZM3800FS 18.66 11565.00 (3) 3/0–500
Main Lugs Terminal Boxes (3Ø Incoming and 3Ø Outgoing)
3Ø4W 208Y/120 Vac
or
240/120 Vac Delta
225 800 A Al EZM3225TBd11.50 1013.00 (1) 4–300
400 800 A Al EZM3400TBh17.00 1113.00 (2) 3/0–500
600 800 A Al EZM3600TBh17.00 1196.00 (2) 1/0–750 or (4) 1/0–300
800 800 A Al EZM3800TBh18.66 1442.00 (4) 3/0–500
800 800 A Cu EZM3800TBCUih 23.93 3545.00 (4) 3/0–500
1600 1200 A Al/Cu EZM31600TBcih 22.33 4028.00 (6) 3/0–600
2000 1200 A Cu EZM32000TBh30.19 11820.00 6 (Order Lugs Separately)
Table 2.19: Main Device, Underground Feed Only
System Type Ampere
Rating
Horizontal Cross Bus
Rating and Bus Bar
Material
Cat. No.
Meets EUSERC
Requirements Width $ Price
Factory-Installed Lug Landings
For use with Crimp-Type Lugs
(2-Hole Mounting)
Qty. per Phase and Neutrale
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing)e
65 kAShort Circuit Current Rating (400–800 and 1600 A Max.),
100 kA Short Circuit Current Rating (1000, 1200 and 2000 A Max.)
3Ø4W 208Y/120 Vac
or
240/120 Vac Delta
400 400 A Al EZM3400CBUa20.46 7178.00 1 (Order Lugs Separately)
600 600 A Al EZM3600CBUa20.46 10806.00 2 (Order Lugs Separately)
800 800 A Al EZM3800CBUa20.46 14115.00 2 (Order Lugs Separately)
1000 1000 A Al/Cu EZM31000CBUcf 34.19 17943.00 3 (Order Lugs Separately)
1200 1200 A Al/Cu EZM31200CBUcf 34.19 24323.00 3 (Order Lugs Separately)
1600 1200 A Al/Cu EZM31600CBUbcg 27.69 37170.00 6 (Order Lugs Separately)
2000 1200 A Al/Cu EZM32000CBUcg 30.19 57255.00 6 (Order Lugs Separately)
Main Fusible Switches (3Ø Incoming and 3Ø Outgoing)e
Requires 300 Vac Class T Fuses (Order Separately)
3Ø4W
208Y/120 Vac
or
240/120 Vac
Delta
400 400 A Al EZM3400FSU 20.46 6978.00 1 (Order Lugs Separately)
600 600 A Al EZM3600FSU 20.46 11364.00 2 (Order Lugs Separately)
800 800 A Al EZM3800FSU 20.46 15152.00 2 (Order Lugs Separately)
Main Lugs Terminal Boxes (3Ø Incoming and 3Ø Outgoing) e
3Ø4W 208Y/120 Vac
or
240/120 Vac Delta
400 400 A Al EZM3400TBUh16.16 1838.00 1 (Order Lugs Separately)
800 800 A Al EZM3800TBUh24.16 2100.00 2 (Order Lugs Separately)
1200 1200 A Al/Cu EZM31200TBUch 32.16 4463.00 3 (Order Lugs Separately)
EZM31600CB
EZM3600FS
New!
New!
DE4 Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
© 2009 Schneider Electric
All Rights Reserved 2-13
EZ Meter-Pak® Meter Centers Branch Devices
Class 4162
Branch Devices—NEMA 3R Construction
aFor 1200 A main cross bus, add suffix “X” to catalog number. Example: EZMR313125X. Add 3% adder to list per device. Allow 6 weeks for delivery.
bSnap-On aluminum sealing rings supplied as standard.
cFor 240/120 Vac Delta Systems add Suffix “CA” to catalog number (Example: EZM314125CA). All meter sockets are phased A and C only. Price remains
the same as the base catalog number. Order only branch units, not stocked in PDS (6-week delivery).
dSupplied with removable drip hood and equipped with an indoor top endwall with knockouts provided.
eDistance between meter sockets as measured from centerline to centerline is 10 inches.
f2P Type QO (40–125 A, 10 kA max. meter center SCCR) or QO-VH and QO-H (40–60 A, 100 kA max. meter center SCCR) may be installed using
EZM125QOA adapter kit, refer to page 2-15.
gFor 240/120 Vac Delta Systems add Suffix “CA” to catalog number (Example: EZM314125CA). All meter sockets are phased A and C only. Price remains
the same as the base catalog number. Order only branch units, not stocked in PDS (6-week delivery).
h2P Type QO (40–125 A, 10 kA max. meter center SCCR) or QO-VH and QO-H (40–60 A, 100 kA max. meter center SCCR) may be installed using
EZM125QOA adapter kit, refer to page 2-15.
iSupplied with bondable neutral, suitable for use as service equipment. Use main lugs tap box type EZM-TBU for Six Disconnect Rule applications to
feed this device. Supplied with copper horizontal bus bars and aluminum vertical bus bars.
jSupplied with removable drip hood and equipped with an indoor top endwall with knockouts provided.
kDoes not meet EUSERC 48 in. minImum / 75 in. maximum meter height requirements for outdoor installations. The bottom meter socket is 37 inches above
ground when the device is mounted with the top meter socket at 75 inches above ground. EUSERC indoor requirements are 36 in. minimum / 75 in. maximum.
