PowerPact® Circuit
Breakers

D- and M-Frame Circuit Breakers
Class 612, 615 / Refer to Catalogs: 0612CT0101, 0616CT0801

www.schneider-electric.us

Table 7.51:
Electronic Trip
Unit Type

Standard

D-Frame (600 A 600 Vac) 3P 50/60 Hz Circuit Breaker with Lugs and Electronic Trip Unitsc
Trip
Function

Trip Unit

LS

STR23SP

LSI

SR53UP-Fb

LSIG

STR53UP-FTb

LSI

STR53UP-FIb

Ammeter
LSIG

STR53UP-FTIb

a
b
c

Table 7.52:

G Interrupting

Continuous
Currenta

J Interrupting

L Interrupting

150 A
250 A
400 A
600 A
150 A
250 A
400 A
600 A
150 A
250 A
400 A
600 A
150 A
250 A
400 A
600 A
150 A
250 A
400 A

Cat. No.
DGL36150E20
DGL36250E20
DGL36400E20
DGL36600E20
DGL36150E53
DGL36250E53
DGL36400E53
DGL36600E53
DGL36150E54
DGL36250E54
DGL36400E54
DGL36600E54
DGL36150E58
DGL36250E58
DGL36400E58
DGL36600E58
DGL36150E59
DGL36250E59
DGL36400E59

$ Price
5081.00
5081.00
5081.00
8315.00
6200.00
6200.00
6200.00
9429.00
7527.00
7527.00
7527.00
10761.00
7661.00
7661.00
7661.00
10895.00
8990.00
8990.00
8990.00

Cat. No.
DJL36150E20
DJL36250E20
DJL36400E20
DJL36600E20
DJL36150E53
DJL36250E53
DJL36400E53
DJL36600E53
DJL36150E54
DJL36250E54
DJL36400E54
DJL36600E54
DJL36150E58
DJL36250E58
DJL36400E58
DJL36600E58
DJL36150E59
DJL36250E59
DJL36400E59

$ Price
8478.00
8478.00
8478.00
8865.00
9597.00
9597.00
9597.00
9984.00
10925.00
10925.00
10925.00
11312.00
11058.00
11058.00
11058.00
11445.00
12387.00
12387.00
12387.00

Cat. No.
DLL36150E20
DLL36250E20
DLL36400E20
DLL36600E20
DLL36150E53
DLL36250E53
DLL36400E53
DLL36600E53
DLL36150E54
DLL36250E54
DLL36400E54
DLL36600E54
DLL36150E58
DLL36250E58
DLL36400E58
DLL36600E58
DLL36150E59
DLL36250E59
DLL36400E59

$ Price
9918.00
9918.00
9918.00
13586.00
11037.00
11037.00
11037.00
14705.00
12365.00
12365.00
12365.00
16032.00
12498.00
12498.00
12498.00
16166.00
13827.00
13827.00
13827.00

600 A

DGL36600E59

9434.00

DJL36600E59

12774.00

DLL36600E59

17495.00

(1) 2–600 Cu or (1) 2–500 Al
(2) 2/0–350 Cu or (2) 2/0–500 Al
(1) 2–600 Cu or (1) 2–500 Al
(2) 2/0–350 Cu or (2) 2/0–500 Al
(1) 2–600 Cu or (1) 2–500 Al
(2) 2/0–350 Cu or (2) 2/0–500 Al
(1) 2–600 Cu or (1) 2–500 Al
(2) 2/0–350 Cu or (2) 2/0–500 Al
(1) 2–600 Cu or (1) 2–500 Al
(2) 2/0–350 Cu or (2) 2/0 –
500 Al

D-frame circuit breakers 400 A and below are 100% rated. 600 A is
standard (80%) rated only.
F = Fault indicator; T = Residual-type ground-fault protection; I = Ammeter
Available with lugs (L) or bus (F) connections only.

D-Frame 3P 600 A Circuit Breaker, Frame Only, and Field-Installable Trip Units
Basic Frame Only (600 Vac)d

Ampere
Rating

Terminal Wire Range (AWG/kcmil)

G Interrupting

Field Installable D-Frame Electronic Trip Unit

J Interrupting

Cat. No.
$ Price
Cat. No.
150 A
DGL36150F40
2766.00 DJL36150F40
250 A
DGL36250F40
2766.00 DJL36250F40
400 A
DGL36400F40
2766.00 DJL36400F40
600 A
DGL36600F60
5904.00 DJL36600F60
d
Available with lugs (L) or bus (F) connections only.

