Manual motor protectors
Product index

M
an
pr ual
ot
ec mot
to or
rs

4

4 - Manual motor protectors

Manual motor protectors............................................ 4.1 – 4.34
Features and benefits..................................................................................................................4.1
General information
Suitable applications.......................................................................................................4.2 - 4.3
Motor ratings..........................................................................................................................4.4
Pilot duty ratings and overload trip classes.............................................................................4.5
Ordering details
Type MS116...........................................................................................................................4.6
Type MS132...........................................................................................................................4.7
Type MS450 /MS451..............................................................................................................4.8
Type MS495 / MS496.............................................................................................................4.9
Accessories............................................................................................................4.10, 4.12 - 4.16
Actuation tables.........................................................................................................................4.11
Connection diagrams................................................................................................................4.17
General accessory mounting layout...........................................................................................4.18
Technical data.................................................................................................................4.19 - 4.31
Approximate dimensions.................................................................................................4.32 - 4.33

4.A

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

or
ot
l m rs
ua cto
n
e
a
M rot
p

Notes

4

4.B	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Manual motor protectors
Types MS116, MS132, MS45x,

M MS
an Se
pr ual ries
ot m
ec ot
MS49x
to or
rs

4
Manual motor protectors are electromechanical devices for motor and circuit protection. These
devices offer local motor disconnect means, manual ON/OFF control, and protection against short
circuit, overload, and phase loss conditions. Manual motor protection saves cost, panel space, and
ensures quick and reliable short-circuit protection by reacting within milliseconds. Close coupling
adaptors are available for combination with ABB contactors in various applications.

Type MS116
•	 Manual motor protectors suitable for use with single and three phase motors up to 25 hp
•	 Suitable as motor disconnect in single motor applications and group motor installations as outlined in NEC Article 430.53(C)
•	 15 thermal setting ranges from 0.16 to 32 Amperes, overload Class 10A
•	 Phase loss sensitivity per IEC/EN 60947-4-1
•	 Short circuit current ratings up to 30 kA
•	 Motor controllers, manual (NLRV, NLRV7), UL file E137861

Manual motor

Protectors

Type MS132
•	 Manual motor protectors suitable for use with single and three phase motors up to 25 hp
•	 Suitable as motor disconnect in single motor applications and group motor installations as outlined in NEC Article 430.53(C)
•	 Suitable for Tap conductor protection as outlined in NEC Article 430.53(D)(3)
•	 Suitable as self-protected combination motor controllers Types E and F as outlined in
UL 508 and UL 60947-4-1A
•	 15 thermal setting ranges from 0.16 to 32 Amperes, overload Class 10
•	 Phase loss sensitivity per IEC/EN 60947-4-1
•	 Short circuit current ratings up to 65 kA
•	 Motor controllers, manual (NLRV, NLRV7), UL file E137861
•	 Combination motor controllers (NKJH, NKJH7), UL file E345003

Type MS45x
•	 Manual motor protectors suitable for use with single and three phase motors up to 50 hp
•	 Suitable as motor disconnect in single motor applications and group motor installations as outlined in NEC Article 430.53(C)
•	 Suitable as self-protected combination motor controller Type E as outlined in UL 508
and UL 60947-4-1A
•	 Phase loss sensitivity per IEC/EN 60947-4-1
•	 3 thermal setting ranges from 28 to 50 Amperes, overload Classes 10 and 20
•	 Short circuit current ratings up to 65 kA
•	 Motor controllers, manual (NLRV), UL file E167205
•	 Combination motor controllers (NKJH, NKJH7), UL file E195536

Type MS49x
•	 Manual motor protectors suitable for use with single and three phase motors up to 100 hp
•	 Suitable as motor disconnect in single motor applications and group motor installations as outlined in NEC Article 430.53(C)
•	 Suitable as self-protected combination motor controller Types E as outlined in UL 508
and UL 60947-4-1A
•	 Phase loss sensitivity per IEC/EN 60947-4-1
•	 6 thermal setting ranges from 28 to 100 Amperes, overload Classes 10 and 20
•	 Short circuit current ratings up to 65 kA
•	 Motor controllers, manual (NLRV), UL file E167205
•	 Combination motor controllers (NKJH, NKJH7), UL file E195536

4.1

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

General information
Suitable applications

Single motor applications, suitable as motor disconnect
A manual motor protector is a simple, compact and economical alternative to conventional magnetic motor
controllers for local control of a single motor.

4

Upstream short-circuit and overcurrent protection in the form of either fuses or a circuit breaker is still required.
Manual motor protectors can replace the overload relay, contactor, and any wiring or components necessary for
controlling a contactor (i.e. pushbuttons) by utilizing the integral rotary handle for manual ON/OFF control.
Manual motor protectors also offer instantaneous (magnetic only) short-circuit trip functionality, allowing for
these devices to be utilized as UL 508/60947-4-1A circuit protectors.
MS Series Manual Motor Protectors are marked as “suitable as motor disconnect”, with the Types MS132 and
MS4xx not requiring additional accessories. This marking allows the devices to be utilized as local disconnects
within line-of-sight of the motor.

Group motor installation
Group motor installations utilize a single branch circuit protective device to protect multiple loads. Per NEC
Article 430.53(C), this branch circuit protection must be in the form of either fuses or an inverse-time (thermal
magnetic, MCCB) circuit breaker. Individual overload protection must be provided for each load. Devices
utilized in group motor installations must be marked as suitable in such applications.
Branch circuit protection for group motor installations is sized based on the sum of:
1. 250% (MCCB) or 175% (fuses) of the full-load current of the largest load in the group, plus
2. The sum of the full-load current of all additional loads
Conductors on the load side of the branch circuit protective device are sized in accordance with the full-load
current rating of said device.
In addition to meeting the requirements outlined above, Type MS132 devices are also suitable for tap conductor
protection in group installations as outlined in NEC Article 430.53(D), allowing the conductors on the load-side
of the branch circuit protective device to be sized no less than one-tenth (1/10) of the full-load current rating of
the protective device.

Devices suitable for these applications
Application

Manual motor protector type
MS116

MS132

MS45x

MS49x

Motor disconnect

•

•

•

•

Group motor installation

•

•

•

•

Tap conductor protection

•

4.2	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

General information
Suitable applications
Combination motor controllers Types E & F
Combination motor controllers, as outlined in UL 508 Section 76, are a manufacturer’s tested combination of either individual
discrete components or a single controller. Fulfilling all the necessary components for a motor branch circuit, combination
motor controllers provide a disconnecting and load switching means, as well as overload and short-circuit protection. These
devices offer additional flexibility when selecting components for motor control and protection.

4

Combination motor controllers can also utilize busbar for self-protected, multiple motor installations. Busbar must be selected
and sized in accordance with the full-load current rating of the feeder circuit protective device.

Definitions
Type E Combination Motor Controllers are comprised of a UL 508 Disconnect, Branch Circuit Protector Device, Motor Controller
and Motor Overload typically included in a single Self-protected Control Device (manual motor protector). Following a shortcircuit fault, Type E Combination Motor Controllers are tested to operate for 6,000 electrical cycles, plus an additional 4,000
mechanical cycles, as outlined in UL 508 Table 83.1.
Type F Combination Motor Controllers are comprised of a UL 508 Disconnect, Branch Circuit Protector Device, and Motor
Overload typically included in a single Manual Self-protected Combination Controller with additional Magnetic or Solid State
Motor Controller utilized for remote operation (manual motor protector + contactor). The operational requirements following a
short-circuit fault differ for the manual motor protector and contactor.

Devices suitable for these applications
Combination motor
controller

Manual motor protector type
MS116

MS132 + S1-M3-xx

MS45x-xxE

MS49x-xxE

Self-protected, Type E

•

•

•

Self-protected,Type F

•

4.3

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

General information
Motor ratings

Horsepower to full-load Amperes for AC induction motors
Full Load Amperes (FLA)

4

Horsepower (hp)

110…120 v ac

200 v ac

208 v ac

220…240 v ac

380…415 v ac

440…480 v ac

550…600 v ac

Single
phase

Three
phase

Single
phase

Three
phase

Single
phase

Three
phase

Single
phase

Three
phase

Single
phase

Three
phase

Single
phase

Three
phase

Single
phase

Three
phase

1/10

3.0

-

-

-

-

-

1.5

-

1.0

-

-

-

-

-

1/8

3.8

-

-

-

-

-

1.9

-

1.2

-

-

-

-

-

1/6

4.4

-

2.5

-

2.4

-

2.2

-

1.4

-

-

-

-

-

1/4

5.8

-

3.3

-

3.2

-

2.9

-

1.8

-

-

-

-

-

1/3

7.2

-

4.1

-

4.0

-

3.6

-

2.3

-

-

-

-

-

1/2

9.8

4.4

5.6

2.5

5.4

2.4

4.9

2.2

3.2

1.3

2.5

1.1

2.0

0.9

3/4

13.8

6.4

7.9

3.7

7.6

3.5

6.9

3.2

4.5

1.8

3.5

1.6

2.8

1.3

1

16.0

8.4

9.2

4.8

8.8

4.6

8.0

4.2

5.1

2.3

4.0

2.1

3.2

1.7

1-1/2

20.0

12.0

11.5

6.9

11.0

6.6

10.0

6.0

6.4

3.3

5.0

3.0

4.0

2.4

2

24.0

13.6

13.8

7.8

13.2

7.5

12.0

6.8

7.7

4.3

6.0

3.4

4.8

2.7

3

34.0

19.2

19.6

11.0

18.7

10.6

17.0

9.6

10.9

6.1

8.5

4.8

6.8

3.9

5

56.0

30.4

32.2

17.5

30.8

16.7

28.0

15.2

17.9

9.7

14.0

7.6

11.2

6.1

7-1/2

80.0

44.0

45.0

25.3

44.0

24.2

40.0

22.0

27.0

14.0

21.0

11.0

16.0

9.0

10

100.0

56.0

57.5

32.2

55.0

30.8

50.0

28.0

33.0

18.0

26.0

14.0.

