Loadcenters and Circuit Breakers
Residential Loadcenters
and Breaker Family
1.1 Type CH Loadcenters and Circuit Breakers
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Surge Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
Type CH Renovation Loadcenter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
Type CH Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
Circuit Analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
1.2 Type BR Loadcenters and Circuit Breakers
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
43
Riser Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65
Type BR Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
67
Type BR Renovation Loadcenters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
69
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
72
1.3 Loadcenter Interiors
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
89
Standards and Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
90
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
91
1.4 Classified Circuit Breakers
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
92
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
93
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
95
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
95
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
96
Learn
Online
2 Volume 1—Residential and Light Commercial
CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Eaton Type CH Convertible Family
Contents
Description Page
Overview
Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Features, Benefits and Functions . . . . . . . . . . . . . . . . . .
3
Standards and Certifications . . . . . . . . . . . . . . . . . . . . . .
5
Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . .
6
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Technical Data and Specifications . . . . . . . . . . . . . . . . . .
17
Surge Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
Type CH Renovation Loadcenter . . . . . . . . . . . . . . . . . . . . .
21
Type CH Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . .
22
Circuit Analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
Overview
Product Selection Guide
CH Loadcenters
Description
Service
Single-phase, three-wire, 120/240 Vac
Three-phase, three-wire, 240V corner grounded delta (see Accessories
Page
26
)
Three-phase, four-wire, 208Y/120 Vac
Three-phase, three-wire, 240 Vac delta
Short-Circuit Current Rating
10 kAIC: All single- and three-phase loadcenters 40–400A, 2–42 circuits except when
series ratings are applied
35 kAIC: All convertible and factory-installed main breakers single-phase loadcenters rated 150–225A using
Type CSH main breakers
42,000 and 100,000 are available on some styles: single-phase and three-phase
Main Breaker/Main Lug Loadcenters
Single-phase
Main breaker: 100, 125, 150, 200, 225, 400A
Main lugs: 40, 70, 125, 150, 200, 225, 400A
Three-phase
Main breaker: 150, 200, 225, 300, 400A
Main lugs: 125, 150, 200, 225, 400A
Convertible Loadcenters
Main breaker or main lugs: single-phase up to 225A
Branch Breakers
Type CH: 10–150A. Single-, two- and three-pole. Selected amperages available in shunt
trip, HACR and switching duty
Ground fault circuit interruptors: 15–60A
Type CH-HID: 15–30A. Single-, two- and three-pole
CH-HM high magnetic
CH-M50 high ambient
Type CH-AFCI arc fault circuit interrupter
Type CHP: 10–125A. Single-, two- and three-pole. three-position commercial trip
Selected amperages available in HACR switching duty
Type CHP-HID: 15–30A. Single-, two- and three-pole
Type CHP-GFCI: 15–30A. Single-pole ground fault breakers
Enclosures
NEMA
®
Type 1 indoor NEMA Type 3R outdoor.
Loadcenter and Breaker Accessories
Branch circuit breaker:
Auxiliary components
Hold-down kits
Handle ties
Lockoffs
Lockdogs
Complete line of ground bar kits 5, 10, 14 and 21 circuits, some with additional #2/0 lugs
Each terminal will accommodate: (3) #14–#10 Cu/Al or (1) #14–#4 Cu/Al
Sub-feed lugs 125, 150A—two- and three-pole
Shunt trips
Universal rainproof conduit hubs Group One: 3/4, 1, 1-1/4, 1-1/2, 2 inches (19.1, 25.4, 31.8, 38.1, 50.8 mm)
Group Two: 2, 2-1/2, 3 inches (50.8, 63.5, 76.2 mm)
Adapter plate
Bussing
Silver flash plated copper bus is a standard feature
Volume 1—Residential and Light Commercial
CA08100002E—December 2010 www.eaton.com
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Product
Description
Loadcenters are enclosures
specifically designed to
house the branch circuit
breakers and wiring required
to distribute power to
individual circuits. They
contain either a main breaker
when used at the service
entrance point or a main lug
when used as a sub-panel
to add circuits to existing
service. The main breaker
protects the main entire
panel and can be used as
a service disconnect. The
branch breakers protect the
wires leading to individual
electrical loads such as
fixtures and outlets.
Features, Benefits and Functions
Loadcenter Construction
Eaton’s Type CH loadcenters
feature silver flash plated
copper bus in all interiors.
Fingers are rated 200A
throughout the CH line.
Therefore, the sum of the
handle ratings connected to
any one stab is limited to
200A maximum. NEMA 1
boxes are manufactured from
cold rolled 16 gauge sheet
steel. Raintight boxes are
manufactured from galvanized
steel. All boxes and trims are
finished using an electrostatic
powder coat, baked urethane
paint process.
Neutrals
Eaton’s Type CH loadcenters
feature three types of neutrals:
Factory-Bonded Split Neutral
Single-phase main circuit
breaker panels are supplied
with a factory-bonded twin
neutral. When used as a sub-
panel, the bonding strap should
be removed, and the bonding
screw should be reinstalled.
The bonded side is now the
ground, and the un-bonded
side is the neutral. When used
as a service entrance panel,
the unused neutral holes on
either side may be used for
terminating ground wires.
Insulated Split Neutral
Most single-phase main
lug panels (12 circuits and
greater) are supplied with a
twin neutral with an insulated
cross strap. These panels
are shipped in an un-bonded
state. For service entrance
applications, the neutral
must be bonded utilizing
the bonding strap supplied
with the panel. For sub-feed
applications, the panel may
be installed as is. Separate
ground bars are provided on
these panels.
Insulated/Bondable
Single Neutral
When a panel is supplied with
a single neutral, it arrives from
the factory in an “unbonded”
state. All that is required to
bond the neutral in a service
entrance application is to
loosen the bonding screw and
the neutral screw directly
beside it, insert the bonding
strap into the neutral bar, and
re-tighten both connections.
The single neutral can be
moved by the contractor to
the other side of the panel, if
desired. In a service entrance
application, where the neutral
is bonded, unused neutral
connections may be used
for the termination of
equipment grounds.
Inboard Plug-On Neutral
Code changes and higher
safety standards are
leading to more arc fault
circuit interrupter (AFCI)
installations. With the
electrical contractor in mind,
Eaton has revolutionized the
way Combination AFCIs are
installed with the Plug-on
Neutral line of loadcenters
and breakers. This unique
product solution enables the
contractor to connect the
breaker directly to the neutral
bar, eliminating the need for
wiring a pigtail.
Grounds
In service entrance
applications where the
neutral is bonded, unused
neutral holes may be used
for terminating ground
conductors. In sub-feed
panels, the neutral must be
isolated (non-bonded), and
ground wires must be
terminated on a separate
ground bar.
The Factory-Bonded Split
Neutral panels have sufficient
terminations for both ground
and neutral conductors. The
Insulated Split Neutral panels
are supplied with a separate
factory-installed ground bar.
Insulated/Bondable Single
Neutral panels are supplied
without a ground bar (unless
otherwise noted), and ground
bar kits if needed must be
purchased separately.
4 Volume 1—Residential and Light Commercial
CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Type CH Loadcenter
Warranty
The minimum warranty
for residential loadcenters,
breakers and surge protection
devices shall be as follows:
Lifetime loadcenter
warranty
Lifetime warranty on all
arc fault circuit interrupting
circuit breakers
Lifetime warranty on
CHSPULTRA including
$5000 connected load
warranty
Lifetime warranty on all
thermal-magnetic and
GFCI branch circuit
breakers
1-year warranty on plug-in
surge protection device
(CHSURGE)
Extra 1.5-Inch (38.1 mm)
Knockout for Bundling
Provides for easier installation,
less installation time.
Top or Bottom Feed
Straight-in wiring saves labor
and material
Only one panel for either application—
no modifications necessary
Commercial Grade Main Breaker
35 kAIC series rated main breaker in
150 and 200A loadcenters
42 and 100 kAIC series ratings
available
Steel Backpan
Provides positive, reliable
breaker mounting
One-piece designed for stability
One-Piece Silver Flash Plated
Copper Bus
Provides superior conductivity
throughout the entire product line.
Drywall Marking on Enclosure
Indicates proper mounting
depth for flush applications.
Single Keyhole Mounting
Just one keyhole at top and bottom
for eas ier mounting
and leveling.
Unique Sandalwood Finish
Immediately recognizable,
aesthetically appealing, scratch
resistant powder coating.
Neutral Design
(for styles as indicated)
Bonding strap is easily removable
for sub-panel applications
providing a ground and neutral
Factory-bonded for service entrance
applications providing a split neutral
Ample additional 2/0 lugs provided;
no kits necessary
200% size neutral
Separately Packaged Covers
Full line of “true” surface and
combination covers.
Built-in flush leveling
feature.
Choice of circuit
identification by breaker labels or
circuit directory.
Improved Endwall Knockouts
Larger KOs are balanced to enhance
installed appearance and to ease use
of existing wiring.
Convertible Styles Available
Uses field installable main breaker
or main lug kits
Flexible inventory—same breaker
is used in loadcenter and circuit breaker
enclosures
“Tangential” Center Knockout
For easier installation
Volume 1—Residential and Light Commercial
CA08100002E—December 2010 www.eaton.com
5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Standards and Certifications
UL
®
Listings
All Eaton Type CH loadcenters
are listed under UL File E8741.
Neutral and Ground Terminals
The standard terminals on
grounds and neutrals are rated
to accept (3)—#14–#10 Cu/Al
or (1)—#14–4 wires. For larger
cables, add-on neutral lugs
may be ordered from the
Accessories on
Page
25
.
Note:
NEC
®
allows only one
current carrying conductor
per hole on neutrals unless
otherwise noted.
Bottom-Fed Loadcenters
When the power cable is
brought into the loadcenter
from below the panel; then
the main lug panels, and
single-phase, 225A and
below, loadcenters can be
rotated 180 degrees to allow
straight-in wiring of power
cables to the main terminals.
Because the CSR main circuit
breaker handle operates
horizontally, the orientation of
the main circuit breaker
handle is consistent with the
requirements of NEC Article
240-81.
Gutter Splicing
Loadcenters are not UL listed
as wiring troughs. Therefore,
gutter splicing of riser cables
to tap off to the main device
is not permitted. Refer to
NEC Article 373-8.
Fire Rating
Due to the numerous
openings in both loadcenter
boxes and trims, they should
not be mounted in firewalls.
There is no approval method
for sealing the enclosures for
this application.
Date Code
The date of manufacture of
each loadcenter is printed on
the outside of the carton as
well as inside the loadcenter.
On the carton, the date code
is printed on the end carton
label. In the loadcenter, the
date code is located on the
small white label located on
the right side wall (with the
main device on top).
The date code is in the
following format: F # # # &.
The “F” is the numeric code
for the Lincoln, IL plant,
and the three numbers
are the year and week of
manufacture e.g., 023. The
“&” sign at the end signifies
the decade of the 2000s.
Therefore, the date code
F023& would indicate
that the product was
manufactured in the 23rd
week of 2000. The 1980s
are represented by a
“+” sign and the 1990s
are represented by a “=”
at the end of the code.
Plug-On Type CH Breakers
Quick-make, quick-break
switch mechanism combined
with inverse time element
tripping operation and trip-
free handle design. Type CH
circuit breakers trip to the
OFF position eliminating
nuisance callbacks. The
thermal-magnetic trip curve
avoids nuisance tripping on
mild overloads while reacting
almost instantaneously
to severe short-circuit
conditions. Multipole
breakers have internal
common trip connection
to operate all poles
simultaneously. Handles
are marked with ON-OFF
indication and ampere rating
of the breaker. Type CH
breakers meet UL Standard
489, NEMA standards, and
Federal Spec Classification
W-C 375 b/Gen. They are
UL listed under File Number
E11713, E8741, E3624 and
E51287: and CSA
®
certified
file number LR87196, except
Type CHT breakers.
Type CH Circuit Breaker Ratings
Single- and double-pole CH
breakers rated 15 and 20A
have low instantaneous
magnetic trip levels. The 15
and 20A breakers with “HM”
suffix have high magnetic trip
settings recommended for
circuits with inherently high
inrush currents. All Type CH
breakers are marked for
heating, air conditioning
and refrigeration (HACR)
equipment application.
Single-pole 15–20A breakers
are also suitable for switching
duty (SWD). Shunt trip coils
operate on 120 Vac and
require one additional pole
space per breaker.
6 Volume 1—Residential and Light Commercial
CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Catalog Number Selection
Loadcenters 100–225A and 12–42 Circuits
Indoor Covers Ordered Separately
Note:
All combinations are not valid, refer to the catalog section.
LC Type
Type CH 3/4-inch (19.1 mm)
branch circuit breakers
Number of Circuits
Selection circuits
2
4
8
12
14
16
18
20
22
24
28
30
32
42
Main Device
L= Main lug only
B= Main breaker
N= Convertible
H= High AIC
main breaker
CH
42
B
200
K
Construction
Blank = Standard
PN = Plug-on neutral
Phases
Blank = Single-phase
3= Three-phase Accessories
Blank = Standard
EC = Surge ready
SUR = Surge factory
installed
Bus Amperes
40
70
100
125
150
200
225
Box Sizes
B
C
D
E
G
J
K
L
R = Outdoor (no cover)
CH
8
K
F
Type CH
Loadcenter
Cover Series
Factory Options
Blank = Standard
SUR = Surge/surge ready
Accessories
Blank = Standard
M= Mechanical interlock
Mounting
F= Combination
flush/surface
S= Surface
Box Size
Indicated in loadcenter
catalog number
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Product Selection
Single-Phase—Main Circuit Breaker Loadcenters—10/35 kAIC
Single-Phase Three-Wire—120/240 Vac—Factory-Bonded Split Neutral (Unless Otherwise Noted)
Notes
All main circuit breaker loadcenters are listed for use as service entrance equipment.
Ground bar kits priced separately. See Page 26.
Combination style covers may be used in surface or flush applications.
Loadcenters are factory-bonded for service entrance applications. Remove bonding strap for separate neutral and ground bars for sub-feed applications.
Can be top or bottom fed by rotating the enclosure and trim 180 degrees.
Loadcenter contains single insulated/bondable neutral.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 26.
35 kAIC series combination rating is obtained when Types CH, CHT and CHP branch breakers are used with CSH main.
Panel includes #4–300 kcmil feed-through lugs.
This cover is for flush applications only (not combination).
Box sizes Pages 41 and 42.
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm)
of Poles
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter 
Catalog Number
Loadcenter Cover
Catalog Number
Combination Surface
CH
10 kAIC
100 14 Indoor B #6–1/0 CH14B100B  CH8BF CH8BS
14 Outdoor B #6–1/0 CH14B100R  ——
18 Indoor C #6–1/0 CH18B100C  CH8CF CH8CS
18 Outdoor C #6–1/0 CH18B100R  ——
22 Indoor C #6–1/0 CH22B100C  CH8CF CH8CS
22 Outdoor C #6–1/0 CH22B100R  ——
30 Indoor D #6–1/0 CH30B100D  CH8DF CH8DS
30 Outdoor D #6–1/0 CH30B100R  ——
125 22 Indoor C #6–1/0 CH22B125C  CH8CF CH8CS
22 Outdoor C #6–1/0 CH22B125R  ——
30 Indoor D #6–1/0 CH30B125D  CH8DF CH8DS
30 Outdoor D #6–1/0 CH30B125R  ——
CSH
35 kAIC
150 8 Outdoor E #2–300 kcmil CH8B150RF  ——
24 Indoor E #2–300 kcmil CH24B150E  CH8EF CH8ES
24 Outdoor E #2–300 kcmil CH24B150R  ——
32 Indoor J #2–300 kcmil CH32B150J  CH8JF CH8JS
32 Outdoor J #2–300 kcmil CH32B150R  ——
200 8 Outdoor E #2–300 kcmil CH8B200RF  ——
24 Indoor E #2–300 kcmil CH24B200E  CH8EF CH8ES
24 Outdoor E #2–300 kcmil CH24B200R  ——
32 Indoor J #2–300 kcmil CH32B200J  CH8JF CH8JS
32 Outdoor J #2–300 kcmil CH32B200R  ——
42 Indoor K #2–300 kcmil CH42B200K  CH8KF CH8KS
42 Outdoor K #2–300 kcmil CH42B200R  ——
24 Indoor E #2–300 kcmil CH24B200E  CH8EF CH8ES
24 Outdoor E #2–300 kcmil CH24B200R  ——
32 Indoor J #2–300 kcmil CH32B200J  CH8JF CH8JS
32 Outdoor J #2–300 kcmil CH32B200R  ——
42 Indoor K #2–300 kcmil CH42B200K  CH8KF CH8KS
42 Outdoor K #2–300 kcmil CH42B200R  ——
225 32 Indoor J #2–300 kcmil CH32B225J  CH8JF CH8JS
32 Outdoor J #2–300 kcmil CH32B225R  ——
42 Indoor K #2–300 kcmil CH42B225K  CH8KF CH8KS
42 Outdoor K #2–300 kcmil CH42B225R  ——
DK
10 kAIC
300 42 Indoor PM (2) 3/0–250 kcmil CH42PM300 CH7PMF CH7PMS
400 42 Indoor PM (2) 3/0–250 kcmil CH42PM400 CH7PMF CH7PMS
CH42B200K
8 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Single-Phase—High Interrupting Rated Main Circuit Breaker Loadcenters—42/100 kAIC
Single-Phase Three-Wire—120/240 Vac—Factory-Bonded Split Neutral (Unless Otherwise Noted)
Notes
All main circuit breaker loadcenters are listed for use as service entrance equipment.
Combination style covers may be used in surface or flush applications.
Series rated for 42 kAIC with all Types CH, CHT and CHP breakers.
Loadcenters are factory-bonded for service entrance applications. Remove bonding strap for separate neutral and ground bars for sub-feed applications.
Loadcenter can be top or bottom fed by rotating the enclosure and trim 180 degrees.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 26.
Loadcenter contains single insulated/bondable neutral.
Series rated for 100 kAIC with all Types CH, CHT and CHP breakers.
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm)
Poles
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Combination Surface
CHB4
42 kAIC
100 20 Indoor C #6–1/0 CH20H100C  CH8CF CH8CS
20 Outdoor C #6–1/0 CH20H100R  ——
28 Indoor D #6–1/0 CH28H100D  CH8DF CH8DS
28 Outdoor D #6–1/0 CH28H100R  ——
CHH
100 kAIC
150 32 Indoor L #2/0–300 kcmil CH32H150L CH8LF CH8LS
32 Outdoor L #2/0–300 kcmil CH32H150R  ——
200 32 Indoor L #2/0–300 kcmil CH32H200L CH8LF CH8LS
32 Outdoor L #2/0–300 kcmil CH32H200R  ——
42 Indoor L #2/0–300 kcmil CH42H200L CH8LF CH8LS
42 Outdoor L #2/0–300 kcmil CH42H200R  ——
225 42 Indoor L #2/0–300 kcmil CH42H225L CH8LF CH8LS
42 Outdoor L #2/0–300 kcmil CH42H225R  ——
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Single-Phase—Main Lug Loadcenters
Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Notes
Requires the use of Type CHNT breakers.
Ground bar kits priced separately, see Page 26.
– For 2/4 circuit loadcenters use Type GBK5 or GBK520 ground bar
– For 4/8 and 8/16 circuit loadcenters use Type GBK10 ground bar
– Ground bars mount to the left side wall of the enclosure for the 4/8 and 8/16 circuit loadcenters
Suitable for use as service equipment when not more than two service disconnecting mains are provided or when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 26.
For use as service entrance applications only.
Neutral/ground holes (6) #14–6 and (3) #14–2/0 AWG Cu/AI.
Suitable for use as service equipment when not more than two service disconnecting mains are provided or when not more than six service disconnecting mains are
provided and when not used as a lighting and appliance panelboard (see Article 408.34 of the NEC).
Suitable for use as service equipment when a main breaker is used or when not more than six service disconnecting mains are provided and when not used as a lighting
and appliance panelboard (see Article 408.34 of the NEC).
Box sizes Pages 41 and 42.
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm) Enclosure
Type
Type of Trim
(Included)
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter
Catalog NumberSpace Poles
40 2 4 Indoor Surface (no door) 5 #14–6 CH2L40SP 
24 Outdoor — 5R #14–6 CH2L40RP 
24 Indoor Flush (no door) 5 #14–6 CH2L40FP 
70 2 4 Indoor Surface (no door) 5 #14–2 CH2L70SP 
24
Outdoor 5R #14–2 CH2L70RP 
24
Indoor Flush (no door) 5 #14–2 CH2L70FP 
125 2 4 Indoor Surface (no door) 6 #14–1/0 CH2L125SP 
24 Outdoor — 6R #14–1/0 CH2L125RP 
22Outdoor — #14–1/0 CH2L125RSE2P 
24 Indoor Flush (no door) 6 #14–1/0 CH2L125FP 
48 Indoor Surface (no door) 7 #14–1/0 CH4L125SP 
48 Outdoor — 7R #14–1/0 CH4L125RP 
48 Indoor Flush (no door) 7 #14–1/0 CH4L125FP 
816 Indoor Surface (no door) 7 #6–1/0 CH8L125SP 
816 Outdoor — 7R #6–1/0 CH8L125RP 
816 Indoor Flush (no door) 7 #6–1/0 CH8L125FP 
Surface Outdoor
Flush Outdoor
Surface (No Door)
Flush (No Door)
Outdoor
10 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Single-Phase Three-Wire—120/240 Vac—Twin Neutral—Factory-Installed Ground Bar
Notes
Suitable for use as service equipment when not more than six disconnecting means are provided and when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 26.
Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and requires hold-down bracket kit
catalog number CH125RB.
Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and must be a Type CHB.
The breaker cannot be a Type CH.
This cover is for flush application only (not combination).
Box sizes Pages 41 and 42.
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm)
Poles
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Combination Surface
125 12 Indoor B #6–2/0 CH12L125B CH8BF CH8BS
12 Outdoor B #6–2/0 CH12L125R  ——
16 Indoor B #6–2/0 CH16L125B CH8BF CH8BS
16 Outdoor B #6–2/0 CH16L125R  ——
20 Indoor C #6–2/0 CH20L125C CH8CF CH8CS
20 Outdoor C #6–2/0 CH20L125R  ——
24 Indoor C #6–2/0 CH24L125C CH8CF CH8CS
24 Outdoor C #6–2/0 CH24L125R  ——
150 24 Indoor D #4–300 kcmil CH24L150D CH8DF CH8DS
24 Outdoor D #4–300 kcmil CH24L150R  ——
32 Indoor D #4–300 kcmil CH32L150D CH8DF CH8DS
32 Outdoor D #4–300 kcmil CH32L150R  ——
200 12 Indoor D #4–300 kcmil CH12L200D CH8DF CH8DS
12 Outdoor D #4–300 kcmil CH12L200R  ——
16 Indoor D #4–300 kcmil CH16L200D CH8DF CH8DS
16 Outdoor D #4–300 kcmil CH16L200R  ——
225 24 Indoor D #4–300 kcmil CH24L225D CH8DF CH8DS
24 Outdoor D #4–300 kcmil CH24L225R  ——
32 Indoor D #4–300 kcmil CH32L225D CH8DF CH8DS
32 Outdoor D #4–300 kcmil CH32L225R  ——
42 Indoor G #4–300 kcmil CH42L225G CH8GF CH8GS
42 Outdoor G #4–300 kcmil CH42L225R  ——
400 42 Indoor P (2) 1/0–300 kcmil
(1) 750 kcmil
CH42PL400 CH7PF CH7PS
CH42L225G
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Three-Phase—Main Circuit Breaker Loadcenters—10 kAIC
Three-Phase Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Three-Phase—Main Lug Loadcenters
Three-Phase Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Notes
All main circuit breaker loadcenters are listed for use as service entrance equipment.
For ground bar kits, see Page 26.
Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs, refer to Page 26.
This cover for flush application only (not combination).
Requires the use of CHNT breakers.
Suitable for use as service equipment when not more than two service disconnecting means are provided or when not more than six service disconnecting means are
provided and when not used as a lighting and appliance panelboard (see Article 408.34 of the NEC).
Ground bar kits priced separately, see Page 26.
– Use GBK10 ground bar
– Ground bars mount to the left side wall of the enclosure.
Box sizes Pages 41 and 42.
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm)
Poles
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter 
Catalog Number
Loadcenter Cover
Catalog Number
Combination Surface
CC
10 kAIC
150 30 Indoor L #1–4/0 CH30B3150L CH8LF CH8LS
30 Outdoor L #1–4/0 CH30B3150R ——
200 30 Indoor L #2/0–300 kcmil CH30B3200L CH8LF CH8LS
30 Outdoor L #2/0–300 kcmil CH30B3200R ——
42 Indoor L #2/0–300 kcmil CH42B3200L CH8LF CH8LS
42 Outdoor L #2/0–300 kcmil CH42B3200R ——
225 30 Indoor L #2/0–300 kcmil CH30B3225L CH8LF CH8LS
30 Outdoor L #2/0–300 kcmil CH30B3225R ——
42 Indoor L #2/0–300 kcmil CH42B3225L CH8LF CH8LS
42 Outdoor L #2/0–300 kcmil CH42B3225R ——
400 42 Indoor PM (2) 3/0–350 kcmil CH424PM400 CH7PMF CH7PMS
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm) Enclosure
Type
Type of Trim
Included
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter
Catalog NumberSpaces Poles
125 6 12 Indoor Surface no door 7 #14–1/0 CH6L3125SP 
612 Outdoor 7R #14–1/0 CH6L3125RP 
612 Indoor Flush no door 7 #14–1/0 CH6L3125FP 
CH42B3200L
12 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Three-Phase Four-Wire—208Y/120 Vac or 240 Vac—Insulated/Bondable Neutral
Three-Phase—High Interrupting Rated Main Circuit Breaker Loadcenters—100 kAIC
Three-Phase Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Notes
Ground bar Type GBK14 is installed.
Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and requires hold-down bracket kit catalog number Type CH125RB. Suitable for
use as service equipment when not more than six service disconnecting means are provided and when not used as a lighting and appliance panelboard (see Article 408.34 of the NEC).
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 26.
Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and requires hold-down kit catalog number Type CH125RB.
Ground bar Type GBK21 is installed.
Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and must be a Type CHB. The breaker cannot be a Type CH.
For ground bar kits, see Page 26.
This cover is for flush application only (not combination).
All main circuit breaker loadcenters are listed for use as service entrance equipment.
Ground bar kits priced separately.
100 kAIC series combination rating is obtained when Types CH and CHP branch breakers are used with CHH main.
Rainproof loadcenters are furnished with hub closure plates.
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm)
Poles
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Combination Surface
125 12 Indoor B #6–2/0 CH12L3125B  CH8BF CH8BS
12 Outdoor B #6–2/0 CH12L3125R  ——
18 Indoor C #6–2/0 CH18L3125C  CH8CF CH8CS
18 Outdoor C #6–2/0 CH18L3125R  ——
24 Indoor C #6–2/0 CH24L3125C  CH8CF CH8CS
24 Outdoor C #6–2/0 CH24L3125R  ——
150 30 Indoor D #4–300 kcmil CH30L3150D  CH8DF CH8DS
30 Outdoor D #4–300 kcmil CH30L3150R  ——
225 24 Indoor D #4–300 kcmil CH24L3225D  CH8DF CH8DS
24 Outdoor D #4–300 kcmil CH24L3225R  ——
30 Indoor D #4–300 kcmil CH30L3225D  CH8DF CH8DS
30 Outdoor D #4–300 kcmil CH30L3225R  ——
42 Indoor G #4–300 kcmil CH42L3225G  CH8GF CH8GS
42 Outdoor G #4–300 kcmil CH42L3225R  ——
400 42 Indoor P (2) 1/0–300 kcmil
(1) 750 kcmil
CH424PL400  CH7PF CH7PS
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
3/4-Inch (19.1 mm)
of Poles
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Combination Surface
CHH
100 kAIC
200 30 Indoor L #2/0–300 kcmil CH30H3200L CH8LF CH8LS
30 Outdoor L #2/0–300 kcmil CH30H3200R ——
42 Indoor L #2/0–300 kcmil CH42H3200L CH8LF CH8LS
42 Outdoor L #2/0–300 kcmil CH42H3200R ——
225 42 Indoor L #2/0–300 kcmil CH42H3225L CH8LF CH8LS
42 Outdoor L #2/0–300 kcmil CH42H3225R ——
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 13
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Convertible Loadcenters MCB or MLO—Base Units and Main Devices—10/35 kAIC
Complete assembly consists of: loadcenter, cover, and either main breaker kit or main lug kit.
