Brochure

97101-Catalog 97101-Catalog 97101-Catalog 785901 Batch6 unilog cesco-content

2014-07-30

: Pdf 117125-Brochure 117125-Brochure 785901 Batch6 unilog

Open the PDF directly: View PDF PDF.
Page Count: 5

www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
© 2009 Schneider Electric
All Rights Reserved 7-5
Selection Information Molded Case Circuit Breakers
Class 500, 600, 800
100 A F-Frame PowerPact 250 A J-Frame PowerPact 250 A Q-Frame
Circuit Breaker Type FI FY JD JG JJ JL QB QD QG QJ
Number of Poles 2, 3 1 2,3a2,3a2,3a2,3a2, 32, 32, 32, 3
Current Range 20–100 15–30 150–250 A 150–250 A 150–250 A 150–250 A 70–250b70–250b70–250b70–250b
Interrupting Ratings
UL/CSA/NOM
Rating
(kA RMS)
(50/60 Hz)
240 Vac 200 14 25 65 100 125 10 25 65 100
480Y/277 Vac 200 14 18 35 65 100
480 Vac 200 18 35 65 100
600Y/347 Vac10014182550
600 Vac 100 14 18 25 50
DC Ratings 250 Vdc—20202020
500 Vdcc———20——————
IEC Rating
(kA RMS)
Icu/lcsd
240 Vac 25/25 65/65 100/100 125/125 10/5 10/5 10/5 10/5
415 Vac 6/1.5 18/18 35/35 65/65 100/100 10/5 10/5 10/5 10/5
IEC 50/60 Hz For additional IEC ratings, see
the Supplemental Digest.
Special Ratings
Fed. Specs W-C-375B/GENXXXXXXXXX
HACR (2P, 3P) XXXXXXX
Connections/Terminations
Unit Mount XXXXXXXXX
I-Line®XXXXXXXXXX
Rear Connection X X X X
Drawout —— X X X X ————
Optional Lugs X X X X X
Accessories and Modifications
Shunt Trip Xf X X X X ————
Undervoltage Trip Xf X X X X ————
Auxiliary Switches Xf X X X X ————
Alarm Switch Xf X X X X ————
Motor Operator X X X X X
Handle Operators X X X X
Mechanical Interlocks (3P) XXXXXXXX
Handle Padlock AttachmentXXXXXXXXXX
Cylinder Lock (3Pf) ——————————
Optional GF ProtectioneX —————————
Trip System Type
Thermal-magnetic XXXXXXXXXX
Instantaneous-only (MCP) XgXg—————
Molded Case Switch (Automatic) X X X X X
Electronic —————————
Enclosures (Pages 7-56–7-58)
General Purpose (NEMA 1) X X X X X X X X
Raintight (NEMA 3R) X X X X X X X X
Dust-tight (NEMA 12) X X X X —————
Watertight (NEMA 4, 4X, 5) X X X X
Explosion Proof (NEMA 7, 9)
Dimensions
(3P Unit Mount)
in. (mm)
Height 8 (203) 7.5 (191) 6.47 (164)
Width 4.5 (114) 4.1 (104) 4.5 (114)
Depth 4.75 (121) 3.4 (86) 3.93 (100)
Pages (Unit Mount)/(I-Line) Pages 7-49/9-24 Pages 7-22, 7-23, 7-28, 7-33, 7-34/9-25 Pages 7-24/9-24
Note: All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted.
a2P in a 3P module
bI-Line Q-frame circuit breakers are available 70–225 A only. 250 A Q-frame unit-mount circuit breakers are limited to Cu conductors only.
cUngrounded UPS systems only. See page 7-34. Special DC J-Frame only.
dDual UL and IEC ratings and CE markings on circuit breakers. For additional IEC ratings, see the Supplemental Digest.
eRequires factory-installed “G” shunt trip and 3P module.
fFactory-installed option only.
g3P only.
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
© 2009 Schneider Electric
All Rights Reserved 7-21
PowerPact® Molded Case
Circuit Breakers
PowerPact Family
Class 611
The PowerPact Advantage
Proven Performance: Industry-leading circuit breaker innovation and protection for heavy-duty commercial and industrial
applications.
Flexible: Full range of molded case circuit breakers from 15 A to 3000 A, delivering the ratings, configurations, and operators for
your unique applications.
Simple: Common catalog numbers, standardized ratings, and a full range of field-installable accessories make product selection,
installation and maintenance easier than ever.
Common Design Features: Mounting holes, door trim, and handle accessories
aP-frame K interrupting is 50 kA at 480 and 600 Vac.
bFor amperage of M-, P- or R-frame circuit breakers, add a zero to the three amperage digits; for example, 120 = 1200 A.