400 A maximum Commercial Branch Units . . . . . . . . . . . . . . . . . Page 2-14.
Table 2.20: Branch Units—3Ø Incoming and 1Ø Outgoing
System
Type Width
(in.)
Number
of
Meter
Sockets
Horizontal
Cross Bus
Ratinga
and Bus Bar
Material
Ring Type
5-Jaw Meter Socket
without Bypassb
Ringless Type
5-Jaw Meter Socket
without Bypass
Ringless Type
5-Jaw Meter Socket
with Horn Bypass
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
125 A Maximum (Order Type QO, QO-VH or QOH Circuit Breakers Separately)cd
3Ø4W
208Y/120 Vac
5-Jaw-Meter Socket
2P Branch
Circuit Breakers
12.25
3
800 A Al EZM313125a1554.00 EZMR313125a1554.00 EZMH313125a1875.00
800 A Cu EZM313125M10e4253.00 — — — —
1200 A Cu EZM313125CUX 2473.00 EZMR313125CUX 2473.00 EZMH313125CUX 2980.00
4
800 A Al EZM314125a2034.00 EZMR314125a2039.00 EZMH314125a2474.00
800 A Cu EZM314125M10e5670.00 — — — —
1200 A Cu EZM314125CUX 3234.00 EZMR314125CUX 3234.00 EZMH314125CUX 3933.00
5
800 A Al EZM315125a2592.00 EZMR315125a2592.00 EZMH315125a3111.00
800 A Cu EZM315125M10e7088.00 — — — —
1200 A Cu EZM315125CUX 4121.00 EZMR315125CUX 4121.00 EZMH315125CUX 4947.00
6800 A Al EZM316125a2991.00 EZMR316125a2991.00 EZMH316125a3788.00
1200 A Cu EZM316125CUX 4756.00 EZMR316125CUX 4756.00 EZMH316125CUX 6023.00
225 A Maximum (Order Type QBP-TM, QDP-TM,QGP-TM or QJP-TM Circuit Breakers Separately)cf
3Ø4W
208Y/120 Vac
5-Jaw-Meter Socket
2P Branch
Circuit Breakers
17.38
2800 A Al EZM312225a2273.00 EZMR312225a2273.00 EZMH312225a2474.00
1200 A Cu EZM312225CUX 3615.00 EZMR312225CUX 3615.00 EZMH312225CUX 2473.00
3800 A Al EZM313225a2792.00 EZMR313225a2792.00 EZMH313225a3111.00
1200 A Cu EZM313225CUX 4438.00 EZMR313225CUX 4438.00 EZMH313225CUX 4947.00
4800 A Al EZM314225a3749.00 EZMR314225a3749.00 EZMH314225a4148.00
1200 A Cu EZM314225CUX 5961.00 EZMR314225CUX 5961.00 EZMH314225CUX 6595.00
51200 A Al/Cu EZM315225 4920.00 EZMR315225 5457.00 EZMH315225 5718.00
1200 A Cu EZM315225CU 7409.00 EZMR315225CU 7409.00 EZMH315225CU 8154.00
Table 2.21: Branch Units—225 A Maximum Commercial
System
Type
Number
of
Meter
Sockets
Horizontal
Cross Bus
Rating
and Bus Bar
Material
Ringless Type
Meter Socket
without Bypass
Ringless Type Meter Socket
with Lever Bypass
and Jaw Release
Ring Type Meter Socket
with Test Block Bypass.
Meets EUSERC
Requirements
Cat. No. Width
(in.) $ Price Cat. No. Width
(in.) $ Price Cat. No. Width
(in.) $ Price
3Ø Incoming and 1Ø Outgoing g
(Order Type QBP-TM, QDP-TM,QGP-TM or QJP-TM circuit breakers separately) h
3Ø4W
208Y/120 Vac
5-Jaw
Meter Sockets
2P
Branch
Circuit
Breakers
1 1200 A Al/Cu — — — — — — EZMT311225i22.42 3545.00
2
1200 A Al/Cu — — — EZML312225
19.44
4266.00 EZMT312225i22.42 6695.00
1200 A Cu — — — EZML312225CU 6785.00 ———
1200 A Al/Cu — — — EZML312225Dj4479.00 ———
3
1200 A Al/Cu — — — EZML313225
19.44
6420.00 EZMT313225ik 22.42 10041.00
1200 A Cu — — — EZML313225CU 10208.00 ———
1200 A Al/Cu — — — EZML313225Dj6741.00 ———
4
1200 A Al/Cu — — — EZML314225
19.44
8732.00 —
—
—
1200 A Cu — — — EZML314225CU 13884.00 ——
1200 A Al/Cu — — — EZML314225Dj9168.00 ——
3Ø Incoming and 3Ø Outgoing (Order QBP-TM, QDP-TM, QGP-TM or QJP-TM circuit breakers separately, see page 2-15)
3Ø4W
240/120 Vac
Delta
or
208Y/120 Vac
7-Jaw
Meter Socket
3P
Branch
Circuit
Breakers
1
1200 A Al/Cu — — — EZML331225
19.44
2792.00 EZMT331225i22.42 3938.00
1200 A Cu — — — EZML331225CU 4438.00 ———
1200 A Al/Cu — — — EZML331225Dj2931.00 ———
2
1200 A Al/Cu EZMR332225
19.44
4686.00 EZML332225
19.44
5105.00 EZMT332225i22.42 6957.00
1200 A Cu EZMR332225CU 7451.00 EZML332225CU 8117.00 ———
1200 A Al/Cu — — EZML332225Dj5360.00 ———
3
1200 A Al/Cu EZMR333225
19.44
7337.00 EZML333225
19.44
7794.00 EZMT333225ik 22.42 10304.00
1200 A Cu EZMR333225CU 11664.00 EZML333225CU 12395.00 ———
1200 A Al/Cu — — EZML333225Dj8184.00 ———
4
1200 A Al/Cu EZMR334225
19.44
10169.00 EZML334225
19.44
10667.00 —
—
—
1200 A Cu EZMR334225CU 16167.00 EZML334225CU 16959.00 ——
1200 A Al/Cu — — EZML334225Dj11214.00 ——
EZML313225
EZMT311225
EZMT311225
Without Cover
DE4 Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2-14 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
2METERING EQUIPMENT
EZ Meter-Pak® Meter Centers EZM Main Devices
Class 4162
Branch Devices—NEMA 3R Construction (Continued)
aDJM circuit breaker has adjustable trip settings from 160–400 A. If required, order seal kit, catalog number 29375. DJM circuit breaker terminal lug kit
32508 factory-installed and accomodates (1) 2 AWG–500 kcmil Al or (1) 2 AWG–600 kcmil Cu per phase. Alternate lug kit 32510 for DJM circuit breaker
is available, see Accessories, page 2-15. Additional field-installed DB circuit breaker accessories are available, see page 7-35.