Table 7.53:
Electronic Trip
Unit Type

L Interrupting

$ Price
6164.00
6164.00
6164.00
6456.00

Cat. No.
DLL36150F40
DLL36250F60
DLL36400F40
DLL36600F60

Long-time, Short-time and Instantaneous Protection

$ Price
7602.00
7602.00
7602.00
11177.00

Description
STR23SP
STR53UP-F
STR53UP-FT
STR53UP-FI
STR53UP-FTI

Factory Code
E20
E53
E54
E58
E59

Trip Function
LS
LSI
LSIG
LSI
LSIG

Cat. No.
36940
36942
36943
36944
36945

$ Price
2033.00
3152.00
4479.00
4613.00
5942.00

M-Frame 800 A, Basic Electronic Trip System Type ET 1.0e Factory-Sealed Trip Unit
Trip Function

G Interrupting

Sensor
Rating

Cat. No.

300 A
350 A
400 A
450 A
500 A
600 A
700 A
800 A

MGL26300
MGL26350
MGL26400
MGL26450
MGL26500
MGL26600
MGL26700
MGL26800

J Interrupting

$ Price

Cat. No.

$ Price

Terminal Wire Range
(AWG/kcmil)

Fixed
Long-time,
Adjustable
Instantaneous
Trip

Basic

MJL26300
MJL26350
MJL26400
MJL26450
MJL26500
MJL26600
MJL26700
MJL26800

7829.00
7829.00
7829.00
7829.00
7829.00
7829.00
9657.00
9657.00

(3) 3/0–500
Al/Cu

3P, 600 Vac 50/60 Hz

e

300 A
MGL36300
7560.00
MJL36300
9456.00
350 A
MGL36350
7560.00
MJL36350
9456.00
Fixed
400 A
MGL36400
7560.00
MJL36400
9456.00
Long-time,
450 A
MGL36450
7560.00
MJL36450
9456.00
(3) 3/0–500
Basic
Adjustable
Al/Cu
500 A
MGL36500
7560.00
MJL36500
9456.00
Instantaneous
Trip
600 A
MGL36600
7560.00
MJL36600
9456.00
11882.00
700 A
MGL36700
9927.00
MJL36700
800 A
MGL36800
9927.00
MJL36800
11882.00
The ET 1.0 trip unit cannot be field replaced or have the long-time trip point setting adjusted. It is considered an electronic equivalent of
a thermal-magnetic circuit breaker.

Table 7.54:
Frame

M-Frame Circuit Breaker
D-Frame

M-Frame

Table 7.55:

Termination Options

Termination
Letter
F
L
M
P
Nf
Df
Sf
F
L
M
P

Termination Option
No Lugs (Includes terminal nut kit on both ends)
Lugs both ends
Lugs ON end Terminal Nut Kit Off end
Lugs OFF end Terminal Nut Kit On end
Plug-in
Drawout
Rear Connected
No Lugs
Lugs both ends
Lugs ON end Terminal Nut Kit Off end
Lugs OFF end Terminal Nut Kit On end

Voltage

g

7

D-Frame Circuit Breaker

5960.00
5960.00
5960.00
5960.00
5960.00
5960.00
7719.00
7719.00

MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS

2P, 600 Vac 50/60 Hz

D- and M-Frame Interrupting Ratings
Interrupting Rating

G
J
240 Vac
65 kA
100 kA
480 Vac
35 kA
65 kA
600 Vac
18 kA
25 kA
L interrupting rating is not available in M-frame.

Lg
150 kA
100 kA
25 kA

For factory-installed termination, place termination letter in
the third block of the circuit breaker catalog number.

M G L 3 6 4 0 0 or D G L 3 6 4 0 0 E 2 0
Termination Letter
f
© 2009 Schneider Electric
All Rights Reserved

For N, D, and S pricing, add termination pricing to price. See page 7-42.