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
H- and J-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
H- and J-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23
G- and Q-Frame Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24
D- and M-Frame Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25
P-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26
R-Frame Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
PowerPact® H- and J-Frame Electronic Motor Circuit Protectors . . . . . . 7-28
Mag-Gard® Motor Circuit Protectors (MCP). . . . . . . . . . . . . . . . . . . . . . . 7-30
Automatic Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-33
500 Vdc Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-34
Mission Critical Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-35
PowerPact® Circuit Breaker Accessories. . . . . . . . . . . . . . . . . . . . . . . . . 7-36
Motor Operators and Rotary Handles . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-37
Locks, Installation Accessories, and Rear Connections . . . . . . . . . . . . . 7-38
Mechanical Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-38
Compression Lugs and Power Distribution Connectors (PDC). . . . . . . . 7-40
Terminal Nuts, Terminal Pads, Terminal Shields and Accessories . . . . . 7-41
Plug-In and Drawout Mountings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-42
Micrologic® Electronic Trip Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-43
Micrologic Trip Unit Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-44
G-Frame
100 A H-Frame
150 A J-Frame
250 A Q-Frame
250 A D-Frame
600 A M-Frame
800 A P-Frame
1200 A R-Frame
3000 A
Table 7.35: PowerPact Interrupting Ratings
Voltage Interrupting Rating
BDGJKL
240 Vac 10 kA 25 kA 65 kA 100 kA 65 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 65 kA a100 kA
600 Vac 14 kA 18 kA 25 kA 65 kA a50 kA
Table 7.36: Common Catalog Numbering System
Frame
Rating
Termination
Poles
Voltage
Amperage
b
Suffix
Code
Suffix
Code
HGL361 5 0 ABS A
110 Vac Shunt Trip
2A/2B Auxiliary Switch
Frame Designation Interrupting Rating Terminations
G 100A Frame 240
Vac 480
Vac 600
Vac
A I-Line
H 150 A Frame L Lugs on Both Ends
J 250 A Frame B 10 kA F Bus Bar (No Lugs)
Q 250 A Frame D 25 kA 18 kA 14 kA M Lugs Line Side Only
D 600 A Frame G 65 kA 35 kA 18 kA P Lugs Load End Only
M 800 A Frame J 100 kA 65 kA 25 kA N Plug-in
P 1200 A Frame K 65 kA 65 kA 65 kA D Drawout
R 3000 A Frame L 125 kA 100 kA 50 kA S Rear Connected Studs
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
7-22 © 2009 Schneider Electric
All Rights Reserved
PowerPact® Circuit
Breakers
H- and J-Frame Circuit Breakers
Class 611 / Refer to Catalog 0611CT0401
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-36
Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-39
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-55
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-56
HD and HG 2P
2P HJ, HL in 3P module
H-Frame
J-Frame
Table 7.37: H-Frame 150 A and J-Frame 250 A Thermal-Magnetic UL Current-Limitinge Circuit Breakers
(600 Vac, 250 Vdc) With Factory Sealed Trip Unit Suitable for Reverse Connectiona
Current
Rating @
40o C
Fixed AC
Magnetic
Trip Cat. No.bc
Interrupting Rating (2nd Letter of Catalog Number)
D G JeLe
Terminal
Wire Range
$ Price
Hold Trip 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
H-Frame, 150A 2P, 600 Vac 50/60 Hz, 250 Vdc
15 A 350 A 750 A H( )L26015(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
AL150HD
14–3/0 AWG
Al or Cu
20 A 350 A 750 A H( )L26020(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
25 A 350 A 750 A H( )L26025(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
30 A 350 A 750 A H( )L26030(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
35 A 400 A 850 A H( )L26035(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
40 A 400 A 850 A H( )L26040(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
45 A 400 A 850 A H( )L26045(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
50 A 400 A 850 A H( )L26050(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
60 A 800 A 1450 A H( )L26060(C) 870.00 1044.00 1269.00 1523.00 1559.00 1871.00 2364.00 2837.00
70 A 800 A 1450 A H( )L26070(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
