BRANCH PANEL MOUNTED SURGE PROTECTIVE DEVICE (SPD)
Cat. Nos. 51120-1	&	51120-3

DI-000-51120-00E

INSTALLATION
WARNINGS & CAUTIONS:
•	
•	
•	
•	

TO	BE	INSTALLED	AND/OR	USED	IN	ACCORDANCE	WITH	ELECTRICAL	CODES	AND	REGULATIONS.
INSTALLATION	OF	CAT.	NOS.	51120-1	AND	51120-3	SPD	DEVICES	IN	A	BRANCH	CIRCUIT	MUST	BE	DONE	BY	AN	ELECTRICIAN.
READ	ALL	INSTRUCTIONS	BEFORE	INSTALLING.
CAT.	NOS.	51120-1	AND	51120-3	SPD	DEVICES	MUST	BE	INSTALLED	ON	A	LINE	THAT	IS	SERVED	BY	DISCONNECT	MEANS,	SUCH	AS	20-AMP	CIRCUIT	BREAKERS	OR	20-AMP	
FUSED	DISCONNECT	SWITCHES.
•	 SPD	MAY	NOT	SURVIVE	SUSTAINED	OVERVOLTAGES.
•	 USE	THIS	DEVICE	ONLY WITH COPPER OR COPPER CLAD WIRE.

FEATURES:
•	
•	
•	
•	
•	
•	
•	
•	
•	

UL	1449	Listed	-	Type	2	SPD
IEEE	C62.41-1991	category	A&B	combination	wave	suppression
Solid-state	semiconductor	SPD	circuitry	for	each	phase
Each	phase	independently	fused
Green	LED	diagnostic	indicator	for	each	phase
NEMA	1	metal	enclosure
Pre-punched	standard	knockouts
Interior	plastic	circuit	enclosure	for	added	safety
Flush	mounting	enclosure

For	superior	local	SPD	protection,	use	Leviton	Surge	Suppression	Outlets	to	protect	against	internally-generated	transients	between	the	branch	panel	and	the	point	of	use.

DESCRIPTION:

Leviton’s	Catalog	Nos.	51120-1	(120/240V,	single	-phase	version)	and	the	51120-3	(120/208V,	3-phase	version)	Branch	Panel	Mounted	SPD	devices	have	been	designed	to	protect	
residential	and	small	commercial	establishments	from	high	voltage	transients.	The	standard	J-Box	metal	enclosure	with	pre-punched	standard	size	knockouts	simplifies	flush	
mounting	in	typical	frame	construction	environments,	and	provides	convenient	connection	means	to	existing	branch	panels.

TO INSTALL:

System Voltage Requirements
1.	 Measure	panel	voltage,	L-N,	to	determine	the	system	voltage.	System	voltage	must	not	exceed	the	specified	maximum	continuous	RMS	voltage	on	the	SPD	device	label.
Location and Mounting
1.	 Locate	the	SPD	device	as	close	as	possible	to	the	branch	circuit	breaker	panel.	Connection	lead	length	between	the	SPD	device	and	circuit	breaker	box	should	be	minimal	for	
best	protection.	The	location	should	also	permit	good	visibility	of	the	SPD	device’s	diagnostic	lights.
2.	 Remove	the	circuit	breaker	panel	cover	and	determine	the	breaker-panel	wiring	entry	point	relative	to	chosen	location	of	the	SPD	device.
NOTE:	Since	the	circuit	breaker	panel	and	the	SPD	unit	have	overlapping	covers,	installation	should	allow	at	least	one	inch	of	clearance	from	the	edge	of	the	circuit	breaker	
panel	cover.
3.	 For	surface-mount	circuit	breaker	panels,	the	SPD	device	may	be	connected	using	rigid	conduit	to	any	conduit	knockout	hole.
4.	 For	non-surface	mount	installations,	secure	the	SPD	to	the	support	stud	in	the	wall	by	cutting	a	6	x	6-inch	mounting	hole.
5.	 Remove	SPD’s	cover	and	connect	3/4-inch	flexible	or	rigid	conduit	between	circuit	breaker	box	and	the	SPD.
6.	 Place	the	SPD	device	into	the	6	x	6-inch	mounting	hole	and	secure	it	to	the	exposed	studs.
Wiring Connections
The	SPD	device	terminal	block	accepts	4	AWG	–	12	AWG	COPPER	WIRE	ONLY.	For	wire	range	Solid	or	Stranded	12	AWG	to	10	AWG	use	Torque	25	in-lbs.	For	8	AWG	Stranded	
wire	use	30	in-lbs.	For	Stranded	6	AWG	–	4	AWG	use	35	in-lbs.

