LX SYSTEM NETWORK CABLE REQUIREMENTS
Hubbell Controls' LX Lighting Control System requires the use of Belden #8471 cable for Riser Rated applications OR Windy City Wire
#104500 for Plenum Rated applications. These are the ONLY cables that can be used for network wiring with the LX System.
The use of substitute cables based on similar physical characteristics is not allowed and will VOID any warranty for the LX system or any
LX component connected to the substitute cable.
Riser Rated Belden 8471 Cable
LX SERIES NETWORKED LIGHTING CONTROLS
PROJECT INFORMATION
Project Name
Catalog No. Date
Hubbell Controls' LX network cable is used to interconnect LX Panels, LX Devices
and LX Accessories for a complete communications network. All devices that
communicate on the LX Network are connected with the same type of twisted
pair cable. Both power and data are carried over the same two wires. The LX
System is wired as a topology-free, polarity-insensitive network. Hubbell Controls
supplied LX Network Cables assure proper network communications and should
be specied and installed on all LX System projects.
PRODUCT FEATURES
Interconnects LX Lighting Control Panels and LX network devices
Cable carries both power and data in a single twisted pair
Belden #8471 - twisted pair #16 tinned copper
Single cable type connects to all types of LX network devices
Echelon Guideline Compliant for LON networks
Available in 100 ft and 500 ft reels
Riser Rated
Connects to terminal blocks or with twist on connectors
UL and cUL Listed
One-year limited warranty
INSTALLATION NOTES
1. DO NOT exceed 1500 feet of cable OR connect more than 56 devices per network segment.
2. Each network segment using LP style devices requires an LXLPM2 Link Power Module for device power. Each additional segment requires
an additional LXLPM2 Link Power Module and an LXRRM Repeater for data transmission between segments.
3. Each network segment existing of panels only or that use FT style devices only require termination with LXTERMINATOR instead of LXLPM2 Link Power Module.
4. Run cable and connect network with the shortest distances possible. The most ecient network is wired similar to branch circuit outlets.
5. When using twist-on wire connectors with network cable use no more than three wires per connector.
6. The use of T-taps to minimize cable length is encouraged. Daisy chain topology is allowed, but most often increases overall cable length.
7. DO NOT homerun all devices individually, or leave spare cable at ceiling mounted devices. If devices need to be relocated, cables can be extended with
twist-on wire connectors.
8. DO NOT mix plenum and NON-plenum cables on the same segment.
9. Keep 12” minimum from line voltage, do nut run in the same raceway with line voltage.
*All sales are nal, no returns are allowed.
MODEL
LX8471CBL100* LX Cable Belden 8471 Riser Rated 100 ft Reel
LX8471CBL500* LX Cable Belden 8471 Riser Rated 500 ft Reel
General Specications
Description 1 pair - 16 AWG stranded tinned copper conductors,
PVC Insulation, unshielded twisted pair (UTP), PVC jacket
Shielding Unshielded
Overall Nominal Diameter 0.274 inches
Plenum Rating Not Plenum Rated
Operating Temperature Range -20°C to +80°C (Indoor use only)
Maximum Pulling Tension 61 lbs
Minimum Bend Radius 5.1 inches
Color Pair Color - Black/White, Outer Jacket - Gray
Certications NEC (UL) CMG, CEC/C (UL) CMG,
Flame Test UL Flame Test – UL1685 FT4 Loading,
C (UL) Flame Test FT4
Warranty One-year limited