80 A 800 A 1450 A H( )L26080(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
90 A 800 A 1450 A H( )L26090(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
100 A 900 A 1700 A H( )L26100(C) 1062.00 1274.00 1497.00 1797.00 1721.00 2066.00 2613.00 3137.00
110 A 900 A 1700 A H( )L26110(C) 2072.00 2486.00 3059.00 3671.00 4449.00 5339.00 5534.00 6641.00
125 A 900 A 1700 A H( )L26125(C) 2072.00 2486.00 3059.00 3671.00 4449.00 5339.00 5534.00 6641.00
150 A 900 A 1700 A H( )L26150(C) 2072.00 2486.00 3059.00 3671.00 4449.00 5339.00 5534.00 6641.00
H-Frame 150A 3P, 600 Vac 50/60 Hz, 250 Vdc
15 A 350 A 750 A H( )L36015(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
AL150HD
14–3/0 AWG
Al or Cu
20 A 350 A 750 A H( )L36020(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
25 A 350 A 750 A H( )L36025(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
30 A 350 A 750 A H( )L36030(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
35 A 400 A 850 A H( )L36035(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
40 A 400 A 850 A H( )L36040(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
45 A 400 A 850 A H( )L36045(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
50 A 400 A 850 A H( )L36050(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
60 A 800 A 1450 A H( )L36060(C) 1088.00 1305.00 1493.00 1791.00 1949.00 2339.00 2849.00 3419.00
70 A 800 A 1450 A H( )L36070(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
80 A 800 A 1450 A H( )L36080(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
90 A 800 A 1450 A H( )L36090(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
100 A 900 A 1700 A H( )L36100(C) 1328.00 1592.00 1701.00 2042.00 2099.00 2519.00 3149.00 3779.00
110 A 900 A 1700 A H( )L36110(C) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
125 A 900 A 1700 A H( )L36125(C) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
150 A 900 A 1700 A H( )L36150(C) 2600.00 3120.00 3599.00 4319.00 5174.00 6209.00 6749.00 8099.00
Current
Rating @
40oC
Adjustable AC
Magnetic
Trip Cat. No.bc
Interrupting Rating (2nd Letter of Catalog Number)
D G JeLe
Terminal
Wire Range
$ Price
Low High 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
J-Frame 250A 2P, 600 Vac 50/60 Hz, 250 Vdc
150 A 750 A 1500 A J( )L26150(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00 AL175JD
4–4/0 AWG Al or Cu
175 A 875 A 1750 A J( )L26175(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00
200 A 1000 A 2000 A J( )L26200(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00 AL250JD
3/0 AWG–350 kcmil
Al or Cu
225 A 1125 A 2250 A J( )L26225(C) 2175.00 2610.00 3212.00 3854.00 4671.00 5606.00 5811.00 6972.00
250 A 1250 A 2500 A J( )L26250(C) 2988.00 3585.00 4251.00 5102.00 6225.00 7469.00 7194.00 8633.00
J-Frame 250A 3P, 600 Vac 50/60 Hz, 250 Vdc
150 A 750 A 1500 A J( )L36150(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00 AL175JD
4–4/0 AWG Al or Cu
175 A 875 A 1750 A J( )L36175(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00
200 A 1000 A 2000 A J( )L36200(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00 AL250JD
3/0 AWG–350 kcmil
Al or Cu
225 A 1125 A 2250 A J( )L36225(C) 2730.00 3276.00 3779.00 4535.00 5432.00 6519.00 7086.00 8504.00
250 A 1250 A 2500 A J( )L36250(C) 3749.00 4499.00 5001.00 6002.00 7238.00 8685.00 8993.00 10791.00
aSee page 7-23 for circuit breakers with field interchangeable trip units.
bTo complete catalog number, replace the blank with the appropriate rating (D, G, J, L).
cFor 100% rated circuit breakers add a “C” in the 9th character place (for example, HDL26015C or JDL26150C).
d100% rated J frame breakers have copper lugs and can only be used with copper wire.
eJ and L interrupts are UL certified as current limiting.
Table 7.38: H- and J-Frame Termination Options
Termination Letter
A - I-Line (See Section 9)
F = No Lugs (includes terminal nut kit on both ends)f
L = Lugs both ends
M = Lugs ON end Terminal Nut Kit OFF end
P = Lugs OFF end Terminal Nut Kit ON end
N = Plug-in g
D = Drawout g
S = Rear Connected g
fAdd TS suffix for circuit breaker without terminal nut kit.
gFor N and D pricing, add termination pricing on page 7-42 to price. For S pricing, add termination pricing on page 7-38 to price.
H G L 3 6 1 0 0
For factory-installed
termination, place termination
letter in the third block of the
circuit breaker catalog number.
