ballasts
2008 product catalog
GE Consumer & Industrial
Lighting
GE has a policy of continuous improvement of its products and reserves the
right to change materials and specifications without notice.
© 2007 GE Company
Pub. No. 71883 PC48878
GE Ballast Products Catalog 2008
Transforming
the POWER
of light
US/Canada Customer Ordering and Tracking—www.geelitenet.com
For detailed ballast and lamp specifications—www.gelighting.com
For order, technical or warranty assistance, call: 1-888-GEBALLAST (432-2552)
OEM Customer Service: (T) 1-800-833-4933, (F) 1-800-327-0588
GE Lighting Headquarters, Nela Park, 1975 Noble Rd., Cleveland, OH 44112, (T) 216-266-2121
Transforming
the POWER
of light
GE Consumer & Industrial
Lighting
*M
ea
n l
u
m
e
n m
easu
r
ed
at
4
0%
o
f r
ated
lif
e
*
*
RoHS compliant: European Directive
(2002
/
95EC on the Restriction of Hazardous
Substances) states that (be
y
ond certain
l
imited exemptions) electrical and
e
l
ectronic
p
ro
d
ucts s
h
a
ll
not contain
l
ea
d
,
cadmium, mercur
y
, hexavalent chromium,
olybrominated biphenyls (PBBs), or
p
o
lyb
rominate
d
d
ip
h
en
yl
et
h
ers (PBDEs).
G
E’
s
U
l
t
r
aSta
r
t
®
ba
ll
asts
use
l
ead
-fr
ee
solder and other environmentally preferable
m
ateria
l
s t
h
at meet t
h
e RoHS
d
irective.
RoHS-compliant ballasts are GE’s
commitment to helping our customers meet
th
eir
d
is
p
osa
l
nee
d
s now, an
d
in t
h
e
f
uture.
gelighting.co
m
The future can seem pretty intimidating: Our known reserves of oil and natural gas are expected to be
depleted b
y
2045, the climate is changing, and more than a billion people lack clean water. At GE, we
believe some of the world’s most pressing challenges present an opportunit
y
to do what we do best:
Imagine an
d
b
ui
ld
innovative so
l
utions t
h
at
b
ene
t our customers an
d
society at
l
arge.
As a global leader in energ
y
, technolog
y
, manufacturing and infrastructure, GE is uniquel
y
suited to
help solve environmental challenges, toda
y
and for generations to come. Our customers want a more
prosperous, c
l
eaner
f
uture. By
h
arnessing our most a
b
un
d
ant renewa
bl
e resource—t
h
e imagination
o
f
our peop
l
e—we can create t
h
at
f
uture wit
h
t
h
em. We are ta
k
ing a new approac
h
to so
l
ving some o
f
our customers’ tou
g
hest environmental
p
roblems
.
We call it ecomagination.
sm
Impact of ecomagination:
A manufacturing and warehouse facilit
y
was looking to reduce costs and greenhouse gas emissions:
Existing Lighting
400W MH std. CWA
Light output* 23,000 mean lumens at 8,000 hours (19,200 lumens at 12,000 hours)
Size 100,000 sq. ft. – 300 fixtures
Energy Rate/Burning Hours 10¢ kWh/5,000 per year
Total Watts per Fixture 458
Energy Used $68,700
RoHS compliant** No
Proposed Lighting
4-Lamp T5WM HO with UltraStart® Ballast
Light output* 19,000 mean lumens at 12,000 hours
Watts per Fixture 216
Energy Used $32,400
Energy Saved $36,300
RoHS compliant** Yes
Environmental Impact
Watts Saved 363,000 kilowatt-hours per year
Greenhouse gases (Co2) Reduced by 519,090 lbs. per year
SO2 Reduced by 2,030 lbs. per year
The equivalent effect of:
Equivalent Forestation 71 acres
Equivalent Cars 45 cars removed from the roads for a year
Our heritage, our future
We believe that better technolog
y
is the answer to our customers’ environmental challenges. And we
are con
fid
ent we can
n
d
tomorrows so
l
utions to t
h
ose c
h
a
ll
enges just as we
h
ave since t
h
e
d
ays o
f
our
f
oun
d
er, T
h
omas E
d
ison
.
Throughout our 115-
y
ear histor
y
, we have invented solutions to meet our customers’ greatest needs.
Over many years, we
h
ave
d
eve
l
ope
d
one o
f
t
h
e
b
roa
d
est ranges o
f
environmenta
ll
y a
d
vance
d
tec
h
no
l
ogies. We wi
ll
b
ui
ld
on t
h
is
l
egacy o
f
success
b
y researc
h
ing an
d
d
eve
l
oping next-generation
clean technologies. Our goal is to be a leader in bringing clean energ
y
, air, water and improved qualit
y
o
f lif
e
to
a
ll
o
f
t
h
e
w
o
rl
d
s
c
i
t
iz
e
n
s.
GE Consumer & Industrial
Lighting
Product Warranties
Light your world with a brand
you can trustGE.
GE has been a leader in innovative lighting technologies for over 100 years.
Our name on the label is virtually synonymous with dependable, efficient,
high-quality products—and that is why we are totally confident in the
system performance and reliability of our lamps and ballasts. Also it is why
we are willing to back them with a limited warranty that provides excellent
coverage against defects in materials and workmanship.
If your GE lamp or ballast, when installed and used properly, fails during
its warranty period because of defects in materials or workmanship, our
warranties provide for purchase price credits or replacement. Of course,
every lamp, ballast and system is different and warranty details vary,
so check the individual warranty for your product at
http://genet.gelighting.com/LightProducts/html/warranties.htm.
GE Ultra High Efficiency
Design is Ultra Cool!
Results:
Combine GE’s Ultra ballasts with
cool running fixtures to achieve
maximum system performance in
hot temperatures. GE provides the
Ultra Cool system certification
with high grade fixture systems
which means a 5 year 55°C max
ambient warranty.
1
95
2
System Limite
d
Warrant
y
GE Lamps operating on GE Ba
ll
as
t
C
om
p
act F
l
uorescent Lam
p
Warrant
y
*
El
ectronic Ba
ll
ast Warrant
y
E
l
ectroma
g
netic Ba
ll
ast Warrant
y
D
ou
bl
e Biax
®
:
13-, 18-, 26-watt 4-
p
in
b
as
e
1
year a
f
ter
d
ate o
f
purc
h
ase or 4000
h
rs
.
5 years
f
rom
d
ate o
f
manu
f
acture 2 years
f
rom
d
ate o
f
manu
f
acture
T
ri
pl
e Bia
x
®
: 13-, 18-, 26-, 32-, 42-wat
t
1
year a
f
ter
d
ate o
f
purc
h
ase or 4000
h
rs
.
5 years
f
rom
d
ate o
f
manu
f
acture 2 years
f
rom
d
ate o
f
manu
f
acture
2D
®
: 10-
,
16-
,
21-
,
28-
,
38-watt
1
year a
f
ter
d
ate o
f
purc
h
ase or 4000
h
rs. 5 years
f
rom
d
ate o
f
manu
f
acture 2 years
f
rom
d
ate o
f
manu
f
acture
L
inear F
l
uorescent Lam
p
Warranty
El
ectronic Ba
ll
ast Warrant
y
E
l
ectromagnetic Ba
ll
ast Warranty
F
25T12** 3 years a
f
ter
d
ate o
f
purc
h
ase or 10,500
h
rs
.
5 years
f
rom
d
ate o
f
manu
f
acture
F
28T8
,
F32T8
,
F32T8WM 3 years after date of purchase or 10,500 hrs
.
5 years from date of manufacture
F
32T8/XL
,
F32T8/XL/HL
,
F32T8/XL/W
M
3 years after date of purchase or 12,500 hrs
.
5 years from date of manufacture 2 years from date of manufacture
F
32T8 SXL
,
F32T8/25W 4.5
y
ears after date of purchase or 15,750 hrs. 5
y
ears from date of manufacture
F1
4T5HE
,
F
21
T5HE
,
F
28
T5HE
,
F
35T5HE
,
F54T5H
O
4
y
ears after date of purchase or 14,000 hrs. 5
y
ears from date of manufacture
F
14T5/WM
,
F21T5/WM
,
F28T5/WM
,
F
35T5/WM, F54T5/WM
3.5 years after date of purchase or 12,500 hrs. 5 years from date of manufacture
F
28WT5/H
L
3 years a
f
ter
d
ate o
f
purc
h
ase or 10,500
h
rs
.
5 years
f
rom
d
ate o
f
manu
f
acture
F
96T8
2
years after date of purchase or 8,000 hrs
.
5 years from date of manufacture
F
96T8/XL
,
F96T8/XL/WM. F96T8/XL/WM
P
3 years after date of purchase or 10,500 hrs. 5 years from date of manufacture
HI
D
L
amp
W
arranty
E
lectronic Ballast Warrant
y
Electromagnetic Ballast Warranty
C
M
H
®
Co
n
sta
n
tCo
l
or
®
S
PXX
2
5
0
-
,
3
20
-
,
350-, 400-wat
t
1
year after date of purchase or 5000 hrs
.
5 years from date of manufacture
P
u
l
seAr
c
®
250-
,
320-
,
350-
,
400-wat
t
1
year a
f
ter
d
ate o
f
purc
h
ase or 5000
h
rs
.
5 years
f
rom
d
ate o
f
manu
f
acture
*B
ased
o
n whi
c
h
e
v
e
r
co
m
es
fir
st
**On GE Norma
l
l
i
gh
t out
p
ut U
l
traMa
x
®
,
ProL
i
ne
®
or Mu
l
tivo
l
t Pro
l
ine
®
instant start
b
a
ll
asts
**
*
See warranties at ge
l
ig
h
ting.com
f
or speci
c
l
amp cyc
l
e requirements
f
or instant start & program start
b
a
ll
asts. Cyc
l
e time wit
h
program start
b
a
ll
asts s
h
a
ll
b
e 15
mi
nutes or greater
****A
ll
covR
g
uar
d
®
l
am
p
s are inc
l
u
d
e
d
3
gelighting.com
4 Product overview
6 Quick reference ballast selection guide
16 Quick reference lamp to ballast selection guide
PRODUCTS
T8 Fluorescent Ballasts
36 Understanding T8 Fluorescent Ballasts
T8 INSTANT START BALLASTS
38 UltraMax®Instant Start Multi-Voltage High Efficiency
38 ForF17(2ft),F25(3 ft),F32(4ft),F40(5ft)Lamps
45 For 46 59W 4 ft–8 ft Slimline Lamps
46 ProLine®T8 Multivolt 120V–277V
46 ForF17(2ft),F25(3 ft),F32(4ft),F40(5ft)Lamps
51 For 46 59W 4 ft8 ft Slimline Lamps
52 ProLine®T8 Multivolt, High Output 120V–277V
52 For44–86W4ft8ftHighOutputLamps
53 ProLine®T8 Instant Start High Performance
53 ForF17(2ft),F25(3 ft),F32(4ft),F40(5ft)Lamps
57 For 46 59W 4 ft8 ft Slimline Lamps
58 Residential Grade ProLine®T8 120V
58 ForF17(2ft),F25(3 ft),F32(4ft)Lamps
59 Electromagnetic T8 Ballasts
59 ForF17(2ft),F25(3 ft),F32(4ft)Lamps
T8 PROGRAMMED START BALLASTS
60 UltraStart®T8 Programmed Start
60 ForF17(2ft),F25(3 ft),F32(4ft)Lamps
69 T8 Dimming
69 ForF17(2ft),F25(3 ft),F32(4ft)Lamps
72 Wiring Diagrams
75 Case Dimensions
T5 Fluorescent Ballasts
76 Understanding T5 Electronic Programmed Start Ballasts
T5 ELECTRONIC PROGRAMMED START BALLASTS
77 T5 High Efficiency Programmed Start
77 ForF14(2ft),F21(3 ft),F28(4ft),F35(5ft)HET5Lamps
79 T5 High Output Programmed Start
79 ForF24(2ft),F39(3 ft),F54(4ft),F80(5ft)HOT5Lamps
82 Wiring Diagrams
83 Case Dimensions
T5 lamp lengths are noted to nearest foot and are not exact lengths as noted in
feet. See GE Lamp Catalog for exact lamp length.
T12 Electronic Ballasts
84 Understanding T12 Electronic Ballasts
T12 ELECTRONIC BALLASTS
85 ProLine®T12 Multivolt 120V–277V
85 ForF20(2ft),F30(3 ft),F34/F40(4ft)T12Lamps
87 For T12 (4 ft–8 ft) Slimline Lamps
T12 HIGH OUTPUT BALLASTS
88 For T12 High Output Lamps
T12 MAGNETIC BALLASTS
90 For 2 ft, Circleline, Preheat T12 Lamps
93 ForF30,F34/F40(4ft)T12Lamps
97 For T12 4 ft–8 f t Slimline Lamps
99 For T12 High Output Lamps
FLUORESCENT ACCESSORIES
100 Starters
100 Sockets
101 Wiring Diagrams
104 Case Dimensions
Sign Ballasts
106 Understanding Sign Ballasts
107 Sign Ballasts
107ForT12HighOutputLamps
115 Wiring Diagrams
119 Case Dimensions
Compact Fluorescent Ballasts
120 Understanding Compact Fluorescent Ballasts
123 ProLine®CFL Electronic Ballasts
123 For 13 42W T4 CFL Lamps
125 For 40W Biax®CFL Ballasts
128 For5–26WPreheatCFLLamps
129 CFL Magnetic Ballasts
129 For5-26WPreheatCFLLamps
130 For 36 40W CFL Lamps
131 Wiring Diagrams
133 Case Dimensions
HID Electronic Ballasts
134 Understanding Electronic UltraMax® HID Ballasts
135 Electronic HID
135 For 20 150W Pulse Start HID Lamps
139 For 250 400W Pulse Start HID Lamps
140 Wiring Diagrams
141 Case Dimensions
HID Electromagnetic Ballasts
142 Understanding Electromagnetic HID Ballasts
144 Metal Halide
144 For 20 175W Metal Halide HID Lamps
149 For 250 1500W Metal Halide HID Lamps
155 Pulse Start
155 For 175 1000W Pulse Start Metal Halide HID Lamps
162 High Pressure Sodium
162 For 50 150W High Pressure Sodium HID Lamps
166 For 250 1000W High Pressure Sodium HID Lamps
170 High Intensity Discharge Lamp Ballast Kits
174 Enclosed and Potted Metal Halide
178 F-Can and Post Mount High Pressure Sodium
HID ACCESSORIES
179 Replacement Capacitors
179 Replacement Ignitors for Pulse Start Lamps (MH & HPS)
179 Other Accessories
180 Wiring Diagrams
184 Case Dimensions
186 Glossary
190 Ballast Cross Reference Matrix
194 Contact Information
195 Warranty Information
Table of contents
Inside front cover is in cover file
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
4 5
gelighting.com
2008 Ballast Product Catalog
EcomaginationSM isGEscommitmenttocreateproductsthat
help our customers improve their environmental and operating
performance. GE’s UltraStart®T5 and T8 programmed start and
GE UltraMax®Instant Start ballasts are among the highest
energy-efficient ballasts available and contribute to significant
reductions in energy consumption and the curbing of
greenhouse gas emissions.
ProLine®Electronic Ballast
Offered in dedicated or multivolt (120-277V), these high-
performanceT8instantstartballastsarelonglife,lessthan
10%THDandmostmodelsalsomeetminimumefciency
requirements of the NEMA Premium®ballast program.
Compact Fluorescent Lamp (CFL)
CFLs are single-ended T4 and T5 lamps that are bent to form
a compact shape. Screw-in CFLs have an integral ballast with
a screw base for easy replacement of incandescent lamps. GE
offers multi-voltage, multi-lamp and multi-entry ballasts for a
wide range of CFL plug-in lamps. Multivolt ProLine®CFL ballasts
are designed for plug-in lamps so that a ballast will survive over
the useful life of approximately 3-to-4 lamp lives.
Electromagnetic Ballast (Magnetic Ballast)
Primarily used for T12 lamps. These ballasts operate lamps at
a less efficient 60Hz and typically have efficiencies of 70-80%.
Most ballasts consist of a core and coil transformer assembly.
Today, magnetic ballasts for 4 foot and 8 foot lamps are typically
used only for replacement purposes and are restricted by EPACT
to be sold, even in replacement applications, starting in 2009.
Sign Ballast (Magnetic Ballast)
DesignedtooperateT12HOLampsat120voltsincoldand
damp conditions in sign cabinets.
GE eHID, Electronic High Intensity
Discharge Ballast (eHID)
Electronic HID significantly improves the performance of HID
lighting. GE’s UltraMax®eHID ballast operates pulse start and
ceramic metal halide lamps.
GE High Intensity Discharge Ballast (HID)
HID magnetic ballasts consist of robust core and coil designs
that meet or exceed minimum ANSI requirements. These
ballasts are typically sold as distributor replacement kits which
are pre-wired with a capacitor, ignitor (if applicable) and all
necessary mounting hardware and instructions. Each wattage
is typically offered in quad (MLT-120/208/240/277 volt), 5-tap
(ML5-120/208/240/277/480 volt) or 480 volt (48T) options.
RoHS compliant:
European Directive (2002/95EC on the Restriction of
Hazardous Substances) states that (beyond certain limited
exemptions) electrical and electronic products shall not
contain lead, cadmium, mercury, hexavalent chromium,
polybrominated biphenyls (PBBs), or polybrominated diphenyl
ethers (PBDEs). GE’s electronic ballasts use lead-free solder and
other environmentally preferable materials that meet the RoHS
directive. Although not required in the U.S., RoHS-compliant
ballasts show GEs commitment to helping our customers meet
their disposal needs now, and in the future. GE encourages
customer awareness on the importance of reducing hazardous
materials and getting ahead of complying with environmental
trends. Look for the RoHS-compliant mark on GE ballasts.
UltraMax®Electronic Ballast
A family of high-efficiency GE T8 instant-start electronic linear
fluorescent ballasts designed to optimize GE’s T8 Ultra lamps
for optimal system energy savings. UltraMax®ballasts have
a lamp-friendly low-lamp-current crest factor and virtually
“read” and adapt to incoming voltage from 108V to 305V. Other
features include UL Type CC Anti-Arc Rating and anti-striation
control to eliminate lamp striations and spiraling. All UltraMax®
ballastsexceed90%efciencyandtheNEMAPremium
®ballast
program minimum efficiency requirements.
UltraStart®Electronic Ballast
UltraStart®ballasts are a family of high-efficiency GE
Program Start (see page 36) electronic linear fluorescent
ballasts designed to optimize GEs T8 and T5 Ultra lamps in
frequently switched applications. Instant Start ballasts provide
approximately 10,000 starts before 50% of lamp failure.
UltraStart®provides greater than 100,000 starts. UltraStart®
have the equivalent energy savings and convenience of
instant start ballasts but with the long lamp life of a
programmed start ballast.
UltraStart®T8L,NandHballastsexceed90%efciencyand
theNEMAPremium
®ballast program minimum efficiency
requirements.
Sign Ballast
4
Multivolt ProLine® CFL Ballast
UltraMax® eHID Ballast
This catalog contains North
America ballast and lamp
dataasofDecember2007.
Additional information is
constantly being uncovered
throughresearchandtesting,
which may modify the
data given herein. Changes
may be made at any time.
The data and suggested
applications should not be
takenasrepresentations
or warranties as to the
suitability of a ballast for a
particular application.
gelighting.com
UltraStart® T8 Electronic BallastUltraMax® T8 Electronic Ballast
HID Electromagnetic Ballast Kit
6See page 195 for warranty information. 7
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Quick reference ballast selection guide
Std Pack
Prod Code Description Application
Product Page
Number Pallet Pack DIY Pack
Std Pack
Units Per
Carton
T8 Fluorescent Ballasts
T8 INSTANT START BALLASTS
UltraMax® Instant-Start Multi-Voltage High-Efficiency
For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
72258 GE132MAX-L/ULTRA 1 – F32T8 120 to 277 “L” .77 BF UltraMax®38 10
72259 GE132MAX-N/ULTRA 1 – F32T8 120 to 277 “N” .87 BF UltraMax®38 72260 10
49775 GE232MAX-H/ULTRA 2 or 1 – F32T8 120 to 277 “H” 1.15 BF UltraMax®39 47548 10
72262 GE232MAX-L/ULTRA 2 or 1 – F32T8 120 to 277 “L” .77 BF UltraMax®39 72256 10
72266 GE232MAX-N/ULTRA 2 or 1 – F32T8 120 to 277 “N” .87 BF UltraMax®40 72267 72268 10
71421 GE232MAX-N+ 2 or 1 – F32T8 120 to 277 “N+” 1.0 BF UltraMax®40 10
71714 GE332MAX-H/ULTRA 3 or 2 – F32T8 120 to 277 “H” 1.18 BF UltraMax®41 71715 10
71717 GE332MAX-L/ULTRA 3 or 2 – F32T8 120 to 277 “L” .77 BF UltraMax®41 71718 10
71719 GE332MAX-N/ULTRA 3 or 2 – F32T8 120 to 277 “N” .87 BF UltraMax®42 71721 71722 10
71422 GE332MAX-N+ 3 or 2 – F32T8 120 to 277 “N+” 1.0 BF UltraMax®42 10
71723 GE432MAX-H/ULTRA 4 or 3 – F32T8 120 to 277 “H” 1.18 BF UltraMax®43 71724 10
71725 GE432MAX-L/ULTRA 4 or 3 – F32T8 120 to 277 “L” .77 BF UltraMax®43 71726 10
71727 GE432MAX-N/ULTRA 4 or 3 – F32T8 120 to 277 “N” .87 BF UltraMax®44 71729 71730 10
71423 GE432MAX-N+ 4 or 3 – F32T8 120 to 277 “N+” 1.0 BF UltraMax®44 10
71731 GE632MAX-H90-V60
6, 5, 4 – F32T8 120 to 277 “H” BF UltraMax® 0-10V
100-60% continuous dim 71732 10
71497 GE632MAX-H90-S60
6, 5, 4 – F32T8 120 to 277 “H” BF UltraMax® 95%
100/60% step dim 71502 10
For 46 – 59W 4 ft – 8 ft Slimline Lamps
49766 GE159MAX-N/ULTRA 1 – F96T8 120 to 277 “N” .87 BF UltraMax®45 10
49767 GE259MAX-N/ULTRA 2 or 1 – F96T8 120 to 277 “N” .87 BF UltraMax®45 23954 10
ProLine® T8 Multivolt 120V – 277V
For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
72269 GE-132-MV-N 1 – F32T8 120 to 277 “N”.87 BF MV ProLine®46 72270 10
30198 GE-232-MV-H 2 or 1 – F32T8 120 to 277 “H” 1.18 BF MV ProLine®46 30275 10
72273 GE-232-MV-L 2 or 1 – F32T8 120 to 277 “L.77 BF MV ProLine®47 72274 10
72275 GE-232-MV-N 2 or 1 – F32T8 120 to 277 “N.87 BF MV ProLine®47 72276 72277 10
30199 GE-332-MV-H 3 or 2 – F32T8 120 to 277 “H” 1.15 BF MV ProLine®48 30296 10
30255 GE-332-MV-L 3 or 2 – F32T8 120 to 277 “L” .77 BF MV ProLine®48 30309 10
30192 GE-332-MV-N 3 or 2 – F32T8 120 to 277 “N.87 BF MV ProLine®49 30270 97710 10
30219 GE-432-MV-H 4 or 3 – F32T8 120 to 277 “H” 1.15 BF MV ProLine®49 30303 10
30262 GE-432-MV-L 4 or 3 – F32T8 120 to 277 “L” .77 BF MV ProLine®50 30310 10
30193 GE-432-MV-N 4 or 3 – F32T8 120 to 277 “N.87 BF MV ProLine®50 30271 97711 10
For 46 – 59W 4 ft – 8 ft Slimline Lamps
30195 GE-159-MV-N 1 – F96T8 120 to 277 “N”.87 BF MV ProLine®51 30274 10
30194 GE-259-MV-N 2 or 1 – F96T8 120 to 277 “N.87 BF MV ProLine®51 30272 97712 10
ProLine® T8 Multivolt High Output 120V – 277V
For 44 – 86W 4 ft – 8 ft HO Lamps
30176 GE-286-HO-MV-N 2 or 1 – F96T8HO IS 120 to 277 “N.87 BF 52 30187 10
ProLine® T8 Instant-Start High-Performance
For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
23680 GE-132-120-N 1 – F32T8 120V “N”.87 BF ProLine®53 24161 10
23681 GE-132-277-N 1 – F32T8 277V “N.87 BF ProLine®53 24162 10
23671 GE-232-120-N 2 or 1 – F32T8 120V “N”.87 BF ProLine®54 24163 10
23672 GE-232-277-N 2 or 1 – F32T8 277V “N”.87 BF ProLine®54 24164 10
23673 GE-332-120-N 3 or 2 – F32T8 120V “N”.87 BF ProLine®55 24165 10
23674 GE-332-277-N 3 or 2 – F32T8 277V “N.87 BF ProLine®55 24166 10
23675 GE-432-120-N 4 or 3 – F32T8 120V “N.87 BF ProLine®56 24167 10
23676 GE-432-277-N 4 or 3 – F32T8 277V “N”.87 BF ProLine®56 24168 10
For 46 – 59W 4 ft – 8 ft Slimline Lamps
23677 GE-259-120-N 2 or 1 – F96T8 120V Normal Light .87 BF ProLine®57 24169 10
23678 GE-259-277-N 2 or 1 – F96T8 277V “N”.87 BF ProLine®57 24170 10
Std Pack
Prod Code Description Application
Product Page
Number Pallet Pack DIY Pack
Std Pack
Units Per
Carton
T8 Fluorescent Ballasts
Residential Grade ProLine® T8 120V
For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
97782 GE232-120-RES 2 or 1 – F32T8 120V “N”.87 BF Residential ProLine®58 71037 10
97783 GE432-120-RES 4 or 3 – F32T8 120V “N”.87 BF Residential ProLine®58 71038 10
Electromagnetic T8 Ballasts
For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
87125 GEM232T8RS120 2 – F32T8 RS 120V Magnetic Ballast 59 10
87130 GEM232T8RS277 2 – F32T8 RS 277V Magnetic Ballast 59 10
T8 PROGRAMMED START BALLASTS
UltraStart® T8 Programmed Start
For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
29621 GE-232-120-PS-N
2 – F32T8 120V Normal Light .87 BF <10% THD
UltraStart®60 29630 10
29622 GE-232-277-PS-N
2 – F32T8 277V Normal Light .87 BF <10% THD
UltraStart®60 29632 10
96714 GE232-MVPS-N
2 or 1 – F32T8 120V-277V Normal Light .88 BF
<10% THD UltraStart®61 96717 10
96720 GE232-MVPS-L
2 or 1 – F32T8 120V-277V Low Watts .71 BF
<10% THD UltraStart®61 10
29675 GE-232-MVPS-H
2 – F32T8 120V-277V High Light 1.15 BF <10%
THD UltraStart®62 29651 10
29671 GE-232-MVPS-XL
2 – F32T8 120V-277V Ultra Low Watt .60 BF
<10% THD 62 29665 10
29623 GE-332-120-PS-N
3 – F32T8 120V Normal Light .87 BF <10% THD
UltraStart®63 29633 10
29624 GE-332-277-PS-N
3 – F32T8 277V Normal Light .87 BF <10% THD
UltraStart®63 29634 10
29676 GE-332-MVPS-H
3 – F32T8 120V-277V High Light 1.15 BF <10%
THD UltraStart®64 29656 10
96715 GE332-MVPS-N
3 – F32T8 120V-277V Normal Light .88 BF <10%
THD UltraStart®64 96718 10
96721 GE332-MVPS-L
3 – F32T8 120V-277V Low Watts .71 BF <10%
THD UltraStart®65 10
29672 GE-332-MVPS-XL
3 – F32T8 120V-277V Ultra Low Watt .60 BF
<10% THD 65 29666 10
29625 GE-432-120-PS-N
4 – F32T8 120V Normal Light .87 BF <10% THD
UltraStart®66 29635 10
29627 GE-432-277-PS-N
4 – F32T8 277V Normal Light .87 BF <10% THD
UltraStart®66 29650 10
96716 GE432-MVPS-N
4 – F32T8 120V-277V Normal Light .88 BF <10%
THD UltraStart®67 96719 10
71832 GE432-MVPS-L
4 – F32T8 120V-277V Low Watts .71 BF <10%
THD UltraStart®67 10
29678 GE-432-MVPS-H
4 – F32T8 120V-277V High Light 1.15 BF <10%
THD UltraStart®68 29657 8
T8 Dimming
For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
80353 B132R120V5 1 – F32T8 DIM 100 to 5% RS 120 69 10
80355 B232SR120V5 2 – F32T8 DIM 100 to 5% RS 120 69 10
80362 B232SR277S50 2 – F32T8 Switch 100/50% RS 277 70 10
80356 B232SR277V5 2 – F32T8 DIM 100 to 5% RS 277 70 10
80357 B332SR120V5 3 – F32T8 DIM 100 to 5% RS 120 71 10
80358 B332SR277V5 3 – F32T8 DIM 100 to 5% RS 277 71 10
8
Quick reference ballast selection guide (cont.)
See page 195 for warranty information. 9
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Std Pack
Prod Code Description Application
Product Page
Number Pallet Pack DIY Pack
Std Pack
Units Per
Carton
T5 Fluorescent Ballasts
T5 ELECTRONIC PROGRAMMED START BALLASTS
T5 High Efficiency Programmed Start
For F14 (2 ft), F21 (3 ft), F28 (4 ft), F35 (5 ft) HE T5 Lamps
99653 GE228MVPSH-A
2 or 1 – F14-F28T5HE 120 to 277 UltraStart® PRS
High Light 1.15 BF A Can 77 99654 10
99655 GE228MVPS-A
2 or 1 – F14-F35T5HE 120 to 277 UltraStart® PRS
Normal Light .95 BF A Can 77 99656 10
47536 B228PUNV-C0G1C 2 – F28T5 PRS UNV 50/60 Hz C Can 78 10
T5 High Output Programmed Start
For F24 (2 ft), F39 (3 ft), F54 (4 ft), F80 (5 ft) HO T5 Lamps
47534 B224PUNV-COG1C 2 – F24T5HO PRS UNV 50/60 Hz C Can 79 10
47540 B239PUNV-DOG1C 2 – F39T5HO PRS UNV 50/60 Hz D Can 79 10
99651 GE254MVPS90-F
2 or 1 – F54T5HO 120 to 277 UltraStart® PRS High
Temp F Can 80 99652 10
47542 B254PUNV-DGE1C 2 – F54T5HO PRS UNV 50/60 Hz D Can 80 10
72279 GE254MVPS-D 2 or 1 – F54T5HO 120 to 277 UltraStart® PRS D Can 10
99649 GE454MVPS90-E
4-1 – F54T5HO 120 to 277 UltraStart® PRS High
Temp E Can 81 99650 8
29726 GE454MVPSN1
4,3,2, or 1 – F54T5HO 120-277V UltraStart® PRS
Can 81 29717 12
72280 GE180MVPS-D 1 – F80T5HO 120 to 277 UltraStart® PRS D Can 10
T5 lamp lengths are noted to nearest foot and are not exact lengths as noted in feet. See GE Lamp Catalog for exact lamp length.
T12 Fluorescent Ballasts
T12 ELECTRONIC BALLASTS
ProLine® T12 Multivolt 120V – 277V
For F20 (2 ft), F30 (3 ft), and F34/F40 (4 ft) T12 Lamps
24107 GE-240-RS-MV-N
2 or 1 – F40 or F34T12 Rapid Start 120 to 277 “N”
BF ProLine® T12 85 24773 10
97498 GE240RS120
2 – F40 or F34T12 Rapid Start 120V “N” BF
ProLine® T12 85 97499 10
72110 GE140RS120-DIY
1 – F40 or F34T12 Rapid Start Electronic 120V “N”
BF DIY Pack 86 72110
24109 GE-340-RS-MV-N
3 or 2 – F40 or F34T12 Rapid Start 120 to 277
ProLine® T12 86 24774 10
For T12 4 ft – 8 ft Slimline Lamps
24108 GE-260-IS-MV-N 2 or 1 – F96T12 Instant Start 120 to 277 87 24776 10
T12 HIGH OUTPUT
80162 B295SR120HP 2 – F96T12HOES RS 120 88 6
80163 B295SR277HP 2 – F96T12HOES RS 277 88 6
72109 GE296HO-MV-N
2 or 1 – F96T12 HO RS 120 to 277 Multivolt
ProLine®89
T12 MAGNETIC BALLASTS
For 2 ft, Circleline, Preheat T12 Lamps
89711 GEM120PH120DIY
1 – F20T12, F15T8, F1512, F14T8, F18T8, 120V
Magnetic Ballast (200H2) 90 89711 10
89712 GEM120TC120DIY
1 – F20T12, F15T8, F15T12, F14T12, 120V
Magnetic Ballast (546BTCP) 90 89712 4
89720 GEM1FC16T9RS120
2 – FC12T9, FC16T9, FC8T9, FC12T9, 120V
Magnetic (726VLHWSTCP) 91 89720 4
86227 GEM1FC8T9RS120IP
1 – FC8T9, FC6T9 RS 120V Magnetic Ballast
(547RSWSTCP) 91 89722 10
89717 GEM1FC12T9RS120
2 FC12T9 RS 120V Magnetic Ballast
(449LRWSTCP) 92 89717
80819 GEM220TS120DIY
2– F20T12, F15T8, F15T12, F14T12, 120V
Magnetic Ballast (447LRVLHTCP) 92 80819 4
T8 Fluorescent Ballasts
2008 T8 Ballast Enhancement New Product Code Cross Reference
Prod Code
Existing New Description (Same) Application
Product Page
Number
Units Per
Carton
UltraMax® Instant-Start Multi-Voltage High-Efficiency
49706 72258 GE132MAX-L/ULTRA 1- F32T8 120 to 277 “L” .77BF UltraMax®38 10
49771 72259 GE132MAX-N/ULTRA 1- F32T8 120 to 277”N” .87 BF UltraMax®38 10
23939 72260 GE132MAX-N-DIY 1- F32T8 120 to 277”N” .87 BF UltraMax® DIY Pack 4
49707 72262 GE232MAX-L/ULTRA 2 or 1- F32T8 120 to 277 “L” .77 BF UltraMax®39 10
47546 72263 GE232MAX-L-42T 2 or 1- F32T8 120 to 277 “L” .77 BF UltraMax® Pallet Pack 420
71281 72264 GE232MAX-N/AMP 2 or 1- F32T8 120 to 277 “N” .87 BF UltraMax® w/ AMP Connectors 10
97656 72265 GE232MAX-N/CTR 2 or 1- F32T8 120 to 277 “N” .87 BF UltraMax® w/ JST Connectors 10
49772 72266 GE232MAX-N/ULTRA 2 or 1- F32T8 120 to 277 “N” .87 BF UltraMax®40 10
31052 72267 GE232MAX-N-42T 2 or 1- F32T8 120 to 277 “N” .87 BF UltraMax® Pallet Pack 420
23940 72268 GE232MAX-N-DIY 2 or 1- F32T8 120 to 277 “N” .87 BF UltraMax® DIY Pack 10
49776 71714 GE332MAX-H/ULTRA 3 or 2- F32T8 120 to 277 “H” 1.18 BF UltraMax®41 10
47549 71715 GE332MAX-H-42T 3 or 2- F32T8 120 to 277 “H” 1.18 BF UltraMax® Pallet Pack 420
49708 71717 GE332MAX-L/ULTRA 3 or 2- F32T8 120 to 277 “L” .77 BF UltraMax®41 10
31055 71718 GE332MAX-L-42T 3 or 2- F32T8 120 to 277 “L” .77 BF UltraMax® Pallet Pack 420
97657 71720 GE332MAX-N/CTR 3 or 2- F32T8 120 to 277 “N” .87 BF UltraMax® w/ JST Connectors 10
49773 71719 GE332MAX-N/ULTRA 3 or 2- F32T8 120 to 277 “N” .87 BF UltraMax®42 10
31053 71721 GE332MAX-N-42T 3 or 2- F32T8 120 to 277 “N” .87 BF UltraMax® Pallet Pack 420
23941 71722 GE332MAX-N-DIY 3 or 2- F32T8 120 to 277 “N” .87 BF UltraMax® DIY Pack 4
49777 71723 GE432MAX-H/ULTRA 4 or 3- F32T8 120 to 277 “H” 1.18 BF UltraMax®43 10
47550 71724 GE432MAX-H-42T 4 or 3- F32T8 120 to 277 “H” 1.18 BF UltraMax® Pallet Pack 420
49709 71725 GE432MAX-L/ULTRA 4 or 3- F32T8 120 to 277 “L” .77 BF UltraMax®43 10
47547 71726 GE432MAX-L-42T 4 or 3- F32T8 120 to 277 “L” .77 BF UltraMax® Pallet Pack 420
97658 71728 GE432MAX-N/CTR 4 or 3- F32T8 120 to 277 “N” .87 BF UltraMax® w/ JST Connectors 10
49774 71727 GE432MAX-N/ULTRA 4 or 3- F32T8 120 to 277 “N” .87 BF UltraMax®44 10
31054 71729 GE432MAX-N-42T 4 or 3- F32T8 120 to 277 “N” .87 BF UltraMax® Pallet Pack 420
23942 71730 GE432MAX-N-DIY 4 or 3- F32T8 120 to 277 “N” .87 BF UltraMax® DIY Pack 4
ProLine® T8 Multivolt 120-277V
30189 72269 GE-132-MV-N 1- F32T8 120 to 277 “N”.87 BF Multivolt ProLine®46 10
30268 72270 GE-132-MV-N-42T 1- F32T8 120 to 277 “N.87 BF Multivolt ProLine® Pallet Pack 420
30247 72273 GE-232-MV-L 2 or 1- F32T8 120 to 277 “L.77 BF Multivolt ProLine®47 10
30308 72274 GE-232-MV-L-42T 2 or 1- F32T8 120 to 277 “L.77 BF Multivolt ProLine® Pallet Pack 420
30191 72275 GE-232-MV-N 2 or 1- F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47 10
30269 72276 GE-232-MV-N-42T 2 or 1- F32T8 120 to 277 “N”.87 BF Multivolt ProLine® Pallet Pack 420
97709 72277 GE232MV-N-DIY 2 or 1- F32T8 120 to 277 “N”.87 BF Multivolt ProLine® Pallet Pack DIY Pack 4
10
Quick reference ballast selection guide (cont.)
See page 195 for warranty information. 11
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Std Pack
Prod Code Description Application
Product Page
Number Pallet Pack DIY Pack
Std Pack
Units Per
Carton
T12 Fluorescent Ballasts
For F30, F34/F40 (4 ft) T12 Lamps
89714 GEM140HRS120DIY
1 – F40T12, F40T12, 120V Magnetic Ballast
(412LSLHTCP) 93 89714 4
89709 GEM140RS120DIY
1 – F40T12, F30T12, F48/25W, 120V Magnetic
Ballast (413CTCP) 93 89709 4
80644 GEM230RS120DIY 2 – F30T12 120V Magnetic Ballast (573LTCP) 94 80644 4
89710 GEM240HRS120DIY
2 – F40T12, F40T12, 120V Magnetic Ballast
(420LTCP) 94 89710 4
86139 GEM240RS120IP
2 – F40T12 RS 120V Magnetic Ballast
(446LSLHTCP) 95 46958 10
86124 GEM240RS277IP
2 – F40T12 RS 277V Magnetic Ballast
(443LSLHTCP) 95 89713 10
86341 GEM240RS220IP
2 – F40T12, F40T10, 220V Magnetic Ballast
(754LTCP) 96 10
For T12 4 ft – 8 ft Slimline Lamps
86372 GEM196IS120IP 1 – F96T12 IS 120 Magnetic Ballast (822BRTCP) 97 86372 6
86381 GEM196IS277IP 1 – F96T12 IS 277 Magnetic Ballast (828BRTCP) 97 6
86360 GEM296IS120IP 2 – F96T12 IS 120V Magnetic Ballast (806SLHTCP) 98 46965 6
86379 GEM296IS277IP 2 – F96T12 IS 277V Magnetic Ballast (827SLHTCP) 98 89715 6
For T12 High Output Lamps
86164 GEM296HORS120IP
2 – F96T12HO, F96T8HO, F72T12HO RS 120V
Magnetic Ballast (480SLHTCP) 99 89718 4
86171 GEM296HORS277IP
2 – F96T12HO, F96T8HO, RS 277V Magnetic
Ballast (487SLHTCP) 99 4
80664 493B2 2 – F73T12/BL/HO Suntan 120 Magnetic Ballast 100 10
FLUORESCENT ACCESSORIES
Starters
80619 FS-2-C Starters for 14, 15 & 20 Watt Flu. Lamps 100 24
80620 FS-4-C Starters for 30 & 40 Watt Flu. Lamps 100 24
80621 FS-5-C Starters for 4, 6 & 8 Watt Flu. Lamps 100 24
80622 FS-25-C Starters for 22 & 25 Watt Flu. Lamps 100 24
80629 FS-12-C Starters for 32 Watt Circular Flu. Lamps 100 24
Sockets
80623 BP-SKT Socket Set w/Starter for Bi-Pin Flu. Lamps 100 12
80624 BP Socket Set for Bi-Pin Flu. Lamps 100 12
80625 SL-SS Socket Set for Slimline Flu. Lamps 100 12
80627 BP-FM Face Mount Socket Set for Bi-Pin Flu. Lamps 100 12
80628 BP-LP Low Profile Socket Set for Bi-Pin Flu. Lamps 100 12
Sign Ballasts
For T12 High Output Lamps
72103 GESB-0412-12-IP T12HO Sign ballast, 4 to 12 ft, 1 to 2 lamps 107 1
72104 GESB-0620-24-IP T12HO Sign ballast 6 to 20 ft, 2 to 4 lamps 107 1
72105 GESB-1224-24-IP T12HO Sign ballast 12 to 24 ft, 2 to 4 lamps 108 1
72106 GESB-1240-46-IP T12HO Sign Ballast 12 to 40 ft, 4 to 6 lamps 108 1
72107 GESB-2040-24-IP T12HO Sign Ballast 20 to 40 ft, 4 to 6 lamps 109 1
72108 GESB-2448-46-IP T12HO Sign Ballast 24 to 48 ft, 4 to 6 lamps 109 1
88921 USB-0412-12-IP 4 to 12 ft, 1 to 2 lamps 110
88931 USB-0816-14-IP 08 to 16 ft, 1 to 4 lamps 110 4
88934 USB-1632-24-IP 16 to 32 ft, 2 to 4 lamps 111 2
88936 USB-1024-14-IP 10 to 24 ft, 1 to 4 lamps 111 2
88939 USB-2036-46-IP 20 to 36 ft, 4 to 6 lamps 112 2
88940 USB-2048-46-IP 20 to 48 ft, 4 to 6 lamps 112 2
88918 USB-0218-16-IP Max 3, 02 to 18 ft, 1 to 6 lamps 113 2
88919 USB-1048-16-IP Max 3, 10 to 48 ft, 1 to 6 lamps 113 2
88920 USB-1232-16-IP Max 3, 12 to 32 ft, 1 to 6 lamps 114 2
Prod
Code Description Application
Product
Page
Number
Bottom Exit
with Studs
Dual Exit/
Bottom and
side
3-Way
Mounting
Units Per
Carton
Compact Fluorescent Ballasts
ProLine® CFL Electronic Ballasts
For 13 – 42W T4 CFL Lamps
71430 GEC213-MVPS-3W
2 or 1 - CFQ13W/G24q Bottom Exit 120-277V
ProLine® PS 123 71428 71429 71430 10
71434 GEC218-MVPS-3W
2 or 1 - CFQ18W/G24q Bottom Exit 120-277
ProLine® PS 123 71432 71433 71434 10
71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit
120-277V ProLine® PS 124 71443 71444 71445 10
47509 C242UNVSE-IP 2 - 42/36/32/26/24 watt CFLUNV side exit 124 47506 10
For 40W Biax® CFL Ballasts
80683 C240PUNVHP-B-IP 2 or 1 – FT40W2G11 PS UNV 125 10
80680 C240SI120RH-IP 2 – FT40W/2G11 IS 120 125 10
80681 C240SI277RH-IP 2 – FT40W/2G11 IS 277 126 10
80690 C340SI120RH-IP 3 – FT40W/2G11 IS 120 126 10
80691 C340SI277RH-IP 3 – FT40W/2G11 IS 277 127 10
For 5 – 26W Preheat CFL Lamps
87634 GEM1CF579PH277 1 – CFT579Q9W/G23 Preheat 277 (4205F2P) 128 20
87533 GEM1CF13PH120 1 – CFT/Q13W/GX23 Preheat 120 (4111H2P) 128 20
CFL Magnetic Ballasts
For 5 – 26W Preheat CFL Lamps
87655 GEM2CF13PH277 2 – CFT/Q13W/GX23 Preheat 277 (4214PBES) 129 10
87700 GEM2CF24PH277 2 – CFQ26W/G24d Preheat 277 (4226PBES) 129 10
For 36 – 40W CFL Lamps
87623 GEM2FT36RS120 2 – FT36W/2G11 RS 120 (4150P) 130 10
87625 GEM2FT40RS120 2 – FT40W/2G11RS RS 120 (4152P) 130 10
12
Quick reference ballast selection guide (cont.)
See page 195 for warranty information. 13
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Prod
Code Description Application
Product Page
Number ANSI Lamp Type Circuit Type
Units Per
Carton
HID Electronic Ballasts
For 20 – 150W Pulse Start HID Lamps
87490 GEMH20-MLF-120 1 – 20W M156 120V Electronic HID 135 M156 Electronic 10
87501 GEMH39-MSF-120 1 – 39W M130 120V Electronic HID 135 M130 Electronic 10
87516 GEMH50-MSF-120
1 – 50W M110 M/C148 120V Electronic
HID 136 M148, M110, C148 Electronic 10
87531 GEMH70-MSF-120
1 – 70W M98 M/C143 120V Electronic
HID 136
M98, M143, M139,
C143, C139 Electronic 10
87546 GEMH70-SLJ-MV
1 – 70W M98 M/C143 120V-277V
Electronic HID 137
M139, C139, M98,
M143, C143 Electronic 10
87561 GEMH100-SLJ-MV
1 – 100W M90 M/C140 120V-277V
Electronic HID 137 M90, M140, C140 Electronic 10
87576 GEMH150-SLJ-MV
1 – 150W M102 M/C142 120V-277V
Electronic HID 138 M142, M102, C142 Electronic 10
For 250W – 400W Pulse Start HID Lamps
29377 GE-MH-250-400-MA
1 – 250 to 400W UltraMax® HID
Electronic 208-277 50-60Hz 139
M155, M153, M138,
M135, M132, M131,
M154 Electronic 1
89646 GEMH250-400M-V50
1 – 250 to 400W UltraMax® HID
Dimming 208-277 50-60Hz 139
M155, M154, M153,
M138, M135, M132,
M131 Electronic 1
HID Electromagnetic Ballasts
Metal Halide
For 20 – 175W Metal Halide HID Lamps
86824 GEM50MLTLC3D-5
1 – 50W MH M110 or M148 Quad
(120/208/240/277V) 144 M110 HX-HPF 6
86847 GEM70MLTLC3D-5
1 – 70W MH M98 or M143 Quad
(120/208/240/277V) 144 M98 HX-HPF 6
86839 GEM7048TLC3D-5 1 – 70W MH M98 or M143 480 145 M98 HX-HPF 6
86675 GEM100MLTLC3D-5
1 – 100W MH M90 or M140 Quad
(120/208/240/277V) 145 M92, M90, M140 HX-HPF 6
86667 GEM10048TLC3D-5 1 – 100W MH M90 or M140 480 146 M92, M90, 40 HX-HPF 6
86718 GEM150MLTLC3D-5
1 – 150W MH M102 or M142 Quad
(120/208/240/277V) 146 M142, M102 HX-HPF 6
86711 GEM15048TLC3D-5 1 – 150W MH M102 or M142 480 147 M142, M102, M107 HX-HPF 6
87210 GEM175ML5AC3-5
1 – 175W MH M57 or H39 5-Tap
(120/208/240/277/480V) 147 M57, H39, M109 CWA 6
86741 GEM175MLTAC3-5
1 – 175W MH M57 or H39 Quad
(120/208/240/277V) 148 M57, M107, H39 CWA 6
For 250 – 1500W Metal Halide HID Lamps
87211 GEM250ML5AC3-5
1 – 250W MH M58 or H37 5-Tap
(120/208/240/277/480V) 149 M58, H37 CWA 6
86765 GEM250MLTAC3-5
1 – 250W MH M58 or H37 Quad
(120/208/240/277V) 149 M58, H37 CWA 6
87212 GEM250ML5AC4-5
1 – 250W MH M58 or H37 5-Tap
(120/208/240/277/480V) 150 M58, H37 CWA 3
72300 GEM400ML5AA4-5
1 – 400W MH M59 or H33 5-Tap
(120/208/240/277/480V) Al C&C 150 M59, H33 CWA 3
72149 GEM400MLTAA4-5
1 – 400W MH M59 or H33 Quad
(120/208/240/277V) Al C&C 151 M59, H33 CWA 3
86803 GEM40048TAC4-5 1 – 400W MH M59 or H33 480 151 M59, H33 CWA 3
86650 GEM100048TAC5-5 1 – 1000W MH M47 or H36 480 152 M47, H36 CWA 2
87213 GEM1000ML5AA5-5
1 – 1000W MH M47 or H36 5-Tap
(120/208/240/277/480V) 152 M47, H36 CWA 2
86655 GEM1000MLTAA5-5
1 – 1000W MH M47 or H36 Quad
(120/208/240/277V) 153 M47, H36 CWA 2
86693 GEM150048TAC5-5 1 – 1500W MH M48 480 153 M48 CWA 2
86698 GEM1500MLTAC5-5
1 – 1500W MH M48 Quad
(120/208/240/277V) 154 M48 CWA 2
Prod
Code Description Application
Product Page
Number ANSI Lamp Type Circuit Type
Units Per
Carton
HID Electromagnetic Ballasts
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
86885 GEP175MLTAC3-5
1 – 175W PS M137 or M152 Quad
(120/208/240/277V) 155 M153, M137 CWA 6
86876 GEP17548TAC3-5 1 – 175W PS M137 or M152 480 155 M152, M137 CWA 6
86935 GEP250MLTAC4-5
1 – 250W PS M138 or M153 Quad
(120/208/240/277V) 156 M153, M138 CWA 3
86926 GEP25048TAC4-5 1 – 250W PS M138 or M153 480 156 M153, M138 CWA 3
86959 GEP320MLTAC4-5
1 – 320W PS M132 or 154 Quad
(120/208/240/277V) 157 M154, M132 CWA 3
86952 GEP32048TAC4-5 1 – 320W PS M132 or M154 480 157 M154, M132 CWA 3
86968 GEP320TRIAC4-5
1 – 320W PS M132 or M154 TRI-Voltage
120 277 347 158 M154, M132 CWA 3
86984 GEP350MLTAC4-5
1 – 350W PS M131 Quad
(120/208/240/277V) 158 M131 CWA 3
86999 GEP40048TAC4-5 1 – 400W PS M135 or M155 480 159 M155, M135 CWA 3
87008 GEP400MLTAC4-5
1 – 400W PS M135 or M155 Quad
(120/208/240/277V) 159 M155, M135 CWA 3
46936 GEP75048TAC5-5 1 – 750W PS M149 480 160 M149 CWA 2
46934 GEP750MLTAC5-5
1 – 750W PS M149 Quad
(120/208/240/277V) 160 M149 CWA 2
72281 GEP1000MLTAC5-5
1 – 1000W PS M141 Quad
(120/208/240/277V) 161 M141 CWA 2
72282 GEP1000ML5AC5-5
1 – 1000W PS M141 5-Tap
(120/208/240/277/480V) 161 M141 CWA 2
High-Pressure Sodium
For 50 – 150W High Pressure Sodium HID Lamps
87152 GES50MLTLC3D-5
1 – 50W HPS S68 Quad
(120/208/240/277V) 162 S68 HX-HPF 6
86587 GES70MLTLC3D-5
1 – 70W HPS S62 Quad
(120/208/240/277V) 162 S62 HX-HPF 6
86456 GES7048TLC3D-5 1 – 70W HPS S62 480V 163 S62 HX-HPF 6
87074 GES100MLTLC3D-5
1 – 100W HPS S54 Quad
(120/208/240/277V) 163 S54 HX-HPF 6
87068 GES10048TLC3D-5 1 – 100W HPS S54 480V 164 S54 HX-HPF 6
87094 GES150MLTLC3D-5
1 – 150W HPS S55 Quad
(120/208/240/277V) 164 S55 HX-HPF 6
87087 GES15048TLC3D-5 1 – 150W HPS S55 480V 165 S55 HX-HPF 6
For 250 – 1000W High Pressure Sodium HID Lamps
87214 GES250ML5AC4-5
1 – 250W HPS S50 5-Tap
(120/208/240/277/480V) 166 S50 CWA 3
87121 GES250MLTAC4-5
1 – 250W HPS S50 Quad
(120/208/240/277V) 166 S50 CWA 3
87215 GES400ML5AC4-5
1 – 400W HPS S51 5-Tap
(120/208/240/277/480V) 167 S51 CWA 3
87164 GES400MLTAC4-5
1 – 400W HPS S51 Quad
(120/208/240/277V) 167 S51 CWA 3
87198 GES40048TAC4-5
1 – 400W HPS S51 480V in smaller
frame 168 S51 CWA 3
87048 GES100048TAC5-5 1 – 1000W HPS S52 480V 168 S52 CWA 2
87218 GES1000ML5AC5-5
1 – 1000W HPS S52 5-Tap
(120/208/240/277/480V) 169 S52 CWA 2
87056 GES1000MLTAC5-5
1 – 1000W HPS S52 Quad
(120/208/240/277V) 169 S52 CWA 2
14
Quick reference ballast selection guide (cont.)
