Decorative Emergency Lighting
6 Volt, 11 Watts & 6 Volt, 17 Watt
Maintenance Free, Sealed Lead
Calcium Battery
Shown: FL2OT
Electronics
120/277 VAC dual voltage input with surge-protection
Solid-state charging circuitry provides for a reliable charging system
Brownout protection activates lights when AC voltage drops 20%
below nominal
AC indicator lamp and test switch
Low voltage disconnect feature (LVD) prevents deep battery
discharge
Self-Testing Diagnostics (Optional)
Continuously monitors the critical functions of the equipment,
including: battery disconnect, battery failure, charger failure,
transformer failure and lamp failure
Self-Testing routine performs a one-minute test every 30 days, a
30-minute test on the 6th month and a 90-minute test annually
Code Compliance
UL 924 listed
UL damp location listed standard 68°F (20°C) to 104°F (40°C)
NFPA 101, NEC, BOCA, OSHA, and IBC illumination standards
Application
• Corridors
• Open Plan Office Areas
School Hallways, Lunch Rooms
Hotel, Retail and General Commercial Construction
Housing
Constructed of impact resistant, UL 94 V-O, 5 VA thermoplastic,
completely self contained
White housing is standard, with an optional black housing available
The FL3 offers the option of 6 W remote capability
Battery
Maintenance free, sealed lead calcium battery has an expected
service life of 5 years with an operating range of 68°F (20°C) to
104°F (40°C)*
Battery supplies 90 minutes of emergency power
* Increases or decreases in temperature will affect battery
performance and/or capacity. Optimum battery performance
realized at 77°F (25°C)
Illumination
Illumination is provided by two fully adjustable polycarbonate
6 VDC, 5.4 W T-5 lamps
High impact acrylic refractors minimize glare and maximize optic
control
Warranty
Electronics: 3 years
Battery: 1 year full, 4 years pro-rata
Electrical Specifications
120 VAC: 60 Hz, 0.045 A
277 VAC: 60 Hz, 0.020 A
Type No.
Job Name
Catalog No.
LightGuard is a Philips company
FL2-FL3
FL2-FL3
L2323R11
1/12 IH
Suggested Specification
ALL SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Ordering Information
Dimensions
Furnish and install LightGuard decorative emergency lighting model _____________________________________. The unit shall be constructed to meet Underwriter’s Laboratories,
Inc. Standard #924 and must be installed to conform to Article 700 of the National Electrical Code (NEC).
INSTALLATION AND OPERATION - Unit shall be easily field connected to a 120 or 277 VAC, 60 Hz, unswitched power source. Installation must comply with the NEC as well as
other applicable codes. Upon utility power failure or brownout, the unit shall automatically provide emergency battery power and maintain the stated illumination level and output wattage
for a minimum period of 90 minutes. Upon restoration of utility power, the charging circuitry shall restore the battery to full charge within UL 924 requirements following a rated
discharge of not more than 90 minutes.The unit shall be damp location listed standard.
CHARGING CIRCUITRY - Unit shall utilize a solid-state, fully automatic, voltage regulated charging system which will maintain the battery at full capacity without the need for
periodic exercising or equalization.The following features shall be standard: low voltage disconnect (LVD), brownout protection and AC lockout.
BATTERY - The battery shall be maintenance free, sealed lead calcium with an optimum operating temperature range of 68°F (20°C) to 104°F (40°C). All normal gassing shall be
contained within the battery casing, and will not escape into the atmosphere. Gasses created during recharge cycles will recombine with existing electrolyte.The battery shall have a
recommended service life of 5 years when operated at optimum operating temperature.
ILLUMINATION - The product shall incorporate two fully adjustable lamp heads, witch include a parabolic reflector design and utilize a 6 VDC, 5.4 W T-5 wedge base tungsten lamp.The
lamp head lens shall be constructed of high impact, prismatic, UV stabilized acrylic, and will effectively control sight line glare.
HOUSING - The housing shall be constructed of impact resistant, UL 94 V-0, white thermoplastic, completely self-contained.
11.87”
(30.15 cm)
5.0”
(12.7 cm)
16.0”
(40.6 cm)
Dimensions are approximate and subject to change.
HOUSING
COLOR
Blank = White
B= Black
FACTORY INSTALLED
OPTIONS
OT = Self-Diagnostics
(available in white housing only)
SERIES
FL2 = 6 V, 11 W Emergency
Lighting Unit
FL3 = 6 V, 17 W Emergency
Lighting Unit With 6 W Remote
Capability
ACCESSORIES
(Ordered Separately)
WG5 = Wire Guard
272 West Stag Park Service Road • Burgaw, NC 28425
(910) 259-1131 • FAX (800) 403-6927
www.lightguard.com