Termination Letter
Plug-in Drawout Rear Connected
Table 7.39: H- and J-Frame Interrupting Ratings
Voltage Interrupting Rating
DGJ L
240 Vac 25 kA 65 kA 100 kA 125 kA
480 Vac 18 kA 35 kA 65 kA 100 kA
600 Vac 14 kA 18 kA 25 kA 50 kA
DE2 Discount
Schedule
7-36 © 2009 Schneider Electric
All Rights Reserved
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
PowerPact® Circuit
Breaker Accessories
Electrical Accessories
Class 612 / Refer to Catalog 0612CT0101
Table 7.77: Electrical Accessories
Accessory Description Rated Voltage
G-Frame H-, J-, and D-Frame M-, P-, and R-Frame
Field-
Installable
Cat. No. $ Price Factory-
Installed
Cat. Suffix
H- and J-Frame D-Frame Factory
Installed
Cat. Suffix
Field-
Installable
Cat. No. $ Price
Field-
Installable
Cat. No. $ Price Field-
Installable
Cat. No. $ Price
Auxiliary and Alarm Switches
(OF, SD, SDE) Provides
circuit
breaker
contact
status.
Note: The
location of
the
accessory
in the circuit
breaker
determines
its function.
Standard
Min
Load =
10mA with
24V
1 auxiliary switch (OF) 1a1b AAC 297.00 AA S29450 297.00 S29450 297.00 AA S29450 297.00
2 auxiliary switch (OF) 2a2b AB 2x S29450 594.00 2x S29450 594.00 AB 2x S29450 594.00
3 auxiliary switch (OF) 3a3b AC 3x S29450 891.00 AC 3x S29450 891.00
Alarm Switch (SD) 1a1b AAC 297.00 BC S29450 297.00 S29450 297.00 BC S29450 297.00
Overcurrent trip switch (SDE)
1a1b ——BD338.00 S29450 297.00 BD S29450 297.00
Consisting of: OF Switch S29450 297.00 —— — —
SDE Adapter S29451 40.50 —— — —
Alarm switch and Overcurrent trip
switch ——BE —635.00 2x S29450 594.00 BE 2x S29450 594.00
Consisting of: OF Switch 2x S29450 594.00 —— — —
SDE Adapter S29451 40.50 —— — —
Auxiliary Switch/Alarm
Switch/Adapter (OF/SD/SDE) Kit —— — —S33801c297.00
Low Level
Min
Load =
1mA with
24V
One auxiliary switch (OF) 1a1b AE S29452 372.00 S29452 372.00 AE S29452 372.00
Two auxiliary switches (OF) 2a2b AF 2x S29452 744.00 2x S29452 744.00 AF 2x S29452 744.00
3 auxiliary switches (OF) 3a3b AG 3x S29452 1116.00 AG 3x S29452 1116.00
Alarm Switch (SD) 1a1b BH S29452 372.00 S29452 372.00 BH S29452 372.00
Overcurrent trip switch (SDE)
1a1b ——BJ413.00 S29452 372.00 BJ S29452 372.00
Consisting of: OF Switch S29452 372.00 —— — —
SDE Adapter S29451 40.50 —— — —
Alarm switch and Overcurrent trip
switch BK — 785.00 2x S29452 744.00 BK 2x S29452 744.00
Consisting of: OF Switch 2x S29452 744.00 —— — —
SDE Adapterd——S29451 40.50 —— — —
Shunt Trip (MX)
Trips the circuit
breaker from a remote
location by means of a
trip coil energized from
a separate supply
voltage circuit.
AC
24 —
717.00
SK S29384
717.00
S29384
717.00
SK S33659
755.00
48 SL S29385 S29385 SL S33660
120 GSA —— — —
110/130 SA S29386 S29386 SA S33661
208 GSB —— — —
240 GSC —— — —
200/250 SC S33662
277 GSD —— — —
208/277 SD S29387 S29387 SD S33663
480 GSH ——
380/480 SH S29388 S29388 SH S33664
525/600 SJ S29389 S29389 ——
DC
12 —
717.00
SN S29382
717.00
S29382
717.00
SN S33658
755.00
24 GSO SO S29390 S29390 SK S33659
30 SU S29391 S29391 SK S33659
48 GSP SP S29392 S29392 SL S33660
60 SV S29383 S29383 SL S33660
125 GSR SR S29393 S29393 SA S33661
250 GSS SS S29394 S29394 SC S33662
Undervoltage Trip
Instantaneously
opens the circuit
breaker when the
under-voltage trip
supply voltage drops
to a value between
35% and 70% of its
rated voltage. Closing
is allowed when the
supply voltage of the
undervoltage trip
reaches 85% of rated
voltage.