Indoor—Single-Phase—Three-Wire—120/240V—Factory-Bonded Split Neutral—Top or Bottom Feed
Outdoor—Single-Phase—Three-Wire—120/240V—Insulated/Bondable Neutral
Notes
Panel does not include main. Order main breaker or main lug kit separately.
Loadcenters are factory-bonded for service entrance applications. Remove bonding strap for separate neutral and ground bars for sub-feed applications.
Hold-down kit included.
35 kAIC series combination rating is obtained when Types CH, CHT and CHP branch breakers are used with CSR main.
CSH breakers include line lugs only as standard.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 26.
Includes feed-through lugs for both phase and neutral conductors.
Interrupting rating depends on main circuit breaker selected.
Maximum
Main Ampere
Rating
Maximum
Number of
Single Poles
Box
Size
Loadcenter Box
and Panel
Catalog Number 
Loadcenter Cover
Catalog Number Main Lug Kit Main Breaker Kit
Combination Surface
Wire
Size
Catalog
Number
kAIC
Rating
Wire
Size
Catalog
Number
125 22 C CH22N125C CH8CF CH8CS #10–1/0 CHL125N 10 #10–1/0 CH2100N
CH2125N
200 32 J CH32N200J CH8JF CH8JS #4–300
kcmil
CHL225N 25 #2–300
kcmil
CSH2125N 
CSH2150N 
CSH2175N 
CSH2200N 
225 42 K CH42N225K CH8KF CH8KS #4–300
kcmil
CHL225N 25 #2–300
kcmil
CSH2125N 
CSH2150N 
CSH2175N 
CSH2200N 
CSH2225N 
Maximum
Main Ampere
Rating
Maximum
Number of
Single Poles
Box
Size
Loadcenter Box
and Panel
Catalog Number
Main Lug Kit Main Breaker Kit
Wire
Size
Catalog
Number
kAIC
Rating
Wire
Size
Catalog
Number
200 8 E CH8N200RF  #4–300 kcmil CHL225N 25 #2–300 kcmil CSH2125N
CSH2150N
CSH2175N
CSH2200N
125 22 C CH22N125R #10–1/0 CHL125N 10 #10–1/0 CH2100N
CH2125N
200 32 J CH32N200R #4–300 kcmil CHL225N 25 #2–300 kcmil CSH2125N 
CSH2150N 
CSH2175N 
CSH2200N 
225 42 K CH42N225R #4–300 kcmil CHL225N 25 #2–300 kcmil CSH2125N 
CSH2150N 
CSH2175N 
CSH2200N 
CSH2225N 
14 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Spa Panels
Quick-ProSM
All you need to know to save time
and make more money. Specified
on certain Eaton products, the
Quick-Pro symbol allows for
immediate recognition of products
that are designed for straightforward
installation. When you see Quick-Pro,
you know you can install quickly—
sometimes up to 50% less than the
usual installation time—and move
onto your next job.
Single-Phase Three-Wire—120/240 Vac Insulated/Bondable Neutral—
Factory-Installed Ground Bar
Notes
Includes a CH230GFI breaker, factory installed, and two extra circuits for convenience.
Includes a CH240GFI breaker, factory installed, and two extra circuits for convenience.
Includes a CH250GFI breaker, factory installed, and two extra circuits for convenience.
Includes a CH260GFI breaker, factory installed, and two extra circuits for convenience.
Main
Ampere
Rating
Circuit
Breaker
Included
Enclosure
Type
Type
of Trim
Included
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Catalog
Number
30 CH230GF Outdoor 5R #14–1/0 CH30SPA
40 CH240GF Outdoor 5R #14–1/0 CH40SPA
50 CH250GF Outdoor 5R #14–1/0 CH50SPA
60 CH260GF Outdoor 5R #14–1/0 CH60SPA
CH Spa Panel
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 15
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Single-Phase and Three-Phase Circuit Breaker Unit Enclosures—10/35 kAIC
Type ECB Circuit Breaker Unit Enclosure—Order Type CSR Circuit Breaker Separately—Unit Enclosure
Includes Lug Tree Kit
Type CSH Circuit Breakers 120/240 Vac—
35 kAIC For Use in Type ECB Unit
Enclosures
Shunt Trips
CSR Lug Tree Kit For Replacement
Purposes Only For Use in Type ECB
Unit Enclosures
Wire Data
Notes
CSR2150N factory-installed circuit breaker.
CSR2200N factory-installed circuit breaker.
Order circuit breaker separately.
Wire size is determined by the circuit breaker installed in enclosure.
Maximum wire size and ampere rating is determined by Wire Data table above.
Rainproof panels are furnished with hub closures plates. For rainproof hubs,
refer to Page 26.
One ground lug accepting (1) #14 –#2 is factory installed. Also, there are pre-drilled
holes to accept a GBK5 ground bar.
Approved for service entrance.
Add suffix indicated to end of breaker catalog number.
Box sizes Pages 41 and 42.
Main Ampere
Rating
Unit Enclosure
Type Mounting
Type of
Circuit Breaker
Wire Size Range
Cu/Al 60°C or 75°C
Catalog
Number
Single-Phase Three-Wire—240 Vac Maximum
150 Outdoor CSR (included)  ECB150RB 
200 Outdoor CSR (included)  ECB200RB 
225 Indoor Flush CSR  ECB225F 
Indoor Surface CSR  ECB225S 
Outdoor CSR  ECB225R 
Circuit Breaker
Unit Enclosures
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
for Line Terminals
Two-Pole Breakers
35 kAIC
Catalog Number
100 #2–300 kcmil CSH2100N
125 #2–300 kcmil CSH2125N
150 #2–300 kcmil CSH2150N
175 #2–300 kcmil CSH2175N
200 #2–300 kcmil CSH2200N
225 #2–300 kcmil CSH2225N
Type Volts
Catalog Number
Suffix Adder
CSH 12 SR12
CSH 24 SR24
CSH 120 SR01
Ampere
Rating Description
Wire Size Range
Cu/Al 60°C or 75°C
for Line Terminals
Catalog
Number
225 For use on 125,
150, 175, 200 and
225A CSR breakers
#2–300 kcmil MCBK225
CSH2200N
Wire/Application
Maximum
Wire Size
Maximum
Ampere Rating
Aluminum—standard 250 kcmil 200
Aluminum—service entrance 250 kcmil 225
Copper—standard and service entrance 250 kcmil 225
16 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Type ECC Circuit Breaker Unit Enclosure—Order Type CC Circuit Breaker Separately
Type CC Circuit Breakers 240 Vac—10 kAIC For Use in Type
ECC Unit Enclosures
Shunt Trips, Auxiliary and Alarm Contacts
Wire Data
Notes
Order circuit breaker separately.
Wire size is determined by the circuit breaker installed in enclosure. Maximum wire size
and ampere rating is determined by the Wire Data table above.
One ground lug accepting (1) #14–#2 is factory installed. Also, there are pre-drilled holes to
accept a GBK5 ground bar.
Approved for service entrance.
Rainproof panels are furnished with hub closures plates. For rainproof hubs, refer to
Page 26.
Box sizes Pages 41 and 42.
Main
Ampere Rating
Unit
Enclosure Type Mounting
Circuit Breaker
Type
Wire Size Range
Cu/Al 60°C or 75°C
Catalog
Number
Single-Phase Three-Wire—240 Vac Maximum
225 Indoor Flush CC  ECC225F 
225 Indoor Surface CC  ECC225S 
225 Outdoor CC  ECC225R 
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
for Line Terminals
Type CC
10 kAIC
Catalog Number
Two-Pole
100 #4–4/0 CC2100
125 #4–4/0 CC2125
150 #4–4/0 CC2150
175 #2/0–300 kcmil CC2175
225 #2/0–300 kcmil CC2200
225 #2/0–300 kcmil CC2225
Three-Pole
100 #4–4/0 CC3100
125 #4–4/0 CC3125
150 #4–4/0 CC3150
175 #2/0–300 kcmil CC3175
200 #2/0–300 kcmil CC3200
225 #2/0–300 kcmil CC3225
Type Volts
Catalog Number
Suffix Adder
Shunt Trip
CC 12 DC SR12
CC 24 DC SR24
CC 120 AC SR01
CC 208 AC SR08
CC 240 AC SR02
Auxiliary Contact
CC (1) NO and (1) NC AL1
Alarm Contact
CSR CR1
Wire/Application
Maximum
Wire Size
Maximum
Ampere Rating
Aluminum—standard 250 kcmil 200
Aluminum—service entrance 250 kcmil 225
Copper—standard and service entrance 250 kcmil 225
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 17
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Technical Data and Specifications
General
A. The Contractor shall
furnish and install
loadcenters incorporating
circuit breakers of the
number, rating and type
as specified herein and
as shown on the
contract drawings.
B. The loadcenter and all
components shall be
designed, manufactured
and tested in accordance
with the latest applicable
standards of UL and
NEMA including:
1. UL 67—standards for
panelboards
2. UL 50—standards for
cabinets and boxes
3. UL 489—standards for
molded case circuit
breakers
4. Federal Spec
Classification W-C 375
5. UL 1699 — all fault
interrupting
Qualifications
A. The manufacturer of the
loadcenter shall be the
manufacturer of the
circuit breaker within the
load center. All breakers
shall be full size.
B. For the equipment
specified herein, the
manufacturer shall be
ISO® 9000 certified.
C. The manufacturer of
this equipment shall
have produced similar
electrical equipment
for a minimum period
of seven (7) years.
Manufacturers
A. Eaton
Ratings
A. Loadcenters shall be
rated for 240 Vac and
shall have short-circuit
ratings as shown on the
drawings or as herein
scheduled, but not less
than 10,000 amperes
rms symmetrical.
B. Breakers shall be full
size and a minimum of
125A frame. Breakers
10 –125A trip size shall
take up the same pole
spacing.
C. Loadcenters shall be
labeled with a UL short-
circuit rating. When
series ratings are applied
with integral or remote
devices, a label shall be
provided. Series ratings
shall cover all trip ratings
of installed frames. It
shall state the conditions
of the UL series ratings
including:
1. Size and type of
upstream device.
2. Branch devices that
can be used.
3. UL series short
circuit rating.
Construction
A. All interiors, with the
exception of the branch
circuit breakers shall be
completely factory
assembled with main
breakers, main lugs or
no main device.
B. Interiors shall be so
designed that circuit
breakers can be replaced
without disturbing
adjacent units and
without removing the
main bus connectors and
shall be so designed that
circuits may be changed
without machining,
drilling or tapping.
C. Physical means must
be provided to prevent
the installation of more
overcurrent devices than
that number for which
the enclosure was
designed. Full size
breakers are required.
Bus
A. Bus bars for the main and
cross connectors shall be
of silver flash plated
copper construction in
accordance with UL
standards. Bussing shall
be braced to 65 kAIC.
B. Neutral bussing shall
have a suitable lug for
each outgoing feeder
requiring a neutral
connection of same
ampacity as branch.
Wiring/Termination
A. All wire connectors and
terminals shall be of the
anti-turn solderless type
and suitable for copper
or aluminum wire of the
sizes indicated. All
connectors shall meet
the “Requirements
for Wire Connectors
and Soldering Lugs”
UL 486B.
B. All loadcenters where
marked shall be suitable
for use with 60/75°C
rated wire.
Circuit Breakers
A. Circuit breakers shall
be molded case type,
3/4-inch (19.1 mm) wide
per pole. Multipole circuit
breakers shall be of a
stack pole design to
provide electrical phase
isolation and have an
internal common trip.
B. Each pole of the circuit
breaker will have inverse
time delay overload and
instantaneous short-
circuit protection by
means of both thermal
and magnetic sensors.
Circuit breakers shall be
quick-make/quick-break.
C. The circuit breaker
calibration shall not be
affected by environmental
changes in relative
humidity. Breakers
shall be calibrated
after assembly.
D. All circuit breakers shall
be operated by a toggle-
type handle and multipole
circuit breakers shall have
an internal common trip
mechanism. The circuit
breakers shall incorporate
trip mechanisms that are
mechanically trip-free
from the handle. The
handle position shall
provide good visual
trip indication.
E. Contacts shall be of non-
welding silver alloy.
F. All branch breaker
handles shall be of a
different color than the
case of the breaker.
G. All terminals shall be
listed for use with copper
or aluminum conductors.
Terminals shall be of the
box lug design. The
terminals shall meet
UL 486B requirements
and shall be suitable for
use with either 60° or
75°C wire.
H. Breakers shall be SWD
rated and/or HACR rated
as required.
I. Arc fault interrupting
circuit breakers, (AFC),
shall be provided on all
15 and 20A single-phase
120/240 Vac circuits
except those indicated
as remote controlled
breakers. AFI breakers
shall be “Classified for
mitigating the effects of
arcing faults,” or
conforming to UL
Standard 1699 and as
defined by per article
210-12 Section A of the
1999 NEC Code.
18 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Enclosures
A. Loadcenters shall have
NEMA 1 general purpose
or NEMA 3R rainproof
enclosures as indicated
on the drawings and
shall be surface or flush
mounted except where
noted.
B. For indoor applications,
enclosures shall be rated
NEMA 1. Enclosures
shall be manufactured
from cold-rolled code-
gauge sheet steel having
multiple knockouts
and painted per paint
specification. For outdoor
applications, enclosures
shall be rated NEMA 3R.
Enclosures shall be
manufactured from
galvanized steel which
shall be painted per the
painted as specified.
Enclosures shall be of
sufficient size to meet
or exceed NEC wire
bending space.
C. The cover shall have an
easy adjustment feature
for flush applications.
D. Boxes shall be factory
assembled into a single
rigid structure.
E. Provide circuit breaker
marking labels and
directories.
Finish
A. Boxes and trims shall
be finished with a
high scratch-resistant
aesthetically pleasing
finish. The finish shall
be polyurethane coating
electrostatically applied
to a thickness of 1.8 to
2 mils.
B. All loadcenters shall be
provided with provisions
for accepting a paintable
or wall paperable
decorator accessory
cover. Where loadcenters
are installed in living areas,
provide manufacturer
designed and tested
decorator cover kits.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 19
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Surge Panel Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Surge Panel
Technical Data and Specifications . . . . . . . . . . . . . . . . . . 20
Type CH Renovation Loadcenter . . . . . . . . . . . . . . . . . . . . . 21
Type CH Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 22
Circuit Analyzer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Surge Panel
Product Description
Eaton’s Type CH Surge
Loadcenter includes a factory-
mounted and wired surge
suppressor device. There is
a knockout in the cover that
allows the user to view the
status indication lights on
the surge suppressor. The
CH Surge Loadcenter reduces
the surge current, helping
protect sensitive home
electronic equipment.
Save labor
by installing
a factory-
mounted surge
protective
device.
Factory-Installed
Surge Protection
Includes a CHSPULTRA
and a two-pole 15A
circuit breaker
Increases the
effectiveness of
surge protection due
to reduced lead length
A modified deadfront
allows for easy viewing
of indicating lights
Surge Ready
Provides a mounting
provision for CHSPULTRA
A modified deadfront
allows for easy viewing
of indicating lights
Product Selection
Surge Installed Loadcenters
Notes
Order cover separately.
With main lugs installed.
Ampere
Rating Type
Number
of Circuits
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Combination Surface
225 Convertible 42 CHSUR42N225L CHSUR8LF CHSUR8LS
225 Convertible 42 CHSUR42L225L2 CHSUR8LF CHSUR8LS
200 Main breaker 42 CHSUR42B200L2 CHSUR8LF CHSUR8LS
225 Convertible 32 CHSUR32N225K CHSUR8KF CHSUR8KS
225 Convertible 32 CHSUR32L225K CHSUR8KF CHSUR8KS
200 Main breaker 32 CHSUR32B200KCHSUR8KF CHSUR8KS
150 Main breaker 32 CHSUR32B150KCHSUR8KF CHSUR8KS
100 Main breaker 32 CHSUR32B100K CHSUR8KF CHSUR8KS
125 Convertible 24 CHSUR24L125E CHSUR8EF CHSUR8ES
100 Main breaker 24 CHSUR24B100E CHSUR8KF CHSUR8KS
200 Convertible 40/40 BRSUR4040N200 Cover included
200 Main lug 40/40 BRSUR4040L200 Cover included
200 Main breaker 40/40 BRSUR4040B200 Cover included
200 Convertible 30/40 BRSUR3040N200 Cover included
200 Main lug 30/40 BRSUR3040L200 Cover included
200 Main breaker 30/40 BRSUR3040B200 Cover included
20 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Surge Ready Loadcenters (provision only, CHSPULTRA and breaker not included)
Main Breaker Kits Main Lug Kits
Technical Data and Specifications
Ratings
Loadcenter
35 kAIC main breaker, main lug only, and convertible
main breaker/main lug
Factory installed or provision for field-installed
surge suppressor
Top or bottom feed
Surge suppressor (CHSPULTRA)
Total joules: 3500 joules
Maximum surge current: 175,000A
Per phase (L-N/L-G) surge current: 75,000A
Warranty: lifetime
Connected equipment warranty: $75,000
Notes
Order cover separately.
With main lugs installed.
Ampere
Rating Type
Number
of Circuits
Loadcenter
Catalog Number
Loadcenter Cover Catalog Number
Combination Surface
225 Convertible 42 CHEC42N225L CHSUR8LF CHSUR8LS
225 Convertible 42 CHEC42L225L CHSUR8LF CHSUR8LS
200 Main breaker 42 CHEC42B200L CHSUR8LF CHSUR8LS
225 Convertible 32 CHEC32L225K CHSUR8KF CHSUR8LS
225 Convertible 32 CHEC32N225K CHSUR8KF CHSUR8LS
200 Main breaker 32 CHEC32B200K CHSUR8KF CHSUR8LS
150 Main breaker 32 CHEC32B150K CHSUR8KF CHSUR8LS
100 Main breaker 32 CHEC32B100K CHSUR8KF CHSUR8LS
125 Convertible 24 CHEC24L125E CHSUR8EF CHSUR8LS
100 Main breaker 24 CHEC24B100E CHSUR8EF CHSUR8LS
Maximum Main Ampere Rating Catalog Number
100 CSH2100N
150 CSH2150N
200 CSH2200N
225 CSH2225N
Maximum Main Ampere Rating Catalog Number
125 CHL125N
225 CHL225N
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 21
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Renovation Panel Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Surge Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Type CH Renovation Loadcenter
Type CH Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 22
Circuit Analyzer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Type CH Renovation
Loadcenter
Product Description
Eaton’s Renovation
Loadcenter is designed
for the service contractor.
With the addition of a five-
circuit terminal block factory
mounted in the top left corner
of the loadcenter, the service
contractor can terminate
short-circuit wires instead of
having to use expensive wire
nuts. Also, the Renovation
Loadcenter incorporates a
twin-stacked neutral design
that places the neutral and
ground terminations higher in
the loadcenter. Both of these
features were added without
increasing any size from a
standard loadcenter. These
features will eliminate the
need for wire nuts and make
for a much neater installation.
There is a provision to field
mount a second five-circuit
terminal block (RN5TB) in
the top right corner of the
loadcenter. Choose amongst
Eaton’s Type CH breaker
family for use in the
Renovation Panel.
Product Selection
Single-Phase—Main Circuit Breaker Loadcenters 35 kAIC
Single-Phase, Three-Wire—120/240 Vac—Factory-Bonded Stacked
Split Neutral
Branch Circuit Breakers (CH)
See Pages 2–14.
Renovation Loadcenter
Notes
100A main breaker is rated 10 kAIC.
Combination style covers may be used in surface or flush applications.
All main circuit breaker loadcenters are listed for use as service entrance equipment. Loadcenters
are factory-bonded for service entrance applications. Remove bonding strap for separate neutral
and ground bars for sub-feed applications.
Main
Breaker
Type
Main
Ampere
Rating
Max.
Number
3/4-Inch
(19.1 mm)
of Poles
Enclosure
Type
Box
Size
Wire Size
Range
Cu/Al
60 or 70ºC
for Main
Breakers
Loadcenter
Catalog
Number
Cover Catalog
Number
Combination Surface
CH 100 20 Indoor C #6–1/0 CH22B100CRN CH8CFF CH8CS
CSH 150 32 Indoor J #2–300 kcmil CH32B150JRN CH8JF CH8JS
CSH 200 32 Indoor J #2–300 kcmil CH32B200JRN CH8J CH8JS
CSH 200 42 Indoor K #2–300 kcmil CH42B200KRN CH8KF CH8KS
Description Catalog Number
Five-circuit terminal block kit
Ground bar kits (two maximum per panel)
RN5TB
(See Page 26)
22 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Type CH Retrofit Type CH Retrofit Interior Collar
Adjustable Interior and Assembly with Trim
Type CH Retrofit Interior Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Surge Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Type CH Renovation Loadcenter . . . . . . . . . . . . . . . . . . . . . 21
Type CH Retrofit Interior Kits
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Circuit Analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Type CH Retrofit Interior Kits
Product Description
Replacing existing
loadcenters and panelboards
can be a time consuming and
expensive job. CH retrofit kits
can be the solution to save
time and money. The kit
consists of a standard trim to
fit the interior, a picture frame
trim to fit the existing box,
and a field-adjustable interior
assembly that includes
neutral and ground bars.
These are especially
applicable when the existing
box is flush mounted in
drywall, plaster or block wall.
The existing box, and many
times existing wiring, can
remain.
Features and Benefits
Upgrading Existing Electrical
Infrastructure Is Simple
Replaces vintage brands
that have hard to find,
expensive replacement
breakers
Allows safety upgrade
to arc fault and ground
fault breakers
Maximizes number of
circuits available with
compact design
Meets 2008 NEC wire
bending requirements
Eco-friendly in asbestos-
filled environments
Exclusive design
Save Time and Money
Throughout the Installation
Uses existing panel
box and wires
Eliminates expensive
drywall/paint repair
Saves 2–3 hours compared
to a complete panel
changeout—get off the
job faster
Eliminates precise
measurements with field-
adjustable kit
Detailed Product Guide
All standard retrofit kits are
suitable for a range of
existing box sizes:
Box width ranging from
14.50 to 22.00 inches
(368.3 to 558.8 mm)
Box depth ranging from
4.25 inches (108.0 mm)
for CH to 6.00 inches
(152.4 mm)
Box height ranging from
21.00 to 45.00 inches
(533.4 to 1143.0 mm)
For box dimensions outside
of these ranges, contact
the Lincoln Flex Center at
800-330-6479. Be sure to
provide the existing incoming
line wire size.
Standards and Certifications
Interiors are UL recognized
under UL 67, Panelboard
standard.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 23
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Product Selection
To select the retrofit kit:
1. From the existing box
size determine which
retrofit groups are
suitable (may be more
than one).
2. Use type of interior,
number of phases, and
type of main to find the
selection chart.
3. Select part number from
chart (if main breaker,
replace XXX with specific
amp rating).
4. Note that the overlap
of the existing wall is
the retro cover size
minus the existing
box size. If specific
measurements are
needed, communicate
that you need a custom
trim size.
5. Contact the Lincoln Flex
Center at 800-330-6479
for pricing, lead-times,
and order entry
instructions.
Retro Size Groups
Retrofit Stocking Kits (BR and CH Kits Available) 
Five recommended groups: existing box height determines retro group size.
Notes
Other options are available.
CH retrofit interiors and collar cartons are color coded to ensure accuracy of kit.
Description
Retrofit
Kit Interior
Catalog Number
Collar
Catalog
Number
Cover
Catalog
Number
Existing Enclosure Parameters—Inches (mm) Existing Box Height
Determines Retro
Size Group—Inches (mm)Height Width Depth
BR-Aluminum Bus/CH-Copper Bus
BR 125A MLO 12/24 circuit retro kit RAABR12L125 Included Included 14.00–18.00
(355.6–457.2)
10.50–12.50
(266.7–317.5)
3.50–5.25
(88.9–133.35)
Retro size AA/size
14.00–21.00 (355.6–533.4)
BR 100A MCB 10/20 circuit retro kit RAABR10B100 Included Included 14.00–18.00
(355.6–457.2)
10.50–12.50
(266.7–317.5)
3.50–5.25
(88.9–133.35)
Retro size AA/size
14.00–21.00 (355.6–533.4)
BR 125A MLO 12/24 circuit retro kit RAABR12L125A Included Included 14.00–21.00
(355.6–533.4)
10.50–15.50
(266.7–393.7)
3.50–5.25
(88.9–133.35)
Retro size AA/size
14.00–21.00 (355.6–533.4)
BR 100A MCB 10/20 circuit retro kit RAABR10B100A Included Included 14.00–21.00
(355.6–533.4)
10.50–15.50
(266.7–393.7)
3.50–5.25
(88.9–133.35)
Retro size AA/size
14.00–21.00 (355.6–533.4)
CH interior 125A MCB 22 circuits RACH22B125I RACHFRAME CH8CF 21.00–30.00
(533.4–762.0)
13.00–22.00
(330.2–558.8)
4.25–6.00
(108.0–152.4)
Retro size A/size
21.00–30.00 (533.4–762.0)
CH interior 125A MLO 24 circuits RACH24L125I RACHFRAME CH8CF 21.00–30.00
(533.4–762.0)
13.00–22.00
(330.2–558.8)
4.25–6.00
(108.0–152.4)
Retro size A/size
21.00–30.00 (533.4–762.0)
CH interior 150A MCB 24 circuits RBCH24B150I RACHFRAME CH8EF 29.00–36.00
(736.6–914.4)
13.00–22.00
(330.2–558.8)
4.25–6.00
(108.0–152.4)
Retro size B/size
29.00–36.00 (736.6–914.4)
CH interior 225A MLO 32 circuits RBCH32L225I RACHFRAME CH8DF 29.00–36.00
(736.6–914.4)
13.00–22.00
(330.2–558.8)
4.25–6.00
(108.0–152.4)
Retro size B/size
29.00–36.00 (736.6–914.4)
CH interior 200A MCB 32 circuits RCCH32B200I RCCHFRAME CH8JF 34.00–41.00
(863.3–1041.4)
13.00–22.00
(330.2–558.8)
4.25–6.00
(108.0–152.4)
Retro size C/size
34.00– 41.00 (863.3–1041.4)
CH interior 225A MLO 42 circuits RCCH42L225I RCCHFRAME CH8GF 34.00–41.00
(863.3–1041.4)
13.00–22.00
(330.2–558.8)
4.25–6.00
(108.0–152.4)
Retro size C/size
34.00– 41.00 (863.3–1041.4)
CH interior 200A MCB 42 circuits RDCH42B200I RDCHFRAME CH8KF 37.00–45.00
(939.8–1143.0)
13.00–22.00
(330.2–558.8)
4.25–6.00
(108.0–152.4)
Retro size D/size
37.00–45.00 (939.8–1143.0)
CH interior 225A MLO 42 circuits RDCH42L225I RDCHFRAME CH8KF 37.00–45.00
(939.8–1143.0)
13.00–22.00
(330.0–558.8)
4.25–6.00
(108.0–152.4)
Retro size D/size
37.00–45.00 (939.8–1143.0)
Existing Box Height Determines Retro Size Group
21" 29" 30" 34" 36" 37" 41" 45" 54"
Retro Size A
Retro Size B
Retro Size C
Retro Size D
Retro Size E
24 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Circuit Analyzer Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Surge Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Type CH Renovation Loadcenter . . . . . . . . . . . . . . . . . . . . . 21
Type CH Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 22
Circuit Analyzer
Technical Data and Specifications . . . . . . . . . . . . . . . . . . 25
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . 25
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Circuit Analyzer
Product Description
Eaton’s Circuit Analyzer
provides accurate testing
of AFCI and GFCI devices
while also testing for faulty
wiring conditions.