20.0

11.0

15

135.0

84.0

-

48.3

-

46.2

68.0

42.0

44.0

27.0

34.0

21.0

27.0

17.0

20

-

108.0

-

62.1

-

59.4

88.0

54.0

56.0

34.0

44.0

27.0

35.0

22.0

25

-

136.0

-

78.2

-

74.8

110.0

68.0

70.0

44.0

55.0

34.0

44.0

27.0

30

-

160.0

-

92.0

-

88.0

136.0

80.0

87.0

51.0

68.0

40.0

54.0

32.0

40

-

208.0

-

120.0

-

114.0

176.0

104.0

112.0

66.0

88.0

52.0

70.0

41.0

50

-

260.0

-

150.0

-

143.0

216.0

130.0

139.0

83.0

108.0

65.0

86.0

52.0

60

-

-

-

177.0

-

169.0

-

154.0

-

103.0

-

77.0

-

62.0

75

-

-

-

221.0

-

211.0

-

192.0

-

128.0

-

96.0

-

77.0

100

-

-

-

285.0

-

273.0

-

248.0

-

165.0

-

124.0

-

99.0

125

-

-

-

359.0

-

343.0

-

312.0

-

208.0

-

156.0

-

125.0

150

-

-

-

414.0

-

396.0

-

360.0

-

240.0

-

180.0

-

144.0

200

-

-

-

552.0

-

528.0

-

480.0

-

320.0

-

240.0

-

192.0

250

-

-

-

-

-

-

-

604.0

-

403.0

-

302.0

-

242.0

300

-

-

-

-

-

-

-

722.0

-

482.0

-

361.0

-

289.0

350

-

-

-

-

-

-

-

828.0

-

560.0

-

414.0

-

336.0

400

-

-

-

-

-

-

-

954.0

-

636.0

-

477.0

-

382.0

450

-

-

-

-

-

-

-

1030.0

-

-

515.0

-

412.0

500

-

-

-

-

-

-

-

1180.0

-

786.0

590.0

-

472.0

-

Full-load motor-running currents in Amperes corresponding to various AC horsepower ratings as published in Table 50.1 of UL 508.	

4.4	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

General information
Pilot duty ratings and overload trip classes
Pilot duty ratings for AC control circuit contacts
Contact rating
designation

Continuous
thermal, test
current (A)

Maximum current, 50/60 Hz (A)
120 v ac

240 v ac

480 v ac

600 v ac

Volt-amperes

Make

Break

Make

Break

Make

Break

Make

Break

Make

Break

A150

10

60

6.00

-

-

-

-

-

-

7200

720

A300

10

60

6.00

30

3.00

-

-

-

-

7200

720

A600

10

60

6.00

30

3.00

15

1.50

12

1.20

7200

720

B150

5

30

3.00

-

-

-

-

-

-

3600

360

B300

5

30

3.00

15

1.50

-

-

-

-

3600

360

B600

5

30

3.00

15

1.50

7.5

0.75

6

0.60

3600

360

C150

2.5

15

1.5

-

-

-

-

-

-

1800

180

C300

2.5

15

1.5

7.5

0.75

-

-

-

-

1800

180
180

C600

2.5

15

1.5

7.5

0.75

3.75

0.375

3.00

0.30

1800

D150

1.0

3.60

0.60

-

-

-

-

-

-

432

72

D300

1.0

3.60

0.60

1.80

0.30

-

-

-

-

432

72

E150

0.5

1.80

0.30

-

-

-

-

-

-

216

36

4

Mechanical switching ratings and test values as published in Table 1-4-1 of NEMA ICS 5-2000 (R2005, R2010)

Pilot duty ratings for DC control circuit contacts
Contact rating
designation

Maximum current, 50/60 Hz (A)

Continuous
thermal, test
current (A)

120 v dc

250 v dc

301 to 600 v dc

Volt-amperes

Make / Break

Make / Break

Make / Break

Make / Break

N150

10

2.2

-

-

275

N300

10

2.2

1.1

-

275

N600

10

2.2

1.1

0.40

275

P150

5.0

1.1

-

-

138

P300

5.0

1.1

0.55

-

138

P600

5.0

1.1

0.55

0.20

138

Q150

2.5

0.55

-

-

69

Q300

2.5

0.55

0.27

-

69

Q600

2.5

0.55

0.27

0.10

69

R150

1.0

0.22

-

-

28

R300

1.0

0.22

0.11

-

28

Mechanical switching ratings and test values as published in Table 1-4-1 of NEMA ICS 5-2000 (R2005, R2010)

Overload trip classes
Trip class

Tripping time Tp (seconds)

10A

2 < Tp ≤ 10

10

4 < Tp ≤ 10

20

6 < Tp ≤ 20

30

9 < Tp ≤ 30

Trip classes as published in Table 2 of UL 60947-4-1A.

Pilot duty rating explanation
A - 600
Max. thermal
current

Max. voltage

4.5

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Type MS116
For applications up to 32A

Suitable applications:
• Single motor, suitable as motor
	disconnect

4

• Group motor installation

	
Frame Sz. 1	
Frame Sz. 2
	MS116-0.16…MS116-16	 MS116-20…MS116-32

MS116 Electrical ratings 1
Thermal setting
range (A)

Trip
class

Rated
operational current
Ie (A)

Rated instantaneous short-circuit
current setting
Ii (A)

0.10...0.16

10A

0.16

1.56

0.16...0.25

10A

0.25

2.44

0.25...0.40

10A

0.40

3.90

0.40...0.63

10A

0.63

6.14

0.63...1.0

10A

1.00

11.5

1.0...1.6

10A

1.60

18.4

1.6...2.5

10A

2.50

28.8

2.5...4.0

10A

4.00

50.0

AC Motor ratings, breaking all lines, 50/60 Hz (hp)
Single phase 2
120V

Catalog
number

Three phase
240V

240V

480V

600V

Horsepower not applicable; use upper limit of the device thermal setting range for rated
full-load
current in Amperes

1/10

MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63

1/2

MS116-1.0

3/4

3/4

MS116-1.6

1/6

1/2

1

1.5

MS116-2.5

1/8

1/3

1

2

3

MS116-4.0

4.0...6.3

10A

6.30

78.8

1/4

1/2

1.5

3

5

MS116-6.3

6.3...10.0

10A

10.0

150

1/2

1.5

3

5

7.5

MS116-10

8.0...12.0

10A

12.0

180

1/2

2

3

7.5

10

MS116-12

10.0...16.0

10A

16.0

240

1

2

5

10

10

MS116-16

16.0...20.0

10A

20.0

300

1.5

3

5

10

15

MS116-20

20.0...25.0

10A

25.0

375

2

3

7.5

15

20

MS116-25

25.0...32.0

10A

32.0

480

2

5

10

20

25

MS116-32

MS116 Short circuit current ratings (kA)
UL 508 - Motor controllers, manual (NLRV)
Catalog
number

Max. fuse
size (A)

Fuse
class

Circuit
breaker

Motor disconnect 3
240V
480V

600V

UL 508 - Combination motor controllers (NKJH)
Group motor installation
240V
480V

600V

MS116-0.16

30

5

30

5

MS116-0.25

30

5

30

5

MS116-0.4

30

5

30

5

MS116-0.63

30

5

30

5

MS116-1.0

30

5

30

5

MS116-1.6

30

5

30

5

MS116-2.5
MS116-4.0
MS116-6.3

200

J

No rating

30

5

30

5

18

5

18

5

18

5

18

5

MS116-10

18

5

18

5

MS116-12

18

5

18

5

MS116-16

18

5

18

5

MS116-20

18

5

18

5

MS116-25

18

5

18

5

MS116-32

18

5

18

5

Self-protected
Type E
480Y /
277V

600Y /
347V

Self-protected
Type F
480Y /
277V

600Y /
347V

Type F
contactors

Use Type MS132

1 Always size manual motor protectors based on the full-load current of the motor.
2 For single phase connection diagram see page 4.17.
3 Suitable as motor disconnect only when provide with padlock adaptor SA1 or SA3; see accessories section.

4.6	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Type MS132
For applications up to 32A

Suitable applications:
• Single motor, suitable as motor
disconnect
• Group motor installation

4

• Tap conductor protection
• Combination motor controllers
	 - Type E
	 - Type F

MS132 Electrical ratings 1

	
Frame Sz. 1	
Frame Sz. 2
	MS132-0.16…MS132-10	 MS132-12…MS132-32

Thermal setting
range (A)

Trip
class

Rated
operational current
Ie (A)

Rated instantaneous short-circuit
current
setting Ii (A)

0.10...0.16

10A

0.16

1.56

0.16...0.25

10

0.25

2.44

0.25...0.40

10

0.40

3.90

0.40...0.63

10

0.63

6.14

0.63...1.0

10

1.00

11.5

AC Motor ratings, breaking all lines, 50/60 Hz (hp)

120V

Catalog
number

Three phase

Single phase 2
240V

240V

480V

600V

MS132-0.16

Horsepower not applicable; use upper limit of the device thermal setting range for rated
full-load current in Amperes

MS132-0.25
MS132-0.4
MS132-0.63

1/2

1.0...1.6

10

1.60

18.4

1/10

1.6...2.5

10

2.50

28.8

1/6

1/2

MS132-1.0

3/4

3/4

MS132-1.6

1

1.5

MS132-2.5

2.5...4.0

10

4.00

50.0

1/8

1/3

1

2

3

MS132-4.0

4.0...6.3

10

6.30

78.8

1/4

1/2

1.5

3

5

MS132-6.3

6.3...10.0

10

10.0

150

1/2

1.5

3

5

7.5

MS132-10

8.0...12.0

10

12.0

180

1/2

2

3

7.5

10

MS132-12

10.0...16.0

10

16.0

240

1

2

5

10

10

MS132-16

16.0...20.0

10

20.0

300

1.5

3

5

10

15

MS132-20

20.0...25.0

10

25.0

375

2

3

7.5

15

20

MS132-25

25.0...32.0

10

32.0

480

2

5

10

20

25

MS132-32

MS132 Short circuit current ratings (kA) 3
UL 508 - Motor controllers, manual (NLRV)
Catalog
number

Max. fuse
size (A)

Fuse
class

Circuit
breaker

Motor disconnect

UL 508 - Combination motor controllers (NKJH)
Group motor installation 4

Self-protected
Type E 5

Self-protected
Type F 5

240V
480V

600V

240V
480V

600V

480Y / 277V

600Y / 347V

480Y / 277V

600Y / 347V

Type F
contactors

MS132-0.16

65

47

65

47

65

47

65

47

AF26…AF38

MS132-0.25

65

47

65

47

65

47

65

47

AF26…AF38

MS132-0.4

65

47

65

47

65

47

65

47

AF26…AF38

MS132-0.63

65

47

65

47

65

47

65

47

AF26…AF38

MS132-1.0

65

47

65

47

65

47

65

47

AF26…AF38

MS132-1.6

65

47

65

47

65

47

65

47

AF26…AF38

65

47

65

47

65

47

65

47

AF26…AF38

65

47

65

47

65

47

65

47

AF26…AF38

65

18

65

18 [35]

65

18

65

47

AF26…AF38

65

18

65

18 [35]

65

18

65

47

AF26…AF38

MS132-12

30

18

30 [35]

18 [35]

30

-

30

-

AF26…AF38

MS132-16

30

18

30 [35]

18 [35]

30

-

30

-

AF26…AF38

MS132-20

30

18

30 [35]

18 [35]

30

-

30

-

AF26…AF38

MS132-25

30

18

30 [35]

18 [35]

30

-

30

-

AF26…AF38

MS132-32

30

18

30 [35]

18 [35]

30

-

30

-

AF26…AF38

MS132-2.5
MS132-4.0
MS132-6.3

Size per
NEC 6

Any fuse
class

MS132-10

MCCB,
size per
NEC
67

1 Always size manual motor protectors based on the full-load current of the motor.
2 For single phase connection diagram see page 4.17.
3 For higher ratings using S803W current limiters see accessories section.
4 Also suitable for tap conductor protection. Group ratings increased to [x] kA using Class RK5 fuses.
5 Requires the use of line-side feeder terminal S1-M3-xx: see accessories section.
6 NEC refers to the National Electric Code.
7 MCCB interrupting rating must be equal to or greater than the rating of the device.

