FORM 11 ACL ACN 2ACL 2ACN AS COMPRESSIONx 127652 Catalog

2014-10-22

: Pdf 127652-Catalog 127652-Catalog Batch9 unilog

Open the PDF directly: View PDF PDF.
Page Count: 3

SERIES ACL, ACN, 2ACL, 2ACN and AS
Compression Connectors for Aluminum or Copper Conductor
ILSCO TOOLS
94285 Hand Tool (C)
Compression
Terminals
ACL, 2ACL, AS,
ACN, 2ACN
(A)
Color
Code
Die
Code
Left
Die
Right
Die
No. of
Crimps
MT-25
Hand
Dieless
(C)
ILC-12H-N ILC-12-N,
ILC-12, ILC-12H
ILC-14, ILC-14H
12 Ton
ILCB-12-N, ILCB-12,
ILCB-12-LIO
12 Ton Battery
ILC-15H, ILC-15
15 Ton
ILC-30H
30 Ton
IDT-12, IDT-12H
11 Ton Dieless
(C)
IDT-6, IDT-6H
6.2 Ton Dieless
IDTB-6, IDTB-6-LIO
6.2 Ton Dieless Battery
IDTB-12,
12 Ton Dieless Battery
(C)
IDT-12-N 15 Ton
Dieless
(C)
8 Blue 2 M K 2 1 1 1
6 Gray 3 K K 2 1 1 1 1 1 1
4 Green 4 H H 3 1 2 2 1 1 1
2 Pink 7/6 E A 3 2 1/3 1/3 1 1 1
1 Gold 7/6 E A 4 2 1/4 1/4 1 2 1
1/0 Tan 8 A C 5 2 1 1 1 2 1
2/0 Olive 10 A B 4 2 1 1 1 2 1
3/0 Ruby 10 A A 4 2 2 2 1 3 1
4/0 White 12 2 1 1 1 3 2
250 Red 13 2 2 1 3 2
300 Blue 14 2 2 1 4 2
350 Brown 14 2 2 1 4 2
400 Green 16 3 3 1 4 2
500 Pink 16A 3 3 1 4 2
600 Black 17 4 4 1 4 2
700 Purple 17 4 4 1 4 2
750 Yellow 18 5 5 1 4 2
1000 Brown 20 3 1 2
(A) Number of crimps shown on chart must be on each end of the AS splicer connectors.
Connector Installation
1. Select proper ACL, ACN, 2ACL, 2ACN or AS connector for the wire
size to be used. Series can be used with concentric, compressed or
compact aluminum or copper wire.
2. Strip wire insulation using an approved method. Do not nick or ring
the wire. Remove any mylar coating on the wire.
3. Remove surface oxides from the wire with a wire brush.
4. Insert wire all the way into the barrel of the connector.
5. Select the proper die for approved tool. See chart above for approved tools and dies. Compress tang
from tang toward wire, or from inside of AS connector toward wire.
6. When terminating an aluminum connector to a steel or copper stud, use a belleville or compression
type washer in combination with a flat washer. Tighten until the belleville washer is flat.
(C) The ILSCO MT-25, ILSCO 94284, Burndy MY29-3 and all dieless tools are not color coded or do not
contain the die index.
(B) The ACL, 2ACL, ACN, 2ACN AND AS connectors are marked with color, the die numbers and
required number of crimps for ILSCO hydraulic tools. When using other listed tools, consult chart
for crimps required. Crimps should be evenly space on connector.
(D) Consult manufacturers data for catalog numbers of dies for each tool.
Page 1 of 3
FORM 11
Revised July 30, 2004
SERIES ACL, ACN, 2ACL, 2ACN AND AS
Compression Connectors for Aluminum or Copper Conductor
