GE CK Fact Sheet

2014-07-05

: Pdf 108640-Attachment 108640-Attachment 783164 Batch5 unilog

Open the PDF directly: View PDF PDF.
Page Count: 6

MicroVersaTripPlus
& MicroVersaTripPM
Conversion Kits for
GE Power Circuit Breakers
The easy, cost-effective
way to increase reliability,
enhance performance and
extend the life of your
existing equipment.
Easily replace electro-mechanical
trip units with the latest electronic,
digital trip unit technology
Ensure safe, reliable operation with
ANSI C37.59 tested kits
Improve system protection and
increase productivity by eliminating
nuisance tripping
Integrate mixed switchgear with kits
available for Westinghouse, I-T-E
& Allis Chalmers low voltage power
circuit breakers
GE Industrial Systems
GE AKU-2A-50
with MicroVersaTrip PM trip unit upgrade
Now upgrade your low-voltage
power circuit breakers with
electronic trip unit technology
Normal wear and tear of aging electro-mechanical
trip devices on low-voltage power circuit breakers
increases susceptibility to loss of calibration that
can subsequently jeopardize electrical power
system coordination, protection and reliability.
GE has channeled its decades of circuit breaker trip
system experience into the development of the
MicroVersaTrip®Plus and MicroVersaTrip®PM
conversion kits for GE, Westinghouse, I-T-E, and
Allis Chalmers low-voltage power circuit breakers.
ANSI C37.59 design verification tested to ensure safe,
reliable operation, these kits are designed to extend
the life of your mechanically sound breakers and…
Eliminate costly downtime due to nuisance
tripping
• Improve electrical power system coordination
and protection
• Permit easy upgrades to communicating Power
Management Control Systems (PMCS)
• Provide safe, convenient closed-door local
metering via the optional Remote Display
Standard and optional features
Standard MicroVersaTrip Plus and MicroVersaTrip
PM adjustable trip unit functions include:
• Current setting
• Long time
• Long time delay
• Instantaneous
• Local fault trip indicators
Optional features include:
• Short time
• Short time delay with or without I2t
• Ground fault
• Ground fault delay with or without I2t
• Switchable instantaneous/short time and ground
fault (off) (not UL approved for a listed breaker)
• Full function metering (MicroVersaTrip PM)
• Protective relaying (MicroVersaTrip PM)
• Industry standard open communications
capability (MicroVersaTrip PM)
• Remote display module
• Trip unit test set (TVRMS2)
MicroVersaTrip Plus conversion kit features
• Superior trip unit accuracy and system protection is achieved by
taking 64 samples per 60 Hz cycle. This provides true RMS sensing
of electrical distribution systems that include AC and DC variable
speed drives, rectifiers, induction heaters and other loads that
contribute to non-sinusoidal (high-harmonic) current wave forms.
Easy system coordination with maximum flexibility is obtained
using multiple trip setpoints, time-delay bands and ramp time
functions.
• Visual pickup and trip indicators for overload, short circuit and
ground fault, display type of fault,
phase and current magnitude when
applicable
• Predictive and preventative
maintenance decisions are made
easily using the trip operations
counter that stores the total number
of Long time, Short time,
Instantaneous and Ground Fault
trips.
• Continuously self-testing micro-
processor eliminates trip unit
bench-testing
Non-volatile memory
• High-visibility LCD display
• Cold setup capability and target
viewing from long-life (5-year)
field- replaceable lithium battery – external power not required
Positive setpoint recognition, values flash until entered and
accepted
• Easy access 5-button keypad with positive action
• Phase selectable ammeter (±2% accuracy)
Sealable, clear Lexan protective cover over LCD display and
“Enter” key prevents unauthorized access to protective functions
and target reset
Interchangeable rating plug
• Quick-disconnect trip unit design speeds installation and allows for
easy upgrade to MicroVersaTrip PM units with communications
capability, full-function metering and optional protective relaying
functions
AKO25 C 3 F 06 02 PM
1.Only applicable to trip units with ground fault
2.Not applicable for converting breakers equipped with Power Sensor -contact factory
3.Contact the factory for stationary breaker applications
4.Available only for MicroVersaTrip™ or MicroVersaTrip™ RMS-9 type AKR breakers equipped with fixed current sensors
5.Only available on AKR-75 breaker frames
6.Order rating plug separately, see chart on facing page
7.For converting AK-2 version breakers and newer, not applicable for AK-1 or AKR
8.Breakers equipped with older style open fuse lockout devices (OFLO), must be retrofitted with newer style OFLO device prior to conversion process.