1.	 WARNING:	TO	AVOID	FIRE,	SHOCK	OR	DEATH,	TURN OFF POWER	AT	CIRCUIT	BREAKER	OR	FUSE	AND	TEST	THAT	POWER	IS	OFF	BEFORE	WIRING!
2.	 Connect	wire	leads	to	terminal	block:	BLACK	to	PHASES,	WHITE	to	NEUTRAL	and	GREEN	to	GROUND.	See	Figures 1	through	4	on	reverse	side.
CAUTION:	If	plastic	conduit	is	used,	Green	ground	wire	must	be	connected	to	ground	lug,	and	Green	wire	inside	enclosure	must	also	be	connected	to	ground	lug.	Failure	to	do	
so	may	result	in	fire	or	shock.	See	Fig. 1,	Fig. 2,	Fig. 3	and	Fig. 4	on	reverse	side	for	installation	diagrams.
3.	 Thread	the	SPD	device’s	wire	leads	through	the	conduit	to	circuit	breaker	interior.
4.	 Secure	the	SPD	cover	with	the	screws	removed	previously.
5.	 Select	circuit	breakers	as	close	as	possible	to	each	service	entrance	lug.	Twenty-Amp	(20A)	circuit	breakers	are	recommended,	and	may	share	SPD	device	and	branch	circuit	
leads.	The	breakers	provide	additional	failure	protection	as	well	as	a	SPD	connection	and	servicing	disconnect.
NOTE:	Do	not	connect	SPD	leads	directly	to	service	entrance	lugs.	This	may	result	in	fire,	shock	or	death.
6.	 Lead	lengths	should	be	as	short	as	possible.	Connect	the	BLACK	leads	to	each	PHASE	through	the	selected	circuit	breakers.	Connect	the	WHITE	lead	to	NEUTRAL	as	close	as	
possible	to	NEUTRAL	entrance	service	lug.
NOTE: Avoid	long	loops	and	do	not	coil	extra	lead	wire.
7.	 Replace	the	circuit	breaker	panel	cover.	Installation	is	complete.
Power ON
1.	 Restore	power	to	circuit	breaker	panel.	The	green	diagnostic	lights	on	the	SPD	device	should	turn	ON.
2.	 If	during	normal	operation	a	diagnostic	light	shuts	off,	have	an	electrician	determine	if	phase	power	is	applied.	If	power	is	present,	then	a	transient	surge	has	exceeded	the	SPD	
device’s	rating.	The	unit	should	be	replaced	and/or	upgraded	as	soon	as	possible.

FIGURE 2 - THREE-PHASE INSTALLATION

FIGURE 1 - SINGLE-PHASE INSTALLATION

L1

L1
120 V

L2

N

208 V 208 V
120 V

208 V

120 V 240 V

L2

51120-1
120/240 V
1Ø

Suitable for use on a circuit capable of delivering no more than 10,000
rms symmetrical amperes, 120 volts maximum when protected by a 20
ampere circuit breaker rated 120 volts minimum. The interrupting rating of
the fuse or circuit breaker shall not be less than the available fault current.

L3
120 V

Suitable for use on a circuit capable of delivering no more than 10,000
rms symmetrical amperes, 120 volts maximum when protected by a 20
ampere circuit breaker rated 120 volts minimum. The interrupting rating of
the fuse or circuit breaker shall not be less than the available fault current.

FIGURE 4 - THREE-PHASE WIRING

Flexible Conduit
to J-Box

51120-1

51120-3

Circuit Breaker Panel
(Cover Removed)

G
L1
L2

20

20

20

20

20
20
40

N

51120-3
120/208 V
3Ø

N

FIGURE 3 - SINGLE-PHASE WIRING

Flexible Conduit
to J-Box

120 V

Circuit Breaker Panel
(Cover Removed)