DE2

Discount
Schedule

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-36
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-39
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-55
Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-56

7-25

Selection Information

Molded Case Circuit Breakers
Class 600, 612, 800

www.schneider-electric.us

600 A L-Frame

Circuit Breaker Type
Number of Poles
Current Range

PowerPact 800 A M-Frame

PowerPact 1200 A P-Frame

1000 A M-Frame

LX

LXI

LE

MG

MJ

PG

PJ

PK

PL

MA

MH

MX

3

3

3

2, 3

2, 3

2, 3, 4

2, 3, 4

2, 3, 4

2, 3, 4

2, 3

2, 3

3

3

100–600

100–600

100–600

300–800

300–800

300–1200

450–800

450–800

100–1200 100–1200 100–1200 100–1200 300–1200

ME

Interrupting Ratings

UL/CSA/NOM
Rating
(kA RMS)
(50/60 Hzb)

240 Vac

100

200

100

65

100

65

100

65

125

42

65

65

65

480Y/277 Vac

65

200

65

35

65

35

65

50

100

30

65

65

65
65

480 Vac

65

200

65

35

65

35

65

50

100

30

65

65

600Y/347 Vac

35

100

35

18

25

18

25

50

25

22

25

25

25

600 Vac

35

100

35

18

25

18

25

50

25

22

25

25

25

DC Ratings
IEC
(kA RMS)
Icu/lcsc

250 Vdc

—

—

—

—

—

—

—

—

—

14

50

—

—

500 Vdca

—

—

—

—

—

—

—

—

—

—

20

—

—

240 Vac

—

—

—

50/25

65/35

50/25

65/35

50/25

125/65

—

—

—

—

35/20

50/25

35/20

50/25

50/25

85/45

415 Vac

IEC 50/60 Hz

65/65f
—
65/65f
For additional IEC ratings, see the
Supplemental Digest.

30/30
65/33
65/33
65/33
For additional IEC ratings, see the
Supplemental Digest.

Special Ratings
Fed. Specs W-C-375B/GEN

X

X

X

X

X

X

X

X

X

X

X

HACR (2P, 3P)

—

—

—

X

X

X

X

X

X

X

X

X

X

Unit Mount

X

X

X

X

X

X

X

X

X

X

X

X

X

I-Line®

X

X

X

X

X

X

X

X

X

X

X

X

X

Connections/Terminations

Rear Connection

—

—

—

—

—

—

—

—

—

X

X

—

—

Drawout

—

—

—

—

—

Xe

Xe

Xe

Xe

—

—

—

—

Optional Lugs

X

X

X

X

X

X

X

X

X

X

X

X

X

Shunt Trip

X

X

X

X

X

X

X

X

X

X

X

Xe

Xe

Undervoltage Trip

X

X

X

X

X

X

X

X

X

X

X

Xe

Xe

Auxiliary Switches

X

X

X

X

X

X

X

X

X

X

X

Xe

Xe

Alarm Switch

X

X

X

X

X

X

X

X

X

X

X

Xe

Xe

Motor Operator

—

—

—

—

—

Xe

Xe

Xe

Xe

X

X

—

—

Handle Operators

—

—

—

—

—

Xe

Xe

Xe

Xe

X

X

X

X

Mechanical Interlocks (3P)

—

—

—

—

—

X

X

X

X

Xd

Xd

—

—

Handle Padlock Attachment

X

X

X

X

X

X

X

X

X

X

X

X

X

Cylinder Lock (3P)

—

—

—

X

X

—

—

—

—

X

X

—

—

Optional GF Protection

Xe

Xe

Xe

—

—

X

X

X

X

—

—

Xe

Xe

Thermal-magnetic

—

—

—

—

—

—

—

—

—

X

X

—

—

Instantaneous-only (MCP)

—

—

—

—

—

—

X

X

—

X

X

—

—

Molded Case Switch (Automatic)

—

—

—

—

—

X

X

X

X

—

X

—

—

Electronic

X

X

X

X

X

X

X

X

X

—

—

X

X

MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS

Accessories and Modifications

7

Trip System Type

Enclosures (Pages 7-56–7-58)
General Purpose (NEMA 1)

—

—

—

X

X

X

X

X

X

X

X

X

X

Raintight (NEMA 3R)

—

—

—

X

X

X

X

X

X

X

X

X

X
X

Dust-tight (NEMA 12)

X

X

X

X

X

X

X

X

X

X

X

X

Watertight (NEMA 4, 4X, 5)

—

—

—

X

X

—

—

—

—

X

X

X

X

Explosion Proof (NEMA 7, 9)

—

—

—

—

—

—

—

—

—

—

—

—

—

Dimensions
(3P Unit Mount)

Note:
a
b
c
d
e
f

Height–in. (mm)

11.86 (301)

12.80 (325)

16.20 (413)

Width—in. (mm)

7.5 (190)

8.30 (210)

8.30 (210)

