2P
ENR Dead Front Interlocked
Circuit Breaking Receptacles
ENP Plugs General Purpose
ArkɀGard®2; Factory Sealed
Cl. I, Div. 1 & 2, Groups B†,C,D
Cl. II, Div. 1 & 2, Groups F,G
Cl. III
NEMA 3,7BCD,9FG,12
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Application:
ENR receptacles and ENP plugs are used:
ɀwith portable electrical equipment such as
compressors, tools, lighting systems, and
similar devices
ɀin areas made hazardous by the presence
of flammable vapors and gases or
combustible dusts
ɀwherever portable electrical equipment is
likely to be transferred from hazardous to
nonhazardous areas
ɀin damp and corrosive areas
ɀwhen power requirements do not exceed
20 amperes
ɀwhere general purpose application is
required
Features:
ɀ
ArkȿGard 2
receptacle incorporates three
spring-loaded slide keys that prevent the
receptacle face plate from being rotated until
the ENP plug is fully inserted into the
receptacle. To make the connection, the ENP
plug is fully inserted; and the receptacle face
moved inward by pushing the plug forward
(Fig. 1). The plug is then rotated, (Fig. 2),
closing the circuit. As rotation begins, the
plug becomes locked in the receptacle and
cannot be accidentally disengaged. In
making or breaking the circuit, any resulting
electrical arc is confined in the factory-sealed
chamber.
ɀFactory-sealed chamber encloses the
potential arcing components between two
explosion-proof threaded joints. These
threads are specially coated to guarantee
freedom of movement, which ensures on-off
action. No additional seals are required.
ɀOne piece molded gasket seals cover plate
and ENP plug when plug is inserted,
providing full environmental protection at the
receptacle face.
ɀTop-hinged cover design with 45°
downward angle provides superior protection
in damp, wet, and dirty locations.
ɀMolded-in contact design provides superior
interior contact reliability.
ɀENP plugs can be used in nonhazardous
areas with standard U-ground NEMA/EEMAC
configuration 5 and 6 receptacles, eliminating
the need for two separately equipped
portable units of the same type. The ENR
receptacle will not accept standard NEMA/
EEMAC configuration plugs.
ɀENP plug handle body is designed with an
internal cord strain relief mechanism and a
cable sealing grommet which will accept
various cable diameters.
ɀField assembly is accomplished with
standard tools.
ɀUse standard EDS back boxes.
Single gang receptacles purchased as a complete
assembly with EDS back box are suitable for Class I, Group
B usage. Two gang receptacles can be modified for Class I,
Group B usage. Add the letter B to Cat. No. Example:
ENRB22201. Seals must be installed within 112of each
conduit opening. Receptacle units only (ie. ENR5201) are not
suitable for Class I, Group B.
Figure 1
Grounding:
ɀNEC Article 501 and CEC Section 18
requires that metal frames or exposed non-
current-carrying metal parts of portable
devices used in hazardous locations be
grounded through an extra conductor in the
portable cord. ENR receptacles and ENP
plugs are provided with an extra grounding
pole.
Standard Materials:
ɀReceptacle housing, spring door and plug
body – die cast copper-free aluminum
ɀInteriors: receptacle –
Krydon
®fiberglass-
reinforced polyester material; plugs – nylon
100
ɀContacts: receptacle blade – brass;
receptacle switch – silver; plug – brass
ɀReceptacle cover hinge pin and spring –
stainless steel
ɀReceptacle gasket – neoprene
ɀPlug bushing – neoprene
Figure 2
Standard Finishes:
ɀCopper-free aluminum – aluminum acrylic
paint
ɀBrass – natural
Electrical Rating Ranges:
ɀReceptacles – 20 amperes; 125 vac and
250 vac, 50-400 hertz
ɀPlugs – 15 amperes; 125 vac and 250 vac,
50-400 hertz
20 amperes; 125 vac and 250 vac,
50-400 hertz
Certifications and
Compliances:
ɀNEC:
Class I, Division 1 and 2, Groups B†,C,D
Class II, Division 1 and 2, Groups F,G
Class III
ɀANSI/UL Standard 1010
ɀNEMA/EEMAC 3,7BCD,9FG
ɀCEC:
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Group G
Class III
CAUTION: To reduce the risk of ignition of
hazardous atmospheres, do not use plugs or
receptacles in Class II, Group F locations that
contain electrically conductive dusts.
Dimensions
a=312for single gang; 7916 for two gang.
