Instruction_Sheet Installation Directions

323263-Installation 323263-Installation 323263-Installation 751928 Batch4 unilog cesco-content

2014-06-03

: Pdf 323263-Installationsheet 323263-InstallationSheet 751928 Batch4 unilog

Open the PDF directly: View PDF PDF.
Page Count: 1

Operation:
All controls are designed to turn-on within a
range of 1-5 foot candles and turn-off within a
range of 3-15 foot candles.
The FT and SFT controls have a movable
shutter to provide for turn-on/turn-off settings.
Test:
To test all controls simply cover photocell to
simulate darkness and wait approximately 5
minutes for control to respond.
FA - To prevent water entry into photocontrol,
always install photocontrol with wire side down
and a drip loop on the lead wires.
Installation Instructions:
1. Turn off all power at fuse or breaker box.
2. Ensure that the supply voltage matches the
photocontrol voltage rating (see table)
3. Wire control as indicated in Figure 1.
Installation must be in compliance with NFPA
National Electrical Code which requires both
sides of an ungrounded single phase or
multi-phase line be broken (article 410-48)
for lighting loads.
4. The control should be mounted such that the
“photocell” faces away from artificial light
sources. It must not be illuminated by the
lamp it controls or it will cycle on & off at
night.
5. Control should be mounted with wires facing
down to prevent moisture ingress.
6. Once power is restored lamp will come on.
7. Allow up to 5 minutes for lamp to turn off for
daytime operation.
Installation Instructions:
1. Turn off all power at fuse or breaker box.
2. Ensure that the supply voltage matches the photocontrol voltage rating (see table)
3. Wire socket as indicated in wiring diagrams shown.
4. The socket should be mounted such that the “photocell” faces away from artificial light
sources. It must not be illuminated by the lamp it controls or it will cycle on & off at night.
5. Installation must be in compliance with NFPA National Electrical Code which requires both sides
of an ungrounded single phase or multi-phase line be broken (article 410-48) for lighting loads.
6. To install the control, firmly place it into the socket and twist it clockwise until it locks into place.
7. To confirm proper control installation, during daylight hours, cover the window completely to
simulate darkness. The control should switch the load on within 1-2 minutes.
*Note: NS47671, NS47673 socket shall ne mounted directly through standard 1/2” NPT or
1/2” knockout, for NS47671, NS47673 a 1/4” NPT or 1/4” knockout, connection to junction
box must be watertight through the use of thread compound or suitable weatherproof washer.
Operation:
All controls are designed to turn-on within a range of 1-5 foot candles and turn-off
within a range of 3-15 foot candles.
OUTDOOR LIGHTING CONTROLS
FROM FP OLC
54 Commercial Street
Raynham, MA 02767 USA
508-884-9732
www.fisherpierceolc.com
H3007
Installation
Mounting:
Figure1
KNURLED NUT
MODEL
FA - 105
FA - 1068
RED
BLACK
WHITE
AC SUPPLY
NEUTRAL
LAMP
(SEE TABLE)
SINGLE PHASE
GROUNDED LINE
GASKET
N L1
BW
W
UNGROUNDED SINGLE PHASE
OR MULTI PHASE LINE
DPST
RELAY
FT15, SFT15 120 2000W 1000VA
FT168, FFST168 208-277 2000W 1000VA
FT19**, SFT19** 480 2000W 1000VA
FL115 120 2000W 1000VA
FA105, FA105P.W 120 2000W 1000VA
FA1068, FA1068P.W 208-277 2000W 1000VA
Model Line Load Rating
Voltage Tungsten Ballast*
** Not UL Listed or CSA Certified
*HID Ballast Rating
Control Model Line Voltage Load Rating-HID
N7762E 120 1800VA
N7772E 240 1800VA
N7790B 105-285 1800VA
N7792E 105-285 1800VA
N7793 350 1800VA
N7794 480 1800VA
FP240 240 1800VA
FP240H 240 1800VA
Control Model Line Voltage Load Rating-HID
FP120 120 1800VA
FP208-277 208-277 1800VA
FP480* 420-530 1800VA
N7760 120 1800VA
N7841* 120 1800VA
N7842* 208-277 1800VA
MULTI-RELAYS
N251A/N252A* 120 3000VA
N261/N262* 120 3000VA
N271/N272* 120 3000VA
NS476XX UP to 480 15 Amps Max.
NAT9021 Up to 480 15 Amps Max.
** Not UL Listed or CSA Certified
*HID Ballast Rating
FA Series controls are designed for mount-
ing in any UL approved junction box. The
control is provided with a neoprene gasket
and one knurled nut for mounting in a wall
plate with 11/16” center opening. The FA
series with post collar is provided with a self
tapping screw for grounding the post collar.
Drill a 1/8” diameter hole into existing post
through hole in adapter and install self-tapping
ground screw. The FT, SFT & FL series are
designed to mount in a standard UL approved
junction box.
Photocontrol can be mounted directly
through standard 1/2” NPT or 1/2” knockout.
Connection to junction box must be watertight
through the use of thread compound or
suitable weatherproof washer. SFT and FL
series are provided with an elbow to allow the
control’s “photocell” to be directed away from
ambient light sources.
TYPICAL WIRING DIAGRAMS
GROUND
SCREW
FA105P
FA1068P
FA105W
FA1068W
FT15
FT168
FT19
ADJUSTMENT
SHUTTER
SFT15
SFT168
SFT19
FL115
B
R
W
N L1 DPST
RELAY
SINGLE PHASE
GROUNDED LINE
UNGROUNDED SINGLE PHASE
OR MULTI PHASE LINE
SINGLE PHASE
GROUNDED SUPPLIES AND LOADS
N L1
LINE (BLACK)
LOAD (RED)
NEUT. (WHITE)
LOAD
NFP AND N6690/N7700 PHOTOCONTROLS
Cupola
7840 SERIES
STANDARD NS47671
NS47673
N251/N252A
NS47681
NAT9021
N271/N272 SERIES
N281/N282 SERIES
SEE NOTE
54 Commercial Street
Raynham, MA 02767
P: 508-821-1597, FAX: 508-822-0593
www.fpolc.com