There are other testing devices
on the market, but this will be
the only one available from an
AFCI manufacturer. Eaton
has more than 100 years of
electrical control and power
distribution experience, and a
thorough understanding of
what arc faults are all about.
This experience with AFCI
breakers led to developing
a feature of the analyzer that
will save contractors time
and aggravation. It allows
contractors to verify whether
they have a grounded neutral
simply by depressing the
red Neutral Isolation test
button. In this way, they will
be able to determine whether
they have a grounded neutral
or have other neutrals
connected before they leave
the job site. Additionally,
the Circuit Analyzer has a
button that tests AFCI and
two that test GFCI devices
(both 40 mA and 8 mA).
Application Description
The Circuit Analyzer serves
as a handy troubleshooting
tool for contractors and
electrical inspectors. It
provides accurate testing of
AFCI and GFCI devices while
also testing for faulty wiring
conditions.
Features, Benefits and Functions
All-in-one tester for ground
fault, arc fault and faulty
wiring conditions
Neutral isolation test
button is a feature that
allows the contractor to
determine whether they
have a grounded neutral
or have other neutrals
connected before leaving
the job
Additional Test button for
AFCI and two that test
GFCI devices (40 mA
and 8 mA)
Only product available from
an AFCI manufacturer
Three standard
accessories enhance
the usefulness of the
Circuit Analyzer:
An alligator clip
attachment to test
hardwired circuits, such
as smoke detectors,
that lack a receptacle.
The clip simply is
attached to the smoke
alarm’s terminals
An adapter (three-prong
to two-prong) for testing
in older homes that lack
three-prong receptacles
Light socket adapter for
AFCI testing when no
receptacle is available.
Examples are ceiling
fans that contain
sockets and recessed
lighting
Additionally, the Circuit
Analyzer comes with a
black carrying case
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 25
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Technical Data and Specifications
How it Works
1. Plug the tester (or one
of the accessories) into
the receptacle, light
fixture or hardwired
terminals to be tested.
2. Check the wiring LEDs
on the Circuit Analyzer to
determine if the circuit is
wired correctly.
3. If the circuit is wired
correctly, then proceed
to test for neutral
isolation, arc fault or
ground fault conditions,
depending on the
breaker or receptacle
type that is on the circuit.
4. To perform these tests,
press the corresponding
button on the Circuit
Analyzer and review
the results.
Options and Accessories
Field Installation and Parts
Note
Must be purchased in multiples of ordering quantities indicated.
Description
Ordering
Quantity
Catalog
Number
Sub-feed lug blocks—two-pole, 125A, 3/4-inch (19.1 mm) spaces needed 1 CHSF2125
Sub-feed lug blocks—three-pole, 125A, 3/4-inch (19.1 mm) spaces needed 1 CHSF3125
Neutral/ground lug—add-on neutral or ground lug 1 NL20
1NL30
1NL300
Filler plates—3/4-inch (19.1 mm) space circuit breaker space 25 CHFP
CSR main circuit breaker filler plate (with hardware) 1 CSRFP
Door lock—12–42 circuits, and 100–225A 1 TDL
Sandlewood spray paint 1 SPCSW
ANSI-61 light gray touchup paint for outdoor loadcenters 1 SPC61
Isolated neutral assembly (computer circuits) 1 BINA
Circuit directory—adhesive backed 10 TCD
Cover screws 25 LCCS
Cover replacement latch 14-5/16 inch (363.55 mm) wide loadcenters only 1 CHRLS
Circuit marking strip (next to breakers) 10 CHMS
Circuit identification label (preprinted breaker labels next to breakers) 25 CHBL
Series rated caution label 25 SRL
Branch circuit numbering strip 20 CHNS
Bonding strap with screw 1 BSSUSE
CHSF2125
CHSF3125
CHFP
TDL
BINA
CHRLS
26 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Field Installation Rainproof Conduit Hubs
Ground Bar Kits
Ground Bar Legend
Grounded “B” Phase Adapters Neutral Bar Accessories
Notes
Must be purchased in multiples of ordering quantities indicated.
Distance between mounting holes is 1-3/4 inches (44.5 mm).
For single- and three-phase 400A loadcenters.
Distance between mounting holes is 2-13/32 inches.
Cannot be used in Safety Breaker Panels. Classic Plus Panels only.
Description
Conduit Size Ordering
Quantity
Catalog
NumberInches (mm)
Group 1—for use with 70, 100 and 125A MLO and MCB loadcenters and circuit breaker enclosures,
and the following 150 and 200A panels: CH8B150RF, CH8B200RF
0.75 (19.1) 1 DS075H1
1.00 (25.4) 1 DS100H1
1.25 (31.8) 1 DS125H1
1.50 (38.1) 1 DS150H1
2.00 (50.8) 1 DS200H1
Group 2—for use with 150, 200 and 225A MLO and MCB loadcenters and circuit breaker enclosure
except for the following 150 and 200A panels: CH8B150RF, CH8B200RF
2.00 (50.8) 1 DS200H2
2.50 (63.5) 1 DS250H2
3.00 (76.2) 1 DS300H2
Adapter kit—allows Installing a Group 1 hub on devices arranged for Group 2 hubs 1 DS900AP
Group 1—small blank hub closure plate 1 DS900CP1
Group 2 — large blank hub closure plate 1 DS900CP2
Description (See Legend)
Length Ordering
Quantity
Catalog
NumberInches (mm)









2.54 (64.5) 1 GBK5
3.59 (91.2) 1 GBK520
4.29 (109.0) 1 GBK10
5.34 (135.6) 1 GBK1020
4.61 (117.1) 1 GBK13
5.69 (144.5) 1 GBK14
6.74 (171.2) 1 GBK1420
8.14 (206.8) 1 GBK21
9.19 (233.4) 1 GBK2120
7.94 (201.7) 1 CH9GP21 
DS100H1
GBK14
=(3) #14–#10 Cu/Al or (1) #14–#4 Cu/Al
=(1) #6–2/0 Cu/Al
=(1) 1/0–14 or (3) #10–12 Cu/Al
=(1) #14–1/0 Cu/Al or (3) #14–#10 Cu/Al
=Mounting hole
 
Maximum
Amperes
Three-Phase Loadcenter
Types of Panels
Kit Catalog
Number
125 12–32 circuit main lug CHGRD1
225 Main lug and CHH main breaker panels CHGRD2
CC main CB panels CHGRD3
Description
Catalog
Number
Split neutral kit for 22 circuit 125A maximum CHSN125C
Split neutral kit for 32 circuit 200A maximum CHSN225J
Split neutral kit for 42 circuit 200A maximum CHSN225K
Replacement neutral for all C type boxes CHN125C
Replacement neutral for all D type boxes CHN125D
Replacement neutral for all L type boxes CHN225L
Isolated Neutral Assembly (computer circuits) BINA
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 27
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Mechanical Interlock Covers
Covers mechanically interlock
two breakers. Type A covers
interlock two CH breakers
mounted across from one
another. Type B covers
interlock a main Type CSR
breaker with a Type CH.
Mechanical Interlocks
Type
Fits Loadcenter
Catalog Numbers
Mechanical Interlock Panel Cover Catalog Number
Flush Surface
ACH12L125B, CH16L125B, CH12L3125B, CH14B100B CH8BFM CH8BSM
CH20L125C, CH24L125C, CH18L3125C, CH24L3125C, CH22B100C, CH22N100C CH8CFM CH8CSM
CH24L150D, CH32L150D, CH24L3225D, CH30L3150D CH8DFM CH8DSM
CH42L225G, CH42L3225G CH8GFM CH8GSM
Inner cover of Box B raintight — CH8BRM
Inner cover of Box C raintight — CH8CRM
BCH24B150E, CH24B200E CH8EFM CH8ESM
CH32B150J, CH32B200J, CH3242B200J, CH32N200J, CH32B225J CH8JFM CH8JSM
CH42B200K, CH42N200K, CH42B225K CH8KFM CH8KSM
CHPC32B150L, CHPC32B200L, CHPC32N200L CHPC8B32LFM —
CHPC42B150L, CHPC42B200L, CHPC42N200L CHPC8B42LFM —
CH8B150RF, CH8B200RF, CH8N200RF, CH24B150R, CH24B200R CH3RDF7M —
CH32B150R, CH32B200R, CH32N200R, CH32B225R CH3RDF9M —
CH42B200R, CH42N200R, CH42B225R CH3RDF10M —
CH8BRM Type A
CH8EFM Type B
28 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Decorator Cover Accessory
For easy use with CH loadcenters mounted in living space
Easily wallpapered or painted to match any decor
Loadcenter accessory—exclusively from Eaton
Now you see it … … Now you don’t.
Decorator Cover Accessory
CH Loadcenter Goof Collars
Don’t let an ugly drywall problem ruin a beautiful
electrical installation.
Eaton’s Goof Collar is designed to cover gaps between the
finished drywall and loadcenter enclosure. This is often
necessary when upgrading the electrical service and the drywall
surrounding the panel is damaged. The collar allows 2 inches of
overhang beyond the standard flush trim.
Currently available in three sizes for the CH style loadcenters.
Goof Collars are also available for the BR style loadcenters
upon request. Please contact the Lincoln Flex Center at
1-800-330-6479 for questions and product opportunities.
Before After
Goof Collars
Note
For interlock covers for loadcenters not listed in chart, please contact the Flex Center
at 1-800-330-6479.
Catalog Number
Corresponding Cover Existing CH Loadcenter Cover
CH8BF CH8KDNB
CH8CF CH8KDNC
CH8DF/EF CH8KDND
CH8GF/JF CH8KDNJ
CH8KF CH8KDNK Inches (mm) Catalog Number
Height Width Loadcenter Cover Goof Collar
26.00 (660.4) 19.00 (482.6) CH8CF CH8CFC1926
39.00 (990.6) 19.00 (482.6) CH8JF CH8JFC1939
42.00 (1066.8) 19.00 (482.6) CH8KF CH8KFC1942
SCOTT
HAS
PHOTO
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 29
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Plug-On Circuit Breakers Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Surge Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Type CH Renovation Loadcenter . . . . . . . . . . . . . . . . . . . . . 21
Type CH Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 22
Circuit Analyzer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . 37
Technical Data and Specifications . . . . . . . . . . . . . . . . . . 39
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Circuit Breakers
Product Description
Quick-make, quick-break
switch mechanism combined
with inverse time element
tripping operation and trip-
free handle design. Type CH
circuit breakers trip to the
OFF position, eliminating
nuisance callbacks. The
thermal-magnetic trip curve
avoids nuisance tripping on
mild overloads while reacting
almost instantaneously
to severe short-circuit
conditions. Multipole breakers
have internal common trip
connection to operate all
poles simultaneously. Handles
are marked with ON-OFF
indication and ampere rating
of the breaker.
Special Application Plug-On
Circuit Breakers—Type CH
10 kAIC 120 Vac and 120/240 Vac
Branch Feeder Type Arc
Fault Circuit Breakers
A branch feeder type arc fault
circuit interrupter is a device
intended to mitigate high
current arcing faults in the
complete circuit, including
connected cords. High
current arcing faults can
occur from line to neutral or
line to ground. These arcing
faults are in parallel with the
load and produce the most
energy of all arcing faults.
The branch feeder type AFCI
is required in the 1999 and
2002 National Electrical Code.
The Combination Type AFCI
is required in the 2005 and
2008 National Electrical Code.
Combination Type Arc
Fault Circuit Breakers
A combination type arc fault
circuit interrupter is a device
that includes all of the
protection offered by the
branch feeder AFCI (mitigation
of high current arcing faults in
the complete circuit, including
connected cords). In addition
it provides direct detection of
persistent low current arcing
faults down to 5 amps with
associated mitigation of
fire hazards in the cords
connected to the outlets. High
current arcing faults can occur
from line to neutral or line to
ground. These arcing faults
are in parallel with the load
and produce the most energy
of all arcing faults. The current
level of low current arcing
faults is limited by the load.
Ground Fault Circuit
Breakers—Ground Fault
Application Notes
Single-pole Type CHGFIs are
designed for use in two-wire,
120 Vac circuits. The diagram
on Page 39 shows a typical
wiring configuration.
Two-pole Type CHGFIs are
designed for use in three-
wire, 120/240 Vac circuits,
120 Vac multiwire circuits
employing common, neutral
and two-wire, 240 Vac
circuits obtained from a
120/240 Vac source.
Diagrams on Page 39 illustrate
typical wiring configurations
for 120/240 Vac multiwire
circuits.
The diagram on Page 39
depicts a 240 Vac, two-wire
circuit. Note the “panel
neutral” conductor connects
to the neutral bar, even
though the neutral is not
included in the load circuit.
This connection is necessary
to supply a 120 Vac power
source to the ground fault
sensing circuit.
The figures are shown with
a 120/240 Vac, single-phase,
three-wire power source,
but are also applicable to a
120/208 Vac, three-phase,
four-wire power supply.
For all figures, the electrical
operation of the Type CHGFI
is not affected by the
equipment ground.
30 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Features
Plug-On Type CH Breaker
Latch
Spring
Over-Center
To g g l e Spring
Latch
Lever
Magnetic
Armature
Current
Bi-Metal
Calibration
Screw
(under
UL label)
Load
Ter minal
Magnetic
Pole Piece
Contact
Contact
Clip Spring
Line
Contact
Clip
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 31
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Product Selection
10 kAIC, 120 Vac, 120/240 Vac and 240 Vac
Type CH Breakers, 3/4-Inch (19.1 mm) per Pole 120, 120/240 or 240 Vac, 10 kAIC
Notes
For single- and two-pole breakers.
Solid and stranded wire can be used together.
For three-pole breakers.
Single-pole 60–70A, two-pole 80–125A, three-pole 40–100A.
Single-pole 40–50A, two-pole 40–70A.
Two-pole 150A.
Switching duty rated.
HACR rated.
CH2150 requires four-pole spaces and is not suitable for use on three-phase panels, not CSA certified.
With trip indication.
For factory-installed options, refer to Page 38.
Ampere
Rating
Wire Size
Range Cu/Al
60ºC or 75°C
Catalog Number
Single-Pole 120/240 Vac
Requires One
3/4-Inch (19.1 mm) Space
10 per Shelf Carton
Two-Pole 120/240 Vac
Common Trip Requires Two
3/4-Inch (19.1 mm) Spaces
5 per Shelf Carton
Three-Pole 240 Vac
Common Trip Requires Three
3/4-Inch (19.1 mm) Spaces
5 per Shelf Carton
10 (1) #14–8
(2) #14–10 
(1) #14–6
CH110 CH210 CH310
15 CH115  CH215 CH315
20 CH120  CH220 CH320
25 CH125 CH225 CH325
30 CH130 CH230 CH330
15 CHF115 CHF215 CHF315
20 CHF120 CHF220 CHF320
25 CHF125 CHF225 CHF325
30 CHF130 CHF230 CHF330
35 #14–2
#14–6
CH135 CH235 CH335
40 #10–1/0
#14–2
#3/0
CH140 CH240 CH340
45 CH145 CH245 CH345
50 CH150 CH250 CH350
70 CH170 CH270 CH370
80 CH280 CH3080
90 CH290 CH3090
100 CH2100 CH3100
110 CH2110 —
125 CH2125 —
150 CH2150
Plug-On Circuit
Breakers
32 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Plug-On Branch Feeder Type Arc Fault Circuit Breakers, Type CH 10 kAIC, 120 Vac and 120/240 Vac
Type CH 3/4-Inch (19.1 mm) Wide FIRE-GUARD® AFCI Circuit Breakers
Plug-On Combination Type Arc Fault Circuit Breakers, Type CH 10 kAIC,120 Vac and 120/240 Vac
Type CH 3/4-Inch (19.1 mm) Wide FIRE-GUARD Combination Type AFCI Circuit Breakers
Plug-On Ground Fault Circuit Breakers, Type CH 10 kAIC, 120 Vac and 120/240 Vac
Type CH Ground Fault Circuit Breakers (5 Milliampere) 3/4-Inch (19.1 mm) per Pole 120 Vac or
120/240 Vac,10 kAIC
Notes
Clamshell packaging available with CS modification code on the end of catalog number.
Common trip refers to two-pole 240V load application sourced by 120/240 Vac (see diagram on Page 39).
Independent trip refers to two-pole multi-wire, home run or shared neutral circuits (see diagrams on Page 39).
Requires plug-on neutral loadcenter.
60A breaker listed for 75°C Cu wire only.
Poles Ampere Rating Configuration Catalog Number
Single-pole
10 kAIC
15 AFCI CH115AF
20 AFCI CH120AF
Two-Pole
10 kAIC 
15 AFCI common trip CH215AF
20 AFCI common trip CH220AF
Poles Ampere Rating Configuration Catalog Number
Single-pole
10 kAIC
15 AFCI CH115CAF
AFCI plug-on neutral, no pigtail CH115CAFPN
20 AFCI CH120CAF
AFCI plug-on neutral, no pigtail CH120CAFPN
Two-pole
10 kAIC
15 AFCI CH215CAF
AFCI plug-on neutral, no pigtail CH215CAFPN
20 AFCI CH220CAF
AFCI plug-on neutral, no pigtail CH220CAFPN
Ampere Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Catalog Number—1 per Shelf Carton
Single-Pole 120 Vac Requires
One 3/4-Inch (19.1 mm) Space
Two-Pole 120/240 Vac Common Trip
Requires Two 3/4-Inch (19.1 mm) Spaces
15 #14–6 CH115GF CH215GF
20 #14–6 CH120GF CH220GF
25 #14–6 CH125GF CH225GF
30 #14–6 CH130GF CH230GF
35 #14–6 — CH235GF
40 #14–6 — CH240GF
45 #14–6 — CH245GF
50 #14–6 — CH250GF
60 #14–6 — CH260GF
Type CH Single-Pole
AFCI Circuit Breaker
Type CH Single-Pole
PON Combo AFCI
Circuit Breaker
Type CH Single-Pole
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 33
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Type CH Ground Fault Equipment Protectors (30 Milliampere) 3/4-Inch (19.1 mm) per Pole 120 Vac or
120/240 Vac, 10 kAIC
Type CH Switching Neutral Breakers—10 kAIC, 120 Vac and 120/240 Vac
Used to open the neutral along power line(s) for applications of gas pumps.
3/4-Inch (19.1 mm) per Pole 120/240 or 240 Vac, 10 kAIC
Type CH-HID Circuit Breakers—10 kAIC, 120 Vac, 120/240 and 240 Vac
Suitable for use in circuits for fluorescent and high intensity discharge lighting. Also suitable for HACR applications.
3/4-Inch (19.1 mm) per Pole 120 Vac, 120/240 and 240 Vac, 10 kAIC
Notes
60A breaker listed for 75°C Cu wire only.
For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space.
Switching duty rated.
CH215HID is rated for 120/240V.
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Catalog Number—1 per Shelf Carton
Single-Pole 120 Vac Requires
One 3/4-Inch (19.1 mm) Space
Two-Pole 120/240 Vac Common Trip
Requires Two 3/4-Inch (19.1 mm) Spaces
15 #14–6 CH115EPD CH215EPD
20 #14–6 CH120EPD CH220EPD
25 #14–6 CH125EPD —
30 #14–6 CH130EPD CH230EPD
40 #14–6 — CH240EPD
50 #14–6 — CH250EPD
60 #14–6 — CH260EPD
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Catalog Number—1 per Shelf Carton
Two-Pole 120 Vac
Common Trip Requires
Two 3/4-Inch (19.1 mm) Spaces
Three-Pole 120/240 Vac
Common Trip Requires
Three 3/4-Inch (19.1 mm) Spaces
15 #14–8 CH215SW CH315SW
20 #14–8 CH220SW CH320SW
30 #14–8 CH230SW CH330SW
40 #14–8 CH240SW CH340SW
50 #14–8 CH250SW CH350SW
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°
Single-Pole 120/240 Vac
Requires One
3/4-Inch (19.1 mm) Space
Two-Pole 240 Vac
Common Trip Requires
Two 3/4-Inch (19.1 mm) Spaces
Three-Pole 240 Vac
Common Trip Requires
Three 3/4-Inch (19.1 mm) Spaces
10 per Shelf Carton
Catalog Number
5 per Shelf Carton
Catalog Number
5 per Shelf Carton
Catalog Number
15 #14–8 CH115HID CH215HID CH315HID
20 #14–8 CH120HID CH220HID CH320HID
30 #14–8 CH130HID CH230HID CH330HID
Type CH Two-Pole
CH220SW
N
eut
r
a
l I
n
N
eut
r
a
l
Ou
t
(Hot le
g
)
N
eut
r
a
l I
n
N
eut
r
a
l
Ou
t
Ph
ase
Ph
ase
34 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Non-CTL Plug-On Replacement Circuit Breakers, Type CHNT 10 kAIC, 120/240 Vac
For use as replacement in loadcenters built prior to 1968 and within the current style 2–8 circuit
loadcenters as indicated in the loadcenter section.
3/4-Inch (19.1 mm) per Pole 120 Vac, Non-CTL 10 kAIC
CTL Plug-On Circuit Breakers, Type CHT Twin 10 kAIC, 120/240 Vac
All circuit breakers have rejection feature. Use only with loadcenters marked for use with CHT breakers.
Twin (CTL) 3/4-Inch (19.1 mm) per Pole 120 Vac Class CTL 10 kAIC
Notes
Switching duty rated.
HACR rated.
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole Requires
One 3/4-Inch (19.1 mm) Space
10 per Shelf Carton
Catalog Number
15–15 #14–8 CHNT1515 
15–20 #14–8 CHNT1520 
20–20 #14–8 CHNT2020 
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole Requires
One 3/4-Inch (19.1 mm) Space
10 per Shelf Carton
Catalog Number
15–15 #14–8 CHT1515 
15–20 #14–8 CHT1520 
20–20 #14–8 CHT2020 
120
/
240 V
a
c
120
/
240 V
a
c
Type CH and CHT
Circuit Breakers
Mounted in Twin
Breaker Panel
120
/
240 V
a
c
120
/
240 V
a
c
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 35
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Type CHP Commercial Breakers—10 kAIC, 120 Vac, 120/240 Vac and 240 Vac
Note: CHP breakers feature on-off and trip positions for commercial applications.
3/4-Inch (19.1 mm) per Pole 120, 120/240 or 240 Vac, 10 kAIC
Type CHP-GFCI Circuit Breakers—10 kAIC, 120 Vac and 120/240 Vac
Note: CHP breakers offer on-off and trip positions for commercial applications.
5 Milliampere—3/4-Inch (19.1 mm) per Pole
120V and 120/240 Vac, 10 kAIC
Notes
For single- and two-pole breakers.
Solid and stranded wire can be used together.
For three-pole breakers.
Single-pole 60–70A, two-pole 80–125A, three-pole 40–100A.
Single-pole 40–50A, two-pole 40–70A.
Switching duty rated.
HACR rated.
CHP breakers offer on-off and trip positions for commercial applications.
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole 120/240 Vac
Requires One 3/4-Inch
(19.1 mm) Space
Two-Pole 120/240 Vac
Common Trip
Requires Two 3/4-Inch
(19.1 mm) Spaces
Three-Pole 240 Vac
Common Trip
Requires Three 3/4-Inch
(19.1 mm) Spaces
10 per Shelf Carton
Catalog Number
5 per Shelf Carton
Catalog Number
5 per Shelf Carton
Catalog Number
10 (1) #14–8
(2) #14–10 
(1) #14–6
CHP110 CHP210 CHP310
15 CHP115  CHP215 CHP315
20 CHP120  CHP220 CHP320
25 CHP125 CHP225 CHP325
30 CHP130 CHP230 CHP330
35 #14–2
#14–6
CHP135 CHP235 CHP335
40 #10–1/0
#14–2
CHP140 CHP240 CHP340
45 CHP145 CHP245 CHP345
50 CHP150 CHP250 CHP350
60 CHP160 CHP260 CHP360
70 CHP170 CHP270 CHP370
80 CHP280 —
90 CHP290 —
100 CHP2100 CHP3100
110 CHP2110 —
125 CHP2125 —
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole 120 Vac Requires
One 3/4-Inch (19.1 mm) Space
1 per Individual Carton
Catalog Number
15 #14–6 CHP115GF
20 #14–6 CHP120GF
30 #14–6 CHP130GF
36 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Type CHP Neutral Switching Breakers—10 kAIC, 120 Vac and 120/240 Vac
Used to open the neutral along power line(s) for applications of gas pumps.
3/4-Inch (19.1 mm) per Pole 120 or 120/240 Vac, 10 kAIC
Type CH-M50 High Ambient Breaker
3/4-Inch (19.1 mm) per Pole 120 or 120/240 Vac, 10 kAIC
Type CH-HM and CHP-HM High Magnetic Breakers
3/4-Inch (19.1 mm) per Pole 120 or 120/240 Vac, 10 kAIC
Note
For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space, obtain pricing from Page 38.
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Two-Pole 120 Vac Common Trip
Requires Two 3/4-Inch (19.1 mm) Spaces
Three-Pole 120/240 Vac Common Trip
Requires Three 3/4-Inch (19.1 mm) Spaces
1 per Shelf Carton
Catalog Number
1 per Shelf Carton
Catalog Number
15 #14–8 CHP215SW CHP315SW
20 #14–8 CHP220SW CHP320SW
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole 120/240 Vac
Requires One 3/4-Inch (19.1 mm) Space
Two-Pole 120/240 Vac Common Trip
Requires Two 3/4-Inch (19.1 mm) Spaces
10 per Shelf Carton
Catalog Number
5 per Shelf Carton
Catalog Number
15 (1) #14–8
(2) #14–10
CH115M50 CH215M50
20 CH120M50 CH220M50
25 CH125M50 CH225M50
30 CH130M50 CH230M50
35 CH135M50 CH235M50
40 CH140M50 CH240M50
45 CH145M50 CH245M50
50 CH150M50 CH250M50
60 — CH260M50
70 — CH270M50
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole 120/240 Vac
Requires One 3/4-Inch (19.1 mm) Space
Two-Pole 120/240 Vac Common Trip
Requires Two 3/4-Inch (19.1 mm) Spaces
10 per Shelf Carton
Catalog Number
5 per Shelf Carton
Catalog Number
15 (1) #14–8
(2) #14–10
CH115HM CH215HM
20 CH120HM CH220HM
15 (1) #14–8
(2) #14–10
CHP115HM CHP215HM
20 CHP120HM CHP220HM
N
eut
r
a
l I
n
N
eut
r
a
l
Ou
t
(Hot le
g
)
N
eut
r
a
l I
n
N
eut
r
a
l
Ou
t
Ph
ase
Ph
ase
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 37
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Options and Accessories
Field Installation Kits and Parts
Notes
Must be purchased in multiples of ordering quantities indicated.
Handle ties: typically used to join two similar independent single-pole breakers to form a two-pole noncommon trip breaker.
Handle lockoffs: devices that use a padlock to lock the circuit breaker’s handle in the ON or OFF position.
Requires one additional pole space.
Escutcheon mounted: device mounted semipermanently to the face of the circuit breaker and secured by the loadcenter deadfront.
Screw mounted: device permanently mounted to the face of the circuit breaker by the use of a non-removable screw.
Handle lockdogs: devices that are used to secure a circuit breaker’s handle in the ON or OFF position. Handle lockdogs are not padlockable devices.
Handle mounted: device mounted above or below handle using spring pressure.
Hold-down kits: devices used to secure the circuit breaker to the loadcenter for back-feed main application. See NEC Article 384-16(g).