bSupplied with Class 320 lever bypass meter socket. Use anti-inversion clip kit, catalog number MMLRK, if required. Order from page 2-15.
cFor 240/120 Vac Delta Systems add Suffix “CA” to catalog number (Example: EZML312400CA). All meter sockets are phased A and C only. Price
remains the same as the base catalog number. “Order only” branch units, not stocked in PDS (4–6 week delivery). Order point Lexington.
EZM Main with Busway Tap
EZ Meter-Pak metering equipment is available for use in high rise applications for connection to 800–5000 A I-Line® or
I-Line II plug-in busway installed as a vertical riser. Three phase only EZM main devices in the form of a main circuit
breaker or main fusible switch are available with an integral busway tap extending from the right or left side of the main
device and phased to align with the busway for either neutral front or neutral back installations.
Busway Mains, 3Ø only (Indoor only) ordering instructions:
Step 1: Determine height to center line of busway plug-in opening, check local utility requirements for minimum and
maximum meter socket heights.
Step 2: Determine side of EZM main section for busway tap to extend from (busway tap is an integral part of the main
and extends to the left or right on the EZM device as viewed from the front).
Step 3: Check phasing of busway riser to insure that it matches phasing of busway tap on main section (indicated as
neutral front or neutral back as viewed from the front).
Step 4: Select Cat. No. from tables below.
Step 5: Busway main devices are build to order specials and require 4 to 6 weeks for delivery (order point Lexington).
dHas a maximum 65 kA short circuit current rating.
eHas a 100 kA short circuit current rating. Requires Class T ( 300 Vac) fuses, order separately.
fSupplied with copper horizontal bus bars and aluminum vertical bus bars.
gRequires use of branch units supplied with 1200 A horizontal cross bus.
Note: Dimensions shown will position the centerline of top meter socket of a 125 A, 5-Gang or 6-Gang branch unit at 72" above floor level. Check with utility
to meet local requirements.
Table 2.22: Branch Units—400 A Maximum Commercial
System
Type
Number
of Meter
Sockets
Horizontal
Cross Bus
Rating
Ringless Type Meter Socket
with Lever Bypass and Jaw Release—
IncludesFactory-Installed
400 A Type DJM Circuit Breaker. ab
Ringless Type K Bolt-on Meter Socket
with Manual Bypass—
Includes Factory-Installed
400 A Type DJM Circuit Breaker. a
Cat. No. Width
(in.) $ Price Cat. No. Width
(in.) $ Price
3Ø Incoming and 1Ø Outgoing c
3Ø4W
208Y/120 Vac
5-Jaw Meter Socket
2P Branch Circuit Breakers
1 1200 A Cu EZML311400 23.21 5981.00 EZMK311400 27.56 8924.00
2 1200 A Cu EZML312400 23.21 11963.00 EZMK312400 27.56 17534.00
3Ø Incoming and 3Ø Outgoing
3Ø4W
240/120 Vac Delta
or 208Y/120 Vac
7-Jaw Meter Socket
3P Branch Circuit Breakers
1 1200 A Cu EZML331400 23.21 6978.00 EZMK331400 27.56 10515.00
2 1200 A Cu EZML332400 23.21 13956.00 EZMK332400 27.56 20715.00
Table 2.23: EZM Mains with Busway Tap (Three Phase Only—Note positioning left or right below)
Ampere
Rating Width
(in.)