See page 195 for warranty information. 15
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Prod
Code Description Application
Product Page
Number ANSI Lamp Type Circuit Type
Units Per
Carton
HID Electromagnetic Ballasts
High Intensity Discharge Lamp Ballast Kits
71701 GEM175ML5AC3-55
1 – 175W MH M57 or H39 5-Tap
(120/208/240/277/480V) Lamp
& Ballast Kit (-55) 170
M57 Mogul Base
Elliptical Lamp CWA 1
71702 GEM250ML5AC3-55
1 – 250W MH M58 or H37 5-Tap
(120/208/240/277/480V) Lamp
& Ballast Kit (-55) 170
M58 Mogul Base
Elliptical Lamp CWA 1
71703 GEM400ML5AC4-55
1 – 400W MH M59 or H33 5-Tap
(120/208/240/277/480V) Lamp
& Ballast Kit (-55) 171
M59 Mogul Base
Elliptical Lamp CWA 1
71704 GEM1000ML5AC4-55
1 – 1000W MH M47 or H36 5-Tap
(120/208/240/277/480V) Lamp
& Ballast Kit (-55) 171
M47 Mogul Base
Elliptical Lamp CWA 1
71705 GES100MLTLC3D-55
1 – 100W HPS S54 Quad
(120/208/240/277V) Lamp & Ballast
Kit (-55) 172
S54 Medium Base
Elliptical Lamp HX-HPF 1
71706 GES250ML5AC4-55
1 – 250W HPS S50 5-Tap
(120/208/240/277/480V) Lamp &
Ballast Kit (-55) 172
M50 Mogul Base ED18
Lamp CWA 1
71707 GES400ML5AC4-55
1 – 400W HPS S51 5-Tap
(120/208/240/277/480V) Lamp &
Ballast Kit (-55) 173
S51 Mogul Base ED18
Lamp CWA 1
Enclosed and Potted Metal Halide
86576 11210277CTC000C
1 – 70W M85 120/277 Enclosed
& Potted 174 M85 HX-HPF 4
86578 11210506CTC000C
1 – 70W M98 120/277 Enclosed
& Potted 174 M98 HX-HPF 4
86574 11210239CTC000I
1 – 100W M90 120/277 Enclosed
& Potted 175 M90 HX-HPF 4
86563 1110245SCTC000I
1 – 175W M57 120/277 Enclosed
& Potted 175 M57, H39 CWA 2
86564 1110246CTC000C
1 – 250W M58 120/277 Enclosed
& Potted 176 M58, H37 CWA 2
42670 1110-247SC-TC
1 – 400W M59 120/277 Enclosed
& Potted F-can 176 M59, H33 CWA 2
80728 1111-247SCTC000I
1 – 400W M59 120/277 Enclosed
& Potted 177 M59, H33 CWA 4
F-Can and Post Mount High Pressure Sodium
86605 1233142U000I 1 – 70W S62 120 Reactor-NPF 178 S62 R-HPF, R-NPF 6
86596 12210237CTC000I
1 – 70W S62 120/277 E and P
F-Can built-in starter 178 S62 HX-HPF 4
86606 1233154U000I 1 – 150W S55 120 Reactor-NPF 179 S55 R-NPF 6
Prod
Code Description Application
Product Page
Number ANSI Lamp Type Circuit Type
Units Per
Carton
HID Electromagnetic Ballasts
HID ACCESSORIES
Replacement Capacitors 20
88980 005-1184-MF
10.0 MFD 400V 90C 2.4 MEG 1.50 oval
2.7 ht 179 20
88982 005-1185-MF
15.0 MFD 400V 90C 1.6 MEG 1.75 oval
2.7 ht 179 20
89007 005-1422-MF
48.0 MFD 300V 90C 0.6 MEG 1.75 oval
3.9 ht 179 20
89077 005-2779-MF 24.0 MFD 480V 90C 1.75 oval 3.9 ht 179 20
89083 005-3160-MF
24.0 MFD 360V 90C 1.0 MEG 1.75 oval
3.1 ht 179 20
Replacement Ignitors for Pulse Start lamps – (MH and HPS)
86864 MH100-3A Ignitor for MH 30 50 70 100 179 20
86635 HPS150-3A
Ignitor HPS 150 watts or less except
150W-S56 179 20
86641 HPS400-3A
Ignitor HPS 200-400 watts &
150W S56 179 10
Other Accessories
47621 000-8724
HIDP Adjustable Mounting Bracket
Hardware Kit 179 100
86467 001-2009 Splice Box 179 10
86468 004-9177
Adjustable Mounting Bracket For 4"
HID 179 50
86624 2BMB1000C HID Parts E&P Mounting Bracket 179 50
16 See page 195 for warranty information. 17
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Quick reference lamp to ballast selection guide
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F13T5 2 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71427 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 44
F14T12 1 120 Magnetic - Rapid Start 89712 GEM120TC120DIY 1 - F20T12 F15T8 F15T12 F14T12 120V Magnetic Ballast (546BTCP) 90
F14T5/HE
2 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
2 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
F14T5/WM
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
F14T8 1 120 Magnetic - Rapid Start 89711 GEM120PH120DIY 1 - F20T12 F15T8 F1512 120V Magnetic Ballast (200H2) 90
F15T12 2 120 Magnetic - Rapid Start 80819 GEM220TS120DIY
2- F20T12 F15T8 F15T12 F14T12 120V Magnetic Ballast
(447LRVLHTCP) 92
1 120 Magnetic - Rapid Start 89711 GEM120PH120DIY 1 - F20T12 F15T8 F1512 120V Magnetic Ballast (200H2) 90
1 120 Magnetic - Rapid Start 89712 GEM120TC120DIY 1 - F20T12 F15T8 F15T12 F14T12 120V Magnetic Ballast (546BTCP) 90
F15T8 2 120 Magnetic - Rapid Start 80819 GEM220TS120DIY
2- F20T12 F15T8 F15T12 F14T12 120V Magnetic Ballast
(447LRVLHTCP) 92
1 120 Magnetic - Rapid Start 89711 GEM120PH120DIY 1 - F20T12 F15T8 F1512 120V Magnetic Ballast (200H2) 90
1 120 Magnetic - Rapid Start 89712 GEM120TC120DIY 1 - F20T12 F15T8 F15T12 F14T12 120V Magnetic Ballast (546BTCP) 90
F17T8
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®44
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
4 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
4 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
4 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
4 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
4 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®62
4 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F17T8
(cont)
3 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
3 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
3 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
3 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
3 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
3 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
3 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N.87 BF ProLine®55
3 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
3 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
3 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
3 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
3 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
3 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
2 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N 2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
2 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
2 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
2 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
2 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
2 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
2 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
2 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
2 277 Magnetic - Rapid Start 87130 GEM232T8RS277 2 - F32T8 RS 277V Magnetic Ballast (M232SR277C) 59
2 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
2 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
2 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
2 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72258 GE132MAX-L/ULTRA 1 - F32T8 120 to 277 “L” .77BF UltraMax®38
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72259 GE132MAX-N/ULTRA 1 - F32T8 120 to 277”N” .87 BF UltraMax®38
1 120-277 Electronic - Multivolt Instant Start 72269 GE-132-MV-N 1 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®46
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
18
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 19
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F17T8
(cont)
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®43
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
1 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
1 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N
2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD
UltraStart®61
1 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
1 277 Electronic - Standard Instant Start 23681 GE-132-277-N 1 - F32T8 277V “N”.87 BF ProLine®53
1 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
1 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 23680 GE-132-120-N 1 - F32T8 120V “N”.87 BF ProLine®53
1 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
1 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
F18T8 1 120 Magnetic - Rapid Start 89711 GEM120PH120DIY 1 - F20T12 F15T8 F1512 120V Magnetic Ballast (200H2) 90
F20T12
2 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
2 120 Magnetic - Rapid Start 80819 GEM220TS120DIY
2- F20T12 F15T8 F15T12 F14T12 120V Magnetic Ballast
(447LRVLHTCP) 92
1 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
1 120 Magnetic - Rapid Start 89711 GEM120PH120DIY 1 - F20T12 F15T8 F1512 120V Magnetic Ballast (200H2) 90
1 120 Magnetic - Rapid Start 89712 GEM120TC120DIY 1 - F20T12 F15T8 F15T12 F14T12 120V Magnetic Ballast (546BTCP) 90
F21T5/HE
2 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
15 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
1 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
14 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
F21T5/WM
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
F24T5/HO
2 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 79
2 120-277 Electronic - Program / Rapid Start 47540 B239PUNV-DOG1C 2 - F39T5HO PRS UNV 50/60 Hz 79
2 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3-Way Mounting Kit 120-277V
ProLine® PS 124
2 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 79
1 120-277 Electronic - Program / Rapid Start 47540 B239PUNV-DOG1C 2 - F39T5HO PRS UNV 50/60 Hz 79
F25T12
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F25T12
(cont)
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
4 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
4 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
3 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
3 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
3 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
3 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®43
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
2 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
2 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
2 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 2 F40 or F34T12 Rapid Start Electronic 120V “N” BF 85
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72258 GE132MAX-L/ULTRA 1 - F32T8 120 to 277 “L” .77BF UltraMax®38
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72259 GE132MAX-N/ULTRA 1 - F32T8 120 to 277”N” .87 BF UltraMax®38
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®43
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
1 277 Electronic - Standard Instant Start 23681 GE-132-277-N 1 - F32T8 277V “N”.87 BF ProLine®53
1 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
1 120 Electronic - Standard Instant Start 23680 GE-132-120-N 1 - F32T8 120V “N”.87 BF ProLine®53
1 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
F25T8
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
4 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
3 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
20
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 21
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F25T8
(cont)
4 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
4 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
4 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
4 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
4 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
4 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
3 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
3 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
3 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
3 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
3 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
3 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
3 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
3 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
3 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
3 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
3 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
3 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
3 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
2 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N
2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD Ultra-
Start®61
2 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
2 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
2 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
2 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
2 277 Electronic - Dimming 80362 B232SR277S50 2 - F32T8 Switch 100/50% RS 277 70
2 277 Electronic - Dimming 80362 B232SR277S50 2 - F32T8 Switch 100/50% RS 277 70
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F25T8
(cont)
2 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
2 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
2 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
2 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
2 277 Magnetic - Rapid Start 87130 GEM232T8RS277 2 - F32T8 RS 277V Magnetic Ballast (M232SR277C) 59
2 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
2 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
2 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
2 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72258 GE132MAX-L/ULTRA 1 - F32T8 120 to 277 “L” .77BF UltraMax®38
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72259 GE132MAX-N/ULTRA 1 - F32T8 120 to 277”N” .87 BF UltraMax®38
1 120-277 Electronic - Multivolt Instant Start 72269 GE-132-MV-N 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®46
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
1 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
1 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N
2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD
UltraStart®61
1 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
1 277 Electronic - Standard Instant Start 23681 GE-132-277-N 1 - F32T8 277V “N”.87 BF ProLine®53
1 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
1 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Dimming 80353 B132R120V5 1 - F32T8 DIM 100 to 5% RS 120 69
1 120 Electronic - Dimming 80353 B132R120V5 1 - F32T8 DIM 100 to 5% RS 120 69
1 120 Electronic - Standard Instant Start 23680 GE-132-120-N 1 - F32T8 120V “N”.87 BF ProLine®53
1 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
1 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
F28T5
2 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
8 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
1 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
7 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
F28T5/HE
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
F28T5/HL
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
F28T5/WM
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15 BF
A Can 77
22
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 23
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F28T8
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
4 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
3 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
4 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
4 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
4 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
4 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
4 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
4 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
3 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
3 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
3 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
3 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
3 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
3 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
3 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
3 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
3 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
3 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
3 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
3 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
3 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F28T8
(cont)
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
2 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N 2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
2 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
2 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
2 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
2 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
2 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
2 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
2 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
2 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
2 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
2 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
2 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72258 GE132MAX-L/ULTRA 1 - F32T8 120 to 277 “L” .77BF UltraMax®38
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72259 GE132MAX-N/ULTRA 1 - F32T8 120 to 277”N” .87 BF UltraMax®38
1 120-277 Electronic - Multivolt Instant Start 72269 GE-132-MV-N 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®46
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
1 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
1 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N
2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD
UltraStart®61
1 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
1 277 Electronic - Standard Instant Start 23681 GE-132-277-N 1 - F32T8 277V “N”.87 BF ProLine®53
1 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
1 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 23680 GE-132-120-N 1 - F32T8 120V “N”.87 BF ProLine®53
1 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
1 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
F30T12
3 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
2 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 2 F40 or F34T12 Rapid Start Electronic 120V “N” BF 85
2 120 Magnetic - Rapid Start 80644 GEM230RS120DIY 2 - F30T12 120V Magnetic Ballast (573LTCP) 94
1 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 - F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
1 120 Magnetic - Rapid Start 89709 GEM140RS120DIY 1 - F40T12 F30T12 F48/25W 120V Magnetic Ballast (413CTCP) 93
F30T12/WM
2 120 Magnetic - Rapid Start 80644 GEM230RS120DIY 2 - F30T12 120V Magnetic Ballast (573LTCP) 94
3 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
2 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
1 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
F32T8
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
4 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
24
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 25
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F32T8
(cont)
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
3 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
4 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
4 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
4 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
4 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
4 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
4 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
3 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
3 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
3 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
3 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
3 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
3 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
3 277 Electronic - Dimming 80358 B332SR277V5 3 - F32T8 DIM 100 to 5% RS 277 71
3 277 Electronic - Dimming 80358 B332SR277V5 3 - F32T8 DIM 100 to 5% RS 277 71
3 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
3 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
3 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
3 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Dimming 80357 B332SR120V5 3 - F32T8 DIM 100 to 5% RS 120 71
3 120 Electronic - Dimming 80357 B332SR120V5 3 - F32T8 DIM 100 to 5% RS 120 71
3 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
3 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
3 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
3 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F32T8
(cont)
2 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
2 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N 2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
2 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
2 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
2 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
2 277 Electronic - Dimming 80362 B232SR277S50 2 - F32T8 Switch 100/50% RS 277 70
2 277 Electronic - Dimming 80362 B232SR277S50 2 - F32T8 Switch 100/50% RS 277 70
2 277 Electronic - Dimming 80362 B232SR277S50 2 - F32T8 Switch 100/50% RS 277 70
2 277 Electronic - Dimming 80356 B232SR277V5 2 - F32T8 DIM 100 to 5% RS 277 70
2 277 Electronic - Dimming 80356 B232SR277V5 2 - F32T8 DIM 100 to 5% RS 277 70
2 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
2 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
2 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
2 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
2 277 Magnetic - Rapid Start 87130 GEM232T8RS277 2 - F32T8 RS 277V Magnetic Ballast (M232SR277C) 59
2 120 Electronic - Dimming 80355 B232SR120V5 2 - F32T8 DIM 100 to 5% RS 120 69
2 120 Electronic - Dimming 80355 B232SR120V5 2 - F32T8 DIM 100 to 5% RS 120 69
2 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
2 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
2 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
2 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
2 120 Magnetic - Rapid Start 87125 GEM232T8RS120 2 - F32T8 RS 120V Magnetic Ballast (M232SR120C) 59
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72258 GE132MAX-L/ULTRA 1 - F32T8 120 to 277 “L” .77BF UltraMax®38
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72259 GE132MAX-N/ULTRA 1 - F32T8 120 to 277”N” .87 BF UltraMax®38
1 120-277 Electronic - Multivolt Instant Start 72269 GE-132-MV-N 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®46
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
1 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
1 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N 2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®61
1 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
1 277 Electronic - Standard Instant Start 23681 GE-132-277-N 1 - F32T8 277V “N”.87 BF ProLine®53
1 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
1 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Dimming 80353 B132R120V5 1 - F32T8 DIM 100 to 5% RS 120 69
1 120 Electronic - Dimming 80353 B132R120V5 1 - F32T8 DIM 100 to 5% RS 120 69
1 120 Electronic - Standard Instant Start 23680 GE-132-120-N 1 - F32T8 120V “N”.87 BF ProLine®53
1 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
1 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
F32T8/WM
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
4 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
3 120-277 Electronic - Program / Rapid Start 71832 GE432-MVPS-L 4 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®67
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
26
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 27
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F32T8/WM
(cont)
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
4 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
4 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
4 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
4 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
4 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
4 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
4 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
4 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
4 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
3 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
3 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
3 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
3 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
3 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71725 GE432MAX-L/ULTRA 4 or 3 - F32T8 120 to 277 “L” .77 BF UltraMax®43
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71727 GE432MAX-N/ULTRA 4 or 3 - F32T8 120 to 277 “N” .87 BF UltraMax®44
3 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
3 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Program / Rapid Start 29678 GE-432-MVPS-H 4 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®68
3 120-277 Electronic - Program / Rapid Start 96716 GE432-MVPS-N 4 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®67
3 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
3 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
3 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
3 277 Electronic - Program / Rapid Start 29627 GE-432-277-PS-N 4 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
3 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
3 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
3 120 Electronic - Program / Rapid Start 29625 GE-432-120-PS-N 4 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®66
3 120 Electronic - Standard Instant Start 97783 GE432-120-RES 4 or 3 F32T8 120V Normal Light Residential Grade FCC Class B 58
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
2 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
2 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
2 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N 2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®61
2 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71717 GE332MAX-L/ULTRA 3 or 2 - F32T8 120 to 277 “L” .77 BF UltraMax®41
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F32T8/WM
(cont)
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71719 GE332MAX-N/ULTRA 3 or 2 - F32T8 120 to 277 “N” .87 BF UltraMax®42
2 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
2 120-277 Electronic - Program / Rapid Start 29676 GE-332-MVPS-H 3 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 96721 GE332-MVPS-L 3 - F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®65
2 120-277 Electronic - Program / Rapid Start 96715 GE332-MVPS-N 3 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®64
2 120-277 Electronic - Program / Rapid Start 29672 GE-332-MVPS-XL 3 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 65
2 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
2 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
2 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
2 277 Electronic - Program / Rapid Start 29624 GE-332-277-PS-N 3 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®63
2 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
2 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
2 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
2 120 Electronic - Program / Rapid Start 29623 GE-332-120-PS-N 3 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®63
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72258 GE132MAX-L/ULTRA 1 - F32T8 120 to 277 “L” .77BF UltraMax®38
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72259 GE132MAX-N/ULTRA 1 - F32T8 120 to 277”N” .87 BF UltraMax®38
1 120-277 Electronic - Multivolt Instant Start 72269 GE-132-MV-N 1 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®46
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72262 GE232MAX-L/ULTRA 2 or 1 - F32T8 120 to 277 “L” .77 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 72266 GE232MAX-N/ULTRA 2 or 1 - F32T8 120 to 277 “N” .87 BF UltraMax®40
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Program / Rapid Start 29675 GE-232-MVPS-H 2 - F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®62
1 120-277 Electronic - Program / Rapid Start 96720 GE232-MVPS-L 2 or 1 F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®61
1 120-277 Electronic - Program / Rapid Start 96714 GE232-MVPS-N 2 or 1 - F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®61
1 120-277 Electronic - Program / Rapid Start 29671 GE-232-MVPS-XL 2 - F32T8 120V-277V Ultra Low Watt .60 BF <10% THD 62
1 277 Electronic - Standard Instant Start 23681 GE-132-277-N 1 - F32T8 277V “N”.87 BF ProLine®53
1 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
1 277 Electronic - Program / Rapid Start 29622 GE-232-277-PS-N 2 - F32T8 277V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 23680 GE-132-120-N 1 - F32T8 120V “N”.87 BF ProLine®53
1 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
1 120 Electronic - Program / Rapid Start 29621 GE-232-120-PS-N 2 - F32T8 120V Normal Light .87 BF <10% THD UltraStart®60
1 120 Electronic - Standard Instant Start 97782 GE232-120-RES 2 or 1 - F32T8 120V “N.87 BF Residential ProLine®58
F34T12
3 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
2 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 2 F40 or F34T12 Rapid Start Electronic 120V “N” BF 85
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 2 F40 or F34T12 Rapid Start Electronic 120V “N” BF 85
1 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 - F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
1 120 Magnetic - Rapid Start 89714 GEM140HRS120DIY 1 - F40T12 F40T12 120V Magnetic Ballast (412LSLHTCP) 93
1 120 Magnetic - Rapid Start 89709 GEM140RS120DIY 1 - F40T12 F30T12 F48/25W 120V Magnetic Ballast (413CTCP) 93
F35T5/HE
2 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
2 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
12 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 47536 B228PUNV-C0G1C 2 - F28T5 PRS UNV 50/60 Hz 78
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99653 GE228MVPSH-A
11 or 1 - F14-F35HE 120 to 277 UltraStart® PRS High Light 1.15
BF A Can 77
F35T5/WM 2 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
1 120-277 Electronic - Program / Rapid Start 99655 GE228MVPS-A
2 or 1 - F14-F35HE 120 to 277 UltraStart® PRS Normal Light .95
BF A Can 77
F39T5/HO
2 120-277 Electronic - Program / Rapid Start 47540 B239PUNV-DOG1C 2 - F39T5HO PRS UNV 50/60 Hz 79
1 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 79
1 120-277 Electronic - Program / Rapid Start 47540 B239PUNV-DOG1C 2 - F39T5HO PRS UNV 50/60 Hz 79
28
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 29
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F40T10
3 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
2 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 277 Magnetic - Rapid Start 86124 GEM240RS277IP 2 - F40T12 RS 277V Magnetic Ballast (443LSLHTCP) 95
2 120 Magnetic - Rapid Start 89710 GEM240HRS120DIY 2 - F40T12 F40T12 120V Magnetic Ballast (420LTCP) 94
2 120 Magnetic - Rapid Start 86139 GEM240RS120IP 2 - F40T12 RS 120V Magnetic Ballast (446LSLHTCP) 95
1 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
1 120 Magnetic - Rapid Start 89714 GEM140HRS120DIY 1 - F40T12 F40T12 120V Magnetic Ballast (412LSLHTCP) 93
F40T12
2 220 Magnetic - Rapid Start 86341 GEM240RS220IP 2 - F40T12 F40T10 220V Magnetic Ballast (754LTCP) 96
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 - F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
3 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
2 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 277 Magnetic - Rapid Start 86124 GEM240RS277IP 2 - F40T12 RS 277V Magnetic Ballast (443LSLHTCP) 95
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 2 F40 or F34T12 Rapid Start Electronic 120V “N” BF 85
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 2 F40 or F34T12 Rapid Start Electronic 120V “N” BF 85
2 120 Magnetic - Rapid Start 89710 GEM240HRS120DIY 2 - F40T12 F40T12 120V Magnetic Ballast (420LTCP) 94
2 120 Magnetic - Rapid Start 86139 GEM240RS120IP 2 - F40T12 RS 120V Magnetic Ballast (446LSLHTCP) 95
1 120-277 Electronic - Program / Rapid Start 24107 GE-240-RS-MV-N 2 or 1 - F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12 85
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
1 120 Magnetic - Rapid Start 89714 GEM140HRS120DIY 1 - F40T12 F40T12 120V Magnetic Ballast (412LSLHTCP) 93
1 120 Magnetic - Rapid Start 89709 GEM140RS120DIY 1 - F40T12 F30T12 F48/25W 120V Magnetic Ballast (413CTCP) 93
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 - F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
F40T12/
WM
2 277 Magnetic - Rapid Start 86124 GEM240RS277IP 2 - F40T12 RS 277V Magnetic Ballast (443LSLHTCP) 95
2 120 Magnetic - Rapid Start 86139 GEM240RS120IP 2 - F40T12 RS 120V Magnetic Ballast (446LSLHTCP) 95
F40T12/
WMP
3 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120-277 Electronic - Program / Rapid Start 24109 GE-340-RS-MV-N 3 or 2 - F40 or F34T12 Rapid Start 120 to 277 ProLine® T12 86
2 120 Magnetic - Rapid Start 89710 GEM240HRS120DIY 2 - F40T12 F40T12 120V Magnetic Ballast (420LTCP) 94
1 120 Magnetic - Rapid Start 89714 GEM140HRS120DIY 1 - F40T12 F40T12 120V Magnetic Ballast (412LSLHTCP) 93
F40T8
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71423 GE432MAX-N+ 4 or 3 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®44
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71422 GE332MAX-N+ 3 or 2 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®42
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49766 GE159MAX-N/ULTRA 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49775 GE232MAX-H/ULTRA 2 or 1 - F32T8 120 to 277 “H” 1.15 BF UltraMax®39
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 71421 GE232MAX-N+ 2 or 1 - F32T8 120 to 277 “N+” 1.0 BF UltraMax®40
1 120 Electronic - Standard Instant Start 23671 GE-232-120-N 2 or 1 - F32T8 120V “N”.87 BF ProLine®54
3 120-277
Electronic - High Efficiency
Multivolt Instant Start 71723 GE432MAX-H/ULTRA 4 or 3 - F32T8 120 to 277 “H” 1.15 BF UltraMax®43
3 120-277 Electronic - Multivolt Instant Start 30219 GE-432-MV-H 4 or 3 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®49
3 120-277 Electronic - Multivolt Instant Start 30262 GE-432-MV-L 4 or 3 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 120-277 Electronic - Multivolt Instant Start 30193 GE-432-MV-N 4 or 3 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®50
3 277 Electronic - Standard Instant Start 23676 GE-432-277-N 4 or 3 - F32T8 277V “N”.87 BF ProLine®56
3 120 Electronic - Standard Instant Start 23675 GE-432-120-N 4 or 3 - F32T8 120V “N”.87 BF ProLine®56
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 71714 GE332MAX-H/ULTRA 3 or 2 - F32T8 120 to 277 “H” 1.15 BF UltraMax®41
2 120-277 Electronic - Multivolt Instant Start 30199 GE-332-MV-H 3 or 2 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30255 GE-332-MV-L 3 or 2 - F32T8 120 to 277 “L” .77 BF Multivolt ProLine®48
2 120-277 Electronic - Multivolt Instant Start 30192 GE-332-MV-N 3 or 2 - F32T8 120 to 277 “N.87 BF Multivolt ProLine®49
2 277 Electronic - Standard Instant Start 23674 GE-332-277-N 3 or 2 - F32T8 277V “N”.87 BF ProLine®55
2 120 Electronic - Standard Instant Start 23673 GE-332-120-N 3 or 2 - F32T8 120V “N”.87 BF ProLine®55
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 30198 GE-232-MV-H 2 or 1 - F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®46
1 120-277 Electronic - Multivolt Instant Start 72273 GE-232-MV-L 2 or 1 - F32T8 120 to 277 “L”.77 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277 Electronic - Multivolt Instant Start 72275 GE-232-MV-N 2 or 1 - F32T8 120 to 277 “N”.87 BF Multivolt ProLine®47
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
1 277 Electronic - Standard Instant Start 23672 GE-232-277-N 2 or 1 - F32T8 277V “N”.87 BF ProLine®54
F48T12
2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
2 277 Magnetic - Standard Instant Start 86379 GEM296IS277IP 2 - F96T12 IS 277V Magnetic Ballast (827SLHTCP) 98
2 120 Magnetic - Standard Instant Start 86360 GEM296IS120IP 2 - F96T12 IS 120V Magnetic Ballast (806SLHTCP) 98
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
F48T12/
25W
1 120 Electronic - Program / Rapid Start 72110 GE140RS120-DIY 1 F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack 86
1 120 Magnetic - Rapid Start 89709 GEM140RS120DIY 1 - F40T12 F30T12 F48/25W 120V Magnetic Ballast (413CTCP) 93
F48T12/HO 2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1 - F96T12 HO RS 120 to 277 Multivolt ProLine®89
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1 - F96T12 HO RS 120 to 277 Multivolt ProLine®89
F48T8/HO 2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F4T5 1 277 Magnetic - Preheat 87634 GEM1CF579PH277 1 - CFT579Q9W/G23 Preheat 277 (4205F2P) 128
F54T5/HO
4 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
4 120-277 Electronic - Program / Rapid Start 29726 GE454MVPSN1 4,3,2 or 1 - F54T5HO 120-277V UltraStart® PRS Stick Can 81
3 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
3 120-277 Electronic - Program / Rapid Start 29726 GE454MVPSN1 4,3,2 or 1 - F54T5HO 120-277V UltraStart® PRS Stick Can 81
2 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
2 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
2 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 29726 GE454MVPSN1 4,3,2 or 1 - F54T5HO 120-277V UltraStart® PRS Stick Can 81
1 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
1 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
1 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
1 120-277 Electronic - Program / Rapid Start 29726 GE454MVPSN1 4,3,2 or 1 - F54T5HO 120-277V UltraStart® PRS Stick Can 81
F54T5/WM
4 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
3 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
2 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
1 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
1 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
F58T8
4 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
3 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
2 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
1 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
F58T8
(cont)
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
1 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
F60T12 2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
F60T12/HO 2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1 - F96T12 HO RS 120 to 277 Multivolt ProLine®89
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1- F96T12 HO RS 120 to 277 Multivolt ProLine®89
F60T8/HO 2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N.87 BF 52
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
F64T12 2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
F6T5 1 277 Magnetic - Preheat 87634 GEM1CF579PH277 1 - CFT579Q9W/G23 Preheat 277 (4205F2P) 128
F72T12
2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
2 277 Magnetic - Standard Instant Start 86379 GEM296IS277IP 2 - F96T12 IS 277V Magnetic Ballast (827SLHTCP) 98
2 120 Magnetic - Standard Instant Start 86360 GEM296IS120IP 2 - F96T12 IS 120V Magnetic Ballast (806SLHTCP) 98
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
1 277 Magnetic - Standard Instant Start 86381 GEM196IS277IP 1 - F96T12 IS 277 Magnetic Ballast (828BRTCP) 97
1 120 Magnetic - Standard Instant Start 86372 GEM196IS120IP 1 - F96T12 IS 120 Magnetic Ballast (822BRTCP) 97
F72T12/HO
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1- F96T12 HO RS 120 to 277 Multivolt ProLine®89
2 277 Electronic - Program / Rapid Start 80163 B295SR277HP 2 - F96T12HOES RS 277 88
2 277 Magnetic - Rapid Start 86171 GEM296HORS277IP 2 - F96T12HO RS 277V Magnetic Ballast (487SLHTCP) 99
2 120 Electronic - Standard Instant Start 80664 493B2 2 - F73T12/BL/HO Suntan 120 Magnetic Ballast 100
2 120 Electronic - Program / Rapid Start 80162 B295SR120HP 2 - F96T12HOES RS 120 88
2 120 Magnetic - Rapid Start 86164 GEM296HORS120IP 2 - F96T12HO F72T12HO RS 120V Magnetic Ballast (480SLHTCP) 99
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1 - F96T12 HO RS 120 to 277 Multivolt ProLine®89
F72T8 2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
F72T8/HO 2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
F73T12/HO 2 120 Electronic - Standard Instant Start 80664 493B2 2 - F73T12/BL/HO Suntan 120 Magnetic Ballast 100
F84T12 2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
F84T12/HO 2 277 Electronic - Program / Rapid Start 80163 B295SR277HP 2 - F96T12HOES RS 277 88
2 120 Electronic - Program / Rapid Start 80162 B295SR120HP 2 - F96T12HOES RS 120 88
F8T5 1 277 Magnetic - Preheat 87634 GEM1CF579PH277 1 - CFT579Q9W/G23 Preheat 277 (4205F2P) 128
F8T9 1 120 Electronic - Program / Rapid Start 97498 GE240RS120 2 F40 or F34T12 Rapid Start Electronic 120V “N” BF 85
F96T12
2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
2 277 Magnetic - Standard Instant Start 86379 GEM296IS277IP 2 - F96T12 IS 277V Magnetic Ballast (827SLHTCP) 98
2 120 Magnetic - Standard Instant Start 86360 GEM296IS120IP 2 - F96T12 IS 120V Magnetic Ballast (806SLHTCP) 98
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
1 277 Magnetic - Standard Instant Start 86381 GEM196IS277IP 1 - F96T12 IS 277 Magnetic Ballast (828BRTCP) 97
1 120 Magnetic - Standard Instant Start 86372 GEM196IS120IP 1 - F96T12 IS 120 Magnetic Ballast (822BRTCP) 97
F96T12/HO
1 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1 - F96T12 HO RS 120 to 277 Multivolt ProLine®89
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1 - F96T12 HO RS 120 to 277 Multivolt ProLine®89
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1- F96T12 HO RS 120 to 277 Multivolt ProLine®89
2 277 Electronic - Program / Rapid Start 80163 B295SR277HP 2 - F96T12HOES RS 277 88
2 277 Magnetic - Rapid Start 86171 GEM296HORS277IP 2 - F96T12HO RS 277V Magnetic Ballast (487SLHTCP) 99
2 120 Electronic - Program / Rapid Start 80162 B295SR120HP 2 - F96T12HOES RS 120 88
2 120 Magnetic - Rapid Start 86164 GEM296HORS120IP 2 - F96T12HO F72T12HO RS 120V Magnetic Ballast (480SLHTCP) 99
1 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1- F96T12 HO RS 120 to 277 Multivolt ProLine®89
30
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 31
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Linear Fluorescent Lamps
F96T12/
HO/WM
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1 - F96T12 HO RS 120 to 277 Multivolt ProLine®89
2 120-277 Electronic - Program / Rapid Start 72109 GE296HO-MV-N 2 or 1- F96T12 HO RS 120 to 277 Multivolt ProLine®89
F96T12/
WM
2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
2 277 Magnetic - Standard Instant Start 86379 GEM296IS277IP 2 - F96T12 IS 277V Magnetic Ballast (827SLHTCP) 98
2 120 Magnetic - Standard Instant Start 86360 GEM296IS120IP 2 - F96T12 IS 120V Magnetic Ballast (806SLHTCP) 98
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
1 277 Magnetic - Standard Instant Start 86381 GEM196IS277IP 1 - F96T12 IS 277 Magnetic Ballast (828BRTCP) 97
1 120 Magnetic - Standard Instant Start 86372 GEM196IS120IP 1 - F96T12 IS 120 Magnetic Ballast (822BRTCP) 97
F96T12/
WMP
2 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
1 120-277 Electronic - Multivolt Instant Start 24108 GE-260-IS-MV-N 2 or 1 - F96T12 Instant Start 120 to 277 87
F96T8
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
2 120-277 Electronic - Multivolt Instant Start 30194 GE-259-MV-N 2 or 1 - F96T8 120 to 277 “N”.87 BF Multivolt ProLine®51
2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
2 277 Electronic - Standard Instant Start 23678 GE-259-277-N 2 or 1 - F96T8 277v “N”.87 BF ProLine®57
2 120 Electronic - Standard Instant Start 23677 GE-259-120-N 2 or 1 - F96T8 120v Normal Light .87 BF ProLine®57
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49766 GE159MAX-N/ULTRA 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277 Electronic - Multivolt Instant Start 30195 GE-159-MV-N 1 - F96T8 120 to 277 “N.87 BF Multivolt ProLine®51
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277 Electronic - Multivolt Instant Start 30194 GE-259-MV-N 2 or 1 - F96T8 120 to 277 “N”.87 BF Multivolt ProLine®51
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
1 277 Electronic - Standard Instant Start 23678 GE-259-277-N 2 or 1 - F96T8 277v “N”.87 BF ProLine®57
1 120 Electronic - Standard Instant Start 23677 GE-259-120-N 2 or 1 - F96T8 120v Normal Light .87 BF ProLine®57
F96T8/HO 2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N.87 BF 52
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
F96T8/HO/
WM
2 277 Electronic - Program / Rapid Start 80163 B295SR277HP 2 - F96T12HOES RS 277 88
2 277 Magnetic - Rapid Start 86171 GEM296HORS277IP 2 - F96T12HO RS 277V Magnetic Ballast (487SLHTCP) 99
2 120 Electronic - Program / Rapid Start 80162 B295SR120HP 2 - F96T12HOES RS 120 88
2 120 Magnetic - Rapid Start 86164 GEM296HORS120IP 2 - F96T12HO F72T12HO RS 120V Magnetic Ballast (480SLHTCP) 99
F96T8/WM
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
2 120-277 Electronic - Multivolt Instant Start 30194 GE-259-MV-N 2 or 1 - F96T8 120 to 277 “N”.87 BF Multivolt ProLine®51
2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
2 277 Electronic - Standard Instant Start 23678 GE-259-277-N 2 or 1 - F96T8 277v “N”.87 BF ProLine®57
2 120 Electronic - Standard Instant Start 23677 GE-259-120-N 2 or 1 - F96T8 120v Normal Light .87 BF ProLine®57
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49766 GE159MAX-N/ULTRA 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277 Electronic - Multivolt Instant Start 30195 GE-159-MV-N 1 - F96T8 120 to 277 “N.87 BF Multivolt ProLine®51
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277 Electronic - Multivolt Instant Start 30194 GE-259-MV-N 2 or 1 - F96T8 120 to 277 “N”.87 BF Multivolt ProLine®51
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
1 277 Electronic - Standard Instant Start 23678 GE-259-277-N 2 or 1 - F96T8 277v “N”.87 BF ProLine®57
1 120 Electronic - Standard Instant Start 23677 GE-259-120-N 2 or 1 - F96T8 120v Normal Light .87 BF ProLine®57
F96T8/
WMP
2 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
2 120-277 Electronic - Multivolt Instant Start 30194 GE-259-MV-N 2 or 1 - F96T8 120 to 277 “N”.87 BF Multivolt ProLine®51
2 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
2 277 Electronic - Standard Instant Start 23678 GE-259-277-N 2 or 1 - F96T8 277v “N”.87 BF ProLine®57
2 120 Electronic - Standard Instant Start 23677 GE-259-120-N 2 or 1 - F96T8 120v Normal Light .87 BF ProLine®57
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49766 GE159MAX-N/ULTRA 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277 Electronic - Multivolt Instant Start 30195 GE-159-MV-N 1 - F96T8 120 to 277 “N.87 BF Multivolt ProLine®51
1 120-277
Electronic - High Efficiency
Multivolt Instant Start 49767 GE259MAX-N/ULTRA 2 or 1 - F96T8 120 to 277 “N” .87 BF UltraMax®45
1 120-277 Electronic - Multivolt Instant Start 30194 GE-259-MV-N 2 or 1 - F96T8 120 to 277 “N”.87 BF Multivolt ProLine®51
1 120-277 Electronic - Program / Rapid Start 30176 GE-286-HO-MV-N 2 or 1 - F96T8HO IS 120 to 277 “N”.87 BF 52
1 277 Electronic - Standard Instant Start 23678 GE-259-277-N 2 or 1 - F96T8 277v “N”.87 BF ProLine®57
1 120 Electronic - Standard Instant Start 23677 GE-259-120-N 2 or 1 - F96T8 120v Normal Light .87 BF ProLine®57
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Circleline Fluorescent Lamps
FC12T5HO
4 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
3 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
2 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
1 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
1 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
1 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
FC12T9
2 120 Electronic - Rapid Start 89717 GEM1FC12T9RS120 2 FC12T9 RS 120V Magnetic Ballast (449LRWSTCP) 92
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 5 - F40 or F34T12 Rapid Start 120V “N” BF ProLine® T12 85
1 120 Electronic - Program / Rapid Start 97498 GE240RS120 4 - F40 or F34T12 Rapid Start 120V “N” BF ProLine® T12 85
1 120 Magnetic - Rapid Start 89720 GEM1FC16T9RS120 2 - FC12T9 FC16T9 FC8T9 FC12T9 120V Magnetic (726VLHWSTCP) 91
FC16T9
1 120 Electronic - Program / Rapid Start 97499 GE240RS120 3 - F40 or F34T12 Rapid Start 120V “N” BF ProLine® T12
1 120 Magnetic - Rapid Start 89720 GEM1FC16T9RS120 2 - FC12T9 FC16T9 FC8T9 FC12T9 120V Magnetic (726VLHWSTCP) 91
1 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
FC6T9 1 120 Magnetic - Rapid Start 86227 GEM1FC8T9RS120IP 1 - FC8T9 RS 120V Magnetic Ballast (547RSWSTCP) 91
FC8T9 2 120 Electronic - Rapid Start 89717 GEM1FC12T9RS120 2 FC12T9 RS 120V Magnetic Ballast (449LRWSTCP) 92
1 120 Magnetic - Rapid Start 86227 GEM1FC8T9RS120IP 1 - FC8T9 RS 120V Magnetic Ballast (547RSWSTCP) 91
Compact Fluorescent Lamps
CFM36W/
2G10
2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
1 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
CFM42W 2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
1 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
CFM57W 1 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs124
CFM70W 1 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs124
CFQ13W/
2P
2 277 Magnetic - Preheat 87655 GEM2CF13PH277 2 - CFT/Q13W/GX23 Preheat 277 (4214PBES) 129
1 120 Magnetic - Preheat 87533 GEM1CF13PH120 1 - CFT/Q13W/GX23 Preheat 120 (4111H2P) 128
CFQ13W/
G24q
2 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
CFQ18W/
G24q
1 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
2 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
CFQ26W/2P 2 277 Magnetic - Preheat 87700 GEM2CF24PH277 2 - CFQ26W/G24d Preheat 277 (4226PBES) 129
CFQ26W/
G24q
2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
2 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
2 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
CFS16W/
GR10q
2 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
2 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
CFS21W/
GR10q
2 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
2 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
2 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
CFS28W/
GR10q
2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs
1 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
CFT13W/2P 2 277 Magnetic - Preheat 87655 GEM2CF13PH277 2 - CFT/Q13W/GX23 Preheat 277 (4214PBES) 129
1 120 Magnetic - Preheat 87533 GEM1CF13PH120 1 - CFT/Q13W/GX23 Preheat 120 (4111H2P) 128
32
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 33
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Compact Fluorescent Lamps
CFT5W/2P 1 277 Magnetic - Preheat 87634 GEM1CF579PH277 1 - CFT579Q9W/G23 Preheat 277 (4205F2P) 128
CFT7W/2P 1 277 Magnetic - Preheat 87634 GEM1CF579PH277 1 - CFT579Q9W/G23 Preheat 277 (4205F2P) 128
CFT9W/2P 1 277 Magnetic - Preheat 87634 GEM1CF579PH277 1 - CFT579Q9W/G23 Preheat 277 (4205F2P) 128
CFTR13W/
GX24q
2 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
CFTR18W/
GX24q
2 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
2 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71430 GEC213-MVPS-3W 2 or 1 - CFQ13W/G24q 120-277V ProLine® PS 3-Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71429 GEC213-MVPS-XX 2 or 1 - CFQ13W/G24q Bottom Exit 120-277V ProLine® PS 123
1 120-277 Electronic - Program / Rapid Start 71434 GEC218-MVPS-3W 2 or 1 - CFQ18W/G24q 120-277V ProLine® PS 3 Way Kit 123
1 120-277 Electronic - Program / Rapid Start 71433 GEC218-MVPS-XX 2 or 1 - CFQ18W/G24q Bottom Exit 120-277 ProLine® PS 123
CFTR26W/
2P 2 277 Magnetic - Preheat 87700 GEM2CF24PH277 2 - CFQ26W/G24d Preheat 277 (4226PBES) 129
CFTR26W/
GX24q
2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
2 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
2 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
CFTR32W/
GX24q
2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs
1 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
CFTR42W/
GX24q
1 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
1 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
FC12T5 2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
1 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
FC9T5 2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
FC9T5 &
FC12T5 1 & 1 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs
FT24W/
2G10
2 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 123
1 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 123
FT24W/
2G11
2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
2 120-277 Electronic - Program / Rapid Start 71445 GEC226-MVPS-3W
2 - CFQ26W, FT24 or 1-42W, CFTR32 3 Way Mounting Kit 120-277V
ProLine® PS 124
2 120-277 Electronic - Program / Rapid Start 71444 GEC226-MVPS-XX
2 - CFQ26W, FT24 or 1-42W, CFTR32 Bottom Exit 120-277V
ProLine® PS 124
FT24W/4P 2 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 79
1 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 79
FT39W/4P
4 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
3 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 47540 B239PUNV-DOG1C 2 - F39T5HO PRS UNV 50/60 Hz 79
2 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
2 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
2 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
2 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120 Electronic - Program / Rapid Start 97498 GE240RS120 6 - F40 or F34T12 Rapid Start 120V “N” BF ProLine® T12 85
2 120 Magnetic - Rapid Start 87623 GEM2FT36RS120 2 - FT36W/2G11 RS 120 (4150P) 130
1 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 79
1 120-277 Electronic - Program / Rapid Start 47534 B224PUNV-COG1C 2 - F24T5HO PRS UNV 50/60 Hz 79
1 120-277 Electronic - Program / Rapid Start 47540 B239PUNV-DOG1C 2 - F39T5HO PRS UNV 50/60 Hz 79
1 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
1 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
1 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
FT40W/4P
3 277 Electronic - Standard Instant Start 80691 C340SI277RH-IP 3 - FT40W/2G11 IS 277 127
3 120 Electronic - Standard Instant Start 80690 C340SI120RH-IP 3 - FT40W/2G11 IS 120 126
2 120-277 Electronic - Program / Rapid Start 80683 C240PUNVHP-B-IP 2 or 1 - FT40W2G11 PS UNV 125
2 277 Electronic - Standard Instant Start 80681 C240SI277RH-IP 2 - FT40W/2G11 IS 277 126
2 277 Electronic - Standard Instant Start 80691 C340SI277RH-IP 3 - FT40W/2G11 IS 277 127
2 120 Electronic - Standard Instant Start 80680 C240SI120RH-IP 2 - FT40W/2G11 IS 120 125
2 120 Electronic - Standard Instant Start 80690 C340SI120RH-IP 3 - FT40W/2G11 IS 120 126
2 120 Magnetic - Rapid Start 87625 GEM2FT40RS120 2 - FT40W/2G11RS RS 120 (4152P) 130
1 120-277 Electronic - Program / Rapid Start 80683 C240PUNVHP-B-IP 2 or 1 - FT40W2G11 PS UNV 125
1 277 Electronic - Standard Instant Start 80681 C240SI277RH-IP 2 - FT40W/2G11 IS 277 126
1 120 Electronic - Standard Instant Start 80680 C240SI120RH-IP 2 - FT40W/2G11 IS 120 125
Lamp Type
# of
Lamps Voltage Fluorescent Ballast Type
Ballast
Product
Code Ballast Description Fluorescent Ballast Long Description
Prod Code
Page No
Compact Fluorescent Lamps
FT50W/
2G11
4 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
3 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
2 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
1 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
1 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
FT55W/
2G11
4 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
3 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
2 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
2 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
1 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
1 120-277 Electronic - Program / Rapid Start 47542 B254PUNV-DGE1C 2 - F54T5HO PRS UNV 50/60 Hz 80
1 120-277 Electronic - Program / Rapid Start 47506 C242UNVBES-IP 2- 42 / 36 / 32 / 26 / 24 watt CFL UNV Bottom Exit w/Studs 124
1 120-277 Electronic - Program / Rapid Start 99651 GE254MVPS90-F 2 or 1 - F54T5HO 120 to 277 UltraStart® PRS High Temp F Can 80
1 120-277 Electronic - Program / Rapid Start 99649 GE454MVPS90-E 4-1 - F54T5HO 120 to 277 UltraStart® PRS High Temp E Can 81
34
Quick reference lamp to ballast selection guide (cont.)
See page 195 for warranty information. 35
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Lamp
Type
Use with ANSI
Lamp Types Wattage PC New GE Description Circuit Type Frame Size Voltage Cap. Ignitor
Prod Code
Page No
High Intensity Discharge (HID) Lamps
Metal
Halide
M110 50 86824 GEM50MLTLC3D-5 HX-HPF 3x4 120/208/240/277 6MFD 280V MH350-1A 144
M148 50 86824 GEM50MLTLC3D-5 HX-HPF 3x4 120/208/240/277 6MFD 280V MH350-1A 144
M143 70 86839 GEM7048TLC3D-5 HX-HPF 3x4 120/480 8MFD 280V MH350-1A 145
M143 70 86847 GEM70MLTLC3D-5 HX-HPF 3x4 120/208/240/277 8MFD 280V MH350-1A 144
M85 70 86576 11210277CTC000C HX-HPF F-Can 120/277 N/A N/A 174
M98 70 86578 11210506CTC000C HX-HPF F-Can 120/277 N/A N/A 174
M98 70 86839 GEM7048TLC3D-5 HX-HPF 3x4 120/480 8MFD 280V MH350-1A 145
M98 70 86847 GEM70MLTLC3D-5 HX-HPF 3x4 120/208/240/277 8MFD 280V MH350-1A 144
M140 100 86667 GEM10048TLC3D-5 HX-HPF 3x4 120/480 12MFD 280V MH350-1A 146
M140 100 86675 GEM100MLTLC3D-5 HX-HPF 4.25x5.75 120/208/240/277 12MFD 280V MH350-1A 145
M90 100 86574 11210239CTC000I HX-HPF F-Can 120/277 N/A N/A 175
M90 100 86667 GEM10048TLC3D-5 HX-HPF 3x4 120/480 12MFD 280V MH350-1A 146
M90 100 86675 GEM100MLTLC3D-5 HX-HPF 4.25x5.75 120/208/240/277 12MFD 280V MH350-1A 145
M92 100 86667 GEM10048TLC3D-5 HX-HPF 3x4 120/480 12MFD 280V MH350-1A 146
M92 100 86675 GEM100MLTLC3D-5 HX-HPF 4.25x5.75 120/208/240/277 12MFD 280V MH350-1A 145
M102 150 86711 GEM15048TLC3D-5 HX-HPF 3x4 120/480 16MFD 280V MH350-1A 147
M102 150 86718 GEM150MLTLC3D-5 HX-HPF 3x4 120/208/240/277 16MFD 280V MH350-1A 146
M107 150 86711 GEM15048TLC3D-5 HX-HPF 3x4 120/480 16MFD 280V MH350-1A 147
M107 150 86718 GEM150MLTLC3D-5 HX-HPF 3x4 120/208/240/277 16MFD 280V MH350-1A 146
M142 150 86711 GEM15048TLC3D-5 HX-HPF 3x4 120/480 16MFD 280V MH350-1A 147
M142 150 86718 GEM150MLTLC3D-5 HX-HPF 3x4 120/208/240/277 16MFD 280V MH350-1A 146
M57 175 86563 1110245SCTC000I CWA F-Can 120/277 N/A N/A 175
M57 175 87210 GEM175ML5AC3-5 CWA 3x4 120/208/240/277/480 10MFD 400V 147
M57 175 86741 GEM175MLTAC3-5 CWA 3x4 120/208/240/277 10MFD 400V 148
M58 250 86564 1110246CTC000C CWA F-Can 120/277 N/A N/A 176
M58 250 87211 GEM250ML5AC3-5 CWA 3x4 120/208/240/277/480 15MFD 400V 149
M58 250 87212 GEM250ML5AC4-5 CWA 4.25x4.75 120/208/240/277/480 15MFD 400V 150
M58 250 86765 GEM250MLTAC3-5 CWA 3x4 120/208/240/277 15MFD 400V 149
M59 400 42670 1110-247SC-TC CWA F-Can 120/277 N/A N/A 176
M59 400 80728 1111-247SCTC000I CWA F-Can 120/277 N/A N/A 177
M59 400 86803 GEM40048TAC4-5 CWA 4.25x4.75 120/480 24MFD 400V 151
M59 400 72300 GEM400ML5AA4-5 CWA 4.25x4.75 120/208/240/277/480 24MFD 400V
M59 400 72149 GEM400MLTAA4-5 CWA 4.25x4.75 120/208/240/277 24MFD 400V 151
M47 1000 86650 GEM100048TAC5-5 CWA 4.25x6.00 120/480 24MFD 480V 152
M47 1000 87213 GEM1000ML5AC5-5 CWA 4.25x6.00 120/208/240/277/480 24MFD 480V 152
M47 1000 86655 GEM1000MLTAC5-5 CWA 4.25x6.00 120/208/240/277 24MFD 480V 153
M48 1500 86693 GEM150048TAC5-5 CWA 4.25x6.00 120/480 32MFD 525V 153
M48 1500 86698 GEM1500MLTAC5-5 CWA 4.25x6.00 120/208/240/277 32MFD 525V 154
Pulse
Start
M156 20 87490 GEMH20-MLF-120 eHID 3.7x1.6x1.0 Side Lead 120 N/A N/A 135
M130 39 87501 GEMH39-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 135
C148 50 87516 GEMH50-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
M110 50 87516 GEMH50-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
M148 50 87516 GEMH50-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
C143 70 87531 GEMH70-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
C143 70 87546 GEMH70-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 137
M139 70 87531 GEMH70-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
M139 70 87531 GEMH70-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
M143 70 87531 GEMH70-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
M143 70 87546 GEMH70-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 137
M98 70 87531 GEMH70-MSF-120 eHID 3.7x3.0x1.2 Side Lead 120 N/A N/A 136
M98 70 87546 GEMH70-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 137
C140 100 87561 GEMH100-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 137
M140 100 87561 GEMH100-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 137
M90 100 87561 GEMH100-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 137
C142 150 87576 GEMH150-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 138
M102 150 87576 GEMH150-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 138
M142 150 87576 GEMH150-SLJ-MV eHID 7.3x2.6x2.2 BE w/Studs 120-277 N/A N/A 138
M137 175 86876 GEP17548TAC3-5 CWA 3x4 120/480 10MFD 400V MH350-1A 155
M137 175 86885 GEP175MLTAC3-5 CWA 3x4 120/208/240/277 10MFD 400V MH350-1A 155
M152 175 86876 GEP17548TAC3-5 CWA 3x4 120/480 10MFD 400V MH350-1A 155
M152 175 86885 GEP175MLTAC3-5 CWA 3x4 120/208/240/277 10MFD 400V MH350-1A 155
CMH250 250 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
CMH250 250 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M138 250 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
M138 250 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M138 250 86926 GEP25048TAC4-5 CWA 4.25x4.75 120/480 15MFD 400V MH350-1A 156
M138 250 86935 GEP250MLTAC4-5 CWA 4.25x4.75 120/208/240/277 15MFD 400V MH350-1A 156
M153 250 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
M153 250 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M153 250 86926 GEP25048TAC4-5 CWA 4.25x4.75 120/480 15MFD 400V 156
M153 250 86935 GEP250MLTAC4-5 CWA 4.25x4.75 120/208/240/277 15MFD 400V MH350-1A 156
CMH320 320 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
CMH320 320 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M132 320 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
M132 320 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M132 320 86952 GEP32048TAC4-5 CWA 4.25x4.75 120/480 21MFD 345V MH350-1A 157
M132 320 86959 GEP320MLTAC4-5 CWA 4.25x4.75 120/208/240/277 21MFD 345V MH350-1A 157
M132 320 86968 GEP320TRIAC4-5 CWA 4.25x4.75 120/277/347 21MFD 345V MH350-1A 158
Lamp
Type
Use with ANSI
Lamp Types Wattage PC New GE Description Circuit Type Frame Size Voltage Cap. Ignitor
Prod Code
Page No
High Intensity Discharge (HID) Lamps
Pulse
Start
(cont)
M154 320 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
M154 320 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M154 320 86952 GEP32048TAC4-5 CWA 4.25x4.75 120/480 21MFD 345V MH350-1A 157
M154 320 86959 GEP320MLTAC4-5 CWA 4.25x4.75 120/208/240/277 21MFD 345V MH350-1A 157
M154 320 86968 GEP320TRIAC4-5 CWA 4.25x4.75 120/277/347 21MFD 345V MH350-1A 158
CMH350 350 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
CMH350 350 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M131 350 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
M131 350 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M131 350 86984 GEP350277RCE-5 RX-NPF 3.75x4.5 277 22.5MFD 345V MH350-1A 158
M131 350 86984 GEP350MLTAC4-5 CWA 4.25x4.75 120/208/240/277 22.5MFD 345V MH350-1A 158
CMH400 400 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
CMH400 400 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M135 400 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
M135 400 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M135 400 86999 GEP40048TAC4-5 CWA 4.25x4.75 120/480 24MFD 400V MH350-1A 159
M135 400 87008 GEP400MLTAC4-5 CWA 4.25x4.75 120/208/240/277 24MFD 400V MH350-1A 159
M155 400 29377 GE-MH-250-400-MA eHID 208-277 N/A N/A 139
M155 400 89646 GEMH250-400MV50 eHID Dim 208-277 N/A N/A 139
M155 400 87008 GEP400MLTAC4-5 CWA 4.25x4.75 120/208/240/277 24MFD 400V MH350-1A 159
M155 400 86999 GEP40048TAC4-5 CWA 4.25x4.75 120/480 24MFD 400V MH350-1A 159
M149 750 46936 GEP75048TAC5-5 CWA 4.25x6.00 120/480 24MFD 400V MH750-1B 160
M149 750 46934 GEP750MLTAC5-5 CWA 4.25x6.00 120/208/240/277 24MFD 400V MH750-1B 160
M141 1000 72282 GEP1000ML5AC5-5 CWA 4.25x6.00 120/208/240/277/480 24MFD 480V HPS1000-4B 161
M141 1000 72281 GEP1000MLTAC5-5 CWA 4.25x6.00 120/208/240/277 24MFD 480V HPS1000-4B 161
High
Pressure
Sodium
S68 50 87152 GES50MLTLC3D-5 HX-HPF 3x4 120/208/240/277 5MFD 280V HPS150-3A 162
S62 70 86596 12210237CTC000I HX-HPF F-Can 120/277 N/A N/A 178
S62 70 86605 1233142U000I R-HPF, R-NPF 2.81x3.94 120 178
S62 70 86456 GES7048TLC3D-5 HX-HPF 3x4 120/480 7MFD 300V HPS150-3A 163
S62 70 86587 GES70MLTLC3D-5 HX-HPF 3x4 120/208/240/277 7MFD 300V HPS150-3A 162
S54 100 87068 GES10048TLC3D-5 HX-HPF 3x4 120/480 10MFD 280V 164
S54 100 87074 GES100MLTLC3D-5 HX-HPF 3x4 120/208/240/277 10MFD 280V HPS150-3A 163
S55 150 86606 1233154U000I R-NPF 2.81x3.94 120 179
S55 150 87087 GES15048TLC3D-5 HX-HPF 3x4 120/480 14MFD 280V HPS150-3A 165
S55 150 87094 GES150MLTLC3D-5 HX-HPF 3x4 120/208/240/277 14MFD 280V HPS150-3A 164
S50 250 87214 GES250ML5AC4-5 CWA 4.25x4.75 120/208/240/277/480 35MFD 240V HPS400-3A 166
S50 250 87121 GES250MLTAC4-5 CWA 4.25x4.75 120/208/240/277 35MFD 240V HPS400-3A 166
S51 400 87198 GES40048TAC4-5 CWA 4.25x4.75 120/480 55MFD 240V HPS400-3A 168
S51 400 87215 GES400ML5AC4-5 CWA 4.25x4.75 120/208/240/277/480 55MFD 240V HPS400-3A 167
S51 400 87164 GES400MLTAC4-5 CWA 4.25x4.75 120/208/240/277 55MFD 240V HPS400-3A 167
S52 1000 87048 GES100048TAC5-5 CWA 4.25x6.00 120/480 26MFD 525V HPS24 168
S52 1000 87218 GES1000ML5AC5-5 CWA 4.25x6.00 120/208/240/277/480 26MFD 525V HPS1000-4B 169
S52 1000 87056 GES1000MLTAC5-5 CWA 4.25x6.00 120/208/240/277 26MFD 525V HPS1000-4B 169
Mercury
H39 175 87210 GEM175ML5AC3-5 CWA 3x4 120/208/240/277/480 10MFD 400V 147
H39 175 86741 GEM175MLTAC3-5 CWA 3x4 120/208/240/277 10MFD 400V 148
H37 250 87211 GEM250ML5AC3-5 CWA 3x4 120/208/240/277/480 15MFD 400V 149
H37 250 87212 GEM250ML5AC4-5 CWA 4.25x4.75 120/208/240/277/480 15MFD 400V 150
H37 250 86765 GEM250MLTAC3-5 CWA 3x4 120/208/240/277 15MFD 400V 149
H33 400 86803 GEM40048TAC4-5 CWA 4.25x4.75 120/480 24MFD 400V 151
H33 400 72300 GEM400ML5AA4-5 CWA 4.25x4.75 120/208/240/277/480 24MFD 400V 150
H33 400 72149 GEM400MLTAA4-5 CWA 4.25x4.75 120/208/240/277 24MFD 400V 151
H36 1000 86650 GEM100048TAC5-5 CWA 4.25x6.00 120/480 24MFD 480V 152
H36 1000 87213 GEM1000ML5AC5-5 CWA 4.25x6.00 120/208/240/277/480 24MFD 480V 152
H36 1000 86655 GEM1000MLTAC5-5 CWA 4.25x6.00 120/208/240/277 24MFD 480V 153
See page 195 for warranty information. 37
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Understanding T8
Fluorescent Ballasts
A comprehensive range of solutions…from GE, the name you trust.
GE introduced the first fluorescent ballast more than 60 years ago. Today we are providing
high-frequency electronic ballasts for almost every fluorescent application.
With our UltraMax® and UltraStart® ballasts, we are bringing you
the future in ballast performance.
GE revolutionizes lighting again with breakthrough technology. Our patented UltraMax®
instant-start and UltraStart® programmed start electronic ballasts transform the power of
light into efficiency and savings from store shelves to the installation site. The foundation of
the “Ultra” family of ballasts starts with its high efficiency ratings. High efficiency ballasts
are a minimum of 90% efficiency with some ballasts nearly 95% efficient which means the
ballast only consumes 5-10% of the total system power. These high efficiency ballasts exceed
minimum high efficiency standards as established by almost all energy advocate groups,
utility rebate programs and the NEMA Premium® ballast program. The ballasts are marked with
the Ultra brand as well as the NEMA Premium® ballast mark. These ballasts have multi-voltage
control (MVC), which automatically adjusts to handle voltage from 120V through 277V. That
cuts the ballast models you need to stock from 40 down to 13, which can dramatically reduce
inventory carrying costs. UltraMax® ballasts have ArcGuard Protection, too, with a UL Type
CC Anti-Arc Rating. Plus, they’re ultra-lamp-friendly, with a low lamp current crest factor of
1.4 for optimal lamp performance. Both UltraMax® and UltraStart® have anti-striation control
for better light quality with no lamp striations (spiraling). And the small, low-profile design of
these ballasts makes retrofits effortless at the job site. Also unique to our programmed start
UltraStart® ballasts is parallel lamp operation which ensures if one lamp fails the others remain
on, and quick starting times of less than 700 milliseconds which is necessary in avoiding delays
with automatic sensors.
Electronic Instant Start
The most common fluorescent ballast is the instant start and is used
typically in long 3 to 10-hour lamp cycle applications. These ballasts
are energy efficient and can deliver up to 20% to greater than 40%
energy savings when installed with energy-efficient lamps in building
retrofits. These ballasts deliver >550 open circuit volts when starting
lamps and operate lamps at high frequencies which offers flicker-free
operation and better lamp efficiencies. The ballasts are significantly
quieter than conventional magnetic ballasts and are backed by
GE’s ultra system 5-year ballast limited warranty and extended
lamp warranties.
UltraMax®
A family of high-efficiency GE T8 instant-start electronic linear
fluorescent ballasts designed to optimize GE’s T8 Ultra lamps for
optimal system energy savings. UltraMax® ballasts have a low lamp
current crest factor and virtually “read” and adapt to incoming voltage
from 108V to 305V. Other features include UL Type CC Anti-Arc Rating
and anti-striation control to eliminate lamp striations and spiraling.
These ballasts are offered in ballast factors: low wattage (.77), normal
light (.87), normal-high (N+) (1.0) and high (>1.15).
ProLine®
Offered in dedicated or multi-volt (120-277V), these high-performance
T8 instant-start ballasts also meet minimum efficiency requirements
as established with the NEMA Premium® ballast program. These
ballasts are offered in ballast factors: low wattage (.77), normal light
(.87), and high (>1.15).
Programmed Start
Programmed Start electronic ballasts have a lamp starting method
that preheats lamp filaments while not allowing the lamp to ignite
and then applies an open circuit voltage (OCV) to start the lamp. Use
Programmed Start ballasts to ensure long lamp life when turning
lamps on and off more than five times in a day or in conjunction with
any automatic light control or sensor. This type of starting circuit
keeps lamp-end blackening to a minimum and improves lamp
life performance, especially in applications where the lamps are
frequently switched on and off.
UltraStart®
UltraStart® is a family of high-efficiency GE Programmed Start
electronic linear fluorescent ballasts that also exceed NEMA Premium®
ballast efficiency requirements but are designed to optimize GE’s
T8 Ultra lamps in frequently switched applications. Instant start
ballasts provide 7,000-13,000 starts before 50% lamp failure.
UltraStart®provides greater than 100,000 starts before 50% lamp
failure. UltraStart® ballasts have the same energy savings and
convenience of instant start ballasts but with the long lamp life of
a programmed start ballast. These ballasts are offered in ballast
factors: programmed start x-low wattage (XL) (.60), low wattage (.71),
normal light (.87), and high (>1.15).
Ballast Date Codes
Date Codes
GE electronic ballast manufacturing date codes are located on
the upper right-hand corner of the label. The code lists the month,
year and day of manufacture. A typical code is C06-073, where
the month is listed as A (January), B (February), C (March) (as in this
code) followed by the year 06 (2006) and the date of manufacture
073 (the 73rd day of 2006).
Ballast Life
GE electronic ballasts are designed and manufactured to an
average life expectancy of 60,000 hours of operation at maximum
rated case temperatures. As a rule of thumb, ballast life is doubled
for every 10C reduction in ballast case temperature. However
there are other variables such as transients, voltage sags and
swells, ambient temperature, etc., which affect ballast life as well.
Instant Start vs. Rapid Start Sockets
When using programmed start or dimming ballasts in fixtures,
sockets must be 2-pin rapid start type. Fixtures with T8 instant
start ballasts must use jumpered rapid start sockets or shunted
lamp holders (internal to the lamp holder) that bridge the lamp
bi-pins together into one contact on each side of the lamp. If
retrofitting from a instant start ballast fixture with shunted
sockets to a dimming or programmed start ballast, rapid start
type sockets must be used to properly start lamps and maintain
rated lamp life.