4.7

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Type MS450 / MS451
For applications up to 50A

Suitable applications:

4

• Single motor, suitable as motor
disconnect
• Group motor installation
• Combination motor controller
	 - Type E

	
Frame Sz. 3	
Frame Sz. 3
	MS450-40…MS450-50	 MS451-16…MS451-50

MS450 / MS451 Electrical ratings 1
Thermal setting
range (A)

Trip
class

Rated
operational
current Ie (A)

Rated instantaneous short-circuit
current
setting Ii (A)

120V

240V

240V

480V

600V

AC Motor ratings, breaking all lines, 50/60 Hz (hp)

Catalog
number
3

Three phase

Single phase 2

28.0…40.0

10

40.0

520

3

7.5

15

30

40

36.0…45.0

10

45.0

585

5

7.5

15

30

40

40.0…50.0

10

50.0

650

5

10

20

40

50

11.0…16.0

20

16.0

208

1

3

5

10

15

14.0…20.0

20

20.0

260

1.5

3

7.5

15

20

18.0…25.0

20

25.0

325

2

5

10

20

25

22.0…32.0

20

32.0

416

3

5

10

25

30

28.0…40.0

20

40.0

520

3

7.5

15

30

40

36.0…45.0

20

45.0

585

5

7.5

15

30

40

40.0…50.0

20

50.0

650

5

10

20

40

50

MS450-40
MS450-40E
MS450-45
MS450-45E
MS450-50
MS450-50E
MS451-16
MS451-16E
MS451-20
MS451-20E
MS451-25
MS451-25E
MS451-32
MS451-32E
MS451-40
MS451-40E
MS451-45
MS451-45E
MS451-50
MS451-50E

MS450 / MS451 Short circuit current ratings (kA)
UL 508 - Motor controllers, manual (NLRV)
Catalog number
4

Max. fuse
size (A)

Fuse class

Circuit
breaker

Motor disconnect

UL 508 - Combination motor controllers (NKJH)
Self-protected
Type E 3

Group motor installation

Self-protected
Type F

240V
480V

600V

480Y/
277V

600Y/
347V

480Y / 277V

600Y / 347V

480Y / 277V

600Y / 347V

Type F
contactors

MS450-40x

65

25

65

25

65

25

-

-

-

MS450-45x

65

25

65

25

65

25

-

-

-

MS450-50x

65

25

65

25

65

25

-

-

-

65

25

65

25

65

25

-

-

-

65

25

65

25

65

25

-

-

-

65

25

65

25

65

25

-

-

-

65

25

65

25

65

25

-

-

-

MS451-40x

65

25

65

25

65

25

-

-

-

MS451-45x

65

25

65

25

65

25

-

-

-

MS451-50x

65

25

65

25

65

25

-

-

-

MS451-16x
MS451-20x
MS451-25x
MS451-32x

500

Any
fuse
class

MCCB,
500A
max.
5

1 Always size manual motor protectors based on the full-load current of the motor.
2 For single phase connection diagram see page 4.17.
3 MS45x-xxE part numbers include the necessary components for Type E applications – Self-protected Type E ratings apply only to these devices.
4 Replace “x” in part number with “E” for self-protected Type E ratings. All other ratings leave blank.
5 MCCB interrupting rating must be equal to or greater than the rating of the device.

4.8	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Type MS495 / MS496
For applications up to 100A

Suitable applications:
• Single motor, suitable as motor
disconnect
• Group motor installation
• Combination motor controller
	 - Type E

	
Frame Sz. 4	
Frame Sz. 4
	MS495-40…MS495-100	MS496-40…MS496-100

MS495 / MS496 Electrical ratings 1
Thermal
setting range (A)

Trip
class

Rated
operational
current Ie (A)

Rated instantaneous short-circuit
current
setting Ii (A)

120V

240V

240V

480V

600V

AC Motor ratings, breaking all lines, 50/60 Hz (hp)
Single phase 2

Catalog number
3

Three phase

28.0…40.0

10

40.0

520

3

7.5

15

30

40

36.0…50.0

10

50.0

650

5

10

20

40

50

45.0…63.0

10

63.0

819

5

15

25

50

60

57.0…75.0

10

75.0

975

7.5

15

25

60

75

70.0…90.0

10

90.0

1170

10

20

30

75

100

80.0…95.0

10

100.0

1235

10

20

40

75

100

28.0…40.0

20

40.0

520

3

7.5

15

30

40

36.0…50.0

20

50.0

650

5

10

20

40

50

45.0…63.0

20

63.0

819

5

15

25

50

60

57.0…75.0

20

75.0

975

7.5

15

25

60

75

70.0…90.0

20

90.0

1170

10

20

30

75

100

80.0…95.0

20

95.0

1235

10

20

40

75

100

MS495-40
MS495-40E
MS495-50
MS495-50E
MS495-63
MS495-63E
MS495-75
MS495-75E
MS495-90
MS495-90E
MS495-100
MS495-100E
MS496-40
MS496-40E
MS496-50
MS496-50E
MS496-63
MS496-63E
MS496-75
MS496-75E
MS496-90
MS496-90E
MS496-100
MS496-100E

MS495 / MS496 Short circuit current ratings (kA)
UL 508 - Motor controllers, manual (NLRV)
Catalog number
4

Max. fuse
size (A)

Fuse
class

Circuit
breaker

Motor disconnect
240V
480V

UL 508 - Combination motor controllers (NKJH)
Group motor installation

Self-protected Type F

Self-protected Type E 3

600V

480Y/
277V

600Y/
347V

480Y / 277V

600Y / 347V

480Y / 277V

600Y / 347V

Type F
contactors

MS495-40x

65

30

65

30

65

30

-

-

-

MS495-50x

65

30

65

30

65

30

-

-

-

MS495-63x

65

30

65

30

65

30

-

-

-

MS495-75x

65

30

65

30

65

30

-

-

-

MS495-90x

65

30

65

30

65

-

-

-

-

65

30

65

30

65

-

-

-

-

65

30

65

30

65

30

-

-

-

65

30

65

30

65

30

-

-

-

MS496-63x

65

30

65

30

65

30

-

-

-

MS496-75x

65

30

65

30

65

30

-

-

-

MS496-90x

65

30

65

30

65

-

-

-

-

MS496-100x

65

30

65

30

65

-

-

-

-

MS495-100x
MS496-40x
MS496-50x

500

Any
fuse
class

MCCB,
500A
max.
5

1 Always size manual motor protectors based on the full-load current of the motor.
2 For single phase connection diagram see page 4.17.
3 MS49x-xxE part numbers include the necessary components for Type E applications – Self-protected Type
E ratings apply only to these devices.

4 Replace “x” in part number with “E” for self-protected Type E ratings. All other ratings leave blank.
5 MCCB interrupting rating must be equal to or greater than the rating of the device.

4.9

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

4

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Accessories
For Types MS116, MS132, MS45x, MS49x
Auxiliary contacts

HKF1-11

4
HK4-11

45x

Auxiliary contacts

Mounting
position
/ max.
quantity

For use with MS…
49x

Pilot duty rating

Catalog
number

132

NO

NC

NO

NC

•

•

1

1

-

-

HK1-11

•

•

2

-

-

-

HK1-20

•

•

-

2

-

-

HK1-02

•

•

-

-

2

-

HK1-20L

•

•

1

1

-

-

HKF1-11

•

•

2

-

-

-

HKF1-20

1

1

-

-

HKS4-11

2

-

-

-

HKS4-20

Front / 1

dc

Lagging / leading

116

Right / 2

ac

Instantaneous

B600

Q600

B300

Q300

•

•

•

•

•

•

-

2

-

-

HKS4-02

•

•

1

1

-

-

HK4-11

•

•

-

1

1

-

HK4-W

Left / 1

Front / 1

A600

Q300

C300

R300

	 HK1-11	HKS4-20	

Signalling contacts
For use with MS…
Description
116

132

•

•

•

•

•

•

45x

49x

Trip (bell)
alarm
•

•

•
	SK1-11	

CK1-11	

SK4-11

Shortcircuit
trip alarm

•
•

Mounting
position
/ max.
quantity

ac

dc

NO

NC

1

1

SK1-11

Right / 1

B600

Q600

2

-

SK1-20

-

2

SK1-02

Left / 1

A600

Q300

2

2

SK4-11

1

1

CK1-11

Right / 1

B600

Q600

2

-

CK1-20

-

2

CK1-02

Pilot duty rating

Contacts

Catalog
number

Note(s):
CK1-xx contacts must mount flush on the right side of the MS132; these devices are supplementary and not required for use in UL 508 Type E &
F applications
SK4-11 contacts are required for UL 508 Type E applications using types MS4xx; included when purchasing types MS4xx-xxE

Trip units
For use with MS…
Description
116

132

60 Hz

50/60

dc

Catalog
number

•

24 v

20...70 v

AA1-24

•

110 v

70…190 v

AA1-110

•

•

200…240 v

190…330 v

AA1-230

350…415 v

330…500 v

AA1-400

20…24 v

20...70 v

AA4-24

30…110 v

70…190 v

AA4-110

210…240 v

190…330 v

AA4-240

350…415 v

330…500 v

Left / 1
•

•

•

•

•

•

•

•

•

•

Shunt
trip
Right / 1

•

-

24 v

-

AA4-400
-

UA1-24

•

•

110 v

120 v

-

-

UA1-120

•

•

-

208 v

-

-

UA1-208

•

•

•

•

•

•

Left / 1

•

•

•

•

•

•

•

•

Undervoltage
release

4.10	
1SXU000023C0202 Rev. A	

50 Hz

Brief voltage rating;
5 seconds max.