Horizontal
Cross Bus
Rating
Main Circuit Breaker with Busway Tap dMain Fusible Switch with Busway Tap e
Neutral Front Neutral Back $ Price Neutral Front Neutral Back $ Price
Busway to RIGHT of metering equipment lineup
400 18.66 400 A Al EZM3400CBNFBTR EZM3400CBNBBTR 8886.00 EZM3400FSNFBTR EZM3400FSNBBTR 6732.00
600 18.66 600 A Al EZM3600CBNFBTR EZM3600CBNBBTR 12513.00 EZM3600FSNFBTR EZM3600FSNBBTR 10640.00
800 18.66 800 A Al EZM3800CBNFBTR EZM3800CBNBBTR 15744.00 EZM3800FSNFBTR EZM3800FSNBBTR 13830.00
1000 18.66 1000 A Al EZM31000CBNFBTRgEZM31000CBNBBTRg19292.00 ———
1200 30.19 1200 A Al/Cu EZM31200CBNFBTRfg EZM31200CBNBBTRfg 25394.00 ———
Busway to LEFT of metering equipment lineup
400 18.66 400 A Al EZM3400CBNFBTL EZM3400CBNBBTL 8886.00 EZM3400FSNFBTL EZM3400FSNBBTL 6732.00
600 18.66 600 A Al EZM3600CBNFBTL EZM3600CBNBBTL 12513.00 EZM3600FSNFBTL EZM3600FSNBBTL 10640.00
800 18.66 800 A Al EZM3800CBNFBTL EZM3800CBNBBTL 15744.00 EZM3800FSNFBTL EZM3800FSNBBTL 13830.00
1000 18.66 1000 A Al EZM31000CBNFBTLgEZM31000CBNBBTLg19292.00 ———
1200 30.19 1200 A Al/Cu EZM31200CBNFBTLfg EZM31200CBNBBTLfg 25394.00 ———
EZMK311400
56.11
1425
31.11
790
4.11
104
Floor Level
Top of EZM
Mounting
Channel
EZM
Bus Tap
C
L of Busway
Plug-in Opening
EZM3800FSNBBTL
Width
(See Note)
56.11
1425
31.11
790
4.11
104
Floor Level
Top of EZM
Mounting
Channel
EZM
Bus Tap
C
L of Busway
Plug-in Opening
EZM3800CBNFBTR
Width
(See Note)
5.75
146
C
L of
Busway
Plan View Detail
Wall
DE4 Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
www.schneider-electric.us
2METERING EQUIPMENT
© 2009 Schneider Electric
All Rights Reserved 2-15
EZ Meter-Pak® Meter Centers
Class 4162
EZ Meter-Pak® Meter Centers and Accessories
Accessories
eConsult your nearest Square D/Schneider Electric sales office for details.
fAll sockets include 5th Jaw factory-installed except EZM11__ devices.
gMeter center short circuit current rating is 10,000 RMS symmetrical amperes with manual
circuit closers installed (bypass is not designed for use as continuous duty).
hFor use on ring type meter sockets only.
Busway Transition Section
EZM busway transition section provides no overcurrent protection for
the downstream EZM branch units. Tenant main circuit breakers in
these branch units must be selected as “fully rated” equipment.
(Examples: QO for 10 kA, QO-VH for 22 kA or QOH for 42 kA.)
Table 2.24: Tenant Circuit Breakers
Poles Ampere
Rating
10 k AIR 22 k AIR 42 k AIR 100 k AIR
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
125 A Max. EZM Branch Unit Tenant Circuit Breakers
2
40 QO240 67.00 QO240VH 146.00 QOH240 317.00 ——
50 QO250 67.00 QO250VH 146.00 QOH250 317.00 ——
60 QO260 67.00 QO260VH 146.00 QOH260 317.00 ——
70 QO270 134.00 QO270VH 224.00 QOH270 528.00 ——
80 QO280 189.00 QO280VH 315.00 QOH280 651.00 ——
90 QO290 189.00 QO290VH 315.00 QOH290 651.00 ——
100 QO2100 189.00 QO2100VH 315.00 QOH2100 651.00 ——
110 QO2110 428.00 QO2110VH 1034.00 QOH2110 1389.00 ——
125 QO2125 428.00 QO2125VH 1034.00 QOH2125 1389.00 ——
225 A Max. EZM Branch Unit Tenant Circuit Breakers
Poles Ampere
Rating 10 k AIR 25 k AIR 65 k AIR 100 k AIR
2
40 QO240a67.00 QO240VHba 146.00 QOH240ca 317.00 ——
50 QO250a67.00 QO250VHba 146.00 QOH250ca 317.00 ——
60 QO260a67.00 QO260VHba 146.00 QOH260ca 317.00 ——
70 QBP22070TM 474.00 QDP22070TM 1143.00 QGP22070TM 1521.00 QJP22070TM 1890.00
80 QBP22080TM 474.00 QDP22080TM 1143.00 QGP22080TM 1521.00 QJP22080TM 1890.00
90 QBP22090TM 474.00 QDP22090TM 1143.00 QGP22090TM 1521.00 QJP22090TM 1890.00
100 QBP22100TM 474.00 QDP22100TM 1143.00 QGP22100TM 1521.00 QJP22100TM 1890.00
110 QBP22110TM 474.00 QDP22110TM 1143.00 QGP22110TM 1521.00 QJP22110TM 1890.00
125 QBP22125TM 474.00 QDP22125TM 1143.00 QGP22125TM 1521.00 QJP22125TM 1890.00
150 QBP22150TM 474.00 QDP22150TM 1143.00 QGP22150TM 1521.00 QJP22150TM 1890.00
175 QBP22175TM 474.00 QDP22175TM 1143.00 QGP22175TM 1521.00 QJP22175TM 1890.00
200 QBP22200TM 474.00 QDP22200TM 1143.00 QGP22200TM 1521.00 QJP22200TM 1890.00
225 QBP22225TM 474.00 QDP22225TM 1143.00 QGP22225TM 1521.00 QJP22225TM 1890.00
3
70 QBP32070TM 1248.00 QDP32070TM 1784.00 QGP32070TM 2442.00 QJP32070TMd2796.00
80 QBP32080TM 1248.00 QDP32080TM 1784.00 QGP32080TM 2442.00 QJP32080TMd2796.00
90 QBP32090TM 1248.00 QDP32090TM 1784.00 QGP32090TM 2442.00 QJP32090TMd2796.00
100 QBP32100TM 1248.00 QDP32100TM 1784.00 QGP32100TM 2442.00 QJP32100TMd2796.00
110 QBP32110TM 1248.00 QDP32110TM 1784.00 QGP32110TM 2442.00 QJP32110TMd2796.00
125 QBP32125TM 1248.00 QDP32125TM 1784.00 QGP32125TM 2442.00 QJP32125TMd2796.00
150 QBP32150TM 1248.00 QDP32150TM 1784.00 QGP32150TM 2442.00 QJP32150TMd2796.00
175 QBP32175TM 1248.00 QDP32175TM 1784.00 QGP32175TM 2442.00 QJP32175TMd2796.00
200 QBP32200TM 1248.00 QDP32200TM 1784.00 QGP32200TM 2442.00 QJP32200TMd2796.00
225 QBP32225TM 1248.00 QDP32225TM 1784.00 QGP32225TM 2442.00 QJP32225TMd2796.00
aMust use EZM125QOA adapter.