G
L1

20

L2
L3

20
40

20

20

20

20

20
20
40

N

20
20
40

LIMITED LIFETIME WARRANTY AND EXCLUSIONS
Leviton	 warrants	 to	 the	 original	 consumer	 purchaser	 and	 not	 for	 the	 benefit	 of anyone	 else	 that	 this	 product	 at	 the	 time	 of	 its	 sale	 by	 Leviton	 is	 free	 of	 defects	 in	 materials	 and	 workmanship	 under	
normal	 and	 proper	 use	 during	 the	 lifetime	 of	 the	 product.	 Leviton’s	 only	 obligation	 is	 to	 correct	 such	 defects	 by	 repair	 or	 replacement,	 at	 its	 option,	 if	 the	 product	 is	 returned	 prepaid,	 with	 proof	 of	
purchase	 date,	 and	 a	 description	 of	 the	 problem	 to	 Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, N.Y. 11747.	This	 warranty	 excludes	 and	
there	 is	 disclaimed	 liability	 for	 labor	 for	 removal	 of	 this	 product	 or	 reinstallation.	 This	 warranty	 is	 void	 if	 this	 product	 is	 installed	 improperly	 or	 in	 an	 improper	 environment,	 overloaded,	 misused,	 opened,	
abused,	 or	 altered	 in	 any	 manner,	 or	 is	 not	 used	 under	 normal	 operating	 conditions	 or	 not	 in	 accordance	 with	 any	 labels	 or	 instructions.	 There	 are	 no	 other	 or	 implied	 warranties	 of	 any	 kind,	 including	
merchantability	and	fitness	for	a	particular	purpose.	Leviton	is	not	liable	for	incidental,	indirect,	special,	or	consequential	damages,	including	without	limitation,	damage	to,	or	loss	of	use	of,	any	equipment,	
lost	 sales	 or	 profits	 or	 delay	 or	 failure	 to	 perform	 this	 warranty	 obligation.	 The	 remedies	 provided	 herein	 are	 the	 exclusive	 remedies	 under	 this	 warranty,	 whether	 based	 on	 contract,	 tort	 or	 otherwise.
For Technical Assistance Call:
1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only)
www.leviton.com

©	2010	Leviton	Mfg.	Co.,	Inc.

DI-000-51120-00E

ARTWORK PRINT SPECIFICATIONS
PART NUMBER

DI-000-51120-00E

REV

DESCRIPTION

Instruction sheet

SPECIFICATIONS :
Dimensions: 11" x 8.5"

Color(s):

Thickness: 20 lb.

1

over

Fonts:

1

1: Black

Material: Offset
Finish:

3:

:

1: Helvetica

Spot

2:

2:
3:

CMYK

4:

4:

For manuals - designates cover specifications

MANUAL INTERIORS / BINDERY / FOLD SCHEME :
Color(s):

Body Material:

over

Fonts:

1:

Thickness:

2:

Bindery
Die cut

Fold

Saddle Stitch

Perfect Bind

Drill

Trim

1:

Spot

3:

2:
3:

CMYK

4:

4:

FOLD SCHEME / BINDERY DIAGRAM

PROCESS :

8.5"

Offset

8.5"

Part No.

Flexo

Part No.

Other

5.5"

11"

Line Screen:
FINAL

Angle:
Resolution:
Die Cut

Punch/Drill Hole

Fold Line

COMMENTS :

The information in this document is the exclusive PROPRIETARY property of LEVITON MANUFACTURING COMPANY, INC. It is disclosed
with the understanding that acceptance or review by the recipient constitues an undertaking by the recipient. (1) to hold this information in strict
confidence, and (2) not to disclose, duplicate, copy, modify or use the information for any pupose other than that for which disclosed.

© 2010 Leviton Mfg. Co., Inc.
Unpublished, All Rights Reserved

FOR LEVITON USE ONLY
Approvals:

PN-ARN:
Artist:

Plant 01

CQA J. Rhinestine

PM

Mktg

Eng

S&A

Cust

Other

CI0054-3154
H Sanchez

C. Clemente

C. Corona

ECO Number:

T. Pulsonetti

Other

V. Lonigro

Pilot Rev:
Artwork Release Date:

10/13/10

Notes:
Artwork Print Specification Sheet Rev A06.eps



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Tagged PDF                      : No
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03
Format                          : application/pdf
Title                           : Leviton 51120-1 Surge Protector Installation Instructions
Title (x-repair)                : Leviton 51120-1 Surge Protector Installation Instructions
Description                     : Buy Leviton 51120-1 AC Surge Protectors at low prices from 1000Bulbs.com!
Description (x-repair)          : Buy Leviton 51120-1 AC Surge Protectors at low prices from 1000Bulbs.com!
Creator                         : 1000Bulbs.com
Subject                         : surge protectors, surge protection, panel mounted, 7847782764, leviton 51120-1, nema 1, spd, leviton surge protector, residential surge protectors, panel surge protector
Producer                        : Adobe PDF Library 9.0; modified using iTextSharp 4.1.6 by 1T3XT
Keywords                        : surge protectors; surge protection; panel mounted; 7847782764; leviton 51120-1; nema 1; spd; leviton surge protector; residential surge protectors; panel surge protector
Trapped                         : Unknown
Create Date                     : 2010:10:13 10:36:32-04:00
Creator Tool                    : Adobe InDesign CS4 (6.0)
Modify Date                     : 2013:11:19 14:56:39-06:00
Metadata Date                   : 2013:11:19 14:56:39-06:00
Document ID                     : uuid:5434b4c6-8874-486e-8158-7de9e9612bfe
Instance ID                     : uuid:2fb3572f-147a-4067-941e-c6e729dc4767
Page Count                      : 3
Author                          : 1000Bulbs.com
EXIF Metadata provided by EXIF.tools

Navigation menu