Order replacement OFLO kits as follows: AKU-50 - order OFLO kit #121C287OG2, AK-75 - order OFLO kit #121C287OG3, AK-100 - order OFLO kit #121C287OG4
9.High range instantaneous trip function option (H) only available for AKO25 conversion kits
Easy conversion kit and
rating plug catalog number selection
Catalog Number Structure
Breaker
AK-1-15 = AK115
AK-15 = AKO157
AK-1-25 =AK125
AK-25
AKU-25 = AKO257
AKR-30
AKR-30H = AKR30
AKRU-30
AKR-30S
AKRU-30S = AKR3S
AK-1-50 =AK150
AK-50
AKU-508
AKT-50 = AKO507
AKS-50
AKSU-508
AKST-50
AKR-50
AKR-50H
AKRU-50
AKRT-50
AKRT-50H = AKR502
AKJ-50
AKJ-50H
AKJT-50
AKJT-50H
AK-758= AKO753
AKR-75 = AKR753
AK-1008= AKO103
AKR-100 = AKR103
AKW-100 = AKW103
Model
C= Generation
Wiring
3 Wire = 3
4 Wire1=4
Sensor Type
F= Fixed CTs
Sensor Rating Selection
Frame Breaker Catalog Numbers Sensors
225 AK-1-15 150A
AK-15 225A
AK-1-25 150A
600 AK-25 225A
AKU-25 600A
AKR-30, AKR-30H 150A
800 AKRU-30 400A
AKR-30S, AKRU-30S 800A
1600 AK-1-50, AK-50, AKU-50, AKS-50, AKSU-50 800A
AKR-50, AKR-50H, AKRU-50, AKJ-50, AKJ-50H 1600A
2000 AKT-50, AKST-50, AKRT-50, AKRT-50H, AKJT-50, AKJT-50H 2000A
3000 AK-75 3000A
3200 AKR-75 3200A
4000 AK-100, AKR-100, AKW-100 4000A
Sensor Rating6
150A = 01
no CTs4=XA
225A = 02
400A = 04
no CTs4=XC
600A = 06
800A = 08
no CTs4=XE
1600A = 16
no CTs4=XF
2000A = 20
no CTs4=XG
3000A = 30
3200A5=32
no CTs4,5=XI
4000A = 40
no CTs4=XJ
Trip Functions
LI = 02
LIG = 03
LSI = 04
LSIG = 05
LS = 06
LSG = 07
LSIGX = 08
LH9=09
LHG9=10
LSH9=11
LSHG9=12
Trip Unit Functions
LI Long Time & Instantaneous
LIG Long Time, Instantaneous
& Ground Fault
LSI Long Time, Short Time
& Instantaneous
LSIG Long Time, Short Time,
Instantaneous & Ground Fault
LS Long Time & Short Time
LSG Long Time, Short Time
& Ground Fault
LSIGX Long Time, Short Time/Inst. &
Switchable Ground Fault (off), not
approved for a UL Listed breaker
LH Long Time & High-Range
Instantaneous
LHG Long Time, High-Range
Instantaneous & Ground Fault
LSH Long Time, Short Time &
High-Range Instantaneous
LSHG Long Time, Short Time, High-Range
Instantaneous & Ground Fault
Options
Blank= Plus
M= Metering &
Communication
PM = Metering,
Communication &
Protective Relaying
(Rating plugs priced and ordered separately)
For details and ordering information, contact your local ED&C sales office, or visit us at www.ge.com/industrialsystems
Frame Size Sensor Rating Current Rating Current Range Rating Plug
(Amps) (Amps) (Amps) (Amps) Catalog No.
60 30-66 TR1B60
80 40-88 TR1B80
225 150 100 50-110 TR1B100
125 63-138 TR1B125
150 75-165 TR1B150
225 100 50-110 TR225B100
or 225 150 75-165 TR225B150
600 225 113-248 TR225B225
300 150-330 TR6B300
400 200-440 TR6B400
600 600 450 225-495 TR6B450
500 250-550 TR6B500
600 300-660 TR6B600
60 30-66 TR1B60
80 40-88 TR1B80
800 150 100 50-110 TR1B100
125 63-138 TR1B125
150 75-165 TR1B150
150 75-165 TR4B150
200 100-220 TR4B200
800 400 225 113-248 TR4B225
250 125-275 TR4B250
300 150-330 TR4B300
400 200-440 TR4B400
300 150-330 TR8B300
400 200-440 TR8B400
800 450 225-495 TR8B450
or 800 500 250-550 TR8B500
1600 600 300-660 TR8B600
700 350-770 TR8B700
800 400-880 TR8B800
Frame Size Sensor Rating Current Rating Current Range Rating Plug
(Amps) (Amps) (Amps) (Amps) Catalog No.