GE Fluorescent Ballast Types
36
GE Ballast Electronic nomenclature
GE-2 32-MVPS-N-42T
Maximum
number
of lamps
supported
by this ballast
– 1, 2, 3, 4, 6
IS = Instant Start,
standard if not shown
RS = Rapid Start
PS = Program Start
120 = 120 volt
277 = 277 volt
MAX or MV =
120 – 277V
Lamp Watts
(Primary Lamp)
T8 = 32-four foot,
59-eight foot
T12 = 40-four foot,
60-eight foot Ballast Factor
L =Low Power for
MAX savings
N = Normal for
New Fixtures
H = High Power,
Hi-Light, Hi-Bay
GE Ballast
GE = LFL
GEC = CFL
Ultra-Hi Efficiency
84T, 42T, T = 840, 420 qty
OEM pallet packs
A, D, E, F = Can sizes
BES = Bottom exit with studs
SE = Dual – side & bottom exit
3W = 3 way mounting kit
38 See page 195 for warranty information. 39
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
72258 – GE132MAX-L/ULTRA (replaces 49706)
UltraMax® Instant Start Multi-Voltage High-Efficiency
1 – F32T8 120 to 277 “L” .77 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Dimensions
Wiring diagram – LFL 1A – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Red 41 in (1041 mm)
White 25 in (635 mm)
Blue 34 in (864 mm)
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
1 120 28 0.24 A 0.87 3.10 99 1.5 10 -22 / -30
1 277 28 0.11 A 0.87 3.10 98 1.5 10 -22 / -30
F32T8/WM
1 120 27 0.23 A 0.87 3.22 99 1.5 10 60 / 16
1 277 27 0.10 A 0.87 3.22 98 1.5 10 60 / 16
F28T8
1 120 25 0.22 A 0.87 3.48 99 1.5 10 60 / 16
1 277 25 0.10 A 0.87 3.48 98 1.5 10 60 / 16
F25T12
1 120 25 0.22 A 99 1.5 10 0 / -18
1 277 25 0.10 A 94 1.5 17 0 / -18
F25T8
1 277 24 0.09 A 93 1.5 18 0 / -18
1 120 23 0.19 A 99 1.5 10 0 / -18
F17T8
1 120 17 0.14 A 99 1.5 10 0 / -18
1 277 17 0.07 A 90 1.5 22 0 / -18
FE15T8
1 120 14 0.12 A 99 1.5 11 0 / -18
1 277 14 0.06 A 88 1.5 25 0 / -18
Other compatible lamps: F32T8/25W
72259 – GE-132MAX-N/ULTRA (replaces 49771)
UltraMax® Instant Start Multi-Voltage High-Efficiency
1 – F32T8 120 to 277 “N” .87 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1A – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue 34 in (864 mm)
Red 41 in (1041 mm)
White 25 in (635 mm)
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
1 120 25 0.22 A 0.77 3.08 99 1.5 10 -22 / -30
1 277 25 0.10 A 0.77 3.08 94 1.5 10 -22 / -30
F32T8/WM
1 120 24 0.21 A 0.77 3.20 99 1.5 10 60 / 16
1 277 24 0.09 A 0.77 3.20 93 1.5 10 60 / 16
F28T8
1 120 22 0.20 A 0.77 3.50 99 1.5 10 60 / 16
1 277 22 0.09 A 0.77 3.50 93 1.5 10 60 / 16
F25T8
1 120 21 0.18 A 99 1.5 10 0 / -18
1 277 21 0.08 A 92 1.5 20 0 / -18
F25T12
1 120 21 0.19 A 99 1.5 10 0 / -18
1 277 21 0.09 A 92 1.5 20 0 / -18
F17T8
1 120 15 0.13 A 99 1.5 12 0 / -18
1 277 15 0.07 A 88 1.5 25 0 / -18
FE15T8
1 120 12 0.10 A 86 1.5 13 0 / -18
1 277 12 0.05 A 99 1.5 27 0 / -18
Other compatible lamps: F32T8/25W
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72258
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72259 72260 (replaces 23939)
• Energy-saving high-efficiency instant-start electronic ballast (>90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70kHz
• Energy-saving high-efficiency instant-start electronic ballast (>90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70kHz
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
49775 – GE232MAX-H/ULTRA
UltraMax® Instant Start Multi-Voltage High-Efficiency
2 or 1 – F32T8 120 to 277 “H” 1.15 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Dimensions
Wiring diagram LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue 34 in (864 mm)
White 25 in (635 mm)
Red 41 in (1041 mm)
72262 – GE232MAX-L/ULTRA (replaces 49707)
UltraMax® Instant Start Multi-Voltage High-Efficiency
2 or 1 – F32T8 120 to 277 “L” .77 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
White 25 in (635 mm)
Blue 34 in (864 mm)
Red 41 in (1041 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
49775 47548
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72262 72256 (replaces 47546)
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70kHz
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 74 0.62 A 1.15 1.55 99 1.5 10 0 / -18
2 277 73 0.27 A 1.15 1.57 98 1.5 10 0 / -18
1 277 41 0.16 A 1.15 2.80 96 1.5 10 0 / -18
1 120 40 0.36 A 1.15 2.87 99 1.5 10 0 / -18
F32T8/WM
2 120 71 0.59 A 1.15 1.61 99 1.5 10 60 / 16
2 277 70 0.26 A 1.15 1.64 98 1.5 10 60 / 16
1 120 39 0.34 A 1.15 2.94 99 1.5 10 60 / 16
1 277 39 0.15 A 1.15 2.94 96 1.5 10 60 / 16
F28T8
2 120 66 0.58 A 1.15 1.74 99 1.5 10 60 / 16
2 277 65 0.26 A 1.15 1.76 97 1.5 10 60 / 16
1 120 36 0.32 A 1.15 3.19 99 1.5 10 60 / 16
1 277 36 0.15 A 1.15 3.19 96 1.5 10 60 / 16
Other compatible lamps: FE15T8, F40T8, F25T8, F25T12, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 51 0.42 A 0.78 1.53 99 1.5 10 -22/ -30
2 277 50 0.19 A 0.78 1.56 97 1.5 10 -22/ -30
1277 29 0.11 A 0.77 2.65 93 1.5 10 -22/ -30
1 120 28 0.24 A 0.77 2.75 99 1.5 10 -22/ -30
F32T8/WM
2 120 47 0.40 A 0.77 1.64 99 1.5 10 60 / 16
2 277 47 0.18 A 0.77 1.63 97 1.5 10 60 / 16
1 277 27 0.11 A 0.77 2.85 93 1.5 10 60 / 16
1 120 26 0.22 A 0.77 2.96 99 1.5 10 60 / 16
F28T8
2 120 43 0.38 A 0.74 1.72 99 1.5 10 60 / 16
2 277 43 0.18 A 0.74 1.72 97 1.5 10 60 / 16
1 277 25 0.10 A 0.77 3.08 92 1.5 10 60 / 16
1 120 24 0.21 A 0.77 3.20 99 1.5 10 60 / 16
F25T12
2 120 42 0.36 A 99 1.5 10 0 / -18
2 277 42 0.16 A 96 1.5 19 0 / -18
1 120 24 0.21 A 99 1.5 11 0 / -18
1 277 24 0.10 A 91 1.5 20 0 / -18
Other compatible lamps: F25T8, FE15T8, F17T8, F32T8/25W
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor NRCan UL Type CC RoHS Compliant UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type CC UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor NRCan UL Type HL FCC – CLASS A Non-Consumer RoHS Compliant UL Class P cUL Listed UL Type CC UL Listed
Safety and performance
40 See page 195 for warranty information. 41
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
72266 – GE232MAX-N/ULTRA (replaces 49772)
UltraMax® Instant Start Multi-Voltage High-Efficiency
2 or 1 – F32T8 120 to 277 “N” .87 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Dimensions
Wiring diagram LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue 34 in (864 mm)
Red 41 in (1041 mm)
White 25 in (635 mm)
71421 – GE232MAX-N+
UltraMax® Instant Start Multi-Voltage High-Efficiency
2 or 1 – F32T8 120 to 277 “N+” 1.0 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 41 in (1041 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
Blue 34 in (864 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72266 72267 (replaces 31052) 72268 (replaces 23940)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71421
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70kHz
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
71714 – GE332MAX-H/ULTRA (replaces 49776)
UltraMax® Instant Start Multi-Voltage High-Efficiency
3 or 2 – F32T8 120 to 277 “H” 1.18 BF UltraMax®
71717 – GE332MAX-L/ULTRA (replaces 49708)
UltraMax® Instant Start Multi-Voltage High-Efficiency
3 or 2 – F32T8 120 to 277 “L” .77 BF UltraMax®
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70 kHz
• UL 55C Ambient Temperature rating
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70 kHz
• UL 55C Ambient Temperature rating
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2120 54 0.47 A 0.87 1.61 99 1.5 10 -22/ -30
2 277 53 0.21 A 0.87 1.64 96 1.5 10 -22/ -30
1 120 31 0.26 A 0.87 2.80 99 1.5 10 -22/ -30
1 277 31 0.12 A 0.87 2.80 94 1.5 10 -22/ -30
F32T8/WM
2 120 53 0.45 A 0.87 1.64 99 1.5 10 60 / 16
2 277 52 0.20 A 0.87 1.67 96 1.5 10 60 / 16
1 120 29 0.25 A 0.87 3.00 99 1.5 10 60 / 16
1 277 29 0.12 A 0.87 3.00 94 1.5 10 60 / 16
F28T8
2 120 49 0.42 A 0.87 1.77 99 1.5 10 60 / 16
2 277 48 0.19 A 0.87 1.81 96 1.5 10 60 / 16
1 120 27 0.24 A 0.87 3.22 99 1.5 10 60 / 16
1 277 27 0.11 A 0.87 3.22 93 1.5 10 60 / 16
F25T12
2 120 48 0.41 A 99 1.5 10 0 / -18
2 277 48 0.18 A 97 1.5 16 0 / -18
1 120 27 0.24 A 99 1.5 10 0 / -18
1 277 27 0.11 A 93 1.5 22 0 / -18
Other compatible lamps: FE15T8, F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 63 0.53 A 1.00 1.59 99 1.5 10 -22/ -30
2 277 62 0.23 A 1.00 1.61 98 1.5 10 -22/ -30
1 277 35 0.13 A 0.96 2.77 96 1.5 10 -22/ -30
1120 34 0.29 A 0.96 2.81 99 1.5 10 -22/ -30
F32T8/WM
2 120 60 0.50 A 1.00 1.67 99 1.5 10 60 / 16
2 277 60 0.22 A 1.00 1.68 98 1.5 10 60 / 16
1 277 33 0.13 A 0.97 2.91 96 1.5 10 60 / 16
1 120 33 0.28 A 0.97 2.96 99 1.5 10 60 / 16
F28T8
2 120 58 0.48 A 1.00 1.79 99 1.5 10 60 / 16
2 277 57 0.21 A 1.00 1.75 98 1.5 10 60 / 16
1 120 32 0.26 A 0.98 3.11 99 1.5 10 60 / 16
1 277 32 0.12 A 0.97 3.02 96 1.5 10 60 / 16
F25T12
2 120 56 0.47 A 0.97 1.74 99 1.5 10 0 / -18
2 277 56 0.21 A 0.97 1.75 98 1.5 15 0 / -18
1 120 31 0.26 A 0.95 3.11 99 1.5 10 0 / -18
1 277 31 0.12 A 0.95 3.05 96 1.5 18 0 / -18
Other compatible lamps: FE15T8, F25T8, F17T8, F40T8, F32T8/25W
UL Type 1 Outdoor RoHS Compliant UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC NRCan UL Listed
Safety and performance
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 34 in (864 mm)
Red 41 in (1041 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71714 71715 (replaces 47549)
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 111 0.92 A 1.18 1.06 99 1.5 10 -22/ -30
3 277 109 0.40 A 1.18 1.08 98 1.5 10 -22/ -30
2 120 77 0.68 A 1.15 1.49 99 1.5 10 -22/ -30
2 277 76 0.30 A 1.15 1.51 97 1.5 10 -22/ -30
F32T8/WM
3 120 106 0.89 A 1.15 1.08 99 1.5 10 60 / 16
3 277 104 0.39 A 1.15 1.10 98 1.5 10 60 / 16
2 120 73 0.65 A 1.15 1.57 99 1.5 10 60 / 16
2 277 73 0.28 A 1.15 1.57 97 1.5 10 60 / 16
F28T8
3 120 98 0.86 A 1.15 1.17 99 1.5 10 60 / 16
3 277 96 0.37 A 1.15 1.19 98 1.5 10 60 / 16
2 120 68 0.59 A 1.15 1.69 99 1.5 10 60 / 16
2 277 67 0.26 A 1.15 1.71 97 1.5 10 60 / 16
F25T12
3 120 98 0.86 A 99 1.5 10 0 / -18
3 277 96 0.37 A 98 1.5 13 0 / -18
2 120 68 0.60 A 99 1.5 10 0 / -18
2 277 68 0.26 A 97 1.5 17 0 / -18
Other compatible lamps: FE15T8, F40T8, F25T8, F17T8, F32T8/25W
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor RoHS Compliant UL Type CC UL Type HL NRCan FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Dimensions
Wiring diagram LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Red 41 in (1041 mm)
White 25 in (635 mm)
Blue 34 in (864 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71717 71718 (replaces 31055)
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 73 0.63 A 0.77 1.05 99 1.5 10 -22/ -30
3 277 72 0.27 A 0.77 1.06 98 1.5 10 -22/ -30
2 120 53 0.45 A 0.77 1.45 99 1.5 10 -22/ -30
2 277 53 0.20 A 0.77 1.45 97 1.5 10 -22/ -30
F32T8/WM
3 120 69 0.60 A 0.77 1.11 99 1.5 10 60 / 16
3 277 68 0.26 A 0.77 1.13 98 1.5 10 60 / 16
2 120 49 0.42 A 0.77 1.57 99 1.5 10 60 / 16
2 277 49 0.19 A 0.77 1.57 97 1.5 10 60 / 16
F28T8
3 120 65 0.57 A 0.77 1.18 99 1.5 10 60 / 16
3 277 65 0.25 A 0.77 1.18 98 1.5 10 60 / 16
2 120 46 0.40 A 0.77 1.67 99 1.5 10 60 / 16
2 277 46 0.18 A 0.77 1.67 96 1.5 10 60 / 16
F25T12
3 120 63 0.53 A 99 1.5 10 0 / -18
3 127 63 0.24 A 97 1.5 13 0 / -18
2 120 63 0.56 A 99 1.5 18 0 / -18
2 277 63 0.25 A 97 1.5 10 0 / -18
Other compatible lamps: FE15T8, F25T8, F17T8, F32T8/25W
UL Type 1 Outdoor UL Type CC UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
42 See page 195 for warranty information. 43
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
71719 GE332MAX-N/ULTRA (replaces 49773)
UltraMax® Instant Start Multi-Voltage High-Efficiency
3 or 2 – F32T8 120 to 277 “N” .87 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 221°F (105°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal – High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Dimensions
Wiring diagram LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 34 in (864 mm)
White and Black 25 in (635 mm)
Red 41 in (1041 mm)
Blue 34 in (864 mm)
71422 – GE332MAX-N+
UltraMax® Instant Start Multi-Voltage High-Efficiency
3 or 2 – F32T8 120 to 277 “N+” 1.0 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
White 25 in (635 mm)
Red 41 in (1041 mm)
Blue 34 in (864 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71719 71721 (replaces 31053) 71722 (replaces 23941)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71422
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70 kHz
• UL 55C Ambient Temperature rating
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
71723 – GE432MAX-H/ULTRA (replaces 49777)
UltraMax® Instant Start Multi-Voltage High-Efficiency
4 or 3 – F32T8 120 to 277 “H” 1.18 BF UltraMax®
Dimensions
Wiring diagram LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 34 in (864 mm)
Black 25 in (635 mm)
White 25 in (635 mm)
Yellow 41 in (1041 mm)
71725 – GE432MAX-L/ULTRA (replaces 49709)
UltraMax® Instant Start Multi-Voltage High-Efficiency
4 or 3 – F32T8 120 to 277 “L” .77 BF UltraMax®
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Red 34 in (864 mm)
Blue 34 in (864 mm)
Yellow 41 in (1041 mm)
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71723 71724 (replaces 47550)
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71725 71726 (replaces 47547)
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70 kHz
• UL 55C Ambient Temperature rating
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70 kHz
• UL 55C Ambient Temperature rating
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 82 0.70 A 0.87 1.06 99 1.5 10 -22/ -30
3 277 80 0.30 A 0.87 1.08 98 1.5 10 -22/ -30
2 120 58 0.49 A 0.87 1.50 99 1.5 10 -22/ -30
2 277 58 0.22 A 0.87 1.50 97 1.5 10 -22/ -30
F32T8/WM
3 120 78 0.66 A 0.87 1.11 99 1.5 10 60 / 16
3 277 77 0.29 A 0.87 1.12 98 1.5 10 60 / 16
2 120 55 0.46 A 0.87 1.58 99 1.5 10 60 / 16
2 277 55 0.21 A 0.87 1.58 97 1.5 10 60 / 16
F28T8
3 120 72 0.63 A 0.87 1.20 99 1.5 10 60 / 16
3 277 71 0.28 A 0.87 1.22 98 1.5 10 60 / 16
2 120 51 0.44 A 0.87 1.70 99 1.5 10 60 / 16
2 277 51 0.20 A 0.87 1.70 97 1.5 10 60 / 16
F25T12
3 120 72 0.61 A 99 1.5 10 0 / -18
3 277 71 0.27 A 98 1.5 13 0 / -18
2 120 49 0.44 A 99 1.5 10 0 / -18
2 277 49 0.19 A 97 1.5 16 0 / -18
Other compatible lamps: FE15T8, F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 91 0.77 A 1.00 1.09 99 1.5 10 -22/ -30
3 277 90 0.33 A 1.00 1.11 98 1.5 10 -22/ -30
2120 64 0.54 A 0.94 1.47 99 1.5 10 -22/ -30
2277 64 0.24 A 0.94 1.48 97 1.5 10 -22/ -30
F32T8/WM
3 120 87 0.73 A 1.00 1.15 99 1.5 10 60 / 16
3 277 86 0.32 A 1.00 1.17 98 1.5 10 60 / 16
2 120 61 0.52 A 0.95 1.55 99 1.5 10 60 / 16
2 277 61 0.23 A 0.95 1.56 97 1.5 10 60 / 16
F28T8
3 120 83 0.69 A 1.00 1.21 99 1.5 10 60 / 16
3 277 82 0.30 A 1.00 1.23 98 1.5 10 60 / 16
2 120 59 0.50 A 0.96 1.62 99 1.5 10 60 / 16
2 277 59 0.22 A 0.95 1.62 97 1.5 10 60 / 16
F25T12
3 120 80 0.67 A 0.93 1.16 99 1.5 10 0 / -18
3 277 79 0.29 A 0.93 1.18 98 1.5 16 0 / -18
2 120 57 0.48 A 0.93 1.63 99 1.5 10 0 / -18
2 277 57 0.22 A 0.93 1.65 97 1.5 19 0 / -18
Other compatible lamps: F25T8, F15T8, F40T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 148 1.36 A 1.18 0.80 99 1.5 10 -22/ -30
4 277 145 0.59 A 1.18 0.81 98 1.5 10 -22/ -30
3 120 115 1.04 A 1.15 1.00 99 1.5 10 -22/ -30
3 277 113 0.45 A 1.15 1.01 97 1.5 10 -22/ -30
F32T8/WM
4 120 145 1.31 A 1.15 0.79 99 1.5 10 60 / 16
4 277 141 0.56 A 1.15 0.81 97 1.5 10 60 / 16
3 120 110 0.99 A 1.15 1.04 99 1.5 10 60 / 16
3 277 109 0.43 A 1.15 1.05 97 1.5 10 60 / 16
F25T12
4 120 134 1.21 A 99 1.5 10 0 / -18
4 277 132 0.52 A 97 1.5 14 0 / -18
3 120 102 0.92 A 99 1.5 10 0 / -18
3 277 101 0.40 A 97 1.5 17 0 / -18
F28T8
4 120 133 1.20 A 1.15 0.86 99 1.5 10 60 / 16
4 277 131 0.52 A 1.15 0.87 98 1.5 10 60 / 16
3 120 101 0.91 A 1.15 1.13 99 1.5 10 60 / 16
3 277 100 0.40 A 1.15 1.15 97 1.5 10 60 / 16
Other compatible lamps: FE15T8, F40T8, F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 97 0.84 A 0.77 0.79 99 1.5 10 -22/ -30
4 277 96 0.37 A 0.77 0.80 98 1.5 10 -22/ -30
3120 78 0.65 A 0.77 0.98 99 1.5 10 -22/ -30
3 277 77 0.29 A 0.77 1.00 97 1.5 10 -22/ -30
F32T8/WM
4 120 92 0.80 A 0.77 0.83 99 1.5 10 60 / 16
4 277 91 0.36 A 0.77 0.84 98 1.5 10 60 / 16
3 120 72 0.61 A 0.77 1.06 99 1.5 10 60 / 16
3 277 72 0.27 A 0.77 1.06 97 1.5 10 60 / 16
F28T8
4 120 87 0.77 A 0.77 0.88 99 1.5 10 60 / 16
4 277 86 0.34 A 0.77 0.89 98 1.5 10 60 / 16
3 120 67 0.59 A 0.77 1.14 99 1.5 10 60 / 16
3 277 67 0.26 A 0.77 1.14 97 1.5 10 60 / 16
F25T12
4 120 84 0.71 A 99 1.5 10 0 / -18
4 277 83 0.31 A 97 1.5 15 0 / -18
3 120 65 0.58 A 99 1.5 10 0 / -18
3 277 65 0.25 A 97 1.5 18 0 / -18
Other compatible lamps: FE15T8, F25T8, F17T8, F32T8/25W
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC UL Listed RoHS Compliant
Safety and performance
RoHS Compliant UL Type 1 Outdoor UL Type CC UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type CC UL Type HL FCC – CLASS A Non-Consumer RoHS Compliant UL Class P cUL Listed UL Listed
Safety and performance
44 See page 195 for warranty information. 45
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
71727 – GE432MAX-N/ULTRA (replaces 49774)
UltraMax® Instant Start Multi-Voltage High-Efficiency
4 or 3 – F32T8 120 to 277 “N” .87 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 221°F (105°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal – High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Dimensions
Wiring diagram LFL 1D – see example on page 72
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.16 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Yellow 41 in (1041 mm)
Blue and Red 34 in (864 mm)
White and Black 25 in (635 mm)
Black 25 in (635 mm)
71423 – GE432MAX-N+
UltraMax® Instant Start Multi-Voltage High-Efficiency
4 or 3 – F32T8 120 to 277 “N+” 1.0 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 34 in (864 mm)
White 25 in (635 mm)
Yellow 41 in (1041 mm)
Black 25 in (635 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71727 71729 (replaces 31054) 71730 (replaces 23942)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71423
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Anti-striation control for better light quality, with no striations
• Lamp frequency >70 kHz
• UL 55C Ambient Temperature rating
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
49766 – GE159MAX-N/ULTRA
UltraMax® Instant Start Multi-Voltage High-Efficiency
1 – F96T8 120 to 277 “N” .87 BF UltraMax®
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Dimensions
Wiring diagram LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue 58 in (1473 mm)
White 25 in (635 mm)
Red 66 in (1676 mm)
49767 – GE259MAX-N/ULTRA
UltraMax® Instant Start Multi-Voltage High-Efficiency
2 or 1 – F96T8 120 to 277 “N” .87 BF UltraMax®
Order information
10 Pack Pallet Pack DIY Pack IP Pack
49767 23954
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• UL Type CC Rating provides protection against arcing in electrical devices
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
• Energy-saving high-efficiency instant-start electronic ballast (> 90%)
• Multi-voltage technology handles voltage from 120 to 277V
• Active Current Regulation regulates the output to each lamp with individual lamp inverter modules
• Anti-striation control for better light quality, with no striations
• UL Type CC Rating provides protection against arcing with F96T8 lamps only
UltraMax® Instant Start Multi-Voltage High-Efficiency
T8 Instant Start Ballasts For 46 – 59W 4 ft – 8 ft Slimline Lamps
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 109 0.94 A 0.87 0.79 99 1.5 10 -22/ -30
4 277 107 0.40 A 0.87 0.81 98 1.5 10 -22/ -30
3 120 85 0.72 A 0.87 1.02 99 1.5 10 -22/ -30
3 277 84 0.32 A 0.87 1.03 99 1.5 10 -22/ -30
F32T8/WM
4 120 105 0.90 A 0.87 0.82 99 1.5 10 60 / 16
4 277 103 0.39 A 0.87 0.84 98 1.5 10 60 / 16
3 120 81 0.68 A 0.87 1.07 99 1.5 10 60 / 16
3 277 80 0.30 A 0.87 1.08 97 1.5 10 60 / 16
F28T8
4 120 98 0.84 A 0.87 0.88 99 1.5 10 60 / 16
4 277 96 0.37 A 0.87 0.90 98 1.5 10 60 / 16
3 120 76 0.67 A 0.87 1.14 99 1.5 10 60 / 16
3 277 75 0.29 A 0.87 1.16 97 1.5 10 60 / 16
F25T8
4 120 91 0.76 A 99 1.5 10 0 / -18
4 277 89 0.33 A 98 1.5 14 0 / -18
3 120 72 0.64 A 99 1.5 10 0 / -18
3 277 71 0.28 A 97 1.5 17 0 / -18
Other compatible lamps: FE15T8, F25T12, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 124 1.03 A 1.00 0.81 99 1.5 10 -22/ -30
4 277 121 0.45 A 1.00 0.83 98 1.5 10 -22/ -30
3 277 113 0.45 A 1.15 1.02 97 1.5 10 -22/ -30
3 120 97 0.81 A 0.97 1.00 99 1.5 10 -22/ -30
F32T8/WM
4 120 119 1.00 A 1.00 0.84 99 1.5 10 60 / 16
4 277 117 0.44 A 1.00 0.86 98 1.5 10 60 / 16
3 120 92 0.77 A 0.99 1.07 99 1.5 10 60 / 16
3 277 92 0.35 A 0.99 1.08 97 1.5 10 60 / 16
F28T8
4 120 114 0.95 A 1.00 0.88 99 1.5 10 60 / 16
4 277 96 0.36 A 1.00 1.04 97 1.5 10 60 / 16
3 120 89 0.74 A 0.99 1.12 99 1.5 10 60 / 16
3 277 88 0.33 A 0.99 1.13 96 1.5 10 60 / 16
F25T12
4 120 110 0.92 A 0.96 0.87 99 1.5 10 0 / -18
4 277 108 0.40 A 0.96 0.89 97 1.5 16 0 / -18
3 120 86 0.72 A 0.97 1.13 99 1.5 10 0 / -18
3 277 86 0.32 A 0.97 1.13 96 1.5 19 0 / -18
Other compatible lamps: FE15T8, F25T8, F40T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F96T8
2 120 107 0.91 A 0.87 0.81 99 1.5 10 0 / -18
2 277 105 0.40 A 0.87 0.82 98 1.5 15 0 / -18
1 120 62 0.53 A 0.87 1.40 99 1.5 10 0 / -18
1 277 62 0.24 A 0.87 1.40 97 1.5 20 0 / -18
F96T8/WM
2 120 102 0.87 A 0.87 0.85 99 1.5 10 50 / 10
2 277 100 0.38 A 0.87 0.87 98 1.5 15 50 / 10
1 120 59 0.50 A 0.87 1.47 99 1.5 10 50 / 10
1 277 59 0.23 A 0.87 1.47 97 1.5 20 50 / 10
F96T8/WMP
2 120 85 0.78 A 0.89 1.04 99 1.5 10 50 / 10
2 277 84 0.32 A 0.89 1.05 98 1.5 15 50 / 10
1 120 59 0.50 A 0.87 1.47 99 1.5 10 50 / 10
1 277 59 0.23 A 0.87 1.47 97 1.5 20 50 / 10
F72T8
2 120 79 0.72 A 0.99 1.5 10 0 / -18
2 277 78 0.29 A 0.98 1.5 13 0 / -18
1 120 44 0.39 A 0.99 1.5 10 0 / -18
1 277 44 0.17 A 0.96 1.5 20 0 / -18
Other compatible lamps: F40T8
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type CC UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
General characteristics
Ballast Type Electronic – High-Efficiency Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1A – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (27.94 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White 25 in (635 mm)
Red 66 in (1676 mm)
Black 25 in (635 mm)
Blue 58 in (1473 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
49766
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F96T8
1 120 54 0.46 A 0.87 1.61 99 1.5 10 0 / -18
1 277 53 0.21 A 0.87 1.64 95 1.5 15 0 / -18
F96T8/WM
1 120 51 0.43 A 0.87 1.70 99 1.5 10 0 / -18
1 277 51 0.20 A 0.87 1.70 95 1.5 15 0 / -18
F40T8
1 120 38 0.32 A 99 1.5 10 0 / -18
1 277 38 0.15 A 95 1.5 18 0 / -18
F96T8/WMP
1120 99 1.5 10 0 / -18
1277 95 1.5 15 0 / -18
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type CC UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
46 See page 195 for warranty information. 47
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
72269 – GE-132-MV-N (replaces 30189)
ProLine® T8 Multivolt 120V – 277V
1 – F32T8 120 to 277 “N” .87 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1A – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 48 in (1219 mm)
White 22 in (559 mm)
Blue 30 in (762 mm)
Black 22 in (559 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72269 72270 (replaces 30268)
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
ProLine® T8 Multivolt 120V – 277V
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
30198 – GE-232-MV-H
ProLine® T8 Multivolt 120V – 277V
2 or 1 – F32T8 120 to 277 “H” 1.18 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 48 in (1219 mm)
White 22 in (559 mm)
Blue 30 in (762 mm)
Black 22 in (559 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30198 30275
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
ProLine® T8 Multivolt 120V – 277V
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
72273 – GE-232-MV-L (replaces 30247)
ProLine® T8 Multivolt 120V – 277V
2 or 1 – F32T8 120 to 277 “L” .77 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 48 in (1219 mm)
White 22 in (559 mm)
Blue 30 in (762 mm)
Black 22 in (559 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72273 72274 (replaces 30308)
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
72275 – GE-232-MV-N (replaces 30191)
ProLine® T8 Multivolt 120V – 277V
2 or 1 – F32T8 120 to 277 “N” .87 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 48 in (1219 mm)
White 22 in (559 mm)
Blue 30 in (762 mm)
Black 22 in (559 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72275 72276 (replaces 30269) 72277 (replaces 97709)
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
1 120 29 0.28 A 0.87 3.00 99 1.7 10 0 / -18
1 277 28 0.13 A 0.87 3.11 95 1.7 10 0 / -18
F32T8/WM
1 120 29 0.25 A 0.83 2.88 99 1.7 10 60 / 16
1 277 29 0.12 A 0.83 2.87 95 1.7 10 60 / 16
F28T8
1 120 27 0.22 A 0.80 3.01 99 1.7 10 60 / 16
1 277 27 0.11 A 0.80 3.01 94 1.7 10 60 / 16
F25T8
1 120 25 0.21 A 0.88 3.54 99 1.7 10 0 / -18
1 277 25 0.10 A 0.88 3.52 94 1.7 15 0 / -18
F17T8
1 277 19 0.08 A 0.88 4.68 91 1.7 20 0 / -18
1 120 18 0.16 A 0.88 4.78 99 1.7 10 0 / -18
Other compatible lamps: F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 77 0.65 A 1.18 1.53 99 1.7 10 0 / -18
2 277 76 0.28 A 1.18 1.55 98 1.7 10 0 / -18
1 120 48 0.44 A 1.34 2.79 99 1.7 10 0 / -18
1 277 48 0.20 A 1.34 2.79 97 1.7 10 0 / -18
F32T8/WM
2 120 70 0.63 A 1.13 1.61 99 1.7 10 60 / 16
2 277 69 0.28 A 1.13 1.63 98 1.7 10 60 / 16
1 120 45 0.42 A 1.30 2.88 99 1.7 10 60 / 16
1 277 45 0.19 A 1.30 2.88 96 1.7 10 60 / 16
F28T8
2 120 65 0.57 A 1.10 1.68 99 1.7 10 60 / 16
2 277 64 0.26 A 1.10 1.71 98 1.7 10 60 / 16
1 120 42 0.39 A 1.28 3.04 99 1.7 10 60 / 16
1 277 42 0.18 A 1.28 3.04 96 1.7 10 60 / 16
F25T8
2 120 57 0.51 A 1.16 2.03 99 1.7 7 0 / -18
2 277 57 0.23 A 1.16 2.03 97 1.7 15 0 / -18
1 120 38 0.35 A 1.32 3.47 99 1.7 10 0 / -18
1 277 38 0.16 A 1.32 3.47 96 1.7 18 0 / -18
Other compatible lamps: F17T8, F40T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 49.5 0.50 A 0.79 1.58 99 1.7 10 0 / -18
2 277 48.6 0.22 A 0.79 1.60 96 1.7 10 0 / -18
1 120 35.0 0.32 A 0.94 2.68 99 1.7 10 0 / -18
1 277 35.0 0.14 A 0.94 2.68 94 1.7 10 0 / -18
F32T8/WM
2 120 48.0 0.43 A 0.75 1.57 99 1.7 10 60 / 16
2 277 47.0 0.19 A 0.75 1.59 96 1.7 10 60 / 16
1 120 31.0 0.29 A 0.90 2.90 99 1.7 10 60 / 16
1 277 31.0 0.13 A 0.90 2.90 94 1.7 10 60 / 16
F28T8
2 120 44.0 0.41 A 0.74 1.69 99 1.7 10 60 / 16
2 277 43.0 0.17 A 0.74 1.71 96 1.7 10 60 / 16
1 120 29.0 0.28 A 0.86 2.96 99 1.7 10 60 / 16
1 277 29.0 0.13 A 0.86 2.96 94 1.7 10 60 / 16
F25T8
2 120 40.0 0.36 A 0.81 2.01 99 1.7 10 0 / -18
2 277 40.0 0.16 A 0.81 2.03 95 1.7 18 0 / -18
1 120 27.0 0.25 A 0.94 3.48 99 1.7 10 0 / -18
1 277 27.0 0.12 A 0.94 3.48 93 1.7 21 0 / -18
Other compatible lamps: F40T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 55 0.52 A 0.87 1.58 99.0 1.7 10 0 / -18
2 277 54 0.23 A 0.87 1.61 96.8 1.7 10 0 / -18
1 277 42 0.16 A 1.02 2.44 95.6 1.7 10 0 / -18
1 120 41 0.36 A 1.02 2.46 99.0 1.7 10 0 / -18
F32T8/WM
2 120 55 0.48 A 0.82 1.50 99.0 1.7 10 60 / 16
2 277 54 0.21 A 0.82 1.52 96.5 1.7 10 60 / 16
1 120 40 0.33 A 0.97 2.45 95.0 1.7 10 60 / 16
1 277 40 0.15 A 0.97 2.44 95.5 1.7 10 60 / 16
F28T8
2 120 49 0.44 A 0.80 1.63 99.0 1.7 10 60 / 16
2 277 48 0.19 A 0.80 1.67 96.2 1.7 10 60 / 16
1 277 36 0.14 A 0.94 2.63 95.4 1.7 10 60 / 16
1 120 33 0.29 A 0.94 2.89 99.0 1.7 10 60 / 16
F25T8
2 120 46 0.41 A 0.85 1.85 99.0 1.7 10 0 / -18
2 277 46 0.18 A 0.85 1.86 96.0 1.7 16 0 / -18
1 277 34 0.13 A 1.03 3.06 94.7 1.7 19 0 / -18
1 120 33 0.29 A 1.03 3.08 99.0 1.7 10 0 / -18
Other compatible lamps: F17T8, F40T8, F32T8/25W
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor NRCan UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor NRCan UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor NRCan UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
48 See page 195 for warranty information. 49
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
ProLine® T8 Multivolt 120V – 277V
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
ProLine® T8 Multivolt 120V – 277V
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
30199 – GE-332-MV-H
ProLine® T8 Multivolt 120V – 277V
3 or 2 – F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 48 in (1219 mm)
White 22 in (559 mm)
Blue 30 in (762 mm)
Black 22 in (559 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30199 30296
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
30255 – GE-332-MV-L
ProLine® T8 Multivolt 120V – 277V
3 or 2 – F32T8 120 to 277 “L” .77 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 48 in (1219 mm)
White 22 in (559 mm)
Blue 30 in (762 mm)
Black 22 in (559 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30255 30309
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
30192 – GE-332-MV-N
ProLine® T8 Multivolt 120V – 277V
3 or 2 – F32T8 120 to 277 “N” .87 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 48 in (1219 mm)
White 22 in (559 mm)
Blue 30 in (762 mm)
Black 22 in (559 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30192 30270 97710
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
30219 – GE-432-MV-H
ProLine® T8 Multivolt 120V – 277V
4 or 3 – F32T8 120 to 277 “H” 1.15 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 22 in (559 mm)
Red 36 in (914 mm)
Yellow 38 in (965 mm)
Blue 30 in (762 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30219 30303
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 113 0.95 A 1.15 1.01 99 1.7 10 0 / -18
3 277 110 0.41 A 1.15 1.04 98 1.7 10 0 / -18
2 120 86 0.79 A 1.27 1.47 99 1.7 10 0 / -18
2 277 85 0.34 A 1.27 1.49 97 1.7 10 0 / -18
F32T8/WM
3 120 103 0.91 A 1.11 1.07 99 1.7 10 60 / 16
3 277 101 0.39 A 1.11 1.09 98 1.7 10 60 / 16
2 120 79 0.73 A 1.22 1.54 99 1.7 10 60 / 16
2 277 78 0.32 A 1.22 1.56 97 1.7 10 60 / 16
F40T8
2 120 102 0.95 A 99 1.7 8 0 / -18
2 277 100 0.41 A 98 1.7 15 0 / -18
F28T8
3 120 94 0.84 A 1.07 1.13 99 1.7 10 0 / -18
3 277 92 0.36 A 1.07 1.16 98 1.7 10 0 / -18
2 120 72 0.67 A 1.20 1.66 99 1.7 10 0 / -18
2 277 72 0.30 A 1.20 1.66 97 1.7 10 0 / -18
Other compatible lamps: F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 74 0.70 A 0.78 1.05 99 1.7 10 0 / -18
3 277 73 0.31 A 0.80 1.06 98 1.7 10 0 / -18
2 120 60 0.55 A 0.87 1.46 99 1.7 10 0 / -18
2 277 59 0.24 A 0.87 1.47 97 1.7 10 0 / -18
F32T8/WM
3 120 69 0.62 A 0.74 1.07 99 1.7 10 60 / 16
3 277 68 0.27 A 0.74 1.08 98 1.7 10 60 / 16
2 120 56 0.50 A 0.83 1.51 99 1.7 10 60 / 16
2 277 55 0.22 A 0.83 1.52 97 1.7 10 60 / 16
F40T8
2 120 69 0.63 A 99 1.7 8 0 / -18
2 277 68 0.27 A 98 1.7 15 0 / -18
F28T8
3 120 63 0.57 A 0.74 1.17 99 1.7 10 60 / 16
3 277 63 0.25 A 0.74 1.18 98 1.7 10 60 / 16
2 120 50 0.46 A 0.83 1.67 99 1.7 10 60 / 16
2 277 50 0.20 A 0.83 1.66 97 1.7 10 60 / 16
Other compatible lamps: F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 81 0.73 A 0.87 1.06 99.0 1.7 10 0 / -18
3 277 80 0.32 A 0.87 1.08 98.3 1.7 10 0 / -18
2 120 62 0.56 A 0.96 1.54 99.0 1.7 10 0 / -18
2 277 62 0.26 A 0.96 1.55 97.8 1.7 10 0 / -18
F32T8/WM
3 120 75 0.68 A 0.83 1.10 99.0 1.7 10 60 / 16
3 277 74 0.30 A 0.83 1.11 98.1 1.7 10 60 / 16
2 120 58 0.52 A 0.92 1.59 99.0 1.7 10 60 / 16
2 277 57 0.23 A 0.92 1.60 97.6 1.7 10 60 / 16
F40T8
2 120 75 0.67 A 99.0 1.7 10 0 / -18
2 277 73 0.29 A 98.1 1.7 13 0 / -18
F28T8
3 120 67 0.60 A 0.80 1.19 99.0 1.7 10 60 / 16
3 277 67 0.26 A 0.80 1.20 97.9 1.7 10 60 / 16
2 120 52 0.46 A 0.87 1.68 99.0 1.7 10 60 / 16
2 277 51 0.29 A 0.87 1.71 97.4 1.7 10 60 / 16
Other compatible lamps: F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F40T8
3 120 145 1.30 A 99 1.7 8 0 / -18
3 277 141 0.57 A 98 1.7 15 0 / -18
F32T8
4 120 144 1.35 A 1.15 0.79 99 1.7 10 0 / -18
4 277 140 0.57 A 1.15 0.82 98 1.7 10 0 / -18
3 120 122 1.13 A 1.24 1.01 99 1.7 10 0 / -18
3 277 120 0.49 A 1.24 1.03 98 1.7 10 0 / -18
F32T8/WM
4 120 135 1.25 A 1.11 0.82 99 1.7 10 60 / 16
4 277 133 0.54 A 1.11 0.83 98 1.7 10 60 / 16
3 120 112 1.00 A 1.20 1.07 99 1.7 10 60 / 16
3 277 110 0.45 A 1.20 1.09 97 1.7 10 60 / 16
F28T8
4 120 122 1.13 A 1.08 0.88 99 1.7 10 60 / 16
4 277 120 0.48 A 1.08 0.90 98 1.7 10 60 / 16
3 120 102 0.94 A 1.17 1.14 99 1.7 10 60 / 16
3 277 101 0.41 A 1.17 1.15 97 1.7 10 60 / 16
Other compatible lamps: F25T8, F17T8, F32T8/25W
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
50 See page 195 for warranty information. 51
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
ProLine® T8 Multivolt 120V – 277V
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
ProLine® T8 Multivolt 120V – 277V
T8 Instant Start Ballasts For 46 – 59W 4 ft – 8 ft Slimline Lamps
30262 – GE-432-MV-L
ProLine® T8 Multivolt 120V – 277V
4 or 3 – F32T8 120 to 277 “L” .77 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in 43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 22 in (559 mm)
Red 36 in (914 mm)
Yellow 38 in (965 mm)
Blue 30 in (762 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30262 30310
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
30193 – GE-432-MV-N
ProLine® T8 Multivolt 120V – 277V
4 or 3 – F32T8 120 to 277 “N” .87 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 22 in (559 mm)
Red 36 in (914 mm)
Yellow 38 in (965 mm)
Blue 30 in (762 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30193 30271 97711
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
30195 – GE-159-MV-N
ProLine® T8 Multivolt 120V – 277V
1 – F96T8 120 to 277 “N” .87 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1A – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.00 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.87 in (22.00 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.06 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 66 in (1676 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
Blue 58 in (1473 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30195 30274
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
30194 – GE-259-MV-N
ProLine® T8 Multivolt 120V – 277V
2 or 1 – F96T8 120 to 277 “N” .87 BF Multivolt ProLine®
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 66 in (1676 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
Blue 58 in (1473 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30194 30272 97712
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F40T8
3 120 102 0.94 A 99 1.7 10 0 / -18
3 277 100 0.41 A 97 1.7 15 0 / -18
F32T8
4 120 100 0.95 A 0.80 0.80 99 1.7 10 0 / -18
4 277 98 0.41 A 0.80 0.81 98 1.7 10 0 / -18
3 120 87 0.80 A 0.87 1.00 99 1.7 10 0 / -18
3 277 86 0.35 A 0.87 1.01 97 1.7 10 0 / -18
F32T8/WM
4 120 95 0.84 A 0.76 0.80 99 1.7 10 60 / 16
4 277 93 0.36 A 0.76 0.81 98 1.7 10 60 / 16
3 120 79 0.73 A 0.83 1.05 99 1.7 10 60 / 16
3 277 78 0.32 A 0.83 1.06 97 1.7 10 60 / 16
F28T8
4 120 86 0.77 A 0.73 0.84 99 1.7 10 60 / 16
4 277 85 0.33 A 0.73 0.85 97 1.7 10 60 / 16
3 120 73 0.67 A 0.79 1.08 99 1.7 10 60 / 16
3 277 72 0.29 A 0.79 1.09 97 1.7 10 60 / 16
Other compatible lamps: F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 113 0.99 A 0.88 0.78 99.0 1.7 10 0 / -18
4 277 110 0.43 A 0.88 0.79 98.1 1.7 10 0 / -18
3 120 93 0.83 A 0.93 0.99 99.0 1.7 10 0 / -18
3 277 92 0.36 A 0.93 1.01 97.9 1.7 10 0 / -18
F40T8
3 120 112 0.99 A 99.0 1.7 10 0 / -18
3 277 110 0.43 A 98.1 1.7 14 0 / -18
F32T8/WM
4 120 103 0.90 A 0.83 0.80 99.0 1.7 10 60 / 16
4 277 103 0.40 A 0.83 0.80 98.0 1.7 10 60 / 16
3 120 87 0.77 A 0.91 1.04 99.0 1.7 10 60 / 16
3 277 86 0.33 A 0.91 1.05 97.8 1.7 10 60 / 16
F28T8
4 120 93 0.83 A 0.80 0.85 99.0 1.7 10 60 / 16
4 277 92 0.36 A 0.80 0.87 97.9 1.7 10 60 / 16
3 120 77 0.68 A 0.85 1.10 99.0 1.7 10 60 / 16
3 277 77 0.30 A 0.85 1.10 97.6 1.7 10 60 / 16
Other compatible lamps: F25T8, F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F96T8
1 120 60 0.55 A 0.89 1.48 99 1.7 10 0 / -18
1 277 59 0.22 A 0.89 1.50 96 1.7 18 0 / -18
F96T8/WM
1 120 56 0.51 A 0.85 1.53 99 1.7 10 50 / 10
1 277 54 0.22 A 0.85 1.57 96 1.7 18 50 / 10
F96T8/WMP
1120 99 1.7 10 50 / 10
1277 96 1.7 18 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F96T8
2 120 113 1.01 A 99.0 1.7 10 0 / -18
2 277 110 0.40 A 98.0 1.7 10 0 / -18
1 120 72 0.66 A 99.0 1.7 10 0 / -18
1 277 72 0.29 A 97.0 1.7 16 0 / -18
F96T8/WM
2 120 104 0.93 A 99.0 1.7 10 50 / 10
2 277 101 0.42 A 98.4 1.7 13 50 / 10
1 120 67 0.63 A 99.0 1.7 10 50 / 10
1 277 66 0.28 A 97.0 1.7 17 50 / 10
F96T8/WMP
2120
2277
1120
1277
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
52 See page 195 for warranty information. 53
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
ProLine® T8 Multivolt High Output 120V – 277V
T8 Instant Start Ballasts For 44 – 86W 4 ft – 8 ft HO Lamps
30176 – GE-286-HO-MV-N
ProLine® T8 Multivolt High Output 120V – 277V
2 or 1 – F96T8HO IS 120 to 277 “N” .87 BF
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.04 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 58 in (1473 mm)
White 25 in (635 mm)
Red 66 in (1676 mm)
Black 25 in (635 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
30176 30187
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F96T8/HO
2 120 146 1.30 A 0.80 0.54 99 1.7 10 0 / -18
2 277 143 0.56 A 0.82 0.57 97 1.7 14 0 / -18
1 120 92 0.82 A 0.82 0.89 98 1.7 10 0 / -18
1 277 90 0.36 A 0.82 0.91 96 1.7 19 0 / -18
F96T8
2 120 142 1.29 A 1.17 0.82 99 1.7 10 0 / -18
2 277 139 0.52 A 1.17 0.84 97 1.7 14 0 / -18
1 120 87 0.79 A 99 1.7 10 0 / -18
1 277 86 0.33 A 97 1.7 19 0 / -18
F96T8/WM
2 120 136 1.23 A 99 1.7 10 0 / -18
2 277 134 0.51 A 98 1.7 14 0 / -18
1 120 86 0.77 A 99 1.7 10 0 / -18
1 277 86 0.33 A 97 1.7 20 0 / -18
F96T8/WMP
2 120 125 1.11 A 99 1.7 10 0 / -18
2 277 123 0.47 A 98 1.7 15 0 / -18
1 120 78 0.69 A 99 1.7 10 0 / -18
1 277 77 0.30 A 96 1.7 21 0 / -18
F72T8HO
2 120 115 1.02 A 99 1.7 10 0 / -18
2 277 114 0.43 A 97 1.7 16 0 / -18
1 120 73 0.64 A 99 1.7 10 0 / -18
1 277 72 0.28 A 95 1.7 22 0 / -18
F40T8
2 120 98 0.87 A 99 1.7 10 0 / -18
2 277 97 0.37 A 97 1.7 17 0 / -18
1 120 62 0.55 A 99 1.7 11 0 / -18
1 277 62 0.25 A 94 1.7 23 0 / -18
F60T8HO
2 120 95 0.84 A 99 1.7 10 0 / -18
2 277 92 0.35 A 97 1.7 18 0 / -18
1 277 62 0.24 A 94 1.7 23 0 / -18
1 120 60 0.53 A 99 1.7 11 0 / -18
F58T8
2 120 78 0.72 A 99 1.7 10 0 / -18
2 277 78 0.30 A 96 1.7 20 0 / -18
1 277 50 0.20 A 93 1.7 27 0 / -18
1 120 49 0.45 A 99 1.7 13 0 / -18
F48T8HO
2 120 78 0.70 A 99 1.7 10 0 / -18
2 277 77 0.30 A 96 1.7 21 0 / -18
1 120 51 0.45 A 99 1.7 13 0 / -18
1 277 51 0.20 A 93 1.7 26 0 / -18
ProLine® T8 Instant Start High Performance
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
23680 GE-132-120-N
ProLine® T8 Instant Start High Performance
1 – F32T8 120V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1A – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 24 in (610 mm)
Red 32 in (813 mm)
White 24 in (610 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23680 24161
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
23681 – GE-132-277-N
ProLine® T8 Instant Start High Performance
1 – F32T8 277V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1A – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 24 in (610 mm)
Red 32 in (813 mm)
White 24 in (610 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23681 24162
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 1 120 30 0.26 A 0.87 2.90 99 1.7 10 0 / -18
F32T8/WM 1 120 28 0.24 A 0.86 3.07 99 1.7 10 60 / 16
F25T12 1 120 25 0.22 A 0.87 3.48 99 1.7 10 0 / -18
F28T8 1 120 25 0.22 A 0.84 3.36 99 1.7 10 60 / 16
F25T8 1 120 24 0.21 A 0.87 3.62 99 1.7 10 0 / -18
F17T8 1 120 18 0.16 A 0.91 5.05 99 1.7 10 0 / -18
FE15T8 1 120 15 0.13 A 0.91 6.06 99 1.7 10 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 1 277 30 0.12 A 0.87 2.90 99 1.7 10 0 / -18
F32T8/WM 1 277 28 0.11 A 0.86 3.07 99 1.7 10 60 / 16
F28T8 1 277 26 0.97 A 0.84 3.23 97 1.7 10 60 / 16
F25T12 1 277 25 0.10 A 0.87 3.48 97 1.7 11 0 / -18
F25T8 1 277 25 0.10 A 0.87 3.48 97 1.7 11 0 / -18
F17T8 1 277 18 0.07 A 0.91 5.05 96 1.7 14 0 / -18
FE15T8 1 277 15 0.06 A 0.91 6.06 94 1.7 16 0 / -18
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
54 See page 195 for warranty information. 55
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
23671 – GE-232-120-N
ProLine® T8 Instant Start High Performance
2 or 1 – F32T8 120V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 24 in (610 mm)
Red 32 in (813 mm)
White 24 in (610 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23671 24163
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
ProLine® T8 Instant Start High Performance
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
ProLine® T8 Instant Start High Performance
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
23672 – GE-232-277-N
ProLine® T8 Instant Start High Performance
2 or 1 – F32T8 277V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 24 in (610 mm)
Red 32 in (813 mm)
White 24 in (610 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23672 24164
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
23673 – GE-332-120-N
ProLine® T8 Instant Start High Performance
3 or 2 – F32T8 120V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 24 in (610 mm)
Red 32 in (813 mm)
White 24 in (610 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23673 24165
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
23674 – GE-332-277-N
ProLine® T8 Instant Start High Performance
3 or 2 – F32T8 277V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1C – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 24 in (610 mm)
Red 32 in (813 mm)
White 24 in (610 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23674 24166
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 57 0.49 A 0.87 1.52 99 1.7 10 0 / -18
1 120 36 0.31 A 0.94 2.61 99 1.7 10 0 / -18
F32T8/WM
2 120 53 0.45 A 0.86 1.62 99 1.7 10 60 / 16
1 120 33 0.29 A 0.94 2.84 99 1.7 10 60 / 16
F28T8
2 120 48 0.41 A 0.84 1.75 99 1.7 10 60 / 16
1 120 30 0.26 A 0.91 3.03 99 1.7 10 60 / 16
F25T12
2 120 46 0.40 A 0.87 1.89 99 1.7 10 0 / -18
1 120 30 0.26 A 0.94 3.13 99 1.7 10 0 / -18
F25T8
2 120 45 0.38 A 0.87 1.93 99 1.7 10 0 / -18
1 120 28 0.25 A 0.97 3.46 99 1.7 10 0 / -18
F40T8 1 120 43 0.37 A 99 1.7 10 0 / -18
F17T8
2 120 31 0.27 A 0.91 2.93 99 1.7 10 0 / -18
1 120 20 0.18 A 0.97 4.85 98 1.7 13 0 / -18
FE15T8
2 120 25 0.22 A 0.91 3.64 98 1.7 11 0 / -18
1 120 17 0.15 A 0.98 5.76 98 1.7 15 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 277 57 0.22 A 0.87 1.52 99 1.7 10 0 / -18
1 277 37 0.14 A 0.94 2.54 99 1.7 10 0 / -18
F32T8/WM
2 277 53 0.20 A 0.86 1.62 99 1.7 10 60 / 16
1 277 34 0.13 A 0.94 2.76 99 1.7 10 60 / 16
F28T8
2 277 48 0.18 A 0.84 1.75 99 1.7 10 60 / 16
1 277 31 0.12 A 0.91 2.93 97 1.7 10 60 / 16
F25T12
2 277 47 0.18 A 0.87 1.85 98 1.7 10 0 / -18
1 277 31 0.12 A 0.94 3.03 97 1.7 13 0 / -18
F25T8
2 277 45 0.17 A 0.87 1.93 98 1.7 10 0 / -18
1 277 29 0.11 A 0.97 3.34 97 1.7 13 0 / -18
F40T8 1 277 44 0.16 A 99 1.7 10 0 / -18
F17T8
2 277 32 0.12 A 0.91 2.84 98 1.7 12 0 / -18
1 277 22 0.08 A 0.97 4.40 96 1.7 16 0 / -18
FE15T8
2 277 26 0.10 A 0.91 3.50 97 1.7 14 0 / -18
1 277 18 0.07 A 0.98 5.44 95 1.7 17 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 85 0.73 A 0.87 1.02 99 1.7 10 0 / -18
2 120 65 0.56 A 0.94 1.44 99 1.7 10 0 / -18
F32T8/WM
3 120 79 0.68 A 0.86 1.08 99 1.7 10 60 / 16
2 120 60 0.51 A 0.94 1.56 99 1.7 10 60 / 16
F40T8 2 120 78 0.67 A 99 1.7 10 0 / -18
F28T8
3 120 72 0.62 A 0.84 1.16 99 1.7 10 60 / 16
2 120 54 0.47 A 0.91 1.68 99 1.7 10 60 / 16
F25T12
3 120 69 0.60 A 0.87 1.26 99 1.7 10 0 / -18
2 120 54 0.46 A 0.94 1.74 99 1.7 10 0 / -18
F25T8
3 120 67 0.58 A 0.87 1.29 99 1.7 10 0 / -18
2 120 51 0.44 A 0.97 1.90 99 1.7 10 0 / -18
F17T8
3 120 47 0.41 A 0.91 1.93 99 1.7 10 0 / -18
2 120 30 0.31 A 0.97 3.23 99 1.7 12 0 / -18
2 120 30 0.26 A 0.98 3.26 98 1.7 13 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 277 84 0.31 A 0.87 1.03 99 1.7 10 0 / -18
2 277 64 0.24 A 0.94 1.46 99 1.7 10 0 / -18
F32T8/WM
3 277 78 0.29 A 0.86 1.10 99 1.7 10 60 / 16
2 277 59 0.22 A 0.94 1.59 99 1.7 10 60 / 16
F40T8 2 277 77 0.29 A 99 1.7 10 0 / -18
F28T8
3 277 70 0.26 A 0.84 1.20 99 1.7 10 60 / 16
2 277 53 0.20 A 0.91 1.71 98 1.7 10 60 / 16
F25T12
3 277 68 0.25 A 0.87 1.27 99 1.7 10 0 / -18
2 277 53 0.20 A 0.94 1.77 98 1.7 11 0 / -18
F25T8
3 277 65 0.24 A 0.87 1.33 99 1.7 10 0 / -18
2 277 50 0.19 A 0.97 1.94 98 1.7 12 0 / -18
F17T8
3 277 46 0.17 A 0.91 1.97 98 1.7 12 0 / -18
2 277 36 0.13 A 0.97 2.69 97 1.7 15 0 / -18
FE15T8
3 277 36 0.14 A 0.91 2.52 98 1.7 15 0 / -18
2 277 28 0.11 A 0.98 3.50 97 1.7 16 0 / -18
UL Type 1 Outdoor NRCan UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor NRCan UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
56 See page 195 for warranty information. 57
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
ProLine® T8 Instant Start High Performance
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft), F40 (5 ft) Lamps
ProLine® T8 Instant Start High Performance
T8 Instant Start Ballasts For 46 – 59W 4 ft – 8 ft Slimline Lamps
23675 – GE-432-120-N
ProLine® T8 Instant Start High Performance
4 or 3 – F32T8 120V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Yellow 45 in (1143 mm)
Red 32 in (813 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23675 24167
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
23676 – GE-432-277-N
ProLine® T8 Instant Start High Performance
4 or 3 – F32T8 277V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Yellow 45 in (1143 mm)
Red 32 in (813 mm)
Blue 32 in (813 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23676 24168
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
23677 – GE-259-120-N
ProLine® T8 Instant Start High Performance
2 or 1 – F96T8 120V Normal Light .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Red 66 in (1676 mm)
White 25 in (635 mm)
Blue 58 in (1473 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23677 24169
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
23678 – GE-259-277-N
ProLine® T8 Instant Start High Performance
2 or 1 – F96T8 277V “N” .87 BF ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Red 66 in (1676 mm)
White 25 in (635 mm)
Blue 58 in (1473 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
23678 24170
• High-performance electronic ballast for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Lightweight, low-profile housing
• < 10% THD, > 99% power factor
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 113 0.97 A 0.87 0.76 0.87 1.7 10 0 / -18
3 120 93 0.80 A 0.94 1.01 0.94 1.7 10 0 / -18
F40T8 3 120 113 0.97 A 1.7 10 0 / -18
F32T8/WM
4 120 105 0.90 A 0.86 0.81 0.86 1.7 10 60 / 16
3 120 86 0.74 A 0.94 1.09 0.94 1.7 10 60 / 16
F28T8
4 120 96 0.81 A 0.84 0.87 0.84 1.7 10 60 / 16
3 120 77 0.66 A 0.91 1.18 0.91 1.7 10 60 / 16
F25T12
4 120 91 0.78 A 0.87 0.95 0.87 1.7 10 0 / -18
3 120 75 0.65 A 0.94 1.25 0.94 1.7 10 0 / -18
F25T8
4 120 87 0.74 A 0.87 1.00 0.87 1.7 10 0 / -18
3 120 72 0.62 A 0.97 1.34 0.97 1.7 10 0 / -18
F17T8
4 120 60 0.52 A 0.91 1.51 0.91 1.7 10 0 / -18
3 120 50 0.43 A 0.97 1.94 0.97 1.7 11 0 / -18
FE15T8
4 120 48 0.42 A 0.91 1.89 0.91 1.7 12 0 / -18
3 120 40 0.35 A 0.98 2.45 0.98 1.7 14 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F40T8 3 277 111 0.41 A 1.7 10 0 / -18
F32T8
4 277 110 0.41 A 0.87 0.79 1.7 10 0 / -18
3 277 92 0.34 A 0.94 1.02 1.7 10 0 / -18
F32T8/WM
4 277 102 0.38 A 0.86 0.84 1.7 10 60 / 16
3 277 84 0.32 A 0.94 1.11 1.7 10 60 / 16
F28T8
4 277 93 0.35 A 0.84 0.90 1.7 10 60 / 16
3 277 75 0.29 A 0.91 1.21 1.7 10 60 / 16
F25T12
4 277 89 0.33 A 0.87 0.97 1.7 10 0 / -18
3 277 75 0.28 A 0.94 1.25 1.7 10 0 / -18
F25T8
4 277 85 0.32 A 0.87 1.02 1.7 10 0 / -18
3 277 70 0.26 A 0.97 1.38 1.7 10 0 / -18
F17T8
4 277 59 0.22 A 0.91 1.54 1.7 12 0 / -18
3 277 49 0.19 A 0.97 1.97 1.7 13 0 / -18
FE15T8
4 277 47 0.18 A 0.91 1.93 1.7 14 0 / -18
3 277 39 0.15 A 0.98 2.51 1.7 15 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F96T8
2 120 112 0.96 A 0.87 0.77 99 1.7 10 0 / -18
1 120 71 0.61 A 1.04 1.46 99 1.7 10 0 / -18
F96T8/WM
2 120 104 0.89 A 0.87 0.83 99 1.7 10 0 / -18
1 120 65 0.56 A 1.04 1.60 99 1.7 10 0 / -18
F96T8/WMP
1120 99 1.7 10 0 / -18
2120 99 1.7 10 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F96T8
2 277 110 0.41 A 0.87 0.79 99 1.7 10 0 / -18
1 277 71 0.27 A 1.04 1.46 99 1.7 13 0 / -18
F96T8/WM
2 277 102 0.38 A 0.87 0.85 99 1.7 10 0 / -18
1 277 66 0.25 A 1.04 1.57 98 1.7 13 0 / -18
F96T8/WMP
1277 98 1.7 13 0 / -18
2277 99 1.7 10 0 / -18
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed RoHS Compliant
Safety and performance
58 See page 195 for warranty information. 59
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Residential Grade ProLine® T8 120V
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
Electromagnetic T8 Ballasts
T8 Instant Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
97782 – GE232-120-RES
Residential Grade ProLine® T8 120V
2 or 1 – F32T8 120V “N” .87 BF Residential ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Supply Current Frequency (MIN) 50 Hz
Dimensions
Wiring diagram – LFL 1B – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 36 in (914 mm)
Blue 31 in (787 mm)
White and Black 25 in (635 mm)
Yellow 38 in (965 mm)
Black 25 in (635 mm)
87125 – GEM232T8RS120
Electromagnetic T8 Ballasts
2 – F32T8, RS, 120V, Magnetic Ballast (M232SR120C)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 73
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.60 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 26 in (660 mm)
White and Black 20 in (508 mm)
Yellow 36 in (914 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87125 87125
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
• Great for areas requiring no EMI/RFI noise
97783 – GE432-120-RES
Residential Grade ProLine® T8 120V
4 or 3 – F32T8 120V “N” .87 BF Residential ProLine®
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Supply Current Frequency (MIN) 50 Hz
Dimensions
Wiring diagram – LFL 1D – see example on page 72
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Red 31 in (787 mm)
Blue 31 in (787 mm)
White and Black 25 in (635 mm)
Yellow 38 in (965 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
97783 70138
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 105 1.62 A 0.83 0.79 5 1.7 147 0 / -18
3 120 86 1.38 A 0.88 1.02 5 1.7 157 0 / -18
F32T8/WM
4 120 98 1.50 A 0.81 0.82 5 1.7 150 60 / 16
3 120 81 1.29 A 0.88 1.08 5 1.7 159 60 / 16
F28T8
4 120 90 1.42 A 0.79 0.87 5 1.7 155 60 / 16
3 120 75 1.23 A 0.87 1.16 5 0.19 165 60 / 16
F25T8
4 120 83 1.31 A 0.87 1.04 5 1.7 158 0 / -18
3 120 68 1.13 A 0.94 1.38 5 1.7 167 0 / -18
F17T8
4 120 58 0.98 A 0.86 1.48 48 1.7 175 0 / -18
3 120 48 0.84 A 0.93 1.93 44 1.7 185 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 2 120 32 0.60 A 0.94 2.93 98 1.7 18 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 2 277 77 0.28 A 0.98 1.27 98 1.7 20 50 / 10
F25T8 2 277 60 0.22 A 1.00 1.66 98 1.7 20 50 / 10
F17T8 2 277 47 0.18 A 1.09 2.31 96 1.7 25 50 / 10
87130 – GEM232T8RS277
Electromagnetic T8 Ballasts
2 – F32T8, RS, 277V, Magnetic Ballast (M232SR277C)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 73
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.60 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 26 in (660 mm)
White and Black 20 in (508 mm)
Yellow 36 in (914 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87130 87130
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
• Great for areas requiring no EMI/RFI noise
Order information
10 Pack Pallet Pack DIY Pack IP Pack
97782 70137
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 53 0.81 A 0.83 1.56 5 1.7 145 0 / -18
1 120 32 0.55 A 0.99 3.09 48 1.7 170 0 / -18
F32T8/WM
2 120 51 0.79 A 0.82 1.60 5 1.7 146 60 / 16
1 120 32 0.54 A 0.99 3.09 48 1.7 170 60 / 16
F28T8
2 120 46 0.72 A 0.81 1.76 5 1.7 152 60 / 16
1 120 29 0.50 A 0.97 3.34 48 1.7 177 60 / 16
F25T8
2 120 43 0.69 A 0.88 2.04 5 1.7 155 0 / -18
1 120 28 0.48 A 1.04 3.71 48 1.7 178 0 / -18
F17T8
2 120 31 0.52 A 0.88 2.83 49 1.7 172 0 / -18
1 120 20 0.37 A 1.03 5.15 45 1.7 195 0 / -18
Other compatible lamps: F32T8/25W
RoHS Compliant UL Type 1 Outdoor UL Type HL ANSI – C62.41 UL Class P FCC Part 18 Class B at 120 Volts cUL Listed
Safety and performance
UL Type 1 Outdoor RoHS Compliant UL Type HL ANSI – C62.41 FCC Part 18 Class B at 120 Volts UL Class P cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL CSA UL Class P UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P UL Listed
Safety and performance
60 See page 195 for warranty information. 61
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
29621 – GE-232-120-PS-N
UltraStart® T8 Programmed Start
2 – F32T8 120V Normal Light .87 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Yellow 48 in (1219 mm)
White 25 in (635 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29621 29630
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
29622 – GE-232-277-PS-N
UltraStart® T8 Programmed Start
2 – F32T8 277V Normal Light .87 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/ 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Yellow 48 in (1219 mm)
White 25 in (635 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29622 29632
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
96714 – GE232-MVPS-N
UltraStart® T8 Programmed Start
2 or 1 – F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed/ Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/Supply Current Frequency (MIN)/ 50 Hz/ 60 (MIN)
Supply Current Frequency (MIN) 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 4a – see example on page 73
Case dimensions – Ref Drawing A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
White 25 in (635 mm)
Yellow 48 km
• < 10% THD, > 99% power factor
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Anti-striation control for better light quality, with no striations
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Multi-voltage technology handles voltage from 120 to 277V
96720 – GE232-MVPS-L
UltraStart® T8 Programmed Start
2 or 1 – F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency (MIN) 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
White 25 in (635 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Anti-striation control for better light quality, with no striations
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Multi-voltage technology handles voltage from 120 to 277V
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
96720
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 57 0.49 A 0.89 1.56 99 1.7 10 0 / -18
1 120 35 0.29 A 1.03 2.94 99 1.7 10 0 / -18
F32T8/WM
2 120 54 0.46 A 0.88 1.62 99 1.7 10 60 / 16
1 120 33 0.28 A 1.02 3.09 99 1.7 10 60 / 16
F28T8
2 120 49 0.42 A 0.85 1.73 99 1.7 10 60 / 16
1 120 30 0.26 A 0.97 3.23 99 1.7 10 60 / 16
F25T8
2 120 45 0.39 A 0.89 1.97 99 1.7 10 0 / -18
1 120 28 0.24 A 1.04 3.71 98 1.7 10 0 / -18
F17T8
2 120 32 0.28 A 0.89 2.78 99 1.7 10 0 / -18
1 120 20 0.17 A 1.02 5.10 98 1.7 10 0 / -18
Other compatible lamps: F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 277 57 0.21 A 0.89 1.56 97 1.7 10 0 / -18
1 277 36 0.14 A 1.03 2.86 95 1.7 10 0 / -18
F32T8/WM
2 277 54 0.21 A 0.88 1.62 97 1.7 10 60 / 16
1 277 34 13.00 A 1.01 2.97 94 1.7 10 60 / 16
F28T8
2 277 49 0.19 A 0.86 1.75 97 1.7 10 60 / 16
1 277 31 0.12 A 0.98 3.16 94 1.7 10 60 / 16
F25T8
2 277 46 0.18 A 0.90 1.95 96 1.7 10 0 / -18
1 277 28 0.11 A 1.03 3.67 93 1.7 13 0 / -18
F17T8
2 277 32 0.12 A 0.90 2.81 93 1.7 10 0 / -18
1 277 21 0.08 A 1.02 4.85 88 1.7 15 0 / -18
Other compatible lamps: F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 47 0.39 A 0.71 1.51 99 1.7 10 0 / -18
2 277 47 0.17 A 0.71 1.51 95 1.7 10 0 / -18
1 120 30 0.28 A 0.81 2.70 98 1.7 10 0 / -18
1 277 30 0.11 A 0.81 2.70 90 1.7 10 0 / -18
F32T8/WM
2 120 44 0.36 A 0.67 1.52 99 1.7 10 60 / 16
2 277 44 0.16 A 0.67 1.52 95 1.7 10 60 / 16
1 120 28 0.26 A 0.79 2.82 98 1.7 10 60 / 16
1 277 28 0.11 A 0.79 2.82 90 1.7 10 60 / 16
F28T8
2 120 41 0.34 A 0.65 1.58 99 1.7 10 60 / 16
2 277 41 0.15 A 0.65 1.58 94 1.7 10 60 / 16
1 120 26 0.24 A 0.77 2.96 98 1.7 10 60 / 16
1 277 26 0.10 A 0.77 2.96 90 1.7 10 60 / 16
F25T8
2 277 38 0.14 A 0.73 1.92 94 1.7 16 0 / -18
2 120 37 0.31 A 0.73 1.97 99 1.7 10 0 / -18
1 277 25 0.09 A 0.86 3.44 85 1.7 16 0 / -18
1 120 24 0.23 A 0.86 3.58 97 1.7 10 0 / -18
Other compatible lamps: F17T8, F32T8/25W
RoHS Compliant UL Type 1 Outdoor UL Type HL NRCan FCC – CLASS A Non-Consumer ANSI – C62.41 UL Class P cUL Listed UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL Type HL FCC – CLASS A Non-Consumer NRCan UL Class P cUL Listed UL Listed
Safety and performance
Order information
10 Pack Pallet Pack DIY Pack IP Pack
96714 96717
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 59 0.48 A 0.89 1.50 99 1.7 10 0 / -18
2 277 58 0.21 A 0.89 1.53 96 1.7 10 0 / -18
1 120 37 0.30 A 1.05 2.83 98 1.7 10 0 / -18
1 277 37 0.14 A 1.05 2.83 93 1.7 10 0 / -18
F32T8/WM
2 120 55 0.45 A 0.88 1.60 99 1.7 10 50 / 10
2 277 54 0.20 A 0.88 1.62 96 1.7 10 50 / 10
1 120 34 0.28 A 1.02 3.00 98 1.7 10 50 / 10
1 277 34 0.13 A 1.02 3.00 93 1.7 10 50 / 10
F28T8
2 120 51 0.42 A 0.86 1.68 99 1.7 10 50 / 10
2 277 50 0.18 A 0.86 1.72 95 1.7 10 50 / 10
1 120 32 0.26 A 1.00 3.12 98 1.7 10 50 / 10
1 277 32 0.12 A 1.00 3.12 92 1.7 10 50 / 10
Other compatible lamps: F17T8, F25T8, F32T8/25W
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P ANSI – C62.41 RoHS Compliant cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer ANSI – C62.41 RoHS Compliant UL Class P cUL Listed UL Listed
Safety and performance
62 See page 195 for warranty information. 63
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
29675 – GE-232-MVPS-H
UltraStart® T8 Programmed Start
2 – F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 33 in (838 mm)
Black 25 in (635 mm)
White 25 in (635 mm)
Yellow 48 in (1219 mm)
Blue 33 in (838 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29675 29651
29671 – GE-232-MVPS-XL
UltraStart® T8 Programmed Start
2 – F32T8 120V-277V Ultra Low Watt .60 BF <10% THD
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Ultra low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/ 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 33 in (838 mm)
White and Black 25 in (635 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29671 29665
29623 – GE-332-120-PS-N
UltraStart® T8 Programmed Start
3 – F32T8 120V Normal Light .87 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS3 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29623 29633
29624 – GE-332-277-PS-N
UltraStart® T8 Programmed Start
3 – F32T8 277V Normal Light .87 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS3 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29624 29634
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 75 0.64 A 1.15 1.53 98 1.7 10 0 / -18
2 277 74 0.28 A 1.15 1.55 94 1.7 10 0 / -18
1 277 47 0.19 A 1.37 2.91 90 1.7 10 0 / -18
1 120 46 0.40 A 1.37 2.97 98 1.7 10 0 / -18
F32T8/WM
2 120 69 0.60 A 1.14 1.65 98 1.7 10 60 / 16
2 277 69 0.27 A 1.14 1.65 95 1.7 10 60 / 16
1 120 43 0.36 A 98 1.7 10 60 / 16
1 277 43 0.18 A 1.34 3.11 90 1.7 10 60 / 16
F28T8
2 120 63 0.54 A 1.10 1.74 94 1.7 10 60 / 16
2 277 62 0.25 A 1.11 1.79 98 1.7 10 60 / 16
1 277 39 0.16 A 1.29 3.30 89 1.7 10 60 / 16
1 120 38 0.32 A 98 1.7 10 60 / 16
F25T8
2 120 59 0.50 A 1.14 1.93 98 1.7 10 0 / -18
2 277 59 0.24 A 1.14 1.93 93 1.7 16 0 / -18
1 120 37 0.32 A 1.34 3.62 98 1.7 10 0 / -18
1 277 37 0.15 A 1.34 3.62 87 1.7 21 0 / -18
Other compatible lamps: F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
2 120 45 0.39 A 0.60 1.33 98.0 1.7 10 0 / -18
2 277 44 0.19 A 0.60 1.36 90.0 1.7 10 0 / -18
1 277 28 0.12 A 0.70 2.50 83.0 1.7 10 0 / -18
1 120 27 0.24 A 0.70 2.59 98.0 1.7 10 0 / -18
F32T8/WM
2 120 42 0.15 A 0.59 1.40 99.0 1.7 10 60 / 16
2 277 42 0.24 A 0.59 1.40 87.0 1.7 10 60 / 16
1 120 27 0.22 A 0.9 1.7 10 60 / 16
1 277 27 0.20 A 0.68 2.51 81.0 1.7 10 60 / 16
F28T8
2 120 39 0.12 A 0.59 1.51 99.0 1.7 10 60 / 16
2 277 39 0.15 A 0.59 1.51 86.0 1.7 10 60 / 16
1 277 25 0.12 A 0.67 2.68 79.0 1.7 10 60 / 16
1 120 24 0.20 A 98.0 1.7 10 60 / 16
F25T8
2 120 36 0.31 A 0.61 1.69 98.0 1.7 10 0 / -18
2 277 36 0.15 A 0.61 1.69 87.0 1.7 15 0 / -18
1 277 23 0.10 A 79.0 1.7 0 / -18
1 277 23 0.10 A 0.68 2.95 79.0 1.7 16 0 / -18
1 120 22 0.20 A 0.68 3.09 98.0 1.7 10 0 / -18
Other compatible lamps: F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 84 0.71 A 0.89 1.05 99.00 1.7 10 0 / -18
2 120 64 0.56 A 1.00 1.56 99.00 1.7 10 0 / -18
F32T8/WM
3 120 80 0.69 A 0.87 1.08 0.99 1.7 10 60 / 16
2 120 60 0.52 A 0.98 1.63 99.00 1.7 10 60 / 16
F28T8
3 120 72 0.62 A 0.85 1.18 99.00 1.7 10 60 / 16
2 120 54 0.47 A 0.95 1.75 99.00 1.7 10 60 / 16
F25T8
3 120 66 0.57 A 0.89 1.34 99.00 1.7 10 0 / -18
2 120 51 0.43 A 0.99 1.94 99.00 1.7 10 0 / -18
F17T8
3 120 45 0.39 A 0.88 1.95 99.00 1.7 10 0 / -18
2 120 35 0.31 A 0.98 2.80 99.00 1.7 10 0 / -18
Other compatible lamps: F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 277 85 0.32 A 0.89 1.04 97 1.7 10 0 / -18
2 277 65 0.25 A 1.00 1.53 97 1.7 10 0 / -18
F32T8/WM
3 277 80 0.30 A 0.88 1.10 98 1.7 10 60 / 16
2 277 61 0.23 A 0.98 1.60 98 1.7 10 60 / 16
F28T8
3 277 72 0.27 A 0.86 1.19 98 1.7 10 60 / 16
2 277 55 0.21 A 0.95 1.72 98 1.7 10 60 / 16
F25T8
3 277 67 0.26 A 0.89 1.32 97 1.7 10 0 / -18
2 277 51 0.20 A 0.99 1.94 96 1.7 11 0 / -18
F17T8
3 277 47 0.18 A 0.89 1.89 96 1.7 10 0 / -18
2 277 36 0.14 A 0.98 2.72 94 1.7 13 0 / -18
Other compatible lamps: F32T8/25W
UL Type 1 Outdoor UL Type HL RoHS Compliant FCC – CLASS A Non-Consumer ANSI – C62.41 UL Class P cUL Listed UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL Type HL NRCan FCC Part 18 Class B at 120 Volts UL Class P cUL Listed UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL Type HL NRCan FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
64 See page 195 for warranty information. 65
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
29676 – GE-332-MVPS-H
UltraStart® T8 Programmed Start
3 – F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS3 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29676 29656
96715 – GE332-MVPS-N
UltraStart® T8 Programmed Start
3 – F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Anti-striation control, TCLP compliant,
Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency (MIN) 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS3 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Anti-striation control for better light quality, with no striations
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Parallel lamp operation means system maintenance is easier to manage
• Starting time visually the same as instant start
Order information
10 Pack Pallet Pack DIY Pack IP Pack
96715 96718
96721 – GE332-MVPS-L
UltraStart® T8 Programmed Start
3 – F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency (MIN) 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS3 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Anti-striation control for better light quality, with no striations.