bQO-VH tenant circuit breaker is rated 22 k AIR max.
cQOH tenant circuit breaker is rated 42 k AIR max.
d3-pole QJP tenant circuit breaker is rated 65 k AIR max. at 240/120 Vac,
3Ø4W High Leg Delta, or 100 k AIR max. at 208Y/120 Vac, 3Ø4W.
QO2100VH
2P, Plug-on Type
Circuit Breaker
QDP22200TM
Table 2.25: Accessories
Accessory Description Cat. No. $ Price
1200 A Bus
Extension (Indoor/
Outdoor Cu bus)
1Ø3W Bus Extension (6 in.wide)
1Ø3W Bus Extension (12 in.wide)
3Ø4W Bus Extension (6 in. wide)
3Ø4W Bus Extension (12 in. wide)
EZM1EXT6
EZM1EXT
EZM3EXT6
EZM3EXT
767.00
767.00
966.00
966.00
1200 A Bussed
Corner Sections
(Indoor Cu bus only)
1Ø3W Inside Corner (14.75 in. wide)
1Ø3W Outside Corner (6.20 in. wide)
3Ø4W Inside Corner (14.75 in. wide)
3Ø4W Outside Corner (6.20 in. wide)
EZM1CORNER
EZM1ELBOW
EZM3CORNER
EZM3ELBOW
1788.00
1788.00
2217.00
2217.00
1200 A Transition
Sections—
Old to New
(10.7 in. wide Cu
bus)
Add right of old style 1Ø EZM lineup
Add right of old style 3Ø EZM lineup
Add left of old style 1Ø EZM lineup
Add left of old style 3Ø EZM lineup
EZM1TRANR
EZM3TRANR
EZM1TRANL
EZM3TRANL
237.00
252.00
315.00
332.00
Mounting Channel 72" long EZM72MC 63.00
Secondary Surge
Arrester Mounting kit For use with 1 or 2-SDSA1175 or 1-SDSA3650
(order surge arrester separately) MMSAMKe80.00
Stud Kit for EZM-TB
400–600 A terminal
box
Includes (2) 1/2 in.-13 studs per pad and mounting
hardware. Four pads per kit. With suffix TBCU only. EZMSK2 246.00
Al/Cu Lug Kits
(Each kit includes
three, 2-barrel lugs.)
(1) 1/0–600 kcmil or (2) 1/0–250 kcmil per lug MMLK250 150.00
(2) 3/0–500 kcmil per lug MMLK500 200.00
(2) 2–600 kcmil per lug MMLK600 233.00
Feed -Thru for
EZM-TBCU 800 A
Ter mi na l Box
(4) 750 kcmil Al/Cu lugs per phase and neutral. Al
wire 600 A max. Cu wire 800 A max. EZM600FTLK3 480.00
Feed-Thru for
EZM-TB 1600 A
Ter mi na l Box
(24) additional lugs, 600 kcmil Al/Cu, (6) per phase
and neutral. EZM1600FTLK3 915.00
Fifth jaw Kit 1 per kit 5J f18.30
Horn Bypass Kit Use with Type EZMR 1Ø meter socket only MMHB 16.70
Slider Type Manual
Circuit Closer For (1) 125–225 A ring-type socket only—
indoor/outdoor MM200MBgh 171.00
Anti-inversion Clip Rejects 100 A and 200 A watt-hour meters in Class
320 meter sockets in Type EZML branch units. MMLRK 12.00
QO Adapter for bolt-
on Q-frame tenant
circuit breakers
For 2P Type QO (40–125 A, 10 kA max. meter
center SCCR) or QO-VH and QOH (40–60 A, 100
kA max. meter center SCCR) EZM125QOA 273.00
DJM Circuit Breaker
Alternate Lug (DE2) Kit includes (3) 2-barrel lugs for (2) 2/0 AWG–350
kcmil AL/Cu or (2) 2/0 AWG–500 kcmil AL per lug. 32510 —
DJM Circuit Breaker
Seal Kit Tamper-evident kit to seal DJM trip dial cover, (1)
per circuit breaker, if required. Meets NEC 240-6 [c] 29375 —
Meter Socket Closing
Plates Lexan Closing Plate—EZM, EZMR, EZMH, EZMT
Metal Closing plate—EZMR, EZMH, EZML 29007
RSG4 10.10
122.00
Sealing Rings Snap-on (Stainless Steel)
Screw-Type (Aluminum)
Latch-Type (Aluminum)-standard
ARP00026
29008W
2920910001
16.70
20.10
8.00
Barrel Lock Kit For use on ringless EZM or MP branch unit covers,
includes 6 each of head protectors, lock nuts and
sealing caps. (Barrel lock not included.) MMBLC 66.00
