Type No.
Job Name
Catalog No.

FL2-FL3
Shown: FL2OT

Decorative Emergency Lighting
6 Volt, 11 Watts & 6 Volt, 17 Watt
Maintenance Free, Sealed Lead
Calcium Battery

Housing
• Constructed of impact resistant, UL 94 V-O, 5 VA thermoplastic,
completely self contained
• White housing is standard, with an optional black housing available
• The FL3 offers the option of 6 W remote capability

Electronics
• 120/277 VAC dual voltage input with surge-protection
• Solid-state charging circuitry provides for a reliable charging system
• Brownout protection activates lights when AC voltage drops 20%
below nominal
• AC indicator lamp and test switch

Battery
• Maintenance free, sealed lead calcium battery has an expected
service life of 5 years with an operating range of 68°F (20°C) to
104°F (40°C)*
• Battery supplies 90 minutes of emergency power
* Increases or decreases in temperature will affect battery
performance and/or capacity. Optimum battery performance
realized at 77°F (25°C)

• Low voltage disconnect feature (LVD) prevents deep battery
discharge

Illumination
• Illumination is provided by two fully adjustable polycarbonate
6 VDC, 5.4 W T-5 lamps
• High impact acrylic refractors minimize glare and maximize optic
control
Warranty
• Electronics: 3 years
• Battery: 1 year full, 4 years pro-rata
Electrical Specifications
• 120 VAC: 60 Hz, 0.045 A
• 277 VAC: 60 Hz, 0.020 A

LightGuard is a Philips company

Self-Testing Diagnostics (Optional)
• Continuously monitors the critical functions of the equipment,
including: battery disconnect, battery failure, charger failure,
transformer failure and lamp failure
• Self-Testing routine performs a one-minute test every 30 days, a
30-minute test on the 6th month and a 90-minute test annually
Code Compliance
• UL 924 listed
• UL damp location listed standard 68°F (20°C) to 104°F (40°C)
• NFPA 101, NEC, BOCA, OSHA, and IBC illumination standards
Application
• Corridors
• Open Plan Office Areas
• School Hallways, Lunch Rooms
• Hotel, Retail and General Commercial Construction

FL2-FL3
Ordering Information

SERIES
FL2 = 6 V, 11 W Emergency
Lighting Unit
FL3 = 6 V, 17 W Emergency
Lighting Unit With 6 W Remote
Capability

Dimensions

HOUSING
COLOR

FACTORY INSTALLED
OPTIONS

ACCESSORIES
(Ordered Separately)

Blank = White
B = Black

OT = Self-Diagnostics
(available in white housing only)

WG5 = Wire Guard

16.0”
(40.6 cm)

5.0”
(12.7 cm)

11.87”
(30.15 cm)

Dimensions are approximate and subject to change.

Suggested Specification
Furnish and install LightGuard decorative emergency lighting model _____________________________________. The unit shall be constructed to meet Underwriter’s Laboratories,
Inc. Standard #924 and must be installed to conform to Article 700 of the National Electrical Code (NEC).
INSTALLATION AND OPERATION - Unit shall be easily field connected to a 120 or 277 VAC, 60 Hz, unswitched power source. Installation must comply with the NEC as well as
other applicable codes. Upon utility power failure or brownout, the unit shall automatically provide emergency battery power and maintain the stated illumination level and output wattage
for a minimum period of 90 minutes. Upon restoration of utility power, the charging circuitry shall restore the battery to full charge within UL 924 requirements following a rated
discharge of not more than 90 minutes.The unit shall be damp location listed standard.
CHARGING CIRCUITRY - Unit shall utilize a solid-state, fully automatic, voltage regulated charging system which will maintain the battery at full capacity without the need for
periodic exercising or equalization.The following features shall be standard: low voltage disconnect (LVD), brownout protection and AC lockout.
BATTERY - The battery shall be maintenance free, sealed lead calcium with an optimum operating temperature range of 68°F (20°C) to 104°F (40°C). All normal gassing shall be
contained within the battery casing, and will not escape into the atmosphere. Gasses created during recharge cycles will recombine with existing electrolyte.The battery shall have a
recommended service life of 5 years when operated at optimum operating temperature.
ILLUMINATION - The product shall incorporate two fully adjustable lamp heads, witch include a parabolic reflector design and utilize a 6 VDC, 5.4 W T-5 wedge base tungsten lamp.The
lamp head lens shall be constructed of high impact, prismatic, UV stabilized acrylic, and will effectively control sight line glare.
HOUSING - The housing shall be constructed of impact resistant, UL 94 V-0, white thermoplastic, completely self-contained.
ALL SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

272 West Stag Park Service Road • Burgaw, NC 28425
(910) 259-1131 • FAX (800) 403-6927
www.lightguard.com

L2323R11
1/12 IH



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0 (Windows)
Create Date                     : 2009:06:03 15:25:30-04:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2012:02:23 15:24:38-05:00
Metadata Date                   : 2012:02:23 15:24:38-05:00
Format                          : application/pdf
Title                           : fl2-fl3 l2323.qxp
Creator                         : KNarusewicz
Document ID                     : uuid:8579bb82-d327-490a-91d6-9fe7328b9916
Instance ID                     : uuid:6d9bec23-b149-40d7-9c1f-f7f1867a4beb
Has XFA                         : No
Page Count                      : 2
Author                          : KNarusewicz
EXIF Metadata provided by EXIF.tools

Navigation menu