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Multi-voltage technology handles voltage from 120 to 277V
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
96721
29672 – GE-332-MVPS-XL
UltraStart® T8 Programmed Start
3 – F32T8 120V-277V Ultra Low Watt .60 BF <10% THD
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Ultra low
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS3 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29672 29666
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 110 0.95 A 1.15 1.04 98 1.7 10 0 / -18
3 277 108 0.41 A 1.15 1.06 96 1.7 10 0 / -18
2 120 82 0.70 A 1.28 1.56 98 1.7 10 0 / -18
2 277 82 0.32 A 94 1.7 10 0 / -18
F32T8/WM
3 120 102 0.88 A 1.13 1.10 99 1.7 10 60 / 16
3 277 100 0.39 A 1.14 1.14 96 1.7 10 60 / 16
2 120 77 0.64 A 98 1.7 10 60 / 16
2 277 76 0.30 A 1.26 1.65 95 1.7 10 60 / 16
F28T8
3 120 92 0.79 A 1.09 1.18 99 1.7 10 60 / 16
3 277 91 0.35 A 1.10 1.20 96 1.7 10 60 / 16
2 277 69 0.27 A 1.23 1.78 94 1.7 10 60 / 16
2 120 58 0.58 A 98 1.7 10 60 / 16
F25T8
3 120 86 0.74 A 1.14 1.32 98 1.7 10 0 / -18
3 277 85 0.33 A 1.14 1.34 96 1.7 14 0 / -18
2 120 65 0.56 A 1.25 1.92 98 1.7 10 0 / -18
2 277 64 0.26 A 93 1.7 16 0 / -18
Other compatible lamps: F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 86 0.72 A 0.89 1.03 99 1.7 10 0 / -18
3 277 84 0.30 A 0.89 1.05 97 1.7 10 0 / -18
2 120 66 0.54 A 0.98 1.48 98 1.7 10 0 / -18
2 277 65 0.24 A 0.98 1.50 95 1.7 10 0 / -18
F32T8/WM
3 120 80 0.66 A 0.86 1.07 99 1.7 10 60 / 16
3 277 79 0.28 A 0.86 1.08 97 1.7 10 60 / 16
2 120 61 0.51 A 0.96 1.57 98 1.7 10 60 / 16
2 277 61 0.22 A 0.96 1.57 95 1.7 10 60 / 16
F28T8
3 120 73 0.61 A 0.84 1.15 99 1.7 10 60 / 16
3 277 72 0.26 A 0.84 1.16 97 1.7 10 60 / 16
2 120 57 0.47 A 0.93 1.63 98 1.7 10 60 / 16
2 277 57 0.21 A 0.93 1.63 95 1.7 10 60 / 16
Other compatible lamps: F17T8, F25T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 69 0.60 A 0.71 1.02 99 1.7 10 0 / -18
3 277 68 0.26 A 0.71 1.04 96 1.7 10 0 / -18
2 120 52 0.45 A 0.77 1.48 98 1.7 10 0 / -18
2 277 52 0.19 A 0.77 1.48 92 1.7 10 0 / -18
F32T8/WM
3 120 63 0.54 A 0.67 1.06 99 1.7 10 60 / 16
3 277 62 0.24 A 0.67 1.08 95 1.7 10 60 / 16
2 120 48 0.40 A 0.75 1.56 98 1.7 10 60 / 16
2 277 48 0.18 A 0.75 1.56 92 1.7 10 60 / 16
F28T8
3 120 58 0.49 A 0.66 1.13 99 1.7 10 60 / 16
3 277 58 0.22 A 0.66 1.13 95 1.7 10 60 / 16
2 120 45 0.38 A 0.74 1.64 98 1.7 10 60 / 16
2 277 45 0.17 A 0.74 1.64 92 1.7 10 60 / 16
F25T8
3 277 58 0.22 A 0.66 1.13 95 1.7 15 0 / -18
3 120 54 0.45 A 0.74 1.37 99 1.7 10 0 / -18
2 120 41 0.35 A 0.82 2.00 98 1.7 10 0 / -18
2 277 0.158 90.0 A 0.82 1.7 15 0 / -18
Other compatible lamps: F17T8, F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
3 120 67 0.58 A 0.60 0.89 98 1.7 10 0 / -18
3 277 66 0.26 A 0.60 0.90 93 1.7 10 0 / -18
2 277 50 0.21 A 0.64 1.28 92 1.7 10 0 / -18
2 120 49 0.42 A 0.64 1.30 98 1.7 10 0 / -18
F32T8/WM
3 120 61 0.53 A 0.59 0.96 99 1.7 10 60 / 16
3 277 60 0.24 A 0.59 0.98 94 1.7 10 60 / 16
2 120 45 0.04 A 98 1.7 10 60 / 16
2 277 45 0.18 A 0.64 1.42 92 1.7 10 60 / 16
F28T8
3 120 57 0.49 A 0.58 1.01 99 1.7 10 60 / 16
3 277 56 0.22 A 0.58 1.03 94 1.7 10 60 / 16
2 120 42 0.35 A 98 1.7 10 60 / 16
2 277 42 0.17 A 0.63 1.50 91 1.7 10 60 / 16
F25T8
3 120 53 0.45 A 0.60 1.13 98 1.7 10 0 / -18
3 277 53 0.21 A 0.60 1.13 92 1.7 13 0 / -18
2 120 40 0.35 A 0.64 1.60 98 1.7 10 0 / -18
2 277 40 0.16 A 0.64 1.60 89 1.7 14 0 / -18
Other compatible lamps: F17T8, F32T8/25W
UL Type 1 Outdoor UL Type HL RoHS Compliant FCC – CLASS A Non-Consumer ANSI – C62.41 UL Class P cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL RoHS Compliant FCC – CLASS A Non-Consumer ANSI – C62.41 UL Class P cUL Listed UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL RoHS Compliant FCC – CLASS A Non-Consumer UL Class P ANSI – C62.41 cUL Listed UL Listed
Safety and performance
66 See page 195 for warranty information. 67
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
29625 – GE-432-120-PS-N
UltraStart® T8 Programmed Start
4 – F32T8 120V Normal Light .87 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS4 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Blue/White 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29625 29635
29627 – GE-432-277-PS-N
UltraStart® T8 Programmed Start
4 – F32T8 277V Normal Light .87 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS4 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Blue/White 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29627 29650
96716 – GE432-MVPS-N
UltraStart® T8 Programmed Start
4 F32T8 120V-277V Normal Light .88 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Rapid start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency (MIN) 50 Hz/ 60 Hz
Dimensions
Wiring diagram – LFL PS4 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Blue/White 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Anti-striation control for better light quality, with no striations
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Multi-voltage technology handles voltage from 120 to 277V
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
96716 96719
71832 – GE432-MVPS-L
UltraStart® T8 Programmed Start
4 – F32T8 120V-277V Low Watts .71 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Low – PS
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Anti-striation control, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz
Supply Current Frequency (MIN) 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS4 – see example on page 73
Case dimensions – Ref Drawing -A – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.18 in (30.00 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.1 in (28.70 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Blue/White 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Anti-striation control for better light quality, with no striations
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Multi-voltage technology handles voltage from 120 to 277V
• Parallel lamp operation means system maintenance is easier to manage
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 112 0.95 A 0.89 0.79 99 1.7 10 0 / -18
3 120 92 0.79 A 0.96 1.04 99 1.7 10 0 / -18
F32T8/WM
4 120 106 0.92 A 0.87 0.82 99 1.7 10 60 / 16
3 120 87 0.75 A 0.94 1.08 99 1.7 10 60 / 16
F28T8
4 120 96 0.83 A 0.84 0.87 99 1.7 10 60 / 16
3 120 79 0.68 A 0.91 1.15 99 1.7 10 60 / 16
F25T8
4 120 87 0.75 A 0.88 1.01 99 1.7 10 0 / -18
3 120 73 0.63 A 0.95 1.30 99 1.7 10 0 / -18
F17T8
4 120 61 0.53 A 0.89 1.45 99 1.7 10 50 / 10
3 120 51 0.44 A 0.96 1.88 99 1.7 10 0 / -18
Other compatible lamps: F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 277 112 0.42 A 0.89 0.79 99 1.7 10 0 / -18
3 277 93 0.35 A 0.96 1.03 98 1.7 10 0 / -18
F32T8/WM
4 277 103 0.39 A 0.86 0.83 98 1.7 10 60 / 16
3 277 85 0.32 A 0.94 1.10 98 1.7 10 60 / 16
F28T8
4 277 93 0.35 A 0.84 0.90 98 1.7 10 60 / 16
3 277 77 0.29 A 0.91 1.18 98 1.7 10 60 / 16
F25T8
4 277 88 0.33 A 0.88 1.00 97 1.7 10 0 / -18
3 277 72 0.28 A 0.95 1.31 98 1.7 10 0 / -18
F17T8
4 277 62 0.24 A 0.88 1.41 97 1.7 10 0 / -18
3 277 51 0.20 A 0.95 1.86 96 1.7 11 0 / -18
Other compatible lamps: F32T8/25W
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 114 0.97 A 0.89 0.78 99 1.7 10 0 / -18
4 277 112 0.41 A 0.89 0.79 97 1.7 10 0 / -18
3 120 93 0.78 A 0.96 1.03 98 1.7 10 0 / -18
3 277 92 0.34 A 0.96 1.04 95 1.7 10 0 / -18
F32T8/WM
4 120 105 0.88 A 0.86 0.81 99 1.7 10 60 / 16
4 277 103 0.37 A 0.86 0.83 97 1.7 10 60 / 16
3 120 86 0.72 A 0.94 1.09 98 1.7 10 60 / 16
3 277 85 0.31 A 0.94 1.10 95 1.7 10 60 / 16
F28T8
4 120 96 0.81 A 0.83 0.86 99 1.7 10 60 / 16
4 277 95 0.35 A 0.83 0.87 97 1.7 10 60 / 16
3 120 79 0.66 A 0.92 1.16 98 1.7 10 60 / 16
3 277 78 0.29 A 0.92 1.17 95 1.7 10 60 / 16
Other compatible lamps: F17T8, F25T8, F32T8/25W
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71832
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 90 0.39 A 0.71 0.78 1 1.7 10 0 / -18
4 277 88 0.32 A 0.71 0.80 1 1.7 10 0 / -18
3 120 72 0.68 A 0.58 0.81 1 1.7 10 0 / -18
3 277 71 0.78 A 0.58 0.82 1 1.7 10 0 / -18
F32T8/WM
4 120 85 0.71 A 0.69 0.81 1 1.7 10 60 / 16
4 277 83 0.30 A 0.69 0.83 1 1.7 10 60 / 16
3 120 68 0.58 A 0.57 0.84 1 1.7 10 60 / 16
3 277 67 0.26 A 0.57 0.85 1 1.7 10 60 / 16
F28T8
4 120 77 0.64 A 0.68 0.88 1 1.7 10 60 / 16
4 277 76 0.28 A 0.68 0.89 1 1.7 10 60 / 16
3 120 63 0.53 A 0.55 0.88 1 1.7 10 60 / 16
3 277 63 0.23 A 0.55 0.88 1 1.7 10 60 / 16
Other compatible lamps: F17T8, F25T8, F32T8/25W
RoHS Compliant UL Type 1 Outdoor UL Type HL ANSI – C62.41 FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor UL Type HL ANSI – C62.41 FCC – CLASS A Non-Consumer UL Class P UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed
Safety and performance
68 See page 195 for warranty information. 69
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
UltraStart® T8 Programmed Start
T8 Programmed Start Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
T8 Dimming
T8 Dimming Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
29678 – GE-432-MVPS-H
UltraStart® T8 Programmed Start
4 – F32T8 120V-277V High Light 1.15 BF <10% THD UltraStart®
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor High
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS4 – see example on page 73
Case dimensions – Ref Drawing LG – see page 75
Length (L) 11.75 in (298.45 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.6 in (41.91 mm)
Mounting dimensions
Mount Length (M) 11.1 in (282.97 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.10 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Blue/White 33 in (838 mm)
Red/White 33 in (838 mm)
Yellow 48 in (1219 mm)
• A new generation of ultra-efficient Programmed Start ballasts (> 90% efficiency)
• Extends lamp life in frequently switched applications (> 100,000 on/off cycles)
• Starting time visually the same as instant start
• Multi-voltage technology handles voltage from 120 to 277V (H and XL series)
• Parallel lamp operation means system maintenance is easier to manage
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29678 29657
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8
4 120 147 1.27 A 1.16 0.78 98 1.7 10 0 / -18
4 277 144 0.55 A 1.16 0.80 96 1.7 10 0 / -18
3 120 120 1.03 A 1.26 1.05 98 1.7 10 0 / -18
3 277 120 0.45 A 1.26 1.05 96 1.7 10 0 / -18
F32T8/WM
4 120 139 1.20 A 1.15 0.82 97 1.7 10 60 / 16
4 277 136 0.52 A 1.15 0.84 97 1.7 10 60 / 16
3 120 114 0.95 A 98 1.7 10 60 / 16
3 277 112 0.43 A 1.24 1.10 97 1.7 10 60 / 16
F28T8
4 120 125 1.08 A 1.12 0.89 97 1.7 10 60 / 16
4 277 123 0.47 A 1.12 0.91 97 1.7 10 60 / 16
3 120 103 0.86 A 98 1.7 10 60 / 16
3 277 101 0.39 A 1.21 1.19 97 1.7 10 60 / 16
F25T8
4 120 117 1.00 A 1.15 0.98 98 1.7 10 0 / -18
4 277 115 0.44 A 1.15 1.00 96 1.7 16 0 / -18
3 120 97 0.83 A 1.23 1.26 98 1.7 10 0 / -18
3 277 96 0.37 A 1.23 1.28 96 1.7 15 0 / -18
F17T8
4 120 81 0.69 A 1.15 1.41 98 1.7 10 0 / -18
4 277 80 0.31 A 1.15 1.43 95 1.7 16 0 / -18
3 120 67 0.58 A 1.23 1.83 98 1.7 10 0 / -18
3 277 67 0.26 A 1.23 1.83 95 1.7 15 0 / -18
Other compatible lamps: F32T8/25W
80353 – B132R120V5
T8 Dimming Ballasts
1 – F32T8 DIM 100 to 5% RS 120
General characteristics
Ballast Type Electronic – Dimming
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 18b – see example on page 74
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.30 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 51 in (1295 mm)
Gray and Violet 33 in (838 mm)
White and Black 25 in (635 mm)
• Integrate dimming ballasts with daylight harvesting for significant energy savings
• Greater control of workspace lighting, ability to create a mood, energy savings
• Designed to ensure optimum lamp performance with lamp current crest factor below the
1.7 ANSI standard
• Start lamps according to ANSI recommendations throughout the entire dimming range
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80353
80355 – B232SR120V5
T8 Dimming Ballasts
2 – F32T8 DIM 100 to 5% RS 120
General characteristics
Ballast Type Electronic – Dimming
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 19 – see example on page 74
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.30 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 33 in (838 mm)
Gray and Violet 33 in (838 mm)
White and Black 25 in (635 mm)
Yellow 51 in (1295 mm)
• Integrate dimming ballasts with daylight harvesting for significant energy savings
• Greater control of workspace lighting, ability to create a mood, energy savings
• Designed to ensure optimum lamp performance with lamp current crest factor below the
1.7 ANSI standard
• Start lamps according to ANSI recommendations throughout the entire dimming range
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80355
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 1 120 32 0.26 A 0.88 2.75 99 1.6 10 50 / 10
F25T8 1 120 26 0.21 A 0.90 3.46 99 1.6 10 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 2 120 62 0.52 A 0.88 1.41 99 1.6 10 50 / 10
RoHS Compliant ANSI – C62.41 UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed CSA
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed CSA
Safety and performance
70 See page 195 for warranty information. 71
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T8 Dimming
T8 Dimming Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
T8 Dimming
T8 Dimming Ballasts For F17 (2 ft), F25 (3 ft), F32 (4 ft) Lamps
80362 – B232SR277S50
T8 Dimming Ballasts
2 – F32T8 Switch 100/50% RS 277
General characteristics
Ballast Type Electronic – Dimming
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 16 – see example on page 74
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.30 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Black/White 25 in (635 mm)
• Integrate dimming ballasts with daylight harvesting for significant energy savings
• Greater control of workspace lighting, ability to create a mood, energy savings
• Designed to ensure optimum lamp performance with lamp current crest factor below the
1.7 ANSI standard
• Start lamps according to ANSI recommendations throughout the entire dimming range
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80362
80356 – B232SR277V5
T8 Dimming Ballasts
2 – F32T8 DIM 100 to 5% RS 277
General characteristics
Ballast Type Electronic – Dimming
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 19 – see example on page 74
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.30 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 33 in (838 mm)
Gray and Violet 33 in (838 mm)
White and Black 25 in (635 mm)
Yellow 51 in (1295 mm)
• Integrate dimming ballasts with daylight harvesting for significant energy savings
• Greater control of workspace lighting, ability to create a mood, energy savings
• Designed to ensure optimum lamp performance with lamp current crest factor below the
1.7 ANSI standard
• Start lamps according to ANSI recommendations throughout the entire dimming range
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80356
80357 – B332SR120V5
T8 Dimming Ballasts
3 – F32T8 DIM 100 to 5% RS 120
General characteristics
Ballast Type Electronic – Dimming
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 20 – see example on page 74
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.30 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Gray and Violet 33 in (838 mm)
Blue and Red 36 in (914 mm)
Red/White 36 in (914 mm)
White and Black 25 in (635 mm)
Yellow 36 in (914 mm)
• Integrate dimming ballasts with daylight harvesting for significant energy savings
• Greater control of workspace lighting, ability to create a mood, energy savings
• Designed to ensure optimum lamp performance with lamp current crest factor below the
1.7 ANSI standard
• Start lamps according to ANSI recommendations throughout the entire dimming range
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80357
80358 – B332SR277V5
T8 Dimming Ballasts
3 – F32T8 DIM 100 to 5% RS 277
General characteristics
Ballast Type Electronic – Dimming
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 20 – see example on page 74
Case dimensions – Ref Drawing ST – see page 75
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.30 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Gray and Violet 33 in (838 mm)
Blue and Red 36 in (914 mm)
Red/White 36 in (914 mm)
White and Black 25 in (635 mm)
Yellow 36 in (914 mm)
• Integrate dimming ballasts with daylight harvesting for significant energy savings
• Greater control of workspace lighting, ability to create a mood, energy savings
• Designed to ensure optimum lamp performance with lamp current crest factor below the
1.7 ANSI standard
• Start lamps according to ANSI recommendations throughout the entire dimming range
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80358
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 2 277 62 0.23 A 0.88 1.41 99 1.7 10 50 / 10
F25T8 2 277 48 0.18 A 0.88 1.83 99 1.7 10 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 2 277 62 0.22 A 0.88 1.41 1.6 10 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 3 120 92 0.77 A 0.88 0.95 99 1.5 10 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor% (>=) Crest Factor (<=) THD% (<=) Min. Starting Temp (°F/°C)
F32T8 3 277 92 0.33 A 0.88 0.95 99 1.5 10 50 / 10
UL Type 1 Outdoor Canadian Energy Standards UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed CSA
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed CSA
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed CSA
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed CSA
Safety and performance
72 See page 195 for warranty information. 73
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Wiring Diagrams
T8 Fluorescent Ballasts
Wiring Diagrams
T8 Fluorescent Ballasts
LFL 1A LFL 1B LFL 4a LFL PS2
LFL PS3 LFL PS4LFL 1C LFL 1D
74 See page 195 for warranty information. 75
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Case Dimensions
T8 Fluorescent Ballasts
-A
ST
LG
Wiring Diagrams
T8 Fluorescent Ballasts
LFL 18b LFL 19
LFL 16 LFL 20
77
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information. *T5 lamp lengths are noted to nearest foot and are not exact lengths as noted in feet. See GE Lamp Catalog for exact lamp length.
T5 High Efficiency – Programmed Start
T5 Electronic Programmed Start For F14 (2 ft), F21 (3 ft), F28 (4 ft), F35 (5 ft) HE T5 Lamps*
99653 – GE228MVPSH-A
T5 High Efficiency - UltraStart® Programmed Start
2 or 1 – F14-F28T5HE, 120 to 277 UltraStart® PRS High Light 1.15 BF A Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor High (1.15)
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Universal voltage, Anti-striation control
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 4a – see example on page 82
Case dimensions – Ref Drawing -A Can – see page 83
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.2 in (30.48 mm)
Mounting dimensions
Mount Length (M) 8.9 in (226.06 mm)
Mount Slots (MS) 0.3 in (6.35 mm)
Weight 1.49 lbs
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 34 in (864 mm)
Green 3.5 in (89 mm)
Yellow 45 in (1143 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
99653 99654
99655 – GE228MVPS-A
T5 High Efficiency - UltraStart® Programmed Start
2 or 1 – F14-F35T5HE, 120 – 277 UltraStart® PRS Normal Light - .95 BF A Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Universal voltage, Anti-striation control
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 4a – see example on page 82
Case dimensions – Ref Drawing -A Can – see page 83
Length (L) 9.5 in (241.30 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.2 in (30.48 mm)
Mounting dimensions
Mount Length (M) 8.9 in (226.06 mm)
Mount Slots (MS) 0.3 in (6.35 mm)
Weight 1.49 lbs
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 34 in (864 mm)
Green 3.5 in (89 mm)
Yellow 45 in (1143 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
99655 99656
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F35T5/HE
2 120 75 0.62 A 99 1.7 10 5 / -15
2 277 73 0.27 A 97 1.7 9 5 / -15
1 120 46 0.39 A 99 1.7 10 5 / -15
1 277 46 0.18 A 93 1.7 10 5 / -15
F28T5/HE
2 120 60 0.50 A 0.96 1.60 99 1.7 10 5 / -15
2 277 59 0.23 A 0.96 1.63 96 1.7 9 5 / -15
1 120 38 0.31 A 1.09 2.87 99 1.7 10 5 / -15
1 277 38 0.15 A 1.09 2.87 91 1.7 10 5 / -15
F28T5/WM
2 120 57 0.48 A 0.95 1.67 99 1.7 10 5 / -15
2 277 57 0.21 A 0.95 1.67 95 1.7 10 5 / -15
1 120 36 0.30 A 99 1.7 10 5 / -15
1 277 36 0.15 A 90 1.7 10 5 / -15
Other compatible lamps: F21T5/HE, F21T5/WM, F14T5/HE, F14T5/WM, F35T5/WM, F28T5/HL
UL Type CC UL Type 1 Outdoor UL Listed UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed Meets ANSI Standard C62.41-1991
RoHS Compliant Meets ANSI Standard C82.11- cons 2002
Safety and performance
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F28T5/HE
2 120 72 0.60 A 1.16 1.61 99 1.7 10 5 / -15
2 277 70 0.25 A 1.16 1.66 97 1.65 9 5 / -15
1 120 45 0.37 A 1.36 3.02 99 1.7 10 5 / -15
1 277 45 0.17 A 1.36 3.02 93 1.7 10 5 / -15
F28T5/WM
2 120 68 0.57 A 99 1.7 10 5 / -15
2 277 67 0.25 A 96 1.7 10 5 / -15
F21T5/HE
2 120 57 0.47 A 99 1.7 10 5 / -15
2 277 56 0.21 A 95 1.7 10 5 / -15
1 120 36 0.30 A 99 1.7 10 5 / -15
1 277 36 0.14 A 90 1.7 10 5 / -15
F28T5WM
1 120 43 0.36 A 99 1.7 10 5 / -15
1 277 43 0.17 A 92 1.7 10 5 / -15
Other compatible lamps: F28T5/WM, F14T5/HE, F14T5/WM, F21T5/WM, F28T5/HL
• High Efficiency T5 ballast with Continuous Cathode Cutout Technology
• Lower Maintenance Costs with Parallel Lamp Operation
• Fast Starting Time <700ms
• Multi-Voltage technology means a single ballast handles voltage from 108V to 305V
• Auto-Restart withstands temporary losses in power without the need to cycle power
• UltraCool Operation 90C case rating
• High Efficiency T5 ballast with Continuous Cathode Cutout Technology
• Lower Maintenance Costs with Parallel Lamp Operation
• Fast Starting Time <700ms
• Multi-Voltage technology means a single ballast handles voltage from 108V to 305V
• Auto-Restart withstands temporary losses in power without the need to cycle power
• UltraCool Operation 90C case rating
UL Type CC UL Type 1 Outdoor UL Listed UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed Meets ANSI Standard C62.41-1991
RoHS Compliant Meets ANSI Standard C82.11- cons 2002
Safety and performance
Understanding T5
Electronic Programmed Start Ballasts
UltraStart® T5 programmed start ballasts for T5uorescent lamps.
GE has developed a line of T5 ballasts that incorporate the benefits of programmed start
ballasts with the energy savings, fast starting and parallel lamp operation of instant start
ballasts. GE’s UltraStart® T5 ballasts use low energy loss, high efficiency components along
with continuous cathode cutout (CCC) technology—resulting in 8 fewer watts than standard
4-lamp 54 watt T5 ballasts. GE’s UltraStart® T5 ballasts offer a 44% improvement over
standard T5 ballasts and create a new industry threshold for high efficiency ballasts.
The GE UltraStart® Watt-Miser® T5 Lamp and Ballast System Advantage
• 18 watts lower than standard 4-lamp, 54 watt T5 systems with the same light output
• Operates lamps in parallel (which means if one lamp fails, the other lamps remain on)
– significantly reduces lamp maintenance costs
• Fast starting programmed start ballast < 700 milliseconds compared to standard
T5 at > 1.1 to 1.5 seconds
GE UltraStart® T5 programmed start ballasts use a control circuit to apply very precise
cathode heat to ensure lamp cathodes have reached optimum temperature during lamp
starting. Precise starting reduces the amount of cathode degradation associated with
each start and increases lamp life significantly. After starting the lamps, continuous cathode
cutout technology (CCC) is applied—which eliminates wasted power to the lamps, resulting
in high efficiencies. GE UltraStart® systems also have the advantage of operating lamps in
parallel. Parallel (versus series) lamp operation ballasts typically reduce spot relamping costs by
50% or extend group relamping by 15% or more due to average lamp mortality early failures.
T5 Lamps
GE T5 lamps can be electrically characterized into two groups:
High Efficiency (HE) Lamps (F14T5, F21T5, F28T5, F35T5 – standard, high-lumen
and Watt-Miser®)
These lamps are high efficiency (HE), delivering around 100 lumens per watt and, while
operating at the same lamp arc current, can be operated on the same ballast if the ballast
system power and starting voltage are appropriate for the lamp load.
High Output (HO) Lamps (F24T5, F39T5, F54T5, F49T5, F80T5 – standard and Watt-Miser®)
These lamps are driven for high light output and are slightly less efficient (LPW) than HE lamps.
They have unique lamp arc currents and starting voltages by wattage that require a specific
ballast for each HO lamp wattage.
76 See T8 ballast section (page 37) for nomenclature information.
78 See page 195 for warranty information. 79
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information. *T5 lamp lengths are noted to nearest foot and are not exact lengths as noted in feet. See GE Lamp Catalog for exact lamp length.
• Electronic ballasts for all general fluorescent applications
• Extends lamp life in frequently switched applications
• Reduced lamp replacement cost; ideal for use with occupancy sensors
T5 High Efficiency – Programmed Start
T5 Electronic Programmed Start For F14 (2 ft), F21 (3 ft), F28 (4 ft), F35 (5 ft) HE T5 Lamps*
47536 – B228PUNV-C0G1C
T5 High Efficiency - Programmed Start
2 – F28T5 PRS UNV 50/60 Hz, C Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 4b – see example on page 82
Case dimensions – Ref Drawing -C Can – see page 83
Length (L) 14.25 in (361.95 mm)
Width (W) 1.2 in (29.97 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Mount Length (M) 13.75 in (349.25 mm)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight 1.00 lb
Exit Type Poke-in
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Order information
10 Pack Pallet Pack DIY Pack IP Pack
47536
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F35T5/HE
2 120 81 0.67 A 0.98 1.20 1.7 10 0 / -18
2 277 78 0.28 A 0.98 1.25 1.7 10 0 / -18
1 120 40 0.34 A 0.98 2.45 1.7 10 0 / -18
1 277 40 0.15 A 0.95 2.37 1.7 10 0 / -18
F28T5/HE
2 120 66 0.55 A 0.98 1.48 1.7 10 0 / -18
2 277 64 0.23 A 0.98 1.53 1.7 10 0 / -18
1 120 33 0.28 A 0.98 2.96 1.7 10 0 / -18
1 277 33 0.12 A 0.95 2.87 1.7 10 0 / -18
F21T5/HE
2 120 49 0.41 A 0.98 2.00 1.7 10 0 / -18
2 277 48 0.17 A 0.98 2.04 1.7 10 0 / -18
1 120 25 0.21 A 0.98 3.92 1.7 10 0 / -18
F14T5/HE
2 120 34 0.28 A 0.98 2.88 1.7 10 0 / -18
2 277 34 0.12 A 0.95 2.79 1.7 10 0 / -18
1 120 18 0.15 A 0.98 5.44 1.7 10 0 / -18
1 277 18 0.07 A 0.95 5.27 1.7 15 0 / -18
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
47540 – B239PUNV-DOG1C
T5 High Output - Programmed Start
2 – F39T5HO PRS UNV 50/60 Hz D Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagrams – LFL 4b – see example on page 82
Case dimensions – Ref Drawing -D Can – see page 83
Length (L) 16.9 in (428.75 mm)
Width (W) 1.2 in (29.97 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Mount Length (M) 16.2 in (411.48 mm)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight
Exit Type Poke-in
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Order information
10 Pack Pallet Pack DIY Pack IP Pack
47540
T5 High Output – Programmed Start
T5 Electronic Programmed Start For F24 (2 ft), F39 (3 ft), F54 (4 ft), F80 (5 ft) HO T5 Lamps*
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F39T5/HO
2 120 89 0.74 A 0.98 1.10 1.7 10 0 / -18
2 277 88 0.32 A 0.98 1.11 1.7 10 0 / -18
1 120 47 0.39 A 0.98 2.08 1.7 10 0 / -18
1 277 47 0.17 A 0.95 2.02 1.7 10 0 / -18
FT39W/4P
2 120 71 0.59 A 0.98 1.38 97 1.7 10 0 / -18
2 277 70 0.25 A 0.95 1.35 97 1.7 10 0 / -18
1 120 38 0.31 A 0.98 2.57 1.7 10 0 / -18
1 277 38 0.14 A 0.90 2.36 1.7 10 0 / -18
F24T5/HO
2 120 59 0.51 A 0.98 1.66 1.7 10 0 / -18
2 277 59 0.22 A 0.95 1.61 1.7 10 0 / -18
1 120 32 0.26 A 0.98 3.06 1.7 10 0 / -18
1 277 32 0.12 A 0.90 2.81 1.7 10 0 / -18
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
• Electronic ballasts for all general fluorescent applications
• Extends lamp life in frequently switched applications
• Reduced lamp replacement cost; ideal for use with occupancy sensors
47534 – B224PUNV-COG1C
T5 High Output - Programmed Start
2 – F24T5HO PRS UNV 50/60 Hz C Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 75°C (167°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 4b – see example on page 82
Case dimensions – Ref Drawing -C Can – see page 83
Length (L) 14.3 in (361.95 mm)
Width (W) 1.2 in (29.97 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Mount Length (M) 13.8 in (349.25 mm)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight 1.0 lb
Exit Type Poke-in
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Order information
10 Pack Pallet Pack DIY Pack IP Pack
47534
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F24T5/HO
2 120 53 0.45 A 0.98 1.84 1.7 10 0 / -18
2 277 52 0.19 A 0.98 1.88 1.7 10 0 / -18
1 120 28 0.23 A 0.98 3.50 1.7 10 0 / -18
1 277 28 0.10 A 0.95 3.39 1.7 10 0 / -18
FT24W/4P
2 120 52 0.43 A 0.98 1.88 1.7 10 0 / -18
2 277 51 0.18 A 0.98 1.92 1.7 10 0 / -18
1 120 27 0.22 A 0.98 3.62 1.7 10 0 / -18
1 277 27 0.10 A 0.95 3.51 1.7 15 0 / -18
FT24W/2G10
2 120 48 0.40 A 0.98 2.04 1.7 10 0 / -18
2 277 47 0.17 A 0.98 2.08 1.7 10 0 / -18
1 120 24 0.20 A 0.98 4.08 1.7 10 0 / -18
1 277 24 0.09 A 0.95 3.95 1.7 15 0 / -18
F39T5/HO
1 120 41 0.34 A 0.98 2.39 95 1.7 10 0 / -18
1 277 40 0.15 A 0.98 2.45 95 1.7 10 0 / -18
FT36W/4P
1 120 36 0.30 A 0.98 2.72 95 1.7 10 0 / -18
1 277 36 0.13 A 0.95 2.63 95 1.7 10 0 / -18
Other compatible lamps: F36W/2G10
• Electronic ballasts for all general fluorescent applications
• Extends lamp life in frequently switched applications
• Reduced lamp replacement cost; ideal for use with occupancy sensors
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
80 See page 195 for warranty information. 81
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information. *T5 lamp lengths are noted to nearest foot and are not exact lengths as noted in feet. See GE Lamp Catalog for exact lamp length.
T5 High Output – Programmed Start
T5 Electronic Programmed Start For F24 (2 ft), F39 (3 ft), F54 (4 ft), F80 (5 ft) HO T5 Lamps*
99651 – GE254MVPS90-F
T5 High Output - UltraStart® Programmed Start
2 or 1 – F54T5HO 120 to 277V UltraStart® PRS High Temp F Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Universal voltage, Anti-striation control
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 4a, LFL 4b – see example on page 82
Case dimensions – Ref Drawing -F – see page 83
Length (L) 11.8 in (298.45 mm)
Width (W) 1.7 in (43.18 mm)
Height (H) 1.2 in (30.48 mm)
Mounting dimensions
Mount Length (M) 11.1 in (282.95 mm)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight 1.85 lbs
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 34 in (864 mm)
Yellow 45 in (1143 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
99651 99652
47542 – B254PUNV-DGE1C
T5 High Output - UltraStart® Programmed Start
2 – F54T5HO PRS UNV 50/60 Hz D Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 4b – see example on page 82
Case dimensions – Ref Drawing -D Can – see page 83
Length (L) 16.8 in (428.75 mm)
Width (W) 1.1 in (29.97 mm)
Height (H) 1.2 in (30.48 mm)
Mounting dimensions
Mount Length (M) 16.2 in (411.48 mm)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight
Exit Type Poke-in
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Order information
10 Pack Pallet Pack DIY Pack IP Pack
47542
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT50W/4P
2 120 117 0.99 A 99 1.7 1 5 / -15
2 277 115 0.43 A 0.98 1.53 98 1.7 1 5 / -15
1 120 72 0.61 A 0.98 2.96 99 1.7 10 5 / -15
1 277 72 0.27 A 0.95 2.87 97 1.7 1 5 / -15
F54T5/HO
2 120 116 0.98 A 1.00 0.86 99 1.68 4.6 5 / -15
2 277 115 0.43 A 1.00 0.87 98 1.68 7.9 5 / -15
1 120 71 0.60 A 99 1.7 10 5 / -15
1 277 71 0.26 A 97 1.7 10 5 / -15
F54T5WM
2 120 109 0.91 A 1.00 0.92 99 1.7 10 5 / -15
2 277 107 0.40 A 1.00 0.93 97 1.7 10 5 / -15
1 120 66 0.56 A 1.12 1.70 99 1.7 10 5 / -15
1 277 66 0.25 A 1.12 1.70 97 1.7 10 5 / -15
Other compatible lamps: FC12T5HO, F58T8, FT39W/4P, FT55W/4P
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F54T5/HO
2 120 120 1.03 A 1.00 0.83 99 1.7 10 0 / -18
2 277 117 0.43 A 1.00 0.85 98 1.7 10 0 / -18
1 120 63 0.52 A 1.02 1.61 99 1.7 10 0 / -18
1 277 62 0.23 A 1.02 1.64 95 1.7 10 0 / -18
FC12T5-55W
2 120 106 0.88 A 0.85 0.80 99 1.7 10 0 / -18
2 277 103 0.38 A 0.85 0.82 98 1.7 10 0 / -18
1 120 56 0.46 A 0.87 1.55 99 1.7 10 0 / -18
1 277 56 0.21 A 0.87 1.55 95 1.7 10 0 / -18
FT36W/4P
2 120 90 0.75 A 1.20 1.33 99 1.7 10 0 / -18
2 277 88 0.32 A 1.20 1.36 98 1.7 10 0 / -18
1 120 44 0.37 A 1.22 2.77 99 1.7 10 0 / -18
1 277 44 0.17 A 1.22 2.77 90 1.7 10 0 / -18
FT55W/4P
1 120 60 0.50 A 1.12 1.86 99 1.7 10 0 / -18
1 120 60 0.48 A 0.92 1.53 99 1.7 10 0 / -18
UL Type 1 Outdoor UL Type CC UL Listed UL Type HL Meets ANSI Standard C62.41-1991 UL Class P Meets ANSI Standard C82.11- cons 2002 RoHS Compliant
FCC – CLASS A Non-Consumer
Safety and performance
• Electronic ballasts for all general fluorescent applications
• Extends lamp life in frequently switched applications
• Reduced lamp replacement cost; ideal for use with occupancy sensors
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P UL Listed CSA
Safety and performance
• High Efficiency T5 ballast with Continuous Cathode Cutout Technology
• Lower Maintenance Costs with Parallel Lamp Operation
• Fast Starting Time <700ms
• Multi-Voltage technology means a single ballast handles voltage from 108V to 305V
• Auto-Restart withstands temporary losses in power without the need to cycle power
• UltraCool Operation 90C case rating
99649 – GE454MVPS90-E
T5 High Output - UltraStart® Programmed Start
4 – 1 – F54T5HO 120 – 277 UltraStart® PRS High Temp E Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
Auto-restart, End-of-Life Protection (EOL), Thermally protected,
Anti-striation control
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 4c – see example on page 82
Case dimensions – Ref Drawing -E – see page 83
Length (L) 16.7 in (424.0 mm)
Width (W) 1.7 in (43.2 mm)
Height (H) 1.36 in (34.5 mm)
Mounting dimensions
Mount Length (M) 16.10 in (408.70 mm)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight 3.15 lb
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black, White and Grey 25 in (636 mm)
Red and Blue 34 in (863 mm)
Red/White and Blue/White 34 in (863 mm)
Yellow and Orange 45 in (1140 mm)
Green 3.5 in (90 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
99649 99650
T5 High Output – Programmed Start
T5 Electronic Programmed Start For F24 (2 ft), F39 (3 ft), F54 (4 ft), F80 (5 ft) HO T5 Lamps*
29726 – GE454MVPSN1
T5 High Output - UltraStart® Programmed Start
4, 3, 2 or 1 – F54T5HO 120 to 277 UltraStart® PRS J Can
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Programmed start
Lamp Wiring Series – parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, End-of-Life Protection (EOL), Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagrams – LFL 62-1, LFL 62-2, LFL 62-3 – see example on page 82
Case dimensions – Ref Drawing -J – see page 83
Length (L) 24 in (609.60 mm)
Width (W) 1.2 in (31.49 mm)
Height (H) 1.1 in (29.97 mm)
Mounting dimensions
Mount Length (M) 23.5 in (597.99 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.78 lbs
Exit Type Poke-in
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Order information
10 Pack Pallet Pack DIY Pack IP Pack
29726 29717
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F54T5/HO
4 120 238 2.00 A 1.00 0.42 99 1.4 8 0 / -18
4 277 233 0.86 A 1.00 0.42 99 1.4 8 0 / -18
3 120 185 1.52 A 99 1.4 8 0 / -18
3 277 182 0.66 A 99 1.4 8 0 / -18
2 120 122 0.99 A 99 1.4 8 0 / -18
2 277 120 0.43 A 98 1.4 12 0 / -18
1 277 65 0.24 A 95 1.4 14 0 / -18
1 120 64 0.52 A 99 1.4 12 0 / -18
RoHS compliant UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer ANSI-C62.41 UL Class P cUL Listed UL Type CC UL Listed
Safety and performance
RoHS Compliant UL Type 1 Outdoor UL Type CC ANSI – C62.41 UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
• Electronic ballasts for all general fluorescent applications
• Extends lamp life in frequently switched applications
• Reduced lamp replacement cost; ideal for use with occupancy sensors
• Slim profile housing
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F54T5WM
4 277 216 0.79 A 1.00 0.46 0.98 1.63 7 5 / -15
3 277 174 0.66 A 1.01 0.58 0.95 1.62 9 5 / -15
2 277 117 0.48 A 0.96 0.82 0.90 1.61 11 5 / -15
1 277 77 0.34 A 1.12 1.46 0.81 1.56 16 5 / -15
4 120 220 1.84 A 0.96 0.44 0.99 1.64 6 5 / -15
3 120 177 1.48 A 1.00 0.56 0.99 1.62 7 5 / -15
2 120 118 0.99 A 0.96 0.81 0.99 1.60 10 5 / -15
1 120 77 0.64 A 1.12 1.46 0.99 1.55 13 5 / -15
F54T5HO
4 277 226 0.83 A 1.00 0.44 0.98 1.64 7 5 / -15
3 277 185 0.69 A 1.01 0.55 0.97 1.62 8 5 / -15
2 277 121 0.49 A 0.96 0.80 0.89 1.63 12 5 / -15
1 277 78 0.35 A 1.12 1.43 0.81 1.56 14 5 / -15
4 120 232 1.94 A 0.96 0.41 0.99 1.65 6 5 / -15
3 120 188 1.58 A 1.00 0.53 0.99 1.64 8 5 / -15
2 120 121 1.024 A 0.96 0.79 0.99 1.62 9 5 / -15
1 120 82 0.69 A 1.12 1.36 0.99 1.55 12 5 / -15
Other compatible lamps: FT55W/4P, FT50W/4P, FT39W/4P, FC12T5HO, F58T8
• Lower Maintenance Costs with Parallel Lamp Operation
• Fast starting time <700 ms
• Auto Restart withstands temporary losses in power without the need to cycle power
• UltraCool Operation 90C case rating
• Bi-Level Switching
• Anti-striation control for better light quality, with no striations
82 See page 195 for warranty information. 83
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information. *T5 lamp lengths are noted to nearest foot and are not exact lengths as noted in feet. See GE Lamp Catalog for exact lamp length.