•

•

UA1-24

49x

Voltage rating; continuous

•

AA1-24

AA4-24

45x

Mounting
position /
max. quantity

230 v

240 v

-

-

UA1-230

415 v

480 v

-

-

UA1-415

575 v

-

Right / 1

-

-

UA1-575

24 v

-

-

UA4-24

110…120 v

-

-

UA4-120

230…240 v

-

-

UA4-240

-

-

UA4-400

400 v

-

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Actuation tables
For Types MS116, MS132, MS45x, MS49x
Auxiliary and signaling contact actuation tables
Condition / state
Catalog
number

Description

Off

For use with MS…

On

Thermal
overload trip

Short-circuit
trip

Under-voltage
trip

Shunt trip

Terminal numbers

116

132

•

•

1 NO

O

X

O

O

O

O

33…34

1 NC

X

O

X

X

X

X

41…42

HK1-20

2 NO

O

X

O

O

O

O

33…34, 43…44

•

•

HK1-02

2 NC

X

O

X

X

X

X

31…32, 41…42

•

•

HK1-20L

2 NO leading contacts

O

X

O

O

O

O

 33…34, 43…44

•

•

1 NO

O

X

O

O

O

O

 13…14

1 NC

X

O

X

X

X

X

 21…22

•

•

2 NO

O

X

O

O

O

O

13…14, 23…24

•

•

1 NO

O

X

O

O

O

O

33…34

1 NC

X

O

X

X

X

X

41…42

HKS4-20

2 NO

O

X

O

O

O

O

HKS4-02

2 NC

X

O

X

X

X

X

1 NO

O

X

O

O

O

O

13…14

1 NC

X

O

X

X

X

X

21…22

1 NO, leading (form C)

O

X

O

O

O

O

11…14

1 NC (form C)

X

O

X

X

X

X

11…12

1 NO

O

O

X

X

X

X

57…58

1 NC

X

X

O

O

O

O

65…66

SK1-20

2 NO

O

O

X

X

X

X

SK1-02

2 NC

X

X

O

O

O

O

1 NO

O

O

X

X

X

X

57…58

HK1-11

HKF1-11
HKF1-20
HKS4-11

HK4-11
HK4-W
SK1-11

SK4-11

49x

4

•

•

33…34, 43…44

•

•

31…32, 41…42

•

•

•

•

•

•

•

•

•

•

57…58, 67…68

•

•

55…56, 65…66

•

•

1 NC

X

X

O

O

O

O

65…66

1 NO

O

O

O

X

O

O

77…78

1 NC

X

X

X

O

X

X

85…86

1 NO

O

O

O

X

O

O

77…78

1 NC

X

X

X

O

X

X

85…86

CK1-20

2 NO

O

O

O

X

O

O

77…78, 87…88

•

CK1-02

2 NC

X

X

X

O

X

X

75…76, 85…86

•

CK1-11

45x

•

Note:
X = Indicates closed state
O = Indicates open state
For connection diagrams, see page 4.17.

Operator positions
Operator position
Type

Off

On

Thermal overload
trip

Short-circuit
trip

Undervoltage
trip

Shunt
trip

Key

MS116-…
1
MS132-…

MS45x-…

MS49x-…

1 + I>> indicator window = red.

4.11

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Accessories
For Types MS116, MS132, MS45x, MS49x

4

	PS1-2-0-65	

PS1-3-1-100

Three phase busbar
For use with MS…
116

132

•

•

•

•

•

•

Rated current (A)

45x

Description

49x

600 v ac

2-position
busbar

•
•

•

•

•

•

•

•

•

•

•

•

65
3-position
busbar
•

•

•

•

•

•

•

•

•

•

65
4-position
busbar
•

•

•

•

•

•

•

•

•

•

•

•

92
108

•
•

92

108

•
•

65

108

•
•

Max. quantity of
MMP’s

5-position
busbar

65

92

•

Max. quantity
of shunt trips or
U.V. releases per
MMP

Max. quantity of auxiliary and signaling
contacts per MMP

Catalog
number

2

-

-

PS1-2-0-65

2

1

-

PS1-2-1-65

2

2

2

-

2

1

3

-

3

1

3

2

3

or

1

PS1-2-2-65

-

PS4-2-0

1

PS4-2-2

-

PS1-3-0-65

-

PS1-3-1-65

1

PS1-3-2-65

-

-

PS1-3-0-100

3

1

-

PS1-3-1-100

3

2

3

-

3

1

4

-

4

1

4

2

4

or

or

or

1

PS1-3-2-100

-

PS4-3-0

1

PS4-3-2

-

PS1-4-0-65

-

PS1-4-1-65

1

PS1-4-2-65

-

-

PS1-4-0-100

4

1

-

PS1-4-1-100

4

-

-

PS4-4-0

4

1

1

PS4-4-2

5

-

-

PS1-5-0-65

5

1

-

PS1-5-1-65

5

2

1

PS1-5-2-65

5

-

-

PS1-5-0-100

5

1

-

PS1-5-1-100

or

or

or

or

Empty position busbar cover

BS1-3

Empty position busbar cover

BS4-3

Note: Use of PS1 or PS4 busbar in group motor or self-protected Type E or F applications does not inhibit or alter the short-circuit current ratings for the devices utilized.

Three phase feeder terminals
For use with MS…

S1-M3-25

Description

45x

Rated current
(A)
600 v ac

49x

Required for UL 508 Types E or F
applications

132

•

•

65

10…4

•

•

65

10…4

•

•

65

10…4

•

•

•

92

8…2

•

108

10…1/0

140

10…1/0

Feeder terminal
•
•

DX495

Connecting
capacity (AWG)

116

Type E terminal ins. barrier

Catalog
number

S1-M1-25
S1-M2-25
S1-M3-25
S1-M3-35
S4-M1
•

DX495

Note(s): Only the S1-M3-xx terminals are acceptable for UL 508 Type E or F applications using type MS132.
The DX495 terminal is included when purchasing type MS49x-xxE devices.

Terminal shrouds
For use with MS…
116

132

45x

Description

49x

•
•
•

Terminal shroud, short
Terminal shroud, long

Catalog
number

KA450
KA495
KA495C

KA450

4.12	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

Accessories
For Types MS116, MS132

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

ABB Manual motor protectors can also be connected to the SMISSLINE power distribution bus system, which provides a versatile and flexible means of distributing power to a wide variety of
electrical devices. For complete system information, see Section 24.

SMISSLINE busbar adaptors for types MS116 / MS132
For use with MS…
45x

Description

49x

4

Catalog number

116

132

•

•

Adaptor, L1,L2,L3 bottom feed

ZMS930

•

•

Adaptor, L1,L2,L3 top feed

ZMS932

•

•

Adaptor, without feed wires

ZMS139

9 mm wide additional housing

ZMS935

Note(s):
The 9 mm wide additional housing is needed when an odd number of combi modules are
plugged on the socket; required to fill space into a full module (18 mm).
The 9 mm wide additional housing must also be used when a side-mount auxiliary contact is
used.

SMISSLINE busbar combi modules for types MS116 / MS132 +
AF Contactors
For use with MS…
45x

Description

49x

Catalog number

116

132

•

•

Combi module, L1,L2,L3 top feed

ZMS930

•

•

Combi module, without feed wires

ZMS137

Connection pin set for mounting two combi
modules side-by-side

E210-SPV

4.13

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Accessories
For Types MS116, MS132, MS45x, MS49x
Locking accessories
For use with MS…
116

132

45x

49x

•
•

4

•

•

•

•
	SA1	

SA2

Description

Catalog number

Lock adapter

SA1

Padlock + 2 keys

SA2

Lock adapter + padlock + 2 keys

SA3

Note: Types MS132 and MS4xx have integral locking mechanisms

Door mount kits - Type 12 & IP 65
For use with MS…

	DMS132-G

116

132

•

•

45x

49x

Door mount w/ handle, black/gray

Description

On / Trip / Off

Rotary positions

DMS132-G

Catalog number

•

•

Door mount w/ handle, red/yellow

On / Trip / Off

DMS132-Y

Note(s):	 Type MS116 devices trip to the “Off” position
Max. 3 padlocks with bail diameter Ø 4…6.5 mm

Through-door hardware - Types 1, 3R, 12 and IP 64
For use with MS…
116

132

45x

49x

•

•

•

•

•

•

•

•

•

•

•

•

•

•

•

•

•

•

•

•

•

	MSHD-LY	

MSHD-LTY

•

	1SAM101923R0002	

1SAM101924R0013

	1SAM201920R1000

•

•

Description

Rotary positions

Catalog number

On / Off

MSHD-LB

On / Trip / Off

MSHD-LTB

On / Off

MSHD-LY

On / Trip / Off

MSHD-LTY

Shaft coupler, coded, 6 mm, MSMN

-

1SAM101923R0002

•

Shaft coupler, un-coded, 6 mm, MSMNO

-

1SAM101923R0012

•

Drive spindle, 6 x 30 mm, for horizontal mounting,
MSOX-30

-

1SAM101924R0013

Selector handle, black, defeatable, padlockable
Selector handle, red/yellow, defeatable, padlockable

•

•

•

•

Drive spindle, 6 x 32 mm, for vertical (standard) mounting, MSOX-32

-

1SAM101924R0003

•

•

•

•

Shaft, 6 x 85 mm

-

OXS6X85

•

•

•

•

Shaft, 6 x 105 mm

-

OXS6X105

•

•

•

•

Shaft, 6 x 130 mm

-

OXS6X130

•

•

•

•

Shaft, 6 x 180 mm

-

OXS6X180

•

•

•

•

Shaft alignment ring, MSH-AR

-

1SAM201920R1000

Note(s): Through-door selector handles are rated Type 1, 3R and 12; IP 64 degree of protection
Max. 3 padlocks with bail diameter Ø 5…8 mm
For coded shaft couplers, the “On” position is dependent on the mounting orientation of the MMP
Must have handle, shaft coupler and shaft for through-door operation. Drive spindles can replace both shaft coupler and shaft.