9 (229)

Depth—in. (mm)

6.74 (171)

8.10 (205)

8.10 (205)

6.5 (165)

Pages (Unit Mount)/(I-Line)
Page 7-52/9-28
Page 7-25/9-28
Page 7-26, 7-30, 7-33/9-29
All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted.
Ungrounded UPS systems only. See page 7-34.
UL PowerPact MG/MJ and PG/PJ/PK/PL are 60 Hz only.
Dual UL and IEC ratings and CE markings on circuit breakers. For additional IEC ratings, see the Supplemental Digest.
Requires breaker with WB suffix
Factory-installed option only.
65/50 kA Icu/Ics for 450–600 A ratings.

© 2009 Schneider Electric
All Rights Reserved

14 (356)

Supplemental Digest Section 3

7-7

Dimensions and Shipping Weights
Miniature and Molded Case Circuit Breakers
www.schneider-electric.us

A
G

A
G

A
G

Table 7.140:

D
C

QO®, QOU, Multi 9TM Circuit Breakers

Circuit Breaker
Cat. No. Prefix

B E

B E

B E

Figure 1

Figure 3

Figure 2
A
G

A
G

B

A
G

A
G

QO-GFI, QO-PL
QO-EPD

Figure 5

Figure 4

A
G

B E

Figure 6

D
C

E

E
B

B E

QO, QOB

D
C

F

B E

Figure 7

QOU, QYU
Low Ampere

Figure 8

A

D
C

A

A

B

Figure 9
QO-PLPS

Circuit Breaker
Cat. No. Prefix

B E

Figure 10

Figure 11

Figure 12

7

D
A

A

MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS

B

B

A

A

B

B

Figure 13

Figure 14

Figure 15

A

A

A

C

E

Figure 16

B

Figure 17
E

B

B

Figure 18

B
G

C

B E

B

Figure 19

Figure 20

C120

B
E

B
G
HH

F

G

—
—
—
—
—
—
—
—
5.00d
5.00d
5.00f
6.78
6.78
6.78
—
—
—
—
—

0.59
1.34
2.09
2.85
4.35
0.59
1.34
2.09
0.62
1.37
2.12
—
—
—
—
—
—
—
—

QB, QD, QG, QJ, Q4, FA, FI, KA, KC, KI, LA, LC, LI,
LE, LX, LXI, MA Circuit Breakers
Dimensions—Inches
D

E

F

G

H

2
3
1
2
3

22
23
21
22
23

6.47
6.47
6.00
6.00
6.00

3.00
4.50
1.50
3.00
4.50

3.02
3.02
3.16
3.16
3.16

3.93
3.93
4.13
4.13
4.13

g
g
0.44
0.44
0.44

4.25
4.25
5.13
5.13
5.13

—
1.50
1.50
—
1.50

—
0.75
—
—
0.75

FIL, KAL, KCL,
2&3
23
8.00
4.50
3.66 4.75 0.44
KHL, KIL
Q4L, LAL, LHL
2&3
23
11.00 6.00
4.06 5.84 0.88
LIL, LEL, LXL, LXIL, 2 & 3
24
11.86 7.50
5.48 6.74 0.55
LCL
MAL, MHL
2&3
23
14.00 9.00
4.53 6.50 1.66
g
Dimensions E are 1.59 in at ON end and 0.63 in at OFF end.

7.13

1.50

0.75

9.25

2.00

1.00

10.75

2.50

10.69

3.00

Frame Size

1.50

Shipping Weightsh
Approx. Shipping
Weight (Lbs.)

Approx. Shipping
Weight (Lbs.)

Frame Size

FAL, FHL 1P

2

KIL

9

FAL, FHL 2P

3

LAL, LHL

15

FAL, FHL 3P

5

LEL, LIL, LXL, LXIL, LCL

25

FIL

8

Q4L

15

QB, QD, QG, QJ

4

MAL, MHL

34

KAL, KHL

7

h

E

E
2.25
2.25
2.25
3.78
3.78
2.25
2.25
2.25
2.25
2.25
2.25
2.25
2.25
2.25
1.77
1.77
1.77
1.77
—

C

C60
D

D

B

Table 7.142:

A

C

A

FAL, FHL

QOU
High Ampere

B

Fig.
No.

B F

B E

A

Poles

QB, QD,
QG, QJ

B E

Dimensions—Inches

Fig.
No.