Wiring Diagrams
T5 Fluorescent Ballasts
LFL 4a LFL 4b
LFL 4c LFL 62-1
LFL 62-2
LFL 62-3
Case Dimensions
T5 Fluorescent Ballasts
-A Can, -E, -F
-D Can
-J
-C Can
R
R
Y
Y
B
B
G
N
L
16.88”
16.28”
1.18”
1.00”
0.59”
R
R
Y
Y
B
B
G
N
L
14.25”
13.75”
1.18”
1.00”
0.59”
See page 195 for warranty information. 85
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
GE Ballast LFL magnetic nomenclature
GEM-2 32-HO-RS-120-DIY
Maximum number of
lamps supported by
this ballast: 1, 2, 3, 4
HO = High Output
VHO = Very High Output
Lamp Watts
(Primary Lamp)
T8 = 32 – 4 foot,
59 – 8 foot
T12 = 40 – 4 foot,
60 – 8 foot
T12 Electronic =
40 – 2-4 foot, 2 pin
60 – 4-8 foot, 1 pin
96 – 4-8 foot HO,
2 pin
T12 Magnetic =
40 – 2-4 foot, 2 pin
96 – 4-8 foot, 2 pin
GE Ballast
M = Electromagnetic
Ballast
GEH = HID
Pack Type
IP = Individual corrugated
box per ballast
84T = Pallet bulk pack
(84=840, 42=420 ballasts)
DIY = Shrinkwrap ballast in
tray pack
DIY72 = Shrinkwrap ballast
in pallet pack (Qty)
No extension = 10 pack
Understanding T12
Electronic Ballasts
Electronic T12
GE multivolt and dedicated voltage ProLine® T12 high-performance ballasts are designed for
replacement of magnetic T12 electronic ballasts during maintenance or retrofits. GE multivolt
ProLine® T12 ballasts have the same wiring and mounting requirements as standard magnetic
ballasts and provide up to 20% energy savings by simply replacing the ballast.
The DOE ballast ruling effective April 1, 2005, prevents the sale of 4 foot and 8 foot lamp
electromagnetic ballasts that operate T12 lamps and do not meet federal ballast efficiency
requirements. GE ProLine® T12 electronic ballasts meet the DOE minimum ballast efficiency
requirements and also allow facility managers to reduce ballast maintenance inventories by
consolidating the number of ballasts needed. GE ProLine® T12 ballasts operate both energy-
saving and standard wattage lamps and are also multi-voltage (120-277V). With 2 ballasts, the
multi-voltage ProLine® T12 can consolidate over 40 different magnetic ballasts.
Performance Features
• GE240RSMVN and GE240RS120 comply
with FCC for residential use
• Low-profile and lightweight housing
simplifies installation and reduces
transportation costs (GE240 = 1.3 lbs. lighter
than magnetic; GE260 = 5.3 lbs. lighter than
magnetic)
• Parallel operation — if one lamp fails,
others remain lit
• Significantly quieter than magnetic
• High-frequency operation virtually
eliminates lamp flickering typical in T12
electromagnetic systems
• Five-year limited ballast warranty
Electromagnetic T12
• Complete line of ballasts for 2-to-8 foot
lamps, circleline and high-output lamps
• 100% thermally protected
• High-grade lamination steel assures lowest
wattage loss
• UL, CSA and/or cUL approved
• 888-GEBALLAST on every ballast
• Two-year limited ballast warranty
Color-Coded Ballast and Outer Box Labels
120V – Yellow
277V – Red
Packaging
• Standard 10 packs
• IP Packs – individually packed with
instructions
• DIY – shrink-wrapped and tray-packed
with instructions
IS = Instant Start,
default if not shown
RS = Rapid Start
PH = Preheat
PT= Preheat/Trigger
H = Hybrid
D50 = Dimming (min level)
120V – Yellow
277V – Red
220V – Green
240V – Orange
347 – Gray
24107 – GE-240-RS-MV-N
ProLine® T12 Multivolt 120V – 277V
2 or 1 – F40 or F34T12 Rapid Start 120 to 277 “N” BF ProLine® T12
General characteristics
Ballast Type Electronic – Programmed/ Rapid Start
Starting Method Rapid start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.4 in (60.45 mm)
Height (H) 1.6 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.9 in (225.80 mm)
Mount Width (X or F) 1.7 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 33 in (838 mm)
White and Black 25 in (635 mm)
Yellow 48 in (1219 mm)
• High-performance electronic ballast for all general fluorescent applications
• Multi-voltage technology handles voltage from 120 to 277V
• Light weight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
Order information
Std. pack Pallet Pack DIY Pack IP Pack
24107 24773
ProLine® T12 Multivolt 120V – 277V
T12 Electronic Ballasts For F20 (2 ft), F30 (3 ft), F34/F40 (4 ft) T12 Lamps
97498 – GE240RS120
ProLine® T12 120V – 277V
2 – F40 or F34T12 Rapid Start 120V “N” BF ProLine® T12
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 221°F (105°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Passive
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing B1 – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 1.3 in (33.02 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.9 in (22.35 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.38 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Yellow 48 in (1219 mm)
Yellow 36 in (914 mm)
• High-performance electronic ballast for all general fluorescent applications
• Light weight, low-profile housing
Order information
Std. pack Pallet Pack DIY Pack IP Pack
97498 97499
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T10
2 120 75 0.63 A 99 1.7 7 50 / 10
2 277 58 0.22 A 93 1.7 16 50 / 10
1 120 42 0.35 A 99 1.7 10 50 / 10
1 277 42 0.17 A 88 1.7 16 50 / 10
F40T12
2 120 74 0.67 A 0.89 1.20 99 1.7 7 0 / -18
2 277 73 0.30 A 0.89 1.21 94 1.7 14 0 / -18
1 120 48 0.41 A 99 1.7 10 0 / -18
1 277 48 0.19 A 89 1.7 17 0 / -18
F34T12
2 120 63 0.56 A 0.87 1.38 99 1.7 8 50 / 10
2 277 62 0.26 A 0.87 1.40 93 1.7 15 0 / -18
1 120 41 0.35 A 99 1.7 10 50 / 10
1 277 41 0.17 A 86 1.7 19 50 / 10
F30T12
2 120 60 0.31 A 99 1.7 8 50 / 10
2 277 58 0.22 A 93 1.7 16 50 / 10
1 120 37 0.31 A 99 1.7 10 50 / 10
1 277 37 0.16 A 86 1.7 22 50 / 10
Other compatible lamps: F20T12, F30T12/WM
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F25T12 2 120 73 0.62 A 1.10 1.50 1 1.7 20 32/0
F40T12
2 120 73 0.62 A 0.85 1.16 98 1.7 20 32/0
2 120 72 0.62 A 0.85 1.18 98 1.7 20
FT36W/4P 2 120 70 0.60 A 0.58 0.82 0.98 1.7 20 32/0
F34T12
2 120 63 0.54 A 0.85 1.34 98 1.7 20
2120 62 0.53 A 0.85 1.37 96 1.7 25 32/0
F30T12 2 120 59 0.50 A 0.92 1.55 0.92 1.7 25 32/0
F12T9
2 120 59 0.50 A 0.53 0.89 0.95 1.7 0.53 32/0
1120 32/0
F8T9 1 120 32/0
F16T9 1 120 32/0
UL Type 1 Outdoor UL Type HL UL Class P NRCan FCC Part 18 Class B at 120 volts cUL Listed UL Listed RoHS compliant
Safety and performance
CSA UL Type 1 Outdoor ANSI – 62.41 UL Type HL FCC Part 18 Class B at 120 volts UL Class P ANSI – C82.11 UL Listed NRCan
Safety and performance
84
86 See page 195 for warranty information. 87
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
72110 – GE140RS120-DIY
ProLine® T12 120V
1 - F40 or F34T12 Rapid Start Electronic 120V “N” BF DIY Pack
General characteristics
Ballast Type Electronic – Programmed/ Rapid Start
Starting Method Rapid start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 75°C (167°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info End-of-Life Protection (EOL), Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 2 – see example on page 102
Case dimensions – Ref Drawing 29 – see page 105
Length (L) 6.46 in (164.08 mm)
Width (W) 1.37 in (34.80 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Mount Length (M) 6.0 in (152.40 mm)
Mount Width (X or F) 1.37 in (34.80 mm)
Mount Slots (MS)
Weight
Exit Type Side
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Lead lengths Length (± 1 in)
Blue and Red 25 in (635 mm)
White and Black 15 in (381 mm)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
72110
ProLine® T12 Multivolt 120V – 277V
T12 Electronic Ballasts For F20 (2 ft), F30 (3 ft), F34/F40 (4 ft) T12, F40T10 Lamps
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T12/40W 1 120 36 0.53 A 0.88 2.44 57 1.58 150 0 / -18
F40T12/25W 1 120 36 0.53 A 1.33 3.69 57 1.54 150 0 / -18
F34T12/34W 1 120 30 0.45 A 0.88 2.93 55 1.50 150 0 / -18
F30T12/30W 1 120 28 0.41 A 0.93 3.32 58 1.51 150 0 / -18
Meets FCC Part 18 (Class B) Consumer Limits cUL Listed UL Listed ANSI 62.41
Safety and performance
24109 – GE-340-RS-MV-N
ProLine® T12 Multivolt 120V – 277V
3 or 2 – F40 or F34T12 Rapid Start 120 to 277 ProLine® T12
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Rapid start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS3 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 33 in (838 mm)
Red/White 33 in (838 mm)
White and Black 25 in (635 mm)
Yellow 48 in (1219 mm)
• High-performance electronic ballasts for all general fluorescent applications
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
Order information
Std. pack Pallet Pack DIY Pack IP Pack
24109 24774
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T12
3 120 114 0.98 A 0.89 0.78 99 1.7 5 50 / 10
3 277 111 0.43 A 0.89 0.80 97 1.7 11 50 / 10
2 120 86 0.74 A 99 1.7 6 50 / 10
2 277 85 0.33 A 96 1.7 12 50 / 10
F40T10
3 120 107 90.00 A 99 1.7 5 50 / 10
3 277 105 0.39 A 97 1.7 12 50 / 10
2 120 80 0.67 A 99 1.7 6 50 / 10
2 277 79 0.30 A 96 1.7 13 50 / 10
F34T12
3 120 96 0.81 A 0.87 0.90 99 1.7 6 50 / 10
3 277 94 0.36 A 0.87 0.92 96 1.7 12 50 / 10
2 120 71 0.60 A 99 1.7 7 50 / 10
2 277 70 0.27 A 95 1.7 13 50 / 10
F30T12
3 120 90 0.75 A 99 1.7 5 50 / 10
3 277 87 0.33 A 97 1.7 12 50 / 10
2 277 67 0.25 A 95 1.7 13 50 / 10
2 120 66 0.55 A 99 1.7 6 50 / 10
Other compatible lamps: F30T12/WM, F40T12/WMP
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
ProLine® T12 Multivolt 120V – 277V
T12 Electronic Ballasts For T12 4 ft – 8 ft Slimline Lamps
24108 – GE-260-IS-MV-N
ProLine® T12 Multivolt 120V – 277V
2 or 1 – F96T12 Instant Start 120 to 277
General characteristics
Ballast Type Electronic – Multivolt Instant Start
Starting Method Instant start
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL 14 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 67 in (1702 mm)
Red 59 in (1499 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
• High-performance electronic ballasts for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
• Multi-voltage technology handles voltage from 120 to 277V
• Lightweight, low-profile housing
• Parallel lamp operation means system maintenance is easier to manage
Order information
Std. pack Pallet Pack DIY Pack IP Pack
24108 24776
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12
2 120 144 1.21 A 0.87 0.60 99 1.7 6 0 / -18
2 277 140 0.52 A 0.87 0.62 97 1.7 14 0 / -18
1 120 90 0.76 A 99 1.7 9 0 / -18
1 277 89 0.33 A 96 1.7 20 0 / -18
F84T12
2 120 126 1.05 A 99 1.7 8 0 / -18
2 277 124 0.46 A 98 1.7 16 0 / -18
1 277 78 0.29 A 96 1.7 27 0 / -18
1 120 77 0.65 A 99 1.7 10 0 / -18
F96T12/WM
2 120 115 0.94 A 0.90 0.78 99 1.7 7 0 / -18
2 277 113 0.41 A 0.90 0.79 97 1.7 16 0 / -18
1 120 72 0.59 A 99 1.7 10 0 / -18
1 277 71 0.27 A 95 1.7 22 0 / -18
F72T12
2 120 109 0.91 A 99 1.7 9 0 / -18
2 277 107 0.40 A 97 1.7 17 0 / -18
1 120 69 0.58 A 99 1.7 11 0 / -18
1 277 68 0.26 A 95 1.7 22 0 / -18
F96T12/WMP
2 120 101 0.87 A 99 1.7 9 0 / -18
2 277 99 0.37 A 97 1.7 17 0 / -18
1 120 63 0.54 A 99 1.7 11 0 / -18
1 277 63 0.24 A 95 1.7 22 0 / -18
F64T12
2 120 98 0.84 A 99 1.7 9 0 / -18
2 277 97 0.36 A 97 1.7 17 0 / -18
1 120 62 0.53 A 99 1.7 11 0 / -18
1 277 62 0.23 A 95 1.7 22 0 / -18
F60T12
2 120 92 0.77 A 99 1.7 9 0 / -18
2 277 91 0.34 A 96 1.7 18 0 / -18
1 120 59 0.49 A 99 1.7 12 0 / -18
1 277 59 0.23 A 94 1.7 21 0 / -18
F48T12
2 120 73 0.61 A 99 1.7 10 0 / -18
2 277 73 0.28 A 95 1.7 21 0 / -18
1 120 48 0.41 A 99 1.7 13 0 / -18
1 277 48 0.20 A 89 1.7 27 0 / -18
UL Type 1 Outdoor NRCan UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Listed
Safety and performance
88 See page 195 for warranty information. 89
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T12 Electronic Ballasts T12 High Output
For T12 High Output Lamps
80162 – B295SR120HP
T12 High Output 120V Electronic
2 – F96T12HOES RS 120
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing SL – see page 104
Length (L) 11.75 in (298.45 mm)
Width (W) 3.1 in (79.50 mm)
Height (H) 1.7 in (45.21 mm)
Mounting dimensions
Mount Length (M) 11.4 in (289.81 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 4.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 46 in (1168 mm)
Yellow 66 in (1676 mm)
• Electronic ballasts for all general fluorescent applications
Order information
Std. pack Pallet Pack DIY Pack IP Pack
80162
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12/HO 2 120 208 1.77 A 0.90 0.43 99 1.7 10 -20 / -29
F84T12/HO 2 120 185 1.60 A 0.89 0.48 99 1.7 10 -20 / -29
F96T8/HO/WM 2 120 174 1.47 A 0.88 0.50 99 1.7 10 60 / 16
F72T12/HO 2 120 169 1.40 A 0.95 0.56 99 1.7 10 -20 / -29
UL Type 1 Outdoor Canadian Energy Standards UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
80163 – B295SR277HP
T12 High Output 277V Electronic
2 – F96T12 HOES RS 277
General characteristics
Ballast Type Electronic – Programmed / Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70°C (158°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing SL – see page 104
Length (L) 11.75 in (298.45 mm)
Width (W) 3.1 in (79.50 mm)
Height (H) 1.7 in (45.21 mm)
Mounting dimensions
Mount Length (M) 11.4 in (289.81 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 4.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp 18 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 25 in (635 mm)
Blue and Red 46 in (1168 mm)
Yellow 66 in (1676 mm)
• Electronic ballasts for all general fluorescent applications
Order information
Std. pack Pallet Pack DIY Pack IP Pack
80163
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12/HO 2 277 208 0.76 A 0.90 0.43 99 1.7 10 -20 / -29
F84T12/HO 2 277 185 0.69 A 0.91 0.49 99 1.7 10 -20 / -29
F96T8/HO/WM 2 277 174 0.63 A 0.88 0.51 99 1.7 10 60 / 16
F72T12/HO 2 277 169 0.61 A 0.95 0.56 99 1.7 10 -20 / -29
UL Type 1 Outdoor Canadian Energy Standards UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
T12 Electronic Ballasts T12 High Output
For T12 High Output Lamps
72109 – GE296HO-MV-N
T12 High Output ProLine® T12 Multivolt 120V – 277V
2 or 1 – F96T12 HO RS 120 to 277 Multivolt ProLine®
General characteristics
Ballast Type Electronic – Programmed/ Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 75°C (167°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing SL – see page 104
Length (L) 11.8 in (299.72 mm)
Width (W) 2.15 in (54.61 mm)
Height (H) 1.61 in (40.89 mm)
Mounting dimensions
Mount Length (M) 11.0 in (279.40 mm)
Mount Width (X or F) 2.15 in (54.61 mm)
Mount Slots (MS)
Weight
Exit Type Side
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Order information
Std. pack Pallet Pack DIY Pack IP Pack
72109
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12/HO
2 120 196 1.65 A 0.90 0.46 99 1.7 10 0 / -18
2 277 196 0.73 A 0.90 0.46 97 1.7 10 0 / -18
1 120 104 0.88 A 0.92 0.88 99 1.7 15 0 / -18
1 277 104 0.42 A 0.92 0.88 95 1.7 15 0 / -18
F96T12/HO/
ES/95W
2 120 164 1.38 A 0.90 0.55 99 1.7 10 0 / -18
2 277 164 0.62 A 0.90 0.55 96 1.7 10 0 / -18
F72T12/
HO/85W
2 120 154 1.30 A 0.90 0.58 99 1.7 10 0 / -18
2 277 154 0.57 A 0.90 0.58 96 1.7 10 0 / -18
F60T12/
HO/75W
2 120 132 1.10 A 0.90 0.68 99 1.7 10 0 / -18
2 277 132 0.50 A 0.90 0.68 96 1.7 10 0 / -18
F48T12/
HO/60W
2 120 112 0.95 A 0.90 0.80 99 1.7 15 0 / -18
2 277 113 0.43 A 0.90 0.80 95 1.7 15 0 / -18
cUL Listed UL Listed FCC Part 18 (Class A) Non Consumer
Safety and performance
90 See page 195 for warranty information. 91
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T12 Magnetic Ballasts
For 2 ft Circleline, Preheat T12 Lamps
89711 – GEM120PH120DIY
T12 Magnetic Ballasts
1 – F20T12, F15T8, F1512, F14T8, F18T8, 120V, Magnetic Ballast (200H2)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Preheat
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 21 – see example on page 101
Case dimensions – Ref Drawing 2 – see page 104
Length (L) 3.0 in (77.01 mm)
Width (W) 1.25 in (31.75 mm)
Height (H) 1.75 in (44.45 mm)
Mounting dimensions
Bracket Length (BL) 3.0 in (77.01 mm)
Mount Length (M) 2.75 in (69.85 mm)
Mount Width (X or F)
Mount Slots (MS) 0.2 in (5.58 mm)
Weight 0.65 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 9 in (229 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89711
89712 – GEM120TC120DIY
T12 Magnetic Ballasts
1 – F20T12, F15T8, F15T12, F14T12, 120V, Magnetic Ballast (546BTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Trigger start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 21 – see example on page 101
Case dimensions – Ref Drawing 9 – see page 105
Length (L) 6.4 in (163.57 mm)
Width (W) 1.9 in (48.51 mm)
Height (H) 1.9 in (49.27 mm)
Mounting dimensions
Bracket Length (BL) 6.4 in (163.57 mm)
Mount Length (M) 6.0 in (152.40 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight 2.10 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 10 in (254 mm)
White 17 in (432 mm)
Blue 18 in (457 mm)
Red 14 in (356 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89712
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F14T8 1 120 18 0.31 A 0.84 4.66 48 1.6 10 50 / 10
F15T12 1 120 18 0.31 A 0.95 5.27 48 1.6 10 50 / 10
F15T8 1 120 18 0.28 A 0.82 4.55 52 1.6 10 50 / 10
F18T8 1 120 18 0.25 A 0.65 3.61 57 1.6 10 50 / 10
F20T12 1 120 18 0.26 A 0.69 3.83 59 1.6 10 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F20T12 1 120 29 0.59 A 0.80 2.75 40 1.5 10 50 / 10
F15T8 1 120 28 0.59 A 0.96 3.42 39 1.6 10 50 / 10
F14T12 1 120 27 0.62 A 0.86 3.18 36 1.6 10 50 / 10
F15T12 1 120 26 0.59 A 1.01 3.88 37 1.5 10 50 / 10
UL Type 1 Outdoor UL Type HL cUL Listed CSA UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
89720 – GEM1FC16T9RS120
T12 Magnetic Ballasts
2 – FC12T9, FC16T9, FC8T9, FC12T9, 120V, Magnetic (726VLHWSTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 037 – see example on page 102
Case dimensions – Ref Drawing 10 – see page 105
Length (L) 6.5 in (166.62 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.6 in (42.92 mm)
Mounting dimensions
Bracket Length (BL) 6.5 in (166.62 mm)
Mount Length (M) 6.0 in (152.40 mm)
Mount Width (X or F)
Mount Slots (MS) 0.30 in (7.87 mm)
Weight 2.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White 12 in (305 mm)
Black 12 in (305 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89720
T12 Magnetic Ballasts
For 2 ft, Circleline, Preheat T12 Lamps
86227 – GEM1FC8T9RS120IP
T12 Magnetic Ballasts
1 – FC8T9, FC6T9, RS, 120V, Magnetic Ballast (547RSWSTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 29 – see example on page 102
Case dimensions – Ref Drawing 9 – see page 105
Length (L) 6.4 in (163.57 mm)
Width (W) 1.9 in (48.51 mm)
Height (H) 1.9 in (49.27 mm)
Mounting dimensions
Bracket Length (BL) 6.4 in (163.57 mm)
Mount Length (M) 6.0 in (152.40 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight 2.10 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 10 in (254 mm)
Black and White 12 in (305 mm)
White 10 in (254 mm)
Blue 9 in (229 mm)
Red 9 in (229 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89722 86227
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F16T9 1 120 30 0.55 A 0.56 1.86 0.45 1.5 10 50 / 10
F12T9 1 120 0.46 A 0.45 0.54 1.5 10 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FC8T9 1 120 25 0.58 A 0.80 3.20 50 1.6 10 50 / 10
FC6T9 1 120 24 0.63 A 0.81 3.37 50 1.6 10 50 / 10
UL Type 1 Outdoor UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
92 See page 195 for warranty information. 93
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T12 Magnetic Ballasts
For 2 ft, Circleline, Preheat T12 Lamps
89717 – GEM1FC12T9RS120
T12 Magnetic Ballasts
2 – FC12T9, RS, 120V, Magnetic Ballast (449LRWSTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 037 – see example on page 102
Case dimensions – Ref Drawing D10 – see page 105
Length (L) 11.7 in (297.18 mm)
Width (W) 3.1 in (78.74 mm)
Height (H) 1.8 in (45.72 mm)
Mounting dimensions
Bracket Length (BL) 11.7 in (297.18 mm)
Mount Length (M) 11.3 in (287.02 mm)
Mount Width (X or F)
Mount Slots (MS) 0.30 in (7.62 mm)
Weight 2.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White 10 in (254 mm)
White and Black 12 in (305 mm)
White 10 in (254 mm)
Blue 9 in (229 mm)
Red 9 in (229 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89717
80819 – GEM220TS120DIY
T12 Magnetic Ballasts
2 – F20T12, F15T8, F15T12, F14T12, 120V, Magnetic Ballast (447LRVLHTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Trigger start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing 10 – see page 105
Length (L) 6.5 in (166.62 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.6 in (42.92 mm)
Mounting dimensions
Bracket Length (BL) 6.5 in (166.62 mm)
Mount Length (M) 6.0 in (152.40 mm)
Mount Width (X or F)
Mount Slots (MS) 0.30 in (7.87 mm)
Weight 2.50 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
Black 1 Left 10 in (254 mm)
White 1 Left 15 in (381 mm)
Blue and Red 2 Right 15 in (381 mm)
Yellow 2 Right 18 in (457 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
80819
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FC8T9/FC12T9 2 120 49 0.70 A 0.65 1.33 59 1.7 10 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F20T12 2 120 37 0.59 A 0.68 1.83 52 1.5 15 50 / 10
F15T12 2 120 36 0.63 A 0.50 1.38 48 1.4 15 50 / 10
F15T8 2 120 36 0.60 A 0.64 1.77 50 1.5 15 50 / 10
UL Type 1 Outdoor UL Type HL UL Class P CSA
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
T12 Magnetic Ballasts
For F30, F34/40 (4 ft) T12 Lamps
89714 – GEM140HRS120DIY
T12 Magnetic Ballasts
1 – F40T12, F40T12, 120V, Magnetic Ballast (412LSLHTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 2 – see example on page 102
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 22 in (559 mm)
Blue 26 in (660 mm)
Red 34 in (864 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
• Energy saving modified rapid start
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89714
89709 – GEM140RS120DIY
T12 Magnetic Ballasts
1 – F40T12, F30T12, F48/25W, 120V, Magnetic Ballast (413CTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 8 – see example on page 102
Case dimensions – Ref Drawing 9 – see page 105
Length (L) 6.4 in (163.57 mm)
Width (W) 1.9 in (48.51 mm)
Height (H) 1.9 in (49.27 mm)
Mounting dimensions
Bracket Length (BL) 6.4 in (163.57 mm)
Mount Length (M) 6.0 in (152.40 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
Weight 2.10 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 10 in (254 mm)
Red 30 in (762 mm)
White 36 in (914 mm)
Blue 36 in (914 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89709
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T10 1 120 50 0.43 A 1.00 2.00 97 1.6 15 50 / 10
F40T12 1 120 50 0.43 A 1.00 2.00 97 1.6 15 50 / 10
F34T12 1 120 43 0.39 A 0.97 2.25 93 1.6 15 60 / 16
F40T12/WMP 1 120 97 1.6 15 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T12 1 120 36 0.63 A 0.60 1.66 47 1.5 15 50 / 10
F30T12 1 120 35 0.70 A 0.67 1.91 42 1.5 15 50 / 10
F48T12/25W 1 120 32 0.59 A 0.96 3.00 45 1.5 15 50 / 10
F34T12 1 120 31 0.65 A 0.58 1.87 40 1.5 15 50 / 10
UL Type 1 Outdoor UL Type HL UL Class P CSA UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
94 See page 195 for warranty information. 95
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T12 Magnetic Ballasts
For F30, F34/40 (4 ft) T12 Lamps
80644 – GEM230RS120DIY
T12 Magnetic Ballasts
2 – F30T12, 120V, Magnetic Ballast (573LTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.60 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 22 in (559 mm)
White and Black 20 in (508 mm)
Yellow 30 in (762 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
80644
89710 – GEM240HRS120DIY
T12 Magnetic Ballasts
2 – F40T12, F40T12, 120V, Magnetic Ballast (420LTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Modified rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 12 in (305 mm)
Blue and Red 12 in (305 mm)
Yellow 12 in (305 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
• Energy saving modified rapid start
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89710
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F30T12 2 120 64 0.55 A 0.80 1.25 95 1.7 20 50 / 10
F30T12/WM 2 120 54 0.45 A 0.75 1.38 95 1.7 20 60 / 16
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T10 2 120 72 0.62 A 0.84 1.16 95 1.6 20 50 / 10
F40T12 2 120 72 0.62 A 0.84 1.16 95 1.6 20 50 / 10
F40T12/WMP 2 120 95 1.6 20 50 / 10
UL Type 1 Outdoor UL Type HL UL Class P CSA UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P UL Listed
Safety and performance
86139 – GEM240RS120IP
T12 Magnetic Ballasts
2 – F40T12, RS, 120V, Magnetic Ballast (446LSLHTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 12 in (305 mm)
Blue and Red 12 in (305 mm)
Yellow 12 in (305 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
46958 86139
T12 Magnetic Ballasts
For F30, F34/40 (4 ft) T12 Lamps
86124 – GEM240RS277IP
T12 Magnetic Ballasts
2 – F40T12, RS, 277V, Magnetic Ballast (443LSLHTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.40 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 12 in (305 mm)
Blue and Red 12 in (305 mm)
White and Black 12 in (305 mm)
Yellow 12 in (305 mm)
Yellow 2 in (51 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89713 86124
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T10 2 120 87 0.73 A 0.95 1.09 98 1.6 20 50 / 10
F40T12 2 120 87 0.73 A 0.95 1.09 98 1.6 20 50 / 10
F40T12/WM 2 120 73 0.64 A 0.89 1.21 95 1.7 20 60 / 16
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T10 2 277 88 0.32 A 0.95 1.07 98 1.6 20 50 / 10
F40T12 2 277 88 0.32 A 0.95 1.07 98 1.6 20 50 / 10
F40T12/WM 2 277 74 0.27 A 0.88 1.18 97 1.7 20 60 / 16
UL Type 1 Outdoor UL Type HL Circle E UL Class P CSA UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL Circle E UL Class P CSA UL Listed
Safety and performance
96 See page 195 for warranty information. 97
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T12 Magnetic Ballasts
For F30, F34/40 (4 ft) T12 Lamps
86341 – GEM240RS220IP
T12 Magnetic Ballasts
2 – F40T12, F40T10 220V Magnetic Ballast (754LTCP)
General characteristics
Ballast Type Magnetic - Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor High
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing 10 – see page 105
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL) 8.8 in (225.80 mm)
Mount Length (M) 1.6 in (42.92 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.04 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 12 in (305 mm)
Blue and Red 12 in (305 mm)
Black and White 12 in (305 mm)
Yellow 12 in (305 mm)
Yellow 2 in (51 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
86341
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F40T12 2 220 40 0.70 2 90 1.7 32 50 / 10
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P cUL Listed UL Type CC UL Listed
Safety and performance
T12 Magnetic Ballasts
For T12 4 ft – 8 ft Slimline Lamps
86372 – GEM196IS120IP
T12 Magnetic Ballasts
1 – F96T12, IS, 120, Magnetic Ballast (822BRTCP)
General characteristics
Ballast Type Magnetic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating B (25-30 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 014 – see example on page 103
Case dimensions – Ref Drawing D10 – see page 105
Length (L) 9.4 in (240.10 mm)
Width (W) 3.0 in (78.58 mm)
Height (H) 1.7 in (45.24 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.82 mm)
Mount Width (X or F) 1.69 in (42.86 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 6.50 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black/White 8 in (203 mm)
Red 44 in (1118 mm)
White 68 in (1727 mm)
White and Black 72 in (1829 mm)
Blue 48 in (1219 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Instant start ballast for long lamp starting cycles and low initial cost
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89719 86372
86381 – GEM196IS277IP
T12 Magnetic Ballasts
1 – F96T12, IS, 277, Magnetic Ballast (828BRTCP)
General characteristics
Ballast Type Magnetic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating B (25-30 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 014 – see example on page 103
Case dimensions – Ref Drawing D10 – see page 105
Length (L) 9.4 in (240.10 mm)
Width (W) 3.0 in (78.58 mm)
Height (H) 1.7 in (45.24 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.82 mm)
Mount Width (X or F) 1.69 in (42.86 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 6.50 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
Black/White 1 8 in (203 mm)
White and Black 1 Left 72 in (1829 mm)
White 1 Left 68 in (1727 mm)
Blue 1 Right 48 in (1219 mm)
Red 1 Right 44 in (1118 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Instant start ballast for long lamp starting cycles and low initial cost
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
86381
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12 1 120 93 0.83 A 0.75 0.80 93 1.85 30 50 / 10
F72T12 1 120 78 0.73 A 0.80 1.02 90 1.85 30 50 / 10
F96T12/WM 1 120 78 0.73 A 0.71 0.91 90 2.00 30 60 / 16
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12 1 277 93 0.36 A 0.75 0.80 90 1.8 30 50 / 10
F72T12 1 277 78 0.30 A 0.80 1.02 90 1.8 30 50 / 10
F96T12/WM 1 277 78 0.30 A 0.71 0.91 90 2.0 30 60 / 16
UL Type 1 Outdoor UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
98 See page 195 for warranty information. 99
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T12 Magnetic Ballasts
For T12 4 ft – 8 ft Slimline Lamps
86360 – GEM296IS120IP
T12 Magnetic Ballasts
2 – F96T12, IS, 120V, Magnetic Ballast, (806SLHTCP)
General characteristics
Ballast Type Magnetic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating B (25-30 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 39 – see example on page 103
Case dimensions – Ref Drawing 15 – see page 105
Length (L) 11.6 in (296.92 mm)
Width (W) 3.0 in (78.48 mm)
Height (H) 1.8 in (45.97 mm)
Mounting dimensions
Bracket Length (BL) 11.6 in (296.92 mm)
Mount Length (M) 11.25 in (285.75 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (7.87 mm)
Weight 7.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 12 in (305 mm)
White 12 in (305 mm)
Blue and Red 12 in (305 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Instant start ballast for long lamp starting cycles and low initial cost
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
46965 86360
86379 – GEM296IS277IP
T12 Magnetic Ballasts
2 – F96T12, IS, 277V, Magnetic Ballast (827SLHTCP)
General characteristics
Ballast Type Magnetic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating B (25-30 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL 025 – see example on page 103
Case dimensions – Ref Drawing 15 – see page 105
Length (L) 11.6 in (296.92 mm)
Width (W) 3.0 in (78.48 mm)
Height (H) 1.8 in (45.97 mm)
Mounting dimensions
Bracket Length (BL) 11.6 in (296.92 mm)
Mount Length (M) 11.25 in (285.75 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (7.87 mm)
Weight 7.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
White and Black 1 Left 12 in (305 mm)
Yellow 2 Left 12 in (305 mm)
Blue and Red 1 Right 12 in (305 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Instant start ballast for long lamp starting cycles and low initial cost
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89715 86379
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12 2 120 158 1.33 A 0.95 0.60 96 1.9 30 50 / 10
F72T12 2 120 124 1.11 A 0.94 0.75 93 1.8 30 50 / 10
F96T12/WM 2 120 120 1.02 A 0.87 0.72 95 1.9 30 60 / 16
F48T12 2 120 98 1.04 A 0.95 0.96 87 1.9 30 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12 2 277 158 0.60 A 0.93 0.58 96 1.7 30 50 / 10
F72T12 2 277 125 0.47 A 0.95 0.76 94 1.8 30 50 / 10
F96T12/WM 2 277 120 0.45 A 0.93 0.77 95 1.9 30 60 / 16
F48T12 2 277 98 0.41 A 0.95 0.96 86 1.8 30 50 / 10
UL Type 1 Outdoor UL Type HL UL Class P Circle E CSA UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P Circle E CSA UL Listed
Safety and performance
T12 Magnetic Ballasts
For T12 High Output Lamps
86164 – GEM296HORS120IP
T12 Magnetic Ballasts
2 – F96T12HO, F96T8HO, F72T12HO, RS, 120V, Magnetic Ballast (480SLHTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating C (31-36 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing 29 – see page 105
Length (L) 11.75 in (298.45 mm)
Width (W) 3.1 in (80.16 mm)
Height (H) 1.5 in (39.70 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.1 in (283.97 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 10.90 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Blue and Red 46 in (1168 mm)
White and Black 18 in (457 mm)
Yellow 65 in (1651 mm)
Blue and Red 48 in (1219 mm)
Yellow 72 in (1829 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
89718 86164
86171 – GEM296HORS277IP
T12 Magnetic Ballasts
2 – F96T12HO, F96T8HO, RS, 277V, Magnetic Ballast (487SLHTCP)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating C (31-36 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing 29 – see page 105
Length (L) 11.75 in (298.45 mm)
Width (W) 3.1 in (80.16 mm)
Height (H) 1.5 in (39.70 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.1 in (283.97 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 10.90 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Blue and Red 46 in (1168 mm)
White and Black 18 in (457 mm)
Yellow 65 in (1651 mm)
Blue and Red 48 in (1219 mm)
Yellow 72 in (1829 mm)
• Magnetic ballast construction for all general fluorescent lighting
• Extends lamp life in frequently switched applications
• Color-coded ballast and package labels reduce misapplication errors (120V Yellow, 277V Red)
Order information
Std. pack Pallet Pack DIY Pack IP Pack
86171
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12/HO 2 120 256 2.14 A 0.99 0.38 98 1.7 20 -20 / -29
F96T8/HO/WM 2 120 221 1.94 A 0.94 0.42 95 1.8 20 60 / 16
F72T12/HO 2 120 208 1.81 A 0.95 0.45 97 1.8 20 -20 / -29
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F96T12/HO 2 277 248 0.92 A 0.97 0.39 98 1.7 20 -20 / -29
F96T8/HO/WM 2 277 214 0.80 A 0.95 0.44 94 1.8 20 60 / 16
F72T12/HO 2 277 202 0.78 A 0.97 0.48 95 1.8 20 -20 / -29
UL Type 1 Outdoor UL Type HL UL Class P Circle E cUL Listed UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P Circle E cUL Listed UL Listed
Safety and performance
100 See page 195 for warranty information. 101
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
T12 Magnetic Ballasts
For T12 High Output Lamps
80664 – 493B2
T12 Magnetic Ballasts
2 – F73T12/BL/HO, Suntan, 120, Magnetic Ballast
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Passive
Sound Rating A (20-24 decibels)
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – LFL PS2 – see example on page 101
Case dimensions – Ref Drawing ST – see page 104
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.50 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue and Red 36 in (914 mm)
White and Black 30 in (762 mm)
Yellow 45 in (1143 mm)
• Electronic ballasts for all general fluorescent applications
• Instant start electronic ballast for long lamp starting cycles and low initial cost
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80664
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F72T12/HO 2 120 180 1.6 A 1.00 0.55 90 1.7 25 50 / 10
F73T12/HO 2 120 180 1.6 A 1.00 0.55 90 1.7 25 50 / 10
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
Fluorescent Accessories Prod Code Description Application Units Per Carton
Starters 80619 FS-2-C Starters for 14, 15 & 20 Watt Flu. Lamps 24
80620 FS-4-C Starters for 30 & 40 Watt Flu. Lamps 24
80621 FS-5-C Starters for 4, 6 & 8 Watt Flu. Lamps 24
80622 FS-25-C Starters for 22 & 25 Watt Flu. Lamps 24
80629 FS-12-C Starters for 32 Watt Circular Flu. Lamps 24
Sockets 80623 BP-SKT Socket Set w/Starter for Bi-Pin Flu. Lamps 12
80624 BP Socket Set for Bi-Pin Flu. Lamps 12
80625 SL-SS Socket Set for Slimline Flu. Lamps 12
80627 BP-FM Face Mount Socket Set for Bi-Pin Flu. Lamps 12
80628 BP-LP Low-Profile Socket Set for Bi-Pin Flu. Lamps 12
Fluorescent Accessories
Wiring Diagrams
T12 Fluorescent Ballasts
LFL PS2 LFL PS3
LFL 14 LFL 21
102 See page 195 for warranty information. 103
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
LFL 2 LFL 8
LFL 014
Wiring Diagrams
T12 Fluorescent Ballasts
LFL 39
LFL 025
Wiring Diagrams
T12 Fluorescent Ballasts
LFL 037 LFL 29
104 See page 195 for warranty information. 105
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
10 D10, 15, 29
Case Dimensions
T12 Fluorescent Ballasts
Case Dimensions
T12 Fluorescent Ballasts
ST B1
SL 2
9
See page 195 for warranty information. 107
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Understanding Sign Ballasts
GE sign ballasts are transitioning from USB to GESB ballast descriptions. These ballasts are
electromagnetic technology for T12 high output lamps. The sign ballasts are high output
(HO) ballasts for rugged outdoor sign cabinet applications. They will start lamps in cold
temperatures down to -20°F. GE sign ballasts are ideal for high moisture environments with
a UL Type 2 Outdoor and type HL rating. They are 120-volt series rapid start and have Class P
thermal protection.
106
GE Sign Ballast nomenclature
GESB-0620-24-IP
This represents
the min/max
linear footage
of lamps it can
operate.
GE Sign Ballast
Examples:
GESB-0620-24-IP can operate a
minimum of two lamps at a total
length of 6 feet, up to four lamps at
a total length of 20 feet.
GESB-2040-46-IP can operate a
minimum of four lamps at a total
length of 20 feet, up to six lamps at
a total length of 40 feet.
Individual packThe last number
represents the
number of lamps
Sign Ballast for T12HO, 120 volt
GE Description Total Lamp Footage
Code GESB Footage
#
lamps 24681012141618202224262830323436384042444648
72103 GESB -0412 -12 IP
88921 GESB -0620 -24 IP
88931 GESB -1224 -24 IP
88936 GESB -2040 -24 IP
88920 GESB -1240 -46 IP
88934 GESB -2448 -46 IP
Sign Ballast for T12HO, 120 volt
GE Description # of Lamps
Code GESB Footage
#
lamps 1 2 3 4 5 6
72103 GESB -0412 -12 IP
88921 GESB -0620 -24 IP
88931 GESB -1224 -24 IP
88936 GESB -2040 -24 IP
88920 GESB -1240 -46 IP
88934 GESB -2448 -46 IP
72103 – GESB-0412-12-IP
Sign Ballasts
T12HO Sign Ballast 4 to 12 ft, 1 to 2 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign 0412 – see example on page 117
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 11.75 in (298.45 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.0 in (279.40 mm)
Mount Width (X or F) 3.19 in (80.96 mm)
Mount Slots (MS)
Weight 8.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown and Blue 80 in (2032 mm)
Orange/Black 60 in (1524 mm)
Orange, Red and Yellow 60 in (1524 mm)
Blue/White 72 in (1829 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72103
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F72T12/HO
2 120 170 1.48 A 0.89 0.52 98 1.9 15 -20/-29
1 120 100 0.92 A 0.81 0.81 92 2.0 35 -20/-29
F96T12/HO 1 120 120 1.03 A 0.84 0.70 96 2.0 25 -20/-29
F48T12/HO
2 120 130 1.13 A 0.85 0.65 97 2.0 20 -20/-29
1 120 80 0.82 A 0.77 0.96 84 2.1 55 -20/-29
F24T12/HO 2 120 90 0.90 A 0.78 0.87 84 2.1 55 -20/-29
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
UL Type 2 Outdoor UL Listed cUL Listed 3-Year Warranty
Safety and performance
72104 – GESB-0620-24-IP
Sign Ballasts
T12HO Sign Ballast 6 to 20 ft, 2 to 4 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagrams – Sign 0620 – see example on page 118
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 11.75 in (298.45 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.0 in (279.40 mm)
Mount Width (X or F) 3.19 in (80.96 mm)
Mount Slots (MS)
Weight 16.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown and Blue 80 in (2032 mm)
Orange/Black 60 in (1524 mm)
Orange, Red and Yellow 60 in (1524 mm)
Blue/White 72 in (1829 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72104
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F60T12/HO 4 120 300 2.56 A 1.06 0.35 95 1.7 15 -20 / -29
F72T12/HO 3 120 240 2.34 A 0.96 0.40 99 1.8 15 -20 / -29
F36T12/HO 2 120 115 1.41 A 0.87 0.76 87 2.0 45 -20 / -29
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
UL Type 2 Outdoor UL Listed cUL Listed 3-Year Warranty
Safety and performance
Sign Ballasts
For T12 High Output Lamps
The best way to select or provide cross-reference to competition ballasts is to understand the
sign ballast nomenclature.
108 See page 195 for warranty information. 109
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
72105 – GESB-1224-24-IP
Sign Ballasts
T12HO Sign Ballast 12 to 24 ft, 2 to 4 lamps
General characteristics
Ballast Type Magnetic –T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign 1224 – see example on page 118
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 11.75 in (298.45 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.0 in (279.40 mm)
Mount Width (X or F) 3.19 in (80.86 mm)
Mount Slots (MS)
Weight 16.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown and Blue 80 in (2032 mm)
Orange/Black 60 in (1524 mm)
Orange, Red and Yellow 60 in (1524 mm)
Blue/White 72 in (1829 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72105
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F72T12/HO
4 120 285 2.70 A 0.84 0.29 99 1.7 10 -20 / -29
3 120 230 2.10 A 0.82 0.36 96 1.8 15 -20 / -29
2 120 170 1.60 A 0.82 0.48 87 1.9 25 -20 / -29
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
UL Type 2 Outdoor UL Listed cUL Listed Class P 3-Year Warranty
Safety and performance
72106 – GESB-1240-46-IP
Sign Ballasts
T12HO Sign Ballast 12 to 40 ft, 4 to 6 lamps
General characteristics
Ballast Type Magnetic - T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign 1240 – see example on page 118
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 11.75 in (298.45 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.0 in (279.40 mm)
Mount Width (X or F) 3.19 in (80.96 mm)
Mount Slots (MS)
Weight 18.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown and Blue 80 in (2032 mm)
Orange/Black 60 in (1524 mm)
Orange, Red and Yellow 60 in (1524 mm)
Blue/White 72 in (1829 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72106
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
(2) F96T12/HO +
(4) F72T12/HO 6 120 415 3.90 A 0.78 0.19 98 1.6 15 -20 / -29
F72T12/HO 5 120 350 3.20 A 0.77 0.22 95 1.7 10 -20 / -29
F48T12/HO 5 120 252 2.70 A 0.78 0.31 82 1.8 20 -20 / -29
F36T12/HO 4 120 183 2.40 A 0.75 0.41 65 1.9 35 -20 / -29
72107 – GESB-2040-24-IP
Sign Ballasts
T12HO Sign Ballast 20 to 40 ft, 4 to 6 lamps
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign 2040 – see example on page 118
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 11.75 in (298.45 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.0 in (279.40 mm)
Mount Width (X or F) 3.19 in (80.96 mm)
Mount Slots (MS)
Weight 18.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown and Blue 80 in (2032 mm)
Orange/Black 60 in (1524 mm)
Orange, Red and Yellow 60 in (1524 mm)
Blue/White 72 in (1829 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72107
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F120T12/HO
4 120 412 4.00 A 0.80 0.19 98 1.7 15 -20 / -29
3 120 318 3.10 A 0.82 0.26 95 1.8 10 -20 / -29
2 120 225 2.70 A 0.86 0.38 78 1.8 25 -20 / -29
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
UL Type 2 Outdoor UL Listed cUL Listed 3-Year Warranty
Safety and performance
UL Type 2 Outdoor UL Listed cUL Listed 3-Year Warranty
Safety and performance
General characteristics
Ballast Type Magnetic - T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating
Additional Info Thermally protected
72108 – GESB-2448-46-IP
Sign Ballasts
T12HO Sign Ballast 24 to 48 ft, 4 to 6 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign 2448 – see example on page 118
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 11.75 in (298.45 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.0 in (279.40 mm)
Mount Width (X or F) 3.19 in (80.96 mm)
Mount Slots (MS)
Weight 18.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown and Blue 80 in (2032 mm)
Orange/Black 60 in (1524 mm)
Orange, Red and Yellow 60 in (1524 mm)
Blue/White 72 in (1829 mm)
Order information
10 Pack Pallet Pack DIY Pack IP Pack
72108
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F96T12/HO
6 120 540 4.50 A 0.86 0.16 96 1.6 10 -20 / -29
5 120 470 3.50 A 0.87 0.19 96 1.7 10 -20 / -29
F72T12/HO
5 120 370 3.20 A 0.89 0.24 92 1.8 10 -20 / -29
4 120 310 3.00 A 0.89 0.29 85 1.8 20 -20 / -29
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
UL Type 2 Outdoor UL Listed cUL Listed 3-Year Warranty
Safety and performance
Sign Ballasts
For T12 High Output Lamps
Sign Ballasts
For T12 High Output Lamps
110 See page 195 for warranty information. 111
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Sign Ballasts
For T12 High Output Lamps
88921 – USB-0412-12-IP
Sign Ballasts
4 to 12 ft, 1 to 2 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S1A, Sign S2A – see example on page 115
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 10.5 in (268.68 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 1.75 in (44.45 mm)
Mounting dimensions
Bracket Length (BL) 11.7 in (297.25 mm)
Mount Length (M) 11.1 in (282.98 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 8.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Blue and Red 38 in (965 mm)
Yellow 48 in (1219 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88921
88931 – USB-0816-14-IP
Sign Ballasts
8 to 16 ft, 1 to 4 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S1B, Sign S4A, Sign S6A, Sign S9 – see example on page 115
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 10.5 in (268.68 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 11.7 in (297.25 mm)
Mount Length (M) 11.1 in (282.98 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 12.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Blue 65 in (1651 mm)
White 36 in (914 mm)
Yellow 39 in (991 mm)
Brown 56 in (1422 mm)
Red 40 in (1016 mm)
Blue/White 48 in (1219 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88931
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F72T12/HO 2 120 160 1.35 A 1.00 0.62 90 -20 / -29
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F48T12/HO 4 120 220 1.90 A 1.00 0.45 90 -20 / -29
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
88934 – USB-1632-24-IP
Sign Ballasts
16 to 32 ft, 2 to 4 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S4A, Sign S6A, Sign S9 – see example on page 115
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 15.625 in (396.87 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 16.6 in (423.87 mm)
Mount Length (M) 16.125 in (409.57 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 16.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
Blue and Brown 80 in (2032 mm)
Yellow 60 in (1524 mm)
White and Black 24 in (610 mm)
Blue/White 72 in (1829 mm)
Red 54 in (1372 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88934
88936 – USB-1024-14-IP
Sign Ballasts
10 to 24 ft, 1 to 4 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S1B, Sign S4A, Sign S6A, Sign S9 – see example on page 115
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 13.19 in (334.96 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 14.3 in (363.52 mm)
Mount Length (M) 13.75 in (349.25 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 14.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
Blue 79 in (2007 mm)
Brown 83 in (2108 mm)
Yellow 75 in (1905 mm)
White and Black 24 in (610 mm)
Red 48 in (1219 mm)
Blue/White 57 in (1448 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Supports 1 to 6 lamps, 2 to 48 feet total length
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88936
Sign Ballasts
For T12 High Output Lamps
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F96T12/HO 4 120 420 3.50 A 1.00 0.23 90 -20 / -29
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F72T12/HO 4 120 325 2.70 A 1.00 0.30 90 -20 / -29
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
112 See page 195 for warranty information. 113
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
88939 – USB-2036-46-IP
Sign Ballasts
20 to 36 ft, 4 to 6 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S5A, Sign S7, Sign S7A – see example on pages 116-117
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 15.625 in (396.87 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 16.6 in (423.87 mm)
Mount Length (M) 16.125 in (409.57 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 18.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
Orange and Blue 50 in (1270 mm)
Orange/Black 50 in (1270 mm)
Red 80 in (2032 mm)
Yellow 70 in (1778 mm)
Blue/White and Brown 38 in (965 mm)
White and Black 24 in (610 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Supports 1 to 6 lamps, 2 to 48 feet total length
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88939
Sign Ballasts
For T12 High Output Lamps
88940 – USB-2048-46-IP
Sign Ballasts
20 to 48 ft, 4 to 6 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S5A, Sign S7, Sign S7A – see example on pages 116-117
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 15.625 in (396.87 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 16.6 in (423.87 mm)
Mount Length (M) 16.125 in (409.57 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 18.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
Blue/White 50 in (1270 mm)
Brown and Orange 50 in (1270 mm)
Orange/Black 50 in (1270 mm)
White and Black 24 in (610 mm)
Blue and Red 80 in (2032 mm)
Yellow 70 in (1778 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL type 2 outdoor and HL rating
• Supports 1 to 6 lamps, 2 to 48 feet total length
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88940
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F72T12/HO 6 120 480 4.00 A 1.00 0.20 90 -20 / -29
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F96T12/HO 6 120 600 5.00 A 1.00 0.16 90 -20 / -29
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
Sign Ballasts
For T12 High Output Lamps
88918 – USB-0218-16-IP
Sign Ballasts
Max 3, 2 to 18 ft, 1 to 6 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S3, Sign S4, Sign S5, Sign S6, Sign S7, Sign S8 – see example on pages 116-117
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 13.19 in (334.96 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 14.3 in (363.52 mm)
Mount Length (M) 13.75 in (349.25 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 15.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown, Blue and Red 60 in (1524 mm)
Orange/Black 60 in (1524 mm)
Orange and Yellow 60 in (1524 mm)
Blue/White 60 in (1524 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88918
88919 – USB-1048-16-IP
Sign Ballasts
Max 3, 10 to 48 ft, 1 to 6 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S1, Sign S2, Sign S3, Sign S4, Sign S7, Sign S8 – see example on pages 116-117
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 15.625 in (396.87 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 16.6 in (423.87 mm)
Mount Length (M) 16.125 in (409.57 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 18.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
Blue and Red 80 in (2032 mm)
Blue/White and Brown 50 in (1270 mm)
Yellow 70 in (1778 mm)
White and Black 24 in (610 mm)
Orange/Black and Orange 60 in (1524 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88919
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F36T12/HO 6 120 240 2.00 A 1.00 0.41 90 -20 / -29
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F96T12/HO 6 120 570 4.80 A 1.00 0.17 90 -20 / -29
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
114 See page 195 for warranty information. 115
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Sign Ballasts
For T12 High Output Lamps
88920 – USB-1232-16-IP
Sign Ballasts
Max 3, 12 to 32 ft, 1 to 6 lamps
General characteristics
Ballast Type Magnetic – T12 Sign Illuminating
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-)
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagrams – Sign S3, Sign S4, Sign S5, Sign S6, Sign S7, Sign S8 – see example on pages 116-117
Case dimensions – Ref Drawing S1 – see page 119
Length (L) 13.19 in (334.96 mm)
Width (W) 3.19 in (80.96 mm)
Height (H) 2.6 in (67.86 mm)
Mounting dimensions
Bracket Length (BL) 14.3 in (363.52 mm)
Mount Length (M) 13.75 in (349.25 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 16.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp Varies
Remote Mounting Wire Gauge Varies
Lead lengths Length (± 1 in)
White and Black 24 in (610 mm)
Brown and Blue 80 in (2032 mm)
Orange/Black 60 in (1524 mm)
Orange, Red and Yellow 60 in (1524 mm)
Blue/White 72 in (1829 mm)
• High-output ballasts for rugged outdoor sign cabinet applications
• Reliable low-temperature starting – as low as -20°F
• Ideal for high-moisture environments – UL Type 2 Outdoor and HL rating
• Class P thermal protection
Order information
10 Pack Pallet Pack DIY Pack IP Pack
88920
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°FC)
F48T12/HO 6 120 410 3.50 A 1.00 0.24 90 -20 / -29
UL Type 2 Outdoor UL Type HL CSA UL Listed
Safety and performance
Wiring Diagrams
Sign Ballasts
SIGN S1A SIGN S2A
SIGN S1B SIGN S4A
SIGN S6A SIGN S9
116 See page 195 for warranty information. 117
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Wiring Diagrams
Sign Ballasts
SIGN S5A SIGN S7A
SIGN S1 SIGN S2
SIGN S3 SIGN S4
SIGN S5 SIGN S6
Wiring Diagrams
Sign Ballasts
SIGN S7 SIGN S8
SIGN 0412
Ballast
BLACK
WHITE
YELLOW
YELLOW
BLUE
BLUE
RED
RED
Lamp 1
LINE
Ballast
BLACK
WHITE
YELLOW
YELLOW
BLUE
BLUE
RED
RED
Lamp 1
Lamp 2
LINE
118 See page 195 for warranty information. 119
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Wiring Diagrams
Sign Ballasts
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
Lamp 3
Lamp 4
LINE
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
Lamp 3
LINE
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
L
INE
SIGN 0620
SIGN 1224
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
Lamp 3
Lamp 4
LINE
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
Lamp 3
LINE
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
L
INE
SIGN 1240
Ballast
BLACK
WHITE
BROWN
BROWN
BLUE WH
BLUE WH
YELLOW
YELLOW
Lamp 3
LINE
Lamp 4
Lamp 2
Lamp 1
BLUE
BLUE
OR BLK
OR BLK
ORAN E
ORAN E
RED
RED
Ballast
BLACK
WHITE
BROWN
BROWN
BLUE WH
BLUE WH
YELLOW
YELLOW
Lamp 4
LINE
Lamp
Lamp 3
Lamp 1
BLUE
BLUE
OR BLK
OR BLK
ORAN E
ORAN E
RED
RED
Lamp 2
Lamp
Ballast
BLACK
WHITE
BROWN
BROWN
BLUE WH
BLUE WH
YELLOW
YELLOW
Lamp 3
LINE
Lamp
Lamp 2
Lamp 1
BLUE
BLUE
OR BLK
OR BLK
ORAN E
ORAN E
RED
RED
Lamp 4
SIGN 2040
Ballast
BLACK
WHITE
BROWN
BROWN
BLUE WH
BLUE WH
YELLOW
YELLOW
Lamp 3
LINE
Lamp 4
Lamp 2
Lamp 1
BLUE
BLUE
OR BLK
OR BLK
ORAN E
ORAN E
RED
RED
Ballast
BLACK
WHITE
BROWN
BROWN
BLUE WH
BLUE WH
YELLOW
YELLOW
Lamp 4
LINE
Lamp
Lamp 3
Lamp 1
BLUE
BLUE
OR BLK
OR BLK
ORAN E
ORAN E
RED
RED
Lamp 2
Lamp
Ballast
BLACK
WHITE
BROWN
BROWN
BLUE WH
BLUE WH
YELLOW
YELLOW
Lamp 3
LINE
Lamp
Lamp 2
Lamp 1
BLUE
BLUE
OR BLK
OR BLK
ORAN E
ORAN E
RED
RED
Lamp 4
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
Lamp 3
Lamp 4
LINE
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
Lamp 3
LINE
Ballast
BLACK
WHITE
BROWN
BROWN
YELLOW
YELLOW
BLUE
BLUE
BLUE/WHITE
BLUE/WHITE
RED
RED
Lamp 1
Lamp 2
LINE
SIGN 2448
Case Dimensions
Sign Ballasts
S1
See page 195 for warranty information. 121
Quick Reference
Guides
gelighting.com
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
See page 195 for warranty information.
Understanding
Compact Fluorescent Ballasts
GE compact fluorescent (CFL) ballasts provide energy saving alternatives to halogen,
incandescent or HID light sources. GE Multivolt ProLine® CFL programmed start ballasts
combine universal voltage (108-305V) technology with multi-lamp capability, dual entry
color-coded connectors and ultra system reliability to create an industry leading CFL solution
for commercial and residential applications.
Multivolt ProLine® CFL ballasts are offered in three different configurations:
1) -SE description – dual entry (side or bottom) connectors, 2) -BES – bottom entry with studs for
mounting to junction boxes and 3) -3W – 3-way mounting kits that allow you to have all three
mounting options with one kit.
Multivolt ProLine® CFL ballasts come with a five-year ballast and one-year lamp limited
warranty. These ballasts also meet the EPA’s ENERGY STAR® fixture program requirements
with a Consumer Class B EMI rating for residential applications, as well as a high power factor
ballast design.
Use the GE Multivolt ProLine® CFL Multi-Lamp compatibility chart (page 121) to find the right
ballast for your need.
GE Compact Fluorescent Ballast nomenclature
GEC213-MVPS-SE
GE Compact
Ballast
SE = Side & Bottom Entry
BES = Bottom Entry with Studs
3W = 3-Way Kit (SE, BE, BES)
IP = Individual Pack
Max number
of lamps and
Primary Lamp
type
MV = Multivolt
(108 to 305 volts)
UNV = Universal Voltage
(Multi-Voltage)
120 or 277 = voltage
PS = Programmed Start
SI = Series Instant Start
PH = Preheat.
RS = Rapid Start
RH = less than 20% THD
120
GE Multivolt ProLine® CFL Multi-Lamp Capability
Lamp Type GEC213-MVPS GEC218-MVPS GEC226-MVPS GEC242MVPS GEC240-MV
T4
1 x 13W (CFQ/G24q, CFTR/GX24q) X
2 x 13W (CFQ/G24q, CFTR/GX24q) X
1 x 18W (CFQ/G24q, CFTR/GX24q) X X
2 x 18W (CFQ/G24q, CFTR/GX24q) X
1 x 26W (CFQ/G24q, CFTR/GX24q) X X X
2 x 26W (CFQ/G24q, CFTR/GX24q) X X
1 x 32W (CFQ/G24q, CFTR/GX24q) X
2 x 32W (CFQ/G24q, CFTR/GX24q) X
1 x 42W (CFQ/G24q, CFTR/GX24q) X X
2 x 42W (CFQ/G24q, CFTR/GX24q) X
T5 Circleline
1 x 22W (FC9T5) X
1 x 22W (FC9T5) X
1 x 22W + 1 x 40W (FC9T5 + FC12T5) X
1 x FC16T9 X
FT TT5
2 x 24 / 27W (FT/2G11) X X
1 x FT36W (2G11) X
2 x FT36W (2G11) X
1 x 40W (FT/2G11) & Energy Saving 28W XX
2 x 40W (FT/2G11) & Energy Saving 28W XX
3 x 40W (FT/2G11) & Energy Saving 28W
2D
1 x 10W (CFS/GR10q) X
2 x 10W (CFS/GR10q) X
1 x 16W (CFS/GR10q) X
2 x 16W (CFS/GR10q) X
1 x 21W (CFS/GR10q) X
2 x 21W (CFS/GR10q) X X
1 x 28W (CFS/GR10q) X
2 x 28W (CFS/GR10q) X
1 x 38W (CFS/GR10q) X
2 x 38W (CFS/GR10q) X
T5
1 x 57W (CFTR/GX24q) X
1 x 70W (CFTR/GX24q) X
CFL – Cross Reference Chart
GE Universal Advance Osram Robertson ESI
GE213-MVPS-3W C213UNVSE/BE/BES ICF-2513-H1-LD QTP 1/2X13CF/UNV PSM213CQMY ES-2/1-CFQ-13/10-UNV-C/D
ES-1-2D-16/10-UNV-D
GE218-MVPS-3W C218UNVSE/BE/BES ICF-2518-H1-LD
REL-2Q18
VEL-2Q18
R-2Q18-4P-TP
V-2Q18-4P-TP
QTP 1/2X18CF/UNV PSM218CQMY ES-2/1-CFQ-18-UNV-C/D
ES-1-2D-21-UNV-D
GE226-MVPS-3W C2642UNVSE/BE/BES
C226SR120BE
C226SR277BE
ICF-2526-H1-LD
REL-1T32
VEL-1T32
REL-1T42
VEL-1T42
QTP 2X26/UNV
QTP 1/2XCF/UNV
PSM226CQMY ES-2/1-CFQ-26-UNV-C/D
ES-1-CFH-42/32/26-UNV-C/D
ES-1-T5C-40/22-UNV-D
122 See page 195 for warranty information. 123
Quick Reference
Guides
gelighting.com
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
See page 195 for warranty information.