Tenant Circuit
Breaker Filler Plates 125 A Branches—2P Type QO (2 per opening)
225 A Branches—2P and 3P Q-Frame QOFP
EZMPCP 3.60
26.00
Table 2.26: EZM Busway Transition Sections (3Ø only)
Ampere
Rating I-Line® Busway location Neutral Front Neutral Back Width
(in.) $ Price
1200 RIGHT of EZM Transition Section EZM3BUSRF EZM3BUSRB 12.00 2625.00
1200 LEFT of EZM Transition Section EZM3BUSLF EZM3BUSLB 12.00 2625.00
Table 2.25: Accessories (continued)
Accessory Description Cat. No. $ Price
4.11
104
56.11
1425
16.11
409
55.11
1400
1.00
25
Floor Level
Top of EZM
Mounting
Channel
EZM
Bus Tap
C
L of Busway
Plug-in Opening
EZM3BUSRF and EZM3BUSRB
4.11
104
56.11
1425
16.11
409
55.11
1400
1.00
25
Floor Level
Top of EZM
Mounting
Channel
EZM
Bus Tap
C
L of Busway
Plug-in Opening
EZM3BUSLF and EZM3BUSLB
Width Width
DE2A Discount
Schedule
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2-16 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
2METERING EQUIPMENT
EZ Meter-Pak® Meter Centers Dimensions
Class 4162
Dimensions
aEach leg of elbow section measures 6.17 in. corner of wall to start of next enclosure.
bDevice supplied without mounting channel, secure to wall by use of swingable mounting feet.
cEach leg of this corner section measures 14.72 in. from wall to start of next enclosure.
dStandard branch units are available without suffix added.
Table 2.27: Main Devices Dimensions (in.)
Cat. No. Height Width Depth MC Cat. No. Height Width Depth MC
EZM11000CB 53.97 18.66 11.50 34.30 EZM1ELBOW (indoor only) a19.50 14.52 8.01 11.85 b
EZM11000CBU 70.05 34.19 18.33 46.99 EZM31000CB 53.97 18.66 11.50 34.30
EZM11200CB 61.19 30.19 18.33 38.13 EZM31000CBU 70.05 34.19 18.33 46.99
EZM11200CBU 70.05 34.19 18.33 46.99 EZM31200CB 61.19 30.19 18.33 38.13
EZM11200FS 61.19 30.19 18.33 38.13 EZM31200CBU 70.05 34.19 18.33 46.99
EZM11200FSU 70.05 34.19 18.33 46.99 EZM31200TBU 44.71 33.16 11.12 31.17
EZM11200TBU 44.71 33.16 11.12 31.17 EZM31600CB 61.19 30.19 18.33 38.13
EZM11600CB 61.19 30.19 18.33 38.13 EZM31600CBU 69.69 27.69 18.45 49.12
EZM11600CBU 69.69 27.69 18.45 49.12 EZM31600TB 51.58 22.33 13.00 27.92
EZM11600TB 51.58 22.33 13.00 27.92 EZM32000CB 68.91 30.19 18.33 44.25
EZM12000CB 68.91 30.19 18.33 44.25 EZM32000CBU 68.91 30.19 18.33 44.25
EZM12000CBU 68.91 30.19 18.33 44.25 EZM32000TB 71.09 30.19 21.46 37.62
EZM12000TB 71.09 30.19 21.46 37.62 EZM3225TB 21.81 11.50 5.81 13.00 b
EZM1225TB 21.81 11.50 5.81 13.00 bEZM3400CB 53.97 18.66 11.50 34.30
EZM1400CB 53.97 18.66 11.50 34.30 EZM3400CBU 69.03 20.46 11.50 49.37
EZM1400CBU 69.03 20.46 11.50 49.37 EZM3400FS 53.97 18.66 11.50 34.30
EZM1400FS 53.97 18.66 11.50 34.30 EZM3400FSU 69.03 20.46 11.50 49.37
EZM1400FSU 69.03 20.46 11.50 49.37 EZM3400TB 30.46 17.00 6.53 16.29
EZM1400TB 30.46 17.00 6.53 16.29 EZM3400TBU 35.71 17.16 8.00 27.17
EZM1400TBU 35.71 17.16 8.00 27.17 EZM3600CB 53.97 18.66 11.50 34.30
EZM1600CB 53.97 18.66 11.50 34.30 EZM3600CBU 69.03 26.19 11.65 49.37
EZM1600CBU 69.03 20.46 11.50 49.37 EZM3600FS 53.97 18.66 11.50 34.30
EZM1600FS 53.97 18.66 11.50 34.30 EZM3600FSU 69.03 26.19 11.65 49.37
EZM1600FSU 69.03 20.46 11.50 49.37 EZM3600TB 30.46 17.00 6.53 16.29