1
1
0.75 3.00a 2.31
2.91
QO, QOB
2
2
1.50 3.00a 2.31
2.91
3
3
2.25 3.00a 2.31
2.91
2
2
3.0
5.72
2.53
4.90
QOB-VH 150 A
QOB-VH 110–150 A
3
3
4.50
5.72
2.53
4.90
1
4
0.75 4.12b 2.31
2.91
QO-PL
QO-GFI
2
5
1.50 4.12b 2.31
2.91
QO-EPD
3
5
2.25 4.12b 2.31
2.91
1
6
0.75 4.05c 2.38
2.98
QOU
QYU
2
7
1.50 4.05c 2.38
2.98
Low Ampere
3
8
2.25 4.05d 2.38
2.98
1
10
0.75
4.45
2.37
2.96
QOU
2
11
1.50
4.45
2.37
2.96
High Ampere
3
12
2.25
4.45
2.37
2.96
1
13
0.71
3.19
1.73
2.76
2
14
1.42
3.19
1.73
2.76
Multi 9™ C60N
3
15
2.13
3.19
1.73
2.76
4
16
2.84
3.19
1.73
2.76
QO-PLPS Power Supply
2
9
1.45
4.35
2.42
3.11
a
35–70 A is 3.12 in; 80–100 A 2P and 70–100 A 3P are 3.50 in.
b
QO-PL is 4.55 in.
c
80–100 A 1P and 80–125 A 2P are 4.45 in
d
80–100 A 1P and 80–125 A 2P are 6.78 in.
e
70–100 A 4.45 in.
f
70–100 A is 6.78 in.

Table 7.141:

D
C

A

Poles

All weights are for 3P circuit breakers unless otherwise noted.

D
C

C/L
A F

C/L

A F
A F

E

E

Figure 21

Figure 22
B
G

E
D
C

Figure 23

E

A F

E

Figure 24

7-54

© 2009 Schneider Electric
All Rights Reserved

Mechanical Accessories
Used on Thermal-magnetic and Electronic Trip Circuit Breakers

www.SquareD.com
For the most up-to-date information

Electrical Operators
Provides remote ON, OFF/RESET control of molded case circuit breakers.
• A complete line of field-installable electrical operators.
• Not applicable on LC/LI/LE/LX/LXI, ME/MX, NA/NC/NE/NX, PG/PJ/PL, RG/RJ/RL
circuit breakers.
• Installing side mounted motor operators on non I-Line® circuit breakers requires the
use of a separate mounting pan.
KAMO2120AC
With KAL Circuit Breaker

• Side mounted electrical operators require an additional 41⁄2 in. (114 mm) of
mounting space in I-Line installations.
Circuit
Breaker
Prefix
FA, FH, FC
FAL, FHL,
FCL
FI, KA, KH,
KC, KI

6

CIRCUIT BREAKERS

FIL, KIL,
KAL, KHL,
KCL
LA, LH, Q4
LAL, LHL,
Q4L
MA, MH
MAL, MHL
PA, PH, PC,
PE, PX

Top Mount

Side Mount

Mounting Pan

Voltage

Catalog No.

Price

Voltage

Catalog No.

Price

Catalog No.

Price

...

...

...

120 Vac

FAMO1

$ 869.

...

...

...

...

...

120 Vac

FAMO1

869.

FAMOP

$ 72.

...

...

...

120 Vac

KAMO1

2337.

...

...

120 Vac
240 Vac
24 Vdc
125 Vdc
...
120 Vac
240 Vac
24 Vdc
125 Vdc
...
120 Vac
240 Vac
24 Vdc
125 Vdc

KAMO2120AC
KAMO2240AC
KAMO224DC
KAMO2125DC
...
LAMO2120AC
LAMO2240AC
LAMO224DC
LAMO2125DC
...
MAMO2120AC
MAMO2240AC
MAMO224DC
MAMO2125DC

$2312.
2312.
2312.
2312.
...
2987.
2987.
2987.
2987.
...
2987.
2987.
2987.
2987.

120 Vac

KAMO1

2337.

KAMOP

89.

120 Vac

LAMO1

3012.

...

...

120 Vac

PAMO2

120 Vac

LAMO1

3012.

LAMOP

123.

120 Vac

MAMO1

3012.

...

...

120 Vac

3520.

...

MAMO1

3012.

...

No. of Poles

...

MAMOP

123.

...

...

Catalog. No.