71428 – GEC213-MVPS-BES
71429 – GEC213-MVPS-SE
71430 – GEC213-MVPS-3W
ProLine® CFL Electronic Ballasts
2 or 1 – CFQ13W/G24q 120-227V ProLine® PS
Dimensions
Wiring diagram – CFL 1-2 – see example on page 132
Case dimensions – Ref Drawing -13 – see page 133
Length (L) 5.0 in (127.00 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 4.63 in (117.60 mm)
Mount Width (X or F) 2.4 in (60.96 mm)
Mount Slots (MS)
Weight 0.57 lbs
Exit Type Dual Entry (SE/BE, BES, 3W)
Remote Mounting Distance to Lamp 20 ft
Remote Mounting Wire Gauge 18 AWG
• Multi-voltage technology means a single ballast handles voltage from 108V to 305V
• Programmed starting for extended lamp life
• End-of-Lamp-Life protection
• Color coded poke-in connectors simplifies wiring
ProLine® CFL Electronic Ballasts
For 13 – 42W T4 CFL Lamps
71432 – GEC218-MVPS-BES
71433 – GEC218-MVPS-SE
71434 – GEC218-MVPS-3W
ProLine® CFL Electronic Ballasts
2 or 1 – CFQ18W/G24q 120-227V ProLine® PS
General characteristics
Ballast Type Electronic – Program / Rapid Start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70 °C (158 °F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info
End-of-Life Protection (EOL), Thermally protected,
Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71428, 71429, 71430
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
F14T5
2 120 31 0.26 A 1.00 3.23 99 1.5 10 -20/-29
2 277 31 0.12 A 1.00 3.23 98 1.5 10 -20/-29
F13T5
2 120 30 0.25 A 1.00 3.33 99 1.5 10 -20/-29
2 277 30 0.11 A 1.00 3.33 98 1.5 10 -20/-29
CFTR13W/
GX24q
2 120 29 0.25 A 1.00 3.45 99 1.5 10 -20/-29
2 277 29 0.11 A 1.00 3.45 99 1.5 10 -20/-29
1 120 16 0.16 A 1.00 6.25 96 1.5 10 -20/-29
1 277 16 0.06 A 1.00 6.25 96 1.5 10 -20/-29
CFQ13W/G24q
2 120 29 0.25 A 1.00 3.45 99 1.5 10 -20/-29
2 277 29 0.11 A 1.00 3.45 99 1.5 10 -20/-29
1 120 16 0.16 A 1.00 6.25 96 1.5 10 -20/-29
1 277 16 0.06 A 1.00 6.25 96 1.5 10 -20/-29
Other compatible lamps: CFQ18W/G24q, CFTR18W/GX24q, CFS16W/GR10q, CFS10W/GR10q
UL Type 1 Outdoor FCC Part 18 Class B at 120 Volts UL Type HL FCC – CLASS B Consumer UL Class P CSA UL Type CC UL Listed
Safety and performance
General characteristics
Ballast Type Electronic – Program / Rapid start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 70°C (158 °F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – CFL 1-2 – see example on page 132
Case dimensions – Ref Drawing -13 – see page 133
Length (L) 5.0 in (127.00 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 4.63 in (117.60 mm)
Mount Width (X or F) 2.4 in (60.96 mm)
Mount Slots (MS)
Weight 1.10 lbs
Exit Type Dual Entry (SE/BE, BES, 3W)
Remote Mounting Distance to Lamp 20 ft
Remote Mounting Wire Gauge 18 AWG
• Multi-voltage technology means a single ballast handles voltage from 108V to 305V
• Programmed starting for extended lamp life
• End-of-Lamp-Life protection
• Color coded poke-in connectors simplifies wiring
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71432, 71433, 71434
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
CFS21W/
GR10q
2 120 40 0.33 A 0.91 2.28 99 1.5 10 -20/-29
2 277 40 0.14 A 0.91 2.28 99 1.5 10 -20/-29
1 120 20 0.16 A 0.9 4.50 97 1.5 15 -20/-29
1 277 20 0.07 A 0.9 4.50 97 1.5 15 -20/-29
CFTR18W/
GX24q
2 120 39 0.33 A 1.05 2.69 97 1.5 10 -20/-29
2 277 39 0.14 A 1.05 2.69 97 1.5 10 -20/-29
1 120 20 0.17 A 1.05 5.25 97 1.5 10 -20/-29
1 277 20 0.08 A 1.05 5.25 97 1.5 10 -20/-29
CFS16W/
GR10q
2 120 37 0.31 A 1.00 2.70 99 1.5 10 -20/-29
2 277 37 0.13 A 1.00 2.70 99 1.5 10 -20/-29
Other compatible lamps: CFTR26W/GX24q, CFQ26W/G24q, CFS28W/GR10q, CFQ18W/G24q
UL Type 1 Outdoor FCC Part 18 Class B at 120 volts FCC – CLASS B Consumer UL Type HL UL Class P CSA UL Type CC UL Listed
Safety and performance
Specifications: Multivolt ProLine® CFL Quick Reference Chart
Lamp Type # of Lamps Input Volts
SE
(Side and
Bottom
Entry)
BES
(Bottom
Exit with
Studs)
3W
(3-Way
Mounting
Kit) Input Watts Line Current
Power
Factor Max THD%
Ballast
Factor
Ballast
Efficiency
Factor
GEC213-MVPS-xx
CFQ13W/GX4q
2
120
71429 71428 71430
29 0.25 0.99 10 1.0 3.45
277 29 0.11 0.99 10 1.0 3.45
1
120 16 0.16 0.96 10 1.0 6.25
177 16 0.06 0.96 10 1.0 6.25
CFTR13W/GX24q
2
120 29 0.25 0.99 10 1.0 3.45
277 29 0.11 0.99 10 1.0 3.45
1
120 16 0.16 0.96 10 1.0 6.25
277 16 0.06 0.96 10 1.0 6.25
CFQ18W/GX24q 1
120 20 0.17 0.99 12 1.0 5.00
277 20 0.07 0.97 12 1.0 5.00
CFTR18W/GX24q 1
120 20 0.17 0.99 12 1.0 5.00
277 20 0.07 0.97 12 1.0 5.00
CFS10W/GR10q
2
120 23 0.19 0.97 11 0.95 4.13
277 23 0.09 0.97 11 0.95 4.13
1
120 13 0.11 0.96 14 1.05 8.08
277 13 0.05 0.96 14 1.05 8.08
CFS16W/GR10q 1
120 17 0.14 0.96 12 1.0 5.88
277 17 0.06 0.96 12 1.0 5.88
GEC218-MVPS-xx
GFQ18W/G24q
2
120
71433 71432 71434
35 0.3 0.99 10 0.95 2.71
277 35 0.13 0.99 10 0.95 2.71
1
120 19 0.16 0.97 10 1.0 5.26
277 19 0.07 0.97 10 1.0 5.26
CFTR18W/GX24q
2
120 39 0.33 0.97 10 1.05 2.69
277 39 0.14 0.99 10 1.05 2.69
1
120 20 0.17 0.97 10 1.05 5.25
277 20 0.08 0.97 10 1.05 5.25
CFQ26W/G24q 1
120 28 0.24 0.99 12 1.0 3.57
277 28 0.10 0.96 12 1.0 3.57
GFTR26W/GX24q 1
120 28 0.24 0.99 12 1.0 3.57
277 28 0.10 0.96 12 1.0 3.57
CFS21W/GR10q
2
120 40 0.33 0.99 10 0.91 2.28
277 40 0.14 0.99 10 0.91 2.28
1
120 20 0.16 0.97 15 0.9 4.5
277 20 0.07 0.97 15 0.9 4.5
CFS16W/GR10q 2
120 37 0.31 0.99 10 1.0 2.70
277 37 0.13 0.99 10 1.0 2.70
CFS28W/GR10q 1
120 31 0.26 0.99 10 1.0 3.23
277 31 0.11 0.97 10 1.0 3.23
GEC226-MVPS-xx
CFQ26W/G24q
2
120
71444 71443 71445
51 0.43 0.99 10 1.0 1.96
277 51 0.19 0.99 10 1.0 1.96
1
120 27 0.23 0.98 10 1.0 3.7
277 27 0.10 0.98 10 1.0 3.7
CFTR26W/GX24q
2
120 54 0.45 0.99 10 1.0 1.85
277 54 0.20 0.99 10 1.0 1.85
1
120 29 0.24 0.98 10 1.10 3.79
277 29 0.11 0.98 10 1.10 3.79
CFTR42W/GX24q 1
120 46 0.38 0.98 10 0.98 2.13
277 46 0.17 0.98 10 0.98 2.13
CFT32W/GX24q 1
120 36 0.031 0.98 10 0.98 2.72
277 36 0.013 0.98 10 0.98 2.72
CFS21W/GR10q 2
120 51 0.042 0.99 10 1.12 2.20
277 51 0.18 0.99 10 1.12 2.20
FT24W/2G11 2
120 48 0.41 0.99 10 0.93 1.94
277 48 0.18 0.99 10 0.93 1.94
FC16T9/40W 1
120 43 0.36 0.99 10 1.00 2.33
277 43 0.16 0.97 10 1.00 2.33
124 See page 195 for warranty information. 125
Quick Reference
Guides
gelighting.com
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
See page 195 for warranty information.
71443 – GEC226-MVPS-BES
71444 – GEC226-MVPS-SE
71445 – GEC226-MVPS-3W
ProLine® CFL Electronic Ballasts
2 – CFQ26W, FT24 or 1 – 24W CFTR32 120-227V ProLine® PS
• Multi-voltage technology means a single ballast handles voltage from 108V to 305V
• Programmed starting for extended lamp life
• End-of-Lamp-Life protection
• Color coded poke-in connectors simplifies wiring
ProLine® CFL Electronic Ballasts
For 13 – 42W T4 CFL Lamps
General characteristics
Ballast Type Electronic – Program / Rapid start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 104°F (40°C)
Case Temperature (MAX) 75°C (167°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto restart, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – CFL 1-2 – see example on page 132
Case dimensions – Ref Drawing 13 – see page 133
Length (L) 5.0 in (127.00 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 4.63 in (117.60 mm)
Mount Width (X or F) 2.4 in (60.96 mm)
Mount Slots (MS)
Weight 0.57 lbs
Exit Type Dual Entry (SE/BE, BES, 3W)
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Order information
10 Pack Pallet Pack DIY Pack IP Pack
71443, 71444, 71445
UL Type 1 Outdoor UL Type HL FCC – CLASS B Consumer FCC Part 18 Class B at 120 volts UL Class P UL Type CC UL Listed CSA
Safety and performance
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
CFTR26W/GX24q
2 120 54 0.45 A 1.00 1.85 99 1.5 10 -20/-29
2 277 54 0.20 A 1.00 1.85 99 1.5 10 -20/-29
1 120 29 0.24 A 1.10 3.79 98 1.5 10 -20/-29
1 277 29 0.11 A 1.10 3.79 98 1.5 10 -20/-29
CFQ26W/G24q
1 120 51 0.43 A 1.00 1.96 99 1.5 10 -20/-29
1 277 51 0.19 A 1.00 1.96 99 1.5 10 -20/-29
2 120 27 0.23 A 1.00 3.70 98 1.5 10 -20/-29
2 277 27 0.10 A 1.00 3.70 98 1.5 10 -20/-29
CFTR42W/GX24q
1 120 46 0.38 A 0.98 2.13 98 1.5 10 -20/-29
1 277 46 0.17 A 0.98 2.13 98 1.5 10 -20/-29
CFTR32W/GX24q
1 120 36 0.31 A 98.00 272.22 98 1.5 10 -20/-29
1 277 36 0.13 A 0.98 2.72 98 1.5 10 -20/-29
Other compatible lamps: F24T5/HO, CFS21W/GR10q, FT24W/2G11, FC16T9/40W
ProLine® CFL Electronic Ballasts
For 40W Biax® CFL Ballasts
80683 – C240PUNVHP-B-IP
ProLine® CFL Electronic Ballasts
2 or 1 – FT40W2G11 PS UNV
General characteristics
Ballast Type Electronic – Program / Rapid Start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70 °C (158 °F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz /60 Hz
Dimensions
Wiring diagram – CFL 20C – see example on page 131
Case dimensions – Ref Drawing -B – see page 133
Length (L) 9.5 in (241.30 mm)
Width (W) 1.5 in (38.10 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 0.8 in (22.35 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 1.10 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 25 in (635 mm)
Blue and Red 33 in (838 mm)
Yellow 48 in (1219 mm)
White 25 in (635 mm)
• Electronic compact fluorescent ballasts for all general fluorescent applications
• Low-profile case
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80683
80680 – C240SI120RH-IP
ProLine® CFL Electronic Ballasts
2 – FT40W/2G11 IS 120
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70 °C (158 °F)
Ballast Factor Normal
Power Factor Correction Passive
Sound Rating A (20-24 decibels)
Additional Info End-of-Life Protection (EOL), Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz /60 Hz
Dimensions
Wiring diagram – CFL 1B – see example on page 131
Case dimensions – Ref Drawing C6 – see page 133
Length (L) 8.3 in (211.07 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL) 9.5 in (241.30 mm)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.87 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 33 in (838 mm)
Red 33 in (838 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
• Electronic compact fluorescent ballasts for all general fluorescent applications
• Low-profile case
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80680
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT40W/4P
2 120 76 0.63 A 0.90 1.18 98 1.5 10 0 / -18
2 277 73 0.26 A 0.90 1.23 98 1.5 10 0 / -18
1 120 41 0.34 A 1.00 2.43 95 1.5 10 0 / -18
1 277 40 0.15 A 1.00 2.50 95 1.5 10 0 / -18
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT40W/4P
2 120 67 0.61 A 0.88 1.31 95 1.7 20 50 / 10
1 120 40 0.40 A 1.02 2.55 90 1.7 20 50 / 10
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
47506 – C242UNVBES-IP
47509 – C242UNVSE-IP
ProLine® CFL Electronic Ballasts
2 – 42/36/32/26/24 watt CFL UNV Side Exit
• Electronic compact fluorescent ballasts for all general fluorescent applications
• Low-profile case
General characteristics
Ballast Type Electronic – Program / Rapid start
Starting Method Programmed start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 122°F (50°C)
Case Temperature (MAX) 75°C (167°F)
Ballast Factor Normal
Power Factor Correction Active
Sound Rating A (20-24 decibels)
Additional Info Auto restart, Thermally protected, Universal voltage
Electrical characteristics
Supply Current Frequency 50 Hz/60 Hz
Dimensions
Wiring diagram – CFL 5 – see example on page 132
Case dimensions – Ref Drawing 13 – see page 133
Length (L) 4.3 in (107.95 mm)
Width (W) 3.0 in (75.69 mm)
Height (H) 1.0 in (25.40 mm)
Mounting dimensions
Bracket Length (BL) 4.9 in (125.47 mm)
Mount Length (M) 4.6 in (117.09 mm)
Mount Width (X or F) 1.6 in (39.37 mm)
Mount Slots (MS)
Weight 0.90 lbs
Exit Type Bottom/Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Order information
10 Pack Pallet Pack DIY Pack IP Pack
47506, 47509
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non Consumer FCC Part 18 Class B at 120 volts UL Class P UL Type CC UL Listed CSA
Safety and performance
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
CFTR42W/4P
2 120 91 0.76 A 0.98 1.08 98 1.6 10 0 / -18
2 277 90 0.32 A 0.98 1.09 98 1.6 10 0 / -18
1 120 45 0.40 A 1.00 2.22 93 1.6 10 0 / -18
1 277 45 0.18 A 1.00 2.22 93 1.6 10 0 / -18
CFTR32W/4P
1 120 69 0.58 A 1.00 1.45 98 1.6 10 0 / -18
1 277 67 0.26 A 1.00 1.49 98 1.6 10 0 / -18
CFTR26W/4P
2 120 56 0.46 A 1.02 1.82 95 1.6 10 0 / -18
2 277 65 0.20 A 1.02 1.85 95 1.6 10 0 / -18
Other compatible lamps: FT55W/4P, FT36W/4P, FT24W/4P, FC9T522W/4P, FC12T555W/4P, FC12T540W/4P, CFTR70W/4P, CFTR57W/4P, CFS28W/4P, CFM3W/4P
126 See page 195 for warranty information. 127
Quick Reference
Guides
gelighting.com
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
See page 195 for warranty information.
ProLine® CFL Electronic Ballasts
For 40W Biax® CFL Ballasts
80681 – C240SI277RH-IP
ProLine® CFL Electronic Ballasts
2 – FT40W/2G11- IS 277
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70 °C (158 °F)
Ballast Factor Normal
Power Factor Correction Passive
Sound Rating A (20-24 decibels)
Additional Info End-of-Life Protection (EOL), Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz /60 Hz
Dimensions
Wiring diagram – CFL 1B – see example on page 131
Case dimensions – Ref Drawing C6 – see page 133
Length (L) 8.3 in (211.07 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL) 9.5 in (241.30 mm)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.87 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 33 in (838 mm)
Red 33 in (838 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
• Electronic compact fluorescent ballasts for all general fluorescent applications
• Low-profile case
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80681
80690 – C340SI120RH-IP
ProLine® CFL Electronic Ballasts
3 – FT40W/2G11 IS 120
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 70 °C (158 °F)
Ballast Factor Normal
Power Factor Correction Passive
Sound Rating A (20-24 decibels)
Additional Info End-of-Life Protection (EOL), Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz /60 Hz
Dimensions
Wiring diagram – CFL 51 – see example on page 131
Case dimensions – Ref Drawing C6 – see page 133
Length (L) 8.3 in (211.07 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL) 9.5 in (241.30 mm)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.87 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 33 in (838 mm)
Red 33 in (838 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
• Electronic compact fluorescent ballasts for all general fluorescent applications
• Low-profile case
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80690
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT40W/4P
2 277 67 0.27 A 0.88 1.31 95 1.7 20 50 / 10
1 277 40 0.17 A 1.02 2.55 90 1.7 20 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT40W/4P
3 120 98 0.88 A 0.88 0.89 95 1.7 20 50 / 10
2 120 75 0.68 A 0.99 1.32 90 1.7 20 50 / 10
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
ProLine® CFL Electronic Ballasts
For 40W Biax® CFL Ballasts
80691 – C340SI277RH-IP
ProLine® CFL Electronic Ballasts
3 – FT40W/2G11 IS 277
General characteristics
Ballast Type Electronic – Standard Instant Start
Starting Method Instant start
Lamp Wiring Series
Line Voltage Regulation (+/-) 10%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 70 °C (158 °F)
Ballast Factor Normal
Power Factor Correction Passive
Sound Rating A (20-24 decibels)
Additional Info End-of-Life Protection (EOL), Thermally protected
Electrical characteristics
Supply Current Frequency 50 Hz /60 Hz
Dimensions
Wiring diagram – CFL 51 – see example on page 131
Case dimensions – Ref Drawing C6 – see page 133
Length (L) 8.3 in (211.07 mm)
Width (W) 2.4 in (60.96 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL) 9.5 in (241.30 mm)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.87 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 2.70 lbs
Exit Type Side
Remote Mounting Distance to Lamp 12 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 33 in (838 mm)
Red 33 in (838 mm)
White 25 in (635 mm)
Black 25 in (635 mm)
• Electronic compact fluorescent ballasts for all general fluorescent applications
• Low-profile case
Order information
10 Pack Pallet Pack DIY Pack IP Pack
80691
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT40W/4P
3 277 98 0.39 A 0.88 0.89 95 1.7 20 50 / 10
2 277 75 0.30 A 0.99 1.32 90 1.7 20 50 / 10
UL Type 1 Outdoor UL Type HL FCC – CLASS A Non-Consumer UL Class P CSA UL Listed
Safety and performance
128 See page 195 for warranty information. 129
Quick Reference
Guides
gelighting.com
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
See page 195 for warranty information.
ProLine® CFL Electronic Ballasts
For 5 – 26W Preheat CFL Lamps
87634 – GEM1CF579PH277
ProLine® CFL Electronic Ballasts
1 – CFT579Q9W/G23 Pre Heat 277 (4205F2P)
General characteristics
Ballast Type Magnetic – Preheat
Starting Method Preheat
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – CFL 21 – see example on page 131
Case dimensions – Ref Drawing 01 – see page 133
Length (L) 2.8125 (71.43 mm)
Width (W) 1.1875 (30.16 mm)
Height (H) 1.6 in (41.14 mm)
Mounting dimensions
Bracket Length (BL) 2.8 in (71.45 mm)
Mount Length (M) 2.3 in (60.45 mm)
Mount Width (X or F)
Mount Slots (MS) 0.1 in (4.77 mm)
Weight 0.60 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 7 in (178 mm)
Black 9 in (229 mm)
• Magnetic compact fluorescent ballast construction for all general fluorescent lighting
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87634
87533 – GEM1CF13PH120
ProLine® CFL Electronic Ballasts
1 – CFT/Q13W/GX23 Pre Heat 120 (4111H2P)
General characteristics
Ballast Type Magnetic – Preheat
Starting Method Preheat
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – CFL 21 – see example on page 131
Case dimensions – Ref Drawing 2 – see page 133
Length (L) 3.0 in (77.01 mm)
Width (W) 1.25 in (31.75 mm)
Height (H) 1.75 in (44.45 mm)
Mounting dimensions
Bracket Length (BL) 3.0 in (77.01 mm)
Mount Length (M) 2.75 in (69.85 mm)
Mount Width (X or F)
Mount Slots (MS) 0.2 in (5.58 mm)
Weight 0.62 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Black 7 in (178 mm)
Black 9 in (229 mm)
• Magnetic compact fluorescent ballast construction for all general fluorescent lighting
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87533
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
CFT7W/2P 1 277 11 0.16 A 0.90 8.18 25 1.7 15 25 / -4
CFT9W/2P 1 277 11 0.15 A 0.85 7.72 27 1.7 15 25 / -4
F8T5 1 277 11 0.14 A 1.00 9.09 50 1.7 15 25 / -4
CFT5W/2P 1 277 10 0.18 A 1.00 10.00 22 1.7 15 25 / -4
F6T5 1 277 9 0.15 A 0.95 10.55 45 1.7 15 25 / -4
F4T5 1 277 8 0.16 A 0.95 11.87 40 1.7 15 25 / -4
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
CFQ13W/2P 1 120 15 0.25 A 0.90 6.00 50 1.7 10 50 / 10
CFT13W/2P 1 120 15 0.25 A 0.90 6.00 50 1.7 10 50 / 10
UL Type 1 Outdoor UL Type HL UL Class P UL Listed
Safety and performance
UL Type HL UL Class P cUL Listed UL Listed
Safety and performance
87655 – GEM2CF13PH277
CFL Magnetic Ballasts
2 – CFT/Q13W/GX23 Pre Heat 277 (4214PBES)
General characteristics
Ballast Type Magnetic – Preheat
Starting Method Preheat
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – CFL 9 – see example on page 131
Case dimensions – Ref Drawing 8 – see page 133
Length (L) 4.75 in (120.65 mm)
Width (W) 2.1 in (55.62 mm)
Height (H) 1.6 in (41.40 mm)
Mounting dimensions
Bracket Length (BL) 4.75 in (120.65 mm)
Mount Length (M) 4.375 in (111.12 mm)
Mount Width (X or F)
Mount Slots (MS) 0.2 in (5.58 mm)
Weight 1.60 lbs
Exit Type Bottom
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 12 in (305 mm)
Black 12 in (305 mm)
White 12 in (305 mm)
• Magnetic compact fluorescent ballast construction for all general fluorescent lighting
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87655
CFL Magnetic Ballasts
For 5 – 26W Preheat CFL Lamps
87700 – GEM2CF24PH277
CFL Magnetic Ballasts
2 – CFQ26W/G24d Pre Heat 277 (4226PBES)
General characteristics
Ballast Type Magnetic – Preheat
Starting Method Preheat
Lamp Wiring Parallel
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (4C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – CFL 8 – see example on page 131
Case dimensions – Ref Drawing 10 – see page 133
Length (L) 6.5 in (166.62 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.6 in (42.92 mm)
Mounting dimensions
Bracket Length (BL) 6.5 in (166.62 mm)
Mount Length (M) 6.0 in (152.40 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (7.87 mm)
Weight 2.93 lbs
Exit Type Bottom
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
Blue 15 in (381 mm)
Black 15 in (381 mm)
White 15 in (381 mm)
• Magnetic compact fluorescent ballast construction for all general fluorescent lighting
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87700
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
CFQ13W/2P 2 277 32 0.12 A 0.90 2.81 95 1.7 30 25 / -4
CFT13W/2P 2 277 32 0.12 A 0.90 2.81 95 1.7 30 25 / -4
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
CFQ26W/2P 2 277 55 0.25 A 0.90 1.63 97 1.5 30 25 / -4
CFTR26W/2P 2 277 55 0.25 A 0.90 1.63 97 1.5 30 25 / -4
UL Type 1 Outdoor UL Type HL UL Class P UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P UL Listed
Safety and performance
130 See page 195 for warranty information. 131
Quick Reference
Guides
gelighting.com
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
See page 195 for warranty information.
CFL Magnetic Ballasts
For 36 – 40W CFL Lamps
87623 – GEM2FT36RS120
CFL Magnetic Ballasts
2 – FT36W/2G11 RS 120 (4150P)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – CFL 5 – see example on page 132
Case dimensions – Ref Drawing ST – see page 133
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.38 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 20 in (508 mm)
Blue and Red 20 in (508 mm)
Yellow 20 in (508 mm)
• Magnetic compact fluorescent ballast construction for all general fluorescent lighting
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87623
87625 – GEM2FT40RS120
CFL Magnetic Ballasts
2 – FT40W/2G11RS RS 120 (4152P)
General characteristics
Ballast Type Magnetic – Rapid Start
Starting Method Rapid start
Lamp Wiring Series
Line Voltage Regulation (+/-) 5%
Ambient Temperature (MAX) 105°F (41°C)
Case Temperature (MAX) 90°C (194°F)
Ballast Factor Normal
Power Factor Correction
Sound Rating A (20-24 decibels)
Additional Info Auto-restart, Thermally protected
Electrical characteristics
Supply Current Frequency 60 Hz
Dimensions
Wiring diagram – CFL 5 – see example on page 132
Case dimensions – Ref Drawing ST – see page 133
Length (L) 9.5 in (241.30 mm)
Width (W) 2.3 in (60.45 mm)
Height (H) 1.5 in (39.37 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 8.8 in (225.80 mm)
Mount Width (X or F) 1.6 in (42.92 mm)
Mount Slots (MS) 0.3 in (7.92 mm)
Weight 3.38 lbs
Exit Type Side
Remote Mounting Distance to Lamp 10 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Length (± 1 in)
White and Black 20 in (508 mm)
Blue and Red 20 in (508 mm)
Yellow 20 in (508 mm)
• Magnetic compact fluorescent ballast construction for all general fluorescent lighting
Order information
10 Pack Pallet Pack DIY Pack IP Pack
87625
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT36W/4P 2 120 78 0.70 A 0.96 1.23 93 1.7 20 50 / 10
Specifications by lamp and wattage
Lamp # of Lamps Line Volts System Watts Nom. Line Current System Ballast Factor Ballast Efficacy Factor Power Factor % (>=) Crest Factor (<=) THD (<=) Min. Starting Temp (°F/°C)
FT40W/4P 2 120 81 0.68 A 1.00 1.23 98 1.7 20 50 / 10
UL Type 1 Outdoor UL Type HL UL Class P UL Listed
Safety and performance
UL Type 1 Outdoor UL Type HL UL Class P UL Listed
Safety and performance
Wiring Diagrams
Compact Fluorescent Ballasts
CFL 20C CFL 1B
CFL 51 CFL 21
CFL 9 CFL 8
132 See page 195 for warranty information. 133
Quick Reference
Guides
gelighting.com
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
See page 195 for warranty information.
Wiring Diagrams
Compact Fluorescent Ballasts
CFL 5
CFL 1-2
Case Dimensions
Compact Fluorescent Ballasts
-B
C6
01
2
8
10
13
ST
See page 195 for warranty information. 135
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Electronic HID
For 20 – 150W Pulse Start HID Lamps
87490 – GEMH20-MLF-120
Electronic HID
1 – 20W M156 120V Electronic HID
General characteristics
Ballast Type Electronic – Low Frequency
ANSI Lamp Codes M156
Voltage 120
Line Voltage Regulation (+/-) 10%
Circuit Type Electronic
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 131°F (55°C)
Case Temperature (MAX) 85°C (185°F)
Sound Rating A (20-24 decibels)
Additional Info End-of-Life Protection (EOL), Inherent thermal protection
Dimensions
Wiring diagram WD-eHID MLF/MSF – see example on page 140
Case dimensions – Ref Drawing MLF – see page 141
Length (L) 3.7 in (94.99 mm)
Width (W) 1.5 in (39.87 mm)
Height (H) 1.0 in (25.40 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 3.3 in (85.34 mm)
Mount Width (X or F) 1.1 in (30.22 mm)
Mount Slots (MS) 0.1 in (4.31 mm)
Weight 0.38 lbs
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths
Black
Brown
White
Red
Electrical characteristics
Lamp Operating Frequency 133 Hz
Supply Current Frequency 60 Hz/ 50 Hz/ Supply Current Frequency (MIN) / 50 Hz
RoHS Compliant ANSI – C62.41 UL 1029 Listed FCC-CLASS A Non-Consumer cUL Listed UL Listed
Safety and performance
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Case 1 12
• Light weight, low-profile housing
• Superior low-frequency square-wave-frequency design maximizes performance and life of
ceramic metal halide lamps
• Ultra-slim can size for fixture design flexibility
87501 – GEMH39-MSF-120
Electronic HID
1 – 39W M130 120V Electronic HID
General characteristics
Ballast Type Electronic – Low Frequency
ANSI Lamp Codes M130
Voltage 120
Line Voltage Regulation (+/-) 10%
Circuit Type
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 131°F (55°C)
Case Temperature (MAX) 90 °C (194 °F)
Sound Rating A (20-24 decibels)
Additional Info End-of-Life Protection (EOL), Thermally protected
Dimensions
Wiring diagram WD-eHID MLF/MSF – see example on page 140
Case dimensions – Ref Drawing MSF – see page 141
Length (L) 3.7 in (94.99 mm)
Width (W) 2.9 in (75.69 mm)
Height (H) 1.2 in (30.73 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 3.3 in (86.10 mm)
Mount Width (X or F) 2.5 in (63.75 mm)
Mount Slots (MS) 0.1 in (4.31 mm)
Weight 0.38 lbs
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths
Black
Brown
White
Red
Electrical characteristics
Lamp Operating Frequency 130 Hz
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 Suitable for recessed use UL 1029 Listed cUL Listed UL Listed
Safety and performance
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Case 1 10
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M156
20W Ceramic
Metal Halide
120
System Wattage (W) 22.50
Nominal Current 0.36 A
Ballast Factor 1
Ballast Efficiency Factor 0.89
Open Circuit Voltage 4,000V
Drop Out Voltage 96V
Power Factor (>=)% 56
Crest Factor (<) 1.40
THD % (<) 79
Min. Starting Temp (°F/°C) 0 / -18
Fuse Rating 3
UL Bench Top Rise
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M130
39W Ceramic
Metal Halide
120
System Wattage (W) 43.00
Nominal Current 0.37 A
Ballast Factor 1.00
Ballast Efficiency Factor 0.91
Open Circuit Voltage
Drop Out Voltage 96V
Power Factor (>=)% 99
Crest Factor (<) 1.40
THD % (<) 6.80
Min. Starting Temp (°F/°C) 0 / -18
Fuse Rating 3
UL Bench Top Rise
Understanding Electronic
UltraMax® HID Ballasts
GE offers a complete line of electronic ballasts for HID lighting systems. Electronic HID,
like electronic fluorescent systems that preceded it, significantly improve the performance
of HID lighting. Electronic UltraMax® eHID Ballasts use solid-state components to start and
operate HID lamps. Electronic eHID ballasts use IC chips to control and give feedback for
optimal performance of the lighting system. GE eHID ballasts improve the efficiency, maintain
higher lumens, enhance lamp life and color control, and operate more quietly than the
magnetic core and coil ballast that they replace.
GE’s line of UltraCool UltraMax® eHID ballasts can provide up to 70% energy savings and
four times the life of standard halogen. End users can meet strict watts per square foot
requirements while achieving significant wattage savings and color control with ceramic
metal halide lamps and GE eHID ballasts.
GE’s UltraMax® eHID ballasts operate only pulse start and ceramic metal halide lamps.
GE UltraMax® eHID ballasts operate lamps at a low frequency square wave to maximize
lamp performance. Extensive analysis of all brands of lamps suggests that the most
compatible driving waveform for an electronic HID electronic ballast is a low-frequency
squared wave (L.F.S.W.) with higher order harmonic content. L.F.S.W. has been established as
a dependable method of ballasting low-wattage HID lamps with significant industry support.
Analysis of lamp data has shown that there are limited operating bands between 1 kHz to
200 kHz in which electronic ballast could operate a lamp wattage family without causing
unacceptable arc instability due to acoustic resonance. GE’s UltraMax® eHID constantly
measures and adjusts the wattage, optimizing the ceramic metal halide lamp performance.
GE high-wattage eHID ballasts will operate 250, 300, 320,350 or 400 watt pulse start or
ceramic metal halide lamps with one ballast. The eHID Ballast with a PulseArc lamp will produce
70% more lumens per watt than the obsolete probe start magnetic core and coil system.
Variable dimming to 50% power reduction is an option with GE eHID high wattage ballast.
134
GE Ballast HID Electronic nomenclature
GEMH100MSF-120
Pack Type
No extension
= Standard
Distributor Pack
B=Bulk pack
Voltage
120 = 120 volt
277 = 277 volt
347 = 347 volt
480 = 480 volt
MV = 120-277 volts
Lamp Watts
Connector
F = Side leads w/ feet
N = Side leads no feet
J = Bottom leads
w/ studs
JN = Bottom leads
no studs
GE Ballast
GEMH = Electronic MH
Housing
MA=Metal
Housing
ML=Mini Slim
MS=Mini Square
SL=Slim Line
E=PCB board
136 See page 195 for warranty information. 137
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Electronic HID
For 20 – 150W Pulse Start HID Lamps
87516 – GEMH50-MSF-120
Electronic HID
1 – 50W, M110, M/C148, 120V. Electronic HID
General characteristics
Ballast Type Electronic – Low Frequency
ANSI Lamp Codes M148, M110, C148
Voltage 120
Line Voltage Regulation (+/-) 10%
Circuit Type Electronic
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 131°F (55°C)
Case Temperature (MAX) 90°C (194°F)
Sound Rating A (20-24 decibels)
Additional Info End of Life Protection (EOL), Thermally protected
Dimensions
Wiring diagram WD-eHID MLF/MSF – see example on page 140
Case dimensions – Ref Drawing MSF – see page 141
Length (L) 3.7 in (94.99 mm)
Width (W) 2.9 in (75.69 mm)
Height (H) 1.2 in (30.73 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 3.3 in (86.10 mm)
Mount Width (X or F) 2.5 in (63.75 mm)
Mount Slots (MS) 0.1 in (4.31 mm)
Weight 0.62 lbs
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
Black 1 Left 10 in (254 mm)
Brown 1 Right 10 in (254 mm)
White 1 Left 10 in (254 mm)
Red 1 Right 10 in (254 mm)
Electrical characteristics
Lamp Operating Frequency 130 Hz
Supply Current Frequency 60 Hz/50 Hz
Housing meets UL94V0 flame retardant RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL 1029 Listed FCC-CLASS A Non-Consumer cUL Listed UL Listed
Safety and performance
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Case 1 10
87531 – GEMH70-MSF-120
Electronic HID
1 – 70W, M98, M/C143, 120V Electronic HID
General characteristics
Ballast Type Electronic – Low Frequency
ANSI Lamp Codes M98, M143, M139, C143, C139
Voltage 120
Line Voltage Regulation (+/-) 10%
Circuit Type
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 131°F (55°C)
Case Temperature (MAX) 90°C (194°F)
Sound Rating A (20-24 decibels)
Additional Info End of Life Protection (EOL), Thermally protected
Dimensions
Wiring diagram WD-eHID MLF/MSF – see example on page 140
Case dimensions – Ref Drawing MSF – see page 141
Length (L) 3.7 in (94.99 mm)
Width (W) 2.9 in (75.69 mm)
Height (H) 1.2 in (30.73 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 3.3 in (86.10 mm)
Mount Width (X or F) 2.5 in (63.75 mm)
Mount Slots (MS) 0.1 in (4.31 mm)
Weight 0.38 lbs
Exit Type Side
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
Black 1 Left 10 in (254 mm)
Brown 1 Right 10 in (254 mm)
White 1 Left 10 in (254 mm)
Red 1 Right 10 in (254 mm)
Electrical characteristics
Lamp Operating Frequency 130 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Case 1 10
Housing meets UL94V0 flame retardant RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL 1029 Listed FCC-CLASS A Non-Consumer cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M98, M143, M139 ,
C143, C139
70W Ceramic
Metal Halide
70W Quartz
Metal Halide
120
System Wattage (W) 77
Nominal Current 0.68 A
Ballast Factor 1.00
Ballast Efficiency Factor 0.91
Open Circuit Voltage
Drop Out Voltage
Power Factor (>=)% 99
Crest Factor (<) 1.4
THD % (<) 8.3
Min. Starting Temp (°F/°C) 0 / -18
Fuse Rating 3
UL Bench Top Rise
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M148
C148
120 M110
50W Quartz
Metal Halide
120
System Wattage (W) 58 System Wattage (W) 58
Nominal Current 0.48 A Nominal Current 0.48 A
Ballast Factor 1 Ballast Factor 1
Ballast Efficiency Factor Ballast Efficiency Factor 0.86
Open Circuit Voltage Open Circuit Voltage
Drop Out Voltage 96V Drop Out Voltage 96V
Power Factor (>=)% 99 Power Factor (>=)% 99
Crest Factor (<) 1.4 Crest Factor (<) 1.4
THD % (<) 6.9 THD % (<) 6.9
Min. Starting Temp (°F/°C) 0 / -18 Min. Starting Temp (°F/°C) 0 / -18
Fuse Rating 130 Fuse Rating 130
UL Bench Top Rise UL Bench Top Rise
87546 – GEMH70-SLJ-MV
Electronic HID
1 – 70W, M98, M/C143, 120V. Electronic HID
General characteristics
Ballast Type Electronic – Low Frequency
ANSI Lamp Codes M98, M143, C143, M139, C139
Voltage 120/277
Line Voltage Regulation (+/-) 10%
Circuit Type
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 131°F (55°C)
Case Temperature (MAX) 90°C (194°F)
Sound Rating A (20-24 decibels)
Additional Info End of Life Protection (EOL), Thermally protected
Dimensions
Wiring diagram WD-eHID SLJ – see example on page 140
Case dimensions – Ref Drawing SLJ – see page 141
Length (L) 7.2 in (184.91 mm)
Width (W) 2.5 in (65.53 mm)
Height (H) 2.2 in (55.88 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 0.4 in (10.92 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 0.38 lbs
Exit Type Bottom Leads with Studs
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
Black 1 Left 10 in (254 mm)
Brown 1 Right 10 in (254 mm)
White 1 Left 10 in (254 mm)
Red 1 Right 10 in (254 mm)
Electrical characteristics
Lamp Operating Frequency 130 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Case 1 10
Electronic HID
For 20 – 150W Pulse Start HID Lamps
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL 1029 Listed FCC-CLASS A Non-Consumer cUL Listed
Safety and performance
87561 – GEMH100-SLJ-MV
Electronic HID
1 – 100W, M90, M/C140, 120V-277V Electronic HID
General characteristics
Ballast Type Electronic – Low Frequency
ANSI Lamp Codes M90, M140, C140
Voltage 120/277
Line Voltage Regulation (+/-) 10%
Circuit Type
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 131°F (55°C)
Case Temperature (MAX) 90°C (194°F)
Sound Rating A (20-24 decibels)
Additional Info End of Life Protection (EOL), Thermally protected
Dimensions
Wiring diagram WD - eHID SLJ – see example on page 140
Case dimensions – Ref Drawing SLJ – see page 141
Length (L) 7.2 in (184.91 mm)
Width (W) 2.5 in (65.53 mm)
Height (H) 2.2 in (55.88 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 0.4 in (10.92 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 0.38 lbs
Exit Type Bottom Leads with Studs
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
Black 1 Left 10 in (254 mm)
Brown 1 Right 10 in (254 mm)
White 1 Left 10 in (254 mm)
Red 1 Right 10 in (254 mm)
Electrical characteristics
Lamp Operating Frequency 130 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Case 1 10
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL 1029 Listed cUL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by Line Voltage
M98, M143, M139,
C143, C139
70W Ceramic
Metal Halide
70W Quartz
Metal Halide
Pulse Arc
120 277
System Wattage (W) 77 77
Nominal Current 0.66 A 0.30 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.91 0.91
Open Circuit Voltage
Drop Out Voltage 96V 96V
Power Factor (>=)% 99 97
Crest Factor (<) 1.4 1.4
THD % (<) 4.9 7.7
Min. Starting Temp (°F/°C) 0 / -18 0 / -18
Fuse Rating 3 3
UL Bench Top Rise
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M90, M140
100W Ceramic
Metal Halide
100W Quartz
Metal Halide
120 277 C140 120 277
System Wattage (W) 110 107 System Wattage (W) 110 107
Nominal Current 0.93 A 0.41 A Nominal Current 0.93 A 0.41 A
Ballast Factor 1 1 Ballast Factor 1 1
Ballast Efficiency Factor 0.91 0.93 Ballast Efficiency Factor
Open Circuit Voltage Open Circuit Voltage
Drop Out Voltage 96V 96V Drop Out Voltage 96V 96V
Power Factor (>=)% 99 98 Power Factor (>=)% 99 98
Crest Factor (<) 1.4 1.4 Crest Factor (<) 1.4 1.4
THD % (<) 4.7 7.8 THD % (<) 4.7 7.8
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 Min. Starting Temp (°F/°C) 0 / -18 0 / -18
Fuse Rating 3 3 Fuse Rating 3 3
UL Bench Top Rise UL Bench Top Rise
138 See page 195 for warranty information. 139
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Electronic HID
For 20 – 150W Pulse Start HID Lamps
87576 – GEMH150-SLJ-MV
Electronic HID
1 – 150W, M102, M/C142, 120V-277V Electronic HID
General characteristics
Ballast Type Electronic – Low Frequency
ANSI Lamp Codes M142, M102, C142
Voltage 120/277
Line Voltage Regulation (+/-) 10%
Circuit Type
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 131°F (55°C)
Case Temperature (MAX) 85°C (185°F)
Sound Rating A (20-24 decibels)
Additional Info End of Life Protection (EOL), Thermally protected
Dimensions
Wiring diagram WD-eHID SLJ – see example on page 140
Case dimensions – Ref Drawing SLJ – see page 141
Length (L) 7.2 in (184.91 mm)
Width (W) 2.5 in (65.53 mm)
Height (H) 2.2 in (55.88 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 0.4 in (10.92 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 0.38 lbs
Exit Type Bottom Leads with Studs
Remote Mounting Distance to Lamp 8 ft
Remote Mounting Wire Gauge 18 AWG
Lead lengths Qty Exit Length (± 1 in)
Black 1 Left 10 in (254 mm)
Brown 1 Right 10 in (254 mm)
White 1 Left 10 in (254 mm)
Red 1 Right 10 in (254 mm)
Electrical characteristics
Lamp Operating Frequency 130 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Case 1 10
RoHS Compliant UL Type 1 Outdoor ANSI – C62.41 UL 1029 Listed FCC-CLASS A Non-Consumer cUL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M102, M142
150W Quartz
Metal Halide,
150W Ceramic
Metal Halide
120 277 C142 120 277
System Wattage (W) 167 164 System Wattage (W) 167 164
Nominal Current 1.44 A 0.62 A Nominal Current 1.44 A 0.62 A
Ballast Factor 1 1 Ballast Factor 1 1
Ballast Efficiency Factor 0.90 0.91 Ballast Efficiency Factor
Open Circuit Voltage Open Circuit Voltage
Drop Out Voltage 96V 96V Drop Out Voltage 96V 96V
Power Factor (>=)% 99 99 Power Factor (>=)% 99 99
Crest Factor (<) 1.4 1.4 Crest Factor (<) 1.4 1.4
THD % (<) 4.2 10.6 THD % (<) 4.2 10.6
Min. Starting Temp (°F/°C) 0 / -18 0 / -18 Min. Starting Temp (°F/°C) 0 / -18 0 / -18
Fuse Rating 3 3 Fuse Rating 3 3
UL Bench Top Rise UL Bench Top Rise
Electronic HID
For 250 – 400W Pulse Start HID Lamps
29377 – GE-MH-250-400-MA
Electronic HID
1 – 250 to 400W, UltraMax® HID, Electronic, 208-277, 50-60 Hz
General characteristics
Ballast Type Electronic – Dimming
ANSI Lamp Codes M155, M153, M138, M135, M132, M131, M154
Voltage 208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type Electronic
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 130°F (54°C)
Case Temperature (MAX)
Sound Rating A (20-24 decibels)
Additional Info Thermally protected
Dimensions
Wiring diagram eHID – see example on page 140
Case dimensions – Ref Drawing eHID - Bracket – see page 141
Length (L) 14.9 in (378.66 mm)
Width (W) 14.9 in (378.66 mm)
Height (H) 9.3 in (237.79 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL) 6.5 in (165.10 mm)
Mount Length (M)
Mount Width (X or F)
Mount Slots (MS)
Weight 10.20 lbs
Exit Type Bottom
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Lead lengths Qty Exit Length (± 1 in)
Black and Green 1 Bottom 9 in (229 mm)
Brown and Red 1 Bottom 10 in (254 mm)
White 1 Bottom 9 in (229 mm)
Yellow 2 Bottom 9 in (229 mm)
Electrical characteristics
Supply Current Frequency 50 Hz/ 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 1
• High efficiency electronic ballast provides 48% less ballast losses compared to electromagnetic
CWA ballasts
• Improves lumen maintenance by 10 points on pulse start lamps
• Multi-voltage technology handles voltage from 208 to 277V
UL Type 1 Outdoor UL Type HL UL Class P FCC-CLASS A Non-Consumer cUL Listed UL Listed
Safety and performance
89646 – GEMH250-400M-V50
Electronic HID
1 – 250 to 400W, UltraMax® HID, Dimming, 208-277, 50-60Hz
General characteristics
Ballast Type Electronic – Dimming
ANSI Lamp Codes M155, M153, M138, M135, M132, M131
Voltage 208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type Electronic
Insulation Class
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Ambient Temperature (MAX) 130°F (54°C)
Case Temperature (MAX)
Sound Rating A (20-24 decibels)
Additional Info Thermally protected
Dimensions
Wiring diagram eHID– see example on page 140
Case dimensions – Ref Drawing eHID-DIM – see page 141
Length (L) 14.9 in (378.66 mm)
Width (W) 14.9 in (378.66 mm)
Height (H) 9.3 in (237.79 mm)
Frame Size (H x L)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 6.5 in (165.10 mm)
Mount Width (X or F)
Mount Slots (MS)
Weight 10.20 lbs
Exit Type Bottom
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Lead lengths Qty Exit Length (± 1 in)
Black and Green 1 Bottom 9 in (229 mm)
Brown and Red 1 Bottom 10 in (254 mm)
White 1 Bottom 9 in (229 mm)
Yellow 2 Bottom 9 in (229 mm)
Electrical characteristics
Supply Current Frequency 50 Hz/ 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 1
UL Type 1 Outdoor UL Type HL Housing meets UL94V0 flame retardant RoHS Compliant UL Listed
UL 1029 Listed FCC-CLASS A Non-Consumer cUL Listed ANSI – C62.41
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M155, M135
400W Quartz
Metal Halide
208 240 277 M154, M132
320W Quartz
Metal Halide
208 240 277
System Wattage (W) 431 431 428 System Wattage (W) 346 346 343
Nominal Current 2.23 A 1.92 A 1.65 A Nominal Current 1.79 A 1.54 A 1.34 A
Ballast Factor 1 1 1 Ballast Factor 1 1 1
Ballast Efficiency Factor 0.93 0.93 0.93 Ballast Efficiency Factor 0.92 0.92 0.93
Open Circuit Voltage Open Circuit Voltage
Drop Out Voltage Drop Out Voltage
Power Factor (>=)% 99 99 99 Power Factor (>=)% 99 99 99
Crest Factor (<) Crest Factor (<)
THD % (<) 15 15 15 THD % (<) 15 15 15
Min. Starting Temp (°F/°C) -20 / -29 -20 / -29 -20 / -29 Min. Starting Temp (°FC) -20 / -29 -20 / -29 -20 / -29
Fuse Rating Fuse Rating
UL Bench Top Rise UL Bench Top Rise
*Specifications by lamp and line voltage limited to two charts, please see gelighting.com for additional lamps.
Specifications by lamp & line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M155, M135
400W Quartz
Metal Halide
208 240 277 M154, M132
320W Quartz
Metal Halide
208 240 277
System Wattage (W) 431 431 428 System Wattage (W) 346 346 343
Nominal Current 2.23 A 1.92 A 1.65 A Nominal Current 1.79 A 1.54 A 1.34 A
Ballast Factor 1 1 1 Ballast Factor 1 1 1
Ballast Efficiency Factor 0.93 0.93 0.93 Ballast Efficiency Factor 0.92 0.92 0.93
Open Circuit Voltage Open Circuit Voltage
Drop Out Voltage Drop Out Voltage
Power Factor (>=)% 99 99 99 Power Factor (>=)% 99 99 99
Crest Factor (<) Crest Factor (<)
THD % (<) 15 15 15 THD % (<) 15 15 15
Min. Starting Temp (°F/°C) -20 / -29 -20 / -29 -20 / -29 Min. Starting Temp (°FC) -20 / -29 -20 / -29 -20 / -29
Fuse Rating Fuse Rating
UL Bench Top Rise UL Bench Top Rise
*Specifications by lamp and line voltage limited to two charts, please see gelighting.com for additional lamps.
140 See page 195 for warranty information. 141
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Wiring Diagrams
HID Electronic
WD-eHID MLF/MSF WD-eHID-SLJ
eHID
MLF
MSF
SLJ
Case Dimensions
HID Electronic
MLF MSF
SLJ eHID-Bracket
eHID-DIM
See page 195 for warranty information. 143
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Understanding Electromagnetic
HID Ballasts
GE offers High Intensity Discharge (HID) ballasts for mercury, probe start metal halide, pulse
start metal halide and high pressure sodium lamps. Standard metal halide lamps or probe
start metal halide over 150 watts, like fluorescent, are electric discharge lamps and require an
open circuit voltage of nearly two times the operating voltage to the initiate the arc between
the two electrodes in the arc tube. High pressure sodium, pulse start metal halide and probe
start metal halide lamps 150 watts or less require an ignitor to initiate the high voltage to
start the lamps. The ballasts provide the starting voltage with the igniter, where required, and
provides stability for the lamp. HID lamps have negative impedance characteristics and would
draw current until destruction unless a ballast was in place to regulate the current.
HID lamps take several minutes to warm-up and reach full light output. If power is interrupted
between the lamp and the ballast, the arc will extinguish and lamp will go out. The lamp must
cool down and reduce the vapor pressure before it will re-start. Typical warm-up and restrike
times are as follows:
142
GE HID Ballast Types
CORE AND COIL
The most common HID ballasts are the core and coil and is used in 90% of the fixture
applications. Core and coil ballasts consist of one, two or three copper (or aluminum) coils on a
core of electrical-grade steel laminations. HID ballasts are classified by the kind of circuit they
use: Reactor (R), High Reactance autotransformer (HX), Constant Wattage Autotransformer
(CWA), Regulated lag (Reg Lag) or Electronic. HID ballast are also classified as high power factor
(HPF) or normal power factor (NPF).
GE HID ballast 150 watts or less have High Reactance Autotransformer circuits and high
power factor (HX-HPF). GE HID ballast greater that 150 watts have Constant Wattage
Autotransformer circuits and are high power factor (HPF).
CWA ballast is the most common circuit for core and coil ballast. CWA circuits provide for
stable light regulation. The CWA circuit consists of a high reactance autotransformer with a
capacitor in series with the lamp resulting with high power factor ballast. In most CWA ballast
circuits a 10% drop in line voltage will only reduce the light output and wattage by 5%. The
CWA circuit ballast requires an igniter for QMH pulse start, ceramic metal halide and HPS
lamps. Igniters are also required for QMH lamps 150 watts or less.
Light Source Warm-Up Time Restrike Time
Mercury 5-7 minutes 3-6 minutes
Metal Halide (Probe Start) 3-4 minutes 10-20 minutes
Metal Halide (Pulse Start) 2 minutes 3-4 minutes
High Pressure Sodium 7-10 minutes 1/2-1 minute
Distributor Ballast Kits
GE stocks a comprehensive inventory of quad and 5-tap HID voltage
ballast kits. The kits contain the appropriate core and coil, capacitor,
ignitor (where required), mounting bracket, mounting hardware and
instructions to allow the stocking distributor to meet the needs of
their customer while minimizing their investment in component parts.
The quad ballast kit has color-coded leads to identify voltages and
operates at 120/208/240/277. The 5-tap HID ballast kits also include
480-volt applications and are listed as ML5, though GE also offers
single-voltage kits for 480-volt with 120-volt taps for stand-by lighting.
Also available for metal halide and high pressure sodium applications
is the 5-tap ballast-lamp replacement kit listed as -55. This easy-to-
carry, convenient, all-in-one kit, ensures ballast-lamp compatibility by
including the lamp as well.
Ignitors and capacitors, where required, are included with the quad
and 5-tap ballast kits.
Capacitors
Most GE capacitors and ignitors are sold in ballast kits that come
pre-wired and reduce labor cost. Capacitors and ignitors are also
sold separately.
Power factor capacitors are used to reduce the negative effects that
inductive devices (HID ballast) have on power factor ratings. GE sells
a complete line of capacitors that must be properly matched to the
lamp and HID ballast. GE capacitors have bleed-in resistors and use
biodegradable, nontoxic (no PCBs) dielectric fluid.
GE Oil-filled Capacitors are packaged in metal cases (up to
520V ratings). All GE capacitors are designed for 60,000 hours of
continuous life.
Dry Capacitors do not contain oil and are manufactured with
plastic casing. Dry casings are rated up 100°C maximum.
Dry capacitors are designed and rated for AC voltages below
400V at 50 or 60Hz.
Ignitors
Ignitors are also sold in individual cartons for replacement needs.
Ignitors supply a high voltage pulse to ionize the gas creating the
glow discharge. Once the lamp is started the ignitor stops providing
the pulse. Ignitors are designed to last thousand of hours; however, if
the lamp fails or the socket is empty, the ignitor will continue to pulse.
The lamps should be replaced or the fixture turned off to prevent
premature failure of the ignitor.
Standard ignitors are supplied with metal halide ballast 150 watts
or less, pulse start metal halide and high-pressure sodium ballast.
There are several different ignitors that meet the needs of many GE
lamp and ballast combinations. The appropriate ignitor is listed in the
catalog under the ballast specifications.
Potted Core and Coil Ballast
GE potted core and coil ballasts are designed for applications
requiring quieter or cooler operation than provided by standard coil
and coil ballast. The potting material is sand-filled polyester which
provides excellent sound-deadening and heat-transfer qualities.
F-Can Ballast
GE F-Can ballast is recommended for indoor applications and
where ballast noise must be minimized. F-Can ballast are encased
in fluorescent ballast-type cans and potted with asphalt insulating
materials to minimize noise.
Ballast Date and Temperature Codes
Date Codes
GE HID core and coil ballast manufacturing date codes are located
on the top end of the core. They are printed in white and indicate year,
month manufactured, and order the ballast was manufactured in the
month. A code of 070100001 would indicate manufacture date of
07 (year 2007), 01 (month of January), and 00001 would be the
manufacturing sequence.
UL Bench Top Temperature Code
To help with UL inspection, the UL Bench top code is listed on the GE
label on the core and coil ballast as 1029X. X is the temperature code
and represented by the following temperature classifications: A, B, C,
D, E and F.
