Riser Rated Belden 8471 Cable
LX SERIES NETWORKED LIGHTING CONTROLS

PROJECT INFORMATION
Project Name						
Catalog No.						Date

PVC Jacket
(Unsheilded)

Hubbell Controls' LX network cable is used to interconnect LX Panels, LX Devices
and LX Accessories for a complete communications network. All devices that
communicate on the LX Network are connected with the same type of twisted
pair cable. Both power and data are carried over the same two wires. The LX
System is wired as a topology-free, polarity-insensitive network. Hubbell Controls
supplied LX Network Cables assure proper network communications and should
be specified and installed on all LX System projects.

BELDEN 8471

Twisted Pair #16 Tinned Copper Conductors, PVC Insulation

PRODUCT FEATURES
•	
•	
•	
•	
•	
•	
•	
•	
•	
•	

	
	
	
	
	
	
	
	
	
	

Interconnects LX Lighting Control Panels and LX network devices
Cable carries both power and data in a single twisted pair
Belden #8471 - twisted pair #16 tinned copper
Single cable type connects to all types of LX network devices
Echelon Guideline Compliant for LON networks
Available in 100 ft and 500 ft reels
Riser Rated
Connects to terminal blocks or with twist on connectors
UL and cUL Listed
One-year limited warranty

LX SYSTEM NETWORK CABLE REQUIREMENTS
Hubbell Controls' LX Lighting Control System requires the use of Belden #8471 cable for Riser Rated applications OR Windy City Wire
#104500 for Plenum Rated applications. These are the ONLY cables that can be used for network wiring with the LX System.
The use of substitute cables based on similar physical characteristics is not allowed and will VOID any warranty for the LX system or any
LX component connected to the substitute cable.

General Specifications
Description 		
		

1 pair - 16 AWG stranded tinned copper conductors, 					
PVC Insulation, unshielded twisted pair (UTP), PVC jacket

Shielding		Unshielded
Overall Nominal Diameter	

	

0.274 inches

Plenum Rating 		

Not Plenum Rated

Operating Temperature Range 	

-20°C to +80°C (Indoor use only)

	

Maximum Pulling Tension 		

61 lbs

Minimum Bend Radius	

5.1 inches

	

Color 		

Pair Color - Black/White, Outer Jacket - Gray

Certifications 		

NEC (UL) CMG, CEC/C (UL) CMG,

Flame Test		
		

UL Flame Test – UL1685 FT4 Loading,
C (UL) Flame Test FT4

Warranty 		

One-year limited

Ordering Information

LX8471CBL100*
LX8471CBL500*

MODEL
LX Cable Belden 8471 Riser Rated 100 ft Reel
LX Cable Belden 8471 Riser Rated 500 ft Reel

*All sales are final, no returns are allowed.

INSTALLATION NOTES
1.	

DO NOT exceed 1500 feet of cable OR connect more than 56 devices per network segment.

2.	
	

Each network segment using LP style devices requires an LXLPM2 Link Power Module for device power. Each additional segment requires
an additional LXLPM2 Link Power Module and an LXRRM Repeater for data transmission between segments.

3.	

Each network segment existing of panels only or that use FT style devices only require termination with LXTERMINATOR instead of LXLPM2 Link Power Module.

4.	

Run cable and connect network with the shortest distances possible. The most efficient network is wired similar to branch circuit outlets.

5.	

When using twist-on wire connectors with network cable use no more than three wires per connector.

6.	

The use of T-taps to minimize cable length is encouraged. Daisy chain topology is allowed, but most often increases overall cable length.

7.	
	

DO NOT homerun all devices individually, or leave spare cable at ceiling mounted devices. If devices need to be relocated, cables can be extended with
twist-on wire connectors.

8.	

DO NOT mix plenum and NON-plenum cables on the same segment.

9. 	

Keep 12” minimum from line voltage, do nut run in the same raceway with line voltage.

9601 Dessau Road | Building One | Austin, Texas 78754 | 512-450-1100 | 512-450-1215 fax | www.hubbell-automation.com

	

3119A 2.4.2016



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.6-c111 79.158366, 2015/09/25-01:12:00
Create Date                     : 2016:02:04 11:21:32-06:00
Metadata Date                   : 2016:02:04 11:21:36-06:00
Modify Date                     : 2016:02:04 11:21:36-06:00
Creator Tool                    : Adobe InDesign CC 2015 (Windows)
Instance ID                     : uuid:52285229-989d-44f9-8f91-dc6786f17a26
Original Document ID            : adobe:docid:indd:cfbfb411-e39d-11e0-8667-d1d86aa20b67
Document ID                     : xmp.id:4d10be41-bff6-0241-830b-21738dc4fb80
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:4b812f25-7584-7d4a-9651-e96557fd80d9
Derived From Document ID        : xmp.did:4050B8E20982E3119529CDFDE2FCEF68
Derived From Original Document ID: adobe:docid:indd:cfbfb411-e39d-11e0-8667-d1d86aa20b67
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CC 2015 (Windows)
History Changed                 : /
History When                    : 2016:02:04 11:21:32-06:00
Format                          : application/pdf
Producer                        : Adobe PDF Library 15.0
Trapped                         : False
Page Count                      : 2
Creator                         : Adobe InDesign CC 2015 (Windows)
EXIF Metadata provided by EXIF.tools

Navigation menu