Description
Ordering
Quantity
Catalog
Number
Handle Ties
Handle tie bar for physically joining the handles of two adjacent single-pole Type CH circuit breakers (molded plastic handle cover) 25 CHHT
Handle Lockoffs 
Padlockable device for locking the handle of single-, two- or three-pole Type CH circuit breakers (escutcheon mounted) 1 CHPL
Padlockable device for locking the handle of a single-, two- or three-pole Type CHGFI circuit breaker (escutcheon mounted) 1CHPLGF
Padlockable device for locking the handle of main circuit breaker Types CC and CCH into the ON or OFF position.(screw mounted) 1CCPL
Padlockable device for locking the handle of main breaker Types BW and CSR into the ON or OFF position (escutcheon mounted) 1MCBPL
Handle Lockdogs 
Device used to secure handle in ON or OFF position for single-pole Type CH circuit breakers (handle mounted) 10 CHLO
Hold-Down Kits
Hold-down retainer kit for single-, two-, three-pole Type CH circuit breakers. For 6–24 circuit 125A single- and three-phase,
12–42 circuit single-phase 225A and 24–42 circuit three-phase 225A MLO Type CH loadcenters
1CH125RB
Hold-down retainer kit for single-, two-, three-pole Type CH circuit breakers for 2–4 circuit MLO CH loadcenters. 1 CH125RB24
Mounting Bases
Mounting base for two-pole Type CH circuit breaker—70A maximum 1 CH9MB270
Main Breaker Lug Kits
Types CC and CCH main breaker lug kit (2) 300 kcmil 1 CCL300
Type CSR main breaker lug kit (2) 300 kcmil 1MCBL300
Mechanical Interlock
Type CH for two-, three- and four-pole breakers 10 CHML
10 CHPLOFF
10 CHPLOFFA
10 CHL1P
10 CHL2P
CHHT
CHPL
C
HPLGF
MCBPL
CHLO
CH125RB
CH9MB270
C
HML
38 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Shunt Trip Options
Handle Position Changeability Chart
Notes
Add suffix indicated to end of breaker catalog number.
Requires one additional pole space.
Description Catalog Number
Suffix Adder
Type Volts
CSR 12 DC SR12
CSR 24 DC SR24
CSR 120 AC SR01
CH 120 AC ST
CC 12 DC SR12
CC 24 DC SR24
CC 120 AC SR01
CC 208 AC SR08
CC 240 AC SR02
Handle Lockoff and
Lockdog Types
To Change Handle Position from
ON to OFF or OFF to ON You Must...
Remove
Padlock
Remove
Device
Remove Loadcenter
Deadfront
Lockoff escutcheon mounted Remove
Lockoff screw mounted Remove
Lockdog handle mounted N/A Remove
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 39
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Technical Data and Specifications
Ratings
Single- and two-pole CH breakers rated 15 and 20A have
low instantaneous magnetic trip levels. The 15 and 20A
breakers with “HM” suffix have high magnetic trip settings
recommended for circuits with inherently high inrush currents.
All Type CH breakers are marked for heating, air conditioning
and refrigeration (HACR) equipment application. Single-pole
15–20A breakers are also suitable for switching duty (SWD).
Shunt trip coils operate on 120 Vac and require one additional
pole space per breaker.
Wiring Diagrams
Typical Single-Pole
Single-Pole 120V Load Application Sourced by 120/240 Vac
Two-Pole Shared Neutral with Multi-Duplex
Receptacle Application
Two-Pole 240V Load Application Sourced by 120/240 Vac
Two-Pole Shared Neutral with Duplex Receptacle Application
Single-Pole 120V Duplex
Receptacle Application
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
Equipment Ground
NA B
120/240 Vac
Source
Two 120V
Duplex
Receptacles
Two-Pole
Line B
Line A
Neutral
Neutral
Equipment Ground
Line B
NA B
120/240 Vac
Source
Line A 240V
Duplex
Receptacle
Two-Pole
Neutral
Equipment Ground
NAB
120/240 Vac
Source
Line A
120V Duplex
Receptacle
(With Line Side
Jumper Removed)
Two-Pole
Line B
Neutral
Neutral
Equipment Ground
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
Equipment Ground
40 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Two-Pole 120V Multi-Duplex Receptacle Application
Two-Pole 120V Duplex Receptacle Application
Two-Pole 240V Duplex Receptacle Application
NA B
120/240 Vac
Source
Two 120V
Duplex
Receptacles
Two-Pole
Line B
Line A
Neutral
Neutral
NAB
120/240 Vac
Source
Line A
120V Duplex
Receptacle
(With Line Side
Jumper Removed)
Two-Pole
Line B
Neutral
Neutral
Line B
NA B
120/240 Vac
Source
Line A 240V
Duplex
Receptacle
Two-Pole
Neutral
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 41
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Residential/Commercial/Unit Enclosure—Box Sizes
Note: Box sizes do not include covers/fronts.
Residential Loadcenters
Commercial Loadcenters
Types ECB and ECC Unit Enclosures
Residential Loadcenter Knockout
Residential NEMA Type 1 Indoor and NEMA Type 3R
Outdoor Enclosures.
Knockouts for Box Sizes 5, 6, 7, 5R, 6R, 7R
Knockout Positions
Box Size Height Width Depth
NEMA Type 1 Indoor
59.50 (241.3) 4.50 (114.3) 3.13 (79.4)
611.38 (288.9) 6.88 (174.6) 3.39 (86.1)
713.00 (330.2) 11.00 (279.4) 3.69 (93.7)
B16.75 (425.5) 14.31 (363.5) 3.88 (98.4)
C21.00 (533.4) 14.31 (363.5) 3.88 (98.4)
D29.13 (739.8) 14.31 (363.5) 3.88 (98.4)
E29.13 (739.8) 14.31 (363.5) 3.88 (98.4)
G34.13 (866.8) 14.31 (363.5) 3.88 (98.4)
J34.13 (866.8) 14.31 (363.5) 3.88 (98.4)
K37.00 (939.8) 14.31 (363.5) 3.88 (98.4)
L39.00 (990.6) 14.31 (363.5) 3.88 (98.4)
NEMA Type 3R Outdoor
5R 9.50 (241.3) 4.50 (114.3) 3.13 (79.4)
6R 11.75 (298.5) 6.50 (165.1) 4.50 (114.3)
7R 13.00 (330.2) 11.00 (279.4) 3.69 (93.7)
B16.75 (425.5) 14.31 (363.5) 5.19 (131.8)
C21.00 (533.4) 14.31 (363.5) 5.19 (131.8)
D29.13 (739.8) 14.31 (363.5) 5.19 (131.8)
E29.13 (739.8) 14.31 (363.5) 5.19 (131.8)
G34.13 (866.8) 14.31 (363.5) 5.19 (131.8)
J34.13 (866.8) 14.31 (363.5) 5.19 (131.8)
K37.00 (939.8) 14.31 (363.5) 5.19 (131.8)
L39.00 (990.6) 14.31 (363.5) 5.19 (131.8)
Box Size Height Width Depth
NEMA Type 1 Indoor
P54.38 (1381.1) 21.00 (533.4) 6.00 (152.4)
PM 62.63 (1590.7) 21.00 (533.4) 6.00 (152.4)
Height Width Depth
NEMA Type 1 Indoor
23.25 (590.6) 8.88 (225.4) 4.50 (114.3)
NEMA Type 3R Outdoor
23.69 (601.7) 9.31 (236.5) 5.44 (138.1)
Code Diameter
A0.50 (12.7)
B0.50 (12.7) 0.75 (19.1)
C0.50 (12.7) 0.75 (19.1) 1.00 (25.4)
D0.50 (12.7) 0.75 (19.1) 1.00 (25.4) 1.25 (31.8)
E0.75 (19.1) 1.00 (25.4) 1.25 (31.8)
F0.75 (19.1) 1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
G1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
H1.00 (25.4) 1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
I1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
Box 6R
Box 7 Box 7R
Box 5 Box 5R
Box 6
A
A
D D D
F
Hub
A
A
B
A
B
B
C
C
F F
F
F
A
B
F
F
H
A
B
A
B
H
F
B B
B
H
Hub
D D
A
A
AA
A
AAA
AAA AAA
B B B
AB B
B
B
B
B
C C
C
C
C
BC
G
G
G
G
G G
F
AAA AAA
AB B
BC
C
G
G G
F
Hub
A
A
A
A
A
A
D D D
D
F
F
42 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Loadcenters and Circuit Breakers
Type CH Loadcenters and Circuit Breakers
Approximate Dimensions in Inches (mm)
Residential and Commercial Loadcenter Knockout
Residential NEMA Type 1 indoor and NEMA Type 3R outdoor enclosures.
Knockouts for Box Sizes 8, 8R, P, PM, B, C, D, E, G, J, K, L
and Outdoor Boxes 12–42 Circuits
Knockout Diagram
Type ECB and ECC Unit Enclosure Knockout
NEMA Type 1—Indoor
NEMA Type 3R—Outdoor
Code Diameter
a0.75 (19.1) ————
b0.50 (12.7) 0.75 (19.1)
c0.50 (12.7) ————
d1.00 (25.4) 1.25 (31.8) 1.50 (38.1) 2.00 (50.8) 2.50 (63.5)
e1.25 (31.8) 1.50 (38.1) 2.00 (50.8) 2.50 (63.5)
f0.75 (19.1) 1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
g0.50 (12.7) 0.75 (19.1) 1.00 (25.4)
h1.50 (38.1) 2.00 (50.8) 2.50 (63.5)
i0.50 (12.7) 0.75 (19.1) 1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
j1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
k1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
m0.75 (19.1) 1.00 (25.4) 1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
n0.75 (19.1) 1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
p2.00 (50.8) 2.50 (63.5)
e
e
e
e
d
b
b
i
b
g
b
c
c
c
c
a
Fl
ush
T
rim
3
/4
c
h
b
b
e
g
b
b
c
c
c
g
e
b
e
g
b
b
c
c
c
g
e
e
e
e
e
gg
d
c
c
c
c
c
b
b
i
c
c
c
c
b
g
b
c
d
c
c
c
c
c
b
b
i
c
c
c
c
c
b
g
b
c
0.45 Dia.0.45 Dia.
0.45 Dia.0.45 Dia.
b
e
g
b
b
c
c
g
e
e
e
e
e
g
g
b
c
c
b
e
g
b
b
c
c
c
g
e
b
c
d
c
c
c
c
c
b
b
i
c
c
c
c
b
g
b
c
d
c
c
c
c
c
b
b
i
c
c
c
c
c
b
g
b
c
0.45 Dia.0.45 Dia.
Box P, PM
Outdoor Boxes
12–42 Circuits 225A Maximum
Box B Box C, D, E, G, J, K, L
0.45 Dia.0.45 Dia.
0.45 Dia.0.45 Dia.
Code Diameter in Inches
NEMA Type 1 Indoor (Flush and Surface Trims)
A0.50 (12.7) ————
B1.25 (31.8) 1.50 (38.1) 1.75 (44.5) 2.00 (50.8) 2.50 (63.5)
NEMA Type 3R Outdoor
A0.50 (12.7) ————
B1.25 (31.8) 1.50 (38.1) 1.75 (44.5) 2.00 (50.8) 2.50 (63.5)
B
B
B
B
A
A
A
A
B
B
B
B
B
B
A
A
B
B
H
UB
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 43
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers Contents
Description Page
Overview
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Features, Benefits and Functions . . . . . . . . . . . . . . . . . . 44
Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . 47
Catalog Number Selection. . . . . . . . . . . . . . . . . . . . . . . . 47
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Riser Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Type BR Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 67
Type BR Renovation Loadcenters . . . . . . . . . . . . . . . . . . . . 69
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Overview
Product Selection Guide
BR Loadcenters
Description
Service
Single-phase, three-wire, 120/240 Vac Three-phase, four-wire, 208Y/120 Vac
Three-phase, three-wire, 240 Vac delta
Short-Circuit Current Rating
10 kAIC: All single- and three-phase loadcenters 70–225A, 8 to 42 circuits
22 kAIC: All convertible loadcenters using 125A rated Type BRH main breakers or
selected factory installed 125A rated Type BRH main breaker
25 kAIC: All convertible and factory-installed single-phase loadcenters rated
150 and 200A using Type BWH main breakers
Main Breaker/Main Lug Loadcenters
Single-phase
Main breaker: 100, 125, 150, 200, 225, 400, 600A
Main lugs: 70, 125, 150, 200, 225, 400, 600A
Three-phase
Main breaker: 100, 125, 150, 200, 225, 400, 600A
Main lugs: 100, 125, 150, 200, 225, 400, 600A
Convertible Loadcenters
Main breaker: single-phase up to 200A and three-phase up to 225A Main lugs: single-phase up to 200A and three-phase up to 150A
Branch Breakers
Types BR, BRH and BRHH: 10–150A. single-, two- and three-pole; selected amperage
available in switching duty, HACR, shunt trip and high magnetic setting
Type GFCB: 15–60A
Types BJ and BJH: 125–225A; two- and three-pole
Type BD Twin: 10–50A; two of one-pole; take one 1-inch (25.4 mm) space
Type BQ and BQC Multibreaker: 15–30A. Two of two-pole or one two-pole and
two one-pole; takes two 1-inch (25.4 mm) spaces
Type BRW: 15–30A; two-pole water heater breakers
Type BRSN: 15–30A; two-pole switching neutral breakers
Type BR 15–100A; two-pole, 240 Vac delta breakers
BR-AFCI arc fault circuit interrupter
Enclosures
NEMA Type 1 indoor
NEMA Type 3R outdoor
NEMA 4X
Meets or exceeds UL requirements for indoor or outdoor applications
Loadcenter and Breaker Accessories
Branch circuit breaker:
Auxiliary components Hold-down kits Handle ties
Lockoffs Lockdogs
Complete line of ground bar kits 5, 10, 14 and 21 circuit, some with additional #2/0 lugs;
each terminal will accommodate: (3) #14–#10 Cu/Al or (1) #14–#4 Cu/Al
Main and sub-feed lugs 125, 150, 225A—two- and three-pole
Shunt trips
Surge protection:
Single-phase plug-on surge protector Single-phase bottle type surge protector
Three-phase bottle type surge protector Single-phase whole home surge protector
Universal rainproof conduit hubs
Group One: 3/4, 1, 1-1/4, 1-1/2, 2 inches (19.1, 25.4, 31.8, 38.1, 50.8 mm)
Group Two: 2, 2-1/2, 3 inches (50.8, 63.5, 76.2 mm)
Adapter plate
Bussing
Tin-plated aluminum as standard Limited copper bus panels available
44 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Product Description
Loadcenters are enclosures
specifically designed to
house the branch circuit
breakers and wiring required
to distribute power to
individual circuits. They
contain either a main breaker
when used at the service
entrance point or a main lug
when used as a sub-panel
to add circuits to existing
service. The main breaker
protects the main entire
panel and can be used as
a service disconnect. The
branch breakers protect the
wires leading to individual
electrical loads such as
fixtures and outlets.
Features, Benefits and Functions
Loadcenter Construction
Eaton’s Type BR loadcenters
have standard tin-plated
aluminum bus with a limited
availability of copper bus.
The sum of the handle
ratings connected to any stab
is limited to 150A maximum
on the 100 and 125A
loadcenters, and 200A on
loadcenters with 150A or
higher main bus. NEMA
Type 1 boxes or enclosures
are manufactured from
galvanized steel. Raintight
boxes are manufactured
from galvanized steel, then
finished using an electrostatic
powder coat, baked urethane
paint process.
Neutrals
Eaton’s Type BR loadcenters
feature three types of neutrals:
Insulated/Bondable Single/
Split Neutral
Panels are supplied with an
insulated neutral and a bonded
ground. For service entrance
applications, the insulated
neutral must be bonded
utilizing the bonding strap
supplied with the panel. When
used as a service entrance
panel, the bonded ground may
be used as a neutral and/or
ground, unused neutral holes
on either side may be used
for termination of equipment
grounds. For non-service
entrance (sub-panel)
applications, the panel may be
installed with bonding strap
not connected to the neutral
(the bonded ground must be
used as a ground only).
Insulated/Bondable
Single Neutral
Panels are supplied with a
single insulated neutral. For
service entrance applications,
all that is required to bond
the neutral is to loosen the
bonding screw and the
neutral screw directly beside
it, insert the bonding strap
into the neutral bar, and re-
tighten both connections. The
single neutral can be moved
by the contractor to the other
side of the panel, if desired.
When used as a service
entrance panel, unused
neutral connections may be
used for the termination of
equipment grounds. For non-
service entrance (sub-panel).
Insulated/Bondable
Split Neutral
Panels are supplied with twin
insulated neutrals with an
insulated cross strap. For
service entrance applications,
the neutral must be bonded
utilizing the bonding strap
supplied with the panel. For
non-service entrance (sub-
panel) applications, the panel
may be installed with bonding
strap not connected to the
neutral. Separate ground bars
must be used on non-service
entrance panels.
Grounds
In service entrance
applications where the
neutral is bonded, unused
neutral holes may be used
for terminating ground
conductors. In sub-feed
panels, the neutral must be
isolated (non-bonded), and
ground wires must be
terminated on a separate
ground bar.
The insulated/bondable
single/split neutral panels
have sufficient terminations
for both ground and neutral
conductors. The insulated/
bondable single split neutral
panels are supplied with a
separate factory-installed
ground bar if the catalog
number contains a “G.” If
not, a separate ground bar
should be installed. Insulated/
Bondable Single Neutral
panels are supplied without
a ground bar (unless
otherwise noted), and ground
bar kits if needed must be
purchased separately.
Neutral and Ground Terminals
The standard terminals on
grounds and neutrals are
rated to accept (3) #14–#10
Cu/Al or (1) #14–4, provided
the cables terminated are of
the same material. For larger
cables, add-on neutral lugs
may be ordered from the
accessories on Page 71.
Note: NEC allows only one
current carrying conductor
per hole on neutrals unless
otherwise noted.
Bottom Fed Loadcenters
For single-phase 225A and
below loadcenters that are
bottom fed, a standard panel
can be rotated 180 degrees
to allow straight-in wiring of
power cables to the main
terminals. Because the main
circuit breaker handle
operates horizontally, the
orientation of the main circuit
breaker handle is consistent
with the requirements of
NEC 2008 Article 240.81.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 45
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Gutter Splicing
Loadcenters are not UL listed
as wiring troughs. Therefore,
gutter splicing of riser cables
to tap off to the main device
is not permitted. Refer to
NEC 2008 Article 312.8.
Fire Rating
Due to the numerous
openings in both loadcenter
boxes and trims, they should
not be mounted in firewalls.
There is no approved method
for sealing the enclosures for
this application.
Date Code
The date of manufacture of
each loadcenter is printed on
the outside of the carton as
well as inside the loadcenter.
On the carton, the date code
is printed on the end carton
label. In the loadcenter, the
date code is located on the
small white label located on
the right side wall (with the
main device on top).
The date code is in the
following format: F # # # &.
The “F” is the numeric
code for the Lincoln, IL
plant, and the three numbers
are the year and week of
manufacturing, e.g., 023. The
“!” sign at the end signifies
the decade of the 2010.
Therefore, the date code
F023& would indicate
that the product was
manufactured in the 23rd
week of 2010. The 1980s
are represented by the “+”
sign and the 1990s are
represented by a “=”
at the end of the code.
Surge Protectors
Complete home surge
protection is available in
multiple options, including
a factory-installed option that
provides the highest level of
surge protection in a
residential design. See Tab 3
for more details.
Circuit Breaker Case
Interrupting Capacity
10 kAIC
22 kAIC
Warranty Information
10-year limited
loadcenter warranty
10-year limited branch
breaker warranty
46 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Type BR Loadcenter—BR4040B200
Six mounting holes (three top, three
bottom) for ease of installation.
Drywall marking on enclosure.
Tw i n neutral design for easier wiring
and balancing of the load, located in
wireway, away from circuit breakers.
Maximum wiring gutter
space for ease of wiring in
compliance with NEC requirements.
One piece roll formed metal
backpan with circuit breaker
alignment notches ensures
accurately aligned breaker
and bus stabs.
Maximum variety of concentric
knockouts, at rear and sides.
Predrilled mounting holes for
ease of installing ground bar kits.
Commercial grade 25 kAIC rated
main breaker in 150A and above
loadcenters designed for straight-in
wiring that allows for top or
bottom feed.
Same size Allen wrench can be used
for phase and neutral lugs.
Standard 14-3/8 inches (365.1 mm)
wide enclosures fit snugly between
wall studs.
Extra 1.50-inch (38.1 mm) knockout
for bundling of wires.
Combination trim has sliding latch
and adjustable deadfront for neat,
clean appearance.
Factory pre-attached neutral
bonding strap.
Ta ngential main knockout for easy installation.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 47
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Standards and Certifications
UL Listings
All Eaton Type BR
loadcenters are listed under
UL File E52977 except the
2–8 circuit loadcenters,
up through and including
125A, which are listed under
UL File E8741.
Catalog Number Selection
Single- and Three-Phase Through 225A
Note
No character space used.
3 BR 30 42 B C 200
Phase
Blank = Single-phase
3= Three-phase
Construction
Blank =No feed thru lugs
F= Feed-through lugs
G= Ground bar
P= Current design
NY =NY City gutter space
Number of 1-Inch
(25.4 mm) Spaces
Factory Options
SUR = Factory integrated surge
Eaton’s Type BR
Loadcenter
Maximum Number
of Circuits
Bus
Blank = Aluminum bus
C= Copper bus
Main Device
B= Main breaker
L= Main lug
N= Convertible main
H= Main breaker high AIC
Enclosure
R= NEMA Type 3R rainproof
S= NEMA Type 1 indoor with
surface trim
F= NEMA Type 1 indoor with
flush trim
Blank = NEMA Type 1 indoor with
combination trim
RIS = Riser panel
Amperes
50 = 50A
70 = 70A
100 = 100A
125 = 125A
150 = 150A
200 = 200A
225 = 225A
48 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single- and Three-Phase 400–600A
Example No. 1: BR1224L125G
Single-phase Type BR
loadcenter rated at 125A with
main lugs, 12 spaces allowing
24 poles, indoor combination
enclosure, aluminum bus and
ground bar.
Example No. 2: BR24L70RP
Single-phase Type BR
loadcenter rated at 70A
with main lugs, two spaces
allowing four poles, rainproof
enclosure with aluminum bus.
Example No. 3: 3B4242EFN
Three-phase Type BR
loadcenter rated at 600A
with main breaker, 42 spaces
allowing 42 poles, indoor
combination enclosure.
Product Selection
Single-Phase—Main Circuit Breaker Loadcenters—10/25 kAIC
Single-Phase, Three-Wire—120/240 Vac—Factory-Bonded Split Neutral
Notes
No character space used.
Combination style covers may be used in surface or flush applications.
All main circuit breaker loadcenters are listed for use as service entrance equipment. Loadcenters are factory-bonded for service entrance applications.
Remove bonding strap for separate neutral and ground bars for sub-feed applications.
3
B
30
4
2
D
F
N
Number of 1-Inch
(25.4 mm) Spaces
Phase
Blank = Single-phase
3= Three-phase
N = Current design
Main
Blank = Main lug
B= Main breaker
Maximum Number
of Circuits
Amperes
D= 400A
E= 600A
Enclosure
F=NEMA Type 1 indoor with
combination trim
S=NEMA Type 1 indoor with
surface trim
R1 = NEMA Type 3R rainproof
Main
Breaker Type
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter Catalog Number
with Combination Cover
Space Circuits
BR
10 kAIC
100 20 20 Indoor C2 #4–1/0 BR2020B100
100 16 24 Indoor C1 BR1624B100
BWH
25 kAIC
150 30 30 Indoor G1 #2–300 kcmil
#2–300 kcmil
BR3030B150
200 20 40 Indoor D1 BR2040B200
200 30 40 Indoor G1 BR3040B200
200 40 40 Indoor L1 BR4040B200
BR4040B200
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 49
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Notes
Combination style covers may be used in surface or flush applications.
Wire range size for BR1020B100SP is #6–#1 Cu/Al.
Includes through-feed lugs for both phase and neutral conductors.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
See copper bus offering, Page 58.
22 kAIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFCB 10 kAIC branch breakers are used in series with Type BRH main breaker.
25 kAIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFCB 10 kAIC branch circuit breakers are used in series with Type BWH main breaker.
Supplied with adapter plate to use DS Group1 hubs on Page 71. If 2.50-inch (63.5 mm) hub is needed, remove adapter and use ARP00007CH25 hub.
Neutral is bonded—suitable for service entrance only—cannot be converted for sub-feed application.
All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with neutral bonding strap preattached. The maximum rating of the
panel is the main circuit breaker rating when used as service entrance equipment. Ground bar kits priced separately. See Page 71.
Main
Breaker Type
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter Catalog Number
with Combination or
NEMA Type 3R CoverSpaces Circuits
BR
10 kAIC
100 8 16 Indoor B1 #4–1/0 BR816B100
10 20 Indoor A1 BR1020B100S11
10 20 Indoor A1 BR1020B100F11
10 20 Outdoor B2R BR1020B100RF 
12 12 Indoor B2 BR1212B100
12 20 Indoor B2 BR1220B100
12 24 Outdoor B2R BR1224B100R
16 16 Indoor C1 BR1616B100
16 20 Indoor C1 BR1620B100
16 24 Outdoor C1R BR1624B100R
20 24 Outdoor C3R BR2024B100R
30 30 Indoor  
125 16 24 Indoor C1 #4–2/0 BR1624B125
20 24 Indoor C1 BR2024B125
20 24 Outdoor C3R BR2024B125R
BRH
22 kAIC
100 20 24 Indoor C2 #2/0–300 kcmil BR2024H100
BWH
25 kAIC
150 8 16 Outdoor C3R #2–300 kcmil BR816B150RF 
16 30 Indoor C4 BR1630B150
20 30 Indoor C4 BR2030B150
20 30 Outdoor D1R BR2030B150R
20 40 Indoor D1 BR2040B150
20 40 Outdoor D1R BR2040B150R
24 30 Indoor G1 BR2430B150
30 30 Outdoor G1R BR3030B150R
30 40 Indoor G1 BR3040B150
200 4 8 Outdoor 8R #2–300 kcmil BR48B200RF 
816Outdoor C3R BR816B200RF 
16 32 Indoor C4 BR1632B200
20 40 Outdoor D1R BR2040B200R
24 40 Indoor G1 BR2440B200
30 40 Outdoor G1R BR3040B200R
40 40 Outdoor L1R BR4040B200R
225 42 42 Indoor L2 #1–250 kcmil BR4242B225
42 42 Outdoor L2R BR4242B225R
BR816B100
BR2030B150
50 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Main Circuit Breaker Loadcenters—10/22/25 kAIC
Main Circuit Breaker Loadcenters—With Copper Bus—Single-Phase Three-Wire—120/240 Vac—
Factory-Bonded Split Neutral
Main Circuit Breaker Loadcenters—10/22 kAIC
Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Notes
All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with neutral bonding strap preattached. The maximum rating of the
panel is the main circuit breaker rating when used as service entrance equipment.
Ground bar kits priced separately. See Page 71.
22 kAIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFCB 10 kAIC branch breakers are used in series with Type BRH main breaker.
Ground bar kits priced separately. See Page 71.
The maximum rating of the panel is the main circuit breaker rating when used as service entrance equipment.
Door lock and key included with loadcenter.
Type DK main circuit breaker is rated 65 kAIC at 240 Vac and allows a 22 kAIC series rating on the panel when Types BR, BD and BJ branch circuit breakers are used.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
Type HLD main circuit breaker is rated 65 kAIC at 240 Vac. Type HLD circuit breaker is not series rated with Types BR, BD and BJ branch circuit breakers.
Box sizes Pages 85 through 88.