EZM1600TB 30.46 17.00 6.53 16.29 EZM3800CB 53.97 18.66 11.50 34.30
EZM1800CB 53.97 18.66 11.50 34.30 EZM3800CBU 69.03 26.19 11.65 49.37
EZM1800CBU 69.03 20.46 11.50 49.37 EZM3800FS 53.97 18.66 11.50 34.30
EZM1800FS 53.97 18.66 11.50 34.30 EZM3800FSU 69.03 26.19 11.65 49.37
EZM1800FSU 69.03 20.46 11.50 49.37 EZM3800TB 53.97 18.66 11.50 34.30
EZM1800TB 53.97 18.66 11.50 34.30 EZM3800TBCU 51.76 23.93 6.41 28.01
EZM1800TBCU 51.76 23.93 6.41 28.01 EZM3800TBU 39.96 25.06 11.12 31.17
EZM1800TBU 39.96 25.06 11.12 31.17 EZM3EXT 19.34 11.66 6.37 11.85 b
EZM1EXT 19.34 11.66 6.37 11.85 bEZM3EXT6 19.34 6.00 6.37 11.85 b
EZM1EXT6 19.34 6.00 6.37 11.85 bEZM3CORNER (indoor only) 19.50 14.40 8.02 11.85 b
EZM1CORNER (indoor only) c19.50 14.40 8.02 11.85 b
MC (Mounting Channel)
H
W
Main Device
H
W
T
B
MC (Mounting Channel)
Branch Device
Table 2.28: Branch Device Dimensions (in.)d
Cat. No. Height Width Depth MC Top Bottom Cat. No. Height Width Depth MC Top Bottom
Single Phase
EZM112225 [X, CUX] 43.41 17.38 8.09 32.34 22.18 12.23 EZML111400 44.55 23.21 9.44 37.81 24.02 21.53
EZM113125 [X, CUX] 42.37 12.25 7.09 31.30 13.18 11.19 EZML112225 [CU] 39.06 19.44 9.44 25.51 11.67 13.39
EZM113225 [X, CUX] 43.41 17.38 8.09 32.34 13.18 12.23 EZML112225D 39.06 19.44 9.44 25.51 11.67 13.39
EZM114125 [X, CUX] 48.12 12.25 7.09 31.30 9.93 11.19 EZML112400 69.61 23.21 9.44 37.81 20.64 21.53
EZM114225 [X, CUX] 52.00 17.38 8.09 32.34 12.77 12.23 EZML113225 [CU] 53.06 19.44 9.44 39.51 11.67 13.39
EZM115125 [X, CUX] 57.12 12.25 7.09 31.30 9.93 11.19 EZML113225D 53.06 19.44 9.44 39.51 11.67 13.39
EZM115225 [CU] 61.00 17.38 8.09 32.35 12.77 12.23 EZML114225 [CU] 67.06 19.44 9.44 39.51 11.67 13.39
EZM116125 [X, CUX] 66.12 12.25 7.09 40.30 9.93 11.19 EZML114225D 67.06 19.44 9.44 39.51 11.67 13.39
EZMH112225 [X, CUX] 43.41 17.38 8.09 32.34 22.18 12.23 EZMR112225 [X, CUX] 43.41 17.38 8.09 32.34 22.18 12.23
EZMH113125 [X, CUX] 42.37 12.25 7.09 31.30 13.18 11.19 EZMR113125 [X, CUX] 42.37 12.25 7.09 31.30 13.18 11.19
EZMH113225 [X, CUX] 43.41 17.38 8.09 32.34 13.18 12.23 EZMR113225 [X, CUX] 43.41 17.38 8.09 32.34 13.18 12.23
EZMH114125 [X, CUX] 48.12 12.25 7.09 31.30 9.93 11.19 EZMR114125 [X, CUX] 48.12 12.25 7.09 31.30 9.93 11.19
EZMH114225 [X, CUX] 52.00 17.38 8.09 32.34 12.77 12.23 EZMR114225 [X, CUX] 52.00 17.38 8.09 32.34 12.77 12.23
EZMH115125 [X, CUX] 57.12 12.25 7.09 31.30 9.93 11.19 EZMR115125 [X, CUX] 57.12 12.25 7.09 31.30 9.93 11.19
EZMH115225 [CU] 61.00 17.38 8.09 32.35 12.77 12.23 EZMR115225 [CU] 61.00 17.38 8.09 32.35 12.77 12.23
EZMH116125 [X, CUX] 66.12 12.25 7.09 40.30 9.93 11.19 EZMR116125 [X, CUX] 66.12 12.25 7.09 40.30 9.93 11.19
EZMK111400 45.55 27.56 9.74 37.81 24.51 21.04 EZMT111225 25.45 22.42 9.38 16.19 4.67 20.45
EZMK112400 72.99 27.56 9.74 37.81 22.26 21.04 EZMT112225 60.56 22.42 9.38 43.63 12.67 28.89
EZML111225 [CU] 39.06 19.44 9.44 25.51 25.67 13.39 EZMT113225 79.56 22.42 9.38 48.25 12.67 28.89
EZML111225D 39.06 19.44 9.44 25.51 25.67 13.39
Three Phase
EZM312225 [X, CUX, CA, XCA, CUXCA] 43.41 17.38 8.09 32.34 22.18 12.23 EZML314225 [CU, CA, CUCA] 67.06 19.44 9.44 39.51 11.67 13.39
EZM313125 [X, CUX, CA, XCA, CUXCA] 42.37 12.25 7.09 31.30 13.18 11.19 EZML314225D [CA] 67.06 19.44 9.44 39.51 11.67 13.39