Used to lock the circuit breaker in the OFF position.
Circuit breaker cannot be reset when locked OFF.
Circuit
Breaker
Prefix
FA, FAL, FH, FHLa
KA, KAL, KH, KHLa
LA, LAL, LH, LHL, Q4
MA, MAL, MH, MHL

Catalog Number
Factory Inst.
Field Inst.
Suffix
Factory-installed
—CL
Only
LA1CL
Field-installable
Only
MA1CL

3

Circuit Breaker
Prefix

No. of
Poles

Price
$210.
210.
210.
210.

FKHT

$143.00

Catalog No.

Price

Handle Padlock Attachment (locks ON or OFF)
FY Series 1
Q2

1
2,3

HPAFYQ
HPAFYQ

$13.20
51.50

2,3

QBPA
QBPAFb

FA, FH, FC, FI
FY Series 2, KA, KH
KC, KI

1,2,3
2,3
2,3

HPAFK
HPAFK
HPAFKFb

16.10
16.10
21.70

LA, LH, MA, MH, Q4

2,3

HPALMc
HPAXLMd

17.30
18.40

QB, QD, QG, QJ

Price

Handle Tie
(2)FA
(2)KA,
(2)FI,(2)KI, or
(1)FI + (1)KI
(2)LA or
(2)Q4

Cylinder Lock

a Not available on Mag-Gard circuit breakers and molded case switches.

When remote indication of circuit breaker status is required, order circuit breaker with 1A-1B auxilliary switch for ONOFF Indication and alarm switch for TRIP Indication. Electrical operators require SPDT maintained contact switch. Refer
to Class 9001 control unit listing for operators and pilot lights.

Breaker Prefix

FAMO1 and FAMOP
With FAL Circuit Breaker

LC, LE, LI, LX, LXI

2,3

AHPALI

16.80

PA, PC, PH, PE, PX

2, 3

PAPAF

79.00

Handle Extension
2,3

FKHT

2,3

LAHT

143.00

MA, MH

2,3

MAHEX

63.00

331.00

LA, LC, LH, LE, LI,
LX, LXI, Q4

2,3

AHEXLI

63.00

California Title 24 Comb. Handle Tie and Lock Off
FY
FA

(3)1-pole
(3)1-pole

FY3HT
FA3HT

34.80
34.80

b Locks OFF only.
c MA and MH circuit breakers will not lock in ON position.
d Use with MAHEX handle extension.

Walking Beam Mechanical Interlock Components
Circuit Breaker
Prefix

Walking Beam Ass'y.

Mounting Pan

Suffix

Price
Adder

Catalog No.

Price

Catalog No.

Price

WB
WB
WB
WB

$164.
164.
164.
164.

FA4WB
KA4WB
LA6WB
MA9WB

$ 85.
85.
113.
136.

FAWBP4
KAWBP4
LAWBP6
MAWBP9

$118.
118.
161.
206.

WBMO
WBMO
WBMO
WB

$164.
164.
164.
164.

FA9WB
KA9WB
LA10WB
MA13WB

$127.
127.
135.
159.

FAWBP9
KAWBP9
LAWBP10
MAWBP13

$161.
161.
206.
286.

Manually Operated
FAL, FHL
KAL
LAL, LHL
MAL, MHL

Electrically Operated
FAL, FHL
KAL
LAL, LHL
MAL, MHL

Walking Beam Mechanical Interlock
Requires two circuit breakers with WB suffix,
one walking beam assembly and one mounting pan.

See pages 6-51–6-54 for Enclosures.
Fully enclosed interlocked units are available in Type 1 and Type 3R enclosures, with two neutrals provided
in each enclosure.The completely enclosed assembly is not UL Listed. Please consult your nearest
Square D/Schneider Electric sales office for more information.

Front Mounted Mechanical Interlock
Circuit Breaker
Prefix
Q2, QB, QD, QG, QJ

No. of
Poles
2, 3

Catalog No.

Price

QBMIK

$60.

See pages 6-40–6-42 for accessories for Powerpact® circuit breakers.
QBMIK

DE2

6-36
3/21/05

Discount
Schedule

© 2005 Schneider Electric
All Rights Reserved
3/21/05



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Modify Date                     : 2010:04:27 11:16:11+05:30
Create Date                     : 2010:04:27 11:03:59+05:30
Creator                         : Adobe InDesign CS3 (5.0)
Producer                        : Adobe PDF Library 8.0
Page Count                      : 5
EXIF Metadata provided by EXIF.tools

Navigation menu