Main
Breaker Type
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter Catalog Number
with Combination Cover 
Spaces Circuits
BR
10 kAIC
100 20 20 Indoor C2 #4–1/0 BR2020BC100
30 30 Indoor D1 #4–1/0 BR3030BC100
BRH
22 kAIC
100 30 30 Indoor D1 #4–1/0 BR3030HC100
BWH
25 kAIC
150 30 30 Indoor G1 #2–300 kcmil BR3030BC150
200 20 40 Indoor D1 #2–300 kcmil BR2040BC200
30 40 Indoor G1 #2–300 kcmil BR3040BC200
40 40 Indoor L1 #2–300 kcmil BR4040BC200
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
1-Inch (25.4 mm)
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Commercial Loadcenter
Catalog Number 
Spaces Circuits
With Flush or
NEMA Type 3R Cover
With
Surface Cover
DK 300 42 42 Indoor 24 (2) #3/0–250 kcmil BR304242F BR304242S
400 42 42 Indoor 24 (2) #3/0–250 kcmil B4242DFN B4242DSN
42 42 Outdoor 47 (2) #3/0–250 kcmil B4242DR1N
HLD 600 42 42 Indoor 24 (2) #3/0–500 kcmil B4242EFN B4242ESN
BR3030BC100
B4242DFN
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 51
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single-Phase—Main Lug Loadcenters
Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Notes
Ground bar kits priced separately. See Page 71.
– For 2/4 circuit loadcenters, use GBK5 or GBK520 ground bar.
– For 4/8, 6/12 and 8/16 circuit loadcenters, use GBK10 ground bar.
– Ground bars mount to the left side wall of the enclosure for the 4/8, 6/12 and 8/16 circuit loadcenters.
Suitable for use as service equipment when not more than two service disconnecting mains are provided or when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
Ground bar GBK5 is installed.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
CSA and UL approved.
Neutral/ground holes (6) #14–6 and (3) #14–2/0 AWG Cu/Al.
For use as service entrance applications only.
Neutral/ground holes (6) #14–6 and (3) #14–1/0 AWG Cu/Al.
Suitable for use as service equipment when not more than two service disconnecting mains are provided or when not more than six service disconnecting mains are provided
and when not used as a lighting and appliance panelboard (see Article 408.34 of the NEC).
Suitable for use as service equipment when a main breaker is used or when not more than six service disconnecting mains are provided and when not used
as a lighting and appliance panelboard (see Article 408.34 of the NEC).
Ground bar GBK10 is installed.
Ground bar GBK14 is installed.
Box sizes Pages 85 through 88.
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type Trim Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter
Catalog NumberSpaces Circuits
70 2 4 Indoor Surface (no door) 5 #8–#2 BR24L70SP 
24 Indoor Surface (no door) 5 BR24L70SGP 
24 Outdoor — 5R BR24L70RP 
24 Indoor Flush (no door) 5 BR24L70FP 
24 Indoor Flush (no door) 5 BR24L70FGP 
125 2 4 Indoor Surface (no door) 6 #14–1/0 BR24L125SP 
24 Outdoor — 6R BR24L125RP 
24 Outdoor — 6R BR24L125RSEP 
24 Outdoor — 6R BR24L125RSE2P 
24 Indoor Flush (no door) 6 BR24L125FP 
48 Indoor Surface (no door) 7 #14–1/0 BR48L125SP 
48 Indoor Surface (no door) 7 BR48L125SGP 
48 Outdoor — 7R BR48L125RP 
48 Indoor Flush (no door) 7 BR48L125FP 
48 Indoor Flush (with door) 7 BR48L125FDP 
48 Indoor Flush (no door) 7 BR48L125FGP 
612Indoor Surface (no door) 7 #14–#1 BR612L125SP
612Indoor Surface (no door) 7 BR612L125SGP 
612Indoor Surface (with door) 7 BR612L125SDP
612Indoor Surface (with door) 7 BR612L125SDGP 
612Outdoor — 7R BR612L125RP 
612Indoor Flush (no door) 7 BR612L125FP
612Indoor Flush (no door) 7 BR612L125FGP 
612Indoor Flush (with door) 7 BR612L125FDP
612Indoor Flush (with door) 7 BR612L125FDGP 
816Indoor Surface (no door) 7 #14–#1 BR816L125SP
816Indoor Surface (no door) 7 BR816L125SGP 
816Indoor Surface (with door) 7 BR816L125SDP
816Indoor Surface (with door) 7 BR816L125SDGP 
816Outdoor — 7R BR816L125RP 
816Indoor Flush (no door) 7 BR816L125FP
816Indoor Flush (no door) 7 BR816L125FGP 
816Indoor Flush (with door) 7 BR816L125FDP
816Indoor Flush (with door) 7 BR816L125FDGP 
Surface Outdoor
Flush Outdoor
Surface (No Door)
Flush (No Door)
Outdoor
52 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single-Phase—Main Lug Loadcenters
Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral, continued
Notes
Ground bar kits priced separately unless otherwise noted. See Page 71.
Has notch for BREQS125 hold-down kit.
Single, movable neutral is provided.
Combination cover style.
Suitable for use as service equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
Ground bars GBK5 and GBK520 installed.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
Ground bar GBK1220 installed.
Has notch for BRHDK125 hold-down kit.
Includes through-feed lugs for both phase and neutral conductors.
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter Catalog Number
with Combination or
NEMA Type 3R Cover
Spaces Circuits
125 12 12 Indoor B1 #6–2/0 BR1212L125 
12 24 Indoor B1 BR1224L125 
12 24 Indoor B1 BR1224L125G 
12 24 Indoor B1 BR1224L125DG 
12 24 Outdoor B1R BR1224L125R 
16 16 Indoor B2 BR1616L125 
16 24 Indoor B2 BR1624L125 
16 24 Indoor B2 BR1624L125G 
16 24 Outdoor B2R BR1624L125R 
20 20 Indoor C1 BR2020L125 
20 24 Indoor C1 BR2024L125 
20 24 Indoor C1 BR2024L125G 
20 24 Outdoor C1R BR2024L125R 
24 24 Indoor C2 BR2424L125 
24 24 Indoor C2 BR2424L125G 
150 16 30 Indoor C2 #1–300 kcmil BR1630L150 
20 30 Indoor C2 BR2030L150 
200 8 16 Outdoor B2R #1–300 kcmil BR816L200RF 
12 24 Indoor B2 BR1224L200 
12 24 Outdoor B2R BR1224L200R 
20 40 Indoor C2 BR2040L200 
20 40 Indoor C2 BR2040L200G 
20 40 Outdoor C3R BR2040L200R 
24 40 Indoor C4 BR2440L200 
30 40 Indoor D1 BR3040L200 
30 40 Indoor D1 BR3040L200G 
30 40 Outdoor D1R BR3040L200R 
40 40 Indoor G1 BR4040L200 
40 40 Indoor G1 BR4040L200G 
40 40 Outdoor G1R BR4040L200R 
225 42 42 Indoor L1 #1–300 kcmil BR4242L225
42 42 Outdoor L1R BR4242L225R
BR1224L125
BR1224L200
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 53
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single-Phase—Main Lug Loadcenters, Non-Metallic
Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Single-Phase Three-Wire—120/240 Vac—Single Neutral with Copper Bus
Notes
Suitable for use as service equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
This device has no main lugs. A Type BR or BD breaker is required to be backfed to supply power to branch breakers. This device is single-phase 120 Vac only.
With the use of three Type BR breakers there are two branch circuits available. With the use of three Type BD breakers there are five branch circuits available.
Includes GB4NM ground bar.
2460 RNM uses the non-metrical ACD enclosure. See ACD Section for dimensions.
Box sizes Pages 85 through 88.
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type Trim Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter
Catalog NumberSpaces Circuits
40  Indoor Flush (no door) 2 TT120FLGNM 
 Indoor Surface (no door) 2 TT120SLGNM 
60 2 4 Indoor Flush (no door) 2 #14–2 2460FNM
24 Indoor Surface (no door) 2 2460SNM
24 Indoor Flush (no door) 2 2460FGNM
24 Indoor Surface (no door) 2 2460SGNM
24 Outdoor — 2460RNM
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type Trim Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter
Catalog NumberSpaces Circuits
125 8 16 Indoor Surface (with door) 7 #14–1 BR816LC125SDP
816Indoor Flush (with door) 7 BR816LC125FDP
2460SNM
BR816LC125FDP
54 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single-Phase—Main Lug Loadcenters—400 and 600A
Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Three-Phase—Main Circuit Breaker Loadcenters—10 kAIC
Three-Phase Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Notes
Ground bar kits priced separately unless otherwise noted. See Page 71.
Has notch for BRHDK125 hold-down kit.
Ground bar GBK8 installed.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
Suitable for use as service equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with a neutral bonding strap pre-attached (commercial loadcenters
do not have a pre-attached bonding strip). The maximum main rating of the panel is the main circuit breaker rating when used as service entrance equipment.
Ground bar kits priced separately. See Page 71.
Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm)
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Commercial Loadcenter
Catalog Number 
Spaces Circuits
With Flush or NEMA
Type 3R Cover
With Surface
Cover
400 12 24 Indoor 19 (1) #4/0–750 kcmil
or
(2) #3/0–400 kcmil
1224DSN
12 24 Outdoor 42 1224DR1N 
24 42 Indoor 20 — 2442DSN
42 42 Indoor 22 4242DFN 4242DSN
42 42 Outdoor 46 4242DR1N
600 42 42 Indoor 22 (2) #2–500 kcmil — 4242ESN
Main
Breaker Type
Main
Ampere
Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter Catalog Number 
(With Combination or
NEMA Type 3R Cover)Spaces Circuits
BR
10 kAIC
100 12 24 Indoor C1 #4–1/0 3BR1224B100
12 24 Outdoor C1R 3BR1224B100R
CC
10 kAIC
150 30 42 Indoor L1 #1–3/0 3BR3042B150
30 42 Outdoor L1R 3BR3042B150R
200 30 42 Indoor L1 #1–250 kcmil 3BR3042B200
30 42 Outdoor L1R 3BR3042B200R
42 42 Indoor L2 3BR4242B200
42 42 Outdoor L2R 3BR4242B200R
225 42 42 Indoor L2 #1–300 kcmil 3BR4242B225
42 42 Outdoor L2R 3BR4242B225R
4242DFN
3BR4242B200
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 55
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Three-Phase—Main Circuit Breaker Loadcenters—22/65 kAIC
Three-Phase, Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Three-Phase—High Interrupting Rated Main Circuit Breaker Loadcenters—22/100 kAIC
Three-Phase Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Notes
All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with a neutral bonding strap pre-attached (commercial loadcenters
do not have a pre-attached bonding strip). The maximum main rating of the panel is the main circuit breaker rating when used as service entrance equipment.
Ground bar kits priced separately. See Page 71.
Door lock and key included with loadcenter.
Type DK main circuit breaker is rated 65 kAIC at 240 Vac and allows a 22 kAIC series rating on the loadcenter when Types BR, BD and BJ branch circuit breakers
are used.
Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
The LD main circuit breaker is rated 65 kAIC at 240 Vac. Type LD circuit breaker is not series rated with Types BR, BD and BJ branch circuit breakers.
All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with a neutral bonding strap pre-attached.
Ground bar kits priced separately.
22 kAIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFGB branch breakers are used with BRH main.
100 kAIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFGB branch breakers are used with CHH main.
Box sizes Pages 85 through 88.
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Commercial Loadcenter
Catalog Number 
Spaces Circuits With Combination or NEMA Type 3R Cover
DK
22 kAIC
400 42 42 Indoor 24 (2) #3/0–250 kcmil 3B4242DFN
42 42 Outdoor 47 3B4242DR1N
LD 600 42 42 Indoor 24 (2) #3/0–500 kcmil 3B4242EFN
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
Loadcenter
Catalog Number 
Spaces Poles with Combination Cover with Surface Cover
BRH
22 kAIC
100 12 24 Indoor C1 #4–1/0 3BR1224H100 3BR1224H100S
CHH
100 kAIC
150 30 42 Indoor L1 #1–250 kcmil 3BR3042H150 3BR3042H150S
CHH
100 kAIC
200 30 42 Indoor L1 #1–250 kcmil 3BR3042H200 3BR3042H200S
42 42 Indoor L2 3BR4242H200 3BR4242H200S
3BR4242H200
56 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Three-Phase—Main Lug Loadcenters
Three-Phase Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Three-Phase, Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Notes
Ground bar kits priced separately. See Page 71.
Surface cover only.
Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
Has notch for BREQS125 hold-down kit.
Suitable for use as service equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
Door lock and key included with loadcenter.
Box sizes Pages 85 through 88.
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Loadcenter Catalog Number
(With Combination or
NEMA Type 3R Cover)Spaces Circuits
100 3 3 Indoor 9 #14–1/0 3BR3L100S
33Outdoor 9R 3BR3L100R
125 12 24 Indoor C1 #6–2/0 3BR1224L125 
12 24 Outdoor C1R 3BR1224L125R 
150 24 42 Indoor D1 #1–300 kcmil 3BR2442L150
24 42 Outdoor D1R 3BR2442L150R
200 12 24 Indoor C4 #1–300 kcmil 3BR1224L200
12 24 Outdoor C3R 3BR1224L200R 
30 42 Indoor G1 3BR3042L200
30 42 Outdoor G1R 3BR3042L200R
42 42 Indoor L1 3BR4242L200
42 42 Outdoor L1R 3BR4242L200R
225 42 42 Indoor L1 #1–300 kcmil 3BR4242L225
42 42 Outdoor L1R 3BR4242L225R
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm)
Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Commercial Loadcenter
Catalog Number
Spaces Circuits
With Flush or
NEMA Type 3R Cover
With
Surface Cover
400 18 36 Indoor 19 (1) 250–750 kcmil
or
(2) #3/0–250 kcmil
——
18 36 Outdoor 43 ——
24 42 Indoor 19 ——
42 42 Indoor 22 34242DFN 34242DSN
42 42 Outdoor 46 34242DR1N
600 42 42 Indoor 22 (2) #2–500 kcmil — 34242ESN
3BR1224L125
34242DFN
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 57
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Convertible Loadcenters MCB or MLO—Base Units and Main Devices 10/22/25 kAIC,
Complete Assembly Consists of: Loadcenter and Either Main Breaker Kit or Main Lug Kit
Note: Interrupting rating depends on main circuit breaker selected.
Base Units—Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Notes
The maximum rating of the loadcenter is the main circuit breaker rating when used as service entrance equipment.
100, 125 and 200A convertible base unit catalog numbers include interior, box and cover only. Main devices and accessories must be ordered separately for field
installation. All convertible base units are listed as suitable for use as service entrance equipment when used per Article 384 of the NEC.
Ground bar kits priced separately except as noted, refer to Page 71.
For main breaker, use Type BR. For main lug use Type BRSF.
BREQS125 hold-down screw comes with loadcenter for back-fed Types BR and BRH main circuit breakers.
Convertible to maximum of 100A main circuit breaker and 125A main lug.
Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
For main breaker, use Type BW or BWH. For main lug, use Type BRL.
Includes through-feed lugs for both phase and neutral conductors.
No hold-down provisions for back-fed Types BR and BRH main circuit breakers.
Includes GBK2120 ground bar.
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main
Loadcenter Catalog Number
With Combination or NEMA
Type 3R Cover 
Spaces Circuits
125 12 24 Indoor B2 See main breaker and
main lug kit tables
Page 59.
BR1224N125 
12 24 Outdoor B2R BR1224N125R 
16 24 Indoor C1 BR1624N125
16 24 Outdoor C1R BR1624N125R 
20 24 Indoor C2 BR2024N125
20 24 Outdoor C3R BR2024N125R 
200 816Outdoor C3R BR816N200RF 
12 24 Indoor C4 BR1224N200
12 24 Outdoor C3R BR1224N200R
16 32 Indoor C4 BR1632N200
20 40 Indoor D1 BR2040N200
20 40 Indoor D1 BR2040N200G
20 40 Outdoor D1R BR2040N200R
20 40 Outdoor D1R BR2040N200RG
24 40 Indoor G1 BR2440N200
30 40 Indoor G1 BR3040N200
30 40 Indoor G1 BR3040N200G
30 40 Outdoor G1R BR3040N200R
30 40 Outdoor G1R BR3040N200RG
40 40 Indoor L1 BR4040N200
40 40 Indoor L1 BR4040N200G
40 40 Outdoor L1R BR4040N200R
40 40 Outdoor L1R BR4040N200RG
BR3040N200
58 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Base Units—Three-Phase Four-Wire—208Y/120 Vac or 240 Vac Insulated/Bondable Neutral
Convertible Loadcenters—With Copper Bus 10/22/25 kAIC
Convertible—Single-Phase Three-Wire—120/240 Vac—Insulated/Bondable Neutral
Notes
The maximum rating of the loadcenter is the main circuit breaker rating when used as service entrance equipment.
100, 125 and 200A convertible base unit catalog numbers include interior, box and cover only. Main devices and accessories must be ordered separately for field installation. All
convertible base units are listed as suitable for use as service entrance equipment when used per Article 384 of the NEC.
Ground bar kits priced separately, refer to Page 71.
For main breaker, use Type BR. For main lug, use Type BRSF.
BREQS125 hold-down screw comes with loadcenter for back-fed Types BR and BRH main circuit breakers.
Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
Convertible to maximum of 100A main circuit breaker and 125A main lug.
Suitable for use as service equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard
(see Article 408.34 of the NEC).
All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with a neutral bonding strap preattached. The maximum main
rating of the loadcenter is the main breaker rating when used as service entrance equipment.
Interrupting rating depends on main circuit breaker selected. See Page 71 for mains.
For main breaker, use Type BW or BWH. For main lug, use Type BRL.
Hold-down screw BREQS125 comes with loadcenter for back-fed Types BR and BRH main circuit breakers.
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main
Loadcenter Catalog Number 
(With Combination or
NEMA Type 3R Cover)Spaces Circuits
100 30 30 Indoor D1 See main breaker and
main lug kit tables
next page.
3BR3030N100
30 30 Outdoor D1R 3BR3030N100R 
125 12 24 Indoor C1 3BR1224N125 
12 24 Outdoor C1R 3BR1224N125R 
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main
Loadcenter Catalog Number
with Combination or
NEMA Type 3R Cover 
Spaces Circuits
125
10/22 kAIC 
12 24 Indoor B2 See main breaker
and main lug kit tables
on Page 59.
BR1224NC125
12 24 Outdoor B2R BR1224NC125R 
20 24 Indoor C2 BR2024NC125
20 24 Outdoor C3R BR2024NC125R
200
10/25 kAIC
20 40 Indoor D1 BR2040NC200
20 40 Outdoor D1R BR2040NC200R
30 40 Indoor G1 BR3040NC200
30 40 Outdoor G1R BR3040NC200R
40 40 Indoor L1 BR4040NC200
40 40 Outdoor L1R BR4040NC200R
3BR3030N100
BR3040NC200
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 59
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Convertible Loadcenters MCB or MLO—Base Units and Main Devices 10/22/25 kAIC,
Complete Assembly Consists of: Loadcenter and Either Main Breaker Kit or Main Lug Kit
Note: Interrupting rating depends on main circuit breaker selected.
Main Devices—Two- and Three-Pole
Main Circuit Breakers—120/240 Vac or
208Y/120 Vac or 240 Vac
Main Devices—Two- and Three-Pole
Main Lug Kits—120/240 Vac or
208Y/120 Vac or 240 Vac
Main Circuit Breaker with Accessory
Example: BW22005R01 (Put description with catalog number on
order. See Page 83.)
Spa Panels
Spa Panel—Meets NEC Article 680.40 Through 680.43—Requirements for GFCI Protection
Notes
Series combination rating with Types BD, BR, BQ, BQC and GFCB is 22 kAIC with BRH main and 25 kAIC with BWH main.
Includes a GFCB240 breaker, factory installed.
Includes a GFCB250 breaker, factory installed.
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
for Main Breaker
10 kAIC 22/25 kAIC
Catalog
Number
Catalog
Number
Two-Pole
100 #4–1/0 BR2100 BRH2100
110 #4–1/0 BR2110 BRH2110
125 #4–2/0 BR2125 BRH2125
125 #2–300 kcmil BW2125 BWH2125
150 #2–300 kcmil BW2150 BWH2150
175 #2–300 kcmil BW2175 BWH2175
200 #2–300 kcmil BW2200 BWH2200
Three-Pole
100 #1 BR3100 BRH3100
BW2200
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Catalog
Number
Two-Pole
125 #6–2/0 BRSF125
150 #1–300 kcmil BRL200
175 #1–300 kcmil BRL200
200 #1–300 kcmil BRL200
Three-Pole
150 #6–3/0 3BRSF150
BRL200
Main
Ampere Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range Cu/Al 60°C
or 75°C for Main Lugs
Catalog
NumberSpace Poles
40 Outdoor 5R #8–#2 BR40SPA
50 Outdoor 5R #8–#2 BR50SPA
60 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single-Phase and Three-Phase Circuit Breaker Unit Enclosures—10/25 kAIC
Type ECB Circuit Breaker Unit Enclosure—Order Type BW and BWH Circuit Breaker Separately—
Unit Enclosure Includes Lug Tree Kit
Types BW and BWH Circuit Breakers
120/240 Vac—25 kAIC for Use in
Type ECB Unit Enclosures
BW/BWH Lug Tree Kit for Replacement
Purposes Only for Use in Type ECB
Unit Enclosures
Shunt Trips, Auxiliary and Alarm Contacts
Wire/Application Chart
Notes
Wire size is determined by the circuit breaker installed in enclosure. Maximum wire size and
ampere rating is determined by Wire/Application Chart.
Order circuit breaker separately.
One ground lug accepting (1) #14–#2 is factory installed. Also, there are pre-drilled holes to
accept a GBK5 ground bar.
Approved for service entrance.
Rainproof panels are furnished with hub closure plates. For rainproof hubs, refer to Page 71.
Add suffix indicated to end of breaker catalog number.
Box sizes Pages 85 through 88.
Main
Ampere Rating
Unit Enclosure
Type
Mounting
Type
Circuit Breaker
Type
Wire Size Range
Cu/Al 60°C or 75°C
Catalog
Number
Single-Phase Three-Wire—240 Vac Maximum
225 Indoor Flush BW, BWH ECB225F 
225 Indoor Surface BW, BWH ECB225S 
225 Outdoor BW, BWH ECB225R 
Circuit Breaker Unit
Enclosures
Ampere
Rating
Two-Pole
Breakers Wire Size Range
Cu/Al 60°C or 75°C
for Line Terminals
Two-Pole
Breakers
10 kAIC 25 kAIC
125 BW2125 #2–300 kcmil BWH2125
150 BW2150 BWH2150
175 BW2175 BWH2175
200 BW2200 BWH2200
225 BW2225 BWH2225
Ampere
Rating Description
Wire Size
Range Cu/Al
60°C or 75°C
for Line
Terminals
Catalog
Number
225 For use on
125, 150, 175, 200
and 225A BW and
BWH breakers
#2–300 kcmil MCBK225
Description
Catalog Number
Suffix Adder
Shunt Trip for Types BW/BWH
12V SR12
24V SR24
120V SR01
Auxiliary Contact for Types BW/BWH
1NO and 1NC AL1
2NO and 2NC AL2
Alarm Contacts for Types BW/BWH
Types BW/BWH CR1
Alarm Contacts for Type GFCB (Single-Pole)
Alarm contact for GFCB (single-pole) W1
1NO and 1NC W2
BWH2200
Wire/Application
Maximum
Wire Size
Maximum
Ampere Rating
Aluminum—standard 250 kcmil 200
Aluminum—service entrance 250 kcmil 225
Copper—standard and service entrance 250 kcmil 225
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 61
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Single-Phase and Three-Phase Circuit Breaker Unit Enclosures—10/25 kAIC
Type ECC Circuit Breaker Unit Enclosure—Order Type CC Circuit Breaker Separately
Type CC and CCV Circuit Breaker
240 Vac—10 kAIC for Use in Type ECC Unit
Enclosures
Shunt Trips and Auxiliary Contacts
Wire/Application Chart
Notes
Order circuit breaker separately.
One ground lug accepting (1) #14–#2 is factory installed. Also, there are pre-drilled holes to
accept a GBK5 ground bar.
Approved for service entrance.
Rainproof panels are furnished with hub closures plates. For rainproof hubs, refer to
Page 71.
Wire size is determined by the circuit breaker installed in enclosure. Maximum wire size and
ampere rating is determined by the Wire/Application Chart.
CCV breakers are two-pole only.
Add suffix indicated to end of breaker catalog number.
Box sizes Pages 85 through 88.
Main Ampere
Rating
Unit Enclosure
Type
Mounting
Type
Circuit
Breaker Type
Wire Size Range
Cu/Al 60°C or 75°C
Catalog
Number
Single- and Three-Phase—240 Vac Maximum
225 Indoor Flush CC/CCV ECC225F 
225 Indoor Surface CC/CCV ECC225S 
225 Outdoor — CC/CCV ECC225R 
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
for Line Terminals
Type CCV and
CC 10 kAIC
Catalog Number
Two-Pole
100 #4–4/0 CCV2100
125 CCV2125
150 CCV2150
175 #2/0–300 kcmil CCV2175
200 CCV2200
225 CCV2225
Three-Pole
100 #4–4/0 CC3100
125 CC3125
150 CC3150
175 #2/0–300 kcmil CC3175
200 CC3200
225 CC3225
Description Catalog Number
Suffix Adder
Type Volts
Shunt Trip
CC 12 DC SR12
CC 24 DC SR24
CC 120 AC SR01
CC 208 AC SR08
CC 240 AC SR02
CCV 48–127 AC/48–60 DC SR01
CCV 9–24 AC/12–24 DC SR24
Auxiliary Contact
CC 1NO and 1NC AL1
CCV2200
Wire/Application
Maximum
Wire Size
Maximum
Ampere Rating
Aluminum—standard 250 kcmil 200
Aluminum—service entrance 250 kcmil 225
Copper—standard and service entrance 250 kcmil 225
62 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Commercial Loadcenters—Indoor Enclosures
Main Circuit Breaker, Main Lug and Convertible, New York City Approved
Single-Phase and Three-Phase
Single-Phase Main Circuit Breaker—Factory Installed
Single-Phase Main Lugs—Factory Installed
Three-Phase Convertible Loadcenters
Three-Phase Main Breaker Kits
Three-Phase Main Lugs Kit
Note
Approved for 150A and up for residential services in New York City.
Main
Breaker
Type
Main
Ampere
Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or
75°C for Main Breaker
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Spaces Circuits Flush Surface
Single-Phase Three-Wire—120/240 Vac Insulated/Bondable Neutral
CC 10 kAIC 200 42 42 Indoor A #1–300 kcmil BR4242B200NY 3BR42FTNY 3BR42STNY
Main Lug
Ampere
Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or
75°C for Main Lugs
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Spaces Circuits Flush Surface
Single-Phase Three-Wire—120/240 Vac Insulated/Bondable Neutral
225 42 42 Indoor A #1–300 kcmil BR4242L225NY 3BR42FTNY 3BR42STNY
Main
Ampere
Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or
75°C for Main Breaker
Loadcenter
Catalog Number
Loadcenter Cover
Catalog Number
Spaces Circuits Flush Surface
Three-Phase Four-Wire—120/240 Vac Insulated/Bondable Neutral
225 42 42 Indoor B #1–300 kcmil 3BR4242N225NY 3BR42FTNY 3BR42STNY
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Main Breaker Kit
10 kAIC
150 #4–4/0
#2/0–300 kcmil
CC3150N
175 CC3175N
200 CC3200N
225 CC3225N
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Main
Lugs Kit
225 #2/0–300 kcmil 3BRL225
BR4242B200NY
W
ith 3BR42FTNY
Cover Installed
BR4242L225NY
W
ith 3BR42FTNY
Cover Installed
3BR4242N225NY
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 63
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Technical Data and Specifications
General
A. The Contractor shall
furnish and install
deadfront loadcenters
incorporating circuit
breakers of the number,
rating and type as
specified herein and
as shown on the
contract drawings.
B. The loadcenter and all
components shall be
designed, manufactured
and tested in accordance
with the latest applicable
standards of UL, NEMA
and NEC including:
1. UL 67—Standards
for Panelboards.