Enclosures - Type 12 & IP 65
For use with MS…
116

132

•

•

45x

49x

Molded plastic enclosure, black/gray

Description

On / Trip / Off

Rotary positions

IB132-G

Catalog number

•

•

Molded plastic enclosure, red/yellow

On / Trip / Off

IB132-Y

•

•

Adaptor, PG16 to 1/2 NPT

-

PG16-1/2NPT

Note(s):	 Type E rating for MS132 derated when using IB132 enclosures. Please contact technical support.
Type MS116 devices trip to the “Off” position
Max. 3 padlocks with bail diameter Ø 4…6.5 mm
For UL enclosure type ratings, contact technical support.
	IB132-G

4.14	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Accessories
For Types MS116, MS132, MS45x, MS49x
Close couplers for contactors

MS116-0.16…16

•

A95...A110

•

BEA26-4
•

BEA16-3

•

MS116-32

BEA16-4
•

•

BEA38-4

•

•

BEA38-4

•

BEA7/132
•

MS132-0.16…10

•

BEA16-4
•

BEA26-4

•
•

•

A50...A75, AE50...AE75

BEA7/132

•

•

BEA16-3

•

BEA7/132

•
•

MS132-12…16

BEA16-4

•
•

BEA38-4

•
•

•

MS132-20…25

4

Catalog
number

BEA16-4
•

MS116-20…25

A / AE Contactors

ASL09...ASL16

AF95...AF110

AF50...AF75

•

AS contactors

AF26Z...AF38Z

•

AF26...AF38

•

AF09Z...AF16Z

BC6...BC7

•

AF09...AF16

B6...B7

Manual motor protector

AF contactors

AS09...AS16

Miniature
contactors

MS132-32

BEA16-3

•

BEA16-4

•
•

•

•

•

BEA38-4
BEA38-4

MS45x-40…50

•

MS49x-40…100

•

MS495-40…100

•

BEA50/450

•

BEA75/495

•

•

BEA110/495

Note: For spring terminated AS/ASL, use part number BEA16-3U with integral wire leads for spring terminals.

Close couplers for softstarters

MS116-0.16…16

MS132-12…32
MS45x-40…50
MS49x-40…100
	

MS132 + PSR Softstarter	

MS132 + AF Contactor	

BEA16-4	

PSR60…PSR105

Catalog
number

PSR16-MS116
•

PSR30-MS132

•

PSR16-MS116
•

PSR30-MS132
•

PSR45-MS450
•

PSR105-MS495

BEA16-3	

4.15

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

PSR37…PSR45

•

MS116-20…32
MS132-0.16…10

PSR25…PSR30

Manual motor protector

PSR3…PSR16

PSR Softstarters

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Accessories
For Type MS132

Rated for use with the type MS132, the S803W current limiters can provide selective coordination for individual downstream SCPDs, and can be utilized in combination for short-circuit protection
up to 65 kA at 600 v ac. For more information, see Section 17 - S800 Series.

Current limiters
For use with MS…

4

116

132

45x

49x

Description

Rated current (A)
600 v ac

Connecting capacity (AWG)

32

14…1

S803W-SCL32-SR

63

14…1

S803W-SCL63-SR

100

14…1

S803W-SCL100-SR

•
•

Current limiter, 3-pole

•

Catalog number

Note(s):	 The sum of the rated currents of all downstream motor protectors shall not exceed the rated current of the S803W.
The sum of all load currents including inrush currents shall not exceed the maximum permissible load of the S803W.
S803W-SCL32-SR

MS132 Short circuit current ratings using S803W current limiters (kA)
UL 508 - Motor controllers, manual (NLRV)
Catalog
number

UL 508 - Combination motor controllers (NKJH)
Self-protected
Type E 2

Group motor installation 1
Circuit breaker

240V
480V

600V

480Y/
277V

Self-protected
Type F 2

600Y/
347V

480Y/
277V

600Y/
347V

Type F
contactors

MS132-0.16

65

65

65

47

65

47

AF26…AF38

MS132-0.25

65

65

65

47

65

47

AF26…AF38

MS132-0.4

65

65

65

47

65

47

AF26…AF38

MS132-0.63

65

65

65

47

65

47

AF26…AF38

MS132-1.0

65

65

65

47

65

47

AF26…AF38

MS132-1.6

65

65

65

47

65

47

AF26…AF38

MS132-2.5
MS132-4.0
MS132-6.3

MCCB, 400A
max.
3

MS132-10

65

65

65

47

65

47

AF26…AF38

65

65

65

47

65

47

AF26…AF38

65

65

65

18

65

47

AF26…AF38

65

65

65

18

65

47

AF26…AF38

MS132-12

65

65

65

-

65

-

AF26…AF38

MS132-16

65

65

65

-

65

-

AF26…AF38

MS132-20

65

65

65

-

65

-

AF26…AF38

MS132-25

65

65

65

-

65

-

AF26…AF38

MS132-32

65

65

65

-

65

-

AF26…AF38

Maximum load
10 000

1000

time [s]

100

10

1

0.1

1 Also suitable for Tap Conductor protection.
2 Requires the use of a line-side feeder terminal S1-M3-xx; see accessories section.
3 MCCB interrupting rating must be equal to or greater than the rating of the device.

0.01

4.16	
1SXU000023C0202 Rev. A	

1

10
n x Ie

100

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Connection diagrams
For Types MS116, MS132, MS45x, MS49x
Connection diagrams
Single phase connection diagram for Types MS116,
MS132, and MS4xx

33

43
44

5/L3

4
34

3/L2

1/L1
43
44

5/L3
33
34

3/L2

Single and three phase connection diagram when using contactors	

1/L1

Three phase connection diagram for Types MS116, MS132,
and MS4xx

Q1

U

V

M

U

W

14

14

13

13

5/L3
6/T3

6/T3

3/L2
4/T2

2/T1
1/L1
2/T1

6/T3
5/L3
6/T3

4/T2
3/L2
4/T2

2/T1
1/L1
2/T1

A1
A2

KM1

4/T2

I> I> I>

I> I> I>

V

~

M

3 Phase

Single Phase

~

Accessories for use with Type MS116, MS132 & MS4xx

AA1...
AA4...

C1

D1

U<
D2

41

55

65

75

85

32

42

56

66

76

86

HKF1-02
HK4-02

C2
UA1...
UA4...

31

1 L1 3 L2 5 L3

33

43

34

44

HKF1-20
HK4-20

13

21

14

22

HKF1-11
HK4-11

33

41

34

42

HK1-11
HKS4-11

SK1-02

57

67

58

68

SK1-20

57

65

58

66

SK1-11
SK4-11

CK1-02

77

87

78

88

CK1-20

77

85

78

86

CK1-11
SK4-11

I> I> I>

2 T1 4 T2 6 T3

4.17

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

General accessory mounting layout
MS116 & MS132

S1-M2-25
PS1-..-65

4

S1-M1-25

3-phase busbar up
to 65 A

PS1-..-65

3-phase busbar up
to 92 A

BS1-3
S1-M1-25

HK1
PS1-..-100

SK1

BS1-3

HK1

HK1

SK1
SA1
CK1

AA1

MS116

HK1

CK1

UA1
MS132

HKF1

4.18	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Technical data - IEC/EN
MS116
Main circuit – Utilization characteristics according to IEC/EN
Type

MS116

Standards
Rated operational voltage Ue
Rated frequency
Trip class
Number of poles
Duty time
Rated impulse withstand voltage Uimp
Rated insulation voltage Ui
Rated operational current Ie
Rated instantaneous short-circuit current setting Ii
Rated service short-circuit breaking capacity Ics
Rated ultimate short-circuit breaking capacity Icu

IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
690 V AC
50/60 Hz
10A
3
100 %
6 kV
690 V AC
See ordering details
See ordering details
See table "Short-circuit breaking capacity and back-up fuses"
See table "Short-circuit breaking capacity and back-up fuses"

4

Short-circuit breaking capacity and back-up fuses
lCS Rated service short-circuit breaking capacity
lCU Rated ultimate short-circuit breaking capacity
ICC Prospective short-circuit current at installation location
Note: Maximum rated current of the back-up fuses if ICC > ICS
Type

230 V AC
ICS
kA

MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1.0
MS116-1.6
MS116-2.5
MS116-4.0
MS116-6.3
MS116-10
MS116-12
MS116-16
MS116-20
MS116-25
MS116-32

400 V AC
ICU
kA

gG, aM
A

ICS
kA

440 V AC
ICU
kA

gG, aM
A

ICS
kA

500 V AC
ICU
kA

gG, aM
A

ICS
kA

690 V AC
ICU
kA

gG, aM
A

ICS
kA

ICU
kA

gG, aM
A

No back-up fuse required up to ICC = 30 kA
No back-up fuse required up to ICC = 50 kA

25
16
10
10
10

25
16
15
15
10

80
80
-

25
16
10
10
10

25
16
15
15
10

80
80
-

10
6
6
6
6
6
3
3
3

10
6
6
6
6
6
6
6
6

25
25
63
63
63
63
-

10
6
6
6
6
4
3
3
3

10
6
6
6
6
4
4
4
4

25
25
63
63
63
63
-

5
2
2
2
2
2
2
2
2

5
2
2
2
2
2
2
2
2

25
25
40
50
50
63
-

MS116-10:	No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V.
MS116-16:	No need for back-up fuse in networks with a prospective current of up to 16 kA at 400 V.
	
With an appropriate 80 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.
MS116-32:	No need for back-up fuse in networks with a prospective current of up to 15 kA at 400 V.