EZM313125M10 42.37 12.25 7.09 24.29 10.18 12.19 EZML331225 [CU] 39.06 19.44 9.44 25.51 25.67 13.39
EZM313225 [X, CUX, CA, XCA, CUXCA] 43.41 17.38 8.09 32.34 13.18 12.23 EZML331225D 39.06 19.44 9.44 25.51 25.67 13.39
EZM314125 [X, CUX, CA, XCA, CUXCA] 48.12 12.25 7.09 31.30 9.93 11.19 EZML331400 45.55 23.21 9.44 37.81 24.02 21.53
EZM314125M10 52.12 12.25 7.09 34.29 9.93 12.19 EZML332225 [CU] 39.06 19.44 9.44 35.51 11.67 13.39
EZM314225 [X, CUX, CA, XCA, CUXCA] 52.00 17.38 8.09 32.34 12.77 12.23 EZML332225D 39.06 19.44 9.44 35.51 11.67 13.39
EZM315125 [X, CUX, CA, XCA, CUXCA] 57.12 12.25 7.09 31.30 9.93 11.19 EZML332400 [CU] 69.61 23.21 9.44 37.82 20.64 21.53
EZM315125M10 62.12 12.25 7.09 34.29 9.93 12.19 EZML333225 [CU] 53.06 19.44 9.44 39.51 11.67 13.39
EZM315225 [CU, CA, CUCA] 61.00 17.38 8.09 32.35 12.77 12.23 EZML333225D 53.06 19.44 9.44 39.51 11.67 13.39
EZM316125 [X, CUX, CA, XCA, CUXCA] 66.12 12.25 7.09 40.30 9.93 11.19 EZML334225 [CU] 67.06 19.44 9.44 39.51 11.67 13.39
EZMH312225 [X, CUX, CA, XCA] 43.41 17.38 8.09 32.34 22.18 12.23 EZML334225D 67.06 19.44 9.44 39.51 11.67 13.39
EZMH313125 [X, CUX, CA, XCA] 42.37 12.25 7.09 31.30 13.18 11.19 EZMR312225 [X, CUX, CA, XCA] 43.41 17.38 8.09 32.34 22.18 12.23
EZMH313225 [X, CUX, CA, XCA] 43.41 17.38 8.09 32.34 13.18 12.23 EZMR313125 [X, CUX, CA, XCA] 42.37 12.25 8.09 31.30 13.18 11.19
EZMH314125 [X, CUX, CA, XCA] 48.12 12.25 7.09 31.30 9.93 11.19 EZMR313225 [X, CUX, CA, XCA] 43.41 17.38 8.09 32.34 13.18 12.23
EZMH314225 [X, CUX, CA, XCA] 52.00 17.38 8.09 32.34 12.77 12.23 EZMR314125 [X, CUX, CA, XCA] 48.12 12.25 7.09 31.30 9.93 11.19
EZMH315125 [X, CUX, CA, XCA] 57.12 12.25 7.09 31.30 9.93 11.19 EZMR314225 [X, CUX, CA, XCA] 52.00 17.38 8.09 32.34 12.77 12.23
EZMH315225 [CU, CA, CUCA] 61.00 17.38 8.09 32.35 12.77 12.23 EZMR315125 [X, CUX, CA, XCA] 57.12 12.25 7.09 31.30 9.93 11.19
EZMH316125 [X, CUX, CA, XCA] 66.12 12.25 7.09 40.30 9.93 11.19 EZMR315225 [CU, CA, CUXCA] 61.00 17.38 8.09 32.35 12.77 12.23
EZMK311400 [CA] 45.55 27.56 9.74 30.60 24.51 21.04 EZMR316125 [X, CUX, CA, XCA] 66.12 12.25 7.09 40.30 9.93 11.19
EZMK312400 [CA] 72.99 27.56 9.74 37.81 22.26 21.04 EZMR332225 [CU] 39.06 19.44 9.44 25.51 11.67 13.39
EZMK331400 45.55 27.56 9.74 30.60 24.51 21.04 EZMR333225 [CU] 53.06 19.44 9.44 39.51 11.67 13.39
EZMK332400 72.99 27.56 9.74 37.81 22.26 21.04 EZMR334225 [CU] 67.06 19.44 9.44 39.51 11.67 13.39
EZML311400 [CA] 45.55 23.21 9.44 37.81 24.02 21.53 EZMT311225 [CA] 25.45 22.42 9.38 16.19 4.67 20.45
EZML311225 [CU, CA, CUCA] 39.06 19.44 9.44 25.51 25.67 13.39 EZMT312225 [CA] 60.56 22.42 9.38 43.63 12.67 28.89
EZML312225 [CU, CA, CUCA] 39.06 19.44 9.44 25.51 11.67 13.39 EZMT313225 [CA] 79.56 22.42 9.38 48.25 12.67 28.89
EZML312225D [CA] 39.06 19.44 9.44 25.51 11.67 13.39 EZMT331225 25.12 22.42 9.38 16.19 4.67 20.45
EZML312400 [CA] 69.61 23.21 9.44 37.82 20.64 21.53 EZMT332225 60.56 22.42 9.38 43.63 12.67 28.89
EZML313225 [CU, CA, CUCA] 53.06 19.44 9.44 39.51 11.67 13.39 EZMT333225 79.56 22.42 9.38 48.25 12.67 28.89
EZML313225D [CA] 53.06 19.44 9.44 39.51 11.67 13.39
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com