2. UL 50—Standards for
Cabinets and Boxes.
3. UL 489—Standards for
Molded Case Circuit
Breakers.
4. UL 869—Standards for
Service Equipment.
5. Federal Specification W-
C 375B—Circuit
Breakers.
6. Federal Specification W-
C P115b—Panel
Power Distribution
Type 1, Class 2.
Qualifications
A. The manufacturer of the
loadcenter shall be the
manufacturer of the
circuit breaker within
the loadcenter.
B. For the equipment
specified herein, the
manufacturer shall be
ISO 9000 certified.
C. The manufacturer of
this equipment shall
have produced similar
electrical equipment
for a minimum period
of seven (7) years.
Manufacturers
A. Eaton.
Ratings
A. Loadcenters shall be
rated for 120/240 Vac
and shall have short-
circuit ratings as shown
on the drawings or
as herein scheduled,
but not less than
10,000 amperes rms
symmetrical.
B. Circuit breakers shall be
a minimum of 125A
frame. Circuit breakers
15 through 125A trip size
shall take up the same
pole spacing.
C. Loadcenters shall be
labeled with a UL short-
circuit rating. When
series combination
ratings are applied
with integral or remote
upstream devices, a label
shall be provided. Series
combination ratings shall
cover all trip ratings of
installed frames. It shall
state the conditions of
the UL series ratings
including:
1. Size and type of
upstream device.
2. Branch devices that can
be used.
3. UL series short
circuit rating.
Construction
A. All interiors, with the
exception of the branch
circuit breakers, shall
be completely factory
assembled with main
breakers, main lugs,
or no main device.
B. Interiors shall be
designed so that circuit
breakers can be replaced
without disturbing
adjacent units and
without removing the
main bus connectors and
shall be designed so that
circuits may be changed
without machining,
drilling, or tapping.
C. Physical means shall be
provided to prevent the
installation of more
overcurrent devices than
that number for which
the enclosure was
designed, rated and
approved. Half-size
breakers shall have a
UL listed rejection tab
over the line terminals.
Loadcenter interiors
must have notched stabs
to accept these rejection
tab class CTL breakers, if
required and approved.
Bus
A. Bus bars for the main and
cross connectors shall be
[tin-plated aluminum]
[copper] in accordance
with Underwriters
Laboratories standards.
Busing shall be braced
throughout to conform to
industry standard practice
governing short-circuit
stresses in loadcenters.
Note: Note to spec writer—
select one (copper available
in limited ratings).
B. Neutral busing shall
have a suitable lug for
each outgoing feeder
requiring a neutral
connection of same
ampacity as branch.
Wiring/Termination
A. All wire connectors and
terminals shall be of the
anti-turn solderless type
and shall be suitable for
copper or aluminum wire
of the sizes indicated. All
connectors must meet
the “Requirements for
Wire Connectors and
Soldering Lugs” as
stated in UL 486B.
B. All loadcenters where
marked shall be suitable
for use with 60°C or
75°C rated wire.
Circuit Breakers
A. Circuit breakers shall
be molded case type.
Circuit breakers shall
have four-rivet
construction (GFI Type—
5 rivets). Multipole circuit
breakers shall be of a
stack pole design to
provide electrical
phase isolation.
B. Each pole of the
circuit breaker will
provide inverse time
delay overload and
instantaneous short-
circuit protection by
means of both thermal
and magnetic sensors.
C. The circuit breaker
calibration shall
not be affected by
environmental changes
in relative humidity.
The thermal bimetal
element shall be welded
to the steel frame and
calibration shall be set
independent of the
molded case by
computer controlled
equipment.
D. All circuit breakers
shall be operated by
a toggle-type handle
and multipole circuit
breakers shall have an
internal common trip
mechanism. The
circuit breakers shall
incorporate trip
mechanisms that are
mechanically trip-free
from the handle. The
handle position shall
provide visual trip
indication.
E. Contacts shall be of
non-welding silver alloy.
F. All circuit breakers shall
have the trip rating
inscribed on the handle
on each circuit breaker
pole. Also, unique color-
coded cases that indicate
the UL listed 10 kA or
22 kA interrupting
ratings. Breakers shall
be able to be used
as main or branch
disconnect devices.
64 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
G. Branch circuit breakers
may also be used in
the 1/2-inch (12.7 mm)
per pole ratings that
include two-pole 1-inch
(25.4 mm) wide modules
and four-pole 2-inch
(50.8 mm) wide
modules. Two-pole
circuit breakers must
incorporate a common
trip mechanism. The
exclusive CTL rejection
tab feature shall be
provided to limit the
number of branch
devices for a loadcenter
to 42, in compliance with
NEC Article 384-15.
H. Circuit breakers shall
be completely enclosed
in a molded case of
thermoset material.
No internal aluminum
parts shall be used. All
internal ferrous parts
shall be plated to
prevent corrosion.
I. All terminals shall be
listed for use with copper
or aluminum conductors.
Terminals shall be of the
box lug or clamp type
design. The terminals
shall meet UL 486B
requirements and shall
be suitable for use with
either 60°C or 75°C wire.
J. The calibrated bimetal
assembly shall be
mechanically isolated
from the load terminal
using a flexible braided
copper shunt wire, such
that movement of the
terminals due to twisting
and overtorquing does
not affect breaker
calibration.
K. Breakers shall be SWD
rated and/or HACR rated
as required.
L. Arc Fault Interrupting
circuit breakers, (AFI),
shall be provided on all
15 and 20A single-phase
120/240 Vac circuits
except those indicated
as remote controlled
breakers. AFI breakers
shall be “Classified for
mitigating the effects of
arcing faults,” or
conforming to UL
Standard 1699 and as
defined by Article 210-12
Section A of the 1999
NEC Code.
Surge Protection Devices
See Section 4 of the
Distribution Products Catalog
for complete details on
surge protection.
Enclosures
A. Loadcenter shall have
NEMA Type 1 general
purpose or NEMA Type
3R rainproof enclosures
as indicated on the
drawings and shall be
surface or combination
flush/surface mounted
except where noted.
B. Boxes shall be made
from galvanized sheet
steel having multiple
knockouts. Rainproof
boxes shall use
galvanized steel or
an approved coating
system which meets or
exceeds standards for
outdoor NEMA Type 3R
enclosures. Boxes shall
be of sufficient size to
provide at least a
minimum code gutter
space on all sides.
C. The deadfront shall
have an easy adjustment
feature for flush
applications.
D. Boxes shall be factory
assembled into a single
rigid structure.
E. Unless otherwise noted
on drawings, hinged
doors covering all circuit
breaker handles shall
be included in all trims.
Trim doors shall not
uncover any live parts
in making the circuit
breaker handles
accessible. If key locks
are required, all locks
shall be keyed alike.
F. Combination trims for
flush and surface panels
shall be flat and shall
overlap the box by at
least 5/8-inch (15.9 mm)
all around. Trims shall
be mounted by a
screwdriver without the
need for special tools.
Finish
A. Trims shall be bonderized
and finished with a light
gray ANSI-61 enamel.
The paint finish shall be
of a type to which field
applied paint will adhere.
Factory Testing
A. The standard factory
tests shall be performed
on the equipment
provided under this
section. All tests shall
be in accordance with
the latest version of UL
and NEMA.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 65
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Riser Panel Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Riser Panel
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Type BR Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 67
Type BR Renovation Loadcenters . . . . . . . . . . . . . . . . . . . . 69
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Riser Panel
Product Description
Eaton’s Riser Panel is a
loadcenter with an offset
interior to allow riser cables
to pass through the enlarged
gutter. By using lay-in tap
lugs, the contractor is able to
simply strip off a length of the
riser cable’s insulation, and
tap off to the riser panel’s
main lugs. These panels are
used in the construction of
assisted living homes,
dormitories, public housing
complexes and apartments.
Eaton offers three 125A
and one 200A main lug riser
panels, a 12/24 and a 20/24,
20/30 and 30/40. The panels
are convertible to main
breaker by adding the
appropriate breaker and a
BREQS125 hold-down kit.
Additionally, the 12/24 is
offered in a bulk-packed
version. The bulk-packed
product must be ordered in
multiples of 16, and consists
of a pallet with uncartoned
loadcenters on the bottom,
and cartoned trims on top.
The entire pallet is shrink-
wrapped for protection. By
supplying the loadcenter
without a carton, the
contractor is able to save
the unpacking time as well as
saving on the scrap cardboard
on the site.
For applications higher than
125A, or the circuits provided
by the panels above, we
offer the BRGUTTER. This
is essentially a junction box
that mounts next to, and
assembles to standard BR
or CH loadcenters. There
is a matching concentric
knockout that allows the
tapped cables to pass
through from the BRGUTTER
to the loadcenter. The trims
of the loadcenter and the
BRGUTTER are designed
to allow the two boxes to
bolt to one another in a flush
application. There is no
need to allow for the trim
overhang.
Also offered is the GTAP250,
which is a set of three
lay-in, insulated tap lugs.
The maximum wire size for
the GTAP250 is 250 kcmil.
GTAP250 can be used with
either the riser panels or the
BRGUTTER.
66 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Product Selection
Riser Panel
Accessories
For riser panels not shown, contact the Flex Center at
1-800-330-6479 for both CH and BR riser panels.
Riser Panel Accessories
Notes
Bulk-packaged loadcenter without carton. Must be ordered in
multiples of 16.
Refer to Page 85 for dimensions. BRGUTTER is box size C2.
Main Ampere
Rating
Maximum Number
1-Inch (25.4 mm) Enclosure
Type
Box
Size
Wire Size Range
Cu/Al 60°C or 75°C
for Main Lugs
Catalog
NumberSpace Circuits
125 12 24 Indoor C4 #6–2/0 BR1224L125RIS
125 12 24 Indoor C4 #6–2/0 BR1224L125RISBP
125 20 24 Indoor C4 #6–2/0 BR2024L125RIS
125 20 24 Indoor C4 #6–2/0 BR2024L125RISBP
125 20 30 Indoor C2 #6–2/0 BR2030L125RIS
200 30 40 Indoor D1 #1–300 BR3040L200RIS
BR1224L125RIS
Catalog Number
BRGUTTER
GTAP250
BRGUTTER (Shown
with Loadcenter)
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 67
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
BRRETRO Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Riser Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Type BR Retrofit Interior Kits
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Type BR Renovation Loadcenters . . . . . . . . . . . . . . . . . . . . 69
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Type BR Retrofit Interior Kits
Product Description
Replacing existing
loadcenters and panelboards
can be a time consuming and
expensive job. BR retrofit kits
can be the solution to save
time and money. The kit
consists of a standard trim to
fit the interior, a picture frame
trim to fit the existing box,
and a field adjustable interior
assembly that includes
neutral and ground bars as
well. These are especially
applicable when the existing
box is flush mounted in
drywall, plaster or block wall.
The existing box, and many
times existing wiring, can
remain. Interiors are UL
recognized under UL 67,
Panelboard standard.
Quick-ProSM
All you need to
know to save
time and make
more money.
Specified on certain Eaton
products, the Quick-Pro
symbol allows for immediate
recognition of products
that are designed for
straightforward installation.
When you see Quick-Pro,
you know you can install
quickly—sometimes up to
50% less than the usual
installation time—and move
onto your next job.
Features
Detailed Product Guide
All standard retrofit kits are
suitable for a range of
existing box sizes:
Box width ranging from
14.50 to 22.00 inches
(368.3 to 558.8 mm)
Box depth ranging from
4.00 inches (101.6 mm)
for BR
Box height ranging from
21.00 to 45.00 inches
(533.4 to 1143.0 mm)
For box dimensions outside
of these ranges, contact
the Lincoln Flex Center at
800-330-6479. Be sure to
provide the existing incoming
line wire size.
Product Selection
To select the retrofit kit:
1. From the existing box
size determine which
retrofit groups are
suitable (may be more
than one).
2. Use type of interior,
number of phases, and
type of main to find the
selection chart.
3. Select part number from
chart (if main breaker,
replace XXX with specific
amp rating).
4. Note that the overlap of
the existing wall is the
retro cover size minus
the existing box size. If
specific measurements
are needed, communicate
that you need a custom
trim size.
5. Contact the Lincoln Flex
Center at 800-330-6479
for pricing, lead-times,
and order entry
instructions.
Retro Size Groups
Existing Box Height Determines Retro Size Group
21" 29" 30" 34" 36" 37" 41" 45" 54"
Retro Size A
Retro Size B
Retro Size C
Retro Size D
Retro Size E
68 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Type BR Interior—With Main Breaker
Type BR Interior—Main Lug Only
Notes
Specific cover sizes are available. Be sure to specify the custom cover option and provide exact dimensions required.
XXX is for Main Breaker specific ampere rating.
Main Breaker Rating Existing Box Height Wire
Size
Number
of Circuits
Part
Number
Retro
Size Group
Retro Cover Size
Amperes kAIC Minimum Maximum Height Width
Single-Phase
60–125 10 21.00 (533.4) 30.00 (762.0) #4–2/0 20 RABR20BXXX A33.00 (838.2) 24.00 (609.6)
22 #4–2/0 RABR20HXXX
60–125 10 29.00 (736.6) 36.00 (914.4) #4–1/0 30 RBBR30BCXXX B40.00 (1016.0) 24.00 (609.6)
22 #4–1/0 RBBR30HCXXX
100–200 25 29.00 (736.6)
31.00 (787.4)
30.50 (774.7)
36.00 (914.4)
#2–250 kcmil
#2–300 kcmil
20 RBBR20HXXX
100–225 25 34.00 (863.6)
36.00 (914.4)
35.50 (901.7)
41.00 (1041.4)
#2–250 kcmil
#2–300 kcmil
30 RCBR30HXXX C43.00 (1092.2) 24.00 (609.6)
100–225 25 37.00 (939.8)
39.00 (990.6)
41.00 (1041.4)
38.50 (977.9)
40.50 (1028.7)
45.00 (1143.0)
#2–4/0
#2–250 kcmil
#2–300 kcmil
40 RDBR40HXXX D47.00 (1193.8) 24.00 (609.6)
Three-Phase
60–100 10 21.00 (533.4) 30.00 (762.0) #4–2/0 12 RABR12B3XXX A33.00 (838.2) 24.00 (609.6)
22 #4–2/0 RABR12H3XXX
60–100 10 29.00 (736.6) 36.00 (914.4) #4–1/0 30 RBBR30BXXX B40.00 (1016.0) 24.00 (609.6)
22 #4–1/0 RBBR30H3XXX
100–200 10 37.00 (939.8) 45.00 (1143.0) 2/0–300 kcmil 30 RDBR30B3XXX
100 37.00 (939.8)
39.00 (990.6)
38.50 (977.9)
45.00 (1143.0)
2/0–250 kcmil
2/0–300 kcmil
RDBR30H3XXX D47.00 (1193.8) 24.00 (609.6)
100–225 10 34.00 (863.6) 35.50 (901.7) 2/0–250 kcmil 42 REBR42B3XXX E56.00 (1422.4) 24.00 (609.6)
100 36.00 (914.4) 41.00 (1041.4) 2/0–300 kcmil REBR42H3XXX
Maximum Bus
Ampere Rating
Existing Box Height Wire
Size
Number
of Circuits
Part
Number
Retro
Size Group
Retro Cover Size
Minimum Maximum Height Width
Single-Phase
125 21.00 (533.4) 30.00 (762.0) #14–2/0 24 RABR20L125 A33.00 (838.2) 24.00 (609.6)
200 29.00 (736.6)
32.00 (812.9)
31.50 (800.1)
36.00 (914.4)
#1–250 kcmil
#1–300 kcmil
30 RBBR30L200 B40.00 (1016.0) 24.00 (609.6)
200 34.00 (863.6)
37.00 (939.8)
36.50 (927.1)
41.00 (1041.4)
#1–250 kcmil
#1–300 kcmil
40 RCBR40L200 B43.00 (1092.2) 24.00 (609.6)
200 37.00 (939.8)
39.00 (990.6)
38.50 (977.9)
45.00 (1143.0)
#1–250 kcmil
#1–300 kcmil
42 RDBR42L225 B47.00 (1193.8) 24.00 (609.6)
Three-Phase
125 21.00 (533.4) 30.00 (762.0) #8–2/0 24 RABR12L3125 A33.00 (838.2) 24.00 (609.6)
100 29.00 (736.6) 36.00 (914.4) #8–2/0 24 RBBR30L3100 B40.00 (1016.0) 24.00 (609.6)
150 29.00 (736.6) 36.00 (914.4) #4–4/0 24 RBBR24L3150
200 34.00 (863.6)
36.00 (914.4)
35.50 (901.7)
41.00 (1041.4)
#4–250 kcmil
#4–300 kcmil
30 RCBR30L3200 C43.00 (1092.2) 24.00 (609.6)
225 37.00 (939.8)
39.00 (990.6)
38.50 (977.9)
45.00 (1143.0)
#4–250 kcmil
#4–300 kcmil
42 RDBR42L3225 D47.00 (1193.8) 24.00 (609.6)
225 45.00 (1143.0) 54.00 (1371.6) #4–300 kcmil 42 REBR42L3225 E56.00 (1422.4) 24.00 (609.6)
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 69
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
BR Renovation Loadcenters Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Riser Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Type BR Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 67
Type BR Renovation Loadcenters
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . 70
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Type BR Renovation Loadcenters
Product Description
Available in 10, 20, 30
and 40 circuit main
breaker styles
Designed to replace
existing loadcenters
and fuse boxes
Type BR loadcenter
packaged with circuit
breakers
Factory-installed 5-circuit
terminal block(s)
Twin-stacked neutral
design
Quick-ProSM
All you need to
know to save
time and make
more money.
Specified on certain Eaton
products, the Quick-Pro
symbol allows for immediate
recognition of products
that are designed for
straightforward installation.
When you see Quick-Pro,
you know you can install
quickly—sometimes up to
50% less than the usual
installation time—and move
onto your next job.
Product Selection
BR Value Packs
Note
Indoor enclosure type.
Main
Breaker
Type Description
Wire Size
Range
Number of
5-Circuit
Terminal Blocks
Single-Pole
Breakers
Two-Pole
Breakers
Catalog
Number
BR
10 kAIC
Single-phase 100A 10k main breaker 10/20
circuit surface-mount box is 11.75" wide x 13" tall
#6–1/0 0 (2) BR115 (1) BR230 BR1020B100S11RN
Single-phase 100A 10k main breaker 10/20
circuit flush-mount box is 11.75" wide x 13" tall
0(2) BR115 (1) BR230 BR1020B100F11RN
Single-phase 100A
10 kAIC main breaker 20/20 circuit
1(5) BR120 (1) BR230 BR2020B100RN
BWH
25 kAIC
Single-phase 200A
25 kAIC main breaker 30/40 circuit
#2–300
kcmil
2(5) BR115
(5) BR120
(1) BR230
(1) BR250
BR3040B200RN
Single-phase 200A
25 kAIC main breaker 40/40 circuit
2(6) BR115
(6) BR120
(1) BR230
(1) BR250
BR4040B200RN
BR2020B100RN
Features, Benefits and Functions
Factory-installed terminal
block(s) allows installer to
terminate existing short
wires without using wire
nuts or junction boxes
Twin-stacked neutrals are
mounted up high in the
loadcenter, which allows
for all neutral and ground
wires to be terminated in
the top half of the
loadcenter
Specifically designed for
the service contractor—
this is the ONLY renovation
line in the industry
Single-pole and two-pole
breakers included
10-year warranty on
loadcenter and breakers
70 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Options and Accessories
Mechanical Interlock Cover
Covers mechanically interlock two breakers—Type BW
or BWH main breaker with a Type BR branch breaker.
Mechanical Interlock Cover
Field Installation Kits and Parts
Notes
Must be purchased in multiples of ordering quantities indicated.
#8–2/0 wire size range is 75°C rated only.
Fits Loadcenter
Catalog Numbers
Mechanical Interlock Panel Cover
Catalog Number
Flush
BR816B200RF BR3RDF5M
BR2040B200R BR3RDF11M
BR3040B200R BR3RDF12M
BR4040B200R BR3RDF13M
BR2040B200 BRCOV20D1FM
BR3040B200 BRCOV30G1FM
BR4040B200 BRCOV40L1FM
BR4040B200
Number
of Poles
Ampere
Rating
Number of 1-Inch (25.4 mm)
Spaces Needed
Wire Size Range
Cu/Al 60°C or 75°C
Ordering
Quantity
Catalog
Number
Main and Sub-Feed Lug Blocks
2 125 2 #8–2/0 1 BRSF125
150 2 #8–2/0 1 BRSF150
225 4 #2–300 kcmil 1 BRS225
3 150 3 #8–2/0 1 3BRSF150
225 6 #2–300 kcmil 1 3BRS225
Main Lugs
Two-pole, 200A stud mounted (includes deadfront filler plate) #1–300 kcmil 1 BRL200
Neutral/ground lug
Add-on neutral or ground lug
#2/0 maximum 1 NL20
#3/0 maximum 1 NL30
300 kcmil maximum 1 NL300
Filler Plates
1-inch (25.4 mm) circuit breaker space 25 BRFP
BW main circuit breaker space (with hardware) 1 BWFP
Door lock —12–42 circuits, and 100–225A 1 TDL
Door lock—4–8 circuits, 125A 1CH9FL
ANSI-61 light gray touchup paint for current loadcenters 1 SPC61
Isolated neutral assembly (computer circuits) 1 BINA
Circuit directory—adhesive backed 10 TCD
Cover screws 25 LCCS
Cover replacement latch (gray) 14-5/16 (363.5 mm) wide loadcenters only 1 BRRL
Circuit marking strip (next to breaker) 10 BRMS
Circuit identification label (preprinted breaker labels) 25 CHBL
Series rated caution label 25 SRL
Bonding strip with screw 1BSSUSE
BRSF125
3BRS225
BRL200
TDL
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 71
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Field Installation Rainproof Conduit Hubs
Ground Bar Kits
Ground Bar Legend
Notes
Must be purchased in multiples of ordering quantities indicated.
Distance between mounting holes is 1.75 inches (44.5 mm).
For single- and three-phase 400 and 600A applications.
Distance between mounting holes is 2.34 inches (59.5 mm).
For non-metallic enclosures. Snaps into molded base.
Description
Conduit Size
Inches (mm)
Ordering
Quantity
Catalog
Number
Group 1—for use with 70, 100 and 125A MLO and MCB loadcenters and circuit breaker enclosures and the
following 150 and 200A panels: BR48B200RF
0.75 (19.1) 1 DS075H1
1.00 (25.4) 1 DS100H1
1.25 (31.8) 1 DS125H1
1.50 (38.1) 1 DS150H1
2.00 (50.8) 1 DS200H1
Group 2—for use with 150, 200 and 225A MLO and MCB loadcenters and circuit breaker enclosures except for
the following 200A loadcenters: BR48B200RF. Also for use with 400 and 600A loadcenters and New York City
loadcenters manufactured after November 1, 2005
2.00 (50.8) 1 DS200H2
2.50 (63.5) 1 DS250H2
3.00 (76.2) 1 DS300H2
Type H conduit hubs for loadcenters PL0724R and S3100RN 0.75 (19.1) 1 RH75P
1.00 (25.4) 1 RH100P
1.25 (31.8) 1 RH125P
1.50 (38.1) 1 RH150P
Adapter kit—Allows Installing a Group 1 hub on devices arranged for Group 2 hubs 1 DS900AP
Group 1 small blank hub plate with bump 1 DS900CP1
Group 2 Large blank hub plate with bump 1 DS900CP2
Description
(See Legend)
Length
Inches (mm)
Ordering
Quantity
Catalog
Number
 2.54 (64.5) 1 GBK5
 3.59 (91.2) 1 GBK520
 4.29 (109.0) 1 GBK10
 5.34 (135.6) 1 GBK1020
4.61 (117.1) 1 GBK13
 5.69 (144.5) 1 GBK14
 6.74 (171.2) 1 GBK1420
 8.14 (206.8) 1 GBK21
 9.19 (233.4) 1 GBK2120
5.78 (146.8) 1 BRGBK39512 
 1.84 (46.7) 1 GB4NM
(3) #1410 Cu/Al or (1) #14–4 Cu/Al
(1) #62/0 Cu/Al
(1) #14–1/0 Cu/Al or (3) #14–10 Cu/Al
(1) #146 Cu/Al or (2) #14–12 Cu/Al
Mounting Hole
DS300H2
GBK14
BRGBK39512
72 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
BR Circuit Breakers Contents
Description Page
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Riser Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Type BR Retrofit Interior Kits . . . . . . . . . . . . . . . . . . . . . . . . 67
Type BR Renovation Loadcenters . . . . . . . . . . . . . . . . . . . . 69
Circuit Breakers
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Circuit Breaker Accessories . . . . . . . . . . . . . . . . . . . . . . 81
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Circuit Breakers
Product Description
Plug-On Branch Feeder Type
Arc Fault Circuit Breakers,
Type BR—10 kAIC, 120 Vac
and 120/240 Vac
A branch feeder type arc fault
circuit interrupter is a device
intended to mitigate high
current arcing faults in the
complete circuit, including
connected cords. High
current arcing faults can
occur from line to neutral or
line to ground. These arcing
faults are in parallel with the
load and produce the most
energy of all arcing faults.
The branch feeder type AFCI
is required in the 1999 and
2002
National Electrical Code.
The
Combination Type AFCI
is required in the 2005 and
2008 National Electrical Code.
Plug-On Combination Type
Arc Fault Circuit Breakers,
Type BR—10 kAIC, 120 Vac
and 120/240 Vac
A combination type arc
fault circuit interrupter is a
device that includes all of
the protection offered by the
branch feeder AFCI (mitigation
of high current arcing faults in
the complete circuit, including
connected cords). In addition
it provides direct detection of
persistent low current arcing
faults down to 5 amps with
associated mitigation of
fire hazards in the cords
connected to the outlets. High
current arcing faults can occur
from line to neutral or line to
ground. These arcing faults
are in parallel with the load
and produce the most energy
of all arcing faults. The current
level of low current arcing
faults is limited by the load.
Plug-On Ground Fault Circuit
Breakers, Type GFCB and
GFEP—10/22 kAIC, 120 Vac
and 120/240 Vac
Ground Fault
Application Notes
Single-pole GFCBs are
designed for use in two-
wire, 120 Vac circuits. See
Page 83 for a typical wiring
configuration.
Two-pole GFCBs are
designed for use in three-
wire, 120/240 Vac circuits,
120 Vac multiwire circuits
employing common, neutral
and two-wire, 240 Vac
circuits obtained from a
120/240 Vac source.
Page 83 shows typical wiring
configurations for a 120/240
Vac multiwire circuits, and a
240 Vac, two-wire circuit.
Note the “panel neutral”
conductor connects to the
neutral bar, even though the
neutral is not included in the
load circuit. This connection
is necessary to supply a
120 Vac power source to the
ground fault sensing circuit.
The figures are shown with
a 120/240 Vac, single-phase,
three-wire power source,
but are also applicable to a
120/208 Vac, three-phase,
four-wire power supply.
For all figures, the electrical
operation of the GFCB is
not affected by the
equipment ground.
Non-CTL Plug-On Replacement
—Circuit Breakers, Type BRD—
10 kAIC, 120/240 Vac
Non-CTL 10 kAIC
for Replacement
Purposes Only
For replacement in
enclosures manufactured
prior to 1968 with unnotched
stabs. Circuit breakers do
not have rejection tab.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 73
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Product Selection
Plug-On Circuit Breakers, Types BR—10/22/42 kAIC, 120 Vac, 120/240 Vac and 240 Vac
Type BR Breakers, 1-Inch (25.4 mm) per Pole 120/240, 10, 22 and 42 kAIC
Notes
One pole, 1-inch (25.4 mm) per pole circuit breakers are available with high magnetic setting for switching large tungsten lamp loads. Add suffix H to catalog number.
Switching duty rated.