4.19

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Technical data - UL/CSA
MS116

Main circuit – Utilization characteristics according to UL/CSA
Type

4

MS116

Standards
Maximum operational voltage
Manual motor controller ratings
Trip rating
Motor ratings
Horse power
Full load amps (FLA)
Locked rotor amps (LRA)

UL 508, CSA 22.2 No. 14
600 V AC
See table "UL 508 – Manual motor controller"
125 % FLA
See table "Motor rating, three phase"
See table "Motor rating, three phase"
See table "Motor rating, three phase"

Motor rating, three phase
hp

Horse power

FLA

Full load amps

LRA

Locked rotor amps

Type

MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1.0
MS116-1.6
MS116-2.5
MS116-4.0
MS116-6.3
MS116-10
MS116-12
MS116-16
MS116-20
MS116-25
MS116-32

110-120 V AC

220-240 V AC

440-480 V AC

550-600 V AC

hp

FLA

LRA

hp

FLA

LRA

hp

FLA

LRA

hp

FLA

LRA

1/2
1
1-1/2
2
3
3
5

0.16
0.25
0.4
0.63
1.0
1.6
2.5
4.0
4.4
8.4
12
13.6
19.2
19.2
30.4

0.96
1.5
2.4
3.78
6.0
9.6
15.0
16.0
40
60
80
100
128
128
184

1/2
1
1-1/2
3
3
5
5
7-1/2
10

0.16
0.25
0.4
0.63
1.0
1.6
2.2
4.2
6.4
9.6
9.6
15.2
15.2
22
28

0.96
1.5
2.4
3.78
6.0
9.6
20
30
40
64
64
92
92
127
162

-

0.16
0.25
0.4
0.63
1.0
1.6
2.1
3.4
4.8
7.6
11
14
14
21
27

0.96
1.5
2.4
3.78
6.0
12.5
15
25
32
46
63.5
81
81
116
145

1/2
3/4
1-1/2
3
5
7-1/2
10
10
15
20
25

0.16
0.25
0.4
0.63
0.9
1.3
2.4
3.9
6.1
9
11
11
17
22
27

0.96
1.5
2.4
3.78
8
10
16
25.6
36.8
50.8
64.8
64.8
93
116
146

3/4
1
2
3
5
7-1/2
10
10
15
20

1 Suitable as motor disconnect only when provided with padlock SA1 or SA3...

4.20	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Technical data
MS116
General technical data
Type

Pollution degree
Phase loss sensitive
Ambient air temperature
Operation

MS116

3
Yes
Open - compensated without derating
Open

4

-25 ... +55 °C
-25 ... +70 °C

Enclosed (IB132)
Storage
Ambient air temperature compensation
Maximum operating altitude permissible
Resistance to shock acc. to IEC 60068-2-27
Resistance to vibrations acc. to IEC 60068-2-6

0 ... +40 °C
-50 ... +80 °C
Continuous
2000 m
25 g / 11 ms
5 g / 3 ... 150 Hz

Mounting position
Mounting
Group mounting
Minimum distance to other
units same type

Position 1-6 (optional for single mounting)
DIN-rail (EN 60715)
On request
0 mm
150 mm
0 mm
> 1.5 mm
75 mm
IP20

Minimum distance to
electrical conductive board
Degree of protection

Horizontal
Vertical
Horizontal, up to 400 V
Horizontal, up to 690 V
Vertical
Enclosure / terminals

Main circuit – Connecting characteristics
Type

Connecting capacity
Solid
Flexible
Stranded acc. to UL/CSA
Flexible acc. to UL/CSA
Stripping length
Tightening torques
Connection screw

MS116 ≤ 16 A

1 or 2 x
1 or 2 x
1 or 2 x
1 or 2 x

1 ... 4 mm²
0.75 ... 2.5 mm²
AWG 16-12
AWG 16-12
9 mm
0.8 ... 1.2 Nm / 10 … 12 Ib.in
M3.5 (Pozidriv 2 / 5.5 mm)

2.5 ... 6 mm²
1 ... 6 mm²
AWG 12-8
AWG 12-8
10 mm
2.0 Nm / 18 Ib.in
M4 (Pozidriv 2 / 6.5 mm)

4.21

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

MS116 ≥ 20 A

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Technical data - IEC/EN
MS132

Main circuit – Utilization characteristics according to IEC/EN
Type

4

MS132

Standards
Rated operational voltage Ue
Rated frequency
Trip class
Number of poles
Duty time
Rated impulse withstand voltage Uimp
Rated insulation voltage Ui
Rated operational current Ie
Rated instantaneous short-circuit current setting Ii
Rated service short-circuit breaking capacity Ics
Rated ultimate short-circuit breaking capacity Icu

IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
690 V AC / 250 V DC
DC, 50/60 Hz
10 (10A for MS132-0.16)
3
100 %
6 kV
690 V AC
See ordering details
See ordering details
See table "Short-circuit breaking capacity and back-up fuses"
See table "Short-circuit breaking capacity and back-up fuses"

Short-circuit breaking capacity and back-up fuses
lCS Rated service short-circuit breaking capacity
lCU Rated ultimate short-circuit breaking capacity
ICC Prospective short-circuit current at installation location
Note: Maximum rated current of the back-up fuses if ICC > ICS
Type

230 V AC
ICS
kA

MS132-0.16
MS132-0.25
MS132-0.4
MS132-0.63
MS132-1.0
MS132-1.6
MS132-2.5
MS132-4.0
MS132-6.3
MS132-10
MS132-12
MS132-16
MS132-20
MS132-25
MS132-32

400 V AC
ICU
kA

gG, aM
A

ICS
kA

440 V AC
ICU
kA

500 V AC

690 V AC

gG, aM
A

ICS
kA

ICU
kA

gG, aM
A

ICS
kA

ICU
kA

gG, aM
A

ICS
kA

ICU
kA

gG, aM
A

100
125

20
20
20
20
20
20
20
20

20
20
20
20
20
20
20
20

*
*
*
*
*
*
*
*

20
20
20
20
20
20
10
10

20
20
20
20
20
20
10
10

*
*
*
*
*
*
*
*

3
3
3
3
3
3
3
3

3
3
3
3
3
3
3
3

*
*
*
*
*
*
*
*

No back-up fuse required up to
ICC = 100 kA

50
25

50
50

100
125

50
25

50
50

MS132-16:	No need for back-up fuse in networks with a prospective current of up to 100 kA at 400 V.
MS132-32:	No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V.
	
With an approbiate 125 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA
* not available yet

4.22	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Technical data - UL/CSA
MS132
Main circuit – Utilization characteristics according to UL/CSA
Type

MS132

Standards
Maximum operational voltage
Manual motor controller ratings
Trip rating
Motor ratings
Horse power
Full load amps (FLA)
Locked rotor amps (LRA)

UL 508, CSA 22.2 No. 14
600 V AC
See table "UL 508 – Manual motor controller"
125 % FLA
See table "Motor rating, three phase"
See table "Motor rating, three phase"
See table "Motor rating, three phase"

4

Motor rating, three phase
hp

Horse power

FLA

Full load amps

LRA

Locked rotor amps

Type

MS132-0.16
MS132-0.25
MS132-0.4
MS132-0.63
MS132-1.0
MS132-1.6
MS132-2.5
MS132-4.0
MS132-6.3
MS132-10
MS132-12
MS132-16
MS132-20
MS132-25
MS132-32

110-120 V AC

220-240 V AC

440-480 V AC

550-600 V AC

hp

FLA

LRA

hp

FLA

LRA

hp

FLA

LRA

hp

FLA

LRA

1/2
3/4
1-1/2
2
3
3
5

0.16
0.25
0.4
0.63
1.0
1.6
2.5
4.0
6.3
10.0
12.0
16.0
19.2
19.2
30.4

0.96
1.5
2.4
3.78
6.0
9.6
15.0
24.0
37.8
60.0
72.0
84.0
128.0
128.0
184.0

1/2
1
1-1/2
3
3
5
5
7-1/2
10

0.16
0.25
0.4
0.63
1.0
1.6
2.5
4.0
6.3
9.6
9.6
15.2
15.2
22.0
28.0

0.96
1.5
2.4
3.78
6.0
9.6
15.0
24.0
37.8
64.0
64.0
92.0
92.0
127.0
162.0

3/4
1
2
3
5
7-1/2
10
10
15
20

0.16
0.25
0.4
0.63
1.0
1.6
2.5
4.0
4.8
7.6
11.0
14.0
14.0
21.0
27.0

0.96
1.5
2.4
3.78
6.0
9.6
15.0
24.0
32.0
46.0
64.0
81.0
81.0
116.0
145.0

1/2
3/4
1-1/2
3
5
7-1/2
10
10
15
20
25

0.16
0.25
0.4
0.63
1.0
1.6
2.5
3.9
6.1
9.0
11.0
11.0
17.0
22.0
27.0

0.96
1.5
2.4
3.78
6.0
9.6
15.0
26.0
37.0
51.0
65.0
65.0
93.0
116.0
146.0

4.23

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Technical data
MS132

General technical data
Type

4

Pollution degree
Phase loss sensitive
Ambient air temperature
Operation

MS132

3
Yes
Open - compensated without derating
Open

-25 ... +60 °C
-25 ... +70 °C

Enclosed (IB132)
Storage
Ambient air temperature compensation
Maximum operating altitude permissible
Resistance to shock acc. to IEC 60068-2-27
Resistance to vibrations acc. to IEC 60068-2-6

0 ... +40 °C
-50 ... +80 °C
Continuous
2000 m
25 g / 11 ms
5 g / 3 ... 150 Hz

Mounting position
Mounting
Group mounting
Minimum distance to other
units same type

Position 1-6 (optional for single mounting)
DIN-rail (EN 60715)
On request
0 mm
150 mm
0 mm
> 1.5 mm
75 mm
IP20

Minimum distance to
electrical conductive board
Degree of protection

Horizontal
Vertical
Horizontal, up to 400 V
Horizontal, up to 690 V
Vertical
Enclosure / terminals

Main circuit – Connecting characteristics
Type

Connecting capacity
Solid
Flexible
Stranded acc. to UL/CSA
Flexible acc. to UL/CSA
Stripping length
Tightening torques
Connection screw

MS132-0.16 … MS132-10

1 or 2 x
1 or 2 x
1 or 2 x
1 or 2 x

1 ... 4 mm²
0.75 ... 2.5 mm²
AWG 16-12
AWG 16-12
9 mm
0.8 ... 1.2 Nm / 10 … 12 Ib.in
M3.5 (Pozidriv 2)

4.24	
1SXU000023C0202 Rev. A	

MS132-12 … MS132-16

1 ... 4 mm²
0.75 ... 2.5 mm²
AWG 16-12
AWG 16-12
10 mm
1.5 Nm / 14 Ib.in
M4 (Pozidriv 2)

MS132-20 … MS132-32

2.5 ... 6 mm²
1 ... 6 mm²
AWG 12-8
AWG 12-8
10 mm
2.0 Nm / 18 Ib.in
M4 (Pozidriv 2)

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Technical data
MS116 & MS132 Accessories
General technical data
Type