BURNDY TOOLS (B) (D)
T & B TOOLS (B) (D)
Anderson
Greenlee
Compression
Terminals ACL,
2ACL, AS, ACN,
2ACN (A) Color Code Die Code
MY29-3
Hand (C) Y34A Y35
Y39
Y45
Y46 Y48B
Y644M
Dieless
(C)
Die Code
TBM 8
Hand
13642
12 Ton
TBM 15
15 Ton
21940
40 Ton
Versa-Crimp
Dieless
(C)
1990 Dieless
(C)
8 Blue 374 1 24 1 1 2
6 Gray 346 1 1+ 1 1 1 29 2 2 2 2
4 Green 375 1 1+ 1 1 1 37 2 2 2 2 1 1
2 Pink 348 2 1+ 1 1 1 42 2 2 4* 2 1 1
1 Gold 471 2 1+ 1 1 1 45 3 3 3 3 2 1
1/0 Tan 296 2 1+ 1 1 1 1 50 3 3 3 3 2 1
2/0 Olive 297 2 2+ 2 2 1 1 54 3 3 6* 3 2 1
3/0 Ruby 467 2 2+ 2 2 1 1 60 3 3 3 3 2 1
4/0 White 298 2 2+ 2 2 1 1 66 5 4* 2 2 3 2
250 Red 324 2 2+ 2 2 1 1 71 5 4* 4* 2 3 2
300 Blue 470 2+ 2 2 1+ 1 76 5 4* 2 2 3 2
350 Brown 299 2 2 1+ 1 87 6 4* 4* 2 3 2
400 Green 472 4 4 2+ 1 94 4* 4* 2 4 2
500 Pink 300 4 4 2+ 1 99 4* 4* 2 4 2
600 Black 473 4 4 2+ 1 106 4* 2 2 4 2
700 Purple 936 4 2 1 112 4* 4* 2 2
750 Yellow 936 4 2 1 115 4* 4* 2 2
1000 Brown 302 2+ 1 140 4* 2 2
(A) Number of crimps shown on chart must be on each end of the AS splicer connectors.
* T & B half dies require twice the number of crimps. + These Burndy Tools are listed for use with die and nest indentor combinations.
(C) The ILSCO MT-25, ILSCO 94284, Burndy MY29-3 and all dieless tools are not
color coded or do not contain the die index.
(D) Consult manufacturers data for catalog numbers of dies for each tool.(B) The ACL, 2ACL, ACN, 2ACN AND AS connectors are marked with color, the die numbers and
required number of crimps for ILSCO hydraulic tools. When using other listed tools, consult chart
for crimps required. Crimps should be evenly space on connector.
Page 2 of 3
Form 11
Revised July 30, 2004
Series ACL, ACN, 2ACL, 2ACN and AS
for ILSCO IDT-12, IDT-12-N, IDTB-6, IDT-6, IDT-6H
and Burndy Y644M Dieless Tools
For Aluminum or Copper Conductors
Compression
Terminals
ACL, ACN,
AS
Standard
Wire
Size
Expanded Wire
Size
No. Crimps for
ILSCO IDT-12,
IDT-12-N and
Burndy Y644M
No. Crimps for
ILSCO IDTB-6,
IDTB-6-LIO,
IDT-6 and IDT-
6H
6 6 AWG 6 AWG 1 1
4 4 AWG 4 - 6 AWG 1 1
2 2 AWG 2 - 6 AWG 1 1
1 1 AWG 1 - 2 AWG 1 2
1/0 1/0 AWG 1/0 - 1 AWG 1 2
2/0 2/0 AWG 2/0 - 1 AWG 1 2
3/0 3/0 AWG 3/0 - 1 AWG 1 3
4/0 4/0 AWG 4/0 - 1 AWG 1 3
250 250 MCM 250 MCM - 1/0 AWG 1 3
300 300 MCM 300 MCM - 2/0 AWG 1 4
350 350 MCM 350 MCM - 3/0 AWG 1 4
400 400 MCM 400 MCM - 4/0 AWG 1 4
500 500 MCM 500 MCM - 4/0 AWG 1 4
600 600 MCM 600 MCM - 250 MCM 1 4
700 700 MCM 700 MCM - 350 MCM 1 4
750 750 MCM 750 MCM - 500 MCM 1 4
1000 1000 MCM 1000 MCM - 750 MCM 1
Second Crimp optional for the 2ACL, 2ACN Series
Number of crimps shown on chart must be on each
end of the AS splicer connectors
Page 3 of 3
FORM 11