On the black handle breaker, add suffix “B” to the catalog number to obtain a tapped molded opening for proper use with hold-down kits.
For use as a branch circuit breaker in 400 and 600 ampere panels only.
All Type BR single-, two- and three-pole circuit breakers carry listing for HACR application. For circuit breakers with a shunt trip, add ST suffix.
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Single-Pole 120/240 Vac
Requires One 1-Inch (25.4 mm) Space
Two-Pole 120/240 Vac
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
10 per Shelf Carton 5 per Shelf Carton
10 kAIC 22 kAIC 10 kAIC 22 kAIC 42 kAIC
Catalog
Number
Catalog
Number
Catalog
Number
Catalog
Number
Catalog
Number
10 #14–4 BR110 BR210 —
15 #14–4 BR115  BRH115 BR215 BRH215 —
20 #14–4 BR120  BRH120 BR220 BRH220 —
25 #14–4 BR125 BRH125 BR225 BRH225 —
30 #14–4 BR130 BRH130 BR230 BRH230 —
35 #14–4 BR135 BRH135 BR235 BRH235 —
40 #14–4 BR140 BRH140 BR240 BRH240
45 #14–4 BRH145 BR245 BRH245 —
50 #14–4 BR150 BRH150 BR250 BRH250
55 #14–3 BR150 BRH155 BR255 BRH255 —
60 #8–1/0 BR160 BRH160 BR260 BRH260 BRHH260
70 #8–1/0 BR170 BRH170 BR270 BRH270 BRHH270
80 #8–1/0 ——BR280 BRH280 BRHH280
90 #8–1/0 ——BR290 BRH290 BRHH290
100 #8–1/0 ——BR2100 BRH2100 BRHH2100
110 #8–1/0 ——BR2110 BRH2110 BRHH2110
125 #4–2/0 ——BR2125 BRH2125 BRHH2125
150 #4–2/0 ——BR2150 ——
BR120
BR215
BR320
BRH2100
74 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Type BR Breakers, 1-Inch (25.4 mm) per Pole 240 Vac, 10, 22 and 42 kAIC
Plug-On Branch Feeder Type Arc Fault Circuit Breakers, Type BR—10 kAIC, 120 Vac and 120/240 Vac
Type BR, 1-Inch (25.4 mm) Wide FIRE-GUARD AFCI Circuit Breakers
Notes
One pole, 1-inch (25.4 mm) per pole circuit breakers are available with high magnetic setting for switching large tungsten lamp loads. Add suffix H to catalog number.
Clamshell packaging available with CS modification code on the end of catalog number.
Common trip refers to two-pole 240V load application sourced by 120/240 Vac (see Page 83).
Independent trip refers to two-pole multi-wire, home run or shared neutral circuits (see Pages 83 and 83).
All Type BR single-, two- and three-pole circuit breakers carry listing for HACR application. For circuit breakers with a shunt trip, add ST suffix.
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Three-Pole 240 Vac
Common Trip Requires Three
1-Inch (25.4 mm) Spaces
5 per Shelf Carton
10 kAIC 22 kAIC
Catalog Number Catalog Number
10 #14–4 BR310 —
15 #14–4 BR315 BRH315
20 #14–4 BR320 BRH320
25 #14–4 BR325 BRH325
30 #14–4 BR330 BRH330
35 #14–4 BR335 BRH335
40 #14–4 BR340 BRH340
45 #14–4 BR345 BRH345
50 #14–4 BR350 BRH350
55 #14–3 BR355 BRH355
60 #4–1/0 BR360 BRH360
70 #4–1/0 BR370 BRH370
80 #4–1/0 BR380 BRH380
90 #4–1/0 BR390 BRH390
100 #4–1/0 BR3100 BRH3100
Poles
Ampere
Rating Configuration
Catalog
Number
Single-pole
10 kAIC
15 AFCI BR115AF
20 AFCI BR120AF
Single-pole
22 kAIC
15 AFCI BRH115AF
20 AFCI BRH120AF
Two-pole
10 kAIC 
15 AFCI Common Trip BRL215AF
20 AFCI Common Trip BRL220AF
BR Breakers
Type BR AFCI
Circuit Breaker
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 75
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Plug-On Combination Type Arc Fault Circuit Breakers, Type BR—10 kAIC, 120 Vac and 120/240 Vac
Type BR, 1-Inch (25.4 mm) wide FIRE-GUARD Combination Type AFCI
Circuit Breakers
Plug-On Ground Fault Circuit Breakers, Type GFCB and GFEP—10/22 kAIC, 120 Vac and 120/240 Vac
Type GFCB Ground Fault Circuit Breakers—5 Milliampere—
1-Inch (25.4 mm) per Pole 120 Vac or 120/240 Vac, 10 kAIC
Notes
Clamshell packaging available with CS modification code on the end of catalog number.
Available with bell alarm or auxiliary switch. See circuit breaker accessories on Page 81.
For use with copper wire only.
Poles
Ampere
Rating Configuration
Catalog
Number
Single-pole
10 kAIC
15 AFCI BR115CAF
BRC115CAF
20 AFCI BR120CAF
BRC120CAF
Single-pole
15 kAIC
15 AFCI BRLH115CAF
22 AFCI BRLH120CAF
Two-pole
10 kAIC
15 AFCI BR215CAF
20 AFCI BR220CAF
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Single-Pole 120 Vac
Requires One
1-Inch (25.4 mm) Space
Two-Pole 120/240 Vac
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
1 per Shelf Carton 1 per Shelf Carton
Catalog Number Catalog Number
15 #14–4 GFCB115 GFCB215
20 #14–4 GFCB120 GFCB220
25 #14–4 GFCB125 GFCB225
30 #14–4 GFCB130 GFCB230
40 #14–4 GFCB140 GFCB240
50 #14–4 GFCB250
60 #14–6 — GFCB260
Type GFCB Single-Pole
Type GFCB Two-Pole
76 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Type GFCBH Ground Fault Breakers—5 Milliampere—
1-Inch (25.4 mm) per Pole 120 Vac or 120/240 Vac, 22 kAIC
Type GFEP Ground Fault Equipment Protectors—30 Milliampere—
1-Inch (25.4 mm) per Pole 120 Vac or 120/240 Vac, 10 kAIC
Note
For use with copper wire only.
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Single-Pole 120 Vac
Requires One
1-Inch (25.4 mm) Space
Two-Pole 120/240 Vac
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
1 per Shelf Carton 1 per Shelf Carton
Catalog Number Catalog Number
15 #14–4 GFCBH115 GFCBH215
20 #14–4 GFCBH120 GFCBH220
25 #14–4 GFCBH125 GFCBH225
30 #14–4 GFCBH130 GFCBH230
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Single-Pole 120 Vac
Requires One
1-Inch (25.4 mm) Space
Two-Pole 120/240 Vac
Common Trip Requires Two
1-Inch (25.4 mm) Space
1 per Shelf Carton 1 per Shelf Carton
Catalog Number Catalog Number
15 #14–4 GFEP115 GFEP215
20 #14–4 GFEP120 GFEP220
25 #14–4 GFEP125 GFEP225
30 #14–4 GFEP130 GFEP230
40 #14–4 — GFEP240
50 #14–4 GFEP250
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 77
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
CTL Plug-On Circuit Breakers, Type BD Duplex, BQ and BQC Quadplex—10 kAIC, 120/240 Vac
Class CTL, 1-Inch (25.4 mm) per Pole 10 kAIC—All Circuit Breakers Have Rejection Tab Feature
Notes
All Type BD duplex and BQ quadplex circuit breakers carry listing for HACR applications.
All 15 and 20A single poles are switch-duty rated.
Type BD Duplex
(UL Type BRD)
Wire Size
Range
Cu/Al
65°C or 75°C
Type BQ Quadplex Independent Trip
(UL Type BRD)
Type BQ Quadplex Independent Trip
(UL Type BRD)
Single-Pole
Requires One 1-Inch
(25.4 mm) Space
10 per Shelf Carton
Two-Pole and Single-Pole
Requires Two 1-Inch
(25.4 mm) Spaces
5 per Shelf Carton
Two-Pole
Requires Two 1-Inch
(25.4 mm) Spaces
5 per Shelf Carton
Ampere
Rating
120 Vac 120 Vac 120/240 Vac 120 Vac
Catalog
Number
120/240 Vac
Catalog
Number
Catalog
Number
Ampere Rating Ampere Rating
Outer Left
Single-Pole
Center Two-Pole
Independent Trip
Outer Right
Single-Pole
Outer Two-Pole
Independent Trip
Center Two-Pole
Independent Trip
10–10 BD1010 #14–4 15 20 15 BQ2202115 15 15 BQ215215
15–15 BD1515 #14–4 20 20 20 BQ2202120 15 20 BQ215220
15–20 BD1520 #14–4 15 30 15 BQ2302115 15 30 BQ215230
15–30 BD1530 #14–4 20 30 20 BQ2302120 15 40 BQ215240
20–15 BD2015 #14–4 15 40 15 BQ2402115 15 50 BQ215250
20–20 BD2020 #14–4 20 40 20 BQ2402120 20 20 BQ220220
20–30 BD2030 #14–4 15 50 15 BQ2502115 20 30 BQ220230
25–25 BD2525 #14–4 20 50 20 BQ2502120 20 40 BQ220240
30–15 BD3015 #14–4 — 20 50 BQ220250
30–20 BD3020 #14–4 — 25 25 BQ225225
30–30 BD3030 #14–4 — 30 30 BQ230230
30–40 BD3040 #14–4 — 30 40 BQ230240
30–50 BD3050 #14–4 — 30 50 BQ230250
50–30 BD5030 #14–4 — 40 40 BQ240240
50–50 BD5050 #14–4 — 40 50 BQ240250
——— —50 50 BQ250250
BD2020
BQ2302115
BQ230230
120
/
240 V
a
c
120
/
240 V
a
c
120
/
240 V
a
c
V
a
c
78 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Non-CTL Plug-On Replacement—Circuit Breakers, Type BRD—10 kAIC, 120/240 Vac
Class Non-CTL, 1-Inch (25.4 mm) per Pole 10 kAIC—Breakers Do Not Have Rejection Tab Feature
CTL and Non-CTL Breakers
Note
Type BD Duplex, BQ and BQC Quadplex (CTL) circuit breakers conform to Section 384-15 of the latest National Electrical Code. Install breaker only in panel positions that
have notched bus stabs.
Type BR Duplex
Wire Size
Range
Cu/Al
65°C or 75°C
Type Brand BRD Quadplex Independent Trip
Type BRD Quadplex Common Trip
Center and Outer Poles
Single-Pole Requires One
1-Inch (25.4 mm) Space
10 per Shelf Carton
Two-Pole Requires Two
1-Inch (25.4 mm) Spaces
5 per Shelf Carton
Two-Pole Requires Two
1-Inch (25.4 mm) Spaces
5 per Shelf Carton
Ampere
Rating
120 Vac 120/240 Vac 120/240 Vac
Catalog
Number
120/240 Vac
Catalog
Number
Catalog
Number
Ampere Rating Ampere Rating
Outer Two-Pole
Independent Trip
Center Two-Pole
Independent Trip
Outer Two-Pole
Common Trip
Center Two-Pole
Common Trip
15–15 BR1515 #14–4 15 15 BR415 15 15 BRDC215215
15–20 BR1520 #14–4 20 20 BR420 30 30 BRDC230230
20–15 BR2015 #14–4 30 30 BR430 30 40 BRDC230240
20–20 BR2020 #14–4 20 30 BRD220230 30 50 BRDC230250
30–30 BR3030 #14–4 30 40 BRD230240 ——
30–50 BR3050 #14–4 30 50 BRD230250 ——
BR2020
120
/
240 V
a
c
120
/
240 V
a
c
120
/
240 V
a
c
V
a
c
120
/
240 V
a
c
V
a
c
Notched
Bus Stab
Unnotched
Bus Stab
Type BR or Type BD Duplex, (CTL),
Type BQ and
BQC Quadplex
Type BR Notched
Stab Non-CTL
Non-Circuit
Limiting
Type BR
Type BD
Duplex
Rejection
Tab
CTL Circuit
Limiting
Feature
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 79
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Common Trip Quadplex Breakers
Class CTL, 1-Inch (25.4 mm) per Pole 10 kAIC—All Circuit Breakers Have Rejection Tab Feature
Notes
All Type BQC quadplex circuit breakers carry listing for HACR applications.
All 15 and 20 ampere single poles are switch-duty rated.
Type BQC Quadplex Common Trip Center Poles
(UL Type BRD)
Wire Size Range
Cu/Al 65°C
or 75°C
Type BQC Quadplex Common Trip Center and Outer Poles
(UL Type BRD)
Two-Pole and Single-Pole
Requires Two 1-Inch (25.4 mm) Spaces
5 per Shelf Carton
Two-Pole
Requires Two 1-Inch (25.4 mm) Spaces
5 per Shelf Carton
120 Vac 120/240 Vac 120 Vac
Catalog
Number
120/240 Vac
Catalog
Number
Ampere Rating Ampere Rating
Outer Left
Single-Pole
Center Two-Pole
Common Trip
Outer Right
Single-Pole
Outer Two-Pole
Common Trip
Center Two-Pole
Common Trip
15 20 15 BQC2202115 #14–4 15 15 BQC215215
15 25 15 BQC2252115 #14–4 15 20 BQC215220
15 30 15 BQC2302115 #14–4 15 30 BQC215230
15 40 15 BQC2402115 #14–4 20 15 BQC220215
15 50 15 BQC2502115 #14–4 20 20 BQC220220
—— —#14–4 20 30 BQC220230
—— —#14–4 20 40 BQC220240
—— —#14–4 20 50 BQC220250
20 15 20 BQC2152120 #14–4 25 25 BQC225225
20 20 20 BQC2202120 #14–4 25 30 BQC225230
20 25 20 BQC2252120 #14–4 30 15 BQC230215
20 30 20 BQC2302120 #14–4 30 30 BQC230230
20 40 20 BQC2402120 #14–4 30 40 BQC230240
20 50 20 BQC2502120 #14–4 30 50 BQC230250
30 50 20 BQC2502030 #14–4 40 30 BQC240230
—— —#14–4 40 40 BQC240240
—— —#14–4 40 50 BQC240250
—— —#14–4 50 20 BQC250220
—— —#14–4 50 50 BQC250250
BQC2302115
BQC2302115
120
/
240 V
a
c
V
a
c
80 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Plug-On Circuit Breakers, Types BJ and BJH—10/22 kAIC, 120/240 Vac and 240 Vac
For Use in Single-Phase and Three-Phase Loadcenters—150 Amperes and Above
Types BJ and BJH Breakers, 1-Inch (25.4 mm) per Pole, 120/240 or 240 Vac, 10, 22 kAIC
Plug-On Special Application Circuit Breakers—10 kAIC, 120 Vac, 120/240 Vac and 240 Vac
Special Application Circuit Breakers, 1-Inch (25.4 mm) per Pole
Notes
Breaker uses two 1-inch (25.4 mm) pole spaces on left side and two 1-inch (25.4 mm) pole spaces on right side of loadcenter.
Breaker uses three 1-inch (25.4 mm) pole spaces on left side and three 1-inch (25.4 mm) pole spaces on right side of loadcenter.
If BJ or BJH breakers are used as a main or a back feed device, a hold-down kit is required. See Page 81.
Ampere
Rating
Wire Size Range
Cu/Al 60°C or 75°C
Two-Pole 120/240 Vac
Common Trip Requires Four
1-Inch (25.4 mm) Spaces
10 per Shelf Carton
Three-Pole 240 Vac
Common Trip Requires Six
1-Inch (25.4 mm) Spaces
5 per Shelf Carton
10 kAIC 22 kAIC 10 kAIC 22 kAIC
Catalog Number Catalog Number Catalog Number Catalog Number
125 BJ2125 BJH2125 #2–300 kcmil BJ3125 BJH3125
150 BJ2150 BJH2150 #2–300 kcmil BJ3150 BJH3150
175 BJ2175 BJH2175 #2–300 kcmil BJ3175 BJH3175
200 BJ2200 BJH2200 #2–300 kcmil BJ3200 BJH3200
225 BJ2225 BJH2225 #2–300 kcmil BJ3225 BJH3225
Water Heater Breakers Switching Neutral Breakers
Wire
Size
Range
Cu/Al
60°C or
75°C
240V Breakers Non-Automatic Molded Case Switches
Two-Pole 120/240 Vac
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
Two-Pole 120 Vac
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
Two-Pole 240 Vac
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
Two-Pole 240 Vac
Requires Two
1-Inch (25.4 mm) Spaces
With Isolated Line Terminals
for Separately Metered
Water Heaters
With Switching Neutral Pole
for Gasoline Pump Applications
Where Voltage to
Ground is 240 Vac
For Use as Disconnect Contains No
Magnetic or Thermal Trip Properties
5 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
10 kAIC 10 kAIC 10 kAIC 5 kAIC
Ampere
Rating
Catalog
Number
Ampere
Rating
Catalog
Number
Ampere
Rating
Catalog
Number
Ampere
Rating
Catalog
Number
15 BRWH215 15 BRSN215 #14–4 10 BR210H
20 BRWH220 20 BRSN220 #14–4 15 BR215H
30 BRWH230 25 BRSN225 #14–4 20 BR220H
30 BRSN230 #14–4 25 BR225H
#14–4 30 BR230H
#14–4 35 BR235H
#14–4 40 BR240H
#14–4 45 BR245H
#14–4 50 BR250H 50 BR250NA
#14–4 55 BR255H
#4–1/0 60 BR260H 60 BR260NA
#4–1/0 70 BR270H
#4–1/0 80 BR280H
#4–1/0 90 BR290H
#4–1/0 100 BR2100H 100 BR2100NA
Type BJ
BRWH215
W
ater Heater Breaker
BRSN220
Switching Neutral
Breaker
LIN
E
L
O
A
D
OUT
IN
NE
U
TRA
L
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 81
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Circuit Breaker Accessories
Field Installation Kits and Parts
Notes
Must be purchased in multiples of ordering quantities indicated.
Handle ties: typically used to join two similar independent single-pole breakers to form a two-pole noncommon trip breaker.
Handle lockoffs: devices that use a padlock to lock the circuit breaker’s handle in the ON or OFF position.
See table on Page 82 for handle position changeability chart.
Escutcheon mounted: device mounted semipermanently to the face of the circuit breaker and secured by the loadcenter deadfront.
Handle mounted: device mounted directly to the handle by the use of a set screw.
Screw mounted: device permanently mounted to the face of the circuit breaker by the use of a non-removable screw.
Handle lockdogs: devices that are used to secure a circuit breaker’s handle in the ON or OFF position. Handle Lockdogs are not padlockable devices.
Hold-down kits: devices used to secure the circuit breaker to the loadcenter for back-feed main application. See NEC Article 384-16(g).
Description
Ordering
Quantity
Catalog
Number
Handle Ties
Handle tie bar for physically joining the handles of two adjacent single-pole Type BR circuit breakers (metal cylinder pin type)10BHT
Handle tie bar for joining two independent outside poles of Types BQ and BQC Quadplex and outside poles of two Type BD
duplex circuit breakers
10 THOW
Handle tie bar for joining two adjacent outside poles of Types BQ and BQC Quadplex and outside poles of two Type BD duplex circuit breakers 10 THS1
Handle Lockoffs 
Padlockable device for locking the handle of single-, two- or three-pole Type BR Circuit Breakers and single-pole of a Type BD Duplex
or one independent outside pole of a Type BQ or BQC Quadplex circuit breakers (escutcheon mounted)
10 BRLW
Padlockable device for locking the handle of a single-pole Type BR circuit breaker.(handle mounted) 10 BRLW1
Padlockable device for locking the handle of a two- and three-pole Type BR circuit breaker (handle mounted) 10 BRLW2
Padlockable device for locking the handle of a single-pole Type BD Duplex, BQ or BQC Quadplex breaker (handle mounted) 10 BRDL1
Padlockable device for locking the handle of the two center poles and the two outer poles of a two-pole Types BQ and BQC quadplex
circuit breakers (escutcheon mounted)
10 BRQLW
Padlockable device for locking the handle of main circuit breaker Types CC and CHH into the ON or OFF position (screw mounted) 1 CCPL
Padlockable device for locking the handle of main breaker Types BW and BWH into the ON or OFF position (escutcheon Mounted) 1MCBPL
Device used to secure handle in ON or OFF position for single-, two- or three-pole Type BR circuit breakers and single-pole of Type BD
duplex and one independent outside pole of Type BQ or BQC Quadplex circuit breakers (escutcheon mounted)
10 BHLW
Device used to secure handle in ON or OFF position for single-pole Type BR circuit breakers (handle mounted) 10 BHLW1
Device used to secure handle in ON or OFF position for two- and three-pole Type BR circuit breakers (handle mounted) 10 BHLW2
Device used to secure handle in ON or OFF position for single-pole Type GFCB ground fault circuit breakers (handle mounted) 10 BHGW
Device used to secure handle in ON or OFF position for one independent outside pole of Types BQ and BQC Quadplex or single-pole
Type BD duplex circuit breakers (handle mounted)
10 HLW1
Hold-Down Kits
Hold-down retainer kit for three-pole Type BR circuit breakers in S3100 and 3100R loadcenters only 1 BRHDB
Hold-down screw kit for two-pole Type BR circuit breakers in single-phase MLO loadcenters through 125A 1 BREQS125
Hold-down screw kit for two-pole Type BR circuit breakers in MLO loadcenters 150–225A (single-phase only) 1 BRHDK125
Hold-down screw kit for two-pole Types BJ and BJH circuit breakers in MLO loadcenters 125–225A 1 BJHDS
Hold-down screw kit for three-pole Types BJ and BJH circuit breakers in MLO loadcenters 125–225A 1 BJHDS3P
Main Breaker Lug Kits
Types CC and CHH main breaker lug kit (2) 300 kcmil 1CCL300
Types BW/BWH main breaker lug kit (2) 300 kcmil 1MCBL300
THS1
BHLW2
BRQLW
MCBPL (Installed)
BHLW
BRLW2
BREQS125
BRHDK125
82 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Field Installation Kits and Parts, continued
Shunt Trips, Auxiliary and Alarm Contacts
Handle Position Changeability Chart
Notes
Must be purchased in multiples of ordering quantities indicated.
Add suffix indicated to end of breaker catalog number.
Description
Ordering
Quantity
Catalog
Number
Mechanical Interlocks
Types BR for two-, three- and four-pole breakers 10 BRML
10 BRPLOFF
10 BRPLOFF2P
10 BRPLOFF3P
10 BJL2P
10 BJL3P
10 GHQRLOFF2P
10 GHQRLOFF
10 QCD123PLOFF
Description
Catalog Number
Suffix Adder
Shunt Trip for Types BW/BWH
12 Volts SR12
24 Volts SR24
120 Volts SR01
Shunt Trip for Types BR
120 Volts ST
Auxiliary Contact for Types BW/BWH
1NO and 1NC AL1
2NO and 2NC AL2
Alarm Contacts for Types BW/BWH
Types BW/BWH CR1
Alarm Contacts for Type GFCB (Single-Pole)
Alarm contact for GFCB (single-pole) W1
1NO and 1NC W2
Handle Lockoff and
Lockdog Types
To Change Handle Position from ON to OFF, or OFF to ON
You Must...
Remove
Padlock
Remove
Device
Remove
Loadcenter
Deadfront
Lockoff escutcheon mounted Remove
Lockoff handle mounted Remove Remove
Lockoff screw mounted Remove
Lockdog escutcheon mounted N/A Remove Remove
Lockdog handle mounted N/A Remove
BRML
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 83
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Wiring Diagrams
Single-Pole 120V Load Application Sourced by 120/240 Vac
Two-Pole Shared Neutral with
Multi-Duplex Receptacle Application
Two-Pole 240V Load Application Sourced by 120/240 Vac
Two-Pole Shared Neutral with Duplex Receptacle Application
Single-Pole 120V Load Application Sourced by 120/240 Vac
Single-Pole 120V Duplex Receptacle Application
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
Equipment Ground
NA B
120/240 Vac
Source
Two 120V
Duplex
Receptacles
Two-Pole
Line B
Line A
Neutral
Neutral
Equipment Ground
Line B
NA B
120/240 Vac
Source
Line A 240V
Duplex
Receptacle
Two-Pole
Neutral
Equipment Ground
NAB
120/240 Vac
Source
Line A
120V Duplex
Receptacle
(With Line Side
Jumper Removed)
Two-Pole
Line B
Neutral
Neutral
Equipment Ground
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
Equipment Ground
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
84 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Two-Pole 120V Multi-Duplex Receptacle Application
Two-Pole 120V Duplex Receptacle Application
Two-Pole 240V Duplex Receptacle Application
NA B
120/240 Vac
Source
Two 120V
Duplex
Receptacles
Two-Pole
Line B
Line A
Neutral
Neutral
NAB
120/240 Vac
Source
Line A
120V Duplex
Receptacle
(With Line Side
Jumper Removed)
Two-Pole
Line B
Neutral
Neutral
Line B
NA B
120/240 Vac
Source
Line A 240V
Duplex
Receptacle
Two-Pole
Neutral
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 85
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Residential/Commercial/New York City Loadcenters, Unit Enclosures—Box Sizes
Note: Box sizes do not include covers/fronts.