PS1-x-x-65

Standards

IEC/EN 60947-1, UL 508/60947-4-1A, CAN/CSA C22.2 No.14/60947-4-1-07

PS1-x-x-100

S1-M1-25

S1-M2-25

Rated operational voltage Ue

690 V AC

Rated voltage UL/CSA

600 V AC

S1-M3-25

S1-M3-35

Rated operational current Ie

65 A

100 A

65 A

100 A

Rated current UL/CSA

65 A

92 A

65 A

92 A

Rated frequency

50/60 Hz

Rated impulse withstand voltage Uimp

6 kV

Rated insulation voltage Ui

690 V AC

Pollution degree

3

Cross-section

5 mm²

Ambient air temperature

Operation

-25...+70 °C

Storage

-50...+80 °C

4

5 mm²

Connecting characteristics
Type

S1-M1-25

S1-M2-25

S1-M3-25

S1-M3-35

Connecting capacity
Solid

1x

6mm2…25 mm2

10...35 mm²

Flexible

1x

6mm2…16mm2

10...35 mm²

Stranded acc. to UL/CSA

1x

AWG 10-4

AWG 8-2

Flexible acc. to UL/CSA

1x

AWG 10-4

AWG 8-2

Tightening torques

2.5 Nm / 22 lb.in

4.5 Nm / 40 lb.in

Connection screw

Pozidriv 2 / M3.5

Hexgon SW4

General technical data
Type

UA1

Standards

IEC/EN 60947-1, UL 508/60947-4-1A, CAN/CSA C22.2 No.14/60947-4-1-07

AA1

Pick-up value

% of Uc

≥ 85

≥ 70

Drop-out value

% of Uc

35…70

-

VA

9

VA

3

Operation

-20…+55 °C

Storage

-50…+80 °C

Power consumption

Pick-up
Holding

Ambient air temperature

Connecting characteristics
Type

UA1

AA1

Connecting capacity
Solid
Flexible

1x

0.5...1.5 mm²

2x

0.5...1.5 mm²

1x

0.5...1.5 mm²

2x

0.5...1.5 mm²

Stranded acc. to UL/CSA

1 or 2 x

AWG 18-14

Flexible acc. to UL/CSA

1 or 2 x

AWG 18-14

Stripping length

8 mm

Tightening torques

0.8...1.2 Nm /
7...10.3 Ib.in

Connection screw

Pozidriv 2 / M3

4.25

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Technical data
MS116 & MS132 Accessories

Contact utilization characteristics per IEC
Type

4

HKF1-xx

HK1-xx

Standards

IEC/EN 60947-5-1

Rated operational voltage Ue

250 V AC/

690 V AC/

250 V DC

600 V DC

Conventional free-air thermal current Ith

5A

6A

Rated frequency

50/60 Hz

Rated impulse withstand voltage Uimp

6 kVA

Rated insulation voltage Ui

230 V

Pollution degree

3

Ambient air temperature

Operation

HK1-20L

SK1-xx

CK1-xx

2 leading N.O.

1 N.C. + 1 N.O. or 2 N.O. or 2 N.C.

HK1-20L

SK1-xx

CK1-xx

SK1-xx

CK1-xx

690 V

-20…+55 °C

Storage

-50…+80 °C

Resistance to shock acc. to IEC 60068-2-27

25 g / 11 ms

Resistance to vibrations acc. to IEC 60068-2-6

2 g / 5…150 Hz

Number of poles

1 N.C. + 1 N.O. or 2 N.O. or 2 N.C.

Ie / Rated operational current AC-15 acc. to IEC/EN 60947-5-1 for utilization category
24 V, 50/60 Hz 3

6

120 V, 50/60 Hz 3

6

230 V, 50/60 Hz 1.5

4

400 V, 50/60 Hz -

3

690 V, 50/60 Hz -

1

Ie / Rated operational current DC-13 acc. to IEC/EN 60947-5-1 for utilization category
24 V 1.0

2

125 V 0.27

0.55

250 V 0.10

0.27

600 V -

0.15

Minimum switching capacity

17 V / 5 mA

Short-circuit protective device

10 A Type gG

Duty time

100 %

Mounting

Front of MMS

Mounting positions

1-6

Mechanical durability

100000 cycles

Electrical durability

100000 cycles

Right side of MMS

Contact utilization characteristics per UL/CSA
Type

HKF1-xx

Standards

HK1-xx

UL 508/60947-4-1A, CAN/CSA C22.2 No.14/60947-4-1-07

Rated voltage UL/CSA

240 V AC/ 250 V DC

600 V AC/ 600 V DC

Pilot duty

B300, Q300

B600, Q600

AC thermal rated current 5
AC maximum volt-ampere making 3600
AC maximum volt-ampere breaking 360
DC thermal rated current 2.5
DC maximum volt-ampere make/break 69

Connecting characteristics
Type

HKF1-xx

HK1-xx

HK1-20L

Connecting capacity
Solid

1 or 2 x

1...1.5 mm²

Flexible

1 or 2 x

0.75...1.5 mm²

Flexible with non-insulated ferrule

1 or 2 x

0.75...1.5 mm²

Flexible with insulated ferrule

1 or 2 x

0.75...1.5 mm²

Stranded acc. to UL/CSA

1 or 2 x

AWG 16-14

Flexible acc. to UL/CSA

1 or 2 x

AWG 16-14

Stripping length

8 mm

Tightening torques

0.8...1.2 Nm / 7...10.3 Ib.in

Connection screw

Pozidriv 2 / M3

4.26	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Technical data - IEC/EN
MS45x & MS49x
Main circuit – Utilization characteristics according to IEC/EN
Type

MS45x, MS49x

Standards
Rated operational voltage Ue
Rated frequency
Trip class
Number of poles
Duty time
Rated impulse withstand voltage Uimp
Rated insulation voltage Ui
Rated operational current Ie
Rated instantaneous short-circuit current setting Ii
Rated service short-circuit breaking capacity Ics
Rated ultimate short-circuit breaking capacity Icu

IEC/EN 60947–2, IEC/EN 60947-4-1, IEC/EN 60947-1
690 V AC / 450 V DC
50/60 Hz
10, 20
3
100 %
6 kV
690 V AC
See ordering details
See ordering details
See table "Short-circuit breaking capacity and back-up fuses"
See table "Short-circuit breaking capacity and back-up fuses"

4

Short-circuit breaking capacity and back-up fuses
lCS Rated service short-circuit breaking capacity
lCU Rated ultimate short-circuit breaking capacity
ICC Prospective short-circuit current at installation location
Note: Maximum rated current of the back-up fuses if ICC > ICS
Type

240 V AC
ICS
kA

400 V AC
ICU
kA

gG, aM
A

ICS
kA

440 V AC
ICU
kA

gG, aM
A

ICS
kA

500 V AC
ICU
kA

gG, aM
A

ICS
kA

690 V AC
ICU
kA

gG, aM
A

ICS
kA

ICU
kA

gG, aM
A

10
10
10

100
100
100

2
2
2

4
4
4

63
63
80

12
12
12
8
8
8

125
125
160
160
160
160

3
3
3
3
3
3

6
6
6
5
5
5

63
80
80
100
125
125

Short-circuit protection MS45x
MS45x-40
MS45x-45
MS45x-50
MS45x:	
	

25
50
160
15
50
125
5
25
50
160
15
50
125
5
25
50
160
15
50
125
5
No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V.
With an appropriate 160 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.
No back-up fuse required up to
ICC = 100 kA

Short-circuit protection MS49x
25
50
125
20
50
125
6
MS49x-40
MS49x-50
25
50
125
20
50
125
6
MS49x-63
50
160
20
50
160
6
No back-up fuse required up to 25
ICC = 100 kA
MS49x-75
25
50
160
20
50
160
6
MS49x-90
25
50
160
20
50
160
6
MS49x-100
25
50
160
20
50
160
6
MS49x-40:	 No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V.
	
With an appropriate 125 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.
MS49x-100: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V.
	
With an appropriate 160 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.

4.27

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Technical data - UL/CSA
MS45x & MS49x

Main circuit – Utilization characteristics according to UL/CSA

4

Type

MS45x, MS49x

Standards

UL 508, CSA 22.2 No. 14

Maximum operational voltage

600 V AC

Manual motor controller ratings

See table “UL 508 – Manual motor controller”

Trip rating

125 % FLA

Motor ratings

Horsepower

See table “Motor rating, three phase”

Full load amps (FLA)

See table “Motor rating, three phase”

Locked rotor amps (LRA)

See table “Motor rating, three phase”

Motor rating, three phase
hp

Horsepower

FLA

Full load amps (FLA)

LRA

Locked rotor amps (LRA)

Type

208 V AC
hp

220-240 V AC

440-480 V AC

550-600 V AC

FLA

LRA

hp

FLA

LRA

hp

FLA

LRA

hp

FLA

LRA

Types MS450 / MS451
MS451-16

5

16.7

102.0

5

15.2

92.0

10

14.0

81.0

15

17.0

93.0

MS451-20

5

16.7

102.0

7.5

22.0

92.0

15

21.0

116.0

20

22.0

116.0

MS451-25

7.5

24.2

140.0

10

28.0

127.0

20

27.0

145.0

25

27.0

146.0

MS451-32

10

30.8

179.0

10

28.0

162.0

25

34.0

183.0

30

32.0

174.0

MS45x-40

15

46.2

257.0

15

42.0

232.0

30

40.0

218.0

40

41.0

232.0

MS45x-45

15

46.2

257.0

15

42.0

232.0

30

40.0

218.0

40

41.0

232.0

MS45x-50

15

46.2

257.0

20

54.0

232.0

40

52.0

290.0

50

52.0

290.0

Types MS495 / MS496
MS49x-40

15

46.2

257.0

15

42.0

232.0

30

40.0

218.0

40

41.0

232.0

MS49x-50

15

46.2

257.0

20

54.0

232.0

40

52.0

290.0

50

52.0

290.0

MS49x-63

20

59.4

321.0

25

68.0

290.0

50

65.0

363.0

60

62.0

348.0

MS49x-75

25

74.8

404.0

25

68.0

365.0

60

77.0

435.0

75

77.0

434.0

MS49x-90

30

88.0

481.0

30

80.0

435.0

75

96.0

543.0

100

99.0

580.0

MS49x-100

40

114.0

641.0

40

104.0

580.0

75

96.0

543.0

100

99.0

580.0

4.28	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Technical data
MS45x & MS49x
General technical data
Type

MS45x

Pollution degree
Phase loss sensitive
Ambient air temperature
Operation

3
Yes
Open - compensated without derating
Open

MS49x

4

-20 ... +60 °C
-20 ... +70 °C

Enclosed
Storage
Ambient air temperature compensation
Maximum operating altitude permissible
Resistance to shock acc. to IEC 60068-2-27
Resistance to vibrations acc. to IEC 60068-2-6