UL Bench Top
Letter Code
Temperature Range for
Class H (180C) Ballast
A Less than 75C
B 75C < 80C
C 80C < 85C
D 85C < 90C
E 90C < 95C
F 95C < 100C
GE Ballast HID Electromagnetic nomenclature
GEM1000MLTAC5D-5
GE Ballast
M = EM Ballast
GEH = Mercury
GEM = Metal
Halide
GEP = Pulse
Start Metal
Halide
GES = HPS
Lamp Watts:
1000W Circuit Type:
R = Reactor
A = CWA
I = CWI
O = Iso Reg
L = High
Reactance/lag
M = Mag Lag
Voltage:
MLT = Quad
ML5 = Multi 5
T = Trivolt
48T = 480/120 tap
277 = 277V
230 = 230V Type:
C = Core & Coil Cu
A = Core & Coil
Aluminum
F = F Can
W = Weatherproof
E = Encased/Potted
I = Indoor Encased
Frame Size:
E = E & I
3 = 3x4
4 = 4-3/4
5 = 5-3/4
X = non C & C
Capacitor:
D = Dry Film
O = Oil Film
Pack Type:
-5 = Dist. Kit
-55 = Dist. Kit
& Lamp
-1 = C & C
-1B = C & C
w/welded
bracket
-60 = C & C
no capacitor
-61 = C & C w/
welded bracket,
no cap
144 See page 195 for warranty information. 145
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
86839 – GEM7048TLC3D-5
Metal Halide
1 – 70W MH M98 or M143 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M98
Voltage 480
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 8 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Dimensions
Wiring diagram HID H6 – see example on page 180
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B2.0
Weight 5.00 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
86675 – GEM100MLTLC3D-5
Metal Halide
1 – 100W MH M90 or M140 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M92, M90, M140
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 12 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-86675-86718 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 5.00 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Metal Halide
For 20 – 175W Metal Halide HID Lamps
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M98
70W Ceramic
Metal Halide
70W Quartz
Metal Halide
480
System Wattage (W) 89
Nominal Current 0.20 A
Ballast Factor 1
Ballast Efficiency Factor 0.79
Max Input Current 0.44 A
Starting Current 0.16 A
Open Circuit Voltage 253V
Drop Out Voltage 384V
Power Factor (>=) % 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 1
UL Bench Top Rise C
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M92 120 208 240 277 M90, M140
100W
Ceramic
Metal Halide
100W
Quartz
Metal Halide
120 208 240 277
System Wattage (W) 119 119 119 119 System Wattage (W) 119 119 119 119
Nominal Current 1.10 A 0.60 A 0.50 A 0.50 A Nominal Current 1.10 A 0.60 A 0.50 A 0.50 A
Ballast Factor 1111 Ballast Factor 1111
Ballast Efficiency Factor Ballast Efficiency Factor 0.84 0.84 0.84 0.84
Max Input Current 2.27 A 1.30 A 1.13 A 0.98 A Max Input Current 2.27 A 1.30 A 1.13 A 0.98 A
Starting Current 1.26 A 0.69 A 0.60 A 0.53 A Starting Current 1.26 A 0.69 A 0.60 A 0.53 A
Open Circuit Voltage 274V 274V 274V 274V Open Circuit Voltage 274V 274V 274V 274V
Drop Out Voltage 96V 166V 192V 222V Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=) % 90 90 90 90 Power factor (>=) % 90 90 90
Min. Starting Temp -22 / -30 -22 / -30 -22 / -30 -22 / -30 Min. starting temperature -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 5433 Fuse rating 5433
UL Bench Top Rise D D D D UL bench top rise D D D D
Metal Halide
For 20 – 175W Metal Halide HID Lamps
86824 – GEM50MLTLC3D-5
Metal Halide
1 – 50W MH M110 or M148 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M110 or M148
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 6 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-86824-86847 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A1.0
B2.0
Weight 3.40 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
cUL Listed UL Listed
Safety and performance
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
86847 – GEM70MLTLC3D-5
Metal Halide
1 – 70W MH M98 or M143 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M98 or M143
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 8 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-86824-86847 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 5.00 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M110, M148
50W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 61 61 61 61
Nominal Current 0.60 A 0.30 A 0.30 A 0.20 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.82 0.82 0.82 0.82
Max Input Current 1.16 A 0.67 A 0.58 A 0.50 A
Starting Current 0.61 A 0.34 A 0.30 A 0.26 A
Open Circuit Voltage 264V 264V 264V 264V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 3 3 2 2
UL Bench Top Rise C C C C
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M98, M143
70W Ceramic
Metal Halide
70W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 88 88 88 88
Nominal Current 0.90 A 0.50 A 0.40 A 0.40 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.80 0.80 0.80 0.80
Max Input Current 1.51 A 0.88 A 0.75 A 0.66 A
Starting Current 0.96 A 0.59 A 0.49 A 0.44 A
Open Circuit Voltage 257V 257V 257V 257V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 4 3 3 2
UL Bench Top Rise A A A A
146 See page 195 for warranty information. 147
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Metal Halide
For 20 – 175W Metal Halide HID Lamps
86711 – GEM15048TLC3D-5
Metal Halide
1 – 150W MH M102 or M142 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M142, M102, M107
Voltage 480
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 16 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(E)-87087-86711-86876 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.3
B3.9
Weight 7.00 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
87210 – GEM175ML5AC3-5
Metal Halide
1 – 175W MH M57 or H39 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M57, H39, M109
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 10 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 Volt) featuring a 480-Volt tap
Dimensions
Wiring diagram HID W-(K)-86808-87210-87211 – see example on page 183
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B4.0
Weight 3.40 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M102, M142
150W Ceramic
Metal Halide
150W Quartz
Metal Halide
480 M107 480
System Wattage (W) 185 System Wattage (W) 185
Nominal Current 0.40 A Nominal Current 0.40 A
Ballast Factor 1 Ballast Factor 1
Ballast Efficiency Factor 0.81 Ballast Efficiency Factor 0.83
Max Input Current 0.85 A Max Input Current 0.85 A
Starting Current 0.38 A Starting Current 0.38 A
Open Circuit Voltage 264V Open Circuit Voltage 264V
Drop Out Voltage 384V Drop Out Voltage 384V
Power Factor (>=)% 90 Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30 Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 2 Fuse Rating 2
UL Bench Top Rise E UL Bench Top Rise E
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M57, H39, M109 120 208 240 277 480
System Wattage (W) 202 202 202 202 202
Nominal Current 1.70 A 1.00 A 0.90 A 0.80 A 0.40 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.87 0.87 0.87 0.87 0.87
Max Input Current 1.70 A 1.00 A 0.90 A 0.80 A 0.40 A
Starting Current 0.60 A 0.37 A 0.32 A 0.28 A 0.21 A
Open Circuit Voltage 307V 307V 307V 307V 307V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 5 3 3 2 1.5
UL Bench Top Rise D C C C C
Metal Halide
For 20 – 175W Metal Halide HID Lamps
86667 – GEM10048TLC3D-5
Metal Halide
1 – 100W MH M90 or M140 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M90 or M140
Voltage 480
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 12 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(F)-87068-86667 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 5.00 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
86718 – GEM150MLTLC3D-5
Metal Halide
1 – 150W MH M102 or M142 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M142, M102
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 16 Mfd
Voltage (MIN) 300
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-86675-86718 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.3
B4.0
Weight 7.00 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M90, M140
100W Ceramic
Metal Halide
480
System Wattage (W) 120
Nominal Current 0.30 A
Ballast Factor 1
Ballast Efficiency Factor
Max Input Current 0.56 A
Starting Current 0.33 A
Open Circuit Voltage 271V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 2
UL Bench Top Rise C
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M142, M102
150W
Ceramic
Metal Halide
150W
Quartz
Metal Halide
120 208 240 277
System Wattage (W) 186 186 186 186
Nominal Current 1.60 A 1.00 A 0.80 A 0.70 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.81 0.81 0.81 0.81
Max Input Current 3.37 A 1.95 A 1.68 A 1.39 A
Starting Current 1.86 A 1.03 A 0.89 A 0.77 A
Open Circuit Voltage 257V 257V 257V 257V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 10 5 5 4
UL Bench Top Rise A B A A
148 See page 195 for warranty information. 149
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
87211 – GEM250ML5AC3-5
Metal Halide
1 – 250W MH M58 or H37 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M58, H37
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 15 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Metal Halide
For 250 – 1500W Metal Halide HID Lamps
Dimensions
Wiring diagram HID W-(K)-86808-87210-87211 – see example on page 183
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B4.3
Weight 9.00 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
86765 – GEM250MLTAC3-5
Metal Halide
1 – 250W MH M58 or H37 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M58, H37
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 15 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(C)-86765-86814 – see example on page 181
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B4.3
Weight 9.00 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 2.813 in x 3.939 in
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M58, H37
250W Quartz
Metal Halide
175W Quartz
Metal Halide)
250W Mercury
120 208 240 277 480
System Wattage (W) 280 280 280 280 280
Nominal Current 2.50 A 1.40 A 1.25 A 1.10 A 0.65 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.89 0.89 0.89 0.89 0.89
Max Input Current 2.60 A 1.60 A 1.30 A 1.20 A 0.70 A
Starting Current 1.50 A 1.00 A 0.80 A 0.70 A 0.50 A
Open Circuit Voltage 290V 290V 290V 290V 290V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 4 3 2
UL Bench Top Rise B B B C C
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M58, H37
250W Quartz
Metal Halide
175W Quartz
Metal Halide
250W Mercury
120 208 240 277
System Wattage (W) 294 294 294 294
Nominal Current 2.65 A 1.50 A 1.30 A 1.13 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.85 0.85 0.85 0.85
Max Input Current 2.60 A 1.58 A 1.30 A 1.12 A
Starting Current 1.88 A 1.15 A 0.95 A 0.86 A
Open Circuit Voltage 315V 315V 315V 315V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 4 3
UL Bench Top Rise C D C C
86741 – GEM175MLTAC3-5
Metal Halide
1 – 175W MH M57 or H39 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M57, M107, H39
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 10 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(C)-86655-86698-86741 – see example on page 181
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A1.0
B2.0
Weight 3.40 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Metal Halide
For 20 – 175W Metal Halide HID Lamps
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M57, H39
175W Quartz
Metal Halide
150W Quartz
Metal Halide
175W Mercury
120 208 240 277 M107 120 208 240 277
System Wattage (W) 210 210 210 210 System Wattage (W) 210 210 210 210
Nominal Current 1.80 A 1.00 A 0.90 A 0.80 A Nominal Current 1.80 A 1.00 A 0.90 A 0.80 A
Ballast Factor 1111 Ballast Factor 1111
Ballast Efficiency Factor 0.83 0.83 0.83 0.83 Ballast Efficiency Factor
Max Input Current 1.80 A 1.00 A 0.90 A 0.80 A Max Input Current 1.80 A 1.00 A 0.90 A 0.80 A
Starting Current 0.96 A 0.56 A 0.48 A 0.42 A Starting Current 0.96 A 0.56 A 0.48 A 0.42 A
Open Circuit Voltage 302V 302V 302V 302V Open Circuit Voltage 302V 302V 302V 302V
Drop Out Voltage 96V 166V 192V 222V Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=) % 90 90 90 90 Power factor (>=) % 90 90 90 90
Min. Starting Temp -22 / -30 -22 / -30 -22 / -30 -22 / -30 Min. starting temperature -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 5332 Fuse rating 5332
UL Bench Top Rise B B B C UL bench top rise B B B C
cUL Listed UL Listed
Safety and performance
150 See page 195 for warranty information. 151
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
72149 – GEM400MLTAA4-5
Metal Halide
1 – 400W MH M59 or H33 Quad (120/208/240/277V) A1 C&C
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M59, H33
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID H21 – see example on page 180
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 11.90 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Metal Halide
For 250 – 1500W Metal Halide HID Lamps
86803 – GEM40048TAC4-5
Metal Halide
1 – 400W MH M59 or H33 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M59, H33
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(J)-86650-86693-86803 – see example on page 182
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 12.50 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M59, H33
400W Quartz
Metal Halide
360W Quartz
Metal Halide
400W Mercury
120 208 240 277
System Wattage (W) 446 446 446 446
Nominal Current 3.80 A 2.20 A 1.90 A 1.70 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.93 0.93 0.93 0.93
Max Input Current 3.80 A 2.20 A 1.90 A 1.70 A
Starting Current 3.17 A 1.84 A 1.60 A 1.39 A
Open Circuit Voltage 289V 289V 289V 289V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 10 8 5 5
UL Bench Top Rise C C C C
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M59
400W Quartz
Metal Halide
360W Quartz
Metal Halide
480 H33
400W Mercury
480
System Wattage (W) 432 System Wattage (W) 458
Nominal Current 0.90 A Nominal Current 1.00 A
Ballast Factor 1 Ballast Factor 1
Ballast Efficiency Factor 0.93 Ballast Efficiency Factor 0.87
Max Input Current 0.90 A Max Input Current 1.00 A
Starting Current 0.60 A Starting Current 0.60 A
Open Circuit Voltage 297V Open Circuit Voltage 300V
Drop Out Voltage 384V Drop Out Voltage 384V
Power Factor (>=)% 90 Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30 Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 5 Fuse Rating 5
UL Bench Top Rise A UL Bench Top Rise E
cUL Listed UL Listed
Safety and performance
Metal Halide
For 250 – 1500W Metal Halide HID Lamps
87212 – GEM250ML5AC4-5
Metal Halide
1 – 250W MH M58 or H37 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M58, H37
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 15 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Dimensions
Wiring diagram HID W-(K)-87212-87213 – see example on page 183
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A1.8
B3.6
Weight 10.80 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
72300 – GEM400ML5AA4-5
Metal Halide
1 – 400W MH M59 or H33 5-Tap (120/208/240/277/480V) A1 C&C
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M59, H33
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 Volt) featuring a 480-Volt tap
Dimensions
Wiring diagram HID W-(K)-86808-87210-87211 – see example on page 183
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 12.50 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M58, H37 120 208 240 277 480
System Wattage (W) 293 293 293 293 293
Nominal Current 4.00 A 2.30 A 2.00 A 1.70 A 1.00 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.85 0.85 0.85 0.85 0.85
Max Input Current 2.50 A 1.40 A 1.30 A 1.10 A 0.65 A
Starting Current 2.50 A 1.40 A 1.20 A 1.00 A 0.60 A
Open Circuit Voltage 300V 300V 300V 300V 300V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 4 3 2
UL Bench Top Rise A A A A A
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M59, H33
400W Quartz
Metal Halide
360W Quartz
Metal Halide
400W Mercury
120 208 240 277 480
System Wattage (W) 446 446 446 446 446
Nominal Current 3.70 A 2.10 A 1.90 A 1.60 A 0.90 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.92 0.92 0.92 0.92 0.92
Max Input Current 3.70 A 2.10 A 1.90 A 1.60 A 0.90 A
Starting Current 2.19 A 1.31 A 1.11 A 1.00 A 0.60 A
Open Circuit Voltage 300V 300V 300V 300V 300V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 10 8 5 5 5
UL Bench Top Rise E E E E E
cUL Listed UL Listed
Safety and performance
152 See page 195 for warranty information. 153
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Metal Halide
For 250 – 1500W Metal Halide HID Lamps
86655 – GEM1000MLTAA5-5
Metal Halide
1 – 1000W MH M47 or H36 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M47, H36
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 480
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(C)-86655-86698-86741 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B5.0
Weight 21.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 6.00 in
86693 – GEM150048TAC5M5-5
Metal Halide
1 – 1500W MH M48 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M48
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 32 Mfd
Voltage (MIN) 525
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(J)-86650-86693-86803 – see example on page 182
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A4.0
B6.0
Weight 30.00 lbs
Exit Type Side
Nominal Length 5.2 in (133.35 mm)
Frame Size (H x L) 4.25 in x 6.00 in
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M47, H36
1000W Quartz
Metal Halide
1000W Mercury
120 208 240 277
System Wattage (W) 1,067 1,067 1,067 1,067
Nominal Current 9.00 A 5.00 A 4.50 A 3.90 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.94 0.94 0.94 0.94
Max Input Current 9.00 A 5.00 A 4.50 A 3.90 A
Starting Current 7.44 A 4.35 A 3.79 A 3.30 A
Open Circuit Voltage 421V 421V 421V 421V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 20 15 10 10
UL Bench Top Rise B B B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M48
1500W Quartz
Metal Halide
480
System Wattage (W) 1,581
Nominal Current 3.10 A
Ballast Factor 1
Ballast Efficiency Factor 0.95
Max Input Current 3.10 A
Starting Current 3.18 A
Open Circuit Voltage 449V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 10
UL Bench Top Rise G
Metal Halide
For 250 – 1500W Metal Halide HID Lamps
86650 – GEM100048TAC5-5
Metal Halide
1 – 1000W MH M47 or H36 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M47, H36
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 480
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
• Magnetic ballast construction ideal for a wide variety of lighting applications.
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity.
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(J)-86650-86693-86803 – see example on page 182
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B5.0
Weight 21.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 6.00 in
87213 – GEM1000ML5AA5-5
Metal Halide
1 – 1000W MH M47 or H36 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M47, H36
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 480
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 Volt) featuring a 480-Volt tap
Dimensions
Wiring diagram HID W-(K)-87212-87213 – see example on page 183
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B5.0
Weight 21.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 6.00 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M47, H36
1000W Quartz
Metal Halide
1000W Mercury
480
System Wattage (W) 1,052
Nominal Current 2.20 A
Ballast Factor 1
Ballast Efficiency Factor 0.95
Max Input Current 2.20 A
Starting Current 1.83 A
Open Circuit Voltage 430V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 10
UL Bench Top Rise E
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M47, H36
1000W Quartz
Metal Halide
1000W Mercury
120 208 240 277 480
System Wattage (W) 1,103 1,103 1,103 1,103 1,103
Nominal Current 9.30 A 5.40 A 4.70 A 4.10 A 2.40 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.91 0.91 0.91 0.91 0.91
Max Input Current 9.30 A 5.40 A 4.70 A 4.10 A 2.40 A
Starting Current 6.34 A 3.71 A 3.20 A 2.79 A 1.65 A
Open Circuit Voltage 445V 445V 445V 445V 445V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 20 15 10 10 10
UL Bench Top Rise E C C C D
154 See page 195 for warranty information. 155
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
86885 – GEP175MLTAC3-5
Pulse Start
1 – 175W PS M137 or M152 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M153, M137
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 10 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(A)-46934-86885-86935 – see example on page 181
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 7.50 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 2.813 in x 3.939 in
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
86876 – GEP17548TAC3-5
Pulse Start
1 – 175W PS M137 or M152 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M152, M137
Voltage 120/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 10 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(E)-87087-86711-86876 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 7.00 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M153
250W
Quartz
Metal
Halide
120 208 240 277 M137
175W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 204 204 204 204 System Wattage (W) 204 204 204 204
Nominal Current 1.70 A 1.00 A 0.90 A 0.80 A Nominal Current 1.70 A 1.00 A 0.90 A 0.80 A
Ballast Factor 1 1 1 1Ballast Factor 1 1 1 1
Ballast Efficiency Factor 1.23 1.23 1.23 1.23 Ballast Efficiency Factor 0.86 0.86 0.86 0.86
Max Input Current 1.70 A 1.00 A 0.90 A 0.80 A Max Input Current 1.70 A 1.00 A 0.90 A 0.80 A
Starting Current 0.76 A 0.36 A 0.38 A 0.33 A Starting Current 0.76 A 0.36 A 0.38 A 0.33 A
Open Circuit Voltage 281V 281V 281V 281V Open Circuit Voltage 281V 281V 281V 281V
Drop Out Voltage 96V 166V 192V 222V Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=) % 90 90 90 90 Power factor (>=) % 90 90 90 90
Min. Starting Temp -22 / -30 -22 / -30 -22 / -30 -22 / -30 Min. starting temperature -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 5332Fuse rating 5332
UL Bench Top Rise C D B BUL bench top rise C D B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M152, M137
175W Quartz
Metal Halide
120 480
System Wattage (W) 210 214
Nominal Current 1.85 A 0.50 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.83 0.82
Max Input Current 0.50 A
Starting Current 0.55 A 0.14 A
Open Circuit Voltage 315V 273V
Drop Out Voltage 96V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) 384V -22 / -30
Fuse Rating 2 2
UL Bench Top Rise C C
Metal Halide
For 250 – 1500W Metal Halide HID Lamps
86698 – GEM1500MLTAC5-5
Metal Halide
1 – 1500W MH M48 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M48
Voltage 240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 32 Mfd
Voltage (MIN) 525
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(C)-86655-86698-86741 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A4.0
B6.0
Weight 30.00 lbs
Exit Type Side
Nominal Length 5.2 in (133.35 mm)
Frame Size (H x L) 4.25 in x 6.00 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M48
1500W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 1,602 1,602 1,602 1,602
Nominal Current 13.70 A 7.70 A 6.80 A 6.00 A
Ballast Factor 1 1 11
Ballast Efficiency Factor 0.94 0.94 0.94 0.94
Max Input Current 13.70 A 7.70 A 6.80 A 6.00 A
Starting Current 12.95 A 7.46 A 6.52 A 5.75 A
Open Circuit Voltage 440V 440V 440V 440V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 40 25 20 20
UL Bench Top Rise E A AA
cUL Listed UL Listed
Safety and performance
156 See page 195 for warranty information. 157
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
86959 – GEP320MLTAC4-5
Pulse Start
1 – 320W PS M132 or 154 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M154, M132
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 21 Mfd
Voltage (MIN) 345
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(A)-86959-86984-87008 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Slots (MS) Mount Width (X or F) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 11.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
86952 – GEP32048TAC4M-5
Pulse Start
1 – 320W PS M132 or M154 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M154, M132
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 21 Mfd
Voltage (MIN) 345
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(D)-86952-86999 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Height (H)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 12.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M154, M132 120 208 240 277
System Wattage (W) 370 370 370 370
Nominal Current 3.10 A 1.80 A 1.60 A 1.40 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.86 0.86 0.86 0.86
Max Input Current 3.10 A 1.80 A 1.60 A 1.40 A
Starting Current 1.75 A 1.04 A 0.87 A 0.76 A
Open Circuit Voltage 269V 269V 269V 269V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 7 5 5
UL Bench Top Rise D B B A
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M154, M132 480
System Wattage (W) 369
Nominal Current 0.80 A
Ballast Factor 1
Ballast Efficiency Factor 0.87
Max Input Current 0.80 A
Starting Current 0.50 A
Open Circuit Voltage 268V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 3
UL Bench Top Rise C
86935 – GEP250MLTAC4-5
Pulse Start
1 – 250W PS M138 or M153 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M153, M138
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 15 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C 212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(A)-46934-86885-86935 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 9.00 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
86926 – GEP25048TAC4-5
Pulse Start
1 – 250W PS M138 or M153 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M153, M138
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 15 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(E)-86926 – see example on page 182
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 9.00 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 4.25 in x 4.75 in
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M153, M138
250W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 284 284 284 284
Nominal Current 2.50 A 1.40 A 1.30 A 1.10 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.88 0.88 0.88 0.88
Max Input Current 2.50 A 1.40 A 1.30 A 1.10 A
Starting Current 1.78 A 1.02 A 0.89 A 0.77 A
Open Circuit Voltage 255V 255V 255V 255V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)%90909090
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 5 3
UL Bench Top Rise A A A B
Specifications by lamp and line voltage
Lamp Specifications by line voltage Lamp Specifications by line voltage
M153
250W Quartz
Metal Halide
480 M138 480
System Wattage (W) 290 System Wattage (W) 290
Nominal Current 0.60 A Nominal Current 0.60 A
Ballast Factor 1 Ballast Factor 1
Ballast Efficiency Factor 0.86 Ballast Efficiency Factor
Max Input Current 0.60 A Max Input Current 0.60 A
Starting Current 0.48 A Starting Current 0.48 A
Open Circuit Voltage 254V Open Circuit Voltage 254V
Drop Out Voltage 384V Drop Out Voltage 384V
Power Factor (>=)% 90 Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30 Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 2 Fuse Rating 2
UL Bench Top Rise C UL Bench Top Rise C
158 See page 195 for warranty information. 159
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
cUL Listed UL Listed
Safety and performance
86999 – GEP40048TAC4-5
Pulse Start
1 – 400W PS M135 or M155 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M155, M135
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(D)-86952-86999 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 12.00 lbs
Exit Type Side
Nominal Length 4.6 in (119.12 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M155, M135
400W Quartz
Metal Halide
480
System Wattage (W) 465
Nominal Current 1.00 A
Ballast Factor 1
Ballast Efficiency Factor 0.86
Max Input Current 1.00 A
Starting Current 0.80 A
Open Circuit Voltage 275V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 3
UL Bench Top Rise D
87008 – GEP400MLTAC4-5
Pulse Start
1 – 400W PS M135 or M155 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M155, M135
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(A)-86959-86984-87008 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.8
Weight 12.00 lbs
Exit Type Side
Nominal Length 4.6 in (119.12 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M155, M135
400W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 443 443 443 443
Nominal Current 3.90 A 2.20 A 2.00 A 1.70 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.90 0.90 0.90 0.90
Max Input Current 3.90 A 2.20 A 2.00 A 1.70 A
Starting Current 3.16 A 1.85 A 1.60 A 1.39 A
Open Circuit Voltage 259V 259V 259V 259V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 10 7 5 5
UL Bench Top Rise B C D C
cUL Listed UL Listed
Safety and performance
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
86968 – GEP320TRIAC4-5
Pulse Start
1 – 320W PS M132 or M154 TRI-Voltage 120 277 347
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M154, M132
Voltage 120/277/347
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil Filled
Capacitance 21 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(L)-86968 – see example on page 183
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.3 in (134.62 mm)
Width (W) 1.3 in (33.02 mm)
Mounting dimensions
Mount Length (M) 4.60 in (116.84 mm)
Mount Slots (MS) 0.3 in (7.62 mm)
A
B
Weight 12.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in (4.75 mm)
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
86984 – GEP350MLTAC4-5
Pulse Start
1 – 350W PS M131 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M131
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 21.5 Mfd
Voltage (MIN) 345
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH350-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(A)-86959-86984-87008 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 12.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M154, M132 120 277 347
System Wattage (W) 400 400 400
Nominal Current 3.00 A 1.30 A 1.10 A
Ballast Factor 1 1 1
Ballast Efficiency Factor 0.88 0.88 0.88
Max Input Current 3.00 A 1.30 A 1.10 A
Starting Current 1.89 A 0.83 A 0.66 A
Open Circuit Voltage 281V 281V 281V
Drop Out Voltage 96V 222V 150V
Power Factor (>=)% 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 4 3
UL Bench Top Rise CCC
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M131
350W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 396 396 396 396
Nominal Current 3.40 A 1.90 A 1.70 A 1.40 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.88 0.88 0.88 0.88
Max Input Current 3.40 A 1.90 A 1.70 A 1.40 A
Starting Current 2.31 A 1.31 A 1.12 A 0.99 A
Open Circuit Voltage 262V 262V 262V 262V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 10 7 5 5
UL Bench Top Rise D D D D
160 See page 195 for warranty information. 161
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
72281 – GEP1000MLTAC5-5
Pulse Start
1 – 1000W PS M141 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M141
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 480
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS100-4B
Sound Rating D (37-42 decibels)
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
Dimensions
Wiring diagram HID W-(A)-46934-86935 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Width (W) 7.75 in (196.85 mm)
Length (L) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F) 6.1 in (154.94 mm)
Mount Slots (MS) 0.25 in (9.52 mm)
A2.83
B5.08
Weight 21.00 lbs
Exit Type Side
Nominal Length 4.25 in (107.95 mm)
Frame Size (H x L) 4.25 in x 6.00 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M141 120 208 240 277
System Wattage (W) 1071 1071 1071 1071
Nominal Current 8.80 A 5.10 A 4.30 A 4.00 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.93 0.93 0.93 0.93
Max Input Current 8.80 A 5.10 A 4.30 A 4.00 A
Starting Current 5.70 A 5.70 A 5.70 A 5.70 A
Open Circuit Voltage 420V 420V 420V 420V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 20 15 10 10
UL Bench Top Rise D B B B
cUL Listed UL Listed
Safety and performance
72282 – GEP1000ML5AC5-5
Pulse Start
1 – 1000W PS M141 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M141
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 480
Capacitor Temperature Rating -30°C (-20°F)
GE Igniter HPS1000-4B
Sound Rating D (37-42 decibels)
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
Dimensions
Wiring diagram HID W-(A)-87214-87215-87218 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Width (W) 7.75 in (196.85 mm)
Length (L) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F) 6.1 in (154.94 mm)
Mount Slots (MS) 0.25 in (9.52 mm)
A2.83
B5.20
Weight 21.60 lbs
Exit Type Side
Nominal Length 4.25 in (107.95 mm)
Frame Size (H x L) 4.25 in x 6.00 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M141 120 208 240 277 480
System Wattage (W) 1112 1112 1112 1112 1112
Nominal Current 9.30 A 5.40 A 4.70 A 4.20 A 2.50 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.90 0.90 0.90 0.90 0.90
Max Input Current 9.30 A 5.40 A 4.70 A 4.20 A 2.50 A
Starting Current 5.70 A 5.70 A 5.70 A 5.70 A 5.70 A
Open Circuit Voltage 450V 450V 450V 450V 450V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 20 15 10 10 10
UL Bench Top Rise D C C D E
cUL Listed UL Listed
Safety and performance
Pulse Start
For 175 – 1000W Pulse Start Metal Halide HID Lamps
cUL Listed UL Listed
Safety and performance
46936 – GEP75048TAC5-5
Pulse Start
1 – 750W PS M149 480
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M149
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 480
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH750-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Dimensions
Wiring diagram HID W-(D)-87048-87198-49636 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B5.0
Weight 21.00 lbs
Exit Type Side
Nominal Length 4.2 in (107.95 mm)
Frame Size (H x L) 4.25 in x 6.00 in
46934 – GEP750MLTAC5-5
Pulse Start
1 – 750W PS M149 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M149
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 28 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter MH750-1A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Dimensions
Wiring diagram HID W-(A)-46934-86885-86935 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B5.0
Weight 22.00 lbs
Exit Type Side
Nominal Length 4.2 in (107.95 mm)
Frame Size (H x L) 4.25 in x 6.00 in
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M149
750W Quartz
Metal Halide
480
System Wattage (W) 809
Nominal Current 1.80 A
Ballast Factor 1
Ballast Efficiency Factor 0.93
Max Input Current 1.80 A
Starting Current 1.04 A
Open Circuit Voltage 351V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 6
UL Bench Top Rise E
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M149
750W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 802 802 802 802
Nominal Current 4.10 A 2.40 A 2.10 A 1.80 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.94 0.94 0.94 0.94
Max Input Current 4.10 A 2.40 A 2.10 A 1.80 A
Starting Current 3.98 A 2.32 A 2.03 A 1.76 A
Open Circuit Voltage 351V 351V 351V 351V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 15 8 8 8
UL Bench Top Rise B B B B
162 See page 195 for warranty information. 163
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
High Pressure Sodium
For 50 – 150W High Pressure Sodium HID Lamps
87152 – GES50MLTLC3D-5
High Pressure Sodium
1 – 50W HPS S68 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S68
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 5 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS150-3A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-87094-87152 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A1.0
B3.0
Weight 3.40 lbs
Exit Type Side
Nominal Length 2.7 in (69.85 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
cUL Listed UL Listed
Safety and performance
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
cUL Listed UL Listed
Safety and performance
86587 – GES70MLTLC3D-5
High Pressure Sodium
1 – 70W HPS S62 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S62
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 7 Mfd
Voltage (MIN) 300
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS150-3A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-86587-87074 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 5.50 lbs
Exit Type Side
Nominal Length 2.7 in (69.85 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
86456 – GES7048TLC3D-5
High Pressure Sodium
1 – 70W HPS S62 480V
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S62
Voltage 480
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 7 Mfd
Voltage (MIN) 300
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS150-3A 86635
Sound Rating
Additional Info
Dimensions
Wiring diagram HID H6 – see example on page 180
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 5.80 lbs
Exit Type Side
Nominal Length 2.7 in (69.85 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
High Pressure Sodium
For 50 – 150W High Pressure Sodium HID Lamps
87074 – GES100MLTLC3D-5
High Pressure Sodium
1 – 100W HPS S54 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S54
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 10 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS150-3A 86635
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-86587-87074 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 6.20 lbs
Exit Type Side
Nominal Length 2.7 in (69.85 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S68
50W High
Pressure Sodium
120 208 240 277
System Wattage (W) 69 69 69 69
Nominal Current 0.70 A 0.40 A 0.30 A 0.30 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.72 0.72 0.72 0.72
Max Input Current 0.93 A 0.54 A 0.46 A 0.40 A
Starting Current 0.74 A 0.43 A 0.37 A 0.32 A
Open Circuit Voltage 122V 122V 122V 122V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 5 3 3 2
UL Bench Top Rise B B B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S62
70W High
Pressure Sodium
120 208 240 277
System Wattage (W) 91 91 91 91
Nominal Current 0.80 A 0.50 A 0.40 A 0.40 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.77 0.77 0.77 0.77
Max Input Current 1.34 A 0.78 A 0.67 A 0.59 A
Starting Current 0.78 A 0.46 A 0.39 A 0.35 A
Open Circuit Voltage 118V 118V 118V 118V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 5 3 3 2
UL Bench Top Rise B B B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S62
70W High
Pressure Sodium
480
System Wattage (W) 97
Nominal Current 0.20 A
Ballast Factor 1
Ballast Efficiency Factor 0.72
Max Input Current 0.34 A
Starting Current 0.34 A
Open Circuit Voltage 123V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 2
UL Bench Top Rise A
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S54
100W High
Pressure Sodium
150W High
Pressure Sodium
120 208 240 277
System Wattage (W) 123 123 123 123
Nominal Current 2.20 A 1.30 A 1.10 A 0.90 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 1.22 1.22 1.22 1.22
Max Input Current 2.18 A 1.27 A 1.13 A 0.94 A
Starting Current 0.74 A 0.43 A 0.36 A 0.31 A
Open Circuit Voltage 119V 119V 119V 119V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 5 3
UL Bench Top Rise B B B B
164 See page 195 for warranty information. 165
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
High Pressure Sodium
For 50 – 150W High Pressure Sodium HID Lamps
High Pressure Sodium
For 50 – 150W High Pressure Sodium HID Lamps
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
UL Listed
Safety and performance
87068 – GES10048TLC3D-5
High Pressure Sodium
1 – 100W HPS S54 480V
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S54
Voltage 480
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 10 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS150-3A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(F)-87068-86667 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 6.20 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
87094 – GES150MLTLC3D-5
High Pressure Sodium
1 – 150W HPS S55 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S55
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 14 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS150-3A
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(H)-87094-87152 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B4.0
Weight 7.60 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
87087 – GES15048TLC3D-5
High Pressure Sodium
1 – 150W HPS S55 480V
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S55
Voltage 480
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry film
Capacitance 10 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS150-3A 86635
Sound Rating
Additional Info
Dimensions
Wiring diagram HID W-(E)-87087-86711-86876 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.0
B4.0
Weight 8.70 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S54
100W High
Pressure Sodium
150W High
Pressure Sodium
480
System Wattage (W) 135
Nominal Current 0.30 A
Ballast Factor 1
Ballast Efficiency Factor 1.11
Max Input Current 0.54 A
Starting Current 0.24 A
Open Circuit Voltage 119V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 2
UL Bench Top Rise C
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S55
150W High
Pressure Sodium
250W Quartz
Metal Halide
120 208 240 277
System Wattage (W) 175 175 175 175
Nominal Current 1.60 A 0.90 A 0.80 A 0.70 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 1.43 1.43 1.43 1.43
Max Input Current 2.72 A 1.53 A 1.34 A 1.16 A
Starting Current 1.64 A 0.88 A 0.76 A 0.65 A
Open Circuit Voltage 115V 115V 115V 115V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 10 5 5 5
UL Bench Top Rise B B B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S55
150W High
Pressure Sodium
250W Quartz
Metal Halide
480
System Wattage (W) 188
Nominal Current 0.40 A
Ballast Factor 1
Ballast Efficiency Factor 1.33
Max Input Current 0.73 A
Starting Current 0.31 A
Open Circuit Voltage 114V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 3
UL Bench Top Rise F
166 See page 195 for warranty information. 167
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
High Pressure Sodium
For 250 – 1000W High Pressure Sodium HID Lamps
87214 – GES250ML5AC4-5
High Pressure Sodium
1 – 250W HPS S50 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S50
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 35 Mfd
Voltage (MIN) 240
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS400-3A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
Dimensions
Wiring diagram HID W(B)-87214-87215-87218 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 12.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
87121 – GES250MLTAC4-5
High Pressure Sodium
1 – 250W HPS S50 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S50
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 35 Mfd
Voltage (MIN) 240
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS400-3A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
Dimensions
Wiring diagram HID W-(A)-87056-87121-87164 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 11.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
87215 – GES400ML5AC4-5
High Pressure Sodium
1 – 400W HPS S51 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S51
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 55 Mfd
Voltage (MIN) 240
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS400-3A 86641
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
Dimensions
Wiring diagram HID W-(B)-87214-87215-87218 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 15.00 lbs
Exit Type Side
Nominal Length 4.2 in (107.95 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
High Pressure Sodium
For 250 – 1000W High Pressure Sodium HID Lamps
87164 – GES400MLTAC4-5
High Pressure Sodium
1 – 400W HPS S51 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S51
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 55 Mfd
Voltage (MIN) 240
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS400-3A 86641
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
Dimensions
Wiring diagram HID W-(A)-87056-87121-87164 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B4.0
Weight 13.60 lbs
Exit Type Side
Nominal Length 4.2 in (107.95 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S50
250W High
Pressure Sodium
120 208 240 277 480
System Wattage (W) 292 292 292 292 292
Nominal Current 2.50 A 1.50 A 1.30 A 1.10 A 0.60 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.86 0.86 0.86 0.86 0.86
Max Input Current 2.50 A 1.50 A 1.30 A 1.10 A 0.60 A
Starting Current 1.59 A 0.93 A 0.81 A 0.70 A 0.40 A
Open Circuit Voltage 186V 186V 186V 186V 186V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 4 4 4
UL Bench Top Rise C C B B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S50
250W High
Pressure Sodium
120 208 240 277
System Wattage (W) 303 303 303 303
Nominal Current 2.60 A 1.50 A 1.30 A 1.10 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.83 0.83 0.83 0.83
Max Input Current 2.60 A 1.50 A 1.30 A 1.10 A
Starting Current 1.50 A 0.86 A 0.75 A 0.63 A
Open Circuit Voltage 186V 186V 186V 186V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 4 4
UL Bench Top Rise A A A A
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S51
400W High
Pressure Sodium
120 208 240 277 480
System Wattage (W) 472 472 472 472 472
Nominal Current 4.00 A 2.20 A 2.00 A 1.70 A 1.00 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.85 0.85 0.85 0.85 0.85
Max Input Current 4.00 A 2.20 A 2.00 A 1.70 A 1.00 A
Starting Current 2.87 A 1.66 A 1.44 A 1.25 A 0.72 A
Open Circuit Voltage 191V 191V 191V 191V 191V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 15 8 8 5 5
UL Bench Top Rise C C C C C
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S51
400W High
Pressure Sodium
120 208 240 277
System Wattage (W) 443 443 443 443
Nominal Current 3.80 A 2.20 A 1.90 A 1.60 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.90 0.90 0.90 0.90
Max Input Current 3.80 A 2.20 A 1.90 A 1.60 A
Starting Current 1.78 A 1.03 A 0.90 A 0.77 A
Open Circuit Voltage 186V 186V 186V 186V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 15 8 8 5
UL Bench Top Rise D D D D
168 See page 195 for warranty information. 169
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
High Pressure Sodium
For 250 – 1000W High Pressure Sodium HID Lamps
High Pressure Sodium
For 250 – 1000W High Pressure Sodium HID Lamps
87198 – GES40048TAC4-5
High Pressure Sodium
1 – 400W HPS S51 480V in smaller frame
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S51
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 55 Mfd
Voltage (MIN) 240
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS400-3A
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
Dimensions
Wiring diagram HID W-(D)-87048-87198-46936 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.25 in (133.35 mm)
Width (W) 1.25 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.3
B4.1
Weight 15.00 lbs
Exit Type Side
Nominal Length 4.2 in (107.95 mm)
Frame Size (H x L) 4.25 in x 4.75 in
87048 – GES100048TAC5-5
High Pressure Sodium
1 – 1000W HPS S52 480V
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S52
Voltage 480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 26 Mfd
Voltage (MIN) 525
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS24
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
Dimensions
Wiring diagram HID W-(D)-87048-87198-46936 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A3.8
B6.0
Weight 28.00 lbs
Exit Type Side
Nominal Length 4.7 in (120.65 mm)
Frame Size (H x L) 4.25 in x 6.00 in
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
cUL Listed UL Listed
Safety and performance
87218 – GES1000ML5AC5-5
High Pressure Sodium
1 – 1000W HPS S52 5-Tap (120/208/240/277/480V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S52
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 26 Mfd
Voltage (MIN) 525
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS1000-4B
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
Dimensions
Wiring diagram HID W-(B)-87214-87215-87218 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A4.0
B6.0
Weight 28.00 lbs
Exit Type Side
Nominal Length 4.7 in (120.65 mm)
Frame Size (H x L) 4.25 in x 6.00 in
Lead lengths
Orange
Violet and Black
Violet/White
Black/Yellow
87056 – GES1000MLTAC5-5
High Pressure Sodium
1 – 1000W HPS S52 Quad (120/208/240/277V)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S52
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 26 Mfd
Voltage (MIN) 525
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS1000-4B
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• Quad ballast (120, 208, 240, 277)
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
Dimensions
Wiring diagram HID W-(A)-87056-87121-87164 – see example on page 181
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 7.75 in (196.85 mm)
Width (W) 2.75 in (69.85 mm)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A4.0
B6.0
Weight 28.00 lbs
Exit Type Side
Nominal Length 4.7 in (120.65 mm)
Frame Size (H x L) 4.25 in x 6.00 in
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S51
400W High
Pressure Sodium
480
System Wattage (W) 475
Nominal Current 1.00 A
Ballast Factor 1
Ballast Efficiency Factor 0.84
Max Input Current 1.00 A
Starting Current 0.60 A
Open Circuit Voltage 195V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 5
UL Bench Top Rise D
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S52
1000W High
Pressure Sodium
480
System Wattage (W) 1,129
Nominal Current 2.13 A
Ballast Factor 1
Ballast Efficiency Factor 0.89
Max Input Current 2.13 A
Starting Current 1.80 A
Open Circuit Voltage 433V
Drop Out Voltage 384V
Power Factor (>=)% 90
Min. Starting Temp (°F/°C) -22 / -30
Fuse Rating 8
UL Bench Top Rise D
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S52
1000W High
Pressure Sodium
120 208 240 277 480
System Wattage (W) 1,102 1,102 1,102 1,102 1,102
Nominal Current 9.50 A 5.50 A 4.70 A 4.10 A 2.40 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.91 0.91 0.91 0.91 0.91
Max Input Current 9.50 A 5.50 A 4.70 A 4.10 A 2.40 A
Starting Current 5.75 A 3.40 A 2.90 A 2.60 A 1.80 A
Open Circuit Voltage 435V 435V 435V 435V 435V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 20 15 10 10 8
UL Bench Top Rise D D D D D
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S52
1000W High
Pressure Sodium
120 208 240 277
System Wattage (W) 1,100 1,100 1,100 1,100
Nominal Current 9.50 A 5.50 A 4.80 A 4.20 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 0.91 0.91 0.91 0.91
Max Input Current 9.50 A 5.50 A 4.80 A 4.20 A
Starting Current 5.00 A 3.00 A 2.60 A 2.20 A
Open Circuit Voltage 430V 430V 430V 430V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)%
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 20 15 10 10
UL Bench Top Rise A A A A
170 See page 195 for warranty information. 171
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
High Intensity Discharge Lamp Ballast Kits
71701 – GEM175ML5AC3-55
High Intensity Discharge Lamp Ballast Kits
1 – 175W MH M57 or H39 5-Tap (120/208/240/277/480V) Lamp & Ballast Kit (-55)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M57, H38, M109
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 10 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
Dimensions
Wiring diagram HID W-(K)-86808-87210-87211 – see example on page 183
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.3 in (133.35 mm)
Width (W) 1.3 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (6.35 mm)
A3.0
B4.0
Weight 8.00 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Lead Lengths
Orange and Red
Violet and Black
Black/Yellow
Violet/White
Yellow
High Intensity Discharge Lamp Ballast Kits
71702 – GEM250ML5AC3-55
High Intensity Discharge Lamp Ballast Kits
1 – 250W MH M58 or H37 5-Tap (120/208/240/277/480V) Lamp & Ballast Kit (-55)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M58, H37
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 15 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
cUL Listed UL Listed
Safety and performance
Dimensions
Wiring diagram HID W-(H)-86587-87074 – see example on page 182
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.3 in (133.35 mm)
Width (W) 1.3 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (6.35 mm)
A3.0
B4.3
Weight 9.00 lbs
Exit Type Side
Nominal Length 3.2 in (82.55 mm)
Frame Size (H x L) 2.813 in x 3.939 in
Lead Lengths
Orange and Red
Violet and Black
Black/Yellow
Violet/White
Yellow
cUL Listed UL Listed
Safety and performance
71703 – GEM400ML5AC4-55
High Intensity Discharge Lamp Ballast Kits
1 – 400W MH M59 or H33 5-Tap (120/208/240/277/480V) Lamp & Ballast Kit (-55)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M59, H33
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
Dimensions
Wiring diagram HID W-(K)-86808-87210-87211 – see example on page 183
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 5.3 in (133.35 mm)
Width (W) 1.3 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (6.35 mm)
A2.0
B4.0
Weight 12.50 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Lead Lengths
Orange and Red
Violet and Black
Black/Yellow
Violet/White
Yellow
cUL Listed UL Listed
Safety and performance
71704 – GEM1000ML5AC4-55
High Intensity Discharge Lamp Ballast Kits
1 – 1000W MH M47 or H36 5-Tap (120/208/240/277/480V) Lamp & Ballast Kit (-55)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes M47, H36
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil filled
Capacitance 24 Mfd
Voltage (MIN) 400
Capacitor Temperature Rating 100°C (212°F)
GE Igniter
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 2
Dimensions
Wiring diagram HID W-(K)-86808-87210-87211 – see example on page 183
Case dimensions – Ref Drawing PC1 – see page 185
Length (L) 7.8 in (196.85 mm)
Width (W) 2.8 in (69.85 mm)
Height (H)
Mounting dimensions
Mount Length (M) 6.1 in (154.94 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (6.35 mm)
A3.0
B5.0
Weight 21.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 6.00 in
Lead Lengths
Orange and Red
Violet and Black
Black/Yellow
Violet/White
Yellow
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M57, H39, M109 120 208 240 277 480
System Wattage (W) 202 202 202 202 202
Nominal Current 1.70 A 1.00 A 0.90 A 0.80 A 0.40 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.87 0.87 0.87 0.87 0.87
Max Input Current 1.70 A 1.00 A 0.90 A 0.80 A 0.40 A
Starting Current 0.60 A 0.37 A 0.32 A 0.28 A 0.21 A
Open Circuit Voltage 307V 307V 307V 307V 307V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 5 3 3 2 1.5
UL Bench Top Rise D C C C C
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M58, H37
250W Quartz
Metal Halide
175W Quartz
Metal Halide
250W Mercury
120 208 240 277 480
System Wattage (W) 280 280 280 280 280
Nominal Current 2.50 A 1.40 A 1.25 A 1.10 A 0.65 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.89 0.89 0.89 0.89 0.89
Max Input Current 2.60 A 1.60 A 1.30 A 1.20 A 0.70 A
Starting Current 1.50 A 1.00 A 0.80 A 0.70 A 0.50 A
Open Circuit Voltage 290V 290V 290V 290V 290V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 4 3 2
UL Bench Top Rise B B B C C
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M59, H33
360W Quartz
Metal Halide
400W Quartz
Metal Halide
400W Mercury
120 208 240 277 480
System Wattage (W) 436 436 436 436 436
Nominal Current 3.70 A 2.10 A 1.90 A 1.60 A 0.90 A
Ballast Factor
Ballast Efficiency Factor 0.92 0.92 0.92 0.92 0.92
Max Input Current 3.70 A 2.10 A 1.90 A 1.60 A 0.90 A
Starting Current 2.19 A 1.31 A 1.11 A 1.00 A 0.60 A
Open Circuit Voltage 300V 300V 300V 300V 300V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 10 8 5 5 5
UL Bench Top Rise E E E E E
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M47, H33
1000W Quartz
Metal Halide
1000W Mercury
120 208 240 277 480
System Wattage (W) 1103 1103 1103 1103 1103
Nominal Current 9.30 A 5.40 A 4.70 A 4.10 A 2.40 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.91 0.91 0.91 0.91 0.91
Max Input Current 9.30 A 5.40 A 4.70 A 4.10 A 2.40 A
Starting Current 6.34 A 3.71 A 3.20 A 2.79 A 1.65 A
Open Circuit Voltage 445V 445V 445V 445V 445V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 20 15 10 10 10
UL Bench Top Rise E C C C D
172 See page 195 for warranty information. 173
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
High Intensity Discharge Lamp Ballast KitsHigh Intensity Discharge Lamp Ballast Kits
71705 – GES100MLTLC3D-55
High Intensity Discharge Lamp Ballast Kits
1 – 100W HPS S54 Quad (120/208/240/277V) Lamp & Ballast Kit (-55)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S54
Voltage 120/208/240/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 180C
Type of Capacitor Dry Film
Capacitance 10 Mfd
Voltage (MIN) 280
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS100-3A 86884
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 6
Dimensions
Wiring diagram HID W-(K)-87212-87213 – see example on page 183
Case dimensions – Ref Drawing PC3 – see page 185
Length (L) 5.3 in (133.35 mm)
Width (W) 1.3 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (6.35 mm)
A2.0
B4.0
Weight 6.20 lbs
Exit Type Side
Nominal Length 2.7 in (68.58 mm)
Frame Size (H x L) 2.813 in x 3.939 in
cUL Listed UL Listed
Safety and performance
71706 – GES250ML5AC4-55
High Intensity Discharge Lamp Ballast Kits
1 – 250W HPS S50 5-Tap (120/208/240/277/480V) Lamp & Ballast Kit (-55)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S50
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil Filled
Capacitance 35 Mfd
Voltage (MIN) 240
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS400-3A 86641
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
Dimensions
Wiring diagram HID W-(B)-87214-87215-87218 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.3 in (133.35 mm)
Width (W) 1.3 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (6.35 mm)
A2.0
B4.0
Weight 12.00 lbs
Exit Type Side
Nominal Length 3.7 in (95.25 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Lead Lengths
Orange and Red
Violet and Black
Black/Yellow
Violet/White
Yellow
cUL Listed UL Listed
Safety and performance
71707 – GES400ML5AC4-55
High Intensity Discharge Lamp Ballast Kits
1 – 400W HPS S51 5-Tap (120/208/240/277/480V) Lamp & Ballast Kit (-55)
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S51
Voltage 120/208/240/277/480
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 180C
Type of Capacitor Oil Filled
Capacitance 55 Mfd
Voltage (MIN) 240
Capacitor Temperature Rating 100°C (212°F)
GE Igniter HPS1000-4B
Sound Rating
Additional Info
Electrical characteristics
Supply Current Frequency 60 Hz
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
• Distributor replacement kit contains the appropriate core and coil with color coded leads, a properly
rated capacitor and ignitor (if required) and all other components required for ballast replacement
• 5-tap ballast (120, 208, 240, 277, or 480 volt) featuring a 480-volt tap
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Distributor Kit 1 3
Dimensions
Wiring diagram HID W-(B)-87214-87215-87218 – see example on page 181
Case dimensions – Ref Drawing PC2 – see page 185
Length (L) 5.3 in (133.35 mm)
Width (W) 1.3 in (31.75 mm)
Mounting dimensions
Mount Length (M) 4.6 in (116.84 mm)
Mount Width (X or F)
Mount Slots (MS) 0.3 in (6.35 mm)
A2.0
B4.0
Weight 15.00 lbs
Exit Type Side
Nominal Length 4.2 in (107.95 mm)
Frame Size (H x L) 4.25 in x 4.75 in
Lead Lengths
Orange and Red
Violet and Black
Black/Yellow
Violet/White
Yellow
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S54
100W High
Pressure Sodium
150W High
Pressure Sodium
120 208 240 277
System Wattage (W) 123 123 123 123
Nominal Current 2.20 A 1.30 A 1.10 A 0.90 A
Ballast Factor 1 1 1 1
Ballast Efficiency Factor 1.22 1.22 1.22 1.22
Max Input Current 2.18 A 1.27 A 1.13 A 0.94 A
Starting Current 0.74 A 0.43 A 0.36 A 0.31 A
Open Circuit Voltage 119V 119V 119V 119V
Drop Out Voltage 96V 166V 192V 222V
Power Factor (>=)% 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 5 3
UL Bench Top Rise B B B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S50
250W High
Pressure Sodium
120 208 240 277 480
System Wattage (W) 292 292 292 292 292
Nominal Current 2.50 A 1.50 A 1.30 A 1.10 A 0.60 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.86 0.86 0.86 0.86 0.86
Max Input Current 2.50 A 1.50 A 1.30 A 1.10 A 0.60 A
Starting Current 1.59 A 0.93 A 0.81 A 0.70 A 0.40 A
Open Circuit Voltage 186V 186V 186V 186V 186V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 8 5 4 4 4
UL Bench Top Rise C C B B B
Specifications by lamp and line voltage
Lamp Specifications by line voltage
S51
400W High
Pressure Sodium
120 208 240 277 480
System Wattage (W) 472 472 472 472 472
Nominal Current 4.00 A 2.20 A 2.00 A 1.70 A 1.00 A
Ballast Factor 1 1 1 1 1
Ballast Efficiency Factor 0.85 0.85 0.85 0.85 0.85
Max Input Current 4.00 A 2.20 A 2.00 A 1.70 A 1.00 A
Starting Current 2.87 A 1.66 A 1.44 A 1.25 A 0.72 A
Open Circuit Voltage 191V 191V 191V 191V 191V
Drop Out Voltage 96V 166V 192V 222V 384V
Power Factor (>=)% 90 90 90 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30 -22 / -30 -22 / -30 -22 / -30
Fuse Rating 15 8 8 5 5
UL Bench Top Rise C C C C C
174 See page 195 for warranty information. 175
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
86576 – 11210277CTC000C
Enclosed and Potted Metal Halide
1 – 70W M85 120/277 Enclosed and Potted
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes M98, M143
Voltage
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating
Additional Info Thermally Protected
Electrical characteristics
Supply Current Frequency 60 Hz
• For applications requiring quieter or cooler operation than provided by standard coil and
coil ballasts
• Excellent sound-deadening and heat transfer qualities
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 4
Dimensions
Wiring diagram HID H34 – see example on page 180
Case dimensions – Ref Drawing FCAN1 – see page 184
Length (L) 11.8 in (298.45 mm)
Width (W) 3.2 in (80.96 mm)
Height (H) 2.6 in (66.67 mm)
Mounting dimensions
Mount Length (M) 11.1 in (282.97 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.2 in (5.95 mm)
Weight 11.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp 20 ft
Remote Mounting Wire Gauge 18 AWG
Lead Lengths
Black and White
Red
Black/Yellow
Enclosed and Potted Metal HalideEnclosed and Potted Metal Halide
86578 – 11210506CTC000C
Enclosed and Potted Metal Halide
1 – 70W M98 120/277 Enclosed and Potted
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes M98
Voltage 120/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating
Sound Rating B (25-30 decibels)
Additional Info Thermally Protected
Electrical characteristics
Supply Current Frequency 60 Hz
• For applications requiring quieter or cooler operation than provided by standard coil and
coil ballasts
• Excellent sound-deadening and heat transfer qualities
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 4
Dimensions
Wiring diagram HID H34 – see example on page 180
Case dimensions – Ref Drawing FCAN1 – see page 184
Length (L) 11.8 in (298.45 mm)
Width (W) 3.2 in (80.96 mm)
Height (H) 2.6 in (66.67 mm)
Mounting dimensions
Mount Length (M) 11.1 in (282.97 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.2 in (5.95 mm)
Weight 11.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp 20 ft
Remote Mounting Wire Gauge 18 AWG
Lead Lengths
Black and White
Red
Black/Yellow
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M98
70W Ceramic
Metal Halide
70W Quartz
Metal Halide
120 277
System Wattage (W) 90 90
Nominal Current 0.78 A 0.35 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.78 0.78
Max Input Current 2.00 A 0.90 A
Starting Current 0.60 A 0.27 A
Open Circuit Voltage 250V 250V
Drop Out Voltage 96V 222V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 6 3
UL Bench Top Rise
cUL Listed UL Listed
Safety and performance
86574 11210239CTC000I
Enclosed and Potted Metal Halide
1 – 100W M90 120/277 Enclosed and Potted
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes M90
Voltage 120/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating B (25-30 decibels)
Additional Info Thermally Protected
Electrical characteristics
Supply Current Frequency 60 Hz
• For applications requiring quieter or cooler operation than provided by standard coil and
coil ballasts
• Excellent sound-deadening and heat transfer qualities
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 4
Dimensions
Wiring diagram HID H34 – see example on page 180
Case dimensions – Ref Drawing FCAN1 – see page 184
Length (L) 11.8 in (298.45 mm)
Width (W) 3.2 in (80.96 mm)
Height (H) 2.6 in (66.67 mm)
Mounting dimensions
Mount Length (M) 11.1 in (282.97 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.2 in (5.95 mm)
Weight 11.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp 20 ft
Remote Mounting Wire Gauge 18 AWG
Lead Lengths
Black and White
Red
Black/Yellow
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M90
100W Ceramic
Metal Halide
100W Quartz
Metal Halide
120 277
System Wattage (W) 125 125
Nominal Current 2.20 A 1.10 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.80 0.80
Max Input Current 2.20 A 1.10 A
Starting Current 1.10 A 0.50 A
Open Circuit Voltage 250V 250V
Drop Out Voltage 96V 222V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 8 4
UL Bench Top Rise
86563 – 1110245SCTC000I
Enclosed and Potted Metal Halide
1 – 175W M57 120/277 Enclosed and Potted
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes M57, H39
Voltage 120/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating B (25-30 decibels)
Additional Info Thermally Protected
Electrical characteristics
Supply Current Frequency 60 Hz
• For applications requiring quieter or cooler operation than provided by standard coil and
coil ballasts
• Excellent sound-deadening and heat transfer qualities
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 2
Dimensions
Wiring diagram HID H34 – see example on page 180
Case dimensions – Ref Drawing FCAN2 – see page 184
Length (L) 14.3 in (363.72 mm)
Width (W) 3.2 in (80.96 mm)
Height (H) 2.6 in (66.67 mm)
Mounting dimensions
Mount Length (M) 13.8 in (349.25 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.2 in (5.84 mm)
Weight 14.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Lead Lengths
Black and White
Red
Black/Yellow
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M57, H39
175W Ceramic
Metal Halide
150W Quartz
Metal Halide
175W Mercury
120 277
System Wattage (W) 205 205
Nominal Current 1.75 a 0.75 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.85 0.85
Max Input Current
Starting Current
Open Circuit Voltage 300V 300V
Drop Out Voltage 96V 222V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 5 3
UL Bench Top Rise
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M98, M143
70W Ceramic
Metal Halide
70W Quartz
Metal Halide
120 277
System Wattage (W) 90 90
Nominal Current 0.78 A 0.35 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.78 0.78
Max Input Current 2.00 A 0.90 A
Starting Current 0.60 A 0.27 A
Open Circuit Voltage 250V 250V
Drop Out Voltage 66V 222V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 6 3
UL Bench Top Rise
cUL Listed UL Listed
Safety and performance
176 See page 195 for warranty information. 177
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
86564 – 1110246CTC000C
Enclosed and Potted Metal Halide
1 – 250W M58 120/277 Enclosed and Potted
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes M58, H37
Voltage 120/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating C (31-36 decibels)
Additional Info Thermally Protected
Electrical characteristics
Supply Current Frequency 60 Hz
• For applications requiring quieter or cooler operation than provided by standard coil and
coil ballasts
• Excellent sound-deadening and heat transfer qualities
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 2
Dimensions
Wiring diagram HID H34 – see example on page 180
Case dimensions – Ref Drawing FCAN3 – see page 184
Length (L) 16.8 in (425.45 mm)
Width (W) 3.2 in (81.02 mm)
Height (H) 2.7 in (69.59 mm)
Mounting dimensions
Mount Length (M) 16.1 in (409.57 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.2 in (5.94 mm)
Weight 17.50 lbs
Exit Type Side
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Lead Lengths
Black and White
Red
Black/Yellow
cUL Listed UL Listed
Safety and performance
Enclosed and Potted Metal HalideEnclosed and Potted Metal Halide
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M58, H37
250W Quartz
Metal Halide
175W Quartz
Metal Halide
250W Mercury
120 277
System Wattage (W) 295 295
Nominal Current 2.50 A 1.10 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.85 0.85
Max Input Current
Starting Current
Open Circuit Voltage 280V 280V
Drop Out Voltage 96V 222V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 8 4
UL Bench Top Rise
42670 – 1110-247SC-TC
Enclosed and Potted Metal Halide
1 – 400W M59 120/277 Enclosed and Potted F-Can
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes M59, H33
Voltage 120/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating C (31-36 decibels)
Additional Info Thermally Protected
Electrical characteristics
Supply Current Frequency 60 Hz
• For applications requiring quieter or cooler operation than provided by standard coil and
coil ballasts
• Excellent sound-deadening and heat transfer qualities
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 2
Dimensions
Wiring diagram HID H34 – see example on page 180
Case dimensions – Ref Drawing FCAN4 – see page 184
Length (L) 19.3 in (488.95 mm)
Width (W) 3.2 in (80.96 mm)
Height (H) 2.6 in (66.67 mm)
Mounting dimensions
Mount Length (M) 18.6 in (473.07 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.2 in (5.95 mm)
Weight 23.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Lead Lengths
Black and White
Red
Black/Yellow
cUL Listed UL Listed
Safety and performance
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M59, H39
360W Quartz
Metal Halide
400W Quartz
Metal Halide
400W Mercury
120 277
System Wattage (W) 455 455
Nominal Current 3.90 A 1.70 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.88 0.88
Max Input Current 3.90 A 1.70 A
Starting Current 2.50 A 1.00 A
Open Circuit Voltage 300V 300V
Drop Out Voltage 66V 222V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 10 5
UL Bench Top Rise C C
80728 – 1111-247SCTC000I
Enclosed and Potted Metal Halide
1 – 400W M59 120/277 Enclosed and Potted
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes M59, H33
Voltage 120/277
Line Voltage Regulation (+/-) 10%
Circuit Type CWA
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating C (31-36 decibels)
Additional Info Thermally Protected
Electrical characteristics
Supply Current Frequency 60 Hz
• For applications requiring quieter or cooler operation than provided by standard coil and
coil ballasts
• Excellent sound-deadening and heat transfer qualities
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 4
Dimensions
Wiring diagram HID H36 – see example on page 180
Case dimensions – Ref Drawing FCAN2 – see page 184
Length (L) 14.3 in (363.72 mm)
Width (W) 3.2 in (80.96 mm)
Height (H) 2.6 in (66.67 mm)
Mounting dimensions
Mount Length (M) 13.8 in (349.25 mm)
Mount Width (X or F) 2.0 in (50.80 mm)
Mount Slots (MS) 0.2 in (5.84 mm)
Weight 14.00 lbs
Exit Type Side
Remote Mounting Distance to Lamp
Remote Mounting Wire Gauge
Lead Lengths
Black and White
Red
Black/Yellow
Specifications by lamp and line voltage
Lamp Specifications by line voltage
M59, H33
360W Quartz
Metal Halide
400W Quartz
Metal Halide
400W Mercury
120 277
System Wattage (W) 460 460
Nominal Current 3.90 A 1.70 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.87 0.87
Max Input Current
Starting Current
Open Circuit Voltage 300V 300V
Drop Out Voltage 96V 222V
Power Factor (>=)%
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 10 5
UL Bench Top Rise
cUL Listed UL Listed
Safety and performance
178 See page 195 for warranty information. 179
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
F-Can and Post Mount High Pressure Sodium F-Can and Post Mount High Pressure Sodium
86605 – 1233142U000I
F-Can and Post Mount High Pressure Sodium
1 – 70W S62 120 Reactor-NPF
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S62
Voltage 120
Line Voltage Regulation (+/-) 5%
Circuit Type
R-HPF
R-NPF
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating
Additional Info
Dimensions
Wiring diagram HID H1a, HID H1 – see example on page 180
Case dimensions – Ref Drawing 1 – see page 184
Length (L) 4.00 in (101.60 mm)
Width (W) 0.75 in (19.05 mm)
Height (H) 0.00 in (2.36 mm)
Mounting dimensions
Bracket Length (BL) 4.00 in (101.60 mm)
Mount Length (M) 3.30 in (85.09 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A1.3
B2.6
Weight 2.50 lbs
Exit Type Side
Nominal Length
Frame Size (H x L)
Lead lengths
Black
Blue
White
Electrical characteristics
Supply Current Frequency 60 Hz
cUL Listed UL Listed
Safety and performance
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
86596 – 12210237CTC000I
F-Can and Post Mount High Pressure Sodium
1 – 70W S62 120/277 E & P F-Can built-in starter
General characteristics
Ballast Type Magnetic – F-Can
ANSI Lamp Codes S62
Voltage 120/277
Line Voltage Regulation (+/-) 5%
Circuit Type HX-HPF
Insulation Class 90C
Type of Capacitor
Capacitance
Voltage (MIN)
Capacitor Temperature Rating 100°C (212°F)
Sound Rating
Additional Info Thermally protected
Dimensions
Wiring diagram HID H34 – see example on page 180
Case dimensions – Ref Drawing FCAN1 – see page 184
Length (L) 11.75 in (298.45 mm)
Width (W) 3.188 in (80.96 mm)
Height (H) 2.625 in (66.67 mm)
Mounting dimensions
Bracket Length (BL)
Mount Length (M) 11.14 in (282.97 mm)
Mount Width (X or F) 2.00 in (50.80 mm)
Mount Slots (MS) 0.23 in (5.95 mm)
A
B
Weight 11.00 lbs
Exit Type Side
Nominal Length
Frame Size (H x L)
Lead lengths
White
Black
Black/Yellow
Red
Electrical characteristics
Supply Current Frequency 60 Hz
cUL Listed UL Listed
Safety and performance
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 4
• For applications requiring quieter or cooler operation than provided by standard coil & coil ballasts
• Excellent sound-deadening and heat transfer qualities
86606 – 1233154U000I
F-Can and Post Mount High Pressure Sodium
1 – 150W S55 120 Reactor-NPF
General characteristics
Ballast Type Magnetic – Core and Coil
ANSI Lamp Codes S55
Voltage 120
Line Voltage Regulation (+/-) 5%
Circuit Type R-NPF
Insulation Class 180C
Type of Capacitor
Capacitance 52 Mfd
Voltage (MIN) 120
Capacitor Temperature Rating 100°C (212°F)
Sound Rating
Additional Info Thermally protected
Dimensions
Wiring diagram HID H1 – see example on page 180
Case dimensions – Ref Drawing 1 – see page 184
Length (L) 4.00 in (101.60 mm)
Width (W) 0.75 in (19.05 mm)
Height (H) 0.00 in (2.36 mm)
Mounting dimensions
Bracket Length (BL) 4.00 in (101.60 mm)
Mount Length (M) 3.30 in (85.09 mm)
Mount Width (X or F)
Mount Slots (MS) 0.25 in (6.35 mm)
A2.0
B3.0
Weight 3.50 lbs
Exit Type Side
Nominal Length
Frame Size (H x L) 2.813 in x 3.939 in
Lead lengths
Black
Blue
White
Electrical characteristics
Supply Current Frequency 60 Hz
Order information
Type No. Items Per Sales Unit No. Items Per Standard Package
Standard Pack 1 6
• Magnetic ballast construction ideal for a wide variety of lighting applications
• Precision-wound coils, ensuring even heat dissipation and the highest electrical integrity
cUL Listed UL Listed
Safety and performance
Specifications by lamp & line voltage
Lamp Specifications by line voltage
S62
70W High
Pressure Sodium
120 120
System Wattage (W) 83 83
Nominal Current 0.75 A 1.60 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.84 0.84
Max Input Current 1.30 A 2.10 A
Starting Current 0.90 A 2.10 A
Open Circuit Voltage 120V 120V
Drop Out Voltage 96V 96V
Power Factor (>=)% 90 80
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 5 8
UL Bench Top Rise A A
Specifications by lamp & line voltage
Lamp Specifications by line voltage
S62
70W High
Pressure Sodium
120 277
System Wattage (W) 98 98
Nominal Current 0.87 A 0.39 A
Ballast Factor 1 1
Ballast Efficiency Factor 0.71 0.71
Max Input Current 0.87 A 0.39 A
Starting Current 0.60 A 0.27 A
Open Circuit Voltage 140V 140V
Drop Out Voltage 96V 222V
Power Factor (>=)% 90 90
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 6 3
UL Bench Top Rise
Specifications by lamp & line voltage
Lamp Specifications by line voltage
S55
150W High
Pressure Sodium
250W Quartz
Metal Halide
120 120
System Wattage (W) 171 171
Nominal Current 1.50 A 3.20 A
Ballast Factor 1 1
Ballast Efficiency Factor 1.46 1.46
Max Input Current 2.40 A 4.40 A
Starting Current 2.20 A 4.40 A
Open Circuit Voltage 120V 120V
Drop Out Voltage 96V 96V
Power Factor (>=)% 90 80
Min. Starting Temp (°F/°C) -22 / -30 -22 / -30
Fuse Rating 8 15
UL Bench Top Rise A A
HID Accessories
HID Accessories Prod Code Description Application Units Per Carton
Replacement Capacitors 88980 005-1184-MF 10.0 MFD 400V 90C 2.4 MEG 1.50 oval 2.7 ht 20
88982 005-1185-MF 15.0 MFD 400V 90C 1.6 MEG 1.75 oval 2.7 ht 20
89007 005-1422-MF 48.0 MFD 300V 90C 0.6 MEG 1.75 oval 3.9 ht 20
89077 005-2779-MF 24.0 MFD 480V 90C 1.75 oval 3.9 ht 20
89083 005-3160-MF 24.0 MFD 360V 90C 1.0 MEG 1.75 oval 3.1 ht 20
Replacement Ignitors for Pulse
Start Lamps (MH & HPS)
86864 MH100-3A Ignitor for MH 30 50 70 100 20
86635 HPS150-3A Ignitor HPS 150 watts or less except 150w-S56 20
86641 HPS400-3A Ignitor HPS 200-400 watts & 150w S56 10
Other Accessories 47621 000-8724 HIDP Adjustable Mounting Bracket Hardware Kit 100
86467 001-2009 Splice Box 10
86468 004-9177 Adjustable Mounting Bracket For 4” HID 50
86624 2BMB1000C HID Parts E&P Mounting Bracket 50
180 See page 195 for warranty information. 181
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Wiring Diagrams
HID Electromagnetic Ballasts
HID H1
Wiring Diagrams
HID Electromagnetic Ballasts
HID H1a
HID H34 HID H36
HID H6
HID W-(A)-46934-86885-86935 HID W-(A)-86959-86984-87008
HID W-(A)-87056-87121-87164 HID W-(B)-87214-87215-87218
HID W-(C)-86655-86698-86741 HID W-(C)-86765-86814
HID W-(D)-86952-86999 HID W-(D)-87048-87198-46936
HID H21
182 See page 195 for warranty information. 183
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Wiring Diagrams
HID Electromagnetic Ballasts
HID W-(E)-86926 HID W-(E)-87087-86711-86876
HID W-(F)-87068-86667 HID W-(H)-86587-87074
HID W-(H)-86675-86718 HID W-(H)-86824-86847
HID W-(H)-87094-87152 HID W-(J)-86650-86693-86803
Wiring Diagrams
HID Electromagnetic Ballasts
HID W-(K)-86808-87210-87211 HID W-(K)-87212-87213
HID W-(L)-86968
184 See page 195 for warranty information. 185
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Case Dimensions
HID Electromagnetic Ballasts
FCAN11
FCAN2 FCAN3
A
PC1 PC2
Case Dimensions
HID Electromagnetic Ballasts
PC3
FCAN4
186 187
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
Amperes
(“Amps.) A measure of electrical current. The
current is related to voltage and power as follows:
Watts (power) = Volts x Amps (current).