AC
24 —
717.00
UK S29404
717.00
S29404
717.00
UK S33668
755.00
48 UL S29405 S29405 UL S33669
120 GUA ——
110/130 UA S29406 S29406 UA S33670
208 GUB ——
240 GUC ——
200/250 UC S33671
277 GUD ——
208/277 UD S29407 S29407 ——
480 GUH ——
380/480 UH S29408 S29408 UH S33673
525/600 UJ S29409 S29409 ——
DC
12 —
717.00
UN S29402
717.00
S29402
717.00
——
755.00
24 GUO UO S29410 S29410 UK S33668
30 UU S29411 S29411 UK S33668
48 GUP UP S29412 S29412 UL S33669
60 UV S29403 S29403 UL S33669
125 GUR UR S29413 S29413 UA S33670
250 GUS US S29414 S29414 UC S33671
Undervoltage trip with
externally mounted
adjustable time delay
unit for UVR of 0.5,
0.9, 1.5, 3.0 seconds
before circuit breaker
trips
AC/DC
48/60 — — FL S33680a
b
1140.00
100/130 — — FA S33681a
b
200/250 — — FC S33682a
b
380/480 — — FH S33683a
b
Undervoltage trip with
externally mounted
non-adjustable time
delay unit of 0.25 sec
before circuit breaker
trips.
AC/DC
100/130 — — KA S33684a
b
930.00
200/250 — — KC S33685a
b
aField-installable kit includes time delay module only. Order undervoltage trip separately.
bDiscount schedule DE2F.
cP-frame drawout circuit breaker only.
dSDE Adapter used for H- and J-frame only.
G-Frame
H-, J-, D-, M-, P,
and R-Frame
G-Frame
H-, J-, and
D-Frame
G-Frame
H-, J-, and
D-Frame
Time Delay Unit
DE2 DE2F Discount
Schedule
www.schneider-electric.us
7MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
© 2009 Schneider Electric
All Rights Reserved 7-55
Dimensions and Shipping Weights
Molded Case Circuit Breakers
aAll weights are for 3P circuit breakers unless otherwise noted.
A
B
E
F
C
D
Figure 26
A
E
F
B
G
Figure 25
E
G
A
B
C
D
F
Figure 27
A
C
D
B
G
F
Figure 28
A
AA
EBBEEB
C
D
Figure 29 Figure 30Figure 31
Figure 32
A
EB
C
D
F
E
E
A
DC
G
B
Figure 33
G
B
F
E
A
DC
Figure 34
Table 7.143: HD, HG, HJ, HL, JD, JG, JJ, JL, DG, DJ, and DL
Circuit Breakers
Circuit Breaker
Cat. No.
Prefix
No. of
Poles Fig. No. Dimensions — Inches
ABCDEFG
HD, HG, HJ, HL 2 25 6.40 2.74 2.87 4.36 0.74 4.92
3 26 6.40 4.12 2.87 4.36 0.74 4.92 1.38
JD, JG, JJ, JL 3 27 7.52 4.12 2.87 5.00 1.30 4.92 1.38
DG, DJ, DL 3 28 13.38 5.51 3.75 6.61 2.22 8.93 1.77
Table 7.144: ED, EG, EG and GJL Circuit Breakers
Circuit Breaker
Cat. No.
Prefix
No. of
Poles Fig. No. Dimensions — Inches
ABCDE
ED, EG, EJ 1 29 0.98 5.66 3.09 4.05 3.32
ED, EG, EJ 2 30 1.96 5.66 3.09 4.05 3.32
ED, EG, EJ 3 31 2.94 5.66 3.09 4.05 3.32
GJ 3 32 3.54 4.72 2.76 3.94 2.20
Table 7.145: MG, MJ, PG, PJ, PL, RG, RJ and RL Circuit Breakers
Circuit Breaker
Cat. No.
Prefix
No. of
Poles Fig.
No.
Dimensions — Inches
A BCDEF G
MG, MJ
(800 A and below) 2, 3 33 12.86 8.27 5.77 8.05 2.49 7.87 7.83
PG, PJ, PK, PL
(1000–1200 A) 2, 3 33 16.16 8.27 5.77 8.05 4.19 7.87 7.83
RG, RJ, RL 2, 3 34 16.24 16.54 6.63 14.49 8.73 14.25 15.35
Table 7.146: Shipping Weightsa
Frame Size Approx. Shipping
Weight (Lbs.) Frame Size Approx. Shipping
Weight (Lbs.)
HD, HG, HJ, HL 2P 4 DG, DJ, DL 14
HD, HG, HJ, HL 3P 5 GJ 3
JD, JG, JJ, JL 5 MG, MJ 34
ED, EG, EJ 1P 2 PG, PJ, PL 32
ED, EG, EJ 2P 3 RG, RJ, RL (Without RLTB) 52
ED, EG, EJ 3P 4

Navigation menu