-20 ... +35 °C
-50 ... +80 °C
Continuous
2000 m
25 g / 11 ms
2 g / 5-150 Hz

Mounting position
Mounting
Minimum distance to other units Horizontal
same type
Vertical - up to 240 V
Vertical - up to 440 V
Vertical - up to 500 V
Vertical - up to 690 V
Vertical
Horizontal
Minimum distance to
electrical conductive board
Horizontal - up to 500 V
Horizontal - up to 690 V
Vertical - up to 240 V
Vertical - up to 440 V
Vertical - up to 500 V
Vertical - up to 690 V
Vertical
Degree of protection
Enclosure / terminals

Position 1-6 (optional for single mounting)
DIN-rail 35 mm (EN 60715)
DIN-rail 15 mm / 75 mm (EN 60715)
0 mm
0 mm
50 mm
70 mm
110 mm
150 mm
50 mm
10 mm
10 mm
30 mm
50 mm
70 mm
110 mm
150 mm
50 mm
IP20

-

Main circuit – Connecting characteristics
Type

MS45x

MS49x

0.75 ... 16 mm²
0.75 ... 35 mm²
0.75 ... 25 mm²
AWG 18-2
AWG 18-2
AWG 18-2
AWG 18-2
13 mm
3 - 4.5 Nm / 27 … 40 Ib.in
Pozidriv 2

2.5 ... 16 mm²
10 ... 70 mm²
10 ... 50 mm²
AWG 10-2/0
AWG 10-1/0
AWG 10-2/0
AWG 10-1/0
17 mm
4 - 6 Nm / 35 - 53 Ib.in
Hexagon 4

Connecting capacity
Solid
Flexible
Stranded acc. to UL/CSA
Flexible acc. to UL/CSA
Stripping length
Tightening torques
Connection screw

1 or 2 x
1x
2x
1x
2x
1x
2x

4.29

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Technical data
MS45x & MS49x Accessories

General technical data

4

Type

PS4-xxx

Standards

IEC/EN 60947-1

Rated operational voltage Ue

690 V AC

Rated operational current Ie

108 A

Rated frequency

50/60 Hz

Rated impulse withstand voltage Uimp

6 kV

Rated insulation voltage Ui

690 V AC

Pollution degree

3

Cross-section

10 mm2

Ambient air temperature

Operation

-25... +70°C

Storage

-50... +80°C

S4-M1

25 mm2

Main circuit – Connection characteristics
Type

S4-M1

Connecting capacity
Solid

1x

2.5... 50 mm2

1x

4... 16 mm2

Stranded acc. to UL/CSA

1x

AWG 14-4

Flexible acc. to UL/CSA

1x

AWG 14-4

Flexible

Tightening torques

4 Nm

Connection screw

Pozidriv 2

General technical data
Type

UA4

Standards

IEC/EN 60947-1, UL 508/60947-4-1A, CAN/CSA C22.2 No.14/60947-4-1-07

AA4

Pick-up value

% of Uc ≥ 85

≥ 70

Drop-out value

% of Uc 35…70

-

Power

Pick-up

VA 20.2

Consult factory

consumption

Holding

VA 7.2

Consult factory

Connection characteristics
Type

UA4

AA4

Connecting capacity
Solid

1x

0.5... 2.5 mm²

2x

0.5...1.5 mm² or 0.75...2.5 mm

1x

0.5...2.5 mm²

2x

0.5...1.5 mm² or 0.75...2.5 mm

Stranded acc. to UL/CSA

1 or 2 x

AWG 18-14

Flexible acc. to UL/CSA

1 or 2 x

AWG 18-14

Flexible

Stripping length

10 mm

Tightening torques

0.8...1.2 Nm / 7...10.3 Ib.in

Connection screw

Pozidriv 2 / M3

4.30	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Technical data
MS45x & MS49x Accessories
General technical data
Type

HK4-11

Standards

IEC/EN 60947-1, IEC/EN 60947-5-1, UL 508, CSA22.2 No. 14

HK4-W

HKS4

SK4

Rated operational voltage Ue

230 V AC/220 V DC

690 V AC / 220 V DC

690 V AC

690 V AC

Conventional free-air thermal current Ith

2.5 A

5A

10 A

10 A

Rated frequency

DC, 50/60 Hz

Rated impulse withstand voltage Uimp

6 kV
300 V

690 V

690V

Rated insulation voltage Ui

300 V

Pollution degree

3

Ambient air temperature

Operation

-20 ... +70°C

Storage

-50 ... +80°C

Resistance to shock acc. to IEC 60068-2-27

25 g/11 ms

Resistance to vibrations acc. to IEC 60068-2-6

2 g / 5 ... 150 Hz

Number of poles

1 N.C. + 1 N.O.

Changeover

1 N.C. + 1 N.O. /
2 N.O. / 2 N.C.

2 N.C. + 2 N.O.

24 V , 50/60 Hz

2A

4A

6A

6A

230 V, 50/60 Hz

0.5 A

3A

4A

4A

400 V, 50/60 Hz

–

1.5 A

3A

3A

690 V, 50/60 Hz

–

0.5 A

1A

1A

24 V

1A

1A

2A

2A

48 V

0.3 A

–

–

–

60 V

0.15 A

–

–

–

110 V

–

0.22 A

0.5 A

0.5 A

230 V

–

0.1 A

0.25 A

0.25 A

Front of MMS

Left side of MMS

Left side of MMS

HK4-W

HKS4

SK4

4

Ie / Rated operational current AC-15
acc. to IEC/EN 60947-5-1 for utilization category

Ie / Rated operational current DC-13
acc. to IEC/EN 60947-5-1 for utilization category

Minimum switching capacity

17 V / 1 mA

Short-circuit protective device

10 A Type gG

Duty time

100%

Mounting

Front of MMS

Mounting positions

1-6

Mechanical durability

100,000 cycles

Electrical durability

100,000 cycles

Main circuit – Connecting characteristics
Type

HK4-11

Connecting capacity

Solid

1x

0.5... 2.5 mm2

2x

0.5... 1.5 mm2 or 0.75... 2.5 mm

1x

0.5... 2.5 mm2

2x

0.5... 1.5 mm2 or 0.75... 2.5 mm

Stranded acc. to UL/CSA

1 or 2x

AWG 18-14

Flexible acc. to UL/CSA

1 or 2x

AWG 18-14

Flexible

Stripping length

10 mm

Tightening torques

0.8... 1.2 Nm / 7... 10.3 lb.in.

Connection screw

Pozidriv 2

4.31

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Approximate dimensions

MS116-0.16... MS116-16, MS132-0.16…MS132-10

MS116-0.16…MS116-16 or MS132-0.16…MS132-10 + UA1, AA1,
SK1, HK1, CK1, HKF1-11

80,1 / 3,15"
1,5 / 0,06"

70 / 2,76"
5,5 / 0,22"

43,5 / 1,71"
81 3.19"

4

86.5 3.41"

9 0.35"

18 0.71"

14 / 0,55"

57.8 2.28"

90 3.54"

45 / 1,77"

57,8 / 2,3"

35 / 1,38"

75 / 2,95"

27,5 / 1,1"

1,7 / 0,07"

90 / 3,54"

9 0.35"

14 / 0,55"
45 / 1,77"

MS116-20... MS116-32, MS132-12... MS132-32

MS116-20... MS116-32 or MS132-12... MS132-32 + UA1, AA1, SK1,
HK1, CK1, HKF1-11

79,9 / 3,15"
69,8 / 2,75"
5,5 / 0,22"

1,5 / 0,06"

43,3 / 1,7"

81 3.19"
18 0.71"

86.5 3.41"

9 0.35"

14 / 0,55"

57.8 2.28"

97.8 3.85"

45 / 1,77"

57,8 / 2,3"

35 / 1,38"

75 / 2,95"

27,5 / 1,1"

1,7 / 0,07"

97,8 / 3,85"

9 0.35"

14 / 0,55"
45 / 1,77"

IB132-x

DMS132-x
135.7 5.34"

92 3.62"

24 .94"

118 4.65"

119 4.69"

174 6.85"

0
OFF

194 7.64"

I ON

0
OFF

183 7.2"

121 4.76"

I ON

116.15 4.57"

4.32	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage

M MS
an Se
pr ual ries
ot m
ec ot
to or
rs

Approximate dimensions

MS450-40…MS450-50, MS451-16…MS451-50
17

0.67"

10

0.39"

20

MS495-40…MS495-100, MS496-40…MS496-100
12

0.79"

23

0.47"

8

0.91"

0.31"

30

1.18"

55

2.17"

8 0.32"
109 4.29"
127 5.0"
132 5.2"
144 5.67"

45
116
150
30 1.18"
70

2.56"

7
5

0.20"

0.28"
132 5.20"
153 6.02"
169 6.65"

4.33

Low Voltage Products & Systems	
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage	

1.77"
4.57"
5.91"

6.50"
6.10"

85
130
140
5 0.20"

165
155

1.77"

3.35"
5.12"
5.51"

45

125

4.92"

4

Revised March 2014

1SXU000023C0202 Rev. A

s
rie or
Se mot
MS ual tors
n ec
Ma rot
p

Notes

4

4.34	
1SXU000023C0202 Rev. A	

Low Voltage Products & Systems

Revised March 2014

ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Create Date                     : 2014:03:26 15:40:52-05:00
Metadata Date                   : 2014:03:26 15:46:58-05:00
Modify Date                     : 2014:03:26 15:46:58-05:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:e7e7d450-0b47-42b6-b29d-a3ff10e4ea57
Original Document ID            : adobe:docid:indd:bc19200c-9b88-11dd-9069-9c3ea2bffbfe
Document ID                     : xmp.id:1AD231BD26B5E3118BEF95DD50BAA40D
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:19D231BD26B5E3118BEF95DD50BAA40D
Derived From Document ID        : xmp.did:65B5874ABAFEE111A2DDE9BD451FA54E
Derived From Original Document ID: adobe:docid:indd:bc19200c-9b88-11dd-9069-9c3ea2bffbfe
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2014:03:26 15:40:52-05:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Layout                     : TwoColumnRight
Page Mode                       : UseThumbs
Page Count                      : 36
Creator                         : Adobe InDesign CS6 (Windows)
EXIF Metadata provided by EXIF.tools

Navigation menu