ANSI (American National Standards Institute)
A consensus-based organization which
coordinates voluntary standards for the physical,
electrical and performance characteristics of
lamps, ballasts, luminaires and other lighting and
electrical equipment.
ANSI Ballast Type
Ballast type used to operate lamp in accordance
with ANSI standard.
ANSI Codes
These are 3-letter codes assigned by the American
National Standards Institute. They provide a
system of assuring mechanical and electrical
interchangeability among similarly coded lamps
from various manufacturers. General Electric uses
the assigned ANSI Codes as Lamp Ordering Codes
for most Projection Lamps.
Auto Reset Shutdown Circuit
Circuit senses lamp end life and will automatically
shut off power to the lamp(s). When a new lamp is
inserted in the socket, the ballast resets, and turns
on the lamp automatically. Some shutdown circuits
require the power to be cycled before a new lamp
will re-light.
Ballast
An auxiliary piece of equipment required to start
and to properly control the flow of current to gas
discharge light sources such as fluorescent and
high intensity discharge (HID) lamps. Typically,
magnetic ballasts (also called electromagnetic
ballasts) contain copper windings on an iron core
while electronic ballasts are smaller and more
efficient and contain electronic components.
Ballast Efcacy Factor (BEF)
Defined as ballast factor x100 divided by input
watts. The value is used to evaluate various lighting
systems based on light output and power input.
The BEF can only be used to compare systems
operating the same type and quantity of lamps.
Ballast Factor (BF)
This is the percentage of a lamp’s rated lumen
output that can be expected when operated on a
specific, commercially available ballast. Note that
the “rated output” is sometimes measured on a
reference ballast unlike ones that actually operate
the lamp in the field. For example, a ballast with
a ballast factor of 0.93 will result in the lamp’s
emitting 93% of its rated lumen output. A ballast
with a lower BF results in less light output and also
generally consumes less power.
Ballast Hum
Sound generated by the vibration of laminations in
the iron core or inductor in the ballast.
Ballast Losses
Power or energy dissipated in the ballast as heat
and not converted to lamp energy.
Base Temperature (Maximum)
The maximum operating temperature permitted
for the base in Celsius. Fixture manufacturers need
to ensure that these conditions are satisfied.
Bi-Pin
Any base with two metal pins for electrical contact.
This is the typical base for a fluorescent tube of 1 to
4 feet in length. It consists of 2 prong contacts that
connect into the fixture. Medium bi-pins are used
with type T-8 and T-12 tubular fluorescent lamps,
and miniature bi-pins are used for tubular T-5
fluorescent lamps.
Bottom Exit (BE)
(CFL plug-in ballasts) A configuration with leads or
a wire-trap on the bottom or base of the ballast.
This type of configuration is usually used when the
ballast is mounted onto a junction box plate.
Bottom Exit Studs (BES)
(CFL plug-in ballasts) A configuration with screw
studs mounted on the base plate or bottom of the
ballast. The screws are 3/8-inch long with a #8-32
thread size (#8-32 nut). They are mounted on a
2-inch center. The studs are usually used to mount
the ballast directly onto a junction box plate.
Bulb Size
Bulb shape followed by its size (the maximum
diameter of the bulb expressed in eighths of an
inch). For Compact Fluorescent products, “S”, “D”,
T”, and “Q” are used to represent Single, Double,
Triple and Quad Biax® sizes. The code also includes
a reference such as T4 to represent the size of the
tube. Rectangular headlamps are designated as
“Rect” and the number of millimeters horizontally.
Canadian Energy Standards
Indicates ballast complies with Canadian Energy
Standards and meets the requirements of CAN/
CSA C654-M91.
Canadian Standards Associations (CSA)
Association that generates product
performance and safety standards for
many Canadian industries.
Capacitor
Device in ballast that stores electrical energy,
and is used for power factor correction and
lamp regulation.
Cathode
Metal filaments that emit electrons in a fluorescent
lamp. Negatively charged free electrons emitted
by the cathode are attracted to them, creating an
electric current between the electrodes.
Cathode Resistance
Resistance of the cathode in a Fluorescent lamp. It
is measured “cold” before the lamp is turned on (Rc)
or “hot” after the lamp is turned on (Rh). The ratio
of the hot resistance to the cold resistance is also
measured (Rh/Rc).
Ceramic Metal Halide
A type of metal halide lamp that uses a ceramic
material for the arc tube instead of glass quartz,
resulting in better color rendering (>80 CRI) and
improved lumen maintenance. GE ConstantColor®
CMH® lamps deliver reliability and excellent color.
ChromaFit
A GE brand name for metal halide lamps designed
to operate on HPS ballasts, allowing a user to
switch from the yellowish color of HPS to the white
color of metal halide without changing ballasts.
These products are available in both quartz metal
halide and ceramic metal halide (CMH) versions.
Class P Thermal Protector
A switching device sensitive to current and heat
that automatically disconnects ballast if the
temperature exceeds UL temperature limitations.
Coefficient of Utilization (CU)
In general lighting calculations, the fraction of
initial lamp lumens that reach the work plane. CU
is a function of luminaire efficiency, room surface
reflectances and room shape.
Coil
Windings of copper or aluminum wire surrounding
the steel core in ballast. Also refers to the entire
assembly comprising the inductor or transformer.
Color Rendering Index (CRI)
An international system used to rate a lamp’s
ability to render object colors. The higher the
CRI (based upon a 0-100 scale) the richer colors
generally appear.
Color Temperature (Correlated Color
Temperature – CCT)
A number indicating the degree of “yellowness”
or “blueness” of a white light source. Measured
in kelvins, CCT represents the temperature an
incandescent object (like a filament) must reach
to mimic the color of the lamp. Yellowish-white
(“warm”) sources, like incandescent lamps, have
lower color temperatures in the 2700K-3000K
range; white and bluish-white (“cool”) sources, such
as cool white (4100K) and natural daylight (6000K),
have higher color temperatures. The higher the
color temperature, the bluer the light will be.
Compact Fluorescent Lamp (CFL)
The general term applied to fluorescent lamps that
are single-ended and that have smaller diameter
tubes that are bent to form a compact shape.
Some CFLs have integral ballasts and medium or
candelabra screw bases for easy replacement of
incandescent lamps.
Cool White
A term loosely used to denote a color temperature
of around 4100K. The Cool White (CW) designation
is used specifically for T12 and other fluorescent
lamps using halophosphors and having a CRI of 62.
Core
Component of electromagnetic ballast that is
surrounded by the coil. Core is comprised of steel
laminations or solid ferrite material.
Core & Coil Ballast
A ballast that uses a “Core & Coil” assembly to
operate fluorescent or HID lamps. Refers to copper
or aluminum windings on a steel core.
Cost of Light
Usually refers to the cost of operating and
maintaining a lighting system on an ongoing basis.
The 88-8-4 rule states that (typically) 88% is the
cost of electricity, 8% is labor and only 4% is the
cost of lamps.
Crest Factor (Lamp Current Crest Factor)
Ratio of peak to RMS for any AC waveform. Crest
factor can refer to voltage crest factor or current
crest factor.
Daylight Harvesting
Lighting design for building interiors that makes
use of daylight as a way of reducing energy
consumption.
Dimmer, Dimming Control
A device used to lower the light output of a
source, usually by reducing the wattage it is being
operated at. Dimming controls are increasing in
popularity as energy-conserving devices.
Ecolux®
A term for GE lamps that have reduced mercury
content and pass the TCLP test.
Efficacy
A measurement of how effective the light source is
in converting electrical energy to lumens of visible
light. Expressed in lumens-per-watt (LPW), this
measure gives more weight to the yellow region
of the spectrum and less weight to the blue and
red regions where the eye is not as sensitive. The
efficiency of a light source is simply the fraction
of electrical energy converted to light, i.e. watts of
visible light produced for each watt of electrical
power with no concern about the wavelength
where the energy is being radiated. For example,
a 100-watt incandescent lamp converts 7% of
the electrical energy into light; discharge lamps
convert 25% to 40% into light.
Efficiency of Ballast
The ratio of output power divided by input power.
A premium ballast would have an electrical
efficiency greater than 90%. The efficiency of a
luminaire or fixture is the percentage of the lamp
lumens that actually come out of the fixture.
Electrical Discharge
A condition under which a gas becomes electrically
conducive and becomes capable of transmitting
current, usually accompanied by the emission of
visible and other radiation. An electric spark in air
is an example of an electrical discharge, as are a
welder’s arc and a lightning bolt.
Electrical Testing Laboratory (ETL)
Independent testing laboratory that performs tests
and certifies performance data.
Electrode
Any metal terminal emitting or collecting
charged particles, typically inside the chamber
of a gas discharge lamp. In a fluorescent lamp,
the electrodes are typically metal filaments
coated with special powders called emission mix.
Negatively charged free electrons emitted by one
electrode are attracted to the positive electrode
(anode), creating an electric current arc.
Electromagnetic Ballast (Magnetic Ballast)
A ballast used with discharge lamps that consists
primarily of transformer-like copper or aluminum
windings on a steel or iron core. Also called “core
and coil” (see ELECTRONIC BALLASTS).
EMI (Electromagnetic Inference)
High-frequency electronic ballasts and other
electronic devices can produce a small amount
of radio waves which can interfere with radio
and TV. Federally mandated requirements must
be met for EMI levels before an electronic device
is considered FCC compliant (FCC is the Federal
Communications Commission).
Electronic Ballast
A short name for a fluorescent high-frequency
electronic ballast. Electronic ballasts use solid-
state electronic components and typically operate
fluorescent lamps at frequencies greater than 25
kHz. The benefits are: increased lamp efficacy,
reduced ballast losses and lighter, smaller ballasts
compared to electromagnetic ballasts. Electronic
ballasts may also be used with HID (high intensity
discharge) lamps (see ELECTROMAGNETIC BALLAST).
Energy Policy Act (EPACT)
U.S. Energy legislation setting minimum efficacy
(lumens/watt) requirements. Federal Canadian
legislation sets similar requirements.
Federal Communications Commission (FCC)
The U. S. federal agency that regulates emissions in
the radio frequency portion of the electromagnetic
spectrum. Part 18 of the FCC rules specifies
electromagnetic interference (EMI) from lighting
devices at frequencies greater than 450 kilohertz
(kHz). A consumer-rated Class B ballast is designed
for use in the home near TV and radio receivers. It
produces less electrical noise that could interfere
with consumer products. A Class A-rated ballast
is designed for use in commercial and industrial
applications that are not in the vicinity of TV and
radio receivers.
Flicker
The periodic variation in light level caused by AC
operation that can lead to strobe effects.
Fluorescent Lamp
A high efficiency lamp utilizing an electric
discharge through inert gas and low-pressure
mercury vapor to produce ultraviolet (UV) energy.
The UV excites phosphor materials applied as a
thin layer on the inside of a glass tube that makes
up the structure of the lamp. The phosphors
transform the UV to visible light.
Footcandles
A unit of illuminance or light falling onto a surface.
It stands for the light level on a surface one foot
from a standard candle. One footcandle is equal to
one lumen per square foot.
Four-Pin Compact Fluorescent Lamps
A “plug-in” compact fluorescent lamp with four
pins in the base to make electrical contact.
Frequency
Rate of alternation in an AC current. Expressed in
cycles per second or Hertz (Hz).
Harmonic
An integral multiple of the fundamental frequency
(60 Hz) that becomes a component of the current.
Harmonic Distortion
Distortion of an AC waveform caused by multiples
of the fundamental frequency (harmonics). Odd
triplet harmonics (thirds, ninths, etc.) may result in
large currents on the neutral line in a four-wire Wye
three-phase system.
Hertz (Hz)
Unit used to measure frequency of alteration of
current or voltage.
High Efficiency (Energy-Saving) Electromagnetic
Ballast
Ballast with core and coils, designed to minimize
ballast losses compared to the “standard” ballast.
High Intensity Discharge (HID) Lamp
A general term for mercury, metal halide (GE
ConstantColor® CMH®, Multi-Vapor®, MXR or
Arcstream®) and high-pressure sodium (GE
Lucalox®) lamps. HID lamps contain compact arc
tubes which enclose mercury and various gases
with other chemicals and operate at relatively high
pressures and temperatures.
High Power Factor
A ballast whose power factor is corrected to 90%
or greater.
High-Pressure Sodium (HPS) Lamp
HPS lamps are high intensity discharge light
sources that produce light by an electrical
discharge though sodium vapor operating at
relatively high pressures and temperatures. GE
trade name is Lucalox®.
Hot Restart Time
Time it takes for an HID lamp to reach 90% of light
output after going from on to off to on.
Ignitor
An electronic device providing a high voltage pulse
to initiate an electrical discharge. Typically, the
ignitor is paired with or is a part of the ballast
(see STARTER).
Infrared Radiation
Electromagnetic energy radiated in the
wavelength range of about 770 to 1,000,000
nanometers. Energy in this range cannot be seen
by the human eye, but can be sensed as heat.
Input Voltage
Power supply voltage required for proper operation
of fluorescent or HID ballast.
Input Watts
The total power input to the ballast that includes
lamp watts and ballast losses. The total power
input to the fixture is the input watts to the ballast
or ballasts and is the value to be used when
calculating cost of energy. More than 90% of the
input watts is wattage or power delivered to the
lamp load with typical ballast.
Instant Start
Lamp starting method in which lamps are started
by high voltage input with no preheating of lamp
filaments. Some rapid start lamps are designed so
that they may be instant started.
Instant Start Lamp
A fluorescent lamp, usually with a single pin at each
end, approved to operate on instant start ballasts.
The lamp is ignited by a high voltage without any
filament heating.
Integral
A popular term for a compact fluorescent lamp
that includes a built-in ballast (see CFL).
Kilowatt (kW)
The measure of electrical power equal to 1000
watts.
Kilowatt Hour (kWh)
The standard measure of electrical energy and
the typical billing unit used by electrical utilities for
electricity use. A 100-watt lamp operated for 10
hours consumes 1000 watt-hours (100 x 10) or one
kilowatt-hour. If the utility charges $.10/kWh, then
the electricity cost for the 10 hours of operation
would be 10 cents (1 kWh x $.10).
Laminations
Layers of steel, making up the “core” that is
surrounded by the coils in a core and coil ballast.
Lamp
The term used to refer to the complete light-source
package, including the inner parts as well as
the outer bulb or tube. “Lamp,” of course, is also
commonly used to refer to a type of small light
fixture such as a table lamp.
Lamp Types
Filament lamps: Incandescent, Halogen, Halogen-IR.
Discharge Lamps: Fluorescent, HID (High Intensity
Discharge).
HID Lamps: Mercury, HPS (High Pressure Sodium),
MH (Metal Halide) and Ceramic Metal Halide.
Lamp Watts
Input power used to operate lamps.
Life
(See RATED LAMP LIFE.)
Light
Radiant energy that can be sensed or seen by the
human eye. Visible light is measured in lumens.
Light-Emitting Diode (LED)
A solid that directly converts electrical impulses
into light.
Light Loss Factor
The product of all factors that contribute to
lowering the illumination level including reflector
degradation, dirt, lamp depreciation over time,
voltage fluctuations, etc.
Lumens
A measure of the luminous flux or quantity of light
emitted by a source. For example, a dinner candle
provides about 12 lumens. A 60-watt Soft White
incandescent lamp provides about 840 lumens.
Glossary
188
Glossary (cont.)
189
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
Lumens/Watts
A ratio expressing the luminous efficacy of a light
source. Typical lamp efficacies:
• Thomas Edisons first lamp - 1.4 lpW
• Incandescent lamps - 10-40
• Halogen incandescent lamps - 20-45
• Fluorescent lamps - 35-105
• Mercury lamps - 50-60
• Metal halide lamps - 60-120
• High-pressure sodium lamps - 60-140
Note: The values above for discharge lamps do
not include the effect of the ballasts, which must
be used with those lamps. Taking ballast losses
into account reduces “system” or lamp-ballast
efficacies typically by 10-20% depending upon the
type of ballast used.
Lumen Maintenance
A measure of how well a lamp maintains its light
output over time.
Luminaire Efficiency
The ratio of total lumens emitted by a luminaire to
those emitted by the lamp or lamps used in that
luminaire.
Luminaire
A complete lighting unit consisting of a lamp,
ballast as required, together with the parts
designed to distribute the light, position and
protect the lamps and connect them to the power
supply. A luminaire is often referred to as a fixture.
Lux (lx)
A unit of illuminance or light falling onto a surface.
One lux is equal to one lumen per square meter.
Ten lux approximately equal one footcandle
(see FOOTCANDLE).
Mean Lumens
The average light output of a lamp over its rated
life. Based on the shape of the lumen depreciation
curve, for fluorescent and metal halide lamps,
mean lumens are measured at 40% of rated
lamp life. For mercury, high-pressure sodium and
incandescent lamps, mean lumen ratings refer
to lumens at 50% of rated lamp life (see LUMEN
MAINTENANCE).
Medium Base
Usually refers to the screw base typically used in
household incandescent lamps. There is also the
medium bi-pin base commonly used in T12 and T8
fluorescent lamps.
Metal Cases
Case design used in both magnetic and electronic
ballasts. These ballasts are grounded once they
are mounted to the fixture. They meet all safety
codes, some of which do not allow plastic in open
plenum areas.
Metal Halide Lamp
A high intensity discharge light source in which the
light is produced by the radiation from mercury,
plus halides of metals such as sodium, scandium,
indium and dysprosium. Some lamp types may
also utilize phosphor coatings. GE trade names
include: Multi-Vapor®, ConstantColor® CMH®,
PulseArc®, Staybright®, Watt-Miser®, ChromaFit
and Arcstream®.
Mogul Base
A screw base used on larger lamps, e.g. many
HID lamps.
Mounting Height
Distance from the bottom of the fixture to either
the floor or work plane, depending on usage.
Multi-Vapor®
A GE brand for metal halide lamps.
National Electric Code (NEC)
A nationally accepted electrical installation code
to reduce the risk of fire, developed by the National
Fire Protection Association.
National Energy Standards for Fluorescent
Ballasts
A federal law enacted in 1988 that sets energy
standards for ballasts consistent throughout the
United States.
National Stock Number
The standardized part number used by the U.S.
Government for procurement.
NOM
Laboratory that sets safety standards for building
materials and electrical products for Mexico.
Non-PCB Capacitor
Capacitor used in ballasts to help provide power
factor correction. Contains no polychlorinated
biphenyls and meets EPA requirements.
Normal Power Factor
Ballasts with power factor less than .90 and do not
incorporate any means of Power Factor Correction.
Open Circuit Voltage (OCV)
Open Circuit Voltage measured across the socket
the lamp screws into, with the ballast powered
on. It is dangerous to stick a voltmeter into such a
socket without precise knowledge of the ballast
because exceedingly high voltages could be
present.
Operating Voltage
For electrical discharge lamps, this is the voltage
measured across the discharge when the lamp
is operating. It is governed by the contents of the
chamber and is somewhat independent of the
ballast and other external factors.
Parallel Lamp Operation
Refers to ballasts that employ multiple output
current paths from a single ballast to allow lamps
to operate independently of one another, allowing
other lamps operated by the ballast to remain lit
should companion lamp(s) fail.
PCB (Polychlorinated Biphenyls)
Chemical pollutant formerly used in ballast
capacitors that were part of ballasts. It is now
illegal to use PCBs and most such ballasts have
been replaced over time.
Phosphor
An inorganic chemical compound processed into
a powder and deposited on the inner glass surface
of fluorescent tubes and some mercury and metal-
halide lamp bulbs. Phosphors are designed to
absorb short wavelength ultraviolet radiation and
to transform and emit it as visible light.
Potting
Material used to completely surround and cover
components of some magnetic and electronic
ballasts. Potting compound fulfills functions of
protecting components, dampening sound, and
dissipating heat.
Power Factor
Measurement of the relationship between the AC
source voltage and current. High-power factor
ballasts require less AC operating current at the
same wattage than an equivalent low-power
factor ballast. Formula: power factor equals input
watts divided by the product of line volts times line
amps (volt amps or VA).
Power Factor Corrected
Ballasts that incorporate a means of Power Factor
Correction yielding power factor of 90% or greater.
Preheat Circuit
A type of fluorescent lamp-ballast circuit used with
the first commercial fluorescent lamp products. A
push-button or automatic switch is used to preheat
the lamp cathodes to a glow state before starting.
Product Code
Five-digit code to identify the product.
Programmed Rapid Start
Lamp starting method which preheats the lamp
filaments while not allowing the lamp to ignite and
then applies the open circuit voltage (OCV) to start
the lamp. This type of starting circuit keeps lamp-
end blackening to a minimum and improves lamp-
life performance, especially in applications where
the lamps are frequently switched on and off.
PulseArc®
GE description for a type of metal halide lamp that
provides improved lumen maintenance for longer
useful life and extended relamp cycles. These
products are designed to operate on ballasts that
have ignitors to help with lamp starting.
Pulse Start
An HID ballast with a high voltage ignitor to start
the lamp.
Quartz
A name for fused silica or melted sand from which
many high-temperature containers are fashioned
in the lighting industry. Quartz looks like glass but
can withstand the high temperatures needed to
contain high intensity arc discharges.
Radiation
A general term for the release of energy in a “wave”
or “ray” form. All light is radiant energy or radiation,
as is heat, UV, microwaves, radio waves, etc.
Rapid Start Circuit
A fluorescent lamp-ballast circuit that utilizes
continuous cathode heating, while the system is
energized, to start and maintain lamp light output
at efficient levels. Rapid start ballasts may be either
electromagnetic, electronic or of hybrid designs.
Full-range fluorescent lamp dimming is only possible
with rapid start systems (see INSTANT START).
Rapid Start
Lamp starting method in which lamp filaments are
heated while open circuit voltage (OCV) is applied
to facilitate lamp ignition. A Rapid Start fluorescent
lamp has two pins at each end connected to the
filament. The filaments are heated by the ballast
to aid in starting. Some rapid start lamps may be
instant started without filament heat, for example
the F32T8 lamp.
Rated Lamp Life
For most lamp types, rated lamp life is the length
of time of a statistically large sample between first
use and the point when 50% of the lamps have
died. It is possible to define “useful life” of a lamp
based on practical considerations involving lumen
depreciation and color shift.
Room Cavity Ratio (RCR)
A shape factor (for a room, etc.) used in lighting
calculations.
RCR = 5H (L+W) / L x W, or, alternately,
RCR = (2.5) Total Wall Area / Floor Area.
Where H = height, L = length and W = width of
the room.
A cubical room will have an RCR of 10; the flatter
the room the lower the RCR.
Scotopic/Photopic (S/P) Ratio
This measurement accounts for the fact that of
the two light sensors in the retina, rods are more
sensitive to blue light (scotopic vision) and cones to
yellow light (photopic vision). The scotopic/photopic
(S/P) ratio is an attempt to capture the relative
strengths of these two responses. S/P is calculated
as the ratio of scotopic lumens to photopic
lumens for the light source on an ANSI reference
ballast. Cooler sources (higher color temperature
lamps) tend to have higher values of the S/P ratio
compared to warm sources.
Self-Ballasted Lamps
A discharge lamp with an integral ballasting device
allowing the lamp to be directly connected to a
socket providing line voltage (see CFL).
Series Lamp Operation
Refers to ballasts that employ a single current path
passing through all lamps operated by the ballast.
If one lamp should fail, companion lamps operated
by the same ballasts will also extinguish or dim.
Spacing-to-Mounting-Height Ratio
Ratio of fixture spacing (distance apart) to
mounting height above the work plane; sometimes
called spacing criterion. It is OK to have fixtures
spaced closer than the spacing criterion suggested
by the manufacturer but not farther, or you will get
dark spots in between fixtures.
Specification Series (SP) Colors
Energy-efficient, all-purpose, tri-phosphor
fluorescent lamp colors that provide good color
rendering. The CRI for SP colors is 70 or above and
varies by specific lamp type.
Specification Series Deluxe (SPX) Colors
Energy-efficient, all-purpose, tri-phosphor
fluorescent lamp colors that provide better color
rendering than Specification Series (SP) colors.
The CRI for SPX colors is 80 or above and varies by
specific lamp type. All GE CFL products use
SPX phosphors.
Specification Series Deluxe eXtreme (SPXX) Colors
A color designation for GE ceramic metal halide
lamps with superior color rendering ~ 90.
Specular Reflection
Reflection from a smooth, shiny surface, as
opposed to diffuse reflection.
Spiral® Lamp
GE trademark for its helical family of high-
efficiency, long-life compact fluorescent lamps.
Starcoat®
GE’s special barrier coating applied on the inside
of all GE T8 fluorescent lamps, as well as some
other lamp types, to enhance lamp life and deliver
superior lumen maintenance.
Starter
An electronic module or device used to assist in
starting a discharge lamp, typically by providing a
high-voltage surge (see IGNITOR).
Starting Temperature (Minimum)
The minimum ambient temperature at which the
lamp will start reliably.
T-12, T-8, T-5
A designation for the diameter of a tubular bulb in
eighths of an inch; T-12 is 12 eighths of an inch, or
1-1/2 inches; T-8 is 1 inch, and so on.
Task Lighting
Supplemental lighting provided to assist in
performing a localized task, e.g., a table lamp for
reading or an inspection lamp for fabric inspection.
TCLP Test
The Toxicity Characteristic Leaching Procedure
(TCLP) test, specified in the U.S. Resource
Conservation and Recovery Act (RCRA) of 1990, is
used to characterize fluorescent lamp waste as
hazardous or nonhazardous waste. The TCLP test
measures the ability of the mercury and/or lead in
a lamp to leach from a landfill into groundwater
(see ECOLUX).
THD
(See TOTAL HARMONIC DISTORTION.)
Terminal-to-Terminal Starting Lamp Voltage
(VRMS) (Minimum or Maximum)
The minimum or maximum voltage allowed into
lamp from ballast under varying conditions as
specified.
Total Harmonic Distortion (THD)
A measure of the distortion of the input current on
alternating-current (AC) power systems caused
by higher-order harmonics of the fundamental
frequency (60Hz in North America). THD is
expressed in percent and may refer to individual
electrical loads (such as ballast) or a total electrical
circuit or system in a building. ANSI C82.77
recommends THD not exceed 32% for individual
commercial electronic ballasts, although some
electrical utilities may require lower THDs on some
systems. Excessive THDs on electrical systems can
cause efficiency losses as well as overheating and
deterioration of system components.
Transients
High voltage surges through an electrical system
caused by lightning strikes to nearby transformers,
overhead lines or the ground. May also be caused
by switching of motors or compressors, as well as
by short circuits or utility system switching. Can
lead to premature ballast failure.
Troffer
A long, recessed lighting unit, usually installed in an
opening in the ceiling.
Two-Pin Compact Fluorescent Lamps
Type of lamps that have the glow bottle starter
built into the base of the lamp. Traditionally two-pin
lamps work with electromagnetic ballasts.
Underwriters Laboratories (UL)
A private organization which tests and
lists electrical (and other) equipment for
electrical and fire safety according to
recognized UL and other standards. A UL listing is
not an indication of overall performance. Lamps
are not UL listed except for compact fluorescent
lamp assemblies—those with screw bases and
built-in ballasts.
Uniform Product Code (UPC)
The 12-digit code on the saleable unit that is used
for scanning at the register.
Ultra
A common way of referring to high-efficiency GE
T8 family of lamps and ballast that performs better
than standard T8 lamps. Also refers to the system.
UltraMax® Ballast
A family of high-efficiency GE instant-start
electronic linear fluorescent ballasts designed to
optimize GE’s T8 Ultra lamps for enhanced system
energy savings. UltraMax® ballasts have a low
lamp current crest factor and virtually “read
and adapt to incoming voltage from 108V to
305V. Other features include UL Type CC Anti-Arc
Rating and anti-striation control to eliminate lamp
striations and spiraling. GE also has an UltraMax®
HID ballast which can operate PulseArc® and CMH®
lamps anywhere from 250 watts to 400 watts and
provides greatly improved lumen maintenance.
UltraStart® Ballast
A family of high-efficiency GE programmed start
electronic linear fluorescent ballasts designed to
optimize GE’s T8 Ultra lamps in frequently switched
applications. Instant start ballast provides 10,000
starts. UltraStart® provides 100,000 to 200,000
starts. Use programmed start ballast to ensure
long lamp life when turning lamps on and off more
than twice a day.
Ultraviolet (UV) Radiation
Radiant energy in the range of about 100-380
nanometers (nm). For practical applications, the UV
band is broken down.
The International Commission on Illumination (CIE)
defines the UV band as UV-A (315-400 nm); UV-B
(280-315 nm) and UV-C (100-280 mm).
Ultra Watt-Miser®
GE’s family of energy-saving T8 fluorescent lamps.
Veiling Reflection
Reflected glare from a light source bouncing off a
shiny surface.
Visual Comfort Probability (VCP)
VCP is the percent of people who find the lighting
scheme acceptable in terms of glare.
Volt
A measure of “electrical pressure” between two
points. The higher the voltage, the more current
will be pushed through a resistor connected across
the points. The volt specification is the electrical
“pressure” required to drive it at its designated
point. The “voltage” of a ballast (e.g. 277 V) refers
to the line voltage it must be connected to.
Voltage
A measurement of the electromotive force in
an electrical circuit or device expressed in volts.
Voltage can be thought of as being analogous to
the pressure in a water line.
Wall Temperature (Maximum Bulb)
The maximum operating bulb wall temperature.
Warm-Up Time to 90%
The time it takes for a HID lamp to reach 90% of
light output after being turned on.
Warm White
Refers to a color temperature around 3000K,
providing a yellowish-white light.
Watt
A unit of electrical power. Lamps are rated in watts
to indicate the rate at which they consume energy
(see KILOWATT HOUR).
Watt-Miser®
A Watt-Miser® lamp is a term used by GE
to indicate a reduced-wattage lamp with
performance characteristics (life, light output, etc.)
such that it can usually directly replace a higher-
wattage product.
Wattage Indicator Reduced
Indicates that this is a reduced wattage option for
lamps normally used in this application. Be sure to
check wattage, lumens and life to determine which
lamp is best suited to your needs.
Wavelength
The distance between two neighboring crests of a
traveling wave. The wavelength of light is between
400 and 700 nanometers.
190 See page 195 for warranty information. 191
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Ballast cross reference matrix
Prod
Code Description Advance P/N Universal P/N OSI P/N Howard P/N
T8 Fluorescent Ballasts
T8 INSTANT START BALLASTS
UltraMax® Instant Start Multi-Voltage High Efficiency
72258 GE132MAX-L/ULTRA IOP-1P32LW-SC B132IUNVEL-A
72259 GE132MAX-N/ULTRA IOP-1P32-SC B132IUNVHE-A QHE 1X32T8/UNV ISN-SC-1
49775 GE232MAX-H/ULTRA IOP-2P32HL-SC B232IUNVHEH-A
72262 GE232MAX-L/ULTRA IOP-2P32LW-SC B232IUNVEL-A
72266 GE232MAX-N/ULTRA IOP-2P32-SC B232IUNVHE-A QHE 2X32T8/UNV ISN-SC-1
71421 GE232MAX-N+
71714 GE332MAX-H/ULTRA IOP-3P32HL-90C-SC B332IUNVHEH-A QHE 3X32T8/UNV ISH-SC-1
71717 GE332MAX-L/ULTRA IOP-3P32LW-SC B332IUNVEL-A
71719 GE332MAX-N/ULTRA ICN-3P32-SC B332IUNVHE-A
71422 GE332MAX-N+
71723 GE432MAX-H/ULTRA IOP-4P32HL90CG QHE 4X32T8/UNV ISH-SC-1
71725 GE432MAX-L/ULTRA IOP-4P32LW-SC B432IUNVEL-A
71727 GE432MAX-N/ULTRA ICN-4P32-SC B432IUNVHE-A
71423 GE432MAX-N+
49766 GE159MAX-N/ULTRA
49767 GE259MAX-N/ULTRA IOP-2P59-SC
ProLine® T8 Multivolt 120V - 277V
72269 GE-132-MV-N ICN-1P32-SC B132IUNVHP-B
QTP 1X32T8/UNV ISL-SC/QHE
1X32T8/UNV ISN-SC
30198 GE-232-MV-H REL-2P32-HL-SC/VEL-2P32-HL-SC B232I120RHH-A/B232I277RHH-A
QTP 2X32T8/UNV ISH-SC/QHE
2X32T8/UNV ISH-SC
72273 GE-232-MV-L REL-2P32-LW-SC/VEL-2P32-LW-SC B232I120L-A/B232I277L-A
QTP 2X32T8/UNV ISL-SC/QHE
2X32T8/UNV ISL-SC EPL2/32IS-120-277
72275 GE-232-MV-N ICN-2P32-SC B232IUNVHP-B
QTP 2X32T8/UNV ISN-SC/QHE
2X32T8/UNV ISN-SC EP2/32IS-120-277
30199 GE-332-MV-H REL-3P32-HL-SC/VEL-3P32-HL-SC B332I120RHH-A/B332I277RHH-A
QTP 3X32T8/UNV ISH-SC/QHE
3X32T8/UNV ISH-SC
30255 GE-332-MV-L REL-3P32-LW-SC/VEL-3P32-LW-SC B332I120L-A/B332I277L-A
QTP 3X32T8/UNV ISL-SC/QHE
3X32T8/UNV ISL-SC EPL3/32IS-120-277
30192 GE-332-MV-N ICN-3P32-SC B332IUNVHP-B
QTP 3X32T8/UNV ISN-SC/QHE
3X32T8/UNV ISN-SC EP3/32IS-120-277
30219 GE-432-MV-H REL-4P32-HL-SC/VEL-4P32-HL-SC B432I120RHH-A/B432I277RHH-A QHE 4X32T8/UNV ISH-SC
30262 GE-432-MV-L REL-4P32-LW-SC/VEL-4P32-LW-SC B432I120L-A/B432I277L-A
QTP 4X32T8/UNV ISL-SC/QHE
4X32T8/UNV ISL-SC EPL4/32IS-120-277
30193 GE-432-MV-N ICN-4P32-SC B432IUNVHP-B
QTP 4X32T8/UNV ISN-SC/QHE
4X32T8/UNV ISN-SC EP4/32IS-120-277
30195 GE-159-MV-N
30194 GE-259-MV-N RCN-2P59/VCN-2P59 B259IUNVHP-B
QTP 2X59T8/UNV ISN-SC/QHE
2X59T8/UNV-ISN-SC
ProLine® T8 Multivolt High Output 120V - 277V
30176 GE-286-HO-MV-N RCN-2S86 B259I120RHH/B259I277RHH
QHE 2X86T8HO/UNV-PSN-HT-
SCL/QHE2X59T8/UNV-ISH
ProLine® T8 Instant Start High-Performance
23680 GE-132-120-N RCN-1P32-SC B132I120RH-A QT1X32T8/120/ISN-SC
23681 GE-132-277-N VCN-1P32-SC B132I277RH-A QT1X32T8/277/ISN-SC
23671 GE-232-120-N RCN-2P32-SC B232I120RH-A QT2X32T8/120/ISN-SC
23672 GE-232-277-N VCN-2P32-SC B232I277RH-A QT2X32T8/277/ISN-SC
23673 GE-332-120-N RCN-3P32-SC B332I120RH-A QT3X32T8/120/ISN-SC
23674 GE-332-277-N VCN-3P32-SC B332I277RH-A QT3X32T8/277/ISN-SC
23675 GE-432-120-N RCN-4P32-SC B432I120RH-A QT4X32T8/120/ISN-SC
23676 GE-432-277-N VCN-4P32-SC B4132I277RH-A QT4X32T8/277/ISN-SC
23677 GE-259-120-N RCN-2P59 QT2X59/120IS
23678 GE-259-277-N VCN-2P59 QT2X59/277IS
Residential Grade ProLine® T8 120V
97782 GE232-120-RES REB232-SC B232I120RES-A
97783 GE432-120-RES REB4P32-SC B432I120RES-A
Electromagnetic T8 Ballasts
87125 GEM232T8RS120 R-2P32-TP M232SR120C
87130 GEM232T8RS277 V-2P32-TP M232SR277C
T8 PROGRAM START BALLASTS
UltraStart® T8 Program Rapid Start
29621 GE-232-120-PS-N RCN-2S32-SC
29622 GE-232-277-PS-N VCN-2S32-SC
96714 GE232-MVPS-N IOP-2S32-SC B232PUNVHP-A QTP 2X32T8/UNVPSN-TC
96720 GE232-MVPS-L IOP-2S32-LW-SC QTP 2X32T8/UNV PSX-TC
29675 GE-232-MVPS-H N/A QHE2x32T8/UNV-PSH-HT
29671 GE-232-MVPS-XL N/A
29623 GE-332-120-PS-N RCN-3S32-SC
29624 GE-332-277-PS-N VCN-3S32-SC
29676 GE-332-MVPS-H IOP-3S32-SC
96715 GE332-MVPS-N IOP-3S32-SC B332PUNVHP-A QTP 3X32T8/UNVPSN-SC
Prod
Code Description Advance P/N Universal P/N OSI P/N Howard P/N
T8 Fluorescent Ballasts
96721 GE332-MVPS-L IOP-3S32-LW-SC QTP 3X32T8/UNV PSX-SC
29672 GE-332-MVPS-XL N/A QHE3x32T8/UNV-PSH-HT
29625 GE-432-120-PS-N RCN-4S32-SC
29627 GE-432-277-PS-N VCN-4S32-SC
96716 GE432-MVPS-N IOP-4S32-SC B432PUNVHP-A QTP 4X32T8/UNVPSN-SC
71832 GE432-MVPS-L IOP-4S32-LW-SC QTP 4X32T8/UNV PSX-SC
29678 GE-432-MVPS-H QHE4x32T8/UNV-PSH-HT
T8 Dimming
80353 B132R120V5 RZT-132 B132R120V5
80355 B232SR120V5 RZT-2S32 B232SR120V5
80362 B232SR277S50 VZT-2S32 B232SR277S50
80356 B232SR277V5 VZT-2S32 B232SR277V5
80357 B332SR120V5 RZT-3S32 B332SR120V5
80358 B332SR277V5 VZT-3S32 B332SR277V5
T5 Fluorescent Ballasts
T5 ELECTRONIC PROGRAMMED START BALLASTS
UltraStart® T5 Programmed Rapid Start
99653 GE228MVPSH-A B228PUNV115-D QTP2X28T5/UNVPSN NL
99655 GE228MVPS-A B228PUNV95-D
47536 B228PUNV-C0G1C ICN-2S28 B228PUNV-C
47534 B224PUNV-COG1C ICN-2S24 B224PUNV-D QTP2X39-24T5HO/UNVPSN NL
47540 B239PUNV-DOG1C ICN-2S39 B239PUNV-D QTP2X39-24T5HO/UNVPSN NL
99651 GE254MVPS90-F ICN-2S54-90C B254PUNV-D QTP 2X54T5HO/UNV PSN HT EP2/54HO/PRS/MV/90C
47542 B254PUNV-DGE1C ICN-2S54 B254PUNV-D
72279 GE254MVPS-D QTP2X54T5HO/UNVPSN NL EP2/54HO/PRS/120-277
99649 GE454MVPS90-E ICN4S5490C2LSG B454PUNV-E
QTP 4X54T5HO/UNV PSN HTW
NL
29726 GE454MVPSN1 ICN4S5490C2LS QTP 4X54T5HO/UNV PSN HT
72280 GE180MVPS-D QTP1X80T5HO/UNVPSN NL
T12 Fluorescent Ballasts
T12 ELECTRONIC BALLASTS
ProLine® T12 Multivolt 120V - 277V
24107 GE-240-RS-MV-N R-140-TP B240R120HP/B240R277HP
97498 GE240RS120 REL-2S40-SC/RELB-2S40-SC B234SR120M-A QTP2X40T12/120RSN-SC
72110 GE140RS120-DIY REL-1S40-SC B134SR120M-A QTP1X40T12/120/277RSN-SC
24109 GE-340-RS-MV-N R-3S34-TP B340R120HP/B340R277HP QTP3X40T12/120/277RSN
24108 GE-260-IS-MV-N R2E75STP B260IUNVHP QT2x96/120IS/QT2x96/277IS
80162 B295SR120HP REL-2P60-S-A/REL-2S110 B295SR120HP QT2x96/120HO
80163 B295SR277HP VEL-2P75-S/VEL-2S110 B295SR277HP QT2x96/277HO
72109 GE296HO-MV-N B295SRUNVHP
T12 MAGNETIC BALLASTS
89711 GEM120PH120DIY LC-14-20-C-TP 200H2
89712 GEM120TC120DIY RLQ-120-TP 546BTCP
89720 GEM1FC16T9RS120 RMS-3240-TP-W 726VLHWSTCP
86227 GEM1FC8T9RS120IP RLQS-122-TP-W 547RSWSTCP
89717 GEM1FC12T9RS120 RS-22-32-TP-W 449LRWSTCP
80819 GEM220TS120DIY RS-2SP20-TP 447LRVLHTCP
89714 GEM140HRS120DIY R-140-TP 412LSLHTCP
89709 GEM140RS120DIY RL-140-TP 413CTCP
80644 GEM230RS120 RM-2SP30-TP 573LTCP
89710 GEM240HRS120DIY RK-2S34-TP 420LTCP
86139 GEM240RS120IP R-2P840-TP 446LSLHTCP
86124 GEM240RS277IP V2S40TP 443LSLHTCP
86341 GEM240RS220 MTM-2S40-TP 754LTCP
86372 GEM196IS120IP RSM175STP 822BRTCP
86381 GEM196IS277 VSM175STP 828BRTCP
86360 GEM296IS120IP R2E75STP 806SLHTCP
86379 GEM296IS277IP V2E75STP 827SLHTCP
86164 GEM296HORS120IP R-2S110-TP 480SLHTCP
86171 GEM296HORS277 V-2S110-TP 487SLHTCP
Sign Ballasts
72103 GESB-0412-12-IP ASB-0412-12-BL-TP USB-0412-12-IP
72104 GESB-0620-24-IP ASB-0620-24-BL-TP USB-0816-14-IP
72105 GESB-1224-24-IP ASB-1224-24-BL-TP USB-1024-14-IP
72106 GESB-1240-46-IP ASB-1240-46-BL-TP USB-2036-46-IP
72107 GESB-2040-46-IP ASB-2040-24-BL-TP USB-1632-24-IP
72108 GESB-2448-46-IP ASB-2448-46-BL-TP USB-2048-46-IP
192
Ballast cross reference matrix (cont.)
See page 195 for warranty information. 193
Quick Reference
Guides
T8
Fluorescent Ballasts
T5
Fluorescent Ballasts
T12
Fluorescent Ballasts
Sign
Ballasts
Compact Fluorescent
Ballasts
HID Electronic
Ballasts
HID Electromagnetic
Ballasts
gelighting.com
See page 195 for warranty information.
Prod
Code Description Advance P/N Universal P/N OSI P/N Robertson P/N
Compact Fluorescent Ballasts
CFL ELECTRONIC
71428 GEC213-MVPS-BES ICF-2S13-BE C213UNVBS QTP1/2X13CF/UNVBS PSM213CQMVBS
71429 GEC213-MVPS-SE ICF-2S13-LD C213UNVBES QTP1/2X13CF/UNVTS PSM213CQMV
71430 GEC213-MVPS-3W C213UNVME00K QTP 1/2x13CF/UNV
71432 GEC218-MVPS-BES ICF-2S18-BE C218UNVBS QTP1/2X18CF/UNVBS PSM218CQMVBS
71433 GEC218-MVPS-SE ICF-2S18-LD C218UNVBES QTP1/2X18CF/UNVTS PSM218CQMV
71434 GEC218-MVPS-3W C218UNVME000K QTP 1/2x18CF/UNV
71443 GEC226-MVPS-BES ICF-2S26-BS C2642UNVBES-IP QTP2X26CF/UNVBS PSG242TRMVBS
71444 GEC226-MVPS-SE ICF-2S26-LD C2642UNVSE-IP QTP2X26CF/UNVTS PSG242TRMV
71445 GEC226-MVPS-3W QTP 1/2x26CF/UNV
47506 C242UNVBES-IP IZT-2S42-M2-BS C2642UNVBE QTP2X26/32/42CF/UNVPM PSG242TRMVBS
47509 C242UNVSE-IP IZT-2S42-M2-LS C2642UNVSE QTP2X26/32/42CF/UNVTM PSG242TRMV
80683 C240PUNVHP-B-IP REL-2TTS40 C240PUNVHP-B-IP QTP2X40TT5/120/277PSN-F
80680 C240SI120RH-IP RCN-2TTP40-SC C240SI120RH-IP QHE2X40DL/UNV ISN-SC
80681 C240SI277RH-IP VCN-2TTP40-SC C240SI277RH-IP QHE2X40DL/UNV ISN-SC
80690 C340SI120RH-IP RCN-3TTP40-SC C340SI120RH-IP QHE3X40DL/UNV ISN-SC
80691 C340SI277RH-IP VCN-3TTP40-SC C340SI277RH-IP QHE3X40DL/UNV ISN-SC
87634 GEM1CF579PH277 VL-1B9-TP-W 4205F2P
87533 GEM1CF13PH120 LC-13-TP 4111H2P
87655 GEM2CF13PH277 VH-2B13-TP-BLS 4214PBES
87700 GEM2CF24PH277 VH-2Q26-TP-BLS 4226PBES
87623 GEM2FT36RS120 R-2BS39-TP 4150P
87625 GEM2FT40RS120 R-2BS40-TP 4152P
Prod
Code Description Advance P/N Universal P/N OSI P/N AROMAT/VS P/N
HID Electronic Ballasts
87490 GEMH20-MLF-120 RMH-20-E ECN20-120 QTP1X20MH/UNV F M2012-27CK-5EUF
87501 GEMH39-MSF-120 RMH-39-K ECN39-120 QTP1X39MH/UNV F M3912-27CK-5EUF
87516 GEMH50-MSF-120
87531 GEMH70-MSF-120 IMH-70-G ECN70-120 QTP1X70MH/UNV F M7012-27CK-5EUF
87546 GEMH70-SLJ-MV IMG-70-G ECN70-UNV QTP1X70MH/UNV J M7012-27CK-5EUJ
87561 GEMH100-SLJ-MV IMG-100-A-BLS ECN100-UNV QTP1X100MH/UNV J M10012-27CK-5EUJ
87576 GEMH150-SLJ-MV IMG-150-H-BLS ECN150-UNV M15012-27CK-5EUN-J
29377 GE-MH-250-400-MA IZTEMH4003PS QHE1XxxxMH 208-277V
89646 GEMH250-400M-V50 EPXXXMRVASE
HID Electromagnetic Ballasts
Metal Halide
86824 GEM50MLTLC3D-5 71A5181-500D M50MLTLC3M500K
86847 GEM70MLTLC3D-5 71A5280-500D M70MLTLC3M500K
86839 GEM7048TLC3D-5 M7048TLC3M500K
86675 GEM100MLTLC3D-5 71A5390-001D M100MLTLC3M500K
86667 GEM10048TLC3D-5 71A5340-500DT M10048TLC3M500K
86718 GEM150MLTLC3D-5 71A5492-500D M150MLTLC3M500K
86711 GEM15048TLC3D-5 71A5442-500DT M15048TLC3M500K
87210 GEM175ML5AC3-5 71A3042-001D M175ML5AC3M500K
86741 GEM175MLTAC3-5 71A5570-001D M175MLTAC3M500K
87211 GEM250ML5AC3-5 71A5750-001D M250ML5AC3M500K
86765 GEM250MLTAC3-5 71A3542-001D M250MLTAC3M500K
87212 GEM250ML5AC4-5 71A5750 M250ML5AC4M500K
72300 GEM400ML5AA4-5 71A6051-001D M400ML5AC4M500K
72149 GEM400MLTAA4-5 71A6071-001D M400MLTAC4M500K
86803 GEM40048TAC4-5 71A6042-500DT M40048TAC4M500K
86650 GEM100048TAC5-5 71A6542-001 M100048TAC5M500K
87213 GEM1000ML5AA5-5 71A6552-001 M1000ML5AC5M500K
86655 GEM1000MLTAA5-5 71A6572-001 M1000MLTAC5M500K
86693 GEM150048TAC5-5 71A6742-001 M150048TAC5M500K
86698 GEM1500MLTAC5-5 71A6772-001 M1500MLTAC5M500K
Pulse Start
86885 GEP175MLTAC3-5 71A5593-001D P175MLTAC3M500K
86876 GEP17548TAC3-5 71A5543-500DT P17548TAC3M500K
86935 GEP250MLTAC4-5 71A5792-001D P250MLTAC4M500K
86926 GEP25048TAC4-5 71A5742-500DT P25048TAC4M500K
86959 GEP320MLTAC4-5 71A5892-001D P320MLTAC4M500K
86952 GEP32048TAC4-5 71A5842-500DT P32048TAC4M500K
86968 GEP320TRIAC4-5 71A5837-001D P320TRIAC4M502K
86984 GEP350MLTAC4-5 71A5993-001D P350MLTAC4M500K
86999 GEP40048TAC4-5 71A6042-500DT P40048TAC4M500K
87008 GEP400MLTAC4-5 71A6092-001D P400MLTAC4M500K
46936 GEP75048TAC5-5 71A64F2-500DT P75048TAC5M500K
46934 GEP750MLTAC5-5 71A64E2-500D P750MLTAC5M500K
72281 GEP1000MLTAC5-5 71A6593-500 P1000MLTAC5M500K
72282 GEP1000ML5AC5-5 71A6553-500 P1000ML5AC5M500K
Prod
Code Description Advance P/N Universal P/N OSI P/N AROMAT/VS P/N
HID Electromagnetic Ballasts
High Pressure Sodium
87152 GES50MLTLC3D-5 71A7801-001D S50MLTLC3M500K
86587 GES70MLTLC3D-5 71A7971-001D S70MLTLC3M500K
86456 GES7048TLC3D-5 71A7941-001D S7048TLC3M500K
87074 GES100MLTLC3D-5 71A8001-001D S100MLTLC3M500K
87068 GES10048TLC3D-5 71A8041-001D S10048TLC3M500K
87094 GES150MLTLC3D-5 71A8172-001D S150MLTLC3M500K
87087 GES15048TLC3D-5 71A8142-001D S15048TLC3M500K
87214 GES250ML5AC4-5 71A8251-001D S250ML5AC4M500K
87121 GES250MLTAC4-5 71A8271-001D S250MLTAC4M500K
87215 GES400ML5AC4-5 71A8453-001D S400ML5AC4M500K
87164 GES400MLTAC4-5 71A8473-001D S400MLTAC4M500K
87198 GES40048TAC4-5 71A8443-001D S40048TAC4M500K
87048 GES100048TAC5-5 71A8743-001 S100048TAC5M500K
87218 GES1000ML5AC5-5 71A8753-001 S1000ML5AC5M500K
87056 GES1000MLTAC5-5 71A8773-001 S1000MLTAC5M500K
HID Lamp-Ballast Kits
71701 GEM175ML5AC3-55
71702 GEM250ML5AC3-55
71703 GEM400ML5AC4-55
71704 GEM1000ML5AC4-55
71705 GES100MLTLC3D-55
71706 GES250ML5AC4-55
71707 GES400ML5AC4-55
F-Can & Post Mount Metal Halide
86576 11210277CTC000C 72C5280-NP 11210277CTC000C
86578 11210506CTC000C 72C5282-NP 11210506CTC000C
86574 11210239CTC000I 72C5381-NP 11210239CTC000I
86563 1110245SCTC000I 72C5581-NP 1110245SCTC000I
86564 1110246CTC000C 72C5782-NP 1110246CTC000C
42670 1110-247SC-TC 72C6082-NP 1110-247SC-TC
80728 1111-247SCTC000I 72C6082-NP 1111-247SCTC000I
F-Can & Post Mount HPS
86605 1233142U000I 71A7907-001DB 1233142U000I
86596 12210237CTC000I 72C7984-NP 12210237CTC000I
86606 1233154U000I 71A8107-001DB 1233154U000I

Navigation menu