Residential Loadcenters—NEMA Type 1 Indoor
Residential Loadcenters—NEMA Type 3R Outdoor
Commercial Loadcenters—NEMA Type 1 Indoor
Commercial Loadcenters—NEMA Type 3R Outdoor
New York City Loadcenters—NEMA Type 1 Indoor
Types ECB and ECC Unit Enclosures—NEMA Type 1 Indoor
Types ECB and ECC Unit Enclosures—NEMA Type 3R
Outdoor
Box Size Height Width Depth
A1 15.00 (381.0) 11.25 (285.8) 3.75 (95.3)
B1 16.75 (425.5) 14.31 (363.5) 3.88 (98.4)
B2 18.75 (476.3) 14.31 (363.5) 3.88 (98.4)
C1 21.00 (533.4) 14.31 (363.5) 3.88 (98.4)
C2 23.00 (584.2) 14.31 (363.5) 3.88 (98.4)
C4 27.00 (685.8) 14.31 (363.5) 3.88 (98.4)
D1 29.13 (739.8) 14.31 (363.5) 3.88 (98.4)
G1 34.13 (866.8) 14.31 (363.5) 3.88 (98.4)
L1 39.00 (990.6) 14.31 (363.5) 3.88 (98.4)
L2 45.00 (1143.0) 14.31 (363.5) 3.88 (98.4)
28.63 (219.1) 5.00 (127.0) 3.50 (88.9)
39.44 (239.7) 4.50 (114.3) 3.00 (76.2)
413.00 (330.2) 11.00 (279.4) 3.56 (90.5)
59.44 (239.7) 4.50 (114.3) 3.00 (76.2)
612.00 (304.8) 6.88 (174.6) 4.50 (114.3)
713.00 (330.2) 11.00 (279.4) 3.56 (90.5)
914.50 (368.3) 6.50 (165.1) 3.50 (88.9)
Box Size Height Width Depth
B1R 16.75 (425.5) 14.31 (363.5) 5.19 (131.8)
B2R 18.75 (476.3) 14.31 (363.5) 5.19 (131.8)
C3R 25.00 (635.0) 14.31 (363.5) 5.19 (131.8)
D1R 29.13 (739.8) 14.31 (363.5) 5.19 (131.8)
G1R 34.13 (866.8) 14.31 (363.5) 5.19 (131.8)
L1R 39.00 (990.6) 14.31 (363.5) 5.19 (131.8)
L2R 45.00 (1143.0) 14.31 (363.5) 5.19 (131.8)
2R 8.63 (219.1) 5.00 (127.0) 3.50 (88.9)
3R 9.44 (239.7) 4.50 (114.3) 3.00 (76.2)
4R 13.00 (330.2) 11.00 (279.4) 3.56 (90.5)
5R 9.44 (239.7) 4.50 (114.3) 3.00 (76.2)
6R 11.75 (298.5) 6.50 (165.1) 4.50 (114.3)
7R 13.00 (330.2) 11.00 (279.4) 3.56 (90.5)
8R 27.00 (685.8) 10.50 (266.7) 4.75 (120.7)
9R 14.25 (362.0) 6.50 (165.1) 4.00 (101.6)
C1R 21.00 (533.4) 14.31 (363.5) 5.19 (131.8)
Box Size Height Width Depth
19 44.00 (1117.6) 16.16 (410.4) 6.25 (158.8)
20 44.00 (1117.6) 16.16 (410.4) 6.25 (158.8)
22 54.00 (1371.6) 16.22 (412.0) 6.31 (160.3)
24 66.50 (1689.1) 16.22 (412.0) 6.31 (160.3)
Box Size Height Width Depth
42 38.00 (965.2) 16.31 (414.3) 6.38 (161.9)
43 44.00 (1117.6) 16.31 (414.3) 6.38 (161.9)
46 54.00 (1371.6) 16.31 (414.3) 6.38 (161.9)
47 66.56 (1690.7) 16.31 (414.3) 6.38 (161.9)
Box Size Height Width Depth
A38.00 (965.2) 18.13 (460.4) 5.00 (127.0)
B44.00 (1117.6) 18.13 (460.4) 5.00 (127.0)
C66.50 (1689.1) 18.13 (460.4) 6.25 (158.8)
Height Width Depth
23.25 (590.6) 8.88 (225.4) 4.50 (114.3)
Height Width Depth
23.68 (601.7) 9.31 (236.5) 5.44 (138.1)
86 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Approximate Dimensions in Inches (mm)
Residential Loadcenter Knockouts
Knockouts for Box Sizes A1, B1, B2, C1, C2, C4, D1, G1, L1,
L2, B1R, B2R, C1R, C3R, D1R, G1R, L1R, L2R
Residential NEMA Type 1 Indoor and
NEMA Type 3R Outdoor Enclosures
Code Diameter
A0.50 (12.7) 0.75 (19.1)
B0.50 (12.7) ————
C0.50 (12.7) 1.25 (31.8) 1.50 (38.1) 2.00 (50.8) 2.50 (63.5)
D1.25 (31.8) 1.25 (31.8) 2.00 (50.8) 2.50 (63.5)
E0.50 (12.7) 0.75 (19.1) 1.00 (25.4)
F0.50 (12.7) 0.75 (19.1) 1.00 (25.4) 1.50 (38.1) 2.00 (50.8)
G1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
H0.50 (12.7) 0.75 (19.1) 1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
I1.00 (25.4) 1.25 (31.8) 1.50 (38.1) 2.00 (50.8) 2.50 (63.5)
J1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
J
E
B
B
B
A
B
B
B
B
B
E
J
B
B
B
A
B
B
B
B
B
E
J
J
A
B
A
B
J
J
J
A
B
B
B
B
J
B
B
Outdoor Boxes
B1R, B2R, C1R, C3R, D1R,
G1R, L1R, L2R
Indoor Boxes
B1, B2
Indoor Boxes
C1, C2, C4, D1, G1, L1, L2
.45
(
11.4
)
Dia. K
O
.45
(
11.4
)
Dia. K
O
A
D
E
A
A
B
B
B
E
D
A
D
E
A
A
B
B
B
E
D
D
D
D
D
EE
I
A
A
H
B
B
B
A
E
B
I
B
B
B
B
B
A
A
H
B
B
B
B
A
E
B
.45
(
11.4
)
Dia. K
O
.45
(
11.4
)
Dia. K
O
A
D
E
A
A
B
B
E
D
D
D
D
D
E
E
A
B
B
A
D
E
A
A
B
B
B
E
D
A
B
I
B
B
B
B
A
A
H
B
B
B
B
A
E
B
I
B
B
B
B
A
A
H
B
B
B
A
E
B
2.06
(
52.3
)
Dia
.
(125A
Max.)
A
3.06
(
77.7
)
Dia
.
(225A
Max.)
A
H
u
b
I
B
B
B
B
B
A
A
H
B
B
B
B
B
A
E
A
B
D
D
D
D
.45
(
11.4
)
Dia. K
O
E
E
E
B
Indoor Boxes
A1
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 87
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Approximate Dimensions in Inches (mm)
Knockouts for Box Sizes 3, 4, 5, 6, 7, 9, 2R, 3R, 4R, 5R, 6R,
7R, 8R, 9R
Residential NEMA Type 1 Indoor and NEMA Type 3R Outdoor Enclosures
Code Diameter
A0.50 (12.7)
B0.50 (12.7) 0.75 (19.1)
C0.50 (12.7) 0.75 (19.1) 1.00 (25.4)
D0.50 (12.7) 0.75 (19.1) 1.00 (25.4) 1.25 (31.8)
E0.75 (19.1) 1.00 (25.4) 1.25 (31.8)
F0.75 (19.1) 1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
G1.00 (25.4) 1.25 (31.8) 1.50 (38.1)
H1.00 (25.4) 1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
I1.25 (31.8) 1.50 (38.1) 2.00 (50.8)
Box 2, 2R
R
1.2
5
K
O
31.8
)
K
O
Mountin
g
H
o
l
e
f
or
5
/
16
(
7.9
)
Sc
r
ew
.
50
–.7
5
(
12.
7
19.1
)
2.
38
(
60.3
)
.31
(
7.9
)
.
50
(
12.
7
1
9
.
1
25.4
)
.
50
(
12.
7
6.38
3
3
(161.9)
1
1
A
A
A
A
C
E
A
A
C
E
F
A
A
F
Box 3
A
A
A
A
F
Hub
AAA A
A
A A
BB
B
D
G
G G
Hub
A
A
AA
A
A A A
A
A A
BBB
B
B
B
D
G
AAA A
A
A A
BB
B
D
D D
G
G
G
D
G
G
Box 3R Box 4
Box 4R Box 5 Box 5R Box 6
A
A
A
A
A
A
D D D
D
F
F
A
A
D D D
F
Hub
A
A
B
A
B
B
C
C
F F
F
F
A
B
F
F
H
A
B
A
B
H
Box 6R
F
B B
B
H
Hub
D D
Box 7 Box 7R
A
A
AA
A
AAA
AAA AAA
B B B
AB B
B
B
B
B
C C
C
C
C
BC
G
G
G
G
G G
F
AAA AAA
AB B
BC
C
G
G G
F
Hub
AA
B
C
C
Hub
I
AA
BC
C
I
I
A A
A
A
A A
B
B
B
B
BB
B
C
C
C
G
GG
G
G
GG
G
A
A
B
B
C
GG
G
G
Hub
Box 8R Box 9 Box 9R
88 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Loadcenters and Circuit Breakers
Type BR Loadcenters and Circuit Breakers
Approximate Dimensions in Inches (mm)
Commercial Loadcenter Knockouts
NEMA Type 1 Indoor Commercial Enclosures
Knockouts for Box Sizes 19, 20, 22, 24
NEMA Type 3R Outdoor Commercial Enclosures
Knockouts for Box Sizes 42, 43, 46, 47
Unit Enclosure Knockouts, Types ECB and ECC Knockouts
Indoor Commercial Enclosures
Outdoor Commercial Enclosures
Unit Enclosure Knockouts
Code Diameter
A0.50 (12.7)
B0.50 (12.7) 0.75 (19.1)
C0.75 (19.1) 1.00 (25.4) 1.50 (38.1)
D1.50 (38.1) 2.00 (50.8) 2.50 (63.5) 3.00 (76.2)
E2.00 (50.8) 2.50 (63.5) 3.00 (76.2)
F2.50 (63.5) 3.00 (76.2) 3.50 (88.9)
Code Diameter
A0.50 (12.7)
B0.50 (12.7) 0.75 (19.1)
C0.75 (19.1) 1.00 (25.4) 1.25 (31.8)
D1.50 (38.1) 2.00 (50.8) 2.50 (63.5)
E2.00 (50.8) 2.50 (63.5) 3.00 (76.2)
F2.50 (63.5) 3.00 (76.2) 3.50 (88.9)
G1.25 (31.8) 1.50 (38.1) 2.00 (50.8) 2.50 (63.5)
H3.25 (82.6) Sq.
Code Diameter
NEMA Type 1 Indoor (Flush and Surface Trims)
A0.50 (12.7) ————
B1.25 (31.8) 1.50 (38.1) 1.75 (44.5) 2.00 (50.8) 2.50 (63.5)
NEMA Type 3R Outdoor
A0.50 (12.7) ————
B1.25 (31.8) 1.50 (38.1) 1.75 (44.5) 2.00 (50.8) 2.50 (63.5)
A
H
E
F
A
C
D
D
D
D
E
C
B
B
B
A
H
C
E
E
E
E
E
E
F
A
C
B
B
B
Box 19, 20 Box 22, 24
G
F
E
E
E
D
D
C
B
B
B
B
A
H
UB
H
UB
F
E
E
E
E
D
D
C
B
B
B
B
A
H
UB
H
UB
Box 42 Box 43, 46, 47
B
B
B
B
A
A
A
A
B
B
B
B
B
B
A
A
B
B
H
UB
NEMA Type 1—Indoor NEMA Type 3R—Outdoor
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 89
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Loadcenters and Circuit Breakers
Loadcenter Interiors
OEM Loadcenters Contents
Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Standards and Certifications. . . . . . . . . . . . . . . . . . . . . . . . . 90
Product Description
As a leader in the electrical
distribution equipment
business, Eaton has a
unique product offering for
equipment manufacturers,
panel builders and virtually
any OEM that has a need
for power distribution within
their equipment. The OEM
interior offering consists
of a wide variety of power
distribution options utilizing
components from Eaton’s CH
and BR loadcenter product
lines. With high-volume,
standardized products,
OEMs can expect to
receive high-quality products
covering configurations
meeting virtually any power
distribution need.
Coupled with Eaton’s
expertise in circuit breaker
design and manufacturing,
OEM interiors provide solid
power distribution and circuit
protection in a compact,
easy-to-install package.
Interiors are offered from
2 to 42 circuits and from
70 to 225A.
Quality
Built in ISO 9002 certified
manufacturing facilities,
customers can be assured
of the process quality in place
for the manufacture of these
products. Utilizing the latest
in computer-controlled
plating, painting, molding,
stamping and welding
processes, Eaton’s
customers have come to
expect consistent high-quality
from shipment to shipment.
Two Products Offer
Design Flexibility
As a manufacturer of two
lines of loadcenters, Eaton
is in a unique position to
offer the broadest range of
interiors in the market. Each
line has its own unique
characteristics that appeal
to various segments of the
market. OEM interiors are
UL recognized components
and are listed in either of
the following UL files: E8741
or E52977.
The CH interiors feature
100% copper bus and use
the CH 3/4-inch (19.1 mm)
wide circuit breaker, which
minimizes panel space.
Recognized by contractors
for its sturdy design, the
CH interior will appeal to
those customers seeking
an industrial quality bolted
bus bar and the space saving
of 3/4-inch (19.1 mm) per
bus stab. With a typical
12 circuit CH interior, this
space savings amounts
to an inch and a half savings
over its 1-inch (25.4 mm)
counterparts. The stab
rating of the CH interiors
is 140A maximum meaning
that the handle rating of
breakers mounted across
from one another may not
exceed 140A.
The BR interiors are
manufactured of formed,
plated aluminum or copper,
and use Eaton’s Type BR
1-inch (25.4 mm) wide circuit
breaker. This design affords
customers the most circuit
flexibility as many of these
interiors allow the installation
of standard single- and
two-pole breakers as well as
duplex (two poles in a 1-inch
(25.4 mm) space) or quadplex
(four poles in a 2-inch
(50.8 mm) space) breakers.
The stab rating of the BR
interiors is 200A maximum,
meaning that the handle
rating of the breakers that
are mounted across from
one another may not
exceed 200A.
The interiors are designed
for either horizontal (single-
row breaker mounting), or
vertical (double-row breaker
mounting). To comply with
National Electrical Code
(NEC) requirements, if
mounted horizontally, when
the breaker is ON, the handle
should be in the UP position.
When mounted vertically, the
handle toggles from left to
right, so this is not a concern.
90 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Loadcenters and Circuit Breakers
Loadcenter Interiors
Standards and Certifications
Class CTL
National Electrical Code
Paragraph 384-15 requires
branch circuit panelboards
to be provided with physical
means to prevent the
installation of more
overcurrent devices than
that number of which the
enclosure was designed,
rated and approved. Class
CTL Duplex, Quadplex and
twin breakers (identified
by a catalog number prefix
BD, BQ, BQC and CHT)
are equipped with a
UL listed rejection tab
over the line terminal.
All OEM interiors have
appropriately notched stabs
to accept these rejection
tab Class CTL breakers.
Duplex, Quadplex and twin
breakers manufactured
without the rejection tab
(identified by a catalog
number prefix BR, BRD
and CHNT) are available
for replacement purposes
in older interiors.
Federal Specifications
All loadcenter enclosures
meet Federal Specifications
W-P-115b, Type 1, Class 2
requirements.
All 120/240V breakers, both
1-inch (25.4 mm), 1/2-inch
(12.7 mm) and 3/4-inch
(19.1 mm) per pole meet
the requirement of Federal
Specifications W-C 375B/
Gen Type 1.
Canadian Standards
Association Listing
All single-pole and two-pole,
120/240V breakers, both
1-inch (25.4 mm), 1/2-inch
(12.7 mm) and 3/4-inch
(19.1 mm) per pole, 225A
maximum, are listed as
Certified by the Canadian
Standards Association, Guide
No. 69-11.19, Class 1432,
File 18328.
Underwriters
Laboratories Listing
All grounding bars
manufactured comply
with Underwriters
Laboratories standards
and are listed under
Guide No. DHJR, File
E31424, Volume W,
Section 17.
All circuit breakers 10A
and larger comply with the
Underwriters Laboratories
“Standard for Branch
Circuit and Service Circuit-
Breakers” UL 489; Guide
No. 60 10.2 File E31424, and
“Requirements for Wire
Connectors and Soldering
Lugs,” UL 486B, Guide
No. 461 10-C File E7830.
All Eaton breakers where
marked, are suitable for use
with 60/75ºC rated wire,
unless otherwise specified.
All devices comply with the
22 kAIC–10 kAIC UL series
connected components File
DKSY2 of the Recognized
Components Index.
Lighting and
Appliance Panelboards
Lighting and appliance
branch circuit panelboards are
defined in NEC (Article 384)
as “One having more than
10 percent of its overcurrent
devices rated 30A or less for
which neutral connections
are provided.” Article 384
also limits the number of
overcurrent devices (branch
circuit poles) to a maximum
of 42 in any one cabinet.
When the 42 poles are
exceeded, two or more
separate panels are required.
For more details and
engineering drawings,
see BR.31.02.S.E.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 91
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Loadcenters and Circuit Breakers
Loadcenter Interiors
Product Selection
Type BR Loadcenter Interior Assemblies
Ampere
Rating
Maximum Number 1-Inch (24.5 mm) UL File
Reference
Main Terminal Size
(Per Phase)
Standard
Package Quantity
Catalog
NumberSpaces Single Poles
Single-Phase Single Row Breaker Mounting—Aluminum Bus—120/240 Vac, Three-Wire
70 2 4 (1) #8–#2 AWG Cu/Al 20 24INT70B
125 2 4 E8741 (1) 1/0–#14 AWG Cu
2/0–12 AWG All
20 24INT125B
125 6 12 E52977 (1) 2/0–#14 AWG Cu/Al 20 612INT125SRB
Single-Phase Double Row Breaker Mounting—Aluminum Bus—120/240 Vac, Three-Wire
125 4 8 E8741 (1) 2/0–#14 AWG Cu/Al 20 48INT125B
125 6 12 E8741 (1) 2/0–#14 AWG Cu/Al 20 612INT125B
125 8 16 E8741 (1) 2/0–#14 AWG Cu/Al 20 816INT125B
125 12 812 E52977 (1) 2/0–#14 AWG Cu/Al 20 1212INT125B
125 12 24 E52977 (1) 2/0–#14 AWG Cu/Al 20 1224INT125B
125 16 24 E52977 (1) 2/0–#14 AWG Cu/Al 20 1624INT125B
125 20 24 E52977 (1) 2/0–#14 AWG Cu/Al 10 2024INT125B
125 24 24 E52977 (1) 2/0–#14 AWG Cu/Al 10 2424INT125B
200 8 16 E52977 (1) 300 kcmil–#1 AWG Cu/Al 20 816INT200B
200 12 24 E52977 (1) 300 kcmil–#1 AWG Cu/Al 20 1224INT200B
200 30 40 E52977 (1) 300 kcmil–#1 AWG Cu/Al 10 3040INT200B
200 42 42 E52977 (1) 300 kcmil–#1 AWG Cu/Al 10 4242INT225B
Single-Phase Double Row Breaker Mounting—Copper Bus—120/240 Vac, Three-Wire
125 8 16 E5297 (1) 2/0–#14 AWG Cu/Al 20 816INT125BC
125 12 12 E5297 (1) 2/0–#14 AWG Cu/Al 20 1212INT125BC
200 12 24 E5297 (1) 300 kcmil–#1 AWG Cu/Al 20 1224INT200BC
Three-Phase Double Row Breaker Mounting—Aluminum Bus—208Y/120 Vac, Four-Wire—240 Vac, Three-Wire—
120/240 Vac, Four-Wire Delta
125 12 34 E52977 (1) 2/0–#8 AWG Cu/Al 10 1224INT3125B
150 18 36 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 1836INT3150B
150 24 42 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 2442INT3150B
200 30 42 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 3042INT3200B
225 42 42 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 4242INT3225B
Three-Phase Double Row Breaker Mounting—Copper Bus—208Y/120 Vac, Four-Wire—240 Vac, Three-Wire—
120/240 Vac, Four-Wire Delta
125 12 24 E52977 (1) 2/0–#8 AWG Cu/Al 10 1224INT3125BC
200 12 24 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 1224INT3200BC
BR Loadcenter
Interior Assembly
92 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.4
Loadcenters and Circuit Breakers
Classified Circuit Breakers
Classified Breakers Contents
Description Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Product Description
Eaton UL classified
Replacement Circuit Breakers
are available in both 3/4-inch
Type CHQ and 1-inch Type
CL, single- and two-pole
configurations. These
breakers are classified as
direct replacements by
Underwriters Laboratories.
In addition to a UL listing,
they also come with a
15-year warranty.
Specified vs. UL Classified
Specified breakers are listed
by the manufacturer of the
panelboard for use in a
particular panel. This doesn’t
mean that the panelboard
manufacturer produced the
specified breaker; it merely
means that the panelboard
manufacturer has tested the
breaker in the panel. In fact,
through the years, Eaton has
manufactured thousands of
breakers for other panelboard
manufacturers.
UL classified breakers
are produced by one
manufacturer for use in
place of the breakers
specified on the panelboard.
Like specified breakers,
UL classified breakers have
been tested in the panels for
which they are approved.
Testing
Classified breakers are
tested exten
sively in
numerous General Electric
®
,
Siemens
®
, Murray
®
,
Thomas & Betts®, Square D®,
and Crouse-Hinds® panels.
The tests are con
ducted with
witnesses from Underwriters
Laboratories Inc. and involve
short-circuit,
temperature,
and insertion/withdrawal
applications. This level of
testing ensures
that the
breakers meet identified
standards and have been
found suitable by UL for
the specified purpose.
Understanding Classified
Breaker Terminology
Definitions
Specified circuit breaker—
each manufacturer lists
the brands of circuit
breakers that can be used
in their panelboards. Often,
manufacturers will not list
competitors as specified,
even though they are
suitable replacements.
Classified circuit breaker—
a breaker that is considered
suitable, by a qualified third-
party organization, for use
in another manufacturer’s
panelboard.
Listed breaker—the listing
of a circuit breaker is by an
independent third party. Eaton
classified breakers are listed
by UL.
Labeled breaker—a breaker
with a label affixed by an
independent third party.
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 93
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.4
Loadcenters and Circuit Breakers
Classified Circuit Breakers
Product Selection
Type CHQ Replacement Breakers for Square D Type QO Loadcenters
10 kAIC, 120 and 120/240 Vac
Type CHQ Classified Breakers 3/4-Inch (19.1 mm) per Pole
120 or 120/240 Vac, 10 kAIC
Type CHQ Ground Fault and Arc Fault Replacement Breakers for Square D Type QO Loadcenters
10 kAIC, 120 and 120/240 Vac
Type CHQ Ground Fault Breakers—5 Milliampere—
3/4-Inch (19.1 mm) per Pole, 10 kAIC
Type CHQ Surge Arrester
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole 120/240 Vac
Requires One
3/4-Inch (19.1 mm) Space
10 per Shelf Carton
Two-Pole 120/240 Vac
Common Trip Requires Two
3/4-Inch (19.1 mm) Spaces
5 per Shelf Carton
Catalog Number Catalog Number
15 (1) #14–8
(2) #14–10
CHQ115 CHQ215
20 CHQ120 CHQ220
25 CHQ125 CHQ225
30 CHQ130 CHQ230
35 CHQ135 CHQ235
40 CHQ140 CHQ240
45 CHQ145 CHQ245
50 CHQ150 CHQ250
60 — CHQ260
Ampere
Rating
Wire Size Range
Cu/Al 60ºC or 75°C
Single-Pole 120 Vac
Requires One
3/4-Inch (19.1 mm) Space
10 per Shelf Carton
Two-Pole 120/240 Vac
Common Trip Requires Two
3/4-Inch (19.1 mm) Spaces
5 per Shelf Carton
Catalog Number Catalog Number
15 (1) #14–8
(2) #14–10
CHQ115GF CHQ215GF
20 CHQ120GF CHQ220GF
25 CHQ125GF CHQ225GF
30 CHQ130GF CHQ230GF
35 — CHQ235GF
40 — CHQ240GF
45 — CHQ245GF
50 — CHQ250GF
Catalog Number
CHQSA
CHQ120 CHQ230
CHQ115GF CHQ220GF
94 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.4
Loadcenters and Circuit Breakers
Classified Circuit Breakers
Type CL Replacement Breakers for Square D HOMELINE, General Electric, Crouse-Hinds,
Thomas & Betts, Murray and ITE®/Siemens Loadcenters
Type CL Breakers, 1-Inch (25.4 mm) per Pole, 10 kAIC
Type CL Classified Arc and Ground Fault Breakers (5 Milliampere),
1-Inch (25.4 mm) per Pole, 10 kAIC
Type CL Classified Latching Remote Control Smart Breakers,
1-Inch (25.4 mm) per Pole, 10 kAIC
Ampere
Rating
Wire Size
Range Cu/Al
60°C or 75°C
Single-Pole 120/240V
Requires One
1-Inch (25.4 mm) Space
10 per Shelf Carton
Catalog Number
Two-Pole 120/240V
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
5 per Shelf Carton
Catalog Number
15 #14–4 CL115 CL215
20 #14–4 CL120 CL220
25 #14–4 CL125 CL225
30 #14–4 CL130 CL230
35 #14–4 CL135 CL235
40 #14–4 CL140 CL240
45 #14–4 CL145 CL245
50 #14–4 CL150 CL250
Ampere
Rating
Wire Size
Range Cu/Al
60°C or 75°C
Single-Pole 120/240V
Requires One 1-Inch (25.4 mm) Space
1 per Shelf Carton
Catalog Number
Arc Fault Breakers
15 #14–4 CL115AF
20 #14–4 CL115CAF
20 #14–4 CL120AF
20 #14–4 CL120CAF
Arc Fault/Ground Fault Breakers
15 #14–4 CL115AFGF
20 #14–4 CL120AFGF
Ground Fault Breakers
15 #14–4 CL115GF
20 #14–4 CL120GF
30 #14–4 CL130GF
Ampere
Rating
Wire Size
Range Cu/Al
60°C or 75°C
Single-Pole 120V
Requires One
1-Inch (25.4 mm) Space
10 per Shelf Carton
Catalog Number
Two-Pole 120/240V
Common Trip Requires Two
1-Inch (25.4 mm) Spaces
5 per Shelf Carton
Catalog Number
15 (2) #14–10 CLRP115 CLRP215
20 (2) #14–10 CLRP120 CLRP220
25 (1) #8–6 CLRP125 CLRP225
30 (1) #8–6 CLRP130 CLRP230
CL_
CL_AF
CLR_
Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com 95
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.4
Loadcenters and Circuit Breakers
Classified Circuit Breakers
Accessories
CHQ Breaker Accessories
Description
Catalog
Number
Breaker handle lock CHLO
Technical Data
Arc Fault Application Notes
An arc fault circuit interrupter
is a device intended to
provide protection from
the effects of arc faults by
recognizing characteristics
unique to arcing and by
functioning to de-energize
the circuit when the arc
fault is detected. As of
January 1, 2002, the
National Electrical Code
(NEC) requires all branch
circuits that supply 125V,
single-phase, 15 and 20A
receptacle outlets installed
in dwelling unit bedrooms
shall be protected by an arc
fault circuit interrupter(s).
This includes ceiling lighting
(recessed, ceiling fans, etc.)
as well as smoke detectors
and all other bedroom
outlets. The 2005 NEC
introduced the application of
the Combination Type AFCI
for bedroom circuits required
as of January 1, 2008. The
2008 NEC expands this
application to other living
areas.
Ground Fault
Application Notes
Single-pole GFCBs are
designed for use in two-wire,
120 Vac circuits. Drawing
on Page 96 shows a typical
wiring configuration.
Two-pole GFCBs are
designed for use in three-
wire, 120/240 Vac circuits,
120 Vac multiwire circuits
employing common, neutral
and two-wire, 240 Vac
circuits obtained from a
120/240 Vac source.
Drawings on Page 96
illustrate typical wiring
configurations for
120/240 Vac multiwire
circuits.
Drawing on Page 96 depicts
a 240 Vac, two-wire circuit.
Note the “panel neutral”
conductor connects to the
neutral bar, even though the
neutral is not included in the
load circuit. This connection
is necessary to supply a
120 Vac power source to the
ground fault sensing circuit.
The figures are shown with
a 120/240 Vac, single-phase,
three-wire power source,
ut are also applicable to a
120/208 Vac, three-phase,
four-wire power supply.
For all figures, the electrical
operation of the GFCB
is not affected by the
equipment ground.
96 Volume 1—Residential and Light Commercial CA08100002E—December 2010 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.4
Loadcenters and Circuit Breakers
Classified Circuit Breakers
Wiring Diagrams
Single-Pole 120V Load Application Sourced by 120/240 Vac
Two-Pole Shared Neutral with
Multi-Duplex Receptacle Application
Single-Pole 120V Duplex Receptacle Application
Two-Pole 120V Multi-Duplex Receptacle Application
Two-Pole 240V Load Application Sourced by 120/240 Vac
Two-Pole Shared Neutral with
Duplex Receptacle Application
Two-Pole 120V Duplex Receptacle Application
Two-Pole 240V Duplex Receptacle Application
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
Equipment Ground
NA B
120/240 Vac
Source
Two 120V
Duplex
Receptacles
Two-Pole
Line B
Line A
Neutral
Neutral
Equipment Ground
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
NA B
120/240 Vac
Source
Two 120V
Duplex
Receptacles
Two-Pole
Line B
Line A
Neutral
Neutral
Line B
NA B
120/240 Vac
Source
Line A 240V
Duplex
Receptacle
Two-Pole
Neutral
Equipment Ground
NAB
120/240 Vac
Source
Line A
120V Duplex
Receptacle
(With Line Side
Jumper Removed)
Two-Pole
Line B
Neutral
Neutral
Equipment Ground
NAB
120/240 Vac
Source
Line A
120V Duplex
Receptacle
(With Line Side
Jumper Removed)
Two-Pole
Line B
Neutral
Neutral
Line B
NA B
120/240 Vac
Source
Line A 240V
Duplex
Receptacle
Two-Pole
Neutral