600 300-660 TR16B600
800 400-880 TR16B800
1600 1600 1000 500-1100 TR16B1000
1100 550-1210 TR16B1100
1200 600-1320 TR16B1200
1600 800-1760 TR16B1600
800 400-880 TR20B800
1000 500-1100 TR20B1000
2000 2000 1200 600-1320 TR20B1200
1500 750-1650 TR20B1500
1600 800-1760 TR20B1600
2000 1000-2200 TR20B2000
1200 600-1320 TR30B1200
1600 800-1760 TR30B1600
3000 3000 2000 1000-2200 TR30B2000
2500 1250-2750 TR30B2500
3000 1500-3300 TR30B3000
1200 600-1320 TR32B1200
3200 3200 1600 800-1760 TR32B1600
2400 1200-2640 TR32B2400
3200 1600-3520 TR32B3200
1600 800-1760 TR40B1600
2000 1000-2200 TR40B2000
4000 4000 2500 1250-2750 TR40B2500
3000 1500-3300 TR40B3000
3600 1800-3960 TR40B3600
4000 2000-4400 TR40B4000
Easy conversion kit and
rating plug catalog number selection
Rating Plugs
MicroVersaTrip
®
PM conversion kits—
Power management made easy
The enhanced MicroVersaTrip PM trip unit adds power
management system capability – including advanced
metering and protective relaying – to the basic functions of
the MicroVersaTrip Plus. When connected to GE’s Power
Management Control System (PMCS), it gives you the power
to increase productivity and reduce costs while meeting all
your electrical system monitoring needs. You can easily:
• Use standard graphics packages that allow the end user to
view custom one-lines for metering and trending screens
• Analyze energy consumption and power factor trends
to minimize utility demand and PF charges or provide
low-cost allocations
• Collect precise sequences of alarm and event information
to speed diagnosis and minimize downtime
• Use alarm and event logs to assist with preventive
maintenance interval planning
• Analyze system harmonics (with data input from PQM,
EPM 3710, EPM 3720 or EPM 7700 meters)
• Communicate with other devices, including Spectra
Series™ molded case and Power Break™ insulated
case breakers, full-function electronic power meters,
programmable logic controllers, GE Multilin protective
relays and “smart” motor starters
• Utilize GE’s Power Management Control System and its
industry standard Modbus RTU, Ethernet TCP/IP
open protocols
Optional Remote Display
Provides safe, convenient closed-door access to breaker metering, status
and setup functions
Available for use with either MicroVersaTrip®Plus or MicroVersaTrip PM
trip units
Rugged NEMA Type 1 enclosure with LCD display and keypad
Mounts easily on outside of breaker compartment door
Sealable, clear Lexan protective cover over display and “Enter” key
prohibits unauthorized trip setting changes
Connects to breaker trip unit via tough non-flammable, non-toxic 20-pin
plug-in cable for fast installation
Breaker trip unit operates independently if cable is disconnected
Additional features
• Full-function metering* including
– current (Amps, kAmps)
– voltage (Ph-Ph, Ph-N)
– energy (kWh, MWh, GWh)
– real power (kW, MW)
– total power (kVA, MVA)
– frequency (Hz)
– demand & peak demand (avg. kW, MW)
• Optional protective relaying* functions include
– undervoltage
– overvoltage
– voltage unbalance
– current unbalance
– power reversal
– power direction setup
*Requires potential transformer and
voltage conditioner inputs (not included
in kits – auxiliary panels sold separately)
GE Industrial Systems
General Electric Company
41 Woodford Avenue, Plainville, CT 06062
www.ge.com/edc
© 1998 General Electric Company
For details on other MicroVersaTrip Plus and MicroVersaTrip PM
conversion kits, ask your ED&C sales engineer for these publications:
DET-067B MicroVersaTrip Plus & MicroVersaTrip PM Conversion
Kits for I-T-E Power Circuit Breakers
DET-093B MicroVersaTrip Plus & MicroVersaTrip PM Conversion
Kits for Westinghouse Power Circuit Breakers
DET-226 MicroVersaTrip Plus & MicroVersaTrip PM Conversion
Kits for Allis Chalmers Power Circuit Breakers
DEE-019 GE POWER LEADER™ Product Information
DEP-041 MicroVersaTrip Plus & MicroVersaTrip PM Remote
Display
DEP-056A PMCS Auxiliary Panel Components - Pricing &
Selection Guide
GEP-1100 GE Buylog
(Reference for Power Management Components)
DET-066B 1198 BL
Everything you need in one package
GE’s MicroVersaTrip Plus™ and MicroVersaTrip PM™ kits
are shipped complete with detailed installation instructions
and everything needed for fast and easy trip unit
conversions.
All kits come complete with:
• Digital solid-state trip unit with quick disconnect
• Direct-acting flux shifter with automatic reset
• Epoxy encapsulated high-accuracy current transformers
• Specially designed mounting hardware and wire harnesses
with communications cable for each breaker frame
• Detailed instruction manual
• Interchangeable rating plug (order separately)