2: 5: 50: 95: 98: 100:
SYS19: BASE2 JOB: CRMAIN06-1008-2 Name: 2P-1008 DATE: JAN 19 2006 Time: 6:08:31 PM Operator: RB COLOR: CMYK TCP: 15001 Typedriver Name: TS name csm no.: 100 Zoom: 100
STIBOINFO((CRH:66008com:2P:1008))
1008
PDFINFO C H0 0 2 P - 8
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
2P
ENR Dead Front Interlocked
Circuit Breaking Receptacles
ENP Plugs General Purpose (For US NEC
Applications); ArkȿGard
®
2; Factory Sealed
Cl. I, Div. 1 & 2, Groups B*,C,D
Cl. II, Div. 1 & 2, Groups F,G
Cl. III
NEMA 3,7BCD,9FG,12
Explosionproof
Raintight
Wet Locations
Dust-Ignitionproof
ENR single gang ENR single gang ENR two gang ENR two gang
dead end assembly dead end assembly with dead end assembly dead end assembly with
spring door open one spring door open
ENR receptacle only,
with spring door open
ENP plug
Single Gang Two Gang
Receptacle Receptacle Receptacle 15 Amp 20 Amp
Receptacle Hub Assembly Assmebly Unit Only NEMA Plug NEMA Plug NEMA
Rating Description Size Cat. # ‡ Cat. # ‡ Cat. # Config. Cat. # Config. Cat. # Config.
12ENR11201 ENR12201
Dead End 34ENR21201 ENR22201
1 ENR31201 ENR32201
20 amp, ENR5201 ENP5151 ENP5201
125 volt 5-20R 5-15P 5-20P
12ENRC11201 ENRC12201
Through Feed 34ENRC21201 ENRC22201
1 ENRC31201 ENRC32201
12ENR11202 ENR12202
Dead End 34ENR21202 ENR22202
1 ENR31202 ENR32202
20 amp, ENR6202 ENP6152 ENP6202
250 volt 6-20R 6-15P 6-20P
12ENRC11202 ENRC12202
Through Feed 34ENRC21202 ENRC22202
1 ENRC31202 ENRC32202
*Single gang receptacles purchased as a complete
assembly with EDS back box are suitable for Class I, Group
B usage. Two gang receptacles can be modified for Class I,
Group B usage. Add the letter B to Cat. No. Example:
ENRB22201. Seals must be installed within 112of each
conduit opening. Receptacle units only (ie. ENR5201) are not
suitable for Class I, Group B.
With Feraloy®Iron Alloy EDS, EDSC back boxes.
2: 5: 50: 95: 98: 100:
SYS19: BASE2 JOB: CRMAIN06-1009-1 Name: 2P-1009 DATE: JAN 19 2006 Time: 6:08:33 PM Operator: RB COLOR: CMYK TCP: 15001 Typedriver Name: TS name csm no.: 100 Zoom: 100
STIBOINFO((CRH:66008com:2P:1009))
1009
PDFINFO C H0 0 2 P - 9
US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright©2006 Cooper Crouse-Hinds
2P
ENR Dead Front Interlocked
Circuit Breaking Receptacles
ENP Plugs; General Purpose (For CEC
Applications) ArkȿGard
®
2; Factory Sealed
Cl. I, Div. 1 & 2, Groups B*,C,D
Cl. II, Div. 1 & 2, Group G
Cl. III
EFC 3,7BCD,9G,12
Explosionproof
Raintight
Wet Locations
Dust-Ignitionproof
ENR single gang ENR single gang ENR two gang ENR two gang
dead end assembly dead end assembly with dead end assembly dead end assembly with
spring door open one spring door open
Single Gang Two Gang
Receptacle Receptacle Receptacle
Receptacle Hub Assembly Assembly Unit Only EEMAC Plug EEMAC
Rating Description Size Cat. # ‡ Cat. # ‡ Cat. # Config. Cat. # Config.
12ENR11151 ENR12151
Dead End 34ENR21151 ENR22151
1 ENR31151 ENR32151
15 amp, ENR5151 ENP5151
125 volt 5-15R 5-15P
12ENRC11151 ENRC12151
Through Feed 34ENRC21151 ENRC22151
1 ENRC31151 ENRC32151
12ENR11152 ENR12152
Dead End 34ENR21152 ENR22152
1 ENR31152 ENR32152
15 amp, ENR6152 ENP6152
250 volt 6-15A 6-15P
12ENRC11152 ENRC12152
Through Feed 34ENRC21152 ENRC22152
1 ENRC31152 ENRC32152
12ENR11201 ENR12201
Dead End 34ENR21201 ENR22201
1 ENR31201 ENR32201
20 amp, ENR5201 ENP5201
125 volt 5-20R 5-20P
12ENRC11201 ENRC12201
Through Feed 34ENRC21201 ENRC22201
1 ENRC31201 ENRC32201
12ENR11202 ENR12202
Dead End 34ENR21202 ENR22202
1 ENR31202 ENR32202
20 amp, ENR6202 ENP6202
250 volt 6-20R 6-20P
12ENRC11202 ENRC12202
Through Feed 34ENRC21202 ENRC22202
1 ENRC31202 ENRC32202
*Single gang receptacle units can be modified for Class 1,
Group B usage. Add suffix B to the Cat. No. Example:
ENRB11201. Seals must be installed immediately adjacent to
each conduit opening.
15A With Copper-free aluminum EDS, EDSC back boxes.
20A with
Feraloy
®iron alloy EDS, EDSC back boxes